These architectural and engineering drawings detail a renovation project for Building 1106 at Hanscom Air Force Base, Massachusetts, focusing on repairing and replacing air conditioning units. The documents include comprehensive plans for demolition, construction, mechanical systems, electrical systems, and structural modifications across the first floor and basement of the conference center.
Key technical specifications include replacing existing HVAC equipment with new air conditioning units (AC-1, AC-4, ACCU-1, ACCU-4) using R-454B refrigerant, installing variable air volume (VAV) boxes with electric reheat, and implementing new control systems integrated with the building's management system. The project involves removing existing mechanical infrastructure, creating new ductwork and piping connections, and ensuring compliance with UFC (Unified Facilities Criteria) and NFPA 101 Life Safety Code standards. The construction is scheduled for completion by January 28, 2025, with the work primarily focused on in-kind replacement of mechanical, electrical, and communications equipment while maintaining the existing building's overall configuration.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF DRAWINGS
SYMBOL LEGEND: ● CURRENT ISSUE ○ PREVIOUSLY ISSUED
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IN
G
D
IV
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
G-000
C O
VE
R
JT JT R
W
W
BUILDING 1604
AFLCMC/P2IA
BASE CONTRACTING
BUILDING 1825
BASE ENVIRONMENTAL OFFICE
72 DOW ST
BUILDING 1810
BASE CIVIL ENGINEERING(BCE)
120 GRENIER ST
BUILDING 1721
BASE SAFETY OFFICE
HARTWELL AVE
GATE
ROUTE 2A/VANDENBURG GATE
AND VISITOR CENTER
BUS
PLAYGROUND
PL
AY
G R
O U
N D
O
BS
C U
R E
PL
AY
G R
O U
N D
BA
SK
ET
BA
LL
C
O U
R T
PLAYGROUNDEQUIPMENT
BA
SK
ET
BA
LL
C
O U
R T
I-9
I-9
I-95
I-9
ATLANTIC
OCEAN
BOSTON
BEDFORD
NASHUA
ATLANTIC OCEANMASSACHUSETTS
CONNECTICUT
VERMONT NEW HAMPSHIRE
RHODE
ISLAND
BOSTON
LEXINGTON
LYNN
SALEM
QUINCY
HINGHAM
WEYMOUTH
DEDHAM
BROOKLINE
FRAMINGHAM
BEDFORD
CONCORD
HANSCOM AFB
HANSCOM AFB, MASSACHUSETTS
BUILDING 1106 REPAIR/ REPLACE
AIR CONDITIONING UNITS
SOLICITATION NO. :
CONTRACT NO. : MXRD 15-0009
ISSUE DATE : 01/28/2025
DEPARTMENT OF THE AIR FORCE
AIR FORCE MATERIEL COMMAND
HANSCOM AIR FORCE BASE
PREPARED FOR:
66th ABG/CEN CIVIL ENGINEERING DIRECTORATE
ENGINEERING AND DESIGN SECTION
HANSCOM AIR FORCE BASE
PREPARED BY:
VICINITY MAP N
E
AIR FORCE MAT R
I EL COMMAND TH
GROUP66 AIR BA SE
I-90
I-93
I-93
SHEET
NUMBER SHEET NAME 01
/2 8/
Is su e
Fo r C on st ru ct io n
GENERAL
G-000 COVER ●
LIFE SAFTEY
LS-001 CODE SUMMARY AND LIFE SAFETY PLAN ●
STRUCTURAL
S-001 GENERAL NOTES, FRAMING PART PLAN AND DETAILS ●
ARCHITECTURE
A-001 LEGENDS, NOTES, ABBREVIATIONS ●
AD051 1ST FLOOR DEMOLITION PLAN ●
AD061 1ST FLOOR DEMOLITION REFLECTED CEILING PLAN ●
A-101 FIRST FLOOR CONSTRUCTION PLAN ●
A-102 ROOF CONSTRUCTION PLAN ●
AR101 1ST FLOOR REFLECTED CEILING PLAN ●
A-201 ELEVATIONS AND SCHEDULES ●
A-501 SECTIONS & DETAILS ●
A-502 SITE DETIALS ●
MECHANICAL
M-001 ABBREVIATIONS ●
M-002 SYMBOLS ●
MD101 BASEMENT AND 1ST FLOOR DEMOLITION PLAN ●
M-101 BASEMENT 1ST FLOOR CONSTRUCTION PLAN ●
M-102 ROOF CONSTRUCTION PLAN ●
M-501 DETAILS ●
M-502 DETAILS ●
M-601 SCHEDULES ●
M-701 CONTROL DIAGRAMS ●
M-702 EXISTING UNIT CONTROL DIAGRAMS ●
ELECTRICAL
E-001 SYMBOL LEGEND AND NOTES ●
ED101 1ST FLOOR DEMOLITION PLAN ●
EL101 1ST FLOOR LIGHTING PLAN ●
EP101 1ST FLOOR POWER PLAN ●
EP601 POWER SCHEDULES AND DETAILS ●
PROJECT LOCATION
B1106
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
UP
UP
UP
1' - 4"
7' - 1"
7' - 1"
5' - 2"
12' - 10" xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x7 x8 x8 xA.5 x7.5
50 SF/OCC
BACK
LOBBY
CL.
100 SF/OCC
KITCHEN 32
15 SF/OCC
BURLINGTON
15 SF/OCC
BEDFORD
150 SF/OCC
MAIN
OFFICE
150 SF/OCC
IT
OFFICE
CORR.
15 SF/OCC
HOLZMAN
15 SF/OCC
LINCOLN
150 SF/OCC
FOYER
7 SF/OCC
CONCORD
150 SF/OCC
PROJECTION
ROOM
LEXINGTON
150 SF/OCC
PROJECTION
ROOM
300 SF/OCC
SERVER
ROOM
VEST
300 SF/OCC
MECH
300 SF/OCC
MECH
WOMENS
300 SF/OCC
JANCL.
CL.
CL.
MAIN
ENTRY
HALL
150 SF/OCC
ENTRY
HALL
CL
MENS
DOOR
0.20*
68.5" CLR.
DOOR
0.20*
68.5" CLR.
DOOR
0.20*
68.5" CLR.
DOOR
0.20*
68.5" CLR.
DOOR
0.20*
68.5" CLR.
COMMON PATH = 89' - 10"
TRAVEL DISTANCE=101'
EXITS
MINIMUM NUMBER OF EXITS:
MAXIMUM TRAVEL DISTANCE IN NON-SPRINKLERED BUILDING:
REQUIRED PROVIDED
300 FT
150 FT MAX
CODE SUMMARY
APPLICABLE CODES
UNIFIED FACILITIES CRITERIA (UFC)
UFC 1-200-01: GENERAL BUILDING REQUIREMENTS; 02 FEB 2024 W/ CHANGE 3
UFC 3-600-01: FIRE PROTECTION ENGINEERING FOR FACILITIES; 06 MAY 2021 W/ CHANGE 6 UFC 4-010-01: DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS; 24 MAY 2024 W/ CHANGE 3
ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 - LIFE SAFETY CODE, 2024 EDITION
PROJECT DESCRIPTION
THIS PROJECT IS A RENOVATION/ ALTERATION WITHIN AN EXISTING BUILDING. THE ALTERATIONS TO
THE BUILDING INTERIOR PROPOSED FOR THIS PROJECT DO NOT CHANGE THE CONSTRUCTION
TYPE, OCCUPANCY CLASS OR USE GROUP - NOR DO THEY RESTRICT EXISTING PATHS OF EGRESS
PER NFPA CH.7 LIFE SAFETY CODE. THE EXISTING BUILDING IS NOT A FULLY SPRINKLERED
BUILDING.
THE SCOPE OF WORK FOR THIS PROJECT INCLUDES MINIMAL DEMOLITION OF EXISTING ROOF,
INTERIOR PARTITIONS AND MEP/FP. NEW CONSTRUCTION CONSISTS OF IN KIND REPLACEMENT OF PARTITIONS, MECHANICAL, ELECTRICAL & COMMUNICATIONS EQUIPMENT. CARE WILL BE TAKEN TO
PROTECT EXISTING FFE AND EXISTING MEP/FP INFRASTRUCTURE.
EXISTING BUILDING
AUTOMATIC SPRINKLER SYSTEM NOT PROVIDED
OCCUPANCY/GROUP CLASSIFICATION:
CONSTRUCTION TYPE:
GROSS FLOOR AREA (PER NFPA 101 SECTION 3.3.24.2.2)
OCCUPANT/SQ. FT:
SCOPE OF WORK BOUNDARY SQ. FT:
ASSEMBLY MAX OCCUPANT/SQ. FT:
BUSINESS MAX OCCUPANT/SQ. FT:
STORAGE OCCUPANT/SQ. FT:
TOTAL OCCUPANTS FIRST FLOOR:
ASSEMBLY - A
BUSINESS - B
(B=Accessory Use)
II B
14,870 SF
7/SF TO 300/SF
15,155 SF
1 PER 7 SF
1 PER 150 SF
1 PER 300 SF
CODE PLAN LEGEND
EXIT
NFPA VALUES (NFPA 101
TABLE 7.3.1.2. ) PROVIDED
FOR EGRESS LOAD
CALCULATIONS
XX
SF/OCC
Name ROOM NAME
NUMBER OF OCCUPANTS
OCCUPANT LOAD PER SF
MEANS OF EGRESS COMPONENT
CAPACITY FACTOR (TABLE 7.3.3.1, NFPA 101)
PROVIDED CLEAR WIDTH
CALCULATED OCCUPANT LOAD [OCCUPANT
LOAD FACTOR PER DIVIDED NUMBER OF
EXITS AVAILABLE (AVERAGE DISTRIBUTION) ]
MAXIMUM OCCUPANT CAPACITY (ACTUAL STAIR/DOOR
WIDTH DIVIDED BY CAPACITY FACTOR)
EXIT DOOR
0.20*
33" CLEAR
XXX
EGRESS TRAVEL PATH
DISTANCE AND DIRECTION
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B1152
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
LS-001
C O
D E
SU
M
M
AR
Y
AN
D L
IF
E
SA
FE
TY
P
LA
N
JT JT R
W
W /M
EB
SCALE: 1" = 10'-0"
1ST FLOOR LIFE SAFETY PLANC1
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
(E ) 1
4W F5
(E ) 1
4W F5
(E)12B22
(E)12B22
(E)12B22
(E)12B22
(E)12B22
(E)12B22
(E)12B22
(E)12B22
(E)12B22
3' - 1"
(E ) C
(E) C8
(E) C8
(E) C8
(E) C8
(E) C8
(E) C8
(E) C8
(E) C8
(E) C8
B2
S-001
B2
S-001
SLAB THICKNESS SEE EXIST. DWGS
EXISTING CONCRETE SLAB
ANGLE 6x4x5/16 (LLV) 1 EACH
SIDE OF OPENING
EXISTING STEEL
BEAM T.O. STEEL EL.
SEE PLAN
L6x4x3/8X6"
CLIP ANGLE
ARCH DWGS
COORDINATE WITH
3/16
3/16
TYP.
3/16
3/16
TYP.
EXISTING STEEL
BEAM
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B1152
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
S-001
G
EN
ER
AL
N O
TE
S, F R
AM
IN
G P
AR
T
PL
AN
A N
D D
ET
AI
LS
BR
W
IT
K
BR
W
SCALE: 1/8" = 1'-0"
EXISTING ROOF PART PLAND2
STRUCTURAL STEEL
FABRICATE AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS - ALLOWABLE STRESS DESIGN AND PLASTIC DESIGN," AND THE "CODE OF STANDARD PRACTICE" OF THE AISC. WELDING SHALL CONFORM TO THE REQUIREMENTS OF THE "STRUCTURAL WELDING CODE" OF THE
AMERICAN WELDING SOCIETY.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. STRUCTURAL STEEL CHANNELS SHALL CONFORM TO ASTM A572, GRADE 50. STRUCTURAL TUBES SHALL BE ASTM A500, GRADE B. STRUCTURAL STEEL PIPES SHALL CONFORM TO ASTM A53, GRADE B. STRUCTURAL STEEL PLATES AND ANGLES SHALL
CONFORM TO ASTM A36, UNLESS OTHERWISE NOTED.
DO NOT SPLICE STRUCTURAL STEEL MEMBERS WITHOUT WRITTEN APPROVAL OF THE ARCHITECT.
BOLTED CONNECTIONS SHALL BE MADE WITH THREE-QUARTERS INCH DIAMETER HIGH STRENGTH, ASTM A325-N
BOLTS, UNLESS OTHERWISE NOTED.
WELDING ELECTRODES SHALL CONFORM TO AWS A5.1 E70XX SERIES WITH PROPER ROD TO PRODUCE OPTIMUM
WELD (LOW HYDROGEN).
SCALE: 3/4" = 1'-0"
NEW OPENING IN EXISTING ROOFB2
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
PROFESSIONAL SEAL:
ALIGN
ABBREVIATIONS
WORKPOINT, CONTROL POINT OR DATUM
REFERENCE GRID
CENTERLINE
N.I.C
GENERAL SYMBOLS LEGEND
ENLARGED AREA CALLOUT
SHEET WHERE LOCATED
DETAIL NUMBER
EXTERIOR ELEVATION
INTERIOR ELEVATION - MULTIPLEA-101
DRAWING LOCATION
SHEET LOCATION
BUILDING CROSS SECTION
A-101
SIM
A-101
SIM
WALL SECTION
A-101
SIM
NORTH REFERENCE
PLAN NORTH
TRUE NORTH
SHEET NOTES
PARTITION TYPE G3A
REVISION INDICATOR
AREA OF REVISION
1 REVISION NUMBER - SHEET SPECIFIC
NAME
AREA
NUMBER
NAME
ELEVATION
A-101
SIM
1 1
ROOM NAME
100 SF
A-101
A-101
SIM
DETAIL
N
ALIGN
LIMIT OF WORK LINE
MATERIAL LEGEND
ACOUSTICAL CEILING PANELS
REFER TO RCP'S
ALUMINUM
BRICK
CONCRETE
CONCRETE MASONRY UNIT
STEEL
FINISHED WOOD
GYPSUM BOARD
PLYWOOD
MINERAL WOOL
WOOD BLOCKING
CONCRETE
MASONRY
METALS
WOOD, PLASTICS, AND COMPOSITES
THERMAL AND MOISTURE PROTECTION
POLYISO
XPS
SPRAY FOAM
FINISHES
GYPSUM BOARD - TYPE X
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
A-001
LE
G
EN
D
S, N
O
TE
S, A
BB
R
EV
IA
TI
O
N S
JT JT R
W
W /M
EB
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
AC AIR CONDITION
ACC ACCESSIBLE
ACCU AIR COOLED CONDENSING
UNIT
ACP ACOUSTIC CEILING PANEL
ACS FLR ACCESS FLOOR
ACS PNL ACCESS PANEL
ACST ACOUSTIC
ADJ ADJACENT
ADJA ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING
JUSTIDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANC ANCHOR, ANCHORAGE
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT
AVG AVERAGE
AW ACID WASTE
B/B BACK TO BACK
BALC BALCONY
BD BOARD
BEJ BRICK EXPANSION JOINT
BFF BELOW FINISH FLOOR
BITUM BITUMINOUS
BKBD BACKBOARD
BKG BACKING
BLDG BUILDING
BLKHD BULKHEAD
BLW BELOW
BM BEAM
BOS BOTTOM OF STEEL
BOT BOTTOM
BRDG BRIDGING
BSMT BASEMENT
BU BUILT-UP
C TO C CENTER TO CENTER
CAB CABINET
CB CATCH BASIN
CB CORNER BEAD
CCTV CLOSET CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS
CEM CEMENT
CF CONTRACTOR FURNISHED
CFCI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPEMENT
CFLG COUNTER FLASHING
CFOI CONTRACTOR FURNISHED /
OWNER INSTALLED
CG CORNER GUARD
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLO CLOSET
CLR CLEAR
CLRM CLASSROOM
CLWG CLEAR WIRED GLASS
CMU CONCRETE MASONRY UNIT
CO CABON MONOXIDE
CO2 CARBON DIOXIDE
COL COLUMN
CONC CONCRETE
CONTR CONTRACTOR
COORD COORDINATE
CPT CARPET
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CT STN CUT STONE
CTR CENTER
CTRL CONTROL
CTV CABLE TELEVISION
CU FT CUBIC FEET
D PENNY
DBL DOUBLE
DEFS DIRECT APPLIED EXTERIOR
FINISH SYSTEMS
DEG DEGREE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DR DOOR
DW DISHWASHER
DWG DRAWING
EA EACH
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATIONS
ELVR ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
EOS EDGE OF SLAB
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EPS EXPANDED POLYSTYRENE
BOARD (INSULATION)
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F/F FACE TO FACE
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF EL FINISH FLOOR ELEVATION
FF&E FURNITURE, FIXTURE, AND
EQUIPEMENT
FHC FIRE HOSE CABINET
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FLR FLOOR
FOF FACE OF FINISH
FOS FACE OF STUD
FP FIRE PROTECTION
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC
FT FEET, FOOT
FTG FOOTING
FURN FURNISH
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GF GROUND FACED
GFCI GROUND FAULT CIRCUT
INTERRUPTER
GFRC GLASS-FIBER-REINFORCED
CONCRETE
GFRG GLASS-FIBER-REINFORCED
GYPSUM
GFRP GLASS-FIBER-REINFORCED
PLASTIC
GL GLASS OR GLAZING
GMD GROUP-MOUNTED DEVICES
GWB GYPSUM WALL BOARD
GYM GYMNASIUM
GYP GYPSUM
HAZ HAZARD
HAZMAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HOLLOW CORE
HC HANDICAP
HCWD HOLLOW CORE WOOD DOOR
HDR HEADER
HDWD HARDWOOD
HIGH H
HM HOLLOW METAL
HO HOLD OPEN
HORIZ HORIZONTAL
HOSP HOSPITAL
HT HEIGHT
HW HARDWARE
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
KD KNOCKED DOWN
KIT KITCHEN
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LB POUND
LF LINEAR FOOT, FEET
LIN LINEAR
LINO LINOLEUM
LPT LOW POINT
M MR MOISTURE RESISTANT
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MDF MEDIUM DENSITY
FIBERBOARD
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURER
MISC MISCELLANOUS
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
MWP MEMBRANE WATERPROOFING
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF/CI OWNER FURNISHED /
CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED / OWNER
INSTALLED
OH DR OVERHEAD (COILING) DOOR
OPNG OPENING
OPP OPPOSITE
OPPH OPPOSITE HAND
OPQ OPAQUE
OPR OPERABLE
PAR PARALLEL
PART PARTIAL
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PEJ PREMOLDED EXPANSION
JOINT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLB PLUMB
PLBG PLUMBING
PLWD PLYWOOD
PNL PANEL
POL POLISHED
POLY POLYETHYLENE, PLASTIC
PORC PORCELAIN
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PREP PREPERATION
PRMLD PREMOLDED
PT PAINT
PTN PARTITION
PV PHOTOVOLTATIC
PVC POLYVINYL-CHLORIDE
(ROOFING)
QT QUARRY TILE
QTR QUARTER
QTY QUANITY
RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REINF REINFORCE
REM REMOVABLE
REPL REPLACE
RES RESILIENT
REV REVERSE
RFG ROOFING
RFI REQUEST FOR INFORMATION
RH ROOF HATCH
RH RIGHT HAND
RIS RISER
RM ROOM
RTD RATING, RATED
RTU ROOF TOP UNIT
RWL RAIN WATER LEADER
SC SOLID CORE
SCWD SOLID CORE WOOD DOOR
SD STORE DRAIN
SECT SECTION
SF SQUARE FOOT, SQUARE FEET
SHR SHOWER
SIM SIMILAR
SK SKETCH
SLDG SLIDING
SLNT SEALANT
SPEC SPECIFICATIONS
SQ SQUARE
SST STAINLESS STEEL
STC SOUND TRANSMITION CLASS
STD STANDARD
STN STONE
STNLS STAINLESS
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SUSP CLG SUSPENDED CEILING
SV SHEET VINYL
SYMM SYMMETRICAL
T TREAD
TB TACK BOARD
TEL TELEPHONE
TEMP TEMPORARY
THK THICKNESS
THRES THRESHOLD
TMPD TEMPERED
TMPD GL TEMPERED GLASS
TNG TONGUE AND GROOVE
TNM TIME AND MATERIALS
TO TOP OF
TPD TOILET PAPER DISPENSER
TPH TOILET PAPER HOLDER
TPO THERMOPLASTIC POLYOLEFIN
TRTD TREATED
TYP TYPICAL
UCD UNDERCUT DOOR
UNEX UNEXCAVATED
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
UR URINAL
VAN VANITY
VAR VARIED
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VR VAPOR RETARDER
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WITH
W/O WITHOUT
WC WATER CLOSET
WCN WATER CURTAIN
WD WOOD
WH WALL HUNG
WO WHERE OCCURS
WP WORKING POINT
WPG WATERPROOFING
WPM WATERPROOF MEMBRANE
WPR WEATHERPROOF
WR WEATHER RESISTANT
WWR WELDED WIRE REINFORCING
XFMR TRANSFORMER
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
T
T
M
S xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8 xA.5 x7.5
CL.
KITCHEN
CL
MECH
MECH
CL.
BACK LOBBY HOLZMAN
LINCOLN
ENTRY HALL
FOYER
CONCORD LEXINGTONPROJECTION
ROOM
CORR.
VEST
CL.
SERVER
ROOM
PROJECTION
ROOM
JAN
WOMENSIT OFFICE
CL.
MAIN ENTRY
HALL
MAIN OFFICE
BEDFORDBURLINGTON
CORRIDOR
CORR.
MENS
'-1
1/
2" 2'
-0
D10D10
D4
D1
D2
D8
D8
D8
D8
D6 D11
D9 D9
D5 D3
WP
D9
D5
D4
D7
3' -1
1/
2"
D12 xA xB x7 x8 xA.5 x7.5
779 SF
ELECTRICAL
RM.
AREA
WAY
AREA
WAY
AREA
WAY
EXISTING
CONTROL
PANEL, REFER
TO MEP DWGS
1.
A.
B.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
THE CONTRACTOR SCOPE INCLUDES THE FOLLOWING:
*PRIOR TO DISTURBANCE, THE ACM IDENTIFIED MUST BE
ABATED BY A COMMONWEALTH OF MASSACHUSETTS-
LICENSED ASBESTOS ABATEMENT CONTRACTOR
FOLLOWING ALL FEDERAL, STATE & LOCAL REGULATIONS
GOVERNING ASBESTOS ABATEMENT. ALSO COMPLY
WITH 02 82 14.00 10: ASBESTOS HAZARD CONTROL
ACTIVITIES AND 02 82 16.00 20: ENGINEERING CONTROL
OF ASBESTOS CONTAINING MATERIALS. A COPY OF THE
ASBESTOS WASTE SHIPMENT RECORD MUST BE
RECEIVED WITHIN 35 DAYS OF REMOVAL FROM THE SITE.
ASBESTOS AIR QUALITY SAMPLING MUST BE CONDUCTED
UNDER USEPA REGULATIONS FOLLOWING ASBESTOS
ABATEMENT. IF ADDITIONAL MATERIALS ARE DISCOVERED
THAT HAVE NOT BEEN SAMPLED, THOSE MATERIALS
SHOULD BE CONSIDERED ACMS UNTIL LABORATORY
ANALYSIS DETERMINES OTHERWISE. (CITATION IS FROM
HAZMAT SURVEY & REPORT FOR BUILDING 1106 BY CDW)
REMOVAL OF EXISTING CONSTRUCTION (PARTITIONS,
COMPONENTS, BUILDING EQUIPMENT, ETC) SHOWN
WITHIN SCOPE OF WORK AS REQUIRED TO PERFORM THE
WORK, CONTRACTOR TO COORDINATE DEMOLITION
SCOPE WITH NEW WORK TO ENSURE NO DISRUPTIONS IN
THE PROJECT.
C. BEFORE COMMENCING THE WORK, VERIFICATION AT THE
SITE OF EXISTING CONSTRUCTION TO BE PRESERVED
AND REPORTING TO THE CONTRACTING OFFICER OF ANY
DISCREPANCIES OR QUESTIONABLE ITEMS.
D. COMPLY WITH APPLICABLE CODES AND REGULATIONS
PERTAINING TO SAFETY OF PERSONS, PROPERTY AND
ENVIRONMENTAL PROTECTION.
PROVIDE AND MAINTAIN BARRICADES, LIGHTING AND
GUARDRAILS AS REQUIRED BY APPLICABLE CODES AND
REGULATIONS TO PROTECT OCCUPANTS OF BUILDING AND
WORKERS.
PRIOR TO DEMOLITION, MEET WITH THE CONTRACTING
OFFICER TO IDENTIFY ITEMS WHICH ARE TO BE SALVAGED.
ALL OTHER DEMOLISHED MATERIALS ARE TO BE REMOVED
FROM THE SITE AND DISPOSED OF LEGALLY BY THE
CONTRACTING OFFICER.
ENSURE ADJACENT OCCUPIED SPACES MAINTAIN
ACCEPTABLE ENTRANCE/EGRESS ROUTES.
ERECT AND MAINTAIN DUST-PROOF PARTITIONS AS REQUIRED
TO PREVENT SPREAD OF DUST, FUMES AND SMOKE, ETC. TO
OTHER PARTS OF THE BUILDING. ON COMPLETION, REMOVE
PARTITIONS AND REPAIR DAMAGED SURFACES TO MATCH
ADJACENT SURFACES.
REMOVE AND SALVAGE DEBRIS FROM THE SITE DAILY AS IT
ACCUMULATES. REMOVE RENOVATION MATERIALS FROM THE
SITE, LEAVING A CLEAN, VACUUMED SPACE IN ACCORDANCE
WITH THE INDOOR AIR QUALITY CONSTRUCTION
MANAGEMENT PLAN.
UTILIZE BRACING AND SHORING WHERE NECESSARY TO
PREVENT COLLAPSE OF STRUCTURE OR PARTS THEREOF.
GENERAL CONTRACTOR IS RESPONSIBLE FOR DESIGN AND
CONSTRUCTION OF ALL BRACING AND SHORING.
PROTECT EXISTING CONSTRUCTION TO REMAIN. REPAIR ANY
DAMAGE TO EXISTING CONSTRUCTION IN A MANNER
ACCEPTABLE TO THE CONTRACTING OFFICER OR REPLACE
SUCH DAMAGE WITH NEW ACCEPTABLE TO THE
CONTRACTING OFFICER AND AT NO COST TO THE
GOVERNMENT.
MAINTAIN SERVICES AND SYSTEMS INDICATED TO REMAIN
AND PROTECT AGAINST DAMAGE DURING SELECTIVE
DEMOLITION OPERATIONS.
WHERE MECHANICAL OR ELECTRICAL SYSTEMS ARE
INDICATED TO BE SELECTIVELY DEMOLISHED, LOCATE,
IDENTIFY, DISCONNECT, AND REMOVE. NO SYSTEMS ARE TO
BE ABANDONDED IN PLACE, REMOVE UNUSED DISTRIBUTION
AND INFRASTRUCTURE TO SOURCE. REFER TO ENGINEERED
PLANS FOR FURTHER DEMOLITION OF ENGEERING SYSTEMS.
PATCH UNUSED PENETRATIONS CAUSED FROM DEMOLITION
TO MATCH ADJACENT CONSTRUCTION AND RATINGS.
SALVAGE BUILDING STANDARD LIGHT FIXTURES AT CEILING
DEMOLISHED AREAS FOR RE-USE AS INDICATED ON
ELECTRICAL DRAWINGS. COORDINATE WITH CONTRACTING
OFFICER WHICH LIGHT FIXTURES ARE TO BE SALVAGED FOR
STORAGE.
SALVAGE DEVICES THAT ARE BUILDING STANDARD THAT MEET
CURRENT CODE REQUIREMENTS FOR RE-USE (EXIT SIGNS,
HORN STROBES, EMERGENCY LIGHTS).
ALL AUDIO VISUAL EQUIPMENT THAT ARE SCHEDULED TO
REMAIN ARE TO BE PROTECTED FROM DUST AND DEBRIS
DURING DEMOLITION AND CONSTRUCTION.
DEMOLITION PLAN GENERAL NOTES
*NOTE: ASBESTOS ABATEMENT MUST TAKE PLACE
PRIOR TO DEMOLITION.
DEMOLITION SYMBOLS LEGEND
EXISTING DOOR TO REMAIN,
TYP U.N.O.
REMOVE EXISTING DOOR &
FRAME COMPLETELY.
REMOVE PORTION OF EXISTING WALL.
SEE FLOORPLAN FOR LOCATION AND
DIMENSION. TYP U.N.O.
EXISTING WALL OR PARTITION TO
REMAIN, TYP U.N.O.
D# DEMOLITION SHEETNOTE TAG
REMOVE ALL CONSTRUCTION SHOWN
DASHED COMPLETE, U.N.O.
LIMIT OF WORK LINE
(NIC) NOT IN CONTRACT
WP WORK POINT
AREA OF ASBESTOS ABATEMENT
DEMOLITION SHEET NOTES
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B115204 8 16268
SCALE: 1/8"=1'-0"
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
AD051
1S T
FL
O
O R
D
EM
O
LI
TI
O
N P
LA
N
JT JT R
W
W /M
EB
SCALE: 1/8" = 1'-0"
1ST FLOOR DEMOLITION PLANC1
SCALE: 1/8" = 1'-0"
BASEMENT DEMOLITION PLANA1
D1 REMOVE EXISTING FENCE; SET ASIDE AND PROTECT FOR
REUSE.
D2 REMOVE EXISTING PARTITIONS.
D3 REMOVE EXISTING DOOR.
D4 DEMOLISH EXISTING LOUVERS IN BRICK KNEE WALL.
D5 DEMOLISH EXISTING EXTERIOR CONCRETE PADS.
D6 VERIFY EXISTING CONDITIONS PRIOR TO DEMOLITION.
D7 ABATE FLOOR ASSEMBLY - LIMIT WORK TO ONLY AREA
IMPACTED BY DEMOLITION OR NEW WORK
D8 PROTECT EXISTING TO REMAIN AUDIO VISUAL EQUIPMENT.
D9 PROTECT EXISTING WINDOW TREATMENTS
D10 DISCONNECT AND RELOCATE FFE OUT OF WORK AREA,
CONTRACTOR TO TAKE OWNERSHIP OF FFE DURING
CONSTRUCTION AND RETURN TO THE GOVERNMENT AFTER
THE WORK IS COMPLETE.
D11 PROTECT ETR METAL ROLL-UP DOOR AND COUNTER.
D12 SALVAGE EXISTING ROOM SIGNAGE FOR REINSTALL
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
M
M
M xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8
BEDFORD
KITCHEN
MAIN OFFICE
IT OFFICE
CL.
WOMENS
JANJAN
MAIN ENTRY
HALL
PROJECTION
ROOM
LEXINGTON
SERVER
ROOM
VEST
CL.
PROJECTION
ROOM
HOLZMAN
MECH
MECH
LINCOLN
FOYERCL.
CL.
CL
xA.5 x7.5
ENTRY HALL
BURLINGTON
CONCORD
CORR.
CORR.
BACK LOBBY
CORRIDOR
DR1
DR1
2' -0
"WP
DR3
DR2
DR2
DEMOLITION RCP GENERAL NOTES
1. ALL INFORMATION FROM GENERAL DEMOLITION NOTES
APPLIES TO RCP DEMOLITION, UNLESS OTHERWISE NOTED.
2. ALL ACOUSTICAL CEILING TILE AND GRIDS SHOWN TO BE
REMOVED FOR REUSE ARE TO BE REMOVED CAREFULLY,
STORED AND PROTECTED FOR REINSTALLATION
3. ALL EXISTING FIXTURES THAT ARE TO BE REMOVED FOR
REUSE ARE TO BE SALVAGED, STORED AND PROTECTED
FOR RELOCATION
4. REMOVE ANY CEILING TILE THAT ARE BROKEN,
WARPED, WATER DAMAGED OR DISCOLORED, AND
REPLACE WITH NEW OR REUSED TILES TO MATCH EXISTING.
5. VERIFY LOCATIONS/DIMENSIONS OF GRID TO BE
DEMOLISHED, REFERENCE CONSTRUCTION PLAN FOR
COORDINATION.
DEMOLITION RCP SHEET NOTES
DEMO RCP SYMBOLS LEGEND
REMOVE PORTION OF EXISTING WALL.
SEE FLOORPLAN FOR LOCATION AND
DIMENSION. TYP U.N.O.
EXISTING WALL OR PARTITION TO
REMAIN, TYP U.N.O.
D# DEMOLITION SHEETNOTE TAG
REMOVE ALL CONSTRUCTION SHOWN
DASHED COMPLETE, U.N.O.
LIMIT OF WORK LINE
(NIC) NOT IN CONTRACT
WP WORK POINT
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B115204 8 16268
SCALE: 1/8"=1'-0"
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
AD061
1S T
FL
O
O R
D
EM
O
LI
TI
O
N R
EF
LE
C
TE
D C
EI
LI
N G
P
LA
N
JT JT R
W
W /M
EB
SCALE: 1/8" = 1'-0"
1ST FLOOR DEMOLITION RCPC1
DR1 REMOVE CEILING GRID AND TILE TO NEAREST GRID LINES;
SALVAGE AND STORE FOR REUSE.
DR2 SAWCUT ROOF FOR NEW FRESH AIR INTAKE, REFER TO
ROOF PLANS FOR OPENING LOCATION
DR3 DISCONNECT, REMOVE, CLEAN AND STORE EXISTING
LIGHTING FOR REINSTALL, TYP.
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
T
T
T
S
UP
CONSTRUCTION SYMBOLS LEGEND
EXISTING WALL
EXISTING DOOR
TO REMAIN
NEW WALL
NEW DOOR
(SEE DOOR
SCHEDULE)
G3A PARTITION TYPE
ROOM TAG
ROOM NAME
100 SF
CONSTRUCTION
SHEET NOTE TAG
LIMIT OF WORK LINE
AREA
DOOR NUMBER
(NIC) NOT IN CONTRACT
WP WORK POINT
MECHANICAL SCOPE MAY STILL REQUIRE WORK
AND/OR ACCESS IN THIS AREA
xA xB x7 x8 xA.5 x7.5
779 SF
ELECTRICAL
RM.
AREA
WAY
AREA
WAY
AREA
WAY
APPROXIMATE
LOCATION OF
EXISTING NCE
CONTROLLER
EQUIPMENT IS IN
CLOSE PROXIMITY TO
ELECTRICAL SERVICE
ENTRANCE AND
STEPDOWN
TRANSFORMER (4160v) xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x7 x8 x8
MAIN OFFICE
IT OFFICE
HOLZMAN
LINCOLN
FOYER
CONCORD PROJECTION
ROOM
LEXINGTON
PROJECTION
ROOM
SERVER
ROOM
VEST
BACK LOBBY
WOMENS
JAN
CL.
CL.
CL.
KITCHEN
BURLINGTON BEDFORD
MAIN OFFICE
IT OFFICE
CORR.
HOLZMAN
LINCOLN
FOYER
CONCORD PROJECTION
ROOM
LEXINGTON
PROJECTION
ROOM
SERVER
ROOM
VEST
MECH
MECH
WOMENS
JAN
CL.
CL.
CL.
CL.
MAIN ENTRY
HALL
ENTRY HALL
xA.5 x7.5
A-201
F5
A-201F6
A-201
F9
A1 A-201
45°
AL
IG
N
CORRIDOR
MENS
A1 A-501
A-101 A4
26A
WP
'-0
B
2' -6
7'-4"
3'-2"
TYP.
S4B.U
4" HOUSEKEEPING
PAD
SIZE TO MATCH
EQUIPMENT
FOOTPRINT +1"
AROUND EACH SIDE
2' -2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
ALL EXISTING WALLS TO REMAIN THAT CONNECT WITH NEW
CONSTRUCTION ARE TO BE PATCHED AND REPAIRED TO MEET
REQUIREMENTS OF NEW FINISHES, U.N.O. REFER TO
SPECIFICATIONS FOR LEVEL OF FINISH.
FOR DRYWALL FINISHING, THE CONTRACTOR SHALL COMPLY
WITH MANUFACTURER'S PRINTED INSTRUCTIONS AND
SPECIFICATIONS, EXCEPTION: COMPLY WITH MORE STRINGENT
REQUIREMENTS OF GYPSUM ASSOCIATION GA-216
RECOMMENDED SPECIFICATION FOR THE APPLICATION AND
FINISHING OF GYPSUM BOARD.
PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH
FACE, UNLESS OTHERWISE NOTED. MAINTAIN DIMENSIONS
MARKED "CLEAR" OR "HOLD". ALLOW FOR THICKNESS OF
FINISHES.
PRIOR TO CLOSING ANY WALLS OR CEILINGS, ALL SYSTEMS
(HVAC, PLUMBING, ELECTRICAL) SHALL BE INSPECTED, AND
WHERE REQUIRED, TESTING BY CONTRACTOR ENGINEERS AND
BY PROPER AUTHORITIES HAVING JURISDICTION TO INSURE
THEIR PROPER INSTALLATION AND FUNCTION.
THE CONTRACTING OFFICER RESERVES THE RIGHT TO MOVE
ANY FIXTURE, RECEPTACLE OR BUILT-IN OBJECT UP UNTIL THE
TIME HE/SHE SHALL APPROVE THE WALLS OR CEILINGS TO BE
CLOSED. THIS APPROVAL SHALL TAKE PLACE PRIOR TO THE
INSPECTORS APPROVAL SO AS NOT TO CONFLICT WITH ANY
BUILDING OFFICIALS DECISIONS.
MAINTAIN EXITS, EXIT LIGHTING, FIRE PROTECTIVE DEVICES AND
ALARMS IN CONFORMANCE WITH CODES AND ORDINANCES
DURING CONSTRUCTION.
PROTECT AREA OF WORK AND ADJACENT AREAS FROM DAMAGE
DURING CONSTRUCTION.
MAINTAIN WORK AREAS SECURE AND LOCKABLE DURING
CONSTRUCTION. COORDINATE WITH CONTRACTING OFFICER TO
ENSURE SECURITY.
DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. IN
CASE OF CONFLICT, CONSULT THE CONTRACTING OFFICER.
ALL DOOR OPENINGS TO BE NO LESS THAN 6" FROM NEAREST
PERPENDICULAR PARTITION, U.N.O.
UNDERCUT DOORS TO CLEAR TOP OF FLOOR FINISHES BY 1/4",
UNLESS OTHERWISE NOTED.
ALL PARTITIONS SHALL BE PLUMB, SQUARE, STRAIGHT, AND
PARALLEL, PERPENDICULAR, OR AT 45-DEGREE ANGLE TO THE
CLOSEST BUILDING GRID, U.N.O.
INDICATED PARTITION TYPES ARE CONTINUOUS ABOVE/BELOW
DOOR AND WINDOW OPENINGS AND AROUND CORNERS UNTIL
INTERSECTION WITH A DIFFERENT TYPE. WHERE PARTITIONS
INTERSECT AT “T”, THE INDICATED TYPE RUNS ACROSS THE “T”
U.N.O.
AT LOCATIONS OF ABOVE CEILING MEP PENETRATIONS,
MAINTAIN WALL ACOUSTIC AND FIRE RATING.
ON CONTINUOUS WALL SURFACES WHERE CONSTRUCTION
INVOLVES MORE THAN ONE MATERIAL, FINISH, OR MATERIAL
THICKNESS, LOCATE FRAMING SO THE FINISHED FACES ALIGN,
U.N.O.
REFER TO SHEET A-201 FOR TYPICAL MOUNTING HEIGHTS.
LIMIT OF WORK LINE INCLUDES AREAS SERVED BY NEW AND
EXISTING MECHANICAL SYSTEM - SEE MECHANICAL DRAWINGS -
INCLUDING INTERIOR SPACE WITHIN LIMIT OF WORK LINE SHOWN.
CONSTRUCTION PLAN
GENERAL NOTES
CONSTRUCTION SHEET NOTES
xC
A1 A-501
6'-6" 1'-5"
'-0
3'-0"
4' -0
4' -0
4'-0"
CHAINLINK FENCE GATE
48" x FULL HEIGHT
REFER TO
FOR DETAILS
NEW ATFP COMPLIANT
CHAINLINK FENCE
MECHANICAL
EQUIPMENT
ENCLOSURE
9' -4
4'
-0
8' -5
9'-9"
/C6 A-502
26A
B
MECH
PROVIDE NEW CARPET TO MATCH
TOOTH CARPET INTO EXSITNG
ASSEMBLY TO BLEND
PROVIDE BROADCAST EPOXY
EPOXY TO CARPET TRANSITION
REMOVE AND SALVAGE TILE AS
REQUIRED TO COMPLETE THE WORK
USE SALVAGED TILE TO INFILL AS
REQUIRED TO REPAIR ADJACENT
AREAS IMPACTED BY CONSTRUCTION
(E) 12x12 TILE
(E) CARPET
CARPET SYSTEM UNKNOWN (TILE
OR BROADLOOM)
PROVIDE WALL BASE TO MATCH
EXISTING
PAINT DOOR AND FRAME TO MATCH WALLS
SALVAGE ANY BUILDING STANDARD
SIGNAGE FOR REINSTALL
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B115204 8 16268
SCALE: 1/8"=1'-0"
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
A-101
FI
R
ST
F
LO
O
R C
O N
ST
R
U C
TI
O
N P
LA
N
JT JT R
W
W /M
EB
SCALE: 1/8" = 1'-0"
BASEMENT CONSTRUCTION PLANA1
SCALE: 1/8" = 1'-0"
FIRST FLOOR CONSTRUCTION PLANC1
1 CONCRETE EQUIPMENT PAD
2 REFER TO MECHANICAL
3 PRESERVE AND PROTECT METAL
ROLL-UP DOOR AND COUNTER - ETR
4 MASONRY WALL INFILL
SCALE: 1/4" = 1'-0"
EQUIPMENT PAD PLANA4 SCALE: 1/8" = 1'-0"
FINISH PLANA6
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/ xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8 xA.5 x7.5 A1
A-201
A1 A-501
EQ
R
.O
1' -1
0"
EQ
EQ
R
.O
1' -1
0"
EQ
V.
I.F
4'
-7
V.
I.F
4'
-7
APPROXIMATE
LOCATION OF
STEEL BELOW
2'-6" R.O.
1'-8"
2'-6" R.O.
1'-8"
STRUCTURAL REINFORCING BELOW,
REFER TO STRUCTURAL DRAWINGS
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B115204 8 16268
SCALE: 1/8"=1'-0"
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
A-102
R O
O F
C O
N
ST
R U
C
TI
O N
P
LA
N
JT JT R
W
W /M
EB
SCALE: 1/8" = 1'-0"
ROOF CONSTRUCTION PLANC1
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
S
S
DS
F
F
F
5° R
5°
S xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8 xA.5 x7.5
BEDFORDKITCHEN
MAIN OFFICE
IT OFFICE
CL.
WOMENS
JANJAN
MAIN ENTRY
HALL
PROJECTION
ROOM
LEXINGTON
SERVER
ROOM
VEST
CL.
PROJECTION
ROOM
HOLZMAN
MECH
MECH
LINCOLN
FOYER
CL.
CL.
CL
ENTRY HALL
CORRIDOR
BURLINGTON
CONCORD
CORR.
CORR.
BACK LOBBY
R1
R1
ETS
ETS
WP
R2
R2
REFLECTED CEILING
PLAN GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
THIS PLAN IS FOR CEILING FIXTURE AND EQUIPMENT
LOCATIONS ONLY. REFER TO MEP/FP DRAWINGS FOR
ADDITIONAL INFORMATION.
ALL CEILING HEIGHTS ARE ABOVE FINISH FLOOR, WHERE
THE FINISH FLOOR EQUALS 0'-0". CEILING HEIGHT SHALL BE
UNIFORM THROUGHOUT U.N.O.
ALL DOWN LIGHTS, SMOKE DETECTORS, SPRINKLER HEADS,
EXIT SIGNS, ETC. TO BE CENTERED IN CEILING TILE, U.N.O.
ALL DIMENSIONS OF FIXTURES, DEVICES, SPRINKLER
HEADS, ETC. ARE TO CENTERLINE OF FIXTURE, U.N.O.
WHERE ITEMS ARE IN LINE, CENTERLINE OF ITEMS OR
GROUP OF ITEMS ARE TO ALIGN, U.N.O.
CEILING SYSTEM IS TO BE CENTERED IN ALL ROOMS, U.N.O.
REFER TO RCP FOR GRID LINE OR TILE TO BE CENTERED.
PATCH EXISTING CEILING TO MATCH ADJACENT CEILING
WHERE EXISTING WALLS DEMOLISHED. CUT THROUGH
EXISTING CEILING AND PATCH INTERFACE WHERE NEW
WALL IS BEING BUILT OR BEING EXTENDED TO DECK.
ALL MEP/FP LOCATIONS IN CONFLICT WITH ARCHITECTURAL
DRAWINGS SHOULD BE COORDINATED WITH THE
CONTRACTING OFFICER PRIOR TO INSTALLATION. NOTIFY
CONTRACTING OFFICER OF ANY DISCREPANCY, OMISSION,
OR UNANTICIPATED FIELD CONDITION THAT ALTERS THE
INTENT OF THESE DRAWINGS.
ALL CEILING SYSTEMS SHALL BE SUPPORTED INDEPENDENT
OF ALL NEW AND EXISTING PIPES, DUCTS, CONDUITS, ETC.
COORDINATE LOCATION, SIZE AND MOUNTING OF NEW
PROJECTORS WITH AV CONSULTANT AND CONTRACTING
OFFICER.
REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS
FOR BASELINE TESTING OF EXISTING AND NEW HVAC
SYSTEM.
REPLACE ALL DAMAGED AND STAINED CEILING TILES
WHERE CEILINGS ARE TO BE REUSED. MATCH EXISTING.
FINISH OF HVAC DIFFUSERS, DRAPERY POCKETS AND
SPEAKER GRILLS TO MATCH ADJACENT FINISH, U.N.O.
THE CONTRACTOR SHALL CLEAN AND RE-LAMP ALL LIGHT
FIXTURES TO BE RELOCATED OR THAT ARE EXISTING TO
REMAIN.
THE CONTRACTOR SHALL CLEAN ALL HVAC DIFFUSERS AND
GRILLES THAT ARE EXISTING TO REMAIN.
COORDINATE ALL CEILING ACCESS PANEL LOCATIONS WITH
CONTRACTING OFFICER PRIOR TO INSTALLATION.
EXIT SIGN
WALL WASHER
WALL SCONCE
SUPPLY AIR DIFFUSER
OCCUPANCY SENSOR
DAYLIGHT SENSOR
WIRELESS ACCESS
POINT OUTLET
FIRE ALARM AUDIO/STROBE
FIRE ALARM STROBE ONLY
FIRE ALARM HEAT
DETECTOR, FIXED TEMP
FIRE ALARM HEAT
DETECTOR, COMBO RATE
SMOKE DETECTOR
SPEAKER
SPRINKLER HEAD
UPRIGHT SPRINKLER
NO CEILING - EXPOSED TO
STRUCTURE
(SEE FINISH SCHEDULE
FOR EXPOSED ITEMS TO
BE PAINTED)
NEW 2'X2' ACOUSTICAL
CEILING
NEW GWB CEILING SOFFIT
NEW 2'X4' ACOUSTICAL
CEILING
8'-0"
GWB-8
CEILING HEIGHT (A.F.F.)
ETS
NOTE: GENERIC DEVICE SYMBOLS SHOWN BELOW- SEE SPECIFIC DISCIPLINES (MECH.,
ELEC., ETC.) FOR SPECIFIC DESCRIPTIONS AND ADDITIONAL ITEMS NOT SHOWN.REFLECTED CEILING LEGEND
EXISTING 2'X2' ACOUSTICAL
CEILING
EXISTING 2'X4' ACOUSTICAL
CEILING
EXISTING GWB CEILING SOFFIT
R# REFLECTED
CEILING PLAN
SHEET NOTE
RETURN AIR GRILLE
EXISITNG RETURN AIR
DIFFUSER
EXISTING RETURN AIR GRILL
EXISTING SPRINKLER
WP WORK POINT
REFLECTED CEILING
SHEET NOTES
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B115204 8 16268
SCALE: 1/8"=1'-0"
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
AR101
1S T
FL
O
O R
R
EF
LE
C
TE
D
C
EI
LI
N
G P
LA
N
JT JT R
W
W /M
EB
SCALE: 1/8" = 1'-0"
CONSTRUCTION RCPC1
R1 REINSTALL EXISTING GRID AND TILE FROM SALVAGE.
R2 RE-LAMP SALVAGED LIGHTING AS REQUIRED AND
RE-INSTALL AT THE SAME LOCATION UPON COMPLETION
OF ABOVE CEILING WORK BY OTHER TRADES. MAKE
SURE THAT ALL EXISTING FIXTURES IN OPERATIONAL
CONDITION PRIOR TO RE-INSTALLATION., TYP,
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
T T
TS
T T T
SD
SD
S
1ST FLOOR
0" x1
VINYL COVE
BASE TO MATCH
EXIST.
EXIST.
DOOR AND
CLOSET
PROPOSED
ETR
CONSTRUCTION
MECH. CLOSET
WALL BEYOND
1ST FLOOR
0" xC
EXIST. 4" VINYL
COVE BASE
4" VINYL COVE BASE -
COLOR TO MATCH
EXIST.
45-DEG MECH.
CLOSET WALL
PROPOSED
EXIST.
ELECTRICAL
PANEL - ETR
OPEN
A
DOUBLE WALL ACOUSTIC
TRANSFER DUCT; REFER
TO MECH.
WP
ETR
CONSTRUCTION
1ST FLOOR
0" x1
4" VINYL COVE
BASE - COLOR
TO MATCH EXIST.
45-DEG MECH.
CLOSET WALL
OPEN
B
DOUBLE WALL
ACOUSTIC TRANSFER
DUCT; REFER TO MECH.
SALVAGED CEILING AND
SYSTEMS TO REINSTALL,
REFER TO RCP FOR
LOCATIONS
1ST FLOOR
0"
ROOF
15'-0" xAxBxCxD
EXISTING LOUVER TO
REMAIN
ROOFTOP DUCT
EXTENSION BEYOND
BRICK INFILL TO
MATCH EXISTING
BRICK INFILL TO
MATCH EXISTING
MECHANICAL
EQUIPMENT - SEE
MECH.
CONCRETE
EQUIPMENT PAD
A1 A-501
METAL EQUIPMENT
STAND - SEE MECH.
C5 A-501
TYP
2' -8
E5 A-501
TYP
NEW ATFP COMPLIANT 8' TALL CHAINLINK FENCE EQUIPMENT ENCLOSURE
(E) MECH EQUIPMENT TO REMAIN
8' -0
1'
-6
SWITCHES
OUTLETS
3' -2
CARD READER
THERMOSTAT
FINISHED FLOOR
TYPICAL MOUNTING HEIGHTS
SCALE 1/2" = 1'-0"
6' -8
FIRE ALARM STROBE
4' -0
MOUNTING HEIGHTS GENERAL NOTES
1.
2.
3.
ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FINISHED FLOOR TO CENTERLINE OF DEVICE, U.N.O. EXCLUDING EXIT SIGNS.
DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE WHEREVER POSSIBLE
ALL DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED, U.N.O.
SCHEDULED SHAFTWALL
HM FRAME
SEALANT
DOOR PANEL
2"
1/2"
FRAME ANCHOR PER WALL ASSEMBLY
1/2"
CORRIDORMECH.
EQ.
5/ 8"
EQ.
DOOR PANEL TYPES
AS
S
C H
ED
U
LE
D
PN
L-
F- H
M
SCHED.
AS
FRAME TYPES
C6
A-201
C6
A-201
2"
SCHED.
AS 2"
2"
AS
S C
H
ED
U
LE
D
FRM-00HM-1
HARDWARE SETS
HS-1 STORAGE
3PR BUTT HINGES
1 LOCKSET WITH LEVER - STORAGE FUNCTION
REMOVABLE LOCK CORE1
2 PARALLEL ARM WITH BUILT-IN HOLD OPEN SET TO 170DEG (MOUNTED ON THE INTERIOR)
1 SET FLUSH BOLT W/ DUST PROOF STRIKE - CONSTANT LATCHING
1 COORDINATOR
2 ARMOR PLATE (MOUNTED ON INTERIOR)
DOOR AND HARDWARE GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
DOORS AND DOOR HARDWARE TO BE ADA COMPLIANT WITH BUILDING & FIRE
CODES.
SEE FLOOR PLANS AND PARTITION TYPES FOR THROAT DEPTHS, NEW FRAMES IN
EXISTING PARTITIONS TO HAVE THROAT DEPTHS VERIFIED IN FIELD
MAINTAIN RATING OF EXISTING FIRE RATED DOORS TO REMAIN.
LOCK CORES TO BE COMPATIBLE WITH BASE STANDARD CYLINDERS AND KEYED
TO MASTER SYSTEM. COORDINATE WITH BASE OPERATAIONS AND MAINTANCE
STAFF.
ALL SINGLE DOORS TO RECEIVE 1-1/2" PAIR BUTT HINGES AND DOUBLE DOOR TO
RECEIVE 3 PAIR BUTT HINGES.
DOORS OVER 7'-0" HEIGHT TO RECEIVE 2 PAIRS BUTT HINGES AT THE SINGLE
DOOR AND 4 PAIRS BUTT HINGES AT DOUBLE DOORS
THE HARDWARE SET IS FURNISHED AS INFORMATION AND AS GUIDE ONLY. THE
COMPLETE QUANTITY REQUIREMENTS FOR EACH OPENING SHALL BE THE
RESPONSIBILITY OF GC.
A1 A-201
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B1152
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
A-201
EL
EV
AT
IO
N S
AN
D
S C
H
ED
U
LE
S
JT JT R
W
W /M
EB
SCALE: 1/4" = 1'-0"
INTERIOR ELEVATION AT
KITCHENF9SCALE: 1/4" = 1'-0"
INTERIOR ELEVATION AT CORRIDORF6SCALE: 1/4" = 1'-0"
INTERIOR ELEVATION AT
ENTRANCE FOYERF5
SCALE: 1/4" = 1'-0"
WEST EXTERIOR ELEVATIONA1
DOOR SCHEDULE
DOOR
TO ROOM FROM ROOM
DOOR PANELS
DOOR FIRE
RATING
MINUTES
DOOR FRAME
HARDWARE SET NUMBER
PANEL TYPE PANEL DIMENSIONS
THICKNESS UNDERCUT FINISH 1 TYPE
FACE DIMENSIONS
FINISH 1PANEL 1 PANEL 2
WIDTH
HEIGHT JAMB WIDTH HEAD HEIGHTPANEL 1 PANEL 2
1ST FLOOR
26A CORR. MECH PNL-F-HM PNL-F-HM 3'-0" 2'-0" 7'-0" 1 3/4" 0" PAINT N/A FRM-00HM1 2" 2" PAINTED TO MATCH ADJACENT WALL HS-1 26B CORR. MECH PNL-F-HM PNL-F-HM 1'-6" 1'-6" 7'-0" 1 3/4" 0" PAINT N/A FRM-00HM1 2" 2" PAINTED TO MATCH ADJACENT WALL HS-1
SCALE: 3" = 1'-0"
HOLLOW METAL DOOR JAMB AND HEAD AT GWBC6
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
1ST FLOOR
0"
ROOF
15'-0" x1
CRUSHED STONE
ALL EDGES OF PAD
A-501 E5
C5 A-501
MASONRY INFILL
CONCRETE PAD
CONDENSER UNIT -
SEE MECH
AHU - SEE
MECH
A-501 E7
METAL EQUIPMENT
STAND
A-502 A6
TYP
2' -8
S4B.U
A 26
B
BE
YO
N
D
A-501 B5
NEW ATFP COMPLIANT
CHAINLINK FENCE
MECHANICAL
EQUIPMENT
ENCLOSURE
OUTDOOR AIR INTAKE
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
ALL PARTITIONS ARE TYPE -S4B.U UNLESS OTHERWISE NOTED. PARTITIONS
TYPES ARE KEYED ON FLOOR PLANS.
ALL WORK SHALL COMPLY WITH FEDERAL BUILDING CODES AND REGULATIONS.
VERIFY RATED WALLS WITH CODE PLANS.
REVIEW ALL DRAWINGS AND COORDINATE WALL CONSTRUCTION INCLUDING
LOCATION OF FRAMING MEMBERS WITH PENETRATIONS, RECESSED AND
SURFACE MOUNTED ITEMS. PROVIDE FRAMING AND OR BACKING AS REQUIRED
TO SUPPORT WALL MOUNTED OR RECESSED ITEMS AND WALL CONSTRUCTION
AROUND ITEMS.
WHEN ITEMS PENETRATE WALL DO NOT BEAR PENETRATIONS ON WALLS,
SUPPORT SEPERATELY.
PARTITIONS ENCLOSING SPACES WITHOUT CEILINGS ARE TO EXTEND TO
UNDERSIDE OF SLAB ABOVE.
ALL FIRE RATED PARTITION ASSEMBLIES ARE TO CONTINUE FROM FLOOR TO
DECK ABOVE.
ALL FIRE AND SMOKE RATED PARTITIONS ARE TO HAVE ANY/ALL GAPS FILLED
WITH A MATERIAL THAT WILL MEET OR EXCEED THE RATING AND/OR
CONSTRUCTION REQUIREMENTS OF THE WALL.
THE ENVELOPE CREATED BY FIRE RATED PARTITIONS AND SHAFTS IS REQUIRED
TO BE CONTINUOUS AND UNINTERRUPTED EXCEPT BY TESTED THROUGH-
PENETRATION FIRE STOP ASSEMBLIES AS SPECIFIED. REFER TO THE CODE PLAN
FOR DIAGRAMS.
PROJECT IS BASED ON QUOTED UL DESIGNS. OTHER DESIGNS ACCEPTABLE TO
ALL AGENCIES WITH JURISDICTION MAY BE SUBMITTED FOR APPROVAL.
WALL TYPES DESCRIBED ON THIS SHEET DO NOT ACCOUNT FOR REQUIRED
BACKING AND /OR SUPPORT FOR WALL MOUNT FIXTURES, EQUIPMENT,
CASEWORK AND/OR SYSTEMS FURNITURE. COORDINATE WITH ENLARGED
FLOOR PLANS, INTERIOR ELEVATIONS, AND EQUIPMENT PLANS PRIOR TO THE
COVERING OF STUD FRAMING. REFER TO MANUFACTURER'S
RECOMMENDATIONS.
ALL PARTITIONS DIMENSIONS PROVIDED ARE TO FINISHED FACE UNLESS
OTHERWISE NOTED.
LOCATE HINGE SIDE OF DOOR AT 6" FROM FINISHED FACE OF ADJACENT WALL
UNLESS OTHERWISE NOTED OR DIMENSIONED.
WALL TYPES AND RATINGS INDICATED ON PLAN CONTINUE ABOVE/BELOW
ADJACENT WINDOW OR DOOR OPENINGS.
MAINTAIN FIRE RATING AROUND RECESSED FIXTURES.
DO NOT LOCATE OUTLET BOXES (INCLUDING TELECOM/DATA AND ELECTRICAL)
OPPOSITE ONE ANOTHER IN ACOUSTICALLY RATED PARTITIONS. LOCATE
OUTLETS AT LEAST ONE STUD BAY APART. SEAL THE OUTLET BOXES WITH PUTTY
PADS AND CAULK THE PERIMETER USING ACOUSTIC SEALANT. AT RATED
PARTITIONS, LOCATE OUTLET BOXES 24" APART, MIN. UNLESS AT SHAFT WALLS.
AT ALL ACOUSTICALLY RATED PARTITIONS USE ACOUSTICAL SEALANT APPLIED
PER MANUFACTURERS INSTRUCTIONS.
ON CONTINUOUS WALL SURFACE WHERE CONSTRUCTION INVOLVES MORE THAN
ONE MATERIAL, FINISH, OR MATERIAL THICKNESS ALIGN FACE OF FINISH UNLESS
OTHERWISE NOTED.
REFER TO REFLECTED CEILING PLAN FOR CEILING MATERIALS AND HEIGHTS;
REFER TO ROOM FINISH SCHEDULE FOR FINISHES AND SPECIAL INSTRUCTIONS.
PARTITION GENERAL NOTES
PARTITION PERFORMANCE RATING
PARTITION TYPE LEGEND
G3A.1
U = UNRATED
S = SMOKE PARTITION
1 = 1 HOUR RATED
PARTITION GROUP
C = CHASE WALL
G = GYPSUM
M = MASONRY
S = SHAFT WALL
DEFINES RELATIVE SIZE
TYPE MODIFIER
INSULATION NOT SHOWN FOR CLARITY
PARTITION PRIORITY LEGEND
1.
2.
3.
4.
5.
6.
7.
PARTITION PRIORITY AS FOLLOWS, FROM
HIGHEST TO LOWEST:
FIRE BARRIER
1 HOUR RATED SHAFT WALL
1 HOUR RATED PARTITION
SMOKE PARTITION
ACOUSTICAL PARTITION TO DECK
NON-RATED PARTITION TO DECK
NON-RATED PARTITION
LOWER PRIORITY PARTITIONS
HIGHER PRIORITY PARTITIONS
EXTEND GWB TO
CORNER AT HIGHER
PRIORITY PARTITION
WALL ASSEMBLY
TO BE
UNINTERRUPTED
THROUGH LOWER
PRIORITY
INTERSECTIONS
BASE TO MATCH
EXISTING
FINISHED FLOOR SLAB
BTM. OF CEILING
UNDERSIDE OF
CONCRETE PLANK
5/8" GYPSUM BOARD
4" METAL CH STUD
LO
W
ER
SE
C
TI
O
N
PL
AN
U
PP
ER
SE
TI
O N
4" DEFLECTION TRACK
SOUND ATTENUATION
BLANKET
4" METAL RUNNER
1" GYPSUM BOARD
SHAFT WALL
4 5/8"
S4B.U
ACOUSTIC SEALANT
5/8" GWB
x1
MASONRY WALL -
EXISTING
LAP AVB AT EXPOSED
EXISTING CMU
BRICK TIE
GROUTED SOAP
V.
I.F
C O
U R
SE
S
REMOVE COURSES AS
REQUIRED TO LAP
AVB OVER (E) AVB - 6"
MINIMUM
V.
I.F
C O
U R
SE
S
SOLID GROUTED CMU
TOOTH IN FACE BRICK
TO MATCH EXISTING
COURSING
(E) MASONRY WALL
LAP AVB AT EXPOSED
EXISTING CMU1
FU
LL
B R
IC
K
TOOTH IN FACE BRICK
TO MATCH EXISTING
COURSING
(E) INSULATION
TYPE UNKNOWN
MATCH EXSTING
INSULATION TYPE
(IF ANY)
BRICK TIE
ROOF
15'-0"
PREMANUFACTURED
INSULATED ROOF CURB WITH
CONTINUOUS INSULATION
(E) ROOFING MEMBRANE
(ASSUMED PVC V.I.F.)
METAL ANGLE, REFER
TO STRUCTURAL
MECHANICAL DUCT
COUNTERFLASHING
HIGH TEMPERATURE
SEALANT
1"
PT WOOD BLOCKING
PT WOOD BLOCKING
SELF-ADHERED
TRANSITION STRIP
RIGID INSULATION
CANT-STRIP
MEMBRANE FLASHING
TERMINATION BAR WITH
CONTINUOUS BEADS OF
SEALANT ON TOP &
BOTTOM EDGES
MEMBRANE ROOFING
RIGID INSULATION
6" 6" 6"
(E) TOPPING SLAB
MECHANICAL DUCT
FRICTION FIT MINERAL WOOL
SEALANT AND BACKER ROD
PROVIDE TRANSITION
MEMBRANE AT SURFACE OF
TOPPING SLAB IF EXISTING
MOISTURE MIDIGATION
MEMBRANE EXISTS
(E) CONC. PLANK
ROOF DECK
FRICTION FIT MINERAL WOOL
PROVIDE POSITIVE FASTENING PER CURB
MANUFACTURERES RECOMENDATIONS IN
ACCORDANCE WITH WIND UPLIFT
REQUIREMENTS
JOINT SEALANT
M
AX1"
FRICTION FIT MINERAL WOOL INSULATION
AS SCHEDULED
SHAFTWALL
TRANSFER DUCT; REFER TO MECHANICAL
CARPET
SLOPE
1:20
FLASH PATCH CENTER EDGE STRIP UNDER
DOOR WHERE DOOR OCCURS
EPOXY FLOOR
METAL EDGE STRIP
EPOXY FLOORING
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
A-501
SE
C
TI
O
N S
D
ET
AI
LS
JT JT R
W
W /M
EB
SCALE: 1/2" = 1'-0"
SECTION AT MECHANICAL EQUIPMENTA1 SCALE: 1 1/2" = 1'-0"
TYPICAL PARTITION - S4B.UA7
SCALE: 1 1/2" = 1'-0"
SECTION DETAIL AT LOUVER
INFILLE5
SCALE: 1 1/2" = 1'-0"
PLAN DETAIL AT LOUVER
INFILLC5
SCALE: 1 1/2" = 1'-0"
ROOF-DUCT DETAILE7
SCALE: 3" = 1'-0"
SHAFTWALL SEALANT DETAILB5
SCALE: 3" = 1'-0"
CARPET TO EPOXYA5
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
1/8" R (TYP.) CHAMFER
#5 REBAR @ 12"E.W.
4000 PSI AIR-ENT.
CONCRETE SLAB
(BROOM FINISHED)
COMPACTED GRAVEL
BASE & EDGE STRIP
COMPACTED
SUBGRADE
SCORE JOINT EDGE
1/8" RAD. (TYP.)
1"
1' -0
1'
-6
8"6" 6"
1'-0"
0" AT PAVED SURFACES
6" AT GRASS OR GRAVEL
AREAS
PROVISION FOR PADLOCK
4" LATCH POST
4" DIA HINGE POST
4' -0
48" CLR GATE10' - 0" MAX POST SPACING
6" M
IN
3" M
AX
8' -0
ALL JOINTS ARE
WELDED TO MAKE RIGID
FRAME
CONCRETE FOUNDATIONS SHALL HAVE A DIAMETER EQUAL TO FOUR
TIMES THE DIAMETER OF THE POST, BUT NOT LESS THAN 12".
ALL FENCE PRODUCTS SHALL BE PVC COATED. COLOR TO MATCH
BASE STANDARD.
B1105
B1106
B1102
B1109
B1108
B1107
B1110
B1152
PROPERTY OF THE UNITED STATES AIR FORCE
B1106
SI
ZE
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
IS
SU
E
D
AT
E:
SO
LI
C
IT
AT
IO
N N
O
C O
N
TR
AC
T
N O
D
EP
AR
TM
EN
T
O F
TH
E
AI
R
F O
R C
E th
A
IR
B
AS
E G
R O
U P/
C E
BA
SE
C
IV
IL
E
N G
IN
EE
R
IS
IO
N
H
AN
SC
O
M A
FB
, M
A
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
SHEET IDENTIFICATION
SM
M
A
AN
SI
-D
/0
7/
M
XR
D
5-
1 2 7 8 9 103 4 5 6
A
B
C
D
E
F
G
PLAN NORTH
PROFESSIONAL SEAL:
E
AIR FORCE MAT RIEL COMMAN
D
66 AIR GROUP
TH
BASE
A
IR
F O
R C
E M
A
TE
R
IA
L C
O M
M A
N D
ISSUE FOR CONSTRUCTION
M
XR
D
-0
R
EP
AI
R (R
EP
LA
C E)
A
IR
C O
N D
IT
IO
N
IN
G U
N
IT
C O
N
FE
R
EN
C E
C
EN
TE
R
BU
IL
D
IN
G
A-502
SI
TE
D
ET
IA
LS
JT JT R
W
W /M
EB
SCALE: 3/4" = 1'-0"
TYPICAL CONCRETE PAD DETAIL AT MECHANICAL EQUIPMENTA6
SCALE: 1/4" = 1'-0"
CHAINLINK FENCE DETAILSC6
IS
SU
E
FO
R C
O N
ST
R
U C
TI
O
N
/2 8/
DTS
DTR
CHWS
CHWR
CWR
CWS
CD
GR
GS
V
SHWS
SHWR
SCHWS
SCHWR
RS
RL
PCHWS
PCHWR
PC
MU
MPS
MPR
LPS
HPR
HPS
LPR
HWS
HWR
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CONDENSATE DRAIN
HIGH PRESSURE RETURN
(CONDENSATE)
HIGH PRESSURE STEAM
HOT WATER RETURN
HOT WATER SUPPLY
LOW PRESSURE RETURN
(CONDENSATE)
LOW PRESSURE STEAM
MEDIUM PRESSURE RETURN
(CONDENSATE)
MEDIUM PRESSURE STEAM
MAKE-UP WATER
PUMPED CONDENSATE
PRIMARY CHILLED WATER RETURN
PRIMARY CHILLED WATER SUPPLY
REFRIGERANT LIQUID LINE
REFRIGERANT SUCTION LINE
SECONDARY CHILLED WATER
RETURN
SECONDARY CHILLED WATER
SUPPLY
SECONDARY HOT WATER RETURN
SECONDARY HOT WATER SUPPLY
VENT
GLYCOL SUPPLY
GLYCOL RETURN
DUAL TEMPERATURE RETURN (TWO
PIPE HEATING/COOLING SUPPLY)
DUAL TEMPERATURE SUPPLY (TWO
PIPE HEATING/COOLING RETURN)
ABBREVIATIONS
PIPING SYSTEM ABBREVIATIONSA
ABV ABOVE
AFF ABOVE FINISHED FLOOR
ACC AIR COOLED CONDENSER
AD ACCESS DOOR
AP ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADDM ADDENDUM
ADDL ADDITIONAL
ADJ ADJUSTABLE; ADJACENT; ADJOINING
A/C AIR CONDITIONING
ACCU AIR COOLED CONDENSING UNIT
AFMS AIRFLOW MEASURING STATION
AF AIR FOIL
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
AV AIR VENT
ALM ALARM
ALT ALTERNATE; ALTITUDE
AC ALTERNATING CURRENT
ALUM ALUMINUM
AMB AMBIENT
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AMP AMPERE
ETC ET CETERA
ARCH ARCHITECT
A/E ARCHITECT/ENGINEER
ASB ASBESTOS
AI ANALOG INPUT
AI AIR INTAKE
AO ANALOG OUTPUT
ACU AIR CONDITIONING UNIT
ATM ATMOSPHERE
ATTN ATTENTION
AAV AUTOMATIC AIR VENT
ACP AUTOMATIC CONTROL PANEL
ACD AUTOMATIC CONTROL DAMPER
ACV AUTOMATIC CONTROL VALVE
AFC AUTOMATIC FREQUENCY CONTROLLER
ATFP ANTI TERRORISM FORCE PROTECTION
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AVG AVERAGE
B
BDD BACKDRAFT DAMPER
BFP BACKFLOW PREVENTER
BAL BALANCE
BV BALL VALVE
BB BASEBOARD
BSMT BASEMENT
BAT BATTERY
BLW BELOW
BTW BETWEEN
BLWDN BLOWDOWN
BLR BOILER
BFBP BOILER FEED BOOSTER PUMP
BFS BOILER FEED SYSTEM
BFW BOILER FEEDWATER
BFWP BOILER FEEDWATER PUMP
BOT BOTTOM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
MBTU BRITISH THERMAL UNIT (THOUSAND)
BTUH BRITISH THERMAL UNIT PER HOUR
BRZ BRONZE
BLDG BUILDING
BAS BUILDING AUTOMATION SYSTEM
BFV BUTTERFLY VALVE
C
CUH CABINET UNIT HEATER
CO2 CARBON DIOXIDE
CO CLEANOUT; CARBON MONOXIDE
CLG CEILING
C CELSIUS; CENTIGRADE
CTR CENTER; COOLING TOWER RETURN
CM CENTIMETER
CFT CHEMICAL FEEED TANK
CHW CHILLED WATER
CHWPP CHILLED WATER PRIMARY PUMP
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWSP CHILLED WATER SECONDARY PUMP
CHWS CHILLED WATER SUPPLY
CH CHILLER
CLASS CLASSIFICATION
CW CLOCKWISE
COEFF COEFFICIENT
COP COEFFICIENT OF PERFORMANCE (HEATING)
CLR COLOR; CLEAR; CLEARENCE
COL COLUMN
COMM COMMUNICATION
F (CONTINUED)
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FD FIRE DAMPER; FLOOR DRAIN
FP FIRE PROTECTION
FLMB FLAMMABLE
FOB FLAT ON BOTTOM
FOT FLAT ON TOP; FUEL OIL STORAGE TANK
FLEX FLEXIBLE
FLR FLOOR
FM FLOWMETER; FACTORY MUTUAL
FS FLOW SWITCH
FT FOOT; FEET
FT/LB FOOT/POUND
FT/LBF FOOT/POUND FORCE
FSTAT FREEZESTAT
FO FUEL OIL
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOF FUEL OIL FILL
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FLA FULL LOAD AMPS
F
FA FACE AREA; FIRE ALARM; FRESH AIR
FV FACE VELOCITY
F FAHRENHEIT
FCU FAN COIL UNIT
FTU FAN POWERED TERMINAL UNIT
FF FINAL FILTER
FDW FEED WATER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRP FIBER REINFORCED POLYESTER;
FIBERGLASS REINFORCED PLASTIC
FIG FIGURE
FLTR FILTER
FTR FINNED TUBE RADIATION
FPI FINS PER INCH
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FD FIRE DAMPER; FLOOR DRAIN
FP FIRE PROTECTION
FLMB FLAMMABLE
FOB FLAT ON BOTTOM
FOT FLAT ON TOP; FUEL OIL STORAGE TANK
FLEX FLEXIBLE
FLR FLOOR
FM FLOWMETER; FACTORY MUTUAL
FS FLOW SWITCH
FT FOOT; FEET
FT/LB FOOT/POUND
FT/LBF FOOT/POUND FORCE
FSTAT FREEZESTAT
FO FUEL OIL
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOF FUEL OIL RETURN LINE
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FLA FULL LOAD AMPS
G
GA GAGE
GAL GALLON
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPS GALLONS PER SECOND
GALV GALVANIZED
GEN GENERAL; GENERATOR
GC GENERAL CONTRACTOR
GE GENERAL EXHAUST
GLV GLOBE VALVE
GRV GRAVITY ROOF VENTILATOR; GROOVE
GV GRAVITY VENT; GASOLINE VENT
GND GROUND
GMP GUARANTEED MAXIMUM PRICE
GYP GYPSUM
H
HOA HAND-OFF-AUTOMATIC
HD HAND DAMPER; HEAD
HC HEATING COIL
H HIGH; HUMIDITY
HX HEAT EXCHANGER
HG HEAT GAIN; MERCURY
HP HEAT PUMP; HIGH PRESSURE; HORSEPOWER
HT HEAT TRANSFER
Q HEAT TRANSFER; RATE OF FLOW
U HEAT TRANSFER COEFFICIEN
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
HT HEIGHT
HZ HERTZ
H (CONTINUED)
HDPE HIGH DENSITY POLYETHYLENE
HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HPR HIGH PRESSURE RETURN
HPS HIGH PRESSURE STEAM
HTHW HIGH TEMPERATURE HOT WATER
HR HOUR
HB HOSE BIBB
HW HOT WATER
HWP HOT WATER PUMP
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HWT HOT WATER TANK
HSTAT HUMIDISTAT
I
ID IDENTIFICATION; INSIDE DIAMETER; INSIDE
DIMENSION
ID NO IDENTIFICATION NUMBER
IN WC INCHES, WATER COLUMN
IAQ INDOOR AIR QUALITY
IA INDUCTION AIR
IB INDUCTION AIR BOX
IAU INDUCTION NAIR UNIT
INFO INFORMATION
INFO INFORMATION
IR INFRARED; INSIDE RADIUS
I/O INPUT/OUTPUT
INSUL INSULATION
IBC INTERNATIONAL BUILDING CODE
INV EL INVERT ELEVATION
K
KPA KILPASCAL
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOUR
L
LAB LABORATORY
LFU LAMINAR FLOW UNIT
LH LATENT HEAT; LEFT HAND
LAT LEAVING AIR TEMPERATURE
LDB LEAVING DRY BULB TEMPERATURE
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
LF LINEAR FEET (FOOT)
L LENGTH; LITER
LRA LOCKED ROTOR AMPS
LVR LOUVER
LVDR LOUVER DOOR
LVD LOUVERED
LP LOW PRESSURE (MECHANICAL)
LPCR LOW PRESSURE CONDENSATE RETURN
LPR LOW PRESSURE RETURN
LPS LOW PRESSURE STEAM
LTHW LOW TEMPERATURE HOT WATER
M
MCB MAIN CIRCUIT BREAKER
MAU MAKE UP AIR UNIT
MAV MANUAL AIR VENT
MVD MANUAL VOLUME DAMPER
MFR MANUFACTURER; MASS FLOW RATE
MAX MAXIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MECH MECHANICAL
MED MEDIUM; MEDICAL
MER MECHANICAL EQUIPMENT ROOM
MPCR MEDIUM PRESSURE CONDENSATE RETURN
MPR MEDIUM PRESSURE RETURN
MPS MEDIUM PRESSURE STEAM
MTG MEETING; MOUNTING
MTL METAL
M METER
M/S METERS PER…