This package includes construction documents for renovations and an addition to the Joint Ambulatory Care Clinic in Pensacola, Florida. The project involves renovating and expanding the existing two-story clinic to upgrade facilities and accommodate additional staff and services. Plans cover demolition, site work, structural modifications, interior reconfigurations, mechanical and plumbing system upgrades, electrical and communications infrastructure, finishes, and furnishings. Specific work includes a two-story addition, exam room and office renovations, new core lab and sterile supply areas, mechanical penthouse additions, and ADA compliance improvements. The solicitation seeks offers for a fixed-price construction contract to be awarded by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRIPLE C – THE A&E GROUP
OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE
410 Grand Avenue, Suite 201C Laramie, Wyoming 82070 Telephone: (307) 460-2054 Fax: (307) 460-2053
Addendum Number 01
Project: 520-331 Construct Addition and Renovations to JACC, Pensacola FL
Date: 02/08/2024
NOTICE TO PROPOSERS:
A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated integrally therewith.
Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take precedence.
B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject Proposer to disqualification.
Revisions:
Specifications:
SECTION Description of / Reason for Change
08 80 00 -
Glazing
Glazing types clarified
Drawing Changes:
SHEET NUMBER REVISION
NUMBER
DESCRIPTION OF/REASON FOR CHANGE
A-601 n/a Glazing types assigned to door and window glazing
IN-1.01R-6 n/a Existing bldg. Ground floor reflected ceiling plan for
Reference only
CVE Verified Service-Disabled Veteran-Owned Small Business
TRIPLE C – THE A&E GROUP
OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE
410 Grand Avenue, Suite 201C Laramie, Wyoming 82070 Telephone: (307) 460-2054 Fax: (307) 460-2053
IN-1.02R-6 n/a Existing bldg. Second floor reflected ceiling plan for
Reference only
End of Addendum
Attachments:
08 80 00 – glazing
A-601
IN-1.01R-6
IN-1.02R-6
Addition & Renovation Project #: 520-331
08 80 00 - 1
SECTION 08 80 00
GLAZING
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies the following:
1. Glass.
2. Glazing materials and accessories for both factory and field glazed assemblies.
1.2 RELATED WORK
A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Sustainable Construction Requirements.
B. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES, and Section 08 14 00, WOOD DOORS: Sound resistant doors.
C. Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES: Mirrors.
D. Section 12 36 00, COUNTERTOPS.
E. Section 08 51 13, ALUMINUM WINDOWS: Aluminum Windows.
F. Section 09 06 00, SCHEDULE FOR FINISHES: Color of glass.
G. Section 26 05 19, LOW VOLTAGE ELECTRICAL POWER AND CONDUCTORS AND CABLES: Wiring (120 V AC, 15A or 20A).
H. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Junction and Switch Boxes.
I. Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS: Access Control Systems.
1.3 LABELS
A. Temporary labels:
1. Provide temporary label on each light of glass identifying manufacturer or brand and glass type, quality and nominal thickness.
2. Label in accordance with NFRC label requirements.
3. Temporary labels are to remain intact until glass is approved by Contracting Officer
Representative (COR).
B. Permanent labels:
1. Locate in corner for each pane.
2. Label in accordance with ANSI Z97.1 and SGCC label requirements.
a. Tempered glass.
b. Laminated glass or have certificate for panes without permanent label.
3. Fire rated glazing assemblies: Mark in accordance with IBC.
1.4 PERFORMANCE REQUIREMENTS
A. General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminated Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, thermal movements, building movements, permitted tolerances, and combinations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation; failure of sealants or gaskets to remain watertight and airtight; deterioration of glazing materials; unsafe engagement of the framing system; deflections beyond specified limits; or other defects in construction.
08 80 00 - 2
B. Glazing Unit Design: Design glass, including engineering analysis meeting requirements of authorities having jurisdiction. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers.
1. Design glass in accordance with ASTM E1300, and for conditions beyond the scope of
ASTM E1300, by a properly substantiated structural analysis.
2. Design Wind Pressures: As indicated on construction documents .
3. Wind Design Data: As indicated on construction documents.
4. Maximum Lateral Deflection: For glass supported on all four edges, limit center-of-glass deflection at design wind pressure to not more than the structural capacity of the glazing unit, the threshold at which frame engagement is no longer safely assured, 1/100 times the short-side length.
C. Windborne-Debris-Impact Resistance: Comply with enhanced-protection testing requirements in ASTM E1996 for project wind zone when tested according to ASTM E1886, based upon testing of specimens not less than the size required for project and utilizing installation method identical to that specified for project.
1. Project Wind Zone: Wind Zone 4 (164 MPH).
2. Large-Missile Test: For glazing located within 9.1 m (30 feet) of grade.
1.5 SUBMITTALS
A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Sustainable Design Submittals, as described below:
1. Volatile organic compounds per volume as specified in PART 2 - PRODUCTS.
C. Manufacturer's Certificates:
1. Certificate stating that fire-protection and fire-resistive glazing units meet code requirements for fire-resistance-rated assembly and applicable safety glazing requirements.
2. Certificate on solar heat gain coefficient when value is specified.
3. Certificate on "R" value when value is specified.
4. Certificate test reports confirming compliance with specified bullet resistive rating.
5. Certificate that blast resistant glass meets the specified requirements.
D. Manufacturer Warranty.
E. Manufacturer's Literature and Data:
1. Glass, each kind required.
2. Insulating glass units.
3. Transparent (one-way vision glass) mirrors.
4. Elastic compound for metal sash glazing.
5. Putty, for wood sash glazing.
6. Glazing cushion.
7. Sealing compound.
8. Bullet resistive material.
9. Plastic glazing material, each type required.
F. Samples:
1. Size: 305 mm by 305 mm (12 inches by 12 inches).
2. Tinted glass.
3. Reflective glass.
4. Transparent (one-way vision glass) mirrors.
G. Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazing sealants were tested for adhesion to glass and glazing channel substrates and for compatibility with glass and other glazing materials.
08 80 00 - 3
1.6 DELIVERY, STORAGE AND HANDLING
A. Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.
B. Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.
C. Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.
D. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED
FACE":
1. Treat security glazing as fragile merchandise, and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to prevent edge damage or other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.
2. Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight.
Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals.
3. Temporary protections: The glass front and polycarbonate back of glazing are to be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and re-applied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the film used on exposed polycarbonate surfaces is to be approved and applied by manufacturer.
4. Edge protection: To cushion and protect glass clad, and polycarbonate edges from contamination or foreign matter, the four (4) edges are to be sealed the depth of glazing with continuous standard-thickness thermoplastic rubber tape. Alternatively, continuous channel shaped extrusion of thermoplastic rubber are to be used, with flanges extending into face sides of glazing.
5. Protect "Constant Temperature" units including every unit where glass sheet is directly laminated to or directly sealed with metal-tube type spacer bar to polycarbonate sheet, from exposures to ambient temperatures outside the range of 16 to 24 degrees C (60 to 75 degrees F), during the fabricating, handling, shipping, storing, installation, and subsequent protection of glazing.
1.7 PROJECT CONDITIONS:
A. Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field measured products.
1.8 WARRANTY
A. Construction Warranty: Comply with the FAR clause 52.246-21 “Warranty of Construction”.
B. Manufacturer Warranty: Manufacturer shall warranty their glazing from the date of installation and final acceptance by the Government as follows. Submit manufacturer warranty.
1. Insulating glass units to remain sealed for ten (10) years.
2. Laminated glass units to remain laminated for five (5) years.
1.9 APPLICABLE PUBLICATIONS:
A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.
B. American Architectural Manufacturers Association (AAMA):
800 ........................................ Test Methods for Sealants
08 80 00 - 4
810.1-77 ................................ Expanded Cellular Glazing Tape
C. American National Standards Institute (ANSI):
Z97.1-14 ................................ Safety Glazing Material Used in Building - Safety Performance
Specifications and Methods of Test
D. American Society of Civil Engineers (ASCE):
7-16 ....................................... Wind Load Provisions
E. ASTM International (ASTM):
C542-05(2017) ...................... Lock-Strip Gaskets
C716-06(2020) ...................... Installing Lock-Strip Gaskets and Infill Glazing Materials
C794-18 ................................. Adhesion-in-Peel of Elastomeric Joint Sealants
C864-05(2019) ...................... Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers
C920-18 ................................. Elastomeric Joint Sealants
C964-20 ................................. Standard Guide for Lock-Strip Gasket Glazing
C1036-16 ............................... Flat Glass
C1048-18 ............................... Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass.
C1172-19 ............................... Laminated Architectural Flat Glass
C1349-17 ............................... Standard Specification for Architectural Flat Glass Clad Polycarbonate
C1376-15 ............................... Pyrolytic and Vacuum Deposition Coatings on Flat Glass
D635-18 ................................. Rate of Burning and/or Extent and Time of Burning of Self- Supporting Plastic in a Horizontal Position
D4802-16 ............................... Poly (Methyl Methacrylate) Acrylic Plastic Sheet
E84-20 ................................... Surface Burning Characteristics of Building Materials
E119-20 ................................. Standard Test Methods for Fire Test of Building Construction and Material
E1300-16 ............................... Load Resistance of Glass in Buildings
E1886-19 ............................... Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials
E1996-17 ............................... Standard Specification for Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes
E2141-14 ............................... Test Methods for Assessing the Durability of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units
E2190-19 ............................... Insulating Glass Unit
E2240-06 ............................... Test Method for Assessing the Current-Voltage Cycling Stability at 90 Degree C (194 Degree F) of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units
E2241-06 ............................... Test Method for Assessing the Current-Voltage Cycling Stability at Room Temperature of Absorptive Electrochromic Coatings on Sealed Insulating Glass Units
08 80 00 - 5
E2354-10 ............................... Assessing the Durability of Absorptive Electrochromic Coatings within Sealed Insulating Glass Units
E2355-10 ............................... Test Method for Measuring the Visible Light Transmission Uniformity of an Absorptive Electrochromic Coating on a Glazing Surface
F1233-08(2019) .................... Standard Test Method for Security Glazing Materials and Systems
F1642/F1642M-17 ................. Test Method for Glazing and Glazing Systems Subject to Airblast Loadings
F. Code of Federal Regulations (CFR):
16 CFR 1201-10 .................... Safety Standard for Architectural Glazing Materials
G. Glass Association of North America (GANA):
2010 Edition .......................... GANA Glazing Manual
2008 Edition .......................... GANA Sealant Manual
2019 Edition .......................... GANA Laminated Glazing Reference Manual
2010 Edition .......................... GANA Protective Glazing Reference Manual
H. International Code Council (ICC):
IBC ........................................ International Building Code
I. Insulating Glass Certification Council (IGCC)
J. Insulating Glass Manufacturer Alliance (IGMA):
TB-3001-13 ........................... Guidelines for Sloped Glazing
TM-3000 ................................ North American Glazing Guidelines for Sealed Insulating Glass Units for Commercial and Residential Use
K. Intertek Testing Services – Warnock Hersey (ITS-WHI)
L. National Fire Protection Association (NFPA):
80-19 ..................................... Fire Doors and Windows
252-17 ................................... Fire Tests of Door Assemblies
257-17 ................................... Standard on Fire Test for Window and Glass Block Assemblies
M. National Fenestration Rating Council (NFRC)
1. Safety Glazing Certification Council (SGCC) 2012:
2. Certified Products Directory (Issued Semi-Annually).
N. Underwriters Laboratories, Inc. (UL):
9-08(R2009) .......................... Fire Tests of Window Assemblies
263-14 ................................... Fire Tests of Building Construction and Materials
752-11 ................................... Bullet-Resisting Equipment.
O. Department of Veterans Affairs:
1. Physical Security and Resiliency Design Manual January 2021
2. Architectural Design Manual for VA Facilities (VASDM)
P. Environmental Protection Agency (EPA):
40 CFR 59(2014) .................. National Volatile Organic Compound Emission Standards for
Consumer and Commercial Products
08 80 00 - 6
PART 2 - PRODUCT
2.1 GLASS
A. Provide minimum thickness stated and as additionally required to meet performance requirements.
1. Provide minimum 6 mm (1/4 inch) thick glass units unless otherwise indicated.
B. Obtain glass units from single source from single manufacturer for each glass type.
C. Clear Glass:
1. ASTM C1036, Type I, Class 1, Quality q4.
D. Ultra-clear-Low-Iron Float Glass:
1. ASTM C1036, Type I, Class 1, Quality q4 and with visible light transmission of not less than 90 percent.
2.2 HEAT-TREATED GLASS
A. Roller Wave Limits for Heat-Treated Glass: Orient all roller wave distortion parallel to bottom surface of glazing, and provide units complying with the following limitations:
1. Measurement Parallel to Line: Maximum peak to valley 0.203 mm (0.008 inch).
2. Measurement Perpendicular to Line: Maximum 0.0254 mm (0.001 inch).
3. Bow/Warp: Maximum 50 percent of bow and warp allowed by ASTM C1048.
B. Clear Heat Strengthened Glass:
1. ASTM C1048, Kind HS, Condition A, Type I, Class 1, Quality q3.
C. Clear Tempered Glass:
1. ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.
2.3 COATED GLASS:
A. Reflective-Coated Spandrel Glass:
1. ASTM C1376, Kind CS and ASTM C1048, Kind HS, Condition B, Type I.
B. Reflective-Coated Low-E Coated Tempered Glass:
1. ASTM C1376 and ASTM C1048, Kind FT, Condition C, Type I, Class 1, Quality q3 with reflective metallic coating.
2.4 LAMINATED GLASS
A. Laminated Glass: ASTM C1172. Two or more lites of heat treated glass bonded with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent-resin interlayer complying with interlayer manufacturer's written instructions. Minimum total laminated thickness of 1/4” for blast resistant glazing.
B. Interlayer: Use min. 0.75 mm (0.030 inch) thick interlayer for vertical glazing unless otherwise scheduled.
C. Interlayer: Use 1.5 mm (0.060 inch) thick interlayer for:
1. Horizontal or sloped glazing.
2. Acoustical glazing.
3. Assemblies requiring heat strengthened or fully tempered glass.
D. Interlayer: Use 2.28 mm (0.090 inch) thick interlayer where required to meet performance requirements.
E. Interlayer Color: Clear, unless otherwise scheduled.
2.5 INSULATING GLASS UNITS
A. Provide factory fabricated, hermetically sealed glass unit consisting of two panes of glass separated by a dehydrated air space and comply with ASTM E2190. The exterior glass unit
08 80 00 - 7 shall be fully tempered and the inner glass unit shall be laminated annealed at a minimum for all blast resistant glazing.
B. Assemble units using glass types specified in Insulating Glass Schedule and Blast Glazing assembly requirements
2.6 FIRE PROTECTION AND FIRE RESISTANCE GLAZING
A. Fire-Protection-Rated Glazing: Glazing units tested for use in fire door assemblies or fire windows, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC, for fire-protection ratings as scheduled, based upon positive-pressure testing per NFPA 257 or UL 9, and complying with NFPA 80.
1. Hose-Stream Test: Units must comply, except units having fire-protection rating of 20 minutes.
2. Confirm requirements with authorities having jurisdiction.Temperature Rise Limitation:
Units over 0.065 square meter (100 square inch) must comply with 232 deg. C (450 degress F) limitation.
3. Labeling: Permanently label fire-protection-rated glazing units in accordance with IBC.
4. Safety Glazing: Comply with 16 CFR 1201, Category II.
5. Fire-Protection-Rated Tempered Glass: For 20-minute fire-protection-rated door assemblies, of thickness scheduled.
6. Fire-Protection-Rated Laminated Ceramic Glazing: Units made from two lites of clear, ceramic glass, 8 mm (5/16 inch) total thickness, for rating scheduled.
7. Fire-Protection-Rated Laminated Glass with Intumescent Interlayers: Units made from multiple lites of uncoated, ultra-clear (low-iron) float glass, in intumescent interlayers, of thickness and rating scheduled.
B. Fire-Resistance-Rated Glazing: Glazing units tested for use in fire wall assemblies, UL, ITS- WHI or equivalent listed and labeled by testing agency in accordance with IBC for fire-resistance ratings of wall assemblies as scheduled, based upon testing according to NFPA 252 and ASTM E119 or UL 263.
1. Labeling: Permanently label fire-resistance-rated glazing units in accordance with IBC.
2. Safety Glazing: Comply with 16 CFR 1201, Category II.
3. Fire-Resistance-Rated Laminated Glass with Intumescent Interlayers: Units made from multiple lites of uncoated, ultra-clear low-iron float glass, in intumescent interlayers, of thickness and rating scheduled.
4. Fire-Resistance-Rated Double Glazing Units with Gel Fill: Units made from two lites of uncoated, fully tempered, ultra-clear (low-iron) float glass, with perimeter metal spacer and edge seal forming cavity filled with clear, fully transparent, heat-absorbing gel, of thickness and fire-protection rating scheduled.
2.7 ALUMINUM PARTITIONS WITH GLASS
A. Basis of Design: CRL Aluminum Partition Posts.
B. Partition posts: Square profile at 1-1/2” thick, 30” overall height.
a. Channel to be in post to accept glass.
C. Finish: Brushed stainless.
D. Accessories:
1. Flat cap at top.
2. Welded base.
E. Glass: 1/4" clear and fully tempered with all exposed edges polished.
1. 2” air space to be held between glass and counter.
2.8 GLAZING ACCESSORIES
A. As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work are to have a
08 80 00 - 8 finish that will not corrode or stain while in service. Fire rated glazing to be installed with glazing accessories in accordance with the manufacturer’s installation instructions.
B. Setting Blocks: ASTM C864:
1. Silicone type.
2. Channel shape; having 6 mm (1/4 inch) internal depth.
3. Shore A hardness of 80 to 90 Durometer.
4. Block lengths: 50 mm (2 inches) except 100 to 150 mm (4 to 6 inches) for insulating glass.
5. Block width: Approximately 1.6 mm (1/16 inch) less than the full width of the rabbet.
6. Block thickness: Minimum 4.8 mm (3/16 inch). Thickness sized for rabbet depth as required.
C. Spacers: ASTM C864:
1. Channel shape having a 6 mm (1/4 inch) internal depth.
2. Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick.
3. Lengths: 25 to 76 mm (1 to 3 inches).
4. Shore A hardness of 40 to 50 Durometer.
D. Glazing Tapes:
1. Semi-solid polymeric based closed cell material exhibiting pressure-sensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging.
2. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.
3. Complying with AAMA 800 for the following types:
a. AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant.
b. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid sealant.
E. Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops.
F. Glazing Clips: Galvanized steel spring wire designed to hold glass in position in rabbeted sash without stops.
G. Glazing Points (Sprigs): Pure zinc stock, thin, flat, triangular or diamond shaped pieces, 6 mm (1/4 inch) minimum size.
H. Glazing Gaskets: ASTM C864:
1. Firm dense wedge shape for locking in sash.
2. Soft, closed cell with locking key for sash key.
3. Flanges may terminate above the glazing-beads or terminate flush with top of beads.
I. Lock-Strip Glazing Gaskets: ASTM C542, shape, size, and mounting as indicated.
J. Glazing Sealants: ASTM C920, silicone neutral cure:
1. Type S.
2. Class 25 or 50 as recommended by manufacturer for application.
3. Grade NS.
4. Shore A hardness of 25 to 30 Durometer.
K. Structural Sealant: ASTM C920, silicone acetoxy cure:
1. Type S.
2. Class 25.
3. Grade NS.
4. Shore a hardness of 25 to 30 Durometer.
L. Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C864.
1. Channel shape; flanges may terminate above the glazing channel or flush with the top of the channel.
08 80 00 - 9
2. Designed for dry glazing.
M. Color:
1. Color of glazing compounds, gaskets, and sealants used for aluminum color frames to match color of the finished aluminum and be nonstaining.
2. Color of other glazing compounds, gaskets, and sealants which will be exposed in the finished work and unpainted are to be black, gray, or neutral color.
N. Smoke Removal Unit Targets: Adhesive targets affixed to glass to identify glass units intended for removal for smoke control. Comply with requirements of local Fire Department.
2.9 GLAZING FILM
A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
B. Reference drawings for locations.
C. Material Properties:
1. General: Glass and plastic finishes field-applied application to glass or plastic material as visual opaque or decorative film.
2. Film: Polyester.
3. Decorative Pattern: Printed.
4. Adhesive: Acrylic, Pressure Sensitive, Permanent.
5. Liner: Silicone-coated Polyester.
6. Thickness (Average): 3.2 mils (80 microns).
7. Fire Performance: Surface burning characteristics when tested in accordance with ASTM
E84: Class A:
a. Flame Spread: 25 maximum.
b. Smoke Developed: 450 maximum.
D. INSTALLATION
1. Film Installation, General:
a. Install in accordance with manufacturer's instructions.
b. Cut film edges neatly and square at a uniform distance of 1/8 inch (3 mm) to 1/16 inch (1.5 mm) of window sealant. Use new blade tips after 3 to 4 cuts.
c. Spray the slip solution, composed of one capful of baby shampoo or dishwashing liquid to 1 gallon of water, on window glass and adhesive to facilitate proper positioning of film.
d. Apply film to glass and lightly spray film with slip solution.
e. Squeegee from top to bottom of window. Spray slip solution to film and squeegee a second time.
f. Bump film edge with lint-free towel wrapped around edge of a 5-way tool.
g. Upon completion of film application, allow 30 days for moisture from film installation to dry thoroughly, and to allow film to dry flat with no moisture dimples when viewed under normal viewing conditions.
h. If completing an exterior application, check with the manufacturer as to whether edge sealing is required.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verification of Conditions:
1. Examine openings for glass and glazing units; determine they are proper size; plumb;
square; and level before installation is started.
2. Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer is approved shop drawings.
08 80 00 - 10
B. Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation. Do not proceed with installation until unsatisfactory conditions have been corrected.
C. Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units.
3.2 PREPARATION
A. For sealant glazing, prepare glazing surfaces in accordance with GANA Sealant Manual.
B. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.
C. Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances.
D. Verify that components used are compatible.
E. Clean and dry glazing surfaces.
F. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.
3.3 INSTALLATION – GENERAL
A. Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified otherwise.
B. Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test Requirements specified in other applicable sections of specifications.
C. Set glazing without bending, twisting, or forcing of units.
D. Do not allow glass to rest on or contact any framing member.
E. Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.
F. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.
G. Laminated Glass:
1. Tape edges to seal interlayer and protect from glazing sealants.
2. Do not use putty or glazing compounds.
H. Insulating Glass Units:
1. Glaze in compliance with glass manufacturer's written instructions.
2. When glazing gaskets are used, they are to be of sufficient size and depth to cover glass seal or metal channel frame completely.
3. Do not use putty or glazing compounds.
4. Do not grind, nip, cut, or otherwise alter edges and corners of fused glass units after shipping from factory.
5. Install with tape or gunnable sealant in wood sash.
I. Fire Protective and Fire Resistance Glass:
1. Wire Glass: Glaze in accordance with NFPA 80.
2. Other fire protective and fire resistant glass: Glaze in accordance with manufacturer’s installation instructions and NFPA 80.
3.4 INSTALLATION - DRY METHOD (TAPE AND GASKET SPLINE GLAZING)
A. Cut glazing spline to length; install on glazing pane. Seal corners by butting and sealing junctions with butyl sealant.
08 80 00 - 11
B. Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.
C. Rest glazing on setting blocks and push against fixed stop with sufficient pressure to attain full contact.
D. Install removable stops without displacing glazing spline. Exert pressure for full continuous contact.
E. Do not exceed edge pressures stipulated by glass manufacturers for installing glass lites.
F. Trim protruding tape edge.
3.5 INSTALLATION - WET/DRY METHOD (PREFORMED TAPE AND SEALANT)
A. Cut glazing tape to length and set against permanent stops, 5 mm (3/16 inch) below sight line.
Seal corners by butting tape and dabbing with butyl sealant.
B. Apply heel bead of butyl sealant along intersection of permanent stop with frame ensuring full perimeter seal between glass and frame to complete the continuity of the air and vapor seal.
C. Place setting blocks at 1/4 points with edge block no more than 152 mm (6 inches) from corners.
D. Rest glazing on setting blocks and push against tape and heel bead of sealant with sufficient pressure to achieve full contact at perimeter of pane or glass unit.
E. Install removable stops, with spacer strips inserted between glazing and applied stops, 6 mm (1/4 inch) below sight line. Place glazing tape on glazing pane or unit with tape flush with sight line.
F. Fill gap between glazing and stop with sealant to depth equal to bite of frame on glazing, but not more than 9 mm (3/8 inch) below sight line. Sealant type is to be compatible with glazing tape.
G. Apply cap bead of sealant along void between the stop and the glazing, to uniform line, flush with sight line. Tool or wipe sealant surface smooth.
3.6 INSTALLATION - WET METHOD (SEALANT AND SEALANT)
A. Place setting blocks at ¼ points and install glazing pane or unit.
B. Install removable stops with glazing centered in space by inserting spacer shims both sides at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.
C. Fill gaps between glazing and stops with sealant to depth of bite on glazing, but not more than 9 mm (3/8 inch) below sight line to ensure full contact with glazing and continue the air and vapor seal.
D. Apply sealant to uniform line, flush with sight line. Tool or wipe sealant surface smooth.
3.7 INSTALLATION - INTERIOR WET/DRY METHOD (TAPE AND SEALANT)
A. Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line.
B. Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.
C. Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit.
D. Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.
E. Fill gaps between pane and applied stop with sealant to depth equal to bite on glazing, to uniform and level line. Sealant type is to be compatible with glazing tape.
08 80 00 - 12
F. Trim protruding tape edge.
3.8 INSTALLATION - INTERIOR WET METHOD (COMPOUND AND COMPOUND)
A. Install glazing resting on setting blocks. Install applied stop and center pane by use of spacer shims at 600 mm (24 inch) centers, kept 6 mm (1/4 inch) below sight line.
B. Locate and secure glazing pane using spring wire clips.
C. Fill gaps between glazing and stops with glazing compound until flush with sight line. Tool surface to straight line.
3.9 ALUMINUM PARTITIONS WITH GLASS
A. Posts to be securely mounted to countertops per manufacturer’s recommendations.
3.10 REPLACEMENT AND CLEANING
A. Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by COR.
B. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.
C. Leave glass, putty, and other setting material in clean, whole, and acceptable condition.
3.11 PROTECTION
A. Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.
3.12 MONOLITHIC GLASS SCHEDULE
A. Glass Type MG# 1: Clear fully tempered float glass.
1. Unit Thickness: 6 mm (0.23 inch)
2. Safety glazing label required.
3.13 LAMINATED GLASS SCHEDULE
A. Glass Type LG# 1: Clear laminated glass with two (2) lites of fully tempered float glass.
1. Minimum Thickness of Each Glass Lite: 3 mm (0.12 inch).
2. Interlayer Thickness: 1.52 mm (0.060 inch).
3. Safety glazing label required.
4. Application: Interior glazing of units unless otherwise scheduled.
B. Glass Type LG# 4: Clear laminated glass with two (2) lites of fully tempered ultra-clear (low-iron) float glass.
1. Minimum Thickness of Each Glass Lite: 6 mm (0.24 inch) .
2. Interlayer Thickness: 2.29 mm (0.090 inch) .
3. Safety glazing label required.
4. Windborne debris-resistant glazing unit required.
3.14 INSULATING GLASS SCHEDULE
A. Glass Type IG# 2: Low-E-coated, Tinted insulating glass. (match tint of existing windows to remain)
1. Overall Unit Thickness: 25 mm (1 inch).
2. Minimum Thickness of Each Glass Lite: 6 mm (0.23 inch).
3. Outdoor Lite: Annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.
4. Interspace Content: Argon
5. Indoor Lite: Fully tempered float glass.
6. Low-E Coating: Sputtered on third surface.
7. Visible Light Transmittance: 68 percent minimum.
8. Solar Heat Gain Coefficient: 0.38 maximum.
9. Safety glazing label required.
Shannon Text Box Addendum #1
Shannon Cloud
08 80 00 - 13
3.15 FIRE-PROTECTIVE AND FIRE-RESISTANCE GLAZING SCHEDULE
A. Glass Type FR# 1: Fire-protection-rated tempered glass.
1. Thickness: 12 mm (0.47 inch).
2. Rating: 20 minutes.
3. Application: Fire-protection-rated door assemblies with openings not over 0.65 square meter (100 square inch).
B. Glass Type FR# 2: Fire-protection-rated laminated ceramic glazing.
1. Thickness: 12 mm (0.47 inch)
2. Rating: 45 minute.
3. Application: Fire-protection-rated door and window assemblies.
- - - E N D - - -
Cloud
Shannon Text Box Addendum #1
This page intentionally left blank.
F
FLUSH
2' -9
3'
-7
1'-0" 4"
N
T
NARROW VISION
3' -0
3'
-4
G
6"6"
HALF GLASS
T
FG
5" 5"
5"
T
FULL GLASS
TYPICAL FRAME
2" H
E
IG
H T
2" WIDTH 2"
TERMINATED STOPS
4"
TERMINATED
STOPS @
INTERIOR
DOORS ONLY
xT
MASONRY HEAD
xM
T Y
P
4"
2"
1/2" 1/2"VARIES
SEE PLAN
WALL - SEE PLAN FOR
TYPE
SEALANT - EA. SIDE &
ALL AROUND, TYP.
HOLLOW METAL FRAME
1/ 2"
V A
R
IE
S S
E E
P
LA
N 1/
2"
4" 2"
ADJACENT WALL WHERE
OCCURS
SEALANT - EA SIDE & ALL
AROUND, TYP.
HOLLOW METAL FRAME
WALL - SEE PLAN FOR
TYPE
2"
6"
BRICK VENEER
UNIT
HOLLOW METAL
FRAME
SEALANT, TYP.
2 1/2"
WALL TYPE AS SCHEDULED
METAL FLASHING
OVERLAP WATER-
RESISTANT
BARRIER AND
FLASHING
STEEL ANGLE
LINTEL -
SEE STRUCTURAL
WEEPS (2 MIN) EQ SPACED
ABOVE OPENING (24" O.C. MAX)
2"
6"
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
BRICK VENEER UNIT
STEEL ANGLE SUPPORT -
SEE STRUCTURAL
STUD COLUMN - SEE FRAMING
DETAILS
RETURN WALL FINISH
AT OPENING
1/
2"
W A
LL
T
Y P
E A
S S
C H
E D
U
LE
D
INTERIOR DOUBLE HUNG
WINDOW
SEALANT AND BACKING ROD
EACH SIDE & ALL AROUND,
TYP.
SHIM SPACE AS REQUIRED
ATTACH TO FRAMING PER
MANUFACTURER
STUD BOX BEAM HEADER
VARIES - SEE PLAN
V A
R
IE
S S
E E
P
LA
N
SEALANT & BACKER ROD -
EACH SIDE & ALL AROUND,
TYP.
INTERIOR DOUBLE
HUNG WINDOW
SHIM AS REQUIRED
ATTACH TO FRAMING
PER MANUFACTURER
INTERIOR DOUBLE
HUNG WINDOW
SEALANT AND BACKING ROD
EACH SIDE & ALL AROUND,
TYP.
SHIM SPACE AS REQUIRED
ATTACH TO FRAMING PER
MANUFACTURER
VARIES - SEE PLAN
COUNTERTOP WHERE OCCURS
2' -8
6'
-0
4'-0"
4' -3
1'
-9
W1 W1S
5' -6
16'-0 1/2"
2' -7
2'
-1 1"
3'-6 1/2" * 3'-6" * 1'-11" * 3'-6" * 3'-7" *
W1F
* NOTE: MATCH EXISTING
VERTICAL MULLION
SPACING, VERIFY IN FIELD
A-601
A-601
LAB
DOUBLE
HUNG
COUNTERTOP TO BE
COORDINATED WITH PLAN
WINDOW TO LOCK AND
OPERATE FROM LAB SIDE
GLAZING FILM (GF-1) TO BE APPLIED
ON GLAZING FROM LAB SIDE
3'-0"
2' -1
0" 4'
-0
E1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C THE A&E GROUP
4830 W. Kennedy Blvd. Suite 600 Tampa, FL 33609
(813) 261 1023
MAT PERKINS
09.26.2022
B
IM
/5
-3
C o n s tr u c t R e n o v a ti o n a n d A d d it io n t o
J A
C C
P e n s a c o la
/5
-3
.J A
C C
.P a c k a g e
.A
R C
H .r v t
/7 /2
:5
:1
P
M
A-601
ARCHITECTURAL SCHEDULES 520-331
JACC-2F
09.26.2022 M. PERKINS C. LOWERY
ISSUED FOR
CONSTRUCTION
CONSTRUCT ADDITION AND
RENOVATIONS TO JACC
790 Veterans Way, Pensacola, FL 32503
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME
FIRE
RATING
DETAIL HARDWARE
NOTESROOM NO. ROOM NAME DOOR NO.
WIDTH
H T TYPE MATERIAL TYPE MATERIAL HEAD JAMB ELEC GROUPW1 W2
TOTAL
WIDTH
SECOND FLOOR
2G100 WAITING ROOM 2G101 4' - 0" 7' - 0" 1 3/4" N WD 1 HM 45 MIN D8/A601 D9/A601 AC, ADO, RR, REX HW-5D DOOR FROM PHLEBOTOMY WAITING TO BLOOD DRAW
2G100A RESTROOM 2G100A 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G103 RECEPTION 2G103 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-3G PROVIDE OVERHEAD 90 DEGREE STOP
2G112 RESTROOM 2G112 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G114 RESTROOM 2G114 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G116 RESTROOM 2G116 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G117 CORE LAB 2G117C 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 AC, ADO ,REX HW-5D DOOR FROM BLOOD DRAW TO CORE LAB
2G117 CORE LAB 2G117A 3' - 4" 3' - 4" 6' - 8" 8' - 0" 1 3/4" N/N WD 1 HM 45 MIN D8/A601 D9/A601 AC, ADO, REX HW-10B DOOR FROM SOUTH CORRIDOR TO CORE LAB
2G117 CORE LAB C2-101B 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-1F
2G117A VESTIBULE 2G117B 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 AC, REX HW-5D DOOR FROM STAFF LOUNGE TO CORE LAB
2G118 RESTROOM 2G118 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G119 STERILE SUPPLY 2G119 3' - 6" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G120 BULK STORAGE 2G120 3' - 0" 3' - 0" 6' - 0" 8' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-10B
2G122 NEG. PRESSURE LAB MICROBIOLOGY 2G122 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 ADO, REX (X2) HW-4A MICROBIOLOGY LAB DOOR
2G123 LAB OFFICE TOUCHDOWN 2G123 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G125 LAB OFFICE 2G125 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G126 STAFF RESTROOM 2G126 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G127 LAB OFFICE 2G127 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G128 CONSULT 2G128 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-1G
2G129 CONSULT 2G129 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-1G
2G130 FILE CLOSET 2G130 3' - 4 1/2" 7' - 0" 1 3/4" F WD SLIDING MFG'R D8/A601 D9/A601 ADA-1 SLIDING BARN DOOR
2G131 ELECTRICAL 2G131 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G132 HAC 2G132 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G134 RECEPTION 2G134 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-3G
2G135 INFUSION CLINIC C2-99 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 REX, AC, DPS HW-5D
2G135 INFUSION CLINIC C2-97A 3' - 6" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC, RR, REX HW-5D FROM INFUSION CLINIC TO WAITING ROOM
2G136 EXAM / CONSULT 2G136 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-1G
2G137 ADMIN SUPPORT 2G137 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-3G
2G138 RESTROOM 2G138 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G139 RESTROOM 2G139 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G140 SOILED UTILITY 2G140 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G141 STERILE SUPPLY 2G141 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 HW-5B
2G142 MED ROOM 2G142 3' - 4" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC, REX HW-SH-3 MED ROOM DOOR
2G143 CONFERENCE/ BREAK ROOM 2G143 3' - 0" 7' - 0" 1 3/4" N WD 1 HM D8/A601 D9/A601 HW-4
2G144 STAFF RESTROOM 2G144 3' - 0" 7' - 0" 1 3/4" F WD 1 HM D8/A601 D9/A601 HW-2G
2G145 TELECOM ROOM 2G145 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC, DUAL, DPS, REX HW-SH-3
C2-101 CORRIDOR C2-101A 3' - 0" 7' - 0" 1 3/4" F WD 1 HM 45 MIN D8/A601 D9/A601 AC HW-5D 2G - CORE LAB STAFF AREA TO ATRIUM
STAIR-F STAIR C2-97B 3' - 0" 7' - 0" 1 3/4" N WD 1 HM 90 MIN D8/A601 D9/A601 PEX HW-1E
Grand total: 38
DOOR MODIFICATIONS
DOOR & FRAME NOTES:
ALARM DELAYED DOOR ALARM (DOOR IS EXIT ONLY)
A LAMINATED GLASS
A1 INSULATED TEMPERED LAMINATED GLASS
AC ACCESS CONTROL DEVICE
ADO AUTOMATIC DOOR OPERATOR
D DOUBLE GLAZED TEMPERED GLASS
DEML DELAYED EGRESS MAGNETIC LOCK
DEPH DELAYED EGRESS PANIC EXIT DEVICE
DPS DOOR POSITION MONITORING SWITCH
DUAL DUAL AUTHENTICATION ACCESS CONTROL
EL ELECTRIC LOCK OR ELECTRIC LEVER EXIT DEVICE
ELR ELECTRIC LATCH RETRACTION EXIT DEVICE
EMCH ELECTRO-MECHANICAL CLOSER-HOLDER
F FIRE RATED GLAZING
H ELECTRIC HOLD
KS KEYSWITCH
MHO MAGNETIC HOLD OPEN
ML MAGNETIC LOCK
PEX PUSH TO EXIT PUSH BAR EXIT DEVICE
REX REQUEST TO EXIT SWITCH IN LATCHING DEVICE INSIDE
TRIM
RR REMOTE RELEASE BUTTON
SEC SECURITY ALARM FOR PIV OFFICE
T TEMPERED GLASS
U UNDERCUT 1"
FRAME TYPE NOMENCLATURE
X x
DENOTES FRAME SUB-TYPE
DENOTES FRAME TYPE
(SEE ADJACENT FRAME TYPE ELEVATIONS)
FRAME SUB-TYPES
M MASONRY HEAD
(SEE ADJACENT FRAME SUB-TYPES ELEVATIONS)
MT MASONRY HEAD AND TERMINATED STOPS
(SEE ADJACENT FRAME SUB-TYPES ELEVATIONS)
T TERMINATED STOP
(SEE ADJACENT FRAME SUB-TYPES ELEVATIONS)
NOTES
1. SEE DOOR SCHEDULE FOR DOOR WIDTH AND HEIGHT
2. INSET FRAME DEPTH/THROAT IS 6" UNLESS OTHERWISE
NOTED
3. INSET FRAME'S HEAD WIDTH IS 2" UNLESS DENOTED AS
MASONRY HEAD
4. WRAPPED FRAME'S HEAD WIDTH IS 2"
DOOR PANEL TYPES
DOOR FRAME TYPES
3" = 1'-0" D8
HM - TYP. INTERIOR HEAD
3" = 1'-0"
D9
HM - TYP. INTERIOR JAMB
3" = 1'-0" E8
HM HEAD - BRICK VENEER, STUD WALL
3" = 1'-0" F8
HM JAMB - BRICK VENEER, STUD WALL
DOOR HARDWARE LEGEND
HW-1 Public Restrooms - Passage, with Closer
HW-1E Rated, Non-locking - Passage, With Rim Exit (Panic) Device, Closer
HW-1F Corridor - Passage (F01 Lockset)
HW-1G Exam Rooms - Passage (F01 Lockset) w/ Privacy Deadbolt
HW-2G Single Restrooms - Privacy Locking (F13 Lockset), With Closer
HW-3G Offices - Office Locking (F04 Lockset)
HW-4
Waiting, Conference, Staff Lounge - Classrom Locking (F05/F84 Lockset) with overhead stop
HW-4A Same as Above - Same as Above, with Auto Door Opener
HW-5B Rated, Storage - Storeroom Locking (F07 Lockset) with Closer
HW-5D Storage - Storeroom Locking (F07 Lockset) with Closer
HW-10B Double Doors - Storeroom Locking (F07 Lockset) with Closer, Overhead Stop
HW-SH-3
Secured Access Door - Storeroom Locking (F07 Lockset) with Closer, Overhead Stop, Alarm Contact, Card Reader
HW-SH-12
Stair to Exterior - Electrified Rim Exit (Panic) Device, w/ Closer. No Exterior Hardware
HW-E3
Exterior Roof Access - Storeroom Locking (F13 w/ Rigid outside lever) with closer, overhead stop, threshold, door position switch and power supply.
NOTE: See A-601 and Specification Section 08 71 00 - Door Hardware for more information.
3" = 1'-0"
INTERIOR WINDOW HEAD
3" = 1'-0"
INTERIOR WINDOW JAMB
3" = 1'-0"
INTERIOR WINDOW SILL
1/4" = 1'-0"
EXTERIOR GLAZING - W1/W1S
1/4" = 1'-0"
EXTERIOR GLAZING - W1F
1/4" = 1'-0"
INTERIOR GLAZING - E1
WINDOW SCHEDULE
Type Mark Count Length Height
E1 1 3' - 0" 4' - 0"
W1 17 4' - 0" 6' - 0"
W1F 1 16' - 6 1/2" 5' - 4"0 6
Revisions: Date: 10.07.2022 10.07.2022
Shannon Callout glass type IG#2
Shannon Callout glass type IG#2
Shannon Callout glass type MG#1
Shannon Callout glass type MG#1 at unrated doors
Line
Shannon Text Box
NOT USED
Shannon Line
Shannon Text Box
NOT USED
Shannon Callout glass type FR#2 at rated doors
Cloud
Shannon Text Box Addendum #1
Shannon Text Box Addendum #1
Shannon Text Box 02/08/2024
Shannon Cloud
Shannon Text Box Addendum #1
Shannon Cloud
Shannon Text Box Addendum #1
Shannon Image
Shannon Callout
EXAMPLE PHOTO EXISTING WINDOWS
Shannon Cloud
Shannon Text Box Addendum #1
Image
| 520-331_JACC_pkg1_Addendum1_summary |
| 08 80 00 Glazing |
| 08 80 00 - Glazing |
| A-601 |
| GI000 COVER SHEET |
| GI001 DRAWING INDEX |
| GI050 GENERAL NOTES |
| GI100 OVERALL SITEPLAN |
| GI102F LIFE SAFETY PLAN -AREA F |
| GI200 ICRA PLAN -GROUND FLOOR |
| GI201 ICRA PLAN -SECOND FLOOR |
| VF101 CIVIL SITE SURVEY |
| CD101 CIVIL DEMOLITION PLAN OVERALL |
| CD102 CIVIL DEMOLITION PLAN ENLARGED VIEWS AREAS A & B |
| CD103 CIVIL DEMOLITION PLAN ENLARGED VIEWS AREA C |
| CS101 CIVIL SITE PLAN OVERALL |
| CS102 CIVIL SITE PLAN ENLARGED VIEWS AREAS A & B |
| CS103 CIVIL SITE PLAN ENLARGED VIEW AREA C |
| CG101 CIVIL GRADING PLAN OVERALL |
| CG102 CIVIL GRADING PLAN ENLARGED VIEWS AREAS A & B |
| CG103 CIVIL GRADING PLAN ENLARGED VIEW AREA C |
| CG104 CIVIL EROSION CONTROL PLAN |
| CG501 CIVIL GRADING DETAIL SHEET 1 |
| CG502 CIVIL GRADING DETAIL SHEET 2 |
| CG503 CIVIL EROSION PROTECTION DETAIL SHEET |
| CU101 CIVIL UTILITY PLAN |
| CU102 CIVIL UTILITY PLAN ENLARGED VIEWS |
| CU103 CIVIL UTILITY PLAN ENLARGED VIEWS |
| CU501 CIVIL UTILITY DETAIL SHEET |
| CT101 CIVIL TRAFFIC SIGNAGE AND STRIPING PLAN |
| CT102 CIVIL TRAFFIC SIGNAGE AND STRIPING PLAN ENLARGED VIEWS AREAS A & B |
| CT103 CIVIL TRAFFIC SIGNAGE AND STRIPING PLAN ENLARGED VIEW AREA C |
| CT501 CIVIL SIGNAGE AND STRIPING DETAIL SHEET |
| S-001 GENERAL STRUCTURAL NOTES |
| S-002 GENERAL STRUCTURAL NOTES CONTINUED |
| S-003 SPECIAL INSPECTIONS |
| SD102 STRUCTURAL DEMOLITION PLAN -SECOND FLOOR |
| SD103 STRUCTURAL DEMOLITION PLAN -ROOF |
| S-101 STRUCTURAL FOUNDATION PLAN -OVERALL |
| S-101B2 STRUCTURAL FOUNDATION PLAN -AREA B2 -ENLARGED |
| S-102 STRUCTURAL SECOND FLOOR FRAMING PLAN -OVERALL |
| S-102F STRUCTURAL SECOND FLOOR FRAMING PLAN -AREA F -ENLARGED |
| S-103 STRUCTURAL THIRD FLOOR -MECHANICAL PENTHOUSE |
| S-104 STRUCTURAL ROOF FRAMING PLAN -OVERALL |
| S-104F STRUCTURAL ROOF FRAMING PLAN -AREA F -ENLARGED |
| S-201 BRACED FRAME ELEVATIONS |
| S-301 SECTIONS |
| S-401 ENLARGED PARTIAL FRAMING PLANS |
| S-501 TYPICAL DETAILS |
| S-502 TYPICAL DETAILS |
| S-503 TYPICAL DETAILS |
| S-504 TYPICAL DETAILS |
| S-505 TYPICAL DETAILS |
| S-510 FOUNDATION DETAILS |
| S-511 FOUNDATION DETAILS |
| S-520 FRAMING DETAILS |
| S-521 FRAMING DETAILS |
| S-522 FRAMING DETAILS |
| S-523 FRAMING DETAILS |
| S-524 FRAMING DETAILS |
| S-525 FRAMING DETAILS |
| S-601 GRAPHICAL COLUMN SCHEDULES |
| A-001 ARCHITECTURAL SYMBOLS, & GENERAL NOTES |
| A-003F ARCHITECTURAL ROOM PROGRAM PLAN -SECOND LEVEL -AREA F |
| AD101 ARCHITECTURAL DEMOLITION PLAN -FIRST FLOOR |
| AD102 ARCHITECTURAL DEMOLITION PLAN -SECOND FLOOR |
| A-101 ARCHITECTURAL GROUND FLOOR PLAN -OVERALL |
| A-101B ARCHITECTURAL GROUND FLOOR PLAN -AREA |
| A-102 ARCHITECTURAL SECOND FLOOR PLAN -OVERALL |
| A-102F ARCHITECTURAL SECOND FLOOR PLAN -AREA F |
| A-102F1 ARCHITECTURAL SECOND FLOOR DIMENSION PLAN -AREA F |
| A-103 ARCHITECTURAL THIRD FLOOR -MECHANICAL PENTHOUSES |
| A-104 ARCHITECTURAL ROOF PLAN -OVERALL |
| A-104F ARCHITECTURAL ROOF PLAN -AREA F |
| AC102F ARCHITECTURAL REFLECTED CEILING PLAN -SECOND FLOOR -AREA F |
| A-201 ARHICTECTURAL EXTERIOR ELEVATIONS -AREA F |
| A-251 ARCHITECTURAL SECTIONS -ATRIUM / CLINIC ENTRY |
| A-301 ARCHITECTURAL BUILDING SECTIONS -AREA F |
| A-351 ARCHITECTURAL SECTIONS -EXTERIOR WALL -AREA F |
| A-352 ARCHITECTURAL SECTIONS -EXTERIOR WALL -AREA F |
| A-401 ARCHITECTURAL ENLARGED VIEWS |
| A-402 ARCHITECTURAL ENLARGED VIEWS |
| A-403 ARCHITECTURAL ENLARGED VIEWS |
| A-404 ARCHITECTURAL ENLARGED VIEWS |
| A-405 ARCHITECTURAL ENLARGED VIEWS |
| A-406 ARCHITECTURAL ENLARGED VIEWS |
| A-407 ARCHITECTURAL ENLARGED VIEWS -REFLECTE CEILING PLANS |
| A-501 ARCHITECTURAL DETAILS -EXTERIOR |
| A-502 ARCHITECTURAL DETAILS -EXTERIOR |
| A-551 ARCHITECTURAL CASEWORK DETAILS |
| A-571 ARCHITECTURAL CEILING DETAILS |
| A-601 ARCHITECTURAL SCHEDULES |
| A-720 ARCHITECTURAL STANDARD PARTITION TYPES |
| A-722 ARCHITECTURAL PARTITION FRAMING DETAILS |
| A-730 ARCHITECTURAL TYPICAL MOUNTING HEIGHTS |
| IN001 INTERIOR NOTES AND FINISH LEGEND |
| IN102F INTERIOR FINISH PLANS -SECOND FLOOR -ARE F |
| IN501 INTERIOR FINISH DETAILS |
| IN502 INTERIOR WALL FINISH TYPES AND DETAILS |
| IN601 INTERIOR FINISH LEGEND AND ROOM FINISH SCHEDULE |
| IN901 INTERIOR 3D CONCEPT IMAGES |
| IF102F INTERIOR FURNITURE PLAN -SECOND FLOOR -AREA F |
| IF112F INTERIOR FURNITURE PLAN -SECOND FLOOR -AREA F |
| AW001 ARCHITECTURAL SIGNAGE ABBREVIATIONS,SYMBOLS, GENERAL NOTES AND SCHEDULE |
| AW102F ARCHITECTURAL SIGNAGE PLAN -SECOND FLOOR AREA F |
| Q-102F ARCHITECTURAL EQUIPMENT PLAN -SECOND FLOOR -AREA F |
| Q-401F ARCHITECTURAL EQUIPMENT PLAN -SECOND FLOOR -CORE LAB ENLARGED |
| Q-601 EQUIPMENT SCHEDULE |
| FX000 FIRE PROTECTION NOTES |
| FX001 FIRE PROTECTION NOTES |
| FX102 FIRE PROTECTION SECOND FLOOR PLAN -OVERALL |
| FX102F FIRE PROTECTION SECOND FLOOR PLAN -AREA F |
| FX501 DETAILS -FIRE PROTECTION |
| FA001 FIRE ALARM NOTES & LEGEND |
| FA102F FIRE ALARM SECOND FLOOR PLAN -AREA F |
| P-001 LEGEND -PLUMBING |
| PD101 PLUMBING EXISTING/DEMOLITION GROUND FLOOR PLAN -OVERALL |
| PD101F1 PLUMBING EXISTING/DEMOLITION GROUND FLOOR PLAN -AREA F -UNDER SLAB |
| PD101F2 PLUMBING EXISTING/DEMOLITION GROUND FLOOR PLAN -AREA F -DW,SAN,VENT |
| PD101F3 PLUMBING EXISTING/DEMOLITION GROUND FLOOR PLAN -AREA F -STORM |
| PD102 PLUMBING EXISTING/DEMOLITION SECOND FLOOR PLAN -OVERALL |
| PD102F PLUMBING EXISTING/DEMOLITION SECOND FLOOR PLAN -AREA F |
| PX101 PLUMBING GROUND FLOOR PLAN -OVERALL |
| PX101F1 PLUMBING GROUND FLOOR PLAN -AREA F -UNDER SLAB |
| PX101F2 PLUMBING GROUND FLOOR PLAN -AREA F -SAN,VENT, STORM |
| PX101F3 PLUMBING GROUND FLOOR PLAN -AREA F -DCW, MED GAS |
| PX102 PLUMBING SECOND FLOOR PLAN -OVERALL |
| PX102F1 PLUMBING SECOND FLOOR PLAN -AREA F -SAN VENT & STORM |
| PX102F2 PLUMBING SECOND FLOOR PLAN -AREA F -DW |
| PX102F3 PLUMBING SECOND FLOOR PLAN -AREA F -MED & LAB GAS |
| PX103F PLUMBING ROOF PLAN -AREA F |
| P-501 DETAILS -PLUMBING |
| P-502 SHEDULES & DETAILS -PLUMBING |
| P-902 SANITARY RISER DIAGRAM -AREA F |
| P-904 DOMESTIC RISER DIAGRAM -AREA F |
| P-906 MED GAS RISER DIAGRAM |
| M-001 LEGEND -HVAC |
| M-002 NOTES -HVAC |
| MD101 MECHANICAL DEMOLITION GROUND FLOOR PLA -OVERALL |