This file is an 18MB attachment of architectural drawings for exterior details related to Federal Contract Opportunity 36C77623R0103. The opportunity is a solicitation by the Department of Veterans Affairs Technology Acquisition Center Austin to construct an addition and renovations to the Joint Ambulatory Care Clinic in Pensacola, Florida. The drawings provide specifications for exterior elements of the construction project. Offerors would use these drawings to inform their responses to the solicitation, which is for design and building services. The response deadline and award date are not specified in this attachment.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5/8" 4" 6 1/2" 6 1/2" 4" 5/8"
1'-10 1/4"
5/ 8"
4"
5/ 8"
1/
2"
7/ 8"
5/ 8"
1' -9
/4
GYPSUM WALL BOARD
7/8" FURRING CHANNELS
STRUCTURAL FIREPROOFING
NEW COLUMN - SEE STRUCTURAL
METAL STUD FRAMING
CORNER GUARDS
AS SCHEDULED
B
1'-0" 5 3/4" 8" 6 1/4" 8"
1'-8"
1' -3
/8
3/ 8"
1' -3
/8
3' -3
/8
EXISTING BRICK BELOW
NEW DOWNSPOUT TO
MATCH EXISTING
BRACKET CONNECTION
GYPSUM WALL BOARD
8" METAL STUD FRAMING
BATT INSULATION
EXTERIOR SHEATHING
CONTINUOUS INSULATION
NEW BRICK VENEER TO
MATCH EXISTING
CORNER GUARD
1' -0
NEW BRICK VENEER
TO MATCH EXISTING
NEW STRUCTURE @ 2ND FLOOR
EXISTING TO REMAIN @ 1ST FLOOR
C
NEW BRICK VENEER
TO MATCH EXISTING
BRACKET CONNECTION
NEW DOWNSPOUT
TO MATCH EXISTING
2' -0
4"
4" 2'
-0
1'-0" 5 3/4" 8" 6 1/4" 8"
EXISTING BRICK
BELOW
3' -0
3'
-0
BATT INSULATION
8" METAL STUD FRAMING
GYPSUM WALL BOARD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:5
P
M
A-502
ARCHITECTURAL DETAILS - EXTERIOR 520-331
JACC-2F
09.26.2022 M. PERKINS C. LOWERY
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
1 1/2" = 1'-0"B7 PLAN DETAIL - TYP. INTERIOR COLUMN
1 1/2" = 1'-0"B8 PLAN DETAIL - AREA F CORNER COLUMN & DOWNSPOUT
1 1/2" = 1'-0"E8 PLAN DETAIL - AREA F EXTERIOR COLUMN & DOWNSPOUT
Revisions: Date: 10.07.2022 10.07.2022
RUBBER BASE
FINISHED FLOOR
PLASTIC LAMINATE
DRAWERS AND
PANELS, REFER TO
ELEVATIONS FOR
FINISH
CABINET LINER
BACKING
SOLID SURFACE ON BACK
SPLASH AND COUNTER
TOP AND EDGE
CAULK
DRAWERS ON SLIDES
2'-1"
4"
U .N
.O
. 4
E Q
E Q
E Q
E Q
1/
2" 4"
CAULK ALL EXPOSED COUNTER
AND CASEWORK SURFACES TO
WALL, TYPICAL
2' -1
0"
PLASTIC LAMINATE
ADJUSTABLE SHELF TO
MATCH CABINET FACES
PLASTIC LAMINATE
DOOR PANEL, REFER
TO ELEVATIONS FOR
FINISH
RECESSED ADJ. SHELF
STANDARDS
+0'-0"
FINISHED FLOOR
RUBBER BASE
SOLID SURFACE AS
SCHEDULED ON BACK
SPLASH, COUNTER TOP
AND EDGE
PLASTIC LAMINATE
DRAWER ON SLIDES,
REFER TO
ELEVATIONS FOR
FINISH
CABINET LINER
BACKING
U .N
.O
4"
DOOR PULL
4"
1/ 2"
2'-1"
BACK SPLASH SOLID SURFACE
M A
X 2'
-1 0"
1/
2"
1/ 2"
1'-0"
9"10"
EXPOSED END TO HAVE
FULLY FINISHED SIDE
PANEL TO MATCH
CABINET FACES
REMOVABLE FRONT PLASTIC
LAMINATE PANEL, REFER TO
ELEVATIONS FOR FINISH
EASED EDGE
PLASTIC LAMINATE FINISH; REFER TO ELEVATIONS
METAL
BLOCKING
BLOCKING AS
REQUIRED
BLOCKING AS
REQUIRED
WALL AS SCHEDULED
ANTI-SCALD VALVES AT ALL FIXTURES
ANTI-SCALD VALVES AT ALL FIXTURES, SEE
PLUMBING DRAWINGS FOR MORE INFORMATION
4"
M
IN
2'
-3
1/2"1/2"
SINK AS SCHEDULED WITH 1/2" SINK RIM REVEAL
SINK BRACKETS TO BE INSTALLED PER
MANUFACTURER'S INSTRUCTIONS
COUNTER BEYOND
SOLID SURFACE AS
SCHEDULED ON
BACKSPLASH,
COUNTERTOP AND EDGE.
SCRIBE COUNTER
SURFACE TO WALL,
COLOR MATCH CAULK AT
WALLS
ELEC./DATA
OUTLET WHERE
OCCURS
FINISHED FLOOR
CAULK
U.O.N.
2'-1"
/2
U .O
.N
+0'-0"
WHITE ALUMINUM
COUNTER BRACKETS
AT EACH END AND
6'-0" ON CENTER
CAULK
PAINTED GWB
CABLE
MANAGEMENT
TRAY
2" DIA. BRUSHED NICKEL
GROMMET, ALL LOCATIONS TO
BE COORDINATED WITH COR5"
RUBBER BASE
WALL PER PLAN
SOLID SURFACE AS
SCHEDULED ON
COUNTERTOP AND EDGE.
SCRIBE COUNTER
SURFACE TO WALL,
COLOR MATCH CAULK AT
WALLS
FINISHED FLOOR
+0'-0"
BACKING AS
REQUIRED
CAULK
PAINT AS SCHEDULED
6"
EASED EDGE ALL
EDGES, TYP
O R
A S
S H
O W
N O
N E
LE
V
A T
IO
N
3' -6
PLYWOOD SUBSTRATE
RUBBER BASE
RIGID WALL
COVERING
FINISH; REFER
TO ELEVATIONS
FOR FINISH INFO
SIM
A-722 D10
11 1/4"
O R
A S
S H
O W
N O
N E
LE
V
A T
IO
N
2"
ALUMINUM GLASS PRIVACY SYSTEM PER SPECIFICATIONS
GLAZING IN MANUFACTURER PROVIDED CHANNEL
EMPLOYEE
SIDE
CL
#12 FLAT HEAD SHEET
METAL SCREWS AT 16"
O.C. INTO STUDS
SHELF AND APRON
2 HINGES PER DOOR TYP
PLASTIC LAMINATE
ADJUSTABLE SHELVES
DOOR & PANELS
REFER TO ELEVATIONS
FOR FINISH
DOOR PULL
1'-4"
#3 COUNTERSUNK TEK
SCREWS AT 6" OC
2X BLOCKING
#3 COUNTERSUNK TEK
SCREWS AT 6" OC
2X BLOCKING
PLASTIC LAMINATE
WALL AS SCHEDULED
R E
F E
R T
O E
LE
V
A T
IO
N
F O
R H
E
IG
H T
55°
#12 FLAT HEAD SHEET
METAL SCREWS AT 16"
O.C. INTO STUDS
SHELF
2 HINGES PER DOOR TYP
PLASTIC LAMINATE
ADJUSTABLE SHELVES
DOOR & PANELS
REFER TO ELEVATIONS
FOR FINISH
DOOR PULL
1'-4"
#3 COUNTERSUNK TEK
SCREWS AT 6" OC
2X BLOCKING
#3 COUNTERSUNK TEK
SCREWS AT 6" OC
2X BLOCKING
PLASTIC LAMINATE
WALL AS SCHEDULED
R E
F E
R T
O E
LE
V
A T
IO
N
F O
R H
E
IG
H T
55°
2"
APRON TO CONCEAL
UNDERCABINET LIGHTING
UNDERCABINET LIGHTING;
REF. ELECTRICAL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:0
P
M
A-551
ARCHITECTURAL CASEWORK DETAILS 520-331
JACC-2F
09.26.2022 M. PERKINS N.
BLANCHARD
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
1 1/2" = 1'-0"F6 BASE CAB. W/4 EQ. DRAWERS
1 1/2" = 1'-0"F3 BASE CABINET
1 1/2" = 1'-0"F8 CABINET AT SINK
1 1/2" = 1'-0"D1 COUNTERTOP
1 1/2" = 1'-0"D8 TRANSACTION COUNTERTOP
1 1/2" = 1'-0"D6 SLOPED UPPER CABINET WITH DOOR
INTERIOR SHEET NOTES
A. REFER TO IN001 FOR INTERIOR FINISH GENERAL NOTES
B. REFER TO SPECIFICATIONS FOR MATERIAL AND INSTALLATION REQUIREMENTS.
C. REFER TO IN601 FOR FINISH LEGEND AND ROOM FINISH SCHEDULE.
D. REFER TO A-400 SERIES FOR CASEWORK FINISHES.
E. REFER TO IF SERIES FOR FURNITURE; FURNITURE IS SHOWN FOR REFERENCE
ONLY, ALL FURNITURE IS NIC.
F. REFER TO AW SERIES FOR ALL SIGNAGE.
G. REFER TO Q SERIES FOR EQUIPMENT INFORMATION.
H. PAINT ALL WALLS (P-1) UNO.
I. PAINT ALL EXPOSED SIDES OF INTERIOR CEILING SOFFITS AND GYPSUM WALL
BOARD CEILINGS (P-12) UNO.
J. PAINT ALL HOLLOW METAL DOORS AND HOLLOW METAL FRAMES IN CONTRACT
BOUNDARY (P-15) UNO.
K. PLANS HAVE BEEN SCREENED BACK FOR CLARITY, REFER TO ARCHITECTURE
SERIES FOR WALL CONSTRUCTION INFORMATION
K. PLANS HAVE BEEN SCREENED BACK FOR CLARITY, REFER TO ARCHITECTURE
SERIES FOR WALL CONSTRUCTION INFORMATION
K. ALL GROMMET LOCATIONS TO BE DETERMINED IN FIELD AS DIRECTED AND
APPROVED BY COR.
1 1/2" = 1'-0"D3 SLOPED UPPER CABINET WITH DOOR AND LIGHTING
PARTITION AS
SCHEDULED,
SEE PLAN FOR
TYPE
VARIES, SEE PLAN
5/8" GYPSUM
WALLBOARD
CORNER
BEAD TYP.
3 5/8" METAL
STUD
FRAMING
ACOUSTICAL
CEILINGS
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
5/8" GYPSUM
WALLBOARD
3 5/8" METAL
STUD
FRAMING
ACOUSTICAL
CEILINGS
SLIP
END
SLIP
END
4 DIAGONAL
BRACE WIRES
AT 8'X12' GRID
MAX.
FIXED END
FIXED
END
ADDITIONAL
CROSS RUNNERS
WHERE 2'X2' GRID
OCCURS
MAIN RUNNERS AT
4'-0" O.C.
12 GA. VERTICAL
HANGER HANGER
WIRES AT 4'-0" O.C.
MAX. - TYP.
12 GA. HANGER
WIRE AT
PERIMETER
CROSS RUNNERS
AT 2'-0" O.C.
8" MAX. OR 1/4 OF
LENGTH OF THE END
RUNNER, WHICHEVER
IS LESS
4'-0" MAX. 8'-0" MAX. 8'-0" MAX. 4'-0" MAX.
4' -0
M
A X
'-0
M A
X
4' -0
M
A X
D8
A-571
D8
A-571
C8
A-571
C8
A-571
A-571 A8
8"
8"
8" MAX. OR 1/4 OF
LENGTH OF THE END
RUNNER,
WHICHEVER IS LESS
1 1/2" X 1.12 #/FT. MIN.,
CHANNELS @ 4'- 0" O.C.
7/8" FURRING CHANNELS
@ 2'-0" O.C. MAX.
12 GA. VERT HANGER
WIRES @ 4'-0" O.C MAX.
TYP.
12 GA. HANGER WIRES @
PERIMETER
4 DIAGONAL BRACE WIRES
@ 8'x 12' GRID
MAX.
4' -0
M
A X
'-0
M A
X
4' -0
M
A X
4'-0" MAX. 8'-0" MAX. 8'-0" MAX. 4'-0" MAX.
C4
A-571
C6
A-571
1'-0"
8"
PARALLEL
PERPENDICULAR
ATTACH WIRE THRU
SUPPORT HOLES OR TO 16
GA. STEEL CLIP ATTACHED
TO LIGHT FIXTURE WITH (1) #
10 S.M.S.
12 GA WIRE
LIGHT FIXTURE OR
MECHANICAL AIR DIFFUSER
ATTACH FIXTURE TO CEILING
GRID W/ SEISMIC RESTRAINT
CLIPS (TYP. AT FOUR
CORNERS)
CEILING SUSPENSION SYSTEM
NOTES:
FIXTURES WEIGHING LESS THAN 56 LBS. MAY BE SUPPORTED ON CEILING GRIDS RATED AS "HEAVY DUTY", PROVIDE TWO SLACK 12 GA. SAFETY WIRES ATTACHED TO FIXTURE AT DIAGONAL CORNERS AND TO STRUCTURE ABOVE SUPPORT FIXTERS OVER 56 LBS. WITH FOUR INDEPENDATN TAUT 12 GA. HANGER WIRES ATTACHED TO STRUCTURE. WIRES SHALL BE CAPBABLE OF SUPPORTING FOUR
TIMES THE WEIGHT OF THE FIXTURE
WIRE TIES
TAPE ALL JOINTS AND FINISH AS SPECIFIED
7/8" 26 GA. MIN. HAT CHANNEL
WALL FINISH
GYP. BD.
(1) S-12 SMS @ EA. CHANNEL
PARTITION / STRUCTURAL
ELEMENT
EMBED @ CONC.
1 1/4" MIN.
RUNNER WHICHEVER IS LESS
8" OR 1/4 LENGTH OF THE END 8 GA. HANGER WIRE
W/ 3 TURNS WITHIN
1-1/2" 8 GA. HANGER
WIRE W/ 3 TURN
WITHIN 1-1/2"
1 1/2" X 1.12 #/FT.
MIN. MAIN RUNNER
@ 4'-0" O.C. MAX.
2 1/4" X 7/8" X GA. GALV.
ANGLE W/ #8 SMS @ 16" O.C.
OR .145Ø SHOT PINS @ 16"
O.C. @ CONC. WALL 1-1/4"
MIN. EMBED
MIN.
1/2"
WALL FINISH
TAPE ALL JOINTS AND FINISH AS SPECIFIED
PARTITION / STRUCTURAL
ELEMENT
8 GA. HANGER WIRE W/
3 TURNS WITHIN 1-1/2"
(1) S-12 SMS @ EA. CHANNEL
GYP. BD.
1 1/2" X 1.12 #/FT. MIN.,
MAIN RUNNER @ 4'- 0"
O.C. MAX.
7/8" 26 GA. MIN HAT
CHANNEL
EMBED @ CONC.
1 1/4" MIN
RUNNER WHICHEVER IS LESS
8" MAX. OR 1/4 OF LENGTH OF THE END
1 3/8" X 7/8" X GA. GALV.
ANGLE W/ ATTACHMENT TO
STRUCTURE NOT FINISH W/ (1)
#8 SMS @ 16"O.C. OR
SHOT .145 DIA PINS @ 16" O.C.
@ CONC. WALL 1 1/4" MIN.
EMBED.
MIN.
1/2"
M A
X
1/
2"
1"
PARTITION AS
SCHEDULED; SEE
PLAN FOR TYPE
ACOUSTICAL PANEL
ANGLE MOLDING
GRID
LOOSE SCREW
PARTITION AS
SCHEDULED; SEE PLAN
FOR TYPE
ACOUSTICAL PANEL
ANGLE MOLDING
GRID
TIGHT SCREW
1"
350IU20
250IU20
158IU200.24IN
STRUTrREQ
0.382 0.399 0.410
RSUPP.LENGTH
4'
400IU20 0.380
COMPRESSION STRUT:
1" Ø COMPRESSION STRUT. COMPRESSION
STRUT SHALL NOT REPLACE HANGER WIRE
TYPICAL:
12 GAUGE BRACING WIRE W/
MIN. 4 TIGHT TURNS IN 1-1/2"
BOTH ENDS OF WIRE
MAIN RUNNER
CROSS RUNNER
2" MAX. FROM BRACING
WIRES TO CROSS
RUNNERS
4'-0"
MAX.
4'-0" MAX.
45° MAX. TYP.45° MAX. TYP.
TYPICAL:
12 GAUGE VERTICAL HANGER
WIRE @ 4'-0" EACH WAY W/
MIN. 3 TIGHT TURNS IN 1-1/2"
BOTH ENDS OF WIRE
2 x 4 LIGHT FIXTURE
2 x 4 LIGHT FIXTURE
SPRINKLER HEAD,
DOWNLIGHT OR
CEILING MOUNTED
ITEMS
DIFFUSER OR GRILLE, OR 2 X
2 LIGHT FIXTURE
2x2 OR 2x4 DIVIDED TILE
2x4 CEILING
EQ EQ
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
SPRINKLER HEAD,
DOWNLIGHT OR
CEILING MOUNTED
ITEMS
DIFFUSER OR GRILLE, OR 2 X
2 LIGHT FIXTURE
1'-0" 2'-0" 1'-0"
EQ EQ
2'-0" 2'-0"
1'-0" 1'-0" 1'-0" 1'-0"
SEE PLAN
FOR HEIGHT
SEE PLAN
FOR HEIGHT PAINT OF WALL COVERING
APPLIED TO GWB CEILING
ACOUSTICAL PANEL
ANGLE MOLDING
GRID
LOOSE SCREW
SOFFIT FRAMING TO
STRUCTURE ABOVE
4"
MIN. 6
REFER TO PLAN
5/8" GYP. BD. OVER 3 5/8" X 25
GA. METAL STUDS @ 24" O.C.
3 5/8" X 25GA. BRACE @ 4'-0"
O.C. (TYP.)
GYPSUM WALLBOARD CEILING
SEE PLAN
FOR HEIGHT
6"
SEE PLAN
FOR HEIGHT
SEE PLAN
FOR HEIGHT
CEILING AS SCHEDULED,
SEE PLAN FOR TYPE
WIRE HANGER AS
REQUIRED BY CEILING
GRID SYSTEM
REFER TO PLAN
5/8" GYP. BD. OVER 3 5/8" X 25
GA. METAL STUDS @ 24" O.C.
3 5/8" X 25GA. BRACE @ 4'-0"
O.C. (TYP.)
GYPSUM WALLBOARD CEILING
SEE PLAN
FOR HEIGHT
6"
SEE PLAN
FOR HEIGHT
SEE PLAN
FOR HEIGHT
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
5/8" GYPSUM
WALLBOARD
3 5/8" METAL
STUD FRAMING
SEE PLAN
FOR HEIGHT
ACOUSTICAL
CEILINGS
REFER TO RCP REFER TO RCP REFER TO RCP
6"
SEE PLAN
FOR HEIGHT
SEE PLAN
FOR HEIGHT
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
SEE PLAN
FOR HEIGHT
ACOUSTICAL
CEILINGS
6"
SEE PLAN
FOR HEIGHT
5/8" GYPSUM
WALLBOARD
REFER TO RCP
SEE PLAN
FOR HEIGHT
SEE PLAN
FOR HEIGHT
SEE PLAN
FOR HEIGHT
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
3 5/8" METAL
STUD FRAMING
SEE PLAN
FOR HEIGHT
ACOUSTICAL
CEILINGS
REFER TO RCP REFER TO RCP
6"
SEE PLAN
FOR HEIGHT
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
SEE PLAN
FOR HEIGHT
ACOUSTICAL
CEILINGS
5/8" GYPSUM
WALLBOARD
6"
SEE PLAN
FOR HEIGHT
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
EXISTING FRAMING AND
GYPSUM WALLBOARD TO
REMAIN
REFERENCE PLAN EXISTING TO REMAIN EXISTING TO REMAIN
SEE PLAN
FOR HEIGHT
5/8" GYPSUM
WALLBOARD
8'-6"
EXISTING SOFFIT
EXISTING SOFFIT
EXISTING SOFFITS AND
WALLS TO BE PATCHED
AND PAINTED TO MATCH
EXISTING AS REQUIRED
PARTITION AS
SCHEDULED
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE EXISTING FRAMING AND
GYPSUM WALLBOARD TO
REMAIN
EXISTING TO REMAIN EXISTING TO REMAIN
8'-6"
EXISTING SOFFIT
EXISTING SOFFIT
EXISTING SOFFITS AND
WALLS TO BE PATCHED
AND PAINTED TO MATCH
EXISTING AS REQUIRED
SEE PLAN
FOR HEIGHT
ACOUSTICAL
CEILINGS
6"
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
5/8" GYPSUM
WALLBOARD TO BE
PATCHED AND PAINTED TO
MATCH EXISTING AS
REQUIRED
EXISTING FRAMING
SEE PLAN
FOR HEIGHT
ACOUSTICAL
CEILINGS
REFER TO RCP REFER TO RCP REFER TO RCP
6"
SEE PLAN
FOR HEIGHT
DIAGONAL METAL STUD
BRACE @ 4'-0" O.C. TO
STRUCTURE ABOVE
EXISTING TO
REMAIN
3 5/8" METAL
STUD FRAMING
SEE PLAN
FOR HEIGHT
1/8" = 1'-0"A9
DIAGRAMATIC PLAN: ACOUSTICAL
CEILING SUSPENDED SYSTEM
1/8" = 1'-0"A6
DIAGRAMATIC PLAN-GYP. BD. SUSPENSION
SYSTEM
NTSC9
FIXTURE SUSPENSION AT LAY IN PANEL
CEILING
6" = 1'-0"C6
GYP. BD. PERIMETER PERPENDICULAR
TO MAIN RUNNER
6" = 1'-0"C4
GYP. BD PERIMETER PARALLEL
TO MAIN RUNNER
6" = 1'-0"C8 SLIP CONNECTION AT CEILING PERIMETER
6" = 1'-0"D8
SUSPENDED ACOUSTICAL CEILING
HORIZONTAL CEILING STRUT- FIXED END
3/4" = 1'-0"A8 TYP. ACOUSTICAL CEILING BRACING
1/2" = 1'-0"F9 TYP. CEILING TILE LAYOUTS
1" = 1'-0"F4 SOFFIT AT WALL
3" = 1'-0"F8 CEILING DETAIL AT WAITING ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:0
P
M
A-571
ARCHITECTURAL CEILING DETAILS 520-331
JACC-2F
09.26.2022 M. PERKINS L. BELL
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
1 1/2" = 1'-0"F6 SOFFIT DETAIL AT ACOUSTICAL CEILING TILE
1 1/2" = 1'-0"D6 SOFFIT DETAIL WITH GYP CEILING
1" = 1'-0"F1 DOUBLE STEP DOWN SOFFIT AT ACOUSTICAL CEILING TILE
1" = 1'-0"D4 SOFFIT AT ACOUSTIC CEILING TILE
1" = 1'-0"E1 STEP DOWN SOFFIT AT ACOUSTICAL CEILING TILE
1" = 1'-0"C1 STEP DOWN SOFFIT AT WALL
1" = 1'-0"B4 STEP DOWN SOFFIT AT WALL ATRIUM
1" = 1'-0"B1 STEP DOWN SOFFIT ATRIUM AT ACOUSTICAL CEILING TILE
F
FLUSH
2' -9
3'
-7
1'-0" 4"
N
T
NARROW VISION
3' -0
3'
-4
G
6"6"
HALF GLASS
T
FG
5" 5"
5"
T
FULL GLASS
TYPICAL FRAME
2" H
E
IG
H T
2" WIDTH 2"
TERMINATED STOPS
4"
TERMINATED
STOPS @
INTERIOR
DOORS ONLY
xT
MASONRY HEAD
xM
T Y
P
4"
2"
1/2" 1/2"VARIES
SEE PLAN
WALL - SEE PLAN FOR
TYPE
SEALANT - EA. SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
1/ 2"
V A
R
IE
S S
E E
P
LA
N 1/
2"
4" 2"
ADJACENT WALL WHERE
OCCURS
SEALANT - EA SIDE & ALL
AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN FOR
TYPE
2"
6"
BRICK VENEER
UNIT
HOLLOW METAL
FRAME
SEALANT, TYP.
2 1/2"
WALL TYPE AS SCHEDULED
METAL FLASHING
OVERLAP WATER-
RESISTANT
BARRIER AND
FLASHING
STEEL ANGLE
LINTEL -
SEE STRUCTURAL
WEEPS (2 MIN) EQ SPACED
ABOVE OPENING (24" O.C. MAX)
2"
6"
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
BRICK VENEER UNIT
STEEL ANGLE SUPPORT -
SEE STRUCTURAL
STUD COLUMN - SEE FRAMING
DETAILS
RETURN WALL FINISH
AT OPENING
1/
2"
W A
LL
T
Y P
E A
S S
C H
E D
U
LE
D
INTERIOR DOUBLE HUNG
WINDOW
SEALANT AND BACKING ROD
EACH SIDE & ALL AROUND,
TYP.
SHIM SPACE AS REQUIRED
ATTACH TO FRAMING PER
MANUFACTURER
STUD BOX BEAM HEADER
VARIES - SEE PLAN
V A
R
IE
S S
E E
P
LA
N
SEALANT & BACKER ROD -
EACH SIDE & ALL AROUND,
TYP.
INTERIOR DOUBLE
HUNG WINDOW
SHIM AS REQUIRED
ATTACH TO FRAMING
PER MANUFACTURER
INTERIOR DOUBLE
HUNG WINDOW
SEALANT AND BACKING ROD
EACH SIDE & ALL AROUND,
TYP.
SHIM SPACE AS REQUIRED
ATTACH TO FRAMING PER
MANUFACTURER
VARIES - SEE PLAN
COUNTERTOP WHERE OCCURS
2' -8
6'
-0
4'-0"
4' -3
1'
-9
W1 W1S
5' -6
16'-0 1/2"
2' -7
2'
-1 1"
3'-6 1/2" * 3'-6" * 1'-11" * 3'-6" * 3'-7" *
W1F * NOTE: MATCH EXISTING
VERTICAL MULLION
SPACING, VERIFY IN FIELD
A-601
A-601
LAB
DOUBLE
HUNG
COUNTERTOP TO BE
COORDINATED WITH PLAN
WINDOW TO LOCK AND
OPERATE FROM LAB SIDE
GLAZING FILM (GF-1) TO BE APPLIED
ON GLAZING FROM LAB SIDE
3'-0"
2' -1
0" 4'
-0
E1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:1
P
M
A-601
ARCHITECTURAL SCHEDULES 520-331
JACC-2F
09.26.2022 M. PERKINS C. LOWERY
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME
FIRE
RATING
DETAIL HARDWARE
NOTESROOM NO. ROOM NAME DOOR NO.
WIDTH
H T TYPE MATERIAL TYPE MATERIAL HEAD JAMB ELEC GROUPW1 W2
TOTAL
WIDTH
SECOND FLOOR
2G100 WAITING ROOM 2G101 4' - 0" 7' - 0" 1 3/4" N WD 1 HM 45 MIN D8/A601 D9/A601 AC, ADO, RR, REX HW-5D DOOR FROM PHLEBOTOMY WAITING TO BLOOD DRAW
2G100A RESTROOM 2G100A 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G103 RECEPTION 2G103 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-3G PROVIDE OVERHEAD 90 DEGREE STOP
2G112 RESTROOM 2G112 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G114 RESTROOM 2G114 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G116 RESTROOM 2G116 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G117 CORE LAB 2G117C 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 AC, ADO ,REX HW-5D DOOR FROM BLOOD DRAW TO CORE LAB
2G117 CORE LAB 2G117A 3' - 4" 3' - 4" 6' - 8" 8' - 0" 1 3/4" N/N WD 1 HM 45 MIN D8/A601 D9/A601 AC, ADO, REX HW-10B DOOR FROM SOUTH CORRIDOR TO CORE LAB
2G117 CORE LAB C2-101B 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-1F
2G117A VESTIBULE 2G117B 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 AC, REX HW-5D DOOR FROM STAFF LOUNGE TO CORE LAB
2G118 RESTROOM 2G118 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G119 STERILE SUPPLY 2G119 3' - 6" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G120 BULK STORAGE 2G120 3' - 0" 3' - 0" 6' - 0" 8' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-10B
2G122 NEG. PRESSURE LAB MICROBIOLOGY 2G122 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 ADO, REX (X2) HW-4A MICROBIOLOGY LAB DOOR
2G123 LAB OFFICE TOUCHDOWN 2G123 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G125 LAB OFFICE 2G125 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G126 STAFF RESTROOM 2G126 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G127 LAB OFFICE 2G127 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G128 CONSULT 2G128 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-1G
2G129 CONSULT 2G129 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-1G
2G130 FILE CLOSET 2G130 3' - 4 1/2" 7' - 0" 1 3/4" F WD SLIDING MFG'R D8/A601 D9/A601 ADA-1 SLIDING BARN DOOR
2G131 ELECTRICAL 2G131 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G132 HAC 2G132 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G134 RECEPTION 2G134 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-3G
2G135 INFUSION CLINIC C2-99 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 REX, AC, DPS HW-5D
2G135 INFUSION CLINIC C2-97A 3' - 6" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC, RR, REX HW-5D FROM INFUSION CLINIC TO WAITING ROOM
2G136 EXAM / CONSULT 2G136 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-1G
2G137 ADMIN SUPPORT 2G137 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G138 RESTROOM 2G138 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G139 RESTROOM 2G139 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G140 SOILED UTILITY 2G140 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G141 STERILE SUPPLY 2G141 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G142 MED ROOM 2G142 3' - 4" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC, REX HW-SH-3 MED ROOM DOOR
2G143 CONFERENCE/ BREAK ROOM 2G143 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 HW-4
2G144 STAFF RESTROOM 2G144 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G145 TELECOM ROOM 2G145 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC, DUAL, DPS, REX HW-SH-3
C2-101 CORRIDOR C2-101A 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC HW-5D 2G - CORE LAB STAFF AREA TO ATRIUM
STAIR-F STAIR C2-97B 3' - 0" 7' - 0" 1 3/4" N WD 1 HM 90 MIN D8/A601 D9/A601 PEX HW-1E
Grand total: 38
DOOR MODIFICATIONS
DOOR & FRAME NOTES:
ALARM DELAYED DOOR ALARM (DOOR IS EXIT ONLY)
A LAMINATED GLASS
A1 INSULATED TEMPERED LAMINATED GLASS
AC ACCESS CONTROL DEVICE
ADO AUTOMATIC DOOR OPERATOR
D DOUBLE GLAZED TEMPERED GLASS
DEML DELAYED EGRESS MAGNETIC LOCK
DEPH DELAYED EGRESS PANIC EXIT DEVICE
DPS DOOR POSITION MONITORING SWITCH
DUAL DUAL AUTHENTICATION ACCESS CONTROL
EL ELECTRIC LOCK OR ELECTRIC LEVER EXIT DEVICE
ELR ELECTRIC LATCH RETRACTION EXIT DEVICE
EMCH ELECTRO-MECHANICAL CLOSER-HOLDER
F FIRE RATED GLAZING
H ELECTRIC HOLD
KS KEYSWITCH
MHO MAGNETIC HOLD OPEN
ML MAGNETIC LOCK
PEX PUSH TO EXIT PUSH BAR EXIT DEVICE
REX REQUEST TO EXIT SWITCH IN LATCHING DEVICE INSIDE
TRIM
RR REMOTE RELEASE BUTTON
SEC SECURITY ALARM FOR PIV OFFICE
T TEMPERED GLASS
U UNDERCUT 1"
FRAME TYPE NOMENCLATURE
X x
DENOTES FRAME SUB-TYPE
DENOTES FRAME TYPE
(SEE ADJACENT FRAME TYPE ELEVATIONS)
FRAME SUB-TYPES
M MASONRY HEAD
(SEE ADJACENT FRAME SUB-TYPES ELEVATIONS)
MT MASONRY HEAD AND TERMINATED STOPS
(SEE ADJACENT FRAME SUB-TYPES ELEVATIONS)
T TERMINATED STOP
(SEE ADJACENT FRAME SUB-TYPES ELEVATIONS)
NOTES
1. SEE DOOR SCHEDULE FOR DOOR WIDTH AND HEIGHT
2. INSET FRAME DEPTH/THROAT IS 6" UNLESS OTHERWISE
NOTED
3. INSET FRAME'S HEAD WIDTH IS 2" UNLESS DENOTED AS
MASONRY HEAD
4. WRAPPED FRAME'S HEAD WIDTH IS 2"
DOOR PANEL TYPES
DOOR FRAME TYPES
3" = 1'-0"D8 HM - TYP. INTERIOR HEAD
3" = 1'-0"D9 HM - TYP. INTERIOR JAMB
3" = 1'-0"E8 HM HEAD - BRICK VENEER, STUD WALL
3" = 1'-0"F8 HM JAMB - BRICK VENEER, STUD WALL
DOOR HARDWARE LEGEND
HW-1 Public Restrooms - Passage, with Closer
HW-1E Rated, Non-locking - Passage, With Rim Exit (Panic) Device, Closer
HW-1F Corridor - Passage (F01 Lockset)
HW-1G Exam Rooms - Passage (F01 Lockset) w/ Privacy Deadbolt
HW-2G Single Restrooms - Privacy Locking (F13 Lockset), With Closer
HW-3G Offices - Office Locking (F04 Lockset)
HW-4
Waiting, Conference, Staff Lounge - Classrom Locking (F05/F84 Lockset) with overhead stop
HW-4A Same as Above - Same as Above, with Auto Door Opener
HW-5B Rated, Storage - Storeroom Locking (F07 Lockset) with Closer
HW-5D Storage - Storeroom Locking (F07 Lockset) with Closer
HW-10B Double Doors - Storeroom Locking (F07 Lockset) with Closer, Overhead Stop
HW-SH-3
Secured Access Door - Storeroom Locking (F07 Lockset) with Closer, Overhead Stop, Alarm Contact, Card Reader
HW-SH-12
Stair to Exterior - Electrified Rim Exit (Panic) Device, w/ Closer. No Exterior Hardware
HW-E3
Exterior Roof Access - Storeroom Locking (F13 w/ Rigid outside lever) with closer, overhead stop, threshold, door position switch and power supply.
NOTE: See A-601 and Specification Section 08 71 00 - Door Hardware for more information.
3" = 1'-0"3 INTERIOR WINDOW HEAD
3" = 1'-0"4 INTERIOR WINDOW JAMB
3" = 1'-0"5 INTERIOR WINDOW SILL
1/4" = 1'-0"6 EXTERIOR GLAZING - W1/W1S
1/4" = 1'-0"7 EXTERIOR GLAZING - W1F
1/4" = 1'-0"8 INTERIOR GLAZING - E1
WINDOW SCHEDULE
Type Mark Count Length Height
E1 1 3' - 0" 4' - 0"
W1 17 4' - 0" 6' - 0"
W1F 1 16' - 6 1/2" 5' - 4"0 6
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
09 22 16
METAL STUDS
A-720 D1
A-720 B1
07 92 00
SEALANT BOTH SIDES
09 29 00
5/8" GWB
07 92 00
SEALANT BOTH SIDES
CEILINGCEILING
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 22 16
METAL STUDS
09 29 00
SOUND ATTENUATION
BATTS (SAB), WHERE
OCCURS
AT CHASE WALLS
REFER TO PLAN
1'-4" MIN AT SINGLE
1'-10" MIN AT DOUBLE,
WALL HUNG FIXTURE
CROSS BRACING GUSSETS AT
48" O.C. MAX VERTICALLY.
FABRICATED FROM 6" MTL
STUDS
A-720 D1
07 92 00
SEALANT BOTH SIDES
09 29 00
5/8" GWB PER SIDE
07 92 00
SEALANT BOTH SIDES
CEILING
A-720 B1
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
NOTE:
IF PARTITION TYPE IS USED IN A
CHASE WALL CONDITION, PROVIDE
CROSS BRACING GUSSETS AT 48"
O.C. MAX VERTICALLY. FABRICATED
FROM 6" MTL STUDS.
6”
09 29 00
5/8" GWB
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
07 92 00
SEALANT
09 22 16
METAL STUDS
A-720 E1
LINE OF
STRUCTURE
LINE OF
STRUCTURE
FACE OF WALL OR COLUMN
6”
09 22 16
FURRING CHANNELS
09 22 16
FURRING CHANNEL
HORIZONTAL AT TOP OF GWB
CEILING
07 92 00
SEALANT
09 29 00
5/8" GWB
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
5/8" ACOUSTICALLY ENHANCED
GWB 2 LAYERS
07 92 00
SEALANT BOTH SIDES
07 92 00
SEALANT BOTH SIDES
09 29 00
SOUND ATTENUATION
BATTS (SAB)
09 22 16
METAL STUDS
09 29 00
5/8" ACOUSTICALLY
ENHANCED GWB 2
LAYERS
CEILINGCEILING
A-720 D1
A-720 B1
1/
2" 1/
2" M
IN 09 22 16
2"x16 GA STRAPS
AT 16" O.C.
09 22 16
30 MIL Z-BARS TO
ACCOMMODATE
SFRM THICKNESS
07 81 16
FIREPROOFING
DESIGN BASIS: UL-HW-D-0044
CONCRETE SLAB
09 22 16
METAL STUDS
DESIGN BASIS: UL-HW-D-0043
METAL DECK
(PERPINDICULAR TO FLUTES)
DESIGN BASIS: UL-HW-D-0264
METAL DECK
(PARALLEL TO FLUTES)
09 22 16
METAL STUDS
DESIGN BASIS: UL-HW-D-0252
STEEL BEAM
1/ 2"
M
IN
1/
2"
1/
2" 1/
2" M
IN
09 29 00
5/8" GWB 1 OR 2 LAYERS,
REFER TO PARTITION TYPE
1/ 2"
M
IN
1/
2"
09 29 00
5/8" GWB 1 OR 2 LAYERS,
REFER TO PARTITION TYPE
07 84 00
MINERAL WOOL
07 84 00
FIRESTOPPING
07 84 00
MINERAL WOOL
07 84 00
FIRESTOPPING
07 84 00
MINERAL WOOL
SLOTTED DEEP LEG
DEFLECTION TRACK
SLIP CONNECTION
VERTICAL STUD
GENERAL NOTES
1. CONDITIONS INDICATED SHOW DESIGN INTENT, ESPECIALLY IN REGARD TO ACCOMMODATION OF STRUCTURAL DEFLECTION AND CONTINUITY OF INTEGRITY OF SOUND, SMOKE AND FIRE WALLS.
2. DESIGN INTENT DETAILS ARE NOT INTENDED TO BE PROPRIETARY. CONTRACTOR MAY EMPLOY SIMILAR HEAD-OF-WALL DESIGNS AND COMPONENTS AS APPROPRIATE FOR CONDITIONS.
3. DESIGN INTENT DETAILS MAY NOT SHOW ALL CONDITIONS TO BE ENCOUNTERED ON A PROJECT. COMPLY WITH MANUFACTURER AND UL APPROVED METHODS FOR ATYPICAL CONDITIONS.
4. SECURE TOP OF INTERIOR PARTITIONS TO SUPERSTRUCTURE IN A WAY THAT PROVIDES LATERAL STABILITY (PERPENDICULAR-TO AND IN-PLANE WITH WALL) YET ALLOWING FOR A MINIMUM OF 3/4" OF VERTICAL
DEFLECTION OF THE SUPERSTRUCTURE.
5. RIGIDLY SECURE SLOTTED TOP TRACK TO BUILDING SUPERSTRUCTURE IN AN APPROVED MANNER. EMPLOY Z-BARS, COLD-ROLLED CHANNELS OR SIMILAR SPACER TO ACCOMMODATE THICKNESS OF SECTION
07 81 16 FIREPROOFING.
6. SLOTTED TOP TRACK, INDICATED ON THESE DETAILS, IS THE BASIS FOR DESIGN AND REFERS TO DEEP-LEG TRACKS WITH VERTICALLY SLOTTED HOLES. OPTIONAL MANUFACTURERS MAY PROVIDE SIMILAR, PROPRIETARY METHODS IN ACCORDANCE WITH THE PROVISIONS OF SPECIFICATION SECTION 09 22 16.
7. SECURE VERTICAL STUDS TO SLOTTED TOP TRACK AT MID-HEIGHT OF VERTICAL SLOTS IN TRACK. COMPONENTS INTENDED TO SLIDE VERTICALLY AS SUPERSTRUCTURE DEFLECTS.
8. DO NOT SCREW GYPSUM WALLBOARD TO TOP TRACK OR SUPERSTRUCTURE. GWB SCREWS INTO THE STUDS MUST BE AT LEAST 1" BELOW THE BOTTOM OF THE TOP TRACK.
9. REFER TO PARTITION STANDARDS FOR SPECIFIC WALL TYPES.
10. AT FIRE -RATED WALLS REFER TO SPECIFICATION SECTION 07 84 00 FOR ADDITIONAL REQUIREMENTS REGARDING HEAD-OF-WALL CONDITIONS.
11. MAINTAIN ACOUSTIC RATING WHERE SOUND-CONTROL WALLS ARE INDICATED.
12. FIRESTOPPING AND ACOUSTICAL SEALANTS SHALL AUTOBOND. PROVIDE EXPOSED CLEAN SEALANT (TO CONCEAL FIRESTOPPING) AT FOOD SERVICE, FDA INSPECTED PRODUCTION FACILITIES, VIVARIA, BIOLOGICAL
CONTAINMENT AND CLEAN ROOM APPLICATIONS.
13. WHERE A WALL IS DESIGNATED AS BOTH A SOUND-CONTROL WALL AND A FIRE-RATED WALL, REFER TO FIRE-RATED HEAD-OF-WALL CONDITIONS.
14. WHERE A WALL IS DESIGNATED AS A SOUND-CONTROL WALL, FILL ALL VOIDS WITH SOUND ATTENTUATION BATTS (SAB).
15. SMOKE PARTITIONS REQUIRE THAT AT LEAST ONE LAYER OF GWB, AND SOUND-CONTROL WALLS REQUIRE GWB ON BOTH SIDES, BE CUT TO FOLLOW UNDULATING SURFACES OF THE SUPERSTRUCTURE INCLUDING, BUT NOT LIMITED TO, FLUTES IN METAL DECKING. PROVIDE A CONTINUOUS BEAD OF SEALANT (AS SPECIFIED) TO SUPERSTRUCTURE.
ISOMETRIC VIEW OF SLOTTED TOP TRACK
09 22 16 2"x 30 MIL STRAPS
AT 16" O.C.
09 22 16
30 MIL Z-BARS TO
ACCOMMODATE
SFRM THICKNESS
07 81 16
FIREPROOFING
CONCRETE SLAB
09 22 16
METAL STUDS
METAL DECK
(PERPINDICULAR TO FLUTES)
METAL DECK
(PARALLEL TO FLUTES)
09 22 16
METAL STUDS
STEEL BEAM
EQ EQ
GWB SOUND AND SMOKE
CLOSURE STRIP, SECURED
TO STRUCTURE, PROVIDE
ON BOTH SIDES AT SOUND
WALLS
09 22 16 2"x30 MIL STRAPS AT 16" O.C. 09 22 16
30 MIL Z-BARS TO
ACCOMMODATE
SFRM THICKNESS
07 81 16
FIREPROOFING
CONCRETE SLAB
09 22 16
METAL STUDS
METAL DECK
(PERPINDICULAR TO FLUTES)
METAL DECK
(PARALLEL TO FLUTES)
09 22 16
METAL STUDS
STEEL BEAM
MIN. OF ONE LAYER OF
GWB CUT TO FOLLOW
PROFILE OF DECKING
AT SMOKE PARTITION,
BOTH AT SOUND WALLS
FILL FLUTE VOID W/ SAB
EQ EQ
1/
4"
09 29 00
5/8" GWB
07 92 00
SEALANT BOTH SIDES
09 29 00
5/8" GWB
09 29 00
5/8" GWB
07 92 00
SEALANT BOTH SIDES
STEEL LOOSE LINTEL SCHEDULE
FOR USE IN BRICK AND STONE VENEER APPLICATIONS
OPENING
WIDTH
BEARING
EACH END
LINTEL SUPPORT
4'-0" AND BELOW
4'-0" UP TO 6'-0"
6'-0" UP TO 8'-0"
ANGLE 3 1/2" x 3 1/2" x 3/8" 8"
8"
8"
ANGLE 5" x 3 1/2" x 3/8"
ANGLE 6" x 4" x 3/8"
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
ESTIMATED
LENGTH
A4 4" 5 1/4" 35 1587'
A6 6" 7 1/4" 35 54'
A8 8" 9 1/4" 35 31'
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED CHASE WALLS: UL U420
(TYPE E) CHASE PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
ESTIMATED
LENGTH
E4 4" 4 5/8" 45 70'
(TYPE J) NON-RATED PARTITION
MARK STUD WIDTH PRTN WIDTH
ESTIMATED
LENGTH
J2 2 1/2" 3 1/8" 3'
J3 3 5/8" 4 1/4" 30'
J4 4" 4 5/8" 363'
J6 6" 6 5/8" 17'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:5
P
M
A-720
ARCHITECTURAL STANDARD PARTITION TYPES 520-331
JACC-2F
09.26.2022 M. PERKINS C. LOWERY
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
1. PARTITIONS ARE DISTINGUISHED ON FLOOR PLANS BY SYMBOL
DESIGNATION, GRAPHIC DESIGNATION OR A COMBINATION OF BOTH
DESIGNATIONS. SOME PARTITION TYPES SHOWN ON THIS SHEET MAY NOT BE
USED ON THIS PROJECT.
2. ALL WALLS NOT DESIGNATED WITH A GRAPHIC OR TAG TO BE TYPE A. IF
UNCLEAR CONTACT ARCHITECT.
3. "METAL STUDS" INDICATED ON THIS SHEET FOR INTERIOR PARTITIONS
REFER TO THOSE SPECIFIED IN SECTION 09 22 16 - NON STRUCTURAL METAL
FRAMING. REFER TO SPECIFICATIONS FOR ADDITIONAL CRITERIA SUCH AS
MINIMUM STUD SPACING, MINIMUM GAUGE AND PERMISSIBLE DEFLECTION
LIMITS. SEE SECTION 05 41 04 LOAD BEARING METAL STUD SYSTEM FOR
FRAMING THAT IS OUTSIDE THE SCOPE OF 09 22 16 AND ASTM C754, SUCH AS
LONG HEADERS, CANTILEVERED WALLS, TALL WALLS, WALKABLE CEILINGS
AND THEIR SUPPORTS, WALLS EXCEEDING SPAN TABLES AND OTHER UNUSUAL
FRAMING CONDITIONS.
4. SOUND TRANSMISSION CLASS (STC) IS A RATING SYSTEM THAT DESCRIBES
THE ABILITY OF AN ASSEMBLY TO REDUCE THE TRANSMISSION OF SOUND.
CONFIGURE SOUND-RATED WALL ASSEMBLIES ACCORDING TO THE MINIMUM
REQUIREMENTS STIPULATED IN THE STC TESTS LISTED. STC RATINGS LISTED
ARE BASED ON LABORATORY TESTING AND ARE NOT INDICATIVE OF RESULTS
IN FIELD.
5. REFER TO SECTION 09 29 00 FOR ACOUSTIC SEALANTS.
6. SOUND ATTENUATION BATTS (SAB) ARE SPECIFIED IN SECTION 09 29 00.
WHERE SAB ARE INDICATED, THEY SHALL EXTEND CONTINUOUSLY FROM
FLOOR TO STRUCTURE ABOVE.
7. PARTITIONS ARE INDICATED WITH CONVENTIONAL GYPSUM WALLBOARD
U.N.O.; UPGRADE TO PREMIUM TYPES OF WALLBOARD (I.E., MOISTURE-
RESISTANT, TILE-BACKER BOARD, ACOUSTICALLY ENHANCED, ETC.) BASED ON
THEIR LOCATION AND ACCORDING TO REQUIREMENTS OF SECTION 09 29 00.
8. SEALANTS INDICATED MAY BE FOR FIRE RATING, SMOKE RATING, AIR
PRESSURE CONTAINMENT, ACOUSTIC RATING, VERMIN CONTROL, MOVEMENT
(CRACK) CONTROL AND/OR BIOLOGICAL CONTAINMENT. SEALANT JOINTS ARE
TO BE SIZED FOR EXPECTED MOVEMENT OF JOINT WITH
EXPANSION/CONTRACTION CAPACITY OF SEALANT MATERIAL TO MAINTAIN
THE INTEGRITY OF THE SEAL FOR THESE APPLICABLE PARAMETERS. SEE
SPECIFICATION SECTION 07 92 00 FOR INTERIOR JOINT SEALANTS.
9. REFER TO SECTION 07 84 00 FOR HEAD-OF-WALL FIRESTOPPING AND
SEALING OF THRU-WALL PENETRATIONS.
10. "LINE OF STRUCTURE" INDICATED FOR EACH PARTITION IS DIAGRAMATIC
ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION CONDITIONS OR
GEOMETRY.
11. ALL DIMENSIONS ARE FROM FACE TO FACE, OR CENTERLINE TO
CENTERLINE, U.N.O. REFER TO PARTITION MATRICES FOR PARTITION WIDTH
DIMENSIONS UNLESS INDICATED TO BE SHOWN ON PLAN.
12. LEAD LINING REQUIREMENTS ARE SPECIFIED IN SECTION 09 29 00. WHERE
LEAD LINING IS INDICATED IN PLAN, LEAD LINING IS TO BE PLACED ON
RADIOGRAPHIC SIDE OF ROOM AND TO EXTEND UP TO 7'-0" A.F.F., U.N.O. LEAD
THICKNESS TO BE SPECIFIED BY OWNER'S PHYSICIST REPORT.
13. AT LEAD LINED PARTITIONS THAT ARE ALSO FIRE RATED, REFER TO FIRE
UL FIRE RESISTANCE TEST U419, U430 OR U439.
14. FIRE RESISTANT AND FIRE RESISTANT SMOKE BARRIER RATINGS ARE TO
CONTINUE THROUGH ALL OPENINGS IN RATED PARTITIONS.
15. SMOKE RESISTANT, FIRE RESISTANT, AND FIRE RESISTANT SMOKE
BARRIER PARTITIONS SHALL EXTEND AND SEAL TO INSIDE FACE OF EXTERIOR
SHEATHING, INCLUDING EXTENSIONS THROUGH SOFFITS.
16. REFER TO THE TOILET ACCESSORIES SHEET AND CASEWORK SHEET FOR
MOUNTING DETAIL INFORMATION.
17. REFER TO SHEET A-721 AND A-722 FOR ADDITIONAL PARTITION DETAILS
AND FRAMING INFORMATION.
GENERAL PARTITION NOTES:
THE TYPICAL PARTITION TAG SYMBOL DESIGNATION HAS TWO CHARACTERS.
THE FIRST CHARACTER IS A LETTER INDICATING THE PARTITITON TYPE, THE
SECOND CHARACTER IS A NUMERIC INDICATION OF THE STUD OR CMU WIDTH.
IF A "≠" SYMBOL IS SHOWN AS THE FIRST CHARACTER, THIS INDICATES THE
PARTITION DOES NOT HAVE SOUND ATTENUATION. IN SOME INSTANCES, AN
ADDITIONAL CHARACTER OR "MODIFIER" MAY BE ADDED TO THE END AND/OR
THE LINE BELOW TO INDICATE ADDITIONAL CHARACTERISTICS WITHIN THE
WALL. REFER TO CHART BELOW FOR MODIFIER DEFINITIONS.
IF NO PARTITION TAG OR NUMERIC SECOND CHARACTER EXISTS, THE STUD
SIZE WILL BE 4" TYPICAL, U.N.O.
PARTITION TAGGING LEGEND:
PARTITION
MODIFIER MODIFIER DESCRIPTION
S PROVIDE SECURITY MESH AT GWB.
≠ X# X
SYMBOL INDICATES PARTITION TYPE
NO SOUND
ATTENUATION STUD/CMU WIDTH
PARTITION MODIFIER II PARTITION MODIFIER
(SEE CHART BELOW) (SEE CHART BELOW)
NUMERIC STUD CMU
CHARACTER WIDTH WIDTH
1 1 5/8" 2 2 1/2"
3 5/8" 4 4" 3 5/8" 6 6" 5 5/8" 8 8" 7 5/8"
X
(TYPE M) FURRING PARTITION
MARK STUD WIDTH PRTN WIDTH
ESTIMATED
LENGTH
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V484, U411
(TYPE U) HIGH STC PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
3" = 1'-0"B1 STUD PARTITIONS - FIRE RATED PARTITIONS
3" = 1'-0"F1 GENERAL REQUIREMENTS FOR STUD PARTITIONS
3" = 1'-0"E1 STUD PARTITIONS - NON-FIRE, NON-SMOKE, NON-SOUND CONTROL PARTITIONS
3" = 1'-0"D1 STUD PARTITIONS - SMOKE PARTITIONS AND SOUND CONTROL PARTITIONS
1 1/2" = 1'-0"4 LINTEL SCHEDULES
SECTION
ATTACH STUDS TO KNEE
WALL BRACE TUBE
LINE OF
STRUCTURE
09 22 16
METAL STUDS
IN
D
IC
A T
E W
A
LL
H E
IG
H
T
09 22 16
KNEE WALL BRACE
PLAN
STOP METAL STUD
RUNNER AT BASE PLATE
09 22 16
METAL STUD RUNNER
WALL PARTITION
09 29 00
GWB CAP
09 22 16
KNEE WALL BRACE
STOP METAL STUD RUNNER
AT BASE PLATE
07 92 00
SEALANT BOTH SIDES
30 MIL MIN METAL TRACK
30 MIL CLIP ANGLE
FOR 3 5/8" STUDS. 1 1/2" x 5" FOR 6" STUDS
1" X 30 MIL METAL
STRAP AT 3'-6" O.C.,
EACH SIDE
30 MIL MIN METAL
TRACK AT FLOOR
DOUBLE 30 MIL
METAL STUDS AT
BOTH JAMBS
TYPE A
CONT43 MIL 6" WIDE
METAL BACK-UP STRAP
M O
U N
T
IN
G H
E
IG
H T
S R
E F
T Y
P
IC
A L
TYPE B
30 MIL METAL RUNNER
TRACK - CLIP FLANGES
TO FIT OVER STUDS
6" MIN, DEEPER IF
REQUIRED
M O
U N
T
IN
G H
E
IG
H T
S R
E F
T Y
P
IC
A L
TYPE C
M O
U N
T
IN
G H
E
IG
H T
S R
E F
T Y
P
IC
A L
8" MIN, DEEPER IF
REQUIRED
MIN 30 MIL METAL STUDS
FACING OPPOSITE
DIRECTIONS TO ALLOW
MOUNTING PLATE
ATTACHMENT
68 MIL STEEL RUNNER
TRACK-CLIP FLANGES AND
FOLD WEB TO FORM
ATTACHMENT FLANGE
PROVIDE DIAGONAL BRACING (AT 45° TYP) OF TOP
TRACK AT 48" OC MAX BETWEEN FULL HEIGHT
STUDS
DOOR
OPENING
DOOR
OPENING
DOUBLE DOOR OPENING
BELOW CEILING
OPENING
LARGE BELOW CEILING
OPENING
ABOVE CEILING
OPENING
LARGE ABOVE CEILING
OPENING
MOUNTING DETAIL
TYPE B
DOUBLE STUDSDOUBLE
STUDS
DOUBLE STUDS DOUBLE STUDS
DOUBLE
STUDS
4' - 6" MAX 8' - 6" MAX 4' - 6" MAX 8' - 6" MAX
ALL STUDS ARE TO BE 30 MIL
IF GREATER THAN 8' - 6"
8' - 6" MAX 8' - 6" MAX
4' - 6" MAX
30 MIL MIN BOTTOM
TRACK (TYP)
FLOOR LINE
30 MIL MTL TOP TRACK
(TYP UNO)
CEILING LINE
UNDERSIDE OF
SLAB, FLOOR OR
ROOF DECK
2" WIDE 30 MIL METAL
STRAP
OPENING ABOVE
CEILING WHICH
INTERRUPTS LOWER
OPENING JAMB STUDS
STONE VENEER WALLS
54 MIL MIN STUDS AT 30 MIL MIN STUDS AT
WALL MOUNTED
ARCHITECTURAL
CABINETS/MILLWORK/
ATTACHED SHELVING
DOOR
OPENING
D3 A-722
D3 A-722
D2 A-722
D2 A-722
D5 A-722
D5 A-722
D3 A-722
D3 A-722
D2 A-722
D7 A-722
D7 A-722
D7 A-722
D7 A-722
D7 A-722
D7 A-722
D8 A-722
D3 A-722
SEE: (F8/A-722)
NOTES:
1. DETAILS SHOWN ASSUME STUDS ARE SPACED 16" OC
2. ALL STUDS SHALL BE "C" STUDS WITH 1-1/4" RETURN
FLANGE MINIMUM.
3. INDICATES SHELVING OR CABINETRY
4. INDICATES STONE
5. DOUBLE STUDS AT SIDES OF OPENING SHALL NOT BE CUT
FOR DUCTWORK OR ANY OTHER MECHANICAL SYSTEMS.
6. REFER TO A-730 FOR MOUNTING TYPE DETAILS.
7. PROVIDE PARTITION BRACING AT ALL ASSEMBLIES OVER
15'-0" IN HEIGHT, U.N.O.
FINISHED FLOOR
LINE OF CEILING
ADDITIONAL LAYER OF
GWB AT HORIZONTAL IF
WALL IS 2 HR RATED
MECHANICAL
DUCTWORK OR OTHER
OBSTRUCTION
LINE OF STRUCTURE
ABOVE
M A
X H
E
IG
H T
ADDITIONAL LAYER OF
GWB ON BOTH SIDES IF
WALL IS 2 HR RATED
J-RUNNERS
ADDITIONAL LAYER OF
GWB IF WALL IS 2 HR
RATED
J-RUNNER
W/ 25 GA STUDS
MAX SPAN OF 8'-11"
RATING INFORMATION:
FIRE RATING - 2 HOUR TEST:
U.L. Design No. 411
PEI AER-09038
WHI-495-PSH 0154/0167
1" SHAFTWALL LINER
SEALANT BOTH SIDES
SEALANT BOTH SIDES
54 MIL METAL STUD BRACING @ 48" O.C.,
MAX
STUDS TO BE ENCASED IN A RIGID
METAL LATH TO ACCEPT NECESSARY
THICKNESS OF FIREPROOFING TO
ACHIEVE DESIRED RATING 1-1/2" FOR 1
HR AND 2" FOR 2 HR.
3 LAYERS OF 5/8" GWB AT
HORIZONTAL PLANE
MECHANICAL
DUCTWORK
LINE OF STRUCTURE
ABOVE
REFER RCP
W/ DIFFERENT SIZE AND MATERIAL THICKNESS STUDS
VARYING SPANS CAN BE ACHIEVED
5" M
IN
R
E F
M E
C H
A N
IC
A
L
RATING INFORMATION:
FIRE RATING - 2 HOUR TEST:
PEI AER-09038
WHI-495-PSH 0154/0167
SHAFTWALL
SEALANT BOTH SIDES
3 LAYERS OF 5/8" GWB AT
HORIZONTAL PLANE
MECHANICAL
DUCTWORK
LINE OF STRUCTURE
ABOVE
5" M
IN
M A
X H
E
IG
H T
REF RCP
W/ DIFFERENT SIZE AND MATERIAL THICKNESS STUDS
VARYING SPANS CAN BE ACHIEVED
RATING INFORMATION:
FIRE RATING - 2 HOUR TEST:
PEI AER-09038
WHI-495-PSH 0154/0167
MINIMUM 2 HR FIRE
RATED ASSEMBLY
SHAFTWALL
SEALANT
SEALANT
EXTERIOR SHEATHING
SECOND LAYER OF GWB WHERE
INDICATED BY PARTITION TYPE
RATED PARTITION AS
INDICATED ON PLAN, EXTEND
GWB TO INTERIOR FACE OF
EXTERIOR SHEATHING
INTERSECTION AT RATED PARTITION
AND EXTERIOR WALL
CONCRETE WALL
OR COLUMN
SEALANT BOTH SIDES
FURRING PARTITION
AS INDICATED ON PLAN
RATED PARTITION AS
INDICATED ON PLAN
INTERSECTION OF RATED
PARTITION AND CONCRETE
INTERSECTION AT RATED
PARTITION AND CONCRETE
LOWER PRIORITY
PARTITION
HIGHER PRIORITY
PARTITION
INTERSECTION OF CROSS CORRIDOR
DOOR IN RATED PARTITION
M
IN3"
CONCRETE WALL OR
COLUMN
SEALANT
FURRING PARTITION
AS INDICATED ON PLAN
RATED PARTITION AS
INDICATED ON PLAN
M
IN3"
2 5/8"
SECOND LAYER OF GWB WHERE
INDICATED BY PARTITION TYPE
WALL PRIORITY NOTES:
1. WHERE WALLS OF DIFFERENT FUNCTIONS/ RATINGS INTERSECT: WALLS OF HIGHER PRIORITY SHALL BE CONTINUOUS.
2. LOWER PRIORITY WALLS SHALL "ABUT" AND BE "SEALED TO" HIGHER PRIORITY WALLS, BUT SHALL NOT INTERRUPT CONTINUITY OF THE HIGHER PRIORITY WALL.
2"2"
PROVIDE GAP TO FLANKING
WALL STUD TO ALLOW
SPACE FOR GWB TO PASS
PROVIDE GAP TO FLANKING
WALL STUD TO ALLOW
SPACE FOR GWB TO PASS
2" 2"
2"PROVIDE GAP TO FLANKING
WALL STUD TO ALLOW
SPACE FOR GWB TO PASS
2"
SECOND LAYER OF GWB WHERE
INDICATED BY PARTITION TYPE
INTERSECTION AT VARIOUS WALL
PRIORITY CONFIGURATIONS
LOWER PRIORITY PARTITION
HIGHER PRIORITY PARTITION
(MAINTAIN CONTINUITY
PROVIDE GAP TO FLANKING
WALL STUD TO ALLOW
SPACE FOR GWB TO PASS
2"
PROVIDE GAP TO FLANKING WALL STUD
TO ALLOW SPACE FOR GWB TO PASS2"
LOWER PRIORITY PARTITION
HOLLOW METAL FRAME
PROVIDE FIRE SEALANT
AT INTERFACE BOTH SIDES
5/8" GWB ON EACH SIDE
OF METAL STUD
FRAMING AT PENETRATION IN 1-HR FIRE RATED WALL
RATED PARTITION
AS SCHEDULED
MAINTAIN WALL STC AND FIRE
RATING AS SCHEDULED BEHIND
CABINET/APPLIANCE
FRAMING AT PENETRATION IN RATED WALL
PARTITION AS
SCHEDULED
FRAMING AT PENETRATION IN NON-RATED WALL
FRAMING AT PENETRATION IN NON-RATED CHASE
5/8" GWB ON METAL
STUD
PARTITION AS SCHEDULED
FRAMING AT PENETRATION IN NON-RATED WALL
PARTITION AS SCHEDULED
PARTITION AS SCHEDULED
(6" STUD)
CONFIRM RECESS DIMENSIONS
WITH CABINET/APPLIANCE MFR.
PARTITION AS
SCHEDULED
SOUND ATTENUATION
BLANKET COMPRESSED TO
FILL OPENING AT SOUND
RATED PARTITION
L-BEAD
SEALANT BOTH SIDES,
REF SPECS FOR TYPE
CONTROL JOINT
GWB SUSPENDED
CEILING SYSTEM
PARTITION AS
SCHEDULED
CONTROL JOINT,
BOTH SIDES
CONTROL JOINT IN
GWB PARTITION
1/2" MAX
1HR FIRE RATED
WHI-647-3024
MAX
24'-0”
PARTITION AS
SCHEDULED
CONTROL JOINT,
BOTH SIDES
CONTROL JOINT IN 1 HR
FIRE RATED PARTITION
1/2" MAX
MAX
24'-0”
1 1/2"
2 LAYERS OF 5/8" GWB
2HR FIRE RATED
WHI-651-0318.1
PARTITION AS
SCHEDULED
CONTROL JOINT,
BOTH SIDES
CONTROL JOINT IN 2 HR
FIRE RATED PARTITION
1/2" MAX
MAX
24'-0”
1 1/2"
2 LAYERS OF 5/8" GWB
MAX
24'-0”MAX
24'-0”
CONTROL JOINT AT PARTITION INTERSECTION OR
CHANGE IN CONSTRUCTION
1/2" MAX
CONCRETE, MASONRY OR
STEEL CHANGE IN
CONSTRUCTION
ADDITIONAL NOTES:
1. BUILDING CODE REQUIRES THAT "SMOKE
PARTITIONS" BE SEALED TO STRUCTURE AS
INDICATED TO SUCCESSFULLY "LIMIT THE PASSAGE
OF SMOKE".
2. CONDITIONS INDICATED TO SHOW DESIGN INTENT,
AND NOT INTENDED TO BE PROPRIETARY.
CONTRACTOR MAY EMPLOY SIMILAR UL-APPROVED
CONTROL JOINTS DESIGNS THAT ARE APPROPRIATE
FOR THE SPECIFIC CONDITION. JOINTS TO BE SIZED
TO ACCOMMODATE MOVEMENT CAPABILITIES OF
FIRESTOP ASSEMBLY.
PARTITION AS
SCHEDULED
LC-BEAD
SEALANT, REF
SPECS FOR TYPE
CONTROL JOINT IN PARTITION AT
NON-EXPOSED EDGE
CHANGE IN
CONSTRUCTION
1/2" MAX
CONTROL JOINT IN GYPSUM
BOARD CEILING
MAX
24'-0”
MAX
24'-0”
1/2" MAX
DOUBLE 30 MIL
3 5/8" OR 6" METAL STUDS
30 MIL MIN METAL TRACK
30 MIL MIN METAL TRACK
30 MIL CLIP ANGLE
FOR 3 5/8" STUDS. 1 1/2" x 5" FOR 6" STUDS
30 MIL CLIP ANGLE
FOR 3 5/8" STUDS. 1 1/2" x 5" FOR 6" STUDS
30 MIL MIN METAL TRACK
30 MIL CLIP ANGLE
FOR 3 5/8" STUDS. 1 1/2" x 5" FOR 6" STUDS
1" X 30 MIL METAL STRAP
PLATES AT 3'-6" OC EA
SIDE
30 MIL MIN METAL TRACK
AT FLOOR
DOUBLE 30 MIL
METAL STUDS
30 MIL MIN METAL SILL
TRACK BELOW
30 MIL CLIP ANGLE
FOR 3 5/8" STUDS. 1 1/2" x 5" FOR 6" STUDS
3 LAYERS OF 5/8" GWB AT
HORIZONTAL PLANE
MECHANICAL
DUCTWORK
LINE OF STRUCTURE
REF PLAN
R E
F M
E C
H A
N
IC
A L
5" M
IN
RATING INFORMATION:
FIRE RATING - 2 HOUR TEST:
U.L. Design No. 411
PEI AER-09038
WHI-495-PSH 0154/0167
SEALANT BOTH SIDES
SHAFTWALL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:5
P
M
A-722
ARCHITECTURAL PARTITION FRAMING DETAILS 520-331
JACC-2F
09.26.2022 M. PERKINS C. LOWERY
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
3" = 1'-0"D10 KNEE WALL
3" = 1'-0"D2 DOOR OPENING HEADER
3" = 1'-0"D7 DOOR OPENING JAMB STUDS
NTSF8
METAL BACKING DETAILS
FOR ACCESSORIES AND EQUIP.
1/4" = 1'-0"F2 TYPICAL PARTITION INTERIOR FRAMING
1 1/2" = 1'-0"C7 RATED PARTITION WITH OFFSET
1 1/2" = 1'-0"A10
2 HOUR HORIZONTAL ENCLOSURE
AT BOTTOM OF SHAFT
1 1/2" = 1'-0"A8
2 HOUR HORIZONTAL ENCLOSURE
AT DUCTWORK
3" = 1'-0"C4 TYPICAL GYPSUM WALLBOARD PRIORITY DETAILS
1 1/2" = 1'-0"C2 WALL RECESS DETAIL
3" = 1'-0"E2 GYPSUM WALLBOARD CONTROL JOINT DETAILS
3" = 1'-0"D3
DOUBLE DOOR
LARGE OPENING HEADER
3" = 1'-0"D5 OPENING HEADER
3" = 1'-0"D8 LARGE OPENING JAMB STUDS
1 1/2" = 1'-0"A7
2 HOUR HORIZONTAL ENCLOSURE
AT TOP OF SHAFT
NEED TO ASSURE THAT NO LIVE LOAD IS
PLACED ON TOP OF THIS ASSEMBLY AS
IT IS NOT DESIGNED TO CARRY ANY.
NOTE: LOCATE FLUSH ACTIVATION ON WIDE SIDE AT ALL TOILETS - LOCATE FLUSH VALVE BENEATH ADJACENT GRAB BARS. LAYOUTS BASED ON WALL HUNG TOILETS.
STANDARD LAYOUTS SCALE: 1/4" = 1' - 0"
STANDARD MOUNTING DIAGRAMS
1B
4" MAX
AT FEMALE
TOILET ONLY
O F
W E
T W
A
LL
6' -1
T
O F
IN
IS
H
S1
ACCESSIBLE STALL
PLAN DESIGNATION S1
STANDARD STALL
PLAN DESIGNATION S4
S2
END OF ROW
ACCESSIBLE STALL
PLAN DESIGNATION S2
AT FEMALE
TOILET ONLY
F
IN
IS
H
O F
W E
T W
A
LL
6' -1
4"
M A
X
S4
F
IN
IS
H
O F
W E
T W
A
LL
6' -1
3'-6"
STANDARD
URINAL
PLAN DESIGNATION U1
PLAN DESIGNATION U2
AT ACCESSIBLE
30"x48" CLEAR
FLOOR SPACE
AT U2
U1
U2
1' -9
1' -9
REFER PLAN
A C
C E
S S
IB
LE
L A
V
4'
(3 '-2
M
IN
3'
M A
X
A T
FINISH
FLOOR
SECTION
LAV
COUNTER
MIRROR
LAVATORY
SUPPORT
INSULATE
PIPING
1'-6"
MIN
2'-6" 1'-6"
MIN
2'-6" 1'-6"
2' -0
/4
L1
30" X 48" CLEAR
FLOOR SPACE
PLAN
C
LR
O P
N G
D O
O R
(3 4"
M
IN
CLR OPNG)
34" DOOR
(32" MIN.
EQ EQ
EQ EQ
1'-6"
5'-7" FIN TO FIN 5'-7" FIN TO FIN
C
LE
A R
2' -3
M
IN
MAX
1'-7"
M A
X 2'
-1 0"
2' -1
0"
TOILET ACCESSORY MOUNTING DIAGRAM SCALE: 1/4" = 1'-0"
1. ACCESSORIES LISTED MAY HAVE GAPS IN ALPHA-NUMERIC LISTING.
2. ACCESSORIES CAN APPEAR ON FLOOR PLANS OR INTERIOR ELEVATIONS.
3. SOME ACCESSORIES SHOWN ON THIS SHEET MAY NOT BE USED IN THE PROJECT.
REFER TO SPECIFICATION SECTION 10 28 00
4. NOT ALL ACCESSORIES ARE CFCI. REFER TO SPECIFICATION SECTION 10 28 00
FOR TOILET AND BATH ACCESSORIES TO BE PROVIDED BY CONTRACTOR.
5. LOCATIONS OF ACCESSORIES NOT INCLUDED IN 10 28 00 BUT SHOWN ON FLOOR
PLANS AND INTERIOR ELEVATIONS ARE RECOMMNEDED LOCATIONS FOR OFCI OR
OFOI ITEMS.
FINISH FLOOR
TOILET
ACCESSORY
TYPE
MOUNTING DETAIL -
REFER TO SHEET
A-722/F8, UNO
DRAWING
DESIGNATION
P O
IN
T
3'
T O
D
IS
P E
N S
E
PAPER TOWEL
DISPENSER
7 SURFACE
MOUNTED
PAPER TOWEL
DISPENSER
7A RECESSED
LEADING
EDGE OF
TOILET
TOILET
TISSUE
DISPENSER
2 SURFACE MOUNTED
DOUBLE ROLL
WASTE
RECEPTACLE
SURFACE
MOUNTED
WASTE
RECEPTACLE
SEMI
RECESSED
8B
FEMININE NAPKIN
DISPOSAL (WOMEN'S
ONLY)
5 SURFACE
MOUNTED
SOAP
DISPENSER
9H 10 HOLDERS
ROBE
HOOK
1B SINGLE
ACCESSIBLE
T O
P E
D G
E 3'
-0
T O
T O
P E
D G
E 3'
-9
T O
T O
T O
P 2'
-6
6' -0
ROBE
HOOK
1A SINGLE
5' -6
U
N O
A C
C E
S S
IB
LE
4' -0
M
A X
. A T
MOP/BROOM
RACK
SHOWER
CURTAIN ROD,
CURTAIN &
HOOKS
11 SHOWER CURTAIN
ROD
11A SHOWER
CURTAIN
SOAP DISH
12 RECESSED
6' -8
M
IN
3' -4
11B CURTAIN
HOOKS
FINISH FLOOR
TOILET
ACCESSORY
TYPE
MOUNTING DETAIL -
REFER TO SHEET
A-722/F8, UNO
DRAWING
DESIGNATION
G54
A P
P R
O A
C H
M
IN
3'
-6
LA
T
C H
A P
P R
O A
C H
M
IN
4'
-0
O T
H E
R
LINE OF WALL
G541'-6"
1B
ADJACENT
STALL WALL
M
IN
1A
AT FEMALE
TOILET ONLY
WATER CLOSET
LAYOUTS
PLAN DESIGNATION WC1
AT FEMALE
TOILET ONLY
G541'-6"
TYPICAL ADA/ANSI
66" X 72"
TOILET
CLEAR
SPACE
STANDARD ACCESSIBLE LAVATORY LAYOUTS
PLAN DESIGNATION L2
1'-3" MIN.
2"
FRONT OF
LAV
ADJACENT TO WALL
2"
EDGE OF
MIRROR
9V
30" X 48"
LAVATORY CLEAR
SPACE
L2
2"
9V
2"
FLOATING ALONG WALL
REF. PLAN
LINE OF
CONTROLS
M A
X
1' -7
LAVATORY
SUPPORT
COAT HOOK/
RACK
A C
C E
S S
IB
LE
4' -0
M
A X
A T
1E CUSTOM OR
MULTIPLE
OF TOILET
8" FROM EDGE
2' -1
E D
G E
O F
T
LT
8" F
R O
M
E D
G E
O F
T
LT
8" F
R O
M
E D
G E
O F
T
LT
8" F
R O
M
E D
G E
O F
T
LT
8" F
R O
M
L2
R E
F P
LA
N
2' -2
M
IN
REF PLAN FOR EXTENT
OF WALL RETURN
SURFACE
MOUNTED
HORIZONTAL
WC1 = TYPICAL STAFF OR PUBLIC TOILET
SHOWER SEAT
C
17 WALL MOUNTED
BABY
CHANGING
STATION
21 HORIZONTAL
MOLDED HDPE
STAINLESS
STEEL
FRAMED
MIRROR
13T
T O
P O
F B
A R
4' -0
TOWEL BAR
16 18" LONG
1' -6
STAINLESS STEEL
SHELF
15 16" W X 6" D
4' -0
U
N O
B B B B
SPECIMEN
PASS BOX
TURNTABLE18
C O
N T
R O
L 4'
-0
M A
X T
O
HAND DRYER
SURFACE
MOUNTED
A
TO FIN
1'-3" MIN.
9V
30" X 48"
LAVATORY CLEAR
SPACE
L2
REF. PLAN
L2
9"9" 9"9"
9V
S E
C T
REF PLAN
STANDARD ACCESSIBLE
COUNTER MULTI-LAVATORY
PLAN DESIGNATION L1
3' -6
1'
-0
URINAL
MIN 60"
LONG
HOSE
HAND HELD SHOWER/
SHOWER HEAD
WALL HUNG TOILET
2 1/2"
SERVICE SINK
PARTITION
TYPE C
MOUNTING
TOILET OR
URINAL
PARTITION
1'
5" M
A X
T O
R
IM
A
T A
D A
4' -0
6' -6
1/
4"
T O
0"
F
LU
S H
H N
D L
M A
X T
O
F
LU
S H
H A
N D
LE
M
A X
T O
2' -0
FRONT SIDE
M A
X
SOAP
DISPENSER
9A COUNTER
MOUNTED
36" X 48" CLEAR
FLOOR SPACE
STAINLESS STEEL
FRAMED MIRROR
13 18" W X 36" H
SURFACE MOUNTED
24" W X 60" H
SURFACE MOUNTED
S U
R
FA
C E
3' -4
M
A X
T O
B .O
. R E
F L.
B
FEMININE NAPKIN/
TAMPON DISPENSER
(PUBLIC WOMEN'S
ONLY)
4 SEMI-RECESSED
1'-6"
66" X 72" TLT
CLR SPACE
MINIMUM TOILET DIMENSIONS
1'-3"
7'-7" MIN CLR
NOTE:
1. THE MINIMUM WET WALL DIMENSION IS APPLICABLE WHEN BOTH WATER
CLOSET AND LAVATORY ARE ON SAME WALL.
2. PROVIDE TA-1A AND TA-1B ON THE TOILET ROOM SIDE OF DOOR AT ALL
SINGLE TOILET ROOMS.
30" X 48" LAV
CLR SPACE
22 42 00
HSKP SINK
NOTE: VERIFY CLEAR DIMENSIONS
WITH SHOWER MANUFACTURER
T O
P O
F S
E A
T
-1 9"
T O
1'-6"
66" X 72" TLT
CLR SPACE
1' -3
7'-0 1/4" MIN CLR
30" X 48" LAV
CLR SPACE
T O
C .L
2'
-1 0"
REFER TO PLAN FOR LENGTH
AND CONFIGURATION
GRAB BAR
24"G24
36"G36
ACCESSIBLE TOILET OR
SHOWER L-SHAPED GRAB
BAR
T O
C .L
2'
-1 0”
54 X 42 -
NON-SLIP FINISH
G5442"G42
48"G48
CC
TYPICAL HAC ROOM
PAPER TOWEL
DISPENSERS/
DISPOSALS
6 SEMI RECESSED
TOILET ACCESSORY NOTES:
1C DOUBLE 1D DOUBLE
ACCESSIBLE
DIMENSION TO TOP
OF COIN SLOTS AND
HANDLES
3' -6
4' -0
C L
T O
W E
L S
LO
T
3' -6
C L
4' -0
M
A X
T O
W E
L S
LO
T
3' -6
CL
4' -0
M
A X
S O
A P
V A
LV
E
3' -6
4' -0
M
A X
9V SURFACE
MOUNTED
VERTICAL
9C SS COUNTER
MOUNTED W/
SENSOR
9D COUNTER
MOUNTED W/
SENSOR
10A HOLDERS,
HOOKS, SHELF
& ROD
12A SURFACE
MOUNTED
18" W X 36" H
SURFACE MOUNTED
TILTED FOR ABA
REQUIRMENTS
17A WALL MOUNTED
W/ SWING LEGS
17C CUSTOM
3' -4
3' -9
/4
DOOR18A
DIMENSION TO TOP OF
TABLE IN FOLD-DOWN
POSITION
2' -1
0"
22 VERTICAL
MOLDED HDPE
23 HORIZONTAL SS/
MOLDED HDPE
24 CHILD PROTECTION
SEAT
CENTER OVER
LAVATORY
22 40 00
TOILET
22 40 00
TOILET
2' -1
2' -4
T Y
P . U
.O .N
2'
-1 0"
C L
C L
1' -6
3'-6" 1'-0" 3'-0"
2' -1
0" C L
CL CL
CL
8"
1'-6"
CL
CL
1'-0"CL
27 52 23
NURSE CALL
2' -2
C L
3'-3"
CL
CL CL
WHEEL CHAIR
ACCESSIBLE
AMBULATORY
ACCESSIBLE
CLR.
3'-6"
1'-9"
CL
1' -2
WHEEL CHAIR
ACCESSIBLE
HORIZONTAL BABY
CHANGING STATION
EDGE OF
MIRROR
AMBULATORY
STALL
PLAN DESIGNATION S3
S3
F
IN
IS
H
O F
W E
T W
A
LL
6' -1
3'-6" CLR
EQ EQ
1B
AT FEMALE
TOILET ONLY
E D
G E
O F
T
LT
8" F
R O
M
LINE OF WALL
CLR OPNG)
36" DOOR
(34" MIN
G48
SH1
S E
A T
W A
LL
G56
C O
N T
R O
L W
A
LL
FIN TO FIN *
4'-0"
F
IN
T O
F
IN
4'
-0
G36
G42 G48 BOTH SIDES
22 40 00
TOILET
ACCESSIBLE TRANSFER
SHOWER L-SHAPED GRAB
BAR
T O
C .L
2'
-1 0”
30 X 18 -
NON-SLIP FINISH
G56
C
M
IN
FINISH FLOOR
JSN
JSN
CLR OPNG)
36" DOOR
(34" MIN
36"
A5150A5145A5145
1F BEHAVOR
HEALTH
A5140 A5200
CL
A5090M A5090 AXXXX A5080 A5081 F2017M F2017M A5075 A5175A5135 A5170A5082
SURFACE
MOUNTED,
HANDS FREE
7B
A5075M A5076 A5077
A1080A1066 A1067 A5205A5166 A5030 L1200 A4995 A5084 A5109 A5110 A5110
TOILET
SEAT
COVER
DISPENSER
26 RECESSED
A
26A SURFACE
MOUNTED
HAND
SANITIZER
DISPENSER
A
CL
V A
LV
E
SURFACE
MOUNTED
WET WALL
3'-3"
CL
1/
2" M
IN
SIDE STALL WALL
30"
3' -4
4' -0
M
A X
BA A A A A A A A A A AB A A
S
ID
E S
T A
LL
W
A
LL
4' -0
M
A X
36"
23 3/4" 26A
26A
NURSING DOUBLE
SWING UP GRAB
BARS
3'-0"
CL
G61
22 40 00
TOILET
30" SWING-UP GRAB BAR
30 FLIP UP GRAB BARG60
C
A5115
30…