Seed Project- USDA ARS Las Cruces NM Haz Mat Final Report 08-11-20.pdf

PDF 4 MB Posted

Attached to
Mechanical Electrical Plumbing (MEP) MATOC
Solicitation number
12805B24R0004
Issued by

About this file

This document is a Limited Asbestos and Lead-Based Paint Inspection Report for the USDA Southwestern Cotton Ginning Research Laboratory located in Las Cruces, New Mexico. The inspection was conducted to identify asbestos-containing materials (ACMs) and lead-based paints (LBPs) that may be impacted by a planned renovation project.

The key findings indicate that several ACMs were identified, including mastic, floor tiles and mastics, roof materials, pipe insulation, and wallboard. Numerous LBPs were also found on paints throughout the buildings, including on walls, metal surfaces, floors, and equipment. The report provides specific details on the location and quantities of the identified ACMs and LBPs, as well as recommendations for proper handling and disposal prior to the renovation work. The report states that the ACMs and LBPs must be removed by licensed contractors in accordance with federal, state, and local regulations before the renovation project can commence.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Submission:

Limited Asbestos and Lead- Based Paint Inspection Final Report

Project:

U.S. Department of Agriculture Agriculture Research Service Plains Area

Buildings 48, 52, 49, 53, 50 and 51 Las Cruces, New Mexico

IDIQ Contract No.: AG-32SD-C-15-0044 GES Project No.: F20-025

Presented to:

Date:

August 11, 2020 www.THEGES.com

Engineering

Program Management

Construction Management

Healthcare CommercialScience & Technology Education

APEX COMPANIES, LLC

Limited Asbestos and Lead-Based Paint Inspection Report

USDA Southwestern Cotton Ginning Research Laboratory Buildings 48, 49, 50, 51, 52 and 53 300 E. College Drive Mesilla Park, New Mexico 88047

PREPARED FOR:

Mr. Farshad Majidian, PE Global Engineering Solutions 6700 Rockledge Drive Bethesda, MD 20817

August 10, 2020

PREPARED BY:

Apex Companies, LLC 7979 Broadway Street, Suite 105 San Antonio, TX 78209 Apex Project No. GLOBAL-001

WATER RESOURCES • ENVIRONMENTAL SERVICES • INDUSTRIAL HYGIENE • SAFETY • AIR QUALITY • SUSTAINABILITY AND CLIMATE CHANGE

Apex Companies, LLC • (800) 733-2739 • www.apexcos.com

August 10, 2020

Mr. Farshad Majidian, PE Global Engineering Solutions 6700 Rockledge Drive Bethesda, MD 20817

RE: LIMITED ASBESTOS AND LEAD-BASED PAINT INSPECTION REPORT

USDA Southwestern Cotton Ginning Research Laboratory Buildings 48, 49, 50, 51, 52 and 53 300 East College Drive Mesilla Park, New Mexico 88047

Apex Project No.: GLOBAL-001

Dear Mr. Majidian & Mr. Jones:

Apex Companies, LLC (Apex) has prepared this Limited Asbestos and Lead-Based Paint (LBP) inspection report of Buildings 48, 49, 50, 51, 52 and 53 of the USDA Southwestern Cotton Ginning Research Laboratory located at 300 East College Drive in Mesilla, New Mexico (the Site).

The survey was performed to support the proposed renovation project, which will impact suspect asbestos-containing materials (ACMs) and LBP located at the Site.

Please do not hesitate to contact Apex with any questions related to this report.

Sincerely, Apex Companies, LLC

Armando Flores Osanna Carrasco Asbestos Inspector License 602347 Senior Project Manager Lead Risk Assessor 2070889

Phillip G. Fronczek, CHMM Individual Asbestos Consultant License 105737 i

TABLE OF CONTENTS

EXECUTIVE SUMMARY .......................................................................................................................................... ii

1.0 INTRODUCTION

1.1 Objective

1.2 Scope of Work

1.3 Survey Limitations

2.0 Site Description

3.0 Survey

3.1 Asbestos Sampling and Analysis

3.2 Lead Containing Paint Analysis

4.0 FINDINGS

4.1 Asbestos-Containing Materials

4.2 Lead-Containing Paints

5.0 CONCLUSIONS AND RECOMMENDATIONS

5.1 Asbestos-Containing Materials

5.2 Lead-Containing Paints

TABLES

Tables 1 through 6: Sample Results for Asbestos Table 7 through 12: Sample Results for Lead

FIGURES

APPENDICES

Appendix A – Asbestos and Lead Laboratory Analytical Reports, Associated Chain-of-Custody Documents &

Laboratory Certifications Appendix B – Apex Personnel Certifications Appendix C – Site Photographs ii

EXECUTIVE SUMMARY

Apex Companies, LLC (Apex) was retained by the Global Engineering Solutions to conduct a limited asbestos and lead-containing paints (LCPs) inspection of Buildings 48, 49, 50, 51, 52 and 53 at the USDA Southwestern Cotton Ginning Research Laboratory located at 300 East College Drive, Mesilla Park, New Mexico (the Site). This survey was conducted prior to the planned electrical system upgrades of the one structure which is comprised of Buildings 48, 49, 52 and 53. The survey for Buildings 50 and 51 was conducted since the they are being evaluated for potential upgrades. Apex conducted a limited non-destructive inspection of inspected buildings located at the Site. The purpose of this inspection was to identify and sample suspect asbestos-containing materials (ACMs) to sample lead-based paints (LBP) that may be impacted by the renovation project.

ASBESTOS-CONTAINING MATERIALS

During the non-destructive asbestos inspection, Apex collected a total of one hundred sixty-eight (168) bulk samples of suspect ACMs. The materials below were found to contain asbestos greater than 1% due to laboratory analytical results identified during this inspection. A list of the ACMs noted at each building are listed below:

Building 48:

Mastic associated with the 12” x 12” white pinhole ceiling tile; it should be noted that the white pinhole ceiling tile is not ACM but considered cross-contaminated due do contact with the ACM mastic.

Black/yellow mastic under carpet.

9” x 9” brown floor tile and black mastic.

Black mastic associated with the 12” x 12” tan speckled floor tile.

Black mastic associated with the 12” x 12” gray streaked floor tile.

Sealant on corrugated roof panels.

Roof corrugated cement panels.

Roof seam sealant.

Building 52:

Wall plaster.

Insulation on pipe fittings.

Building 49:

Tan sheet vinyl flooring.

White sealant on roof vents.

Building 53:

Exterior window glazing compound.

Building 50:

White mastic on roof vents.

Building 51:

Black counter tops.

iii

Wall plaster.

It should be noted that the following materials contain ≤1% asbestos via Point Count method and are not considered ACMs per Environmental Protection Agency (EPA) rules and regulations. However, several OSHA regulations apply to any materials containing reportable concentrations of asbestos.

Removal of the materials are required to be performed in accordance with OSHA.

Building 48:

Mastic on tread.

Building 52:

Window glazing.

Building 49:

Window glazing.

Window glazing.

ACMs identified at the Site that may be impacted by the intended renovation project should be removed and disposed in accordance with federal, state and local regulations, prior to disturbance. The asbestos abatement must be performed by a licensed asbestos contractor in accordance the National Emission Standard for Hazardous Air Pollutants (NESHAP) 40 CFR 61 Subpart M. Tables 1-6 provides a summary of all suspect ACM findings.

LEAD-CONTAINING PAINTS

During the survey, Apex collected one hundred-two (102) paint chip samples. The following paints are considered lead-based paint (containing greater than 0.5% of lead by weight) based on analytical results:

Building 48:

White paint on wood wall.

White paint on metal columns.

Yellow paint on metal railing.

Tan paint on metal equipment.

Maroon paint on metal frame.

Brown paint on metal grate floor.

Blue paint on metal railing.

Yellow paint on cement floor.

Tan paint on metal column.

Red paint on metal stairs.

Yellow paint on metal railings.

White paint on metal door and door/frame.

Blue paint om metal equipment.

iv

Yellow paint on metal railing.

Maroon paint on metal grate.

No paint with >0.5% lead.

Yellow paint on metal railing.

Yellow paint on cement floor.

Gray paint on wood stairs.

Green paint on metal equipment.

Necessary precautions must be taken to prevent or minimize worker exposure to lead during disturbance of lead-containing materials, as outlined in OSHA regulations. Lead-containing materials may also require disposal classification in accordance with the federal and state regulations. Tables 7- 12 provides a summary of all lead paint findings.

Confirmation Asbestos and Hazardous Materials Survey Report

1.0 INTRODUCTION

Apex Companies, LLC (Apex) was retained by Global Engineering Solutions to conduct a limited asbestos and lead paint inspection of the USDA Southwestern Cotton Ginning Research Laboratory located at 300 East College Drive in Mesilla Park, New Mexico (the Site). The purpose of this survey was to identify suspect asbestos-containing materials (ACMs) and lead-containing paints (LCPs) located in the buildings that may be impacted by the renovation project.

1.1 Objective

Apex understands that USDA Southwestern Cotton Ginning Research Laboratory is scheduled for renovation. The purpose of this survey was to identify suspect ACMs and LCPs that may be impacted by the renovation activities.

1.2 Scope of Work

The scope of services for this hazardous building materials survey included, and was limited to, the following tasks:

• Perform a non-destructive asbestos of Buildings 48, 49, 50, 51, 52 and 53 at the Site scheduled for renovation for the presence, location, and quantity of ACMs at the Site. Apex performed the sampling the United States Environmental Protection Agency (USEPA) National Emission Standards for Hazardous Air Pollutants (NESHAP). Bulk samples were analyzed for the presence of asbestos using polarized light microscopy (PLM).

• Perform a lead paint survey of representative painted components that may be disturbed during renovation. Apex collected paint chip samples. The sample were analyzed for total lead utilizing EPA Method SW846 7420/3050B.

• Prepare tables indicating sample locations, sample types, analytical results, and/or quantities of ACM and LCP.

• Prepare a report that documents the findings of this inspection and provides recommendations for handling the ACM and LCP building materials identified.

1.3 Survey Limitations

The survey was conducted from May 19 - 23, 2020 by certified Asbestos inspector Mr. Armando Flores.

Mr. Flores is also a certified Lead Risk Inspector/Assessor.

Destructive sampling was not conducted since the buildings are occupied. At the request of the on-site facility representatives, some suspect materials were not sampled, and the roofing sampling was limited to sampling of surface materials only, to not void the roof warranty. It should be noted that additional suspect materials could be present in walls, voids, attics, crawl spaces, beneath the base of walls, and in other areas not easily accessible or not visible. In some areas sampling was not conducted due to the request of the on-site facility representatives.

The findings, conclusions and recommendations discussed in this report are Apex’s professional opinions, based solely upon site conditions during the survey, visual site observations and interpretations of laboratory analyses. All applicable federal, state and local regulations should be verified by building owners and contractors, prior to initiating any work that will disturb regulated building materials.

This report should not be utilized as a bidding document or as a project specification document since it does not have all the components required to serve an as Abatement Project Design document or an Abatement Work Plan.

Limited Asbestos and Lead Inspection Report

2.0 SITE DESCRIPTION

The Site includes multiple structures and this inspection was limited to Buildings 48, 49, 50, 51, 52 and 53.

Building 48 is a three-story structure with masonry and stucco exterior walls, a gravel membrane lower roof and cement gabled higher roof. Interior finishes of Building 48 are comprised of vinyl tile, metal grate, cement, and ceramic floors, with cement, gypsum, ceramic, masonry, and wood panel walls.

Building 49 is a one-story structure with masonry, stucco, and metal exterior walls. The roof is a metal gabled style. Interior finishes in Building 49 are comprised of vinyl sheet, metal grate, and cement floors, with metal, masonry, and wood panel walls.

Building 50 is a one-story structure with metal exterior walls. The roof is a metal gabled style. Interior finishes in Building 50 are comprised of cement and wood floors; with metal and wood panel walls.

Building 51 is a one-story structure with metal exterior walls. The roof is gabled metal style. Interior finishes in Building 51 are comprised cement floors, with metal and wood panel walls.

Building 52 is a one-story structure with metal, stucco, and masonry exterior walls. The roof is a gabled metal style. Interior finishes in Building 52 are comprised of vinyl sheet, metal grate, and cement floors;

with masonry, stucco, and wood walls.

Building 53 is one-story structure with metal exterior walls. The roof is a metal gabled style. Interior finishes in Building 53 are comprised cement floors and metal grate; with metal walls.

3.0 SURVEY

Apex performed sampling to investigate the accessible interior and exterior surfaces. In order to identify suspect ACMs and LCPs, Apex performed a walk-through survey of the Site. Apex accessed each space in the buildings, including the rooftops and the exteriors to identify suspect ACMs and LCPs and estimated the appropriate sample count for these materials. Apex used non-destructive sampling to since the buildings are occupied. At the request of the on-site facility representatives, some suspect materials were not sampled, and the roofing sampling was limited to sampling of surface materials only, to not void the roof warranty.

3.1 Asbestos Sampling and Analysis

The asbestos survey was performed generally following the sampling protocols as outlined as the USEPA NESHAP. Approximate quantities of suspect materials were estimated by field measurements.

The condition (e.g., good, fair, poor) and friability (i.e., easily crumbled, pulverized, or reduced to powder by hand pressure) of suspect ACM was noted for each material. Friability of each sampled material was determined by hand-touch.

• Surfacing materials, including spray-applied or troweled-on wall/ceiling coatings;

• Thermal system insulation (TSI), including pipe insulation, duct insulation, boiler lagging; and

• Miscellaneous materials, including ceiling panels, floor tiles and mastics, gaskets (if accessible), fire doors, and wallboard/joint compound.

Suspected ACMs were grouped into homogeneous areas (i.e., a material that is uniform in texture, color, date of application, use or system, and appears identical in every other respect). Homogeneous areas were determined by the Apex certified Asbestos Inspector based upon date of installation and uniformity of color and texture. Fiberglass, foam glass, rubber, wood products, plastic products, glass and steel were not sampled since they are not considered suspect ACM.

Limited Asbestos and Lead Inspection Report

A total of one-hundred sixty-eight (168) bulk samples were collected from the interior, exterior and roofs of the on-site buildings. Bulk suspect asbestos samples were analyzed utilizing Polarized-Light Microscopy (PLM), following the USEPA PLM Method EPA-600/R-93/116. The bulk samples were analyzed by J3 Resources, Inc. (J3), in Pasadena, Texas. J3 is accredited by the National Institute of Standards and Technology National Voluntary Laboratory Accreditation Program (NVLAP No. 600120- 0). A summary of the samples collected, and analytical results are presented in Tables 1 through 6.

3.2 Lead Containing Paint Analysis

Apex conducted sampling and analysis of accessible painted building components to identify lead concentrations of painted surfaces that will be impacted during renovation-related activities. Sampling was performed generally following industry standards consistent with EPA guidelines.

A total of one-hundred seven (107) paint chip samples were collected from the on-site buildings. The samples were submitted to J3 Resources, Inc. in Pasadena, Texas. The sample were analyzed for total lead utilizing EPA Method SW846 7420/3050B. A summary of the samples collected, and analytical results are presented in the Tables 7 through 12.

4.0 FINDINGS

4.1 Asbestos-Containing Materials

Apex collected a total of one hundred sixty-eight (168) bulk samples of suspect ACMs during the limited inspection. The laboratory analytical results identified greater than 1% asbestos in the following materials in the buildings indicated.

Building 48:

Mastic associated with the 12” x 12” white pinhole ceiling tile located in 311 conference room;

it should be noted that the white pinhole ceiling tile is not ACM but considered cross-contaminated due do contact with the ACM mastic.

Table No. 1 Sample No. 04, 05, 06 Site Photographs for Building 48: Photo No. 4 Page 1

Black/yellow mastic under carpet located in 306, 307, and 308 Offices on the 3rd floor.

Table No. 1 Sample No. 76, 77, 78 Site Photographs for Building 48: Photo No. 10 on Page 2 and Photo No. 16 on Page 3

9” x 9” brown floor tile and black mastic located under carpet in the elevator lobby, office 311 and 305 storage; in 303 Office; in 309 storage; and 310 storage on 3rd floor.

Table No. 1 Sample No. 82, 83, 84 Site Photographs for Building 48: Photo No. 6 on Page 1, Photo 7, 8 and 11 on Page 2, and

Photo No.16 on Page 3 Black mastic associated with the 12” x 12” tan speckled floor tile located in 302 lab and hallway

300 on the 3rd floor.

Table No. 1 Sample No. 85, 86, 87 Site Photographs for Building 48: Photo No. 12 on Page 2

Black mastic associated with the 12” x 12” gray streaked floor tile located on all landings and on all levels of the West Stairwell.

Table No. 1 Sample No. 88, 89, 90 Site Photographs for Building 48: Photo No. 13 and 14 on Page 3

Limited Asbestos and Lead Inspection Report

Sealant on corrugated roof panels located on all of upper roof.

Table No. 1 Sample No. 101 Site Photographs for Building 48: Photo No. 2 on Page 1

Roof corrugated cement panels exists as the entirety of the upper roof.

Table No. 1 Sample No. 100 Site Photographs for Building 48: Photo No. 1 and 2 on Page 1, and Photo No. 19 on Page

4) Roof seam sealant located along east wall seam at lower roof level between Building 48 and

Building 52.

Table No. 1 Sample No. 102 Site Photographs for Building 48: Photo No. 18 on Page 3

Wall plaster exists as the interior West wall.

Table No. 5 Sample No. 01, 02, 03 Site Photographs for Building 52: Photo No. 2 on Page 1

Insulation on pipe fittings located elevated along the east, west, and south walls. ( Table No. 5 Sample No. 04, 05, 06 Site Photographs for Building 52: Photo No. 3 on Page 1

Insulation on pipe fittings, located along south wall elevated in open area.

Table No. 2 Sample No. 01, 02, 03 Site Photographs for Building 49: Photo No. 5 on Page 1

Tan sheet vinyl flooring located within the data room.

Table No. 2 Sample No. 07, 08, 09 Site Photographs for Building 49: Photo No. 4 on Page 1

White sealant on roof vents on roof.

Table No. 2 Sample No. 24

Insulation on pipe fittings located elevated along the east, south, and north walls.

Table No. 6 Sample No. 01, 02, 03 Site Photographs for Building 53: Photo No. 3 and 4 on Page 1

Exterior window glazing compound on windowpanes along north and west walls.

Table No. 6 Sample No. 07, 08, 09 Site Photographs for Building 53: Table No. 6 Photo No. 5 on Page 1

White mastic on roof vents on roof.

Table No. 3 Sample No. 5

Building 51:

Black counter tops located throughout small shop area.

Table No. 4 Sample No. 04, 05, 06 Site Photographs for Building 51: Photo No. 3, 4 and 5 on Page 1

Limited Asbestos and Lead Inspection Report

It should be noted that the following materials contain ≤1% asbestos via Point Count method.

Building 48:

Mastic on stair tread located in the west stairwell.

Table No. 1 Sample No. 73, 74, 75 Site Photographs for Building 48: Photo No. 15 on Page 3

Window glazing on windowpanes along north and south walls.

Table No. 5 Sample No.

Building 49:

Table No. 2 Sample No. 13, 14, 15

Table No. 3 Sample No. 01, 02, 03

A summary of Apex’s asbestos sampling, including analytical results, sample numbers, material descriptions, sample locations and quantities are provided in Tables 1 through 6. Supporting documentation for the sample analyses, including copies of laboratory analytical reports, chain-of-custody documents and laboratory certifications are provided in Appendix A. Asbestos Building Inspector certifications are provided in Appendix B. Site photographs are provided in Appendix C.

4.2 Lead-Containing Paints

Lead-based paint (LBP) is defined as paint containing >1.0 milligrams per square centimeter (mg/cm2) as measured by >0.5% of lead by weight as analyzed by Atomic Absorption, for the purposes of renovation and/or demolition work. Occupational Safety and Health Administration (OSHA) defines LBP as any paint containing detectable amounts of lead. A summary of the samples collected, and analytical results are presented in the Tables 7 through 12.

The laboratory results indicated that the following paints in the buildings indicated were above the >0.5% of lead by weight:

Building 48:

White paint on wood walls in 103 lab and adjacent hallway on the1st floor.

Table No. 7 Sample No. P07 Site Photographs for Building 48: Photo No. 28 and 30 on Page 5

White paint on metal columns that support building can be accessed on 1st and 2nd level of open area.

Table No. 7 Sample No. P13 Site Photographs for Building 48: Photo No. 23 on Page 4

Yellow paint on metal railing located on stairwells and safety railing on 2nd floor platform in open area.

Table No. 7 Sample No. P15 Site Photographs for Building 48: Photo No. 24 on Page 4

Limited Asbestos and Lead Inspection Report

Tan paint on metal equipment located on 1st and 2nd level of open area.

Table No. 7 Sample No. P16 Site Photographs for Building 48: Photo No. 25 on Page 5

Maroon paint on elevator metal door frame located in bay area on the 1st floor.

Table No. 7 Sample No. P18 Site Photographs for Building 48: Photo No. 26 on Page 5

Brown paint on metal grate floor exists as the metal platform floor of the 2nd level in open area.

Table No. 7 Sample No. P21 Site Photographs for Building 48: Photo No. 27 on Page 5

Blue paint on metal railing at all levels in the east stairwell. (Table No. 7 Photo No. 29) Table No. 7 Sample No. P23 Site Photographs for Building 48: Photo No. 29 on Page 5

Yellow paint on cement floor located sporadically on the 1st floor. (Table No. 11 Photo No. 4)

Table No. 11 Sample No. P03 Site Photographs for Building 52: Photo No. 4 on Page 1

Tan paint on metal column exists as structure for 2nd level platform. (Table No. 11 Photo No. 5) Table No. 11 Sample No. P06 Site Photographs for Building 52: Photo No. 5 on Page 1

Red paint on metal stairs located to 2nd and 3rd level stairwells. (Table No. 11 Photo No. 6) Table No. 11 Sample No. P07 Site Photographs for Building 52: Photo No. 6 on Page 1

Yellow paint on metal railings along stairwells rails and safety railing on 2nd and 3rd level platforms. (Table No. 11 Photo No. 7) Table No. 11 Sample No. P09 Site Photographs for Building 52: Photo No. 7 on Page 2

White paint on metal door and door/frame located on door along West wall. (Table No. 11 Photo No. 9) Table No. 11 Sample No. P11 Site Photographs for Building 52: Photo No. 9 on Page 2

Blue paint on metal equipment. (Table No. 11 Photo No. 8) Table No. 11 Sample No. P13 Site Photographs for Building 52: Photo No. 8 on Page 2

Yellow paint on metal railing located on stairwells and safety railing on 2nd floor platform in open area. (Table No. 8 Photo No. 2) Table No. 8 Sample No. P04 Site Photographs for Building 49: Photo No. 2 on Page 1

Maroon paint on metal grate exists as the metal platform floor of the 2nd level in open area.

(Table No. 8 Photo No. 2) Table No. 8 Sample No. P13 Site Photographs for Building 49: Photo No. 2 on Page 1

Limited Asbestos and Lead Inspection Report

No paint with >0.5% lead.

Yellow paint on metal railing located on 2nd floor.

Table No. 9 Sample No. P01 Site Photographs for Building 50: Photo No. 6 on Page 1

Yellow paint on cement floor located sporadically on the 1st floor.

Table No. 9 Sample No. P04 Site Photographs for Building 50: Photo No. 4 on Page 1

Gray paint on wood stairs located on stairwell to the 2nd floor.

Table No. 9 Sample No. P07 Site Photographs for Building 50: Photo No. 5 on Page 1

Green paint on metal equipment in the large shop. (Table 10 Photo No. 6)

Table No. 10 Sample No. P03 2Site Photographs for Building 51: Photo No. 6 on Page 1

Prior to performing renovation activities, the contractor should be made aware of the presence of potential lead-based paint, particularly in the areas of observed damaged paint to satisfy the hazard communication requirements set forth by OSHA regulations. Specifically, contractors should be required to comply with OSHA regulations including 29 CFR 1926.62, Lead Exposure in Construction:

Interim Final Rule and 29 CFR 1926.59, Hazard Communication for the Construction Industry.

5.0 CONCLUSIONS AND RECOMMENDATIONS

The conclusions of this report are Apex’s professional opinions, based solely upon visual Site observations and interpretations of laboratory analyses, as described in this report. The survey was performed to evaluate the potential presence of ACMs and LCPs that may be impacted during the renovation project.

5.1 Asbestos-Containing Materials

Federal, state, and local agencies regulate the condition, handling and disposal of ACM. Asbestos generally does not pose a human health threat unless the asbestos fibers are disturbed, become airborne and are inhaled. Contractors must be informed of the type and location of ACMs located within the work area.

Apex performed sampling in Buildings 48, 49, 50, 51, 52, and 53 at the Site. ACMs identified at the Site that will be impacted by the intended renovation project should be removed and disposed in accordance with federal, state and local regulations, prior to disturbance. The asbestos abatement must be performed by a licensed asbestos contractor in accordance the NESHAP 40 CFR 61 Subpart M. In addition, third party air monitoring must be performed during the abatement. Prior to initiating an asbestos abatement project, written notification must be provided to the New Mexico Environment Department. Notification must be provided no later than 10 calendar days prior to starting abatement.

Contractors should use caution during construction-related activities as concealed hazardous building materials that were not previously analyzed may be encountered. If additional materials, not previously sampled, are later identified during construction-related activities, then supplemental sampling should be performed. Materials identified to contain regulated quantities of asbestos or lead, must be removed

Limited Asbestos and Lead Inspection Report and disposed in accordance with federal, state and local regulations, prior to disturbance. Abatement of regulated building materials must be performed by a licensed abatement contractor.

It should be noted that the materials that contain ≤1% asbestos via Point Count method and are not considered ACMs per EPA rules and regulations. However, several OSHA regulations apply to any materials containing reportable concentrations of asbestos. Removal of those materials are required to be performed in accordance with OSHA.

5.2 Lead-Containing Paints

Paint chip analysis revealed that portions of the Site are coated with lead-based and/or lead-containing paints. The renovation project may impact materials identified to contain lead, as well as disturb unidentified LCPs that were inaccessible during the survey and may result in worker exposure to lead.

In the event that additional painted surface that were not previously sampled, precautions may be necessary to prevent or minimize worker exposure to lead.

Activities that may result in worker exposure to lead include:

• Manual damage to and/or demolition of structures coated with lead-containing paints

• Manual scraping and/or sanding of lead-containing paints

• Heat gun applications on surfaces coated with lead-containing paints

• Power tool cleaning of surfaces coated with lead-containing paints (with or without dust collection systems)

• Any other task that may result in the release of lead in the form of dusts, fumes or mists from lead-containing building materials into the air or onto surrounding environments

Prior to performing renovation activities, the contractor should be made aware of the presence of potential lead-based paint, particularly in any areas of observed damaged paint to satisfy the hazard communication requirements set forth by OSHA regulations. Specifically, contractors should be required to comply with OSHA regulations including 29 CFR 1926.62, Lead Exposure in Construction:

Interim Final Rule and 29 CFR 1926.59, Hazard Communication for the Construction Industry. Initial employee exposure monitoring must be conducted for each separate task involving the disturbance of building materials coated with lead-containing paints. If 8-hour time-weighted average (TWA) exposures exceed the action level of 30 micrograms of lead per cubic meter of air (µg/m3), periodic air monitoring must be continued at specified intervals, and medical surveillance and comprehensive training programs must be instituted. If the 8-hour TWA permissible exposure limit (PEL) of 50 µg/m3 for lead is exceeded, more stringent and additional requirements become effective, such as engineering controls, respiratory protection, regulated work areas and warning signs in lead work areas.

Based on the exposure assessment and previous similar work and exposure monitoring results, workers may have to be provided with any or all of the following:

• Respiratory protection

• Protective clothing

• Clean change areas

• Clean hand-washing facilities

• Biological monitoring (e.g., blood sampling and analysis for lead and zinc protoporphyrin levels)

• Hazard communication training

Limited Asbestos and Lead Inspection Report

All workers and supervisory personnel who will be at the job site must be informed of the presence of lead at the Site. These individuals should be provided additional training concerning the health effects associated with exposure to lead, proper work methods, appropriate use of personnel protective equipment, housekeeping procedures, and regulations governing work practices where lead-containing materials are present.

If any renovation, repair or demolition activity will disturb the lead-containing paint, engineering controls such as barriers and water should be used to minimize dust levels. The public should be prevented from unauthorized access to the work area. Ambient air monitoring is recommended to document engineering controls are adequate and that ambient airborne concentrations do not exceed permissible exposure levels.

All workers and supervisory personnel who will be at the Site must be informed of the presence of hazardous building materials. These individuals should be provided additional training concerning the health effects associated with exposure to lead, asbestos or other hazardous materials, such as proper work methods, appropriate use of personnel protective equipment, housekeeping procedures, and regulations governing specific work practices.

USDA Southwestern Cotton Ginning Research Limited Asbestos and Lead Inspection Report

TABLES

Sample Results for Asbestos

Tables 1 through 6

Table 1: Asbestos Sample Results Summary Southwestern Cotton Ginning Research Laboratory

Building 48 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity

Asbestos %

01, 02, 03 Sheetrock/Joint

Compound

2nd Floor Hallway 2nd Floor File Room

2nd Floor Conference Room N/A None Detected

04, 05, 06 12” x 12” White Pinhole

Ceiling Tile/Mastic 3rd Floor 311 Conference

Room 1,296 SF

CT: None Detected

M: 2% Chrysotile

07, 08, 09 2’ x 4’ White Long Fissure

Ceiling Tile

3rd Floor 311 Conference Room

2nd Floor Hallway 2nd Floor 211 Office

N/A None Detected

10, 11, 12 2’ x 4’ White Wide Long

Fissure Ceiling Tile 2nd Floor 211 Office N/A None Detected

13, 14,15 2’ x 4’ White Pockets

Ceiling Tile

2nd Floor Conference Room 2nd Floor File Room 2nd Floor Hallway

N/A None Detected

16, 17, 18 12” x 12” White Pinhole

Ceiling Tile- Nailed

2nd Floor 202 Office 2nd Floor 207 Office

2nd Floor Conference Room N/A None Detected

19, 20, 21 2’ x 4’ White Long Fissure

Sideways Ceiling Tile 2nd Floor File Room 2nd Floor 205 Office

N/A None Detected

22, 23, 24 Beige Wallpaper/Glue 3rd Floor 311 Conference

Room N/A None Detected

25, 26, 27 2’ x 2’ White Pinhole Wall

Panel - Nailed 2nd Floor Open Area N/A None Detected

28, 29, 30 12” x 12” White Pinhole

Ceiling Tile – Nailed 2nd Floor Open Area N/A None Detected

31, 32, 33 Paint/Texture on CMU

Block 2nd Floor Open Area 1st Floor Open Area

N/A None Detected

34, 35, 36 Plaster/Smooth Texture

Ceiling

3rd Floor 302 Office 3rd Floor 309 Office

3rd Floor 311 Conference Room

N/A None Detected

37, 38, 39 Plaster/Wave Texture Wall 3rd Floor Men’s Restroom

3rd Floor Women’s Restroom

N/A None Detected

40, 41, 42 Plaster/Orange Peel

Texture Wall

3rd Floor 306 Office 3rd Floor 307 Office

3rd 308 Office N/A None Detected

43, 44, 45 Mortar to CMU Block Attic Wall N/A None Detected

46, 47, 48 Mortar to Glass Block

3rd Floor 303 Office 3rd Floor 311 Conference

Room 3rd Floor Corridor

N/A None Detected

Building 48 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity

Asbestos %

49, 50, 51 Gray Moisture Barrier 2nd Floor Conference Room N/A None Detected

52, 53, 54 Gray Light Weight

Concrete/White Moisture Barrier

2nd Floor Open Area Deck N/A None Detected

55, 56, 57 Gray Window Glazing

Compound

3rd Floor Elevator Window 3rd Floor East Stairwell

Window N/A None Detected

58, 59, 60 Black Lab Countertop 3rd Floor 302 Lab Room N/A None Detected

61, 62, 63 Tan Mastic on Metal

Round Duct Attic Duct N/A None Detected

64, 65, 66 Black/Gray Vibration

Dampener Cloth 2nd Floor Open Area

Equipment N/A None Detected

67, 68, 69 White Caulking on Restroom Fixtures

3rd Floor Men’s Restroom 3rd Floor Women’s

Restroom N/A None Detected

70, 71, 72 Covebase/Mastic 3rd Floor 308 Office 2nd Floor File Room

N/A None Detected

73, 74, 75 Tread/Riser Mastic 1st Level West Stairwell 2nd Level West Stairwell 3rd Floor West Stairwell

N/A

T: None Detected

M: 0.99 Chrysotile (PC)

76, 77, 78 Black/Yellow Carpet Mastic

3rd Floor 306 Office 3rd Floor 307 Office 3rd Floor 308 Office

462 SF 2% Chrysotile

79, 80, 81 Green Carpet Mastic under Carpet Squares 3rd Floor 311 Office

3rd Floor Conference Room N/A None Detected

82, 83, 84 9” x 9” Brown Floor tile/Black Mastic

3rd Floor 310 Storage 3rd Floor 311 Office

3rd Floor 311 Conference Room

2,084 SF

T: 2% Chrysotile

M: 4% Chrysotile

85, 86, 87 12” x 12” Tan Speckled Floor tile/Black Mastic

3rd Floor Corridor 3rd Floor 302 Lab

1, 074 SF

T: None Detected

M: 2% Chrysotile

88, 89, 90 12” x 12” Gray Speckled

Floor tile/Black Mastic

1st Floor Level West Stairwell

2nd Floor Level West Stairwell

3rd Floor Level West Stairwell

600 SF

T: None Detected M: 1.09%

Chrysotile (PC)

91, 92, 93 Green Sheet Vinyl

Flooring 2nd Floor 211 Office N/A None Detected

Building 48 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity

Asbestos %

94, 95, 96 Green Sheet Vinyl

Flooring 2nd Floor 205 Office N/A None Detected

97, 98, 99 Brown Streaked Sheet

Vinyl Flooring 2nd Floor 207 Office N/A None Detected

Exterior Sealant on

Corrugated Roof Panel Attic 3,840 SF 8% Chrysotile

Roof Corrugated

Cement Panel Attic 3,840 SF 35%

Chrysotile

102 Roof Seam Sealant North Flat Roof 24 LF 8% Chrysotile

103 Roof Flashing Mastic North Flat Roof N/A None Detected

104 Roof Penetration Mastic North Flat Roof N/A None Detected

105 Roof Duct Mastic North Flat Roof N/A None Detected

106 Exterior Window Caulking Exterior 3rd Floor North

Roof Access N/A None Detected

107 Exterior Window Glazing Exterior 3rd Floor North

Roof Access N/A None Detected

SF – Square Feet LF – Linear Feet N/A – Not Applicable T – Tile M – Mastic CT – Ceiling Tile PC – Point Count

Table 2: Asbestos Sample Results Summary

Building 49 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity

Asbestos %

01, 02, 03 Pipe Insulation and Pipe

Wrap on Fittings 1st Level Open Area 2 LF

W: None Detected

I: 10% Chrysotile

04, 05, 06 Pipe Wrap and Pipe Mastic 1st Level Open Area N/A None Detected

07, 08, 09 Tan Sheet Vinyl Flooring Data Room 399 SF 12%

Chrysotile

10, 11, 12 12” x 12” White Pinhole

Ceiling Tile/Mastic Data Room N/A None Detected

13, 14,15 Window Glazing

Compound

1st Level Open Area – South Window

1st Level Open Area – North Window

1st Level Future Lab – North Window

N/A 1.0% Chrysotile

(PC)

16, 17, 18 Mortar to CMU Block 1st Level Open Area 1st Level Future Lab

N/A None Detected

19, 20, 21 Paint/Texture on CMU 1st Level Open Area 1st Level Future Lab

N/A None Detected

22 Beige Wallpaper/Glue 3rd Floor 311 Conference

Room N/A None Detected

23 White Roof Sealant South Roof N/A None Detected

White Sealant on Roof

Vent South Roof 2 SF 5% Chrysotile

SF – Square Feet LF – Linear Feet N/A – Not Applicable W – Wrap I – Insulation PC – Point Count

Table 3: Asbestos Sample Results Summary

Building 50 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity

Asbestos %

01, 02, 03 Window Glazing

Compound 2nd Level South Window N/A

0.5% Chrysotile

(PC)

04 White Roof Sealant North Roof N/A None Detected

05 White Mastic on Roof Vent

North Roof 6 SF 5% Chrysotile

SF – Square Feet LF – Linear Feet N/A – Not Applicable PC – Point Count

Table 4: Asbestos Sample Results Summary

Building 51 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity

Asbestos %

01, 02, 03 Window Glazing

Compound North Window Large Shop South Window Large Shop

N/A None Detected

04, 05, 06 Black Counter Tops Small Shop Area 77 SF 4 Counters

12% Chrysotile

07 White Roof Sealant East Roof N/A None Detected

08 White Mastic on Roof Vent East Roof N/A None Detected

SF – Square Feet LF – Linear Feet N/A – Not Applicable PC – Point Count

Table 5: Asbestos Sample Results Summary

Building 52 300 East College Drive

Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity Asbestos %

01, 02, 03 Wall Plaster 1st Level West Wall 1,217 SF 2% Chrysotile

04, 05, 06 Pipe Wrap and Pipe Mastic on Fittings 2nd Level East Wall 14 LF

W/M: None Detected

I: 10% Chrysotile

07, 08, 09 Pipe Wrap and Pipe Mastic on Fittings on Runs 2nd Level East Wall N/A 12% Chrysotile

10, 11, 12 Window Glazing

Compound 2nd Level North Window N/A

0.50% Chrysotile (PC)

13 Sealant on Roof Vent South Roof N/A None Detected

SF – Square Feet LF – Linear Feet N/A – Not Applicable W/Mastic – Wrap and Mastic I – Insulation PC – Point Count

Table 6: Asbestos Sample Results Summary

Building 53

300 East College Drive Mesilla, New Mexico 88047

Sample No. Suspect Material Sample Location Estimated Quantity Asbestos %

01, 02, 03 Pipe Wrap and Pipe Mastic on Fittings 2nd Level 15 LF

W/M: None Detected

I: 15% Chrysotile

04, 05, 06 Pipe Wrap and Pipe Mastic on Fittings on Runs 1st Level N/A None Detected

07, 08, 09 Window Glazing Compound

2nd Level West Window 150 LF 5 Windows

2% Chrysotile

10 White Roof Sealant South Roof N/A None Detected

White Sealant on Roof

Vent South Roof 3 SF 5% Chrysotile

SF – Square Feet LF – Linear Feet N/A – Not Applicable W/Mastic – Wrap and Mastic I – Insulation PC – Point Count

Sample Results for Lead Tables 7 through 12

TABLE 7 – LEAD SAMPLE RESULTS SUMMARY

Building 48 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P01 Tan Paint on Sheetrock Interior 2nd Floor File Room <0.005

P02 White Paint on CMU Wall Interior 2nd Floor Open Area 0.0052

P03 Beige Paint on Plaster Wall Interior 3rd Floor Conference

Room <0.005

P04 White Paint on Plaster Wall Interior 3rd Floor 308 Office 0.018

P05 Gray Paint on Plaster Wall Interior 3rd Level East

Stairwell <0.005

P06 Brown Paint on Plaster Wall Interior 3rd Level Stairwell 0.0099

P07 White Paint on Wood Wall Interior 1st Floor 103 Lab 0.8

P08 Blue Paint on Wood Wall Interior 2nd Floor 210 Office 0.099

P09 Beige Paint on Wood Door Interior 3rd Floor 308 Office 0.11

P10 Red Paint on Wood Door Interior 1st Floor 105 Bay

Area 0.031

P11 Tan Paint on Wood Wall Interior 1st Floor 101 Storage 0.38

P12 Gray Paint on Wood Plank Interior 2nd Floor Open Area INS*

P13 White Paint on Metal Column Interior 2nd Floor Open

Area 0.78

P14 White Paint on Metal

Door/Frame Interior 1st Floor 103 Lab 0.22

P15 Yellow Paint on Metal Railing Interior 2nd Floor Open

Area 9.9

P16 Tan Paint on Metal Equipment

Interior 2nd Floor Open Area

0.87

P17 Red Paint on Metal Brace Interior 2nd Floor Open Area 0.47

P18 Maroon Paint on Metal Frame Interior 1st Floor Bay Area Elevator Frame

3.3

P19 Gray Paint on Equipment Interior 2nd Floor Open Area 0.12

P20 Green Paint on Equipment Interior 2nd Floor Open Area 0.36

P21 Brown Paint on Metal Grate Floor

Interior 2nd Floor Open Area

0.55

P22 Beige Paint on Metal

Door/Frame Interior 3rd Floor 311

Conference Room 0.017

P23 Blue Paint on Metal Railing Interior 3rd Level East Stairwell

2.4

TABLE 7 – LEAD SAMPLE RESULTS SUMMARY

Building 48 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P24 Brown Paint on Metal Railing Interior 3rd Level West

Stairwell 0.057

P25 Gray Paint on Cement Floor Interior 1st Floor 100 Open

Area 0.2

P26 Yellow Paint on Cement Floor Interior 1st Floor 100 Open

Area <0.005

P27 Maroon Paint on Cement Curb Interior 1st Floor 105 Bay

Area 0.0087

P28 White Paint on Cement Wall Interior 1st Floor 105 Bay

Area 0.017

P29 Brown Paint on Cement Base Interior 3rd Level West

Stairwell 0.13

P30 Blue Paint on Cement Wall Interior 3rd Level East

Stairwell 0.013

P31 Gray Paint on Cement Tread Interior 3rd Level East

Stairwell 0.059

P32 Light Gray Paint on Concrete

Landing Interior 3rd Level East

Stairwell 0.35

P33 Red Paint on Metal Door/Frame Exterior 3rd Level North Roof <0.005

P34 Red Paint on Metal Window

Frame Exterior 3rd Level North Roof <0.005

P35 Beige Paint on Stucco Wall Exterior 3rd Level North Roof 0.0068

P36 Beige Paint on Metal Duct Exterior 3rd Level North Roof 0.13

INS* – Insufficient Sample Weight

TABLE 8 – LEAD SAMPLE RESULTS SUMMARY

Building 49 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P01 Tan Paint on Wood Wall Interior Data Room Wall 0.14

P02 White Paint on Wood Wall Interior Future Lab Wall 0.13

P03 Green Paint on Metal

Equipment Interior 1st Level Open Area 0.35

P04 Yellow Paint on Metal Rail Interior 2nd Level Open Area

P05 White Paint on Metal

Door/Frame Interior 1st Level Open Area 0.25

P06 Gray Paint on Metal Equipment Interior 1st Level Open Area 0.022

P07 Beige Paint on Metal

Equipment Interior 1st Level Open Area 0.17

P08 Red Paint on Metal Stairs Interior 1st Level Open Area 0.34

P09 Yellow Paint on Cement Floor Interior 1st Level Open Area 0.0098

P10 Gray Paint on Cement Floor Interior 1st Level Open Area 0.066

P11 White Paint on CMU Wall Interior 1st Level Open Area 0.073

P12 Tan Paint on Metal Equipment Interior 2nd Level Open Area <0.005

P13 Maroon Paint on Metal Grate Interior 2nd Level Open

Area 0.75

P14 Silver Paint on Metal

Equipment Interior 2nd Level Open Area 0.1

P15 Beige Paint on Metal Wall Exterior South Wall 0.098

P16 White Paint on Metal Roof Exterior South Roof 0.034

P17 Red Paint on Metal Window Exterior South Wall 0.041

P18 Beige Paint on Stucco Wall Exterior North Wall <0.005

TABLE 9 – LEAD SAMPLE RESULTS SUMMARY

Building 50 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P01 Yellow Paint on Metal Railing Interior 2nd Level 16

P02 Silver Paint on Metal Column Interior 2nd Level 0.41

P03 White Paint on Metal Wall Interior Paint Booth <0.005

P04 Yellow Paint on Cement Floor Interior 1st Level 7.5

P05 Gray Paint on Cement Floor Interior 1st Level 0.24

P06 Gray Paint on Wood Wall Interior 1st Level Compressor

Room 0.35

P07 Gray Paint on Wood Stairs Interior Stairwell 0.69

P08 Beige Paint on Metal

Door/Frame/Walls Interior South Door 0.092

P09 Red Paint on Metal Window

Frame Exterior South Window 0.17

P10 White Paint on Metal Roof Exterior South Roof 0.026

TABLE 10 – LEAD SAMPLE RESULTS SUMMARY

Building 51 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P01 Dark Gray Paint on Cement

Floor Interior Large Shop 0.3

P02 Light Gray Paint on Cement

Floor Interior Small Shop <0.005

P03 Green Paint on Metal Equipment

Interior Large Shop 1.7

P04 Red Paint on Metal Door/Frame Interior Small Shop <0.005

P05 Tan Paint on Metal Door/Frame Interior Large Shop 0.093

P06 Beige Paint on Metal Wall Interior Small Shop West

Wall <0.005

P07 Gray Paint on Metal Equipment Interior Large Shop <0.005

P08 Beige Paint on Metal

Equipment Interior Small Shop 0.18

P09 Blue Paint on Metal Equipment Interior Large Shop <0.005

P10 Tan Paint on Wood Wall Interior Large Shop 0.036

P11 White Paint on Wood

Door/Frame Interior Restroom 0.049

P12 Silver Paint on Metal Column Interior Large Shop 0.06

P13 Beige Paint on Metal Wall Interior North Wall <0.005

P14 Red Paint on Metal Door/Frame Exterior South Door 0.022

P15 Green Paint on Metal Generator Exterior South Exterior <0.005

TABLE 11 – LEAD SAMPLE RESULTS SUMMARY

Building 52 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P01 White Paint on Plaster Wall Interior 1st Level West Wall 0.3

P02 Gray Paint on Cement Floor Interior 1st Level 0.19

P03 Yellow Paint on Cement Floor Interior 1st Level 7.2

P04 Tan Paint on Metal Equipment Interior 2nd Level 0.4

P05 Brown Paint on Metal Grate

Floor Interior 2nd Level 0.48

P06 Tan Paint on Metal Column Interior 1st Level 0.56

P07 Red Paint on Metal Stairs Interior 1st Level 1.5

P08 Green Paint on Metal

Equipment Interior 1st Level 0.11

P09 Yellow Paint on Metal Railing Interior 1st Level 14

P10 Gray Paint on Metal

Door/Frame Interior 1st Level Roll Up

Door 0.22

P11 White Paint on Metal

Door/Frame Interior 1st Level West

Door 1.1

P12 Gray Paint on Metal Equipment Interior 1st Level 0.16

P13 Blue Paint on Metal

Equipment Interior 1st Level 2

P14 Red Paint on Metal Door/Frame Exterior South Door 0.0086

P15 Beige Paint on Metal Wall Exterior South Wall 0.11

TABLE 12 – LEAD SAMPLE RESULTS SUMMARY

Building 53 300 East College Drive

Mesilla, New Mexico 88047

Sample Nos. Color/Substrate Sample Location Lead Concentration

P01 Gray Paint on Cement Floor Interior 1st Level l 0.1

P02 Tan Paint on Metal Column Interior 1st Level <0.005

P03 White Paint on Metal

Door/Frame Interior 1st Level 0.19

P04 Yellow Paint on Metal Rail Interior 2nd Level <0.005% (INS*)

P05 Maroon Paint on Metal Grate Interior 2nd Level 0.12

P06 Beige Paint on Metal

Equipment Interior 2nd Level 0.021

P07 Beige Paint on Metal Wall Exterior South Wall 0.014

P08 Red Paint on Metal Door/Frame Exterior South Door 0.059

INS* – Insufficient Sample Weight

APPENDIX A

ASBESTOS AND LEAD LABORATORY ANALYTICAL RESULTS, ASSOCIATED CHAIN-OF-CUSTODY

DOCUMENTS & LABORATORY CERTIFICATIONS

Laboratory Results for Building 48

Date Received: 22-May-2020 29-May-2020Date Analyzed:

29-May-2020Date Reported:

JP201021595J3 Order #:

GLOBAL-001Project #:

Southwestern Cotton Ginning Research Laboratory-B48

7979 Broadway St., Ste 100 San Antonio TX 78209

Apex Companies, LLC Osanna Carrasco

Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM)

Appx E Sub E 40 CFR 763 / EPA 600/R-93/116

Sample Description Asbestos

ConstituentsSample ID # Non-Asbestos Constituents

J3 Resources, Inc.

3113 Red Bluff Road, Pasadena, TX 77503

Phone: (713) 290-0223 - Fax: (713) 290-0248

J3Resources.com

LAYER 1

Painted Texture, Beige/White, Homogeneous *No Tape or Joint Compound Present

None Detected01 Non-Fibrous Material 100%

Cellulose FiberLAYER 2 Wallboard, Brown/White, Homogeneous

None Detected 10%

Non-Fibrous Material 90%

LAYER 1

Painted Texture, Beige/White, Homogeneous

None Detected02 Non-Fibrous Material 100%

Cellulose FiberLAYER 2 Tape, Beige, Homogeneous

None Detected 100%

LAYER 3

Joint Compound, White, Homogeneous *No Wallboard Present

None Detected Non-Fibrous Material 100%

LAYER 1

Painted Texture, Beige/White, Homogeneous *No Tape or Joint Compound Present

None Detected03 Non-Fibrous Material 100%

Cellulose FiberLAYER 2 Wallboard, Brown/White, Homogeneous

None Detected 10%

Non-Fibrous Material 90%

Cellulose Fiber Fibrous Glass

LAYER 1

Ceiling Tile, White/Gray, Homogeneous

None Detected04 60% 10%

Non-Fibrous Material 30%

LAYER 2

Mastic, Black, Homogeneous

Chrysotile 2% Non-Fibrous Material 98%

Kennetch Castro Analyst Lab DirectorScott Ward, Ph.D.

This report relates only to the materials tested. This report is for the exclusive use of the addressed client and shall not be reproduced except in full, without written approval by J3 Resources, Inc. (J3). Samples are analyzed according to the methods listed above and are subject to the inherent limitations of PLM and interference of matrix components. Reporting limit for the above method is a function of the quantity of sample analyzed, matrix interference, sample preparation, fiber size, and distribution. Asbestos may be detected in concentrations of <1% by area if sufficient material is analyzed. J3 recommends TEM confirmation of soils, vermiculite and non-friable organically bound materials (NOB) reported as None Detected or < 1% Asbestos by PLM. All samples received in good condition unless otherwise noted. This report shall not be used to claim product approval, certification, or endorsement by NVLAP, NIST, or any agency of the federal government.

NVLAP Lab Code: 600120-0 AIHA Lab ID: 157714 TDSHS License: 30-0457 Page 1 of 16

29-May-2020Date Reported:

JP201021595J3 Order #:

GLOBAL-001Project #:

Southwestern Cotton Ginning Research Laboratory-B48

7979 Broadway St., Ste 100 San Antonio TX 78209

Apex Companies, LLC Osanna Carrasco

Bulk Asbestos Fiber Analysis by Polarized Light Microscopy (PLM)

Appx E Sub E 40 CFR 763 / EPA 600/R-93/116

Sample Description Asbestos

ConstituentsSample ID # Non-Asbestos Constituents

J3 Resources, Inc.

3113 Red Bluff Road, Pasadena, TX 77503

Phone: (713) 290-0223 - Fax: (713) 290-0248

J3Resources.com

Cellulose Fiber Fibrous Glass

LAYER 1

Ceiling Tile, White/Gray, Homogeneous

None Detected05 60% 10%

Non-Fibrous Material 30%

LAYER 2

Mastic, Black, Homogeneous

Chrysotile 2% Non-Fibrous Material 98%

Cellulose Fiber Fibrous Glass

LAYER 1

Ceiling Tile, White/Gray, Homogeneous

None Detected06 60% 10%

Non-Fibrous Material 30%

LAYER 2

Mastic, Black, Homogeneous

Chrysotile 2% Non-Fibrous Material 98%

Cellulose Fiber Fibrous Glass

Ceiling Tile, White/Gray, Homogeneous None Detected07 60% 10%

Non-Fibrous Material 30%

Cellulose Fiber Fibrous Glass

Ceiling Tile, White/Gray, Homogeneous None Detected08 60% 10%

Non-Fibrous Material 30%

Cellulose Fiber Fibrous Glass

Ceiling Tile, White/Gray, Homogeneous None Detected09 60% 10%

Non-Fibrous Material 30%

Cellulose FiberCeiling Tile, White/Brown, Homogeneous None Detected10 70%

Non-Fibrous Material 30%

Cellulose FiberCeiling Tile, White/Brown, Homogeneous None Detected11 70%

Non-Fibrous Material 30%

Kennetch Castro Analyst Lab DirectorScott Ward, Ph.D.

This report relates only to the materials…