ATTACHMENT 5 - VAMH-618-17-127 CD SET_5.pdf
PDF 8 MB Posted
- Solicitation number
- 36E77620R0050
About this file
This notice provides details for an upcoming solicitation to renovate mental health wards at the Minneapolis VA Medical Center. The Department of Veterans Affairs intends to issue a request for proposal on or around February 4, 2020 for a firm-fixed-price design-build contract valued between $10-20 million. The contractor shall furnish all labor, materials and equipment for general construction, demolition, structural, civil, mechanical, plumbing and electrical work to renovate wards 1L, 1H and 1K. The period of performance is approximately 790 calendar days from notice to proceed. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and use NAICS code 236220 with a size standard of $39.5 million. All questions must be submitted in writing by the specified date.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
70.VAV.08.1H114A
70.VAV.08.1K118
70.VAV.08.1K114B
70.VAV.08.1K119
70.VAV.08.1K120
70.VAV.08.1K116
70.VAV.08.1K117
70.VAV.08.1K115
70.VAV.08.C171
70.VAV.08.1K122
70.VAV.08.C169
70.VAV.08.1K123
70.VAV.08.1K125
70.VAV.08.1K113
70.VAV.08.1K114
70.VAV.08.1K112
70.VAV.08.1K111
70.VAV.08.1K110
70.VAV.08.1K108
70.VAV.08.1K107
70.VAV.08.1K106
70.VAV.08.1K105
70.VAV.08.1K104
70.VAV.08.1K103
70.VAV.08.1K102
70.VAV.08.1K101
70.VAV.08.1K124
70.VAV.08.1K126
70.AHU.08
MP01
EXERCISE
1K-119
CLN. LIN.
1K-121
STOR.
1K-120
THEATER
1K-118
STOR.
1K-125
SENS
1K-124
HSKP
1K-127
ROUND
1K-123
ROUND
1K-126
SOIL
1K-122
TLT.
1K-106A
TLT.
1K-116A
TLT.
1K-114A
TLT.
1K-115A
TLT.
1K-113A
TLT.
1K-112A
TLT.
1K-104A
TLT.
1K-105A
TLT.
1K-102A
TLT.
1K-103A
TLT.
1K-108A
TLT.
1K-107A
PT. STOR.
1H-114
DOUBLE
1K-115
DOUBLE
1K-114
DOUBLE
1K-113
DOUBLE
1K-117
CORR 1
C1-71
CORR 1
C1-71A
CORR 1
C1-69
SINGLE
1K-105
BARIATRIC SINGLE
1K-107
SINGLE
1K-106
SINGLE
1K-104
SINGLE
1K-103
SINGLE
1K-102
DOUBLE
1K-112
BARIATRIC SINGLE
1K-108
TLT.
1K-117A
70.VAV.08.1H114
70.VAV.08.1H114
PT. STOR.
1H-114
PT. STOR.
1H-114
PT. STOR.
1H-114
3/4" HWR
3/4" HWS
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
3/4" HWS
3/4" HWR
3/4" HWR
3/4" HWS
3/4" HWS
3/4" HWR
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
1. CONNECT VAV INLET DUCTWORK BACK AT EXISTING TAPS IN MAIN WHERE
APPLICABLE. CAP ALL OTHER UNUSED TAPS.
2. ROUTE AND CONNECT HEATING WATER PIPING BACK TO EXISTING MAIN.
3. PROVIDE VOLUME DAMPERS AT ALL RETURN AND EXHAUST DUCT TAKE-OFFS.
4. PROVIDE VOLUME DAMPERS AT ALL SUPPLY BRANCH TAKE-OFFS AFTER THE
VAV BOXES.
5. REBALANCE THE ENTIRE AIR AND HYDRONIC SYSTEMS UPON COMPLETION OF
WORK. THIS INCLUDES AREAS OUTSIDE OF THE REMODELED AREAS THAT HAVE
BEEN AFFECTED BY THE REMODELING. PROVIDE ADDITIONAL VOLUME DAMPERS
AS REQUIRED TO BALANCE THE ENTIRE SYSTEM PROPERLY.
6. ALL HYDRONIC SUPPLY AND RETURN PIPE RUN-OUTS TO TERMINAL UNITS SHALL
BE 3/4" SIZE UNLESS NOTED OTHERWISE.
7. ALL DUCTWORK, VAV BOXES, AND HYDRONIC PIPING SHOWN ON THESE PLANS
SHALL BE INSTALLED IN THE INTERSTITIAL SPACE ABOVE THIS FLOOR. DUCT
DROPS TO GRILLES, REGISTERS, AND DIFFUSERS WILL OCCUR THROUGH THE
INTERSTITIAL DECK. SEE PENETRATION DETAILS ON SHEET MH-501.
8. ALL ROUND DUCT RUNOUTS FROM DUCT MAINS TO VAV BOXES SHALL BE THE
SAME SIZE AS THE BOX INLET UNLESS NOTED OTHERWISE.
9. ALL ROUND DUCT RUNOUTS FROM VAV BOX DISCHARGE DUCT TO SUPPLY
DIFFUSERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED
OTHERWISE.
MECHANICAL GENERAL NOTES
KEYNOTE LEGEND
KEY DESCRIPTION
MP01 RECONNECT EXISTING PIPING TO NEW AHU.
SCALE: 1/8" = 1'-0"1 LEVEL 1 HYDRONIC PIPING PLAN, AREA K, PHASE 2
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger Date: ___________ License Number: 4871001/07/2021
CME
70.VAV.08.1H112
70.VAV.08.1H110
70.VAV.08.1H109
70.VAV.08.1H110A
70.VAV.08.1H107
70.VAV.08.1H104
70.VAV.08.1H105
70.VAV.08.1H108
70.VAV.08.C166
70.VAV.08.1H103
70.VAV.08.C165
70.VAV.08.1H113
70.VAV.08.1H111 CORR 2
C1-67
PT. STOR.
1H-114
MEDS.
1H-112
CORR 2
C1-67
RX OFF.
1H-113
70.VAV.08.1H114
NOURISHMENT
1H-109
WORK ROOM
1H-110A
ASST. RN.
1H-107RESIDENTS TM. RM.
1H-108
PT. STOR.
1H-114
PT. STOR.
1H-114
ELEVATOR LOBBY
C1-314
M-8
STAFF BREAK
1H-104
STAFF LKR/TLT
1H-103
PT. STOR.
1H-114
NURSE STATION-1
1H-110-1
3/4" HWR
3/4" HWS
3/4" HWR
3/4" HWS
1. CONNECT VAV INLET DUCTWORK BACK AT EXISTING TAPS IN MAIN WHERE
APPLICABLE. CAP ALL OTHER UNUSED TAPS.
2. ROUTE AND CONNECT HEATING WATER PIPING BACK TO EXISTING MAIN.
3. PROVIDE VOLUME DAMPERS AT ALL RETURN AND EXHAUST DUCT TAKE-OFFS.
4. PROVIDE VOLUME DAMPERS AT ALL SUPPLY BRANCH TAKE-OFFS AFTER THE
VAV BOXES.
5. REBALANCE THE ENTIRE AIR AND HYDRONIC SYSTEMS UPON COMPLETION OF
WORK. THIS INCLUDES AREAS OUTSIDE OF THE REMODELED AREAS THAT HAVE
BEEN AFFECTED BY THE REMODELING. PROVIDE ADDITIONAL VOLUME DAMPERS
AS REQUIRED TO BALANCE THE ENTIRE SYSTEM PROPERLY.
6. ALL HYDRONIC SUPPLY AND RETURN PIPE RUN-OUTS TO TERMINAL UNITS SHALL
BE 3/4" SIZE UNLESS NOTED OTHERWISE.
7. ALL DUCTWORK, VAV BOXES, AND HYDRONIC PIPING SHOWN ON THESE PLANS
SHALL BE INSTALLED IN THE INTERSTITIAL SPACE ABOVE THIS FLOOR. DUCT
DROPS TO GRILLES, REGISTERS, AND DIFFUSERS WILL OCCUR THROUGH THE
INTERSTITIAL DECK. SEE PENETRATION DETAILS ON SHEET MH-501.
8. ALL ROUND DUCT RUNOUTS FROM DUCT MAINS TO VAV BOXES SHALL BE THE
SAME SIZE AS THE BOX INLET UNLESS NOTED OTHERWISE.
9. ALL ROUND DUCT RUNOUTS FROM VAV BOX DISCHARGE DUCT TO SUPPLY
DIFFUSERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED
OTHERWISE.
MECHANICAL GENERAL NOTES
SCALE: 1/8" = 1'-0"1 LEVEL 1 HYDRONIC PIPING PLAN, AREA H, PHASE 2 Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
70.VAV.07.1L102A
70.VAV.07.1L100
70.VAV.07.1L105
70.VAV.07.1L104
70.VAV.07.1L106
70.VAV.07.1L110
70.VAV.07.C156A
70.VAV.07.1L109
70.VAV.07.1L107 70.VAV.07.C160
70.VAV.07.1L113
70.VAV.07.1L114B
70.VAV.07.1L112B
70.VAV.07.1L112
70.VAV.07.1L114
70.VAV.07.1L116
70.VAV.07.C156B
70.VAV.07.C159
70.VAV.07.1L12670.VAV.07.1L12570.VAV.07.1L12470.VAV.07.1L12370.VAV.07.1L122
70.VAV.07.1L121
70.VAV.07.1L131
70.VAV.07.C162
70.VAV.07.1L130
70.VAV.07.1L120
70.VAV.07.1L127 70.VAV.07.1L128
70.VAV.07.1L115
70.VAV.07.C157
70.VAV.08.1H110B
70.VAV.07.1L129
CORR 1
C1-62
MSA-2
1H-110B-2
CORR 2
C1-61
CORR 2
C1-56
CORR 2
C1-64
DINING
1L-130
CORR 1
1L-100
FAMILY ROOM
1L-105
FAM
1L-107
INTERVIEW
1L-102
EXAM
1L-104
LAUNDRY
1L-106 DAY ROOM
1L-110
REC THERAPY
1L-112
HIGH ACUITY RN
STATION
1L-120
CLN. LIN.
1L-113
TLT.
1L-113A
TLT.
1L-128A
SECL
1L-128B
ANTE RM.
1L-128
SECL
1L-128C
SINGLE
1L-123
SINGLE
1L-124
TLT.
1L-123A
TLT.
1L-122A
SINGLE
1L-122
SINGLE
1L-121
TLT.
1L-121A
CORR 1
C1-59
TLT.
1L-124A
TLT.
1L-125A
SINGLE
1L-124
SINGLE
1L-125
SINGLE
1L-126
TLT.
1L-126A
CORR 2
C1-57
STOR.
1L-140
SENS
1L-129
SOCIAL WRKR
OFFICE
1L-115
SOIL
1L-127
RN-MGR.
1L-109
CORR 1
C1-60
OCC. THER. OFFICE
1L-114B
REC. THER. OFFICE
1L-112B
OCC THERAPY
1L-114
GROUP THERAPY
1L-116
3/4" HWR3/4" HWS
1. CONNECT VAV INLET DUCTWORK BACK AT EXISTING TAPS IN MAIN WHERE
APPLICABLE. CAP ALL OTHER UNUSED TAPS.
2. ROUTE AND CONNECT HEATING WATER PIPING BACK TO EXISTING MAIN.
3. PROVIDE VOLUME DAMPERS AT ALL RETURN AND EXHAUST DUCT TAKE-OFFS.
4. PROVIDE VOLUME DAMPERS AT ALL SUPPLY BRANCH TAKE-OFFS AFTER THE
VAV BOXES.
5. REBALANCE THE ENTIRE AIR AND HYDRONIC SYSTEMS UPON COMPLETION OF
WORK. THIS INCLUDES AREAS OUTSIDE OF THE REMODELED AREAS THAT HAVE
BEEN AFFECTED BY THE REMODELING. PROVIDE ADDITIONAL VOLUME DAMPERS
AS REQUIRED TO BALANCE THE ENTIRE SYSTEM PROPERLY.
6. ALL HYDRONIC SUPPLY AND RETURN PIPE RUN-OUTS TO TERMINAL UNITS SHALL
BE 3/4" SIZE UNLESS NOTED OTHERWISE.
7. ALL DUCTWORK, VAV BOXES, AND HYDRONIC PIPING SHOWN ON THESE PLANS
SHALL BE INSTALLED IN THE INTERSTITIAL SPACE ABOVE THIS FLOOR. DUCT
DROPS TO GRILLES, REGISTERS, AND DIFFUSERS WILL OCCUR THROUGH THE
INTERSTITIAL DECK. SEE PENETRATION DETAILS ON SHEET MH-501.
8. ALL ROUND DUCT RUNOUTS FROM DUCT MAINS TO VAV BOXES SHALL BE THE
SAME SIZE AS THE BOX INLET UNLESS NOTED OTHERWISE.
9. ALL ROUND DUCT RUNOUTS FROM VAV BOX DISCHARGE DUCT TO SUPPLY
DIFFUSERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK UNLESS NOTED
OTHERWISE.
MECHANICAL GENERAL NOTES
SCALE: 1/8" = 1'-0"1 LEVEL 1 HYDRONIC PIPING PLAN, AREA L, PHASE 3 Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
70.VAV.08.1K110
70.AHU.08
MH01
MH02 MH03
MH04
102"x40 1/2" S/A
MH01
MH01
MH08
MH07
MH13MH13
SEE DETAIL 6/MH502
FOR CONTINUATION, SEE SHEET MH102-P2 FOR CONTINUATION, SEE SHEET MH102-P2
EXISTING 32"ROUND
EXISTING 20"ROUND
EXISTING 20"ROUND
EXISTING 60X24
3" STM-HP
3" CHWR
3" CHWS
EXISTING 4"CHWS
EXISTING 4"CHWR
EXISTING 3" 30# HPS
EXISTING SMOKE
CONTROL DMPR
EXISTING AFMS
MH14
MH14
SA-SIL-1
SA-SIL-2
RA-SIL-1
MH15
MH15
MH15
70.AHU.08
40 1/2"x102" S/A MH08
MH01
MH13
70.AHU.08
MH07
SCALE: 1/4" = 1'-0"1 ENLARGED PLAN - MECHANICAL ROOM 1H-110
KEYNOTE LEGEND
KEY DESCRIPTION
MH01 RECONNECT EXISTING DUCTWORK TO NEW AHU PLENUM DISCHARGE DUCT..VERIFY
SIZES AND LOCATIONS OF ALL EXISTING SUPPLY DUCTS.
MH02 RE-RE-ROUTE EXISTING STEAM PIPING AS REQUIRED AND CONNECT NEW PIPING TO
NEW 70.AHU.08
MH03 RE-ROUTE EXISTING CHILLED WATER PIPING AS REQUIRED AND CONNECT NEW
PIPING TO NEW 70.AHU.08
MH04 NEW REPLACEMENT AIR HANDLING UNIT IS A PART OF THIS PROJECT. PROVIDE
TEMPORARY COOLING AND HEATING TO ANY SPACES THAT ARE NOT IN THE LIMITS
OF THE CONSTRUCTION WHILE THE NEW UNIT IS BEING INSTALLED.
MH07 REPLACE EXISTING 70.RF.08 FAN MOTOR WITH WITH NEW FAN MOTOR WITH
VFD.VERIFY EXISTING MOTOR SIZE AND REPLACE WITH SAME MOTOR SIZE.
REBALANCE FAN AFTER ALL WORK IS COMPLETE.
MH08 NEW INSULATED DISCHARGE DUCT. SUPPORT DUCT OFF FLOOR. ROUTE EXISTING
SUPPLY DUCTS TO NEW DISCHARGE DUCT.
MH13 CONNECT EXISTING RETURN AND OUTSIDE AIR DUCTWORK TO NEW AHU. REVISE
EXISTING DUCTWORK AS NECESSARY TO MAKE NEW CONNECTIONS.
MH14 REMOVE EXISTING RELIEF AIR LOUVER, PLENUM AND ALL CONNECTING DUCTWORK
TO FACILITATE THE REMOVAL OF THE EXISTING AHU COMPONENTS AND THE
INSTALLATION OF THE NEW AHU SECTIONS. RECONNECT THE LOUVER AND ALL THE
ASSOCIATED DUCTWORK WHEN THE NEW AHU INSTALLATION IS COMPLETED.
MH15 REMOVE EXISTING PIECE OF DUCTWORK AND INSTALL NEW SOUND ATTENUATOR.
SCALE: 1/4" = 1'-0"2 WEST TO EAST SECTION, FACING NORTH - MECHANICAL ROOM 1H-110
SCALE: 1/4" = 1'-0"3 NORTH TO SOUTH SECTION, FACING EAST - MECHANICAL ROOM 1H-110
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
NOTE: NO FLEX DUCT
ALLOWED IN INTERSTITIAL
SPACE.
TRANSFER GRILLE
TRANSFER GRILLE
MANUAL BALANCING
DAMPER
NOT TO SCALEMH-501
1 FLEXIBLE DUCT CONNECTION
NOT TO SCALEMH-501
2 INTERSTITIAL DECK REPAIR DETAIL
NOT TO SCALEMH-501
3 PIPE HANGERS
NOT TO SCALEMH-501
4 WATER COIL PIPING DETAIL (2-WAY VALVE)
NOT TO SCALEMH-501
5 LINEAR SLOT DIFFUSER DETAIL
NOT TO SCALEMH-501
6 RETURN OR EXHAUST AIR PLENUM BOX WITH FLEXIBLE CONNECTION DETAIL
NOT TO SCALEMH-501
7 TRANSFER DUCT DETAIL
NOT TO SCALEMH-501
8 DUCTWORK HANGING DETAIL
NOT TO SCALEMH-501
9 DUCT SUPPORT DETAIL
NOT TO SCALEMH-501
10 VAV BOX DETAIL
NOT TO SCALEMH-501
11 VAV WITH RE-HEAT COIL DETAIL
NOT TO SCALEMH-501
12 RADIANT PANEL PIPING DETAIL
NOT TO SCALEMH-501
13 RADIATION DETAIL
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
PRESSURE AND
TEMPERATURE GAUGE
CONNECTOR PLUGS
CHWR
CHWS
DRAIN VALVE
(TYPICAL EACH COIL)
UNION
COOLING COIL
MANUAL AIR VENT
(TYPICAL EACH COIL)
THERMOMETER
FLOW MEASURING
AND BALANCING DEVICE
SHUT-OFF VALVE
STRAINER
M
AIR FLOW
CONTROL VALVE
STEAM TRAP
DIRT POCKET CAP
THREADED
FLANGED
FLANGED
LINE SIZE2" & LESS
2.5"-4"
6" & UP 4"
LINE SIZE
STEAM
SIZE
DRIP LEG
SIZE A
2" & LESS-UNIONS
2.5" & LARGER-FLANGED
2.5" & LARGER-FLANGED
DIRT POCKET
CAP
TRAP
CONNS.
CHECK VALVE
UNION
COND
SHUT-OFF
VALVE
STM
STRAINER W/
BLOW DOWN
VALVE
MI
N.6"
LAST CONNECTION
DRIP LEG SIZE A
MI
N.
TRAP MONITOR
TEST TEE
NOTE: UNIT SHALL BE SHIPPED IN SECTIONS
THAT WILL FIT THROUGH EXISTING OUTSIDE
AIR LOUVER. UNIT SHALL THEN BE ASSEMBLED
ON SITE IN THE EXISTING MECHANICAL ROOM.
PRIMING FILLER CAP
NUMBER OF MANIFOLDS SHALL
BE PER REQUIREMENTS FOR
DUSPERSION DISTANCE
HEADER OVERFLOW TRAP
OPPOSITE END CONNECTION
SHOWN ONLY FOR DIAGRAM
CONFIRM TIE-IN POINTS
ALL REDUCERS TO BE ECCENTRIC
TEMPERATURE FLIP
ON/OFF SOLENOID WIRED
TO HEADER FLOAT SWITCH
STEAM/CONDENSATE HEADER
MOUNT HEADER AS
HIGH AS POSSIBLE
MODULATING
STEAM VALVE
ISOLATION VALVE
30 LB MEDIUM
PRESSURE
STEAM
STRAINER
WITH BELOW
DOWN VALVE
TO END OF MAIN DRIP TRAP
ASSEMBLY WITH IMPULSE TYPE
STEAM TRAP AND SARCO
MONITOR INTEGRATED INTO
BUILDING AUTOMATION. REFER
TO DETAIL QW/M52 xxx
SARCO TRAP MONITOR
TIED INTO BUILDING
AUTOMATION
FLOAT AND THERMOSTATIC STEAM
TRAP WITH MONITOR TO BUILDING
AUTOMATION MOUNTED JUST ABOVE
FLOOR, REFER TO DRAWING NOTES
TEST TEE VALVE (TYP.)
AHU WALL
NOT TO SCALEMH-502
CHILLED WATER COIL PIPING DETAIL
W/2-WAY VALVE - MULTIPLE
NOT TO SCALEMH-502
4 END OF MAIN STEAM DRIP DETAIL - PRESSURE GREATER THAN 15 PSI
NOT TO SCALEMH-502
5 MULTIPLE COIL DRAIN PAN DETAIL
NOT TO SCALEMH-502
6 AIR HANDLING UNIT 70.08 DETAIL
NOT TO SCALEMH-502
8 FLOAT AND THERMOSTATIC STEAM TRAP ASSEMBLY
NOT TO SCALEMH-502
7 INVERTED BUCKET STEAM TRAP ASSEMBLY
NOT TO SCALEMH-502
2 STEAM HUMIDIFIER DETAIL
NOT TO SCALEMH-502
3 INTEGRAL FACE AND BYPASS HEATING COIL DETAIL
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
ID DESCRIPTION MANUFACTURER MODEL SYSTEM
FACE
SIZE
BLADE DESIGN INSTALLATION
SPECIFICATION NOTESSPACING
DEFLECT
ION
ANGLE
ORIENTATION BORDER TYPESINGLE
EG1 MAXIMUM SECURITY SUICIDE DETERRENT GRILLE Titus SG-SD E/A 1/2" 0.0° GRID PERFORATED GRILLE WITH 3/16" HOLES, ALL WELDED CONSTRUCTION, COMPLIES WITH NIC GUIDELINES FOR SUICIDE PREVENTION RG1 MAXIMUM SECURITY SUICIDE DETERRENT GRILLE Titus SG-SD R/A 1/2" 0.0° GRID PERFORATED GRILLE WITH 3/16" HOLES, ALL WELDED CONSTRUCTION, COMPLIES WITH NIC GUIDELINES FOR SUICIDE PREVENTION RG2 SECURITY SUICIDE DETERRENT GRILLE Titus 8F 24x24 1/2" 0.0° GRID TYPE 3 (LAY-IN) PERFORATED GRILLE WITH 3/16" HOLES, PROVIDE HOLD DOWN CLIPS TO ATTACH TO T-BAR GRID.
SD1 PERFORATED DIFFUSER WITH DEFLECTORS Titus PSS S/A 24x24 PERFORATED DIFFUSER WITH STAR PATTERN DEFLECTOR TG1 MAXIMUM SECURITY SUICIDE DETERRENT GRILLE Titus SG-SD T/A --- 1/2" 0.0° GRID TYPE 1 (SURFACE) PERFORATED GRILLE WITH 3/16" HOLES, ALL WELDED CONSTRUCTION, COMPLIES WITH NIC GUIDELINES FOR SUICIDE PREVENTION
ID MANUFACTURER
MODEL
NO.
NECK
SIZE TYPE
PRIMARY AIRFLOW
EXTERIOR
ZONE
HEATING COIL HEATING PLANT
UNIT
WEIGHT REMARKSMAX MIN % DESCRIPTION CAP
AIRSIDE WATERSIDE GLYCOL
DESIGN
FLOW EAT(db) LAT(db) ROWS FPI FLOW EWT LWT TYPE %
70.VAV.07.1L100 TITUS DESV 5" SINGLE DUCT 160 CFM 100 No Heating Water Coil 4313 Btu/h 160 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L102A TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L104 TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L105 TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L106 TITUS DESV 4" SINGLE DUCT 95 CFM 100 No Heating Water Coil 2561 Btu/h 95 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L107 TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L109 TITUS DESV 4" SINGLE DUCT 145 CFM 100 No Heating Water Coil 3909 Btu/h 145 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L110 TITUS DESV 7" SINGLE DUCT 540 CFM 100 No Heating Water Coil 14558 Btu/h 540 CFM 55.0 °F 80.0 °F 1 10 1.6 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.07.1L112 TITUS DESV 6" SINGLE DUCT 360 CFM 100 No Heating Water Coil 9705 Btu/h 360 CFM 55.0 °F 80.0 °F 1 10 1.1 GPM 180 °F 160 °F PG 30 37 lb
70.VAV.07.1L112B TITUS DESV 4" SINGLE DUCT 85 CFM 100 No Heating Water Coil 2292 Btu/h 85 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L113 TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L114 TITUS DESV 6" SINGLE DUCT 280 CFM 100 No Heating Water Coil 7549 Btu/h 280 CFM 55.0 °F 80.0 °F 1 10 0.9 GPM 180 °F 160 °F PG 30 37 lb
70.VAV.07.1L114B TITUS DESV 4" SINGLE DUCT 85 CFM 100 No Heating Water Coil 2292 Btu/h 85 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L115 TITUS DESV 5" SINGLE DUCT 200 CFM 100 No Heating Water Coil 5392 Btu/h 200 CFM 55.0 °F 80.0 °F 1 10 0.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L116 TITUS DESV 6" SINGLE DUCT 300 CFM 100 No Heating Water Coil 8088 Btu/h 300 CFM 55.0 °F 80.0 °F 1 10 0.9 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L120 TITUS DESV 4" SINGLE DUCT 90 CFM 100 No Heating Water Coil 2426 Btu/h 90 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L121 TITUS DESV 6" SINGLE DUCT 330 CFM 40 Yes Heating Water Coil 14235 Btu/h 330 CFM 55.0 °F 95.0 °F 1 10 1.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L122 TITUS DESV 5" SINGLE DUCT 240 CFM 80 Yes Heating Water Coil 10352 Btu/h 240 CFM 55.0 °F 95.0 °F 1 10 1.1 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L123 TITUS DESV 6" SINGLE DUCT 350 CFM 60 Yes Heating Water Coil 15097 Btu/h 350 CFM 55.0 °F 95.0 °F 1 10 1.7 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L124 TITUS DESV 5" SINGLE DUCT 240 CFM 80 Yes Heating Water Coil 10352 Btu/h 240 CFM 55.0 °F 95.0 °F 1 10 1.1 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L125 TITUS DESV 6" SINGLE DUCT 260 CFM 30 Yes Heating Water Coil 11215 Btu/h 260 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L126 TITUS DESV 5" SINGLE DUCT 240 CFM 30 Yes Heating Water Coil 10352 Btu/h 240 CFM 55.0 °F 95.0 °F 1 10 1.1 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L127 TITUS DESV 4" SINGLE DUCT 90 CFM 100 No Heating Water Coil 2426 Btu/h 90 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L128 TITUS DESV 6" SINGLE DUCT 295 CFM 100 No Heating Water Coil 7953 Btu/h 295 CFM 55.0 °F 80.0 °F 1 10 0.9 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L129 TITUS DESV 4" SINGLE DUCT 100 CFM 100 No Heating Water Coil 2696 Btu/h 100 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L130 TITUS DESV 12" SINGLE DUCT 1300 CFM 30 Yes Heating Water Coil 56075 Btu/h 1300 CFM 55.0 °F 95.0 °F 1 10 6.0 GPM 180 °F 160 °F PG 30 53 lb 70.VAV.07.1L131 TITUS DESV 6" SINGLE DUCT 390 CFM 40 Yes Heating Water Coil 16823 Btu/h 390 CFM 55.0 °F 95.0 °F 1 10 1.8 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.1L144 TITUS DESV 7" SINGLE DUCT 450 CFM 100 No Heating Water Coil 12132 Btu/h 450 CFM 55.0 °F 80.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.07.C156A TITUS DESV 6" SINGLE DUCT 350 CFM 100 Yes Heating Water Coil 15097 Btu/h 350 CFM 55.0 °F 95.0 °F 1 10 1.7 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.C156B TITUS DESV 6" SINGLE DUCT 350 CFM 100 Yes Heating Water Coil 15097 Btu/h 350 CFM 55.0 °F 95.0 °F 1 10 1.7 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.C157 TITUS DESV 5" SINGLE DUCT 185 CFM 100 No Heating Water Coil 4987 Btu/h 185 CFM 55.0 °F 80.0 °F 1 10 0.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.C159 TITUS DESV 7" SINGLE DUCT 465 CFM 100 No Heating Water Coil 12536 Btu/h 465 CFM 55.0 °F 80.0 °F 1 10 1.4 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.07.C160 TITUS DESV 7" SINGLE DUCT 410 CFM 100 No Heating Water Coil 11053 Btu/h 410 CFM 55.0 °F 80.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.07.C162 TITUS DESV 9" SINGLE DUCT 810 CFM 100 No Heating Water Coil 21837 Btu/h 810 CFM 55.0 °F 80.0 °F 1 10 2.4 GPM 180 °F 160 °F PG 30 46 lb 70.VAV.07.C163 TITUS DESV 5" SINGLE DUCT 240 CFM 100 No Heating Water Coil 6470 Btu/h 240 CFM 55.0 °F 80.0 °F 1 10 0.7 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.07.L161D TITUS DESV 5" SINGLE DUCT 200 CFM 100 No Heating Water Coil 5392 Btu/h 200 CFM 55.0 °F 80.0 °F 1 10 0.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H103 TITUS DESV 7" SINGLE DUCT 420 CFM 100 No Heating Water Coil 11323 Btu/h 420 CFM 55.0 °F 80.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.08.1H104 TITUS DESV 5" SINGLE DUCT 205 CFM 100 No Heating Water Coil 5527 Btu/h 205 CFM 55.0 °F 80.0 °F 1 10 0.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H105 TITUS DESV 6" SINGLE DUCT 385 CFM 100 No Heating Water Coil 10379 Btu/h 385 CFM 55.0 °F 80.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H107 TITUS DESV 4" SINGLE DUCT 130 CFM 100 No Heating Water Coil 3505 Btu/h 130 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H108 TITUS DESV 5" SINGLE DUCT 190 CFM 100 No Heating Water Coil 5122 Btu/h 190 CFM 55.0 °F 80.0 °F 1 10 0.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H109 TITUS DESV 4" SINGLE DUCT 90 CFM 100 No Heating Water Coil 2426 Btu/h 90 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H110 TITUS DESV 7" SINGLE DUCT 425 CFM 100 No Heating Water Coil 11458 Btu/h 425 CFM 55.0 °F 80.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 39 lb
70.VAV.08.1H110A TITUS DESV 7" SINGLE DUCT 445 CFM 100 No Heating Water Coil 11997 Btu/h 445 CFM 55.0 °F 80.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.08.1H110B TITUS DESV 5" SINGLE DUCT 160 CFM 100 No Heating Water Coil 4313 Btu/h 160 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H111 TITUS DESV 6" SINGLE DUCT 305 CFM 100 No Heating Water Coil 8223 Btu/h 305 CFM 55.0 °F 80.0 °F 1 10 0.9 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H112 TITUS DESV 4" SINGLE DUCT 140 CFM 100 No Heating Water Coil 3774 Btu/h 140 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H113 TITUS DESV 4" SINGLE DUCT 65 CFM 100 No Heating Water Coil 1752 Btu/h 65 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1H114 TITUS DESV 4" SINGLE DUCT 95 CFM 100 No Heating Water Coil 2561 Btu/h 95 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb
70.VAV.08.1H114A TITUS DESV 12" SINGLE DUCT 1565 CFM 50 Yes Heating Water Coil 67506 Btu/h 1565 CFM 55.0 °F 95.0 °F 1 10 7.2 GPM 180 °F 160 °F PG 30 53 lb 70.VAV.08.1K101 TITUS DESV 5" SINGLE DUCT 190 CFM 90 Yes Heating Water Coil 8196 Btu/h 190 CFM 55.0 °F 95.0 °F 1 10 0.9 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K102 TITUS DESV 6" SINGLE DUCT 280 CFM 70 Yes Heating Water Coil 12078 Btu/h 280 CFM 55.0 °F 95.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K103 TITUS DESV 5" SINGLE DUCT 205 CFM 90 Yes Heating Water Coil 8843 Btu/h 205 CFM 55.0 °F 95.0 °F 1 10 1.0 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K104 TITUS DESV 6" SINGLE DUCT 255 CFM 70 Yes Heating Water Coil 10999 Btu/h 255 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K105 TITUS DESV 5" SINGLE DUCT 235 CFM 80 Yes Heating Water Coil 10137 Btu/h 235 CFM 55.0 °F 95.0 °F 1 10 1.1 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K106 TITUS DESV 5" SINGLE DUCT 205 CFM 90 Yes Heating Water Coil 8843 Btu/h 205 CFM 55.0 °F 95.0 °F 1 10 1.0 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K107 TITUS DESV 6" SINGLE DUCT 310 CFM 70 Yes Heating Water Coil 13372 Btu/h 310 CFM 55.0 °F 95.0 °F 1 10 1.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K108 TITUS DESV 5" SINGLE DUCT 220 CFM 100 Yes Heating Water Coil 9490 Btu/h 220 CFM 55.0 °F 95.0 °F 1 10 1.1 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K110 TITUS DESV 6" SINGLE DUCT 260 CFM 100 Yes Heating Water Coil 11215 Btu/h 260 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K111 TITUS DESV 5" SINGLE DUCT 250 CFM 100 Yes Heating Water Coil 10784 Btu/h 250 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K112 TITUS DESV 5" SINGLE DUCT 250 CFM 100 Yes Heating Water Coil 10784 Btu/h 250 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K113 TITUS DESV 6" SINGLE DUCT 265 CFM 100 Yes Heating Water Coil 11431 Btu/h 265 CFM 55.0 °F 95.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K114 TITUS DESV 5" SINGLE DUCT 250 CFM 100 Yes Heating Water Coil 10784 Btu/h 250 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb
70.VAV.08.1K114B TITUS DESV 7" SINGLE DUCT 495 CFM 100 No Heating Water Coil 13345 Btu/h 495 CFM 55.0 °F 80.0 °F 1 10 1.5 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.08.1K115 TITUS DESV 6" SINGLE DUCT 400 CFM 80 Yes Heating Water Coil 17254 Btu/h 400 CFM 55.0 °F 95.0 °F 1 10 1.9 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K116 TITUS DESV 6" SINGLE DUCT 300 CFM 100 Yes Heating Water Coil 12940 Btu/h 300 CFM 55.0 °F 95.0 °F 1 10 1.4 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K117 TITUS DESV 5" SINGLE DUCT 250 CFM 100 Yes Heating Water Coil 10784 Btu/h 250 CFM 55.0 °F 95.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K118 TITUS DESV 7" SINGLE DUCT 440 CFM 100 No Heating Water Coil 11862 Btu/h 440 CFM 55.0 °F 80.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.08.1K119 TITUS DESV 6" SINGLE DUCT 330 CFM 100 No Heating Water Coil 8897 Btu/h 330 CFM 55.0 °F 80.0 °F 1 10 1.0 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K120 TITUS DESV 4" SINGLE DUCT 50 CFM 100 No Heating Water Coil 1348 Btu/h 50 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K122 TITUS DESV 5" SINGLE DUCT 245 CFM 100 No Heating Water Coil 6605 Btu/h 245 CFM 55.0 °F 80.0 °F 1 10 0.8 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K123 TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K124 TITUS DESV 5" SINGLE DUCT 180 CFM 100 No Heating Water Coil 4853 Btu/h 180 CFM 55.0 °F 80.0 °F 1 10 0.6 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K125 TITUS DESV 4" SINGLE DUCT 40 CFM 100 No Heating Water Coil 1078 Btu/h 40 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.1K126 TITUS DESV 4" SINGLE DUCT 110 CFM 100 No Heating Water Coil 2966 Btu/h 110 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.C165 TITUS DESV 7" SINGLE DUCT 425 CFM 100 No Heating Water Coil 11458 Btu/h 425 CFM 55.0 °F 80.0 °F 1 10 1.3 GPM 180 °F 160 °F PG 30 39 lb 70.VAV.08.C166 TITUS DESV 4" SINGLE DUCT 145 CFM 100 No Heating Water Coil 3909 Btu/h 145 CFM 55.0 °F 80.0 °F 1 10 0.5 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.C169 TITUS DESV 6" SINGLE DUCT 330 CFM 100 No Heating Water Coil 8897 Btu/h 330 CFM 55.0 °F 80.0 °F 1 10 1.0 GPM 180 °F 160 °F PG 30 37 lb 70.VAV.08.C171 TITUS DESV 7" SINGLE DUCT 410 CFM 100 No Heating Water Coil 11053 Btu/h 410 CFM 55.0 °F 80.0 °F 1 10 1.2 GPM 180 °F 160 °F PG 30 39 lb
ID SERVES MANUFACTURER MODEL NO. TYPE
HEATING COIL
REMARKSCAP (BTUH/FT)
WATERSIDE
EWT LWT PD
RP-1 PERIMETER
ROOMS
STERLING SECURITY RADIANT PANEL CEILING MOUNT 183 175 °F 155 °F 2.0 ftH2O
NOTES:
1. NEW AIR HANDLING UNIT IS TO BE A DEDUCT ALTERNATE TO THE PROJECT. (DEDUCT ALTERNATE #1)
2. STEAM HEATING COIL IS BASED ON 30 PSI STEAM.
3. UNIT STEAM HUMIDIFIER SHALL BE A GRID STYLE 84"W x 94"H USING 30 PSI STEAM, 516.8 LBS./HR
AIR HANDLING UNIT SCHEDULE
ID SERVES MANUFACTURER TYPE ARRANGEMENT
SUPPLY AIR OUTSIDE AIR FAN COOLING COIL STEAM HEATING COIL PRE-FILTER FINAL FILTER
UNIT
WEIGHT VOLT PH REMARKSFLOW FLOW TYPE
AIRFLOW VELOCITY PRESS
RPM
WHEEL
DRIVE
TYPE
MOTOR
TYPE
CAP AIRSIDE WATERSIDE
TYPE CAP
AIRSIDE
WIDTH EFF TYPE WIDTH EFFDESIGN MIN OUTLET ESP TSP TYPE DIA QTY POWER VFD TOTAL SENSIBLE
DESIGN
FLOW EAT(db) EAT(wb) LAT(db) LAT(wb) FA FV PD ROWS FLOW EWT LWT PD
DESIGN
FLOW EAT(db) LAT(db) FA FV PD ROWS
70.AHU.08 AREA H,K TEMTROL CUSTOM BUILT UP DRAW-THROUGH 20000 CFM 6000 CFM FAN WALL (2X2) 20000 CFM 6000 CFM 556 FPM 3.50 in-wg 7.50 in-wg 3450 CENT 18" DIRECT 4 15.00 hp Yes CHILLED WATER 832600 Btu/h 571200 Btu/h 20000 CFM 80.0 °F 67.0 °F 53.1 °F 52.8 °F 41.6 SF 480 FPM 0.76 in-wg 6 138.3 GPM 44 °F 56 °F 5.6 ftH2O STEAM 1798900 Btu/h 20000 CFM -20.0 °F 63.0 °F 32.0 SF 895 FPM 0.51 in-wg 2 2" MERV 8 CARTRIDGE 12" MERV 14 16060 lb 460 V 3 1, 2, 3
ID MANUFACTURER MODEL NO. TYPE
HEATING COIL
ENCLOSURE
HEIGHT
TOP MOUNT
HEIGHT REMARKSBTU PER FT
AIRSIDE WATERSIDE
EAT(db) ROWS FPF
TUBE
DIA EWT LWT
FTR-1 STERLING JVB-2PMP PEDISTAL 1760 70.0 °F 2 50 1" 175 °F 155 °F 0' - 10 3/4" 0' - 10 3/4" CUSTOM ANTI-LIGITURE ENCLOSURE-SEE DETAIL
13/MH501
SOUND ATTENUATOR SCHEDULE
ID SYSTEM NAME SERVES MANUFACTURER MODEL NO. TYPE ARRANGEMENT
SOUND ATTENUATOR DYNAMIC INSERTION LOSS (dB) DIMENSIONS
REMARKSAIRFLOW FV PD
Hz
Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
DUCT UNIT
WIDTH HEIGHT LENGTH
RA-SIL-1 RETURN AIR 70-AHU-8 VIBRO-ACOUSTICS CD-HV-F9-NA DOUBLE WALL Horizontal 20000 CFM 2300 FPM 0.21 in-wg 8 15 24 34 36 24 15 9 0" 0" 6' - 8" 40"ID, 56"OD SA-SIL-1 SUPPLY AIR 70-AHU-8 VIBRO-ACOUSTICS CD-HV-F9-NA DOUBLE WALL Horizontal 6600 CFM 2200 FPM 0.19 in-wg 5 9 20 29 40 39 30 19 0" 0" 5' - 0" 20"ID, 36"OD SA-SIL-2 SUPPLY AIR 70-AHU-8 VIBRO-ACOUSTICS CD-HV-F9-NA DOUBLE WALL Horizontal 6600 CFM 2200 FPM 0.19 in-wg 5 9 20 29 40 39 30 19 0" 0" 5' - 0" 20"ID, 36"OD SA-SIL-3 SUPPLY AIR 1K-111 VIBRO-ACOUSTICS CD-HV-F9-NA DOUBLE WALL Horizontal 250 CFM 300 FPM 0.01 in-wg 4 7 14 26 35 42 43 31 0" 0" 2' - 0" 10"ID, 18"OD SA-SIL-4 SUPPLY AIR 1K-110 VIBRO-ACOUSTICS RD-ULV-F9-NA DOUBLE WALL Horizontal 260 CFM 315 FPM 0.28 in-wg 4 7 16 28 42 36 25 18 6" 12" 3' - 0"
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
SEQUENCE OF OPERATION – RADIANT PANEL / BASEBOARD RADIATOR CONTROL SEQUENCE
GENERAL
STAND ALONE RADIANT PANEL OR BASEBOARD RADIATOR WITH TEMPERATURE SENSOR.
OPERATING SCHEDULE
OPERATING HOURS ARE SCHEDULED THROUGH THE BUILDING AUTOMATION SYSTEM.
OCCUPIED MODE HEATING
RADIANT PANEL OR BASEBOARD RADIATOR TO PROVIDE HEATING ALONG THE PERIMETER DURING HEATING SEASON. ONCE ENABLED, HEATING WATER CONTROL VALVE TO MODULATE AS REQUIRED TO MAINTAIN SPACE TEMPERATURE.
DURING COOLING OPERATION, HEATING WATER FLOW IS DISABLED.
OPERATOR STATION DISPLAY
INDICATE THE FOLLOWING ON THE OPERATOR STATION DISPLAY:
• SYSTEM GRAPHIC
• HOT WATER VALVE POSITION IS (% OPEN)
• SPACE TEMPERATURE
• SPACE TEMPERATURE SET POINT
VAV SEQUENCE OF OPERATIONS
RUN CONDITIONS - SCHEDULED
THE VAV SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE: THE VAV SHALL MAINTAIN
- A 74°F (ADJ.) COOLING SET POINT.
- A 70°F (ADJ.) HEATING SET POINT.
• UNOCCUPIED MODE (NIGHT SETBACK): THE VAV SHALL MAINTAIN
- A 80°F (ADJ.) COOLING SET POINT.
- A 65°F (ADJ.) HEATING SET POINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SET POINT BY A USER DEFINABLE
AMOUNT (ADJ.)
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SET POINT BY A USER DEFINABLE AMOUNT
(ADJ.).
ZONE SET POINT ADJUSTMENT
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SET POINTS AT THE ZONE
SENSOR.
ZONE OPTIMAL START
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF
SCHEDULED OCCUPIED PERIOD.
ZONE UNOCCUPIED OVERRIDE
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL
AUTOMATICALLY RETURN TO THE SCHEDULE.
REVERSING VARIABLE AIR VOLUME - FLOW CONTROL
THE UNIT SHALL MAINTAIN ZONE SET POINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN IT’S COOLING SET POINT, THE ZONE DAMPER SHALL MODULATE BETWEEN
THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SET POINT AND THE HEATING SET POINT, THE ZONE DAMPER
SHALL MAINTAIN THE MINIMUM REQUIRED ZONE VENTILATION (ADJ.).
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SET POINT, THE CONTROLLER SHALL ENABLE HEATING TO
MAINTAIN THE ZONE TEMPERATURE AT ITS HEATING SET POINT.
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM UNOCCUPIED AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SET POINT, THE ZONE DAMPER SHALL MODULATE
BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS
SATISFIED.
• WHEN ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING SET POINT, THE CONTROLLER SHALL ENABLE
HEATING TO MAINTAIN THE ZONE TEMPERATURE AT THE SET POINT.
REHEAT COIL VALVE
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE REHEAT COIL CONTROL VALVE OPEN ON
DROPPING TEMPERATURE TO MAINTAIN ITS HEATING SET POINT.
DISCHARGE AIR TEMPERATURE
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.)
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).
VAV (SHARED TEMPERATURE SENSOR WITH RADIANT CEILING PANEL OR BASEBOARD RADIATOR) SEQUENCE OF
OPERATIONS
RUN CONDITIONS - SCHEDULED
THE VAV SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE: THE VAV SHALL MAINTAIN
- A 74°F (ADJ.) COOLING SET POINT.
- A 70°F (ADJ.) HEATING SET POINT.
• UNOCCUPIED MODE (NIGHT SETBACK): THE VAV SHALL MAINTAIN
- A 80°F (ADJ.) COOLING SET POINT.
- A 65°F (ADJ.) HEATING SET POINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SET POINT BY A USER DEFINABLE
AMOUNT (ADJ.)
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SET POINT BY A USER DEFINABLE AMOUNT
(ADJ.).
ZONE SET POINT ADJUSTMENT
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SET POINTS AT THE ZONE
SENSOR.
ZONE OPTIMAL START
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF
SCHEDULED OCCUPIED PERIOD.
ZONE UNOCCUPIED OVERRIDE
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL
AUTOMATICALLY RETURN TO THE SCHEDULE.
REVERSING VARIABLE AIR VOLUME - FLOW CONTROL
THE UNIT SHALL MAINTAIN ZONE SET POINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN IT’S COOLING SET POINT, THE ZONE DAMPER SHALL MODULATE BETWEEN
THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SET POINT AND THE HEATING SET POINT, THE ZONE DAMPER
SHALL MAINTAIN THE MINIMUM REQUIRED ZONE VENTILATION (ADJ.).
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SET POINT, THE CONTROLLER SHALL ENABLE HEATING TO
MAINTAIN THE ZONE TEMPERATURE AT ITS HEATING SET POINT.
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM UNOCCUPIED AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SET POINT, THE ZONE DAMPER SHALL MODULATE
BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS
SATISFIED.
• WHEN ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING SET POINT, THE CONTROLLER SHALL ENABLE
HEATING TO MAINTAIN THE ZONE TEMPERATURE AT THE SET POINT.
REHEAT COIL VALVE
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE REHEAT COIL CONTROL VALVE OPEN ON DROPPING TEMPERATURE TO MAINTAIN ITS HEATING SET POINT. REHEAT COIL FLOW SHALL NOT BE INITIATED UNTIL CORRESPONDING RADIANT CEILING PANEL CONTROL VALVE IS FULLY OPEN. UPON SPACE TEMPERATURE RISING ABOVE HEATING SETPOINT, REHEAT COIL FLOW SHALL BE STOPPED BEFORE RADIANT CEILING PANEL FLOW IS DECREASED.
DISCHARGE AIR TEMPERATURE
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.)
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).
SEQUENCE OF OPERATION – RADIANT CEILING PANEL / BASEBOARD RADIATION CONTROL SEQUENCE
GENERAL
EITHER RADIANT CEILING PANEL (RCP) OR BASEBOARD RADIATORS WILL BE USED IN EXTERIOR ZONES, SHARING TEMPERATURE SENSOR WITH VAV. RCP OR BASEBOARD RADIATOR IS THE PRIMARY HEAT SOURCE FOR THE SPACE, WITH VAV
SUPPLYING AIR AT APPROXIMATELY SPACE TEMPERATURE.
OPERATING SCHEDULE
OPERATING HOURS ARE SCHEDULED THROUGH THE BUILDING AUTOMATION SYSTEM.
OCCUPIED MODE HEATING
RCP/BASEBOARD RADIATOR TO PROVIDE HEATING ALONG THE PERIMETER DURING HEATING SEASON. ONCE ENABLED, HEATING WATER CONTROL VALVE TO MODULATE AS REQUIRED TO MAINTAIN SPACE TEMPERATURE.
DURING COOLING OPERATION, HEATING WATER FLOW IS DISABLED.
OPERATOR STATION DISPLAY
INDICATE THE FOLLOWING ON THE OPERATOR STATION DISPLAY:
• SYSTEM GRAPHIC
• HOT WATER VALVE POSITION IS (% OPEN)
• SPACE TEMPERATURE
• SPACE TEMPERATURE SET POINT
NOT TO SCALEMH-801
3 RADIANT PANEL CONTROL DIAGRAM
NOT TO SCALEMH-801
1 VAV CONTROL DIAGRAM
NOT TO SCALEMH-801
2 VAV WITH RCP CONTROL DIAGRAM
VAV MECHANICAL POINT LISTING
MARK DESCRIPTION TY
PE
TR
EN
D
SC
HE
DU
LE
D
AL
AR
M
NO
TE
S
TS-DAT DISCHARGE AIR TEMP. AI X X
AFM-SA SUPPLY AIR FLOW AI X
SDPR-VAV ZONE DAMPER AO
CV-HW HEATING WATER CONTROL VALVE AO X
TS-ZN ZONE TEMP AI X X
TS-ZO ZONE OVERRIDE AI X
TS-ZS ZONE SETPOINT ADJUST AI
VAV WITH RADIANT HEATING MECHANICAL POINT LISTING
MARK DESCRIPTION TY
PE
TR
EN
D
SC
HE
DU
LE
D
AL
AR
M
NO
TE
S
TS-DAT DISCHARGE AIR TEMP. AI X
AFM-SA SUPPLY AIR FLOW AI X
SDPR-VAV ZONE DAMPER AO
CV-HWRD RADIANT HEATING WATER CONTROL VALVE AO X X
CV-HWRH REHEAT HEATING WATER CONTROL VALVE AO X
TS-ZN ZONE TEMP AI X
TS-ZO ZONE OVERRIDE AI X
TS-ZS ZONE SETPOINT ADJUST AI
RADIANT HEATING MECHANICAL POINT LISTING
MARK DESCRIPTION TY
PE
TR
EN
D
SC
HE
DU
LE
D
AL
AR
M
NO
TE
S
CV-HW HEATING WATER CONTROL VALVE AO X X
TS-ZS ZONE SETPOINT ADJUST AI X
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
SEQUENCE OF OPERATION – AHU-08
GENERAL
AIR HANDLING UNIT (AHU-01) IS A VARIABLE-AIR-VOLUME (VAV), HORIZONTAL DRAW-THRU UNIT, WHICH CONSISTS OF AN VFD PLENUM SUPPLY AIR FAN ARRAY (SF-01), VFD RETURN AIR FAN ARRAY (RF-01), STEAM COIL, CHILLED WATER COOLING COIL, RETURN AIR DAMPER, EXHAUST AIR DAMPER, AND OUTSIDE AIR DAMPER.
A LOCAL CONTROL PANEL SHALL PROVIDE HAND/OFF/AUTO SELECTION.
RUN CONDITIONS - SCHEDULED
THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
EMERGENCY SHUTDOWN
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY ALARM.
FREEZE PROTECTION
THE UNIT SHALL SHUTDOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZE STATUS, BELOW 38°F (ADJ.).
HIGH STATIC SHUTDOWN
THE UNIT SHALL SHUTDOWN AND GENERATE AN ALARM UPON RECEIVING A HIGH STATIC SHUTDOWN SIGNAL (ADJ.).
SUPPLY AIR SMOKE DETECTION
THE UNITS SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SMOKE DETECTOR STATUS.
AHU OPTIMAL START
THE UNIT SHALL START PRIOR TO SCHEDULED OCCUPANCY BASED ON THE TIME NECESSARY FOR THE ZONES TO REACH THEIR OCCUPIED SET POINTS. THE START TIME SHALL AUTOMATICALLY ADJUST BASED ON CHANGES IN OUTSIDE AIR TEMPERATURE
AND ZONE TEMPERATURES.
SUPPLY AIR FANS
THE SUPPLY FANS SHALL RUN WHENEVER THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FANS SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• SUPPLY FAN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
SUPPLY AIR DUCT STATIC PRESSURE CONTROL
THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND MODULATE THE SUPPLY FAN VFD SPEEDS TO MAINTAIN A DUCT STATIC PRESSURE SET POINT. THE SPEED SHALL NOT DROP BELOW 30% (ADJ). THE STATIC PRESSURE SET POINT SHALL BE RESET BASED ON THE COOLING REQUIREMENTS. THE STATIC PRESSURE SET POINT SHALL BE RESET BASED UPON THE POSITION OF THE ZONE DAMPERS, WITH A GOAL OF REDUCING THE STATIC PRESSURE UNTIL AT LEAST ONE ZONE DAMPER IS FULL OPEN.
• INITIAL DUCT STATIC PRESSURE SET POINT SHALL BE 1.5 IN H2O (ADJ.).
• IF NO ZONE DAMPER IS FULL OPEN, THE SET POINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 1.0 IN H2O (ADJ.).
• AS MORE THAN ONE DAMPER NEARS THE WIDE OPEN POSITION, THE SET POINT SHALL INCREMENTALLY RESET UP TO A
MAXIMUM OF 1.8IN H2O (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN SET POINT.
• LOW SUPPLY STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN SET POINT.
• SUPPLY FAN VFD FAULT.
RETURN FANS
THE RETURN FANS SHALL RUN WHENEVER THE SUPPLY FANS RUN.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• RETURN FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• RETURN FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• RETURN FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
• RETURN FAN VFD FAULT.
BUILDING STATIC PRESSURE CONTROL
THE BUILDING AUTOMATION SYSTEM WILL MAINTAIN A CONSTANT CFM OFFSET BETWEEN SUPPLY AIR FLOW AND RETURN AIR FLOW BY MEASURING SUPPLY AND RETURN AIRFLOW MONITORING SYSTEMS AND MODULATING RETURN FAN SPEED TO
MAINTAIN OFFSET.
SUPPLY AIR TEMPERATURE - OPTIMIZED
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A SUPPLY AIR TEMPERATURE SET
POINT RESET BASED ON ZONE COOLING AND HEATING REQUIREMENTS.
THE SUPPLY AIR TEMPERATURE SET POINT SHALL BE RESET FOR COOLING BASED ON ZONE COOLING REQUIREMENTS AS
FOLLOWS:
• THE INITIAL SUPPLY AIR TEMPERATURE SET POINT SHALL BE 55°F (ADJ.).
• AS COOLING DEMAND INCREASES, THE SET POINT SHALL INCREMENTALLY RESET DOWN TO A MINIMUM OF 53°F (ADJ.).
• AS COOLING DEMAND DECREASES, THE SET POINT SHALL INCREMENTALLY RESET UP TO A MAXIMUM OF 72°F (ADJ.).
STEAM COIL VALVE
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE STEAM CONTROL VALVE TO MAINTAIN ITS HEATING SET POINT. IF THE OUTDOOR AIR TEMPERATURE IS ABOVE 35° F THE DDCC WILL MODULATE BOTH THE FACE AND BYPASS DAMPER AND THE PRE-HEAT VALVE CV-STM, IN SEQUENCE TO MAINTAIN 55° F SUPPLY FAN DISCHARGE. IF THE OUTDOOR AIR TEMPERATURE IS BELOW 35° F THE DDCC WILL FULLY OPEN THE PRE-HEAT VALVE , AND TO MODULATE ONLY THE
FACE AND BY-PASS DAMPERS.
HEATING SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS LOWER THAN 55° F (ADJ.)
• AND ECONOMIZER IS DISABLED.
• AND SUPPLY FAN STATUS IS ON.
• AND COOLING IS NOT ACTIVE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) LESS THAN SET POINT.
SEQUENCE OF OPERATION – AHU-08 (CONTINUED)
WINTER HUMIDIFICATION
THE CONTROLLER SHALL MEASURE THE RETURN AIR RELATIVE HUMIDITY AND MODULATE STEAM FLOW TO THE HUMIDIFIER GRID
TO MAINTAIN RELATIVE HUMIDITY NO LESS THAN 30% (ADJ.).
CHILLED WATER COIL VALVE
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE CHILLED WATER COIL CONTROL VALVE
TO MAINTAIN ITS COOLING SET POINT.
COOLING SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS GREATER THAN 60° F (ADJ.).
• AND THE ECONOMIZER IS DISABLED OR FULLY OPEN.
• AND THE SUPPLY FAN STATUS IS ON.
• AND THE HEATING IS NOT ACTIVE.
THE COOLING COIL VALVE SHALL OPEN TO 50% (ADJ.) WHENEVER THE FREEZE STAT IS ON.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS 5°F (ADJ.) GREATER THAN SET POINT.
ECONOMIZER
THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE OA, RA, AND EA DAMPERS IN SEQUENCE TO MAINTAIN A SET POINT 2°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SET POINT. THE MINIMUM OUTSIDE AIR DAMPER
SHALL MAINTAIN A MINIMUM OUTSIDE AIR WHENEVER OCCUPIED.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
• OUTSIDE AIR TEMPERATURE IS LESS THAN 72°F (ADJ.).
• AND THE OUTSIDE AIR ENTHALPY IS LESS THAN 27 BTU/LB (ADJ.).
• AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE.
• AND THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY.
• AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER;
• MIXED AIR TEMPERATURE DROPS FROM MINIMUM COOLING SET POINT.
• OR THE FREEZE STAT IS ON.
• OR LOSS OF SUPPLY FAN STATUS.
THE SA, OA AND EA DAMPERS SHALL BE CLOSED AND THE RETURN AIR DAMPER SHALL BE OPEN WHEN AHU-1 IS OFF. IF OPTIMAL START UP IS ENABLED THE MIXED AIR DAMPER SHALL OPERATE AS DESCRIBED IN THE OCCUPIED MODE EXCEPT THAT THE
OUTSIDE AIR DAMPERS SHALL MODULATE FULLY CLOSED.
FILTER DIFFERENTIAL PRESSURE MONITOR
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS BOTH THE PRE-FILTERS AND FINAL FILTERS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINED LIMIT (ADJ.).
MIXED AIR TEMPERATURE
THE CONTROLLER SHALL MONITOR THE MIXED AIR TEMPERATURE AND USE AS REQUIRED FOR ECONOMIZER CONTROL.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW MIXED AIR TEMP: IF THE MIXED AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
RETURN AIR TEMPERATURE
THE CONTROLLER SHALL MONITOR THE RETURN AIR TEMPERATURE AND USE AS REQUIRED FOR SET POINT CONTROL OR
ECONOMIZER CONTROL.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW RETURN AIR TEMP: IF THE RETURN AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
SUPPLY AIR TEMPERATURE
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 110°F (ADJ.).
• LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
EMERGENCY SHUTDOWN
AHU-1 AND RF-1 SHALL SHUTDOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.
EMERGENCY AIR DISTRIBUTION SHUTDOWN
EMERGENCY AIR DISTRIBUTION SHUTDOWN SWITCH: ACTIVATION OF THE BUILDING EMERGENCY AIR DISTRIBUTION SHUT DOWN
SWITCH SHALL SHUT DOWN AHU-1 AND RF-1.
SMOKE CYCLE OPERATION
• WHEN THE SMOKE CYCLE IS INITIATED EITHER AUTOMATICALLY AS PART OF A SMOKE INTERLOCK SEQUENCE IN THE ECC PROGRAM, OR MANUALLY BY THE ECC OPERATOR, THE UNIT WILL OPERATE AS SHOWN IN THE SMOKE CYCLE CHART. SMOKE DAMPERS ARE CONTROLLED INDIVIDUALLY TO ALLOW THEM TO BE OPENED OR CLOSED SEPARETELY. IF AN OPERATOR AT THE DDCC DETERMINES IT IS NECESSARY TO DEVIATE FROM THE DAMPER POSITION SPECIFIED IN THE SMOKE CYCLE CHART. LOW LIMIT THERMOSTAT SHALL BE INOPERATIVE. THE HUMIDIFIER AND COOLING COIL VALVES SHALL BE CLOSED
DURING THE SMOKE CYCLE.
• SMOKE MODE VALVE SMCV-STM AND PREHEAT VALVE CV-STM WILL BE MODULATED IN SEQUENCE TO MAINTAIN A 55 F
SUPPLY FAN DISCHARGE.
• IF A ZONE CONDITIONED BY THIS AHU IS IN THE SMOKE MODE, POSITIVE OR NEGATIVE, THE DDCC WILL ELIMINATE THE STATIC PRESSURE SENSORS IN THIS ZONE FROM THE CONTROL SE;ECTION PROCESS AND WILL CONTROL THE SUPPLY FAN FOR THE LOWEST STATIC PRESSURE SENSOR IN THE REMAINING ZONES NOT AFFECTED BY THE SMOKE CONDITION.
NOT TO SCALEMH-802
1 AHU CONTROL DIAGRAM
AHU MECHANICAL POINT LISTING
MARK DESCRIPTION TY
PE
TR
EN
D
SC
HE
DU
LE
D
AL
AR
M
NO
TE
S
HUM-STM TWO-WAY HEATING VALVE AO X
PN-FBDPR STEAM HEATING FACE & BYPASS DAMPER POSITION AO X
ST-FBDPR STEAM HEATING FACE & BYPASS DAMPER STATUS AI X
HS-RAH RETURN AIR RELATIVE HUMIDITY AI X
TS-FS FREEZE STAT BI X X
TS-MAT MIXED AIR TEMP. AI X X
TS-RAT RETURN AIR TEMP. AI X X
TS-SAT SUPPLY AIR TEMP. AI X X
DP-FFLTR FINAL FILTER DIFFERENTIAL PRESSURE AI X
DP-PFLTR PRE-FILTER DIFFERENTIAL PRESSURE AI X
SP-SA SUPPLY AIR PRESSURE AI X
F-RVAV RETURN AIR FAN VFD FAULT BI X
F-SVAV SUPPLY AIR FAN VFD FAULT X 6 FANS BI X
MS-RVAV RETURN AIR FAN VARIABLE SPEED AO X
MS-SVAV SUPPLY AIR FAN VARIABLE SPEED X 6 FANS AO X
SS-RVAV RETURN AIR FAN START/STOP BO X
SS-SVAV SUPPLY AIR FAN START/STOP X 6 FANS BO X
ST-RAF RETURN AIR FAN STATUS BI X
ST-SAF SUPPLY AIR FAN STATUS X 6 FANS BI X
CV-CW CHILLED WATER CONTROL VALVE AO X
CV-STM STEAM CONTROL VALVE AO X
SMCV-STM SMOKE MODE STEAM CONTROL VALVE AO X
SP-SDN HIGH STATIC SHUTDOWN BI X X
SW-EADS EMERGENCY AIR DISTRIBUTION SHUTDOWN SWITCH BI X X
AFM-RA RETURN AIR FLOW AI X
AFM-SA SUPPLY AIR FLOW AI X
PN-EDPR EXHAUST AIR DAMPER POSITON AO X
PN-MODPR MINIMUM OUTDOOR AIR DAMPER POSITION AO X
PN-ODPR OUTDOOR AIR DAMPER POSITION AO X
PN-RDPR RETURN AIR DAMPER POSITION AO X
PN-RSDPR RETURN AIR SMOKE DAMPER POSITION BO X
PN-SSDPR SUPPLY AIR SMOKE DAMPER POSITION BO X
ST-EDPR EXHAUST AIR DAMPER STATUS AI X
ST-MODPR MINIMUM OUTDOOR AIR DAMPER STATUS AI X
ST-ODPR OUTDOOR AIR DAMPER STATUS AI X
ST-RDPR RETURN AIR DAMPER STATUS AI X
ST-RSDPR RETURN AIR SMOKE CONTROL DAMPER STATUS BI X
ST-SSDPR SUPPLY AIR SMOKE CONTROL DAMPER STATUS BI X
SD-RA RETURN AIR SMOKE DETECTOR BI X
SD-SA SUPPLY AIR SMOKE DETECTOR BI X
TS-OAT OUTSIDE AIR TEMP AI X
HS-OAH OUTSIDE AIR HUMIDITY AI X
DP-ZN BLDG STATIC PRESSURE AI X
Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger
LIGHTING FIXTURES
SYMBOL DESCRIPTION
(NOTE: NOT ALL SYMBOLS INDICATED ARE USED ON PLANS. COORDINATE SYMBOLS USED
WITH SYMBOLS LEGEND ACCORDINGLY.)
EMERGENCY LIGHTING UNIT
SWITCHES & CONTROL OUTLETS
SWITCHES - 48" AFF
GANG LIGHT SWITCHES INDICATED ADJACENT TO EACH OTHER IN A
MULTI-GANG BOX AND MULTI-GANG FACEPLATE UNLESS OTHERWISE
NOTED
2 = DOUBLE POLE, SINGLE THROW
3 = THREE WAY
4 = FOUR WAY
K = KEY OPERATED
C = MOMENTARY CONTACT, SPDT, CENTER OFF
P = OFF PILOT LIGHT
a
POWER DISTRIBUTION
POWER OUTLETS
SYMBOL DESCRIPTION
SINGLE RECEPTACLE, MOUNTED AT 18"AFF, UON
SHADED SYMBOL - ON EMERGENCY POWER
PANELBOARD
DUPLEX RECEPTACLE, MOUNTED AT 18"AFF, UON
SHADED SYMBOL - ON EMERGENCY POWER
DOUBLE DUPLEX RECEPTACLE, MOUNTED AT 18"AFF, UON
SHADED SYMBOL - ON EMERGENCY POWER
SPECIAL RECEPTACLE - CONFIGURATION AS INDICATED
MOUNTED 18"AFF, UON
SHADED SYMBOL - ON EMERGENCY POWER
JUNCTION BOX, MOUNTED 18"AFF, UONJ
J
DUPLEX…
This is the start of the file's text. The full file is on GovTribe.