520-331_JACC_pkg1_Addendum1_20240221.pdf

PDF 12 MB Posted

Attached to
Y1DB--Construct Addition and Renovations - Joint Ambulatory Care Clinic - Pensacola FL
Solicitation number
36C77623R0103
Issued by

About this file

This document provides details on a federal contract solicitation for construction and renovation services. The solicitation number is 36C77623R0103 and seeks offers to construct an addition to and renovate the Joint Ambulatory Care Clinic in Pensacola, Florida. The required work includes primary construction and renovation of the clinic facility. The contracting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The solicitation type is listed as a notice seeking competitive proposals for the opportunity, with an estimated period of performance to complete the required construction and renovation services.

View the file

Other files

File Type Posted
Amendment 0006 - Attachment 01 - 23 64 00 - Packaged Water Chillers.pdf PDF
36C77623R0103 0006.pdf PDF
36C77623R0103 0005 - Attachment 01 - Cooler Specifications.pdf PDF
36C77623R0103 0005.pdf PDF
Attachment - VOL 3 BINDER.pdf PDF
Attachment - VOL 1 BINDER.pdf PDF
Attachment - VOL 2 BINDER.pdf PDF
36C77623R0103 0004.pdf PDF
Attachment - RFI Responses 2.29.2024.xlsx XLSX spreadsheet
Attachment - Limitations on Subcontracting.docx DOCX document
Attachment CON-100 INSTRUCTIONS.docx DOCX document
Attachment - Contractor Safety - Environmental Form.docx DOCX document
Attachment - Pensacola JACC 2nd site visit sign in.pdf PDF
Attachment - RFI Responses 2.20.2024.xlsx XLSX spreadsheet
Attachment - JACC 2005 Geotechnical Report.pdf PDF
Attachment - 520-331_JACC_pkg1_Addendum1_20240209.pdf PDF
36C77623R0103 0003.pdf PDF
2nd Site Visit Instructions - 520-331 JACC Minor Lab Infusion.pdf PDF
36C77623R0103 0002.pdf PDF
Attachment 8 - WD FL20240203 - 1.05.2024.pdf PDF
JACC Minor Site Visit Sign in 1-9-2024.pdf PDF
36C77623R0103 0001.docx DOCX document
520-331.JACC.Pre-Bid.Presentation.010924.Redux.pdf PDF
Attachment 7 - Limitations on Subcontracting.docx DOCX document
Attachment 6 - Drawings ELECTRICAL LIGHTING SECOND FLOOR PLAN.pdf PDF
Attachment 4 - Drawings - ARCHITECTURAL DETAILS - EXTERIOR.pdf PDF
Attachment 10 - Site Visit Instructions - 520-331 JACC.pdf PDF
Attachment 5 - Drawings - PLUMBING EXISTING DEMO GROUND FLOOR.pdf PDF
Attachment 3 - Drawings - CIVIL SIGNAGE AND STRIPING.pdf PDF
Attachment 9 - Brand Name JA JACC Addition 05172023.pdf PDF
36C77623R0103_1.docx DOCX document
Attachment 8 - WD FL20230203 01.13.2023.pdf PDF
Attachment 2 - Drawings - COVER SHEET GI000.pdf PDF
Attachment 1 -Specifications 221007 reduced rev2 -.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRIPLE C – THE A&E GROUP

OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE

410 Grand Avenue, Suite 201C Laramie, Wyoming 82070 Telephone: (307) 460-2054 Fax: (307) 460-2053

Addendum Number 01

Project: 520-331 Construct Addition and Renovations to JACC, Pensacola FL

Date: 02/21/2024

NOTICE TO PROPOSERS:

A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated integrally therewith.

Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take precedence.

B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject Proposer to disqualification.

Revisions:

Specifications:

SECTION Description of / Reason for Change

GeoTech 2005 Geotechnical Report Added for Reference

08 80 00 - Glazing Glazing types clarified

23 64 00 – Packaged

Water Chillers

Water Chiller specification added

Drawing Changes:

SHEET NUMBER REVISION

NUMBER

DESCRIPTION OF/REASON FOR CHANGE

A-601 n/a Glazing types assigned to door and window glazing

IN-1.01R-6 n/a Existing bldg. Ground floor reflected ceiling plan for

CVE Verified Service-Disabled Veteran-Owned Small Business

TRIPLE C – THE A&E GROUP

OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE

410 Grand Avenue, Suite 201C Laramie, Wyoming 82070 Telephone: (307) 460-2054 Fax: (307) 460-2053

Reference only

IN-1.02R-6 n/a Existing bldg. Second floor reflected ceiling plan for

Reference only

End of Addendum

Attachments:

GeoTech Report 2005

08 80 00 - Glazing

23 64 00 – Packaged Water ChillersA-601

A-601

IN-1.01R-6

IN-1.02R-6

Addition & Renovation Project #: 520-331

Glazing

08 80 00 - 1

SECTION 08 80 00

GLAZING

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies the following:

1. Glass.

2. Glazing materials and accessories for both factory and field glazed assemblies.

1.2 RELATED WORK

A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Sustainable Construction Requirements.

B. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES, and Section 08 14 00, WOOD DOORS: Sound resistant doors.

C. Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES: Mirrors.

D. Section 12 36 00, COUNTERTOPS.

E. Section 08 51 13, ALUMINUM WINDOWS: Aluminum Windows.

F. Section 09 06 00, SCHEDULE FOR FINISHES: Color of glass.

G. Section 26 05 19, LOW VOLTAGE ELECTRICAL POWER AND CONDUCTORS AND CABLES: Wiring (120 V AC, 15A or 20A).

H. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Junction and Switch Boxes.

I. Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS: Access Control Systems.

1.3 LABELS

A. Temporary labels:

1. Provide temporary label on each light of glass identifying manufacturer or brand and glass type, quality and nominal thickness.

2. Label in accordance with NFRC label requirements.

3. Temporary labels are to remain intact until glass is approved by Contracting Officer

Representative (COR).

B. Permanent labels:

1. Locate in corner for each pane.

2. Label in accordance with ANSI Z97.1 and SGCC label requirements.

a. Tempered glass.

b. Laminated glass or have certificate for panes without permanent label.

3. Fire rated glazing assemblies: Mark in accordance with IBC.

1.4 PERFORMANCE REQUIREMENTS

A. General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminated Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, thermal movements, building movements, permitted tolerances, and combinations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation; failure of sealants or gaskets to remain watertight and airtight; deterioration of glazing materials; unsafe engagement of the framing system; deflections beyond specified limits; or other defects in construction.

08 80 00 - 2

B. Glazing Unit Design: Design glass, including engineering analysis meeting requirements of authorities having jurisdiction. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers.

1. Design glass in accordance with ASTM E1300, and for conditions beyond the scope of

ASTM E1300, by a properly substantiated structural analysis.

2. Design Wind Pressures: As indicated on construction documents .

3. Wind Design Data: As indicated on construction documents.

4. Maximum Lateral Deflection: For glass supported on all four edges, limit center-of-glass deflection at design wind pressure to not more than the structural capacity of the glazing unit, the threshold at which frame engagement is no longer safely assured, 1/100 times the short-side length.

C. Windborne-Debris-Impact Resistance: Comply with enhanced-protection testing requirements in ASTM E1996 for project wind zone when tested according to ASTM E1886, based upon testing of specimens not less than the size required for project and utilizing installation method identical to that specified for project.

1. Project Wind Zone: Wind Zone 4 (164 MPH).

2. Large-Missile Test: For glazing located within 9.1 m (30 feet) of grade.

1.5 SUBMITTALS

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Sustainable Design Submittals, as described below:

1. Volatile organic compounds per volume as specified in PART 2 - PRODUCTS.

C. Manufacturer's Certificates:

1. Certificate stating that fire-protection and fire-resistive glazing units meet code requirements for fire-resistance-rated assembly and applicable safety glazing requirements.

2. Certificate on solar heat gain coefficient when value is specified.

3. Certificate on "R" value when value is specified.

4. Certificate test reports confirming compliance with specified bullet resistive rating.

5. Certificate that blast resistant glass meets the specified requirements.

D. Manufacturer Warranty.

E. Manufacturer's Literature and Data:

1. Glass, each kind required.

2. Insulating glass units.

3. Transparent (one-way vision glass) mirrors.

4. Elastic compound for metal sash glazing.

5. Putty, for wood sash glazing.

6. Glazing cushion.

7. Sealing compound.

8. Bullet resistive material.

9. Plastic glazing material, each type required.

F. Samples:

1. Size: 305 mm by 305 mm (12 inches by 12 inches).

2. Tinted glass.

3. Reflective glass.

4. Transparent (one-way vision glass) mirrors.

G. Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazing sealants were tested for adhesion to glass and glazing channel substrates and for compatibility with glass and other glazing materials.

08 80 00 - 3

1.6 DELIVERY, STORAGE AND HANDLING

A. Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.

B. Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.

C. Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.

D. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED

FACE":

1. Treat security glazing as fragile merchandise, and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to prevent edge damage or other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.

2. Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight.

Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals.

3. Temporary protections: The glass front and polycarbonate back of glazing are to be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and re-applied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the film used on exposed polycarbonate surfaces is to be approved and applied by manufacturer.

4. Edge protection: To cushion and protect glass clad, and polycarbonate edges from contamination or foreign matter, the four (4) edges are to be sealed the depth of glazing with continuous standard-thickness thermoplastic rubber tape. Alternatively, continuous channel shaped extrusion of thermoplastic rubber are to be used, with flanges extending into face sides of glazing.

5. Protect "Constant Temperature" units including every unit where glass sheet is directly laminated to or directly sealed with metal-tube type spacer bar to polycarbonate sheet, from exposures to ambient temperatures outside the range of 16 to 24 degrees C (60 to 75 degrees F), during the fabricating, handling, shipping, storing, installation, and subsequent protection of glazing.

1.7 PROJECT CONDITIONS:

A. Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field measured products.

1.8 WARRANTY

A. Construction Warranty: Comply with the FAR clause 52.246-21 “Warranty of Construction”.

B. Manufacturer Warranty: Manufacturer shall warranty their glazing from the date of installation and final acceptance by the Government as follows. Submit manufacturer warranty.

1. Insulating glass units to remain sealed for ten (10) years.

2. Laminated glass units to remain laminated for five (5) years.

1.9 APPLICABLE PUBLICATIONS:

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

B. American Architectural Manufacturers Association (AAMA):

800 ........................................ Test Methods for Sealants

08 80 00 - 4

810.1-77 ................................ Expanded Cellular Glazing Tape

C. American National Standards Institute (ANSI):

Z97.1-14 ................................ Safety Glazing Material Used in Building - Safety Performance

Specifications and Methods of Test

D. American Society of Civil Engineers (ASCE):

7-16 ....................................... Wind Load Provisions

E. ASTM International (ASTM):

C542-05(2017) ...................... Lock-Strip Gaskets

C716-06(2020) ...................... Installing Lock-Strip Gaskets and Infill Glazing Materials

C794-18 ................................. Adhesion-in-Peel of Elastomeric Joint Sealants

C864-05(2019) ...................... Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers

C920-18 ................................. Elastomeric Joint Sealants

C964-20 ................................. Standard Guide for Lock-Strip Gasket Glazing

C1036-16 ............................... Flat Glass

C1048-18 ............................... Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass.

C1172-19 ............................... Laminated Architectural Flat Glass

C1349-17 ............................... Standard Specification for Architectural Flat Glass Clad Polycarbonate

C1376-15 ............................... Pyrolytic and Vacuum Deposition Coatings on Flat Glass

D635-18 ................................. Rate of Burning and/or Extent and Time of Burning of Self- Supporting Plastic in a Horizontal Position

D4802-16 ............................... Poly (Methyl Methacrylate) Acrylic Plastic Sheet

E84-20 ................................... Surface Burning Characteristics of Building Materials

E119-20 ................................. Standard Test Methods for Fire Test of Building Construction and Material

E1300-16 ............................... Load Resistance of Glass in Buildings

E1886-19 ............................... Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials

E1996-17 ............................... Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes

E2141-14 ............................... Test Methods for Assessing the Durability of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units

E2190-19 ............................... Insulating Glass Unit

E2240-06 ............................... Test Method for Assessing the Current-Voltage Cycling Stability at 90 Degree C (194 Degree F) of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units

E2241-06 ............................... Test Method for Assessing the Current-Voltage Cycling Stability at Room Temperature of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units

08 80 00 - 5

E2354-10 ............................... Assessing the Durability of Absorptive Electrochromic Coatings within Sealed Insulating Glass Units

E2355-10 ............................... Test Method for Measuring the Visible Light Transmission Uniformity of an Absorptive Electrochromic Coating on a Glazing Surface

F1233-08(2019) .................... Standard Test Method for Security Glazing Materials and Systems

F1642/F1642M-17 ................. Test Method for Glazing and Glazing Systems Subject to Airblast Loadings

F. Code of Federal Regulations (CFR):

16 CFR 1201-10 .................... Safety Standard for Architectural Glazing Materials

G. Glass Association of North America (GANA):

2010 Edition .......................... GANA Glazing Manual

2008 Edition .......................... GANA Sealant Manual

2019 Edition .......................... GANA Laminated Glazing Reference Manual

2010 Edition .......................... GANA Protective Glazing Reference Manual

H. International Code Council (ICC):

IBC ........................................ International Building Code

I. Insulating Glass Certification Council (IGCC)

J. Insulating Glass Manufacturer Alliance (IGMA):

TB-3001-13 ........................... Guidelines for Sloped Glazing

TM-3000 ................................ North American Glazing Guidelines for Sealed Insulating Glass Units for Commercial and Residential Use

K. Intertek Testing Services – Warnock Hersey (ITS-WHI)

L. National Fire Protection Association (NFPA):

80-19 ..................................... Fire Doors and Windows

252-17 ................................... Fire Tests of Door Assemblies

257-17 ................................... Standard on Fire Test for Window and Glass Block Assemblies

M. National Fenestration Rating Council (NFRC)

1. Safety Glazing Certification Council (SGCC) 2012:

2. Certified Products Directory (Issued Semi-Annually).

N. Underwriters Laboratories, Inc. (UL):

9-08(R2009) .......................... Fire Tests of Window Assemblies

263-14 ................................... Fire Tests of Building Construction and Materials

752-11 ................................... Bullet-Resisting Equipment.

O. Department of Veterans Affairs:

1. Physical Security and Resiliency Design Manual January 2021

2. Architectural Design Manual for VA Facilities (VASDM)

P. Environmental Protection Agency (EPA):

40 CFR 59(2014) .................. National Volatile Organic Compound Emission Standards for

Consumer and Commercial Products

08 80 00 - 6

PART 2 - PRODUCT

2.1 GLASS

A. Provide minimum thickness stated and as additionally required to meet performance requirements.

1. Provide minimum 6 mm (1/4 inch) thick glass units unless otherwise indicated.

B. Obtain glass units from single source from single manufacturer for each glass type.

C. Clear Glass:

1. ASTM C1036, Type I, Class 1, Quality q4.

D. Ultra-clear-Low-Iron Float Glass:

1. ASTM C1036, Type I, Class 1, Quality q4 and with visible light transmission of not less than 90 percent.

2.2 HEAT-TREATED GLASS

A. Roller Wave Limits for Heat-Treated Glass: Orient all roller wave distortion parallel to bottom surface of glazing, and provide units complying with the following limitations:

1. Measurement Parallel to Line: Maximum peak to valley 0.203 mm (0.008 inch).

2. Measurement Perpendicular to Line: Maximum 0.0254 mm (0.001 inch).

3. Bow/Warp: Maximum 50 percent of bow and warp allowed by ASTM C1048.

B. Clear Heat Strengthened Glass:

1. ASTM C1048, Kind HS, Condition A, Type I, Class 1, Quality q3.

C. Clear Tempered Glass:

1. ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

2.3 COATED GLASS:

A. Reflective-Coated Spandrel Glass:

1. ASTM C1376, Kind CS and ASTM C1048, Kind HS, Condition B, Type I.

B. Reflective-Coated Low-E Coated Tempered Glass:

1. ASTM C1376 and ASTM C1048, Kind FT, Condition C, Type I, Class 1, Quality q3 with reflective metallic coating.

2.4 LAMINATED GLASS

A. Laminated Glass: ASTM C1172. Two or more lites of heat treated glass bonded with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent-resin interlayer complying with interlayer manufacturer's written instructions. Minimum total laminated thickness of 1/4” for blast resistant glazing.

B. Interlayer: Use min. 0.75 mm (0.030 inch) thick interlayer for vertical glazing unless otherwise scheduled.

C. Interlayer: Use 1.5 mm (0.060 inch) thick interlayer for:

1. Horizontal or sloped glazing.

2. Acoustical glazing.

3. Assemblies requiring heat strengthened or fully tempered glass.

D. Interlayer: Use 2.28 mm (0.090 inch) thick interlayer where required to meet performance requirements.

E. Interlayer Color: Clear, unless otherwise scheduled.

2.5 INSULATING GLASS UNITS

A. Provide factory fabricated, hermetically sealed glass unit consisting of two panes of glass separated by a dehydrated air space and comply with ASTM E2190. The exterior glass unit

08 80 00 - 7 shall be fully tempered and the inner glass unit shall be laminated annealed at a minimum for all blast resistant glazing.

B. Assemble units using glass types specified in Insulating Glass Schedule and Blast Glazing assembly requirements

2.6 FIRE PROTECTION AND FIRE RESISTANCE GLAZING

A. Fire-Protection-Rated Glazing: Glazing units tested for use in fire door assemblies or fire windows, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC, for fire-protection ratings as scheduled, based upon positive-pressure testing per NFPA 257 or UL 9, and complying with NFPA 80.

1. Hose-Stream Test: Units must comply, except units having fire-protection rating of 20 minutes.

2. Confirm requirements with authorities having jurisdiction.Temperature Rise Limitation:

Units over 0.065 square meter (100 square inch) must comply with 232 deg. C (450 degress F) limitation.

3. Labeling: Permanently label fire-protection-rated glazing units in accordance with IBC.

4. Safety Glazing: Comply with 16 CFR 1201, Category II.

5. Fire-Protection-Rated Tempered Glass: For 20-minute fire-protection-rated door assemblies, of thickness scheduled.

6. Fire-Protection-Rated Laminated Ceramic Glazing: Units made from two lites of clear, ceramic glass, 8 mm (5/16 inch) total thickness, for rating scheduled.

7. Fire-Protection-Rated Laminated Glass with Intumescent Interlayers: Units made from multiple lites of uncoated, ultra-clear (low-iron) float glass, in intumescent interlayers, of thickness and rating scheduled.

B. Fire-Resistance-Rated Glazing: Glazing units tested for use in fire wall assemblies, UL, ITS- WHI or equivalent listed and labeled by testing agency in accordance with IBC for fire-resistance ratings of wall assemblies as scheduled, based upon testing according to NFPA 252 and ASTM E119 or UL 263.

1. Labeling: Permanently label fire-resistance-rated glazing units in accordance with IBC.

2. Safety Glazing: Comply with 16 CFR 1201, Category II.

3. Fire-Resistance-Rated Laminated Glass with Intumescent Interlayers: Units made from multiple lites of uncoated, ultra-clear low-iron float glass, in intumescent interlayers, of thickness and rating scheduled.

4. Fire-Resistance-Rated Double Glazing Units with Gel Fill: Units made from two lites of uncoated, fully tempered, ultra-clear (low-iron) float glass, with perimeter metal spacer and edge seal forming cavity filled with clear, fully transparent, heat-absorbing gel, of thickness and fire-protection rating scheduled.

2.7 ALUMINUM PARTITIONS WITH GLASS

A. Basis of Design: CRL Aluminum Partition Posts.

B. Partition posts: Square profile at 1-1/2” thick, 30” overall height.

a. Channel to be in post to accept glass.

C. Finish: Brushed stainless.

D. Accessories:

1. Flat cap at top.

2. Welded base.

E. Glass: 1/4" clear and fully tempered with all exposed edges polished.

1. 2” air space to be held between glass and counter.

2.8 GLAZING ACCESSORIES

A. As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work are to have a

08 80 00 - 8 finish that will not corrode or stain while in service. Fire rated glazing to be installed with glazing accessories in accordance with the manufacturer’s installation instructions.

B. Setting Blocks: ASTM C864:

1. Silicone type.

2. Channel shape; having 6 mm (1/4 inch) internal depth.

3. Shore A hardness of 80 to 90 Durometer.

4. Block lengths: 50 mm (2 inches) except 100 to 150 mm (4 to 6 inches) for insulating glass.

5. Block width: Approximately 1.6 mm (1/16 inch) less than the full width of the rabbet.

6. Block thickness: Minimum 4.8 mm (3/16 inch). Thickness sized for rabbet depth as required.

C. Spacers: ASTM C864:

1. Channel shape having a 6 mm (1/4 inch) internal depth.

2. Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick.

3. Lengths: 25 to 76 mm (1 to 3 inches).

4. Shore A hardness of 40 to 50 Durometer.

D. Glazing Tapes:

1. Semi-solid polymeric based closed cell material exhibiting pressure-sensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging.

2. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.

3. Complying with AAMA 800 for the following types:

a. AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant.

b. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid sealant.

E. Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops.

F. Glazing Clips: Galvanized steel spring wire designed to hold glass in position in rabbeted sash without stops.

G. Glazing Points (Sprigs): Pure zinc stock, thin, flat, triangular or diamond shaped pieces, 6 mm (1/4 inch) minimum size.

H. Glazing Gaskets: ASTM C864:

1. Firm dense wedge shape for locking in sash.

2. Soft, closed cell with locking key for sash key.

3. Flanges may terminate above the glazing-beads or terminate flush with top of beads.

I. Lock-Strip Glazing Gaskets: ASTM C542, shape, size, and mounting as indicated.

J. Glazing Sealants: ASTM C920, silicone neutral cure:

1. Type S.

2. Class 25 or 50 as recommended by manufacturer for application.

3. Grade NS.

4. Shore A hardness of 25 to 30 Durometer.

K. Structural Sealant: ASTM C920, silicone acetoxy cure:

1. Type S.

2. Class 25.

3. Grade NS.

4. Shore a hardness of 25 to 30 Durometer.

L. Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C864.

1. Channel shape; flanges may terminate above the glazing channel or flush with the top of the channel.

08 80 00 - 9

2. Designed for dry glazing.

M. Color:

1. Color of glazing compounds, gaskets, and sealants used for aluminum color frames to match color of the finished aluminum and be nonstaining.

2. Color of other glazing compounds, gaskets, and sealants which will be exposed in the finished work and unpainted are to be black, gray, or neutral color.

N. Smoke Removal Unit Targets: Adhesive targets affixed to glass to identify glass units intended for removal for smoke control. Comply with requirements of local Fire Department.

2.9 GLAZING FILM

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Reference drawings for locations.

C. Material Properties:

1. General: Glass and plastic finishes field-applied application to glass or plastic material as visual opaque or decorative film.

2. Film: Polyester.

3. Decorative Pattern: Printed.

4. Adhesive: Acrylic, Pressure Sensitive, Permanent.

5. Liner: Silicone-coated Polyester.

6. Thickness (Average): 3.2 mils (80 microns).

7. Fire Performance: Surface burning characteristics when tested in accordance with ASTM

E84: Class A:

a. Flame Spread: 25 maximum.

b. Smoke Developed: 450 maximum.

D. INSTALLATION

1. Film Installation, General:

a. Install in accordance with manufacturer's instructions.

b. Cut film edges neatly and square at a uniform distance of 1/8 inch (3 mm) to 1/16 inch (1.5 mm) of window sealant. Use new blade tips after 3 to 4 cuts.

c. Spray the slip solution, composed of one capful of baby shampoo or dishwashing liquid to 1 gallon of water, on window glass and adhesive to facilitate proper positioning of film.

d. Apply film to glass and lightly spray film with slip solution.

e. Squeegee from top to bottom of window. Spray slip solution to film and squeegee a second time.

f. Bump film edge with lint-free towel wrapped around edge of a 5-way tool.

g. Upon completion of film application, allow 30 days for moisture from film installation to dry thoroughly, and to allow film to dry flat with no moisture dimples when viewed under normal viewing conditions.

h. If completing an exterior application, check with the manufacturer as to whether edge sealing is required.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verification of Conditions:

1. Examine openings for glass and glazing units; determine they are proper size; plumb;

square; and level before installation is started.

2. Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer is approved shop drawings.

08 80 00 - 10

B. Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation. Do not proceed with installation until unsatisfactory conditions have been corrected.

C. Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units.

3.2 PREPARATION

A. For sealant glazing, prepare glazing surfaces in accordance with GANA Sealant Manual.

B. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.

C. Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances.

D. Verify that components used are compatible.

E. Clean and dry glazing surfaces.

F. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.

3.3 INSTALLATION – GENERAL

A. Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified otherwise.

B. Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test Requirements specified in other applicable sections of specifications.

C. Set glazing without bending, twisting, or forcing of units.

D. Do not allow glass to rest on or contact any framing member.

E. Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.

F. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.

G. Laminated Glass:

1. Tape edges to seal interlayer and protect from glazing sealants.

2. Do not use putty or glazing compounds.

H. Insulating Glass Units:

1. Glaze in compliance with glass manufacturer's written instructions.

2. When glazing gaskets are used, they are to be of sufficient size and depth to cover glass seal or metal channel frame completely.

3. Do not use putty or glazing compounds.

4. Do not grind, nip, cut, or otherwise alter edges and corners of fused glass units after shipping from factory.

5. Install with tape or gunnable sealant in wood sash.

I. Fire Protective and Fire Resistance Glass:

1. Wire Glass: Glaze in accordance with NFPA 80.

2. Other fire protective and fire resistant glass: Glaze in accordance with manufacturer’s installation instructions and NFPA 80.

3.4 INSTALLATION - DRY METHOD (TAPE AND GASKET SPLINE GLAZING)

A. Cut glazing spline to length; install on glazing pane. Seal corners by butting and sealing junctions with butyl sealant.

08 80 00 - 11

B. Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.

C. Rest glazing on setting blocks and push against fixed stop with sufficient pressure to attain full contact.

D. Install removable stops without displacing glazing spline. Exert pressure for full continuous contact.

E. Do not exceed edge pressures stipulated by glass manufacturers for installing glass lites.

F. Trim protruding tape edge.

3.5 INSTALLATION - WET/DRY METHOD (PREFORMED TAPE AND SEALANT)

A. Cut glazing tape to length and set against permanent stops, 5 mm (3/16 inch) below sight line.

Seal corners by butting tape and dabbing with butyl sealant.

B. Apply heel bead of butyl sealant along intersection of permanent stop with frame ensuring full perimeter seal between glass and frame to complete the continuity of the air and vapor seal.

C. Place setting blocks at 1/4 points with edge block no more than 152 mm (6 inches) from corners.

D. Rest glazing on setting blocks and push against tape and heel bead of sealant with sufficient pressure to achieve full contact at perimeter of pane or glass unit.

E. Install removable stops, with spacer strips inserted between glazing and applied stops, 6 mm (1/4 inch) below sight line. Place glazing tape on glazing pane or unit with tape flush with sight line.

F. Fill gap between glazing and stop with sealant to depth equal to bite of frame on glazing, but not more than 9 mm (3/8 inch) below sight line. Sealant type is to be compatible with glazing tape.

G. Apply cap bead of sealant along void between the stop and the glazing, to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.6 INSTALLATION - WET METHOD (SEALANT AND SEALANT)

A. Place setting blocks at ¼ points and install glazing pane or unit.

B. Install removable stops with glazing centered in space by inserting spacer shims both sides at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.

C. Fill gaps between glazing and stops with sealant to depth of bite on glazing, but not more than 9 mm (3/8 inch) below sight line to ensure full contact with glazing and continue the air and vapor seal.

D. Apply sealant to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.7 INSTALLATION - INTERIOR WET/DRY METHOD (TAPE AND SEALANT)

A. Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line.

B. Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.

C. Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit.

D. Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.

E. Fill gaps between pane and applied stop with sealant to depth equal to bite on glazing, to uniform and level line. Sealant type is to be compatible with glazing tape.

08 80 00 - 12

F. Trim protruding tape edge.

3.8 INSTALLATION - INTERIOR WET METHOD (COMPOUND AND COMPOUND)

A. Install glazing resting on setting blocks. Install applied stop and center pane by use of spacer shims at 600 mm (24 inch) centers, kept 6 mm (1/4 inch) below sight line.

B. Locate and secure glazing pane using spring wire clips.

C. Fill gaps between glazing and stops with glazing compound until flush with sight line. Tool surface to straight line.

3.9 ALUMINUM PARTITIONS WITH GLASS

A. Posts to be securely mounted to countertops per manufacturer’s recommendations.

3.10 REPLACEMENT AND CLEANING

A. Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by COR.

B. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.

C. Leave glass, putty, and other setting material in clean, whole, and acceptable condition.

3.11 PROTECTION

A. Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.

3.12 MONOLITHIC GLASS SCHEDULE

A. Glass Type MG# 1: Clear fully tempered float glass.

1. Unit Thickness: 6 mm (0.23 inch)

2. Safety glazing label required.

3.13 LAMINATED GLASS SCHEDULE

A. Glass Type LG# 1: Clear laminated glass with two (2) lites of fully tempered float glass.

1. Minimum Thickness of Each Glass Lite: 3 mm (0.12 inch).

2. Interlayer Thickness: 1.52 mm (0.060 inch).

3. Safety glazing label required.

4. Application: Interior glazing of units unless otherwise scheduled.

B. Glass Type LG# 4: Clear laminated glass with two (2) lites of fully tempered ultra-clear (low-iron) float glass.

1. Minimum Thickness of Each Glass Lite: 6 mm (0.24 inch) .

2. Interlayer Thickness: 2.29 mm (0.090 inch) .

3. Safety glazing label required.

4. Windborne debris-resistant glazing unit required.

3.14 INSULATING GLASS SCHEDULE

A. Glass Type IG# 2: Low-E-coated, Tinted insulating glass. (match tint of existing windows to remain)

1. Overall Unit Thickness: 25 mm (1 inch).

2. Minimum Thickness of Each Glass Lite: 6 mm (0.23 inch).

3. Outdoor Lite: Annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.

4. Interspace Content: Argon

5. Indoor Lite: Fully tempered float glass.

6. Low-E Coating: Sputtered on third surface.

7. Visible Light Transmittance: 68 percent minimum.

8. Solar Heat Gain Coefficient: 0.38 maximum.

9. Safety glazing label required.

Shannon Text Box Addendum #1

Shannon Cloud

08 80 00 - 13

3.15 FIRE-PROTECTIVE AND FIRE-RESISTANCE GLAZING SCHEDULE

A. Glass Type FR# 1: Fire-protection-rated tempered glass.

1. Thickness: 12 mm (0.47 inch).

2. Rating: 20 minutes.

3. Application: Fire-protection-rated door assemblies with openings not over 0.65 square meter (100 square inch).

B. Glass Type FR# 2: Fire-protection-rated laminated ceramic glazing.

1. Thickness: 12 mm (0.47 inch)

2. Rating: 45 minute.

3. Application: Fire-protection-rated door and window assemblies.

- - - E N D - - -

Cloud

Shannon Text Box Addendum #1

This page intentionally left blank.

Pensacola JACC

03-01-20

PACKAGED WATER CHILLERS

23 64 00 - 1

SECTION 23 64 00

PART 1 - GENERAL

1.1 DESCRIPTION

A. Scroll air-cooled chillers with complete accessories.

1.2 RELATED WORK

A. Section 01 00 00, GENERAL REQUIREMENTS.

B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

D. Section 23 05 11, COMMON WORK RESULTS FOR HVAC.

E. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND

EQUIPMENT.

F. Section 23 21 23, HYDRONIC PUMPS

G. Section 23 21 13, HYDRONIC PIPING.

H. Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC.

I. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS.

1.3 DEFINITION

A. BACnet: Building Automation Control Network Protocol, ASHRAE Standard

135.

1.4 QUALITY ASSURANCE

A. Refer to Paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK

RESULTS FOR HVAC.

B. Refer to PART 3 herein after and Section 01 00 00, GENERAL REQUIREMENTS for test performance.

C. Comply with ARI requirements for testing and certification of the chillers.

D. Refer to paragraph, WARRANTY, Section 01 00 00 GENERAL REQUIREMENTS

E. Refer to OSHA 29 CFR 1910.95(a) and (b) for Occupational Noise Exposure

Standard.

F. Minimum performance efficiency per ASHRAE 90.1 and Federal Energy

Management Program.

1.5 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. American Refrigeration Institute (ARI):

23 64 00 - 2

550/590-98..............Standard for Water Chilling Packages Using the

Vapor Compression Cycle

C. American Society of Heating, Refrigerating, and Air-Conditioning

Engineers (ASHRAE):

34-2007.................Designation and Classification of Refrigerants

90.1-2007...............Energy Standard for Buildings Except Low-Rise

Residential Buildings

D. American Society of Mechanical Engineers (ASME):

2007 ...................ASME Boiler and Pressure Vessel Code, Section

VIII, "Rules for Constructive Pressure Vessels"

E. American Society of Testing Materials (ASTM):

C534/C534M-08...........Preformed, Flexible Elastomeric Cellular

Thermal Insulation in Sheet and Tubular Form

C612-04e1...............Mineral-fiber Block and Board Thermal

Insulation

F. National Electrical Manufacturing Association (NEMA):

NEMA 250-2008...........Enclosures for Electrical Equipment (1000 Volts

Maximum)

G. National Fire Protection Association (NFPA):

70-08...................National Electrical Code

H. Underwriters Laboratories, Inc. (UL):

UL 1995................. Heating and Cooling Equipment

1.6 SUBMITTALS

A. Submit in accordance with Specification Section 01 33 23, SHOP

DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Manufacturer's Literature and Data.

1. Scroll water chillers, including motor starters, control panels, and vibration isolators, data shall include the following:

a. Rated capacity.

b. Pressure drop.

c. Efficiency at full load and part load without applying any tolerance indicated in the ARI 550/590-98 Standard.

d. Refrigerant

e. Condenser Fan performance.

f. Accessories.

g. Installation instructions.

23 64 00 - 3

h. Start up procedures.

i. Wiring diagrams, including factory installed and field installed wiring.

j. Noise data report. Manufacturer shall provide noise ratings.

Noise warning labels shall be posted on equipment.

C. Maintenance and operating manuals for each piece of equipment in accordance with Section 01 00 00, GENERAL REQUIREMENTS.

PART 2 - PRODUCTS

2.1 ROTARY-SCREW, AND SCROLL WATER CHILLERS

A. General: Factory assembled and tested, rotary-screw, or scroll water chillers, complete with air-cooler condenser, compressors, motor, starters and controls mounted on a welded steel base. The chiller unit shall consist of two compressors minimum, but not more than eight, mounted on a single welded steel base. Where compressors are paralleled, not more than two shall be interconnected and not less than two independent refrigerant circuits shall be provided. Chiller shall be capable of operating with any of the refrigerants HFC-134a, HFC-407c, or HFC-410a.

B. Applicable Standard: Chillers shall be rated and certified according to

ARI 550/590, and shall be stamped in compliance with ARI certification.

C. Compressor (Rotary-Screw Type): Positive-displacement oil injected type, direct drive, cast-iron casing, precision-machined for minimum clearance about periphery of rotors. Lubrication system shall provide oil at proper temperature to all moving parts. Capacity control shall be by means of single slide valve to modulate the capacity from 100 to

20percent of full unit rated capacity without unstable compressor operation. The slide valve shall be hydraulically operated upon the actuation of temperature or pressure sensor. Minimum efficiency of 1.23 full load kw/ton and 0.98 Integrated Part Load Value kw/ton.

D. Compressor (Scroll Type): Three dimensional, positive-displacement, hermetically sealed design, with suction and discharge valves, crankcase oil heater and suction strainer. Compressor shall be mounted on vibration isolators. Rotating parts shall be factory balanced.

Lubrication system shall consist of reversible, positive displacement pump, strainer, oil level sight glass, and oil charging valve. Capacity

23 64 00 - 4 control shall be by on-off compressor cycling of single and multiple compressors. Minimum efficiency of 1.23 full load kw/ton and 0.86

Integrated Part Load Value kw/ton.

E. Refrigerants Circuit: Each circuit shall include an expansion valve, refrigerant charging connections, compressor suction and discharge shutoff valves, replaceable-core filter drier, sight glass with moisture indicator, liquid-line solenoid valve and insulated suction line.

F. Refrigerant and Oil: Sufficient volume of dehydrated refrigerant and lubricating oil shall be provided to permit maximum unit capacity operation before and during tests. Replace refrigerant charge lost during the warranty period, due to equipment failure, without cost to the Government.

G. Condenser: Air-cooled condenser coils shall have aluminum fins mechanically bonded to coper tubing. Condenser shall have integral subcooling circuit. Direct drive vertical discharge condenser fans with permanently lubricated ball bearings and external thermal overload protection.

H. Refrigerant Receiver: Provide a liquid receiver for chiller units when system refrigerant charge exceeds 80 percent of condenser refrigerant volume. Liquid receivers shall be horizontal-type, designed, fitted, and rated in conformance with ARI 495-1999(R2002). Receiver shall be constructed and tested in conformance with Section VIII D1 of the ASME

Boiler and Pressure Vessel Code. Each receiver shall have a storage capacity not less than 20 percent in excess of that required for fully charged system. Each receiver shall be equipped with inlet, outlet drop pipes, drain plug, purging valve, and relief devices as required by

ASHRAE Standard 15.

I. Controls: Chiller shall be furnished with unit mounted, stand-alone, microprocessor-based controls in NEMA 4 enclosure, hinged and lockable, factory wired with a single point power connection and separate control circuit. The control panel shall provide chiller operation, including monitoring of sensors and actuators, and shall be furnished with light emitting diodes or liquid-crystal display keypad.

1. Following shall display as a minimum on the panel:

a. Water and air temperatures.

23 64 00 - 5

b. Refrigerant pressures and temperatures.

c. Flow switch status.

e. Compressor status

2. Control Functions:

a. Manual or automatic startup and shutdown time schedule.

b. Entering and leaving chilled water temperature and control set points.

3. Safety Functions: Following conditions shall shut down the chiller and require manual reset to start:

a. Low evaporator refrigerant temperature and pressure.

b. High condenser pressure.

c. Critical sensor or detection circuit faults.

e. Electrical distribution faults.

f. Emergency stop.

g. Loss of evaporator water flow.

J. The chiller control panel shall provide leaving chilled water temperature reset based on 4-20 ma or 0-10 VDC signal from DDC.

K. Provide contacts for remote start/stop from DDC.

M. Motor: Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.

Compressor motor furnished with the chiller shall be in accordance with the chiller manufacturer and the electrical specification Section 23 05

12, GENERAL MOTOR REQUIREMENTS FOR HVAC. Starting torque of motors shall be suitable for driven machines.

PART 3 – EXECUTION

3.1 EXAMINATION

A. Examine roughing-in for concrete equipment bases, anchor-bolt sizes and locations, piping and electrical to verify actual locations and sizes before chiller installation and other conditions that might effect chiller performance, maintenance, and operation.

B. Equipment locations shown on drawings are approximate. Determine exact locations before proceeding with installation.

3.2 EQUIPMENT INSTALLATION

A. Install chiller on concrete base with isolation pads or vibration isolators.

1. Vibration isolator types and installation requirements are specified in Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND

EQUIPMENT

23 64 00 - 6

2. Anchor chiller to concrete base according to manufacturer’s written instructions.

3. Charge the chiller with refrigerant, if not factory charged.

4. Install accessories and any other equipment furnished loose by the manufacturer, including remote flow switches, according to the manufacturer written instructions and electrical requirements.

5. Chillers shall be installed in a manner as to provide easy access for and removal of compressor and motors etc.

B. Install thermometers and gages as recommended by the manufacturer and/or as shown on drawings.

C. Piping Connections:

1. Make piping connections to the chiller for chilled water and other connections as necessary for proper operation and maintenance of the equipment.

2. Make equipment connections with flanges and couplings for easy removal and replacement of equipment.

3.3 STARTUP AND TESTING

A. Engage manufacturer's factory-trained representative to perform startup and testing service. Test procedure as per ARI 550/590 and manufacturer’s instructions.

B. Inspect, equipment installation, including field-assembled components, and piping and electrical connections.

C. After complete installation startup checks, according to the manufacturer’s written instructions, do the following to demonstrate to the RE/COTR that the equipment operates and performs as intended.

1. Check refrigerant charge is sufficient and chiller has been tested for refrigerant leak.

2. Check bearing lubrication and oil levels.

3. Verify proper motor rotation.

4. Verify pumps associated with chillers are installed and operational.

5. Verify thermometers and gages are installed.

6. Operate chiller for run-in-period in accordance with the manufacturer’s instruction and observe its performance.

7. Check and record refrigerant pressure, water flow, water temperature, and power consumption of the chiller.

23 64 00 - 7

8. Test and adjust all controls and safeties. Replace or correct all malfunctioning controls, safeties and equipment as soon as possible to avoid any delay in the use of the equipment.

9. Prepare a written report outlining the results of tests and inspections, and submit it to the RE/COTR.

- - - E N D - - -

F

FLUSH

2' -9

3'

-7

1'-0" 4"

N

T

NARROW VISION

3' -0

3'

-4

G

6"6"

HALF GLASS

T

FG

5" 5"

5"

T

FULL GLASS

TYPICAL FRAME

2" H

E

IG

H T

2" WIDTH 2"

TERMINATED STOPS

4"

TERMINATED

STOPS @

INTERIOR

DOORS ONLY

xT

MASONRY HEAD

xM

T Y

P

4"

2"

1/2" 1/2"VARIES

SEE PLAN

WALL - SEE PLAN FOR

TYPE

SEALANT - EA. SIDE &

ALL AROUND, TYP.

HOLLOW METAL FRAME

1/ 2"

V A

R

IE

S S

E E

P

LA

N 1/

2"

4" 2"

ADJACENT WALL WHERE

OCCURS

SEALANT - EA SIDE & ALL

AROUND, TYP.

HOLLOW METAL FRAME

WALL - SEE PLAN FOR

TYPE

2"

6"

BRICK VENEER

UNIT

HOLLOW METAL

FRAME

SEALANT, TYP.

2 1/2"

WALL TYPE AS SCHEDULED

METAL FLASHING

OVERLAP WATER-

RESISTANT

BARRIER AND

FLASHING

STEEL ANGLE

LINTEL -

SEE STRUCTURAL

WEEPS (2 MIN) EQ SPACED

ABOVE OPENING (24" O.C. MAX)

2"

6"

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

BRICK VENEER UNIT

STEEL ANGLE SUPPORT -

SEE STRUCTURAL

STUD COLUMN - SEE FRAMING

DETAILS

RETURN WALL FINISH

AT OPENING

1/

2"

W A

LL

T

Y P

E A

S S

C H

E D

U

LE

D

INTERIOR DOUBLE HUNG

WINDOW

SEALANT AND BACKING ROD

EACH SIDE & ALL AROUND,

TYP.

SHIM SPACE AS REQUIRED

ATTACH TO FRAMING PER

MANUFACTURER

STUD BOX BEAM HEADER

VARIES - SEE PLAN

V A

R

IE

S S

E E

P

LA

N

SEALANT & BACKER ROD -

EACH SIDE & ALL AROUND,

TYP.

INTERIOR DOUBLE

HUNG WINDOW

SHIM AS REQUIRED

ATTACH TO FRAMING

PER MANUFACTURER

INTERIOR DOUBLE

HUNG WINDOW

SEALANT AND BACKING ROD

EACH SIDE & ALL AROUND,

TYP.

SHIM SPACE AS REQUIRED

ATTACH TO FRAMING PER

MANUFACTURER

VARIES - SEE PLAN

COUNTERTOP WHERE OCCURS

2' -8

6'

-0

4'-0"

4' -3

1'

-9

W1 W1S

5' -6

16'-0 1/2"

2' -7

2'

-1 1"

3'-6 1/2" * 3'-6" * 1'-11" * 3'-6" * 3'-7" *

W1F

* NOTE: MATCH EXISTING

VERTICAL MULLION

SPACING, VERIFY IN FIELD

A-601

A-601

LAB

DOUBLE

HUNG

COUNTERTOP TO BE

COORDINATED WITH PLAN

WINDOW TO LOCK AND

OPERATE FROM LAB SIDE

GLAZING FILM (GF-1) TO BE APPLIED

ON GLAZING FROM LAB SIDE

3'-0"

2' -1

0" 4'

-0

E1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C THE A&E GROUP

4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609

(813) 261 1023

MAT PERKINS

09.26.2022

B

IM

/5

-3

C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o

J A

C C

P e n s a c o la

/5

-3

.J A

C C

.P a c k a g e

.A

R C

H .r v t

/7 /2

:5

:1

P

M

A-601

ARCHITECTURAL SCHEDULES 520-331

JACC-2F

09.26.2022 M. PERKINS C. LOWERY

ISSUED FOR

CONSTRUCTION

CONSTRUCT ADDITION AND

RENOVATIONS TO JACC

790 Veterans Way, Pensacola, FL 32503

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME

FIRE

RATING

DETAIL HARDWARE

NOTESROOM NO. ROOM NAME DOOR NO.

WIDTH

H T TYPE MATERIAL TYPE MATERIAL HEAD JAMB ELEC GROUPW1 W2

TOTAL

WIDTH

SECOND FLOOR

2G100 WAITING ROOM 2G101 4' - 0" 7' - 0" 1 3/4" N WD 1 HM 45 MIN D8/A601 D9/A601 AC, ADO, RR, REX HW-5D DOOR FROM PHLEBOTOMY WAITING TO BLOOD DRAW

2G100A RESTROOM 2G100A 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G

2G103 RECEPTION 2G103 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-3G PROVIDE OVERHEAD 90 DEGREE STOP

2G112 RESTROOM 2G112 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G

2G114 RESTROOM 2G114 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G

2G116 RESTROOM 2G116 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G

2G117 CORE LAB 2G117C 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 AC, ADO ,REX HW-5D DOOR FROM BLOOD DRAW TO CORE LAB

2G117 CORE LAB 2G117A 3' - 4" 3' - 4" 6' - 8" 8' - 0" 1 3/4" N/N WD 1 HM 45 MIN D8/A601 D9/A601 AC, ADO, REX HW-10B DOOR FROM SOUTH CORRIDOR TO CORE LAB

2G117 CORE LAB C2-101B 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-1F

2G117A VESTIBULE 2G117B 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 AC, REX HW-5D DOOR FROM STAFF LOUNGE TO CORE LAB

2G118 RESTROOM 2G118 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G

2G119 STERILE SUPPLY 2G119 3' - 6" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B

2…