Attachment 7 - B1176 As-built (2005) v2.pdf

PDF 2 MB Posted

Attached to
Repair Fire Pump Controllers, B1176, HEF Disposal
Solicitation number
W50S6K-26-B-A001
Issued by

About this file

This document is a set of architectural and engineering drawings and specifications for the repair and renovation of Building 1176, an Aircraft Maintenance Hangar at Eielson Air Force Base, Alaska, under FTQW 04-2254 for the Alaska Air National Guard.

The project scope encompasses comprehensive mechanical, plumbing, electrical, and fire protection system upgrades. Key mechanical work includes installation of new sprinkler systems with multiple zones (Zones 1-6), replacement of fire water pump equipment with diesel-powered pumps, new pre-action and dry-pipe riser systems, and high-expansion foam suppression system components scheduled for removal. Electrical work involves extensive lighting fixture upgrades, controls, and fire alarm system modifications including new manual foam release stations with signage, annunciator panels, and connections to existing systems. The fire protection systems require installation of new isolation valves, flow sensors, basket strainers, and foam concentrate proportioning equipment, with detailed specifications for Schedule 40 steel galvanized piping and stainless steel concentrate piping. The project includes removal of existing foam system components, cables, and conduit with proper abandonment procedures. Architectural elements include hangar floor demolition and renovation plans, door and window modifications, ceiling treatments, and roof details. The drawings provide comprehensive mechanical legends, electrical schedules, equipment specifications, and detailed riser diagrams to guide construction and system integration at the facility.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 7 ll.

I e "E i, e ll.

l

- EXISTING 10"¢ WATER

MAIN FROM UTILIDOR

- EXISTING 6"¢ WATER

FROM FIRE DEPARTMENT

CONNECTION -

_J x f- r CONDENSING UNIT FOR L-J-tt--- - --rr;:::=::===

,,-,,,-, '' AC-1 LOCATED ON WALL 7

IN MECH ROOM 120, PIPE__/

CONDENSATION DRAIN ALONG

FLOOR TO NEAREST FD. 8"!1 METER �

LINE (E) --.... lh---1\---------,t------i==f-----t-rt-rr----:::J["l r;=,=--------;;;�;;;;:JJ

' '------T1l ' • &C,, 6"¢ FROM �I'- ,,- lh----i-------'--� FIRE DEPARTMEN' K,..__ f-

CONNECTION--.LL.,._ 1 "

'-'l 0EXISTING WET-PIPE □ ... _ RISER, lYPICAL OF 4==='---H--1(_)1

10"¢ SPRINKLER

Q RISER ---4+-_J

_L._NEW ZO

H

NE 5 RISER TO HANGAR HIGH

T

IGH EXPANSION FOAM SYSTEM -++--��,I

_A NEW ZONE 6 TO PRE-ACTION

T SPRINKLER SYSTEM IN HANGAR --tt-- �,.....JI

NEW JOCKEY

PUMP

BLIND FLANGE

UP, lYP OF 2

L -\ f-

, 1 a"

I

8"

• ' la: llll

◄ I.

- 8"

" ffi

' I lb;::=====�

2 1 /2"

I

C L....::::::::::::.....J

I I

� FOAM CONCENTRATE SUPPLY TO

FOAM PROPORTIONER VALVE

iF

I

- 8"¢ FIRE PIPING BELOW

EXISTING FUEL OIL TANK,

SHOWN FOR CLARllY

NEW DOUBLE WALL FUEL OIL TANK, ADJUST

VERTICALLY TO PROVIDE REQUIRED CLEARANCE

FOR INSTALLATION AND MAINTENANCE

6"\11 RISER TO TEST

HEADER IN HANGAR

6" OS&Y GATE VALVE,

TAMPER LOCKED IN CLOSED

POSITION, FOR FOAM

RISER TEST ONLY

NEW 6" PRE-ACTION

RISER FOR OVERHEAD

SPRINKLERS IN

HANGAR, ZONE 6

ZONE 4(E), 4"\11

- CHECK VALVE, lYPICAL OF FWP-2, PIPING AND VALVES

FIRE SEAL WALL PENETRATIONS

IN FIRE-PUMP ROOM

NEW 6" DRY PIPE RISER FOR HIGH EXPANSION

FOAM SUPPRESSION SYSTEM, ZONE 5

6" OS&Y GATE VALVE, TAMPER LOCKED OPEN

FOAM CONCENTRATE PROPORTIONING VALVE

ZONE 2 (E), 2-1 /2"¢

ZONE 3 (E), 2"¢

ffi r ZONE 1 (E), 2-1/2"¢

IL FLOW SENSOR, TYP

C

=------l,_..,-;------------�6"\11 FDC

EXISTING BACKFLOW PREVENTER

EXTEND NEW STACK 24" ABOVE

EXISTING ROOF, lYPICAL

SEAL, FLASH AND COUNTERFLASH

NEW EXHAUST STACK THROUGH EXISTING

ROOF PENETRATION TO MAKE WEATHER-TIGHT

PUMP ROOM ROOF

PROVIDE STACK EXHAUST STACK

WITH WEATHER COVER , lYPICAL

SEAL, FLASH AND COUNTERFLASH

NEW EXHAUST STACK PENETRATION TO

MAKE WEATHER-TIGHT

INSULATE LAST 48" OF EXHAUST

PIPE GOING THROUGH PUMP

ROOM ROOF, lYPICAL

1--- PROVIDE NEW MUFFLER FOR

NEW FIRE WATER PUMP,

ENGINE, lYPICAL

FLEX CONNECTION BETWEEN

NEW 3" DIESEL EXHAUST STACK

AND NEW FIRE WATER PUMP, lYPICAL p

) ffi r 3'

,_M2.2,, -

PUMP ROOM FLOOR

FIRE PUMP EXHAUST SCHEMATIC

SCALE: NONE

DRY SYSTEM

VALVE, TYP r FLOW METER

8",;&

J.-.-- NEW ISOLATION VALVE (8"!6)

10"\11 SPRINKLER

RISER MANIFOLD

BASKET STRAINER,

WATTS 6" 97FB-CI,

OR EQUAL

o, FIRE SPRINKLER RISER

SCALE: NTS

8x8x8 TEE, ��

CAPPED (E)

.--'h-+------"----'-----, M ;------�

2'"'"\ll:...c,<1---1.-

,...,_ __ -t◄1-{:><:1--, SAFETY RELIEF

�1p VALVE, TYPICAL--t---�,._,\J:7

L--L--1'--'----'--{◄

2" FOAM CONCENTRATE PIPE (�

p

10"¢

2 1 /2"¢ WATER

TO CST-1

l FLOOR ""'' (E) r--- PROVIDE ISOLATION

VALVE WITH TAMPER

SWITCH

NOTES:

1. ALL HIGH EXPANSION FOAM (HEFl SYSTEM PIPING SHALL BE MINIMUM SCHEDULE 40 STEEL.

GALVANIZED PIPING, FITTINGS OR DEVfCES SHALL NOT BE USED IN ANY HEF RELATED SYSTEM.

2. PAINT HEF SYSTEM PIPING IN FACILITY COORDINATE COLOR, COORDINATE WITH OWNER. MARK ALL HEF SYSTEM PIPING WITH IDENTIFICATION AND FLOW MARKINGS AT INTERVALS NOT TO EXCEED 26 FEET.

�HALtLL B�EJ0A�gR�A��t� JfRJ�K}rf. PIPING SHALL BE CAPABLE OF BEING DRAINED. MAIN DRAINS

4. HEF CONCENTRATE PIPING SHALL BE SCHEDULE 40 STAINLESS STEEL WELDED OR FILANGED FITTINGS ONLY.

SCREWED FITTINGS AND GROOVED/ROLLED EDGE COUPLINGS ARE PROHIBITED ON ANY CONCENTRATE PIPING EXCEPT AT THE FOAM CONCENTRATE STORAGE TANK AND THE PROPORTIONING VALVE CONNECTIONS.

5. INSTALL BASKET STRAINER HORIZONTALLY. PROVIDE 10 PIPE DIAMETERS OF STRAIGHT PIPE UPSTREAM, AND

5 PIPE DIAMETERS OF STRAIGHT PIPE DOWNSTREAM OF BASKET STRAINER.

FOR 11 x 17 USE GRAPHIC SCALE

8' 0 8' 16'

Notes:

................ ,.•.,s OF�••

I>, ... ... . .0 ..• •

;J:t.l 49TH \*\ =·····; ... , ................................ \ .....,• • l·····r··········--······················:·�·J \�\ SCOTT V. BELL /f##

•••• ME-7355 .•••:--..:••

. .. .. �-.�•••• ·••"<i5• ... . .. •• 0 ........... �'- ...

,1i'DFESSI �•••

KEYPLAN

AUISXA

.Al.A 111.ATIOH.A!. SU.AMI

�••u"""'"

"\: ;.-.A,. ... �� • u, il{I I Architecture . Engineering

Land Surveying Planning

2515 'A' Street 544 Fourth Avenue Anchorage, Alaska Fairbanks, Alaska 99503 99701

(907) 276-4245 {907) 452-2128

3031 Clinton Drive 290 North Willow St.

Suite 200 Wasilla, Alasko 99654 Juneau, Alaska 99801 {907)376-7815 (907)790-2901

Project:

REPAIR AIRCRAFT

MAINTENACE HANGER

BDLG 1176

EIEI.SON AFB, ALASKA

FI'QW-04-2254

ALASKA AIR NATIONAL GUARD

EIEU!ON AFB, ALASKA

Date Revision By

1 11-05 FL00RPLAN CHANGE WSL

Sheet Contents

NEW WORK - MECH ROOM PLAN

SPRINKLER SCHEMATIC AND DETAILS

Project Mgr. GVN Sheet No.

Drawn MW\/

Drawn M2.2 Checked GVN Date 10/14/05 USKH W.O. 693316

HIGH EXPANSION

FOAM COMPONENTS

TO BE REMOVED

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Rectangle

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

1376523256M Line

FOAM START STATIONS AND SIGNAGE TO BE

REMOVED. CABLES AND CONDUIT TO BE PROPERLY

TERMINATED AND ABANDONED IN PLACE.

1376523256M Line

1376523256M Rectangle

1376523256M Rectangle

1376523256M Rectangle

1376523256M Rectangle

1376523256M Rectangle

1376523256M Rectangle

TYPICAL

ANNUNCIATION 1-------1

CIRCUITS

(E) INFRARED/ULTRAVIOLET 1-&---&---&---&---&----'

FLAME SENSORS / \ / \ / \ / \ / \

TYPICAL

INITIATION

CIRCUITS

CONNECT TAMPER SWITCHES

ON SPRINKLER SYSTEMI--

TO ADDRESSABLE INTERFACE MODULE

CONNECT SPRINKLER SYSTEM

FLOW SWITCHES TO ADDRESSABLE

INTERFACE MODULES,-------�

EACH FLOW SWITCH SHALL

HAVE A UNIQUE ADDRESS

FIRE ALARM

CONTROL PANEL

BATTERY BOX

START ___ __,_ ______ 3" RED LETTERS ON YELLOW

OR LIME YELLOW BACKGROUND

FOAM

SYSTEM

,------7

I I

I FOAM I

I I I

D I

I I I I

I '------' II I

L ______ _J

MANUAL FOAM STATION SIGN

SCALE: NTS

WIRELESS

ANTENNA

ON ROOF

.,,,- COAXIAL

/ CABLE

REMOTE

ANNUNCIATOR

PANEL

RM 101W

SYSTEM INPUTS

FIRE ALARMS

MANUAL F /A STATIONS

SMOKE DETECTORS

HEAT DETECTORS

DUCT SMOKE DETECTORS

SINGLE HANGAR HEAT DETECTOR

MULTIPLE HANGAR HEAT DETECTORS

SPRINKLER FLOW SWITCHES

FOAM SYSTEM FILOW SWITCH

MANUAL FOAM STATION

LOW-LEVEL IR DETECTORS

SUPERVISORY SIGNALS

SPRINKLER TAMPER SWITCHES

FOAM SYSTEM TAMPER SWITCHES

CONTROL COMPONENT COMMON

TROUBLE CONDITION

TROUBLE CONDITIONS

LOW BATTERY VOLTAGE

CIRCUIT FAULT

SUPERVISED COMPONENT FAULT

AC POWER FAILURE

TROUBLE SIGNAL FROM HANGAR PANEL

ALARM SIGNAL FROM HANGAR PANEL

FOAM

SYSTEM

VALVE

FIRE PUMP #1

CONTROL

PANEL

FIRE PUMP #2

CONTROL

PANEL

PREACTION

SPRINKLER

VALVE

ANNUNCIATION AT LOCAL

PANELS

w c,:

....I u, z > 0 I 50

C C � z

X

X

X

X

X

X

X

X

X

X

(E) FOAM

CONTROL PANEL

w ....I

ID

....I (f)

I

C

X

X

X

X

X

X

X z :::;; z :::;;

:::E 0 c,:

:5 0

....I (.) ....I < C < z :::, :::, z (f) u, 0 > w >

5 I ....I I 0 :::, 0

C C 0 C � c,: � z f-

X

X

X w � z

0 C

I z w 0 c,:

a..

s z

C w a..

z 0

X

X

X

X

X

X

X

X

X

X

SUPPRESSION

SYSTEM

FUNCTIONS

� Vl e c,:

� w ::.::: <z ct::

a..

u, X X

X X

....I

Vl w ....I

ID

c,:

f-z

::IE

0 '-'

X

X

X

X

TRANSMIT SIGNALS TO FIRE DEPARTMENT

Vl

,c c,:

� § g :::;; 0 u... w Vl c,:

t;:; :5 il;

c,:

w w C< w w c,: c,: a.. c,: ,c < :::, :r:

Vl G:: ....I (.) c,: w

� u, � z z z C 0 0 ::.::: 0....I ....I N ....I ::::;; < ::::;; < z I ::IE ::IE z ::IE z ct:: c,:

� e 0 (.!) 0 (.!) a.. w '-' u, '-' u, u, a..

X

X

X

X

X

X X

X X

X X X

X X

X X

X

X

X

AUXLIARY

FUNCTIONS

c,:

C

I C

EVACUATION

SIGNALS

z

Vl z

ID

Ej z z 0 Vl ...__ ,c z

....I

� < ::IE 0 z w C ::IE :::, (.!)

f- (.)

:::, u, u, w :r:

c,:

Vl w ....I

C :§ ::IE

z ....I w <

� w 0 c,: u, fr c,: :r: G:: 5

X X

X X X

X X

X X X

X X

X X

X X X

X X X

X X

X

(E) HANGAR ANNUNCIATORS

TYPICAL HANGAR HEAT DETECTOR

CIRCUIT, 4 TOTAL IN CROSS ZONE

LAYOUT.

TYPICAL HANGAR HEAT DETECTOR

CIRCUIT, 4 TOTAL IN CROSS ZONE

LAYOUT.

MANUAL FOAM RELEASE STATIONS

Vl w

ID

c,:

I,;

w ....I

ID

X

X

X

X

CONNECT TO EXISTING SPRINKLER BELL

'--------------Cf-' FOAM SYSTEM FILOW SWITCH

FIRE ALARM RISER DIAGRAM

SCALE: NTS

-2

FOAM SYSTEM TAMPER SWITCHES

Notes:

•• ♦ ,"!-,:: . \_),- /J/ ""•• • , •. \ '.- ......... -./! , -- •

• N :,••• · .. ' •••,/,, f �c.-, ••• *••,I,,/♦ •

• ....,. • ,,--a , • --t *•··•·:.:, /' �

�.,;· .. �··7.··:··· ... , ... ';;Jl ... � ..... y . ..., ........ ...--....... . �/\':,,IHILII·' :cl. ::;cw.u-1:. :�.Ji:

). ¼ •• • "·> •, t.l- C ,,l>... � ._o>-' ,·s,·•.. .. - .. •·,--'.-<·:

• -<:,. •.. ... /· ::,.• • • '··/ci·- •• •• •> •

1 •••• •••• •

•·< .. · ,,_ ......... -··Ji"/. ♦ ••. �,1J-fS3\' .. Y�♦•

ALA�A

.Al.Fl HA11Cll\lA1. SUArul r,.,,,�""""'

U: il(H Architecture ' Engineering

Land Surveying . Planning

2515 'A' Street 544 Fourth Avenue Anchorage, Alaska Fairbanks, Alaska 99503 99701

(907) 276-4245 (907) 452-2128

3031 Clinton Drive 290 North Willow St.

Suite 200 Wasilla, Alaska 99654 Juneau, Alaska 99801 (907)376-7815 (907)790-2901

Project:

REPAIR AIRCRAFT

MAINTENACE HANGER

BDLG 1176

EIELSON AFB, ALASKA

FI'QW-04-2254

ALASKA AIR NATIONAL GUARD

EIELSON AFB, ALASKA

Date Revision By

Sheet Contents

FIRE ALARM

RISER DIAGRAM

Project Mgr. GVN Sheet No.

Drawn PBS Drawn EB Checked GMH Date 10/14/05 USKH w.o. 693316

1376523256M Rectangle

1376523256M Rectangle

1376523256M Callout

REPLACE RELEASING PANEL

1376523256M Callout

REPLACE BOTH CONTROL PANELS

Attachment 7 - B1176 As-built (2005) v2
T1
M0.1
Attachment 8 - Photos 1
Attachment 7 - B1176 As-built (2005) v2
E0
Attachment 7 - Foam Pull Stations
Attachment 8 - Photos 2
Attachment 7 - B1176 As-built (2005) v2
E9

File details come from the government source that posted it. Updated .