Attachment 3 - Drawings 7 of 8.pdf

PDF 10 MB Posted

Attached to
Z2NZ--Retrofit Campus Wide Infrastructure Systems - White City VA Southern Oregon Rehabilitation Center and Clinics (SORCC)
Solicitation number
36E77620R0042
Issued by

About this file

This solicitation is for a retrofit of campus-wide infrastructure systems at the White City VA Southern Oregon Rehabilitation Center and Clinics in White City, Oregon. The contractor will provide all labor, project management, materials, tools, and equipment required to complete the scope of work according to the drawings and specifications. The project must be finished in accordance with the statement of work, specifications, and attachments in the solicitation package. This is a competitive set-aside for a Service-Disabled Veteran-Owned Small Business, with a NAICS code of 236220 and a magnitude of construction between $10-20 million. The soliciting agency is the Department of Veterans Affairs Headquarters.

View the file

Other files

File Type Posted
Technical Questions - White City Retrofit 1 VA SORCC.docx DOCX document
36E77620R0042 0005.docx DOCX document
692-16-101 Access Map.pdf PDF
Technical Questions - White City Retrofit 1_VA SORCC.docx DOCX document
36E77620R0042 0004.docx DOCX document
692-16-101 List of Notes 27 28 and 29 on Sheets C102 through C201.pdf PDF
Construction Wage Rates - Heavy - Jackson County - 8.14.pdf PDF
Construction Wage Rates - Heavy - Jackson County - 8.14.20.pdf PDF
692-16-101 Job Yard and laydown area.pdf PDF
White City Technical Question.docx DOCX document
36E77620R0042 0003.docx DOCX document
692-16-101 Retrofit Infrastructure - Sign in sheets 2020-08-10.pdf PDF
36E77620R0042 0002.docx DOCX document
C301 Sanitary Sewer - Drawing 4 of 8.pdf PDF
S06 - White City Technical Question.docx DOCX document
C101 Potable Water - Drawing 3 of 8.pdf PDF
C502 Surface Restoration Plan - Drawing 6 0f 8.pdf PDF
Attachment 3 - Drawings 8 of 8 - Sheets 85 thru 90.pdf PDF
Amendment 0001.pdf PDF
Attachment 3 - Drawings 8 of 8 - Sheets 80 thru 84.pdf PDF
Attachment 3 - Drawings 4 of 8.pdf PDF
Attachemnt 12 - VA Southern Oregon Rehabilitation Center and Clinics - Site Map.pdf PDF
Attachment 1 - Summary of Work.pdf PDF
S02 - Attachment 4 - Aerial-V1 of 9.pdf PDF
Attachment 3 - Drawings 1 of 8.pdf PDF
Attachment 3 - Drawings 3 of 8.pdf PDF
Attachment 8 - WhiteCityVA_Stormwater Facility Design.pdf PDF
Attachment 5 - Geotechnical Report - 04-21-17.pdf PDF
Attachment 10 - Contractor Safety _ Env Record Form.docx DOCX document
Attachment 3 - Drawings 2 of 8.pdf PDF
S02 - Attachment 4 - Aerial-V7 of 9.pdf PDF
Attachment 3 - Drawings 5 of 8.pdf PDF
36E77620R0042.docx DOCX document
S02 - Attachment 4 - Aerial-V8 of 9.pdf PDF
S02 - Attachment 4 - Aerial-V9 of 9.pdf PDF
Attachment 6 - Geo Infiltration Testing - 2019-12-05 - FNL.pdf PDF
Attachment 9 - ECPDC 692-16-101 - FY20.pdf PDF
Attachment 2 - Final Specifications Revised - 06-29-20.pdf PDF
S02 - Attachment 4 - Aerial-V4 of 9.pdf PDF
Attachment 3 - Drawings 6 of 8.pdf PDF
S02 - Attachment 4 - Aerial-V2 of 9.pdf PDF
S02 - Attachment 4 - Aerial-V5 of 9.pdf PDF
Attachment 7 - 692-16-101 Testing Requirements.pdf PDF
S02 - Attachment 4 - Aerial-V6 of 9.pdf PDF
S02 - Attachment 4 - Aerial-V3 of 9.pdf PDF
Attachment 11 - Construction Wage Rates - 7.3.20.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

LrLr

RL

RL RL

INSTALLATION NOTES:

1. FOR INSTALLATIONS REQUIRING A CLOSE COUPLE

CONNECTION SUBSTITUTE FL X FL GATE VALVE AND FL X

MJ ELBOW. MAKE FLANGED CONNECTION DIRECTLY

BETWEEN ELBOW AND GATE VALVE.

2. HYDRANT SHALL BE LOCATED 2'-6" MIN. FROM EDGE OF

ROAD AND 7'-6" MAX. BEHIND FACE OF CURB

1. ALL FITTINGS SHALL BE DUCTILE IRON PER SPECIFICATIONS.

2. RESTRAINT LENGTH SHOWN IS A MINIMUM BASED ON SOIL LOADING FORCES. RESTRAINT

LENGTH SHALL APPLY TO BOTH SIDES OF THE FITTING AND TO THE BRANCH RUN AT THE

FITTING.

3. USE RESTRAINT LENGTH OF 5 FEET FOR ANY 11.25° HORIZONTAL BENDS.

4. MECHANICAL RESTRAINTS SHALL BE USED TO DEVELOP AT LEAST THE MINIMUM RESTRAINT

LENGTH SHOWN. CONTRACTOR SHALL EVALUATE FIELD CONDITIONS AND INCREASE

RESTRAINT LENGTHS WHERE REQUIRED.

5. RESTRAINT DEVICE SHALL BE USED FOR PLAIN END PIPE AT MECHANICAL JOINT FITTINGS OR

AT PUSH-ON JOINTS WITHIN THE MINIMUM RESTRAINT LENGTH ZONE.

1. BURY UTILITY IDENTIFICATION TAPE 12 INCHES BELOW

FINISH GRADE OVER CENTER OF PIPE ALIGNMENT. UNDER

PAVEMENT AND CONCRETE BURY TAPE 6 INCHES BELOW

SUBGRADE.

2. ATTACH DETECTION WIRE TO NON-METALLIC PIPING AT

INTERVALS NOT TO EXCEED 10 FEET.

3. SEE SPECIFICATIONS 31 20 11 FOR FULL IDENTIFICATION

TAPE AND DEFECTION WIRE REQUIREMENTS.

U.S. Department of Veterans Affairs william wilson architects pc 1022 SW Salmon Street, Suite 350 Portland, OR 97205 503.223.6693

VA Project Number

Building Number

Drawing Number

Revisions: Date:

APPROVAL SIGNATURES

Retrofit Campus Wide Infrastructure Systems - Water, Sewer, Storm

VA Southern Oregon Rehabilitation Center & Clinics 8495 Crater Lake Highway, White City, OR 97503

692-16-101 Drawing TitleCONSULTANT

Date Checked Drawn

Project Title

Location

Approved: Chief ITOS

Approved: Chief FMS

Approved: VA SORCC Director

Approved: Safety Manager

Approved: Service Chief

Approved: Chief of StaffApproved: AFGE

Approved: Associate Director

Approved: Infection Cntrl.

Phase

ARCHITECTOffice of Construction and Facilities Management

STAMP

FINAL CONSTRUCTION DOCUMENTSOREGON

G

E

O

R

L

D

A

K

EXPIRES: 12/31/19

12/22/17 PBS PBS

4412 SW Corbett Avenue

Portland, OR 97239

503.248.1939

PBS Engineering and

Environmental Inc.

pbsusa.com

WATER SYSTEM JOINT RESTRAINT LENGTH TABLE

C701

STANDARD DETAILS

JOINT RESTRAINT DETAIL AND TABLE

SCALE: NONE

2017-12-19T22:50:56-0800

George Drake, PE pbsusa.com C702

2017-12-19T22:52:04-0800

George Drake, PE

ASPHALT PAVEMENT SECTION

pbsusa.com C703

2017-12-19T22:53:16-0800

George Drake, PE pbsusa.com C704

2017-12-19T22:54:15-0800

George Drake, PE pbsusa.com C705

2017-12-19T22:55:09-0800

George Drake, PE

CARRIER PIPE, SIZE

PER PLAN

STEEL CASING,

SIZE PER CHART

CASING FOR BORE AND JACK

CROSS SECTION

TAIL DITCH LENGTH

(2.5 X D)

PIT LENGTH

(12 X d)

DEPTH TO

HOST PIPE

INVERT

EXISTING HOST PIPE CROWNED

OUT TO SPRINGLINE

HDPE PIPE, SIZE AND

TYPE PER PLANS AND

SPECIFICATIONS

EXISTING GRADE

INSERTION PIT FOR PIPE BURSTING

D = DEPTH TO INVERT

d = DIAMETER OF LINER PIPE

CASING SIZE AND CARRIER SIZE

CARRIER PIPE I.D.

(IN)

STEEL CASING DIA.

(IN)

MIN. WALL

THICKNESS (IN)

6 10 0.188

8 14 0.188

10 16 0.219

12 18 0.250

16 22 0.281

18 26 0.344

24 32 0.438

NOTE:

1. SEE SPECIFICATIONS FOR MATERIAL AND

CONSTRUCTION REQUIREMENTS.

2. SEE GEOTECHNICAL REPORT FOR SITE SOIL

CONDITIONS.

CASING

SPACERS,

TYP.

RUBBER END SEAL

RUBBER END SEAL

CARRIER PIPE

STEEL CASING

STAINLESS STEEL BAND

NOTE:

1. SEE SPECIFICATIONS FOR MATERIAL AND CONSTRUCTION

REQUIREMENTS.

2. SEE GEOTECHNICAL REPORT FOR SITE SOIL CONDITIONS.

3. DIMENSIONS OF BORING AND RECEIVING PITS SHALL BE

DETERMINED BY CONTRACTOR.

SOURCE: AREMA MANUAL FOR RAILWAY ENGINEERING

pbsusa.com C706

TRENCHLESS CONSTRUCTION DETAILS

2017-12-19T22:55:58-0800

George Drake, PE

*IF THE WATER PIPE IS UNDER SANITARY SEWER PIPE OR STORMWATER

PIPE, FOLLOW THE REQUIREMENTS BELOW:

IN ADDITION TO THE VERTICAL SEPARATION SHOWN, THE GRAVITY

SANITARY SEWER, STORM SEWER AND WATER PIPE SHALL BE

CONSTRUCTED OF DUCTILE IRON PIPE WITH A FULL 20 FOOT OF PIPE

CENTERED AT THE CROSSING.

WATER PIPING SYSTEMS SHALL HAVE RESTRAINED MECHANICAL

JOINTS.

GRAVITY SEWER OVER WATER SYSTEM DETAIL

WATER PIPE

SANITARY SEWER PIPE OR

STORMWATER PIPE

CLEAR SEPARATION*

WATER PIPE*

SANITARY SEWER PIPE OR

STORMWATER PIPE

18" MIN.

*IF THERE IS LESS THAN 18" OF SEPARATION BETWEEN WATER AND

SANITARY SEWER PIPE OR STORM SEWER PIPE, FOLLOW THE

REQUIREMENTS BELOW. IF THERE IS MORE THAN 18" SEPARATION PVC IS

ACCEPTABLE FOR BOTH PIPES:

THE GRAVITY SEWER AND WATER PIPES SHALL BE CONSTRUCTED

OF DUCTILE IRON PIPE WITH A 20 LF SECTION OF PIPE CENTERED AT

THE CROSSING.

WATER PIPING SYSTEMS SHALL HAVE RESTRAINED MECHANICAL

JOINTS.

GRAVITY SEWER UNDER WATER SYSTEM DETAIL

CORRIDOR STRUCTURE OR OTHER

DESIGNATED TRENCHLESS AREAS

TUNNEL

EXISTING GRADE, TYP.

VARIES

10' TO 20'

VARIES

PROPOSED TRENCHLESS CARRIER PIPE,

SIZE, SLOPE AND INVERT PER PLAN

NOTES:

1. CONTRACTOR TO VERIFY DEPTH OF EXISTING FOOTING.

2. PIPE SHALL BE CONTINUOUS WITHOUT JOINTS UNDER CORRIDOR WITHIN TRENCHLESS

WORK LIMITS.

3. PIPE INSTALLED USING PIPE BURSTING SHALL BE FUSED HDPE PER SPECIFICATIONS.

4. CARRIER PIPE IN BORE AND JACK APPLICATIONS SHALL BE FUSED HDPE OR DUCTILE IRON

WITH RESTRAINED JOINTS PER SPECIFICATIONS.

5. PIPE CASING, CASING SPACERS AND END SEALS IN BORE AND JACK APPLICATIONS SHALL

MEET SPECIFICATIONS.

6. PIPE CASING INSTALLED WITH 5 FEET OF COVER OR GREATER SHALL HAVE ANNULAR SPACE

FILLED WITH SAND PER THE SPECIFICATIONS.

TRENCHLESS UTILITY CORRIDOR CROSSING UNDER STRUCTURE

CORRIDOR

(SOUTH OF BLDG 225)

TUNNEL

EXISTING GRADE, TYP.

10'

NOTES:

1. REMOVE EXISTING 12" STORM THROUGH TUNNEL AND SEAL WALL OPENING.S

2. PIPE SHALL BE DUCTILE IRON PER SPECIFICATIONS.

3. TRANSITION COUPLINGS SHALL BE USED WHEN CHANGING PIPE MATERIAL.

4. ACCESS TO TUNNEL SHALL BE COORDINATED WITH VA IN ADVANCE OR WORK. TUNNEL

HAS OTHER UTILITIES NOT SHOWN INCLUDING STEAM, ELECTRICAL, ETC. STORM

RETROFIT WORK WITHIN TUNNEL SHALL PROTECT OTHER UTILITIES.

UTILITY CORRIDOR CROSSING THROUGH STRUCTURE TUNNEL

FLOOR

FLOOR

CONCRETE FOOTING

WITH STEM WALL, TYP.

CONCRETE FOOTING

WITH STEM WALL, TYP.

PIPE CASING WHEN

APPLICABLE, SEE SHEET C705

TRENCHLESS WORK LIMITS

5'

WORK LIMITS

REMOVE EX. 12" STORM SEWER PIPE

3'

2'

ACCESS PIT SHALL BE AT LEAST

2' CLEAR OF STRUCTURE AND 3'

CLEAR OF FOOTING, TYP.

TRANSITION COUPLING,

IF REQUIRED

WATER TIGHT END SEAL, TYP.

CASING ENDS AT

WORK LIMITS

OPEN TRENCH CONSTRUCTION

OUTSIDE TRENCHLESS WORK

LIMITS

16" DIP STORM SEWER TO SPAN BETWEEN DI WALL

PIPE FITTINGS, SLOPE AT 0.55%

PROPOSED 15" STORM SEWER PIPE,

OPEN TRENCH CONSTRUCTION, TYP.

TRANSITION COUPLING,TYP.

16" DI WALL PIPE FITTING, TYP.

EACH WALL

16" DIP NIPPLE, TYP.

STANDARD BEDDING REQUIRED PER

TRENCH BACKFILL DETAIL

SEAL WALL OPENING WITH

NON-SHRINK GROUT, TYP.

4'±

FIELD VERIFY

DEPTH

0.7'±

FIELD VERIFY

DEPTH

pbsusa.com C707

UTILITY CORRIDOR CROSSING

DETAILS

2017-12-19T22:56:50-0800

George Drake, PE

File details come from the government source that posted it. Updated .