ATTACHMENT 4 - Drawings - Volume 1 - 1 of 8.pdf
PDF 15 MB Posted
- Solicitation number
- 36C77622B0063
About this file
This solicitation is for the expansion of Building 1 for primary care at the Fargo VA Medical Center in North Dakota. The project involves rerouting part of the road between the medical center and the flood wall, relocating the flood wall basin and road further away from the building addition to comply with physical security requirements. Foundation work will include installing helical piers to support the addition. The two-story addition will create a whole health clinic on the first floor and mechanical space and offices for emergency medical services in the basement. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin. Responses are due based on the specified solicitation number and work is to provide an expansion to improve primary care services at the Fargo VA facility.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
COVER SHEET - VOLUME 1
G0.00
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
1 128
EXPAND BUILDING 1 FOR PRIMARY CARE
PROJECT NO. 437-315
FARGO VA HEALTH CARE SYSTEM
DEPARTMENT OF VETERAN'S AFFAIRS
2101 ELM STREET
FARGO, NORTH DAKOTA 58102
VA
U.S DEPARTMENT OF VETERAN'S AFFAIRS
VETERAN'S HEALTH ADMINISTRATION
# POUND OR NUMBER
& AND
@ AT
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
AFF ABOVE FINISH FLOOR
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALUM ALUMINUM
ANOD ANODIZED
ASD ALTERNATE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
BD BOARD
BLK BLOCK
BM BEAM
B.O. BOTTOM OF
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BSMT BASEMENT
BLDG BUILDING
BYND BEYOND
CAB CABINET
CER CERAMIC
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMPR COMPRESSIBLE
CONC CONCRETE
CONST JT CONSTRUCTION JOINT
CONT CONTINUOUS
CPT CARPET
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CT CERAMIC TILE
DBL DOUBLE
DEMO DEMOLISH OR DEMOLITION
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DIR DIRECTION
DN DOWN
DR DOOR
DWG DRAWING
EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR OR ELEVATION
EPDM ETHYLENE PROPYLENE DIENE M-CLASS (ROOFING)
EQ EQUAL
ES EACH SIDE
EXIST EXISTING
EXP Bolt EXPANSION BOLT
EXP JT EXPANSION JOINT
EXT EXTERIOR
FD FLOOR DRAIN OR FIRE DEPARTMENT
FEC FIRE EXTINGUISHER CABINET
FIN FINISH
FIXT FIXTURE
FLR FLOOR
FM FILLED METAL
FND FOUNDATION
F.O. FACE OF
FT FOOT OR FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GP GUSSET PLATE
GR GRADE
GYP GYPSUM
HC HOLLOW CORE
HDR HEADER
HEF HORIZONTAL EACH FACE
HI HIGH
HIF HORIZONTAL INSIDE FACE
HM HOLLOW METAL
HOF HORIZONTAL OUTSIDE FACE
HOR HORIZONTAL
HP HIGH POINT
HR HOUR
HS HIGH STRENGTH
HT HEIGHT
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
ICBO INTERNATIONAL CONFERENCE OF BUILDING
OFFICIALS
ID INSIDE DIAMETER
ILO IN LIEU OF
IN INCH
INCL INCLUDE
INSUL INSULATED OR INSULATION
INT INTERIOR
INV INVERT
IRGWB IMPACT RESISTANT GYPSUM WALL BOARD
JST JOIST
JT JOINT
K KIP (1000 POUNDS)
LLV LONG LEG VERTICAL
LP LOW POINT
LVL LEVEL
LW LIGHT WEIGHT
LWC LIGHT WEIGHT CONCRETE
MAS MASONRY
MAX MAXIMUM
MCB METAL CORNER BEAD
MECH MECHANICAL
MEMBR MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURED
MIN MINIMUM
MO MASONRY OPENING
MRGWB MOISTURE-RESISTANT GYPSUM WALL BOARD
MTL METAL
NF NEAR FACE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND
OPNG OPENING
OZ OUNCE
PC PILE CAP
PCC PRE-CAST CONCRETE
PL PLATE
P.LAM PLASTIC LAMINATE
PLUMB PLUMBING
PLY PLYWOOD
PORC PORCELAIN
PNL PANEL
PNT PAINT OR PAINTED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PT POINT
PR PAIR
PROP PROPERTY
PVC POLYVINYL CHLORIDE
ABBREVIATIONS
R RADIUS
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE RIGHT END
REINF REINFORCED
REF REFERENCE
REQD REQUIRED
RET RETURN
RETG RETAINING
RM ROOM
R.O. ROUGH OPENING
ROW RIGHT OF WAY
SC SOLID CORE
SDI STEEL DECK INSTITUTE
SECT SECTION
SF STEP FOOTING OR SQUARE FOOT
SHT SHEET
SIM SIMILAR
SL SPLICE LENGTH
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SPEC SPECIFIED OR SPECIFICATION
SPK SPRINKLER OR SPEAKER
SQ SQUARE
SSTL STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STIFF STIFFENER
STL STEEL
STR STAIR
STRUCT STRUCTURE OR STRUCTURAL
SUP SUPPORT
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TBD TO BE DETERMINED
T/D TELEPHONE/DATA
TEL TELEPHONE
TEMP TEMPERATURE
THK THICK OR THICKNESS
THRD THREADED
TLT TOILET
T.O. TOP OF
T.O.C TOP OF CONCRETE
T.O.F TOP OF FRAMING
T.O.S TOP OF STEEL/STUD
T.O.W TOP OF WALL
TPD TOILET PAPER DISPENSER
TYP TYPICAL
U/S UNDERSIDE
UNO UNLESS NOTED OTHERWISE
US UNDERSIDE
VB VAPOR BARRIER
VCT VINYL COMPOSITE TILE
VEF VERTICAL EACH FACE
VERT VERTICAL
VIF VERIFY IN FIELD
VOF VERTICAL OUTSIDE FACE
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W/ WITH
WD WOOD
WDW WINDOW
WP WORKING POINT
WRB WEATHER RESISTANT BARRIER
WWF WELDED WIRE FABRIC
CC CONTRACTOR PROVIDED/CONTRACTOR
INSTALLED
VC VA PROVIDED/CONTRACTOR INSTALLED
VV VA PROVIDED/VA INSTALLED
STEEL/METAL
WOOD (ROUGH) BLOCKING OR SHIM
BRICK
GRAVEL
EARTH/ENGINEERED FILL
CONCRETE MASONRY
PLAN AND SECTION
WOOD (ROUGH)
ACOUSTIC CEILING TILE
GYPSUM BOARD
CEILING
CONCRETE
ELEVATION
CENTER LINE
LINE SYMBOLS
GRID LINE
PROPERTY LINE
CUT LINE
BATT INSULATION
WOOD SUBSTRATE
RIGID INSULATION
MATERIAL LEGEND
WM - WALK OFF MAT
EF - EPOXY FLOORING (TROWELED)
FLOORING
BID ALTERNATE
CPT - CARPET
CONC - CONCRETE
PT - PORCELAIN TILE
FIBER CEMENT PANEL SIDING
CORRUGATED METAL PANEL
STANDING SEAM METAL ROOF/
SIDING PANEL
V.A. SYMBOLS
FIRE RESISTIVE RATED LINE, 1 HOUR
FIRE RESISTIVE RATED LINE, 2 HOUR
FIRE RESISTIVE RATED LINE, 3 HOUR
FIRE RESISTIVE RATED LINE, 4 HOUR
FIRE-RATED, SMOKE BARRIER LINE, 1 HOUR
FIRE-RATED, SMOKE BARRIER LINE, 2 HOUR
FIRE-RATED, SMOKE BARRIER LINE, 3 HOUR
FIRE-RATED, SMOKE BARRIER LINE, 4 HOUR
V V ITEM - VA SUPPLIED AND INSTALLED
VC ITEM - VA SUPPLIED AND CONTRACTOR INSTALLED
CC ITEM - CONTRACTOR SUPPLIED AND INSTALLED
A
COLUMN GRID
DIMENSION LINE
NORTH ARROW
CL CENTER LINE
N
Room name
1t
VIEW NAME
1/8" = 1'-0"1 DRAWING TITLE
SCALE
BUILDING SECTION
DIRECTION OF SIGHT
DRAWING NUMBER
SHEET NUMBER
WALL SECTION
DETAIL CUT
A101
DETAIL CALLOUT
A101
A101
A101
A101
DIRECTION OF SIGHT
DRAWING NUMBER
SHEET NUMBER
DRAWING NUMBER
SHEET NUMBER
DRAWING NUMBER
SHEET NUMBER
INTERIOR ELEVATION
DRAWING NUMBER
DIRECTION OF SIGHT
SHEET NUMBER
ROOM TAG
ROOM NAME
ROOM NUMBER
KEYNOTE TAG
5-04 KEYNOTE DESIGNATION
DOOR TAG
DOOR NUMBER
PARTITION TAG
WALL DESIGNATION
WINDOW TAG
WINDOW DESIGNATION
ELEVATION MARKER
HEIGHT
NORTH ARROW
TRUE NORTH
PLAN NORTH
ARCHITECTURAL SYMBOLS
M3A
1. THESE LEGENDS ARE COMPOSED OF STANDRD SYMBOLS
AND ARE PERTINENT TO THE CONDITIONS ON THIS SET OF
DRAWINGS TO THE EXTENT APPLICABLE.
2. ADDITIONAL LEGENDS AND/OR OTHER LEGENDS MAY
APPEAR IN THIS SET OF DRAWINGS TO INDICATE SPECIFIC
CONDITIONS IN LIEU OF SYMBOLS SHOWN ON THIS SHEET.
LEGEND NOTES:
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:5
A
M
CONSTRUCTION DOCUMENTS
11/16/21
LEGENDS, SYMBOLS AND
ABBREVIATIONS
G0.02
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
2 128
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1 /2
:3
:1
A
M
CONSTRUCTION DOCUMENTS
11/16/21
PROJECT DIRECTORY, DRAWING
INDEX AND GENERAL NOTES
G0.03
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
3 128
ARCHITECT
JOEL SIMONYAK, AIA, NCARB
MECHANICAL ENGINEER
MATT KOSCAK, PE
ELECTRICAL ENGINEER
RAY DAWES, PE
STRUCTURAL ENGINEER
AARON HARTWELL, PE, SE
FOURFRONT DESIGN INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PHONE (605) 342-9470
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FIRE PROTECTION ENGINEER
CHRIS LEAVER, CONSULTING MANAGER
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
PROJECT DIRECTORY:
CIVIL ENGINEER
JIM GUSKY, PE
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
GENERAL NOTES:
1. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, AND
ORDINANCES.
2. THE CONTRACTOR SHALL PERFORM ALL TESTING AND INSPECTIONS AS
SPECIFIED, OR AS NECESSARY TO DEMONSTRATE A COMPLETE AND
SATISFACTORY INSTALLATION.
3. THE CONTRACTOR SHALL PROTECT EXISTING BUILDING AND SITE
MATERIALS SCHEDULED TO REMAIN, AND SHALL BE RESPONSIBLE FOR
DAMAGE TO THE SAME RESULTING FROM WORK UNDER THIS CONTRACT.
THE CONTRACTOR SHALL RESTORE DAMAGED EXISTING BUILDING
AND SITE MATERIALS TO THEIR ORIGINAL CONDITION.
4. CONTRACTOR SHALL EXERCISE CAUTION TO AVOID ANY DAMAGE WHEN
PERFORMING EARTHWORK, PAVING, OR ANY CONSTRUCTION IN THE
VICINITY OF EXISTING UTILITIES, BUILDINGS, AND LANDSCAPING.
5. CONTRACTOR SHALL INSPECT SITE AND FIELD VERIFY ALL DIMENSIONS AND
CONDITIONS PRIOR TO COMMENCING CONSTRUCTION. CONTRACTOR
SHALL NOTIFY ARCHITECT/CONTRACTING OFFICER REPRESENTATIVE
IMMEDIATELY OF ANY DISCREPANCIES.
6. CONTRACTOR SHALL COORDINATE ALL WORK AND SHOP DRAWINGS WITH
OTHER TRADES.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL WORK.
CONTRACTOR SHALL ANTICIPATE AREAS WHERE THE INSTALLATION OF
MECHANICAL AND ELECTRICAL WORK WILL BE RESTRICTED, CONGESTED, OR
DIFFICULT TO INSTALL, AND SHALL COORDINATE INSTALLATION BETWEEN ALL
TRADES.
8. SUB-CONTRACTOR SHALL COORDINATE LOCATIONS FOR ALL MECHANICAL
AND ELECTRICAL ITEMS WITH THE GENERAL CONTRACTOR. CONTRACTOR
SHALL NOTIFY ARCHITECT/CONTRACTING OFFICER REPRESENTATIVE OF ANY
DISCREPANCIES PRIOR TO INSTALLATION AND/OR FABRICATION.
9. ALL DIMENSIONS LOCATING BUILDING AND SITE IMPROVEMENTS ARE TO FACE
OF BUILDING, BACK OF CURB, OR EDGE OF WALK, AND RUN PARALLEL OR
PERPENDICULAR TO EXISTING ROADS.
10. ALL BUILDING DIMENSIONS ARE TO FACE OF STUD, FACE OF MASONRY, AND
EXTERIOR WINDOW OR DOOR ROUGH OPENING.
11. ALL ANGLES ON PLANS ARE 45- OR 90-DEGREES, UNLESS NOTED OTHERWISE.
CURVED ELEMENTS ARE LOCATED AS DIMENSIONED.
12. ALL ELEVATIONS INDICATED ON THE DRAWINGS ARE BASED ON A FIRST
FLOOR DATUM OF +100'-0”. WHERE ITEMS ARE LABELED A.F.F. (ABOVE
FINISHED FLOOR), CONTRACTOR SHALL SET THE ITEM AS MEASURED FROM
THE LOCAL FLOOR ELEVATION. COORDINATE ANY DISCREPANCIES
REGARDING THIS SITUATION TO ASSURE THAT ALL BUILDING COMPONENTS
ARE PROPERLY SET TO FUNCTION AS INTENDED.
13. ALL ITEMS ARE NEW UNLESS SPECIFICALLY IDENTIFIED AS EXISTING.
14. LOCATIONS OF FIRE- AND SMOKE-RATED PARTITIONS WILL BE SHOWN ON ALL
FLOOR PLANS.
15. INSTALL BLOCKING WITHIN PARTITIONS AS REQUIRED FOR INSTALLATION OF
WALL-MOUNTED CABINETS, TOILET ACCESSORIES, WALL STOPS, AND
MISCELLANEOUS ITEMS.
16. LOCATE INTERIOR CONTROL JOINTS WHERE INDICATED, BUT AT A MINIMUM
TO DIVIDE ALL GYPSUM BOARD INTO SECTIONS NOT EXCEEDING 30-FEET IN
LENGTH.
17. ALL CEILING GRID SHALL BE CENTERED WITHIN THE ROOM OR CORRIDOR IN
WHICH IT OCCURS, UNLESS SHOWN OTHERWISE.
18. ALL CEILING HEIGHTS LISTED IN THE ROOM FINISH SCHEDULE ARE FROM THE
FINISH FLOOR OF THE LISTED ROOM, UNLESS NOTED OTHERWISE.
19. ALL CHANGES IN FLOOR MATERIALS OCCUR AT THE FOLLOWING LOCATIONS,
UNLESS NOTED OTHERWISE: 1) AT THE CENTER LINE OF DOORS IN THE
CLOSED POSITION, OR; 2) AT THE CENTER LINE OF OPENINGS SEPARATING
ROOMS.
20. ALL METAL STUDS EXTEND TO THE STRUCTURE ABOVE, PROVIDE DOUBLE-
HEAD TRACK TO ALLOW FOR 3/4” MINIMUM DEFLECTION OF THE STRUCTURE.
FIRE AND SMOKE BARRIERS AS WELL AS CORRIDOR WALLS SHALL HAVE ALL
PENETRATION FIRE CAULKED/FIRE PROOFED. WALLS BETWEEN ROOMS
SHALL BE SEALED WITH FIRE TAPING OF THE WALL OR STANDARD CAULKING.
21. ALL MASONRY REINFORCEMENT IS INDICATED ON THE STRUCTURAL
DRAWINGS.
22. ALL EXTERIOR CONTROL JOINTS SHALL RECEIVE BACKER ROD AND SEALANT.
23. IN SOME INSTANCES, THERMAL AND SOUND INSULATION HAS BEEN OMITTED
FROM DETAILS FOR CLARITY. SEE SPECIFICATIONS, PARTITION TYPES, AND
WALL SECTIONS FOR LOCATIONS REQUIRING INSULATION.
24. THE PLANS AND SPECIFICATIONS ARE NOT INTENDED TO DEPICT EACH AND
EVERY CONDITION OR DETAIL OF CONSTRUCTION IN REGARD TO THE AIR AND
MOISTURE RETARDER. THE CONTRACTOR HAS RESPONSIBILITY FOR
ENSURING THE AIR- AND WATER-TIGHT INTEGRITY OF THE STRUCTURE.
25. WORK AT THE DISCRETION OF THE VA MAY BE SHUTDOWN AND
RESCHEDULED DUE TO CRITICAL AREAS OR SPECIAL NEEDS OF PATIENTS
AND STAFF AT NO ADDITIONAL COST TO THE GOVERNMENT.
26. CONTRACTOR SHALL BE REQUIRED TO LOCATE ALL UTILITIES AT THE VA
WORK SITE FOR THIS PROJECT. THE VA DOES NOT LOCATE UTILITIES,
CALLING 811 GETS UTILITIES MARKED UP TO THE VA CAMPUS BUT NOT ON
THE CAMPUS.
27. CONTRACTOR TO INSTALL PROTECTION OR MITIGATION MEASURES TO
ENSURE NO ODORS OR FUMES GET INTO THE BUILDING THOUGH THE
LOUVERED AREAS IN THE EXISTING BUILDING ADJACENT TO THE
CONSTRUCTION SITE. AT A MINIMUM, THE DUCT SHOULD LIKELY BE
TEMPORARILY EXTENDED TO A LOCATION ABOVE THE CLC ROOF, EQUIPMENT
EXHAUST SYSTEM PIPED TO A REMOTE LOCATION AWAY FROM HVAC
LOUVERS, CONTRACTOR TO PROVIDE CHARCOAL FILTERS IN EXISTING AIR
HANDLING UNITS TO ADDRESS CONSTRUCTION ODORS, ETC. FARGO VA HAS
HAD THESE PROBLEMS IN THE PAST AND THESE ARE SOME OF THE
MEASURES TAKEN TO MITIGATE THE FUMES AND ISSUES.
SHEET INDEX
SB101 FOUNDATION PLAN LEVEL B1
SB501 FOUNDATION DETAILS
SB502 FOUNDATION DETAILS
SF101 FLOOR FRAMING PLAN LEVEL 01
SF102 ROOF/FUTURE FLOOR FRAMING PLAN LEVEL 02
SF103 FUTURE FLOOR FRAMING PLAN LEVEL 03
SF104 FUTURE FLOOR FRAMING PLAN LEVEL 04
SF105 FUTURE FLOOR FRAMING PLAN LEVEL 05
SF106 FUTURE FLOOR FRAMING PLAN LEVEL 06
SF401 LATERAL FRAMING ELEVATIONS
SF402 LATERAL FRAMING ELEVATIONS & DETAILS
SF403 LATERAL FRAMING DETAILS
SF404 ENLARGED STAIR FRAMING PLANS AND DETAILS
SF501 FRAMING DETAILS
SF502 FRAMING DETAILS
SF503 FRAMING DETAILS
PLUMBING
P-000 SYMBOLS, LEGENDS AND ABBREVIATIONS
P-101 B/G PLUMBING PLAN - BASEMENT LEVEL
P-102 A/G DRAIN, WASTE AND VENT PLAN - BASEMENT LEVEL
P-103 A/G WATER PLAN - BASEMENT LEVEL
P-104 PLUMBING PLAN - FIRST LEVEL
P-105 ROOF PLUMBING PLAN
P-201 DRAIN, WASTE AND VENT ISOMETRIC
P-202 DOMESTIC WATER ISOMETRIC
P-501 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
ELECTRICAL
E-000 ELECTRICAL LEGENDS AND ABBREVIATIONS
E-001 ELECTRICAL PANEL SCHEDULES - BASEMENT LEVEL
E-002 ELECTRICAL PANEL SCHEDULES - LEVEL 1
E-003 ELECTRICAL SCHEMATICS & SCHEDULES
E-004 ELECTRICAL DETAILS
E-005 SPECIAL SYSTEMS DETAILS
E-100 ELECTRICAL SITE DEMOLITION PLAN
E-101 ELECTRICAL SITE PLAN - NEW CONSTRUCTION
E-200 POWER PLANS
E-300 LIGHTING PLANS
E-400 SPECIAL SYSTEMS PLANS
MECHANICAL
M 0.00 SYMBOLS, LEGENDS AND ABBREVIATIONS
M 0.50 EXISTING MECHANICAL ROOM PLANS
M 1.00 BASEMENT HYDRONIC PIPING PLAN
M 1.01 FIRST FLOOR HYDRONIC PIPING PLAN
M 2.00 BASEMENT HVAC PLAN
M 2.01 FIRST FLOOR HAVC PLAN
M 2.10 MECHANICAL ROOF PLAN
M 3.00 MECHANICAL SECTIONS
M 3.10 HVAC ISOMETRIC VIEWS
M 3.11 HYDRONIC PIPING ISOMETRIC VIEWS
M 3.20 ENLARGED MECHANICAL ROOM PLAN AND SECTIONS
M 4.00 MECHANICAL SCHEDULES
M 4.01 MECHANICAL SCHEDULES
M 5.00 MECHANICAL DETAILS - BUILDING 1 - DRY SIDE 1
M 5.01 MECHANICAL DETAILS - BUILDING 1 - DRY SIDE 2
M 5.10 MECHANICAL DETAILS - BUILDING 1 - WET SIDE 1
M 5.11 MECHANICAL DETAILS - BUILDING 1 - WET SIDE 2
M 5.12 MECHANICAL DETAILS - BUILDING 1 - WET SIDE 3
M 6.01 PIPING AND INSTRUMENTATION DIAGRAM (PID)
M 6.02 CONTROL DIAGRAMS
M 6.03 CONTROL DIAGRAMS
FIRE PROTECTION
FA1.00 FIRE ALARM COVER SHEET
FA1.01 FIRE ALARM - BASEMENT LEVEL
FA1.02 FIRE ALARM - FIRST LEVEL
FP1.00 FIRE PROTECTION COVER SHEET
FP1.01 FIRE PROTECTION - BASEMENT LEVEL
FP1.02 FIRE PROTECTION - FIRST LEVEL
SHEET INDEX
GENERAL
G0.00 COVER SHEET - VOLUME 1
G0.02 LEGENDS, SYMBOLS AND ABBREVIATIONS
G0.03 PROJECT DIRECTORY, DRAWING INDEX AND GENERAL NOTES
G0.04 LOCATION MAP / CONTRACTOR STAGING AREA AND ACCESS
G0.05 INFECTION CONTROL RISK ASSESSMENT
G0.10 PLANS PHASING
G1.01 LIFE SAFETY PLANS
G1.02 OCCUPANCY TABLE
CIVIL
CV100 SURVEY SHEET
CD100 DEMOLITION PLAN
CS100 SITE PLAN
CU100 OVERALL UTILITY PLAN
CU101 STORM SEWER PLAN AND PROFILE
CU102 STORM SEWER PLAN AND PROFILE
CU103 SANITARY SEWER PLAN AND PROFILE
CG100 GRADING PLAN
CG101 GRADING CROSS SECTIONS
CG102 ROADWAY PLAN AND PROFILE
CE100 DRAINAGE AND EROSION CONTROL PLAN
DT100 DETAILS
DT101 DETAILS
DT102 GATE DETAILS
ARCHITECTURAL
AD1.01 DEMOLITION PLAN - FIRST LEVEL
AD1.50 DEMOLITION REFLECTED CEILING PLAN - FIRST LEVEL
AD1.51 DEMOLITION - EAST ELEVATION & DETAILS
A1.01 FLOOR PLAN - BASEMENT LEVEL
A1.02 FLOOR PLAN - FIRST LEVEL
A1.20 DIMENSION PLAN - BASEMENT LEVEL
A1.21 DIMENSION PLAN - FIRST LEVEL
A1.40 WALL TYPES
A1.41 PARTITION FRAMING DETAILS
A1.42 HEAD OF WALL DETAILS
A1.43 PLAN DETAILS
A1.44 PLAN DETAILS
A1.45 CEILING DETAILS
A1.50 REFLECTED CEILING PLAN - BASEMENT LEVEL
A1.51 REFLECTED CEILING PLAN - FIRST LEVEL
A1.60 ROOF PLAN
A1.61 ROOF DETAIL
A2.00 EXTERIOR ELEVATIONS
A3.00 BUILDING SECTIONS
A3.10 WALL SECTIONS
A3.11 WALL SECTIONS
A3.20 CURTAINWALL SECTIONS
A4.00 ENLARGED STAIR PLAN(S) AND SECTONS
A4.01 SECTION DETAILS
A5.00 ROOM FINISH SCHEDULE
A5.01 ENLARGED FLOOR PLAN AND INTERIOR ELEVATIONS -
BASEMENT
A5.02 INTERIOR ELEVATIONS - FIRST FLOOR
A5.10 FLOOR FINISH PLANS
A5.11 WALL PROTECTION AND SIGNAGE PLANS
A5.12 WALL PROTECTION DETAILS
A5.13 SIGNAGE DETAILS
A5.14 CASEWORK SECTIONS
A6.00 DOOR SCHEDULE, ELEVATION AND DETAILS
A6.01 WINDOW SCHEDULE, DETAILS AND ELEVATIONS
A6.02 CURTAINWALL ELEVATIONS AND DETAILS
STRUCTURAL
S-001 STRUCTURAL GENERAL NOTES
S-002 STRUCTURAL ABBREVIATIONS & IBC INSPECTION TABLES
S-003 IBC INSPECTION TABLES
S-004 SNOW DRIFT AND WIND UPLIFT PLANS
S-005 CONCRETE SURFACE REQUIREMENTS
S-601 STANDARD DETAILS / SCHEDULES
S-602 METAL STUD DETAILS / SCHEDULES
MC
MC
AFGE
AFGE
AFGE
AFGE
RO EOM
HCHV
C P
C P
C P
C P
C P
C P
C P
C P
V A
N V
A N
R
MC
R
R R
19th AVE. N.
21st AVE. N.
E L M
S T
R E
E T
E L M
S T
R E
E T
R E D
R
IV
E R
O F T
H E N
O R
T H
CITY
LIFT
STATION
(STORM
SEWER)
BLDG. NO.
1 MEDICAL CENTER
3 ADMINISTRATION OFFICE
8 FLAGPOLE
9 MEDICAL CENTER
10 BOILER PLANT
11 MAINTENANCE GARAGE
12 WAREHOUSE
13 LAUNDRY
30 ADMINISTRATION OFFICE
39 HIGH VOLTAGE SWITCHGEAR BLDG
42 UND SCHOOL OF MEDICINE
46 MEDICAL CENTER
MC- MOTORCYCLE PARKING
CP- CAR/VAN POOL PARKING
- HANDICAPPED PARKING
40 VBA REGIONAL OFFICE
41 OXYGEN STORAGE TANK
43 PICNIC SHELTER AND PATIO
44 XCEL ENERGY BLDG (NATURAL GAS)
20 GATE WELL
50 COLD STORAGE BUILDING
51 HRMS
52 ADMINISTRATION OFFICE
53 HAZMAT STORAGE BUILDING
54 PANDEMIC FLU STORAGE BUILDING
56 CHILLER PLANT
R- RESERVED PARKING
UND- UNIVERSITY OF NORTH DAKOTA
AFGE- AMERICAN FEDERATION GOVERNMENT EMPLOYEE
RO EOM- REGIONAL OFFICE EMPLOYEE OF THE MONTH
HCHV- HEALTH CARE HOMELESS VETERANS
NFFE- NATIONAL FEDERATION FEDERAL EMPLOYEE
39 54 12 13
30E30W
PROJECT
LOCATION
CONTRACTOR SHARED
PARKING & STAGING AREA
TEMPORARY
CONSTRUCTION
SAFETY FENCE.
DRIVE ACCESS
A
A
B
C
A D
E
F
G
H
I
MAP LEGEND
TEMPORARY
CONSTRUCTION SAFETY
FENCE.
HAUL ROUTE
NOTE: THE CONTRACTOR IS REQUIRED TO KEEP THE ROAD CLEAN AND
CLEARED OF ALL DEBRIS, DIRT, GRAVEL, SAND, MUDM ETC. THE CONTRACTOR
SHALL KEEP THE PATH CLEAN AND CLEARED AT ALL TIMES, THIS SHALL NOT
JUST BE ONCE A DAY AND DONE FOR FOR THE DAY.
MATERIAL DELIVERY ROUTE
PROJECTS EXTENTS
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:0
A
M
CONSTRUCTION DOCUMENTS
11/16/21
LOCATION MAP / CONTRACTOR
STAGING AREA AND ACCESS
G0.04
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
4 128
1/64" = 1'-0"
SITE PLAN
N
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
3. NOTE THE CONTRACTOR IS REQUIRED TO KEEP THE ROAD CLEAN AND CLEARED OF ALL
DEBRIS, DIRT, GRAVEL, SAND, MUD, ETC. THE CONTRACTOR SHALL KEEP THE PATH CLEAN
AND CLEARED AT ALL TIMES, THIS SHALL NOT JUST BE ONCE A DAY AND DONE FOR THE DAY.
4. CONTRACTOR SHALL COOPERATE WITH OTHER VA PROJECTS, SERVICE CREWS, ETC. WHO
HAVE WORK GOING ON AT THE SITE .
5. CONTRACTOR, THE NEW ROAD AND FLOOD WALL WORK SHALL BE COMPLETED FIRST AND
THE ROAD AND FLOOD WALL AREAS OPENED BACK UP FOR USE BY THE PUBLIC. OTHER
WORK AREAS MAY START AT THE SAME TIME , BUT THE ROAD AND FLOOD WALL SHALL HAVE
PEOPLE WORKING DAILY TO COMPLETE THE MODIFICATIONS AND OPEN ROADS, SIDEWALKS,
ETC. BACK UP FOR USE.
GENERAL NOTES:
A. CONTRACTOR: PLACE A SIGN AT THE STAIRWELL (INTERNAL ENTRANCES
AND AT THE DOOR EXITING) SAYING "STOP DO NOT ENTER,
CONSTRUCTION AREA, EMERGENCY EXIT ONLY".
B. THE DRIVE BETWEEN THE VA AND UND BUILDINGS SHALL REMAIN OPEN
AND ACCESSIBLE AT ALL TIMES FOR VA AND OTHER CONTRACTORS AND
SERVICE COMPANIES.
C. CONTRACTOR PLACE A SIGN AT THE CORRIDOR EXIT DOOR SAYING "STOP
DO NOT ENTER, CONSTRUCTION AREA, EMERGENCY EXIT ONLY".
D. CURRENT SOUTH ENTRANCE (#6) THE CONTRACTOR SHALL PROVIDE A
LARGE SIGN BY ROOM BD-70 TO REPLACE THE CURRENT SIGN DIRECTING
PEOPLE TO THE SOUTH PARKING LOT. THE NEW SIGN SHALL SAY "NO EXIT,
CONSTRUCTION ZONE".
E. CONSTRUCTION FENCE SHALL BE CONTINUOUS AROUND THE JOB SITE
(AND WILL HAVE TO BE READJUSTED WHEN THE DRIVE AND LOADING
DOCK ARE COMPLETE AND READY FOR THE PUBLIC TO USE WITH NO GAPS
WHERE UNAUTHORIZED VEHICLES OR PEOPLE MAY ENTER THE
CONSTRUCTION SITE. FENCING SHALL BE PROVIDED AND MAINTAINED BY
THE CONTRACTOR. CONTRACTOR SHALL PROVIDE COR WITH PROPOSED
LAYOUT PRIOR TO PERIMETER ADJUSTMENTS.
F. CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL MEASURES DURING THE
MORNING AND EVENING TIMES OF PEAK TRAFFIC. CONTRACTOR SHALL
PROVIDE A COMBINATION OF SIGNAGE AND PERSONELL AS REQURIED TO
MAINTAIN SMOOTH TRAFFIC AND MINIMIZE CONCERNS.
G. SIGNS WILL BE REQUIRED AT BOTH THE 19TH AVE. N. ENTRANCE AND THE
21ST AVE N. ENTRANCE GUIDING TRAFFIC. CONTRACTOR SHALL PROVIDE
TRAFFIC CONTROL SIGNAGE THAT ADJUSTS WITH THE CONDITIONS OF
TRAFFIC AROUND THE PROJECT. SIGNAGE SHALL FOLLOW THE
REQUIREMENTS OF THE FARGO VA HOSPITAL SIGNAGE STANDARDS.
H. KEEP THE CONSTRUCTION FENCE DOWN TO THE SOUTH AS MUCH AS
POSSIBLE SO THE SEMI'S WHO NEED TO GET TO THE EAST LOADING DOCK
OR OXYGEN TANKS ARE ABLE TO PULL PAST THE EAST LOADING DOCK
ACCESS ROAD AND BACK UP TO THE LOADING DOCK. COORDINATE
LOCATION OF FENCE WITH VA COR, SCM, POLICE SERVICE AND THE
ROADS / GROUND CREW TO ENSURE ACCESS ISSUES ARE NONEXISTENT
OR MINIMIZED TO THE EXTENT POSSIBLE.
I. CONTRACTOR TO PROVIDE MAPS, SIGNS, ETC. AT ALL DRIVEWAY
ENTRANCES AND EXITS, BUILDING ENTRANCES AND EXITS, ANYWHERE
SIGNS WILL BE NEEDED TO DIRECT PATIENTS, VISITORS AND STAFF
AROUND THE CAMPUS. DIRECT SEMI TRUCKS TO 21ST AVE N ENTRANCE.
ETC. CONTRACTOR SHALL WORK WITH COR, POLICE SERVICE AND VA
GROUNDS CREW TO DETERMINE THE TYPE OF SIGNAGE AND WHAT THE
SIGNAGE WILL SAY. IT MAY BE AS SIMPLE AS PROVIDING A STANDARD
STOP SIGN OR IT MAY HAVE TO BE A CUSTOM SIGN TELLING SEMI'S TO USE
THE 21ST AVE N ENTRANCE.
SHEET SPECIFIC NOTES:
UP
F F
S P
S P
S P
S P
SPSP SPSP
S P
S P
S P
SPSP SPSPSPSPSP
S P
S P
S P
S P
S P
S P
SP
S P
SP SPSP SP
S P
S P
S P
S P
DN
UP
1 HOUR SMOKE RATED
TEMPORARY CONSTRUCTION
PARTITION. PROVIDE AT
AREAS ONLY REQUIRED BY
IMMEDIATE WORK AND
REMOVE WHEN NOT IN USE.
EXTENT OF TEMPORARY
PARTITION WALLS SHOULD BE
MINIMIZED TO ONLY PROVIDE
THE NECESSARY
CONTAINMENT AND LIMITED
CONTRACTOR ACCESS.
CONTRACTOR SHALL VERIFY
PRIOR TO BIDDING AS TO THE
CONDITION OF ANY EXISTING
WALLS TO BE USED AS THE
BARRIER. VERIFY THAT
WALLS ARE CONSTRUCTED
TO DECK AND SEALED TIGHT
AGAINST THE PASSAGE OF
SMOKE.
TEMPORARY
CONSTRUCTION BARRIER
EBD - 70
EBD - 80
EBD - 95
BD - 133
BD - 132 BD - 131 BD - 130
BD - 110
BD - 117
BD - 130A
BD - 120
BD - 121
BD - 118
BD - 119
BD - 122
BD - 116 BD - 115
BD - 112
BD - 123
BD - 114
BD - 124
BD - 126 BD - 127
BD - 128
BD - 129
BD - 125
BD - 113
CO01
CO02
CO03
STAIRWELL #24
EBD - 70A
BD - 118A
BD - 118B
BD - 119A
BD - 119B
1D -176 1D -175 1D -174 1D -172 1D -171 1D -193
1D -1991D -198 1D -178
1D -189 1D -1901D -1871D -1861D -1851D -184
1D -181
1D -179
1D -177
1D -188A
1D -191A
1D -191
1D -196
1D -188
1D -192 1D -1951D -194
E1D -86 E1D -102
E1D -103
E1D -104
E1D -109
E1D -108
E1D -110
E1D -112
E1D -113
E1D -115 E1D -121
E1D -122
E1D -123
E1D -124 E1D -126
E1D -127
E1D-127A
E1D -131
E1D -132
E1D -133
E1D -134 E1D -135 E37
E1D - 128E1D - 129 E1D - 130
STAIRWELL #24
E1D - 117
1D -197
1D -173
1D -180
1D -182
1D -183
CO04
CO05
CO06
E1D -116 E1D -120
1D -121
EBD - 70A
1D -193
CO04
CO04
M
IN
INFECTION CONTROL RISK ASSESSMENT
STEP ONE: TYPE D
USING THE FOLLOWING TABLE, IDENTIFY THE TYPE OF CONSTRUCTION PROJECT ACTIVITY (TYPE A-D)
TYPE A
INSPECTION AND NON-INVASIVE ACTIVITIES.
INCLUDES, BUT IS NOT LIMITED TO:
• REMOVAL OF CEILING TILES FOR VISUAL INSPECTION ONLY, E.G., LIMITED TO 1 TILE PER 50
SQUARE FEET.
• PAINTING (BUT NOT SANDING).
• WALL COVERING, ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES WHICH DO
NOT GENERATE DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER
THAN FOR VISUAL INSPECTION.
TYPE B
SMALL SCALE, SHORT DURATION ACTIVITIES WHICH CREATE MINIMAL DUST
INCLUDES, BUT IS NOT LIMITED TO:
• INSTALLATION OF TELEPHONE AND COMPUTER CABLING.
• ACCESS TO CHASE SPACE.
• CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED.
TYPE C
WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION
OR REMOVAL OF ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES.
INCLUDES, BUT IS NOT LIMITED TO:
• SANDING OF WALLS FOR PAINTING OR WALL COVERING.
• REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK.
• NEW WALL CONSTRUCTION.
• MINOR DUCT WORK ABOVE CEILINGS.
• MAJOR CABLING ACTIVITIES.
• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORK SHIFT.
TYPE D
MAJOR DEMOLITION AND CONSTRUCTION PROJECTS
INCLUDES, BUT IS NOT LIMITED TO:
• ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS
• REQUIRES HEAVY DEMOLITION ON REMOVAL OF A COMPLETE CABLING SYSTEM
• NEW CONSTRUCTION
STEP TWO: HIGHEST RISK
USING THE FOLLOWING TABLE, IDENTIFY THE PATIENT RISK GROUPS THAT WILL BE AFFECTED. IF
MORE THAN ONE RISK GROUP WILL BE AFFECTED, SELECT THE HIGHER RISK GROUP
LOW RISK MEDIUM RISK HIGH RISK HIGHEST RISK
• OFFICE AREA • CARDIOLOGY
• ECHOCARDIOGRAPHY
• ENDOSCOPE
• NUCLEAR MEDICINE
• PHYSICAL THERAPY
• RADIOLOGY / MRI
• RESPIRATORY
THERAPY
• CCU
• EMERGENCY ROOM
• LABOR AND DELIVERY
• LABORATORIES (SPECIMEN)
• MEDICAL UNITS
• NEWBORN NURSERY
• OUTPATIENT SURGERY
• PEDIATRICS
• PHARMACY
• POST ANESTHESIA CARE
UNIT
• SURGICAL UNITS
• ANY AREA CARING FOR
IMMUNE COMPROMISED
PATIENTS
• BURN UNITS
• CARDIAC CATH LAB
• CENTRAL STERILE SUPPLY
• INTENSIVE CARE UNIT
• NEGATIVE PRESSURE
ISOLATION ROOMS
• ONCOLOGY
• OPERATING ROOMS
INCLUDING C SECTION
ROOMS
STEP THREE:
MATCH THE PATIENT RISK GROUP (LOW, MEDIUM, HIGH, HIGHEST) WITH THE PLANNED ...
CONSTRUCTION PROJECT TYPE (A, B, C, D) ON THE FOLLOWING MATRIX, TO FIND THE ...
CLASS OF PRECAUTIONS (I, II, III OR IV) OR LEVEL OF INFECTION CONTROL ACTIVITIES REQUIRED.
CLASS I - IV OR COLOR-CODED PRECAUTIONS ARE DELINEATED ON THE FOLLOWING PAGE.
IC MATRIX - CLASS OF PRECAUTIONS: CONSTRUCTION PROJECT BY PATIENT RISK
CONSTRUCTION PROJECT TYPE
PATIENT RISK GROUP TYPE A TYPE B TYPE C TYPE D
LOW RISK GROUP I II II III / IV
MEDIUM RISK GROUP I II III IV
HIGH RISK GROUP I II III / IV IV
HIGHEST RISK GROUP II III / IV III / IV IV
NOTE: INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND
RISK LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.
UPON COMPLETION OF PROJECTDURING CONSTRUCTION PROJECT
CLASS I
1. EXECUTE WORK BY METHODS TO MINIMIZE
RAISING DUST FROM CONSTRUCTION
OPERATIONS
2. IMMEDIATELY REPLACE A CEILING TILE
DISPLACED FOR VISUAL INSPECTION
1. CLEAN WORK AREA UPON COMPLETION
OF TASK.
CLASS II
1. PROVIDE ACTIVE MEANS TO PREVENT
AIRBORNE DUST FROM DISPERSING INTO
ATMOSPHERE
2. WATER MIST WORK SURFACE TO
CONTROL
DUST WHILE CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT
OF WORK AREA.
6. REMOVE OR ISOLATE HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED.
1. WIPE WORK SURFACES WITH CLEANER /
DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE
BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
3. WET MOP AND / OR VACUUM WITH HEPA
VACUUM BEFORE LEAVING WORK AREA.
4. UPON COMPLETION, RESTORE HVAC
SYSTEM WHERE WORK WAS PERFORMED
CLASS III
1. REMOVE OR ISOLATE HVAC SYSTEM IN
AREA WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT
SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS I.E.
SHEETROCK, PLASTIC, TO SEAL
AREA FROM NON WORK AREA OR
IMPLEMENT
CONTROL CUBE METHOD (CART WITH
PLASTIC COVERING AND SEALED
CONNECTION TO WORK SITE WITH HEPA
VACUUM FOR VACUUMING PRIOR TO EXIT)
BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE
WITHIN
WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS.
4. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
5. COVER TRANSPORT RECEPTACLES OR
CARTS. TAPE COVERING UNLESS SOLID LID.
1. DO NOT REMOVE BARRIERS FROM WORK
AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE OWNER'S SAFETY
DEPARTMENT AND INFECTION PREVENTION
AND CONTROL DEPARTMENT AND
THOROUGHLY CLEANED BY THE OWNER'S
ENVIRONMENTAL SERVICES DEPARTMENT.
2. REMOVE BARRIER MATERIALS CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION.
3. VACUUM WORK AREA WITH HEPA
FILTERED
VACUUMS.
4. WET MOP AREA WITH CLEANER /
DISINFECTANT.
5. UPON COMPLETION, RESTORE HVAC
SYSTEM WHERE WORK WAS PERFORMED
CLASS IV
1. ISOLATE HVAC SYSTEM IN AREA WHERE
WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS I.E.
SHEETROCK, PLASTIC, TO SEAL AREA FROM
NON WORK AREA OR IMPLEMENT CONTROL
CUBE METHOD (CART WITH PLASTIC
COVERING AND SEALED CONNECTION TO
WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE
WITHIN WORK SITE UTILIZING HEPA
EQUIPPED AIR FILTRATION UNITS.
4. SEAL HOLES, PIPES, CONDUITS, AND
PUNCTURES.
5. CONSTRUCT ANTEROOM AND REQUIRE
ALL PERSONNEL TO PASS THROUGH THIS
ROOM SO THEY CAN BE VACUUMED USING A
HEPA VACUUM CLEANER BEFORE LEAVING
WORK SITE OR THEY CAN WEAR CLOTH OR
PAPER COVERALLS THAT ARE REMOVED
EACH TIME THEY LEAVE THE WORK SITE.
(VA DOES NOT PROVIDE ANY ITEMS
MENTIONED ABOVE).
6. ALL PERSONNEL ENTERING THE WORK
SITE ARE REQUIRED TO WEAR SHOE
COVERS. SHOE COVERS MUST BE CHANGED
EACH TIME THE WORKER EXITS THE WORK
AREA. (VA DOES NOT PROVIDE ANY ITEMS
MENTIONED ABOVE).
1. DO NOT REMOVE BARRIERS FROM WORK
AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE OWNER'S SAFETY
DEPARTMENT AND INFECTION PREVENTION
AND CONTROL DEPARTMENT AND
THOROUGHLY CLEANED BY THE OWNER'S
ENVIRONMENTAL SERVICES DEPT.
2. REMOVE BARRIER MATERIAL CAREFULLY
TO MINIMIZE SPREADING OF DIRT AND
DEBRIS ASSOCIATED WITH CONSTRUCTION.
3. CONTAIN CONSTRUCTION WASTE
BEFORE TRANSPORT IN COVERED
CONTAINERS.
4. COVER TRANSPORT RECEPTACLES OR
CARTS. TAPE COVERING UNLESS SOLID LID.
5. VACUUM WORK AREA WITH I-IEPA
FILTERED VACUUMS.
6. WET MOP AREA WITH CLEANER /
DISINFECTANT.
7. UPON COMPLETION, RESTORE HVAC
SYSTEM WHERE WORK WAS PERFORMED
STEP THREE: CLASS IV
DESCRIPTION OF REQUIRED INFECTION CONTROL PRECAUTIONS BY CLASS
SUPPLY DUCTS.
COVER TO KEEP DUST
OUT
COVER ALL RETURNS AT
THE GRATE/DIFFUSERS
FIRE EXTINGUISHER ON
PORTABLE FLOOR
BRACKET (ILSM MAY
REQUIRE MORE THAN
ONE).
TEMPORARY SWING
DOOR, OR SUSPENDED
PLASTIC ZIPPER WALL
CURTAIN BARRIER WITH
PRIOR VA APPROVAL
FIRE PULL
STATION WITH
AUDIO / VISUAL
PROVIDE STICKY MATS
(CHANGED AS NECESSARY
TO MAINTAIN CLEANLINESS).
POST ICRA, ILSM, FIRE
INSPECTION SHEETS
VISIBLE TO PUBLIC
F L E
X D
U C
T
2' - 11"
TEMPORARY MECHANICAL UNIT
TO PROVIDE NEGATIVE AIR SPACE
ILSM TEMPORARY BARRIER TAG
PROJECT:
PRIME CONTRACTOR:
SUB CONTRACTOR:
EMERGENCY CONTACT NO.:
BARRIER INSTALLATION DATE:
BARRIER EXPIRATION DATE:
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:3
A
M
CONSTRUCTION DOCUMENTS
11/16/21
INFECTION CONTROL RISK
ASSESSMENT
G0.05
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
5 128
INFECTION CONTROL NOTES - CLASS IV CONSTRUCITON:
A. THE ONE-HOUR FIRE-RATED CONSTRUCTION BARRIERS SHALL BE CONSTRUCTED PRIOR TO BEGINNING OTHER WORK.
B. FIRE PROTECTION SYSTEMS SHALL REMAIN FUNCTIONAL FOR OCCUPIED AREAS OF THE FLOOR.
C. PROVIDE FIRE EXTINGUISHERS IN CONSTRUCTION AREA; REVIEW WITH COR AND VA SAFETY GROUP.
D. CONTRACTOR SHALL PROVIDE FIRE WATCH FOR ALL HOT WORK ACTIVITIES AND WHEN FIRE ALARM OR SPRINKLER SYSTEMS
ARE OFFLINE MORE THAN 4 HOURS IN A 24 HOUR PERIOD.
E. MAINTAIN NEGATIVE AIR PRESSURE IN CONSTRUCTION AREA AT ALL TIMES (24/7), WHETHER OCCUPIED OR NOT, THROUGHOUT DURATION OF PROJECT USING HEPA EQUIPPED AIR FILTRATION UNITS.
F. MAINTAIN EXIT LIGHTS IN CONSTRUCTION AREA.
G. CONSTRUCTION AREA SHALL REMAIN ISOLATED FROM THE OTHER AREAS OF THE MEDICAL CENTER; NO HVAC RETURN OR
EXHAUST SHALL PASS INTO THE AREAS OUTSIDE THE CONSTRUCTION AREA.
H. REDIRECT ALL MEDICAL CENTER PERSONNEL, PATIENTS, AND VISITORS SO THEY DO NOT EXIT THROUGH THE
CONSTRUCTION AREA. PROVIDE SIGNS ON DOORS INTO THE CONSTRUCTION AREA THAT READ: "CONSTRUCTION AREA -DO
NOT ENTER".
I. GENERAL CONTRACTOR SHALL MAINTAIN DAILY LOGS AND KEEP A CURRENT HOT WORK PERMIT ON SITE.
J. TACKY MATS SHALL BE PLACED AT ALL DOORS INTO THE CONSTRUCTION AREA AND SHALL BE MONITORED TO MAKE SURE
THEY REMAIN EFFECTIVE.
K. MAINTAIN A CLEAN AND ORDERLY CONSTRUCTION AREA TO PREVENT CONTAMINATION OF EXISTING DUCT SYSTEMS.
L. OBTAIN INFECTION CONTROL PERMIT FROM VA PRIOR TO BEGINNING WORK.
M. ISOLATE HVAC SYSTEM WITHIN CONSTRUCTION AREA TO PREVENT CONTAMINATION OF EXISTING DUCT SYSTEM.
N. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK, PLASTIC, TO SEAL AREA FROM NON WORK AREA OR IMPLEMENT
CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM
FOR VACUUMING PRIOR TO EXIT BEFORE CONSTRUCTION BEGINS.
O. AFTER COMPLETION OF WORK AND BETWEEN PHASES; VACUUM CONSTRUCTION AREA WITH HEPA FILTERED VACUUMS, WET MOP WITH DISINFECTANT, REMOVE CONSTRUCTION BARRIERS (UPON APPROVAL), PATCH OR REPAIR ANY DAMAGE FROM CONSTRUCTION BARRIER REMOVAL, AND REMOVE ISOLATION OF HVAC SYSTEM. UPON COMPLETION, RESTORE HVAC
SYSTEM WHERE WORK WAS PERFORMED.
P. SEAL ALL HOLES, PUNCTURES, AND PENETRATIONS FROM PIPES AND/OR CONDUITS APPROPRIATELY AND IMMEDIATELY TO
MAINTAIN FIRE RATING DUST PROTECTION AND NEGATIVE AIR PRESSURE.
Q. CONSTRUCT ANTEROOM AT ENTRANCES TO CONSTRUCTION AREAS AND REQUIRE ALL CONSTRUCTION PERSONNEL TO PASS THROUGH THIS ROOM TO BE VACUUMED WITH A HEPA VACUUM CLEANER PRIOR TO LEAVING THE SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE WORK SITE (VA DOES NOT PROVIDE).
Q.A. CONSTRUCTION WORKERS WILL NOT BE ENTERING ANY OCCUPIED VA SPACES.
Q.B. DIRECT ACCESS TO OUT THROUGH ANTEROOM (EXIT/ENTRANCE)
R. ALL PERSONNEL ENTERING WORK SITE (ONLY IF ENTERING VA SPACE) ARE REQUIRED TO WEAR SHOE COVERING. (VA DOES
NOT PROVIDE.)
S. CONSTRUCTION BARRIERS SHALL NOT BE REMOVED UNTIL PROJECT IS COMPLETED AND INSPECTION BY VA SAFETY
PERSONNEL, INFECTION CONTROL GROUP, AND COR.
T. REMOVE BARRIERS MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION.
CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS. COVER TRANSPORT
RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
U. FACE MASKS REQUIRED DUE TO COVID POLICY AT FARGO VA.
GENERAL NOTES:
1/16" = 1'-0"
INFECTION CONTROL - BASEMENT LEVEL
1/16" = 1'-0"
NEW FLOOR PLAN - FIRST LEVEL
1/4" = 1'-0"
INFECTION CONTROL RISK ASSESSMENT
1/2" = 1'-0"
TYPICAL CONSTRUCTION PLAN LAYOUT
ROOM SCHEDULE - BASEMENT LEVEL
Number Name
BD - 110 STANDALONE PRIMARY
BD - 112 EMS WORKROOM
BD - 113 OFFICE PROGRAM SUPPORT ASST
BD - 114 OFFICE
BD - 115 CART STORAGE
BD - 116 EQUIPMENT STORAGE
BD - 117 MECHANICAL
BD - 118 MEN'S LOCKER ROOM
BD - 118A MEN'S SHOWER
BD - 118B MEN'S TOILET
BD - 119 WOMEN'S LOCKER ROOM
BD - 119A WOMEN'S SHOWER
BD - 119B WOMEN'S TOILET
BD - 120 GEMS STORAGE
BD - 121 HOUSEKEEPING EXPENDABLES
BD - 122 LEADS WORKROOM
BD - 123 STAFF LOUNGE
BD - 124 OFFICE SUPERVISORS
BD - 125 OFFICE GEMS COORDINATOR
BD - 126 SECRETARY OFFICE
BD - 127 OFFICE EMS CHIEF
BD - 128 OFFICE EMS ASST CHIEF
BD - 129 OFFICE ADMIN OFFICER
BD - 130 CONFERENCE ROOM
BD - 130A ELECTRICAL
BD - 131 OFFICE
BD - 132 TOILET
BD - 133 WET ROOM
CO01 CORRIDOR
CO02 CORRIDOR
CO03 CORRIDOR
EBD - 70 MECHANICAL ROOM
EBD - 80 STORAGE
STAIRWELL #24 STAIRWELL #24
ROOM SCHEDULE - FIRST LEVEL
Number Name
1D -121 CORRIDOR
1D -171 EXAM
1D -172 EXAM
1D -173 WORK ROOM
1D -174 EXAM
1D -175 EXAM
1D -176 BARIATRIC EXAM
1D -177 EXAM
1D -178 HAC
1D -179 EXAM
1D -180 CLEAN LINEN
1D -181 EXAM
1D -182 TOILET
1D -183 SOILED LINEN
1D -184 EXAM
1D -185 EXAM
1D -186 EXAM
1D -187 EXAM
1D -188 BREAK ROOM
1D -188A STAFF TLT
1D -189 EXAM
1D -190 EXAM
1D -191 WELLNESS
1D -191A EQUIP STG
1D -192 PHARMACY OFFICE
1D -193 RECEPTION/WAITING
1D -194 LOGISTICS STG
1D -195 ELECT
1D -196 OFFICE
1D -197 OFFICE
1D -198 OFFICE
1D -199 OFFICE
CO04 CORRIDOR
CO05 CORRIDOR
CO06 CORRIDOR
E1D -108 OFFICE (M.H.)
E1D -110 CONSULT (M.H.)
E1D -112 OFFICE (M.H.)
E1D -116 CONSULT PHARM
E1D -120 WORK ROOM (P.C. DOC'S)
E1D -122 OFFICE (PHARM)
E1D -124 WORK ROOM (P.C. DOC'S)
E1D -126 CONSULT (S.W.)
E1D - 128 LOCKER
E1D - 129 CONF
E1D - 130 STAFF BREAK ROOM
E1D-127A TOILET
EBD - 70A STAIRWELL
STAIRWELL #24 STAIRWELL #24
12" = 1'-0"
ILSM TEMPORARY BARRIER TAG
NOTE: GENERAL CONTRACTOR SHALL COORDINATE WITH FARGO VA COR
TO OBTAIN AN ICRA/PCRA FROM FILLED OUT BY LOCAL FARGO VA STAFF
WITH REQUIREMENT BASED UPON AREA OF WORK AND ADJACENCIES.
1. SHEET SIZE FOR PROPER SCALE IS 30X42.
2. SEE SHEET G0.03 FOR GENERAL NOTES
BASEMENT AREA LEGEND:
PHASE 1
PHASE 2
LEVEL 1 AREA LEGEND:
PHASE 1
PHASE 2
1D -176 1D -175 1D -174 1D -172 1D -171 1D -193
1D -1991D -198 1D -178
1D -189 1D -1901D -1871D -1861D -1851D -184
1D -181
1D -179
1D -177 1D -188A
1D -191A
1D -191
1D -196
1D -188
1D -192 1D -194 1D -197
1D -180
1D -182
1D -183
1D -173
SOILED
E1D -86
SOILED
E1D -103
EXAM
E1D -104
TLT
E1D -109
OFFICE (M.H.)
E1D -108
OFFICE (M.H.)
E1D -112
LINEN
E1D -113
TLT
E1D -115
COPY AREA
E1D -121
TLT
E1D -123
WORK ROOM
(P.C. DOC'S)
E1D -124
TOILET
E1D -127
TOILET
E1D-127A
HAC
E1D -131
SOCIAL
WORKERS
E1D -133
MEDS
E1D -134
OPER 8
E1D -135
LOCKER
E1D - 128
CONF
E1D - 129
STAFF BREAK
ROOM
E1D - 130
STAIRWELL
#24
TLT
E1D - 117
CONSULT (S.W.)
E1D -126
1D -195 CO06
E1D -120E1D -116
1D -121
CO04
CO05
OFFICE (PHARM)
E1D -122
CONSULT (M.H.)
E1D -110
CO04
C O
M
IN
BD - 133
BD - 132 BD - 131
BD - 130
BD - 110
BD - 117
BD - 130A
BD - 120 BD - 121
BD - 118
BD - 119
BD - 122
BD - 116
BD - 115
BD - 112
BD - 123
BD - 114
BD - 124
BD - 126
BD - 127 BD - 128 BD - 129
BD - 125
BD - 113
MECHANICAL
ROOM
EBD - 70
STORAGE
EBD - 80
BREAK ROOM
EBD - 95
9427 SF
BASEMENT LEVEL
STAIRWELL
#24
BD - 118ABD - 119A
BD - 118BBD - 119B
CO01
CO02
CO03
STAIRWELL
EBD - 70A
AREA OF WORK NOT IN THE SCOPE.
EXISTING TO REMAIN.
NEW PLAN AREA LEGEND:
1 HOUR SMOKE RATED
TEMPORARY CONSTRUCTION
PARTITION. PROVIDE AT
AREAS ONLY REQUIRED BY
IMMEDIATE WORK AND
REMOVE WHEN NOT IN USE.
EXTENT OF TEMPORARY
PARTITION WALLS SHOULD BE
MINIMIZED TO ONLY PROVIDE
THE NECESSARY
CONTAINMENT AND LIMITED
CONTRACTOR ACCESS.
CONTRACTOR SHALL VERIFY
PRIOR TO BIDDING AS TO THE
CONDITION OF ANY EXISTING
WALLS TO BE USED AS THE
BARRIER. VERIFY THAT
WALLS ARE CONSTRUCTED
TO DECK AND SEALED TIGHT
AGAINST THE PASSAGE OF
SMOKE.
TEMPORARY
CONSTRUCTION BARRIER
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:4
:0
A
M
CONSTRUCTION DOCUMENTS
11/16/21
PLANS PHASING
G0.10
EXPAND BLDG. 1 FOR
PRIMARY CARE
JGCJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
6 128
NET ROOM AREA SCHEDULE
No. Name Area
BD - 110 STANDALONE PRIMARY 527 SF
BD - 112 EMS WORKROOM 357 SF
BD - 113 OFFICE PROGRAM SUPPORT ASST 94 SF
BD - 114 OFFICE 95 SF
BD - 115 CART STORAGE 764 SF
BD - 116 EQUIPMENT STORAGE 719 SF
BD - 117 MECHANICAL 804 SF
BD - 118 MEN'S LOCKER ROOM 258 SF
BD - 118A MEN'S SHOWER 47 SF
BD - 118B MEN'S TOILET 45 SF
BD - 119 WOMEN'S LOCKER ROOM 224 SF
BD - 119A WOMEN'S SHOWER 47 SF
BD - 119B WOMEN'S TOILET 45 SF
BD - 120 GEMS STORAGE 284 SF
BD - 121 HOUSEKEEPING EXPENDABLES 288 SF
BD - 122 LEADS WORKROOM 222 SF
BD - 123 STAFF LOUNGE 288 SF
BD - 124 OFFICE SUPERVISORS 205 SF
BD - 125 OFFICE GEMS COORDINATOR 119 SF
BD - 126 SECRETARY OFFICE 220 SF
BD - 127 OFFICE EMS CHIEF 150 SF
BD - 128 OFFICE EMS ASST CHIEF 117 SF
BD - 129 OFFICE ADMIN OFFICER 126 SF
BD - 130 CONFERENCE ROOM 303 SF
BD - 130A ELECTRICAL 78 SF
BD - 131 OFFICE 114 SF
BD - 132 TOILET 75 SF
BD - 133 WET ROOM 313 SF
CO01 CORRIDOR 625 SF
CO02 CORRIDOR 434 SF
CO03 CORRIDOR 285 SF
EBD - 70 MECHANICAL ROOM 3209 SF
EBD - 80 STORAGE 1892 SF
STAIRWELL #24 STAIRWELL #24 149 SF
1D -121 CORRIDOR 203 SF
1D -171 EXAM 162 SF
1D -172 EXAM 162 SF
1D -173 WORK ROOM 541 SF
1D -174 EXAM 162 SF
1D -175 EXAM 162 SF
1D -176 BARIATRIC EXAM 161 SF
1D -177 EXAM 135 SF
1D -178 HAC 60 SF
1D -179 EXAM 140 SF
1D -180 CLEAN LINEN 77 SF
1D -181 EXAM 138 SF
1D -182 TOILET 66 SF
1D -183 SOILED LINEN 67 SF
1D -184 EXAM 147 SF
1D -185 EXAM 150 SF
1D -186 EXAM 151 SF
1D -187 EXAM 150 SF
1D -188 BREAK ROOM 188 SF
1D -188A STAFF TLT 60 SF
1D -189 EXAM 151 SF
1D -190 EXAM 151 SF
1D -191 WELLNESS 633 SF
1D -191A EQUIP STG 234 SF
1D -192 PHARMACY OFFICE 114 SF
1D -193 RECEPTION/WAITING 338 SF
1D -194 LOGISTICS STG 150 SF
1D -195 ELECT 74 SF
1D -196 OFFICE 106 SF
1D -197 OFFICE 107 SF
1D -198 OFFICE 104 SF
1D -199 OFFICE 108 SF
CO04 CORRIDOR 927 SF
CO05 CORRIDOR 576 SF
CO06 CORRIDOR 377 SF
E1D -108 OFFICE (M.H.) 113 SF
E1D -110 CONSULT (M.H.) 118 SF
E1D -112 OFFICE (M.H.) 119 SF
E1D -116 CONSULT PHARM 167 SF
E1D -120 WORK ROOM (P.C. DOC'S) 207 SF
E1D -122 OFFICE (PHARM) 118 SF
E1D -124 WORK ROOM (P.C. DOC'S) 242 SF
E1D -126 CONSULT (S.W.) 119 SF
E1D - 128 LOCKER 226 SF
E1D - 129 CONF 180 SF
E1D - 130 STAFF BREAK ROOM 336 SF
E1D-127A TOILET 54 SF
EBD - 70A STAIRWELL 140 SF
STAIRWELL #24 STAIRWELL #24 149 SF
NET ROOM TOTAL: 83 23040 SF
NORTH
N
NORTH
N
TOTAL BUILDING GROSS AREA
Name Area
BASEMENT LEVEL 9427 SF
FIRST LEVEL 9119 SF
Total 18546 SF
3/32" = 1'-0"
NEW AREA FLOOR PLAN - FIRST LEVEL
3/32" = 1'-0"
NEW AREA FLOOR PLAN - BASEMENT LEVEL
SEQUENCE OF WORK:
PRECONSTRUCTION ACTIVITIES
• ESTABLISH CONTRACTOR STAGING AREA IN
COORDINATION WITH THE COR ON STATION.
• PROVIDE AND INSTALL TEMPORARY CONSTRUCTION
FENCING TO SECURE AND PROTECT THE PROJECT SITE.
• SUBMIT PROJECT SCHEDULE TO COR. IDENTIFY ALL
TRADES THAT WILL BE NECESSARY TO COMPLETE
DEMOLITION EFFICIENTLY AND CONCURENTLY.
• OBTAIN A PRE-CONSTRUCTION RISK ASSESSMENT AS
PER VA REQUIREMENTS.
• PROTECT ALL ITEMS AND EQUIPMENT NOTED TO REMAIN
AS NECESSARY. THE GENERAL CONTRACTOR SHALL BE
RESPONISBLE TO MAINTAIN THE EXISTING CONDITION
AND REPAIR ANY DAMAGE TO PRE-CONSTRUCTION
CONDITION PRIOR TO PROJECT COMPLETION.
• ESTABLISH ALTERNATE EXITING ROUTES FOR EXISITNG
DOOR THAT WILL BE BLOCKED BY CONSTRUCTION
BEGINNING IN PHASE 1.
PHASE 1
• PERFORM SITE DEMOLITION WORK IDENTIFIED IN CIVIL
DRAWINGS
• ROAD AND FLOOD WALL WORK SHALL BE COMPLETED
FIRST. RETURN THE ROAD FOR PUBLIC USE AS SOON
AS POSSIBLE. UNDERGROUND UTILITY WORK NEEDS TO
BE PLANNED FOR AND EXECUTED FIRST. FLOOD WALL
WORK NEEDS TO BE COMPLETE FOR SPRING FLOODING
EVENT(S) AND IF WORK NOT DONE, CONTRACTOR WILL
BE REQUIRED TO PROVIDE TEMPORARY FLOOD
PROTECTION MEASURES.
• TURN OVER ITEMS NOTED TO BE SALVAGED TO THE
OWNER TO A LOCATION DESIGNATED BY THE COR (ON-
SITE). IT WILL BE THE RESPONSIBILTY OF THE GENERAL
CONTRACTOR TO RELOCATE SALVAGED ITEMS AND TO
PREVENT DAMAGE TO THEIR PRE-CONSTRUCTION
CONDITION.
• REMOVE ALL SERVICE/UTILITY SYSTEMS NOTED FOR
DEMOLITION.
• PROVIDE FILL MATERIALS NECESSARY TO BEGIN
FOUNDATION SYSTEM.
• CONSTRUCT NEW BUILDING STRUCTURE..
• CONSTRUCT NEW PARTITION WALLS INCLUDING ROUGH-
IN FOR MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION.
• INSTALL ALL MECHANICAL, ELECTRICAL, PLUMBING AND
FIRE PROTECTION SYSTSEMS.
• INSTALL ALL CASEWORK, EQUIPMENT DOORS AND
HARDWARE IDENTIFIED IN THE CONSTRUCTION
DOCUMENTS.
• COORDINATE THE INSTALLATION OF OWNER PROVIDED
CONTRACTOR INSTALLED AND OWNER PROVIDED,
OWNER INSTALLED EQUIPMENT WITH THE OWNER AND
THEIR VENDORS.
PHASE 2
• INSTALL TEMPORARY ONE-HOUR FIRE RATED
CONSTRUCTION BARRIERS WHERE SHOWN TO
SEPARATE AREAS OF CONSTRUCTION ACTIVITY
FROM ADJACENT AREAS OF THE HOSPITAL THAT WILL
REMAIN OCCUPIED AND OPERATIONAL
• INSTALL HEPA FILTERS AND SEAL PROJECT BOUNDARY
TO ENSURE NEGATIVE AIR PRESSURE AS PER INFECTION
CONTROL REQUIREMENTS.
• PERFORM DEMOLITION WORK IDENTIFIED IN PHASE 2
BOUNDARIES ON BOTH FIRST FLOOR AND BASEMENT
FLOOR.
• TURN OVER ITEMS NOTED TO BE SALVAGED TO THE
OWNER TO A LOCATION DESIGNATED BY THE COR (ON-
SITE). IT WILL BE THE RESPONSIBILTY OF THE GENERAL
CONTRACTOR TO RELOCATE SALVAGED ITEMS AND TO
PREVENT DAMAGE TO THEIR PRE-CONSTRUCTION
CONDITION.
• REMOVE ALL MECAHNICAL AND ELECTRICAL SYSTEMS
NOTED FOR DEMOLITION.
• CLEAN AND REPAIR EXISITNG CONCRETE SLAB FOR
INTSTALLATION OF FINISH FLOORING MATERIAL.
• CONSTRUCT NEW PARTITION WALLS INCLUDING ROUGH-
IN FOR MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION.
• INSTALL ALL MECHANICAL, ELECTRICAL, PLUMBING AND
FIRE PROTECTION SYSTSEMS.
• COMPLETE FINISHES AND REMOVE TEMPORARY
PARTITIONS. REPAIR EXISTING AS NECESSARY.
NOTE:
EGRESS STAIR TO REMAIN OPEN AND SAFE
FOR USE THROUGHOUT DURATION OF
PROJECT, CONTRACTOR TO PROVIDE
TEMPORARY BARRIERS AS NECESSARY TO
ENSURE SAFE EGRESS OUT OF STAIR IN
CASE OF AN EVENT WITHIN EXISTING
HOSPITAL.
F F
S P
S P
S P
S P
SPSP SPSP
S P
S P
S P
SPSP SPSPSPSPSP
S P
S P
S P
S P
S P
S P
SP
S P
SP SPSP SP
S P
S P
S P
S P
DN
UP
S P
S P
S P
SP SP
S P
S P
S P
SPSP
S P
S P
S P
SP SPSP SP
SP SP
SPSP
S P
S P
S P
S P
SP SP
SP SP
SP SP
MECHANICAL
ROOM
EBD - 70
STORAGE
EBD - 80
BREAK ROOM
EBD - 95
WET ROOM
BD - 133
TOILET
BD - 132
OFFICE
BD - 131
CONFERENCE
ROOM
BD - 130
STANDALONE
PRIMARY
BD - 110
MECHANICAL
BD - 117
ELECTRICAL
BD - 130A
GEMS STORAGE
BD - 120
HOUSEKEEPING
EXPENDABLES
BD - 121
MEN'S LOCKER
ROOM
BD - 118
WOMEN'S
LOCKER ROOM
BD - 119
LEADS
WORKROOM
BD - 122
EQUIPMENT
STORAGE
BD - 116
CART STORAGE
BD - 115
EMS WORKROOM
BD - 112
STAFF LOUNGE
BD - 123
OFFICE
BD - 114
OFFICE
SUPERVISORS
BD - 124
SECRETARY
OFFICE
BD - 126
OFFICE EMS
CHIEF
BD - 127 OFFICE EMS
ASST CHIEF
BD - 128
OFFICE ADMIN
OFFICER
BD - 129
OFFICE GEMS
COORDINATOR
BD - 125
OFFICE
PROGRAM
SUPPORT ASST
BD - 113
STAIRWELL
#24
TD 2
TD 3
CP 2
FEC
FEC
F E
C
FE
EXIT 26
EXIT 25
EXIT 24
STAIRWELL
EBD - 70A
MEN'S TOILET
BD - 118B
WOMEN'S TOILET
BD - 119B
WOMEN'S
SHOWER
BD - 119A
MEN'S SHOWER
BD - 118A
CORRIDOR
CO01
BARIATRIC EXAM
1D -176
EXAM
1D -175
EXAM
1D -174
EXAM
1D -172
EXAM
1D -171
RECEPTION/WAITING
1D -193
OFFICE
1D -199
OFFICE
1D -198
HAC
1D -178
EXAM
1D -189
EXAM
1D -190
EXAM
1D -187
EXAM
1D -186
EXAM
1D -185
EXAM
1D -184
EXAM
1D -181
EXAM
1D -179
EXAM
1D -177 STAFF TLT
1D -188A
WELLNESS
1D -191
OFFICE
1D -196
BREAK ROOM
1D -188
PHARMACY
OFFICE
1D -192
ELECT
1D -195
LOGISTICS STG
1D -194
EXAM
E1D -104
OFFICE (M.H.)
E1D -108
CONSULT (M.H.)
E1D -110
OFFICE (M.H.)
E1D -112
OFFICE (PHARM)
E1D -122
WORK ROOM
(P.C. DOC'S)
E1D -124
CONSULT (S.W.)
E1D -126
TOILET
E1D -127
TOILET
E1D-127A
SOCIAL
WORKER'S
CONSULT
E1D -132
SOCIAL
WORKERS
E1D -133
LOCKER
E1D - 128
CONF
E1D - 129
STAFF BREAK
ROOM
E1D - 130
STAIRWELL
#24
OFFICE
1D -197
EQUIP STG
1D -191A
CLEAN LINEN
1D -180
TOILET
1D -182
SOILED LINEN
1D…