This document provides details for the renovation of the Mental Health Ward 1L, 1H and 1K at the Minneapolis Veterans Affairs Medical Center. The project includes general construction, demolition, structural, civil, mechanical, plumbing, electrical work and low voltage systems to renovate the specified areas. The solicitation will be issued as a Request for Proposal set aside for Service-Disabled Veteran-Owned Small Businesses with a NAICS code of 236220 and size standard of $39.5 million. The period of performance is expected to be approximately 790 calendar days from notice to proceed. The magnitude of construction is estimated between $10-20 million. The solicitation is anticipated to be issued on or around February 4, 2020 and all questions must be submitted in writing to the specified email.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 | P a g e
VA Project: Renovate MH Ward 1L, 1H, and 1K
VA Project #: 618-17-127
VA Addendum Items: Anderson Revision Set 2 Date: April 5, 2021
DRAWING REVISIONS
Revise drawing sheets listed below as follows:
Architectural
A101-P1 – Add an additional 25’ for handrail HR-1 to existing corridor C1-64A. Coordinate specific location of additional handrail with COR.
Mechanical
MP101-P1 – MECHANICAL PIPING PLANS – LEVEL 1 – AREA L – PHASE 1; Add General Note 10. All thermostats located in patient areas shall be anti-ligature type.
MP1012-P2 – MECHANICAL PIPING PLANS – LEVEL 1 – AREA K – PHASE 2; Add General Note 10. All
MP104-P3 – MECHANICAL PIPING PLANS – LEVEL 1 – AREA L – PHASE 3; Add General Note 10. All
MH-601 – MECHANICAL SCHEDULES; VAV Terminal Unit Schedule, disregard reference to 30% PG in heating water solution. Heating water contains no glycol.
Electrical
ED101-P1 – ELECTRICAL LIGHTING DEMOLITION AREA L PHASE 1
Demolish exit sign located outside room 1L-123 in C1-59 and exit signs in C1-57. Replace with XA fixture.