This document outlines requirements for an EHRM infrastructure upgrade construction project at the VA Medical Center in Fort Wayne, Indiana. Key details include upgrading the fiber optic backbone, installing new Category 6A cabling to approximately 656 work area outlets across two phases, and replacing telecommunications room equipment. The solicitation was issued by the VA Technology Acquisition Center and involves upgrading the medical center's IT and telecommunications systems. The response due date is not provided.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
STANDARD MOUNTING HEIGHTSANNOTATION
ELECTRICAL:
AUDIBLE APPLIANCES (CENTERLINE) 84"
ALARMS 48"
ANNUNCIATOR PANELS 48"
CLOCK OUTLETS (CENTERLINE) 84"
CONTROLS (TOP) 48"
EXIT SIGNS (WALL-MOUNTED, BOTTOM) 80"
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY) 60"
FIRE ALARM BELL (EXTERIOR) 120"
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY) 60"
INTERCOM (AFEA ONLY) 36"
INTERCOMS (TOP) 48"
PANELS & PANELBOARDS (TOP) 72"
PULL STATIONS (HANDLE) 48"
PHOTOCELLS 144"
RECEPTACLES (BOTTOM) 18"
RECEPTACLES (EXTERIOR) 24"
RECEPTACLES (GARAGES) 26"
RECEPTACLES IN EQUIPMENT ROOMS (TOP) 48"
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS) 48"
REMOTE INDICATING LIGHT (FINISHED AREAS) CEILING
SAFETY SWITCHES & STARTERS 48"
SWITCHES (TOP) 48"
TELEPHONE/DATA/TV OUTLETS (BOTTOM) 18"
VISIBLE APPLIANCES (CENTERLINE) 84"
(AFF, AFG UNLESS NOTED OTHERWISE)
CU
MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT
PLUMBING PLAN NOTE CALL OUT
ELECTRICAL, TECHNOLOGY OR FIRE ALARM PLAN NOTE
CALL OUT
PLUMBING EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION TAG
OWNER FURNISHED, CONTRACTOR INSTALLED
EQUIPMENT DESIGNATION
NEW WORK TO EXISTING WORK CONNECTION POINT
IC
CATV
FO
T
T/D
D
S
IC
UC
S
WAP
#D/#TV
M
S
V
COMMUNICATIONS OUTLET, TYPE AS NOTED
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
SPEAKER, WALL MOUNTED
SPEAKER, CEILING MOUNTED
SERVER RACK, TWO-POST, FLOOR MOUNTED
3/4"x4'x8', FIRE-RATED PLYWOOD BACKBOARD
GROUND BAR, TYPE AS NOTED
SERVER RACK, WALL MOUNTED
CABLE TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
TELEPHONE LINE
TELEPHONE/DATA LINE
DATA LINE
SPEAKER LINE
INTERCOM LINE
INTERCOM, "M" DENOTES MASTER STATION
VOLUME CONTROL, WALL MOUNTED
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
UNDERGROUND COMMUNICATIONS LINE,
CABLING TYPE AS NOTED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
SERVER RACK, FOUR-POST, FLOOR MOUNTED
SERVER CABINET, FLOOR MOUNTED
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#D = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
#D = DATA, # = QUANTITY OF CABLES
#E = ELEVATOR, # = QUANTITY OF CABLES
#FMS = FACILITY MONITORING SYSTEM,
# = QUANTITY OF CABLES
TELECOMMUNICATIONS SYMBOLS
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
X
W
V
U
T
S
R
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB JUNCTION BOX
J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT
INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
DETAIL REFERENCE
SECTION CUT DESIGNATION
EP-101
EP-101
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR12100034 EXP. 12/31/2021
MECH ENGR REG. NO. PE12100220 EXP. 7/31/2022
ELEC ENGR REG. NO. PE12100195 EXP. 7/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR BEACH, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TECHNOLOGY LEGEND AND
ABBREVIATIONS
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
610A4-21-701
VANIHCS
T-000
No. REVISION DESCRIPTION DATE
11/12/2021 WAMAJS
2121 LAKE AVE,
FORT WAYNE, IN 46805
69 119Willam A. McClendon - 11/12/2021
SCALE: NOT TO SCALE (NTS)
D O
W N
BELOW GRADE - OPEN AIR
D O
W N
BELOW GRADE - OPEN AIR "WINDOW WELL" & H.V.A.C. EQUIPMENT
BELOW GRADE - OPEN AIR "WINDOW WELL"
U P
L A K E A V E N U E
R A
N D
A L L I A
D R
I V E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
C
ITY B
U S S
TO
P
W
GTE
BUILDING
Building 5 Building 6
Building 10
B uilding 7
B uilding 3
BUILDING - 2
BUILDING - 1
Ambulatory Care Addition
(1-Story)
Building 16
Building 4
T1 T2
'U pper'
S
ER
V
IC
E PIT
'D rive'
'Low er'
S
ER
V
IC
E PIT
'D rive'
D O
W N
D O W
N
D O
W N
VERMONT
AVENUE
NEVADA
AVENUE
H
W
H
H
W
W W
T T T T
H
W
H
S
IG
N S
TR
U C
TU
R E
VA-Medical Center Ft. Wayne, IN
17 (MRI)
BUILDING - 1
(5-Stories)
T3
D O
W N
B U
ILD
IN
G
- T6
B U
ILD
IN
G
- T5
B U
ILD
IN
G
- T4 D
O W
N
D O
W N
D O
W N
D O
W N
D O
W N
D O
W N
D O
W N
S
IG
N S
TR
U C
TU
R E
S
IG
N S
TR
U C
TU
R E
Redundant/Diverse Fiber Optic Cable Pathways
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
PR
O
PER
TY LIN
E
To C arew
S t
PROPERTY LINE
PROPERTY LINEPROPERTY LINE
FIB
ER
PA
TH
W A Y B
-1 (N
FIB
ER
PA
TH
W A Y B
-1 (N
FIBER PATHWAY B-1 (N)
FIBER PATHWAY A-1 (N)
FIBER PATHWAY A-1 (N)
FIBER PATHWAY A-1 (E)
FIBER
PATH
W
AY B-2 (N
FI
BE
R
PA
TH
W
AY
A
-1 (E
FIB
ER
PA
TH
W A Y B
-2 (E)
FIBER PATHWAY A-1 (N)
FIBER PATHWAY B-2 (N)
FIBER PATHWAY A-2 (N)
FI
BE
R
PA
TH
W
AY
A
-2 (N
(1) NEMA 3R PULL BOX MOUNTED
ON OUTSIDE WALL HERE - TURN
CONDUITS UP AND STUB INTO PULL BOX
APPROXIMATE CABLE FOOTAGES FROM OUTSIDE OF BUILDING 1
CABLE PATHWAY "A-1"
BUILDING 3 - 360'
BUILDING 5 - 900'
BUILDING 6 - 700'
BUILDING T-4 - 510'
BUILDING T-5 - 570'
BUILDING T-6 - 630'
BUILDING 2 - 350'
BUILDING 4 - 300'
CABLE PATHWAY "B-1"
BUILDING 3 - 550'
BUILDING 5 - 750'
BUILDING 6 - 730'
BUILDING T-6 - 600'
CABLE PATHWAY "B-2"
BUILDING 4 - 650'
BUILDING T-4 - 700 '
BUILDING T-5 - 620'
(1) NEMA-3R PULL BOX
MOUNTED ON OUTSIDE
FIB
ER
PA
TH
W A Y B
-1 (N
FIB
ER
PA
TH
W A Y B
-2 (N
R O
U
TE C
O N
D U
ITS
U
N D
ER
PA
R K
IN
G
LO
T S
PEED
B U
M
PS
IN
TH
IS
A
R
EA
HERE - TURN CONDUITS
UP & STUB INTO PULL BOX
FIB
ER
PA
TH
W A Y A
-1 (N
FIB
ER
PA
TH
W A Y B
-2 (E)
FIBER PATHWAY B-2 (N)
EXISTING TUNNEL
CABLE PATHWAY "A-2"
BUILDING 2 - 150'
FIBER PATHWAY B-1 (N)
FIBER PATH
W
AY A-1 (E)
FIB
ER
PA
TH
W A Y A
-1 (N
(1) NEMA-3R PULL BOX
MOUNTED ON OUTSIDE
HERE - TURN CONDUITS
UP & STUB INTO PULL BOX
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR12100034 EXP. 12/31/2021
MECH ENGR REG. NO. PE12100220 EXP. 7/31/2022
ELEC ENGR REG. NO. PE12100195 EXP. 7/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR BEACH, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TECHNOLOGY SITE PLAN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
610A4-21-701
VANIHCS
TS101
No. REVISION DESCRIPTION DATE
N
SCALE: NTS1 TECHNOLOGY SITE PLAN
DIFFERENTIATE IT AS THE IT SYSTEM CABLING. SEE SPCIFICATIONS
1. ALL FIBER OPTIC CABLE SHALL BE AMORED, WITH A GREEN JACKET TO
2. ALL FIBER PATCH PANEL ENCLOSURES SHALL BE SIZED FOR 50% SPARE CAPACITY
OUTSIDE PLANT (OSP) BACKBONE GENERAL NOTES
3. ALL FIBER STRANDS SHALL BE FIELD TERMINATED WITH LC CONNECTORS.
4. ALL NEW FIBER CABLES SHALL BE TERMINATED ONTO NEW FIBER PATCH.
PANEL ENCLOSURES IN EACH BUILDING'S TR AND IN THE NEW SERVER.
ROOM.
5. WHEREVER POSSIBLE, THE NEW FIBER BACKBONE AROUND THE CAMPUS
SHALL USE EXISTING CONDUIT PATHWAYS.
6. AFTER CUTOVER, REMOVE THE OLD FIBER IN ALL UNDERGROUND
PATHWAYS AND ALL ASSOCIATED FIBER PATCH PANEL ENCLOSURES.
HARDWARE AND SUPPORT STRUCTURE FROM THE TR ALL THE WAY BACK
TO BLDG 1, SERVER ROOM. ENSURE THAT ANY CABLING THAT IS FOR
OTHER SYSTEMS IS NOT DISTURBED.
7. CABLE FOOTAGES SHOWN ARE APPROXIMATE. CONTRACTOR TO CONFIRM
LENGTHS BEFORE ORDERING CABLE. INCLUDE LENGTH TO PROVIDE CABLE
SLACK LOOPS AROUND THE INSIDE OF EACH MAINTENANCE & HANDHOLES.
OSP FIBER OPTIC BACKBONE KEYNOTES
8. ALL OUTSIDE PLANT (OSP) WORK SHALL ADHERE TO ANSI/TIA/EIA-758
(CUSTOMER-OWNED OUTSIDE PLANT TELECOMMUNICATIONS CABLING STANDARD)
AND BICSI's CUSTOMER-OWNED OUTSIDE PLANT DESIGN MANUAL (Current Edition).
9. NEW UNDERGROUND CONDUITS (NUC) PASSING BENEATH THE PARKING LOTS,
SUBSEQUENTLY CONCRETE ENCASED. PVC CONDUITS TO BE BURIED 36" TO
TOP OF CONDUIT.
10. NEW UNDERGROUND CONDUITS (NUC) AT ALL OTHER LOCATIONS SHALL BE
SCHEDULE-40 PVC CONDUIT PLACED VIA AN OPEN TRENCH AND SUBSEQUENTLY
CONCRETE ENCASED. PVC CONDUITS TO BE BURIED AT 36" MINIMUM TO TOP OF
CONDUITS.
11. A METALLIC WARNING TAPE SHALL BE PLACED IN THE OPEN TRENCH 12"
BELOW GROUND LEVEL. WARNING TAPE SHOULD NOTE SOMETHING TO THE
EFFECT OF "WARNING: FIBER OPTIC CABLE BELOW".
12. NEW HANDHOLE (NHH) INSTALLED SHALL BE 36"W x 48"L x 48"D, PRECAST
CONCRETE, AS MANUFACTURED BY JENSEN, OLDCASTLE, CONCAST OR
EQUIVALENT.
13. NEW HANDHOLE TO BE EQUIPPED WITH LID, SUMP, PULLING-IN IRONS, GROUND
ROD, BONDING RIBBON, CABLE RACKS & HOOKS.
PROVIDE AND INSTALL (7) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY A-1 REDUNDANT HOMERUNS TO BUILDINGS 2, 3, 5, 6, T-4, T-5 & T-6.
PROVIDE AND INSTALL (3) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY B-1 REDUNDANT HOMERUNS TO BUILDINGS 3, 5 & 6.
PROVIDE AND INSTALL (5) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY B-2 REDUNDANT HOMERUNS TO BUILDINGS 2, 4, T-4, T5 & T-6.
PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY B-2 REDUNDANT HOMERUN TO BUILDING 4.
PROVIDE AND INSTALL (2) 4" 3-CELL FABRIC INNERDUCTS INSIDE ONE (1)
PROVIDE AND INSTALL (4) NEW 4" SCHEDULE-80 RIGID PVC CONDUITS VIA
OPEN TRENCH METHOD, 36" BELOW GROUND LEVEL TO TOP OF CONDUIT.
TO TOP OF CONDUIT.
PROVIDE AND INSTALL (4) NEW 4" SCHEDULE-40 RIGID PVC CONDUITS VIA
OPEN TRENCH METHOD, 36" BELOW GROUND LEVEL TO TOP OF CONDUIT.
EXISTING UNDERGROUND CONDUITS
EXISTING MAINTENANCE HOLE (PREVIOUSLY REFERRED TO AS MANHOLE)
EXISTING IN-GROUND HANDHOLE
NEW IN-GROUND HANDHOLE
PROVIDE AND INSTALL (1) NEW 4" SCHEDULE-40 RIGID PVC CONDUIT VIA
OPEN TRENCH, 36" BELOW GROUND LEVEL TO TOP OF CONDUIT.
PROVIDE AND INSTALL (1) NEW NEMA 3R PULL BOX (18"W x 18"L x 12"D).
PROVIDE AND INSTALL (1) 4" 3-CELL FABRIC INNERDUCT (e.g.: MAXCELL)
EXISTING CONDUIT AND INSIDE ONE (1) NEW 4" PVC CONDUIT (e.g.: MAXCELL)
SHALL BE SCHEDULE-80 RIGID PVC CONDUIT PLACED VIA AN OPEN TRENCH AND
PROVIDE AND INSTALL (6) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY A-1 REDUNDANT HOMERUNS TO BUILDINGS 3, 5, 6, T-4, T-5 & T-6.
PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY A-1 REDUNDANT HOMERUN TO BUILDING 2.
PROVIDE AND INSTALL (1) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY A-2 REDUNDANT HOMERUN TO BUILDING 4.
PROVIDE AND INSTALL (2) NEW 4" SCHEDULE-40 RIGID PVC CONDUITS VIA
OPEN TRENCH METHOD, 36" BELOW GROUND LEVEL TO TOP OF CONDUIT.
11/12/2021 WAM
PROVIDE AND INSTALL (2) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY A-1 REDUNDANT HOMERUNS TO BUILDINGS 5 & 6.
PROVIDE AND INSTALL (3) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY A-1 REDUNDANT HOMERUNS TO BUILDINGS T4, T5 & T6.
PROVIDE AND INSTALL (3) EACH 24-STRAND, INDOOR/OUTDOOR, ARMORED
OS2, SINGLEMODE FIBER OPTIC CABLE (OFCP), WITH A GREEN JACKET.
PATHWAY B-2 REDUNDANT HOMERUNS TO BUILDINGS T4, T5 & T6.
AJS
2121 LAKE AVE,
FORT WAYNE, IN 46805
SERVICE PROVIDER (VERIZON) IN-BOUND 144 STRAND, OS2,
SINGLEMODE FIBER OPTIC CABLE.
ONE (1) NEW 4" SCHEDULE-80 RIGID PVC CONDUIT VIA OPEN
TRENCH, 36" BELOW GROUND LEVEL TO TOP OF CONDUIT.
70 119Willam A. McClendon - 11/12/2021 71 OF 120
PHARMACY
STORAGE
005A
MECH
STORAGE
008B
HAC
006 FOOD
MECH/STORAGE
OFFICE
PANTRY
CANTEEN
STORAGE
008A
DN
FREEZER
F01
OFFICE
OFFICE
REFRIGERATOR
R03
FOOD
STORAGE
REFRIGERATOR
R02
EMS
KITCHEN
UP
REFRIGERATOR
R01
OFFICE
DISHWASHER
MECH
022A
STORAGE
STORAGE
STORAGE
TOILET ELEVATOR
TOILET UP
PHARMACY
UP
MECH
VESTIBULE
025A
STORAGE
STORAGE
STORAGE
STORAGE
STORAGE
017 ELEVATOR
VESTIBULE
FIRE
PROTECTION
ELEVATOR
OXYGEN
STORAGE
MORGUE
BATH
060B
WOMENS
LOCKER
ROOM
UP
STAIR #4
CORRIDOR
TOILET
PHARMACY
STORAGE
WOMENS
TOILET
STORAGE
STORAGE
MENS
TOILET
STAIR 2
UP
WET VAC
HAC
SOILED
UTILITY
MECH
OFFICE
WORKSHOP
044A
TOILET
045A
MECH
MAINTENANCE
MENS
LOCKER
ROOM
LOUNGE
045B
MECH
MECH
BIO MED
OFFICE
ELEC
42A
OFFICE
B601
OFFICE
B602
ELEC
WATER
TREATMENT
049C
CORRIDOR
BCC2
VESTIBULE
BC110
CUBICLE,
CLERIVAL
STAFF
B603
MENS
OFFICE
B603A CONFERENCE
B604
ELECTRICAL
B607
STORAGE
B619
STORAGE
HAC
B618A
MECH
036A STORAGE
(FUTURE
STORAGE
(FUTURE LOGISTICS LOGISTICS
STORAGE
B618B
SCOPE
DECONTAMINATION
B618C
SCOPE
STERILIZATION
B605A
LOUNGE,
STAFF
B608
WOMENS
LOCKER
ROOM
B608B
PURCHASING
B610
LOCKER
ROOM
B608A
OFFICE
(FUTURE
ELEV)
B609
SHELL
SPACE
STAIR9
BCST9
UP
HAC
SOILED
UTILITY
STAIR CORRIDOR
BBC4
MAIL ROOM
049A
BIOMETRICS
(ARMAMENTARIUM
REINTEGRATION)
050 OFFICE
050A
DATA
053A
STORAGE
HAC
UP
CORRIDOR CLOSET
TO OSP REDUNDANT PATHWAY A-1
OSP FIBER CABLES TO BLDG's 2, 3, 5, 6, TO OSP REDUNDANT PATHWAY A-1
OSP FIBER CABLES TO BLDG's 2, 3, 5, 6, T-4, T-5 & T-6.
T-4, T-5 & T-6.
TO 1ST, 2ND, 3RD, 4TH & 5TH FLOOR TR's
ISP FIBER BACKBONE CABLES VERTICAL PATHWAY "B"
TO 1ST, 2ND, 3RD, 4TH & 5TH FLOOR TR's
ISP FIBER BACKBONE CABLES VERTICAL PATHWAY "A"
TO OSP REDUNDANT PATHWAY B-2
OSP FIBER CABLES TO BLDG's 2, 4, T-4, T5 & T6.
TO OSP REDUNDANT PATHWAY A-2
OSP FIBER CABLE TO BLDG 4.
MAIN COMPUTER ROOM/DATA CENTER/SERVER ROOM #057
TR-B606
HAC
063A
063A
LG
D
U A
L IN
V
ER
TER
A
C C O
R N
IN
G
M A S
UP TO 1ST FLOOR (PATHWAY YET TO BE DETERMINED)
ISP FIBER BACKBONE CABLE PATHWAY "B"
TR-63/TCB
LENEL/ALTRONIX RS2 SYSTEM
POWER PANEL
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR12100034 EXP. 12/31/2021
MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR BEACH, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
BUILDING 1 - BASEMENT
TECHNOLOGY FLOOR PLAN
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
610A4-21-701
VANIHCS
T-100
No. REVISION DESCRIPTION DATE
ISP FIBER OPTIC BACKBONE KEYNOTES:
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE
CABLE TRAY.
NOT TO SCALE (NTS)
B1 - BASEMENT LEVEL - TECHNOLOGY PLAN
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE
CABLE TRAY.
PROVIDE AND INSTALL (7) EACH 24-STRAND, SINGLEMODE (OS2),
ARMORED, FIBER OPTIC CABLES (OFCP), WITH A GREEN JACKET
FOR OSP PATHWAYS A-1 REDUNDANT HOMERUNS TO
BUILDINGS 2, 3, 5, 6, T-4, T-5 & T-6.
PROVIDE AND INSTALL (3) EACH 24-STRAND, SINGLEMODE (OS2),
ARMORED, FIBER OPTIC CABLES (OFCP), WITH A GREEN JACKET
FOR OSP PATHWAYS B-1 REDUNDANT HOMERUNS TO
BUILDINGS 3, 5, & 6.
PROVIDE AND INSTALL (5) EACH 24-STRAND, SINGLEMODE (OS2),
ARMORED, FIBER OPTIC CABLES (OFCP), WITH A GREEN JACKET
FOR OSP PATHWAYS B-2 REDUNDANT HOMERUNS TO
BUILDINGS 2, 4, T-4, T-5 & T-6.
PROVIDE AND INSTALL (1) EACH 24-STRAND, SINGLEMODE (OS2),
ARMORED, FIBER OPTIC CABLES (OFCP), WITH A GREEN JACKET
FOR OSP PATHWAYS A-2 REDUNDANT HOMERUN TO
BUILDING 4.
PROVIDE AND INSTALL (5) EACH 12-STRAND SINGLEMODE (OS2)/
24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC
CABLES, WITH A GREEN JACKET, FOR ISP PATHWAY "A"
REDUNDANT HOMERUNS TO TR's ON THE 1ST, 2ND, 3RD, 4TH & 5TH
FLOORS..
PROVIDE AND INSTALL (6) EACH 12-STRAND SINGLEMODE (OS2)/
24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC
CABLES, WITH A GREEN JACKET, FOR ISP PATHWAY "B"
REDUNDANT HOMERUNS TO TR's ON THE BASEMENT, 1ST, 2ND, 3RD, 4TH & 5TH FLOORS.
PROVIDE AND INSTALL (1) EACH 12-STRAND SINGLEMODE (OS2)/
24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC
CABLE, WITH A GREEN JACKET, FOR ISP PATHWAY "A"
REDUNDANT HOMERUN TO TR-63/TCB.
PROVIDE AND INSTALL (1) EACH 12-STRAND SINGLEMODE (OS2)/
24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC
CABLE, WITH A GREEN JACKET, FOR ISP PATHWAY "B"
REDUNDANT HOMERUN TO TR-63/TCB.
PROVIDE AND INSTALL (1) EACH 12-STRAND SINGLEMODE (OS2)/
24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC
CABLE, WITH A GREEN JACKET, FOR ISP PATHWAY "A"
REDUNDANT HOMERUN TO TR-B606.
PROVIDE AND INSTALL (1) EACH 12-STRAND SINGLEMODE (OS2)/
24-STRAND MULTIMODE (OM4) HYBRID, ARMORED, FIBER OPTIC
CABLE, WITH A GREEN JACKET, FOR ISP PATHWAY "B"
REDUNDANT HOMERUN TO TR-B606.
N
11/12/2021 WAMAJS
2121 LAKE AVE,
FORT WAYNE, IN 46805
11971Willam A. McClendon - 11/12/2021
REFRIGERATOR
MECH
022A
STORAGE
STORAGE
028A
PHARMACY
MECH
029A
LINEN
STORAGE
030B
OFFICE
030C
BREAKROOM
UP
MECH
VESTIBULE
025A
STORAGE
STORAGE
STORAGE
STORAGE
EMS OFFICE
SUPERVISOR
030A
EMS
STORAGE
030D
WOMENS
TOILET
STORAGE
STORAGE
STORAGE
MENS
TOILET
STAIR 2
UP
HAC
SOILED
UTILITY
MECH
UP
MECH
BIO MED
OFFICE
ELEC
MECH
036A
TO 1ST, 2ND, 3RD, 4TH & 5TH FLOOR TR's
ISP FIBER BACKBONE CABLES VERTICAL PATHWAY "A"
2 2
4 2
MATCHLINE
T100-A
T1
-A T1
-D
MATCHLINE
T100-A
M
AT
C H
LI
N
E T1
-B
M
AT
C H
LI
N
E
JH
JH
JH
JH JH
JH
JH
JH
JH
JH
JH
JH
N ot e:
A ll W
AO
C ab le s in a re a T1
-D to b e ro ut ed to , a nd te rm in at ed in T
R -6
3/
TC
B N ot e:
A ll
W
AO
C ab le s in a re a
T1
-A to b e ro ut ed to
, a nd te rm in at ed in
T R
-6 3/
TC
B
(N ot e:
A ll W
AO
C ab le s in a re a T1
-B to b e ro ut ed to , a nd te rm in at ed in T
R -0
/T
C B)
(Note: All WAO Cables in area T100-A to be routed to, and terminated in TR-63/TCB)
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR12100034 EXP. 12/31/2021
MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR BEACH, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
STAMP:
Drawing Number
Building Number
BUILDING 1 - BASEMENT
TECHNOLOGY FLOOR PLAN - AREA A
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
610A4-21-701
VANIHCS
T100A
No. REVISION DESCRIPTION DATE
1 B1 - BASEMENT LEVEL - TECHNOLOGY PLAN
N
11/12/2021 WAM
SCALE: 1/8" = 1'0"
AJS
2121 LAKE AVE,
FORT WAYNE, IN 46805
11972
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
TECHNOLOGY KEYNOTES:
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'A' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'B' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 12"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA
OUTLET (WAO) STATION CABLES.
tiles and the floor above. If in the event that the cable tray cannot be installed , a J-Hook pathway shall be established to support the Category 6A station cables.
Note: Cable Tray Installation is contingent upon the amount of congestion evident in the space between the drop ceiling grid/
INTERSECTING CABLE TRAYS WILL BE SEPARATED VERTICALLY, SO AS TO AVOID CABLE ROUTING CONFLICTS
BETWEEN FIBER BACKBONE CABLES AND UTP STATION CABLES.
LEGEND:
VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101
FOR MORE DETAILS)
VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101
FOR MORE DETAILS)
ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS
(IF POSSIBLE) IN GENERAL PATHWAYS.
ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS
SECONDARY BONDING BUSBAR.
AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES
WHERE CABLING WAS REMOVED.
AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE
CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
A.
B.
C.
D.
E.
F.
G.
H.
CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING
ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE
DROPS.
ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO
THE NEW CABLING.
EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.
EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN
OLTS AND AN OTDR PER THE TIER 2 STANDARD.
PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE
MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K.
L.
M.
N.
PHASE 1 - INSTALL APPROXIMATELY (0) NEW CATEGORY 6A DATA CABLES ON THE BASEMENT LEVEL TO A MIXTURE OF
(0) DUAL AND QUAD NEW WORK AREA OUTLET LOCATIONS.
O.
W
WAP
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.
(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B
(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2).
INSTALLATION..
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
GENERAL NOTES:
PROVIDE AND INSTALL 18"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA
OUTLET (WAO) STATION CABLES.
PROVIDE AND INSTALL J-HOOK PATHWAYS TO SUPPORT CATEGORY 6A STATION CABLES FROM WAO TO MAIN CABLE TRAY OR MAIN J-HOOK PATHWAY BACK TO THE ASSOCIATED TR (TYPICAL). INSTALL AT 5' (MAXIMUM) .
INTERVALS O.C. (NOTE: J-HOOK PATHWAYS DEPICTED ARE JUST A FEW EXAMPLES. ALL STATION CABLING MUST BE SUPPORTED BY J-HOOK PATHWAYS THAT ARE PARALLEL AND PERPENDICULAR TO BUILDING LINES.)
= 4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)
X
X = PHASE 1 - THESE NEW WORK AREA OUTLET LOCATIONS (NWAO's) ARE TO BE INSTALLED IN PHASE 1.
= PHASE 2 - THESE EXISTING WORK AREA OUTLET LOCATIONS (EWAO's) ARE TO BE INSTALLED IN PHASE 2.
PHASE 2 - INSTALL APPROXIMATELY (160) NEW CATEGORY 6A DATA CABLES ON THE BASEMENT LEVEL TO A MIXTURE
OF (76) DUAL AND QUAD EXISTING WORK AREA OUTLET LOCATIONS.
P.
Willam A. McClendon - 11/12/2021 73 OF 120
PHARMACY
STORAGE
005A
MECH
STORAGE
008B
HAC
006 FOOD
MECH/STORAGE
OFFICE
PANTRY
CANTEEN
STORAGE
008A
DN
FREEZER
F01
OFFICE
OFFICE
REFRIGERATOR
R03
FOOD
STORAGE
REFRIGERATOR
R02
EMS
KITCHEN
UP
REFRIGERATOR
R01
OFFICE
DISHWASHER
MECH
022A
STORAGE
STORAGE
STORAGE
STORAGE
028A
TOILET ELEVATOR
TOILET UP
PHARMACY
UP
TO OSP REDUNDANT PATHWAY A-1
OSP FIBER CABLES TO BLDG's 2, 3, 5, 6, TO OSP REDUNDANT PATHWAY A-1
OSP FIBER CABLES TO BLDG's 2, 3, 5, 6, T-4, T-5 & T-6.
T-4, T-5 & T-6.
(Note: All WAO Cables in area T100-C to be routed to, and terminated in TR-B606)
M
AT
C H
LI
N
E T1
-B
M
ATC
H
LIN
E T100-B
MATCHLINE
T100-A
M
AT
C H
LI
N
E T1
-B
MATCHLINE
T100-C
M
ATC
H
LIN
E T100-B
MATCHLINE
T-100-D T-100-B
JHJH
JH
JH
JH
JH
JH
JH
POWER PANEL
(N ote: All W
AO
C ables in area T100-B to be routed to, and term inated in TR
-063/TC
B)
(N ot e:
A ll W
AO
C ab le s in a re a T1
-B to b e ro ut ed to , a nd te rm in at ed in T
R -0
/T
C B)
(Note: All WAO Cables in area T100-A to be routed to, and terminated in TR-63/TCB)
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR12100034 EXP. 12/31/2021
MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR BEACH, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
STAMP:
Drawing Number
Building Number
BUILDING 1 - BASEMENT
TECHNOLOGY FLOOR PLAN - AREA B
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
610A4-21-701
VANIHCS
T100B
No. REVISION DESCRIPTION DATE
1 B1 - BASEMENT LEVEL - TECHNOLOGY PLAN
N
11/12/2021 WAM
SCALE: 1/8" = 1'0"
AJS
2121 LAKE AVE,
FORT WAYNE, IN 46805
11973
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
TECHNOLOGY KEYNOTES:
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'A' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'B' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 12"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA
OUTLET (WAO) STATION CABLES.
tiles and the floor above. If in the event that the cable tray cannot be installed , a J-Hook pathway shall be established to support the Category 6A station cables.
Note: Cable Tray Installation is contingent upon the amount of congestion evident in the space between the drop ceiling grid/
INTERSECTING CABLE TRAYS WILL BE SEPARATED VERTICALLY, SO AS TO AVOID CABLE ROUTING CONFLICTS
BETWEEN FIBER BACKBONE CABLES AND UTP STATION CABLES.
LEGEND:
VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101
FOR MORE DETAILS)
VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101
FOR MORE DETAILS)
ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS
(IF POSSIBLE) IN GENERAL PATHWAYS.
ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS
SECONDARY BONDING BUSBAR.
AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES
WHERE CABLING WAS REMOVED.
AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE
CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
A.
B.
C.
D.
E.
F.
G.
H.
CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING
ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE
DROPS.
ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO
THE NEW CABLING.
EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.
EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN
OLTS AND AN OTDR PER THE TIER 2 STANDARD.
PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE
MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K.
L.
M.
N.
PHASE 1 - INSTALL APPROXIMATELY (0) NEW CATEGORY 6A DATA CABLES ON THE BASEMENT LEVEL TO A MIXTURE OF
(0) DUAL AND QUAD NEW WORK AREA OUTLET LOCATIONS.
O.
W
WAP
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.
(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B
(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2).
INSTALLATION..
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
GENERAL NOTES:
PROVIDE AND INSTALL 18"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA
OUTLET (WAO) STATION CABLES.
PROVIDE AND INSTALL J-HOOK PATHWAYS TO SUPPORT CATEGORY 6A STATION CABLES FROM WAO TO MAIN CABLE TRAY OR MAIN J-HOOK PATHWAY BACK TO THE ASSOCIATED TR (TYPICAL). INSTALL AT 5' (MAXIMUM) .
INTERVALS O.C. (NOTE: J-HOOK PATHWAYS DEPICTED ARE JUST A FEW EXAMPLES. ALL STATION CABLING MUST BE SUPPORTED BY J-HOOK PATHWAYS THAT ARE PARALLEL AND PERPENDICULAR TO BUILDING LINES.)
= 4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)
X
X = PHASE 1 - THESE NEW WORK AREA OUTLET LOCATIONS (NWAO's) ARE TO BE INSTALLED IN PHASE 1.
= PHASE 2 - THESE EXISTING WORK AREA OUTLET LOCATIONS (EWAO's) ARE TO BE INSTALLED IN PHASE 2.
PHASE 2 - INSTALL APPROXIMATELY (160) NEW CATEGORY 6A DATA CABLES ON THE BASEMENT LEVEL TO A MIXTURE
OF (76) DUAL AND QUAD EXISTING WORK AREA OUTLET LOCATIONS.
Willam A. McClendon - 11/12/2021 74 OF 120
UP
OXYGEN
STORAGE
MORGUE
BATH
060B
WOMENS
LOCKER
ROOM
UP
STAIR #4
CORRIDOR
TOILET
PHARMACY
STORAGE
WET VAC
MECH
MENS
LOCKER
ROOM
LOUNGE
045B
MECH
OFFICE
B601
OFFICE
B602
WATER
TREATMENT
049C
CORRIDOR
BCC2
VESTIBULE
BC110
CUBICLE,
CLERIVAL
STAFF
B603
MENS
OFFICE
B603A CONFERENCE
B604
ELECTRICAL
B607
STORAGE
B619
STORAGE
HAC
B618A
AUTOMATIC
CART WASH
B618E
DECONTAMINATION
B618
HAC
CORRIDOR
BCC1
TEMP
STORAGE
(FUTURE
MECH)
B617
LOUNGE
B616 SPS
ASSITANT
OFFICE
B616C
B605C
OFFICE
B613
STERILE/NON-STERILE
STORAGE
B615
CART PREP
B605
STORAGE
(FUTURE
DUMBWAITER)
B605D
STORAGE
(FUTURE
EQUIP.
ROOM)
B615A
CORRIDOR
BCC3
HAC
B612
LOGISTICS
DIRECTOR
B611B
LOGISTICS
MANAGEMENT
B611
LOGISTICS
SUPERVISOR
B611A
STORAGE
B618B
SCOPE
DECONTAMINATION
B618C
SCOPE
STERILIZATION
B605A
LOUNGE,
STAFF
B608
WOMENS
LOCKER
ROOM
B608B
PURCHASING
B610
LOCKER
ROOM
B608A
OFFICE
(FUTURE
ELEV)
B609
SHELL
SPACE
STAIR9
BCST9
UP
HAC
SOILED
UTILITY
STAIR CORRIDOR
BBC4
MAIL ROOM
049A
BIOMETRICS
(ARMAMENTARIUM
REINTEGRATION)
050 OFFICE
050A
053A
STORAGE
HAC
UP
CORRIDOR CLOSET
PREP/ASSEMBLY
B605B
WOMENS
LOCKER
ROOM
B616A
UP
STAIR 10
BCST10
STERILIZER
ACCESS
B614A
MENS
LOCKER
ROOM
B616B
WAREHOUSE
B614
TO 1ST, 2ND, 3RD, 4TH & 5TH FLOOR TR's
ISP FIBER BACKBONE CABLES VERTICAL PATHWAY "B"
TO OSP REDUNDANT PATHWAY B-2
TO OSP REDUNDANT PATHWAY A-2
OSP FIBER CABLE TO BLDG 4.
2 2
2 2 2
2 2
MATCHLINE
(Note: All WAO Cables in area T100-C to be routed to, and terminated in TR-B606)
M
AT
C H
LI
N
E T1
-C
MATCHLINE
T100-C
M
ATC
H
LIN
E T100-B
T1
-D
JH
JH
JH
JH
JH
JH
JH
JHJHJH
JH
JH
JH
JH
JH
JHJH
MAIN COMPUTER ROOM/DATA CENTER/SERVER ROOM
Scale: 1" = 1'
TR-B606
T100-C
(N ot e:
A ll W
AO
C ab le s in a re a T1
-C to b e ro ut ed to , a nd te rm in at ed in T
R -B
6)
(N ot e:
A ll W
AO
C ab le s in a re a T1
-D to b e ro ut ed to , a nd te rm in at ed in T
R -6
3/
TC
B)
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. AR12100034 EXP. 12/31/2021
MECH ENGR REG. NO. PE12100220 EXP. 07/31/2022
ELEC ENGR REG. NO. PE12100195 EXP. 07/31/2022
CIVIL ENGINEER
OLSSON
550 ST LOUIS ST,
SPRINGFIELD, MO 65806
(417) 885-1736
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
TELECOMMUNICATIONS
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 85712
(928) 774-0992
PHYSCIAL SECURITY
FORCE PROTECT
3210 GULF BLVD, UNIT 304
BELLEAIR BEACH, FL 33786
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
STAMP:
Drawing Number
Building Number
BUILDING 1 - BASEMENT
TECHNOLOGY FLOOR PLAN - AREA C
BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES FORT WAYNE,
INDIANA
610A4-21-701
VANIHCS
T100C
No. REVISION DESCRIPTION DATE
1 B1 - BASEMENT LEVEL - TECHNOLOGY PLAN
N
11/122021 WAM
SCALE: 1/8" = 1'0"
AJS
2121 LAKE AVE,
FORT WAYNE, IN 46805
11974
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 4"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
TECHNOLOGY KEYNOTES:
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'A' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 2"W x 2"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT REDUNDANT FIBER OPTIC
BACKBONE 'B' CABLE. (SEE PLAN SHEET T-101 FOR MORE DETAILS)
PROVIDE AND INSTALL 12"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA
OUTLET (WAO) STATION CABLES.
tiles and the floor above. If in the event that the cable tray cannot be installed , a J-Hook pathway shall be established to support the Category 6A station cables.
Note: Cable Tray Installation is contingent upon the amount of congestion evident in the space between the drop ceiling grid/
INTERSECTING CABLE TRAYS WILL BE SEPARATED VERTICALLY, SO AS TO AVOID CABLE ROUTING CONFLICTS
BETWEEN FIBER BACKBONE CABLES AND UTP STATION CABLES.
LEGEND:
VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'A' CABLES. (SEE PLAN SHEET T-101
FOR MORE DETAILS)
VERTICAL PATHWAY FOR REDUNDANT-DIVERSE FIBER OPTIC BACKBONE 'B' CABLES. (SEE PLAN SHEET T-101
FOR MORE DETAILS)
ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND CABLE TRAYS
(IF POSSIBLE) IN GENERAL PATHWAYS.
ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE TELECOMMUNICATIONS
SECONDARY BONDING BUSBAR.
AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES
WHERE CABLING WAS REMOVED.
AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE THAT ANY CABLING IN THE
CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
A.
B.
C.
D.
E.
F.
G.
H.
CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND DURING
ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF ADDITIONAL CABLE
DROPS.
ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL CUT-OVER TO
THE NEW CABLING.
EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S DESIGNATED TR.
EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED UTILIZING AN
OLTS AND AN OTDR PER THE TIER 2 STANDARD.
PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE
MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)
NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE
PATHWAYS.
I. EXISTING CONDUITS TO REMAIN.
J. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
K.
L.
M.
N.
PHASE 1 - INSTALL APPROXIMATELY (0) NEW CATEGORY 6A DATA CABLES ON THE BASEMENT LEVEL TO A MIXTURE OF
(0) DUAL AND QUAD NEW WORK AREA OUTLET LOCATIONS.
O.
W
WAP
WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B.
(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
WIRELESS ACCESS POINT CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME TO BE T568B
(EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2).
INSTALLATION..
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLORE TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (EXISTING WAO LOCATION TO BE INSTALLED IN PHASE 2)
GENERAL NOTES:
PROVIDE AND INSTALL 18"W x 4"D WIRE BASKET TYPE CABLE TRAY TO SUPPORT CATEGORY 6A UTP WORK AREA
OUTLET (WAO) STATION CABLES.
PROVIDE AND INSTALL J-HOOK PATHWAYS TO SUPPORT CATEGORY 6A STATION CABLES FROM WAO TO MAIN CABLE TRAY OR MAIN J-HOOK PATHWAY BACK TO THE ASSOCIATED TR (TYPICAL). INSTALL AT 5' (MAXIMUM) .
INTERVALS O.C. (NOTE: J-HOOK PATHWAYS DEPICTED ARE JUST A FEW EXAMPLES. ALL STATION CABLING MUST BE SUPPORTED BY J-HOOK PATHWAYS THAT ARE PARALLEL AND PERPENDICULAR TO BUILDING LINES.)
= 4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES TERMINATED ONTO (2)
CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)
4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (4) CATEGORY 6A UTP CABLES TERMINATED ONTO (4) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR TO BE BLUE. TERMINATION SCHEME
TO BE T568B. (NEW WAO LOCATION TO BE INSTALLED IN PHASE 1)
X
X = PHASE 1 - THESE NEW WORK AREA OUTLET LOCATIONS (NWAO's) ARE TO BE INSTALLED IN PHASE 1.
= PHASE 2 - THESE EXISTING WORK AREA OUTLET LOCATIONS (EWAO's) ARE TO BE INSTALLED IN PHASE 2.
PHASE 2 - INSTALL APPROXIMATELY (160) NEW CATEGORY 6A DATA CABLES ON THE BASEMENT LEVEL TO A MIXTURE
OF (76) DUAL AND QUAD EXISTING WORK AREA OUTLET LOCATIONS.
P.
Willam A. McClendon - 11/12/2021
MECH
022A
STORAGE
STORAGE
STORAGE
TOILET ELEVATOR
TOILET UP
PHARMACY
UP
MECH
VESTIBULE
025A
STORAGE
STORAGE
STORAGE
STORAGE
STORAGE
017 ELEVATOR
VESTIBULE
FIRE
PROTECTION
ELEVATOR
OXYGEN
STORAGE
MORGUE
BATH
060B
WOMENS
LOCKER
ROOM
WOMENS
TOILET
STORAG…