4-4-2021 VA Addendum 2.Attachments.pdf

PDF 3 MB Posted

Attached to
Z1DA--Renovate MH Ward 1L, 1H and 1K - Minneapolis VAMC
Solicitation number
36E77620R0050
Issued by

About this file

This document provides details of a federal contract opportunity for the renovation of a mental health ward at the Minneapolis VA Medical Center. The Department of Veterans Affairs will solicit proposals and award a firm-fixed-price contract for design-bid-build services including general construction, demolition, structural, civil, mechanical, plumbing, electrical, low voltage, and equipment work. The solicitation will be a total Service-Disabled Veteran-Owned Small Business set-aside with a NAICS code of 236220 and size standard of $39.5 million. The period of performance is approximately 790 calendar days with construction values between $10-20 million. Questions must be submitted in writing by February 4, 2020, and award is anticipated on or around that date.

View the file

Other files

File Type Posted
36E77620R0050 0009.docx DOCX document
R4-A702.pdf PDF
Revision Set 4 - Narrative.pdf PDF
R4-A701.pdf PDF
Technical Questions Spreadsheet.pdf PDF
R4-A703.pdf PDF
VA Addendum-Revision Set 3.pdf PDF
36E77620R0050 0008.docx DOCX document
Construction Wage Rates - Hennepin County - 1.1.20.pdf PDF
1K Rec Area Utility Plan.pdf PDF
1K Landscape plan.pdf PDF
Technical Questions Spreadsheet.xlsx XLSX spreadsheet
Exterior Site Plan_Dumpster_Laydown.pdf PDF
4-4-2021 Combined Documents Addendum 2.pdf PDF
VA Pre-Bid Addendum 2 Revision Set 2.pdf PDF
36E77620R0050 0007.docx DOCX document
Technical Question Tracking Sheet.pdf PDF
23 07 11.pdf PDF
4-4-2021 VA Addendum 2.Narrative.pdf PDF
Renovate Inpatient Mental Health Project 618-17-127 Exterior Modifications.pdf PDF
36E77620R0050 0006.docx DOCX document
Renovate Mental Health Inpatient Ward Project Addendum 1.docx DOCX document
01 45 00 Quality Control.pdf PDF
36E77620R0050 0005.docx DOCX document
083313 Coiling Counter Doors.pdf PDF
Technical Question Tracking Sheet.docx DOCX document
Q 26 crafted plank oak grove.pdf PDF
36E77620R0050 0004.docx DOCX document
S05 -Technical Question Tracking Sheet.docx DOCX document
Minneapolis Mental Health Site Visit Sign-In.pdf PDF
36E77620R0050 0003.pdf PDF
36E77620R0050 0001.docx DOCX document
36E77620R0050 0002.docx DOCX document
ATTACHMENT 6 - 2018-27 MSP IPMH Renovation Specifications Vol 1 and Vol 2.pdf PDF
ATTACHMENT 1 - VAMH-618-17-127 CD SET_1.pdf PDF
ATTACHMENT 5 - VAMH-618-17-127 CD SET_5.pdf PDF
ATTACHMENT 3 - VAMH-618-17-127 CD SET_3.pdf PDF
ATTACHMENT 7 - Contractor Safety _ Env Record Form.docx DOCX document
36E77620R0050.docx DOCX document
ATTACHMENT 2 - VAMH-618-17-127 CD SET_2.pdf PDF
ATTACHMENT 4 - VAMH-618-17-127 CD SET_4.pdf PDF
ATTACHMENT 8 - Construction Wage Rates - Hennepin County - 1.1.20.pdf PDF
ATTACHMENT 6 - 2018-27 MSP IPMH Renovation Specifications Vol 1 and Vol 2 - 2-1-21.pdf PDF
ATTACHMENT 9 - Brand Name JA - Minneapolis.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ISOMETRIC DETAIL

VERTICAL STUDS @ 2' - 0" MAX

W/ GYPSUM BD 1' - 4" W/ GYPSUM LATH &

PLASTER DOUBLE STUDS FOR SUPPORTING CONC

BACKER BOARD

PROVIDE CONTINUOUS BRACING WHEN STUDS

EXCEED 10' - 0" & ARE FINISHED BOTH SIDES

JAMB ANCHOR CLIPS 3 PER SIDE -

COORDINATE W/ HINGE REINFORCEMENT

NOTE 1:

OMIT BRACE WHEN "D" DIMENSION IS LESS THAN 2' - 0"

FOR GYP WALLBD. OR 16" FOR PLASTER PARTITION.

CRIPPLE STUD

DO NOT ANCHOR TO

BEARING STUD

GYPBD PANELS

CONTROL

JOINT

PROVIDE SOUND

DEADENING

WHERE REQ'D.

ISOMETRIC OF CONSTRUCTION JT.

SECTION A DETAIL C

JAMB ANCHORS

(FURNISHED WITH FRAME)

DETAIL D

DOUBLE STUDS

JAMB ANCHOR

SHIM AS

REQ'D

METAL

ANCHOR CLIP

METAL DOOR

FRAME

SANITARY STOP

WHERE REQ'D

SEC B

CONTROL JOINT

6" M

A X

DETAIL D

SEE DOOR SCHEDULE

VARIES

SHIM AS REQ'D

DETAIL C

V A

R

IE

S

E Q

E Q

E Q

E Q

D

RUNNER

BET.

STUDS

MTL

DOOR

FRAME

A A

1/2" MIN

1/ 2"

M

IN

SECTION B

STUDWIDTH

FRAME FACE

MINUS 3/16"

KYKC

3/ 4"

M

IN

JAMB DEPTDH

MINUS 3/16"

FRAME FACE

MINUS 3/16"3/

4"

M

IN

1/2" M

IN

5/8" M

AX

STUDWIDTH

3/ 4"

M

IN

GYPSUM

CONTROL JOINT

@ DOOR HEADS

VA JOB NUMBER: 618-17-127

VA MEDICAL CENTER, MINNEAPOLIS, MN

RENOVATE MENTAL HEALTH WARD. BLDG 1338

Date:

SHEETRENOVATE MH WARD 1L,1H,1K

FRAME DETAILS 03/30/21

AE103

1 1/2" = 1'-0"

TYPICAL PARTITION CONTROL JOINT FRAMING AT DOORS

AE

A002

WX

A401

9 7

A401

A5112A5196 P9400

A5081

P9160

A1086

A5074

A5140

SINGLE 102

1K-102

TLT.

1K-102A

A5140

M7011

.0

3'-0"

R 2'-9"

6'-5"

27.0°

3'-2"

SLOPE

C1

C1

C1

VA JOB NUMBER: 618-17-127

VA MEDICAL CENTER, MINNEAPOLIS, MN

RENOVATE MENTAL HEALTH WARD. BLDG 1338

Date:

DETAILRENOVATE MH WARD 1L,1H,1K

TPY SINGLE PATIENT ROOM 04/02/21

1/A401

1/4" = 1'-0"

TYPICAL- SINGLE PATIENT AND TOILET RM

SINGLE TOILET P9400 Toilet, Wall Hung, Siphon Jet, Psychiatric CC

SINGLE TOILET P9160 Lavatory, China, for Disturbed Patient CC

SINGLE TOILET P5350 Shower, Patient, Psychiatric CC

SINGLE TOILET A5207 Bar, Towel, 1" Diameter, SS, Surface Mntd, Psych CC

SINGLE TOILET A5196 Dispenser, Toilet Tissue, Psychiatric CC

SINGLE TOILET A5140 Hook, Garment, Security CC

SINGLE TOILET A5112 Grab Bar, Psychiatric CC

SINGLE TOILET A5081 Dispenser, Paper Towel, SS, Recessed, Psychiatric CC

SINGLE TOILET A5074 Soap Dispenser, Recessed, SS, Psychiatric CC

SINGLE TOILET A1086 Mirror, Safety, Psychiatric CC

SINGLE TOILET M7011 Bed, Platform, Without Visible Legs, Psychiatric CC

SINGLE A5140 Hook, Garment, Security CC

Room Number JSN Content Name Provided By

0 4' 8'2'

WX

A401

A5207

A5112

A5196

P9400

A5081

P9160

A5074

A1086

A5140

CONTRACTOR SHALL SECURE

BEDS TO CONCRETE FLOOR

BELOW PER BED MANUFACTURER

DETAILS

BARIATRIC

SINGLE 107

1K-107

TLT.

1K-107A

A5140

M7011

3'-0" 6'-3 1/2" 2'-9 1/2"

27.0°

1'-1"

.0

1K-107A

SLOPE

C1

C1

C1

/2

/2

VA JOB NUMBER: 618-17-127

VA MEDICAL CENTER, MINNEAPOLIS, MN

RENOVATE MENTAL HEALTH WARD. BLDG 1338

Date:

DETAILRENOVATE MH WARD 1L,1H,1K

TYP BARIATRIC SINGLE 04/02/21

2/A401

1/4" = 1'-0"

TYPICAL - BARIATRIC SINGLE AND TOILET RM

DOUBLE PATIENT TOILET P9400 Toilet, Wall Hung, Siphon Jet, Psychiatric CC

DOUBLE PATIENT TOILET P9160 Lavatory, China, for Disturbed Patient CC

DOUBLE PATIENT TOILET P5350 Shower, Patient, Psychiatric CC

DOUBLE PATIENT TOILET A5207 Bar, Towel, 1" Diameter, SS, Surface Mntd, Psych CC

DOUBLE PATIENT TOILET A5196 Dispenser, Toilet Tissue, Psychiatric CC

DOUBLE PATIENT TOILET A5140 Hook, Garment, Security CC

DOUBLE PATIENT TOILET A5112 Grab Bar, Psychiatric CC

DOUBLE PATIENT TOILET A5081 Dispenser, Paper Towel, SS, Recessed, Psychiatric CC

DOUBLE PATIENT TOILET A5074 Soap Dispenser, Recessed, SS, Psychiatric CC

DOUBLE PATIENT TOILET A1086 Mirror, Safety, Psychiatric CC

DOUBLE PATIENT TOILET M7011 Bed, Platform, Without Visible Legs, Psychiatric CC

DOUBLE PATIENT A5140 Hook, Garment, Security CC

TU

A5074

P9160

A1086

A5081

A5112

P9400

A5196

CONTRACTOR SHALL SECURE

BEDS TO CONCRETE FLOOR

BELOW PER BED MANUFACTURER

DETAILS

DOUBLE 115

1K-115

TLT.

1K-115A

A5140

A5140

M7011 M70113'-0"

.0

6'-2"

/2

/2 " C1

C1

C1

1'-1 1/2"

2'-1 1/2"

VA JOB NUMBER: 618-17-127

VA MEDICAL CENTER, MINNEAPOLIS, MN

RENOVATE MENTAL HEALTH WARD. BLDG 1338

Date:

DETAILRENOVATE MH WARD 1L,1H,1K

TPY DOUBLE PATIENT ROOM 04/02/21

3/A401

1/4" = 1'-0"

TYPICAL - DOUBLE PATIENT AND TOILET RM

BARIATRIC SINGLE TOILET P9400 Toilet, Wall Hung, Siphon Jet, Psychiatric CC

BARIATRIC SINGLE TOILET P9160 Lavatory, China, for Disturbed Patient CC

BARIATRIC SINGLE TOILET P5350 Shower, Patient, Psychiatric CC

BARIATRIC SINGLE TOILET A5207 Bar, Towel, 1" Diameter, SS, Surface Mntd, Psych CC

BARIATRIC SINGLE TOILET A5196 Dispenser, Toilet Tissue, Psychiatric CC

BARIATRIC SINGLE TOILET A5140 Hook, Garment, Security CC

BARIATRIC SINGLE TOILET A5112 Grab Bar, Psychiatric CC

BARIATRIC SINGLE TOILET A5081 Dispenser, Paper Towel, SS, Recessed, Psychiatric CC

BARIATRIC SINGLE TOILET A5074 Soap Dispenser, Recessed, SS, Psychiatric CC

BARIATRIC SINGLE TOILET A1086 Mirror, Safety, Psychiatric CC

BARIATRIC SINGLE TOILET M7011 Bed, Platform, Without Visible Legs, Psychiatric CC

BARIATRIC SINGLE A5140 Hook, Garment, Security CC

Temporary AHU Location

Locate temporary AHU on-grade outside of 'K' Mechanical Room.

Confirm location with

COR.

RESIDENTS TM. RM.

1H-108

CORR 2

C1-67

PT. STOR.

1H-114

STAFF LKR/TLT

1H-103

STAFF BREAK

1H-104

NOURISHMENT

1H-109

MEDS.

1H-112

3" FD-B

2" FD-B

3" FD-B

2" FD-B

P-201

P-511

P-103

P-702

P-702

P-103

P-104

P-402

P-402

P-402 P-402

1 1/2" HW

1" HW

1" HW

3/4" HW

3/4" HW

2" CW

2 1/2" CW

2 1/2" CW

3/4" CW

1" CW

3/4" CW

3" V

3" V

1 1/2" V

3" FD-B

3" FD-B

2 1/2" CW

1 1/2" HW

3" V

3" V

1 1/2" V

1 1/2" HW

1 1/2" HW

1" HW-R

1 1/2" HW

2 1/2" CW

1" HW-R 1" HW

1 1/2" CW

EXISTING SANITARY WASTE PIPING

SERVING THE FLOORS ABOVE TO

REMAIN. TYPICAL

P-512

P-708

TMV-1

P-512

F.C.O.

3/4" HW

P-702

4" SS

PP11

PP11

PP11

PP11

PP11

PP11

1" HW-R

PP12

PP11

1" HW-R

1" HW-R

1" HW-R

1" HW-R

1" HW-R

1" HW-R

1" HW-R

PP13

1 1/4" HW-R

P-601

P-510

3/4" CW

3/4" HW

1/2" CW

3" FD-C

PP16

PP17

P-702

PLUMBING GENERAL NOTES

A. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO THE

START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE PROJECT

ENGINEER PRIOR TO START OF DEMOLITION OF CONSTRUCTION ACTIVITIES.

B. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF NATIONAL AND LOCAL

CODES, WHICHEVER IS MORE STRINGENT.

C. COORDINATE DEMOLITION WITH SCHEDULES, CONSTRUCTION REQUIREMENTS

AND SUBCONTRACTOR'S OPERATIONS. COORDINATE SEQUENCING WITH THE

CONSTRUCTION MANAGER AND PROCEED ONLY AFTER OBTAINING THE

OWNERS ACCEPTANCE OF DEMOLITION SCHEDULE.

D. NO WORK SHALL BE STARTED WHICH AFFECTS EXISTING FACILITY OPERATIONS

WITHOUT PRIOR COORDINATION AND APPROVAL OF THE WORK WITH THE

OWNER.

E. PROVIDE FIRE PROTECTION EQUIPMENT (FIRE EXTINGUISHERS, ETC.) AS

REQUIRED FOR DEMOLITION & CONSTRUCTION ACTIVITIES.

F. FACILITY NEEDS TO BE KEPT WEATHER TIGHT REGARDLESS OF WEATHER

CONDITIONS AT THE END OF EACH DAY. MAINTAIN WEATHER TIGHT CONDITIONS

24 HOURS A DAY FOR THE DURATION OF THE PROJECT.

G. ALL PLUMBING EQUIPMENT, ACCESSORIES AND/OR PLUMBING FIXTURES WILL

BE SECURED WITH VANDAL RESISTANT MOUNTING HARDWARE.

H. INSTALL VERTICAL SANITARY AND VENT PIPING TRUE AND PLUMB.

I. INSTALL ALL HORIZONTAL SANITARY PIPING SLOPED AT 1/4" PER FOOT.

J. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.

K. REFER TO ARCHITECTURAL PLANS FOR PIPING ACCESS PANEL LOCATIONS.

L. REFER TO FIRE PROTECTION DRAWINGS FOR PIPING AND SPRINKLER HEAD

LOCATIONS.

M. PROVIDE OFFSETS AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO

AVOID INTERFERENCE WITH OTHER TRADES. ROUTE ALL PIPING AS HIGH AS

POSSIBLE.

N. COORDINATE FINAL LOCATIONS OF NEW PIPING AND PLUMBING FIXTURES WITH

EXISTING SYSTEMS, STRUCTURE, LIGHTING, ARCHITECTURAL ELEMENTS,

DUCTWORK, PIPING AND SPRINKLERS.

O. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO

PLUMBING EQUIPMENT.

P. PROVIDE DRAIN VALVES WITH CAPPED HOSE END CONNECTIONS AT THE

BOTTOM OF EACH RISER AND AT ALL LOW POINTS IN EACH PRESSURE PIPING

SYSTEM. VERIFY WITH ACCESS PANEL LOCATIONS.

Q. PROVIDE SLEEVES AT EACH PENETRATION OF FIRE AND SMOKE RATED

ASSEMBLIES AND SEAL WITH INTUMESCENT MATERIAL.

R. CONNECT PIPE AND EQUIPMENT HANGERS TO TOP CHORD OF ROOF JOISTS,

BEAM FLANGES OR CONCRETE FLOOR DECK BY APPROVED MEANS.

S. FOR PLUMBING PIPE SIZES, SEE RISER DIAGRAMS.

T. ALL LAVATORIES AND HAND SINKS SHALL HAVE THERMOSTATIC MIXING VALVES

BELOW THE SINKS TO MAINTAIN A MAXIMUM HOT WATER TEMPERATURE OF 110

DEGREES F. MIXING VALVE SHALL BE A WATTS SERIES LFUSG-B LEAD FREE OR

EQUAL.

U. REBALANCE THE BUILDING RECIRCULATED HOT WATER SYSTEM UPON

COMPLETION OF NEW WORK. PROVIDE NEW, OR ADDITIONAL RECIRC. PUMP AS

REQUIRED FOR A COMPLETE AND WORKING BUILDING CIRCULATED HOT WATER

SYSTEM.

V. PROVIDE ISOLATION SHUT-OFF VALVES ON ALL PIPE RUNOUTS FROM MAINS TO

PATIENT ROOMS ,FROM MAINS TO SINGLE PLUMBING FIXTURES, AND WEREVER

SHOWN ON PLANS AND RISERS.

W. FIELD VERIFY ALL NEW WATER, WASTE, AND VENT CONNECTIONS, AND PROVIDE

NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING SYSTEMS.

X. PITCH UNDERFLOOR SANITARY WASTE PIPING AT 1/4" PER FOOT, UNLESS

NOTED OTHERWISE.

Y. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"

MINIMUM.

Z. PROVIDE CLEANOUTS IN ACCESSIBLE LOCATIONS AT THE BASE OF ALL

PLUMBING RISERS.

KEYNOTE LEGEND

KEY DESCRIPTION

PP11 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURNS . BALANCE

FLOW TO .25 GPM

PP12 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURN MAIN. BALANCE

FLOW TO 4.5 GPM

PP13 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURN MAIN. BALANCE

FLOW TO 5.75 GPM

PP16 1/2" CW DOWN TO ICE/WATER DISPENSER. STUB OUT OF WALL AND PROVIDE BALL

VALVE, BACKFLOW PREVENTER AND WATER FILTER.

PP17 PROVIDE 3/4" COPPER DRAIN FROM ICE/WATER DISPENSER DRAIN CONNECTION

DOWN TO FUNNEL FLOOR DRAIN BELOW COUNTER. PROVIDE 1" MINIMUM AIR GAP.

SCALE: 1/8" = 1'-0"1 LEVEL 1 PLUMBING PLAN, AREA H, PHASE 2

CME

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger Date: ___________ License Number: 4871001/07/2021

2.0

GPM

1.0 GPM

3/4"HWR

1-1/2"HW

1"HW

1"HWR

1"HWR

1-1/4"HWR

EXERCISE

1K-119

CLN. LIN.

1K-121

STOR.

1K-120

THEATER

1K-118

STOR.

1K-125

SENS

1K-124

HSKP

1K-127

ROUND

1K-123 ROUND

1K-126

SOIL

1K-122

TLT.

1K-106A

TLT.

1K-116A

TLT.

1K-114A

TLT.

1K-115A

TLT.

1K-113A

TLT.

1K-112A

TLT.

1K-104A

TLT.

1K-105A

TLT.

1K-102A

TLT.

1K-103A

TLT.

1K-108A

TLT.

1K-107A

PT. STOR.

1H-114

MEDS.

1H-112

DOUBLE

1K-115

DOUBLE

1K-114

DOUBLE

1K-113

DOUBLE

1K-117

P-401 P-101 P-101 P-401

P-701

P-701

P-701

P-101

P-101

P-401

P-401

P-701

P-701

P-701

P-101

P-101

P-101

P-401

P-101

P-101

P-101

P-401

P-401 P-101

P-101

P-401

P-401

P-101

P-101

P-101

P-101

P-701

P-701

P-401

P-401

P-701

P-701

P-701

P-401

P-401

1" HW-R

2 1/2" CW

1 1/2" HW

1" HW

2" CW

P-512

P-501

P-701

P-701

P-701

P-701

P-701

P-401 P-401

3" V

1" HW-R 1" HW

1 1/2" CW

1" HW

1 1/2" CW

1" HW-R

3/4" HW-R

2 1/2" CW

2" HW

2 1/2" CW2" HW

3" V

3" V

3" V

2" V

3" V

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-12" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

2" TD-1

3/4" HW-R

2" HW

2 1/2" CW

3" V

3" V

3" V

3" V

3" V

1 1/2" V

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP05

PP10

PP08

PP07

PP09

EXISTING SANITARY WASTE PIPING

SERVING THE FLOORS ABOVE TO

REMAIN. TYPICAL

EXISTING SANITARY WASTE PIPING

SERVING THE FLOORS ABOVE TO

REMAIN. TYPICAL

DOUBLE 112

1K-112

DOUBLE 111

1K-111

BARIATRIC SINGLE 108

1K-108

BARIATRIC SINGLE 107

1K-107

SINGLE 106

1K-106

SINGLE 105

1K-105

SINGLE 104

1K-104

SINGLE 103

1K-103

SINGLE 102

1K-102

SINGLE

1K-101

CORR 1

C1-71A

C-7 C-7

STOR

1K-109

DOUBLE 110

1K-110

TMV-1

TMV-1

P-708

P-708

PP05

PP05

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

1 1/4" HW-R

1 1/4" HW-R

1 1/4" HW-R

PP11

1" HW-R

3/4" HW-R

3/4" HW-R

P-601

3/4" CW

3/4" HW

1/2" CW

1" HW-R

PLUMBING GENERAL NOTES

A. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO THE

START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE PROJECT

ENGINEER PRIOR TO START OF DEMOLITION OF CONSTRUCTION ACTIVITIES.

B. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF NATIONAL AND LOCAL

CODES, WHICHEVER IS MORE STRINGENT.

C. COORDINATE DEMOLITION WITH SCHEDULES, CONSTRUCTION REQUIREMENTS

AND SUBCONTRACTOR'S OPERATIONS. COORDINATE SEQUENCING WITH THE

CONSTRUCTION MANAGER AND PROCEED ONLY AFTER OBTAINING THE

OWNERS ACCEPTANCE OF DEMOLITION SCHEDULE.

D. NO WORK SHALL BE STARTED WHICH AFFECTS EXISTING FACILITY OPERATIONS

WITHOUT PRIOR COORDINATION AND APPROVAL OF THE WORK WITH THE

OWNER.

E. PROVIDE FIRE PROTECTION EQUIPMENT (FIRE EXTINGUISHERS, ETC.) AS

REQUIRED FOR DEMOLITION & CONSTRUCTION ACTIVITIES.

F. FACILITY NEEDS TO BE KEPT WEATHER TIGHT REGARDLESS OF WEATHER

CONDITIONS AT THE END OF EACH DAY. MAINTAIN WEATHER TIGHT CONDITIONS

24 HOURS A DAY FOR THE DURATION OF THE PROJECT.

G. ALL PLUMBING EQUIPMENT, ACCESSORIES AND/OR PLUMBING FIXTURES WILL

BE SECURED WITH VANDAL RESISTANT MOUNTING HARDWARE.

H. INSTALL VERTICAL SANITARY AND VENT PIPING TRUE AND PLUMB.

I. INSTALL ALL HORIZONTAL SANITARY PIPING SLOPED AT 1/4" PER FOOT.

J. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.

K. REFER TO ARCHITECTURAL PLANS FOR PIPING ACCESS PANEL LOCATIONS.

L. REFER TO FIRE PROTECTION DRAWINGS FOR PIPING AND SPRINKLER HEAD

LOCATIONS.

M. PROVIDE OFFSETS AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO

AVOID INTERFERENCE WITH OTHER TRADES. ROUTE ALL PIPING AS HIGH AS

POSSIBLE.

N. COORDINATE FINAL LOCATIONS OF NEW PIPING AND PLUMBING FIXTURES WITH

EXISTING SYSTEMS, STRUCTURE, LIGHTING, ARCHITECTURAL ELEMENTS,

DUCTWORK, PIPING AND SPRINKLERS.

O. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO

PLUMBING EQUIPMENT.

P. PROVIDE DRAIN VALVES WITH CAPPED HOSE END CONNECTIONS AT THE

BOTTOM OF EACH RISER AND AT ALL LOW POINTS IN EACH PRESSURE PIPING

SYSTEM. VERIFY WITH ACCESS PANEL LOCATIONS.

Q. PROVIDE SLEEVES AT EACH PENETRATION OF FIRE AND SMOKE RATED

ASSEMBLIES AND SEAL WITH INTUMESCENT MATERIAL.

R. CONNECT PIPE AND EQUIPMENT HANGERS TO TOP CHORD OF ROOF JOISTS,

BEAM FLANGES OR CONCRETE FLOOR DECK BY APPROVED MEANS.

S. FOR PLUMBING PIPE SIZES, SEE RISER DIAGRAMS.

T. ALL LAVATORIES AND HAND SINKS SHALL HAVE THERMOSTATIC MIXING VALVES

BELOW THE SINKS TO MAINTAIN A MAXIMUM HOT WATER TEMPERATURE OF 110

DEGREES F. MIXING VALVE SHALL BE A WATTS SERIES LFUSG-B LEAD FREE OR

EQUAL.

U. REBALANCE THE BUILDING RECIRCULATED HOT WATER SYSTEM UPON

COMPLETION OF NEW WORK. PROVIDE NEW, OR ADDITIONAL RECIRC. PUMP AS

REQUIRED FOR A COMPLETE AND WORKING BUILDING CIRCULATED HOT WATER

SYSTEM.

V. PROVIDE ISOLATION SHUT-OFF VALVES ON ALL PIPE RUNOUTS FROM MAINS TO

PATIENT ROOMS ,FROM MAINS TO SINGLE PLUMBING FIXTURES, AND WEREVER

SHOWN ON PLANS AND RISERS.

W. FIELD VERIFY ALL NEW WATER, WASTE, AND VENT CONNECTIONS, AND PROVIDE

NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING SYSTEMS.

X. PITCH UNDERFLOOR SANITARY WASTE PIPING AT 1/4" PER FOOT, UNLESS

NOTED OTHERWISE.

Y. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"

MINIMUM.

Z. PROVIDE CLEANOUTS IN ACCESSIBLE LOCATIONS AT THE BASE OF ALL

PLUMBING RISERS.

KEYNOTE LEGEND

KEY DESCRIPTION

PP05 PROVIDE SOLENOID SHUT OFF VALVE ON EACH HOT AND COLD WATER LINE THAT

SERVES AN INDIVIDUAL PATIENT ROOM. THE SOLENOID VALVE SHALL BE

CONTROLLED BY A USER PROGRAMMABLE TOUCH SCREEN DIGITAL MONITOR

LOCATED IN A PANEL BACK IN THE NURSES STATION.

PP07 CONNECT TO EXISTING MINIMUM 3" COLD WATER MAIN. VERIFY SIZE AND LOCATION

OF EXISTING PIPING.

PP08 CONNECT TO EXISTING MINIMUM 2" HOT WATER MAIN. VERIFY SIZE AND LOCATION

OF EXISTING PIPING.

PP09 CONNECT TO EXISTING MINIMUM 1-1/2" RECIRCULATED HOT WATER MAIN. VERIFY

SIZE AND LOCATION OF EXISTING PIPING.

PP10 CONNECT NEW SANITARY VENTS TO EXISTING VENT RISER. VERIFY SIZE AND

LOCATION OF EXISTING RISER.

PP11 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURNS . BALANCE

FLOW TO .25 GPM

SCALE: 1/8" = 1'-0"1 LEVEL 1 PLUMBING PLAN, AREA K, PHASE 2

CME

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger Date: ___________ License Number: 4871001/07/2021

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

S S

S

S

2"HW

2"HW

1-1/2"HW

2"HW

2"HW

2"HW

2"HW

1-1/2"HW

1"HW

P-701

P-401P-101 P-101 P-401

P-401

P-101

P-101

P-101

P-701P-701P-701P-701 P-701

P-101

P-101

P-401

3" FD-A

1" HW

3/4" CW

P-511

P-511

P-511

3" FD-A

P-401

P-701

P-101

1" CW

1" HW

3" C

W 2"

H W

1 1/2" CW1 1/2" HW

3/4 " H

W -R

3/4" CW

3/4" HW

1" CW1 1/2" HW

1 1/2" HW

3/4" HW

3/4" CW

P-402

P-103

P-702

1 1/2" CW

P-808

1" HW

3/4" CW1 1/2" CW

1 1/2" HW 1 1/2" CW

3" FD-B

2" TD-1

2" TD-1 2" TD-1 2" TD-1 2" TD-1 2" TD-1

2" TD-1

1 1/2" V

1 1/2" V

1 1/2" V1 1/2" V1 1/2" V

3" V 3" V 3" V

3" V

3" V

2" V

3" V

2" V2" V

2" V2" V

1 1/4" HW

PP05

PP05

PP05PP05

PP05

PP05

PP05

PP05

PP05

PP05 PP05PP05

PP05

PP05

PP05 PP09

PP07

PP08

PP10

PP10

3" SD

EXISTING STORM DRAIN PIPING TO

REMAIN. VERIFY SIZE AND LOCATION.

EXISTING SANITARY WASTE PIPING THAT SERVES

THE FLOORS ABOVE TO REMAIN. TYPICAL

SOIL

1L-127 SECL

1L-128B

ANTE RM.

1L-128 SECL

1L-128C

CLN. LIN.

1L-113 TOILET 113

1L-113A

TLT.

1L-128A

SOCIAL WRKR OFFICE

1L-115

SENS

1L-129

STOR.

1L-140

GROUP THERAPY

1L-116

OCC THERAPY

1L-114

OCC. THER. OFFICE

1L-114B

REC. THER. OFFICE

1L-112B

REC THERAPY

1L-112DAY ROOM

1L-110CI-61

C1-61

TOILET 101

1L-101

INTERVIEW

1L-102

EXAM

1L-104

LAUNDRY

1L-106

FAMILY ROOM

1L-105

FAM

1L-107

CORR 1

1L-100

RN-MGR.

1L-109

HIGH ACUITY RN STATION

1L-120

SINGLE 121

1L-121 SINGLE 122

1L-122 SINGLE 123

1L-123

SINGLE 124

1L-124

CI-57

C1-57

CI-57

C1-57

CORR 1

C1-60

CORR 1

C1-60

SERVING AREA

1L-131

DINING

1L-130

P-401

P-401

P-512

P-510

3/4" HW

3/4" CW

1 1/2" V

1 1/2" V

2" FD-B

3" FD-B

1" HW-R

3/4" HW-R3/4" HW-R

3/4" HW-R

3/4" HW-R

3/4" HW-R

3/4" HW-R

3/4" HW-R

1" HW-R

1" HW-R

1" HW-R

3/4" HW-R

PP11

PP11

PP11

PP11

PP11

PP11PP11

PP11

PP11

PP11

PP11

PP11

PP11

PP11

1" HW-R

3/4" HW-R

PP14

PP15

3" V

EXISTING SANITARY WASTE PIPING THAT

SERVES THE FLOORS ABOVE TO REMAIN.

TYPICAL

F.C.O.

F.C.O.

F.C.O.F.C.O.F.C.O.

F.C.O.

P-401

P-402

1 1/2" CW

CORR 2

C1-57

TLT.

1L-123A

SINGLE

1L-126

SINGLE

1L-126

SINGLE

1L-126

SINGLE

1L-125

3" FD-C

PP16

PP17

P-402

PLUMBING GENERAL NOTES

A. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO THE

START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO THE PROJECT

ENGINEER PRIOR TO START OF DEMOLITION OF CONSTRUCTION ACTIVITIES.

B. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF NATIONAL AND LOCAL

CODES, WHICHEVER IS MORE STRINGENT.

C. COORDINATE DEMOLITION WITH SCHEDULES, CONSTRUCTION REQUIREMENTS

AND SUBCONTRACTOR'S OPERATIONS. COORDINATE SEQUENCING WITH THE

CONSTRUCTION MANAGER AND PROCEED ONLY AFTER OBTAINING THE

OWNERS ACCEPTANCE OF DEMOLITION SCHEDULE.

D. NO WORK SHALL BE STARTED WHICH AFFECTS EXISTING FACILITY OPERATIONS

WITHOUT PRIOR COORDINATION AND APPROVAL OF THE WORK WITH THE

OWNER.

E. PROVIDE FIRE PROTECTION EQUIPMENT (FIRE EXTINGUISHERS, ETC.) AS

REQUIRED FOR DEMOLITION & CONSTRUCTION ACTIVITIES.

F. FACILITY NEEDS TO BE KEPT WEATHER TIGHT REGARDLESS OF WEATHER

CONDITIONS AT THE END OF EACH DAY. MAINTAIN WEATHER TIGHT CONDITIONS

24 HOURS A DAY FOR THE DURATION OF THE PROJECT.

G. ALL PLUMBING EQUIPMENT, ACCESSORIES AND/OR PLUMBING FIXTURES WILL

BE SECURED WITH VANDAL RESISTANT MOUNTING HARDWARE.

H. INSTALL VERTICAL SANITARY AND VENT PIPING TRUE AND PLUMB.

I. INSTALL ALL HORIZONTAL SANITARY PIPING SLOPED AT 1/4" PER FOOT.

J. INSTALL HORIZONTAL SANITARY VENT PIPING SLOPED AT 1/8" PER FOOT.

K. REFER TO ARCHITECTURAL PLANS FOR PIPING ACCESS PANEL LOCATIONS.

L. REFER TO FIRE PROTECTION DRAWINGS FOR PIPING AND SPRINKLER HEAD

LOCATIONS.

M. PROVIDE OFFSETS AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO

AVOID INTERFERENCE WITH OTHER TRADES. ROUTE ALL PIPING AS HIGH AS

POSSIBLE.

N. COORDINATE FINAL LOCATIONS OF NEW PIPING AND PLUMBING FIXTURES WITH

EXISTING SYSTEMS, STRUCTURE, LIGHTING, ARCHITECTURAL ELEMENTS,

DUCTWORK, PIPING AND SPRINKLERS.

O. REFER TO PLUMBING DETAILS FOR ACCESSORIES AND FINAL CONNECTIONS TO

PLUMBING EQUIPMENT.

P. PROVIDE DRAIN VALVES WITH CAPPED HOSE END CONNECTIONS AT THE

BOTTOM OF EACH RISER AND AT ALL LOW POINTS IN EACH PRESSURE PIPING

SYSTEM. VERIFY WITH ACCESS PANEL LOCATIONS.

Q. PROVIDE SLEEVES AT EACH PENETRATION OF FIRE AND SMOKE RATED

ASSEMBLIES AND SEAL WITH INTUMESCENT MATERIAL.

R. CONNECT PIPE AND EQUIPMENT HANGERS TO TOP CHORD OF ROOF JOISTS,

BEAM FLANGES OR CONCRETE FLOOR DECK BY APPROVED MEANS.

S. FOR PLUMBING PIPE SIZES, SEE RISER DIAGRAMS.

T. ALL LAVATORIES AND HAND SINKS SHALL HAVE THERMOSTATIC MIXING VALVES

BELOW THE SINKS TO MAINTAIN A MAXIMUM HOT WATER TEMPERATURE OF 110

DEGREES F. MIXING VALVE SHALL BE A WATTS SERIES LFUSG-B LEAD FREE OR

EQUAL.

U. REBALANCE THE BUILDING RECIRCULATED HOT WATER SYSTEM UPON

COMPLETION OF NEW WORK. PROVIDE NEW, OR ADDITIONAL RECIRC. PUMP AS

REQUIRED FOR A COMPLETE AND WORKING BUILDING CIRCULATED HOT WATER

SYSTEM.

V. PROVIDE ISOLATION SHUT-OFF VALVES ON ALL PIPE RUNOUTS FROM MAINS TO

PATIENT ROOMS ,FROM MAINS TO SINGLE PLUMBING FIXTURES, AND WEREVER

SHOWN ON PLANS AND RISERS.

W. FIELD VERIFY ALL NEW WATER, WASTE, AND VENT CONNECTIONS, AND PROVIDE

NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING SYSTEMS.

X. PITCH UNDERFLOOR SANITARY WASTE PIPING AT 1/4" PER FOOT, UNLESS

NOTED OTHERWISE.

Y. WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"

MINIMUM.

Z. PROVIDE CLEANOUTS IN ACCESSIBLE LOCATIONS AT THE BASE OF ALL

PLUMBING RISERS.

SCALE: 1/8" = 1'-0"1 LEVEL 1 PLUMBING PLAN. AREA L, PHASE 3

KEYNOTE LEGEND

KEY DESCRIPTION

PP05 PROVIDE SOLENOID SHUT OFF VALVE ON EACH HOT AND COLD WATER LINE THAT

SERVES AN INDIVIDUAL PATIENT ROOM. THE SOLENOID VALVE SHALL BE

CONTROLLED BY A USER PROGRAMMABLE TOUCH SCREEN DIGITAL MONITOR

LOCATED IN A PANEL BACK IN THE NURSES STATION.

PP07 CONNECT TO EXISTING MINIMUM 3" COLD WATER MAIN. VERIFY SIZE AND LOCATION

OF EXISTING PIPING.

PP08 CONNECT TO EXISTING MINIMUM 2" HOT WATER MAIN. VERIFY SIZE AND LOCATION

OF EXISTING PIPING.

PP09 CONNECT TO EXISTING MINIMUM 1-1/2" RECIRCULATED HOT WATER MAIN. VERIFY

SIZE AND LOCATION OF EXISTING PIPING.

PP10 CONNECT NEW SANITARY VENTS TO EXISTING VENT RISER. VERIFY SIZE AND

LOCATION OF EXISTING RISER.

PP11 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURNS . BALANCE

FLOW TO .25 GPM

PP14 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURN MAIN. BALANCE

TO 3.5 GPM

PP15 PROVIDE BALANCE VALVE ON RECIRCULATED HOT WATER RETURN MAIN. BALANCE

TO 1.75 GPM

PP16 1/2" CW DOWN TO ICE/WATER DISPENSER. STUB OUT OF WALL AND PROVIDE BALL

VALVE, BACKFLOW PREVENTER AND WATER FILTER.

PP17 PROVIDE 3/4" COPPER DRAIN FROM ICE/WATER DISPENSER DRAIN CONNECTION

DOWN TO FUNNEL FLOOR DRAIN BELOW COUNTER. PROVIDE 1" MINIMUM AIR GAP.

CME

Professional Engineer I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

Signature: ______________________________________ Typed or printed name: Chad Michael Eslinger Date: ___________ License Number: 4871001/07/2021

S

S

S

SS

S

S

SS

S

S

S

S

S

S

1.0

GPM

1.0

GPM

2"HW

1-1/2"HW1-1/2"HW

2"HW

3/4"HWR

3/4"HWR

1"HW

3/4"HWR

MINNEAPOLIS VAMC BLDG. 70 Specification 618-17-127

RENOVATE MH WARD 1L,1H AND 1K Section No. 07 21 13

4-02-21

07 27 26 - 1

SECTION 07 27 26

FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Fluid-applied vapor-permeable air barrier at exterior above grade wall assemblies.

2. Connection to adjacent air barrier components providing a durable, continuous, full building air barrier.

1.2 RELATED WORK

A. Section 01 45 29 TESTING LABORATORY SERVICES: General Quality Assurance and Quality Control Requirements.

B. Section 01 91 00 GENERAL COMMISSIONING REQUIREMENTS: Commissioning of building envelope components.

C. Section 04 20 00 UNIT MASONRY: Masonry Unit Air Barrier Substrates.

D. Section 07 92 00, JOINT SEALANTS: Joint Sealants.

E. Division 08 sections for glazed aluminum curtain walls

F. Section 09 29 00 GYPSUM BOARD: Wall Sheathings Air Barrier Substrates.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. Air Barrier Association of America (ABAA):

Quality Assurance Program.

C. ASTM International (ASTM):

C920-18.................Elastomeric Joint Sealants.

C1193-16................Use of Joint Sealants.

D412-16.................Vulcanized Rubber and Thermoplastic

Elastomers-Tension.

E96/E96M-16.............Water Vapor Transmission of Materials.

E162-16.................Surface Flammability of Materials Using a

Radiant Heat Energy Source.

E783-02(2018)...........Field Measurement of Air Leakage Through

Installed Exterior Windows and Doors.

E1186-17................Air Leakage Site Detection in Building

Envelopes and Air Barrier Systems.

E2178-13................Air Permanence of Building Materials.

07 27 26 - 2

E2357-18................Determining Air Leakage of Air Barrier

Assemblies.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

1. Show size, configuration, and fabrication and installation details.

B. Manufacturer's Literature and Data:

1. Description of each product.

2. Installation instructions.

1.5 QUALITY ASSURANCE

A. Coordinate work with adjacent and related work to provide continuous, unbroken, durable air barrier system.

B. Manufacturer Qualifications:

1. Regularly and presently manufactures specified products.

2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.

C. Installer Qualifications:

1. Regularly and presently installs specified products.

2. Approved by manufacturer.

1.6 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.7 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight, conditioned facility.

B. Protect products from damage during handling and construction operations.

1.8 FIELD CONDITIONS

A. Environment:

1. Work Area Ambient Temperature Range: 4 to 32 degrees C (40 to

90 degrees F) continuously, beginning 48 hours before installation.

2. Surface Requirements: visibly dry, and complying with manufacturer's instructions.

07 27 26 - 3

1.9 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 SYSTEM PERFORMANCE

A. Air-Barrier Assembly Air Leakage: Maximum 0.2 L/s/square meter

(0.04 cfm/square feet) of surface area at 75 Pa (1.57 psf) differential pressure when tested according to ASTM E2357.

B. Provide full system of compatible materials under conditions of service and application required. Compatibility based on testing by material manufacturer.

C. Perform as continuous vapor permeable air barrier and moisture drainage plane.

D. Transition to adjacent flashings and discharge water to building exterior.

E. Accommodate substrate movement and seal expansion and control joints, construction material transitions, opening transitions, penetrations, and perimeter conditions without moisture deterioration and air leakage exceeding performance requirements.

2.2 PRODUCTS - GENERAL

A. Provide air barrier system components from one manufacturer.

2.3 AIR BARRIER

A. Fluid-Applied, Vapor-Permeable Membrane Air Barrier:

1. Elastomeric, modified bituminous or synthetic polymer membrane.

2. Air Permeance: ASTM E2178: 0.02 L/s/square meter

(0.004 cfm/square feet) of surface area at 75 Pa (1.57 psf) differential pressure.

3. Vapor Permeance: ASTM E96/E96M: Minimum 580 ng/Pa/s/square meter

(10 perms).

4. Elongation: Ultimate, ASTM D412, Die C: 200 percent, minimum.

5. Thickness: Minimum 1.0 mm (40 mils) dry film thickness, applied in single continuous coat.

6. Surface Burning Characteristics: When tested according to ASTM E84.

a. Flame Spread Rating: 25 maximum.

b. Smoke Developed Rating: 450 maximum.

07 27 26 - 4

2.4 ACCESSORIES

A. Primer: Waterborne primer complying with VOC requirements, recommended air barrier manufacturer to suit application.

B. Counterflashing Sheet: Modified bituminous, minimum 1.0 mm (40 mils) thick, self-adhering composite sheet consisting of minimum 0.8 mm

(33 mils) of rubberized asphalt laminated to polyethylene film.

C. Substrate Patching Material: Manufacturer's standard trowel-grade filler material.

D. Sprayed Polyurethane Foam Sealant: Foamed-in-place, 24 to 32 kg/cu. m

(1.5 to 2.0 pcf) density, with maximum flame-spread index of 25 when tested according to ASTM E84.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

B. Protect existing construction and completed work from damage.

C. Correct substrate deficiencies:

1. Remove projections and excess materials and fill voids with substrate patching material.

2. Remove contaminants capable of affecting subsequently installed product's performance.

D. Prepare and treat substrate joints and cracks according to ASTM C1193 and membrane air barrier manufacturer's instructions.

3.2 INSTALLATION - AIR BARRIER

A. Install products according to manufacturer's instructions.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Apply primer.

C. Install transition strips and accessory materials.

D. Seal air barrier to adjacent components of building air barrier system.

E. At penetrations, seal transition strips around penetrating objects with termination mastic.

1. Fill gaps at perimeter of penetrations with sprayed polyurethane foam sealant.

F. At top of through-wall flashings, seal with continuous transition strip of manufacturer's recommended material to suit application.

07 27 26 - 5

G. Apply air barrier in full contact with substrate to produce continuous seal with transitions.

H. Apply fluid membrane in thickness recommended by manufacturer, and minimum specified thickness.

I. Leave air barrier exposed until tested and inspected and approved by

Contracting Officer’s Representative.

3.3 FIELD QUALITY CONTROL

A. Field Inspections and Tests: Performed by testing laboratory specified in Section 01 45 29, TESTING LABORATORY SERVICES.

1. Perform inspections and tests before concealing air barrier with subsequent work.

B. Inspection:

1. Compatibility of materials within air barrier system and adjacent materials.

2. Suitability of substrate and support for air barrier.

3. Suitability of conditions under which air barrier is applied.

4. Adequacy of substrate priming.

5. Application and treatment of joints and edges of transition strips, flexible opening transitions, and accessory materials.

6. Continuity and gap-free installation of air barrier, transition strips, and accessory materials.

C. Submit inspection and test reports to Contracting Officer’s

Representative within seven calendar days of completing inspection and test.

D. Defective Work:

1. Correct deficiencies, make necessary repairs, and retest as required to demonstrate compliance with specified requirements.

3.4 CLEANING

A. Remove masking materials.

B. Clean spills and overspray using cleaning agents recommended by manufacturers of affected construction.

3.5 PROTECTION

A. Protect air barrier from construction operations.

B. Protect air barrier from exposure to UV light exposure exceeding manufacturer's recommendation.

C. Replace overexposed materials and retest.

07 27 26 - 6

- - E N D - -

RENOVATE MH WARD 1L,1H,AND 1K Section No. 28 05 00

10-18

Issued For Construction 28 05 13 - 1

SECTION 28 05 13

CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies the finishing, installation, connection, testing and certification the conductors and cables required for a fully functional for electronic safety and security (ESS) system.

1.2 RELATED WORK

A. Section 01 00 00 - GENERAL REQUIREMENTS. For General Requirements.

B. Section 07 84 00 - FIRESTOPPING. Requirements for firestopping application and use.

C. Section 28 05 00 – COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND

SECURITY. Requirements for general requirements that are common to more than one section in Division 28.

D. Section 28 05 26 - GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND

SECURITY. Requirements for personnel safety and to provide a low impedance path for possible ground fault currents.

E. Section 28 05 28.33 - CONDUITS AND BOXES FOR ELECTRONIC SECURITY AND

SAFETY. Requirements for infrastructure.

F. Section 28 08 00 - COMMISSIONING OF ELECTRONIC SAFETY AND SECURITY

SYSTEMS. Requirements for commissioning.

G. Section 31 20 00 - EARTH MOVING. For excavation and backfill for cables that are installed in conduit.

1.3 DEFINITIONS

A. BICSI: Building Industry Consulting Service International.

B. EMI: Electromagnetic interference.

C. IDC: Insulation displacement connector.

D. Ladder Cable Tray: A fabricated structure consisting of two longitudinal side rails connected by individual transverse members

(rungs).

E. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote-control and signaling power-limited circuits.

F. Open Cabling: Passing telecommunications cabling through open space

(e.g., between the studs of a wall cavity).

G. RCDD: Registered Communications Distribution Designer.

H. Solid-Bottom or Nonventilated Cable Tray: A fabricated structure consisting of integral or separate longitudinal side rails, and a bottom without ventilation openings.

I. Trough or Ventilated Cable Tray: A fabricated structure consisting of integral or separate longitudinal rails and a bottom having openings sufficient for the passage of air and using 75 percent or less of the plan area of the surface to support cables.

J. UTP: Unshielded twisted pair.

1.4 QUALITY ASSURANCE

A. See section 28 05 00, Paragraph 1.4.

1.5 SUBMITTALS

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES, furnish the following:

1. Manufacturer's Literature and Data: Showing each cable type and rating.

2. Certificates: Two weeks prior to final inspection, deliver to the

Resident Engineer/COTR four copies of the certification that the material is in accordance with the drawings and specifications and diagrams for cable management system.

Issued For Construction 28 05 13 - 2

3. Shop Drawings: Cable tray layout, showing cable tray route to scale, with relationship between the tray and adjacent structural, electrical, and mechanical elements. Include the following:

a. Vertical and horizontal offsets and transitions.

b. Clearances for access above and to side of cable trays.

c. Vertical elevation of cable trays above the floor or bottom of ceiling structure.

d. Load calculations to show dead and live loads as not exceeding manufacturer's rating for tray and its support elements.

e. System labeling schedules, including electronic copy of labeling schedules that are part of the cable and asset identification system of the software specified in Parts 2 and 3.

4. Wiring Diagrams. Show typical wiring schematics including the following:

a. Workstation outlets, jacks, and jack assemblies.

b. Patch cords.

c. Patch panels.

5. Cable Administration Drawings: As specified in Part 3

"Identification" Article.

6. Project planning documents as specified in Part 3.

7. Maintenance Data: For wire and cable to include in maintenance manuals.

1.6 APPLICABLE PUBLICATIONS

A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by the basic designation only.

B. American Society of Testing Material (ASTM):

D2301-04................Standard Specification for Vinyl Chloride

Plastic Pressure Sensitive Electrical

Insulating Tape

C. Federal Specifications (Fed. Spec.):

A-A-59544-08............Cable and Wire, Electrical (Power, Fixed

Installation)

D. National Fire Protection Association (NFPA):

70-11...................National Electrical Code (NEC)

E. Underwriters Laboratories, Inc. (UL):

44-05...................Thermoset-Insulated Wires and Cables

83-08...................Thermoplastic-Insulated Wires and Cables

467-07..................Electrical Grounding and Bonding Equipment

486A-03.................Wire Connectors and Soldering Lugs for Use with

Copper Conductors

486C-04.................Splicing Wire Connectors

486D-05.................Insulated Wire Connector Systems for

Underground Use or in Damp or Wet Locations

486E-00.................Equipment Wiring Terminals for Use with

Aluminum and/or Copper Conductors

493-07..................Thermoplastic-Insulated Underground Feeder and

Branch Circuit Cable

514B-04.................Fittings for Cable and Conduit

1479-03.................Fire Tests of Through-Penetration Fire Stops

1.7 DELIVERY, STORAGE, AND HANDLING

A. Test cables upon receipt at Project site.

1. Test optical fiber cable to determine the continuity of the strand end to end. Use optical loss test set.

Issued For Construction 28 05 13 - 3

2. Test optical fiber cable on reels. Use an optical time domain reflectometer (OTDR) to verify the cable length and locate cable defects, splices, and connector; include the loss value of each.

Retain test data and include the record in the maintenance data.

3. Test each pair of UTP cable for open and short circuits.

1.8 PROJECT CONDITIONS

A. Environmental Limitations: Do not deliver or install UTP, optical fiber, and coaxial cables and connecting materials until wet work in spaces is complete and dry, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.

PART 2 - PRODUCTS

2.1 GENERAL

A. General: All cabling locations shall be in conduit systems as outlined in Division 28 unless a waiver is granted in writing or an exception is noted on the construction drawings.

B. Support of Open Cabling: NRTL labeled for support of Category 6 cabling, designed to prevent degradation of cable performance and pinch points that could damage cable.

1. Support brackets with cable tie slots for fastening cable ties to brackets.

2. Lacing bars, spools, J-hooks, and D-rings.

3. Straps and other devices.

C. Cable Trays:

1. Cable Tray Materials: Metal, suitable for indoors, and protected against corrosion by electroplated zinc galvanizing, complying with

ASTM B 633, Type 1, not less than 0.000472 inch (0.012 mm) thick.

2. Basket Cable Trays: 6 inches (150 mm) wide and 2 inches (50 mm) deep. Wire mesh spacing shall not exceed 2 by 4 inches (50 by 100 mm).

3. Trough Cable Trays: Nominally 6 inches (150 mm) wide.

4. Ladder Cable Trays: Nominally 18 inches (455 mm) wide, and a rung spacing of 12 inches (305 mm).

5. Channel Cable Trays: One-piece construction, nominally 4 inches

(100 mm) wide. Slot spacing shall not exceed 4-1/2 inches (115 mm) o.c.

6. Solid-Bottom Cable Trays: One-piece construction, nominally 12 inches (305 mm) wide. Provide with solid covers.

D. Conduit and Boxes: Comply with requirements in Division 28 Section

"Conduits and Backboxes for Electrical Systems." Flexible metal conduit shall only be used in lengths less than 3 feet.

1. Outlet boxes shall be no smaller than 2 inches (50 mm) wide, 3 inches (75 mm) high, and 2-1/2 inches (64 mm) deep.

2.2 BACKBOARDS

A. Backboards: Plywood, fire-retardant treated, 3/4 by 48 by 96 inches

(19 by 1220 by 2440 mm). Comply with requirements for plywood backing panels in Division 06 Section "Rough Carpentry".

2.3 UTP CABLE

A. Description: 100-ohm, 4-pair UTP, formed into 25-pair binder groups covered with a blue thermoplastic jacket.

1. Comply with ICEA S-90-661 for mechanical properties.

2. Comply with TIA/EIA-568-B.1 for performance specifications.

3. Comply with TIA/EIA-568-B.2, Category 6.

4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70 for the following types:

Issued For Construction 28 05 13 - 4

a. Communications, General Purpose: Type CM or CMG.

b. Communications, Plenum Rated: Type CMP, complying with NFPA 262.

c. Communications, Riser Rated: Type CMR, complying with UL 1666.

d. Communications, Limited Purpose: Type CMX.

e. Multipurpose: Type MP or MPG.

f. Multipurpose, Plenum Rated: Type MPP, complying with NFPA 262.

g. Multipurpose, Riser Rated: Type MPR, complying with UL 1666.

2.4 UTP CABLE HARDWARE

A. UTP Cable Connecting Hardware: IDC type, using modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of the same category or higher.

B. Duress buttons shall use Orange colored Category 6 cable and shall terminate in a Security System Control Panel. Unused pairs shall be neatly coiled and supported at or near the Security System Control

Panel. Confirm location of Security System Control Panel with VA COR.

2.5 OPTICAL FIBER CABLE

A. Description: Multimode, 50/125-micrometer, minimum 6-fiber, tight buffer, optical fiber cable.

1. Comply with ICEA S-83-596 for mechanical properties.

2. Comply with TIA/EIA-568-B.3 for performance specifications.

3. Comply with TIA/EIA-492AAAA-B or TIA/EIA-492AAAA-A as applicable for detailed specifications.

4. Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444, UL 1651, and NFPA 70 for the following types:

a. General Purpose, Nonconductive: Type OFN or OFNG.

b. Plenum Rated, Nonconductive: Type OFNP, complying with NFPA 262.

c. Riser Rated, Nonconductive: Type OFNR, complying with UL 1666.

d. General Purpose, Conductive: Type OFC or OFCG

e. Plenum Rated, Conductive: Type OFCP, complying with NFPA 262.

f. Riser Rated, Conductive: Type OFCR, complying with UL 1666.

5. Conductive cable shall be steel armored type.

6. Maximum Attenuation: 3.50 dB/km at 850 nm; 1.5 dB/km at 1300 nm.

7. Minimum Modal Bandwidth: 160 MHz-km at 850 nm; 500 MHz-km at 1300 nm.

B. Jacket:

1. Jacket Color: Aqua for 50/125-micrometer cable.

2. Cable cordage jacket, fiber, unit, and group color shall be according to TIA/EIA-598-B.

3. Imprinted with fiber count, fiber type, and aggregate length at regular intervals not to exceed 40 inches (1000 mm).

2.6 OPTICAL FIBER CABLE HARDWARE

A. Cable Connecting Hardware: Meet the Optical Fiber Connector

Intermateability Standards (FOCIS) specifications of TIA/EIA-604-2, TIA/EIA-604-3-A, and TIA/EIA-604-12. Comply with TIA/EIA-568-B.3.

1. Quick-connect, simplex and duplex, Type SC connectors. Insertion loss shall be not more than 0.75 dB.

2. Type SFF connectors may be used in termination racks, panels, and equipment packages.

2.7 COAXIAL CABLE

A. General Coaxial Cable Requirements: Broadband type, recommended by cable manufacturer specifically for broadband data transmission applications. Coaxial cable and accessories shall have 75-ohm nominal impedance with a return loss of 20 dB maximum from 7 to 806 MHz.

B. RG-11/U: NFPA 70, Type CATV.

1. No. 14 AWG, solid, copper-covered steel conductor.

Issued For Construction 28 05 13 - 5

2. Gas-injected, foam-PE insulation.

3. Double shielded with 100 percent aluminum polyester tape and 60 percent aluminum braid.

4. Jacketed with sunlight-resistant, black PVC or PE.

5. Suitable for outdoor installations in ambient temperatures ranging from minus 40 to plus 85 deg C.

C. RG59/U: NFPA 70, Type CATVR.

1. No. 20 AWG, solid, silver-plated, copper-covered steel conductor.

2. Gas-injected, foam-PE insulation.

3. Triple shielded with 100 percent aluminum polyester tape and 95 percent aluminum braid; covered by aluminum foil with grounding strip.

4. Color-coded PVC jacket.

D. RG-6/U: NFPA 70, Type CATV or CM.

1. No. 16 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.

2. Double shielded with 100 percent aluminum-foil shield and 60 percent aluminum braid.

3. Jacketed with black PVC or PE.

4. Suitable for indoor installations.

E. RG59/U: NFPA 70, Type CATV.

1. No. 20 AWG, solid, copper-covered steel conductor; gas-injected, foam-PE insulation.

2. Double shielded with 100 percent aluminum polyester tape and 40 percent aluminum braid.

3. PVC jacket.

F. RG59/U (Plenum Rated): NFPA 70, Type CMP.

1. No. 20 AWG, solid, copper-covered steel conductor; foam fluorinated ethylene propylene insulation.

2. Double shielded with 100 percent aluminum-foil shield and 65 percent aluminum braid.

3. Copolymer jacket.

2.8 COAXIAL CABLE HARDWARE

A. Coaxial-Cable Connectors: Type BNC, 75 ohms.

2.9 RS-232 CABLE

A. Standard Cable: NFPA 70, Type CM.

1. Paired, 2 pairs, No. 22 AWG, stranded (7x30) tinned copper conductors.

2. Polypropylene insulation.

3. Individual aluminum foil-polyester tape shielded pairs with 100 percent shield coverage.

4. PVC jacket.

5. Pairs are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper drain wire.

6. Flame Resistance: Comply with UL 1581.

B. Plenum-Rated Cable: NFPA 70, Type CMP.

1. Paired, 2 pairs, No. 22 AWG, stranded (7x30) tinned copper conductors.

2. Plastic insulation.

3. Individual aluminum foil-polyester tape shielded pairs with 100 percent shield coverage.

4. Plastic jacket.

5. Pairs are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper drain wire.

6. Flame Resistance: Comply with NFPA 262.

Issued For Construction 28 05 13 - 6

2.10 RS-485 CABLE

A. Standard Cable: NFPA 70, Type CM.

1. Paired, 2 pairs, twisted, No. 22 AWG, stranded (7x30) tinned copper conductors.

2. PVC insulation.

3. Unshielded.

4. PVC jacket.

5. Flame Resistance: Comply with UL 1581.

B. Plenum-Rated Cable: NFPA 70, Type CMP.

1. Paired, 2 pairs, No. 22 AWG, stranded (7x30) tinned copper conductors.

2. Fluorinated ethylene propylene insulation.

3. Unshielded.

4. Fluorinated ethylene propylene jacket.

5. Flame Resistance: NFPA 262, Flame Test.

2.11 LOW-VOLTAGE CONTROL CABLE

A. Paired Lock Cable: NFPA 70, Type CMG.

1. 1 pair, twisted, No. 16 AWG, stranded (19x29) tinned copper conductors.

2. PVC insulation.

3. Unshielded.

4. PVC jacket.

5. Flame Resistance: Comply with UL 1581.

B. Plenum-Rated, Paired Lock Cable: NFPA 70, Type CMP.

1. 1 pair, twisted, No. 16 AWG, stranded (19x29) tinned copper conductors.

2. PVC insulation.

3. Unshielded.

4. PVC jacket.

5. Flame Resistance: Comply with NFPA 262.

C. Paired Lock Cable: NFPA 70, Type CMG.

1. 1 pair, twisted, No. 18 AWG, stranded (19x30) tinned copper conductors.

2. PVC insulation.

3. Unshielded.

4. PVC jacket.

5. Flame Resistance: Comply with UL 1581.

D. Plenum-Rated, Paired Lock Cable: NFPA 70, Type CMP.

1. 1 pair, twisted, No. 18 AWG, stranded (19x30) tinned copper conductors.

2. Fluorinated ethylene propylene insulation.

3. Unshielded.

4. Plastic jacket.

5. Flame Resistance: NFPA 262, Flame Test.

2.12 CONTROL-CIRCUIT CONDUCTORS

A. Class 1 Control Circuits: Stranded copper, Type THHN-THWN, in raceway complying with UL 83.

B. Class 2 Control Circuits: Stranded copper, Type THHN-THWN, in raceway complying with UL 83.

C. Class 3 Remote-Control and Signal Circuits: Stranded copper, Type TW or TF, complying with UL 83.

2.13 FIRE ALARM WIRE AND CABLE

A. General Wire and Cable Requirements: NRTL listed and labeled as complying with NFPA 70, Article 760.

B. Signaling Line Circuits: Twisted, shielded pair, size as recommended by system manufacturer.

Issued For Construction 28 05 13 - 7

1. Circuit Integrity Cable: Twisted shielded pair, NFPA 70, Article

760, Classification CI, for power-limited fire alarm signal service

Type FPL. NRTL listed and labeled as complying with UL 1424 and UL

2196 for a 2-hour rating.

C. Non-Power-Limited Circuits: Solid-copper conductors with 600-V rated, 75 deg C, color-coded insulation.

1. Low-Voltage Circuits: No. 16 AWG, minimum.

2. Line-Voltage Circuits: No. 12 AWG, minimum.

3. Multiconductor Armored Cable: NFPA 70, Type MC, copper conductors, Type TFN/THHN conductor insulation, copper drain wire, copper armor with red identifier stripe, NTRL listed for fire alarm and cable tray installation, plenum rated, and complying with requirements in

UL 2196 for a 2-hour rating.

2.14 IDENTIFICATION PRODUCTS

A. Comply with UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers.

2.15 SOURCE QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to evaluate cables.

B. Factory test UTP and optical fiber cables on reels according to

TIA/EIA-568-B.1.

C. Factory test UTP cables according to TIA/EIA-568-B.2.

D. Factory test multimode optical fiber cables according to TIA/EIA-526-

14-A and TIA/EIA-568-B.3.

E. Factory sweep test coaxial cables at frequencies from 5 MHz to 1 GHz.

Sweep test shall test the frequency response, or attenuation over frequency, of a cable by generating a voltage whose frequency is varied through the specified frequency range and graphing the results.

F. Cable will be considered defective if it does not pass tests and inspections.

G. Prepare test and inspection reports.

2.16 WIRE LUBRICATING COMPOUND

A. Suitable for the wire insulation and conduit it is used with, and shall not harden or become adhesive.

B. Shall not be used on wire for isolated type electrical power systems.

2.17 FIREPROOFING TAPE

A. The tape shall consist of a flexible, conformable fabric of organic composition coated one side with flame-retardant elastomer.

B. The tape shall be self-extinguishing and shall not support combustion.

It shall be arc-proof and fireproof.

C. The tape shall not deteriorate when subjected to water, gases, salt water, sewage, or fungus and be resistant to sunlight and ultraviolet light.

D. The finished application shall withstand a 200-ampere arc for not less than 30 seconds.

E. Securing tape: Glass cloth electrical tape not less than 0.18 mm

(7 mils) thick, and 19 mm (3/4 inch) wide.

PART 3 - EXECUTION

3.1 INSTALLATION OF CONDUCTORS AND CABLES

A. Comply with NECA 1.

B. General Requirements for Cabling:

1. Comply with TIA/EIA-568-B.1.

2. Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices."

3. Install 110-style IDC termination hardware unless otherwise indicated.

Issued For Construction 28 05 13 - 8

4. Terminate all conductors; no cable shall contain un-terminated elements. Make terminations only at indicated outlets, terminals, and cross-connect and patch panels.

5. Cables may not be spliced. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, and terminals.

6. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIM, "Cabling Termination Practices"

Chapter. Install lacing bars and distribution spools.

7. Do not install bruised, kinked, scored, deformed, or abraded cable.

Do not splice cable between termination, tap, or junction points.

Remove and discard cable if damaged during installation and replace it with new cable.

8. Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not be used for heating.

9. Pulling…

This is the start of the file's text. The full file is on GovTribe.