Attachment 6 - Drawings ELECTRICAL LIGHTING SECOND FLOOR PLAN.pdf

PDF 5 MB Posted

Attached to
Y1DB--Construct Addition and Renovations - Joint Ambulatory Care Clinic - Pensacola FL
Solicitation number
36C77623R0103
Issued by

About this file

This package of construction documents outlines requirements for an addition and renovations project at the Joint Ambulatory Care Clinic in Pensacola, Florida. The project involves upgrades and renovations to existing medical facilities as well as construction of new parking areas. Drawings and specifications cover proposed architectural, mechanical, electrical, and plumbing systems. Estimated project costs total over $10 million. The solicitation is open to small businesses with a response date in late 2022 and anticipated award in early 2023.

View the file

Other files

File Type Posted
Amendment 0006 - Attachment 01 - 23 64 00 - Packaged Water Chillers.pdf PDF
36C77623R0103 0006.pdf PDF
36C77623R0103 0005 - Attachment 01 - Cooler Specifications.pdf PDF
36C77623R0103 0005.pdf PDF
520-331_JACC_pkg1_Addendum1_20240221.pdf PDF
Attachment - VOL 3 BINDER.pdf PDF
Attachment - VOL 1 BINDER.pdf PDF
Attachment - VOL 2 BINDER.pdf PDF
36C77623R0103 0004.pdf PDF
Attachment - RFI Responses 2.29.2024.xlsx XLSX spreadsheet
Attachment - Limitations on Subcontracting.docx DOCX document
Attachment CON-100 INSTRUCTIONS.docx DOCX document
Attachment - Contractor Safety - Environmental Form.docx DOCX document
Attachment - Pensacola JACC 2nd site visit sign in.pdf PDF
Attachment - RFI Responses 2.20.2024.xlsx XLSX spreadsheet
Attachment - JACC 2005 Geotechnical Report.pdf PDF
Attachment - 520-331_JACC_pkg1_Addendum1_20240209.pdf PDF
36C77623R0103 0003.pdf PDF
2nd Site Visit Instructions - 520-331 JACC Minor Lab Infusion.pdf PDF
36C77623R0103 0002.pdf PDF
Attachment 8 - WD FL20240203 - 1.05.2024.pdf PDF
JACC Minor Site Visit Sign in 1-9-2024.pdf PDF
36C77623R0103 0001.docx DOCX document
520-331.JACC.Pre-Bid.Presentation.010924.Redux.pdf PDF
Attachment 7 - Limitations on Subcontracting.docx DOCX document
Attachment 4 - Drawings - ARCHITECTURAL DETAILS - EXTERIOR.pdf PDF
Attachment 10 - Site Visit Instructions - 520-331 JACC.pdf PDF
Attachment 5 - Drawings - PLUMBING EXISTING DEMO GROUND FLOOR.pdf PDF
Attachment 3 - Drawings - CIVIL SIGNAGE AND STRIPING.pdf PDF
Attachment 9 - Brand Name JA JACC Addition 05172023.pdf PDF
36C77623R0103_1.docx DOCX document
Attachment 8 - WD FL20230203 01.13.2023.pdf PDF
Attachment 2 - Drawings - COVER SHEET GI000.pdf PDF
Attachment 1 -Specifications 221007 reduced rev2 -.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OS OS

O S

O S

O S

O S

OS

OS O

S

O S

O S

O S

O S

O S

O S

OS

OS

OS

OS

OS

O S

OS

OS

O S

O S

O S

O S

OS

OS

O S

O S

O S

OS

3 33

OS

OS

OS

E E

D D

C C

B B

RESTROOM

2G118

RESTROOM

2G116

RESTROOM

2G114

RESTROOM

2G112

PHLEBOTOMY

2G101

SPECIMEN DROP OFF

2G111

SPECIMEN 09

2G113

LAB OFFICE TOUCHDOWN

2G123

STAFF RESTROOM

2G126LAB OFFICE

2G127

CORRIDOR

C2-101

COLD STORAGE

2G121

LAB OFFICE

2G125

WAITING ROOM

2G100

RECEPTION

2G103

SPECIMEN 08

2G105

SPECIMEN 07

2G107

SPECIMEN 06

2G109

CORE LAB

2G117

SPECIMEN 05

2G110

SPECIMEN 04

2G108

SPECIMEN 03

2G106

SPECIMEN 02

2G104

SPECIMEN 01

2G102

RESTROOM

2G100A

STAFF RESTROOM

2G144

VESTIBULE

2G117A

CORRIDOR

C2-99

CONFERENCE/ BREAK ROOM

2G143

TREATMENT 2

2G135C

TREATMENT 1

2G135B

NURSE STATION

2G135A

TREATMENT 3

2G135D

TREATMENT 4

2G135E

TREATMENT 5

2G135F

TREATMENT 6

2G135G

TREATMENT 7

2G135H

TREATMENT 8

2G135I

TREATMENT 9

2G135J

TREATMENT 10

2G135K

MED ROOM

2G142

RESTROOM

2G139

RESTROOM

2G138

INFUSION CLINIC

2G135

SOILED UTILITY

2G140

BULK STORAGE

2G120

STERILE SUPPLY

2G141

EXAM / CONSULT

2G136

ADMIN SUPPORT

2G137

RECEPTION

2G134

WAITING ROOM

2G133

HAC

2G132

STERILE SUPPLY

2G119

ELECTRICAL

2G131

FILE CLOSET

2G130

CONSULT

2G129

CORRIDOR

C2-97

CONSULT

2G128

NEG. PRESSURE LAB

MICROBIOLOGY

2G122

CORE LAB

2G117CORE LAB

2G117

INFUSION CLINIC

2G135

SPECIMEN 10

2G115

B

B

B

B

B

B

B

B

B

B

B B B H H H H H H

H H

H H

B

B

H

H H

H

A A A

A

A

B

B

B

B

B

B

B

B

B

B

B BBB B B

B BB B

B B

B

B

B

B

B

B

B

B B B B B B

B B

B B

B B

B

B

B

B

H H

H H

A

A

AA

A AA

A

A

A A A A

A A

A

A A

A

A

A A

A

A

A

AA

A1

A A A

A

A AAAAA

A A A A

A

A

A

A

A

A

A

C C

C C

C C

C C

C

C

C C

C C

C C

F

F

X

X

X

X

A

AAAA

A

A A A

A A A

A

X

HH

H H

A

A

A

A A

A

A A

A

A

A

A A

A

A

A

A

A

A

A A A

A A

AA

TELECOM ROOM

2G145

F F F

A

A A

1 1

B B

R1

H2F - 3

X

R1

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

X

H2F - 11

EM

H2F - 13

H2F - 1

H2F - 9

H2F - 7

ELH2F - 1

H2F - 5

EM

A

EM

EM

(TYP.)

EM

3 TYP.

TYP.

EM

ECH2F - 7

C C C

C

C

C

C

C

C

C C C

CCC

C

C

A. NO WORK REQUIRED IN HATCHED AREAS. ALL LIGHTING FIXTURES,

CONTROLS, POWER DEVICES, CIRCUITING AND ASSOCIATED

WIRING SHALL BE EXISTING TO REMAIN.

B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND

SLABS ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR THE

RATED APPLICATION.

C. PROVIDE DUAL TECHNOLOGY OCCUPANCY/VACANCY SENSORS

FOR AUTOMATIC LIGHTING CONTROL IN ALL COMMON SPACES

EXCEPT ELECTRICAL, MECHANICAL AND IT ROOMS.

D. ALL OCCUPANCY AND VACANCY SENSORS SHALL TURN OFF

WITHIN 20 MINUTES OF THE SPACE BECOMING UNOCCUPIED.

E. OCCUPANCY SENSORS SHALL FAILSAFE "ON".

F. LIGHTING CONTROL CONTRACTOR SHALL PROVIDE CONTROLS

AND SENSORS WITH APPROPRIATE COVERAGE PATTERNS AND

ADJUSTMENTS OF SENSITIVITY LEVELS TO PREVENT NUISANCE

SWITCHING ON AND OFF OF LIGHTS.

G. FIXTURES LOCATED IN CORRIDORS, NURSE STATIONS, WAITING

ROOM AND ALL COMMON AREAS SHALL BE CONTROLLED BY

EXISTING BMS SYSTEM VIA LOCAL LCP. LCP IS LOCATED IN LOCAL

ELECTRICAL ROOM. LCP SHALL BE TIED TO EXISTING BMS

LOCATED IN MECHANICAL PENTHOUSE. COORDINATE EXACT

LOCATION, WIRING, AND ALL OTHER ASSOCIATED REQUIREMENTS.

H. FOR ALL FIXTURES CONTAINING EMERGENCY BATTERY PACKS,

THEY SHALL BE INSPECTED AND TESTED MONTHLY. SEE LIGHTING

FIXTURE SCHEDULE ON SHEET E-502 FOR ADDITIONAL

INFORMATION.

I. UPON ACTIVIATION OF THE BUILDING FIRE ALARM, LIGHT FIXTURES

DESIGNATED AS LIFE SAFETY SHALL AUTOMATICALLY TURN "ON"

AND LOCAL LIGHTING CONTROLS ARE OVERRIDEN. PROVIDE

RELAY AS REQUIRED.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

N

SEC 6

(F)

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:4

P

M

EL102F

ELECTRICAL LIGHTING SECOND FLOOR PLAN -

AREA F

520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F3 ELECTRICAL LIGHTING SECOND FLOOR PLAN - AREA F

1 ALL LIGHT FIXTURES IN THIS AREA SHALL BE CONTROLLED BY THE

EXISTING BUILDING MANAGEMENT SYSTEM (BMS) LOCATED IN THE

MECHANICAL PENTHOUSE VIA LOCAL LIGHTING CONTROL PANEL (LCP).

COORDINATE SCHEDULE TIME OF DAY WITH VA.

2 MANUAL OVERRIDE SWITCH FOR CORRIDOR LIGHTING.

3 THE INTENT FOR FIXTURES DESIGNATED WITH A 'H' IN THE TREATMENT

AREA IS TO HAVE THEM CONTROLLED LOCALLY BY THE CHAIR

CONTROLLER IN THAT ROOM.

Revisions: Date:

2022.09.23

10.07.2022

2022.10.07

J

J

J

J

J

J

J J

J

J

J

J

JJ

J

J

J

J

J

J J

J

J

J J

J

J

J

J

J

J

J

J J

J

J

M

J

J

J

J J

J

J

J

J

J JJ

J JJ

J JJ

J JJ

JJJ

JJ J

JJ J

J

J

J

J

J

JJ

J

J

J

J

J

J

J J

J J

J

J

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J

J

J J

J

J J

J

J

J

J

J

J

J

J

J J

J

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

E E

D D

C C

B B

H2F

T-H2F

L2F2

ELH2F

ECH2F

T-ECH2F

ECL2F

CONSULT

2G128

CONSULT

2G129

FILE CLOSET

2G130 ELECTRICAL

2G131

CORRIDOR

C2-101

LAB OFFICE

2G127

STAFF RESTROOM

2G126

LAB OFFICE

2G125

LAB OFFICE TOUCHDOWN

2G123

RESTROOM

2G118

SPECIMEN 10

2G115

SPECIMEN 09

2G113RESTROOM

2G116

RESTROOM

2G114

SPECIMEN DROP OFF

2G111

COLD STORAGE

2G121

BULK STORAGE

2G120

STERILE SUPPLY

2G119

HAC

2G132

NEG. PRESSURE LAB

MICROBIOLOGY

2G122

STERILE SUPPLY

2G141

WAITING ROOM

2G133

CORE LAB

2G117

SPECIMEN 06

2G109

SPECIMEN 07

2G107

SPECIMEN 08

2G105

RECEPTION

2G103

WAITING ROOM

2G100 PHLEBOTOMY

2G101

RESTROOM

2G100A

SPECIMEN 01

2G102

SPECIMEN 02

2G104

SPECIMEN 03

2G106

SPECIMEN 04

2G108

SPECIMEN 05

2G110

CONFERENCE/ BREAK ROOM

2G143

CORRIDOR

C2-99

VESTIBULE

2G117A

STAFF RESTROOM

2G144

TREATMENT 3

2G135D

NURSE STATION

2G135A

TREATMENT 4

2G135E

TREATMENT 5

2G135F

MED ROOM

2G142

TREATMENT 6

2G135G

TREATMENT 7

2G135H

TREATMENT 10

2G135K

TREATMENT 8

2G135I

TREATMENT 9

2G135J

INFUSION CLINIC

2G135

SOILED UTILITY

2G140

RESTROOM

2G139

RESTROOM

2G138

ADMIN SUPPORT

2G137

RECEPTION

2G134

EXAM / CONSULT

2G136

CORRIDOR

C2-97

RESTROOM

2G112

REF

CORE LAB

2G117TV

9' AFF

QMATIC TV

+60" AFF

COPIER

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

STACKED

TV

+60" AFF

TELECOM ROOM

2G145

ECL2FIT

SENSOR

COPIER

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

WARMING

CABINET

UC FRZ

SENSOR

SENSOR

TV

+72" AFF

UC

REF

OMNI

CELL

OMNI

CELL

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

E9

E8

E15

E16

PRINTER PRINTER

E12

E14

E13

E8

E11

E10

PRINTER

PRINTER

39" AFF

E17

E13

E2

E1F E1E

E1D

E1C

E1B

E1A

COPIERREF FRZ FRZ FRZ

PRINTER

PRINTER

E18

E25E26

EFRE2

EFRE3

E4

E3

SENSOR

E5

E5A

E5B

E5C

E6C

E6

E6A

E6B

E7

PRINTER

REF FRZ

E20 E23

E24

E22

E19

(TYP.)

(TYP.)

E-7

OMNI

CELL

LCP

EQH2F

ECL2FIT - 1

ECL2FIT - 3

E1G

ECL2F2 - 12

ECL2F2 - 14

ECL2F2 - 47

ECL2F2 - 44

ECL2F2 - 45

ECL2F2 - 43

L2F - 8

ECL2F2 - 27

ECL2F2 - 25

ECL2F2 - 23

ECL2F2 - 35

ECL2F2 - 37

ECL2F2 - 39

ECL2F2 - 33

ECL2F2 - 21

L2F2 - 3

L2F2 - 1

L2F2 - 5

L2F2 - 7

L2F2 - 43

L2F2 - 11

L2F - 17

L2F - 19

L2F - 21

L2F - 23

L2F - 12

L2F2 - 13

L2F - 25

GFCI

GFCI

GFCI

GFCI

GFCI

L2F2 - 15

L2F2 - 17

L2F2 - 19

L2F2 - 23

L2F2 - 8

L2F2 - 10

L2F2 - 12

L2F2 - 14

L2F2 - 16

L2F2 - 41

L2F2 - 20

L2F2 - 22

L2F2 - 24

L2F2 - 26

L2F2 - 28

GFCI

GFCI

ECL2F - 29

ECL2F - 31

ECL2F - 33

ECL2F - 35

L2F2 - 30

L2F2 - 32

L2F2 - 34

L2F2 - 36

L2F2 - 38

GFCI

GFCI

ICE MAKER

ECL2F - 30

ECL2F - 32

ECL2F - 37

ECL2F - 3

L2F2 - 18

ECL2F2 - 41

EWC

GFCI

ECL2F2

E7A

L2F2 - 25 L2F2 - 27

L2F2 - 29ECL2F2 - 1 ECL2F2 - 3

ECL2F2 - 5

GFI

GFI

L2F - 1

E6

E5

TR

TR

TR

TR

TR

L2F2 - 37

ECL2F2 - 22

ECL2F2 - 20

KIOSK

L2F2 - 9

ECL2F2 - 42

ECL2F2 - 22

15 15

ECL2F2 - 10

ECL2F2 - 8

ECL2F2 - 49

ECL2F2 - 51

ECL2F2 - 53

ECL2F2 - 55 ECL2F2 - 57

ECL2F2 - 52

L2F2 - 21

ECL2F2 - 54

ECL2F2 - 56

ECL2F2 - 58

ECL2F2 - 60

ECL2F2 - 59 ECL2F2 - 61

ECL2F2 - 62

ECL2F2 - 64

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

SENSOR

39" AFF

39" AFF

TREATMENT 1

2G135B

TREATMENT 2

2G135C

L2F - 1

(TYP.)

L2F - 3

L2F - 1

L2F2 - 31

ECL2F2 - 7

L2F - 3

L2F2 - 33

ECL2F2 - 9

L2F - 3

L2F2 - 35

ECL2F2 - 11

L2F - 5

L2F2 - 42

ECL2F2 - 15

L2F - 5

L2F2 - 40

ECL2F2 - 13

L2F - 7

ECL2F2 - 17

L2F2 - 44

ECL2F - 39

L2F - 7

ECL2F2 - 19

L2F2 - 46

ECL2F2 - 63

ECL2F2 - 40

ECL2F2 - 38

39" AFF

39" AFF

ECL2F2 - 66

39" AFF

39" AFF

39" AFF

39" AFF

39" AFF

ECL2F - 60

ECL2F - 60

GBB

TGB

MED GAS ALARM PANEL

L2F

L2FIT

ECL2FIT - 7

ECL2FIT - 11

ECL2FIT - 8

ECL2FIT - 9

UPS

A A BB

A A BB

ECL2FIT - 17,19,21

ECL2FIT - 10

ECL2FIT - 12,14,16

ECL2FIT - 18,20

ECL2FIT - 22,24

L2FIT - 1,3,5

L2FIT - 7,9,11

ECL2FIT - 5

L2FIT - 13,15

L2FIT - 17,19

(TYP.)

A. NO WORK REQUIRED IN HATCHED AREAS. ALL LIGHTING FIXTURES,

CONTROLS, POWER DEVICES, CIRCUITING AND ASSOCIATED

WIRING SHALL BE EXISTING TO REMAIN.

B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND

SLABS ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR THE

RATED APPLICATION.

C. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY WALL

MOUNTED ITEM (ELECTRICAL/DATA/LIGHT) WITH ARCHITECT PRIOR

TO INSTALLATION.

D. FINAL LOCATION OF POWER DEVICES SHALL BE COORDINATED

WITH THE VA DURING WALK THROUGH PRIOR TO ROUGH-IN.

E. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO

ORDERING AND INSTALLATION.

F. ELECTRICAL CONTRACTOR SHALL VERIFY ALL POWER AND

CONNECTION REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO

ORDERING AND INSTALLATION. VERIFY ALL DEVICE LOCATION AND

MOUNTING HEIGHT. MAKE ADJUSTMENT IN FIELD TO MATCH

ACTUAL EQUIPMENT NAMEPLATE BEING INSTALLED.

G. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

H. REFER TO ONE-LINE DIAGRAM AND PANEL SCHEDULES FOR

ADDITIONAL INFORMATION.

I. ALL SPECIAL SYSTEMS FURNITURE LOCATED IN THE TREATMENT

SPACES SHALL BE EQUIPPED WITH POWER/NURSE CALL/DATA

FLOOR BOX CONNECTIONS. CONTRACTOR SHALL VERIFY ALL

CONNECTION REQUIREMENTS FOR SELECTED FURNITURE PRIOR

TO INSTALLATION AND BIDDING. POWER SHALL BE HARDWIRED TO

MODULES. ROUTE CABLES THROUGH CABINETRIES AS SHOWN ON

INSTALLATION MANUAL. PROVIDE DUPLEX, DATA AND NURSE CALL

DEVICES AS REQUIRED WITHIN MODULES FOR A FULLY

FUNCTIONAL SYSTEM.

J. FOR ALL OUTLETS LOCATED IN THE CORE LAB AREA, SEE A-404-06,

408 AND LAB CASEWORK FOR ADDITIONAL DETAILS

K. ALL OUTLETS SHALL BE COORDINATED WITH FINAL FURNITURE

LAYOUT TO ENSURE ALL DEVICES ARE ACCESSIBLE.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

LAB EQUIPMENT SCHEDULE

CODE EQUIPMENT DESCRIPTION VOLTS PHASE WATTS NEMA PLUG AMPS/POLES CIRCUIT NUMBER

EFRE2 BIOMED FREEZER

EFRE3 BIOMED FREEZER

E1A IRIS IQ200 ELITE ANALYZER

E1B ARKRAY AUTION MAX AX-4030

*E1C ARKRAY AUTION MAX AX-4030

*E1D ARKRAY CPU

E1E ARKRAY MONITOR

E1F ARKRAY PRINTER

E1G ARKRAY UPS

E2 CENTRIFUGE - THERMO ELECTRON CL2

E3 CENTRIFUGE - STATSPIN EXPRESS 3

E4

E5 BECKMAN ANALYZER DXC 660i

E5A BECKMAN ANALYZER UCTA

E5B BECKMAN ANALYZER DXI 600

E5C EVOQUA ELGA DV 25

E6 BECKMAN ANALYZER DXC 660i

E6A BECKMAN ANALYZER UCTA

E6B BECKMAN ANALYZER DXI 600

E6C EVOQUA ELGA DV 25

*E7 REMISOL SYSTEM - LABTRONICS

*E8 ROCKER-TEST TUBE

*E9 ROCKER-TEST TUBE

*E10 SEDRATE ANALYZER - EXCYTE 20

*E11 G8 HPLC ANALYZER - TOSOH

E12 HEMATEK 3000 SLIDE STAINING

E13 OLYMPUS MICROSCOPE - BX45-TF-S

E14 CELLAVISION DM1200

E15 UNICEL DXH 900

E16 UNICEL DXH 900

*E17 STAGO STA COMPACT ANALYZER

E18 CENTRIFUGE LABORATORY

*E19 POLYMEDCO / OC-AUTO MICRO 80

E20 ABBOT ID NOW ANALYZER

E21 FLAMMABLE CABINET MEDLINE

E22 FUME HOOD - LABCONCO

E23 VORTEX MIXER - GENIE 2

E24 BD MAX ANALYZER

E25 VORTEX MIXER - GENIE

E26 QUICKSPIN PLUS / EBA200S

E27 FLAMMABLE CABINET

CENTRIFUGE - SILENCER S2510

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

220-240 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

120 1

208 1

208 1

120 1

120 1

120 1

120 1

NA

120 1

120 1

120 1

120 1

120 1

NA

360 5-20P 20A/1P

1200 5-20P 20A/1P

4800 L6-20R 20A/2P

1800 5-20P 20A/1P

1800 5-20P 20A/1P

1200 5-20P 20A/1P

220-240 4800 L6-20R 20A/2P

1800 5-20P 20A/1P

1800 5-20P 20A/1P

1200 5-20P 20A/1P

1200 5-20P 20A/1P

108 5-15P 20A/1P ECL2F2 - 36

108 5-15P 20A/1P

200 5-20P 20A/1P ECL2F2 - 34

200 5-20P 20A/1P ECL2F2 - 34

420 5-20P 20A/1P

180 5-20P 20A/1P

1200 5-20P 20A/1P

720 5-20P 20A/1P

1000 5-20P 20A/1P

1664 6-20P 20A/2P

1664 6-20P 20A/2P

1800 5-20P 20A/1P ECL2F2 - 26

175 5-20P 20A/1P

175 5-20P 20A/1P

114 5-20P 20A/1P ECL2F2 - 24

200 5-20P 20A/1P

200 5-20P 20A/1P

200 5-20P 20A/1P ECL2F2 - 31

1560 5-20P 20A/1P ECL2F2 - 29

1 114 5-20P 20A/1P

1680 5-20P 20A/1P

200 5-20P 20A/1P

150 5-20P 20A/1P

150 5-20P 20A/1P

100 5-20P 20A/1P

100 5-20P 20A/1P

100 5-20P 20A/1P

800 5-20P 20A/1P

ECL2F - 1

NOTE:

1) ALL EQUIPMENT TO BE ON EMERGENCY POWER.

2) SEE ARCHITECTURAL PLANS FOR ELEVATIONS AND ADDITIONAL INFORMATION.

3) COORDINATE ALL POWER REQUIREMENTS WITH EQUIPMENT INSTALLATION MANUAL PRIOR TO INSTALLATION/ORDERING.

4) *MOUNT ABOVE COUNTER; 39" AFF.

ECL2F2 - 53

ECL2F - 5

ECL2F - 7,9

ECL2F - 11

ECL2F - 13

ECL2F - 15

ECL2F - 8,10

ECL2F - 12

ECL2F - 14

ECL2F - 16

ECL2F - 18

ECL2F - 22

ECL2F - 17

ECL2F - 19,21

ECL2F - 23,25

ECL2F - 24

ECL2F - 26

ECL2F - 27

ECL2F - 28

ECL2F - 20

ECL2F - 59

ECL2F - 45

ECL2F - 47

ECL2F2 - 34

ECL2F2 - 34

ECL2F2 - 32

ECL2F2 - 28 ECL2F2 - 30

ECL2F - 45

ECL2F - 45

ECL2F - 45

ECL2F - 45

ECL2F - 45

ECL2F - 41 ECL2F - 43 ECL2F - 34

ECL2F - 36

ECL2F - 40 ECL2F - 49 ECL2F - 38

ECL2F - 42

E7A REMISOL SYSTEM - SERVER STATION 120 1 1200 5-20P 20A/1P ECL2F - 51

ECL2F - 53,55

ECL2F - 56,58

ECL2F2 - 31

N

SEC 6

(F)

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:2

P

M

EP102F

ELECTRICAL POWER SECOND FLOOR PLAN -

AREA F

520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F3 ELECTRICAL POWER SECOND FLOOR PLAN - AREA F

1 PROVIDE POWER TO FURNITURE FEED. COORDINATE TERMINATION

REQUIREMENTS WITH FURNITURE VENDOR.

2 IG CIRCUIT TO BE PROVIDED WITH DEDICATED NEUTRAL AND ISOLATED

EQUIPMENT GROUND FROM MAIN SERVICE BONDING LOCATION.

3 PROVIDE 1-1/4" CONDUIT FOR TV/COMMUNICATIONS AT FURNITURE FEED.

COORDINATE TERMINATION REQUIREMENTS WITH FURNITURE VENDOR.

PROVIDE CABLE WITH ENOUGH SLACK TO MAKE ALL CONNECTIONS. ALL

CABLES SHALL ORIGINATE FROM CLOSEST TELECOMMICATION BACKBOARD.

4 TTB, TELEPHONE TERMINAL BACKBOARD - PROVIDE (2) COATS OF GRAY FLAME

RETARDANT PAINT OR STAMPED/MARKED LISTED FIRE RATED PLYWOOD

BACKBOARD.

5 JUNCTION BOX FOR INFUSION PUMPS. COORDINATE EXACT LOCATION WITH VA

PRIOR TO INSTALLATION.

6 RECEPTACLE FOR TREATMENT CHAIR. COORDINATE EXACT LOCATION WITH VA

PRIOR TO INSTALLATION.

7 WALK-IN COOLER EVAPORATOR COIL. PROVIDE ADDITIONAL 3/4" CONDUITS

WITH CONTROL WIRES TO COOLER CONTROL PANEL AND EVAPORATOR

WITHIN UNIT. COORDINATE ALL REQUIREMENTS PER MANUFACTURER'S

SPECIFICATIONS.

8 JUNCTION BOX FOR WALK-IN COOLER LIGHTS.

9 JUNCTION BOX FLUSH MOUNTED WITH FLOOR. PROVIDE POWER AND DATA

FOR FURNITURE FEED TO SERVE WORKSTATION. RUN WIRES AND CIRCUIT AS

SHOWN, COORDINATE EXACT LOCATION AND DIMENSIONS WITH CASEWORK

DRAWINGS PRIOR TO INSTALLATION.

10 PROVIDE RECEPTACLE AT 72" AFF FOR LAB STAT BOARD. SEE SPECIAL

SYSTEMS PLANS FOR DATA LOCATION.

11 ANALYZER LEFT FACE HOOKUP WALL. SEE ARCHITECTURAL DRAWINGS Q-401F

FOR ELEVATIONS. PROVIDE (1) QUAD OUTLET AND (1) NEMA L6-2OR OUTLET.

EACH OUTLET SHALL BE PROVIDED WITH A DEDICATED CIRCUIT. SEE "LAB

EQUIPMENT SCHEDULE" FOR EQUIPMENT CIRCUIT NUMBER AND COORDINATE

EQUIPMENT LAYOUT AS REQUIRED.

12 ANALYZER RIGHT FACE HOOKUP WALL. SEE ARCHITECTURAL DRAWINGS

Q-401F FOR ELEVATIONS. PROVIDE (1) QUAD OUTLET AND (1) 4 DATA PORT

OUTLET. EACH OUTLET SHALL BE PROVIDED WITH A DEDICATED CIRCUIT. SEE

"LAB EQUIPMENT SCHEDULE" FOR EQUIPMENT CIRCUIT NUMBER AND

COORDINATE EQUIPMENT LAYOUT AS REQUIRED.

13 JUNCTION BOX FOR UNDERCOUNTER LIGHT FIXTURE MOUNTED 62" AFF.

MOUNT ASSOCIATED LIGHT SWITCH 50" AFF.

14 RECEPTACLES SHOWN ON ANALYZER ISLAND ARE SHOWN FOR REFERENCE

ONLY. ACTUAL HOOKUP ARE ON ADJACENT WALL. SEE KEYNOTES # 11-12 AND

LAB EQUIPMENT SCHEDULE ON THIS SHEET FOR ADDITIONAL INFORMATION.

15 JUNCTION BOX MOUNTED AT 18" AFF FOR CASEWORK POWER. COORDINATE

TERMINATION REQUIREMENTS WITH CASEWORK DRAWINGS. PROVIDE

ENOUGH CABLE SLACK TO MAKE ALL CONNECTIONS. COORDINATE EXACT

LOCATION, REQUIREMENTS AND CONNECTIONS WITH LAB CASEWORK

DRAWINGS/VENDOR, MODULAR PHARMACY SOLUTIONS, MPS.

16 RECEPTACLE FOR EQUIPMENT E3 SHOWN ON CASEWORK SHOWN FOR

REFERENCE ONLY. CIRCUIT IS COMING OFF OF ADJACENT WALL AND

THROUGH FURNITURE CHASE.

17 JUNCTION BOX LOCATED ABOVE CEILING FOR CASEWORK POWER.

COORDINATE TERMINATION REQUIREMENTS WITH CASEWORK DRAWINGS.

PROVIDE CONDUIT ABOVE CEILING FROM JUNCTION BOX TO FURNITURE

CHASE AND ENOUGH CABLE SLACK TO MAKE ALL CONNECTIONS. COORDINATE

EXACT LOCATION, REQUIREMENTS AND CONNECTIONS WITH LAB CASEWORK

DRAWINGS/VENDOR, MODULAR PHARMACY SOLUTIONS, MPS.

18 JUNCTION BOX FOR DW SHUT OFF TO STAFF RESTROOM CONTROLLER.

COORDINATE EXACT REQUIREMENTS AND LOCATION WITH PLUMBING AND

OWNER PRIOR TO INSTALLATION.

19 PROVIDE 3/4" CONDUIT NURSE CALL AT FURNITURE FEED. COORDINATE

TERMINATION REQUIREMENTS WITH FURNITURE VENDOR. PROVIDE CABLE

WITH ENOUGH SLACK TO MAKE ALL CONNECTIONS. ALL CABLES SHALL

ORIGINATE FROM NURSE CALL MASTER STATION.

20 JUNCTION BOX MOUNTED ABOVE CEILING FOR UNDERCOUNTER LIGHT

FIXTURE MOUNTED 62" AFF. MOUNT ASSOCIATED LIGHT SWITCH 50" AFF.

21 STACKED DRY-TYPE TRANSFORMERS. CONTRACTOR SHALL PROVIDE STACK

MOUNTING STRUCTURE TO SUPPORT TRANSFORMER.

22 PROVIDE OVERHEAD POWER DROP CORD WITH L21-20 RECEPTACLE.

SPECIAL RECEPT. - SEE NEMA PLUG COLUMN ABOVE FOR SPECIFIC EQUIPMENT OUTLET REQUIREMENTS.

Revisions: Date:

2022.09.23

M

M

E E

D D

C C

B B

A.9 A.9

EF-2F-2

WP

EF-2F-L2

EF-2F-1

30/3P/3R

EQH2F - 8,10,12

30/3P/3R

WP

ECL2F2 - 18

DSSO-2G131

DSSO-2G145

30/2P/3R

30/2P/3R

GFI

WP

GFI

WP

(TYP.)

ECL2F2 - 16

ECL2F2 - 46,48

ECL2FIT - 13,15

30/2P/3R

COOLER

30/2P/3R

COOLER

LPH - 27,29

LPH - 23,25

EQH2F - 1,3,5

EF-2F-L1

L2F2 - 39

A. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY

REVIEW AND UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS

INCLUDES BUT IS NOT LIMITED TO ALL DRAWINGS, SPECIFICATION

SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC IN NATURE.

THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR

SHALL REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY

FIELD CONDITIONS WITHOUT EXTRA COST TO THE OWNER. ANY

MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE

ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL

REFLECT THE TOTAL COST OF THE NEW EQUIPMENT AND

MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT

WRITTEN CONSENT AND APPROVAL FROM ENGINEER AND

ARCHITECT.

B. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL

RATED WALLS, CEILING AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIAL

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILING AND

SLABS ASSEMBLY. CONTRACTOR SHALL PROVIDE AN ASSEMBLY

INSTALLED IN ACCORDANCE WITH UL FOR THE RATED APPLICATION.

C. CONTRACTOR SHALL INSTALL LIGHTNING PROTECTION SYSTEM

REQUIRED TO COMPLY WITH NFPA 780 AND MEET THE

REQUIREMENTS OF UL 96A. CONTRACTOR MAY NEED TO ADD

ADDITIONAL AIR TERMINALS, CONDUCTORS, BONDS, CONNECTORS,

ETC. TO MEET CODE COMPLIANCE. PROVIDE A UL LETTER OF

FINDINGS FOR LIGHTING PROTECTION SYSTEM.

D. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING

AND INSTALLATION.

E. ELECTRICAL CONTRACTOR SHALL VERIFY ALL POWER AND

CONNECTION REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO

ORDERING AND INSTALLATION. VERIFY ALL DEVICE LOCATION AND

MOUNTING HEIGHT. MAKE ADJUSTMENT IN FIELD TO MATCH ACTUAL

EQUIPMENT NAMEPLATE BEING INSTALLED.

F. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

G. REFER TO ONE-LINE DIAGRAM AND PANEL SCHEDULES FOR

ADDITIONAL INFORMATION.

H. DISCONNECTS ARE SHOWN MOUNTED ON ASSOCIATED HVAC UNIT

IS FOR DIAGRAMMATICAL PURPOSES ONLY. DISCONNECTS SHALL

NOT BE INSTALLED ON HVAC EQUIPMENT. DISCONNECTS SHALL BE

PROVIDED WITH WEATHERPROOF RESISTANT STAND ALONE

SUPPORTING HARDWARE RATED FOR DISCONNECT WEIGHT AND

WIND LOAD.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

N

SEC 6

(F)

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:3

P

M

EP103F

ELECTRICAL ROOF PLAN - AREA F 520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F3 ELECTRICAL ROOF PLAN - AREA F

1 EXTEND BARE COPPER WIRE TO EXISTING LIGHTNING PROTECTION

SYSTEM DOWN CONDUCTORS AS REQUIRED.

2 TIE ROOF TOP HVAC EQUIPMENT TO LIGHTNING PROTECTION

SYSTEM.

3 RELOCATED WP JUNCTION BOX FOR EXISTING SATELLITE. EXTEND

CONDUIT AND WIRE AS NEEDED TO MAINTAIN CONTINUITY.

COORDINATE RELOCATION OF SATELLITE WITH VA/COR/NAVY FOR

NAVY MIST TRAINING SYSTEM. RELOCATION SHALL RESULT IN

MINIMAL DISRUPTION OF SERVICE.

4 PROVIDE MOUNTING STRUCTURE AS REQUIRED. CONDUIT SHALL

NOT BE USED AS A SUPPORT.

5 COLD STORAGE COOLER CONDENSER.

Revisions: Date:

2022.09.23

TV

TV

TV

TV

N N

N

N

N

N

N

N

N

N

N

N

N

N

N

N

N

E

E E

E E

E

E

E E E

E E

E

E E

E E

PA PA

PA

PA

PA PA

PA

PA

PA

PA

PA

PA

PAPA

PA

PA

J

AC

J

AC R

AC

R

R AC

D

P S

R

R

J

AC

AC

R

AC

R

AC

DPS

J

DPS AC D P

R

AC

AC

AC

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

J

V

TV

V

TV

V

TV

V

S

E

TV

D

V

ES

ML

DC

CL

CR

MD

S

N

TV

N

N

P R

D

DPS

AC

D

E E

D D

C C

B B

WAITING ROOM

2G100

RESTROOM

2G100A

SPECIMEN 01

2G102

SPECIMEN 02

2G104

SPECIMEN 03

2G106

SPECIMEN 04

2G108

SPECIMEN 05

2G110

PHLEBOTOMY

2G101

RECEPTION

2G103

RESTROOM

2G112

RESTROOM

2G114

RESTROOM

2G116

SPECIMEN 08

2G105

SPECIMEN 07

2G107

SPECIMEN 06

2G109

SPECIMEN DROP OFF

2G111

SPECIMEN 09

2G113

SPECIMEN 10

2G115RESTROOM

2G118

LAB OFFICE

2G127

STAFF RESTROOM

2G126

LAB OFFICE

2G125

LAB OFFICE TOUCHDOWN

2G123

COLD STORAGE

2G121

NEG. PRESSURE LAB

MICROBIOLOGY

2G122

VESTIBULE

2G117A

STAFF RESTROOM

2G144

CONFERENCE/ BREAK ROOM

2G143

TREATMENT 1

2G135B

TREATMENT 2

2G135C TREATMENT 3

2G135D

NURSE STATION

2G135A

MED ROOM

2G142

TREATMENT 4

2G135E

TREATMENT 5

2G135F

TREATMENT 6

2G135G

TREATMENT 7

2G135H

TREATMENT 8

2G135I

TREATMENT 9

2G135J

TREATMENT 10

2G135K

INFUSION CLINIC

2G135

RESTROOM

2G139

RESTROOM

2G138

ADMIN SUPPORT

2G137

EXAM / CONSULT

2G136

CORRIDOR

C2-97

SOILED UTILITY

2G140

RECEPTION

2G134

WAITING ROOM

2G133

HAC

2G132

STERILE SUPPLY

2G119

CONSULT

2G128

CONSULT

2G129

FILE CLOSET

2G130

CORRIDOR

C2-101

ELECTRICAL

2G131

BULK STORAGE

2G120

STERILE SUPPLY

2G141

CORE LAB

2G117

CORRIDOR

C2-99

INFUSION CLINIC

2G135

CORE LAB

2G117

CORE LAB

2G117

TELECOM ROOM

2G145

3 3

4D

2D/2V

2D/2V 4D

4D

4D

4D

4D

4D

4D

4D

(TYP.)

(TYP.)

STAIR

STAIR-F

(TYP.)

L2F2 - 48

L2F2 - 48

L2F2 - 48L2F2 - 45

L2F2 - 45

L2F2 - 47

L2F2 - 47

TV

9' AFF

QMATIC TV

60" AFF

(TYP.)

TV

60" AFF

ECL2F2 - 27

HEADEND

NURSE CALL

39" AFF

39" AFF

39" AFF

39" AFF

ECL2F - 57

A. NO WORK REQUIRED IN HATCHED AREAS. ALL LIGHTING FIXTURES,

CONTROLS, POWER DEVICES, CIRCUITING AND ASSOCIATED

WIRING SHALL BE EXISTING TO REMAIN.

B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND

SLABS ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR THE

RATED APPLICATION.

C. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY WALL

MOUNTED ITEM (ELECTRICAL/DATA/LIGHT) WITH ARCHITECT PRIOR

TO INSTALLATION.

D. FINAL LOCATION OF COMMUNICATION/SECURITY DEVICES SHALL

BE COORDINATED WITH THE VA DURING WALK THROUGH PRIOR TO

ROUGH-IN.

E. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL SECURITY

DEVICES WITH VA PRIOR TO ORDERING AND INSTALLATION.

F. THE CONTRACTOR IS RESPONSIBLE FOR TELE/DATA CONDUIT,

WIRING, TERMINATIONS, ANY REQUIRED PATCH PANELS, ETC.

NECESSARY FOR ALL SPECIAL SYSTEMS UNLESS OTHERWISE

NOTED. INSTALL ALL CONDUITS ALL THE WAY UP TO THE CABLE

TRAY.

G. THE NURSE CALL SYSTEM SHALL BE USED FOR BID PURPOSES

ONLY. CONTRACTOR SHALL OBTAIN ACTUAL WIRING

DIAGRAM/SYSTEM FROM FINAL SELECTED VENDOR. SUBMIT SHOP

DRAWINGS TO COR FOR FINAL APPROVAL. THE CONTRACTOR

SHALL PROVIDE ALL NECESSARY DEVICES, BACKBOXES, CONDUIT,

WIRING ETC. TO PROVIDE A FULLY FUNCTIONAL SYSTEM.

H. ALL EQUIPMENT AND DEVICES ON PLAN ARE SHOWN AS NEW

UNLESS NOTED OTHERWISE INDICATED WITH AN (E).

I. FOR ALL EXAM ROOMS, OFFICES, RECEPTIONS, ETC. THAT

REQUIRE A DURESS CALL BUTTON, THESE ROOMS SHALL BE

FITTED WITH A WORK STATION THAT HAS A DURESS CALL

INTEGRATED WITHIN THE SYSTEM. COORDINATE WITH VA FOR ALL

REQUIREMENTS. CONTRACTOR SHALL PROVIDE AN ALLOWANCE

FOR DURESS CALL BUTTON IF OTHERWISE DIRECTED BY VA.

J. FOR ALL NEW PUBLIC ADDRESS SPEAKERS, THEY SHALL BE

COMPATIBLE WITH THE EXISTING PA SYSTEM, PZS 140RA. SEE

SHEET E-503 FOR ADDITIONAL INFORMATION. CONTRACTOR SHALL

TEST, PROGRAM, PROVIDE PROGRAM CARDS, CONDUITS,

ADJUSTING HARDWARE AND SOFTWARE FOR A COMPLETE

FUNCTIONAL SYSTEM.

K. ALL DATA OUTLETS SHOWN IN THE CORE LAB SHALL BE MOUNTED

ABOVE COUNTER UNLESS NOTED OTHERWISE.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

CEILING DATA OUTLET

FLOOR DATA OUTLET

FLOOR TELEPHONE OUTLET

CLNG

NURSE CALL STAFF STATION

TELEPHONE OUTLET

VOICE/DATA OUTLET

VOLUME CONTROL

CATV OUTLET

TV OUTLET

SYMBOLSYMBOL SYMBOL

ELECTRICAL SYMBOL LEGEND

DESCRIPTION DESCRIPTION DESCRIPTION

CEILING DATA OUTLET

FLOOR DATA OUTLET

(4) FOUR RJ45 OUTLET

FLOOR TELEPHONE OUTLET

CLNG

ELECTRIC STRIKE

MAGNETIC LOCK

COMBINATION LOCK

DOOR CONTACT

CARD READER

SECURITY KEYPAD

MOTION DETECTOR

NURSE CALL STAFF STATION

NURSE CALL DOME LIGHT (1-COLOR)

TELEPHONE OUTLET

VOICE/DATA OUTLET

DOOR BELL

DOOR BUZZER

DOOR CHIME

DOOR SIGNAL

VOLUME CONTROL

CATV OUTLET

TV OUTLET

NURSE CALL DOME LIGHT (4-COLORS)

NURSE CALL DOME LIGHT (2-COLORS)

AUTO DOOR PUSH PAD

NURSE CALL EMERGENCY STATION

NURSE CALL MASTER STATION

360 DEGREES SECURITY CAMERA

FIXED SECURITY CAMERA

PUSHBAR TO EXIT

REQUEST TO EXIT

DUAL AUTHENTICATION

ACCESS CONTROL

DOOR POSITION SWITCH

DURESS ALARM BUTTON

N

SEC 6

(F)

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:4

P

M

EY102F

ELECTRICAL SPECIAL SYSTEMS SECOND FLOOR

PLAN - AREA F

520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F3 ELECTRICAL SPECIAL SYSTEMS SECOND FLOOR PLAN - AREA F

1 PROVIDE (1) 1" CONDUIT FOR LOW VOLTAGE WIRING THROUGH

WALL.

2 PROVIDE (1) 1-1/2" CONDUIT FOR LOW VOLTAGE WIRING THROUGH

FIRE RATED WALL.

3 PROVIDE (1) 2-1/2" CONDUIT FOR LOW VOLTAGE WIRING THROUGH

FIRE RATED WALL.

4 PROVIDE (11) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH

FIRE RATED WALL.

5 2"Dx2"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

6 2"Dx4"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

7 2"Dx6"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

8 2"Dx12"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

9 2"Dx20"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

10 4"Dx16"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

11 4"Dx18"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

12 4"Dx20"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

13 AUTOMATIC DOOR OPENER. IN ADDITION TO THE CEILING MOUNTED

JUNCTION SHOWN ON DRAWINGS, INSTALL CONDUIT STUBBED UP

INTO CEILING SPACE WITH PULL STRING. LOCATION SHALL BE

COORDINATED WITH COR. CONTRACTOR SHALL COORDINATE

EXACT REQUIREMENTS WITH COR SECURITY VENDOR AND DOOR

HARDWARE MANUFACTURER. ACCOUNT FOR ALL REQUIRED

PROVISIONS PRIOR TO BID ISSUANCE.

14 PROVIDE PUBLIC ADDRESS SPEAKER WITH LOCAL VOLUME

CONTROLS.

15 REMISOL WORKSTATIONS - PROVIDE ENDPOINT CONNECTION TO

LAB EQUIPMENT E5 AND E6. REMISOL WORKSTATION SHALL TIE

BACK TO REMISOL SERVER STATION LOCATED IN ROOM 2G123.

VERIFY ALL CONNECTIONS WITH COR.

16 REMISOL WORKSTATIONS - PROVIDE ENDPOINT CONNECTION TO

LAB EQUIPMENT E15 AND E16. REMISOL WORKSTATION SHALL TIE

BACK TO REMISOL SERVER STATION LOCATED IN ROOM 2G123.

VERIFY ALL CONNECTIONS WITH COR.

17 EQUIPMENT TO BE CONNECTED TO REMISOL WORKSTATION. SEE

EQUIPMENT PLAN FOR ADDITIONAL INFORMATION.

18 PROVIDE DATA OUTLET FOR STAT BOARD MOUNTED 72" AFF.

REMISOL SHALL BE COMMUNICATE WITH STAT BOARD. COORDINATE

ALL REQUIREMENTS WITH EQUIPMENT VENDOR.

19 (2) 4-POST RACKS WITH 48 PORT PATCH PANELS AND UPS. SEE

COMMUNICATION SYSTEM RISER DIAGRAM FOR ADDITIONAL

INFORMATION ON SHEET E-503.

20 PROVIDE (5) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH

FIRE RATED WALL.

21 FLOOR OUTLET FOR PILLOW SPEAKER AT CHAIR LOCATION.

COORDINATE ALL REQUIREMENTS WITH VA PRIOR TO

INSTALLATION.

22 CEILING MOUNTED JUNCTION BOX FOR QMATIC NUMBERING

SYSTEM. SYSTEM SHALL REPORT TO RECEPTION COMPUTER IN

ROOM 2G103 AND BE DISPLAYED ON THE QMATIC TV LOCATED IN

WAITING ROOM 2G100. COORDINATE ALL REQUIREMENTS WITH VA

PRIOR TO INSTALLATION. PROVIDE LOW VOLTAGE TRANSFORMER

AS REQUIRED.

23 REMOTE RELEASE PUSH BUTTON. COORDINATE EACH LOCATION

WITH VA PRIOR TO INSTALLATION.

24 6"Dx20"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH CEILING UTILITIES.

Revisions: Date:

2022.09.23

Q.8 Q.8

Q Q

P P

N N

M M

L L

K K

Q.9 Q.9

CT-3

EQDP - 49,51,53

DPHB - 1

200/NF/1

MECHANICAL ROOM

1B179

CH-3

(E)CH-2(E)CH-1

CWP-1.3

DPM - 67,69,71

(E)CT-2

(E)CT-1

VFD-CT-3VFD-CWP-1.3

MSB-A - 5

HWP-1.1

HWP-1.2

DPM - 68,70,72

CHWP-2.3

DPM - 62,64,66

A. NO WORK REQUIRED IN HATCHED AREAS. ALL LIGHTING FIXTURES,

CONTROLS, POWER DEVICES, CIRCUITING AND ASSOCIATED

WIRING SHALL BE EXISTING TO REMAIN.

B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND

SLABS ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR THE

RATED APPLICATION.

C. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO

ORDERING AND INSTALLATION.

D. ELECTRICAL CONTRACTOR SHALL VERIFY ALL POWER AND

CONNECTION REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO

ORDERING AND INSTALLATION. VERIFY ALL DEVICE LOCATION AND

MOUNTING HEIGHT. MAKE ADJUSTMENT IN FIELD TO MATCH

ACTUAL EQUIPMENT NAMEPLATE BEING INSTALLED.

E. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

F. ALL WIRING FROM LOAD SIDE OF VFD TO CONNECTION AT

EQUIPMENT SHALL BE XLPE (XHHW-2) INSTALLED IN ACCORDANCE

WITH EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

N

SEC 2

(B)

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:5

P

M

EM101B

MECHANICAL POWER GROUND FLOOR PLAN -

AREA B

520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F2 MECHANICAL POWER GROUND FLOOR PLAN - AREA B

1 VSD AND DISCONNECT FACTORY INSTALLED.

2 ROUTE CONDUIT TO SUPPLY SIDE OF NEW NEMA 3R VFD WITH INTEGRAL

DISCONNECT FOR COOLING TOWER. PROVIDE XLPE WIRE (XHHW-2) FROM

VFD LOAD SIDE TERMINAL TO COOLING TOWER. VERIFY EXACT LOCATION

OF VFD WITH MECHANICAL CONTRACTOR.

3 ROUTE CONDUIT TO SUPPLY SIDE OF NEW NEMA 3R VFD WITH INTEGRAL

DISCONNECT FOR CWP-1.3. PROVIDE XLPE WIRE (XHHW-2) FROM VFD

LOAD SIDE TERMINAL TO PUMP. VERIFY EXACT LOCATION OF VFD WITH

MECHANICAL CONTRACTOR.

DEDUCTIVE ALTERNATES

D1 DEDUCTIVE ALTERNATE #1: REMOVE ALL SCOPE OF WORK ASSOCIATED

WITH ~51,200 SF OF NEW PARKING. SEE GI100.

D2 DEDUCTIVE ALTERNATE #2: REMOVE ALL SCOPE OF WORK ASSOCIATED

WITH ~39,000 SF OF NEW PARKING. SEE GI100.

D3 DEDUCTIVE ALTERNATE #3: REDUCE WINDOW QUANTITY BY 8. SEE

A-201.

D4

DEDUCTIVE ALTERNATE #4: REMOVE ALL SCOPE ASSOCIATED

WITH 600 TON CHILLER (CH-3) REPLACEMENT IN MECHANICAL

ROOM 1B179.

NOTE: DEDUCTIVE ALTERNATES ARE CASCADING. EACH DEDUCT WILL BE TAKEN IN

SUCCESSION AND SHALL BE PRICED UNDER SEQUENTIAL, SEPARATE CLINs

(CONTRACT LINE ITEM NUMBER) SO DETERMINATIONS CAN BE MADE AND

PRIORITIES ESTABLISHED BASED ON BIDS RECEIVED.

D4

Revisions: Date:

2022.09.23

M M M M

M

M

M

M M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M M

M

M

E E

D D

C C

B B

CONSULT

2G128

CONSULT

2G129

FILE CLOSET

2G130

ELECTRICAL

2G131

CORRIDOR

C2-101

LAB OFFICE

2G127

STAFF RESTROOM

2G126

LAB OFFICE

2G125

LAB OFFICE TOUCHDOWN

2G123

RESTROOM

2G118

SPECIMEN 10

2G115

SPECIMEN 09

2G113

RESTROOM

2G116

RESTROOM

2G114

SPECIMEN DROP OFF

2G111

COLD STORAGE

2G121

BULK STORAGE

2G120

STERILE SUPPLY

2G119

HAC

2G132

NEG. PRESSURE LAB

MICROBIOLOGY

2G122

STERILE SUPPLY

2G141

WAITING ROOM

2G133

CORE LAB

2G117

SPECIMEN 06

2G109

SPECIMEN 07

2G107

SPECIMEN 08

2G105

RECEPTION

2G103

WAITING ROOM

2G100

PHLEBOTOMY

2G101

RESTROOM

2G100A

SPECIMEN 01

2G102

SPECIMEN 02

2G104

SPECIMEN 03

2G106

SPECIMEN 04

2G108

SPECIMEN 05

2G110

CONFERENCE/ BREAK ROOM

2G143

CORRIDOR

C2-99

VESTIBULE

2G117A STAFF RESTROOM

2G144

TREATMENT 1

2G135B

TREATMENT 2

2G135C

TREATMENT 3

2G135D

NURSE STATION

2G135A

TREATMENT 4

2G135E

TREATMENT 5

2G135F

MED ROOM

2G142

TREATMENT 6

2G135G

TREATMENT 7

2G135H

TREATMENT 10

2G135K

TREATMENT 8

2G135I

TREATMENT 9

2G135J

INFUSION CLINIC

2G135

SOILED UTILITY

2G140

RESTROOM

2G139

RESTROOM

2G138

ADMIN SUPPORT

2G137

RECEPTION

2G134 EXAM / CONSULT

2G136

CORRIDOR

C2-97

RESTROOM

2G112

CORE LAB

2G117

TELECOM ROOM

2G145

DSSI-2G131

EAV-2F-2G119

SAV-2F-2G119

RH-2F-2G119

ATU-2F-C2-97

ATU-2F-2G130 ATU-2F-2G133

ATU-2F-2G145

SAV-2F-2G141

ATU-2F-2G129

ATU-2F-2G128

ATU-2F-2G127

ATU-2F-2G125

ATU-2F-2G123

ATU-2F-2G115

ATU-2F-2G126

ATU-2F-2G113

SAV-2F-2G122

ATU-2F-2G120

ATU-2F-2G112

ATU-2F-2G111

ATU-2F-2G105

ATU-2F-2G103

ATU-2F-2G100

ATU-2F-2G101

ATU-2F-2G107

ATU-2F-2G109

ATU-2F-2G100A

ATU-2F-2G102 ATU-2F-2G104 ATU-2F-2G106 ATU-2F-2G108

ATU-2F-2G110

ATU-2F-2G143

ATU-2F-2G144

ATU-2F-2G135-1

ATU-2F-2G135-3

ATU-2F-2G142

ATU-2F-2G135

ATU-2F-2G138

ATU-2F-2G140

ATU-2F-2G134

ATU-2F-2G137

EAV-2F-2G122

ATU-2F-2G136

DSSI-2G145

L2F - 9

L2F - 11

L2F - 15

L2F - 13

EAV-2F-2G117

SAV-2F-2G117-2

SAV-2F-2G117-3 ATU-2F-2G135-2

RH-2F-2G117-1

A. NO WORK REQUIRED IN HATCHED AREAS. ALL LIGHTING FIXTURES,

CONTROLS, POWER DEVICES, CIRCUITING AND ASSOCIATED

WIRING SHALL BE EXISTING TO REMAIN.

B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND

SLABS ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR THE

RATED APPLICATION.

C. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO

ORDERING AND INSTALLATION.

D. ELECTRICAL CONTRACTOR SHALL VERIFY ALL POWER AND

CONNECTION REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO

ORDERING AND INSTALLATION. VERIFY ALL DEVICE LOCATION AND

MOUNTING HEIGHT. MAKE ADJUSTMENT IN FIELD TO MATCH

ACTUAL EQUIPMENT NAMEPLATE BEING INSTALLED.

E. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

N

SEC 6

(F)

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:0

P

M

EM102F

MECHANICAL POWER SECOND FLOOR PLAN -

AREA F

520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F3 MECHANICAL POWER SECOND FLOOR - AREA F

1 PROVIDE 3/4" CONDUIT WITH POWER AND CONTROLS FOR SPLIT SYSTEM

EVAPORATOR. MAKE CONNECTIONS PER MANUFACTURER.

Revisions: Date:

2022.09.23

K K

J J

H H

G G

F F

LPH

T-HPH

HPH

DPPH - 20,22,24

DPPH - 2,4,6

LPH - 13

30/NF/1

100/NF/1

ECH2CA

AHU-3 (E)

AHU-2 (E)

AHU-5 (E)

(E)GEF-31

(E)GEF-1

GEF-4B(E)

AHU-2-N

(E)GEF-4A

(E)GEF-5

DPPH

LPH - 10

DDC CONTROLLER

LPH - 15

AHU-2-N PUMP 3

A. NO WORK REQUIRED IN HATCHED AREAS. ALL LIGHTING FIXTURES,

CONTROLS, POWER DEVICES, CIRCUITING AND ASSOCIATED

WIRING SHALL BE EXISTING TO REMAIN.

B. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING

ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS

SHALL MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND

SLABS ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR THE

RATED APPLICATION.

C. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO

ORDERING AND INSTALLATION.

D. ELECTRICAL CONTRACTOR SHALL VERIFY ALL POWER AND

CONNECTION REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO

ORDERING AND INSTALLATION. VERIFY ALL DEVICE LOCATION AND

MOUNTING HEIGHT. MAKE ADJUSTMENT IN FIELD TO MATCH

ACTUAL EQUIPMENT NAMEPLATE BEING INSTALLED.

E. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANICAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

F. ALL WIRING FROM LOAD SIDE OF VFD TO CONNECTION AT

EQUIPMENT SHALL BE XLPE (XHHW-2) INSTALLED IN ACCORDANCE

WITH EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

G. FOR AHU-2-N, A DUCT SMOKE DETECTOR IS REQUIRED. DUCT

SMOKE DETECTOR SHALL BE PROVIDED BY MECHANICAL AND

WIRED BY ELECTRICAL. COORDINATE ALL REQUIREMENTS WITH

MECHANICAL PRIOR TO INSTALLATION.

KEYNOTES

KEY PLAN

GENERAL SHEET NOTES

N

JACC KEYPLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d

A d d it io n t o

J A

C C

P e n s a c o la /5

-2

.J

A C

C .P a c k a g e .M

E P

F

R

.r v t

/2

/2

:0

:1

P

M

EM103P

MECHANICAL POWER THIRD FLOOR PLAN -

PENTHOUSE NORTH

520-331

JACC-2F

09.26.2022 JR SC

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

1/8" = 1'-0"F3 MECHANICAL POWER THIRD FLOOR PLAN - PENTHOUSE NORTH

1 HUMIDITY GENERATOR AND LIGHTING/RECEPTACLE DISCONNECTS

SHALL BE PROVIDED BY GENERAL CONTRACTOR. COORDINATE

MOUNTING WITH MANUFACTURER DURING INSTALLATION.

2 VFD AND DISCONNECT FACTORY INSTALLED.

3 AHU-2-N- PUMP. COORDINATE EXACT LOCATION WITH MECHANICAL

PRIOR TO INSTALLATION.

Revisions: Date:

2022.09.23

SECTION A-A

A

A

GROUNDING DETAIL

GROUND

BAR

NEUTRAL

BAR

CATV FA SEC

ELEC

METER

GROUND

BAR

NEUTRAL

BAR

TWO HOLE STRAP OR

CADWELD CONNECTION TYPE

''LK'', TYPICAL

MOUNTING BRACKETS

FIBERGLASS INSULATORS

4"

MIN.

NOTES:

1. PREDRILLED BOLT HOLE SIZE AND SPACING AS REQUIRED FOR INDICATED TERMINATIONS .

2. PROVIDE LENGTH SUFFICIENT FOR ALL INDICATED TERMINATIONS AND 20% SPARE MOUNTING

SPACE. CONNECTIONS SHALL UTILIZE TWO HOLE COMPRESSIONS CONNECTOR.

3. GROUND BAR SHALL BE MOUNTED MINIMUM 2" OFF WALL AND 12" AFF.

4. FIBERGLASS INSULATORS SHALL HAVE A MINIMUM DIELECTRIC STRENGTH OF 15kV.

INSULATED COPPER

GROUND CONDUCTOR TO

BUILDING GROUNDING

ELECTRODE CONDUCTOR

GROUND BUS DETAIL

NOTES:

1. TYPICAL FOR WOOD AND METAL STUD ROUGH-IN.

2. PLASTER RINGS NOT SHOW.

3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND

MECHANICAL DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.

4. IN ACCORDANCE WITH UBC 4304 OUTLETS ON OPPOSITE SIDES OF WALLS OR

PARTITIONS IN THE SAME STUD SPACE MUST BE SEPARATED BY A MIN. OF 24"

HORIZONTAL DISTANCE.

5. TOENAILING OF OUTLET BOXES DIRECTLY TO THE STUDS WILL NOT BE

ACCEPTED.

6. OUTLETS SHOWN TOGETHER ON PLAN SHALL BE INSTALLED TOGETHER.

TYPICAL

WALL

OUTLETS

PROVIDE CONDUIT SUPPORTS IN

ACCORDANCE WITH NEC. SPACING

REQUIREMENTS FOR TYPE OF RACEWAY

REQUIRED.

AS REQUIRED FOR TYPE

OF CONSTRUCTION.

BOX

SUPPORT

TYPICAL

OUTLET

BOX.

TYPICAL ROUGH-IN

61_

MIN.

DEDICATED

ELECTRICAL

SPACES

PERMITTED

LUMINARIE

PERMITTED

PERMITTED

STRUCTURAL

CEILING

SUSPENDED

CEILING

SIDE VIEW FRONT

6' OR

LESS

DEDICATED EQUIPMENT SPACE NOTES:

1. THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE EQUIPMENT AND EXTENDING

FROM THE FLOOR TO A HEIGHT OF 6'-0" ABOVE THE EQUIPMENT OR TO THE

STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE DEDICATED TO THE

ELECTRICAL INSTALLATION. NO PIPING, DUCTS, LEAK PROTECTION APPARATUS OR

OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION SHALL BE

LOCATED IN THIS ZONE.

2. THE AREA ABOVE THE DEDICATED SPACE SHALL BE PERMITTED TO CONTAIN

FOREIGN SYSTEMS, PROVIDED PROTECTION IS INSTALLED TO AVOID DAMAGE TO

THE ELECTRICAL EQUIPMENT FROM CONDENSATION, LEAKS, OR BREAKS IN SUCH

FOREIGN SYSTEMS.

3. SPRINKLER PROTECTION SHALL BE PERMITTED FOR THE DEDICATED SPACE WHERE

THE PIPING COMPLIES WITH THESE NOTES.

4. A DROPPED, SUSPENDED, OR SIMILAR CEILING THAT DOES NOT ADD STRENGTH TO

THE BUILDING STRUCTURE SHALL NOT BE CONSIDERED A STRUCTURAL CEILING.

DEDICATED ELECTRICAL SPACES ELECTRICAL EQUIPMENT NAMEPLATE PENETRATIONS THROUGH RATED WALLS

C6

NTS

D7

NTS

D6

NTS

F9

NTS

F6

NTS

F7

NTS

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. (51 mm) by 4 in.

(102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC.

Additional studs installed to completely frame the opening.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max area of opening is 352 sq in. (2271 sq cm) with max dimension of 22 in. (559 mm) wide.

The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Cable Tray* — Max 18 in. (457 mm) wide by max 6 in. (152 mm) deep open-ladder or solid-back cable tray with channel-shaped side rails formed of 0.065 in. (1.65 mm) thick aluminum or 0.060 in. (1.52 mm) thick steel and with 1-1/2 in. (38 mm) wide by 1 in. (25 mm) channel shape rungs spaced 9 in. (229 mm) OC or a 0.029 in. (0.74 mm) thick steel solid back, respectively. One cable tray to be installed in the opening. The max annular space between the cable tray and the periphery of the opening shall be min 1 in. (25 mm) to max 7 in. (178 mm) Cable tray to be rigidly supported on both sides of floor or wall assembly.

3. Cables — Aggregate cross-sectional area of cables in cable tray to be max 30 percent of the cross-sectional area of the cable tray.

Any combination of the following types and sizes of copper conductor cables may be used:

A. 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and PVC jacket.

B. 100 pair - No. 24 AWG cable with PVC insulation and jacket.

C. 1/C, 750 kcmil (or smaller) with PVC insulation and jacket.

4. Through-Penetrants — One or more pipe or tube to be installed within the opening. The total number of through-penetrants is dependent on the size of the opening and types and sizes of the penetrants. Any combination of the penetrants described below may be used provided that the following parameters relative to the annular spaces and the spacings between the pipes are maintained. The space between the pipe or tube and the periphery of the opening shall be min 1-1/2 in. (38 mm) to max 9-1/4 in. (235 mm). Pipe or tube to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of non-metallic or metallic pipes, or tubes may be used:

A. Polyvinyl Chloride (PVC) Pipe — Max 3 in. (76 mm) diam Schedule 40 solid core PVC pipe (or smaller) for use in closed (process or supply) or vented (drain, waste or vent) piping system.

B. Steel Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe.

C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) diam steel conduit.

D. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.

E. Copper Tube — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.

4A. Pipe Covering — (Not Shown) Nom 1-1/2 in. (38 mm) thick hollow cylindrical heavy density (min 3.5 pcf) (56kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory applied self-sealing lap tape.

Transverse joints secured with metal fasteners or with butt tape supplied with the product.

See Pipe and Equipment Covering and Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 may be used.

5. Cables — Max 1-1/2 in. (38 mm) diam tight bundle of cables installed within the opening and rigidly supported on both surfaces of wall. The space between the cables and periphery of the opening shall range from 1-3/16 in. (30.2 mm) min to a max of 1-1/2 in. (38 mm). Any combination of the following types and sizes of cables may be used:

A. 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.

B. 25 pair — No. 24 AWG cable with PVC insulation and jacket.

C. Type R GU/59 coaxial cable with PVC outer jacket.

D. 24 fiber optic cable with PVC sub unit and outer jacket.

6. Firestop System — The firestop system shall consist of the following:

A. Fill, Void or Cavity Material* — Fire Blocks For walls incorporating max 3-5/8 in. (92 mm) steel studs or max 2 (51 mm) by 4 in.

(102 mm) wood studs, fire block installed with 5 in. (127 mm) dimension projecting through and centered in opening. For walls constructed of larger steel or wood studs, fire block installed with long dimension passing through and centered in opening. Blocks may or may not be cut flush with both surfaces of wall. When multiple layers of gypsum board are used, blocks may be recessed 1/2

in. (13 mm) from surface of wall. Blocks to be firmly packed in opening. Either one or a combination of the block types specified below may be used.

B. Fill, Void or Cavity Material* — Sealant or Putty - Fill material to be forced into interstices of cables, between cables and cable trays, around each penetrant and where obvious voids are observed to max extent possible on both surfaces of the penetration.

GROUNDING DETAIL KEYNOTES

1. GROUND BUS BAR LOCATED IN MAIN ELECTRICAL ROOM OR WITHIN

SERVICE ENTRANCE MAIN. 0.25" X 4" X 12" WITH 18 HOLES MINIMUM FOR

EXTERNAL INSTALLATION.

2. GROUNDING TRIAD, 3-3/4" X 10'-0" COPPERCLAD GROUND RODS DRIVEN

INTO GROUND AT LEAST 1 ROD'S LENGTH APART. PROVIDE WITH

INSPECTION TEST WELL.

3. COPPER GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC TABLE

250.66, MINIMUM SIZE #8.

4. SERVICE ENTRANCE MAIN BONDING JUMPER SIZED PER NEC TABLE

250.66. NEUTRAL SHALL ONLY BE BONDED AT SERVICE ENTRANCE, ALL

OTHER NEUTRALS SHALL BE CONSIDERED FLOATING.

5. CONNECTIONS TO BUILDING STEEL SHALL BE BY EXOTHERMIC WELD.

6. CONNECTIONS TO REBAR ENCASED IN CONCRETE SHALL BE BY

EXOTHERMIC WELD.

7. BOND METALLIC COLD WATER PIPE WITHIN 5' - 0" OF ENTERING

BUILDING. CONNECTION SHALL BE MADE WITH NON-CORROSIVE

MATERIAL GROUNDING ELECTRODE CLAMP.

8. SERVICE ENTRANCE NEUTRAL CONDUCTOR.

9. ALL EQUIPMENT ENCLOSURES AND METAL RACEWAYS SHALL BE

GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR SIZED PER

NEC TABLE 250.122.

10. EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122.

11. NEUTRAL CONDUCTOR WITH INSULATED EQUIPMENT GROUNDING

CONDUCTOR TO BRANCH CIRCUIT PANELS/EQUIPMENT.

12. ALL TELECOM ROOMS SHALL HAVE A GROUNDING BUS BAR. TIE INTO

MAIN ELECTRICAL ROOMS MAIN SYSTEM USING, AT MINIMUM, AWG #8

COPPER.

X

SERVICE ENTRANCE MAIN

BRANCH CIRCUIT PANEL

GRADE

3 3 3

TO UPPER FLOORS, REMOTE

ELECTRICAL ROOMS, IT CLOSETS

WHERE APPLICABLE

HEM

120/208V, 3PH, 4W

FED FROM MSB BKR. 11

SCA 36,921A 01/03/12

LETTER (FILL) COLOR

EMERGENCY = WHITE

NORMAL - WHITE

INDICATED

VOLTAGE,

NO. OF PHASES,

NO OF WIRES

INDICATES WHERE

THIS EQUIPMENT IS

FED FROM

(TRANSFER

SWITCHES WILL HAVE

TWO LINES.)

CALCULATED

AVAILABLE FAULT

CURRENT

ATTACH

NAMEPLATE

WITH 2 SCREWS

NAMEPLATE COLOR

LIFE SAFETY - YELLOW

CRITICAL - ORANGE

EQUIPMENT - GREEN

NORMAL - BLACK

EMERGENCY - RED

LETTERING

SHALL BE

1/4" HIGH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

B

IM

/5

-3

C o…