Attachment 7 - Seed Project Drawings.pdf
PDF 12 MB Posted
- Attached to
- Mechanical Electrical Plumbing (MEP) MATOC Federal contract opportunity
- Solicitation number
- 12805B24R0004
About this file
This document appears to be Attachment 7 - Seed Project Drawings related to Solicitation Number 12805B24R0004 for a Mechanical Electrical Plumbing (MEP) Multiple Award Task Order Contract (MATOC) issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area.
The drawings appear to include site plans, floor plans, and elevations for a "Seed Project" facility. The drawings provide detailed specifications and dimensions for the building's mechanical, electrical, and plumbing systems. No other details about the specific services or contract requirements are included in this attachment. This appears to be a technical drawing document that would be used to support responses to the overall solicitation for the MEP MATOC contract.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST
SHEET NO. DRAWING NO. TITLE
T-101 1 OF 35 TITLE SHEET
M-001 2 OF 35 HVAC GENERAL NOTES, LEGEND, & ABBREVIATIONS
MD101 3 OF 35 PHASE 1 HVAC DEMOLITION PLAN
MD102 4 OF 35 PHASE 2 HVAC DEMOLITION PLAN
MD103 5 OF 35 PHASE 3 HVAC DEMOLITION PLAN
MD104 6 OF 35 PHASE 4 HVAC DEMOLITION PLAN
M-101 7 OF 35 PHASE 1 HVAC PLAN
M-102 8 OF 35 PHASE 2 HVAC PLAN
M-103 9 OF 35 PHASE 3 HVAC PLAN
M-104 10 OF 35 PHASE 4 HVAC PLAN
M-501 11 OF 35 HVAC DETAILS
M-502 12 OF 35 HVAC DETAILS
M-503 13 OF 35 HVAC DETAILS
M-504 14 OF 35 HVAC DETAILS PHASE 1 WIRING AND PIPING
M-505 15 OF 35 HVAC DETAILS PHASE 2 WIRING AND PIPING
M-506 16 OF 35 HVAC DETAILS PHASE 3 WIRING AND PIPING
M-507 17 OF 35 HVAC DETAILS PHASE 4 WIRING AND PIPING 1 OF 2
M-508 18 OF 35 HVAC DETAILS PHASE 4 WIRING AND PIPING 2 OF 2
M-601 19 OF 35 HVAC EQUIPMENT SCHEDULES
M-602 20 OF 35 HVAC EQUIPMENT SCHEDULES
M-701 21 OF 35 HVAC CONTROLS
MP101 22 OF 35 PHASE 1 CONDENSATE PIPING PLAN
MP102 23 OF 35 PHASE 2 CONDENSATE PIPING PLAN
MP103 24 OF 35 PHASE 3 CONDENSATE PIPING PLAN
MP104 25 OF 35 PHASE 4 CONDENSATE PIPING PLAN
E-001 26 OF 35 ELECTRICAL LEGEND AND GENERAL NOTES
ED101 27 OF 35 FIRST FLOOR ELECTRICAL PLAN: DEMO
ED102 28 OF 35 SECOND FLOOR ELECTRICAL PLAN: DEMO
ED103 29 OF 35 THIRD FLOOR ELECTRICAL PLAN: DEMO
E-101 30 OF 35 SECOND AND THIRD FLOOR ELECTRICAL PLAN
E-102 31 OF 35 SECOND AND THIRD FLOOR ELECTRICAL PLAN
E-103 32 OF 35 SECOND AND THIRD FLOOR ELECTRICAL PLAN
E-104 33 OF 35 SECOND AND THIRD FLOOR ELECTRICAL PLAN
E-501 34 OF 35 ELECTRICAL DETAILS
E-601 35 OF 35 ELECTRICAL SCHEDULES
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
T-
1.
dw g M ay
3,
- 9 :3
1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
LAS CRUCES BUILDING 48 HVAC DESIGN
A-E CONTRACT NO: 12805B23D0001
A-E TASK ORDER NO: 12805B23F0148
SOUTHWESTERN COTTON GIN RESEARCH LABORATORY
LAS CRUCES, NM
PROJECT LOCATION
GENERAL NOTES:
1. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS
PRIOR TO PERFORMING WORK OR FABRICATION OR PURCHASE OF EQUIPMENT,
MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. THE FACILITY WILL REMAIN IN OPERATION DURING ALL PHASES OF CONSTRUCTION. ALL
MEANS OF EGRESS MUST REMAIN FREE AND CLEAR.
3. COORDINATE CONSTRUCTION ACCESS AND STAGING AREA(S) WITH CONTRACTING
OFFICER PRIOR TO COMMENCING WORK.
PRE-FINAL DESIGN SUBMITTAL
PROJECT LOCATION
TITLE SHEET
T-101
JND
JGM
PHASING:
1. THE CONTRACTOR SHALL COORDINATE ALL PHASES WITH THE CONTRACTING OFFICER.
2. THE CONTRACTOR SHALL PROVIDE A SEPARATE PRICE FOR EACH PHASE AS SPECIFIED IN THE BID DOCUMENTS PROVIDED BY USDA.
3. PHASES SHALL BE CONTRACTED SEPARATELY OR MULTIPLE PHASES MAY BE COMBINED IN ONE CONTRACT. (SEE BID DOCUMENT).
4. THE PHASE NUMBERS DO NOT NECESSARILY REPRESENT THE ORDER IN WHICH THE PHASES SHALL BE AWARDED AND EXECUTED.
5. EACH PHASE SHALL BE A COMPLETE AND USEABLE SYSTEM THAT IS NOT DEPENDENT ON ANY OTHER PHASES TO BE PERFORMED.
6. THE CONTRACTOR SHALL PROVIDE A DETAILED PHASE PLAN AND A MILESTONE CONSTRUCTION SCHEDULE FOR APPROVAL PRIOR TO THE START OF
CONSTRUCTION.
7. PHASES THAT ARE SHOWN AND DESCRIBED IN THESE DOCUMENTS CAN NOT BE SCHEDULED CONCURRENTLY IN ORDER TO MEET THE MILESTONE DATES
IN THE CONTRACT CONSTRUCTION SCHEDULE. THE GOVERNMENT WILL VACATE ONE PHASE WORK AREA AT A TIME. THE CONTRACTOR WILL PROVIDE A MINIMUM TWO WEEK WORK HIATUS IN BETWEEN EACH PHASE TO ALLOW THE GOVERNMENT ACCESS TO THE COMPLETED PHASE AND TO VACATE THE
NEXT PHASE. COORDINATE WITH THE COR.
LOCATION MAP VICINITY MAP
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M -0
.d w g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
GENERAL DEMOLITION NOTES GENERAL NOTES
1. THIS PROJECT IS A RENOVATION OF AN EXISTING OCCUPIED FACILITY. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION
OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICERS ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. ALL WORK SHALL BE PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE OPERATION OF
THE FACILITY.
3. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL
POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR SHALL PROVIDE
A COMPLETE AND FUNCTIONAL HEATING, VENTILATING, AND AIR CONDITIONING SYSTEM
(HVAC) AS INDICATED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS
AS INDICATED.
4. REMOVE CONNECTING UTILITIES (WATER, DRAINAGE, POWER, GAS, ETC.) AS INDICATED OR
NECESSARY FOR FUTURE RECONNECTION IF REQUIRED.
5. CONTRACTOR SHALL EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN
NECESSARY SKILLS TO PERFORM DEMOLITION WORK.
6. CONTRACTOR SHALL USE APPROPRIATE TOOLS AND SHALL NOT IMPART EXCESSIVE
VIBRATIONS TO THE EXISTING STRUCTURE OR OTHER BUILDING COMPONENTS.
7. COORDINATE DUCTWORK AND PIPING WITH EXISTING STRUCTURAL, ELECTRICAL, PLUMBING, AND COMMUNICATION. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER
TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. CONTRACTOR SHALL PROVIDE
COORDINATION DRAWINGS OF TRADES.
8. ALL DUCTWORK SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS UNLESS OTHERWISE NOTED.
9. PROVIDE THERMOSTATS WHERE SHOWN ON THE DRAWINGS. MOUNT DEVICE AT 4'-6" ABOVE
THE FINISHED FLOOR UNLESS OTHERWISE NOTED.
10. PRESSURE TEST REFRIGERANT PIPING TO A MINIMUM OF 450 PSIG WITH NO LOSS IN
PRESSURE FOR A PERIOD OF 24 HOURS. RECORD TEMPERATURE BEFORE AND AFTER TEST.
A 0.3 PSI DECREASE IN PRESSURE IS ALLOWED FOR EACH DECREASE IN °F. EVACUATE LINES
TO ABSOLUTE PRESSURE OF 300 MICROMETERS FOR ONE HOUR WITHOUT INCREASE IN
PRESSURE. CHARGE SYSTEM. COMPLY WITH HVAC SYSTEM AND REFRIGERANT
MANUFACTURER'S CHARGING INSTRUCTIONS.
11. ALL NEW REFRIGERANT PIPING SHALL BE INSULATED COMPLETELY.
12. ALL NEW AND DEMOLISHED PENETRATIONS SHALL BE FULLY SEALED WATERTIGHT.
13. PROVIDE CONCRETE PADS FOR ALL GROUND MOUNTED CONDENSING UNITS PER DETAILS.
14. PROVIDE COMPOSITE ROOF RAILS FOR ROOF MOUNTED CONDENSING UNITS PER DETAILS.
15. CONTRACTOR SHALL PROVIDE SEALANTS AT ALL BUILDING PENETRATIONS. ALL
PENETRATIONS SHALL BE SEALED WEATHER TIGHT AFTER WORK IS COMPLETE.
16. CONTRACTOR SHALL REPAIR ALL EXISTING CONSTRUCTION (INTERIOR AND EXTERIOR) THAT
IS DAMAGED AS A RESULT OF THE WORK. ALL SURFACES SHALL BE CLEAN, FINISHED AND
PAINTED TO MATCH THE EXISTING COLORS AND FINISHES.
17. BASIS OF DESIGN MANUFACTURERS ARE SHOWN TO ESTABLISH A STANDARD OF QUALITY,
NOT TO LIMIT COMPETITION. EQUIVALENT PRODUCTS FROM OTHER MANUFACTURERS SHALL
BE ACCEPTABLE PROVIDED THEY MEET THE SPECIFICATIONS AND PERFORMANCE
REQUIREMENTS. PRODUCTS SHALL COMPLY WITH "BUY AMERICAN ACT".
18. COORDINATE SUPPLY OF ELECTRICAL DISCONNECT SWITCHES BETWEEN TRADES AS
REQUIRED.
ACCU AIR COOLED CONDENSING UNIT
AD ACCESS DOOR
A.F.F. ABOVE FINISHED FLOOR
A.F.G. ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AP ACCESS PANEL
APPROX. APPROXIMATE
ARCH ARCHITECTURAL
CD CEILING DIFFUSER
CL CENTER LINE
C.O. CLEAN OUT
C.V. CHECK VALVE
CFM CUBIC FEET PER MINUTE
CLG CEILING
CONC. CONCRETE
CONT. CONTINUATION
CP CONDENSER WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CWP CHILLED WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
CT COOLING TOWER
CTE CONNECT TO EXISTING
CU CONDENSING UNIT
dB DECIBELS
DIFF. DIFFUSER
DN. DOWN
DET. DETAIL
DIA. DIAMETER
DIM. DIMENSION
DWG. DRAWING
EA. EACH
E/A EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EWT ENTERING WATER TEMPERATURE
ECC ECCENTRIC
EFF EFFICIENCY
ELEC. ELECTRICAL
ELEV. ELEVATION
ET EXPANSION TANK
F FAHRENHEIT
FLR FLOOR
FDC FIRE DEPARTMENT CONNECTION
F/SD FIRE/SMOKE DAMPER
FPM FEET PER MINUTE
FCO FLOOR CLEAN OUT
FCU FAN COIL UNIT
UH UNIT HEATER
ABBREVIATIONS
COMMON TERMS
FT. FOOT
FIN. FINISHED
G NATURAL GAS PIPING
GA. GAUGE
GAL. GALLONS
GALV. GALVANIZED
GEN. GENERAL
G.P.H. GALLONS PER HOUR
G.P.M. GALLONS PER MINUTE
HR. HOUR
I.D. INSIDE DIMENSION
IN INCHES
K.W. KILOWATT
L LOUVER
LB POUND
LD LINEAR DIFFUSER
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAU MAKEUP AIR UNIT
MAX. MAXIMUM
MFR. MANUFACTURER
MECH. MECHANICAL
MIN. MINIMUM OR MINUTE
NC NORMALLY CLOSED
NO NORMALLY OPENED
NPT NATIONAL PIPE THREAD
Ø DIAMETER
O/A OUTSIDE AIR
O.D. OUTSIDE DIMENSION
PH PHASE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
R/A RETURN AIR
RAD RADIUS
RAR RETURN AIR REGISTER
RED. REDUCER
REINF. REINFORCING
REQ'D. REQUIRED
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
S/A SUPPLY AIR
SAG SUPPLY AIR GRILLE
SD SMOKE DETECTOR
SEN SENSIBLE
SF SQUARE FEET
SQ. SQUARE
TA TRANSFER AIR
TEMP TEMPERATURE
TH THERMOMETER
TYP. TYPICAL
U.N.P. UNLESS NOTED OTHERWISE
UC UNIT COOLER
UH UNIT HEATER
VA VALVE
VAV VARIABLE AIR VOLUME (BOX)
V VOLTS
VRV VARIABLE REFRIGERANT VOLUME
W/ WITH
WT WEIGHT
COMMON TERMS
(2) E1
1430 CFM
DESIGN AIRFLOW RATE
GRD MARK (REFER TO
GRD SCHEDULE)
QUANTITY
FORMAT FOR CALLING OUT GRILLES REGISTERS AND DIFFUSERS (GRD)
DM
JGM M-001
HVAC GENERAL NOTES,
LEGEND & ABBREVIATIONS
1. THE DEMOLITION PLANS AND EXISTING CONDITIONS ARE APPROXIMATE. ITEMS TO BE REMOVED ARE DESIGNATED BY HATCHING AND/OR DASHED LINES AND/OR KEY NOTES. OTHER ITEMS ARE INTENDED
TO REMAIN IN PLACE UNLESS NOTED OTHERWISE.
2. THE BUILDING IS KNOWN TO CONTAIN ASBESTOS CONTAINING MATERIALS AND LEAD BASED PAINTS.
A REPORT DETAILING THE LOCATIONS OF ACM AND LBP IS INCLUDED IN THE SPECIFICATIONS.
HANDLE AND DISPOSE OF ALL HAZARDOUS MATERIALS PER THE SPECIFICATIONS AND IN
ACCORDANCE WITH ALL STATUTES.
STAIRS UP
OFFICE
STAIRS UP
ST1
OFFICE OFFICE
FILE
ROOM
OFFICE
CONFERENCE
ROOM
OFFICE
STAIRS DOWN
OPEN SHAFT
FROM FIRST
FLOOR H200
EL2
EL1
OFFICE
OFFICE
RESTROOMS
ST1
STAIRS UP
OFFICE
STORAGE
H300
OFFICE
OFFICE
LAB
310 306
OUTSIDE
ROOF
AREA
STORAGE OFFICE
OUTSIDE
ROOF
AREA
307STORAGE
OFFICE
EL1
OFFICE
CONFERENCE
ROOM
ST2
T
T
T
T
T
T
OUTSIDE
ROOF
AREA
OUTSIDE
ROOF
AREA
T
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M D
1.
dw g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
PLAN
NORTH
SCALE:
SECOND FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD101
1. DISMANTLE AND REMOVE ALL EXISTING
WALL MOUNTED THERMOSTAT.
2. DISMANTLE AND REMOVE EXISTING
PACKAGED UNIT, DUCTWORK, CONTROLS,
AND ALL APPURTENANCES. EXISTING
ROOF CURB IS TO REMAIN. ROOF CURB
TO BE COVERED PER DETAIL 3/M-503.
DM
JGM MD101
PHASE 1 HVAC DEMOLITION PLAN
PLAN
NORTH
SCALE:
THIRD FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD101
PHASE 2
PHASE 4
PHASE 1
PHASE 3
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
1. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND BRING ANY
DISCREPANCIES TO THE ATTENTION OF THE
CONTRACTING OFFICER
2. REMOVE AND STORE ALL SUSPENDED
CEILING TILES AND ACCESSORIES TO
PERFORM HVAC WORK. PROTECT TILES
FROM DAMAGE AND REINSTALL AFTER
OTHER WORK IS COMPLETED. DAMAGED
TILES AND ACCESSORIES ARE TO BE
REPLACED WITH NEW MATCHING
COMPONENTS.
3. LIGHT FIXTURES AND OTHER ITEMS
MOUNTED INTO OR ON THE SUSPENDED
CEILING SYSTEM SHALL BE TEMPORARILY
SUPPORTED AND REINSTALLED IN THE
CEILING SYSTEM AFTER OTHER WORK HAS
BEEN COMPLETED.
OFFICE
STAIRS UP
ST1
OFFICE OFFICE
FILE
ROOM
OFFICE
CONFERENCE
ROOM
OFFICE
STAIRS DOWN
OPEN SHAFT
FROM FIRST
FLOOR H200
EL2
EL1
OFFICE
OFFICE
RESTROOMS
ST1
STAIRS UP
OFFICE
STORAGE
H300
OFFICE
OFFICE
LAB
310 306
OUTSIDE
ROOF
AREA
STORAGE OFFICE
OUTSIDE
ROOF
AREA
307STORAGE
OFFICE
EL1
OFFICE
CONFERENCE
ROOM
ST2
T
T
T
T
T
T
OUTSIDE
ROOF
AREA
OUTSIDE
ROOF
AREA
T
DM
JGM MD102
PHASE 2 HVAC DEMOLITION PLAN
PLAN
NORTH
SCALE:
THIRD FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD102
2 1
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M D
1.
dw g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
PLAN
NORTH
SCALE:
SECOND FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD102
EXISTING 10 TON
CONDENSING UNIT.
(ON GROUND)
PHASE 2
PHASE 4
PHASE 3
PHASE 1
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
1. DISMANTLE AND REMOVE EXISTING
FURNACE, DUCTWORK, PIPING,
CONTROLS, AND ALL APPURTENANCES.
2. DISMANTLE AND REMOVE EXISTING
COOLING COIL, DUCTWORK, PIPING,
CONTROLS, AND ALL APPURTENANCES.
3. DISMANTLE AND REMOVE EXISTING
CONDENSING UNIT, CONCRETE SUPPORT,
REFRIGERANT PIPING, AND ALL
APPURTENANCES.
4. DISMANTLE AND REMOVE ALL EXISTING
WALL MOUNTED THERMOSTAT.
1. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND BRING ANY
DISCREPANCIES TO THE ATTENTION OF THE
CONTRACTING OFFICER
2. REMOVE AND STORE ALL SUSPENDED
CEILING TILES AND ACCESSORIES TO
PERFORM HVAC WORK. PROTECT TILES
FROM DAMAGE AND REINSTALL AFTER
OTHER WORK IS COMPLETED. DAMAGED
TILES AND ACCESSORIES ARE TO BE
REPLACED WITH NEW MATCHING
COMPONENTS.
3. LIGHT FIXTURES AND OTHER ITEMS
MOUNTED INTO OR ON THE SUSPENDED
CEILING SYSTEM SHALL BE TEMPORARILY
SUPPORTED AND REINSTALLED IN THE
OFFICE
STAIRS UP
ST1
OFFICE OFFICE
FILE
ROOM
OFFICE
CONFERENCE
ROOM
OFFICE
STAIRS DOWN
OPEN SHAFT
FROM FIRST
FLOOR H200
EL2
EL1
OFFICE
OFFICE
RESTROOMS
ST1
STAIRS UP
OFFICE
STORAGE
H300
OFFICE
OFFICE
LAB
310 306
OUTSIDE
ROOF
AREA
STORAGE OFFICE
OUTSIDE
ROOF
AREA
307STORAGE
OFFICE
EL1
OFFICE
CONFERENCE
ROOM
ST2
T
T
T
T
T
T
OUTSIDE
ROOF
AREA
OUTSIDE
ROOF
AREA
T
DM
JGM MD103
PHASE 3 HVAC DEMOLITION PLAN
PLAN
NORTH
SCALE:
THIRD FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD103
2 3
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M D
1.
dw g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
PLAN
NORTH
SCALE:
SECOND FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD103
C/U # 1
PHASE 2
PHASE 4
PHASE 3
PHASE 1
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
1. DISMANTLE AND REMOVE ALL EXISTING
WALL MOUNTED THERMOSTATS.
2. DISMANTLE AND REMOVE EXISTING
FURNACE, DUCTWORK, PIPING,
CONTROLS, AND ALL APPURTENANCES.
3. DISMANTLE AND REMOVE EXISTING
COOLING COIL, DUCTWORK, PIPING,
CONTROLS, AND ALL APPURTENANCES.
4. DISMANTLE AND REMOVE EXISTING
OUTDOOR AIR INTAKE AND ASSOCIATED
DUCTWORK. SEAL EXISTING OPENING
WATER TIGHT.
5. DISMANTLE AND REMOVE EXISTING
CONDENSING UNIT, REMOVE EXISTING
CONCRETE SUPPORT TILE, REFRIGERANT
PIPING, AND ALL APPURTENANCES.
1. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND BRING ANY
DISCREPANCIES TO THE ATTENTION OF THE
CONTRACTING OFFICER
2. REMOVE AND STORE ALL SUSPENDED
CEILING TILES AND ACCESSORIES TO
PERFORM HVAC WORK. PROTECT TILES
FROM DAMAGE AND REINSTALL AFTER
OTHER WORK IS COMPLETED. DAMAGED
TILES AND ACCESSORIES ARE TO BE
REPLACED WITH NEW MATCHING
COMPONENTS.
3. LIGHT FIXTURES AND OTHER ITEMS
MOUNTED INTO OR ON THE SUSPENDED
CEILING SYSTEM SHALL BE TEMPORARILY
SUPPORTED AND REINSTALLED IN THE
OFFICE
STAIRS UP
ST1
OFFICE OFFICE
FILE
ROOM
OFFICE
CONFERENCE
ROOM
OFFICE
STAIRS DOWN
OPEN SHAFT
FROM FIRST
FLOOR H200
EL2
EL1
OFFICE
OFFICE
RESTROOMS
ST1
STAIRS UP
OFFICE
STORAGE
H300
OFFICE
OFFICE
LAB
310 306
OUTSIDE
ROOF
AREA
STORAGE OFFICE
OUTSIDE
ROOF
AREA
307STORAGE
OFFICE
EL1
OFFICE
CONFERENCE
ROOM
ST2
T
T
T
T
T
T
OUTSIDE
ROOF
AREA
OUTSIDE
ROOF
AREA
T
DM
JGM MD104
PHASE 4 HVAC DEMOLITION PLAN
PLAN
NORTH
SCALE:
THIRD FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD104
UNIT REMOVED AND CAPPED IN
PHASE 1. REFERENCE MD101.
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M D
1.
dw g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
PLAN
NORTH
SCALE:
SECOND FLOOR
HVAC DEMOLITION PLAN
1/8"=1'-0"
MD104
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
PHASE 2PHASE 2
PHASE 4
PHASE 3
PHASE 1
EXISTING FAN TO
BE DEMOLISHED
C/U # 2
C/U # 3
C/U # 4
EXISTING
EXHAUST
SYSTEM TO
REMAIN
1. DISMANTLE AND REMOVE ALL EXISTING
WALL MOUNTED THERMOSTATS.
2. DISMANTLE AND REMOVE EXISTING
FURNACE, DUCTWORK, PIPING,
CONTROLS, AND ALL APPURTENANCES.
3. DISMANTLE AND REMOVE EXISTING
COOLING COIL, DUCTWORK, PIPING,
CONTROLS, AND ALL APPURTENANCES.
4. DISMANTLE AND REMOVE EXISTING
OUTDOOR AIR INTAKE AND ASSOCIATED
DUCTWORK. SEAL EXISTING OPENING
WATER TIGHT.
5. EXISTING EXHAUST FAN, DUCTWORK, AND
ALL APPURTENANCES TO REMAIN.
6. DISMANTLE AND REMOVE EXISTING
CONDENSING UNIT, REMOVE EXISTING
CONCRETE SUPPORT TILE, REFRIGERANT
PIPING, AND ALL APPURTENANCES.
UNIT REMOVED AND CAPPED IN
PHASE 1. REFERENCE MD101.
1. CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND BRING ANY
DISCREPANCIES TO THE ATTENTION OF THE
CONTRACTING OFFICER
2. REMOVE AND STORE ALL SUSPENDED
CEILING TILES AND ACCESSORIES TO
PERFORM HVAC WORK. PROTECT TILES
FROM DAMAGE AND REINSTALL AFTER
OTHER WORK IS COMPLETED. DAMAGED
TILES AND ACCESSORIES ARE TO BE
REPLACED WITH NEW MATCHING
COMPONENTS.
3. LIGHT FIXTURES AND OTHER ITEMS
MOUNTED INTO OR ON THE SUSPENDED
CEILING SYSTEM SHALL BE TEMPORARILY
SUPPORTED AND REINSTALLED IN THE
UP
DN
UP
UP
UP
UP
DN
DN DN
STORAGE
OFFICE
OFFICE
FILE ROOM
OFFICE
ST1
STAIR
BREAK ROOM
OFFICE
OFFICE
OFFICE
EL1
ELEVATOR
MEZZANINE
CONFERENCE ROOM
EL2
OPEN SHAFT
EL1
ELEVATOR
WOMENST1
STAIR
ST2
STAIR
ST2
STAIR
MEN
LAB
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE ROOM
STORAGE
STORAGE
OFFICE
STORAGE
OFFICE
H300
HALLWAY
14Ø 12Ø12x12 x1
14Ø 12Ø
8Ø
8Ø8x
8x8 8x8
14Ø 12Ø x1
8Ø 6Ø
8x8
8x
8x
8x
8x8
8x
8Ø
8Ø 8Ø
8x
6x
8x8 8x8 8x8
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Ø
8Ø
6x6
6x6
6Ø
6Ø
6Ø
6Ø 6Ø
6Ø
T
6Ø
6Ø
6Ø 6Ø
PLAN
NORTH
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M -1
.d w g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
SCALE:
SECOND FLOOR HVAC PLAN
1/8"=1'-0"
M-101
PLAN
NORTH
SCALE:
THIRD FLOOR HVAC PLAN
1/8"=1'-0"
M-101
CU-1
(ON GROUND)
EAG1
20 CFM
SAD1
20 CFM
EAG1
60 CFM
ERV-1
SAD1
60 CFM
EAG1
20 CFM
EAG1
35 CFM
EAG1
30 CFM
SAD1
20 CFM
L-1
L-2
DM
JGM M-101
PHASE 1 HVAC PLAN
IDU-1-1
IDU-1-2
IDU-1-3
IDU-1-4
IDU-1-5
IDU-1-6
IDU-1-7
PHASE 2
PHASE 4
PHASE 3
PHASE 1
1. INSTALL AIR COOLED CONDENSING UNIT ON
CONCRETE EQUIPMENT PAD PER DETAIL 1/M-502.
2. CAP ROOF CURB PER DETAIL 3/M-503.2
35 CFM
OA
35 CFM
OA
UP
UP
UP
UP
DN
DN DN
STORAGE
OFFICE
OFFICE
FILE ROOM
OFFICE
ST1
STAIR
BREAK ROOM
OFFICE
OFFICE
OFFICE
EL1
ELEVATOR
MEZZANINE
CONFERENCE ROOM
EL2
OPEN SHAFT
EL1
ELEVATOR
WOMENST1
STAIR
ST2
STAIR
ST2
STAIR
MEN
LAB
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE ROOM
STORAGE
STORAGE
OFFICE
STORAGE
OFFICE
H300
HALLWAY
14Ø 12Ø12x12 x1
14Ø 12Ø
8Ø
8Ø8x
8x8 8x8
14Ø 12Ø x1
8Ø 6Ø
8x8
8x
8x
8x
8x8
8x
8Ø
8Ø 8Ø
8x
6x
8x8 8x8 8x8
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Ø
8Ø
6x6
6x6
6Ø
6Ø
6Ø
6Ø 6Ø
6Ø
T
6Ø
6Ø
6Ø 6Ø
1. INSTALL AIR COOLED CONDENSING UNIT ON
CONCRETE EQUIPMENT PAD PER DETAIL 1/M-502.
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
SCALE:
SECOND FLOOR HVAC PLAN
1/8"=1'-0"
M-102
PLAN
NORTH
SCALE:
THIRD FLOOR HVAC PLAN
1/8"=1'-0"
M-102
CU-2
ERV-2 EAG1
50 CFM
EAG1
20 CFM
EAG1
20 CFM
EAG1
20 CFM
EAG1
20 CFM
SAD2
200 CFM
SAD2
200 CFM
SAD2
200 CFM
SAD2
200 CFM
L-4
L-3
DM
JGM M-102
PHASE 2 HVAC PLAN
IDU-2-1
IDU-2-2
IDU-2-3
IDU-2-4
IDU-2-5
IDU-1-1
PHASE 2
PHASE 4
PHASE 3
PHASE 1
PLAN
NORTH
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M -1
.d w g
M ay
3,
- 9
:3 1a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
6"Ø, 50 CFM OA 6"Ø, 20 CFM OA
6"Ø, 20 CFM OA
6"Ø, 20 CFM OA
8"Ø, 150
CFM OA
VOLUME DAMPER
(TYPICAL)
UP
UP
UP
UP
DN
DN DN
STORAGE
OFFICE
OFFICE
FILE ROOM
OFFICE
ST1
STAIR
BREAK ROOM
OFFICE
OFFICE
OFFICE
EL1
ELEVATOR
MEZZANINE
CONFERENCE ROOM
EL2
OPEN SHAFT
EL1
ELEVATOR
WOMENST1
STAIR
ST2
STAIR
ST2
STAIR
MEN
LAB
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE ROOM
STORAGE
STORAGE
OFFICE
STORAGE
OFFICE
H300
HALLWAY
14Ø 12Ø12x12 x1
14Ø 12Ø
8Ø
8Ø8x
8x8 8x8
14Ø 12Ø x1
8Ø 6Ø
8x8
8x
8x
8x
8x8
8x
8Ø
8Ø 8Ø
8x
6x
8x8 8x8 8x8
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Ø
8Ø
6x6
6x6
6Ø
6Ø
6Ø
6Ø 6Ø
6Ø
T
6Ø
6Ø
6Ø 6Ø
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
SCALE:
SECOND FLOOR HVAC PLAN
1/8"=1'-0"
M-103
PLAN
NORTH
SCALE:
THIRD FLOOR HVAC PLAN
1/8"=1'-0"
M-103
CU-3 1
SAD2
185 CFM
SAD2
185 CFM
SAD2
185 CFM
SAD2
185 CFM
SAD2
185 CFM
SAD2
185 CFM
SAD2
185 CFM
SAD2
185 CFM
SAD3
220 CFM
RAG1
740 CFM
EAG2
150 CFM EAG1
740 CFM
L-7L-8
DM
JGM M-103
PHASE 3 HVAC PLAN
IDU-3-1
IDU-3-2
ERV-3
PHASE 2
PHASE 4
PHASE 3
PHASE 1
PLAN
NORTH
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M -1
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
1. INSTALL AIR COOLED CONDENSING UNIT ON
COMPOSITE ROOF RAILS PER DETAIL 2/M-502.
UP
UP
UP
UP
DN
DN DN
STORAGE
OFFICE
OFFICE
FILE ROOM
OFFICE
ST1
STAIR
BREAK ROOM
OFFICE
OFFICE
OFFICE
EL1
ELEVATOR
MEZZANINE
CONFERENCE ROOM
EL2
OPEN SHAFT
EL1
ELEVATOR
WOMENST1
STAIR
ST2
STAIR
ST2
STAIR
MEN
LAB
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE ROOM
STORAGE
STORAGE
OFFICE
STORAGE
OFFICE
H300
HALLWAY
14Ø 12Ø12x12 x1
14Ø 12Ø
8Ø
8Ø8x
8x8 8x8
14Ø 12Ø x1
8Ø 6Ø
8x8
8x
8x
8x
8x8
8x
8Ø
8Ø 8Ø
8x
6x
8x8 8x8 8x8
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Ø
8Ø
6x6
6x6
6Ø
6Ø
6Ø
6Ø 6Ø
6Ø
T
6Ø
6Ø
6Ø 6Ø
0 16'8'4' 24'
SCALE: 1/8"= 1'-0"
SCALE:
SECOND FLOOR HVAC PLAN
1/8"=1'-0"
M-104
PLAN
NORTH
SCALE:
THIRD FLOOR HVAC PLAN
1/8"=1'-0"
M-104
CU-4B1
CU-4A 1
ERV-4
EAG2
150 CFM
EAG2
150 CFM
20 CFM OA
20 CFM OA
SAD1
30 CFM
L-6L-5
DM
JGM M-104
PHASE 4 HVAC PLAN
IDU-4A-1
IDU-4A-2
IDU-4A-3
IDU-4A-4
IDU-4A-8
IDU-4A-7
IDU-4A-6
IDU-4A-5
IDU-4B-6
IDU-4B-3
IDU-4B-1
IDU-4B-5
IDU-4B-2
IDU-4B-4
PHASE 2
PHASE 4
PHASE 3
PHASE 1
PLAN
NORTH
PPM
REVISIONS
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
C :\U se rs
\tl ov el ac e.
JM
C
FI
R M
\A pp
D at a\ Lo ca l\T em p\
Ac Pu bl is h_
0\
M -1
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
1. INSTALL AIR COOLED CONDENSING UNIT ON
COMPOSITE ROOF RAILS PER DETAIL 2/M-502.
20 CFM OA
20 CFM OA
20 CFM OA
20 CFM OA
20 CFM OA
20 CFM OA
10 CFM OA
10 CFM OA
VOLUME DAMPER
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
MIN
MIN
3.5"
2" MIN
6.5"
DRAIN PAN
UNION
PITCH DOWN TOWARD FLOOR
DRAIN. SPILL AT FLOOR DRAIN.
UNION FOR DRAINING
CLEAN OUT
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE
DRAIN PAN. SEE PLANS FOR SIZES.
PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE
UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL
BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT
AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET
DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE
CEILINGS.
TRUNK
DUCT
OVAL BRANCH
DUCT
45° CLINCH COLLAR PER SMACNA
USE AT ALL BRANCH TAPS
UNLESS
SPLITTER DAMPERS ARE
INDICATED.
BELL-MOUTH
FITTING
NOTE:
DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, RETURN AIR
AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.
LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.
ROUND
DUCT
TURNING VANES, TYPICAL
TURNS 45° OR LARGER
RUNNER
INSTALL VANES
TANGENT TO
AIRSTREAM
DOUBLE SIDED TURNING
VANES REQUIRED WHERE
DUCT HEIGHT IS 24" OR
GREATER.
TOP RUNNER NOT SHOWN FOR
CLARITY.
NUMBER AND CONFIGURATION OF
VANES PER SMACNA STANDARDS.
DUCT HANGERS, ATTACH TO THE
STRUCTURE ABV.
DUCT MAIN WITH
EXTERNAL INSULATION
CEILING DIFFUSER
DUCT HANGERS, ATTACH TO THE STRUCTURE ABV.
DUCT MAIN WITH EXTERNAL INSULATION
CEILING DIFFUSER
AREAS WITH
HARD OR LAY
IN CEILINGS
AREAS ABOVE
CEILING (TYP.)
ROUND DUCT WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ATTACH THE FLEXIBLE DUCT TO
THE RIGID DUCT AND THE
DIFFUSER USING TWO (2) BANDS;
ONE FOR THE DUCT AND ONE FOR
THE INSULATION.
U.L. LISTED FLEXIBLE DUCT.
SUPPORT TO PREVENT SAG.
FLEXIBLE DUCT SHALL BE LESS
THAN 5 FT. IN LENGTH AND SHALL
NOT BE USED FOR BENDS
GREATER THAN 45°.
MANUAL DAMPER WITH LOCKING
QUADRANT REGULATOR.
RIGID 90° DUCT ELBOW
WITH EXTERNAL
INSULATION
ROUND DUCT WITH EXTERNAL
INSULATION
20% MAXIMUM
AREA REDUCTION
R=H (MIN.)
L
W 15°H
W
L
DIM. "D"
ELEVATION
VIEW
PLAN
VIEW
DUCT DIM.
(SEE PLAN)
DUCT "VENTURI"
DEPRESSION DETAIL
NOTE: USE DETAIL
WHERE REQUIRED BY
FIELD CONDITIONS.
H R
TRANS.
DN.
TRANS.
UP
MIN. 2/3
"D"
TYPICAL
OBSTRUCTION TO
DUCT PATH
3"
CABLE WRAP
AROUND BEAM
AND BAR JOIST
CL20
DUCTMATE
CLUTCHERS
WR20 CABLE
DUCT
DUCT
INSULATION
THREADED ROD
DOUBLE NUT
UNISTRUT OR
ANGLE
UNISTRUT BAR
BAR JOIST
CL20
DUCTMATE
CLUTCHER OR
EQUAL
DUCTMATE
WR20 CABLE
OR EQUAL
MINIMUM 3/8"
DIA. THREADED
ROD
12 GAUGE
GALVANIZED
STEEL
DUCT
DUCT
INSULATION
DOUBLE NUT
DUCT
EXTERNAL INSULATION WHERE
SPECIFIED
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
NOTE: SEMI-CIRCLE
HANGER. 61"-72" DIAMETER
WITH 10' MAXIMUM
SPACING.
END VIEW ELEVATION VIEW
2"3 1/2" 1"
NOTE: FOR SIZES UP TO 60"
WITH 10' MAXIMUM SPACING.
SINGLE
DOUBLE
NOTE: 10' MAXIMUM SPACING.
97-120
85-96
72-84
61-72
DUCT SIZE (IN.) STRUT SIZE
1 5/8 X 1 5/8 X 12 GA
N/A
N/A
N/A
2 1/2 X 2 1/2 X 1/4
2 X 2 X 1/4
N/A
ANGLE SIZE
3 X 3 X 1/4
3/8
ROD SIZE
3/8
3/8
3/8
SCALE:
CONDENSATE DRAIN P-TRAP DETAIL
NOT TO SCALE
M-501
SCALE:
BRANCH DUCT TAP DETAIL
NOT TO SCALE
M-501
SCALE:
TURNING VANE DETAIL
NOT TO SCALE
M-501
SCALE:
DUCT DEPRESSION FOR STRUCTURAL CONFLICTS DETAIL
NOT TO SCALE
M-501
SCALE:
TYPICAL DIFFUSER CONNECTION DETAIL
NOT TO SCALE
M-501
SCALE:
DUCT HANGER DETAILS
NOT TO SCALE
M-501
DM
JGM M-501
HVAC DETAILS
SCALE:
WALL LOUVER DETAIL
NOT TO SCALE
M-501
WALL
MOUNTING FLANGE
FURNISHED WITH LOUVER.
ATTACH TO STRUCTURE.
LOUVER PER SCHEDULE
AND SPECIFICATIONS
APPLY SEALANT WHERE
LOUVER MEETS STRUCTURE
(TYPICAL)
SHIM AS REQUIRED
DUCTWORK PER PLANS
HEAD DETAIL
JAMB DETAIL
JAMB DETAIL
BIRD OR INSECT
SCREEN AS SCHEDULED
WALL
WALL
WALL
MOUNTING FLANGE
FURNISHED WITH LOUVER.
ATTACH TO STRUCTURE.
BIRD OR INSECT
SCREEN AS SCHEDULED
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
MOUNTING HOLES. ANCHOR UNIT
TO CONCRETE IN ACCORDANCE
WITH MANUFACTURER
SPECIFICATIONS
48-7/8"
SCALE:
GROUND MOUNTED CONDENSING UNIT DETAIL - CU-1, CU-2
NOT TO SCALE
M-502
SCALE:
CEILING CASSETTE DETAIL
NOT TO SCALE
M-502
24-7/16"
24-7/16"
DRAIN CONNECTION
SIDE
PIPE CONNECTION
SIDE
AIR OUTLET
SUCTION GRILLE
POWER SUPPLY
CONNECTION
22-5/8" 2-1/2"
7/8" 7/8"
7-1/2" 11 -1
3/
O
R M
O R
E
3/8" OR LESS3/8" OR LESS
47 1/4"
/1 6"
/8
PLAN
ELEVATION
SCALE:
DUCTLESS WALL MOUNT UNIT DETAIL
NOT TO SCALE
M-502
DRAIN PIPE
CONNECTION
LIQUID PIPE CONNECTION
GAS PIPE CONNECTION
CEILING
CEILING
SUPPORT FROM
STRUCTURE ABOVE
SUPPORT FROM
STRUCTURE ABOVE
BACK LEFT PIPE
BOTTOM LEFT
PIPE
BACK RIGHT
PIPE
BOTTOM RIGHT
PIPE
GROUNDING TERMINAL
AIR OUTLET
PIPING AND WIRING INTAKE
DRAIN HOSE
LIQUID PIPE
GAS PIPE
LEFT SIDE PIPE
CONNECTION
HOLE
FRONT GRILLE
PIPING AND WIRING INTAKE
(FLEXIBLE TUBE PART)(FILTER PART)
3-1/8Ø HOLE
FULL OPEN FRONT PANEL
SUSPENSION BOLT
SUSPENSION BOLT
CONDENSATE PIPE
CONDENSING PIPE
CONCRETE PAD (MIN. 4" THICK
AND MIN. 6" WIDER THAN
EQUIPMENT ON ALL SIDES)
WITH 3/4" CHAMFER AS SHOWN.
REFRIGERANT
PIPING
FIELD INSTALLED
CONDENSATE PUMP
EQUAL TO
RECTORSEAL 83939
FIELD INSTALLED CONDENSATE
PUMP EQUAL TO RECTORSEAL 83939.
ROUTE CONDENSATE PIPING PER
SHEETS MP101 THRU MP104.
EXTEND SLAB TO FACE OF
BUILDING. MAINTAIN
MANUFACTURER REQUIRED
CLEARANCES
DM
JGM M-502
HVAC DETAILS
-1
1/
MOUNTING HOLES. ANCHOR UNIT TO
ROOF RAILS IN ACCORDANCE WITH
MANUFACTURER SPECIFICAITONS
SCALE:
ROOF MOUNTED CONDENSING UNIT DETAIL - CU-3, CU-4A, CU-4B
NOT TO SCALE
M-502
COMPOSITE RAILS WITH MOUNTING STRUT
EQUAL TO DIVERSITECH FF-1000-S. APPLY
BITUMINOUS COATING BETWEEN RAIL AND
ROOF. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
REFRIGERANT
PIPING
-1
1/
SWEEP BALLAST FROM AREA
AND REPLACE AFTER
MOUNTING EQUIPMENT.
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
MAIN DUCT
RIGID ELBOW
T-BAR CEILING
PLASTIC ZIP TIE
INSULATED FLEX
CABLE HANGER FROM STRUCTURE
VOLUME DAMPER
VOLUME DAMPER
RIGID
ELBOW
CEILING T-BAR
INSULATION
INSULATION
CONICAL FITTING WITH VOLUME
DAMPER AND LOCKING QUADRANT.
CABLE HANGER FROM
STRUCTURE
NOTE:
1. MAXIMUM RUN-OUT LENGTH OF FLEXIBLE DUCT IS 5' - 0".
2. PROVIDE EXTENDED SHAFT FOR ATTACHMENT OF
DAMPER. QUADRANT ON EXTERIOR OF DUCT.
COORDINATE STANDOFF DISTANCE WITH INSULATION
THICKNESS AS REQUIRED.
3. FLEX DOWN FROM RIGID DUCT WHERE CLEARANCE
ALLOWS.
SUPPLY DIFFUSER OR
RETURN GRILLE - SEE
PLANS AND AIR DEVICE
SCHEDULE
SCALE:
BRANCH CONNECTION TO CEILING DIFFUSER DETAIL
NOT TO SCALE
M-503
39-3/8"
37-1/2" 37-1/2"
9-
/16
-1
3/1 6"
TOP VIEW
FRONT VIEW BACK VIEW
LEFT SIDE VIEW RIGHT SIDE VIEW
SCALE:
CONCEALED DUCTED UNIT DETAIL
NOT TO SCALE
M-503
AIR OUTLET
AIR INTLET
DRAIN SOCKET
AIR OUTLET FLANGE
HANGER
AIR INLET FLANGE
DRAIN HOSE
3D VIEW
SOCKET FOR
MAINTENANCE
LIQUID PIPE
CONNECTION
GAS PIPE
CONNECTION
DRAIN PIPE
CONNECTION
TRANSMISSION AND REMOTE
CONTROLLER WIRING CONNECTION
CONTROL BOX (INSIDE)
GROUND TERMINAL (CONTROL BOX)
POWER SUPPLY WIRING
CONNECTION
DM
JGM M-503
HVAC DETAILS
NEW 2" GASKETED (5/32"DIA) STAINLESS STEEL
SCREWS @ 4" O.C. ON ALL SIDES
CONTINUOUS BEAD OF SEALANT ALONG
PERIMETER OF CAP
NEW 20 GAUGE STAINLESS STEEL
SHEET CAP WITH MIN 2% SLOPE TO
EDGE. TYPICAL ALL DIRECTIONS.
4" M
IN
EXISTING
ROOF CURB
SUBSTRATE
EXISTING
DIMENSION
FIELD VERIFY
SCALE:
ROOF CURB CAP DETAIL
NOT TO SCALE
M-503
SCALE:
TYPICAL ROOF PATCH DETAIL
NOT TO SCALE
M-503
EXISTING MECHANICAL SUPPORT TO
BE REMOVED
REPLACE ROOF BALLAST IN-KIND TO
COVER ALL CONDITIONS
EXISTING BALLASTED ROOF SYSTEM TO
REMAIN. PROTECT DURING CONSTRUCTION
EXISTING COMPROMISED MEMBRANE ROOF
AREA AT DEMOLISHED MECHANICAL SUPPORT.
FILL AREA WITH ROOFING BITUMEN SOLID
TYPICAL MECHANICAL
SUPPORT FASTENER:
REMOVE AND SEAL TIGHT
ANY OPENINGS IN SUBSTRATE
6" TYP ALL SIDES
PROVIDE ROOF MEMBRANE PATCH THAT IS
COMPATIBLE WITH EXISTING ROOF MEMBRANE
WITH 6" OVERLAP ON ALL SIDES. USE SOLID
ADHESIVE COMPATIBLE WITH ROOF MEMBRANE
FILL VOID WITH FOIL FACED
BATT INSULATION
INSULATED SHEET METAL (1/2"
POLYISO BOARD OR EQUAL
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
SCALE:
CU-1 PIPING DETAIL
NONE
M-504
DM
JGM M-504
HVAC DETAILS
PHASE 1 WIRING AND PIPING
KHRP26A33TA
IDU-1-2
FXAQ09PVJU
KHRP26A33TA
IDU-1-3
FXZQ15TBVJU
KHRP26A22TA
IDU-1-1
FXAQ18PVJU
KHRP26A22TA
IDU-1-4
FXZQ15TBVJU
KHRP26A22TA
IDU-1-5
FXAQ07PVJU
KHRP26A22TA
IDU-1-6
FXZQ15TBVJU
IDU-1-7
FXZQ15TBVJU
17.5 ft 3/8 x 7/8 "
#5.1
10.6 ft [2]
1/4 x 1/2 "
#5.2
12.6 ft [1] 3/8 x 7/8 "#5.3
9.3 ft [1] 1/4 x 1/2 "
#5.4
5.9 ft 3/8 x 3/4 "#5.5
36.1 ft [2] 1/4 x 1/2 "
#5.6
6.2 ft 3/8 x 5/8 "#5.7
9.3 ft [1] 1/4 x 1/2 "
#5.8
17.2 ft 3/8 x 5/8 "#5.9
9.7 ft [2] 1/4 x 1/2 "
#5.10
29.5 ft 3/8 x 5/8 "#5.11
9.3 ft [1] 1/4 x 1/2 "
#5.12
32.5 ft [1] 1/4 x 1/2 "
#5.13
CU-1
RXLQ96TATJA
RXLQ96TATJA
IN F1,F2
CU-1
RXLQ96TATJA L1, L2, L3 76.5A 3ph
IDU-1-2
FXAQ09PVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
IDU-1-3
FXZQ15TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-1-1
FXAQ18PVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-1-4
FXZQ15TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-1-5
FXAQ07PVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
IDU-1-6
FXZQ15TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-1-7
FXZQ15TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
SCALE:
CU-1 WIRING DETAIL
NONE
M-504
CONTROL WIRING PROVIDED BY
MECHANICAL CONTRACTOR
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
SCALE:
CU-2 PIPING DETAIL
NONE
M-504
DM
JGM M-505
HVAC DETAILS
PHASE 2 WIRING AND PIPING
CU-2
RXLQ72TATJA
SCALE:
CU-2 WIRING DETAIL
NONE
M-504
KHRP26A33TA
IDU-2-1
FXZQ12TBVJU
KHRP26A22TA
IDU-2-4
FXZQ09TBVJU
KHRP26A22TA
IDU-2-2
FXZQ09TBVJU
KHRP26A22TA
IDU-2-3
FXZQ09TBVJU
IDU-2-5
FXSQ30TAVJU
14.5 ft 3/8 x 3/4 "
#1.1
8.2 ft [3]
1/4 x 1/2 "
#1.2
3.9 ft 3/8 x 3/4 "#1.3
18.2 ft [3] 1/4 x 1/2 "
#1.4
7.1 ft 3/8 x 5/8 "#1.5
6.2 ft [1] 1/4 x 1/2 "
#1.6
9.2 ft [1] 3/8 x 5/8 "#1.7
22.5 ft [2] 1/4 x 1/2 "
#1.8
23.8 ft [1] 3/8 x 5/8 "
#1.9
RXLQ72TATJA
IN F1,F2
CU-2
RXLQ72TATJA L1, L2, L3 60.8A 3ph
IDU-2-1
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-2-4
FXZQ09TBVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
IDU-2-2
FXZQ09TBVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
IDU-2-3
FXZQ09TBVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
IDU-2-5
FXSQ30TAVJU
P1,P2
F1,F2
L1, L2 1.8A 1ph
BRC1E73
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
SCALE:
CU-3 PIPING DETAIL
NONE
M-504
DM
JGM M-506
HVAC DETAILS
PHASE 3 WIRING AND PIPING
CU-3
RXLQ72TATJA
SCALE:
CU-3 WIRING DETAIL
NONE
M-504
RXLQ72TATJA
IN F1,F2
CU-3
RXLQ72TATJA L1, L2, L3 60.8A 3ph
IDU-3-1
FXSQ30TAVJU
P1,P2
F1,F2
L1, L2 1.8A 1ph
BRC1E73
IDU-3-2
FXSQ30TAVJU
P1,P2
F1,F2
L1, L2 1.8A 1ph
BRC1E73
KHRP26A33TA
IDU-3-1
FXSQ30TAVJU
IDU-3-2
FXSQ30TAVJU
13.4 ft 3/8 x 3/4 "
#3.1
11.7 ft [3]
3/8 x 5/8 "
#3.2
15.7 ft [1] 3/8 x 5/8 "
#3.3
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
SCALE:
CU-4A PIPING DETAIL
NONE
M-504
DM
JGM M-507
HVAC DETAILS
PHASE 4 WIRING AND PIPING 1 OF 2
CU-4A
RXLQ72TATJA
SCALE:
CU-4A WIRING DETAIL
NONE
M-504
RXLQ72TATJA
IN F1,F2
CU-4A
RXLQ72TATJA L1, L2, L3 60.8A 3ph
IDU-4A-8
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4A-7
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4A-6
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4A-5
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4A-4
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4A-3
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4A-2
FXAQ07PVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
IDU-4A-1
FXAQ07PVJU
P1,P2
F1,F2
L1, L2 0.3A 1ph
BRC1E73
KHRP26A33TA
IDU-4A-8
FXZQ12TBVJU
KHRP26A33TA
IDU-4A-7
FXZQ12TBVJU
KHRP26A22TA
IDU-4A-6
FXZQ12TBVJU
KHRP26A22TA
IDU-4A-5
FXZQ12TBVJU
KHRP26A22TA
IDU-4A-4
FXZQ12TBVJU
KHRP26A22TA
IDU-4A-3
FXZQ12TBVJU
KHRP26A22TA
IDU-4A-2
FXAQ07PVJU
IDU-4A-1
FXAQ07PVJU
34.5 ft [1] 3/8 x 7/8 "
#4.1
10.5 ft [1]
1/4 x 1/2 "
#4.2
10.4 ft 3/8 x 7/8 "#4.3
10.4 ft [1] 1/4 x 1/2 "
#4.4
10.4 ft 3/8 x 3/4 "#4.5
10.4 ft [1] 1/4 x 1/2 "
#4.6
10.1 ft 3/8 x 5/8 "#4.7
10.2 ft [1] 1/4 x 1/2 "
#4.8
10.7 ft 3/8 x 5/8 "#4.9
10.4 ft [1] 1/4 x 1/2 "
#4.10
10.2 ft 3/8 x 5/8 "#4.11
10.3 ft [1] 1/4 x 1/2 "
#4.12
10.0 ft 3/8 x 5/8 "#4.13
15.3 ft [2] 1/4 x 1/2 "
#4.14
10.7 ft [1] 1/4 x 1/2 "
#4.15
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -5
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
SCALE:
CU-4B PIPING DETAIL
NONE
M-504
DM
JGM M-508
HVAC DETAILS
PHASE 4 WIRING AND PIPING 2 OF 2
CU-4B
RXLQ96TATJA
SCALE:
CU-4B WIRING DETAIL
NONE
M-504
RXLQ96TATJA
IN F1,F2
CU-4B
RXLQ96TATJA L1, L2, L3 76.5A 3ph
IDU-4B-1
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4B-2
FXAQ12PVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4B-3
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4B-4
FXAQ18PVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4B-5
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
IDU-4B-6
FXZQ12TBVJU
P1,P2
F1,F2
L1, L2 0.4A 1ph
BRC1E73
KHRP26A33TA
IDU-4B-1
FXZQ12TBVJU
KHRP26A22TA
IDU-4B-2
FXAQ12PVJU
KHRP26A22TA
IDU-4B-3
FXZQ12TBVJU
KHRP26A22TA
IDU-4B-4
FXAQ18PVJU
KHRP26A22TA
IDU-4B-5
FXZQ12TBVJU
IDU-4B-6
FXZQ12TBVJU
10.7 ft 3/8 x 7/8 "
#2.1
11.7 ft [1]
1/4 x 1/2 "
#2.2
4.6 ft 3/8 x 3/4 "#2.3
9.8 ft [2] 1/4 x 1/2 "
#2.4
13.6 ft [1] 3/8 x 3/4 "#2.5
11.0 ft [1] 1/4 x 1/2 "
#2.6
4.0 ft 3/8 x 5/8 "#2.7
7.4 ft 1/4 x 1/2 "
#2.8
9.0 ft 3/8 x 5/8 "#2.9
9.3 ft [1] 1/4 x 1/2 "
#2.10
23.5 ft [2] 1/4 x 1/2 "
#2.11
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -6
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
HVAC EQUIPMENT SCHEDULES
M-601
NOTES
1. PROVIDE CONDENSATE PUMP
2. 10 YEAR PARTS WARRANTY
3. SYSTEM SHALL BE PROVIDED WITH CENTRALIZED TOUCH SCREEN CONTROLLER.
DM
JGM
VRV INDOOR HVAC UNIT SCHEDULE
MARK ROOM
BASIS OF DESIGN
NOMINAL
TONNAGE TYPE OUTDOOR
UNIT
SUPPLY FAN
AIR FLOW RATE
(CFM)
COOLING CAPACITY HEATING
CAPACITY
(BTU/HR)
ENTERING
AIR
DRY BULB
(°F)
ELECTRICAL DATA DIMENSIONS
H x W x D
(INCHES)
WEIGHT
(LB) OPTIONS AND ACCESSORIES NOTES CONSTRUCTION
PHASEMANUFACTURER MODEL NO. TOTAL
BTU/HR
SENSIBLE
BTU/HR
ENTERING AIR
VOLTAGE MCA MOP
DB (°F ) WB (°F )
IDU-1-1 STAIRS-ST1 DAIKIN FXAQ18PVJU 1.5 WALL MOUNT CU-1 500 18,000 13,700 80 67 20,000 70 208-230V/1 0.5 15 11-3/8 x 41-3/8 x 9-1/4 31.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 1
IDU-1-2 OFFICE-207 DAIKIN FXAQ09PVJU 0.75 WALL MOUNT CU-1 280 9,500 7,300 80 67 10,500 70 208-230V/1 0.4 15 11-3/8 x 31-1/4 x 9-1/4 26.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 1
IDU-1-3 FILE ROOM-208 DAIKIN FXZQ15TAVJU 1.25 CEILING
CASSETTE CU-1 405 15,000 10,800 80 67 17,000 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 1
IDU-1-4 FILE ROOM-208 DAIKIN FXZQ15TAVJU 1.25 CEILING
CASSETTE CU-1 405 15,000 10,800 80 67 17,000 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 1
IDU-1-5 STORAGE-209 DAIKIN FXAQ07PVJU 0.5 WALL MOUNT CU-1 260 7,500 6,400 80 67 8,500 70 208-230V/1 0.4 15 11-3/8 x 31-1/4 x 9-1/4 26.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 1
IDU-1-6 OFFICE-210 DAIKIN FXZQ15TAVJU 1.25 CEILING
CASSETTE CU-1 405 15,000 10,800 80 67 17,000 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL
IDU-1-7 OFFICE-211 DAIKIN FXZQ18TAVJU 1.5 CEILING
CASSETTE CU-1 510 18,000 13,000 80 67 20,000 70 208-230V/1 0.6 15 10-1/4 x 22-5/8 x 22-5/8 40.8 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL
IDU-2-1 OFFICE-203 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-2 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 2
IDU-2-2 OFFICE-204 DAIKIN FXZQ09TAVJU 0.75 CEILING
CASSETTE CU-2 315 9,500 6,600 80 67 10,500 70 208-230V/1 0.3 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 2
IDU-2-3 OFFICE-205 DAIKIN FXZQ09TAVJU 0.75 CEILING
CASSETTE CU-2 315 9,500 6,600 80 67 10,500 70 208-230V/1 0.3 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 2
IDU-2-4 OFFICE-202 DAIKIN FXZQ09TAVJU 0.75 CEILING
CASSETTE CU-2 315 9,500 6,600 80 67 10,500 70 208-230V/1 0.3 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 2
IDU-2-5 OFFICE-200 DAIKIN FXSQ30TAVJU 2.5 DUCTED AHU CU-2 800 30,000 22,600 80 67 34,000 70 208-230V/1 1.8 15 9-5/8 x 39-3/8 x 31-1/2 82.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 2
IDU-3-1 CONFERENCE
ROOM-312 DAIKIN FXSQ30AVJU 2.5 DUCTED AHU CU-3 740 24,000 17,100 80 67 27,000 70 208-230V/1 1.8 15 9-5/8 x 39-3/8 x 31-1/2 77.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 3
IDU-3-2 CONFERENCE
ROOM-312 DAIKIN FXSQ30AVJU 2.5 DUCTED AHU CU-3 740 24,000 17,100 80 67 27,000 70 208-230V/1 1.8 15 9-5/8 x 39-3/8 x 31-1/2 77.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 3
IDU-4A-1 WOMEN-300 DAIKIN FXAQ07PVJU 0.5 WALL MOUNT CU-4A 260 7,500 6,400 80 67 8,500 70 208-230V/1 0.4 15 11-3/8 x 31-1/4 x 9-1/4 26.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-2 MEN-301 DAIKIN FXAQ07PVJU 0.5 WALL MOUNT CU-4A 260 7,500 6,400 80 67 8,500 70 208-230V/1 0.4 15 11-3/8 x 31-1/4 x 9-1/4 26.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-3 LAB-302 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4A 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-4 LAB-302 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4A 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-5 OFFICE-304 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4A 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-6 OFFICE-306 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4A 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-7 OFFICE-307 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4A 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4A-8 OFFICE-308 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4A 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4B-1 OFFICE-303 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4B 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4B-2 OFFICE-305 DAIKIN FXAQ12PVJU 1.0 WALL MOUNT CU-4B 290 12,000 8,900 80 67 13,500 70 208-230V/1 0.4 15 11-3/8 x 31-1/4 x 9-1/4 26.0 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4B-3 OFFICE-311 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4B 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
IDU-4B-4 HALLWAY- H300 DAIKIN FXAQ18PVJU 1.5 WALL MOUNT CU-4B 500 18,000 13,700 80 67 20,000 70 208-230V/1 0.5 15 11-3/8 x 41-3/8 x 9-1/4 31.0 BRC1E73 (1), BYFQ60C3W1W (1) ALL 4
IDU-4B-5 STORAGE-310 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4B 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), BYFQ60C3W1W (1) ALL 4
IDU-4B-6 STORAGE-309 DAIKIN FXZQ12TAVJU 1.0 CEILING
CASSETTE CU-4B 350 12,000 7,800 80 67 13,500 70 208-230V/1 0.4 15 10-1/4 x 22-5/8 x 22-5/8 36.4 BRC1E73 (1), DACA-CFS1 (1), DACA-CP1-1 (1) ALL 4
DESCRIPTION
SHEET
DATEP.A.
FIRM
U
NO.
D
REAL PROPERTY
SAFETY & HEALTH
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MGR
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson-McAdams
ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT
T:
\2
Pr oj ec ts
\2
3- M
U
SD
A
- B
H
VA
C
D es ig n
- L as
C ru ce s
N M
\0
W or ki ng
F ol de r\M ec h\
M -6
.d w g
M ay
3,
- 9
:3 2a m
EPM
TEL
2523-M
B. DEAN
D. HILDEBRAND
D. CORDRAY
X. JONES 5/3/24
Agricultural
Service Research
USDA ARS
2150 CENTRE AVENUE
BLDS D, SUITE 300
FORT COLLINS, CO 80526
LAS CRUCES BUILDING 48 HVAC DESIGN
SOUTHWESTERN COTTON GINNING RESEARCH LABORATORY
300 EAST COLLEGE DRIVE - LAS CRUCES, NM 88005
HVAC EQUIPMENT SCHEDULES
M-602
VRV AIR-COOLED CONDENSING UNIT SCHEDULE
MARK
BASIS OF DESIGN
NOMINAL
TONNAGE
COOLING CAPACITY HEATING CAPACITY ELECTRICAL
DIMENSIONS
HxWxD
(INCHES)
WEIGHT
(LB) EER OPTIONS AND
ACCESSORIES NOTES CONSTRUCTION
PHASEMANUFACTURER MODEL
NO. BTU/HR
AMBIENT
DESIGN
DRY BULB
(°F)
BTU/HR
AMBIENT
DESIGN
DRY BULB
(°F)
VOLTAGE MCA MOP
CU-1 DAIKIN RXLQ96T 8 92,000 95 103,000 47 208/3 76.5 80 66-11/16 x 48-7/8 x 30-3/16 793 14.90 / 12.30 VRV4HGL-K1 (1) ALL 1 CU-2 DAIKIN RXLQ72T 6 69,000 95 77,000 47 208/3 60.8 70 66-11/16 x 48-7/8 x 30-3/16 727 15.10 / 13.00 VRV4HGL-K1 (1) ALL 2 CU-3 DAIKIN RXLQ72T 6 69,000 95 77,000 47 208/3 60.8 70…
This is the start of the file's text. The full file is on GovTribe.