Renovate Mental Health Inpatient Ward Project Addendum 1.docx

DOCX document 504 KB Posted

Attached to
Z1DA--Renovate MH Ward 1L, 1H and 1K - Minneapolis VAMC
Solicitation number
36E77620R0050
Issued by

About this file

This document contains an addendum and related federal contract opportunity. The addendum provides revisions to architectural, civil, mechanical, electrical, low voltage, and specification elements of the Renovate Mental Health Inpatient Ward Project at the Minneapolis VAMC. Revisions include adding drawings and scope of work, phasing revisions, retrofitting doors, revising wall ratings and door hardware, and adding anti-ligature covers to wireless access points.

The related federal contract opportunity is a solicitation for the Design-Bid-Build renovation of Mental Health Wards 1L, 1H and 1K at the Minneapolis VAMC. The solicitation will be issued as a Request for Proposal to SDVOSB concerns only and awarded as a single, firm-fixed price contract. The period of performance is approximately 790 calendar days with a magnitude of construction between $10-20 million. The solicitation is scheduled for issue on February 4, 2020.

View the file

Other files

File Type Posted
36E77620R0050 0009.docx DOCX document
R4-A702.pdf PDF
Revision Set 4 - Narrative.pdf PDF
R4-A701.pdf PDF
Technical Questions Spreadsheet.pdf PDF
R4-A703.pdf PDF
VA Addendum-Revision Set 3.pdf PDF
36E77620R0050 0008.docx DOCX document
Construction Wage Rates - Hennepin County - 1.1.20.pdf PDF
1K Rec Area Utility Plan.pdf PDF
1K Landscape plan.pdf PDF
Technical Questions Spreadsheet.xlsx XLSX spreadsheet
Exterior Site Plan_Dumpster_Laydown.pdf PDF
4-4-2021 Combined Documents Addendum 2.pdf PDF
VA Pre-Bid Addendum 2 Revision Set 2.pdf PDF
36E77620R0050 0007.docx DOCX document
Technical Question Tracking Sheet.pdf PDF
4-4-2021 VA Addendum 2.Attachments.pdf PDF
23 07 11.pdf PDF
4-4-2021 VA Addendum 2.Narrative.pdf PDF
Renovate Inpatient Mental Health Project 618-17-127 Exterior Modifications.pdf PDF
36E77620R0050 0006.docx DOCX document
01 45 00 Quality Control.pdf PDF
36E77620R0050 0005.docx DOCX document
083313 Coiling Counter Doors.pdf PDF
Technical Question Tracking Sheet.docx DOCX document
Q 26 crafted plank oak grove.pdf PDF
36E77620R0050 0004.docx DOCX document
S05 -Technical Question Tracking Sheet.docx DOCX document
Minneapolis Mental Health Site Visit Sign-In.pdf PDF
36E77620R0050 0003.pdf PDF
36E77620R0050 0001.docx DOCX document
36E77620R0050 0002.docx DOCX document
ATTACHMENT 6 - 2018-27 MSP IPMH Renovation Specifications Vol 1 and Vol 2.pdf PDF
ATTACHMENT 1 - VAMH-618-17-127 CD SET_1.pdf PDF
ATTACHMENT 5 - VAMH-618-17-127 CD SET_5.pdf PDF
ATTACHMENT 3 - VAMH-618-17-127 CD SET_3.pdf PDF
ATTACHMENT 7 - Contractor Safety _ Env Record Form.docx DOCX document
36E77620R0050.docx DOCX document
ATTACHMENT 2 - VAMH-618-17-127 CD SET_2.pdf PDF
ATTACHMENT 4 - VAMH-618-17-127 CD SET_4.pdf PDF
ATTACHMENT 8 - Construction Wage Rates - Hennepin County - 1.1.20.pdf PDF
ATTACHMENT 6 - 2018-27 MSP IPMH Renovation Specifications Vol 1 and Vol 2 - 2-1-21.pdf PDF
ATTACHMENT 9 - Brand Name JA - Minneapolis.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

List of Addendum Items for Project 618-17-127 Renovate Mental Health Inpatient Ward

Civil Revision Items

1. Add VA drawings and scope of work to 1K exercise yard to contract documents.

Phasing Revision

1. Delete installation of door C1-57F and associated temp wall during phase 1 and 2, install during phase 3. Omit Card Reader shown on LV sheets.

2. Install construction barrier as noted below during phase 2 work. Complete the remainder of the finishes update in corridor C1-76 and C1-65 in multiple short phases to ensure access to area L through these corridors during phase 2. Limited complete corridor shutdown during off hours(8PM to 5AM) are acceptable to replace corridor flooring and ceilings and demolish cross corridor walls, etc.

3. Retrofit phase 1 sally port door with auto operator. Door should match inner sally port door in function and capability.

Architectural Revision Items:

Sheet G101 Revise wall rating at MSA room 1H-110B:

Sheet A701

1. Door 1K-118 to have frame type 6.

2. Door C1-61D Hardware Group to change to HW-12C

3. Door 1L-108 Hardware Group to change to 12H.1. Add 45 Minute Rating.

4. Door 1H-110E Hardware Group to change to HW-1Y. Add 45 Minute Rating.

5. Door C1-64 add 45 Minute Rating

6. Door 1L-106 add 45 Minute Rating

7. Door 1L-140 add 45 Minute Rating

8. Door C1-57C add 45 Minute Rating

9. Door 1K-120 add 45 Minute Rating

10. Door C1-67 add 45 Minute Rating Sheet A702

1. Change glass type for windows W4, W7 and W21 to rated glass. More info to come in future addendum.

Sheet AF002

1. Add note in rooms C1-313 and 314 that existing paint and tile needs to be matched at wall infills.

Low Voltage Revision Items General Note

1. Add general note that all existing and new wireless access points of all types, need to be outfitted with Anti-ligature covers in all areas.

Sheet LV101

1. Add note- Phase 3 nurse call, camera and staff assist systems to be temporarily installed during phase 1 for use during phase 2. Systems to be salvaged for reinstallation during phase 3. Confirm layout of each temp system with COR.

Sheet LV 102

1. Add CR Symbol on Corridor side of MD Office Door 1H-111 Sheet LV 103

1. Add WB symbol at rooms 1K-104, 1K-105 and 1K-106

2. Delete CR symbol at room 1K-119

3. Add interior and exterior CR symbol at door 1K-118 Sheet LV 104

1. Add interior CR symbol at doors 1L-110 and 1L-112

2. Add CR symbol on corridor C1-57 side of doors C1-60B and C1-59B

3. Add CR symbol on C1-60 side of door C1-60A

4. Add CR symbol on C1-59 side of C1-59A. Add DA symbol for door C1-59A.

5. Add note for remote release button RI at High Acuity Nurse Station for door C1-59A.

6. Add CR Symbol for door C1-57C on corridor C1-57 side.

7. Add DH Symbol in room 1L-140 Mechanical Items

1. Add general note H requiring all Duct mains to remain will be cleaned.

2. Room 1H-110B is to be fed from AHU 70.AHU.07.

Electrical

1. Copy note 16 from sheet EP106-P3 on power for Pneumatic Tube Station and add to sheet EP104-P2 Work Room 1H-110A

2. “Greyed” outlets at the new nurses station desk on sheet EP102-P1 are new and to be provided and installed with new desk.

3. Note that new VFD and Motor are to be install/connected for return air fan, reuse existing circuits. Missing note missing from sheet EP103-P2

4. Room 1H-110B on sheet FA100 is to be included with area L not area K.

Specifications

87100

Hardware Group HW-12C

1. Delete the following as noted:

Add the following:

HW-12C

Each Pair Integrated Double Egress Doors to Have:
RATED
1 Steel Frame
-

1 Integrated Pair Doors w/Elec Exit Exit Devices Q2331 x TYPE 8 (E04) ELECTRIC EXIT DEVICES (F01)

2 Continuous Hinges
A51031B
Electric Power Transfer
EPT 10
1 Overlapping Astragal with SelfAdhesive Seal
R5Y634 x R0E154 x THRUBOLTS
1 Set SelfAdhesive Seals
R0E154

2 Key Switch

Power, wiring, conduit, and fire alarm connection by Division 26.

Power transfer shared by electric panic and reactivation sensor wiring (reactivation sensors provided by Section 08 71 13).

Auto door operator and controls by Section 08 71 13, AUTOMATIC DOOR OPERATORS.

Key switch to allow 1 door to open at a time with key.

Hardware Group HW-12H.1

1. Provide hold open closers for doors C1-59A and C1-60A.

2. No Card Readers required for door 1L-108

088000

Fire Rated glazing is required for doors in rated walls and windows. Add rated glass type for windows W4, W7 and W21 and for glass in all rated doors. More info to come in future addendum.

149200

Pneumatic Tube Stations are to be removed and reinstalled. New stations are not needed as the existing stations were recently upgraded.

image3.png image4.emf image5.emf image1.emf image2.emf image6.jpeg