This attachment is a drawing file related to a federal solicitation for the expansion of Building 1 for primary care at the Fargo VA Medical Center. The project involves rerouting part of the road between the medical center and the flood wall, relocating the flood wall basin and road further away from the building addition to comply with physical security requirements. Foundation work will include installing helical piers to support the addition, which will provide a two-story structure with a whole health clinic and supporting rooms on the first floor and mechanical space and offices for emergency medical services in the basement. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the expansion and relocation work.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING INC.
3202 W MAIN ST C,
RAPID CITY, SOUTH DAKOTA 57702
PHONE (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of Veterans Affairsof
/1 /2
:2
:2
A M
CONSTRUCTION DOCUMENTS
11/16/21
COVER SHEET - VOLUME 2
G2.00
EXPAND BLDG. 1 FOR
PRIMARY CARE
AuthorJS
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
57 128
EXPAND BUILDING 1 FOR PRIMARY CARE
PROJECT NO. 437-315
FARGO VA HEALTH CARE SYSTEM
DEPARTMENT OF VETERAN'S AFFAIRS
2101 ELM STREET
FARGO, NORTH DAKOTA 58102
VA
U.S DEPARTMENT OF VETERAN'S AFFAIRS
VETERAN'S HEALTH ADMINISTRATION
1/2" 1"0" 2"SCALE: FULL
MATCH LINE
SEE XN/XXNNN
XC1 R1
XX" Ø X
XX'-X" XX'-X"
X
XN
XXNNN
XN
XXNNN
XN
XXNNN
F1
A
HSS _x_x_
B1
20GA TYPE 'W3' MTL DECK
PC S
PAN
Hx R15:12
B
B
GENERAL STRUCTURAL NOTES INDEX TO STRUCTURAL SHEETSSYMBOLS LEGEND
COORDINATE SYSTEM
S J
W--x--
(XXX'-XX")
ELEVATION
INDICATOR
CUT SECTION
INDICATOR
WALL
REINFORCING
INDICATOR
PC SPAN
IDENTIFIER
STEP TOP OF
WALL INDICATOR
PIER TAG CALLOUT INDICATOR
ROOF SLOPE
INDICATOR
STEP TOP OF
FOOTING
IDENTIFIER
MASONRY PIER
INDICATOR
CORNER REINF
INDICATOR
CONTINUOUS
BEAM
INDICATOR
MATCH LINE INDICATOR
PLAN NORTH ORIENTED 90°
TO THE SHEET W/ MAGNETIC
NORTH (OPTIONAL)
SHEET TYPE DESIGNATORS
SHEET IDENTIFICATION
SHEET TYPE
DESIGNATOR
SHEET SEQUENCE
NUMBER 01-99
MODIFIER
CHARACTER
DISCIPLINE
CHARACTER
-S
AA
DETAIL BUBBLE
INDICATOR
DETAIL/SECTION/PLAN
BLOCK TITLE INDICATOR
EXT ELEVATION
INDICATOR
COLUMN
INDICATOR(S)
KEYNOTE
IDENTIFIER
REVISION
SYMBOL
NNN
0 GENERAL (SYMBOLS LEGEND, NOTES, ETC)
1 PLANS (HORIZONTAL VIEWS)
2 ELEVATIONS (VERTICAL VIEWS)
3 SECTIONS (SECTIONAL VIEWS)
4 LARGE SCALE VIEWS (PLANS, ELEV, OR SECTIONS, NOT DETAILS)
5 DETAILS
6 SCHEDULES AND DIAGRAMS
7 USER DEFINED
8 USER DEFINED
9 3D REPRESENTATIONS (ISOMETRICS, PERSPECTIVES, PHOTOGRAPHS)
A1
54321
FOOTING/PIER
IDENTIFIER
STEP
INDICATOR
HOLDOWN
INDICATOR
BEAM
INDICATOR(S)
MOMENT
INDICATOR
DECK INDICATOR
SHEAR WALL
INDICATOR
LINTEL
INDICATOR
RAFTER
INDICATOR
ASTERISK
INDICATOR
SLOPE
INDICATOR
WORK POINT
INDICATOR
54321
D
B
A
C
D
B
A
C
A3
C5C4
D4
C3
D3
XN
ELEVATION INDICATOR
SECTION
INDICATOR
COLUMN/FND
GRID INDICATOR
SLAB JOINT
INDICATOR
STRUCTURAL HATCH PATTERNS
BRICK
CONCRETE
NATIVE
UNDISTURBED
SOIL
BACKFILL/FILL
ENGINEERED FILL
DRAINAGE
COURSE
GYPSUM
BOARD
WD- BLKG
OR SHIM
PLYWOOD/OSB
/PARTICLE BD
WD- GLUED
/LAMINATED
WOOD-
CONTINUOUS
FRAMING
INSUL/FIRE
SAFING
METAL FLOOR
GRATING
GROUT
RIGID
INSUL/ICF/SIP
/EIFS SYSTEMS
METALS
MORTAR
CMU
ROUGH LOG
WALL
WOOD STUD
BRG WALL
CONC WALL
HOLDOWN
(BLOCKOUT)
STONE/
ROCK WALL
C1
Hx
S W x
XXX' - XX"
TOx
N
CONT
MC-x
-xx"
CONCRETE CURING
STRENGTH SCHEDULE
LOCATION
28 DAY
COMPRESSIVE
STRENGTH
ENTRAINED
AIR
SLUMP
MAX W/C
RATIO
HELICAL PIER CAPS
INTERIOR SLABS
GRADE BEAMS &
ALL OTHER CONC
EXTERIOR SLABS
3,500 PSI
4,500 PSI
4,000 PSI
5,000 PSI
4.0% - 6.0%
5.0% - 7.0%
< 3.0%
5.0% - 7.0%
5" +/- 1"
4"+/- 1"
3" +/- 1"
3" +/ - 1"
0.55
0.45
0.5
0.40
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB
SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND
SITE DRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS AND
OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
2. ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
PROCEEDING WITH THE AFFECTED PART OF THE WORK.
3. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO
DETERMINE ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE
BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION
OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING (AND ACCOMPANYING
FOOTINGS), GUYS OR TIE-DOWNS.
4. ADDITIONAL OBSERVATIONS AS A RESULT OF REJECTION OF WORK COMPLETED
AND/OR ADDITIONAL OBSERVATIONS DUE TO THE DEFICIENCIES IN WORK OBSERVED
WILL BE AT THE EXPENSE OF THE CONTRACTOR.
5. ALL STRUCTURAL SHOP DRAWINGS TO BE REVIEWED BY JOB SUPERINTENDENT IN
ADDITION TO ALL PERSONNEL DEEMED NECESSARY BY CONTRACTOR PRIOR TO
SUBMITTAL TO ENGINEER FOR APPROVAL.
6. ALL SHOP DRAWINGS TO BE REVIEWED BY ALBERTSON ENGINEERING INC. SHALL
HAVE ELECTRONIC COPIES PROVIDED TO ALBERTSON ENGINEERING INC. FOR
REVIEW. AN ELECTRONIC MARKED SET OF THOSE DRAWINGS WILL BE RETURNED TO
THE CONTRACTOR. NO ADDITIONAL HARD COPIES OF THE SHOP DRAWINGS NEED TO
BE PROVIDED TO ALBERTSON ENGINEERING INC., ALTHOUGH OTHER PARTIES MAY
REQUIRE HARD COPIES OF THE MARKED UP DRAWINGS. THESE REQUIREMENTS ARE
IN ADDITION TO THE TYPICAL PROJECT SHOP DRAWING SUBMITTAL REQUIREMENTS
STATED IN THE PROJECT SPECIFICATIONS.
7. THE DESIGN OF THE STRUCTURE SHOWN IN THESE CONSTRUCTION DOCUMENTS IS
FOR THE ONE-TIME USE AT THE SPECIFIC SITE REFERENCED IN THE GEOTECHNICAL
REPORT.
1. SEE THE FOLLOWING REPORT FOR COMPLETE GEOTECHNICAL RECOMMENDATIONS
AND INSTALLATION PROCEDURES. SITE PREPARATION AND FOUNDATION SHALL
COMPLY WITH THE FOLLOWING:
PREPARED BY: NORTHERN TECHNOLOGIES, LLC
TITLE: GEOTECHNICAL EXPLORATION AND ENGINEERING REVIEW
VA BUILDING 1 EXPANSION
FARGO, NORTH DAKOTA
NTI PROJECT 20.FGO 10880
DATE: DECEMBER 3, 2020
2. GEOTECHNICAL RECOMMENDATIONS WERE PREPARED WITH SPECIFIC KNOWLEDGE
OF THE SPECIFIC BUILDING TYPE, CONSTRUCTION TYPE, AND LIKELY LOADS SHOWN ON
THE CONSTRUCTION DOCUMENTS. DETERMINING THE AMOUNT OF SETTLEMENT
ACCEPTABLE FOR THE BUILDING TYPE IS THE RESPONSIBILITY OF THE GEOTECHNICAL
ENGINEER. ALL STRUCTURAL DESIGNS WERE BASED UPON STAYING WITHIN THE
LIMITS GIVEN WITHIN THE GEOTECHNICAL REPORT FOR THE LOADS PRESCRIBED BY
THE BUILDING CODE REFERENCED IN THE DESIGN CODES SECTION OF THESE
STRUCTURAL NOTES.
3. DESIGNS BASED UPON HELICAL PIER SYSTEM DESIGNED BY OTHERS. SEE
GEOTECHNICAL REPORT FOR ALL REQUIREMENTS RELATED TO THE CONSTRUCTION
OF THE HELICAL PIER SYSTEM AND SLAB-ON-GRADE.
MINIMUM SLEEVE SPACING SHALL BE TWO DIAMETERS CENTER TO CENTER TO THE
LARGER SLEEVE OR 6" CLEAR BETWEEN SLEEVES, WHICHEVER IS GREATER. PRIOR TO
CONSTRUCTION SLEEVE LOCATIONS AND SIZES SHALL BE APPROVED BY THE
STRUCTURAL ENGINEER OF RECORD.
SHALL BE A POLYMER INJECTION SYSTEM SUCH AS HILTI-HY 200 EPOXY, OR APPROVED
EQUAL, INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS.
INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
1. SHALL BE A36 THREADED ROD. PROVIDE HOT DIP GALVANIZE FINISH ON ALL
ANCHOR BOLTS PERMANENTLY EXPOSED TO EXTERIOR OR IN CONTACT WITH
PRESSURE TREATED LUMBER.
2. THREADED ROD EMBEDMENT DEPTH SPECIFIED IN THE DRAWINGS SHALL BE FROM
TOP OF CONCRETE TO TOP OF DOUBLE NUT.
1. CONCRETE TESTING SHALL BE PAID FOR BY THE CONTRACTOR. TESTING
LABORATORY APPROVED BY THE CONTRACTING OFFICER SHALL PERFORM THE
FOLLOWING TEST ON CAST-IN-PLACE CONCRETE:
A. ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF PORTLAND CEMENT
CONCRETE."
B. ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF
CYLINDRICAL CONCRETE SPECIMENS. A SEPARATE TEST SHALL BE CONDUCTED
FOR EACH CLASS, FOR EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), PLACED
PER DAY. REQUIRED CYLINDER(S) QUANTITIES AND TEST AGE AS FOLLOWS:
a. AT 7 DAYS
b. AT 28 DAYS
C. PROVIDE ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THE
DIRECTION OF THE ENGINEER, IF REQUIRED. IF 28 DAY STRENGTH IS ACHIEVED,
THE ADDITIONAL CYLINDER(S) MAY BE DISCARDED.
D. TESTING SHALL BE BASED UPON CONCRETE TAKEN AT POINT OF PLACEMENT.
E. IN ADDITION TO TYPICAL TESTING REQUIREMENTS, SLUMP AND AIR CONTENT
SAMPLES SHALL BE TAKEN AT BEGINNING OF FIRST TRUCK PRIOR TO ANY
PLACEMENT AND REPEATED AT THE MIDDLE OF FIRST TRUCK. CONCRETE
PLACEMENT SHALL NOT START IF INITIAL TEST(S) FAIL AND SHALL NOT CONTINUE
OF TEST TAKEN AT MIDDLE OF FIRST LOAD FAILS.
F. IF ANY SLUMP OR AIR CONTENT FAILS DURING PLACMENT, TESTS SHALL BE
IMMEDIATELY REPORTED AND RETAKEN. IF RETAKEN TESTS FAIL THEN ALL
SUBSEQUENT LOADS MUST BE TESTED AT ARRIVAL AND TEST MUST SHOW
COMPLIANCE PRIOR TO THE CONCRETE IN THAT TRUCK BEING ALLOWED FOR USE
ON PROJECT. ALL COSTS FOR ADDITIONAL TESTING SHALL BE THE RESPONSIBILITY
OF THE CONTRACTOR.
NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERS OTHER THAN THOSE
LOCATED ON THESE DRAWINGS.
1. CONCRETE MIX SHALL BE DESIGNED BY RECOGNIZE TESTING LABORATORY TO
ACHIEVE A STRENGTH AT 28 DAYS AS SHOWN IN THE BELOW CONCRETE CURING
STRENGTH SCHEDULE WITH A PLASTIC AND WORKABLE MIX:
2. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR LAB TESTS FOR
REVIEW PRIOR TO USE. MIX SHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR
OTHER POSITIVE IDENTIFICATION. CONCRETE SHALL COMPLY WITH ALL THE
REQUIREMENTS OF ASTM STANDARD C94 FOR MEASURING, MIXING,
TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME STAMPED WHEN
CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM THE TIME THE MIXING
WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED
ONE AND ONE HALF (1-1/2) HOURS. IF FOR ANY REASON THERE IS A LONGER DELAY
THAN STATED ABOVE, THE CONCRETE SHALL BE DISCARDED. IT SHALL BE THE
RESPONSIBILITY OF THE TESTING LAB TO NOTIFY THE OWNER'S REPRESENTATIVE
AND THE CONTRACTOR OF ANY NONCOMPLIANCE WITH THE ABOVE. ALL SLABS
SHALL BE CURED USING CURING COMPOUND MEETING ASTM STANDARD C309 TYPE
1 AND SHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL BE PLACED AS SOON
AS THE FINISHING IS COMPLETED OR AS SOON AS THE WATER HAS LEFT THE
UNFINISHED CONCRETE. ALL SCUFFED OR BROKEN AREAS IN THE CURING
MEMBRANE SHALL BE RECOATED DAILY. CALCIUM CHLORIDES SHALL NOT BE
UTILIZED; OTHER ADMIXTURES MAY BE USED ONLY WITH THE APPROVAL OF THE
ENGINEER.
3. CONCRETE SHALL UTILIZE TYPE I/II CEMENT.
4. COARSE AND FINE AGGREGATES SHALL COMPLY WITH ASTM C33 AND ACI 302.1,
CURRENT VERSIONS.
a. COMPLIANCE WITH THE NON-REACTIVE REQUIREMENTS OF ACI 302.1 SHALL NOT
BE PROVIDED FOR BY THE PROVISION OF ACI 302.1 (SUBSECTION 7.3) THAT
EXCLUDES THE AGGREGATES BEING CLASSIFIED AS DELETERIOUSLY REACTIVE
WITH ALKALIES IF THE AGGREGATE HAS A SATISFACTORY SERVICE RECORD
EVALUATION OR WITH THE ADDITION OF A MATERIAL THAT HAS SHOWN TO
PREVENT HARMFUL EXPANSION DUE TO ALKALI-AGGREGATE REACTION.
b. CONCRETE MIX DESIGN SHALL INCLUDE TEST RECORDS OF THE COMPLIANCE
OF THE AGGREGATE MEETING THE REQUIREMENTS OF ASTM C1260, AND THAT
THE EXPANSION OF THE MORTAR SAMPLE SHALL NOT EXCEED 0.10% WHEN
TESTED IN ACCORDANCE WITH ASTM C1260 AT 14 DAYS. USE OF ADMIXTURES
THAT MITIGATE THE EFFECT OF THE REACTIVE AGGREGATE TO BE PROPOSED
IN CONCRETE MIX SHOP DRAWING MAY BE AN APPROVED APPROACH BY THE
ENGINEER TO ALLOW FOR THE USE OF OTHERWISE REACTIVE AGGREGATES. IF
SUCH MITIGATING MEASURES ARE PROPOSED, THEY MUST BE INCLUDED WITHIN
MIX DESIGN SUBMITTAL. THE ENGINEER IS GIVEN DISCRETION AS TO WHETHER
OR NOT TO ACCEPT MITIGATING MEASURES OR TO MAINTAIN REQUIREMENTS
THAT NONREACTIVE AGGREGATES MUST BE USED. AT A MINIMUM, SUCH
DOCUMENTATION MUST SHOW THAT REACTIVE AGGREGATES USED IN
COMBINATION WITH A GIVEN AMOUNT OF ADMIXTURE RESULTS IN THE
EXPANSION OF THE MORTAR SAMPLE BEING LESS THAN 0.10% WHEN TESTED IN
ACCORDANCE WITH ASTM C1567 AT 14 DAYS. LIABILITY OF THE PERFORMANCE
OF THE CONCRETE MIX REMAINS SOLELY WITH GENERAL CONTRACTOR.
c. IF CONCRETE MIXES ARE APPROVED BY THE ENGINEER THAT CONTAIN EITHER
FINE OR COARSE AGGREGATE, THAT EITHER SEPARATELY OR IN COMBINATION
EXCEED THE 0.10% EXPANSION WHEN TESTED ACCORDING TO ASTM C1260,
SPECIAL CONSIDERATIONS MUST BE GIVEN TO SLAB CURING (SLABS ON GRADE
AND ELEVATED SLABS). IN SUCH INSTANCES SLABS SHALL BE CURED USING
EITHER A WET BURLAP OR CONTINUOUS WETTING/FOGGING METHOD FOR
SLABS FOR AT LEAST 10 DAYS. USE OF CURING AND/OR SEALING COMPOUNDS
IS NOT ACCEPTABLE UNTIL THE SLAB HAS CURED A MINIMUM OF 28 DAYS AND
THE CONDITIONS FOR THE APPLICATION OF THE CURING COMPOUND ON THE
CONCRETE SLAB SET BY THE MANUFACTURER’S RECOMMENDATIONS HAVE
BEEN MET.
d. ENGINEER HAS SOLE DISCRETION IN DETERMINING ACCEPTABILITY OF A
CONCRETE SLAB THAT IS EXHIBITING ALKALI-SILICA REACTION. FOR SLABS
SHOWING AN ALKALI SILICA REACTION SOLELY WITHIN THE FINE AGGREGATE: A
SLAB SHOWING AN AVERAGE DENSITY OF POPOUTS GREATER THAN 1 PER 8
SQUARE FEET OVER ANY CONTIGUOUS AREA OF 100 SQUARE FEET OR LARGER,
OR ANY AREA WITH A DENSITY OF 1 POPOUTS PER 2 SQUARE FEET WITHIN ANY
AREA UP TO 100 SQUARE FEET WOULD BE CONSIDERED AS A BASIS FOR THE
REJECTION OF THE SLAB FROM WHICH THOSE SAMPLE AREAS ARE INCLUDED.
FOR A ALKALI SILICA REACTION WITHIN THE COARSE AGGREGATE: THE POPOUT
DENSITIES CONSIDERED FOR REJECTION OF THE CONCRETE SLAB SHALL BE ½
OF THE DENSITIES GIVEN FOR FINE AGGREGATE. THE EXTENT OF REJECTED
SLAB TO BE DETERMINED BY ENGINEER. THE TIME FRAME FOR OBSERVATION
OF ALKALI SILICA REACTIONS AND DETERMINATION OF REJECTION OF THE
CONCRETE SLAB SHALL BE AT LEAST 56 DAYS FROM THE DATE OF POUR.
e. CONCRETE MIXES UTILIZING CRUSHED LIMESTONE AS COARSE AGGREGATE
AND CONTAINING AT LEAST 25% CLASS F FLY ASH AND HAVING A
SATISFACTORY SERVICE RECORD PER ACI 302.1 IS CONSIDERED AN
ACCEPTABLE ALTERNATIVE APPROACH TO THE COMPLIANCE REQUIREMENTS
OUTLINED IN PROVISIONS 4a THROUGH 4d ABOVE.
5. THE CONCRETE STRENGTHS SHOWN IN THE SECTION ABOVE AND IN THE
SPECIFICATIONS ARE MINIMUM COMPRESSIVE STRENGTHS. THE ENGINEER SHALL
DETERMINE IF THE CONCRETE IS ACCEPTABLE, OR TO BE REMOVED, OR TO
RECEIVE SPECIAL CURING IF THE COMPRESSIVE STRENGTHS ARE LESS THAN
SPECIFIED.
6. WATER REDUCING AGENTS MAY BE USED IN THE CONCRETE MIX. PLASTICIZERS
AND SUPER-PLASTICIZERS MAY BE USED ONLY WHEN WRITTEN PERMISSION OF THE
ENGINEER IS GIVEN.
7. NO SALTS OF ANY KIND MAY BE USED IN CONCRETE BEFORE OBTAINING THE
ENGINEER'S WRITTEN PERMISSION FOR THEIR USE.
1. PRIOR TO BEGINNING WORK, THE CONTRACTOR SHALL CONSTRUCT THREE (3) TEST
PRISMS FOR TESTING. THEY SHALL BE CONSTRUCTED OF TWO (2) 8"x8"x16" PRISMS
FOR TESTING, ONE (1) ON TOP OF THE OTHER, JOINED WITH TYPE "S" MORTAR, AND
FILLED WITH 3,000 PSI CONCRETE GROUT. PRISMS SHALL BE CURED FOR 28 DAYS. NO
REINFORCING SHALL BE USED IN THE CONSTRUCTION OF THE PRISMS.
2. PRISMS SHALL BE MADE OF THE SAME MATERIALS, UNDER THE SAME CONDITIONS,
AND INSOFAR AS POSSIBLE, WITH THE SAME BONDING ARRANGEMENTS AS FOR THE
STRUCTURE. THE MOISTURE CONTENT OF THE UNITS AT THE TIME OF LAYING,
CONSISTENCY OF MORTAR, AND WORKMANSHIP SHALL BE THE SAME AS WILL BE USED
IN THE STRUCTURE. THE VALUE OF f'm SHALL BE THE AVERAGE OF ALL SPECIMENS
TESTED BUT SHALL BE NOT MORE THAN 125 PERCENT OF THE MINIMUM VALUE
DETERMINED BY THE TEST, WHICHEVER IS LESS.
3. TESTING SHALL INCLUDE TESTS IN ADVANCE OF BEGINNING OPERATIONS AS
DESCRIBED ABOVE, AND AT LEAST ONE (1) FIELD TEST DURING CONSTRUCTION FOR
EACH 5,000 SQUARE FEET OF WALL, BUT NOT LESS THAN ONE (1) FIELD TEST MINIMUM
IF TOTAL SQUARE FEET OF WALL FOR ENTIRE PROJECT IS LESS THAN 5,000 S.F. ONLY
WALLS INDICATED ON STRUCTURAL PLANS NEED BE TESTED.
4. THE COMPRESSIVE STRENGTH, f'm, SHALL BE COMPUTED BY DIVIDING THE ULTIMATE
LOAD BY THE NET AREA OF THE MASONRY USED IN THE CONSTRUCTION OF THE
PRISMS.
5. TEST PRISMS SHALL BE STORED FOR SEVEN DAYS IN AIR, AT A TEMPERATURE OF 70
DEGREES, PLUS OR MINUS 5 DEGREES, IN A RELATIVE HUMIDITY EXCEEDING 90%, AND
THEN IN AIR AT A TEMPERATURE OF 70 DEGREES, PLUS OR MINUS 5 DEGREES, UNTIL
TESTED. THOSE CONSTRUCTED IN THE FIELD SHALL BE STORED UNDISTURBED FOR
FROM 48 TO 96 HOURS UNDER WET MATERIAL TO SIMULATE 90% HUMIDITY, THEN
TRANSPORTED TO LABORATORY FOR CONTINUED CURING AS DESCRIBED ABOVE.
6. NOT LESS THAN THREE (3) PRISM SPECIMENS SHALL BE MADE FOR EACH FIELD TEST
TO CONFIRM THAT THE MATERIALS ARE AS ASSUMED IN THE DESIGN. THE STANDARD
AGE OF TEST SPECIMENS SHALL BE 28 DAYS, BUT 7 DAY TESTS MAY BE USED,
PROVIDED THE RELATION BETWEEN THE 7 DAY AND 28 DAY STRENGTHS OF THE
MASONRY IS ESTABLISHED BY ADEQUATE TEST DATA FOR THE MATERIALS USED.
1. MASONRY UNITS SHALL MEET ASTM C90 FOR HOLLOW LOAD BEARING TYPE MASONRY
WITH A UNIT STRENGTH OF 2,800 PSI ON THE NET AREA (f'm = 2,000 PSI).
2. MORTAR SHALL BE TYPE "M" (BELOW GRADE) OR "S" (ABOVE GRADE) AND SHALL MEET
ASTM C270. GROUT SHALL BE 3,000 PSI PEA-GRAVEL CONCRETE AND SHALL MEET ASTM
C476. MORTAR MIX SHALL BE A PRE-BLENDED MIX AS MANUFACTURED BY SPEC-MIX, OR
APPROVED EQUAL. GROUT SHALL BE A READY-MIX GROUT AND SHALL HAVE THE MIX
DESIGN SUBMITTED FOR APPROVAL PRIOR TO CONSTRUCTION.
1. ALL MASONRY SHALL BE LAID IN RUNNING BOND UNLESS NOTED OTHERWISE.
MATERIALS TO BE LAID AND MATERIALS TO BE BUILT UPON SHALL BE FREE FROM
SNOW & ICE.
2. PROVIDE DUR-O-WALL (OR EQUAL PER SPECIFICATIONS) LADDER OR TRUSS
HORIZONTAL JOINT REINFORCEMENT AT EACH SECOND COURSE IN RUNNING BOND,
AND EACH COURSE IN STACKED BOND, UNLESS NOTED OTHERWISE. DISCONTINUE
HORIZONTAL JOINT REINFORCEMENT AT CONTROL JOINTS.
3. PROVIDE BOND BEAMS REINFORCED WITH (2) #5 BARS EVERY 6'-0" OF VERTICAL
WALL, AT TOPS OF ALL MASONRY WALLS, AND WHERE SHOWN ON DRAWINGS. AT
BOND BEAM CORNERS AND TEE JOINTS, PROVIDE BENT BARS TO MATCH QUANTITY
AND BAR SIZE IN THE BOND BEAM. LAPS IN BOND BEAMS SHALL BE 48 BAR
DIAMETERS OR A MINIMUM OF 2'-0", WHICHEVER IS GREATER.
4. WHERE SHOWN ON THE DRAWINGS, CORES IN CONCRETE BLOCKS UNITS SHALL BE
FILLED WITH 3,000 PSI CONCRETE GROUT FROM TOP OF FOOTING TO BOTTOM OF
BEARING, OR TO THE TOP OF WALL, DEPENDING ON THE CONDITION. INSPECTION OF
OPENING AT BOTTOM IS REQUIRED.
5. WHERE REINFORCING STEEL IS CALLED FOR IN FILLED CORES, IT SHALL EXTEND
FROM TOP OF FOOTING TO BOTTOM OF BEARING, OR TOP OF WALL. DEPENDING ON
CONDITION.
6. WHERE REINFORCING STEEL IS INTERRUPTED BY AN OPENING IN THE WALL, THE
QUANTITY OF BARS INTERRUPTED ARE TO BE MOVED TO EACH SIDE OF THE
OPENING, HALF OF REINFORCING TO ONE SIDE AND REMAINING HALF TO THE OTHER
SIDE. REINFORCING SHALL BE FROM TOP OF FOOTING TO TOP OF WALL. PROVIDE A
MINIMUM OF (2) #5 VERTICAL REINFORCING BARS AT EACH JAMB. SEE PLAN NOTES
AND / OR DETAILS FOR VERTICAL REINFORCING SPACING.
7. WHERE VERTICAL REINFORCING STEEL IS SPLICED IN MASONRY, PROVIDE A MINIMUM
OF 48 BAR DIAMETERS, LAP SPLICE, UNLESS NOTED OTHERWISE.
8. THE MINIMUM DISTANCE BETWEEN PARALLEL BARS, EXCEPT IN COLUMNS, SHALL BE
NOT LESS THAN THE DIAMETER OF THE BAR EXCEPT THAT LAPPED SPLICES MAY BE
WIRED TOGETHER. THE CENTER TO CENTER SPACING OF BARS WITHIN A COLUMN
SHALL BE NOT LESS THAN 2 AND ONE-HALF TIMES THE BAR DIAMETER.
9. ALL BARS SHALL BE COMPLETELY EMBEDDED IN MORTAR OR CONCRETE.
REINFORCEMENT EMBEDDED IN HORIZONTAL MORTAR JOINTS SHALL HAVE NOT LESS
THAN 5/8" MORTAR COVERAGE FROM THE EXPOSED FACE. ALL OTHER REINFORCING
SHALL HAVE A MINIMUM COVERAGE OF ONE BAR DIAMETER OVER ALL BARS, BUT NOT
LESS THAN 3/4", EXCEPT WHERE EXPOSED TO WEATHER OR SOIL IN WHICH CASE THE
MINIMUM COVERAGE SHALL BE 2".
10. WHERE REINFORCING IS SHOWN TO BE LOCATED ALONG TWO FACES OF A MASONRY
BLOCK WALL, THE CONTRACTOR SHALL BREAK OUT THE SHELL OF THE LOWEST
MASONRY BLOCK TO GAIN ACCESS TO THE REINFORCING STEEL. THE REINFORCING
STEEL SHALL THEN BE WIRED INTO ITS CORRECT POSITION, AND THE ACCESS HOLE
COVERED. THE CONCRETE GROUT FILL SHALL BE PUDDLED OR VIBRATED TO
ASSURE COMPLETE FILLING OF THE CORE.
11. REINFORCED MASONRY PIERS AND COLUMNS SHALL HAVE THE REINFORCING STEEL
ACCURATELY LOCATED BY WIRING THE TOP AND BOTTOM OF ALL VERTICAL STEEL
INTO ITS CORRECT POSITION. PROVIDE AN ACCESS HOLE AT THE BOTTOM OF ALL
COLUMNS OR PIERS.
12. ALL REINFORCED HOLLOW UNIT MASONRY SHALL BE BUILT TO PRESERVE THE
UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO BE FILLED. WALLS AND
CROSS WEBS FORMING SUCH CELLS TO BE FILLED SHALL BE FULLBEDDED IN
MORTAR TO PREVENT LEAKAGE OF CONCRETE GROUT. ALL HEAD (OR END) JOINTS
SHALL BE SOLIDLY FILLED WITH MORTAR FOR A DISTANCE IN FROM THE FACE OF THE
WALL OR UNIT NOT LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS.
BOND SHALL BE PROVIDED BY LAPPING UNITS IN SUCCESSIVE VERTICAL COURSES OR
BY EQUIVALENT MECHANICAL ANCHORAGE.
A. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO
MAINTAIN A CLEAR, UNOBSTRUCTED CONTINUOUS VERTICAL CELL MEASURING
NOT LESS THAN 2"x3".
B. CLEANOUT OPENINGS SHALL BE PROVIDED AT THE BOTTOM OF ALL CELLS TO BE
FILLED AT EACH POUR OF CONCRETE WHERE SUCH CONCRETE POUR IS IN
EXCESS OF 6' IN HEIGHT. ANY OVERHANGING MORTAR, OTHER OBSTRUCTION OR
DEBRIS SHALL BE REMOVED AND / OR CLEANED AT TIME OF INSPECTION AND
PRIOR TO CORE FILLING. INSPECT AND SEAL ALL OPENINGS BEFORE
CONCRETING.
C. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT TOP AND BOTTOM
AND AT INTERVALS NOT EXCEEDING 192 DIAMETERS OF THE REINFORCEMENT.
D. ALL CELLS CONTAINING REINFORCEMENT SHALL BE FILLED SOLIDLY WITH
CONCRETE. CONCRETE SHALL BE POURED IN LIFTS OF 8' MAXIMUM HEIGHT. ALL
CONCRETE SHALL BE CONSOLIDATED AT THE TIME OF POURING BY PUDDLING
FOR LIFTS OF 4' OR LESS, OR BY VIBRATING FOR LIFTS GREATER THAN 4'.
CONCRETE SHOULD LATER BE CONSOLIDATED AGAIN BY PUDDLING, BEFORE
PLASTICITY IS LOST.
E. WHEN TOTAL CONCRETE POUR EXCEEDS 8' IN HEIGHT, THE CONCRETE SHALL BE
PLACED IN 4' MAXIMUM LIFTS MINIMUM CELL DIMENSION SHALL BE 3".
F. WHEN CONCRETING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL
CONSTRUCTION JOINTS SHALL BE FORMED BY STOPPING THE POUR OF
CONCRETE 1 1/2" BELOW THE TOP OF THE UPPERMOST UNIT.
13. PROVIDE A MINIMUM OF 8" BEARING FOR ALL MASONRY LINTELS.
14. WHERE LINTEL BLOCKS ARE USED IN LIEU OF HOLLOW MASONRY BLOCKS, THE
REINFORCING STEEL SHALL BE ANCHORED TO THE LOWER STEEL OR DOWELS AND
THE LINTEL BLOCKS LAID AROUND THE STEEL. THE CONCRETE FILL SHALL BE
INSTALLED IN LIFTS NO TO EXCEED 2' IN HEIGHT. THE REINFORCING STEEL SHALL BE
MAINTAINED IN THE SAME POSITION AS THE DOWELS. STOP THE POUR OF THE
CONCRETE 1 1/2" BELOW THE TOP OF THE UPPERMOST UNIT.
15. SPECIFICATION REQUIREMENTS FOR COLD WEATHER AND HOT WEATHER MASONRY
CONSTRUCTION SHALL BE MAINTAINED.
1. UNLESS NOTED OTHERWISE ALL BEAMS SUPPORTED BY MASONRY WALLS SHALL BEAR
ON A BEAM BEARING PLATE POCKETED INTO THE WALL. BEAM SHALL BEAR A
DISTANCE NO LESS THAN THE SPAN DISTANCE DIVIDED BY 16. FOR BEAMS
PERPENDICULAR TO THE SUPPORTING WALL, THE BEAM SHALL EXTEND TO WITHIN 2"
OF THE OPPOSITE SIDE OF WALL. BEAM BEARING PLATES SHALL BE 5/8" THICK AND
SHALL HAVE (2)1/2"DIA.x5" H.S. STUDS AT 8" ON CENTER MAXIMUM (2 MINIMUM). PLATES
SHALL BE 2" WIDER THAN BEAM. ALL CELLS IN MASONRY BELOW BEAM BEARING
PLATES SHALL BE GROUTED SOLID. THESE REQUIREMENTS APPLY TO NEW AND
EXISTING CMU WALLS UNLESS NOTED OTHERWISE.
1. STEEL SHALL CONFORM TO ASTM A992 (Fy=50 KSI) FOR ALL W-SHAPES, AND ASTM A36 (Fy=36 KSI) FOR ALL OTHER MISCELLANEOUS SHAPES AND PLATES.
STRUCTURAL TUBING SHALL CONFORM TO ASTM A500, GRADE B OR GRADE C (Fy=46
KSI). STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B, TYPE "E" OR "S"
(Fy=35 KSI).
2. STEEL SHALL CONFORM TO THE LATEST EDITION OF AISC SPECIFICATIONS FOR
STRUCTURAL STEEL BUILDINGS.
3. ALL SHOP CONNECTIONS TO BE WELDED (UTILIZING E70XX ELECTRODES) AND FIELD
CONNECTIONS TO BE BOLTED, UNLESS OTHERWISE NOTED. STEEL TO RECEIVE ONE
SHOP COAT AND ONE FIELD TOUCH UP COAT OF APPROVED PAINT, EXCEPT WHERE
GALVANIZED IS INDICATED ON THE DRAWINGS.
4. WELDS FOR ALL EXPOSED STRUCTURAL STEEL SHALL BE GROUND SMOOTH UNLESS
NOTED OTHERWISE.
5. ALL BOLTED CONNECTIONS SHALL CONSIST OF 3/4" DIA. (MIN.) F3125 GR A325 GR
F1852 BOLTS, UNLESS NOTED OTHERWISE
A. FAILURE OF A BOLT OR NUT DURING INSTALLATION PROCESS RESULTING IN A
CRACK IN THE BOLT OR NUT SHALL BE GROUNDS FOR REJECTION OF ALL THE
FAILED BOLTS OR NUTS COMING FROM THE SAME LOT. IF THE DOCUMENTATION
OF THE LOT OF ORIGIN FOR THE FAILED NUT(S) OR BOLT(S) DOES NOT EXIST, OR
IS NOT PROVIDED, THEN ALL OF THE BOLT(S) OR NUT(S) SHALL BE ASSUMED TO
COME FROM THE LOT CONTAINING THE FAILED NUT(S) OR BOLT(S).
6. CONTRACTOR SHALL MAINTAIN ERECTION TOLERANCES OF STRUCTURAL STEEL AND
ARCHITECTURALLY EXPOSED STRUCTURAL STEEL WITHIN AISC'S CODE OF
STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES.
7. ANCHOR BOLT HOLES IN STRUCTURAL STEEL SHALL BE OVERSIZED NO MORE THAN
1/8" MAX, UNLESS NOTED OTHERWISE.
1. SHEAR STUD CONNECTORS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE
WITH AWS D1.1, "STRUCTURAL WELDING CODE", SECTION 7 - STUD WELDING. STUDS
SHALL BE TYPE "B", HEADED STUDS, HAVING A MINIMUM TENSILE STRENGTH OF 60,000
PSI, AND SHALL BE OF LENGTH AND DIAMETER SHOWN ON THE DRAWINGS.
1. COMPOSITE FORM DECK SHALL BE 2" DEEP, 18 GAUGE G60 CORRUGATED STEEL
COMPOSITE DECK (2VLI-18) AND SHALL CONFORM TO THE PROVISIONS OF THE STEEL
DECK INSTITUTE (SDI) SPECIFICATIONS FOR COMPOSITE STEEL DECK.
2. POUR STOPS AND GIRDER FILLERS: WELD STEEL SHEET POUR STOPS AND GIRDER
FILLERS TO SUPPORTING STRUCTURE ACCORDING TO SDI RECOMMENDATIONS,
UNLESS OTHERWISE INDICATED.
3. FLOOR DECK CLOSURES: WELD STEEL SHEET COLUMN CLOSURES, CELL CLOSURES,
AND Z-CLOSURES TO DECK, ACCORDING TO SDI RECOMMENDATIONS, TO PROVIDE
TIGHT FITTING CLOSURES AT OPEN ENDS OF RIBS AND SIDES OF DECKING. WELD
COVER PLATES AT CHANGES IN DIRECTION OF FLOOR DECK PANELS, UNLESS
OTHERWISE INDICATED.
4. DECKING SHALL HAVE MINIMUM OF (3) SPANS.
1. STEEL STUD, TRACK, AND LINTEL MEMBERS SHALL BE OF THE TYPE SHOWN ON THE
DRAWINGS AND IN THE SPECIFICATIONS AND SHALL CONFORM TO ASTM A653
STRUCTURAL QUALITY GRADE 33 FOR 18 GAUGE THICKNESS OR LESS, AND ASTM A653
STRUCTURAL QUALITY GRADE 50, CLASS 1 FOR 16 GAUGE OR GREATER. MEMBERS
SHALL HAVE HOT DIPPED GALVANIZED COATING CONFORMING TO ASTM A924, CLASS
G60.
2. METAL STUD MEMBERS SHALL CONFORM TO THE FOLLOWING MINIMUM AISI
SECTIONS:
6"x16 GA. : 600 S 162-54
3. ALL FRAMING MEMBERS SHALL BE CUT SQUARELY OR AT AN ANGLE AS REQUIRED TO
FIT SQUARELY AGAINST ABUTTING MEMBERS. MEMBERS SHALL BE HELD FIRMLY IN
PLACE UNTIL PROPERLY JOINED.
4. JOINING OF STRUCTURAL MEMBERS SHALL BE MADE WITH SELF-DRILLING SCREWS
OR WELDED. WIRE TYING OF FRAMING MEMBERS IN STRUCTURAL APPLICATIONS
SHALL NOT BE PERMITTED.
5. ATTACHMENT OF COLLATERAL MATERIALS TO STEEL MEMBERS SHALL BE MADE WITH
SELF-DRILLING SCREWS OR HARDENED SCREW SHANK NAILS. METAL LATH MAY ALSO
BE CONNECTED TO STEEL BY STAPLES OR OTHER FASTENERS, IF APPROVED BY
LOCAL BUILDING CODES.
6. STUDS SHALL SIT SQUARELY IN THE TOP AND BOTTOM RUNNER TRACK WITH
ABUTMENT AGAINST TRACK WEBS. STUDS SHALL BE ALIGNED OR PLUMBED AND
SECURELY FASTENED TO THE FLANGES OF BOTH TOP AND BOTTOM RUNNER TRACKS.
7. VERTICAL SLIP CONNECTORS TO ALLOW THE VERTICAL MOVEMENT OF THE
SUPPORTING STRUCTURE RELATIVE TO THE STUD. CONNECTOR MANUFACTURER
RESPONSIBLE FOR PROVIDING DOCUMENTATION THAT CONNECTOR HAS ADEQUATE
CAPACITY FOR INSTALLATIONS IN WHICH THEY ARE TO BE INSTALLED, AS WELL AS
SPECIFYING THE CONNECTION OF THEIR CONNECTOR TO BOTH THE METAL STUD AND
SUPPORTING STRUCTURE.
STRUCTURAL SHEET INDEX
SHT NO SHEET NAME
S-001 STRUCTURAL GENERAL NOTES
S-002 STRUCTURAL ABBREVIATIONS & IBC INSPECTION TABLES
S-003 IBC INSPECTION TABLES
S-004 SNOW DRIFT AND WIND UPLIFT PLANS
S-005 CONCRETE SURFACE REQUIREMENTS
S-601 STANDARD DETAILS / SCHEDULES
S-602 METAL STUD DETAILS / SCHEDULES
SB101 FOUNDATION PLAN LEVEL B1
SB501 FOUNDATION DETAILS
SB502 FOUNDATION DETAILS
SF101 FLOOR FRAMING PLAN LEVEL 01
SF102 ROOF/FUTURE FLOOR FRAMING PLAN LEVEL 02
SF103 FUTURE FLOOR FRAMING PLAN LEVEL 03
SF104 FUTURE FLOOR FRAMING PLAN LEVEL 04
SF105 FUTURE FLOOR FRAMING PLAN LEVEL 05
SF106 FUTURE FLOOR FRAMING PLAN LEVEL 06
SF401 LATERAL FRAMING ELEVATIONS
SF402 LATERAL FRAMING ELEVATIONS & DETAILS
SF403 LATERAL FRAMING DETAILS
SF404 ENLARGED STAIR FRAMING PLANS AND DETAILS
SF501 FRAMING DETAILS
SF502 FRAMING DETAILS
SF503 FRAMING DETAILS
1. ALL CONCRETE SHALL BE PLACED IN ACCORDANCE WITH ACI 301 AND ACI 117
EXCEPT AS MODIFIED BELOW:
A. ACI 117 ITEM 4.3.1.1 ELEVATIONS OF SLABS-ON-GRADE TOP OF SLAB ELEVATION
SHALL BE WITHIN A 3/8" ENVELOPE EITHER SIDE OF THE THEORETICAL DESIGN
SURFACE.
B. ACI 117 ITEM 4.5.7 FLOOR FINISH TOLERANCES AS MEASURED BY PLACING A
FREESTANDING (UNLEVELED) 10 FT. STRAIGHTEDGE ANYWHERE ON THE SLAB
AND ALLOWING IT TO REST UPON TWO HIGH SPOTS WITHIN 28 DAYS AFTER
SLAB CONCRETE PLACEMENT. THE GAP AT ANY POINT BETWEEN THE
STRAIGHT EDGE AND THE FLOOR SHALL NOT EXCEED 1/4".
2. ALL REINFORCING STEEL TO BE ASTM A615, GRADE 60 (#4 AND LARGER), EXCEPT
WHERE NOTED OTHERWISE. REINFORCING SHALL NOT BE WELDED
3. WELDED WIRE FABRIC TO CONFORM TO ASTM A185 AND SHALL BE FREE FROM OIL,
SCALE, AND RUST. PLACE WWF IN ACCORDANCE WITH THE TYPICAL PLACING
DETAILS OF ACI STANDARDS AND THE SPECIFICATIONS. MINIMUM LAPS SHALL BE
ONE SPACE PLUS 2"
4. ALL REINFORCING STEEL BARS TO BE DETAILED AND PLACED IN ACCORDANCE
WITH THE LATEST ACI MANUALS.
5. LAP ALL REINFORCING SPLICES IN CONCRETE A MINIMUM OF 48 BAR DIAMETERS
OR 24 INCHES, WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE ON
DRAWINGS (CLASS B SPLICE).
6. PROVIDE CORNER BARS OF SAME BAR DIAMETER AS SPECIFIED FOR THE WALL,
BEAM OR FOOTING. PROVIDE MINIMUM OF 40 BAR DIAMETER LAP FOR ALL CORNER
BARS, UNLESS NOTE OTHERWISE.
7. PROVIDE FOUNDATION DOWELS AS SHOWN. MINIMUM SIZE DOWELS TO BE #4,
UNLESS OTHERWISE NOTED. ALL VERTICAL REINFORCING STEEL IN COLUMNS AND
PIERS, OR VERTICAL REINFORCING IN WALLS, SHALL BE DOWELED INTO THE
FOOTINGS WITH SAME SIZE AND QUANTITY DOWEL AS THE VERTICAL
REINFORCING.
8. WHERE SHOWN ON THE DRAWINGS, PROVIDE WELD PLATES, WELDMENTS, OR
CONCRETE INSERTS FOR FASTENING AND SECURING OTHER COMPONENTS.
CONCRETE INSERTS SHALL BE FURNISHED BY THE CONTRACTOR REQUIRING
THEM AND INSTALLED BY THE CONTRACTOR CASTING THE CONCRETE AROUND
THEM. CLIP ANGLES SHALL BE FURNISHED BY THE CONTRACTOR REQUIRING
THEM.
9. REINFORCING STEEL SHALL RECEIVE CONCRETE COVER AS FOLLOWS:
DESCRIPTION MINIMUM COVER
CAST AGAINST & PERMANENTLY 3"
EXPOSED TO EARTH
EXPOSED TO EARTH OR WEATHER
#6 THROUGH #18 BARS 2"
#5 BARS OR SMALLER 1 1/2"
NOT EXPOSED TO EARTH OR WEATHER
OR IN CONTACT WITH THE GROUND, SLABS
AND WALLS
#11 BARS OR SMALLER 3/4"
#14 AND #18 1 1/2"
BEAMS AND COLUMNS 1 1/2"
SHELLS, FOLDED PLATE MEMBERS:
NO. 6 BAR AND LARGER 3/4"
NO. 5 BAR, W31 OR D31 WIRE AND SMALLER 1/2"
10. PROVIDE TWO (2) #5'S, ONE AT EACH FACE, UNLESS NOTED OTHERWISE, AROUND
ALL OPENINGS GREATER THAN 12"x12" IN CAST-IN-PLACE CONCRETE. EXTEND
REINFORCING 2'-0" BEYOND OPENING IN BOTH DIRECTIONS. CONTACT ENGINEER
FOR ALL OPENINGS GREATER THAN 12"x12" FOR DESIGN.
11. COLD WEATHER AND HOT WEATHER PROVISIONS OF ACI 306 AND 305 (CURRENT
EDITIONS), RESPECTIVELY, SHALL BE MAINTAINED.
12. UNLESS NOTED OTHERWISE ALL UNDER SLAB VAPOR RETARDERS SHALL
CONFORM TO THE REQUIREMENTS OF ASTM E1745 CLASS A AND SHALL BE
INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS.
13. PRIOR TO SCREEDING AN ELEVATED SLAB, CONCRETE SHALL BE UNIFORMLY
PLACED ON ALL (3) SPANS OF THE DECK TO A THICKNESS APPROXIMATELY EQUAL
TO THE SPECIFIED SLAB THICKNESS AT EACH BEAM OR JOIST LINE.
14. CONTRACTOR IS RESPONSIBLE FOR ESTIMATING CONCRETE QUANTITIES ON
ELEVATED SLABS AND SHALL ACCOUNT FOR DEFLECTIONS IN THE FLOOR
STRUCTURE.
15. CONTRACTOR SHALL MAINTAIN A CONSTANT THICKNESS OVER THE ENTIRE
ELEVATED SLAB. ELEVATED SLAB THICKNESS SHALL NOT BE 1/4" LESS THAN THE
SPECIFIED THICKNESS.
16. LASER SCREED OR OTHER SIMILARLY FUNCTIONING EQUIPMENT SHALL NOT BE
PERMITTED FOR ELEVATED SLABS UNLESS AUTHORIZED BY ALBERTSON
ENGINEERING INC.
GENERAL NOTES:
DESIGN CODES:
DESIGN LOADS:
FOUNDATIONS:
PLUMBING SLEEVES:
PENETRATIONS:
CONCRETE MIX DESIGN: CONCRETE AND REINFORCING PLACEMENT:
CONCRETE TESTING:
CHEMICAL ANCHORS:
ANCHOR BOLTS:
MASONRY AND REINFORCING MASONRY PLACEMENT:
MASONRY PRISM TESTING:
MASONRY BEAM BEARING PLATES:
MASONRY MATERIALS:
STRUCTURAL STEEL:
SHEAR STUD CONNECTORS:
COMPOSITE STEEL FORM DECK:
COLD FORMED LIGHT GAUGE STRUCTURAL STEEL:
• STRUCTURAL DESIGN MANUAL FOR HOSPITAL PROJECTS: DEPARTMENT OF
VETERANS AFFAIRS, FEBRUARY 1, 2014.
• 2018 INTERNATIONAL BUILDING CODE.
• ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND
COMMENTARY.
• AISC 360-16 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS.
• AISI S100-16 NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED
STEEL STRUCTURAL MEMBERS.
• ASCE 7-16 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND
OTHER STRUCTURES.
• SDI C-2017 STANDARD FOR COMPOSITE STEEL FLOOR DECK.
• SDI NC-2017 STANDARD FOR NON-COMPOSITE STEEL FLOOR DECK.
• TMS 402-16 / ACI 530-16 BUILDING CODE FOR MASONRY STRUCTURES.
PE-5261
MICHAEL D.
ALBERTSON
R E
G
IS
T E
R
ED E
NG
I N
E E
R
PROFESS I ONAL
N O
R T H
D A KO TA
DATE
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
CALIBRE
9090 S RIDGELINE BLVD, SUITE 105
HIGHLANDS RANCH COLORADO 80129
PHONE (303) 730-0434
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 343-9606
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 of
11-16-21
/1 /2
:0
:0
A
M
CONSTRUCTION DOCUMENTS
11/16/2021
STRUCTURAL GENERAL NOTES
S-001
EXPAND BLDG. 1 FOR
PRIMARY CARE
MDRAJH
2101 ELM STREET
FARGO, ND 58102FARGO VAHCS
437-315
58 128
PHOTO DOCUMENTATION OF CONSTRUCTION OF STRUCTURAL ITEMS
1. CONTRACTOR SHALL PROVIDE SETS OF PERIODIC DIGITAL PHOTOGRAPHS OF THE CONSTRUCTION OF THE STRUCTURAL PORTIONS OF THE CONSTRUCTION PROJECT TO THE ENGINEER FOR APPROVAL. PHOTOGRAPHS SHALL BE SUBMITTED TO THE ENGINEER WITHIN 2 WORKING DAYS OF WHEN THEY WERE TAKEN. THE MINIMUM SETS OF PHOTOGRAPHS TO BE TAKEN
INCLUDE THE FOLLOWING:
EVENT
OVERALL CONSTRUCTION PROGRESS
OCCURRENCES
MINIMUM OF ONCE WEEKLY DURING CONSTRUCTION. CAN
INCLUDE PHOTOS FROM OTHER REQUIRED AREAS.
ITEMS TO DOCUMENT
GENERAL PROGRESSION OF CONSTRUCTION PROJECT. SET
OF PHOTOGRAPHS TO BE SUFFICIENT TO SHOW MAJOR
ASPECTS OF CONSTRUCTION, WITH A MINIMUM OF 8
PHOTOGRAPHS PER SET.
CONCRETE POURS PRIOR TO EACH CONCRETE POUR CONDITION OF FORM WORK, PLACEMENT OF CONCRETE
REINFORCING, METHODS USED TO SECURE REINFORCING IN
CORRECT LOCATIONS. MINIMUM NUMBER OF
PHOTOGRAPHS TO BE AS REQUIRED TO SHOW ALL
DIFFERING CONDITIONS.
CONCRETE MASONRY CONSTRUCTION PRIOR TO GROUTING PLACEMENT OF REINFORCING AND METHODS USED TO
SECURE REINFORCING IN CORRECT LOCATIONS. MINIMUM
NUMBER OF PHOTOGRAPHS TO BE AS REQUIRED TO SHOW
ALL DIFFERING CONDITIONS
STEEL CONSTRUCTION PRIOR TO ENCLOSURE TYPICAL CONNECTIONS. MINIMUM NUMBER OF
PHOTOGRAPHS TO BE AS REQUIRED TO SHOW ALL
DIFFERING CONDITIONSMAJOR MILESTONES
2. ALL PHOTOGRAPHS TAKEN SHALL CLEARLY SHOW THE LOCATIONS AT WHICH THE PHOTOGRAPHS ARE BEING TAKEN. TYPICALLY THE LOCATIONS ARE SELF-EVIDENT, BUT FOR THOSE CASES WHERE THEY ARE NOT, CONTRACTOR TO INCLUDE SOME METHOD OF DOCUMENTING THE LOCATIONS. THE PHOTOGRAPHS SUBMITTED MAY BE EITHER A HARD COPY OR ELECTRONIC FORMAT. HARD COPIES OF THE PHOTOGRAPHS ARE NOT REQUIRED, AND IT IS STRONGLY PREFERRED THAT THE PHOTOGRAPHS BE E-MAILED TO ALBERTSON ENGINEERING, VA COR AND THE ARCHITECT AT THE FOLLOWING E-MAIL ADDRESSES:
ALBERTSON ENGINEERING INC.
ENGINEER OF RECORD: E-MAIL ADDRESS: VA COR: E-MAIL ADDRESS:
MICHAEL D. ALBERTSON mike@albertsonengineering.com DENNIS LANGEVIN Dennis.Langevin@va.gov AARON HARTWELL aaron@albertsonengineering.com
ARCHITECT: E-MAIL ADDRESS:
FOURFRONT DESIGN Joel.Simonyak@fourfrontdesign.com
THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED WITH THE
FOLLOWING SUPERIMPOSED LOADINGS BASED ON A RISK CATEGORY IV:
ROOF:
SNOW LOAD 42 PSF + DRIFT
GROUND SNOW LOAD 50 PSF
SNOW EXPOSURE FACTOR 1.0
SNOW THERMAL FACTOR 1.0
SNOW IMPORTANCE FACTOR 1.2
DEAD LOAD 20 PSF
LIVE LOAD 20 PSF (REDUCIBLE)
RAIN INTENSITY 3.0 IN/HR
WIND:
ULTIMATE WIND SPEED 124 MPH
EXPOSURE CATEGORY C
INTERNAL PRESSURE COEFFICIENT 0.18
COMPONENT AND CLADDING PRESSURES SEE TABLE ON SHEET S-004
SEISMIC:
SEISMIC DESIGN CATEGORY A
SITE CLASSIFICATION D
SEISMIC IMPORTANCE FACTOR 1.5
MAPPED SPECTRAL RESPONSE COEFFICIENTS
Ss = 0.059 S1 = 0.019
SEISMIC FORCE RESISTING SYSTEM
RIGID DIAPHRAGM (COMPOSITE METAL DECK), STEEL ORDINARY
CONCENTRICALLY BRACE FRAMES, AND STEEL ORDINARY MOMENT FRAMES
DESIGN BASE SHEAR 0.01W
SEISMIC RESPONSE COEFFICIENT 0.03
RESPONSE MODIFICATION COEFFICIENTS (R)
STEEL ORDINARY CONCENTRICALLY BRACED FRAMES 3.25
ANALYSIS PROCEDURE
EQUIVALENT LATERAL FORCE PROCEDURE
1. SEE GEOTECHNICAL REPORT FOR ANTICIPATED DEPTHS AND INSTALLATION
REQUIREMENTS.
2. HELICAL PIERS AND HELICAL PIER CAPS SHALL BE DESIGNED BY SPECIALTY
CONTRACTOR TO THE LOAD CARRYING CAPACITY SHOWN ON THE DRAWINGS AND
THE SPECIFICATIONS. DETERMINING SHAFT SIZE, PLATE SIZE, CONFIGURATION,
QUANTITY, AND SPACING IS THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE
INCLUDED IN THE BASE BID.
3. HELICAL PIERS SHALL BE DESIGNED FOR A MAXIMUM VERTICAL DEFLECTION OF 0.33in
AND LATERAL DEFLECTION OF 0.5IN.
4. A HELICAL PIER SHALL BE LOAD TESTED ACCORDING TO ASTM D1143. TESTED PIER
CAN BE A PRODUCTION PILE AT SPECIALTY ENGINEER'S CHOICE. SEE GEOTECHNICAL
REPORT FOR ADDITIONAL TESTING REQUIREMENTS. IF TEST PIER FAILS, CONTRACTOR
SHALL MODIFY THEIR DESIGN AND INSTALL AND TEST ANOTHER PIER AT THEIR
EXPENSE.
5. SHOP DRAWINGS AND A LETTER OF CERTIFICATION SHALL BE SUBMITTED FOR
REVIEW AND APPROVAL PRIOR TO INSTALLATION, AND SHOP DRAWINGS SHALL BEAR
THE SIGNATURE AND SEAL OF A NORTH DAKOTA REGISTERED PROFESSIONAL
ENGINEER. SHOP DRAWINGS SHALL INDICATE THE DESIGN LOADS AND JOB NAME
AND NUMBER. THEY SHALL INCLUDE DRAWINGS OF THE HELICAL PIERS AND THE
CONNECTION TO THE PILE CAPS OR GRADE BEAMS.
6. STRUCTURAL DESIGN OF ALL HELICAL PIER COMPONENTS ARE TO BE DONE BY
HELICAL PIER CONTRACTOR. STRUCTURAL DESIGN TO BE COMPLETED BY A
PROFESSIONAL ENGINEER LICENSED IN THE STATE OF NORTH DAKOTA.
PROFESSIONAL ENGINEER(S), OR SOMEONE WORKING UNDER THEIR DIRECT
SUPERVISION SHALL MAKE PERIODIC OBSERVATIONS DURING THE INSTALLATION OF
THE HELICAL PIERS TO VERIFY THAT INSTALLATION IS IN CONFORMANCE WITH THEIR
SEALED DOCUMENTS. A MINIMUM OF TWO SEPARATE OBSERVATIONS SHALL BE MADE
BY SUCH PARTY. COST FOR SUCH PROFESSIONAL ENGINEER(S) OR SOMEONE
WORKING UNDER THEIR DIRECT SUPERVISION SHALL BE INCLUDED IN THE BASE BID.
ANY AND ALL DEFICIENT ITEMS SHALL BE RECORDED BY THE PROFESSIONAL
ENGINEER AND ITEMS SHALL BE CORRECTED AND CORRECTIONS VERIFIED BY THE
PROFESSIONAL ENGINEER(S) FOR THE HELICAL PIER CONTRACTOR. PROFESSIONAL
ENGINEER(S) FOR HELICAL PIER CONTRACTOR SHALL CERTIFY THAT INSTALLATION IS
IN CONFORMANCE WITH THEIR DESIGN DOCUMENTS AT THE COMPLETION OF THEIR
WORK. PROFESSIONAL ENGINEER(S) FOR HELICAL PIER CONTRACTOR SHALL PROVIDE
CERTIFICATION AND WRITTEN OBSERVATION REPORTS FOR EVERY VISIT MADE TO
THE ARCHITECT. OBSERVATION REPORTS SHALL BE GIVEN TO ARCHITECT WITHIN 3
WORKING DAYS OF THE VISIT TO THE SITE.
HELICAL PIERS:
7. FOR THE PURPOSES OF THIS STRUCTURAL NOTES SECTION, ALL OF THE FIELD
OBSERVATION WORK DESCRIBED TO BE PERFORMED BY PROFESSIONAL ENGINEER
RESPONSIBLE FOR DESIGN OF HELICAL PIERS OR SOMEONE WORKING UNDER
HIS/HER DIRECT SUPERVISION. ALL OBSERVATION REPORTS TO BE SIGNED BY
PERSON WHO MADE OBSERVATION AND PROFESSIONAL ENGINEER RESPONSIBLE
FOR THE DESIGN.
SPECIAL INSPECTION AND TESTING:
1. SPECIAL INSPECTION AND MINIMUM TESTING SHALL BE PERFORMED IN ACCORDANCE WITH 2018 IBC AND ALL REFERENCED MATERIALS AND TABLES.
2. INSPECTION SHALL BE PROVIDED BY AN INDEPENDENT TESTING AGENCY HIRED AT THE CONTRACTOR'S EXPENSE. AGENCY INSPECTION PERSONNEL SHALL MEET THE INSPECTOR
QUALIFICATIONS FOR EACH MATERIAL ITEM AS INDICATED IN THE SPECIFICATIONS.
3. ANY MATERIAL OR PLACEMENT DEVIATIONS FROM MINIMUMS SHOWN ON THE DRAWINGS OR IN SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
4. IN ADDITION TO THE IBC INSPECTION TABLES, THE INSPECTOR SHALL VERIFY THAT ALL STEEL MAINTAIN ERECTION TOLERANCE OF STRUCTURAL STEEL AND ARCHITECTURALLY EXPOSED STRUCTURAL STEEL WITHIN AISC'S CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES.
5. IN ADDITION TO THE CONCRETE AND MASONRY IBC INSPECTION TABLES, THE INSPECTOR SHALL VERIFY THAT ALL CONCRETE AND MASONRY MAINTAIN TOLERANCES SPECIFIED IN ACI 117-90 STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS.
6. TESTING - ALL TEST REPORTS SHALL BE PROVIDED TO THE VA COR. ANY FAILED FIELD TEST SHALL BE REPORTED TO ALBERTSON ENGINEERING INC AND THE VA COR
IMMEDIATELY.
a. WHERE APPLICABLE, SEE SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSEUD BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
WELDING OR REINFORCING BARS.
SPECIAL INSPECTIONS OF WELDING AND QUALIFICATIONS OF SPECIAL INSPECTORS FOR REINFORCING BARS SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF AWS D1.4 FOR
SPECIAL INSPECTION AND AWS D1.4 FOR SPECIAL INSPECTOR QUALIFICATION.
MATERIAL TESTS.
IN THE ABSENCE OF SUFFICIENT DATA OR DOCUMENTATION PROVIDING EVIDENCE OF CONFORMANCE TO QUALITY STANDARDS FOR MATERIALS IN CHAPTERS 19 AND 20 OF ACI 318, THE BUILDING OFFICIAL SHALL REQUIRE TESTING OF MATERIALS IN ACCORDANCE WITH THE APPROPRIATE STANDARDS AND CRITERIA FOR THE MATERIAL IN CHAPTERS 19 AND 20 OF ACI 318.
TMS 602-16 SECTION 1.6A TABLE 3 MINIMUM
VERIFICATION REQUIREMENTS
MINIMUM VERIFICATION
REQUIRED FOR
QUALITY ASSURANCE(a) REFERENCE FOR CRITERIA
LEVEL 1 LEVEL 2 LEVEL 3 TMS 602
PRIOR TO CONSTRUCTION, VERIFICATION OF COMPLIANCE OF SUBMITTALS. R R R ART 1.5
PRIOR TO CONSTRUCTION, VERIFICATION OF F1 m AND F1
AAC, EXCEPT WHERE SPECIFICALLY
EXEMPTED BY THE CODE. NR R R ART 1.4 B
DURING CONSTRUCTION, VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) WHEN SELF-CONSOLIDATING GROUT IS DELIVERED TO THE PROJECT SITE. NR R R ART 1.5 & 1.6.3
NR NR R ART 1.4 BDURING CONSTRUCTION, VERIFICATION OF F1 m AND F1
AAC, FOR EVERY 5,000 SQ. FT. (465 SQ. M).
DURING CONSTRUCTION, VERIFICATION OF PROPORTIONS OF MATERIALS AS DELIVERED TO THE
PROJECT SITE FOR PREMIXED OR PREBLENDED MORTAR, PRESTRESSING GROUT, AND GROUT
OTHER THAN SELF-CONSOLIDATING GROUT.
NR NR R ART 1.4 B
(a) R = REQUIRED, NR = NOT REQUIRED
TMS 602-16 SECTION 1.6A TABLE 4
MINIMUM SPECIAL INSPECTION REQUIREMENTS
INSPECTION TASK
FREQUENCY(a) REFERENCE FOR CRITERIA
LEVEL 1 LEVEL 2 LEVEL 3 TMS 402
1. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE.
A. PROPORTIONS OF SITE-PREPARED MORTAR. NR P P ART. 2.1, 2.6 A &
2.6 C
B. GRADE AND SIZE OF PRESTRESSING TENDONS AND ANCHORAGES. NR
NR
C. GRADE, TYPE AND SIZE OF REINFORCEMENT, CONNECTORS, ANCHOR BOLTS, AND
PRESTRESSING TENDONS AND ANCHORAGES.
D. PRESTRESSING TECHNIQUE NR
(a) FREEQUENCY REFERS TO THE FREQUENCY OF INSPECTIONS, WHICH MAY BE CONTINUOUS DURING LISTED TASK OR PERIODICALLY DURING LISTED TASK, AS DEFINED IN
THE TABLE.
NR = NOT REQUIRED, P = PERIODIC, C = CONTINUOUS
(b) REQUIRED FOR THE FIRST 5,000 SQUARE FEET. (465 SQ METERS) OF AAC MASONRY.
(c) REQUIRED AFTER THE FIRST 5,000 SQUARE FEET. (465 SQ METERS) OF AAC MASONRY.
TMS 602
P P ART. 2.4 B
& 2.4 H
P P ART. 3.4
& 3.6 A
P P ART. 36 B
E. PROPERTIES OF THIN-BED MORTAR FOR AAC MASONRY. NR C(b) P(c) C ART. 2.1 C.1
F. SAMPLE PANEL CONSTRUCTION NR P C ART. 1.6D
2. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE.
A. GROUT SPACE NR P C ART. 3.2 D &
3.2F
B. PLACEMENT OF PRESTRESSING TENDONS AND ANCHORAGES NR P P ART. 2.4
& 3.6
SEC. 10.8 &
10.9
C. PLACEMENT OF REINFORCEMENT, CONNECTORS, AND ANCHOR BOLTS NR P C ART. 3.2 E
& 3.4
SEC. 6.1, 6.3.1,
6.3.6 & 6.3.7
NR
D. PROPORTIONS OF SITE-PREPARED GROUT AND PRESTRESSING GROUT FOR BONDED
TENDONS P P ART. 2.6 B
& 2.4 G.1.B
3. VERIFY COMPLIANCE OF THE FOLLOWING DURING CONSTRUCTION
A. MATERIALS AND PROCEDURES WITH THE APPROVED SUBMITTALS NR P P ART. 1.5
B. PLACEMENT OF MASONRY UNITS AND MORTAR JOINT CONSTRUCTION NR P P ART. 3.3 B
C. SIZE AND LOCATION OF STRUCTURAL MEMBERS NR P P ART. 3.3 F
D. TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING OTHER DETAILS OF ANCHORAGE OF
MASONRY TO STRUCTURAL MEMBERS, FRAMES, OR OTHER CONSTRUCTION NR P C
SEC. 1.2.1(c), 6.2.1 & 6.3.1
E. WELDING OF REINFORCEMENT NR C C SEC. 6.1 & 6.1.2
F. PREPERATION, CONSTRUCTION, AND PROTECTION OF MASONRY DURING COLD WEATHER
(TEMPERATURE BELOW 40°F (4.4°C)) OR HOT WEATHER (TEMPERATURE ABOVE 90°F (32.2°C)) NR P P
ART. 1.8 C &
1.8 D
G. APPLICATION AND MEASUREMENT OF PRESTRESSING FORCE NR C C ART. 3.6 B
NRH. PLACEMENT OF GROUT AND PRESTRESSING GROUT FOR BONDED TENDONS IS IN COMPLIANCE C C
ART. 3.5
& 3.6 C
I. PLACEMENT OF AAC MASONRY UNITS AND CONSTRUCTION OF THIN-BED MORTAR JOINTS NR C(b) P(c) C ART. 3.3 B.9 & 3.3 F.1.B
4. OBSERVE PREPERATION OF GROUT SPECIMENS, MORTAR SPECIMENT, AND/OR PRISMS NR P C ART. 1.4 B.2.a.3,
1.4 B.2.b.3,
1.4 B.2.c.3,
1.4 B.3 & 1.4 B.4
THIS PROJECT SHALL FOLLOW LEVEL 2 VERIFICATION AND
INSPECTION REQUIREMENTS TABLE 1.1 INSPECTION OR EXECUTION TASKS
PRIOR TO DECK PLACEMENT
A. VERIFY COMPLIANCE OF MATERIALS (DECK AND ALL DECK ACCESSORIES) WITH CONSTRUCTION
DOCUMENTS, INCLUDING PROFILES, MATERIAL PROPERTIES, AND BASE METAL THICKNESS
PERFORM
B. DOCUMENT ACCEPTANCE OR REJECTION OF DECK AND DECK ACCESSORIES
TASK QC QA
PERFORM
PERFORMPERFORM
TABLE 1.2 INSPECTION OR EXECUTION TASKS
AFTER DECK PLACEMENT
A. VERIFY COMPLIANCE OF DECK AND ALL DECK ACCESSORIES INSTALLATION WITH
CONSTRUCTION DOCUMENTS
B. VERIFY DECK MATERIALS ARE REPRESENTED BY THE MILL CERTIFICATIONS THAT COMPLY
WITH THE CONSTRUCTION DOCUMENTS
C. DOCUMENT ACCEPTANCE OR REJECTION OF INSTALLATION OF DECK AND DECK
ACCESSORIES
TASK
PERFORM
QC QA
PERFORM
PERFORMN/A
PERFORMPERFORM
TABLE 1.3 INSPECTION OR EXECUTION TASKS
PRIOR TO WELDING
A. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE
B. MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
C. MATERIAL IDENTIFICATION (TYPE/GRADE)
D. CHECK WELDING EQUIPMENT
TASK
OBSERVE
QC QA
OBSERVE
OBSERVEOBSERVE
OBSERVEOBSERVE
OBSERVEOBSERVE
TABLE 1.4 INSPECTION OR EXECUTION
TASKS DURING WELDING
A. USE OF QUALIFIED WELDERS
B. CONTROL AND HANDLING OF WELDING CONSUMABLES
C. ENVIRONMENTAL CONDITIONS (WIND SPEED, MOISTURE, TEMPERATURE)
D. WPS FOLLOWED
TASK
OBSERVE
QC QA
OBSERVE
OBSERVEOBSERVE
OBSERVEOBSERVE
OBSERVEOBSERVE
NOTE:
• QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE INSTALLER
• QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY THE CERTIFIED TESTING AGENCY
TABLE 1.8 INSPECTION OR EXECUTION TASKS AFTER
MECHANICAL FASTENING
INSPECTION TASKS AFTER MECHANICAL FASTENING
A. CHECK SPACING, TYPE, AND INSTALLATION OF SUPPORT FASTENERS
B. CHECK SPACING, TYPE, AND INSTALLATION OF SIDELAP FASTENERS
C. CHECK SPACING, TYPE, AND INSTALLATION OF PERIMETER FASTENERS
D. VERIFY REPAIR ACTIVITIES
E. DOCUMENT ACCEPTANCE OR REJECTION OF MECHANICAL FASTENERS
TABLE 1.5 INSPECTION OR EXECUTION
TASKS AFTER WELDING
A. VERIFY SIZE & LOCATION OF WELDS, INCLUDING SUPPORT, SIDELAP, & PERIMETER WELDS
B. WELDS MEET VISUAL ACCEPTANCE CRITERIA
C. VERIFY REPAIR ACTIVITIES
D. DOCUMENT ACCEPTANCE OR REJECTION OF WELDS
TASK
PERFORM
QC
PERFORM
PERFORMPERFORM
PERFORMPERFORM
PERFORMPERFORM
TABLE 1.6 INSPECTION OR EXECUTION TASKS PRIOR TO
MECHANICAL FASTENING
A. MANUFACTURER INSTALLATION INSTRUCTIONS AVAILABLE FOR MECHANICAL FASTENERS
B. PROPER TOOLS AVAILABLE FOR FASTENER INSTALLATION
C. PROPER STORAGE FOR MECHANICAL FASTENERS
TASK
OBSERVE
QC
OBSERVE
OBSERVEOBSERVE
OBSERVEOBSERVE
TABLE 1.7 INSPECTION OR EXECUTION TASKS DURING
MECHANICAL FASTENING
A. FASTENERS ARE POSITIONED AS REQUIRED OBSERVE
B. FASTENERS ARE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS
INSPECTION TASKS DURING MECHANICAL FASTENING QC
OBSERVE
OBSERVEOBSERVE
PERFORM
QC
PERFORM
PERFORMPERFORM
PERFORMPERFORM
PERFORMPERFORM
PERFORMPERFORM
STANDARD FOR QUALITY CONTROL AND QUALITY ASSURANCE
FOR THE INSTALLATION OF STEEL DECK
MASONRY CONSTRUCTION
QA
QA
QA
QA
IBC 2018 TABLE 1705.3 REQUIRED SPECIAL INSPECTION
AND TESTS OF CONCRETE CONSTRUCTION
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.b
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
A. APPLICATION OF PRESTRESSING FORCES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
ACI 318: CH. 26.9
ACI 318: 26.10
ACI 318: 26.5.3-26.5.5
ACI 318: 26.5
ASTM C172, ASTM C31,
ACI 318: 26.5, 26.12
ACI 318: 17.8.2.4,
ACI 318: 17.8.2
X
X
X
X
X
X
X
ACI 318: 26.11.2
1908.9
1908.6, 1908.7, 1908.8
1908.10
3. INSPECT ANCHORS CAST IN CONCRETE.
2. REINFORCING BAR WELDING:
1. INSPECTION REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT
TYPE
ACI 318 CH 20, 25.2,
25.3, 26.6.1-26.6.3
REFERENCED
STANDARDa
CONTINUOUS
SPECIAL
INSPECTION
X
AWS D1.4,
ACI 318: 26.6.4
IBC REFERENCE
1908.4
X
ACI 318: 17.8.2
5. VERIFY USE OF REQUIRED DESIGN MIX.
ACI 318: CH. 19,
26.4.3, 26.4.4
X
1904.1, 1904.2, 1908.2, 1908.3
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING FORMED. ACI 318: 26.11.1.2(b)X
9. INSPECT OF PRESTRESSED CONCRETE FOR:
B. GROUTING OF BONDED PRESTRESSING TENDONS.
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF
SHORES ANDFORMS FROM BEAMS AND STRUCTURAL SLABS.
X
A. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706.
X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16".
C. INSPECT ALL OTHER WELDS
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLLY INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT
DEFINED IN 4A.
X
X
X
PERIODIC
SPECIAL
INSPECTION
REQUIRED ON
PROJECT
YES
NO
YES
YES
YES
YES
YES
NO
NO
NO
YES
YES
NO
1. IF PROFESSIONAL DESIGN SERVICES OR CERTIFICATIONS BY A DESIGN
PROFESSIONAL RELATED TO SYSTEMS, MATERIALS, OR EQUIPMENT ARE
SPECIFICALLY REQUIRED OF THE CONTRACTOR BY THE CONTRACT DOCUMENTS;
THE ARCHITECT AND/OR ALBERTSON ENGINEERING, INC. WILL SPECIFY THE
PERFORMANCE AND DESIGN CRITERIA THAT SUCH SERVICES MUST SATISFY WITHIN
THE CONTRACT DOCUMENTS.
2. THE CONTRACTOR SHALL BE ENTITLED TO RELY UPON THE ADEQUACY AND
ACCURACY OF THE PERFORMANCE AND DESIGN CRITERIA PROVIDED IN THE
CONTRACT DOCUMENTS. THE CONTRACTOR SHALL CAUSE SUCH SERVICES OR
CERTIFICATIONS TO BE PROVIDED BY AN APPROPRIATELY…