This attachment is a technical design document consisting of mechanical engineering drawings and specifications prepared by McFarland Johnson for the New Hampshire Department of Administrative Services, Division of Public Works, and the New Hampshire Department of Corrections. The document outlines boiler heating system repairs and emergency domestic hot water (DHW) heating operation modifications for the New Hampshire Correctional Facility for Women (NHCFW) located at 42 Perimeter Road, Concord, New Hampshire. The project scope includes installation of 3-inch and 4-inch hot water supply (HWS) and hot water return (HWR) piping, isolation valves, balancing valves, and modifications to the building's direct digital controls (DDC) system to enable emergency DHW operation from the existing building hot water heating loop. Key components specified include two fully modulating hot water boilers (B-1 and B-2, each with 2,702 MBH input and 2,508 MBH output at 30 PSI), four secondary circulating pumps (P-1A, P-1B, P-2A, P-2B) with variable frequency drives, and a domestic water heating unit (DWH-1) with 3,373 MBH input. The document includes an enlarged mechanical equipment room plan and HVAC schematic with detailed keyed notes. Two scope items were deleted via addendum, and one water meter was deleted via addendum, with the addendum dated July 24, 2024.
The technical specifications detail the existing heating sequence of operation incorporating a lead/lag cascade control scheme to minimize boiler operation and maintain hot water supply temperature between 140 degrees Fahrenheit at 0 degrees outside air temperature and 110 degrees Fahrenheit at 60 degrees outside air temperature. The emergency DHW sequence requires manual activation through the existing Building Management System to enable both secondary loop pumps with differential pressure modulation. Primary pump control includes independent boiler circulating pump operation with modulated speed to maintain minimum temperature difference across heat exchangers, while secondary pump control utilizes remote differential pressure transmitters to maintain system differential pressure as two-way valves operate. The boiler control system incorporates automatic lead boiler rotation every seven days, with provisions for manual operator selection and automatic bypass of powered-down or tripped boilers. All control modifications require Building Management System programming and coordination with the existing boiler plant controller to maintain system stability and operational efficiency.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4444 12121212
ACACACAC
ABABABAB
7777 10101010
PROVIDE
3" HWR
4" HWS
4" HWR (E)
3/4" HWS (E)
3/4" HWR (E)
4" HWS (E)
4" HWS (E)
2" HWS (E)
3" HWS (E)
3" HWR (E)
4" HWR (E)
PROVIDE
3" HWS
2" HWS (E)
53 REGIONAL DRIVE
CONCORD, NEW HAMPSHIRE 03301
TEL (603) 225-2978
FAX (603) 225-0095
www.mjinc.com
PLACE STAMP HERE SHEET:
DESCRIPTION
REVISIONS
No DATE
OF
JOHN O. MORTON BUILDING
7 HAZEN DRIVE BOX 483 ROOM 250
CONCORD, NEW HAMPSHIRE 03302-0483
(603) 271-3516 FAX(603) 271-3515
DRAWN BY: SCALE: DATE:ENGINEER/ARCHITECT: DESIGNED BY: APPROVED BY: CHECKED BY:
MCFARLAND JOHNSON
STATE OF NEW HAMPSHIRE
DEPARTMENT OF ADMINISTRATIVE SERVICES
DIVISION OF PUBLIC WORKS DESIGN & CONSTRUCTION
McFarland Johnson
PROJECT No:
CONTRACT:
MJ Project No: 1/4" = 1'-0"DEN PP PP PP 02/06/2024
81309
B
New Hampshire Correctional Facility for Women (NHCFW) Boiler
Heating System Repairs
42 Perimeter Rd, Concord, NH 03301
NH DEPARTMENT OF CORRECTIONS
M-300
ENLARGED MECHANICAL ROOM PLAN
3 418888.14
SCALE: 1/4" = 1'-0"1 ENLARGED MECHANICAL EQUIPMENT ROOM PLAN
KEYED NOTES
DEMO EXISTING 4" HWS LINE AS NECESSARY AND PROVIDE A 4x4x3 TEE.
DEMO EXISTING 4" HWR LINE AS NECESSARY AND PROVIDE A 4x4x3 TEE.
DEMO EXISTING 3" HWS LINE AS NECESSARY AND PROVIDE A 3x3x3 TEE.
DEMO EXISTING 3" HWR LINE AS NECESSARY AND PROVIDE A 3x3x3 TEE.
PROVIDE 3" BALANCING VALVE AND BALANCE TO 144 GPM.
PROVIDE 3" SHUTOFF VALVE (N.C.)
SCOPE OF WORK
1. EMERGENCY DOMESTIC HOT WATER (DHW) HEATING OPERATION:
A. PROVIDE A 3" HWS AND A 3" HWR LINE FROM THE EXISTING BUILDING HOT WATER HEATING
LOOP TO THE EXISTING DOMESTIC WATER HEATING LOOP.
B. PROVIDE 3" ISOLATION VALVES THAT WILL BE MANUALLY OPERATED IN THE EVENT OF AN
EMERGENCY.
C. PROVIDE BALNCING VALVE ON THE 3" HWR LINE.
D. MODIFY DDC CONTROLS AS NOTED IN THE REVISED SEQUENCE OF OPERATION ON M-500.
2. SCOPE ITEM DELETED VIA ADDENDUM.
3. SCOPE ITEM DELETED VIA ADDENDUM.
1 Addendum 2 07/24/2024
B
B
P
HC
P
1A
P
1B
AS
ET
P
2A
P
2B
TO EXISTING BUILDING LOADS
FROM EXISTING BUILDING LOADS
2" HWR (E)
HX
F R
O M
E X
IS
T
IN
G
D H
W
R E
C
IR
C L
O O
P
T O
E X
IS
T
IN
G
D
C
IR
C L
O O
P
VFD
VFD
VFD
VFD
3" HWR (E)
PS
3" HWS
3" HWR
DHW
SHUT OFF
VALVE N.C.
(TYP)
3" HWS (E)
P-2A GPM: 155 P-2B GPM: 155
P-1B GPM: 300
P-1A GPM: 300
B-1 MBH:
IN: 2702 @ 30 PSI
OUT: 2508
B-2 MBH:
IN: 2702 @ 30 PSI
OUT: 2508
4" HWR (E)
4" HWS (E)
3" HWS (E)3" HWR (E)
4" HWR (E)
3" HWS (E)
3" HWR (E)
1"
4" HWS (E)
4" HWS (E)
4" HWS (E)
DWH-1 MBH:
IN: 3373
BALANCING
VALVE
BALANCE
AT 144 GPM
4" HWR (E)4" HWS (E)
2" HWS (E) 2" HWR (E)
HX
F R
O M
E X
IS
T
IN
G
D
C
IR
C L
O O
P
T O
E X
IS
T
IN
G
D
C
IR
C L
O O
P
2" HWS (E)
RP
RP-4 GPM: 144RP
RP-3 GPM: 144
WATER METER DELETED
VIA ADDENDUM
53 REGIONAL DRIVE
CONCORD, NEW HAMPSHIRE 03301
TEL (603) 225-2978
FAX (603) 225-0095
www.mjinc.com
PLACE STAMP HERE SHEET:
DESCRIPTION
REVISIONS
No DATE
OF
JOHN O. MORTON BUILDING
7 HAZEN DRIVE BOX 483 ROOM 250
CONCORD, NEW HAMPSHIRE 03302-0483
(603) 271-3516 FAX(603) 271-3515
DRAWN BY: SCALE: DATE:ENGINEER/ARCHITECT: DESIGNED BY: APPROVED BY: CHECKED BY:
MCFARLAND JOHNSON
STATE OF NEW HAMPSHIRE
DEPARTMENT OF ADMINISTRATIVE SERVICES
DIVISION OF PUBLIC WORKS DESIGN & CONSTRUCTION
McFarland Johnson
PROJECT No:
CONTRACT:
MJ Project No: NOT TO SCALEDEN PP PP PP 02/06/2024
81309
B
New Hampshire Correctional Facility for Women (NHCFW) Boiler
Heating System Repairs
42 Perimeter Rd, Concord, NH 03301
NH DEPARTMENT OF CORRECTIONS
M-500
HVAC SCHEMATIC
4 418888.14
SCALE: NOT TO SCALE1 HEATING SYSTEM SCHEMATIC
EXISTING HEATING SEQUENCE OF OPERATION (FOR REFERENCE):EXISTING HEATING SEQUENCE OF OPERATION (FOR REFERENCE):EXISTING HEATING SEQUENCE OF OPERATION (FOR REFERENCE):EXISTING HEATING SEQUENCE OF OPERATION (FOR REFERENCE):
A. GENERAL
1. THE EXISTING BOILER HOT WATER CONTROL SYSTEM COORDINATES THE OPERATION OF TWO FULLY MODULATING HOT WATER BOILERS
AND THEIR ASSOCIATED BOILER PRIMARY CIRCULATING PUMPS IN ORDER TO MAINTAIN HOT WATER SUPPLY (HWS) TEMPERATURE AT
SETPOINT.
2. THE BUILDING MANAGEMENT SYSTEM (BMS) CONTROLS THE SECONDARY PUMPS, PROVIDES PLANT ENABLE/DISABLE CONTROL, HWS
TEMPERATURE SETPOINT, AND OA RESET CONTROL OUTPUTS TO THE BOILER PLANT CONTROLLER. THE BMS MONITORS BOILER OPERATION
AND DISPLAYS BOILER STATUS AT THE USER'S WORKSTATION.
B. APPLICATION
1. BOILER BURNER CONTROL: WITH THE BOILER CONTROL SYSTEM BMS INTERFACE SET TO ACTIVE, THE MODULATION OF THE BOILER IS
CONTROLLED THROUGH A 0-10V OR 4-20 MA DC (AS REQUIRED BY THE BOILER) BMS INPUT. THE BMS MONITORS THE HWS SYSTEM
TEMPERATURE AND COMPARES IT TO THE ACTIVE SETPOINT TO ESTABLISH A TARGET BOILER FIRING RATE. IF AN INDIVIDUAL BOILER
OUTLET TEMPERATURE EXCEEDS A PRE-SET MAXIMUM SETPOINT, THAT BOILER'S FIRING RATE SHALL BE AUTOMATICALLY CUT BACK BY A PID
LOOP TO PREVENT A HIGH TEMPERATURE TRIP. MODULATION SIGNALS ARE ELECTRICALLY ISOLATED CHANNEL-CHANNEL AND CHANNEL-
GROUND.
2. HOT WATER SUPPLY (HWS) TEMPERATURE SETPOINT: WHEN THE BOILER CONTROL SYSTEM BMS INTERFACE IS SET TO (ACTIVE), THE BMS
CALCULATES AN OUTSIDE AIR TEMPERATURE RESET SETPOINT. WHEN IN (INACTIVE) MODE THE OPERATOR MAY SET THE HWS
TEMPERATURE VIA THE FRONT PANEL DISPLAY.
3. TEMPERATURE RESET SCHEDULE:
a. HWS=140 DEG. F AT 0 DEG. F OUTSIDE AIR TEMPERATURE.
b. HWS=110 DEG F AT 60 DEG. F OUTSIDE AIR TEMPERATURE.
C. BOILER SEQUENCE:
1. THE BOILER CONTROL SYSTEM INCORPORATES A (LEAD/LAG) CASCADE CONTROL SCHEME FOR OPERATION. THE CONTROLLER UTILIZES
BOTH HWS TEMPERATURE, AS SENSED AT TS-1, AND BOILER FIRING RATE PERCENT TO START AND STOP THE BOILERS AND MINIMIZE THE
TOTAL NUMBER OF BOILERS IN OPERATION. THE CONTROLLER STARTS AND STOPS BOILERS WHEN THE HWS TEMPERATURE IS OUTSIDE THE
ADJUSTABLE TEMPERATURE LIMIT FOR LONGER THAN THE ADJUSTABLE TIME DELAY.
2. IN ORDER TO MINIMIZE HEADER TEMPERATURE DEVIATIONS THE CONTROL SYSTEM STARTS AND STOPS THE NEXT BOILER WHEN THE "LEAD"
BOILER IS AT AN ADJUSTABLE FIRING RATE LIMIT FOR LONGER THAN THE ADJUSTABLE TIME DELAY. THE CONTROL SYSTEM MONITORS BOTH
BOILER LOCKOUT AND LIMIT CIRCUITS TO AUTOMATICALLY SKIP OVER BOILERS THAT ARE POWERED DOWN FOR MAINTENANCE, TRIPPED OR
OTHERWISE WILL NOT START.
3. THE LEAD BOILER EITHER AUTOMATICALLY ROTATES EVERY 7 DAYS OR IS MANUALLY SELECTED BY THE OPERATOR.
4. THE BOILER RUNS AT LOW FIRE FOR WARM-UP FOR A PRESET LOW FIRE HOLD TIME. THE CONTROL SYSTEM REDUCES THE FIRING RATE TO A
MINIMUM BEFORE STOPPING A BOILER TO PREVENT ACCUMULATION OF FUEL IN THE FURNACE.
D. BOILER PRIMARY PUMP SEQUENCE: (P-2A, P-2B):
1. THE BOILER CONTROL SYSTEM INCLUDES INDEPENDENTLY OPERATED PRIMARY WATER PUMP CONTROL. ON A CALL FOR HEAT, THE BOILER
CONTROL SYSTEM CONFIRMS GAS PRESSURE AT GAS HIGH AND LOW PRESSURE SWITCHES, AND SENDS A SIGNAL TO THE ASSOCIATED
CIRCULATING PUMP TO START. FLOW IS PROVEN AT THE FLOW SWITCH PRIOR TO BOILER FIRING. PRIMARY PUMPS SHALL OPERATE
WHENEVER THE ASSOCIATED BOILER IS FIRING.
2. PUMP SPEED IS MODULATED FROM A 0-10V SYSTEM OUTPUT TO MAINTAIN A MIMINUM TEMPERATURE DIFFERENCE ACROSS THE HEAT
EXCHANGER. THE SYSTEM MUST KEEP AT LEAST ONE PUMP RUNNING TO ENSURE WATER IS ALWAYS MOVING PAST THE HEADER
TEMPERATURE SENSOR. THERE ARE AVAILABLE SEQUENCES TO WARM UP COLD BOILERS, AND ADJUSTABLE COOL DOWN PERIOD AFTER THE
BOILER HAS STOPPED. THE PUMP STOPS IMMEDIATELY IF ANY TRIPS OCCUR DURING PRE-PURGE, PILOT, OR MAIN FLAME TRIAL FOR
IGNITION.
E. SECONDARY PUMP CONTROL (P-1A & 1B)
1. THE LEAD SECONDARY CIRCULATING PUMP RUNS CONTINUOUSLY WHEN THE HEATING PLANT IS ENABLED. A REMOTE DIFFERENTIAL
PRESSURE TRANSMITTER IS CONNECTED TO THE SUPPLY AND RETURN LINES. PUMP VFD MODULATES AS REQUIRED TO MAINTAIN SYSTEM
DIFFERENTIAL PRESSURE AS 2-WAY VALVES OPEN AND CLOSE.
2. IF THE LEAD PUMP CANNOT MAINTAIN SECONDARY SYSTEM PRESSURE DIFFERENTIAL, IT MODULATES OFF AND BOTH THE LEAD AND LAG
PUMPS MODULATE ON SIMULTANEOUSLY TO MAINTAIN SYSTEM DP.
3. IF BOTH PUMPS ARE AT MINIMUM VFD SPEED AND THE SYSTEM DP IS ABOVE SETPOINT, THE LAG PUMP IS DE-ENERGIZED AND THE LEAD
PUMP IS MODULATED TO MAINTAIN SETPOINT.
4. THE SCHEDULE AUTOMATICALLY ROTATES THE LEAD/LAG PUMPS.
5. THE PUMPS ARE MONITORED AND ALARMED IF ONE OF THEM FAILS. IF THE LEAD PUMP FAILS, THE LAG PUMP IS ENERGIZED.
EMERGENCY DOMESTIC WATER HEATING OPERATION:
A. GENERAL:
1. IN THE EVENT OF DOMESTIC HOT WATER FAILURE THE MAINTENANCE STAFF SHALL BE ABLE TO MANUALY ENABLE AN
EMERGENCY DOMESTIC HOT WATER MODE THROUGH THE EXSITING BUILDING MANAGEMENT SYSTEM (BMS).
2. CONTRACTOR SHALL PROVIDE PROGRAMING AND CONTROL DEVICES NECESSARY TO IMPLEMENT THE SEQUENCE
DESCRIBED HEREIN.
B. EMERGENCY DOMESTIC HOT WATER (DHW) SEQUENCE:
1. WHEN THE EMERGENCY DHW SEQUENCE IS ACTIVATED, THE BMS SHALL ENABLE BOTH SECONDARY LOOP PUMPS (P-1A & P-1B).
2. THE LEAD PUMP SHALL RUN CONTINUOUSLY AND THE PUMP VFD SHALL MODULATE THE PUMP TO MAINTAIN THE
DIFFERENTIAL PRESSURE (DP) SETPOINT.
3. IF THE PUMP IS UNABLE TO MAINTAIN THE SETPOINT, BOTH PUMPS SHALL BE STARTED AND THEIR SPEED WILL MODULATE VIA THEIR RESPECTIVE VFDs. BOTH PUMPS SHALL RUN AT THE SAME SPEED.
4. IF BOTH PUMPS ARE AT MINIMUM VFD SPEED AND THE SYSTEM DP IS ABOVE SETPOINT, THE LAG PUMP IS DE-ENERGIZED
AND THE LEAD PUMP IS MODULATED TO MAINTAIN SETPOINT.
1 Addendum 2 07/24/2024
| Sheets |
| M-300 - ENLARGED MECHANICAL ROOM PLAN |
| M-500 - HVAC SCHEMATIC |
| Sheets |
| M-300 - ENLARGED MECHANICAL ROOM PLAN |
| M-500 - HVAC SCHEMATIC |