Attachment 11 20250130_MXRD150009_DRAWINGS_IFC_SEED PROJECT.pdf

PDF 7 MB Posted

Attached to
MULTIPLE AWARD CONSTRUCTION CONTRACT (MACC) IDIQ - Request for Proposal
Solicitation number
FY25MACC
Issued by

About this file

These architectural and engineering drawings detail a renovation project for Building 1106 at Hanscom Air Force Base, Massachusetts, focusing on repairing and replacing air conditioning units. The documents include comprehensive plans for demolition, construction, mechanical systems, electrical systems, and structural modifications across the first floor and basement of the conference center.

Key technical specifications include replacing existing HVAC equipment with new air conditioning units (AC-1, AC-4, ACCU-1, ACCU-4) using R-454B refrigerant, installing variable air volume (VAV) boxes with electric reheat, and implementing new control systems integrated with the building's management system. The project involves removing existing mechanical infrastructure, creating new ductwork and piping connections, and ensuring compliance with UFC (Unified Facilities Criteria) and NFPA 101 Life Safety Code standards. The construction is scheduled for completion by January 28, 2025, with the work primarily focused on in-kind replacement of mechanical, electrical, and communications equipment while maintaining the existing building's overall configuration.

View the file

Other files

File Type Posted
MACC IDIQ RFP Questions and Answers_14July2025.xlsx XLSX spreadsheet
Attachment 07 Section L_Instructions conditions and notices to offerors or respondents_09July2025.pdf PDF
FA283525R0002 RFP Cover Letter 09July2025.pdf PDF
Solicitation FA283525R00020002 - SF 1442.pdf PDF
Solicitation Amendment FA283525R00020002 - SF 30.pdf PDF
FA283525R0002 RFP Cover Letter 02July2025.pdf PDF
Solicitation - FA283525R00020001.pdf PDF
Attachment 07 Section L_Instructions conditions and notices to offerors or respondents_02July2025.pdf PDF
Attachment 15 Davis Bacon Act WD MA20250001 Modification 6 Building Dated May 16 2025.pdf PDF
MACC IDIQ RFP Questions and Answers_2July2025.xlsx XLSX spreadsheet
Solicitation Amendment FA283525R00020001 SF 30.pdf PDF
Solicitation - FA283525R0002_26June2025.pdf PDF
Attachment 07 Section L_Instructions conditions and notices to offerors or respondents_26June2025.pdf PDF
FA283525R0002 RFP Cover Letter 26June2025.pdf PDF
RFP SITE VISIT - LIST OF COMPANIES THAT SIGNED IN.pdf PDF
Attachment 07 Section L_Instructions conditions and notices to offerors or respondents_25June2025.pdf PDF
Solicitation - FA283525R0002.pdf PDF
1106 HAZMAT Records.xlsx XLSX spreadsheet
FA283525R0002 RFP Cover Letter 25June2025.pdf PDF
Carlisle Roofing System Warranty - 1236627_Redacted.pdf PDF
MACC IDIQ RFP Questions and Answers_Final.xlsx XLSX spreadsheet
Attachment 07 Section L_Instructions conditions and notices to offerors or respondents_updated 25June2025.pdf PDF
FA283525R0002 RFP Cover Letter 18June2025signed.pdf PDF
Solicitation - FA283525R0002.pdf PDF
Attachment 07 Section L_Instructions conditions and notices to offerors or respondents.pdf PDF
Pre Proposal Site Visit MACC_Revision 2.pdf PDF
Pre Proposal Site Visit MACC_Revision 1.pdf PDF
Attachment 01 MACC SOW 30 April 2025 Version 3.pdf PDF
Attachment 08 Section M Evaluation factors for award.pdf PDF
Attachment 09 01 30 00 ADMINISTRATIVE REQUIREMENTS.pdf PDF
Attachment 15 Davis Bacon Act WD MA20250001 Modification 2 Building Dated March 14 2025.pdf PDF
Attachment 03 Appendix 2 HAFB Design Guide V2.0.pdf PDF
Attachment 04 Appendix 3 Architectural Compatibility Plan (Jan 2013).pdf PDF
Attachment 06 Appendix 5 HAFB Landscape Standards 06 27 2017_Compressed.pdf PDF
Attachment 10 MACC IDIQ Task Order 01 and 02 Price Schedule.pdf PDF
Attachment 12 MXRD150009 SOW 30JAN2025_SEED PROJECT.pdf PDF
FA283525R0002 RFP Cover Letter 30May25.pdf PDF
Attachment 02 Appendix 1 - Div 1 Specs.pdf PDF
Attachment 05 Appendix 4 Hanscom AFB Environmental Requirements.pdf PDF
Attachment 13 MXRD150009_IFC_SPECIFICATIONS 30JAN2025_SEED PROJECT.pdf PDF
Pre Proposal Site Visit MACC.pdf PDF
Solicitation - FA283525R0002.pdf PDF
Attachment 07 Section L Instructions conditions and notices to offerors or respondents.pdf PDF
Attachment 14 MXRD150009_IFC_SUB REGISTER 30JAN2025_SEED PROJECT.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX OF DRAWINGS

SYMBOL LEGEND: ● CURRENT ISSUE ○ PREVIOUSLY ISSUED

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IN

G

D

IV

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

G-000

C O

VE

R

JT JT R

W

W

BUILDING 1604

AFLCMC/P2IA

BASE CONTRACTING

BUILDING 1825

BASE ENVIRONMENTAL OFFICE

72 DOW ST

BUILDING 1810

BASE CIVIL ENGINEERING(BCE)

120 GRENIER ST

BUILDING 1721

BASE SAFETY OFFICE

HARTWELL AVE

GATE

ROUTE 2A/VANDENBURG GATE

AND VISITOR CENTER

BUS

PLAYGROUND

PL

AY

G R

O U

N D

O

BS

C U

R E

PL

AY

G R

O U

N D

BA

SK

ET

BA

LL

C

O U

R T

PLAYGROUNDEQUIPMENT

BA

SK

ET

BA

LL

C

O U

R T

I-9

I-9

I-95

I-9

ATLANTIC

OCEAN

BOSTON

BEDFORD

NASHUA

ATLANTIC OCEANMASSACHUSETTS

CONNECTICUT

VERMONT NEW HAMPSHIRE

RHODE

ISLAND

BOSTON

LEXINGTON

LYNN

SALEM

QUINCY

HINGHAM

WEYMOUTH

DEDHAM

BROOKLINE

FRAMINGHAM

BEDFORD

CONCORD

HANSCOM AFB

HANSCOM AFB, MASSACHUSETTS

BUILDING 1106 REPAIR/ REPLACE

AIR CONDITIONING UNITS

SOLICITATION NO. :

CONTRACT NO. : MXRD 15-0009

ISSUE DATE : 01/28/2025

DEPARTMENT OF THE AIR FORCE

AIR FORCE MATERIEL COMMAND

HANSCOM AIR FORCE BASE

PREPARED FOR:

66th ABG/CEN CIVIL ENGINEERING DIRECTORATE

ENGINEERING AND DESIGN SECTION

HANSCOM AIR FORCE BASE

PREPARED BY:

VICINITY MAP N

E

AIR FORCE MAT R

I EL COMMAND TH

GROUP66 AIR BA SE

I-90

I-93

I-93

SHEET

NUMBER SHEET NAME 01

/2 8/

Is su e

Fo r C on st ru ct io n

GENERAL

G-000 COVER ●

LIFE SAFTEY

LS-001 CODE SUMMARY AND LIFE SAFETY PLAN ●

STRUCTURAL

S-001 GENERAL NOTES, FRAMING PART PLAN AND DETAILS ●

ARCHITECTURE

A-001 LEGENDS, NOTES, ABBREVIATIONS ●

AD051 1ST FLOOR DEMOLITION PLAN ●

AD061 1ST FLOOR DEMOLITION REFLECTED CEILING PLAN ●

A-101 FIRST FLOOR CONSTRUCTION PLAN ●

A-102 ROOF CONSTRUCTION PLAN ●

AR101 1ST FLOOR REFLECTED CEILING PLAN ●

A-201 ELEVATIONS AND SCHEDULES ●

A-501 SECTIONS & DETAILS ●

A-502 SITE DETIALS ●

MECHANICAL

M-001 ABBREVIATIONS ●

M-002 SYMBOLS ●

MD101 BASEMENT AND 1ST FLOOR DEMOLITION PLAN ●

M-101 BASEMENT 1ST FLOOR CONSTRUCTION PLAN ●

M-102 ROOF CONSTRUCTION PLAN ●

M-501 DETAILS ●

M-502 DETAILS ●

M-601 SCHEDULES ●

M-701 CONTROL DIAGRAMS ●

M-702 EXISTING UNIT CONTROL DIAGRAMS ●

ELECTRICAL

E-001 SYMBOL LEGEND AND NOTES ●

ED101 1ST FLOOR DEMOLITION PLAN ●

EL101 1ST FLOOR LIGHTING PLAN ●

EP101 1ST FLOOR POWER PLAN ●

EP601 POWER SCHEDULES AND DETAILS ●

PROJECT LOCATION

B1106

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

UP

UP

UP

1' - 4"

7' - 1"

7' - 1"

5' - 2"

12' - 10" xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x7 x8 x8 xA.5 x7.5

50 SF/OCC

BACK

LOBBY

CL.

100 SF/OCC

KITCHEN 32

15 SF/OCC

BURLINGTON

15 SF/OCC

BEDFORD

150 SF/OCC

MAIN

OFFICE

150 SF/OCC

IT

OFFICE

CORR.

15 SF/OCC

HOLZMAN

15 SF/OCC

LINCOLN

150 SF/OCC

FOYER

7 SF/OCC

CONCORD

150 SF/OCC

PROJECTION

ROOM

LEXINGTON

150 SF/OCC

PROJECTION

ROOM

300 SF/OCC

SERVER

ROOM

VEST

300 SF/OCC

MECH

300 SF/OCC

MECH

WOMENS

300 SF/OCC

JANCL.

CL.

CL.

MAIN

ENTRY

HALL

150 SF/OCC

ENTRY

HALL

CL

MENS

DOOR

0.20*

68.5" CLR.

DOOR

0.20*

68.5" CLR.

DOOR

0.20*

68.5" CLR.

DOOR

0.20*

68.5" CLR.

DOOR

0.20*

68.5" CLR.

COMMON PATH = 89' - 10"

TRAVEL DISTANCE=101'

EXITS

MINIMUM NUMBER OF EXITS:

MAXIMUM TRAVEL DISTANCE IN NON-SPRINKLERED BUILDING:

REQUIRED PROVIDED

300 FT

150 FT MAX

CODE SUMMARY

APPLICABLE CODES

UNIFIED FACILITIES CRITERIA (UFC)

UFC 1-200-01: GENERAL BUILDING REQUIREMENTS; 02 FEB 2024 W/ CHANGE 3

UFC 3-600-01: FIRE PROTECTION ENGINEERING FOR FACILITIES; 06 MAY 2021 W/ CHANGE 6 UFC 4-010-01: DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS; 24 MAY 2024 W/ CHANGE 3

ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 101 - LIFE SAFETY CODE, 2024 EDITION

PROJECT DESCRIPTION

THIS PROJECT IS A RENOVATION/ ALTERATION WITHIN AN EXISTING BUILDING. THE ALTERATIONS TO

THE BUILDING INTERIOR PROPOSED FOR THIS PROJECT DO NOT CHANGE THE CONSTRUCTION

TYPE, OCCUPANCY CLASS OR USE GROUP - NOR DO THEY RESTRICT EXISTING PATHS OF EGRESS

PER NFPA CH.7 LIFE SAFETY CODE. THE EXISTING BUILDING IS NOT A FULLY SPRINKLERED

BUILDING.

THE SCOPE OF WORK FOR THIS PROJECT INCLUDES MINIMAL DEMOLITION OF EXISTING ROOF,

INTERIOR PARTITIONS AND MEP/FP. NEW CONSTRUCTION CONSISTS OF IN KIND REPLACEMENT OF PARTITIONS, MECHANICAL, ELECTRICAL & COMMUNICATIONS EQUIPMENT. CARE WILL BE TAKEN TO

PROTECT EXISTING FFE AND EXISTING MEP/FP INFRASTRUCTURE.

EXISTING BUILDING

AUTOMATIC SPRINKLER SYSTEM NOT PROVIDED

OCCUPANCY/GROUP CLASSIFICATION:

CONSTRUCTION TYPE:

GROSS FLOOR AREA (PER NFPA 101 SECTION 3.3.24.2.2)

OCCUPANT/SQ. FT:

SCOPE OF WORK BOUNDARY SQ. FT:

ASSEMBLY MAX OCCUPANT/SQ. FT:

BUSINESS MAX OCCUPANT/SQ. FT:

STORAGE OCCUPANT/SQ. FT:

TOTAL OCCUPANTS FIRST FLOOR:

ASSEMBLY - A

BUSINESS - B

(B=Accessory Use)

II B

14,870 SF

7/SF TO 300/SF

15,155 SF

1 PER 7 SF

1 PER 150 SF

1 PER 300 SF

CODE PLAN LEGEND

EXIT

NFPA VALUES (NFPA 101

TABLE 7.3.1.2. ) PROVIDED

FOR EGRESS LOAD

CALCULATIONS

XX

SF/OCC

Name ROOM NAME

NUMBER OF OCCUPANTS

OCCUPANT LOAD PER SF

MEANS OF EGRESS COMPONENT

CAPACITY FACTOR (TABLE 7.3.3.1, NFPA 101)

PROVIDED CLEAR WIDTH

CALCULATED OCCUPANT LOAD [OCCUPANT

LOAD FACTOR PER DIVIDED NUMBER OF

EXITS AVAILABLE (AVERAGE DISTRIBUTION) ]

MAXIMUM OCCUPANT CAPACITY (ACTUAL STAIR/DOOR

WIDTH DIVIDED BY CAPACITY FACTOR)

EXIT DOOR

0.20*

33" CLEAR

XXX

EGRESS TRAVEL PATH

DISTANCE AND DIRECTION

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B1152

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

LS-001

C O

D E

SU

M

M

AR

Y

AN

D L

IF

E

SA

FE

TY

P

LA

N

JT JT R

W

W /M

EB

SCALE: 1" = 10'-0"

1ST FLOOR LIFE SAFETY PLANC1

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

(E ) 1

4W F5

(E ) 1

4W F5

(E)12B22

(E)12B22

(E)12B22

(E)12B22

(E)12B22

(E)12B22

(E)12B22

(E)12B22

(E)12B22

3' - 1"

(E ) C

(E) C8

(E) C8

(E) C8

(E) C8

(E) C8

(E) C8

(E) C8

(E) C8

(E) C8

B2

S-001

B2

S-001

SLAB THICKNESS SEE EXIST. DWGS

EXISTING CONCRETE SLAB

ANGLE 6x4x5/16 (LLV) 1 EACH

SIDE OF OPENING

EXISTING STEEL

BEAM T.O. STEEL EL.

SEE PLAN

L6x4x3/8X6"

CLIP ANGLE

ARCH DWGS

COORDINATE WITH

3/16

3/16

TYP.

3/16

3/16

TYP.

EXISTING STEEL

BEAM

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B1152

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

S-001

G

EN

ER

AL

N O

TE

S, F R

AM

IN

G P

AR

T

PL

AN

A N

D D

ET

AI

LS

BR

W

IT

K

BR

W

SCALE: 1/8" = 1'-0"

EXISTING ROOF PART PLAND2

STRUCTURAL STEEL

FABRICATE AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS - ALLOWABLE STRESS DESIGN AND PLASTIC DESIGN," AND THE "CODE OF STANDARD PRACTICE" OF THE AISC. WELDING SHALL CONFORM TO THE REQUIREMENTS OF THE "STRUCTURAL WELDING CODE" OF THE

AMERICAN WELDING SOCIETY.

STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. STRUCTURAL STEEL CHANNELS SHALL CONFORM TO ASTM A572, GRADE 50. STRUCTURAL TUBES SHALL BE ASTM A500, GRADE B. STRUCTURAL STEEL PIPES SHALL CONFORM TO ASTM A53, GRADE B. STRUCTURAL STEEL PLATES AND ANGLES SHALL

CONFORM TO ASTM A36, UNLESS OTHERWISE NOTED.

DO NOT SPLICE STRUCTURAL STEEL MEMBERS WITHOUT WRITTEN APPROVAL OF THE ARCHITECT.

BOLTED CONNECTIONS SHALL BE MADE WITH THREE-QUARTERS INCH DIAMETER HIGH STRENGTH, ASTM A325-N

BOLTS, UNLESS OTHERWISE NOTED.

WELDING ELECTRODES SHALL CONFORM TO AWS A5.1 E70XX SERIES WITH PROPER ROD TO PRODUCE OPTIMUM

WELD (LOW HYDROGEN).

SCALE: 3/4" = 1'-0"

NEW OPENING IN EXISTING ROOFB2

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

PROFESSIONAL SEAL:

ALIGN

ABBREVIATIONS

WORKPOINT, CONTROL POINT OR DATUM

REFERENCE GRID

CENTERLINE

N.I.C

GENERAL SYMBOLS LEGEND

ENLARGED AREA CALLOUT

SHEET WHERE LOCATED

DETAIL NUMBER

EXTERIOR ELEVATION

INTERIOR ELEVATION - MULTIPLEA-101

DRAWING LOCATION

SHEET LOCATION

BUILDING CROSS SECTION

A-101

SIM

A-101

SIM

WALL SECTION

A-101

SIM

NORTH REFERENCE

PLAN NORTH

TRUE NORTH

SHEET NOTES

PARTITION TYPE G3A

REVISION INDICATOR

AREA OF REVISION

1 REVISION NUMBER - SHEET SPECIFIC

NAME

AREA

NUMBER

NAME

ELEVATION

A-101

SIM

1 1

ROOM NAME

100 SF

A-101

A-101

SIM

DETAIL

N

ALIGN

LIMIT OF WORK LINE

MATERIAL LEGEND

ACOUSTICAL CEILING PANELS

REFER TO RCP'S

ALUMINUM

BRICK

CONCRETE

CONCRETE MASONRY UNIT

STEEL

FINISHED WOOD

GYPSUM BOARD

PLYWOOD

MINERAL WOOL

WOOD BLOCKING

CONCRETE

MASONRY

METALS

WOOD, PLASTICS, AND COMPOSITES

THERMAL AND MOISTURE PROTECTION

POLYISO

XPS

SPRAY FOAM

FINISHES

GYPSUM BOARD - TYPE X

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

A-001

LE

G

EN

D

S, N

O

TE

S, A

BB

R

EV

IA

TI

O

N S

JT JT R

W

W /M

EB

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT

AC AIR CONDITION

ACC ACCESSIBLE

ACCU AIR COOLED CONDENSING

UNIT

ACP ACOUSTIC CEILING PANEL

ACS FLR ACCESS FLOOR

ACS PNL ACCESS PANEL

ACST ACOUSTIC

ADJ ADJACENT

ADJA ADJUSTABLE

ADMIN ADMINISTRATION

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING

JUSTIDICTION

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

ANC ANCHOR, ANCHORAGE

ANOD ANODIZED

APPROX APPROXIMATE

ARCH ARCHITECT

AVG AVERAGE

AW ACID WASTE

B/B BACK TO BACK

BALC BALCONY

BD BOARD

BEJ BRICK EXPANSION JOINT

BFF BELOW FINISH FLOOR

BITUM BITUMINOUS

BKBD BACKBOARD

BKG BACKING

BLDG BUILDING

BLKHD BULKHEAD

BLW BELOW

BM BEAM

BOS BOTTOM OF STEEL

BOT BOTTOM

BRDG BRIDGING

BSMT BASEMENT

BU BUILT-UP

C TO C CENTER TO CENTER

CAB CABINET

CB CATCH BASIN

CB CORNER BEAD

CCTV CLOSET CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS

CEM CEMENT

CF CONTRACTOR FURNISHED

CFCI CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPEMENT

CFLG COUNTER FLASHING

CFOI CONTRACTOR FURNISHED /

OWNER INSTALLED

CG CORNER GUARD

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLO CLOSET

CLR CLEAR

CLRM CLASSROOM

CLWG CLEAR WIRED GLASS

CMU CONCRETE MASONRY UNIT

CO CABON MONOXIDE

CO2 CARBON DIOXIDE

COL COLUMN

CONC CONCRETE

CONTR CONTRACTOR

COORD COORDINATE

CPT CARPET

CS CAST STONE

CSWK CASEWORK

CT CERAMIC TILE

CT STN CUT STONE

CTR CENTER

CTRL CONTROL

CTV CABLE TELEVISION

CU FT CUBIC FEET

D PENNY

DBL DOUBLE

DEFS DIRECT APPLIED EXTERIOR

FINISH SYSTEMS

DEG DEGREE

DEMO DEMOLITION

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DR DOOR

DW DISHWASHER

DWG DRAWING

EA EACH

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATIONS

ELVR ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

EOS EDGE OF SLAB

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EPS EXPANDED POLYSTYRENE

BOARD (INSULATION)

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

F/F FACE TO FACE

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF EL FINISH FLOOR ELEVATION

FF&E FURNITURE, FIXTURE, AND

EQUIPEMENT

FHC FIRE HOSE CABINET

FHP FULL HEIGHT PARTITION

FIN FINISH

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FLR FLOOR

FOF FACE OF FINISH

FOS FACE OF STUD

FP FIRE PROTECTION

FRG FIBER REINFORCED GYPSUM

FRMG FRAMING

FRP FIBERGLASS REINFORCED

PLASTIC

FT FEET, FOOT

FTG FOOTING

FURN FURNISH

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERAL

GF GROUND FACED

GFCI GROUND FAULT CIRCUT

INTERRUPTER

GFRC GLASS-FIBER-REINFORCED

CONCRETE

GFRG GLASS-FIBER-REINFORCED

GYPSUM

GFRP GLASS-FIBER-REINFORCED

PLASTIC

GL GLASS OR GLAZING

GMD GROUP-MOUNTED DEVICES

GWB GYPSUM WALL BOARD

GYM GYMNASIUM

GYP GYPSUM

HAZ HAZARD

HAZMAT HAZARDOUS MATERIALS

HB HOSE BIBB

HC HOLLOW CORE

HC HANDICAP

HCWD HOLLOW CORE WOOD DOOR

HDR HEADER

HDWD HARDWOOD

HIGH H

HM HOLLOW METAL

HO HOLD OPEN

HORIZ HORIZONTAL

HOSP HOSPITAL

HT HEIGHT

HW HARDWARE

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

INV INVERT

JAN JANITOR

KD KNOCKED DOWN

KIT KITCHEN

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LB POUND

LF LINEAR FOOT, FEET

LIN LINEAR

LINO LINOLEUM

LPT LOW POINT

M MR MOISTURE RESISTANT

MATL MATERIAL

MAX MAXIMUM

MB MARKER BOARD

MDF MEDIUM DENSITY

FIBERBOARD

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MEMB MEMBRANE

MEZZ MEZZANINE

MFR MANUFACTURER

MISC MISCELLANOUS

MO MASONRY OPENING

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

MWP MEMBRANE WATERPROOFING

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OF/CI OWNER FURNISHED /

CONTRACTOR INSTALLED

OF/OI OWNER FURNISHED / OWNER

INSTALLED

OH DR OVERHEAD (COILING) DOOR

OPNG OPENING

OPP OPPOSITE

OPPH OPPOSITE HAND

OPQ OPAQUE

OPR OPERABLE

PAR PARALLEL

PART PARTIAL

PBD PARTICLEBOARD

PCC PRECAST CONCRETE

PEJ PREMOLDED EXPANSION

JOINT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLB PLUMB

PLBG PLUMBING

PLWD PLYWOOD

PNL PANEL

POL POLISHED

POLY POLYETHYLENE, PLASTIC

PORC PORCELAIN

PR PAIR

PREFAB PREFABRICATED

PREFIN PREFINISHED

PREP PREPERATION

PRMLD PREMOLDED

PT PAINT

PTN PARTITION

PV PHOTOVOLTATIC

PVC POLYVINYL-CHLORIDE

(ROOFING)

QT QUARRY TILE

QTR QUARTER

QTY QUANITY

RAD RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REINF REINFORCE

REM REMOVABLE

REPL REPLACE

RES RESILIENT

REV REVERSE

RFG ROOFING

RFI REQUEST FOR INFORMATION

RH ROOF HATCH

RH RIGHT HAND

RIS RISER

RM ROOM

RTD RATING, RATED

RTU ROOF TOP UNIT

RWL RAIN WATER LEADER

SC SOLID CORE

SCWD SOLID CORE WOOD DOOR

SD STORE DRAIN

SECT SECTION

SF SQUARE FOOT, SQUARE FEET

SHR SHOWER

SIM SIMILAR

SK SKETCH

SLDG SLIDING

SLNT SEALANT

SPEC SPECIFICATIONS

SQ SQUARE

SST STAINLESS STEEL

STC SOUND TRANSMITION CLASS

STD STANDARD

STN STONE

STNLS STAINLESS

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPENDED

SUSP CLG SUSPENDED CEILING

SV SHEET VINYL

SYMM SYMMETRICAL

T TREAD

TB TACK BOARD

TEL TELEPHONE

TEMP TEMPORARY

THK THICKNESS

THRES THRESHOLD

TMPD TEMPERED

TMPD GL TEMPERED GLASS

TNG TONGUE AND GROOVE

TNM TIME AND MATERIALS

TO TOP OF

TPD TOILET PAPER DISPENSER

TPH TOILET PAPER HOLDER

TPO THERMOPLASTIC POLYOLEFIN

TRTD TREATED

TYP TYPICAL

UCD UNDERCUT DOOR

UNEX UNEXCAVATED

UNFIN UNFINISHED

UON UNLESS OTHERWISE NOTED

UR URINAL

VAN VANITY

VAR VARIED

VB VAPOR BARRIER

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VNR VENEER

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

W WITH

W/O WITHOUT

WC WATER CLOSET

WCN WATER CURTAIN

WD WOOD

WH WALL HUNG

WO WHERE OCCURS

WP WORKING POINT

WPG WATERPROOFING

WPM WATERPROOF MEMBRANE

WPR WEATHERPROOF

WR WEATHER RESISTANT

WWR WELDED WIRE REINFORCING

XFMR TRANSFORMER

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

T

T

M

S xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8 xA.5 x7.5

CL.

KITCHEN

CL

MECH

MECH

CL.

BACK LOBBY HOLZMAN

LINCOLN

ENTRY HALL

FOYER

CONCORD LEXINGTONPROJECTION

ROOM

CORR.

VEST

CL.

SERVER

ROOM

PROJECTION

ROOM

JAN

WOMENSIT OFFICE

CL.

MAIN ENTRY

HALL

MAIN OFFICE

BEDFORDBURLINGTON

CORRIDOR

CORR.

MENS

'-1

1/

2" 2'

-0

D10D10

D4

D1

D2

D8

D8

D8

D8

D6 D11

D9 D9

D5 D3

WP

D9

D5

D4

D7

3' -1

1/

2"

D12 xA xB x7 x8 xA.5 x7.5

779 SF

ELECTRICAL

RM.

AREA

WAY

AREA

WAY

AREA

WAY

EXISTING

CONTROL

PANEL, REFER

TO MEP DWGS

1.

A.

B.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

THE CONTRACTOR SCOPE INCLUDES THE FOLLOWING:

*PRIOR TO DISTURBANCE, THE ACM IDENTIFIED MUST BE

ABATED BY A COMMONWEALTH OF MASSACHUSETTS-

LICENSED ASBESTOS ABATEMENT CONTRACTOR

FOLLOWING ALL FEDERAL, STATE & LOCAL REGULATIONS

GOVERNING ASBESTOS ABATEMENT. ALSO COMPLY

WITH 02 82 14.00 10: ASBESTOS HAZARD CONTROL

ACTIVITIES AND 02 82 16.00 20: ENGINEERING CONTROL

OF ASBESTOS CONTAINING MATERIALS. A COPY OF THE

ASBESTOS WASTE SHIPMENT RECORD MUST BE

RECEIVED WITHIN 35 DAYS OF REMOVAL FROM THE SITE.

ASBESTOS AIR QUALITY SAMPLING MUST BE CONDUCTED

UNDER USEPA REGULATIONS FOLLOWING ASBESTOS

ABATEMENT. IF ADDITIONAL MATERIALS ARE DISCOVERED

THAT HAVE NOT BEEN SAMPLED, THOSE MATERIALS

SHOULD BE CONSIDERED ACMS UNTIL LABORATORY

ANALYSIS DETERMINES OTHERWISE. (CITATION IS FROM

HAZMAT SURVEY & REPORT FOR BUILDING 1106 BY CDW)

REMOVAL OF EXISTING CONSTRUCTION (PARTITIONS,

COMPONENTS, BUILDING EQUIPMENT, ETC) SHOWN

WITHIN SCOPE OF WORK AS REQUIRED TO PERFORM THE

WORK, CONTRACTOR TO COORDINATE DEMOLITION

SCOPE WITH NEW WORK TO ENSURE NO DISRUPTIONS IN

THE PROJECT.

C. BEFORE COMMENCING THE WORK, VERIFICATION AT THE

SITE OF EXISTING CONSTRUCTION TO BE PRESERVED

AND REPORTING TO THE CONTRACTING OFFICER OF ANY

DISCREPANCIES OR QUESTIONABLE ITEMS.

D. COMPLY WITH APPLICABLE CODES AND REGULATIONS

PERTAINING TO SAFETY OF PERSONS, PROPERTY AND

ENVIRONMENTAL PROTECTION.

PROVIDE AND MAINTAIN BARRICADES, LIGHTING AND

GUARDRAILS AS REQUIRED BY APPLICABLE CODES AND

REGULATIONS TO PROTECT OCCUPANTS OF BUILDING AND

WORKERS.

PRIOR TO DEMOLITION, MEET WITH THE CONTRACTING

OFFICER TO IDENTIFY ITEMS WHICH ARE TO BE SALVAGED.

ALL OTHER DEMOLISHED MATERIALS ARE TO BE REMOVED

FROM THE SITE AND DISPOSED OF LEGALLY BY THE

CONTRACTING OFFICER.

ENSURE ADJACENT OCCUPIED SPACES MAINTAIN

ACCEPTABLE ENTRANCE/EGRESS ROUTES.

ERECT AND MAINTAIN DUST-PROOF PARTITIONS AS REQUIRED

TO PREVENT SPREAD OF DUST, FUMES AND SMOKE, ETC. TO

OTHER PARTS OF THE BUILDING. ON COMPLETION, REMOVE

PARTITIONS AND REPAIR DAMAGED SURFACES TO MATCH

ADJACENT SURFACES.

REMOVE AND SALVAGE DEBRIS FROM THE SITE DAILY AS IT

ACCUMULATES. REMOVE RENOVATION MATERIALS FROM THE

SITE, LEAVING A CLEAN, VACUUMED SPACE IN ACCORDANCE

WITH THE INDOOR AIR QUALITY CONSTRUCTION

MANAGEMENT PLAN.

UTILIZE BRACING AND SHORING WHERE NECESSARY TO

PREVENT COLLAPSE OF STRUCTURE OR PARTS THEREOF.

GENERAL CONTRACTOR IS RESPONSIBLE FOR DESIGN AND

CONSTRUCTION OF ALL BRACING AND SHORING.

PROTECT EXISTING CONSTRUCTION TO REMAIN. REPAIR ANY

DAMAGE TO EXISTING CONSTRUCTION IN A MANNER

ACCEPTABLE TO THE CONTRACTING OFFICER OR REPLACE

SUCH DAMAGE WITH NEW ACCEPTABLE TO THE

CONTRACTING OFFICER AND AT NO COST TO THE

GOVERNMENT.

MAINTAIN SERVICES AND SYSTEMS INDICATED TO REMAIN

AND PROTECT AGAINST DAMAGE DURING SELECTIVE

DEMOLITION OPERATIONS.

WHERE MECHANICAL OR ELECTRICAL SYSTEMS ARE

INDICATED TO BE SELECTIVELY DEMOLISHED, LOCATE,

IDENTIFY, DISCONNECT, AND REMOVE. NO SYSTEMS ARE TO

BE ABANDONDED IN PLACE, REMOVE UNUSED DISTRIBUTION

AND INFRASTRUCTURE TO SOURCE. REFER TO ENGINEERED

PLANS FOR FURTHER DEMOLITION OF ENGEERING SYSTEMS.

PATCH UNUSED PENETRATIONS CAUSED FROM DEMOLITION

TO MATCH ADJACENT CONSTRUCTION AND RATINGS.

SALVAGE BUILDING STANDARD LIGHT FIXTURES AT CEILING

DEMOLISHED AREAS FOR RE-USE AS INDICATED ON

ELECTRICAL DRAWINGS. COORDINATE WITH CONTRACTING

OFFICER WHICH LIGHT FIXTURES ARE TO BE SALVAGED FOR

STORAGE.

SALVAGE DEVICES THAT ARE BUILDING STANDARD THAT MEET

CURRENT CODE REQUIREMENTS FOR RE-USE (EXIT SIGNS,

HORN STROBES, EMERGENCY LIGHTS).

ALL AUDIO VISUAL EQUIPMENT THAT ARE SCHEDULED TO

REMAIN ARE TO BE PROTECTED FROM DUST AND DEBRIS

DURING DEMOLITION AND CONSTRUCTION.

DEMOLITION PLAN GENERAL NOTES

*NOTE: ASBESTOS ABATEMENT MUST TAKE PLACE

PRIOR TO DEMOLITION.

DEMOLITION SYMBOLS LEGEND

EXISTING DOOR TO REMAIN,

TYP U.N.O.

REMOVE EXISTING DOOR &

FRAME COMPLETELY.

REMOVE PORTION OF EXISTING WALL.

SEE FLOORPLAN FOR LOCATION AND

DIMENSION. TYP U.N.O.

EXISTING WALL OR PARTITION TO

REMAIN, TYP U.N.O.

D# DEMOLITION SHEETNOTE TAG

REMOVE ALL CONSTRUCTION SHOWN

DASHED COMPLETE, U.N.O.

LIMIT OF WORK LINE

(NIC) NOT IN CONTRACT

WP WORK POINT

AREA OF ASBESTOS ABATEMENT

DEMOLITION SHEET NOTES

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B115204 8 16268

SCALE: 1/8"=1'-0"

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

AD051

1S T

FL

O

O R

D

EM

O

LI

TI

O

N P

LA

N

JT JT R

W

W /M

EB

SCALE: 1/8" = 1'-0"

1ST FLOOR DEMOLITION PLANC1

SCALE: 1/8" = 1'-0"

BASEMENT DEMOLITION PLANA1

D1 REMOVE EXISTING FENCE; SET ASIDE AND PROTECT FOR

REUSE.

D2 REMOVE EXISTING PARTITIONS.

D3 REMOVE EXISTING DOOR.

D4 DEMOLISH EXISTING LOUVERS IN BRICK KNEE WALL.

D5 DEMOLISH EXISTING EXTERIOR CONCRETE PADS.

D6 VERIFY EXISTING CONDITIONS PRIOR TO DEMOLITION.

D7 ABATE FLOOR ASSEMBLY - LIMIT WORK TO ONLY AREA

IMPACTED BY DEMOLITION OR NEW WORK

D8 PROTECT EXISTING TO REMAIN AUDIO VISUAL EQUIPMENT.

D9 PROTECT EXISTING WINDOW TREATMENTS

D10 DISCONNECT AND RELOCATE FFE OUT OF WORK AREA,

CONTRACTOR TO TAKE OWNERSHIP OF FFE DURING

CONSTRUCTION AND RETURN TO THE GOVERNMENT AFTER

THE WORK IS COMPLETE.

D11 PROTECT ETR METAL ROLL-UP DOOR AND COUNTER.

D12 SALVAGE EXISTING ROOM SIGNAGE FOR REINSTALL

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

M

M

M xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8

BEDFORD

KITCHEN

MAIN OFFICE

IT OFFICE

CL.

WOMENS

JANJAN

MAIN ENTRY

HALL

PROJECTION

ROOM

LEXINGTON

SERVER

ROOM

VEST

CL.

PROJECTION

ROOM

HOLZMAN

MECH

MECH

LINCOLN

FOYERCL.

CL.

CL

xA.5 x7.5

ENTRY HALL

BURLINGTON

CONCORD

CORR.

CORR.

BACK LOBBY

CORRIDOR

DR1

DR1

2' -0

"WP

DR3

DR2

DR2

DEMOLITION RCP GENERAL NOTES

1. ALL INFORMATION FROM GENERAL DEMOLITION NOTES

APPLIES TO RCP DEMOLITION, UNLESS OTHERWISE NOTED.

2. ALL ACOUSTICAL CEILING TILE AND GRIDS SHOWN TO BE

REMOVED FOR REUSE ARE TO BE REMOVED CAREFULLY,

STORED AND PROTECTED FOR REINSTALLATION

3. ALL EXISTING FIXTURES THAT ARE TO BE REMOVED FOR

REUSE ARE TO BE SALVAGED, STORED AND PROTECTED

FOR RELOCATION

4. REMOVE ANY CEILING TILE THAT ARE BROKEN,

WARPED, WATER DAMAGED OR DISCOLORED, AND

REPLACE WITH NEW OR REUSED TILES TO MATCH EXISTING.

5. VERIFY LOCATIONS/DIMENSIONS OF GRID TO BE

DEMOLISHED, REFERENCE CONSTRUCTION PLAN FOR

COORDINATION.

DEMOLITION RCP SHEET NOTES

DEMO RCP SYMBOLS LEGEND

REMOVE PORTION OF EXISTING WALL.

SEE FLOORPLAN FOR LOCATION AND

DIMENSION. TYP U.N.O.

EXISTING WALL OR PARTITION TO

REMAIN, TYP U.N.O.

D# DEMOLITION SHEETNOTE TAG

REMOVE ALL CONSTRUCTION SHOWN

DASHED COMPLETE, U.N.O.

LIMIT OF WORK LINE

(NIC) NOT IN CONTRACT

WP WORK POINT

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B115204 8 16268

SCALE: 1/8"=1'-0"

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

AD061

1S T

FL

O

O R

D

EM

O

LI

TI

O

N R

EF

LE

C

TE

D C

EI

LI

N G

P

LA

N

JT JT R

W

W /M

EB

SCALE: 1/8" = 1'-0"

1ST FLOOR DEMOLITION RCPC1

DR1 REMOVE CEILING GRID AND TILE TO NEAREST GRID LINES;

SALVAGE AND STORE FOR REUSE.

DR2 SAWCUT ROOF FOR NEW FRESH AIR INTAKE, REFER TO

ROOF PLANS FOR OPENING LOCATION

DR3 DISCONNECT, REMOVE, CLEAN AND STORE EXISTING

LIGHTING FOR REINSTALL, TYP.

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

T

T

T

S

UP

CONSTRUCTION SYMBOLS LEGEND

EXISTING WALL

EXISTING DOOR

TO REMAIN

NEW WALL

NEW DOOR

(SEE DOOR

SCHEDULE)

G3A PARTITION TYPE

ROOM TAG

ROOM NAME

100 SF

CONSTRUCTION

SHEET NOTE TAG

LIMIT OF WORK LINE

AREA

DOOR NUMBER

(NIC) NOT IN CONTRACT

WP WORK POINT

MECHANICAL SCOPE MAY STILL REQUIRE WORK

AND/OR ACCESS IN THIS AREA

xA xB x7 x8 xA.5 x7.5

779 SF

ELECTRICAL

RM.

AREA

WAY

AREA

WAY

AREA

WAY

APPROXIMATE

LOCATION OF

EXISTING NCE

CONTROLLER

EQUIPMENT IS IN

CLOSE PROXIMITY TO

ELECTRICAL SERVICE

ENTRANCE AND

STEPDOWN

TRANSFORMER (4160v) xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x7 x8 x8

MAIN OFFICE

IT OFFICE

HOLZMAN

LINCOLN

FOYER

CONCORD PROJECTION

ROOM

LEXINGTON

PROJECTION

ROOM

SERVER

ROOM

VEST

BACK LOBBY

WOMENS

JAN

CL.

CL.

CL.

KITCHEN

BURLINGTON BEDFORD

MAIN OFFICE

IT OFFICE

CORR.

HOLZMAN

LINCOLN

FOYER

CONCORD PROJECTION

ROOM

LEXINGTON

PROJECTION

ROOM

SERVER

ROOM

VEST

MECH

MECH

WOMENS

JAN

CL.

CL.

CL.

CL.

MAIN ENTRY

HALL

ENTRY HALL

xA.5 x7.5

A-201

F5

A-201F6

A-201

F9

A1 A-201

45°

AL

IG

N

CORRIDOR

MENS

A1 A-501

A-101 A4

26A

WP

'-0

B

2' -6

7'-4"

3'-2"

TYP.

S4B.U

4" HOUSEKEEPING

PAD

SIZE TO MATCH

EQUIPMENT

FOOTPRINT +1"

AROUND EACH SIDE

2' -2

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

ALL EXISTING WALLS TO REMAIN THAT CONNECT WITH NEW

CONSTRUCTION ARE TO BE PATCHED AND REPAIRED TO MEET

REQUIREMENTS OF NEW FINISHES, U.N.O. REFER TO

SPECIFICATIONS FOR LEVEL OF FINISH.

FOR DRYWALL FINISHING, THE CONTRACTOR SHALL COMPLY

WITH MANUFACTURER'S PRINTED INSTRUCTIONS AND

SPECIFICATIONS, EXCEPTION: COMPLY WITH MORE STRINGENT

REQUIREMENTS OF GYPSUM ASSOCIATION GA-216

RECOMMENDED SPECIFICATION FOR THE APPLICATION AND

FINISHING OF GYPSUM BOARD.

PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH

FACE, UNLESS OTHERWISE NOTED. MAINTAIN DIMENSIONS

MARKED "CLEAR" OR "HOLD". ALLOW FOR THICKNESS OF

FINISHES.

PRIOR TO CLOSING ANY WALLS OR CEILINGS, ALL SYSTEMS

(HVAC, PLUMBING, ELECTRICAL) SHALL BE INSPECTED, AND

WHERE REQUIRED, TESTING BY CONTRACTOR ENGINEERS AND

BY PROPER AUTHORITIES HAVING JURISDICTION TO INSURE

THEIR PROPER INSTALLATION AND FUNCTION.

THE CONTRACTING OFFICER RESERVES THE RIGHT TO MOVE

ANY FIXTURE, RECEPTACLE OR BUILT-IN OBJECT UP UNTIL THE

TIME HE/SHE SHALL APPROVE THE WALLS OR CEILINGS TO BE

CLOSED. THIS APPROVAL SHALL TAKE PLACE PRIOR TO THE

INSPECTORS APPROVAL SO AS NOT TO CONFLICT WITH ANY

BUILDING OFFICIALS DECISIONS.

MAINTAIN EXITS, EXIT LIGHTING, FIRE PROTECTIVE DEVICES AND

ALARMS IN CONFORMANCE WITH CODES AND ORDINANCES

DURING CONSTRUCTION.

PROTECT AREA OF WORK AND ADJACENT AREAS FROM DAMAGE

DURING CONSTRUCTION.

MAINTAIN WORK AREAS SECURE AND LOCKABLE DURING

CONSTRUCTION. COORDINATE WITH CONTRACTING OFFICER TO

ENSURE SECURITY.

DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. IN

CASE OF CONFLICT, CONSULT THE CONTRACTING OFFICER.

ALL DOOR OPENINGS TO BE NO LESS THAN 6" FROM NEAREST

PERPENDICULAR PARTITION, U.N.O.

UNDERCUT DOORS TO CLEAR TOP OF FLOOR FINISHES BY 1/4",

UNLESS OTHERWISE NOTED.

ALL PARTITIONS SHALL BE PLUMB, SQUARE, STRAIGHT, AND

PARALLEL, PERPENDICULAR, OR AT 45-DEGREE ANGLE TO THE

CLOSEST BUILDING GRID, U.N.O.

INDICATED PARTITION TYPES ARE CONTINUOUS ABOVE/BELOW

DOOR AND WINDOW OPENINGS AND AROUND CORNERS UNTIL

INTERSECTION WITH A DIFFERENT TYPE. WHERE PARTITIONS

INTERSECT AT “T”, THE INDICATED TYPE RUNS ACROSS THE “T”

U.N.O.

AT LOCATIONS OF ABOVE CEILING MEP PENETRATIONS,

MAINTAIN WALL ACOUSTIC AND FIRE RATING.

ON CONTINUOUS WALL SURFACES WHERE CONSTRUCTION

INVOLVES MORE THAN ONE MATERIAL, FINISH, OR MATERIAL

THICKNESS, LOCATE FRAMING SO THE FINISHED FACES ALIGN,

U.N.O.

REFER TO SHEET A-201 FOR TYPICAL MOUNTING HEIGHTS.

LIMIT OF WORK LINE INCLUDES AREAS SERVED BY NEW AND

EXISTING MECHANICAL SYSTEM - SEE MECHANICAL DRAWINGS -

INCLUDING INTERIOR SPACE WITHIN LIMIT OF WORK LINE SHOWN.

CONSTRUCTION PLAN

GENERAL NOTES

CONSTRUCTION SHEET NOTES

xC

A1 A-501

6'-6" 1'-5"

'-0

3'-0"

4' -0

4' -0

4'-0"

CHAINLINK FENCE GATE

48" x FULL HEIGHT

REFER TO

FOR DETAILS

NEW ATFP COMPLIANT

CHAINLINK FENCE

MECHANICAL

EQUIPMENT

ENCLOSURE

9' -4

4'

-0

8' -5

9'-9"

/C6 A-502

26A

B

MECH

PROVIDE NEW CARPET TO MATCH

TOOTH CARPET INTO EXSITNG

ASSEMBLY TO BLEND

PROVIDE BROADCAST EPOXY

EPOXY TO CARPET TRANSITION

REMOVE AND SALVAGE TILE AS

REQUIRED TO COMPLETE THE WORK

USE SALVAGED TILE TO INFILL AS

REQUIRED TO REPAIR ADJACENT

AREAS IMPACTED BY CONSTRUCTION

(E) 12x12 TILE

(E) CARPET

CARPET SYSTEM UNKNOWN (TILE

OR BROADLOOM)

PROVIDE WALL BASE TO MATCH

EXISTING

PAINT DOOR AND FRAME TO MATCH WALLS

SALVAGE ANY BUILDING STANDARD

SIGNAGE FOR REINSTALL

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B115204 8 16268

SCALE: 1/8"=1'-0"

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

A-101

FI

R

ST

F

LO

O

R C

O N

ST

R

U C

TI

O

N P

LA

N

JT JT R

W

W /M

EB

SCALE: 1/8" = 1'-0"

BASEMENT CONSTRUCTION PLANA1

SCALE: 1/8" = 1'-0"

FIRST FLOOR CONSTRUCTION PLANC1

1 CONCRETE EQUIPMENT PAD

2 REFER TO MECHANICAL

3 PRESERVE AND PROTECT METAL

ROLL-UP DOOR AND COUNTER - ETR

4 MASONRY WALL INFILL

SCALE: 1/4" = 1'-0"

EQUIPMENT PAD PLANA4 SCALE: 1/8" = 1'-0"

FINISH PLANA6

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/ xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8 xA.5 x7.5 A1

A-201

A1 A-501

EQ

R

.O

1' -1

0"

EQ

EQ

R

.O

1' -1

0"

EQ

V.

I.F

4'

-7

V.

I.F

4'

-7

APPROXIMATE

LOCATION OF

STEEL BELOW

2'-6" R.O.

1'-8"

2'-6" R.O.

1'-8"

STRUCTURAL REINFORCING BELOW,

REFER TO STRUCTURAL DRAWINGS

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B115204 8 16268

SCALE: 1/8"=1'-0"

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

A-102

R O

O F

C O

N

ST

R U

C

TI

O N

P

LA

N

JT JT R

W

W /M

EB

SCALE: 1/8" = 1'-0"

ROOF CONSTRUCTION PLANC1

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

S

S

DS

F

F

F

5° R

5°

S xA x1 xB xC xD x2 x3 x4 x5 x6 x7 x8 xA.5 x7.5

BEDFORDKITCHEN

MAIN OFFICE

IT OFFICE

CL.

WOMENS

JANJAN

MAIN ENTRY

HALL

PROJECTION

ROOM

LEXINGTON

SERVER

ROOM

VEST

CL.

PROJECTION

ROOM

HOLZMAN

MECH

MECH

LINCOLN

FOYER

CL.

CL.

CL

ENTRY HALL

CORRIDOR

BURLINGTON

CONCORD

CORR.

CORR.

BACK LOBBY

R1

R1

ETS

ETS

WP

R2

R2

REFLECTED CEILING

PLAN GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

THIS PLAN IS FOR CEILING FIXTURE AND EQUIPMENT

LOCATIONS ONLY. REFER TO MEP/FP DRAWINGS FOR

ADDITIONAL INFORMATION.

ALL CEILING HEIGHTS ARE ABOVE FINISH FLOOR, WHERE

THE FINISH FLOOR EQUALS 0'-0". CEILING HEIGHT SHALL BE

UNIFORM THROUGHOUT U.N.O.

ALL DOWN LIGHTS, SMOKE DETECTORS, SPRINKLER HEADS,

EXIT SIGNS, ETC. TO BE CENTERED IN CEILING TILE, U.N.O.

ALL DIMENSIONS OF FIXTURES, DEVICES, SPRINKLER

HEADS, ETC. ARE TO CENTERLINE OF FIXTURE, U.N.O.

WHERE ITEMS ARE IN LINE, CENTERLINE OF ITEMS OR

GROUP OF ITEMS ARE TO ALIGN, U.N.O.

CEILING SYSTEM IS TO BE CENTERED IN ALL ROOMS, U.N.O.

REFER TO RCP FOR GRID LINE OR TILE TO BE CENTERED.

PATCH EXISTING CEILING TO MATCH ADJACENT CEILING

WHERE EXISTING WALLS DEMOLISHED. CUT THROUGH

EXISTING CEILING AND PATCH INTERFACE WHERE NEW

WALL IS BEING BUILT OR BEING EXTENDED TO DECK.

ALL MEP/FP LOCATIONS IN CONFLICT WITH ARCHITECTURAL

DRAWINGS SHOULD BE COORDINATED WITH THE

CONTRACTING OFFICER PRIOR TO INSTALLATION. NOTIFY

CONTRACTING OFFICER OF ANY DISCREPANCY, OMISSION,

OR UNANTICIPATED FIELD CONDITION THAT ALTERS THE

INTENT OF THESE DRAWINGS.

ALL CEILING SYSTEMS SHALL BE SUPPORTED INDEPENDENT

OF ALL NEW AND EXISTING PIPES, DUCTS, CONDUITS, ETC.

COORDINATE LOCATION, SIZE AND MOUNTING OF NEW

PROJECTORS WITH AV CONSULTANT AND CONTRACTING

OFFICER.

REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS

FOR BASELINE TESTING OF EXISTING AND NEW HVAC

SYSTEM.

REPLACE ALL DAMAGED AND STAINED CEILING TILES

WHERE CEILINGS ARE TO BE REUSED. MATCH EXISTING.

FINISH OF HVAC DIFFUSERS, DRAPERY POCKETS AND

SPEAKER GRILLS TO MATCH ADJACENT FINISH, U.N.O.

THE CONTRACTOR SHALL CLEAN AND RE-LAMP ALL LIGHT

FIXTURES TO BE RELOCATED OR THAT ARE EXISTING TO

REMAIN.

THE CONTRACTOR SHALL CLEAN ALL HVAC DIFFUSERS AND

GRILLES THAT ARE EXISTING TO REMAIN.

COORDINATE ALL CEILING ACCESS PANEL LOCATIONS WITH

CONTRACTING OFFICER PRIOR TO INSTALLATION.

EXIT SIGN

WALL WASHER

WALL SCONCE

SUPPLY AIR DIFFUSER

OCCUPANCY SENSOR

DAYLIGHT SENSOR

WIRELESS ACCESS

POINT OUTLET

FIRE ALARM AUDIO/STROBE

FIRE ALARM STROBE ONLY

FIRE ALARM HEAT

DETECTOR, FIXED TEMP

FIRE ALARM HEAT

DETECTOR, COMBO RATE

SMOKE DETECTOR

SPEAKER

SPRINKLER HEAD

UPRIGHT SPRINKLER

NO CEILING - EXPOSED TO

STRUCTURE

(SEE FINISH SCHEDULE

FOR EXPOSED ITEMS TO

BE PAINTED)

NEW 2'X2' ACOUSTICAL

CEILING

NEW GWB CEILING SOFFIT

NEW 2'X4' ACOUSTICAL

CEILING

8'-0"

GWB-8

CEILING HEIGHT (A.F.F.)

ETS

NOTE: GENERIC DEVICE SYMBOLS SHOWN BELOW- SEE SPECIFIC DISCIPLINES (MECH.,

ELEC., ETC.) FOR SPECIFIC DESCRIPTIONS AND ADDITIONAL ITEMS NOT SHOWN.REFLECTED CEILING LEGEND

EXISTING 2'X2' ACOUSTICAL

CEILING

EXISTING 2'X4' ACOUSTICAL

CEILING

EXISTING GWB CEILING SOFFIT

R# REFLECTED

CEILING PLAN

SHEET NOTE

RETURN AIR GRILLE

EXISITNG RETURN AIR

DIFFUSER

EXISTING RETURN AIR GRILL

EXISTING SPRINKLER

WP WORK POINT

REFLECTED CEILING

SHEET NOTES

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B115204 8 16268

SCALE: 1/8"=1'-0"

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

AR101

1S T

FL

O

O R

R

EF

LE

C

TE

D

C

EI

LI

N

G P

LA

N

JT JT R

W

W /M

EB

SCALE: 1/8" = 1'-0"

CONSTRUCTION RCPC1

R1 REINSTALL EXISTING GRID AND TILE FROM SALVAGE.

R2 RE-LAMP SALVAGED LIGHTING AS REQUIRED AND

RE-INSTALL AT THE SAME LOCATION UPON COMPLETION

OF ABOVE CEILING WORK BY OTHER TRADES. MAKE

SURE THAT ALL EXISTING FIXTURES IN OPERATIONAL

CONDITION PRIOR TO RE-INSTALLATION., TYP,

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

T T

TS

T T T

SD

SD

S

1ST FLOOR

0" x1

VINYL COVE

BASE TO MATCH

EXIST.

EXIST.

DOOR AND

CLOSET

PROPOSED

ETR

CONSTRUCTION

MECH. CLOSET

WALL BEYOND

1ST FLOOR

0" xC

EXIST. 4" VINYL

COVE BASE

4" VINYL COVE BASE -

COLOR TO MATCH

EXIST.

45-DEG MECH.

CLOSET WALL

PROPOSED

EXIST.

ELECTRICAL

PANEL - ETR

OPEN

A

DOUBLE WALL ACOUSTIC

TRANSFER DUCT; REFER

TO MECH.

WP

ETR

CONSTRUCTION

1ST FLOOR

0" x1

4" VINYL COVE

BASE - COLOR

TO MATCH EXIST.

45-DEG MECH.

CLOSET WALL

OPEN

B

DOUBLE WALL

ACOUSTIC TRANSFER

DUCT; REFER TO MECH.

SALVAGED CEILING AND

SYSTEMS TO REINSTALL,

REFER TO RCP FOR

LOCATIONS

1ST FLOOR

0"

ROOF

15'-0" xAxBxCxD

EXISTING LOUVER TO

REMAIN

ROOFTOP DUCT

EXTENSION BEYOND

BRICK INFILL TO

MATCH EXISTING

BRICK INFILL TO

MATCH EXISTING

MECHANICAL

EQUIPMENT - SEE

MECH.

CONCRETE

EQUIPMENT PAD

A1 A-501

METAL EQUIPMENT

STAND - SEE MECH.

C5 A-501

TYP

2' -8

E5 A-501

TYP

NEW ATFP COMPLIANT 8' TALL CHAINLINK FENCE EQUIPMENT ENCLOSURE

(E) MECH EQUIPMENT TO REMAIN

8' -0

1'

-6

SWITCHES

OUTLETS

3' -2

CARD READER

THERMOSTAT

FINISHED FLOOR

TYPICAL MOUNTING HEIGHTS

SCALE 1/2" = 1'-0"

6' -8

FIRE ALARM STROBE

4' -0

MOUNTING HEIGHTS GENERAL NOTES

1.

2.

3.

ALL MOUNTING HEIGHTS SHALL BE MEASURED FROM FINISHED FLOOR TO CENTERLINE OF DEVICE, U.N.O. EXCLUDING EXIT SIGNS.

DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE WHEREVER POSSIBLE

ALL DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATED, U.N.O.

SCHEDULED SHAFTWALL

HM FRAME

SEALANT

DOOR PANEL

2"

1/2"

FRAME ANCHOR PER WALL ASSEMBLY

1/2"

CORRIDORMECH.

EQ.

5/ 8"

EQ.

DOOR PANEL TYPES

AS

S

C H

ED

U

LE

D

PN

L-

F- H

M

SCHED.

AS

FRAME TYPES

C6

A-201

C6

A-201

2"

SCHED.

AS 2"

2"

AS

S C

H

ED

U

LE

D

FRM-00HM-1

HARDWARE SETS

HS-1 STORAGE

3PR BUTT HINGES

1 LOCKSET WITH LEVER - STORAGE FUNCTION

REMOVABLE LOCK CORE1

2 PARALLEL ARM WITH BUILT-IN HOLD OPEN SET TO 170DEG (MOUNTED ON THE INTERIOR)

1 SET FLUSH BOLT W/ DUST PROOF STRIKE - CONSTANT LATCHING

1 COORDINATOR

2 ARMOR PLATE (MOUNTED ON INTERIOR)

DOOR AND HARDWARE GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

DOORS AND DOOR HARDWARE TO BE ADA COMPLIANT WITH BUILDING & FIRE

CODES.

SEE FLOOR PLANS AND PARTITION TYPES FOR THROAT DEPTHS, NEW FRAMES IN

EXISTING PARTITIONS TO HAVE THROAT DEPTHS VERIFIED IN FIELD

MAINTAIN RATING OF EXISTING FIRE RATED DOORS TO REMAIN.

LOCK CORES TO BE COMPATIBLE WITH BASE STANDARD CYLINDERS AND KEYED

TO MASTER SYSTEM. COORDINATE WITH BASE OPERATAIONS AND MAINTANCE

STAFF.

ALL SINGLE DOORS TO RECEIVE 1-1/2" PAIR BUTT HINGES AND DOUBLE DOOR TO

RECEIVE 3 PAIR BUTT HINGES.

DOORS OVER 7'-0" HEIGHT TO RECEIVE 2 PAIRS BUTT HINGES AT THE SINGLE

DOOR AND 4 PAIRS BUTT HINGES AT DOUBLE DOORS

THE HARDWARE SET IS FURNISHED AS INFORMATION AND AS GUIDE ONLY. THE

COMPLETE QUANTITY REQUIREMENTS FOR EACH OPENING SHALL BE THE

RESPONSIBILITY OF GC.

A1 A-201

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B1152

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

A-201

EL

EV

AT

IO

N S

AN

D

S C

H

ED

U

LE

S

JT JT R

W

W /M

EB

SCALE: 1/4" = 1'-0"

INTERIOR ELEVATION AT

KITCHENF9SCALE: 1/4" = 1'-0"

INTERIOR ELEVATION AT CORRIDORF6SCALE: 1/4" = 1'-0"

INTERIOR ELEVATION AT

ENTRANCE FOYERF5

SCALE: 1/4" = 1'-0"

WEST EXTERIOR ELEVATIONA1

DOOR SCHEDULE

DOOR

TO ROOM FROM ROOM

DOOR PANELS

DOOR FIRE

RATING

MINUTES

DOOR FRAME

HARDWARE SET NUMBER

PANEL TYPE PANEL DIMENSIONS

THICKNESS UNDERCUT FINISH 1 TYPE

FACE DIMENSIONS

FINISH 1PANEL 1 PANEL 2

WIDTH

HEIGHT JAMB WIDTH HEAD HEIGHTPANEL 1 PANEL 2

1ST FLOOR

26A CORR. MECH PNL-F-HM PNL-F-HM 3'-0" 2'-0" 7'-0" 1 3/4" 0" PAINT N/A FRM-00HM1 2" 2" PAINTED TO MATCH ADJACENT WALL HS-1 26B CORR. MECH PNL-F-HM PNL-F-HM 1'-6" 1'-6" 7'-0" 1 3/4" 0" PAINT N/A FRM-00HM1 2" 2" PAINTED TO MATCH ADJACENT WALL HS-1

SCALE: 3" = 1'-0"

HOLLOW METAL DOOR JAMB AND HEAD AT GWBC6

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

1ST FLOOR

0"

ROOF

15'-0" x1

CRUSHED STONE

ALL EDGES OF PAD

A-501 E5

C5 A-501

MASONRY INFILL

CONCRETE PAD

CONDENSER UNIT -

SEE MECH

AHU - SEE

MECH

A-501 E7

METAL EQUIPMENT

STAND

A-502 A6

TYP

2' -8

S4B.U

A 26

B

BE

YO

N

D

A-501 B5

NEW ATFP COMPLIANT

CHAINLINK FENCE

MECHANICAL

EQUIPMENT

ENCLOSURE

OUTDOOR AIR INTAKE

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

ALL PARTITIONS ARE TYPE -S4B.U UNLESS OTHERWISE NOTED. PARTITIONS

TYPES ARE KEYED ON FLOOR PLANS.

ALL WORK SHALL COMPLY WITH FEDERAL BUILDING CODES AND REGULATIONS.

VERIFY RATED WALLS WITH CODE PLANS.

REVIEW ALL DRAWINGS AND COORDINATE WALL CONSTRUCTION INCLUDING

LOCATION OF FRAMING MEMBERS WITH PENETRATIONS, RECESSED AND

SURFACE MOUNTED ITEMS. PROVIDE FRAMING AND OR BACKING AS REQUIRED

TO SUPPORT WALL MOUNTED OR RECESSED ITEMS AND WALL CONSTRUCTION

AROUND ITEMS.

WHEN ITEMS PENETRATE WALL DO NOT BEAR PENETRATIONS ON WALLS,

SUPPORT SEPERATELY.

PARTITIONS ENCLOSING SPACES WITHOUT CEILINGS ARE TO EXTEND TO

UNDERSIDE OF SLAB ABOVE.

ALL FIRE RATED PARTITION ASSEMBLIES ARE TO CONTINUE FROM FLOOR TO

DECK ABOVE.

ALL FIRE AND SMOKE RATED PARTITIONS ARE TO HAVE ANY/ALL GAPS FILLED

WITH A MATERIAL THAT WILL MEET OR EXCEED THE RATING AND/OR

CONSTRUCTION REQUIREMENTS OF THE WALL.

THE ENVELOPE CREATED BY FIRE RATED PARTITIONS AND SHAFTS IS REQUIRED

TO BE CONTINUOUS AND UNINTERRUPTED EXCEPT BY TESTED THROUGH-

PENETRATION FIRE STOP ASSEMBLIES AS SPECIFIED. REFER TO THE CODE PLAN

FOR DIAGRAMS.

PROJECT IS BASED ON QUOTED UL DESIGNS. OTHER DESIGNS ACCEPTABLE TO

ALL AGENCIES WITH JURISDICTION MAY BE SUBMITTED FOR APPROVAL.

WALL TYPES DESCRIBED ON THIS SHEET DO NOT ACCOUNT FOR REQUIRED

BACKING AND /OR SUPPORT FOR WALL MOUNT FIXTURES, EQUIPMENT,

CASEWORK AND/OR SYSTEMS FURNITURE. COORDINATE WITH ENLARGED

FLOOR PLANS, INTERIOR ELEVATIONS, AND EQUIPMENT PLANS PRIOR TO THE

COVERING OF STUD FRAMING. REFER TO MANUFACTURER'S

RECOMMENDATIONS.

ALL PARTITIONS DIMENSIONS PROVIDED ARE TO FINISHED FACE UNLESS

OTHERWISE NOTED.

LOCATE HINGE SIDE OF DOOR AT 6" FROM FINISHED FACE OF ADJACENT WALL

UNLESS OTHERWISE NOTED OR DIMENSIONED.

WALL TYPES AND RATINGS INDICATED ON PLAN CONTINUE ABOVE/BELOW

ADJACENT WINDOW OR DOOR OPENINGS.

MAINTAIN FIRE RATING AROUND RECESSED FIXTURES.

DO NOT LOCATE OUTLET BOXES (INCLUDING TELECOM/DATA AND ELECTRICAL)

OPPOSITE ONE ANOTHER IN ACOUSTICALLY RATED PARTITIONS. LOCATE

OUTLETS AT LEAST ONE STUD BAY APART. SEAL THE OUTLET BOXES WITH PUTTY

PADS AND CAULK THE PERIMETER USING ACOUSTIC SEALANT. AT RATED

PARTITIONS, LOCATE OUTLET BOXES 24" APART, MIN. UNLESS AT SHAFT WALLS.

AT ALL ACOUSTICALLY RATED PARTITIONS USE ACOUSTICAL SEALANT APPLIED

PER MANUFACTURERS INSTRUCTIONS.

ON CONTINUOUS WALL SURFACE WHERE CONSTRUCTION INVOLVES MORE THAN

ONE MATERIAL, FINISH, OR MATERIAL THICKNESS ALIGN FACE OF FINISH UNLESS

OTHERWISE NOTED.

REFER TO REFLECTED CEILING PLAN FOR CEILING MATERIALS AND HEIGHTS;

REFER TO ROOM FINISH SCHEDULE FOR FINISHES AND SPECIAL INSTRUCTIONS.

PARTITION GENERAL NOTES

PARTITION PERFORMANCE RATING

PARTITION TYPE LEGEND

G3A.1

U = UNRATED

S = SMOKE PARTITION

1 = 1 HOUR RATED

PARTITION GROUP

C = CHASE WALL

G = GYPSUM

M = MASONRY

S = SHAFT WALL

DEFINES RELATIVE SIZE

TYPE MODIFIER

INSULATION NOT SHOWN FOR CLARITY

PARTITION PRIORITY LEGEND

1.

2.

3.

4.

5.

6.

7.

PARTITION PRIORITY AS FOLLOWS, FROM

HIGHEST TO LOWEST:

FIRE BARRIER

1 HOUR RATED SHAFT WALL

1 HOUR RATED PARTITION

SMOKE PARTITION

ACOUSTICAL PARTITION TO DECK

NON-RATED PARTITION TO DECK

NON-RATED PARTITION

LOWER PRIORITY PARTITIONS

HIGHER PRIORITY PARTITIONS

EXTEND GWB TO

CORNER AT HIGHER

PRIORITY PARTITION

WALL ASSEMBLY

TO BE

UNINTERRUPTED

THROUGH LOWER

PRIORITY

INTERSECTIONS

BASE TO MATCH

EXISTING

FINISHED FLOOR SLAB

BTM. OF CEILING

UNDERSIDE OF

CONCRETE PLANK

5/8" GYPSUM BOARD

4" METAL CH STUD

LO

W

ER

SE

C

TI

O

N

PL

AN

U

PP

ER

SE

TI

O N

4" DEFLECTION TRACK

SOUND ATTENUATION

BLANKET

4" METAL RUNNER

1" GYPSUM BOARD

SHAFT WALL

4 5/8"

S4B.U

ACOUSTIC SEALANT

5/8" GWB

x1

MASONRY WALL -

EXISTING

LAP AVB AT EXPOSED

EXISTING CMU

BRICK TIE

GROUTED SOAP

V.

I.F

C O

U R

SE

S

REMOVE COURSES AS

REQUIRED TO LAP

AVB OVER (E) AVB - 6"

MINIMUM

V.

I.F

C O

U R

SE

S

SOLID GROUTED CMU

TOOTH IN FACE BRICK

TO MATCH EXISTING

COURSING

(E) MASONRY WALL

LAP AVB AT EXPOSED

EXISTING CMU1

FU

LL

B R

IC

K

TOOTH IN FACE BRICK

TO MATCH EXISTING

COURSING

(E) INSULATION

TYPE UNKNOWN

MATCH EXSTING

INSULATION TYPE

(IF ANY)

BRICK TIE

ROOF

15'-0"

PREMANUFACTURED

INSULATED ROOF CURB WITH

CONTINUOUS INSULATION

(E) ROOFING MEMBRANE

(ASSUMED PVC V.I.F.)

METAL ANGLE, REFER

TO STRUCTURAL

MECHANICAL DUCT

COUNTERFLASHING

HIGH TEMPERATURE

SEALANT

1"

PT WOOD BLOCKING

PT WOOD BLOCKING

SELF-ADHERED

TRANSITION STRIP

RIGID INSULATION

CANT-STRIP

MEMBRANE FLASHING

TERMINATION BAR WITH

CONTINUOUS BEADS OF

SEALANT ON TOP &

BOTTOM EDGES

MEMBRANE ROOFING

RIGID INSULATION

6" 6" 6"

(E) TOPPING SLAB

MECHANICAL DUCT

FRICTION FIT MINERAL WOOL

SEALANT AND BACKER ROD

PROVIDE TRANSITION

MEMBRANE AT SURFACE OF

TOPPING SLAB IF EXISTING

MOISTURE MIDIGATION

MEMBRANE EXISTS

(E) CONC. PLANK

ROOF DECK

FRICTION FIT MINERAL WOOL

PROVIDE POSITIVE FASTENING PER CURB

MANUFACTURERES RECOMENDATIONS IN

ACCORDANCE WITH WIND UPLIFT

REQUIREMENTS

JOINT SEALANT

M

AX1"

FRICTION FIT MINERAL WOOL INSULATION

AS SCHEDULED

SHAFTWALL

TRANSFER DUCT; REFER TO MECHANICAL

CARPET

SLOPE

1:20

FLASH PATCH CENTER EDGE STRIP UNDER

DOOR WHERE DOOR OCCURS

EPOXY FLOOR

METAL EDGE STRIP

EPOXY FLOORING

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

A-501

SE

C

TI

O

N S

D

ET

AI

LS

JT JT R

W

W /M

EB

SCALE: 1/2" = 1'-0"

SECTION AT MECHANICAL EQUIPMENTA1 SCALE: 1 1/2" = 1'-0"

TYPICAL PARTITION - S4B.UA7

SCALE: 1 1/2" = 1'-0"

SECTION DETAIL AT LOUVER

INFILLE5

SCALE: 1 1/2" = 1'-0"

PLAN DETAIL AT LOUVER

INFILLC5

SCALE: 1 1/2" = 1'-0"

ROOF-DUCT DETAILE7

SCALE: 3" = 1'-0"

SHAFTWALL SEALANT DETAILB5

SCALE: 3" = 1'-0"

CARPET TO EPOXYA5

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

1/8" R (TYP.) CHAMFER

#5 REBAR @ 12"E.W.

4000 PSI AIR-ENT.

CONCRETE SLAB

(BROOM FINISHED)

COMPACTED GRAVEL

BASE & EDGE STRIP

COMPACTED

SUBGRADE

SCORE JOINT EDGE

1/8" RAD. (TYP.)

1"

1' -0

1'

-6

8"6" 6"

1'-0"

0" AT PAVED SURFACES

6" AT GRASS OR GRAVEL

AREAS

PROVISION FOR PADLOCK

4" LATCH POST

4" DIA HINGE POST

4' -0

48" CLR GATE10' - 0" MAX POST SPACING

6" M

IN

3" M

AX

8' -0

ALL JOINTS ARE

WELDED TO MAKE RIGID

FRAME

CONCRETE FOUNDATIONS SHALL HAVE A DIAMETER EQUAL TO FOUR

TIMES THE DIAMETER OF THE POST, BUT NOT LESS THAN 12".

ALL FENCE PRODUCTS SHALL BE PVC COATED. COLOR TO MATCH

BASE STANDARD.

B1105

B1106

B1102

B1109

B1108

B1107

B1110

B1152

PROPERTY OF THE UNITED STATES AIR FORCE

B1106

SI

ZE

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

IS

SU

E

D

AT

E:

SO

LI

C

IT

AT

IO

N N

O

C O

N

TR

AC

T

N O

D

EP

AR

TM

EN

T

O F

TH

E

AI

R

F O

R C

E th

A

IR

B

AS

E G

R O

U P/

C E

BA

SE

C

IV

IL

E

N G

IN

EE

R

IS

IO

N

H

AN

SC

O

M A

FB

, M

A

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SHEET IDENTIFICATION

SM

M

A

AN

SI

-D

/0

7/

M

XR

D

5-

1 2 7 8 9 103 4 5 6

A

B

C

D

E

F

G

PLAN NORTH

PROFESSIONAL SEAL:

E

AIR FORCE MAT RIEL COMMAN

D

66 AIR GROUP

TH

BASE

A

IR

F O

R C

E M

A

TE

R

IA

L C

O M

M A

N D

ISSUE FOR CONSTRUCTION

M

XR

D

-0

R

EP

AI

R (R

EP

LA

C E)

A

IR

C O

N D

IT

IO

N

IN

G U

N

IT

C O

N

FE

R

EN

C E

C

EN

TE

R

BU

IL

D

IN

G

A-502

SI

TE

D

ET

IA

LS

JT JT R

W

W /M

EB

SCALE: 3/4" = 1'-0"

TYPICAL CONCRETE PAD DETAIL AT MECHANICAL EQUIPMENTA6

SCALE: 1/4" = 1'-0"

CHAINLINK FENCE DETAILSC6

IS

SU

E

FO

R C

O N

ST

R

U C

TI

O

N

/2 8/

DTS

DTR

CHWS

CHWR

CWR

CWS

CD

GR

GS

V

SHWS

SHWR

SCHWS

SCHWR

RS

RL

PCHWS

PCHWR

PC

MU

MPS

MPR

LPS

HPR

HPS

LPR

HWS

HWR

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

CONDENSATE DRAIN

HIGH PRESSURE RETURN

(CONDENSATE)

HIGH PRESSURE STEAM

HOT WATER RETURN

HOT WATER SUPPLY

LOW PRESSURE RETURN

(CONDENSATE)

LOW PRESSURE STEAM

MEDIUM PRESSURE RETURN

(CONDENSATE)

MEDIUM PRESSURE STEAM

MAKE-UP WATER

PUMPED CONDENSATE

PRIMARY CHILLED WATER RETURN

PRIMARY CHILLED WATER SUPPLY

REFRIGERANT LIQUID LINE

REFRIGERANT SUCTION LINE

SECONDARY CHILLED WATER

RETURN

SECONDARY CHILLED WATER

SUPPLY

SECONDARY HOT WATER RETURN

SECONDARY HOT WATER SUPPLY

VENT

GLYCOL SUPPLY

GLYCOL RETURN

DUAL TEMPERATURE RETURN (TWO

PIPE HEATING/COOLING SUPPLY)

DUAL TEMPERATURE SUPPLY (TWO

PIPE HEATING/COOLING RETURN)

ABBREVIATIONS

PIPING SYSTEM ABBREVIATIONSA

ABV ABOVE

AFF ABOVE FINISHED FLOOR

ACC AIR COOLED CONDENSER

AD ACCESS DOOR

AP ACCESS PANEL

ACT ACOUSTICAL CEILING TILE

ADDM ADDENDUM

ADDL ADDITIONAL

ADJ ADJUSTABLE; ADJACENT; ADJOINING

A/C AIR CONDITIONING

ACCU AIR COOLED CONDENSING UNIT

AFMS AIRFLOW MEASURING STATION

AF AIR FOIL

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

AV AIR VENT

ALM ALARM

ALT ALTERNATE; ALTITUDE

AC ALTERNATING CURRENT

ALUM ALUMINUM

AMB AMBIENT

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATING, AND AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AMP AMPERE

ETC ET CETERA

ARCH ARCHITECT

A/E ARCHITECT/ENGINEER

ASB ASBESTOS

AI ANALOG INPUT

AI AIR INTAKE

AO ANALOG OUTPUT

ACU AIR CONDITIONING UNIT

ATM ATMOSPHERE

ATTN ATTENTION

AAV AUTOMATIC AIR VENT

ACP AUTOMATIC CONTROL PANEL

ACD AUTOMATIC CONTROL DAMPER

ACV AUTOMATIC CONTROL VALVE

AFC AUTOMATIC FREQUENCY CONTROLLER

ATFP ANTI TERRORISM FORCE PROTECTION

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AVG AVERAGE

B

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BAL BALANCE

BV BALL VALVE

BB BASEBOARD

BSMT BASEMENT

BAT BATTERY

BLW BELOW

BTW BETWEEN

BLWDN BLOWDOWN

BLR BOILER

BFBP BOILER FEED BOOSTER PUMP

BFS BOILER FEED SYSTEM

BFW BOILER FEEDWATER

BFWP BOILER FEEDWATER PUMP

BOT BOTTOM

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BHP BRAKE HORSEPOWER

BTU BRITISH THERMAL UNIT

MBTU BRITISH THERMAL UNIT (THOUSAND)

BTUH BRITISH THERMAL UNIT PER HOUR

BRZ BRONZE

BLDG BUILDING

BAS BUILDING AUTOMATION SYSTEM

BFV BUTTERFLY VALVE

C

CUH CABINET UNIT HEATER

CO2 CARBON DIOXIDE

CO CLEANOUT; CARBON MONOXIDE

CLG CEILING

C CELSIUS; CENTIGRADE

CTR CENTER; COOLING TOWER RETURN

CM CENTIMETER

CFT CHEMICAL FEEED TANK

CHW CHILLED WATER

CHWPP CHILLED WATER PRIMARY PUMP

CHWP CHILLED WATER PUMP

CHWR CHILLED WATER RETURN

CHWSP CHILLED WATER SECONDARY PUMP

CHWS CHILLED WATER SUPPLY

CH CHILLER

CLASS CLASSIFICATION

CW CLOCKWISE

COEFF COEFFICIENT

COP COEFFICIENT OF PERFORMANCE (HEATING)

CLR COLOR; CLEAR; CLEARENCE

COL COLUMN

COMM COMMUNICATION

F (CONTINUED)

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FD FIRE DAMPER; FLOOR DRAIN

FP FIRE PROTECTION

FLMB FLAMMABLE

FOB FLAT ON BOTTOM

FOT FLAT ON TOP; FUEL OIL STORAGE TANK

FLEX FLEXIBLE

FLR FLOOR

FM FLOWMETER; FACTORY MUTUAL

FS FLOW SWITCH

FT FOOT; FEET

FT/LB FOOT/POUND

FT/LBF FOOT/POUND FORCE

FSTAT FREEZESTAT

FO FUEL OIL

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOF FUEL OIL FILL

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FLA FULL LOAD AMPS

F

FA FACE AREA; FIRE ALARM; FRESH AIR

FV FACE VELOCITY

F FAHRENHEIT

FCU FAN COIL UNIT

FTU FAN POWERED TERMINAL UNIT

FF FINAL FILTER

FDW FEED WATER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FRP FIBER REINFORCED POLYESTER;

FIBERGLASS REINFORCED PLASTIC

FIG FIGURE

FLTR FILTER

FTR FINNED TUBE RADIATION

FPI FINS PER INCH

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FD FIRE DAMPER; FLOOR DRAIN

FP FIRE PROTECTION

FLMB FLAMMABLE

FOB FLAT ON BOTTOM

FOT FLAT ON TOP; FUEL OIL STORAGE TANK

FLEX FLEXIBLE

FLR FLOOR

FM FLOWMETER; FACTORY MUTUAL

FS FLOW SWITCH

FT FOOT; FEET

FT/LB FOOT/POUND

FT/LBF FOOT/POUND FORCE

FSTAT FREEZESTAT

FO FUEL OIL

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOF FUEL OIL RETURN LINE

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FLA FULL LOAD AMPS

G

GA GAGE

GAL GALLON

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPS GALLONS PER SECOND

GALV GALVANIZED

GEN GENERAL; GENERATOR

GC GENERAL CONTRACTOR

GE GENERAL EXHAUST

GLV GLOBE VALVE

GRV GRAVITY ROOF VENTILATOR; GROOVE

GV GRAVITY VENT; GASOLINE VENT

GND GROUND

GMP GUARANTEED MAXIMUM PRICE

GYP GYPSUM

H

HOA HAND-OFF-AUTOMATIC

HD HAND DAMPER; HEAD

HC HEATING COIL

H HIGH; HUMIDITY

HX HEAT EXCHANGER

HG HEAT GAIN; MERCURY

HP HEAT PUMP; HIGH PRESSURE; HORSEPOWER

HT HEAT TRANSFER

Q HEAT TRANSFER; RATE OF FLOW

U HEAT TRANSFER COEFFICIEN

HTG HEATING

HVAC HEATING, VENTILATING, AND AIR

CONDITIONING

HT HEIGHT

HZ HERTZ

H (CONTINUED)

HDPE HIGH DENSITY POLYETHYLENE

HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)

HPR HIGH PRESSURE RETURN

HPS HIGH PRESSURE STEAM

HTHW HIGH TEMPERATURE HOT WATER

HR HOUR

HB HOSE BIBB

HW HOT WATER

HWP HOT WATER PUMP

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HWT HOT WATER TANK

HSTAT HUMIDISTAT

I

ID IDENTIFICATION; INSIDE DIAMETER; INSIDE

DIMENSION

ID NO IDENTIFICATION NUMBER

IN WC INCHES, WATER COLUMN

IAQ INDOOR AIR QUALITY

IA INDUCTION AIR

IB INDUCTION AIR BOX

IAU INDUCTION NAIR UNIT

INFO INFORMATION

INFO INFORMATION

IR INFRARED; INSIDE RADIUS

I/O INPUT/OUTPUT

INSUL INSULATION

IBC INTERNATIONAL BUILDING CODE

INV EL INVERT ELEVATION

K

KPA KILPASCAL

KVA KILOVOLT AMPERE

KW KILOWATT

KWH KILOWATT HOUR

L

LAB LABORATORY

LFU LAMINAR FLOW UNIT

LH LATENT HEAT; LEFT HAND

LAT LEAVING AIR TEMPERATURE

LDB LEAVING DRY BULB TEMPERATURE

LWB LEAVING WET BULB TEMPERATURE

LWT LEAVING WATER TEMPERATURE

LF LINEAR FEET (FOOT)

L LENGTH; LITER

LRA LOCKED ROTOR AMPS

LVR LOUVER

LVDR LOUVER DOOR

LVD LOUVERED

LP LOW PRESSURE (MECHANICAL)

LPCR LOW PRESSURE CONDENSATE RETURN

LPR LOW PRESSURE RETURN

LPS LOW PRESSURE STEAM

LTHW LOW TEMPERATURE HOT WATER

M

MCB MAIN CIRCUIT BREAKER

MAU MAKE UP AIR UNIT

MAV MANUAL AIR VENT

MVD MANUAL VOLUME DAMPER

MFR MANUFACTURER; MASS FLOW RATE

MAX MAXIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MECH MECHANICAL

MED MEDIUM; MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MPCR MEDIUM PRESSURE CONDENSATE RETURN

MPR MEDIUM PRESSURE RETURN

MPS MEDIUM PRESSURE STEAM

MTG MEETING; MOUNTING

MTL METAL

M METER

M/S METERS PER…