This document contains a mechanical schedule and specifications for a Cyber Operations Facility project. Key details include mechanical equipment to be provided such as water source heat pumps, air handlers, fans, pumps, cooling towers, and electric boilers. It also includes specifications for air distribution devices including diffusers, grilles, and registers. The project is solicited under solicitation number W91236-21-B-2013 issued by the Department of the Army Corps of Engineers Engineering District Norfolk for an Invitation for Bid. The schedule provides requirements for equipment capacity, electrical characteristics, and installation notes.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A I
N I
G
RI
VFOHTLAE
W
N O
M M
O C
P R
O F
E
SS I ONAL ENG
I N E
E R
BRANDON E. WOOD
Lic. No. 35155
08/15/2019
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
W -1
-D
-0
W S
P
B
E N
D
IX
R O
A D
S U
IT
E
V
IR
G
IN
IA
B
E A
C H
V
A
UNCLASSIFIED\\FOR OFFICIAL USE ONLY
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
N O
R F
O L K
D
IS
T R
IC
T
N O
R F
O L K
V
A
DATE & TIME STAMP:
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
H E
L M
S A
V E
J B
L E
C Y
B E
R O
P S
F A
C
IL
IT
Y
RTA SUBMITTAL9/12/2019 10:27:24 AM
M-602
S C
H E
D U
L E
S
D e s ig n e r
A u th o r
C h e c k e r
/1
/2
M U
H J
C M
T
2. PROVIDE VERTICAL DIAPHRAGM TYPE EXPANSION TANK WITH FLOOR SKIRT, PRE-CHARGE TO 12 PSIG.
1. PROVIDE CENTRIFUGAL TYPE AIR SEPARATOR WITH HIGH CAPACITY AIR VENT.
NOTES:
CONDENSER WATER AS-1 228 5 4 ET-1 8.0 2.4 12" 20" SEE NOTES
SYSTEM TAG G.P.M. P.D. FT. SIZE TAG (GAL.) CAPACITY (GAL.) DIAMETER HEIGHT REMARKS
MAX. CAPACITY ACCEPTED APPROX. APPROX.
AIR SEPARATOR EXPANSION TANK
AIR CONTROL SCHEDULE
1. PROVIDE WITH INTEGRAL TAMPER RESISTANT THERMOSTAT, INTEGRAL ELECTRICAL DISCONNECT AND BLOWER.
NOTES:
EUH-1 400 3300 12 277 1 SEE NOTES
TAG CFM WATTS MBH VOLTS PHASE REMARKS
NOMINAL
ELECTRIC UNIT HEATER SCHEDULE
2. PROVIDE EF-1 WITH ELECTRONIC SPEED CONTROLLER. RF-1 SHALL BE CONTROLLED BY VFD.
1. PROVIDE INLINE FANS WITH CHATTERPROOF BDD, INTEGRAL ELECTRIC DISCONNECT, DUCT FLANGES, AND 4 POINT VIBRATION HANGER SYSTEM.
NOTES:
RF-1 127 - MECH INLINE 1715 1.50 DIRECT 1 208 3 SQ SEE NOTES
EF-1 127 - MECH INLINE 575 0.50 DIRECT 1/6 208 1 SQ SEE NOTES
TAG LOCATION FAN TYPE C.F.M. (IN. WG.) DRIVE H.P. VOLTS PHASE NO. REMARKS
E.S.P. ELECTRICAL DATA MODEL
FAN SCHEDULE
2. PROVIDE UNITS WITH HOSE KIT, 4-POINT SUSPENSION MOUNTING KIT WITH VIBRATION ISOLATION (HORIZONTAL DUCTED UNIT ONLY), AND MANUFACTURER'S PUMPING PACKAGE SIZED TO MATCH FLOW AND PRESSURE DROP REQUIREMENTS OF EACH HEAT PUMP (INCLUDING HOSE/VALVE KIT).
1. UNIT TYPE: HD = HORIZONTAL DUCTED, VC=VERTICAL CONSOLE.
NOTES:
WAHP-11 VC 390 - 0.3 3.0 9.3 9.2 74.2 61.8 13.6 13.5 85 94.1 12.6 69.7 9.5 55 48.7 0.08 7.0 15 277 1 11.0 SEE NOTES
WAHP-10B HD 2160 460 0.3 15.0 47.5 41.8 70.5 60.4 72.5 13.0 85 94.7 65.0 66.8 49.7 55 48.4 1 12.5 20 480 3 16.0 SEE NOTES
WAHP-10A HD 2160 460 0.3 15.0 47.5 41.8 70.5 60.4 72.5 13.0 85 94.7 65.0 66.8 49.7 55 48.4 1 12.5 20 480 3 16.0 SEE NOTES
WAHP-9 HD 430 110 0.3 3.0 10.3 8.1 69.7 60.1 14.2 13.2 85 94.5 13.3 66.2 10.2 55 48.2 0.13 7.0 15 277 1 5.0 SEE NOTES
WAHP-8 HD 460 150 0.3 3.8 10.6 8.0 68.4 59.6 17.1 12.9 85 94.1 16.4 65.2 12.5 55 48.4 0.13 8.7 15 277 1 6.0 SEE NOTES
WAHP-7 HD 1140 230 0.3 9.0 27.5 22.6 70.7 60.5 40.2 13.7 85 93.9 40.6 67.0 31.6 55 48.0 0.5 8.7 15 480 3 6.0 SEE NOTES
WAHP-6 HD 1020 170 0.3 9.0 24.1 20.8 71.4 60.7 39.5 13.7 85 93.8 40.4 67.5 30.9 55 48.1 0.5 8.7 15 480 3 6.0 SEE NOTES
WAHP-5 HD 745 135 0.3 6.0 18.8 15.1 71.1 60.6 28.0 13.6 85 94.3 27.0 67.3 20.5 55 48.2 0.33 13.5 20 277 1 12.0 SEE NOTES
WAHP-4 HD 390 - 0.3 3.0 9.3 9.2 74.2 61.8 14.2 13.2 85 94.5 13.3 66.2 10.2 55 48.2 0.13 7.0 15 277 1 5.0 SEE NOTES
WAHP-3 HD 590 135 0.3 4.5 15.5 11.4 70.2 60.3 21.4 13.0 85 94.5 19.9 66.6 15.3 55 48.2 0.33 11.2 15 277 1 8.0 SEE NOTES
WAHP-2 HD 280 30 0.3 2.3 6.6 6.0 72.5 61.1 10.8 12.4 85 94.6 10.0 68.4 7.7 55 48.2 0.08 4.0 15 277 1 5.0 SEE NOTES
WAHP-1 HD 740 70 0.3 6.0 18.5 16.2 72.7 61.2 28.2 13.6 85 94.4 27.0 68.5 20.3 55 48.2 0.33 5.5 15 480 3 12.0 SEE NOTES
TAG TYPE (NOTE 1) CFM CFM (IN. W.G.) GPM M.B.H. M.B.H. DB WB REJECTION EER (°F) (°F) M.B.H. DB ABSORPTION (°F) (°F) HP MCA MOCP VOLTS PHASE FT. HD. REMARKS
TOTAL AIR E.S.P. TOTAL SENS. EAT OF EWT LWT TOTAL EAT OF EWT LWT FAN EXCHANGER,
OUTSIDE HEAT HEAT DROP THROUGH
FAN DATA COOLING DATA HEATING DATA ELECTRICAL DATA MAX. PRESSURE
WATER SOURCE HEAT PUMP SCHEDULE - WATER TO AIR
3. PROVIDE 4-WAY PATTERN CEILING DIFFUSERS, U.O.N. ON PLANS OR SCHEDULE.
(INCLUDING HEAD OF SCREWS), MAXIMUM NC=25 AT HIGHEST CFM AND PROVIDE SQUARE TO ROUND TRANSITION AS REQUIRED.
2. PROVIDE ALUMINUM DIFFUSERS AND REGISTERS WITH OPPOSED BLADE VOLUME DAMPERS, BAKED STANDARD WHITE ENAMEL FINISH
1. MAXIMUM PRESSURE DROP SHALL INCLUDE VOLUME DAMPER WHERE DAMPER IS PROVIDED.
THE FOLLOWING NOTES ARE TYPICAL UNLESS OTHERWISE NOTED:
Z GRILLE RETURN/EXHAUST 605-1900 22x22 0.02 2'x2' LAY IN, 35° DEFLECTION, 3/4" SPACING
Y GRILLE RETURN/EXHAUST 125-600 12x12 0.02 2'x2' LAY IN, 35° DEFLECTION, 3/4" SPACING
W GRILLE RETURN/EXHAUST 50-120 6x6 0.02 2'x2' LAY IN, 35° DEFLECTION, 3/4" SPACING
V GRILLE RETURN/EXHAUST 380 12x12 0.02 SURFACE MOUNT, 35° DEFLECTION, 3/4" SPACING
U GRILLE RETURN 200 8x8 0.02 18 x 18 MODULE, SURFACE MOUNT, 35° DEFLECTION, 3/4" SPACING
T GRILLE RETURN/EXHAUST 380 12x12 0.02 SURFACE MOUNT, 35° DEFLECTION, 3/4" SPACING
H GRILLE SUPPLY 390 10x10 0.1 SURFACE MOUNT, DOUBLE DEFLECTION, 3/4" BLADE SPACING
G DIFFUSER SUPPLY 825 16"Ø 0.1 2'x2' LAY IN, SQUARE PERFORATED FACE, ADJUSTABLE DISCHARGE
F DIFFUSER SUPPLY 185 8"Ø 0.1 18 x 18 MODULE, SURFACE MOUNT, SQUARE LOUVERED FACE, ADJUSTABLE DISCHARGE
E DIFFUSER SUPPLY 530-725 14"Ø 0.1 2'x2' LAY IN, SQUARE LOUVERED FACE, ADJUSTABLE DISCHARGE
D DIFFUSER SUPPLY 385-525 12"Ø 0.1 2'x2' LAY IN, SQUARE LOUVERED FACE, ADJUSTABLE DISCHARGE
C DIFFUSER SUPPLY 230-380 10"Ø 0.1 2'x2' LAY IN, SQUARE LOUVERED FACE, ADJUSTABLE DISCHARGE
B DIFFUSER SUPPLY 125-225 8"Ø 0.1 2'x2' LAY IN, SQUARE LOUVERED FACE, ADJUSTABLE DISCHARGE
A DIFFUSER SUPPLY 50-120 6"Ø 0.1 2'x2' LAY IN, SQUARE LOUVERED FACE, ADJUSTABLE DISCHARGE
TAG TYPE SERVICE RANGE SIZE A.P.D. REMARKS
C.F.M. NECK MAX.
GRILLE, REGISTER & DIFFUSER SCHEDULE
3. FOR CHP-1/2, PROVIDE INVERTER DUTY RATED MOTOR.
2. PROVIDE NON OVERLOADING PUMP SELECTIONS.
1. PROVIDE NEMA PREMIUM EFFICIENCY MOTORS.
NOTES:
BP-1/2 HEATING HOT WATER INLINE 9 20 1/4 208 1 SEE NOTES
CHP-4 CONDENSER WATER INLINE 100 60 3 460 3 SEE NOTES
CHP-3 CONDENSER WATER INLINE 100 60 3 460 3 SEE NOTES
CHP-2 CONDENSER WATER BASE MOUNTED 228 60 7.5 480 3 SEE NOTES
CHP-1 CONDENSER WATER BASE MOUNTED 228 60 7.5 480 3 SEE NOTES
TAG SERVICE TYPE G.P.M. (FT.) H.P. VOLTS PHASE REMARKS
HEAD ELECTRICAL DATA
PUMP SCHEDULE
7. PROVIDE ALL STAINLESS STEEL CONSTRUCTION AND ELECTRONIC WATER LEVEL CONTROL. PROVIDE EXTERNAL SOLENOID VALVE WHICH SHALL BE INSULATED AND HEAT TRACED.
6. MAX INSTALLED HEIGHT = 12'-0".
5. PROVIDE ALUMINUM LADDER, VIBRATION SWITCH AND ALL STAINLES STEEL CONSTRUCTION.
4. PROVIDE CONTACTOR IN NEMA 4 ENCLOSURE FOR SUMP HEATER.
3. PROVIDE COMBINATION STARTER/DISCONNECT SWITCH IN NEMA 4 ENCLOSURE FOR SPRAY PUMP. PROVIDE OVERSIZED CONTROL TRANSFORMER TO SERVE POSITIVE CLOSURE DAMPER(S) MOTOR.
2. PROVIDE NEMA PREMIUM EFFICIENCY, INVERTER DUTY FAN MOTORS. PROVIDE VFD (WITH INTEGRAL BYPASS) IN NEMA 4 ENCLOSURE FOR FAN MOTOR.
1. PROVIDE WITH SUMP THERMOSTAT AND SUMP HEATER CONTACTOR.
NOTES:
CCC-1 FORCED DRAFT 228 10.0 78 95 85 37,600 30 460 3 345 2 460 3 1 6 460 3 SEE NOTES
(FT. WATER) (°F W.B.) (°F) (°F) C.F.M. H.P. VOLTS PHASE G.P.M. H.P. VOLTS PHASE NO. (EACH) VOLTS PHASE
TAG TYPE G.P.M. MAX. P.D. E.A.T. E.W.T. L.W.T. KW REMARKS
TOWER FAN SPRAY PUMP SUMP HEATER
LOW PROFILE CLOSED CIRCUIT COOLING TOWER SCHEDULE
3. PROVIDE ALL TRIM AND APPURTENANCES RECOMMENDED BY THE MANUFACTURER FOR INDICATED APPLICATION.
2. PROVIDE CONTROL PANEL WITH CONTACTS TO INTERFACE WITH BUILDING DDC CONTROL SYSTEM. PROVIDE BACNET INTERFACE.
1. PROVIDE PACKAGED, SKID MOUNTED, ELECTRIC HOT WATER BOILER COMPLETE WITH VERTICAL 16 GALLON STORAGE VESSEL.
NOTES:
B-1 108 3 369 9.2 5 135 55 131.0 480 3 SEE NOTES
TAG (KW) STAGES (M.B.H.) G.P.M. (FT H20) (ºF) (ºF) F.L.A. VOLTS PHASE REMARKS
INPUT OUTPUT W.P.D. L.W.T. E.W.T. ELECTRICAL DATA
ELECTRIC HOT WATER BOILER SCHEDULE
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
C
C C
-1 S
C H
E D
U L
E R
E V
IS
IO
N
/1
/2