ATTACHMENT 8 - Drawings - Volume 1 - 5 of 8.pdf
PDF 14 MB Posted
- Solicitation number
- 36C77622B0063
About this file
This attachment provides drawings for a federal construction project solicitation to expand Building 1 for primary care at the Fargo VA Medical Center. The project involves rerouting part of the road between the medical center and flood wall, relocating the flood wall basin and road further from a building addition to comply with physical security standards. Foundation work will include helical piers to support the addition, which provides a two-story structure with a whole health clinic and supporting rooms on the first floor and mechanical space and offices for emergency medical services in the basement. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin to expand primary care facilities at the Fargo VA Medical Center in compliance with security requirements.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
02-1602-16
FIELD VERIFY
18' - 10"
F
IE
L D
V E
R
IF
Y
/1
02-28
02-3102-31
02-29
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
FIELD VISIT THE PROJECT AND VERIFY EXISTING
CONDITIONS/DIMENSIONS AND PROPOSED
CONDITIONS. COORDINATE DEMOLITION BETWEEN
ALL TRADES. NOTIFY A/E IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
3. EXISTING DOORS SHOW AT 45 DEGREE ANGLE FOR
CLARITY WITH THE EXCEPTION OF TOILET
PARTITIONS.
4. EXISTING WALL SHADED FOR CLARITY.
AREA OF WORK NOT IN THE SCOPE.
EXISTING TO REMAIN.
ITEMS TO BE DEMOLISHED. SEE
KEYNOTES.
PERIMETER OF NEW BUILDING
FOOTPRINT
AD1.51
AD1.51
02-31
02-28
02-28 02-28 02-33
FIRST LEVEL
100' - 0"
T.O. EXISTING ROOF DECK
111' - 2 3/4"
02-31
02-32
02-31
02-16
02-3102-31
02-28
02-29
02-26
02-27
02-2202-2202-2202-02
02-2202-2202-2202-2202-2202-2202-2202-22
02-25
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
DEMOLITION - EAST ELEVATION &
DETAILS
AD1.51
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
24 128
1/4" = 1'-0"
DEMO ELEVATION
GENERAL NOTES:
KEYNOTES:
02-02 REMOVE EXISTING DOOR, DOOR HARDWARE, AND
FRAME COMPLETELY.
02-16 REMOVE EXISTING MASONRY VENEER TO THE
EXTENTS SHOWN. ACCOMODATE NEW MASONRY AS
REQUIRED AT NEW PLANE. FIELD VERIFY.
02-22 DEMO EXISTING ALUMINUM WINDOW. PREP ROUGH
OPENING FOR INFILL. SEE SHEET A1.40 WALL TYPE
M3D FOR INFILL.
02-25 SAWCUT (PLANE) THE FACE OF THE PRE-CAST
ACCENT AT THE BASE OF THE BRICK. THE PRE-CAST
SHALL BE PLANED TO ALIGN WITH FACE BRICK ABOVE.
SEE STRUCTURAL DRAWINGS FOR FURTHER DETAIL.
02-26 REMOVE EXISTING BAY WINDOW SILL TO
ACCOMODATE NEW ROOF.
02-27 REMOVE PART OF EXISTING FRAMING AND GLAZING,
ACCOMODATE WINDOW PER NEW ROOF.
02-28 REMOVE EXISTING METAL FASCIA TO ITS ENTIRETY TO
ACCOMODATE NEW ROOF.
02-29 REMOVE EXISITNG CAST STONE BAND TO
ACCOMODATE NEW FLOOR PLAN.
02-31 REMOVE AND DISPOSE OF EXISTING ROOF ACCESS
HATCH AND RAILS.
02-32 REMOVE EXISTING LADDER AND REPLACE TO
ACCOMODATE NEW HEIGHT OF ROOF.
02-33 SEE MECHANICAL DRAWINGS FOR THE REMOVAL AND
REPLACEMENT OF THE EXISTING ROOF DRAIN.
DEMOLITION LEGEND:
SHEET SPECIFIC NOTES:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VISIT THE PROJECT AND VERIFY EXISTING
CONDITIONS/DIMENSIONS AND PROPOSED CONDITIONS.
2. THE DEMOLITION PLAN INDICATES GENERAL INFORMATION AND INTENT. THE CONTRACTOR SHALL COORDINATE
DEMOLITION WITH NEW CONSTRUCTION TO ENSURE QUALITY OF FINAL PRODUCT.
3. DASHED BOLD LINES INDICATE EXTENT OF DEMOLITION INCLUDING THE FOLLOWING: INTERIOR PARTITIONS (REMOVE TO STRUCTURE); CEILINGS, INCLUDING CEILING SUSPENSION SYSTEM, MISC. STEEL SUPPORTS FOR SUSPENDED EQUIPMENT, SUSPENDED EQUIPMENT, LIGHT FIXTURES, DIFFUSERS AND GRILLES ETC.; FLOOR FINISHES (TO CONCRETE) INCLUDING CARPET, RESILIENT TILE, SHEET VINYL, CERAMIC TILE ETC; DOORS AND FRAMES UNLESS NOTED OTHERWISE; CMU BLOCK/BRICK AND BACKUP WALL SYSTEM; CABINET WORK, SHELVING, BASES; TOILET
PARTITIONS AND ACCESSORIES; EQUIPMENT ITEMS; PLUMBING FIXTURES.
4. GENERAL CONTRACTOR SHALL COORDINATE DEMOLITION BETWEEN ALL TRADES. NOTIFY A/E IMMEDIATELY OF ANY
CONFLICTS OR DISCREPANCIES.
5. REFER TO PHASING SHEET FOR PROJECT PHASING AND SEQUENCE OF WORK. ALL DEMOLITION AND REMODEL WORK
MUST BE CLOSELY COORDINATED WITH THE COR.
6. THE GENERAL CONTRACTOR SHALL INSPECT AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK, INCLUDING ELEMENTS SUBJECT TO DAMAGE OR MOVEMENT DURING DEMOLITION, CUTTING OR PATCHING.
7. MATERIAL PRODUCT FROM DEMOLITION SHALL BECOME THE PROPERTY AND RESPONSIBILITY OF THE CONTRACTOR WITH THE EXCEPTION OF SPECIFIED ITEMS DESIGNATED EITHER IN THE PLANS OR VERBALLY REQUESTED BY THE
(COR) TO BE RETAINED BY THE VA.
8. OFFSITE DISPOSAL OF THE DEMOLISHED ITEMS IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE
DISPOSED OF LAWFULLY.
9. DEMOLITION MATERIALS SHALL BE REMOVED FROM SITE ON A DAILY BASIS. COORDINATE WITH THE COR THE
IDENTIFICATION AND TRANSFER OF ANY ITEMS THAT NEED TO BE SALVAGED.
10. VERIFY LOCATION OF EXISTING UTILITY LINES PRIOR TO STARTING DEMOLITION. MAY NOT BE LIMITED TO UTILITIES SHOWN ON ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL PLANS. REFER TO THE THESE DRAWINGS
FOR ADDITIONAL INFORMATION.
11. UPON ENCOUNTERING UNFORESEEN CONDITIONS DURING REMODEL WORK, THE CONTRACTOR SHALL NOTIFY THE
(COR) BEFORE PROCEEDING.
12. COORDINATE DEMOLITION SHOWN ON THIS SHEET WITH DEMOLITION SHOWN ON MECHANICAL, PLUMBING, AND ELECTRICAL DEMOLITION DRAWINGS. CREATE PENETRATIONS AS REQUIRED FOR NEW CONSTRUCTION ON
MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
13. THE CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION TO REMAIN. DAMAGE TO EXISTING CONSTRUCTION
SHALL BE REPAIRED TO EXISTING OR BETTER CONDITION.
14. ERECT AND MAINTAIN TEMPORARY PARTITIONS AND ENCLOSURES FOR EXTERIOR OPENINGS TO PREVENT THE
TRANSMISSION OF DUST, ODOR, AND NOISE AND MAINTAIN WEATHER TIGHT CONDITIONS.
15. PROVIDE TEMPORARY MECHANICAL EXHAUST SYSTEMS TO MAINTAIN A NEGATIVE PRESSURE WITHIN DEMOLITION
ZONES.
16. AT INTERSECTIONS OF REMOVED WALLS WITH WALL TO REMAIN, REPAIR REMAINING WALLS TO MATCH ADJACENT
FINISHED WALLS OR BETTER.
17. CONTRACTOR SHALL PROVIDE TEMPORARY SEAL AT ALL DOOR AND WALL OPENINGS AT PERIMETER WALLS DURING
DEMOLITION WORK TO PROTECT ADJACENT AREAS FROM DUST INTRUSION.
18. SOLID SHADED (GRAY) REGIONS DEPICT EXISTING CONSTRUCTION TO REMAIN.
19. SEE MECHANICAL, ELECTRICAL AND FIRE PROTECTION DRAWINGS FOR OTHER DEMOLITION WORK.
20. CONTRACTOR SHALL BE RESPONSIBLE FOR MOVING ALL FURNISHINGS AND NON PERMANENTLY ATTACHED
EQUIPMENT PRIOR TO COMMENCEMENT OF DEMOLITION. CONTRACTOR SHALL COORDINATE WITH COR ON LOCATION
OF STORED FURNISHINGS.
21. CAP/ABANDON ALL UTILITIES NOT REMOVED TO MAKE ROOM FOR NEW CONSTRUCTION AS REQUIRED. COORDINATE
WITH PROPOSED NEW CONSTRUCTION CONDITIONS.
22. SEE DEMOLITION CEILING PLAN FOR CEILING DEMOLITION.
23. CONTRACTOR SHALL PROTECT ADJACENT ROOMS FROM DAMAGE DURING CONSTRUCTION. RESTORE ALL DAMAGE
TO ORIGINAL CONDITION.
24. ALL INFILL AND PATCHWORK SHALL MATCH ADJACENT SURFACES, IE. WALL, CEILINGS, FLOORS, ETC. COORDINATE
WITH NEW FINISHES WHERE REQUIRED; SEE FINISH SCHEDULE FOR DISTURBED/DAMAGED BY DEMOLITION AND NEW
CONSTRUCTION.
25. DEMOLITION PLANS SHOW EXISTING ROOM NAMES AND NUMBERS. ALL OTHER DRAWINGS SHOW NEW AND EXISTING
ROOM NAMES AND NUMBERS.
1/8" = 1'-0"
DEMOLITION - ROOF PLAN
3/4" = 1'-0"
DEMO ROOF HATCH ACCESS LADDER
1/4" = 1'-0"
Elevation 3 - a
NORTH
N
UP
S P
S P
S P
S P
SPSP SPSP
S P
S P
S P
SPSP SPSPSPSPSP
S P
S P
S P
S P
S P
S P
SP
S P
SP SPSP SP
S P
S P
S P
S P
SP SP
A2.001
A2.00 3
A
A3.00
A3.00
A3.00
A3.00
A3.00
A3.00
A4.00
A4.00
MECHANICAL
ROOM
EBD - 70
STORAGE
EBD - 80
BREAK ROOM
EBD - 95
WET ROOM
BD - 133
TOILET
BD - 132
OFFICE
BD - 131
CONFERENCE
ROOM
BD - 130
STANDALONE
PRIMARY
BD - 110
MECHANICAL
BD - 117
ELECTRICAL
BD - 130A
GEMS STORAGE
BD - 120
HOUSEKEEPING
EXPENDABLES
BD - 121
MEN'S LOCKER
ROOM
BD - 118
WOMEN'S
LOCKER ROOM
BD - 119
LEADS
WORKROOM
BD - 122
EQUIPMENT
STORAGE
BD - 116
CART STORAGE
BD - 115
EMS WORKROOM
BD - 112
STAFF LOUNGE
BD - 123
OFFICE
BD - 114
OFFICE
SUPERVISORS
BD - 124
SECRETARY
OFFICE
BD - 126
OFFICE EMS
CHIEF
BD - 127
OFFICE EMS
ASST CHIEF
BD - 128
OFFICE ADMIN
OFFICER
BD - 129
OFFICE GEMS
COORDINATOR
BD - 125
OFFICE
PROGRAM
SUPPORT ASST
BD - 113
A5.01
A4.00
A4.00
B
C
CORRIDOR
CO01
CORRIDOR
CO02
CORRIDOR
CO03
B D
-1
BD-116
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
B D
-1
BD-130A
C O
BD-110
BD-112
BD-125
BD-124
CO03A
BD-117B
STAIRWELL
#24
STAIRWELL
EBD - 70A 09-35 09-35 09-35
A1.43
A1.43
A1.43
A1.43
A1.43
A1.43
A1.43
A1.43
SIM
A1.43
SIM
A1.43
A1.43
A1.43
SIM
A1.43
A1.43
SIM
A1.43
A1.43
SIM
A1.43
SIM
A1.43
A1.43
A1.43
A1.44
A1.44
A4.00
A3.00
A3.20
A5.019
A5.0113
A5.01 15
A5.01 19
A3.00
A3.00
CO01
CO03B
BD-118A
BD-118B BD-119B
BD-119A
B D
-1
B D
-1
MHO
WOMEN'S
SHOWER
BD - 119A
MEN'S SHOWER
BD - 118A
WOMEN'S TOILET
BD - 119B
MEN'S TOILET
BD - 118B
A5.0232
A3.11
FEC
F E
C
FEC
SIM.
11-01
11-01
07-0707-07
A1.43
Sim
D
07-07
09-4409-4409-44
A5.01
AREA NOT IN THE SCOPE. EXISTING
TO REMAIN.
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL
EXPOSED STRUCTURAL STEEL,
DECKING,SECONDARY STRUCTURE WITHIN
CEILING SPACE ABOVE BASEMENT & FIRST
FLOOR LEVEL CEILING, TYP. EXCEPT STAIRS.
KEYPLAN
NOT TO SCALE
N
FIRE BARRIER SYMBOLS
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
SMOKE PARTITION
2-HOUR SMOKE BARRIER
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
FLOOR PLAN - BASEMENT LEVEL
A1.01
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
25 128
1/8" = 1'-0"
NEW FLOOR PLAN - BASEMENT LEVEL
LEGEND:
SHEET SPECIFIC NOTES:
1. 88' - 0" FINISH FLOOR BASEMENT LEVEL
2. SEE CODE PLAN FOR CODE INFORMATION.
3. SEE DIMENSION PLAN FOR DIMENSIONS AND WALL
TYPES.
4. SYSTEMS FURNISHINGS AND OWNER PROVIDED
CONTRACTOR INSTALLED ITEMS SHOWN DASHED
LINEWORK, SEE FFE PLANS FOR CLARITY.
5. MECHANICAL, PLUMBING, & ELECTRICAL FIXTURES
SHOWN FOR REFERENCE ONLY, SEE
MECHANICAL/ELECTRICAL DRAWINGS.
6. REFER TO PHASING PLAN FOR AREAS OF WORK
SEQUENCE AND TEMPORARY CONSTRUCTION
PARTITIONS.
GENERAL NOTES:
KEYNOTES:
07-07 APPLY 60 MIL INTUMESCENT FIRE-PROOFING PAINT, UL
BXUV. Y634 ALL ALL EXPOSED STEEL STRUCTURE (IE
BEAMS, DECK, LATERAL BRACING).
09-35 INFILL WITH WALL TYPE M3D (2HR RATED WALL). PAINT
AND FINISH INTERIOR TO MATCH EXISTING ADJACENT
WALL AREA.
09-44 SEE DIMENSION PLAN FOR WALL TYPES BEING PLACED
IN OPENINGS LEFT FROM THE REMOVED LOUVERS.
WALL INFILL SHALL BE CONSTRUCTED TIGHT TO THE
NEW DUCTWORK THAT IS SHOWN ON MECHANCIAL
DRAWINGS.
11-01 WALL MOUNTED DISPLAY BY OWNER. TYPICAL. SEE
ELECTRICAL FOR CONNECTION TYP.
NORTH
N
ROOM SCHEDULE - BASEMENT LEVEL
Number Name
BD - 110 STANDALONE PRIMARY
BD - 112 EMS WORKROOM
BD - 113 OFFICE PROGRAM SUPPORT ASST
BD - 114 OFFICE
BD - 115 CART STORAGE
BD - 116 EQUIPMENT STORAGE
BD - 117 MECHANICAL
BD - 118 MEN'S LOCKER ROOM
BD - 118A MEN'S SHOWER
BD - 118B MEN'S TOILET
BD - 119 WOMEN'S LOCKER ROOM
BD - 119A WOMEN'S SHOWER
BD - 119B WOMEN'S TOILET
BD - 120 GEMS STORAGE
BD - 121 HOUSEKEEPING EXPENDABLES
BD - 122 LEADS WORKROOM
BD - 123 STAFF LOUNGE
BD - 124 OFFICE SUPERVISORS
BD - 125 OFFICE GEMS COORDINATOR
BD - 126 SECRETARY OFFICE
BD - 127 OFFICE EMS CHIEF
BD - 128 OFFICE EMS ASST CHIEF
BD - 129 OFFICE ADMIN OFFICER
BD - 130 CONFERENCE ROOM
BD - 130A ELECTRICAL
BD - 131 OFFICE
BD - 132 TOILET
BD - 133 WET ROOM
CO01 CORRIDOR
CO02 CORRIDOR
CO03 CORRIDOR
EBD - 70 MECHANICAL ROOM
EBD - 80 STORAGE
STAIRWELL #24 STAIRWELL #24
DN
S P
S P
S P
SP SP
S P
S P
S P
SPSP
S P
S P
S P
SP SPSP SP
SP SP
SPSP
S P
S P
S P
S P
SP SP
SP SP
SP SP
A2.001
A2.00 3
BARIATRIC EXAM
1D -176
EXAM
1D -175
EXAM
1D -174
EXAM
1D -172
EXAM
1D -171
RECEPTION/WAITING
1D -193
OFFICE
1D -199
OFFICE
1D -198
HAC
1D -178
EXAM
1D -189
EXAM
1D -190
EXAM
1D -187
EXAM
1D -186
EXAM
1D -185
EXAM
1D -184
EXAM
1D -181
EXAM
1D -179
EXAM
1D -177
STAFF TLT
1D -188A
EQUIP STG
1D -191A
WELLNESS
1D -191
OFFICE
1D -196
BREAK ROOM
1D -188
PHARMACY
OFFICE
1D -192
ELECT
1D -195
LOGISTICS STG
1D -194
SOILED
E1D -86
EXAM
E1D -102 SOILED
E1D -103
EXAM
E1D -104
TLT
E1D -109
OFFICE (M.H.)
E1D -108
CONSULT (M.H.)
E1D -110
OFFICE (M.H.)
E1D -112
LINEN
E1D -113
TLT
E1D -115
COPY AREA
E1D -121
OFFICE (PHARM)
E1D -122
TLT
E1D -123
WORK ROOM
(P.C. DOC'S)
E1D -124
CONSULT (S.W.)
E1D -126
TOILET
E1D -127
TOILET
E1D-127A
HAC
E1D -131
SOCIAL
WORKER'S
CONSULT
E1D -132
SOCIAL
WORKERS
E1D -133
MEDS
E1D -134
OPER 8
E1D -135
ELEV
E37
LOCKER
E1D - 128
CONF
E1D - 129
STAFF BREAK
ROOM
E1D - 130
STAIRWELL
#24
TLT
E1D - 117
A
OFFICE
1D -197
A3.00
A3.00
A3.00
A3.00
A3.00
A3.00
A4.00
A4.00
WORK ROOM
1D -173
CLEAN LINEN
1D -180
TOILET
1D -182
SOILED LINEN
1D -183
A4.00
B
C
CORRIDOR
CO04
CORRIDOR
CO05
CORRIDOR
CO06
1D-176 1D-175 1D-174 1D-172 1D-171
D
-1
D
-1
D
-1
D
-1
D
-1
D
-1
D
-1
1D-184 1D-185 1D-186 1D-187 1D-189 1D-190 1 D
-1 A
D
-1
D
-1 B
D
-1 7 1D-178
D
-1
1D-180
1D-182
D
-1
1D-183
1D-191
CO06A
D
-1 A
A1.02
D
-1 B
A1.43
A1.43
A1.43
A1.43
A1.43
A1.43
A1.43
A1.43
CONSULT PHARM
E1D -116
WORK ROOM
(P.C. DOC'S)
E1D -120
CORRIDOR
1D -121
A1.43
SIM
09-3509-35 09-35 09-35 09-35 09-35
09-35 09-35 09-35 09-35 09-35 09-35
SIM
SIM
SIM SIM SIM
A1.43
A1.43
SIM
A1.43
A1.43
A1.43
SIMA1.43
SIM
A1.43
SIM
A1.43
1D-188A
A5.02 2
A5.0221
A5.02
A5.0231
A5.02
A5.02
A5.02
A4.00
A3.00
A3.20
A3.00
A3.00
1D-192
D
-1
15 9
MHO
A6.01
A3.11
A5.02 33
FEC
FEC
F E
C
FEC
A1.44
A5.02
CORRIDOR
E1D - CO
11-01
11-01
11-01
21-02
A5.02
A5.0227
A5.0226
07-0707-07
A5.02
1 Sim
S im
3 Sim
S im
A5.02
2 Sim
S im
4 Sim
S im
A5.02 2
S im
S im
1 Sim
3 Sim
D
11-21
E D
-1
AREA NOT IN THE SCOPE. EXISTING
TO REMAIN.
KEYPLAN
NOT TO SCALE
N
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL
EXPOSED STRUCTURAL STEEL,
DECKING,SECONDARY STRUCTURE WITHIN
CEILING SPACE ABOVE BASEMENT & FIRST
FLOOR LEVEL CEILING, TYP. EXCEPT STAIRS.
FIRE BARRIER SYMBOLS
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
SMOKE PARTITION
2-HOUR SMOKE BARRIER
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:2
A
M
CONSTRUCTION DOCUMENTS
11/16/21
FLOOR PLAN - FIRST LEVEL
A1.02
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
26 128
NORTH
N
1/8" = 1'-0"
NEW FLOOR PLAN - FIRST LEVEL
LEGEND:
ROOM SCHEDULE - FIRST LEVEL
Number Name
1D -121 CORRIDOR
1D -171 EXAM
1D -172 EXAM
1D -173 WORK ROOM
1D -174 EXAM
1D -175 EXAM
1D -176 BARIATRIC EXAM
1D -177 EXAM
1D -178 HAC
1D -179 EXAM
1D -180 CLEAN LINEN
1D -181 EXAM
1D -182 TOILET
1D -183 SOILED LINEN
1D -184 EXAM
1D -185 EXAM
1D -186 EXAM
1D -187 EXAM
1D -188 BREAK ROOM
1D -188A STAFF TLT
1D -189 EXAM
1D -190 EXAM
1D -191 WELLNESS
1D -191A EQUIP STG
1D -192 PHARMACY OFFICE
1D -193 RECEPTION/WAITING
1D -194 LOGISTICS STG
1D -195 ELECT
1D -196 OFFICE
1D -197 OFFICE
1D -198 OFFICE
1D -199 OFFICE
CO04 CORRIDOR
CO05 CORRIDOR
CO06 CORRIDOR
E1D -108 OFFICE (M.H.)
E1D -110 CONSULT (M.H.)
E1D -112 OFFICE (M.H.)
E1D -116 CONSULT PHARM
E1D -120 WORK ROOM (P.C. DOC'S)
E1D -122 OFFICE (PHARM)
E1D -124 WORK ROOM (P.C. DOC'S)
E1D -126 CONSULT (S.W.)
E1D - 128 LOCKER
E1D - 129 CONF
E1D - 130 STAFF BREAK ROOM
E1D-127A TOILET
EBD - 70A STAIRWELL
STAIRWELL #24 STAIRWELL #24
SHEET SPECIFIC NOTES:
GENERAL NOTES:
FURNITURE SCHEDULE
TAG NAME
1 BARIATRIC CHAIR
2 STANDARD CHAIR
3 DUAL MONITOR DESK
4 ACUPUNCTURE TABLE
5 HANDWASHING SINK
6 EXAM ROOM CURTAIN
7 FOLDING CHAIR
8 WORK CHAIR
1/4" = 1'-0"
TYPICAL - FURNITURE PLAN LAYOUT
SHEET SPECIFIC NOTES:
1. 100' - 0" FINISH FLOOR FIRST LEVEL
2. SEE CODE PLAN FOR CODE INFORMATION.
3. SEE DIMENSION PLAN FOR DIMENSIONS AND WALL
TYPES.
4. SYSTEMS FURNISHINGS AND OWNER PROVIDED
CONTRACTOR INSTALLED ITEMS SHOWN DASHED
LINEWORK, SEE FFE PLANS.
5. MECHANICAL, PLUMBING, & ELECTRICAL FIXTURES
SHOWN FOR REFERENCE ONLY, SEE
MECHANICAL/ELECTRICAL DRAWINGS.
6. REFER TO PHASING PLAN FOR AREAS OF WORK
SEQUENCE AND TEMPORARY CONSTRUCTION
PARTITIONS.
KEYNOTES:
07-07 APPLY 60 MIL INTUMESCENT FIRE-PROOFING PAINT, UL
BXUV. Y634 ALL ALL EXPOSED STEEL STRUCTURE (IE
BEAMS, DECK, LATERAL BRACING).
09-35 INFILL WITH WALL TYPE M3D (2HR RATED WALL). PAINT
AND FINISH INTERIOR TO MATCH EXISTING ADJACENT
WALL AREA.
11-01 WALL MOUNTED DISPLAY BY OWNER. TYPICAL. SEE
ELECTRICAL FOR CONNECTION TYP.
11-21 BLANKET WARMER BY OWNER. SEE ELECTRICAL FOR
CONNECTION.
21-02 OVERFLOW ROOF DRAIN LAMBS TOUNGE. COORDINATE
PLACEMENT WITH MECHANICAL DRAWINGS.
S P
S P
S P
S P
SPSP SPSP
S P
S P
S P
SPSP SPSPSPSPSP
S P
S P
S P
S P
S P
S P
SP
S P
SP SPSP SP
S P
S P
S P
S P
SP SP
16 16
14 14
13 13
A
18 18
MECHANICAL
ROOM
EBD - 70
STORAGE
EBD - 80
BREAK ROOM
EBD - 95
91' - 0"
13' - 4"
1' - 10" 87' - 4" 1' - 10" 11' - 6" 1' - 10" 20' - 8" 18' - 2" 1' - 5"
WET ROOM
BD - 133
TOILET
BD - 132
OFFICE
BD - 131 CONFERENCE
ROOM
BD - 130
STANDALONE
PRIMARY
BD - 110
MECHANICAL
BD - 117
ELECTRICAL
BD - 130A
GEMS STORAGE
BD - 120
HOUSEKEEPING
EXPENDABLES
BD - 121
MEN'S LOCKER
ROOM
BD - 118
WOMEN'S
LOCKER ROOM
BD - 119
LEADS
WORKROOM
BD - 122
EQUIPMENT
STORAGE
BD - 116
CART STORAGE
BD - 115
EMS WORKROOM
BD - 112
STAFF LOUNGE
BD - 123
OFFICE
BD - 114
OFFICE
SUPERVISORS
BD - 124
SECRETARY
OFFICE
BD - 126
OFFICE EMS
CHIEF
BD - 127
OFFICE EMS
ASST CHIEF
BD - 128
OFFICE ADMIN
OFFICER
BD - 129
OFFICE GEMS
COORDINATOR
BD - 125
OFFICE
PROGRAM
SUPPORT ASST
BD - 113
B
C
3' - 3"7' - 3"2' - 8"8' - 6"
22' - 7" 13' - 0" 11' - 6" 13' - 9" 10' - 10" 13' - 8"
2' - 2" 1' - 3"1' - 3" ± 1' - 8"
29' - 0" 29' - 1" 10' - 2" 9' - 8"
2' - 6" 18' - 11"
2' - 0"
6' - 3"
19' - 10"
41' - 11" 36' - 0"
42' - 2" 10' - 4" 25' - 5"
6' - 2"
10' - 3"
12' - 10"
2' - 4"
15' - 8" 11' - 8" 9' - 3" 10' - 1" 8' - 11"
1' - 7"
1' - 2"
1' - 0"
18' - 6" 7' - 10" 9' - 10" 10' - 8"
15' - 4" 17' - 6"
2' - 0"
2' - 4"
9' - 10" 19' - 6"
4' - 0" 13' - 2"
2' - 4"
"1
6' - 6" 3' - 0" 5' - 4" 3' - 0" 6' - 4" 3' - 0" 13' - 0"
3' - 0"
1' - 0"
3' - 0"
1' - 0"
3' - 0" 4' - 0"
16' - 0" 3' - 8"
1' - 10" 30' - 0" 20' - 11" 19' - 3"
8' - 2"
M6A
M6A
SW1
SW1
M2A
SW1
M2A
M3A
M3A
M2A
M3A
M3A
M2A
M3A
M2A
M3AM3A
M3A
M3A
M3A
M2A
M3A
M3A M3B M3B M3B
M3B
M3A
M3B
M3B
M3A
M6B
M3A
M3AM3A
M3A
M2A
M3A
M14A
M3B
M3A
M2A
M6B
M2A
M3A M3A M3A
M6A
M2A
M2A
M3A
M3AM2A
M2A
M6B
M3A
M3A
M3A
M3A
M3AM3A
M3A
M3A
M2A
M3A
M3A M3A
M2A
M2A
M3A
M3B
B12D
B8C E3 2E3 2
M3A
M2A
M3A
M6A
M3A
M3A M3A
M12A
M3A
M3A
M3A
M2A
M3B
M3B
SW1SW1
M3B
D DD
D D D
A
F M3A
M3A
STAIRWELL
EBD - 70A
WOMEN'S
SHOWER
BD - 119A
MEN'S SHOWER
BD - 118A
WOMEN'S TOILET
BD - 119B
MEN'S TOILET
BD - 118B
STAIRWELL
#24
6' - 6 13/16" 7' - 8 13/16"
/8
/4
5' - 4 1/16"
C
88' - 0"
M3DM3DM3DM3DM3DM3DSW1
M3B
SW1
M3A
D
M3B
A1.44
KEYPLAN
NOT TO SCALE
N
AREA NOT IN THE SCOPE. EXISTING
TO REMAIN.
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL
EXPOSED STRUCTURAL STEEL,
DECKING,SECONDARY STRUCTURE WITHIN
CEILING SPACE ABOVE BASEMENT & FIRST
FLOOR LEVEL CEILING, TYP. EXCEPT STAIRS.
FIRE BARRIER SYMBOLS
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
SMOKE PARTITION
2-HOUR SMOKE BARRIER
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:3
A
M
CONSTRUCTION DOCUMENTS
11/16/21
DIMENSION PLAN - BASEMENT LEVEL
A1.20
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
27 128
1/8" = 1'-0"
DIMENSION PLAN - BASEMENT LEVEL
LEGEND:
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. ALL DIMENSIONS ARE FACE OF STUD OR FACE OF
MASONRY UNLESS NOTED OTHERWISE. AT
PARTITION WALLS, DIMENSIONS ARE TO ONE SIDE
OF WALL.
2. OPENINGS ARE DIMENSIONED TO FRAME WIDTH.
CONTRACTOR TO COORDINATE ROUGH OPENING
DIMENSIONS AS REQUIRED.
3. SEE ENLARGED AREA PLANS FOR WALL TYPE
INDICATIONS AND DIMENSIONS.
NORTH
N
DN
S P
S P
S P
SP SP
S P
S P
S P
SPSP
S P
S P
S P
SP SPSP SP
SP SP
SPSP
S P
S P
S P
S P
SP SP
SP SP
SP SP
A
BARIATRIC EXAM
1D -176
EXAM
1D -175
EXAM
1D -174
EXAM
1D -172
EXAM
1D -171
RECEPTION/WAITING
1D -193
OFFICE
1D -199
OFFICE
1D -198
HAC
1D -178
EXAM
1D -189
EXAM
1D -190
EXAM
1D -187
EXAM
1D -186
EXAM
1D -185
EXAM
1D -184
EXAM
1D -181
EXAM
1D -179
EXAM
1D -177 STAFF TLT
1D -188A
EQUIP STG
1D -191A
WELLNESS
1D -191
OFFICE
1D -196
BREAK ROOM
1D -188
PHARMACY
OFFICE
1D -192
ELECT
1D -195
LOGISTICS STG
1D -194
SOILED
E1D -86
EXAM
E1D -102
SOILED
E1D -103
EXAM
E1D -104
TLT
E1D -109
OFFICE (M.H.)
E1D -108
CONSULT (M.H.)
E1D -110
OFFICE (M.H.)
E1D -112
LINEN
E1D -113
TLT
E1D -115
COPY AREA
E1D -121
OFFICE (PHARM)
E1D -122
TLT
E1D -123
WORK ROOM
(P.C. DOC'S)
E1D -124
CONSULT (S.W.)
E1D -126
TOILET
E1D -127
TOILET
E1D-127A
HAC
E1D -131
SOCIAL
WORKER'S
CONSULT
E1D -132
SOCIAL
WORKERS
E1D -133
MEDS
E1D -134
OPER 8
E1D -135
ELEV
E37
LOCKER
E1D - 128
CONF
E1D - 129
STAFF BREAK
ROOM
E1D - 130
STAIRWELL
#24
TLT
E1D - 117
OFFICE
1D -197
SOILED LINEN
1D -183
TOILET
1D -182
CLEAN LINEN
1D -180
B
C
4' - 4"
3' - 0"
1' - 0"
3' - 0"
4' - 4"
3' - 0"
1' - 0"
3' - 0"
4' - 8"
3' - 0"
1' - 0"
3' - 0"
4' - 4"
3' - 0"
1' - 0"
3' - 0"
4' - 8"
3' - 0"
1' - 0"
3' - 0"
4' - 4"
3' - 0"
1' - 0"
3' - 0" 22' - 0"
10' - 9" 11' - 6" 11' - 6" 11' - 6" 11' - 6" 11' - 6"
4' - 2"
13' - 3"
1' - 8" 22' - 9" 23' - 4" 24' - 1" 17' - 3" 1' - 8" 11' - 8" 22' - 6" 19' - 5"
1' - 9" 1' - 5"
90' - 8" 53' - 6"
4' - 0"
3' - 8"
4" 3' - 0"
3' - 4"
3' - 0" 5' - 4" 3' - 0"
6' - 4"
3' - 0" 8' - 0" 3' - 4"
1' - 6"
6' - 1" 10' - 4"
19' - 10" 10' - 2"
5' - 5"
14' - 5"
11' - 11" 12' - 5" 12' - 5" 12' - 5" 12' - 5"
14' - 7"
11' - 5" 44' - 8"
8' - 6" 9' - 7" 11' - 9" 6' - 2" 8' - 10" 8' - 10" 8' - 10" 8' - 11" 8' - 10"
M6B
M3C M6C M3C
M6C
M2A
M6CM3C M6CM3C
M2A
M6CM3C M3C
M3B
M3A M2AM3C
M6C
M6C
M6C
M3C M2A
M2A M3C
M3C
M3C
M3B
M3B
M6A M6A M6A M6A M3CM6B
M3C M3C M3C M3C
SW1 SW1 SW1
M3A M3A
M3A
CONSULT PHARM
E1D -116
WORK ROOM
(P.C. DOC'S)
E1D -120
M3C
M2A
SW1
SW1 SW1
M12A
SW1
M3A
M3AM3A
M3A
M3AM2AM3C
M3A
M6A
M3A
M6A
M6A
M6A
M16A M3A
M3A
M2A M3A
M2A
M3A
M3B
M2A
M6C
M3A
M3A
M3A
M3A M6A M3C M3C
M3C
M3C M3C M3CM2A B8C
M2A M2A
M3A M3C M3C
SW1
M3C M3C M3C
SW1 B12D
E3'E3'
M3A
M3A
SW1
SW1SW1
M3A'
M2A
M3D M3D M3D M3D M3D M3D
D
D
E
D
D
D
D
D
D
E
D D D D D D D D D D D D
D
D D D C
A
B
M6A
WORK ROOM
1D -173
M2AM2A
SW1SW1 M3D M3D M3DM3D M3D M3D
M2A
M3A
E3
100' - 0"
M3B
D
8' - 4"
3' - 8"
6' - 7"
3' - 4" 7' - 7"
10"
10"
13' - 5" 8' - 6" 16' - 3"
KEYPLAN
NOT TO SCALE
N
AREA NOT IN THE SCOPE. EXISTING
TO REMAIN.
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL
EXPOSED STRUCTURAL STEEL,
DECKING,SECONDARY STRUCTURE WITHIN
CEILING SPACE ABOVE BASEMENT & FIRST
FLOOR LEVEL CEILING, TYP. EXCEPT STAIRS.
FIRE BARRIER SYMBOLS
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
SMOKE PARTITION
2-HOUR SMOKE BARRIER
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
DIMENSION PLAN - FIRST LEVEL
A1.21
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
28 128
1/8" = 1'-0"
DIMENSION PLAN - FIRST LEVEL
NORTH
N
LEGEND:
GENERAL NOTES:
SHEET SPECIFIC NOTES:
1. ALL DIMENSIONS ARE FACE OF STUD OR FACE OF
MASONRY UNLESS NOTED OTHERWISE. AT
PARTITION WALLS, DIMENSIONS ARE TO ONE SIDE
OF WALL.
2. OPENINGS ARE DIMENSIONED TO FRAME WIDTH.
CONTRACTOR TO COORDINATE ROUGH OPENING
DIMENSIONS AS REQUIRED.
3. SEE ENLARGED AREA PLANS FOR WALL TYPE
INDICATIONS AND DIMENSIONS.
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL
EXPOSED STRUCTURAL STEEL,
DECKING,SECONDARY STRUCTURE WITHIN
CEILING SPACE ABOVE BASEMENT & FIRST
FLOOR LEVEL CEILING, TYP. EXCEPT STAIRS.
E2
FACE BRICK
7/8" DRAINAGE MAT
1" RIGID INSULATION
FLUID APPLIED MEMBRANE AIR/MOISTURE BARRIER
1/2" GYPSUM BOARD SHEATHING
6" METAL STUDS AT 16" O.C. WITH BLOWN IN BLANKET SYSTEM INSULATION
5/8" GYPSUM BOARD
5/8" TYPE 'X' GYPSUM BOARD
1 5/8" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
M2A
5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
"M3A
5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
NOTE:
1. PROVIDE ACOUSTICAL INSULATION AT WALL CAVITIES.
2. ALL WALLS (NO MATTER WHAT TYPE OR IF JUST FURRING OUT AN
EXISTING WALL) WILL GO DECK TO DECK. FIRE AND SMOKE BARRIERS AS
WELL AS CORRIDOR WALLS SHALL HAVE ALL PENETRATIONS FIRE
CAULKED / FIRE PROOFED. WALLS BETWEEN ROOMS SHALL BE SEALED
WITH FIRE TAPING OF THE WALL OR STANDARD CAULKING. UNLESS
HIGHER LEVEL OF PROTECTION REQUIRED IF WALL IS RATED.
ALL WALLS GET MENERAL WOOL AT MINIMUM IN CAVITY. RATED WALLS
GET 2 HR FIRE STOP PRODUCTS & APPLIES TO ALL CORRIDOR WALLS AS
WELL. BETWEEN ROOM GET SILICONE, TAPED/MUDDED, ETC. FOR 1 HR
WALL.
3. SEE DRAWING SHEET G1.01 FOR RATED WALL (BOTH FIRE AND SMOKE)
REQUIREMENTS.
4. CEMENTISOUS TILE BACKER BOARD SHALL BE SUBSTITUTED FOR
GYPSUM WALL BOARD AT ALL LOCATIONS WITH WALL TILE.
M3B
5/8" TYPE 'X' GYPSUM BOARD
6" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
M6A
5/8" TYPE 'X' GYPSUM BOARD
6" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
"M6B
M12A
M14A
5/8" TYPE 'X' GYPSUM BOARD
8" CMU
1 5/8" METAL STUDS AT 16"O.C.
5/8" TYPE 'X' GYPSUM BOARD
8" CMU
B8C
B12D
5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16" O.C.
FULL BATT INSULATION
6 3/4" AIR GAP
3 5/8" METAL STUDS AT 16" O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
"M16A
5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16" O.C.
FULL BATT INSULATION
8 3/4" AIR GAP
3 5/8" METAL STUDS AT 16" O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
(2) 5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
(2) 5/8" TYPE 'X' GYPSUM BOARD
"M3D
STC=40 MIN
UL419 = 2 HOURS
5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16" O.C.
FULL BATT INSULATION
4 3/4" AIR GAP
3 5/8" METAL STUDS AT 16" O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
(2) 5/8" TYPE 'X' GYPSUM BOARD
6" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
M6C
STC=40 MIN
E3
NEW FACE BRICK
3/8" DRAINAGE MAT
EXIST. 1 1/2" RIGID INSULATION
EXIST. FLUID APPLIED MEMBRANE AIR/MOISTURE BARRIER
EXIST. 1/2" GYPSUM BOARD SHEATHING
EXIST. 6" METAL STUDS AT 16" O.C. WITH BLOWN IN BLANKET SYSTEM INSULATION
EXIST. 5/8" GYPSUM BOARD
SW1
1" SHAFT LINER
2 1/2" STEEL C - H CHANNELS AT 16" O.C.
(2)5/8" TYPE 'X' GYPSUM BOARD
UL 415 2 HOURS
"M3C
5/8" TYPE 'X' GYPSUM BOARD
3 5/8" METAL STUDS AT 16"O.C.
FULL BATT INSULATION
5/8" TYPE 'X' GYPSUM BOARD
STC=40 MIN
SMOKE PARTITION, WHERE INDICATED
ON DRAWING SHEET G1.01
SMOKE PARTITION, WHERE INDICATED
ON DRAWING SHEET G1.01
SMOKE PARTITION, WHERE INDICATED
ON DRAWING SHEET G1.01
SMOKE PARTITION, WHERE INDICATED
ON DRAWING SHEET G1.01
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
WALL TYPES
A1.40
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
29 128
GENERAL NOTES:
20 GAUGE MINIMUM METAL SILL
TRACK BELOW
DOUBLE 20 GAUGE MTL
STUDS
20 GAUGE MINIMUM METAL TRACK
AT FLOOR
1" X 20 GAUGE METAL STRAP
PLATES AT 3'-6" OC EACH
SIDE
CLIP ANGLE
1" X 20 GAUGE METAL
STRAP AT 3'-6" O.C.,
EACH SIDE
DOUBLE 20 GAUGE
METAL STUDS AT
BOTH JAMBS
20 GAUGE MINIMUM
METAL TRACK
AT FLOOR
GENERAL NOTES:
1. CONTRACTOR SHALL
COORDINATE LOCATIONS
OF HORIZONTAL
FASTENERS. PLAN
WALL FINISH
VERTICAL WALL STUDS
AT 16" [406mm] OR 24" [610mm] O.C.
CUT HORIZONTAL
FASTENER FROM
STUD
FASTEN AT BOTH ENDS
WITH MINIMUM 4 TAPPING
SCREWS.
TYPE C
14 GAUGE STEEL RUNNER TRACK-
CLIP FLANGES AND FOLD
WEB TO FORM
ATTACHMENT FLANGE
MIN 20 GAUGE METAL STUDS
FACING OPPOSITE
DIRECTIONS TO ALLOW
MOUNTING PLATE
ATTACHMENT
8" MINIMUM, DEEPER IF
REQUIRED
6" MINIMUM, DEEPER IF
REQUIRED
TYPE B
20 GAUGE METAL RUNNER
TRACK - CLIP FLANGES
TO FIT OVER STUDS
CONT16 GAUGE 6" WIDE
METAL BACK-UP STRAP
TYPE A
M O
U N
T I N
G H
E
IG
H T
S
R E
F E
R E
N C
E T
Y P
IC
A
L M
O U
N T
I N G
H E
IG
H
T S
R E
F E
R E
N C
E T
Y P
IC
A
L M
O U
N T
I N G
H E
IG
H
T S
R E
F E
R E
N C
E T
Y P
IC
A
L
1/2" MAX
1/2" MAX1/2" MAX
CONTROL JOINT,
BOTH SIDES
1 1/2"
CONTROL JOINT,
BOTH SIDES
1HOUR FIRE RATED
WHI-647-3024
2 LAYERS OF 5/8"
GYPSUM WALLBOARD
PARTITION AS
SCHEDULED PARTITION AS
SCHEDULED
MAX
24'-0”
MAX
24'-0” 24'-0”
MAX
1 1/2"
CONTROL JOINT,
BOTH SIDES
2HOUR FIRE RATED
WHI-651-0318.1
2 LAYERS OF 5/8" GYPSUM
WALLBOARD
PARTITION AS
SCHEDULED
SOUND ATTENUATION
BLANKET COMPRESSED TO
FILL OPENING AT SOUND
RATED PARTITION
MAX
24'-0”
MAX
24'-0”
CONCRETE, MASONRY OR
STEEL CHANGE IN
CONSTRUCTION
1/2" MAX
CHANGE IN
CONSTRUCTION
PARTITION AS
SCHEDULED
1/2" MAX
LC-BEAD
SEALANT, REFERENCE
SPECS FOR TYPE
MAX
24'-0”
MAX
24'-0”
CONTROL JOINT
1/2" MAX
L-BEAD
SEALANT BOTH SIDE,
PARTITION AS
SCHEDULED GYPSUM WALLBOARD
SUSPENDED
CEILING SYSTEM
REFERENCE SPECS FOR TYPE
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. APPLY 1 1/2" THICK FIREPROOFING AT ALL
EXPOSED STRUCTURAL STEEL,
DECKING,SECONDARY STRUCTURE WITHIN
CEILING SPACE ABOVE BASEMENT & FIRST
FLOOR LEVEL CEILING, TYP. EXCEPT STAIRS.
DOOR, SEE SCHEDULE
HOLLOW METAL DOOR FRAME,
FILL WITH LIGHTWEIGHT
PLASTER
SEALANT AT FRAME PERIMETER
METAL STUD WALL, SEE WALL
TYPES
5/8" GYPSUM BOARD
T Y
P
ADJACENT WALL
S E
E W
A L L
T Y
P E
SEE WALL TYPE
20 GAUGE MINIMUM
METAL TRACK
CLIP ANGLE
FINE, NEAT SEALANT BEAD AT PERIMETER.
FIRE EXTINGUISHER CABINET, VERIFY DIMENSIONS WITH MFR.
AND VA SAFETY STAFF THROUGH VA COR TO ENSURE CURRENT
FARGO VA FIRE EXTINGUISHER SIZE FITS IN FEC.
NOTE:
INSTALL PER MANUFACTURER'S REQUIREMENTS.
PARTITION AS SCHEDULED, SEE LIFE SAFETY PLAN FOR RATED PARTITIONS.
CONTRACTOR TO INSTALL HOOK TO HANG VA
FIRE EXTINGUISHERS
CONCRETE SLAB
LOCKER
RESINOUS FLOOR
4" METAL LOCKER BASE
BY LOCKER MANUFACTURER
1' - 3"
ADDITIONAL NOTES:
1. CONDITIONS INDICATED TO SHOW DESIGN INTENT, AND NOT
INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR
UL-APPROVED CONTROL JOINTS DESIGNS THAT ARE APPROPRIATE
FOR THE SPECIFIC CONDITION. JOINTS TO BE SIZED TO
ACCOMMODATE MOVEMENT CAPABILITIES OF FIRESTOP ASSEMBLY.
METAL STUD BLOCKING FOR WALL MOUNTED
ITEMS SUCH AS CABINETS, TELEVISION
BRACKETS, COUNTERS, WHITE BOARDS,
AND SIMILAR ITEMS. COORDINATE
REQUIREMENTS WITH ITEM TO BE MOUNTED
2" WIDE 20 GAUGE
METAL STRAP
20 GAUGE METAL TOP TRACK
(TYPICAL UNLESS NOTED
OTHERWISE)
ABOVE CEILING
OPENING
PROVIDE DIAGONAL BRACING (AT
45° TYPICAL) OF TOP TRACK AT 48°
O.C. MAX BETWEEN FULL HEIGHT
STUDS
UNDERSIDE OF SLAB,
FLOOR OR ROOF DECK
CEILING LINE
OPENING ABOVE CEILING
WHICH INTERRUPTS LOWER
OPENING JAMB STUDS.
DOUBLE STUDS
DOOR
OPENING
20 GAUGE MINIMUM
BOTTOM TRACK (TYPICAL)
FLOOR LINE
LARGE BELOW
CEILING OPENING
BELOW
CEILING
OPENING
DOUBLE DOOR OPENING
DOOR
OPENING
DOOR
OPENING
NOTES:
1. ALL STUDS ARE SPACED 16" OC MAXIMUM.
2. ALL STUDS SHALL BE "C" STUDS WITH 1/4"
RETURN FLANGE MINIMUM.
3. INDICATES SHELVING OR
CABINETRY.
4. DOUBLE STUDS AT SIDES OF OPENING
SHALL NOT BE CUT FOR DUCT WORK OR
ANY OTHER MECHANICAL SYSTEMS.
5. REFER TO INTERIOR SHEET FOR
MOUNTING TYPE DETAILS.
MOUNTING
DETAIL TYPE B
20 GAUGE MINIMUM STUDS
AT WALL MOUNTED
ARCHITECTURAL
CABINETS/MILLWORK/
ATTACHED SHELVING.
DOUBLE
STUDS
4' 6" MAX
DOUBLE STUDS
8' 6" MAX 4' 6" MAX 8' 6" MAX
ALL STUDS ARE TO BE 20 GAUGE
IF GREATER THAN 8' 6"
8' 6" MAX 4' 6" MAX
8' 6" MAX
LARGE ABOVE CEILING
OPENING
TOP TRACK
A1.41 3
A1.41
A1.41
A1.41
A1.41
A1.41
A1.41
A1.41
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
PARTITION FRAMING DETAILS
A1.41
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
30 128
GENERAL NOTES:
3" = 1'-0"
DOOR DETAIL TYPICAL
1" = 1'-0"
LARGE OPENING JAMB STUDS
1" = 1'-0"
DOOR OPENING JAMB STUDS
1" = 1'-0"
OPENING HEADER
1 1/2" = 1'-0"
FIRE EXTINGUISHER CABINET AT METAL STUD
1" = 1'-0"
DETAIL - ANCHORAGE - GRAB BARS AND CABINETS
1" = 1'-0"
METAL BACKING DETAILS FOR ACCESSORIES AND EQUIPMENT
1 1/2" = 1'-0"
LOCKER BASE
1" = 1'-0"
GYPSUM WALLBOARD CONTROL JOINT DETAILS
1/4" = 1'-0"
FRAMING ELEVATION
1/4" = 1'-0"
TYPICAL INTERIOR PARTITION FRAMING
SLOTTED SLIP TRACK
UNDERSIDE OF STRUCTURAL DECKING
METAL STUD FRAMING AT 16" O.C.
FLEXIBLE SEALANT, EACH SIDE
SEE WALL TYPE
DEFLECTION GAP
SAFING INSULATION
ANCHOR STUD TO SLIP
TRACK WITH WAFER HEAD
SCREW
20 GA 3" STEEL
STRAP AT 16" O.C.
WHERE REQUIRED
1 1/2" THICK FIREPROOFING AT
ALL EXPOSED STEEL
STRUCTURE
STRUCTURAL DECK-PROVIDE
INFILL TO DECK
SLOTTED SLIP TRACK
SAFING INSULATION
ANCHOR STUD TO SLIP TRACK
WITH WAFER HEAD
SCREEN
ATTACH 8" GYPSUM BOARD WITH
SCREW ANCHOR
GYPSUM BOARD
DEFLECTION GAP
DEFLECTION GAP
DECKING CHANNEL DEPTH
1 1/2" THICK FIREPROOFING AT
ALL EXPOSED STEEL
STRUCTURE
METAL DECK
(PERPENDICULAR TO FLUTES)
METAL DECK
(PARALLEL TO FLUTES)
STEEL BEAM
"OTHER WALLS" - ADDITIONAL NOTES:
1. UPGRADE TO DETAIL "6/A1.42" WHERE WALL IS DESIGNED WITH A FIRE-RESISTANCE RATING.
2. UPGRADE TO DETAIL "5/A1.42" WHERE WALL IS DESIGNED AS A "SOUND-CONTROL" WALL.
SLOTTED TOP TRACK
STUD
PDF 0.145 INCH X 1 1/4" HILTI
X-DN1 ESR-1663 OR EQUAL
AT 16" O.C.
PDF 0.145 INCH X 1 1/4" HILTI
X-DN1 ESR-1663 OR EQUAL
AT 16" O.C.
#8 SMS MID HEIGHT OF
SLOT TYP
SPRAY-APPLIED
FIRE- RESISTIVE
MATERIAL (SFRM)
2"X20 GAUGE STRAPS AT
16" O.C.
#8 SMS MIDDLE HEIGHT OF
SLOT TYPICAL
SLOTTED TOP TRACK
STUD
18 GAUGE METAL Z-BAR AT 16" O.C.,
ATTACH TO STEEL BEAM WITH (2) MINIMUM
1/8" PDF, 1/2" MINIMUM EMBEDMENT
#8 SMS MIDDLE HEIGHT OF
SLOT TYP
/8
1" 1" 5 /8
/8
1 1/2" THICK FIREPROOFING AT
ALL EXPOSED STEEL
STRUCTURE
1 1/2" THICK FIREPROOFING AT
ALL EXPOSED STEEL
STRUCTURE
METAL ROOF OR FLOOR DECK
MINERAL WOOL OR PREMOLDED
FILLER IN FLUTES
SLOTTED TOP TRACK
TRACK SHALL ALLOW FOR 3/4" VERTICAL
DEFLECTION UP AND DOWN.
PROVIDE METAL EDGE TRIM AT FIRE
RATED PARTITIONS
ATTACH TRACK TO DECK WITH POWDER
ACTUATED FASTENERS FOR CONCRETE
DECK.
METAL DECK
(PERPENDICULAR TO FLUTES)
CUT ONE LAYER GWB TO
FOLLOW PROFILE OF
DECKING. SEAL
CONTINUOUSLY WITH
ACOUSTICAL SEALENT.
SLOTTED TOP TRACK
STUD
SAB
GWB
PDF 0.145 INCH X 1 1/4" HILTI
X-DN1 ESR-1663 OR EQUAL
AT 16" O.C.
#8 SMS MID HEIGHT OF
SLOT TYP.
FILL FLUTE VOID W/ SAB
PDF 0.145 INCH X 1 1/4" HILTI
X-DN1 ESR-1663 OR EQUAL
AT 16" O.C.
GWB SOUND AND
SMOKE CLOSURE
STRIP SECURE TO
STRUCTURE AND
SEAL WITH
ACOUSTICAL
SEALENT
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL (SFRM)
2"X20 GA STRAPS AT
16" O.C.
ACOUSTICAL SEALENT
(BOTH SIDES)
#8 SMS MID HEIGHT OF
SLOT TYP
SLOTTED TOP TRACK
STUD
SAB
GWB
18GA MET Z-BAR AT 16" O.C.,
ATTACH TO STL BEAM W/(2) MIN
1/8" PDF, 1/2" MIN EMBEDMENT
ACOUSTICAL SEALENT
(BOTH SIDES)
#8 SMS MID HEIGHT OF
SLOT TYP
METAL DECK
(PARALLEL TO FLUTES)
STEEL BEAM
/8
/8
1" 1"
/8
"SOUND-CONTROL WALLS" - ADDITIONAL NOTES:
1. UPGRADE TO DETAIL "6/A1.42" WHERE WALL IS DESIGNATED WITH A FIRE-RESISTANCE RATING.
2. FILL VOIDS WITH SOUND ATTENUATION BATTS (SAB).
3. SOUND WALLS REQUIRE THAT AT LEAST ONE LAYER OF GWB BOTH SIDES OF STUDS BE CUT TO FOLLOW UNDULATING SURFACES OF SUPERSTRUCTURES INCLUDING BUT NOT LIMITED TO FLUTES METAL DECKING. JOINT GWB TO SUPERSTRUCTURE WITH A CONTINUOUS BEAD OF ACOUSTICAL SEALANT. SEE DETAIL "6/A1.42" FOR WAHT HAPPENS AT RATED WALLS.
1 1/2" THICK
FIREPROOFING AT
ALL EXPOSED STEEL
STRUCTURE
1 1/2" THICK
FIREPROOFING AT
ALL EXPOSED STEEL
STRUCTURE
SLOTTED TOP TRACK
1 LAYERS OF GYPSUM
WALLBOARD; SEE WALL
TYPE
STUD
SAB
MINERAL WOOL
FORMING
MATERIAL
PDF 0.145 INCH X 1
1/4" HILTI X-DN1
ESR-1663 AT 16" O.C.
/8
/8
1" 1"
FIRE STOP JOINT
#8 SMS MIDDLE HEIGHT OF
SLOT TYPICAL
PDF 0.145 INCH X 1 1/4" HILTI
X-DN1 ESR-1663 AT 16" O.C.
SPRAY-APPLIED
FIRE-RESISTIVE
MATERIAL (SFRM)
/8
"2"X20 GAUGE STRAPS AT
16" O.C.
FIRE STOP JOINT
#8 SMS MIDDLE HEIGHT OF
SLOT TYPICAL
SLOTTED TOP TRACK
1 LAYERS OF GYPSUM
WALLBOARD; SEE
WALL TYPE
STUD
SAB
#8 SMS MIDDLE HEIGHT OF
SLOT TYPICAL
18 GAUGE METAL Z-BAR AT 16" O.C.,
ATTACH TO STEEL BEAM WITH (2) MINIMUM
1/8" PDF, 1/2" MINIMUM EMBEDMENT
MINERAL WOOL FORMING
MATERIAL
DESIGN BASIS:
METAL DECK
(PERPENDICULAR TO FLUTES)
DESIGN BASIS:
METAL DECK
(PARALLEL TO FLUTES)
DESIGN BASIS:
STEEL BEAM
"FIRE-RATED WALLS"- ADDITIONAL NOTES:
1. CONDITIONS INDICATED TO SHOW DESIGN INTENT. THEY ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR A UL-APPROVED TOP-OF-WALL DESIGNS THAT ARE APPROPRIATE FOR CONDITIONS.
2. REFER TO SECTION 07 84 00 FIRESTOPPING FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITION FOR FIRE-RATED WALLS.
GENERAL NOTES
1. CONDITIONS INDICATED SHOW DESIGN INTENT, ESPECIALLY IN REGARD TO ACCOMMODATION OF STRUCTURAL DEFLECTION AND CONTINUITY OF INTEGRITY OF SOUND WALLS.
2. DESIGN INTENT DETAILS ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR HEAD-OF-WALL DESIGNS AND COMPONENTS AS APPROPRIATE FOR CONDITIONS.
3. DESIGN INTENT DETAILS MAY NOT SHOW ALL CONDITIONS TO BE ENCOUNTERED ON A PROJECT. COMPLY WITH MANUFACTURER AND UL APPROVED METHODS FOR ATYPICAL CONDITIONS.
4. SECURE TOP OF INTERIOR PARTITIONS TO SUPERSTRUCTURE IN A WAY THAT PROVIDES LATERAL STABILITY (PERPENDICULAR-TO AND IN-PLANE WITH WALL) YET ALLOWING FOR A MINIMUM OF 3/4" OF
VERTICAL DEFLECTION OF THE SUPERSTRUCTURE.
5. RIGIDLY SECURE SLOTTED TOP TRACK TO BUILDING SUPERSTRUCTURE IN AN APPROVED MANNER. EMPLOY Z-BARS, COLD-ROLLED CHANNELS OR SIMILAR SPACERS TO ACCOMMODATE THICKNESS OF
SPRAY-APPLIED FIRE-RESISTIVE MATERIALS (SFRM).
6. SLOTTED TOP TRACK, INDICATED ON THESE DETAILS, IS THE BASIS FOR DESIGN AND REFERS TO DEEP-LEG TRACKS WITH VERTICALLY SLOTTED HOLES. OPTIONAL MANUFACTURERS MAY PROVIDE
SIMILAR, PROPRIETARY METHODS IN ACCORDANCE WITH THE PROVISIONS OF SPECIFICATION SECTION 09 22 16.
7. SECURE VERTICAL STUDS TO SLOTTED TOP TRACK AT MID-HEIGHT OF VERTICAL SLOTS IN TRACK. COMPONENTS INTENDED TO SLIDE VERTICALLY AS SUPERSTRUCTURE DEFLECTS.
8. DO NOT SCREW GYPSUM WALLBOARD TO TOP TRACK OR SUPERSTRUCTURE. GWB SCREWS INTO THE STUDS MUST BE AT LEAST 1" BELOW THE BOTTOM OF THE TOP TRACK
9. REFER TO PARTITION STANDARDS FOR SPECIFIC WALL TYPES.
10. AT FIRE-RATED WALLS REFER TO SPECIFICATION SECTION 07 84 00 FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITIONS.
11. MAINTAIN ACOUSTIC RATING WHERE SOUND-CONTROL WALLS ARE INDICATED.
12. FIRE STOPPING AND ACOUSTICAL SEALANTS SHALL AUTOBOND. PROVIDE EXPOSED CLEAN SEALANT (TO CONCEAL FIRESTOPPING).
13. WHERE A WALL IS DESIGNATED AS A SOUND-CONTROL WALL REFER TO FIRE-RATED HEAD-OF-WALL CONDITIONS.
14. WHERE A WALL IS DESIGNATED AS A SOUND-CONTROL WALL, FILL ALL VOIDS WITH SOUND ATTENUATION BATTS (SAB)
SLOTTED DEEP LEG
DEFLECTION TRACK
SLIP
CONNECTION
VERTICAL STUD
ISOMETRIC VIEW OF SLOTTED TOP TRACK
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:0
A
M
CONSTRUCTION DOCUMENTS
11/16/21
HEAD OF WALL DETAILS
A1.42
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
31 128
3" = 1'-0"
DEFLECTION DETAIL-PARALLEL TO DECK
3" = 1'-0"
DEFLECTION DETAIL - PERPENDICULAR TO DECK
1" = 1'-0"
HEAD-OF-WALL CONDITIONS - STUD WALLS - NON-FIRE, NON-SMOKE, NON-SOUND CONTROL
WALLS
1 1/2" = 1'-0"
PARTITION DETAIL AT DECK
1" = 1'-0"
HEAD-OF-WALL CONDITIONS - STUD WALLS - SOUND CONTROL WALL
1" = 1'-0"
HEAD-OF-WALL CONDITIONS - STUD WALLS - FIRE RATED WALLS
3/4" = 1'-0"
ISOMETRIC VIEW OF SLOTTED TOP TRACK
File details come from the government source that posted it. Updated .