This document is a solicitation for project WAAR152202 to remodel and add to civil engineering building 151 and remodel buildings 119a and 119b at Springfield Air National Guard Base. The project includes mechanical, electrical, plumbing, communications, security, and finish work. The construction duration is 360 calendar days with inspection and punch list. The solicitation is set aside for 8(a) small businesses. The NAICS code is 236220 with a $39.5 million average annual revenue size standard. The pre-bid conference is September 1 and bids are due September 24. Interested contractors must register in SAM and check the website periodically for amendments. The total contract value is estimated between $5-10 million.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P
VFD
MS
MX
RACEWAY SYMBOLS
SURFACE MOUNTED CONDUIT
JUNCTION BOX - CEILING MOUNTED
CONCEALED CONDUIT IN CEILING OR WALL
JUNCTION BOX - WALL MOUNTED
J
J
RECEPTACLE SYMBOLS
DUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT
SIMPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SPECIFIC USE RECEPTACLE. NEMA CONFIGURATIONAS
NOTED ON DRAWINGS AND/OR SCHEDULE.
CEILING MOUNTED DUPLEX RECEPTACLE
DATA/POWER POLE
ABOVE COUNTER DUPLEX RECEPTACLE
C
F FLOOR BOX
60"
RECEPTACLE NOTATIONS:
DENOTES WEATHER PROOF OUTLETSWP
DENOTES GROUND FAULT INTERRUPTER OUTLETSGFCI
DENOTES ELECTRIC WATER COOLER OUTLETSEWC
CORD REELE
DENOTES ISOLATED GROUND OUTLETSIG
SERVICE & DISTRIBUTION SYMBOLS
GROUND ACCESS WELL
GROUND ROD
PANELBOARD
LIGHTNING ROD
EPO EMERGENCY POWER OFF
MOTOR & EQUIPMENT CONNECTION
SYMBOLS
ELECTRICAL CONNECTION TO EQUIPMENT AND MOTORS,
SIZED PER NEC. COORDINATE REQUIREMENTS WITH
CONTRACTOR FURNISHING MOTOR OR EQUIPMENT. REFER
TO SPECIFICATIONS AND EQUIPMENT WIRING SCHEDULE
FOR ADDITIONALWORK ASSOCIATED WITH MOTOR OR
EQUIPMENT.
COMBINATION MAGNETIC CONTROLLER
VARIABLE FREQUENCY MOTOR CONTROLLER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
ATS
MTS
MOTOR STARTING SWITCH WITH OVERLOADS
MOTOR STARTING SWITCH WITHOUT OVERLOADS
AUTOMATIC TRANSFER SWITCH
MANUAL TRANSFER SWITCH
MAGNETIC CONTROLLER - FULL VOLTAGE, ACROSS THE LINE,
ELECTRICALLY HELD
GENERAL SYMBOLS
DETAIL NUMBER / SHEET NUMBER#/E-###
LINE TYPE KEY
EXISTING TO BE REMOVED BY THIS
CONTRACTOR (DARK DASHED LINE)
EXISTING TO REMAIN WORK
(THIN SOLID LINE)
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDER FLOOR BY
THIS CONTRACTOR
ONE-LINE EQUIPMENT ENCLOSURE
SITE UNDERGROUND ELECTRICE
SITE REMOVED UNDERGROUND
ELECTRIC
//E//
SINGLE POLE SWITCH
LUMINAIRE CONTROL SYMBOLS
PHOTO ELECTRIC CONTROL (X REPRESENTS
OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)
OCCUPANCY SENSOR CEILING MOUNT (X REPRESENTS
OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)
DAYLIGHT SENSOR (X REPRESENTS OCCUPANCY/PHOTO
SENSOR SCHEDULE DESIGNATION)
LIGHTING CONTROL PANEL
LUMINAIRE SYMBOLS
RECESSED LUMINAIRE
RECESSED TROFFER
SURFACE ROUND LUMINAIRE
WALL MOUNTED EXIT SIGN
CEILING MOUNTED EXIT SIGN
SURFACE LINEAR
SURFACE COVE STRIP
PENDANT ROUND LUMINAIRE
UL 924 LISTED EMERGENCY LIGHTING BYPASS
CONTROL UNIT
OS X
DS X
PE
LCP
PT
ARROW DENOTES EXIT SIGN CHEVRON
EMERGENCY BATTERY UNIT
SWITCH NOTATIONS:
3 DENOTES 3-WAY SWITCH
4 DENOTES 4-WAY SWITCH
D DENOTES WALL BOX DIMMER SWITCH
K DENOTES KEY SWITCH
WS DENOTES OCCUPANCY SENSOR
P DENOTES PILOT SWITCH
T DENOTES TIMER SWITCH
WL DENOTES WET LOCATION SWITCH
EMERGENCY SHADING MODIFIER
PENDANT LINEAR
PENDANT INDUSTRIAL
WALL SURFACE BRACKET
WALL SURFACE LINEAR
A1
1a
LUMINAIRE TYPE
LUMINAIRE CIRCUITRY & CONTROL KEY:
LOWER CASE LETTER INDICATES SWITCHLEG CONTROL
NUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER
SURFACE INDUSTRIAL
SITE SYMBOLS
ELECTRIC HANDHOLEE
TRANS
ELECTRIC TRANSFORMER
FLOOD LIGHT POLE
BOLLARD LIGHT
DOUBLE LIGHT POLE
LIGHT POLE
DEMOLITION GENERAL NOTES:
THE INFORMATION SHOWN IS BASED ON EXISTING
DRAWINGS AND SITE OBSERVATIONS TO ASSIST
CONTRACTOR IN BIDDING. THE ELECTRICAL DRAWINGS
INDICATE EXISTING ELECTRICAL ITEMS TO BE REMOVED.
THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE
OF WORK REQUIRED AND DO NOT INDICATE EVERY BOX,
CONDUIT, OR WIRE THAT MUST BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE PRIOR TO
SUBMITTING A BID AND VERIFY EXISTING CONDITIONS.
REFER TO SPECIFICATION SECTION 26 05 02 FOR
ADDITIONAL REQUIREMENTS.
DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING
WALLS BEING DEMOLISHED. REFER TO THE
ARCHITECTURAL DEMOLITION PLANS FOR THE EXACT
EXTENT OF WORK REQUIRED BY THIS PROJECT. REMOVE
ALL DEVICES ON DASHED WALLS NOT SHOWN ON THE
CONTRACT DRAWINGS. REFER TO DEMOLITION
DRAWINGS OF OTHER TRADES. WHERE MOTORS
CONTROL PANELS, AND OTHER LOADS OR APPARATUS
THAT HAVE ELECTRICAL CONNECTION ARE BEING
REMOVED, INCLUDE DISCONNECTION AND REMOVAL OF
ALL ASSOCIATED CONDUIT, WIRING, ETC.
ELECTRICAL ITEMS (i.e., LIGHTING FIXTURES, PANELBOARDS, DISCONNECTS, MOTOR CONTROLLERS , ETC.) REMOVED AND NOT RELOCATED REMAIN THE
PROPERTY OF THE OWNER AND SHALL BE TURNED OVER
TO THE OWNER, IN A STORAGE AREA TO BE DESIGNATED
BY THE OWNER. EQUIPMENT BEING REMOVED SHALL BE
HANDLED SO AS NOT TO FURTHER REDUCE ITS VALUE TO
THE OWNER. THE CONTRACTOR SHALL DISPOSE OF
MATERIAL THE OWNER DOES NOT WANT TO REUSE OR
RETAIN FOR MAINTENANCE PURPOSES.
WHERE LIGHTS, SWITCHES, RECEPTACLES, ETC., ARE
BEING REMOVED ALL ASSOCIATED CONDUIT AND WIRE
BACK TO THE PANELBOARD OR FEEDER JUNCTION BOX
SERVING THE DEVICE SHALL ALSO BE REMOVED, UNLESS
THE CONDUIT CAN BE REUSED FOR NEW CONDUCTORS.
THE CONTRACTOR SHALL DISPOSE OF MATERIAL THE
OWNER DOES NOT WANT TO REUSE OR RETAIN FOR
MAINTENANCE PURPOSES.
ALL BOXES THAT REMAIN IN PLACE IN EXISTING MASONRY
WALLS THAT ARE TO REMAIN SHALL BE PROVIDED WITH A
BLANK COVERPLATE. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS ASSOCIATED WITH TYPE AND
ATTACHMENT.
ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE
BEING REMOVED. WHERE CONDUIT IS IN THE CONCRETE
SLAB, CUT OFF FLUSH, PULL OUT WIRE, AND PLUG.
WHERE CONDUIT IS RUN EXPOSED, ALL ASSOCIATED
CLAMPS, SUPPORTS, HANGERS, ETC., SHALL ALSO BE
REMOVED. CONDUIT CONCEALED IN WALL
CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT
AFFECTED BY OTHER CONSTRUCTION.
THIS CONTRACTOR SHALL COORDINATE ALL HIS WORK,
INCLUDING PHASING WITH OTHER CONTRACTORS AT THE
JOB SITE BEFORE REMOVING EXISTING ELECTRICAL AND
INSTALLING NEW ITEMS.
EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED
IN PLACE. RELOCATED EXISTING CONDUIT SHALL NOT BE
ALLOWED. BONDING CONDUCTORS SHALL BE INSTALLED
IN ALL REUSED CONDUIT TO ASSURE PROPER GROUND
PATH.
MAINTAIN CIRCUIT CONTINUITY OF DEVICES LOCATED
OUTSIDE OF CONSTRUCTION AREA. DEVICE AND
EQUIPMENT REMOVAL IN CERTAIN LOCATIONS MAY
REQUIRE THE INSTALLATION OF A JUNCTION BOX TO
RECONNECT CIRCUITS THAT REMAIN IN OPERATION.
EXTEND CONDUIT AND WIRING AS REQUIRED TO MAINTAIN
POWER TO REMAINING EQUIPMENT.
BALLASTS MANUFACTURED PRIOR TO 1980 CONTAIN PCBs
AND SHALL BE DISPOSED OF IN ACCORDANCE WITH
SPECIFICATIONS.
HID AND FLUORESCENT LAMPS CONTAIN MERCURY AND
SHALL BE DISPOSED OF IN ACCORDANCE WITH
SPECIFICATIONS.
CONTRACTOR SHALL REMOVE AND INSTALL ALL CEILING
TILES AS REQUIRED FOR THE EXECUTION OF ELECTRICAL
WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF
CONSTRUCTION. CONTRACTOR SHALL REPLACE CEILING
TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY
THIS CONTRACTOR.
PROVIDE REVISED TYPED CIRCUIT DIRECTORY IN
PANELBOARDS THAT HAVE CIRCUITS REMOVED OR
ADDED CIRCUITS.
REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING
ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING
FINISHES. CUT RACEWAY FLUSH WITH WALLS AND
FLOORS, PATCH SURFACES TO MATCH EXISTING. REMOVE
ALL ASSOCIATED CLAMPS, HANGERS, SUPPORTS, ETC.
ASSOCIATED WITH RACEWAY REMOVAL.
DISCONNECT AND REMOVE ABANDONED LUMINAIRES,
INCLUDING BRACKETS, STEMS, HANGERS, AND OTHER
ACCESSORIES.
DISCONNECT AND REMOVED ELECTRICAL DEVICES AND
EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS
BEEN REMOVED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
REFER TO THE G SERIES DRAWINGS FOR CODE ANALYSIS
PLANS, INFORMATION AND NOTES.
THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE
DETAILS OF WORK, VERIFY DIMENSIONS IN THE FIELD, AND
ADVISE THE CONTRACTING OFFICER OF ANY DISCREPANCY
BEFORE PERFORMING ANY WORK.
THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH
THE ADAAG (AMERICANS WITH DISABILITIES ACT ACCESSIBILITY
GUIDELINES) AND ABA (ARCHITECTURAL BARRIERS ACT).
REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED
WALLS AND FLOORS. MAKE RATED PENETRATIONS AS
REQUIRED. SEAL ALL RATED PENETRATIONS AS IDENTIFIED IN
DIVISION 1 REQUIREMENTS.
FLUSH MOUNT ALL TOGGLE SWITCHES, RECEPTACLE , FIRE
ALARM PULL STATIONS AND FIRE ALARM NOTIFICATION
DEVICES AT HEIGHTS ABOVE FINISHED FLOOR AS SHOWN IN
THE DEVICE MOUNTING HEIGHT DETAIL, EXCEPT WHERE
OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION.
CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL
SCHEDULES PROVIDED. BALANCE THE LOAD ON PANELS AS
EVENLY AS POSSIBLE BETWEEN EACH PHASE. COMMON
NEUTRALS SHALL NOT BE USED FOR BRANCH
CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS
POSSIBLE BETWEEN EACH PHASE.
CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES SHALL
BE RUN IN SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.
A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE
INSTALLED WITH CIRCUIT CONDUCTORS TO ALL RECEPTACLES.
CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING,
ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE
SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS, AND
STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON
BUILDING STRUCTURE. WHERE RACEWAY IS REQUIRED ON
EXISTING CONCRETE AND MASONRY WALLS, SURFACE
RACEWAY MAY BE USED IN LIEU OF CHANNELING WALLS TO
ALLOW CONCEALED ROUTING. THE RACEWAY SHALL BE
SINGLE CHANNEL STYLE TYPE WITH IVORY FINISH. THIS
APPLIES FOR BRANCH CIRCUIT CONDUITS UP TO 3/4" SIZE.
CONDUITS LARGER THAN 3/4" MAY BE ROUTED EXPOSED, BUT
INSTALLED PARALLEL AND/OR PERPENDICULAR TO BUILDING
LINES AND RUN AS UNOBTRUSIVELY AS POSSIBLE.
BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS
SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. "THRU-
THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR
WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
COORDINATE AND CO-LOCATE WALL MOUNTED RECEPTACLE
LOCATIONS WITH TECHNOLOGY (VOICE/DATA,CATV,FIDS, ETC)
OUTLETS SHOWN ON THE T-SERIES DRAWINGS UNLESS
OTHERWISE NOTED, EACH TECHNOLOGY OUTLET SHALL BE
LOCATED WITHIN 24" OF ITS ASSOCIATED RECEPTACLE.
ASSOCIATED RECEPTACLE SHALL BE DEFINED AS THE
RECEPTACLE NEAREST THE LOCATION OF, AND AT THE SAME
HEIGHT AS,THE TECHNOLOGY OUTLET WHEN MULTIPLE
RECEPTACLES ARE SHOWN ON A WALL.
DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS (EWC)
SHALL BE CONCEALED BEHIND WATER COOLER ACCESS PLATE
OR BE DIRECTLY BELOW AND CENTERED ON EWC.
CONTRACTOR SHALL VERIFY TYPE OF EWC TO BE INSTALLED.
CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL
DETECTORS WITH LUMINAIRES, SPRINKLER, AND CEILING
DIFFUSERS. CENTER ALL DEVICES IN CEILING TILE PATTERN.
SMOKE DETECTORS SHALL BE LOCATED NO CLOSER THAN 3
FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR
FURNITURE AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS AND REVIEWED SHOP
DRAWINGS. PRIOR TO ELECTRICAL INSTALLATION THIS
CONTRACTOR SHALL ADJUST RECEPTACLES, OUTLETS OR
CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE
AND/OR EQUIPMENT.
ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE
MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND/OR
ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TECHNOLOGY S EQUIPMENT,
ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL
BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
CONTRACTOR TO PROVIDE SUITABLE MECHANICAL
PROTECTION AROUND ALL CONDUITS STUBBED OUT FROM
FLOORS, WALLS OR CEILINGS DURING CONSTRUCTION TO
PREVENT BENDING OR DAMAGING OF STUB OUTS DUE TO
CARELESSNESS WITH CONSTRUCTION EQUIPMENT.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS
REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO
MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH
WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.
CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING
TILES AS REQUIRED FOR THE EXECUTION OF ELECTRICAL
WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF
CONSTRUCTION. CONTRACTOR SHALL REPLACE CEILING TILES
WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS
CONTRACTOR.
ALL INTERLOCKING REQUIRED BY THE DRIVE MANUFACTURER
BETWEEN THE VARIABLE FREQUENCY DRIVE AND THE
DISCONNECT SWITCHES SHALL BE THE RESPONSIBILITY OF
THE ELECTRICAL CONTRACTOR.
SCCR RATINGS LISTED FOR EQUIPMENT ARE MINIMUM
REQUIREMENTS FOR BUS BRACING AND DEVICE RATING. ALL
EQUIPMENT SHALL BE FULLY RATED UNLESS SPECIFICALLY
NOTED AS SERIES RATED.
ONE-LINE SYMBOLS
AUTOMATIC TRANSFER SWITCH
LOW VOLTAGE CIRCUIT BREAKER
N
L
E
DPM DIGITAL POWER METER
FUSED DISCONNECT SWITCH
GENERATOR
EARTH GROUND
M METER
N NEUTRAL BOND
PANELBOARD (ELEVATION VIEW)
SPD SURGE PROTECTIVE DEVICE
TRANSFORMER
UNINTERRUPTIBLE POWER SUPPLY
(UPS)
UTILITY CONNECTION
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-001
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
N O
T E
S
S Y
M B
O L
S
A B
B R
E V
IA
T
IO
N
S
ELECTRICAL ABBREVIATIONS
3R NEMA 3R RATING
4X NEMA 4X RATING
A AMPERES
A/E ARCHITECT / ENGINEER
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ATS AUTOMATIC TRANSFER SWITCH
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CH CHILLER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CP CIRCULATION PUMP
CRAC COMPUTER ROOM AIR CONDITIONER
CUH CABINET UNIT HEATER
DC DROP CORD
DDC DIGITAL CONTROL PANEL
DISC DISCONNECT
DO DOOR OPERATOR
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ERL EXISTING TO BE RELOCATED
ERLD EXISTING - RELOCATED LOCATION
ETR EXISTING TO REMAIN
EWC ELECTRICAL WATER COOLER
EWH ELECTRICAL WATER HEATER
F FUSED
FA FIRE ALARM
FCU FAN COIL UNIT
FF/W FURNITURE FEED (WALL MOUNTED)
GC GENERAL CONTRACTOR
GFI GROUND FAULT INTERRUPTER
GND GROUND
GWH GAS WATER HEATER
HP HORSEPOWER
HVAC HEATING, VENTILATION, AIR CONDITIONING
HWB HOT WATER BOILER
HWP HOT WATER PUMP
IEWH INSTANTANEOUS ELECTRIC WATER HEATER
IH INFRARED HEATER
IMC INTERMEDIATE METALLIC CONDUIT
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
LBS POUNDS
LFS LIGHTING FIXTURE SCHEDULE
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MIN. MINIMUM
MNS MASS NOTIFICATION SYSTEM
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE
RECPT RECEPTACLE
RF RETURN FAN
RGS RIGID GALVANIZED STEEL CONDUIT
MAY ALSO BE REFERENCED AS RMC OR GRC
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
SE SERVICE ENTRANCE
SF SUPPLY FAN
SP SUMP PUMP
SS STAINLESS STEEL
SW SWITCH
TCP TEMPERATURE CONTROL PANEL
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
VS VERSUS
W WATTS
WH WATER HEATER
WL WET LOCATION LISTED
WP WEATHERPROOF
XFMR TRANSFORMER
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T A
L
TP #1
TP #2
BM #1
BM #2
TP #4
TP #3
BUILDING
MAINTENANCE
GARAGE
CO
E X
IS
T
EXIST 2" PMP GAS
GAS LINE MARKER
EXIST. 2" PMP GAS
8"
6"
APPROXIM
ATE EXIST.20" W
ATER M
AIN
LOCATIO
N
B-6
A-2-3
B-3
B-1
A-2
A-2-2
B-4-1
B-2
B-5
B-2-1
B-2-2
B-4
A-3
A-2-1
D-2
A-3-1
E-1
E-2
APPROXIM
ATE LOCATIO
N EXIST. 6
" S
ANITARY FORCED M
AIN
EXIST. TOP DITCH
EXIST. TOP DITCH
CONC.
C O
N C
ASPH.
ASPH.
ASPH.
EXIST. E
DGE PAVEMENT
ASPH.
ASPH.
CONC.
CONC.
ASPH.
ASPH.
BUILDING ADDITION
BUILDING ADDITION
SEE SHEETS ED101A &
E-101A FOR
CONTINUATION.
EXISTING 125KW
NATURAL GAS GEN SET
480Y/277V, 3-PHASE, 4W
E
E
E
E
E
E
E
E
E
E
E
E
E
EXISTING 300KVA XFMR
480Y/277V, 3-PHASE, 4-WIRE
PAD MOUNTED
TRANSFORMER BY UTILITY.
//E//
//E//
//E//
//E//
//E//
//E//
//E//
EXISTING ATS
200A, 4-POLE
E
E
E
E
E
E
E
E E
E E
E E E E
E
E
E
//E//
//E//
//E//
//E//
E
E
E
E
E
E
E
E
E
9.019
9.0199.019
9.020
9.021
9.020
9.021
9.021
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
/5
/2
:0
:4
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED010
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
S
IT
E P
L A
N
E L
E C
T R
IC
A
L
KEYED NOTES
9.019 INTERCEPT AND REMOVE EXISTING UNDERGROUND
CONDUIT FROM THIS LOCATION BACK TO NEAREST
ACCESSIBLE JUNCTION BOX TO ALLOW FOR BUILDING 151
NEW ADDITION. EXISTING CONDUIT FROM ACCESSIBLE
JUNCTION BOX BACK TO SOURCE SHALL BE RE-USED. REFER
TO KEYED NOTES 9.236 ON SHEET E-010 FOR COORDINATION
AND ADDITIONAL INFORMATION.
9.020 EXISTING UNDERGROUND CONDUIT FROM THIS LOCATION
TO NEAREST EXISTING ACCESSIBLE TERMINATION SHALL
REMAIN. REFER TO KEYED NOTES 9.236 ON SHEET E-010 FOR
COORDINATION AND ADDITIONAL INFORMATION.
9.021 EXISTING BRANCH WIRING FROM NEAREST EXISTING
ACCESSIBLE TERMINATION BACK TO SOURCE SHALL BE
REMOVED. EXISTING WIRING BEING REMOVED SHALL BE
USED TO PULL NEW WIRING IN EXISTING CONDUIT. BRANCH
CIRCUIT BREAKER(S) IN EXISTING PANEL SHALL BE RE-USED.
REFER TO KEYED NOTES 9.327 ON SHEET E-010 FOR
COORDINATION AND ADDITIONAL INFORMATION.
1" = 20'-0"1
DEMO SITE PLAN - ELECTRICAL
10' 20' 40'
SCALE: 1" = 20'
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
C
C
JJ
H
J
K
L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
GFCI, WP
GFCI, WP GFCI, WP
GFCI GFCI
24"
24"
24"
24"
24"
24"
46"
46"
46" 46" 46"46"
E E
1-RH
EF
OHDOHD
MUA
46"
PANEL B1
EF
WELDER
46" 46" LATHE
72"
SHOWS MACH.
52"
52"
24"
OHD
UH-10
EWC
PANEL C1
EF6
OHD OHD
46"
46"
46"
TEST
EF
46" 46"72"
VAV
VAV
EF
CH
E-401
46" 46"
46"CUH
PANEL L1
PANEL EM1
PANEL EM2
SEE SHEET 1/E-401
FOR CONTINUATION.
SEE SHEET ED010
FOR CONTINUATION.
E
E
E
E
DC
E E E E
/1 ED101B
/1 ED101B
CH
CRAC
ACCU
ERL
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:4
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED101A
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A A
P
O W
E R
1/8" = 1'-0"1
DEMO FLOOR PLAN - BUILDING 151 AREA A - POWER
KEYED NOTES
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
F
J J
J J
J
J
J J
J
C
J J J J J
C
A
C
D
E
F
G
H
J
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
GFCI, WP
GFCI, WP
GFCI, WP GFCI, WP
GFCI, WP
GFCI
GFCI
GFCI
66" EWC
46" 46" 46"
AHU-1
46"
46"
EF
46"
VAV
VAV
FF/W
FF/W
FF/W
FF/W
FF/W
FF/W
FF/W
FF/W
FF/W
VAV
VAV
VAV
VAV
VAV
VAV
CH
FT FT
96"
PS
VAV
46"
PS
VAV
96"
VAV
125KW NATURAL GAS GENERATOR
480Y/277V, 3PH, 4W
FF/W
FF/W
FF/W FF/W FF/W TVTV
72" 72"
/1 ED101A
/1 ED101A
PANEL A1
PANEL XL 9.022
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:4
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED101B
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A B
P
O W
E R
KEYED NOTES
9.022 DISCONNECT AND REMOVE EXISTING FEEDER BACK TO
SOURCE. EXISTING CIRCUIT BREAKER SHALL BE TURNED
OFF AND LABELED AS SPARE.
1/8" = 1'-0"1
DEMO FLOOR PLAN - BUILDING 151 AREA B - POWER
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
E
DS-1
PANEL DP-1
48"
48"
48" 48" 48"
9.001
9.011
9.011
9.011 9.011 9.011
9.0119.011
9.0119.011 9.011 9.0119.011
9.011
9.011
9.011
9.0119.0119.0119.011
9.0119.011
AHU
ACCU
48"
48"
GFCI
48"
PANEL B
PANEL A
CUH
48" 48"
48"
48"
48"
72"
48"
48"
48"
48"
48"
48"
48" 48" 48"
48"
DODO
UH UH
DO
EWH
AIR COMPRESSOR
PANEL PUMP
LOAD CENTER
PANEL MDP
MAIN SERVICE DISC.
E
UH
EF
EF
MAU
48"
48"
48" 48"
48"
L5-30
9.016
9.016
9.016
9.016
9.016
EXISTING PULL
BOX ABOVE
DOOR
9.0169.0169.0169.0169.0169.016
9.016
9.016
9.016
9.016
9.0169.016
ACU
ACU
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
2'-8" 5'-4" 10'-8"
SCALE: 3/16" = 1'-0"
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED102
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
F L
O O
R P
L A
N
B U
IL
D
IN
G
S
A
B
P
O W
E R
KEYED NOTES
9.001 EXISTING PANEL 'DP-1' SHALL BE DEMOLISHED. EXISTING PARTIAL FEEDER
SHALL BE REUSED TO SERVE THE NEW 'DP-1' PANEL. REFER TO KEYED
NOTE 9.301 ON SHEET E-102 FOR COORDINATION.
9.011 EXISTING BACKBOX AND PARTIAL CONDUIT SHALL REMAIN TO SERVE TO
NEW BRANCH CIRCUIT AS INDICATED ON SHEET E-102.
9.016 EXISTING BACKBOX, CONDUIT AND BRANCH WIRING SHALL REMAIN TO
SERVE TO NEW DUPLEX RECEPTACLE AS INDICATED ON SHEET E-102.
3/16" = 1'-0"2
DEMO FLOOR PLAN - BUILDING 119A - POWER
3/16" = 1'-0"1
DEMO FLOOR PLAN - BUILDING 119B - POWER
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
H
J
K
L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
WP
PANEL EMA
9.007 9.007 9.0079.007
9.004
9.004
9.004
9.007
9.004
9.008
9.007
ETR ETR ETR
ETR
ETR
ETRETR
ETRETR
ERL
ETR
ETR
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.0039.0039.003
9.0039.003
9.003
/1 ED121B
/1 ED121B
ETR
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:4
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED121A
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A A
L
IG
H
T
IN
G
KEYED NOTES
9.003 DISCONNECT AND REMOVE EXISTING LIGHTING CONTROL
DEVICE(S) AND ASSOCIATED WIRING BACK TO NEAREST
JUNCTION BOX ABOVE ACCESSIBLE CEILING. EXISTING
LIGHTING CONTROL DEVICE BACKBOX AND RACEWAY SHALL
REMAIN FOR RE-USE UNLESS NOTED OTHERWISE.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES AND
ASSOCIATED WIRING BETWEEN LIGHTING FIXTURES TO
NEAREST BACKBOX, UNLESS NOTED OTHERWISE. REFER TO
KEYED 9.206 ON SHEETS E-121A AND E-121B FOR NEW WORK
REQUIREMENTS IN THIS ROOM.
9.004 EXISTING SWITCH AND BACKBOX SHOWN REMOVED AND
BACKBOX NOT RE-USED ON NEW CONSTRUCTION SHALL BE
PROVIDED WITH A BLANK COVER PLATE.
9.007 REMOVE EXISTING RECESSED FIXTURE AND ASSOCIATED
WIRING. MAINTAIN EXISTING BACKBOX AND PARTIAL
CONDUIT FOR NEW FIXTURE INSTALLATION AT THIS
LOCATION.
9.008 REFER TO KEYED NOTE 9.222 ON SHEET E-121A FOR WORK
ASSOCIATED WITH EXISTING LIGHTING CONTROL PANELS.
1/8" = 1'-0"1
DEMO FLOOR PLAN - BUILDING 151 AREA A - LIGHTING
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
D
E
F
G
H
J
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
3 3
9.004
9.0039.003
9.004
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR ETR
ETRETR
ETR ETR
ETR
ETR
ETR
ETR
9.005 9.005
9.005
9.006 (TYP.)
9.004
9.004
9.004
9.0039.003
9.003
9.0039.003 9.0039.003
9.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.0039.003
9.003 9.0039.0039.003
9.0039.003
9.0039.003
9.0039.003
9.004
ETR
/1 ED121A
/1 ED121A
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:4
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED121B
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A B
L
IG
H
T
IN
G
KEYED NOTES
9.003 DISCONNECT AND REMOVE EXISTING LIGHTING CONTROL
DEVICE(S) AND ASSOCIATED WIRING BACK TO NEAREST
JUNCTION BOX ABOVE ACCESSIBLE CEILING. EXISTING
LIGHTING CONTROL DEVICE BACKBOX AND RACEWAY SHALL
REMAIN FOR RE-USE UNLESS NOTED OTHERWISE.
DISCONNECT AND REMOVE EXISTING LIGHT FIXTURES AND
ASSOCIATED WIRING BETWEEN LIGHTING FIXTURES TO
NEAREST BACKBOX, UNLESS NOTED OTHERWISE. REFER TO
KEYED 9.206 ON SHEETS E-121A AND E-121B FOR NEW WORK
REQUIREMENTS IN THIS ROOM.
9.004 EXISTING SWITCH AND BACKBOX SHOWN REMOVED AND
BACKBOX NOT RE-USED ON NEW CONSTRUCTION SHALL BE
PROVIDED WITH A BLANK COVER PLATE.
9.005 EXISTING WIRING SHALL BE REMOVED BACK TO NEAREST
ACCESSIBLE JUNCTION LOCATED ABOVE CEILING. EXISTING
CONDUIT MAY BE RE-USED WHERE EVER FEASIBLE FOR NEW
FIXTURE INSTALLATION. REFER TO KEYED 9.210 ON SHEET
E-121B FOR NEW WORK REQUIREMENTS AT THIS FIXTURE.
9.006 EXISTING BRANCH CIRCUIT AND CONTROL SHALL REMAIN TO
SERVE NEW FIXTURE. REFER TO KEYED 9.214 ON SHEET
E-121B FOR NEW WORK REQUIREMENTS AT THIS FIXTURE.
1/8" = 1'-0"1
DEMO FLOOR PLAN - BUILDING 151 AREA B - LIGHTING
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
OS
OS
OS
WS
PANEL B
PANEL A
WS
PEPE
P E
P E
WP
9.012
9.012 9.012
9.012
9.013
9.013
9.013
9.013
9.013
9.013
(TYP.)
PANEL DP-1
PE
PEPE
PE
MOUNTED TO
UNDERSIDE OF
MEZZANINE FLOOR.
9.012 (TYP.)
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
2'-8" 5'-4" 10'-8"
SCALE: 3/16" = 1'-0"
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED122
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
D E
M O
F L
O O
R P
L A
N
B U
IL
D
IN
G
S
A
B
L
IG
H
T
IN
G
KEYED NOTES
9.012 EXISTING BACKBOX AND PARTIAL CONDUIT SHALL REMAIN TO SERVE TO
NEW EXTERIOR WALL PACK AND BRANCH CIRCUIT AT THIS LOCATION.
9.013 EXISTING PARTIAL CONDUIT SHALL REMAIN TO SERVE NEW SWITCH.
3/16" = 1'-0"1
DEMO FLOOR PLAN - BUILDING 119B - LIGHTING
3/16" = 1'-0"2
DEMO FLOOR PLAN - BUILDING 119A - LIGHTING
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
EXISTING 300KVA XFMR
480Y/277V, 3-PHASE, 4-WIRE
PAD MOUNTED
TRANSFORMER BY UTILITY.
TO SWITCH CENTER 'SC1'
N
L
E
EXISTING ATS
200A, 4-POLE
EXISTING 125KW
NATURAL GAS GEN SET
480Y/277V, 3-PHASE, 4W
MAIN SWITCHBOARD 'MD' - 600A BUS
480/277V-3PH-4W
MINIMUM BREAKER IC RATING = 42,000 RMS
SYM@ 480V
EXISTING 400AS/200AF
FUSED DISCONNECT
60A/3P
SPD
125A/3P
300/3P
DISTRIBUTION PANEL 'DP' - 400A BUS
208/120V-3PH-4W
MINIMUM BREAKER IC RATING = 42,000 RMS
SYM@ 208V
175A/3P
PANEL
L1
200A/3P
AHU1
60A/3P
PANEL
EMA
(7) SPACES
60A/3P
SPD
PANEL
A1
225A/3P
PANEL
B1
225A/3P
PANEL
C1
225A/3P
PANEL
S1
225A/3P 200A/3P
SPARE
30A/3P 60A/3P
UPS
BYBASS
SWITCH
(3) SPACES
30KW
UPS
200A/3P
PANEL
EMB
N
L
E
EXISTING MTS
200A, 3-POLE
EXISTING 200A
FUSED
DISCONNECT
200A/3P
SPARE
200A/3P
MOTOR CONTROL CENTER 'MC1' - 200A BUS
480/277V-3PH-4W
MINIMUM BREAKER IC RATING = 42,000 RMS
SYM@ 208V
7A/3P 15A/3P 10A/3P40A/3P 3A/3P20A/3P
S P
A R
E
20A/3P
S P
A R
E
HWP
7A/3P
HWP
DUST
COLLECTOR
DC
AIR
COMPRESSOR
AC
S P
A R
E
EXHAUST FAN
20A/3P 15A/3P
MAKE-UP AIR
UNIT
200A/3P
PANEL
EM1
PANEL
EM2
S P
A R
E
20A/3P
S P
A R
E
20A/3P
S P
A R
E
7A/3P
EXHAUST FAN
(4) SPACES
62 63
42 42
42 76 77
STORAGE
BUILDING
EXISTING XFMR 'K-13'
SIZE: 75KVA
PRI: 480Y/277V, 3PH, 3W
SEC: 208Y/120V, 3PH, 4W
EXISTING XFMR 'T6'
SIZE: 15KVA
PRI: 480Y/277V, 3PH, 3W
SEC: 208Y/120V, 3PH, 4W
EXISTING XFMR
SIZE: 75KVA
PRI: 480Y/277V, 3PH, 3W
SEC: 208Y/120V, 3PH, 4W
EXISTING 200A
FUSED DISCONNECT
9.023
9.024
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
/5
/2
:0
:4
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
ED701
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
B U
IL
D
IN
G
D
E M
O L
IT
IO
N O
N E
-L
IN
E D
IA
G
R A
M
NO SCALE1
BUILDING 151 DEMOLITION ONE-LINE DIAGRAM
KEYED NOTES
9.023 EXTEND EXISTING SERVICE FEEDERS TO SECONDARY LUGS
OF EXISTING TRANSFORMER. EXISTING SERVICE FEEDER
FROM TRANSFORMER TO BUILDING SWITCHBOARD SHALL
REMAIN. EXISTING TRANSFER SWITCH, FUSED DISCONNECT
AND ASSOCIATED PARTIAL FEEDERS SHALL BE REMOVED IN
IT'S ENTIRETY.
9.024 REMOVE FUSES FROM EXISTING MAIN SERVICE
DISCONNECT. DISCONNECT SHALL REMAIN. FUSES WILL BE
REPLACED IN NEW CONSTRUCTION. REFER TO SHEET E-701
FOR FUSE SIZE.
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
TP #1
TP #2
BM #1
BM #2
TP #4
TP #3
BUILDING
MAINTENANCE
GARAGE
CO
E X
IS
T
EXIST 2" PMP GAS
GAS LINE MARKER
EXIST. 2" PMP GAS
8"
6"
APPROXIM
ATE EXIST.20" W
ATER M
AIN
LOCATIO
N
B-6
A-2-3
B-3
B-1
A-2
A-2-2
B-4-1
B-2
B-5
B-2-1
B-2-2
B-4
A-3
A-2-1
D-2
A-3-1
E-1
E-2
APPROXIM
ATE LOCATIO
N EXIST. 6
" S
ANITARY FORCED M
AIN
EXIST. TOP DITCH
EXIST. TOP DITCH
CONC.
C O
N C
ASPH.
ASPH.
ASPH.
EXIST. E
DGE PAVEMENT
ASPH.
ASPH.
CONC.
CONC.
ASPH.
ASPH.
BUILDING ADDITION
BUILDING ADDITION
SEE SHEETS ED101A &
E-101A FOR
CONTINUATION.
EXISTING 125KW
NATURAL GAS GEN SET
480Y/277V, 3-PHASE, 4W
E
E
E
E
E
E
E
E
E
E
E
E
E
EXISTING 300KVA XFMR
480Y/277V, 3-PHASE, 4-WIRE
PAD MOUNTED
TRANSFORMER BY UTILITY.
E
E
E
E
E
E
E
E E
E E
E E E E
E
E
E
E
E
E
E
E
E
E
E
E
9.326
9.3269.326
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
SEE EQUIPMENT WIRING
SCHEDULE FOR CONDUIT
AND WIRING SIZE.
SEE ONE-LINE DIAGRAM FOR
CONDUIT AND WIRING SIZE.
FUSIBLE DISCONNECT
MOUNTED ON UNI-STRUT.
FIRE PUMP (FP)
9.327
9.327
9.327
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-010
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
S
IT
E P
L A
N
E L
E C
T R
IC
A
L
KEYED NOTES
9.326 PROVIDE NEW CONDUIT AS REQUIRED TO TIE INTO EXISTING
UNDERGROUND CONDUIT AT BUILDING 151 NEW ADDITION
WALL. NEW CONDUIT AT THIS LOCATION SHALL EXTEND UP
TO ABOVE ACCESSIBLE CEILING AND ROUTE BACK TO
EXISTING JUNCTION BOX REFERENCED IN KEYED NOTE 9.019
ON SHEET ED010. NEW CONDUIT SHALL MATCH THAT OF
EXISTING CONDITIONS BEING REMOVED.
9.327 ALL WIRING FROM NEAREST EXISTING ACCESSIBLE
TERMINATION BACK TO SOURCE SHALL BE NEW. WIRING
SHALL MATCH THAT OF EXISTING CONDITIONS BEING
REMOVED.
10' 20' 40'
SCALE: 1" = 20'
1" = 20'-0"1
REVISED SITE PLAN - ELECTRICAL
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
C
JJ
H
J
K
L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
VESTIBULE
41 CORRIDOR
TELCOM
ELECT
MECH
ITE
STORAGE
STAGING
SERVER
ROOM
SECURE
CRYPTO
CORRIDOR
WELDING
SHOP
STORAGE
CARPENTRY /
PAVEMENT &
GROUND
SHOP
MECH. /
UTILITY
SHOP
CORRIDOR
POWER
PRODUCTION
SHOP
SUPERVISORS
TOOL
ROOM
MATERIAL
CONTROL
/ WORK
CONTROL
SUPPLIES
PA
OFFICER
PA
NCOIC
E E
OHD OHD
EF
46"
24"
24"24" 24"
24"
46"
46"
46" 46" 46" 46"
PANEL B1
GFCI, WP
WELDER
46" 46"
GFCI GFCI
LATHE
72"
24"
52"
52"
SHOWS MACH.
OHD
GFCI, WP
OHD
GFCI, WP
EWC
PANEL C1
TEST
OHD
46"
46"
46"
EF
72"
E-401
PANEL L1
PANEL EM1
PANEL EM2
46" 46" 46"
CUH
DC
SEE SHEET 2/E-401
FOR CONTINUATION.
SEE SHEET E-010
FOR CONTINUATION.
E E E E
UH-5
UH-6
MAU-1
UH-7
UH-3 UH-4
UH-1
UH-2
/1 E-101B
/1 E-101B
E
E
E
E
E-401
UH-8
UH-9
DF-1 DF-2
DF-3 DF-4
AC-1
DF-5 DF-6 DF-7
DF-8
DF-9
ATS/XH
PANEL XH
ATS/EM
MTS/EM
PANEL EMH
ECB/XH
ECB/EM
PORTABLE GENERATOR PLUG
100A, 3-POLE.
VERIFY PLUG TYPE AND EXACT
LOCATION WITH BASE.
9.337
GFCI, WP
9.340
A1-14
EM2-21
EM2-21
EM2-21 EM2-35
EM2-35
EM2-35
9.3389.338 (TYP.)
B1-11 B1-11
B1-11B1-11
B1-11
B1-11 B1-11 B1-11
B1-11
B1-29
B1-16
B1-18
B1-27
B1-25B1-23
B1-11
B1-19
B1-13
9.339 (TYP.)9.339
9.3399.339
(TYP.)
9.339 (TYP.)9.339
9.3399.339
EF-2
L1-30,32,34
CUH-1
9.342
FMCP
EML-1
PANEL EML
FTP
EML-3
9.348
EF-6
B1-20
9.339
UH-10
ERLD
HWP-3
MC1
B1-22 9.339
TCP
B1-28
9.339
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-101A
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A A
P
O W
E R
1/8" = 1'-0"1
REVISED FLOOR PLAN - BUILDING 151 AREA A - POWER
KEYED NOTES
9.337 UTILIZE EXISTING FEEDERS AND CIRCUIT BECOMING
AVAILABLE UPON THE DEMOLITION OF EXISTING MAU1 TO
SERVE NEW MAU-1. EXTEND FEEDERS AS REQUIRED FOR
THE INSTALLATION OF THE NEW UNIT.
9.338 UTILIZE EXISTING CIRCUIT BREAKER(S) BECOMING
AVAILABLE UPON DEMOLITION OF EXISTING DEVICES TO
SERVE NEW DEVICE.
9.339 UTILIZE EXISTING SPARE CIRCUIT BREAKER TO SERVE NEW
DEVICE.
9.340 INTERCEPT AND EXTEND EXISTING RECEPTACLE BRANCH
CIRCUIT AS REQUIRED TO NEW RECEPTACLE.
9.342 INTERCEPT AND EXTEND NEAREST RECEPTACLE BRANCH
CIRCUIT TO NEW CABINET UNIT HEATER AS REQUIRED.
9.348 EXISTING SPARE CIRCUIT BREAKERS, CIRCUITS 30, 32 AND
34, IN PANEL L1 SHALL BE REMOVED AND REPLACED (1) 20A,
3-POLE CIRCUIT BREAKER TO SERVE NEW EF-1. NEW CIRCUIT
BREAKER SHALL BE BY THE SAME MANUFACTURER AND
MINIMUM AIC RATING AS EXISTING CIRCUIT BREAKERS.
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
J
J J
J
C
J JJ J J J J
C
J
A
C
D
E
F
G
H
J
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
WING
TRAINING
PUBLISHING
CENTER
TRAINING /
TESTING /
COMPUTER
CLASSROOM
MULTIMEDIA
STUDIO
PA
ADMIN /
PERSONNEL
BREAK
COMM
STORAGE
CONFERENCE
LOBBY
VEST
CLIENT
SER.1
CLIENT
SER. 2
COMPUTER
CAFE
OPS
CHIEF
P & R
CHIEF
COMM
CHIEF
RADIO 4
RADIO 3
STAN /
EVAL
RADIO 1
RADIO 2
CLOSET
CORRIDOR
WOMEN
RESTROOM
VESTIBULE
SIPR
CAFE
NET OPS
CYBER
SECURITY
PLANS
SHOP -
ADMIN
MEN
RESTROOM
VESTIBULE
OPEN
OFFICE
KNOW
OPS
KNOW
OPS
INFRAST.
INFRAST.
INFRAST.
INFRAST.
QA
COMM
CC
REAL
PROP /
RA
POWER
PRO 1
ENGINEERING
DRAFTING
SHARED
ADMIN.
NCOIC
53 EM
TECH
POWER
PRO 2
51 CE
CHIEF
DEP BCE
BCE
TRAINING
MANAGER
ENVIRONMENTAL
REPRODUCTION
GFCI
46" 46" 46"
66" EWC
GFCI
GFCI
46"
46"
FF/W
FF/W
FF/W
FF/W FF/W
FT FT
GFCI, WP
96"
PS
46"
PS
46"
FF/W FF/W
FF/W
FF/W
FF/W FF/W FF/W 72"
TV
72"
TV
/1 E-101A
/1 E-101A
PANEL A1
125KW NATURAL GAS GENERATOR
480Y/277V, 3PH, 4W
PANEL XL
XFMR T/XL
EM1-3 EM1-3
EM1-3EM1-3
FF/W
EM1-2,4
EM1-10,12 EM1-14,16
EM1-5 EM1-5
EM1-37
9.338
9.338(TYP.)
9.338(TYP.)
9.3389.338
9.339
EM1-37
9.339
EM1-32
EM1-39
EM1-41
EM1-41
EM1-32
EM1-32
EM1-41
EM1-39
EM1-39
9.3399.339
9.339
(TYP.)
(TYP.)
9.340
EM2-22
A1-29 A1-33 A1-33
A1-33A1-29
A1-29 A1-27
A1-27
A1-27
A1-25
A1-25
9.3399.3399.339
9.338
(TYP.)
9.338 (TYP.)
9.339 (TYP.)
9.338
(TYP.)
A1-36 A1-36
A1-34
A1-34
A1-34
A1-34
A1-37 A1-37 A1-37
A1-37
EM2-17
EM2-17
EM2-17
EM2-17
EM2-3
EM2-3
EM2-3
EM2-3EM2-1EM2-1
9.338
9.338 (TYP.)
(TYP.)
9.350
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:2
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-101B
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A B
P
O W
E R
1/8" = 1'-0"1
REVISED FLOOR PLAN - BUILDING 151 AREA B - POWER
KEYED NOTES
9.338 UTILIZE EXISTING CIRCUIT BREAKER(S) BECOMING
AVAILABLE UPON DEMOLITION OF EXISTING DEVICES TO
SERVE NEW DEVICE.
9.339 UTILIZE EXISTING SPARE CIRCUIT BREAKER TO SERVE NEW
DEVICE.
9.340 INTERCEPT AND EXTEND EXISTING RECEPTACLE BRANCH
CIRCUIT AS REQUIRED TO NEW RECEPTACLE.
9.350 INCOMING RACEWAYS SHALL BE FED FROM ABOVE CEILING
AND SURFACE MOUNTED TO COLUMN. PAINT RACEWAY
SYSTEM TO MATCH COLUMN FINISH.
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
BAY
BAY
STORAGE
OFFICE
MECH
RESTROOM
JANITOR
PANEL B
48"
48"
DODODO
E
L5-30 48"
PANEL A
24"
EWC
GFCI
GFCI
48"
48"
48" 48"
48"
48" 48"48"
48"
48"
48"
48"
48" 9.310
9.3109.310
9.310
9.3109.3109.310
9.310
9.310
9.310
9.310
9.310 9.310
48"
9.310
9.3109.3109.310
EXISTING PULL
BOX ABOVE
DOOR
GUH-1 GUH-2
MAU-2
EWH-1
ACCU-2
EUH-1
ESEW-1
DF-10 DF-11
E-102
EF-5
(ROOF)
MX
A-1,3,5
A-25
A-22 A-22
A-25
A-7,9
A-29
A-38,40
A-38,40
A-16 A-18
TCP
A-30
OPEN BAYS
STORAGE
E
DS-1
PANEL DP-1 9.301
INV/119A
48"
9.307
48"
9.307
48"
9.307
48"
9.307
48"
9.307
9.3079.307
9.3079.3079.307
9.3079.307
9.307
9.307
9.307 9.307 9.307 9.307
9.307
9.307
9.307
DP-1-5
DP-1-2
DP-1-2
DP-1-4 DP-1-4 DP-1-4
DP-1-6 DP-1-6 DP-1-12 DP-1-12
DP-1-12
DP-1-12
DP-1-10
DP-1-10DP-1-10DP-1-10DP-1-8DP-1-8
DP-1-8
DP-1-8
DP-1-6
DP-1-6
AIR COMPRESSOR
FACP
GWH-1
CP-1
EF-3
MX
EF-4
FAF-1
PANEL DP
EXISTING PULL
BOX
MECH
A-31 A-31
A-26 A-12
A-12
A-14
FTP
A-20
9.3519.351
MS
GUH-3
A-25
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
2'-8" 5'-4" 10'-8"
SCALE: 3/16" = 1'-0"
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-102
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
F L
O O
R P
L A
N
B U
IL
D
IN
G
S
A
B
P
O W
E R
3/16" = 1'-0"2
REVISED FLOOR PLAN - BUILDING 119B - POWER
3/16" = 1'-0"3
REVISED FLOOR PLAN - BUILDING 119A - POWER
3/8" = 1'-0"1
ENLARGED REVISED PLAN - MECH 9
KEYED NOTES
9.301 UTILIZE EXISTING PARTIAL FEEDER BECOMING AVAILABLE UPON THE
DEMOLITION OF EXISTING PANEL 'DP-1'. EXTEND FEEDER AS REQUIRED TO
ACCOMMODATE THE INSTALLATION OF NEW PANEL 'DP-1'. REFER TO KEYED
NOTE 9.001 ON SHEET ED102 FOR COORDINATION.
9.307 UTILIZE EXISTING BACK BOX AND PARTIAL CONDUIT FOR THE INSTALLATION
OF NEW RECEPTACLES. REFER TO KEYED NOTE 9.011 ON SHEET ED102 FOR
COORDINATION.
9.310 UTILIZE EXISTING BACK BOX, CONDUIT AND BRANCH WIRING FOR THE
INSTALLATION OF NEW RECEPTACLE. REFER TO KEYED NOTE 9.016 ON
SHEET ED102 FOR COORDINATION.
9.351 PROVIDE RED, LOCK ON CIRCUIT BREAKERS FOR CIRCUIT BREAKERS
SERVING FTP AND FACP IN PANEL A. IN ADDITION TO REQUIRED CIRCUIT
BREAKER NAMEPLATE DESCRIPTION, PROVIDE LABEL WITH THE
FOLLOWING INSCRIPTION: "FIRE PROTECTION / LIFE SAFETY EQUIPMENT".
LABEL SHALL BE RED LAMINATED PLASTIC WITH WHITE CENTER CORE AND
LETTERING.
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
D
E
F
G
H
J
K
L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
RTU-1
EF2
GRV-1
FC-2 FC-1
ACCU-1
EF-1
EM2-5,7
9.345
L1-24,26,28
9.347
XH-8,10,12 XH-25,27,29
MD
HWP-5 HWP-4
XH-14,16,18 XH-31,33,35
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
8' 16' 32'
SCALE: 1/16" = 1'-0"
/5
/2
:0
:2
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-103
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
R O
O F
P L
A N
B
U
IL
D
IN
G
O V
E R
A L
L
P O
W E
R
KEYED NOTES
9.345 EXISTING CIRCUIT BREAKERS, CIRCUITS 5 & 7, IN PANEL EM2
BECOMING AVAILABLE UPON DEMOLITION SHALL BE
REMOVED AND REPLACED (1) 20A, 2-POLE CIRCUIT BREAKER
TO SERVE NEW ACCU-1. NEW CIRCUIT BREAKER SHALL BE
BY THE SAME MANUFACTURER AND MINIMUM AIC RATING AS
EXISTING CIRCUIT BREAKERS.
9.347 EXISTING SPARE CIRCUIT BREAKERS, CIRCUITS 24,26 AND 28,
IN PANEL L1 SHALL BE REMOVED AND REPLACED (1) 20A,
3-POLE CIRCUIT BREAKER TO SERVE NEW EF-1. NEW CIRCUIT
BREAKER SHALL BE BY THE SAME MANUFACTURER AND
MINIMUM AIC RATING AS EXISTING CIRCUIT BREAKERS.
3/32" = 1'-0"1
REVISED ROOF PLAN - BUILDING 151 OVERALL - POWER
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
OS2
OS1 OS1
OS1
OS2
OS2
OS2
OS2
OS2
OS1
OS1
OS4OS4
OS6
LIGHTING GENERAL NOTES:
1.
2.
3.
4.
ALL INTERIOR AND EXTERIOR EMERGENCY BATTERY UNITS
(EBU) SHALL BE ON THE SAME BRANCH CIRCUIT AS THAT
SERVING THE NORMAL OR EMERGENCY LIGHTING IN THE
AREA CONNECTED AHEAD OF ANY LOCAL SWITCHES OR
CONTROLS, PER NEC. 700.12(F).
ALL 277V EMERGENCY LIGHT FIXTURES (SHOWN SHADED)
SHOWN ON THIS PLAN SHALL BE FED FROM PANEL 'EM'
UNLESS NOTED OTHERWISE. ALL EMERGENCY CIRCUIT
SHALL BE SEGREGATED FROM NON-EMERGENCY CIRCUITS.
ALL EXISTING TO REMAIN (ETR) EXIT SIGNS SHOWN ON THIS
PLAN SHALL BE RE-FED FROM PANEL 'EM'.
ALL EXISTING AND NEW EXIT SIGNS SHOWN ON THIS PLAN
SHALL BE FED FROM PANEL 'EM', CIRCUIT 1', UNLESS NOTED
OTHERWISE. PROVIDE ALL NEW RACEWAY SYSTEMS AS
REQUIRED.
H
J
K
L
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
CORRIDOR
TELCOM
ELECT
MECH
ITE
STORAGE
STAGING
SERVER
ROOM
SECURE
CRYPTO
CORRIDOR
WELDING
SHOP
STORAGE
CARPENTRY
PAVEMENT
GROUND
SHOP
MECH. /
UTILITY
SHOP
CORRIDOR
POWER
PRODUCTION
SHOP
SUPERVISORS
TOOL
ROOM
MATERIAL
CONTROL
/ WORK
CONTROL
SUPPLIES
PANEL EMA
ETR ETR ETR
ETR
ETR
ETR
ETRETR
ETR
ETR
ETR
9.219
T2
9.221
9.2069.206
9.2069.206
9.2069.206
9.212 (TYP.)
9.2129.2069.206
9.212 (TYP.)
9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206
(TYP.)
9.221(TYP.)
(TYP.)
PA
NCOIC
PA
OFFICER
VESTIBULE
9.223
WP
9.212(TYP.)
WS
9.219
OB
X3
S
S
S3S3S3S3
S3S3S3S3
B
S2
A4
A
S
S1S1
X3
B1
A1 A1 ERLD
X3
X3
D
D
X3
3c
OA
DD
9.219
OB
9.219
OB
9.219
OB
T2 T2
T2
T2 T2
T2 T2T2
9.205
S
SS
9.212 (TYP.)
S2
S2
S2
S2 S2
S2
S2
S2
S2
ETR
S3
S3
S3S3
S3
S3
9.219
OB
S1
S1S1
S1
S1
T2
T2
T2 T2
9.205
S1
S4
S4
A4 A4
A4 A4 A4
A A A
A A
9.2069.2069.206
S
B
B BBBBBB
c
VIA PT
cc c
VIA PT
VIA PT
B
B
B
B
B BB B
B
B c c c
B1 B1
A1 A1
/1 E-121B
/1 E-121B
9.212
9.222
B
A5 A5
A5A5
A5 A5
A5
A5
D
EMH-4 EMH-4
EMH-4
VIA PT VIA PT
PT
EMH-4
EMH-4
VIA PT
PT
EMH-4
EMH-4
EMH-4
EMH-4
EMH-4
EMH-4 EMH-4
VIA PT
VIA PT
VIA PT
PT
PT
PT
PT
EMH-5
PT
PT
EMH-5c EMH-5c EMH-5c
EMH-5
EMH-5
PT
VIA PT
VIA PT
EMH-5
EMH-5
VIA PT
EMH-5
VIA PT
EMH-5
VIA PT
PT
EMH-5
USB/XA-22
USB/XA-22
USB/XA-22
USB/XA-22
USB/XA-22 USB/XA-22
USB/XA-22
USB/XA-22
PANEL EMH
PANEL UPS/XA
9.2069.206
9.2069.206
9.2319.231
EMH-5c
VIA PT VIA PT VIA PT VIA PT
VIA PT
EMH-6 EMH-6 EMH-6 EMH-6
EMH-6
EMH-6
VIA PT
9.2069.206
9.212
S3
9.216
S3
9.212 (TYP.)
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:2
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-121A
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A A
L
IG
H
T
II
N G
KEYED NOTES
9.205 MOUNT FIXTURE 1'-0" ABOVE DOOR MEASURED FROM
BOTTOM OF FIXTURE.
9.206 ALL WIRING BETWEEN NEW LIGHTING CONTROL DEVICES
AND LIGHT FIXTURES SHALL BE NEW. EXISTING BRANCH
CIRCUIT SHALL BE EXTENDED FROM ABOVE CEILING
JUNCTION BOX TO THE NEW LIGHT FIXTURES UNLESS NOTED
OTHERWISE. REFER TO KEYED NOTE 9.003 ON SHEETS
ED121A AND ED121B FOR DEMOLITION REQUIREMENTS IN
THIS ROOM.
9.212 MOUNT FIXTURE AT 10'-0" AFF MEASURED FROM BOTTOM OF
FIXTURE.
9.216 CORNER MOUNT OCCUPANCY SENSOR AT 8'-0" AFF.
9.219 NEW FIXTURE SHALL BE INSTALLED AT THE SAME LOCATION
AS EXISTING. UTILIZE EXISTING BACKBOX AND PARTIAL
CONDUIT FOR NEW FIXTURE INSTALLATION AND WIRING.
9.221 MOUNT FIXTURE AT 16'-0" AFF MEASURED FROM BOTTOM OF
FIXTURE.
9.222 EXISTING INTERIOR AND EXTERIOR LIGHTING CONTROL
PANELS SHALL REMAIN. INTERIOR LIGHTING BRANCH
CIRCUITS SHALL BYPASS THE INTERIOR LIGHTING CONTROL
AND SHALL ONLY BE CONTROLLED BY LOCAL DEVICES IN
EACH RESPECTIVE ROOM UNLESS NOTED OTHERWISE.
RELAYS SERVING INTERIOR LIGHTING SHALL NO LONGER BE
USED AND SHALL BE TURNED OFF AND LABELED AS SPARE.
REFER TO SHEET E-602 FOR ADDITIONAL INFORMATION.
9.223 INTERCEPT AND EXTEND AS REQUIRED EXISTING EXIT
BRANCH WIRING AND CONDUIT TO NEW EXIT SIGN. TYPICAL
FOR ALL NEW EXIT SIGNS SHOWN ON THIS PLAN.
9.231 EXTEND AS REQUIRED EXISTING NORMAL BRANCH LIGHTING
CIRCUIT BEING RE-USED TO SERVE TOOL ROOM 68 TO
LIGHTING IN THIS ROOM.
1/8" = 1'-0"1
REVISED FLOOR PLAN - BUILDING 151 AREA A - LIGHTING
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
OS4
OS1OS5
OS1
OS5
OS2OS2
OS2 OS2
OS1
OS1
OS1
OS1
OS1
OS1
OS1
OS1
OS2 OS2
OS1
OS1OS1
OS1
OS1
OS2
OS1
OS1
OS1
OS1
OS1
OS1
OS2
OS2 OS2
OS1
DS1
P T
OS6 OS6
OS4
OS6
A
C
D
E
F
G
H
J
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
WING
TRAINING
PUBLISHING
CENTER
TRAINING /
TESTING /
COMPUTER
CLASSROOM
MULTIMEDIA
STUDIO
PA
ADMIN /
PERSONNEL
BREAK
COMM
STORAGE
CONFERENCE
LOBBY
VEST
CLIENT
SER.1
CLIENT SER. 2
COMPUTER
CAFE
OPS
CHIEF
P & R
CHIEF
COMM
CHIEF
RADIO 4
RADIO 3
STAN / EVAL
RADIO 1
RADIO 2
CLOSET
CORRIDOR
WOMEN
RESTROOM
VESTIBULE
SIPR CAFE
NET OPS
CYBER
SECURITY
PLANS SHOP -
ADMIN
RESTROOM
VESTIBULE
OPEN
OFFICE
KNOW
OPS
KNOW
OPS
INFRAST. 3
INFRAST.
26 25
INFRAST. 2
INFRAST. 4
QA
COMM
CC
REAL
PROP /
RA
POWER
PRO 1
ENGINEERING
DRAFTING
SHARED
ADMIN.
NCOIC
53 EM
TECH
POWER
PRO 2
CE
CHIEF
DEP BCE
BCE
TRAINING
MANAGER
ENVIRONMENTAL
REPRODUCTION
ETR
ETR
ETR
ETR
ETR
ETR
ETR
PA
NCOIC
PA
OFFICER
VESTIBULE
9.223
9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206 9.2069.206
9.2069.206
9.2069.206 9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206
9.2069.206
NL
9.2079.207
NL
9.207
9.217
9.217
9.207
9.207(TYP.)
9.210
G EMH-5a
9.2079.207
PT
9.207(TYP.)
9.209
9.212
9.219 (TYP.)
9.207
9.207(TYP.)
9.224
9.224
9.210
9.214 (TYP.)
9.227
9.226
ETR
ETR
A1 A1 A1
A1A1A1
X3
X3
A3 A3
A3A3
B
D3
D3
C
C D5
D5 D4
C A A
A A
A A
A A
A2
A2
A2A2
A2
D D
AA
D3
D
D
D3
D3
P16
S1
S1
S1
OB
A2
A A
AA
OB
D
D1
D1
P6D
ETR
W W
OW OW
OWOW
P
OP
D
D
D
T
WS
K
WS
T
K
D
D
D
D
D
D
D
D
D
D
D
D
WS
D
MEN
f f f a,c,d,e a,c,d,e a,c,d,e a,c,d,e
D a a a, b d a,b c,d c,d b
S1 S1
(TYP.)
Dd Dc
EMH-3c
A2
XH-20c
A2
XH-20c
A2
XH-20c
A2
XH-20c
A2
EMH-3c
A2
XH-20c
A2
XH-20c
A2
XH-20c
A1
XH-20d
A1
XH-20d
A1 EMH-3d
A1
XH-20d
A1
XH-20d
A1 XH-20d
A2
EMH-3a
A2 b
A2 b
A2 a
A2 a
A2 a
A2 a
A2
EMH-3b
A2 a
ETR
ETR
ETR ETR
ETR ETR
ETR
ETR
ETR
a
Dd D1
D1
Db Da
9.2159.215
NL
(TYP.)
a,b a,b
9.216 (TYP.)
P6IP6D
b b b
9.225 a 3c
Da Db b D3 b
D3 b
D3 b
D3 b
D3 b
D3 b
D3 b a
D3 b
Da
Db
A
A A
A
A2
A2
A1
A1
A4
A4 A4
A4
A4
A4 A4
A4
A
A
A
A
A
A
Df De Dd
A4
3Da
A4 a
A4 a
A4
VIA PT
A4 a
A4 a
A4 a
A4 a
A4
VIA PT
Dg g g
Db b b D b
D b
D b
A4 c
A4 c
A4 c
A4 c
A4
VIA PT
A4 c
A4 c
A4 c
A4 c
A4
EMH-2c
A4 c a,c,d,e,g a,c,d,e a,c,d,e a,c,d,e
A4 d
A4 d
A4 d
A4
A4 d
A4 d
A4 d
A4
VIA PT
A4 d
A4 d
A4 e
A4 e
A4 e
A4 e
A4 e
A4 e
A4 e
A4 e
A4 e
A4 e
D
3a Dc
A4
A4 A4
A4 c c
B c
B
VIA PT
c
9.2069.206
D3 D4
C
D5
9.207
C1
C
C
C
D3
D3
D3
(TYP.)
C1
C1
9.207 (TYP.)
D5D5/1 E-121A
/1 E-121A
3d
A A
X3
OP
(TYP.)
A f
EMH-5c
B
VIA PT
EMH-5c
PT PT
VIA PT
PT
PT
PT
EMH-3d
EMH-6
EMH-6
EMH-6
EMH-2a
EMH-2a
EMH-2a
PT
EMH-2c
PT
EMH-2d
EMH-2d
PT
VIA PT
EMH-2
EMH-2
PT
EMH-3
PT
EMH-3
VIA PT
A4 d
9.216
S3
S3
S3
EMH-2
EMH-2
EMH-6
VIA PT
EMH-6
VIA PT
VIA PT
9.2069.206
9.2069.206
A
A
LIGHTING GENERAL NOTES:
1.
2.
3.
4.
ALL INTERIOR AND EXTERIOR EMERGENCY BATTERY UNITS
(EBU) SHALL BE ON THE SAME BRANCH CIRCUIT AS THAT
SERVING THE NORMAL OR EMERGENCY LIGHTING IN THE
AREA CONNECTED AHEAD OF ANY LOCAL SWITCHES OR
CONTROLS, PER NEC. 700.12(F).
ALL 277V EMERGENCY LIGHT FIXTURES (SHOWN SHADED)
SHOWN ON THIS PLAN SHALL BE FED FROM PANEL 'EM'
UNLESS NOTED OTHERWISE. ALL EMERGENCY CIRCUIT
SHALL BE SEGREGATED FROM NON-EMERGENCY CIRCUITS.
ALL EXISTING TO REMAIN (ETR) EXIT SIGNS SHOWN ON THIS
PLAN SHALL BE RE-FED FROM PANEL 'EM'.
ALL EXISTING AND NEW EXIT SIGNS SHOWN ON THIS PLAN
SHALL BE FED FROM PANEL 'EM', CIRCUIT 1', UNLESS NOTED
OTHERWISE. PROVIDE ALL NEW RACEWAY SYSTEMS AS
REQUIRED.
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
4' 8' 16'
SCALE: 1/8" = 1'-0"
/5
/2
:0
:3
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-121B
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
F L
O O
R P
L A
N
B U
IL
D
IN
G
A
R E
A B
L
IG
H
T
II
N G
KEYED NOTES
9.206 ALL WIRING BETWEEN NEW LIGHTING CONTROL DEVICES
AND LIGHT FIXTURES SHALL BE NEW. EXISTING BRANCH
CIRCUIT SHALL BE EXTENDED FROM ABOVE CEILING
JUNCTION BOX TO THE NEW LIGHT FIXTURES UNLESS NOTED
OTHERWISE. REFER TO KEYED NOTE 9.003 ON SHEETS
ED121A AND ED121B FOR DEMOLITION REQUIREMENTS IN
THIS ROOM.
9.207 PATCH CEILING AROUND NEW DOWNLIGHT TO MATCH
EXISTING.
9.209 MOUNT FIXTURE AT 9'-0" AFF MEASURED FROM BOTTOM OF
FIXTURE.
9.210 WIRING BETWEEN NEW LIGHTING CONTROL DEVICE AND
LIGHT FIXTURE SHALL BE NEW. EXISTING BRANCH CIRCUIT
SHALL BE EXTENDED FROM NEAREST ACCESSIBLE
JUNCTION LOCATED ABOVE CEILING TO NEW LIGHT FIXTURE
AND LIGHTING CONTROL DEVICE. EXISTING CONDUIT MAY BE
RE-USED FOR NEW FIXTURE WIRING INSTALLATION
WHEREVER FEASIBLE. PROVIDE NEW CONDUIT AS REQUIRED
TO ACCOMMODATE FIXTURE INSTALLATION. NEW FIXTURE
SHALL BE MOUNTED AT THE SAME LOCATION AS EXISTING
REMOVED FIXTURE. REFER TO KEYED NOTE 9.005 ON SHEET
ED121B FOR DEMOLITION REQUIREMENTS AT THIS FIXTURE.
9.212 MOUNT FIXTURE AT 10'-0" AFF MEASURED FROM BOTTOM OF
FIXTURE.
9.214 NEW FIXTURE SHALL BE MOUNTED AT THE SAME LOCATION
AS EXISTING REMOVED FIXTURE. UTILIZE BRANCH CIRCUIT
AND CONTROL FOR THE INSTALLATION OF NEW FIXTURE.
REFER TO KEYED NOTE 9.006 ON SHEET ED121B FOR
DEMOLITION REQUIREMENTS AT THIS FIXTURE.
9.215 PAINT CONDUIT TO MATCH EXISTING CANOPY/STRUCTURAL
CEILING.
9.216 CORNER MOUNT OCCUPANCY SENSOR AT 8'-0" AFF.
9.217 KEYED SWITCH SHALL BE LOCKED IN THE "ON" POSITION.
9.219 NEW FIXTURE SHALL BE INSTALLED AT THE SAME LOCATION
AS EXISTING. UTILIZE EXISTING BACKBOX AND PARTIAL
CONDUIT FOR NEW FIXTURE INSTALLATION AND WIRING.
9.223 INTERCEPT AND EXTEND AS REQUIRED EXISTING EXIT
BRANCH WIRING AND CONDUIT TO NEW EXIT SIGN. TYPICAL
FOR ALL NEW EXIT SIGNS SHOWN ON THIS PLAN.
9.224 MOUNT FIXTURE 18" AND CENTERED ABOVE ACRYLIC
CURVED CLOUD.
9.225 MOUNT FIXTURE 18" AND CENTERED BELOW PERFORATED
CURVED CLOUD. FIXTURE SHALL BE SUSPENDED FROM
CLOUD.
9.226 EXTEND EXISTING EXIT SIGN CIRCUIT LOCATED IN LOBBY AS
REQUIRED TO NEW FIXTURE. NEW RACEWAYS SHALL BE
HIDDEN FROM VIEW WHEREVER POSSIBLE.
9.227 FIXTURE SHALL BE CONTROLLED WITH EXTERIOR FIXTURE
TYPE "OW" VIA THIS PT DEVICE.
1/8" = 1'-0"1
REVISED FLOOR PLAN - BUILDING 151 AREA B - LIGHTING
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
OS7 OS7OS7
OS6
OS6
OS7 OS7 OS7
DS1
BAY
BAY
STORAGE
OFFICE
MECH
RESTROOM
JANITOR
X1
3D
S S
S
WS
S S
T1 T1 T1
T1T1T1
9.230(TYP.)
9.203 (TYP.)
T1 T1
T1
9.230(TYP.)
T1
9.203
S S
9.205
OB
OB1
OB1
OB1
X1
9.205
PE
MOUNT ON ROOF
& AIM NORTH.
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
9.228 (TYP.)
9.228
X1
9.205
EX/EBU EX/EBU EX/EBU
EX/EBU
9.205 (TYP.)
PANEL B
PANEL A
INV/119BPT
(3)
VIA PT
VIA PT
WS
S
X1/EBU
9.205
S
SS
VIA PT
INV/119B
INV/119B
INV/119B
INV/119B
INV/119B
INV/119B
A-19
A-19
A-19 A-19
A-19
A-24
A-24
A-24
A-24
A-23 A-23 A-23
A-23 A-23
A-23A-23
A-23 A-23 A-23
OPEN BAYS
STORAGE
PANEL DP-1
T TT
T TT
9.201 (TYP.)
9.202 (TYP.)
T1
T1
T1
T1
T1
T1
T1
T1
9.203 (TYP.)
a,b a,b a,b
INV/119Aa DP-1-1a DP-1-1a INV/119Aa
DP-1-1bINV/119AbDP-1-1bDP-1-1b
9.204 a
3a 3b
WP
WP
3a 3b
WP
WP
X1
9.205
P T
VIA PT
VIA PT
(3)
INV/119A
PE
MOUNT ON ROOF
& AIM NORTH.
9.228 (TYP.)
OB1
OB1 OB1
OB1 OB1
OB1
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
VIA PE FOR
ON/OFF
CONTROL
EX/EBU
9.229
9.230(TYP.)
INV/119A
INV/119A
DP-1-1
DP-1-1 DP-1-1
DP-1-1
DP-1-3 DP-1-3
DP-1-3
DP-1-3DP-1-3
DP-1-3
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
2'-8" 5'-4" 10'-8"
SCALE: 3/16" = 1'-0"
/5
/2
:0
:1
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-122
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
F L
O O
R P
L A
N
B U
IL
D
IN
G
S
A
B
L
IG
H
T
IN
G
KEYED NOTES
9.201 MOUNT FIXTURE AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.202 MOUNT CORNER MOUNT OCCUPANCY SENSOR AT 10'-0" AFF.
9.203 MOUNT OCCUPANCY SENSOR TO UNDERSIDE OF STRUCTURAL JOIST.
OCCUPANCY SENSOR SHALL BE FIELD ADJUSTED TO ALLOW FOR A CLEAN
VIEWING ANGLE.
9.204 MOUNT DAYLIGHT SENSOR TO UNDERSIDE OF STRUCTURAL JOIST.
DAYLIGHT SENSOR SHALL BE FIELD ADJUSTED TO ALLOW FOR A CLEAN
VIEWING ANGLE.
9.205 MOUNT FIXTURE 1'-0" ABOVE DOOR MEASURED FROM BOTTOM OF FIXTURE.
9.228 FIXTURE SHALL BE MOUNTED AT THE SAME LOCATION AND ELEVATION AS
EXISTING REMOVED FIXTURE. UTILIZE EXISTING BACK BOX AND PARTIAL
CONDUIT FOR THE INSTALLATION OF NEW EXTERIOR WALL PACK AND
BRANCH CIRCUIT.
9.229 MOUNT FIXTURE AT 9'-0" AFG MEASURED FROM BOTTOM OF FIXTURE.
9.230 MOUNT FIXTURE AT 15'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
3/16" = 1'-0"1
REVISED FLOOR PLAN - BUILDING 119B - LIGHTING
3/16" = 1'-0"2
REVISED FLOOR PLAN - BUILDING 119A - LIGHTING
M A
R K
D A
T E
D E
S C
R
IP
T
IO
N B
Y
/1
/1
T
Y P
E B
-3 S
U B
M
IT
T
D
E
F
G
H
J
K
L
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
9.317
9.317
9.312(TYP.)
ETR ETR ETR
ETR
ETR
ETR
ETR
ETRETR
ETRETRETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETRETR
ETR
ETR
9.318
ETR
ETR
ETR
ETR
ETR
ETR
ETR
EF-1
NEW AHU
EF2
GRV-1
FC-2 & HWP-5
ACCU-1
9.325 (TYP.)
9.328
EF-1
9.336
FC-1 & HWP-4
LIGHTING GENERAL NOTES:
1.
2.
3.
4.
LIGHTNING PROTECTION SYSTEM DEVICES, CABLES AND
DETAILS SHOWN INDICATE MINIMUM REQUIREMENTS.
LIGHTING PROTECTION INSTALLER SHALL PROVIDE
INSTALLATION DRAWINGS THAT ARE STAMPED, APPROVED
AND LISTED WITH A "MASTER LABEL CERTIFICATION". SEE
SPECIFICATION AND SHEET E-502 FOR ADDITIONAL
INFORMATION.
THE LIGHTING PROTECTION SYSTEM SHALL COMPLY WITH
NFPA 780, CLASS 1, AND ALL LOCAL APPLICABLE CODES
AND ORDINANCES.
ALL ROOF AND WALL PENETRATIONS SHALL BE WATER
PROOF.
INSTALLATION OF LIGHTNING PROTECTION SYSTEM SHALL
NOT VOID THE ROOF WARRANTY.
N
CHKD:
DRWN:
PROJ:
DESN:
A
B
C
D
E
F
2 3 4 5 6 7
Bar measures 1 inch, otherwise drawing is not to scale
C o p yr ig h t:
T e tr a T e c h
8' 16' 32'
SCALE: 1/16" = 1'-0"
/5
/2
:0
:3
A
M C
R e v it L o c a l\4
-1
.0
-1
-E
-C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
4269900-170410.01
MRF
MRF
ARG
E-131
S P
R
IN
G F
IE
L D
-B E
C K
L E
Y A
N G
B O
H
IO
A N
G
A D
A L C
IV
IL
E N
G
IN
E E
R
IN
G B
U
IL
D
IN
G S
W A
A R
R E
V
IS
E D
R O
O F
P L
A N
B
U
IL
D
IN
G
O V
E R
A L
L
L
IG
H T
N
IN
G P
R O
T E
C T
IO
N
3/32" = 1'-0"1
REVISED ROOF PLAN - BUILDING 151 OVERALL - LIGHTNING PROTECTION
KEYED NOTES
9.312 PROVIDE 1/2" X 1/2" SOLID COPPER AIR TERMINAL WITH SIDE
MOUNT BASE. TYPICAL.
9.317 PROVIDE #1/0 COPPER "MAIN-SIZE LIGHTNING PROTECTION
CONDUCTOR" FOR INTERCONNECTION OF ALL NEW AIR
TERMINALS ON ROOF. PROVIDE ALL NECESSARY
EQUIPMENT/DEVICES REQUIRED TO TIE INTO EXISTING
LIGHTNING PROTECTION TERMINAL AND…