Attachment 1_FAKZ189019 B3 Drawings.pdf

PDF 40 MB Posted

Attached to
187 FW F35 Simulator & Base Supply New Construction Federal contract opportunity
Solicitation number
W50S6N-22-B-0001
Issued by
Department of the Army Alabama Army National Guard

About this file

This document provides details for a federal solicitation seeking construction services. The Alabama National Guard intends to award a firm fixed-price contract between $10 million and $25 million to construct a new 19,000 square foot Simulator Facility and 39,000 square foot Base Supply complex in accordance with specifications and drawings dated March 2021. Interested vendors must attend a mandatory pre-bid conference on October 26, 2021 to receive briefing on bid requirements and have questions answered. A site visit will follow. Vendors should submit an entry authorization list by October 21, 2021 and download all attachments before the pre-bid conference. This is a 100% small business set-aside with a size standard of $39.5 million. The North American Industry Classification System code for this project is 236220.

View the file

Other files for this federal contract opportunity

Other files attached to 187 FW F35 Simulator & Base Supply New Construction, newest first.
File Type Posted
W50S6N-22-B-0001-0002.pdf PDF
W50S6N-22-B-0001-0001.pdf PDF
W50S6N-22-B-0001-0003.pdf PDF
ADDENDUM 003 - FAKZ999088 and FAKZ189019.pdf PDF
W50S6N-22-B-0002-0002.pdf PDF
ADDENDUM 2 FAKZ999088 and 189019 SIGNED.pdf PDF
RFI RESPONSES 001 FAKZ999088 and 189019 REVISED SIGNED.pdf PDF
W50S6N-22-B-0002-0001.pdf PDF
FAKZ999088 - FAKZ189019 Addendum Number 1.pdf PDF
Pre Bid Attendance Roster.pdf PDF
Pre Bid Slides_SIMSUPPLY.pdf PDF
Attachment 4_FAKZ189019 Specs VOL 1.pdf PDF
Attachment 6_FAKZ999088 SPECS VOL 1.pdf PDF
J and A for Brand Name-Sole Source - Advantor_Redacted.pdf PDF
Entry Auth List.pdf PDF
W50S6N-22-B-0001 Solicitation.pdf PDF
Attachment 5_FAKZ189019 Specs VOL 2.pdf PDF
J and A for Brand Name-Sole Source - Monaco_Redacted.pdf PDF
Justification and Approval for Brand Name-Sole Source - Pavers_Redacted.pdf PDF
Attachment 2_FAKZ999088 B3 Drawings.pdf PDF
Attachment 3_Consolidated General Specs.pdf PDF
J and A for Brand Name-Sole Source - Stanley Best Locks_Redacted.pdf PDF
Attachment 7_FAKZ999088 SPECS VOL 2.pdf PDF
J and A for Brand Name-Sole Source - Johnson Controls_Redacted.pdf PDF
J and A for Brand Name-Sole Source - Krieger_Redacted.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

T1.0

TITLE SHEET

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

187th Fighter Wing Dannelly Field - AL ANG Montgomery, AL

FAKZ 189019

Approvals:

Title: Signature: Date:

Base Commander

Base Civil Engineer

Base Project Engineer

Bio Environmental Eng.

Safety

Security Police

Base Communications

Fire Chief

Architect:

Design Team:

Option #3

Schedule of Bid Options:

Interior Upgrades

Option #2

Additional Extent of Access Flooring

Option #1

Tiered Auditorium Seating

Option #4

Exterior Concourse UpgradesOption #5

Underslab Vapor Barrier

Plumbing, Mechanical, & Fire Protection:

Consulting Engineers:

Electrical:

Structural:

Civil:

F-35 Flight Simulator Facility

Rev. Description Date

Option #6

Spray Foam Insulation

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

T2.0

GENERAL WORK

NOTES,

ABBREVIATIONS &

SYMBOLS

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

General Project Notes:

GENERAL NOTES APPLY TO THE ENTIRE PROJECT. SPECIFIC NOTES APPLY TO ISOLATED WORK AREAS AND ARE FOR THE CONVENIENCE OF THE CONTRACTOR. HOWEVER, ALL ISOLATED WORK AREAS ARE NOT NOTED.

SHOULD A CONDITION OCCUR THAT IS NOT SPECIFICALLY NOTED, THE CONTRACTOR SHALL PROCEED WITH WORK PER GENERAL DEMOLITION NOTES OR A SPECIFIC WORK NOTE(S) USED IN OTHER SIMILAR

CONDITIONS, WHICHEVER IS MORE STRINGENT, PER APPROVAL OF ARCHITECT.

CONTRACTOR'S REPONSIBILITY TO COORDINATE THE WORK

1. CONTRACTOR TO VERIFY LOCATIONS OF ALL UTILITIES PRIOR TO COMMENCING. FURNISH

INFORMATION NECESSARY TO ADJUST, MOVE OR RELOCATE EXISTING STRUCTURES, UTILITY POLES, LINES, SERVICES OF OTHER SYSTEMS LOCATED IN, OR AFFECTED BY CONSTRUCTION. COORDINATE

WITH LOCAL AUTHORITIES HAVING JURISDICTION WITH CONSTRUCTION.

2. CONTRACTOR TO VERIFY APPLICABLE OPENINGS, DOOR SIZES, AND DIMENSIONS OF MECHANICAL

ROOMS WITH EQUIPMENT. IF DISCREPANCY OCCURS, NOTIFY ARCHITECT PRIOR TO FRAMING.

3. CONTRACTOR TO COORDINATE PLUMBING AND MECHANICAL LINES WITH CEILING HEIGHTS, ABOVE

CEILING AREAS AND STRUCTURAL ELEMENTS.

4. CONTRACTOR TO VERIFY WITH STRUCTURAL, PLUMBING, MECHANICAL, AND ELECTRICAL THE QUANTITY AND SIZES OF ALL SLEEVES REQUIRED. ALL SLEEVES TO BE ONE HOUR RATED, PROVIDE GREATER

RATING IF PENETRATING INTO HIGHER RATED SPACE.

5. CONTRACTOR TO COORDINATE PLUMBING, MECHANICAL, FIRE SPRINKLER, ELECTRICAL, AND LIGHTING WITH STRUCTURAL ELEMENTS WHERE THERE IS EXPOSED STRUCTURE. CONDUIT LINES, ECT. SHALL RUN AT RIGHT ANGLES OR SEGMENTED BETWEEN COLUMN LINES AND BE CLEAN AND NEAT IN APPEARANCE.

6. COORDINATE LOCATION OF SWITCHES, OUTLETS, THERMOSTATS, LIGHTS, ETC. W/ SHELVING, TRIM, MARKER BOARDS, AND CABINETRY. MOVE AS REQUIRED TO MISS SHELVING, STORAGE, CASEWORK, VISUAL DISPLAY BOARDS.

7. COORDINATE CONDUIT, PIPING, AND DUCTWORK SO THAT HEAD HEIGHT IS NOT ENCUMBERED AND SERVICES ARE AS TIGHT UP TO STRUCTURE AS POSSIBLE, THIS WILL INCLUDE JOGGING DUCTS, SPRINKLER LINES, PLUMBING LINES, CONDUIT, ECT. UP AND DOWN OR AROUND AS REQUIRED TO

ACHIEVE CEILING HEIGHTS AS INDICATED. COORDINATE INSTALLATION AND SEQUENCING OF

DISCIPLINES TO ACHIEVE.

8. THE GENERAL CONTRACTOR SHALL STAKE OUT ALL MAJOR FEATURES SHOWN ON THE SITE PLAN TO VERIFY THE SITE LAYOUT RELATIVE TO THE PROPERTY LINES AND SITE CONDITIONS PRIOR TO ANY

UTILITIES OR FOOTINGS BEING INSTALLED.

9. COORDINATE FINAL CEILING HEIGHT WITH ALL WINDOWS. ALL TRADES SHOULD BE ABLE TO FIT WITHIN THE ALLOTTED SPACE IF COORDINATED BY THE GENERAL CONTRACTOR AND EACH TRADE. IF FURR DOWNS ARE REQUIRED TO ACCOMMODATE ABOVE CEILING ITEMS, THE CONTRACTOR IS RESPONSIBLE

TO PROVIDE FURR DOWNS AND COORDINATE LOCATIONS WITH THE ARCHITECT.

10. PLUMBING, FIRE-PROTECTION, MECHANICAL, AND ELECTRICAL WORK REQUIRED BY THIS CONTRACT IS

NOTED ON CONTRACT DOCUMENTS. THE TRADE CONTRACTORS SHALL BE RESPONSIBLE FOR

COORDINATION OF THEIR WORK WITH ALL TRADES. CHANGE ORDERS SHALL NOT BE APPROVED FOR

EXTRA WORK ARISING FROM TRADE CONTRACTORS NOT COORDINATING WORK.

11. CONTRACTOR WILL BE RESPONSIBLE FOR ALL LAYOUT FOR INTERIOR/EXTERIOR WALLS AND FOUNDATION AND WILL BE RESPONSIBLE FOR MAINTAINING A BENCHMARK AND CONTROL LINES AT EACH FLOOR LEVEL. CONTRACTOR IS ALSO RESPONSIBLE FOR VERIFYING ACTUAL FLOOR HEIGHTS AND

COORDINATING NEW AND EXISTING FLOORS TO ALIGN.

12. EACH TRADE CONTRACTOR WILL BE RESPONSIBLE FOR FURNISHING AND INSTALLING CEILING OR WALL-

MOUNTED ACCESS DOORS AS REQUIRED TO ACCESS COMPONENTS OF ITS SYSTEM AND TO

COORDINATE WITH OTHER TRADES SO ACCESS IS MAINTAINED

13. CONTRACTOR SHALL COORDINATE TO ASSURE ALL EQUIPMENT CAN BE BROUGHT INTO THE BUILDING.

THIS INCLUDES MANUFACTURE COMPONENT SIZE/ASSEMBLY, CRITICAL PATH SCHEDULING, AND

COORDINATION OF OTHER TRADES.

ACT Acoustical Ceiling Tile A/C Air Conditioning AB Anchor Bolt ADA American Disabilities Act AFF Above Finish Floor BM Beam BRG Bearing BRK Brick CFCI Contractor Furnished

Contractor Installed CIP Cast In Place CJ Control Joint CL Column Line CLG Ceiling CLR Clear CMU Concrete Masonry Unit COL Column CONC Concrete CONT Continuous CONTR Contractor COORDF Coordination CORR Corridor CT Ceramic Tile CTR Center DBL Double DET Detail DIA Diameter DR Drain DN Down DS Downspout DW Dishwasher DWG Drawing DWR Drawer EA Each EF Exhaust Fan EJ Expansion Joint EL Elevation ELEC Electrical EQ Equal EX Existing EXT Exterior FF Finish Floor FIN Finish FL Floor Line FlSNG Flashing FTG Footing GA Gauge GFRC Glass Fiber Reinforced

Concrete

GWB GWB

HT Height HM Hollow Metal HOR Horizontal

HR Handrail HTR Heater HVAC Heating, Ventilation & Air

Conditioning HxWxL Height, width, length IN Inches INSUL Insulation INT Interior JST Joist JT Joint LAM Laminate LAV Lavatory LVR Louver MIN Minimum MAX Maximum MECH Mechanical MET Metal MFR Manufacturer MH Man Hole MIN Minimum MISC Miscellaneous MLDG Moulding MO Masonry Opening MTD Mounted MW Microwave NIC Not In Contract NO Number NOM Nominal NTS Not to Scale OC On Center OFCI Owner Furnished

Contractor Installed OFOI Owner Furnished

Owner Installed OPP Opposite P Paint PL Plate / Property Line PL LAM Plastic Laminate PLYWD Plywood PNL Panel PT Pressure Treated R Radius / Riser RB Rubber Base REFR Refrigerator REINF Reinforce (D) REV Revised RM Room SCHED Schedule SECT Section SHT Sheet SHW Single Hung Window SIM Similar

Typical Abbreviation Legend:General Project Notes (Continued):

CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY CONDITIONS

1. CONTRACTOR TO VISIT SITE AND TO BECOME TOTALLY FAMILIAR WITH EXTENT OF WORK REQUIRED PRIOR

TO BID.

2. CONTRACTOR TO VERIFY DIMENSIONS OF INTERIOR PARTITION WALLS. IF DISCREPANCY OCCURS, NOTIFY ARCHITECT PRIOR TO FRAMING.

3. CONTRACTOR TO VERIFY ALL FINISHED DIMENSIONS BEFORE INSTALLATION OF CABINET WORK AND

TRIMWORK.

4. DIMENSIONS OF EXISTING STRUCTURES ARE ONLY FOR THE CONVENIENCE OF THE CONTRACTOR, VERIFY

ALL EXISTING CONDITIONS. LOCATION OF WALLS SHALL BE AS SHOWN ON PLAN RELATIVE TO EXISTING

CONDITIONS.

5. CONTRACTOR TO VERIFY ALL DIMENSIONS AND FIELD CONDITIONS WITH THE DRAWINGS, IN PARTICULAR:

WALL DIMENSIONS, INCOMING UTILITIES, ETC. REPORT IMMEDIATELY TO THE ARCHITECT ANY VARIANCES OR FIELD CONDITIONS THAT MAY CAUSE CONSTRUCTION PROBLEMS PRIOR TO COMMENCING WORK.

CONTRACTOR'S RESPONSIBILTY TO COMPLY WITH APPLICABLE GOVERNING CODES/AUTHORITIES:

1. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES, LAWS, AND ORDINANCES. EACH

TRADE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL PERMITS, INSPECTIONS, AND CERTIFICATES

REQUIRED BY GOVERNING ENTITIES.

2. CONTRACTOR TO CONFIRM ALL OSHA AND APPLICABLE STANDARDS TO ASSURE SAFETY OF ALL

PERSONS ON SITE DURING ENTIRE COURSE OF CONSTRUCTION.

3. NEITHER THE ARCHITECT, NOR THE OWNER SHALL BE RESPONSIBLE FOR JOB SAFETY. EACH TRADE CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SITE SAFETY AND SAFETY OF THE PUBLIC DURING CONSTRUCTION AND SHALL PROVIDE APPROPRIATE WARNINGS, BARRICADES, ETC. AS REQUIRED PER

CODES.

4. PROMPTLY NOTIFY THE ARCHITECT IN WRITING IF ANY CONTRACT DOCUMENTS ARE FOUND TO BE IN VARIANCE WITH THE APPLICABLE LAWS AND ORDINANCES. NECESSARY CHANGES WILL BE MADE BY

APPROPRIATE MODIFICATIONS.

5. IF ANY WORK IS PERFORMED KNOWING IT TO BE CONTRARY TO SUCH CODES, LAWS, ORDINANCES, RULES AND REGULATIONS, AND WITHOUT NOTICE TO THE ARCHITECT, THAT TRADE CONTRACTOR ASSUMES FULL RESPONSIBILITY AND BEARS COSTS ATTRIBUTED TO BRING WORK TO COMPLIANCE OF

SUCH CODES, LAWS, ORDINANCES, AND RULES AND REGULATIONS.

GENERAL PROVISIONS FOR FIRE RATED CONSTRUCTION

1. ALL RECESSED ACCESSORIES LOCATED IN FIRE RATED WALLS SHALL BE EITHER OF FIRE RATED

CONSTRUCTION OR COORDINATED WITH THE ADJACENT TRADES TO ALLOW THE GYPSUM BOARD TO BE

CONTINUOUS BEHIND THE ACCESSORIES.

2. EACH RESPONSIBLE CONTRACTOR SHALL SEAL ALL PENETRATIONS MADE AS PART OF THEIR WORK IN FIRE-RATED CONSTRUCTION AS REQUIRED BY ALL APPLICABLE CODES. EACH CONTRACTOR TO VERIFY WITH LOCAL FIRE MARSHAL OR BUILDING OFFICIAL HAVING JURISDICTION. EACH RESPONSIBLE CONTRACTOR WILL SEAL ALL PENETRATIONS MADE AS PART OF THEIR WORK THROUGH NON-RATED

PARTITIONS. ALL FIRE CAULK TO BE THE SAME BRAND AS DETERMINED BY CONTRACTOR.

3. ALL NEW AND EXISTING FIRE WALLS IN WORK AREAS ARE TO BE CARRIED TO THE UNDERSIDE OF THE

ROOF DECK AND SEALED AS REQUIRED FOR NECESSARY FIRE RATINGS, AND LABELED PER THE

AUTHORITY HAVING JURISDICTION.

4. MATERIALS WITHIN PLENUMS. EXCEPT AS REQUIRED BY THE 2009 INTERNATIONAL MECHANICAL CODE SECTION 602.2.1.1 THROUGH 602.2.1.6, MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPEAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT

MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.

MISCELLANEOUS GENERAL PROVISIONS:

1. CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF THERE ARE ANY DISCREPANCIES WITH TAGGED

DETAILS, ENLARGED PLANS, ELEVATIONS, ETC.

2. IN ROOMS WITH FLOOR DRAINS, SLOPE TO DRAIN AT 1 PERCENT SLOPE UNLESS SPECIFICALLY NOTED

OTHERWISE.

DRAWING INDEX

SHEET

NO. SHEET NAME

T-302 TELECOM SINGLE LINE

DIAGRAMS

T-401 TELECOM ENLARGED PLANS

T-402 TELECOM ENLARGED PLANS

T-501 RACK ELEVATIONS

10.1 ELECTRICAL SECURITY

TY-001 SECURITY LEGEND

TY-111 SECURITY FIRST FLOOR PLAN

TY-201 SECURITY DETAILS

TY-202 SECURITY DETAILS

TY-301 SECURITY SINGLE LINE

DIAGRAMS

11 FIRE ALARM

FA001 FIRE ALARM/MASS NOTIFICATION

SYSTEM GENERAL NOTES AND

LEGEND

FA002 FA_MNS RISER

FA003 FA_MNS MATRIX

FA100 FIRE ALARM AND MASS

NOTIFICATION SYSTEM PLAN

FA101 MEZZANINE LEVEL FIRE ALARM

AND MASS NOTIFICATION

SYSTEM PLAN

DRAWING INDEX

SHEET

NO. SHEET NAME

E204 BLUE LIGHT PLAN

E300 LIGHTNING PROTECTION PLAN

E301 LIGHTNING PROTECTION DETAILS

A

E302 LIGHTNING PROTECTION DETAILS

B

E303 GROUNDING PLAN

E600 PANEL SCHEDULES

E601 PANEL SCHEDULES

E602 PANEL SCHEDULES

E603 PANEL SCHEDULES

E604 PANEL SCHEDULES

E-605 PANEL SCHEDULES

10 TELECOM

T-001 TELECOM LEGEND

T-002 TELECOM NOTES

T-003 TELECOM SITE NOTES

T-101 TELECOM SITE

T-102 TELECOM SITE DETAILS

T-111 TELECOM FIRST FLOOR PLAN

T-112 TELECOM PATHWAYS PLAN

T-201 TELECOM DETAILS

T-202 TELECOM DETAILS

T-203 TELECOM DETAILS

T-204 TELECOM DETAILS

T-301 TELECOM SINGLE LINE

DIAGRAMS

DRAWING INDEX

SHEET

NO. SHEET NAME

M-503 HVAC DETAILS -3

M-601 HVAC SCHEDULE-1

M-602 HVAC SCHEDULE-2

M-603 HVAC SCHEDULES-3

M-604 CHILLED WATER PIPING

DIAGRAM-PRIMARY LOOP

M-605 CHILLED WATER PIPING

DIAGRAM-SECONDARY LOOP

M-701 HVAC CONTROLS-1

M-702 HVAC CONTROLS-2

09 ELECTRICAL

E001 ELECTRICAL LEGEND AND

GENERAL NOTES

E002 POWER RISER DIAGRAM

E100 ELECTRICAL POWER PLAN

E101 BRIEF / DEBRIEF ROOM

CALLOUTS

E102 MECHANICAL POWER PLAN

E103 MEZZANINE LEVEL PLAN

E104 ELECTRICAL SITE PLAN

E105 EQUIPMENT SCHEDULE

E200 LIGHTING PLAN

E201 LIGHTING FIXTURE MOUNTING

DETAILS

E202 LIGHTING FIXTURE DETAILS AND

SCHEDULES

E203 LIGHTING FIXTURE DETAILS

DRAWING INDEX

SHEET

NO. SHEET NAME

P-601 PLUMBING SCHEDULES

P-901 PLUMBING WASTE RISER

DIAGRAM

P-902 PLUMBING WATER RISER

DIAGRAM

P-903 PLUMBING REVERSE OSMOSIS

WATER RISER DIAGRAM

08 MECHANICAL

M-001 HVAC LEGENDS & GENERAL

NOTES

M-101 OVERALL FIRST FLOOR - HVAC

PLAN

M-102 OVERALL FIRST FLOOR - HVAC

PIPING PLAN

M-301 HVAC SECTIONS-1

M-302 HVAC SECTIONS-2

M-303 HVAC SECTIONS-3

M-304 HVAC SECTIONS-4

M-401 HVAC PLAN - NORTH EAST

M-402 HVAC PLAN - SOUTH EAST

M-403 HVAC PLAN - NORTH WEST

M-404 HVAC PLAN - SOUTH WEST

M-405 ENLARGED MEZZANINE & MECH

RM - HVAC PLAN

M-406 HVAC DUCT LOCATION

M-501 HVAC DETAILS-1

M-502 HVAC DETAILS-2

DRAWING INDEX

SHEET

NO. SHEET NAME

FP-502 FIRE SUPPRESSION HYDRAULIC

ANALYSIS

06 STRUCTURAL

S1.0 GENERAL STRUCTURAL NOTES

S2.0 FOUNDATION PLAN

S2.0A ALTERNATE FOUNDATION PLAN

S3.0 MECH. MEZZ. FRAMING PLAN

S4.0 ROOF FRAMING PLAN

S5.0 TRUSS DIAGRAMS & NOTES &

SCHEDULES

S6.0 BRACING ELEVATIONS & DETAILS

S7.0 STRUCTURAL DETAILS

S8.0 STRUCTURAL DETAILS

S9.0 STRUCTURAL DETAILS

S10.0 STRUCTURAL DETAILS

S11.0 STRUCTURAL DETAILS

07 PLUMBING

P-001 PLUMBING GENERAL NOTES &

LEGEND

P-101 PLUMBING FLOOR PLAN - BELOW

FOUNDATION

P-102 PLUMBING FLOOR PLAN - ABOVE

FOUNDATION

P-301 PLUMBING INVERT SECTIONS

P-401 PLUMBING ENLARGED PLAN

P-501 PLUMBING DETAILS-1

P-502 PLUMBING DETAILS-2

DRAWING INDEX

SHEET

NO. SHEET NAME

A5.2 EXTERIOR WALL SECTIONS

A5.3 EXTERIOR WALL SECTIONS

A5.4 EXTERIOR WALL SECTIONS

A5.5 COVERED EXIT DETAILS

A6.1 ENLARGED FLOOR PLANS

A6.2 ENLARGED FLOOR PLANS

A6.3 ENLARGED MASS DEBRIEF

ROOM PLAN

A6.4 ENLARGED MASS DEBRIEF

ROOM SECTION AND DETAILS

A7.1 INTERIOR ELEVATIONS

A7.2 INTERIOR ELEVATIONS AND

DETAILS

A7.3 INTERIOR ELEVATIONS

A7.4 CASEWORK DETAILS

A8.1 REFLECTED CEILING PLAN

A8.2 CEILING DETAILS

A9.1 FLOOR PATTERN PLAN

A9.2 RAISED FLOORING DIAGRAM

AND DETAILS

A9.3 TYP. FINISH FLOOR TRANSITION

DETAILS

05 FIRE PROTECTION

FP-101 OVERALL FIRST FLOOR - FIRE

SUPPRESSION PLAN

FP-501 FIRE SUPPRESSION DETAILS &

SECTION

DRAWING INDEX

SHEET

NO. SHEET NAME

C9.1 SIMULATOR - SITE DETAILS

C10.1 SIMULATOR - SITE DETAILS

04 ARCHITECTURAL

A2.1 FIRST FLOOR PLAN

A2.1D DIMENSION PLAN

A2.2 MEZZANINE PLAN

A2.3 MEZZANINE DETAILS

A2.4 ROOF PLAN

A2.5 ROOF DETAILS

A2.6 ROOF DETAILS

A2.7 ROOF DETAILS

A2.8 WALL TYPE PLAN

A2.9 WALL DETAILS

A3.0 FINISH SCHEDULES

A3.1 FINISH SCHEDULE LEGEND

A3.2 DOOR SCHEDULE

A3.3 DOOR DETAILS

A3.4 OPENING SCHEDULE

A3.5 OPENING SCHEDULE

A3.6 CURTAIN WALL, STOREFRONT,

AND WINDOW SECTION DETAILS

A3.7 CURTAIN WALL, STOREFRONT,

AND WINDOW SECTION DETAILS

A3.8 CURTAIN WALL, STOREFRONT,

AND WINDOW SECTION DETAILS

A4.1 ELEVATIONS

A5.1 BUILDING SECTIONS

DRAWING INDEX

SHEET

NO. SHEET NAME

00 TITLE

T1.0 TITLE SHEET

T2.0 GENERAL WORK NOTES,

ABBREVIATIONS & SYMBOLS

T3.0 TYPICAL MOUNTING HEIGHTS &

CLEARANCES

01 LIFE SAFETY

LS1.0 LIFE SAFETY

02 LANDSCAPE

L1.0 BASE BID LANDSCAPE SITE PLAN

L1.1 LANDSCAPE SITE PLAN - BID

OPTION

L2.0 LANDSCAPE DETAILS

L2.1 LANDSCAPE SITE PLAN DETAILS

03 CIVIL

C1.1 SIMULATOR - SITE DEMOLITION

PLAN

C2.1 SIMULATOR - SITE LAYOUT PLAN

C3.1 SIMULATOR - SITE GRADING &

DRAINAGE PLAN

C4.1 SIMULATOR - SITE UTILITES PLAN

C5.1 SIMULATOR - SITE EROSION

AND SEDIMENTATION CONTROL

PLAN

C6.1 SIMULATOR - SITE DETAILS

C7.1 SIMULATOR - SITE DETAILS

C8.1 SIMULATOR - SITE DETAILS

SPECS Specifications SQ Square SS Sanitary Sewer STD Standard SVT Solid Vinyl Tile STL Steel T Tile T&G Tongue & Groove TYP Typical UNO Unless Noted

Otherwise VERT Vertical VTR Vent Thru Roof VWC Vinyl Wall Covering WD Wood WWM Welded Wire Mesh WWF Welded Wire Fabric YP Yellow Pine

Rev. Description Date

" M

A X

" M

IN

" M

A X

PAPER TOWEL DISPENSER

MIRROR

SOAP DISPENSER

ROBE HOOK

TY

P.

" M A X

" M A X

LAVATORY. PROVIDE ADA

INSULATION KIT WHEN REQUIRED

URINAL

42" MIN12" MAX

WATER CLOSET

HORIZONTAL

GRAB BAR

VERTICAL

GRAB BAR

MIN

1' - 3"

39"-41"

SHOWER ROD

HANDHEAD SHOWER

HEAD ON 60" MIN HOSE

FOLDING SEAT

" M A X

TOWEL BAR

EX

TI

N G

U S H

ER

H A N D

LE

" M

AX

T

O

" M A X

TO

S

PO

U T

FIRE

EXTINGUISHER

CABINET

" M A X6

" M

IN

ADA ELECTRIC

WATER

COOLER

DIRECTION INDICATOR

HALL CALL

CONTROLS

ELEVATOR DOOR

*PROVIDED FOR MOUNTING HEIGHT INFORMATION ONLY. FIXTURES SHOWN ARE NOT NECCESSARILY INCLUDED IN PROJECT*

ALLOWABLE

MOUNTING

AREA

54" MIN

TOILET

PAPER

DISPENSER

SANITARY

NAPKIN

DISPOSAL

7"-9"

36" MAX

MIN

42" MAX

" M A X

" M

IN

CL

18"

SHOWER

CONTROLS

" M

IN

" M A X

15" MAX

SIDE

WALL

BACK

WALL

CL

C.L. OF SEAT ON

OPPOSITE WALL

" M

IN

" M

IN

" M

IN

18" MIN

(A)

FRONT APPROACH, PULL SIDE

" M

IN

(B)

FRONT APPROACH, PUSH SIDE

" M

IN12" MIN

(C)

FRONT APPROACH, PUSH SIDE, DOOR

PROVIDED WITH BOTH CLOSER AND LATCH

36" MIN 6

" M

IN

(D)

HINGE APPROACH, PULL SIDE

42" MIN

" M

IN

(E)

HINGE APPROACH, PULL SIDE

" M

IN

22" MIN

(F)

HINGE APPROACH, PUSH SIDE

(G)

HINGE APPROACH, PUSH SIDE, DOOR

PROVIDED WITH BOTH CLOSER AND LATCH

" M

IN

22" MIN

24" MIN

" M

IN

(H)

LATCH APPROACH, PULL SIDE

(I)

LATCH APPROACH, PULL SIDE,

DOOR PROVIDED WITH CLOSER

" M

IN 24" MIN

24" MIN

" M

IN

(J)

LATCH APPROACH, PUSH SIDE

(K)

LATCH APPROACH, PUSH SIDE,

DOOR PROVIDED WITH CLOSER

24" MIN

" M

IN

" M

IN

12" MIN

(C)

PUSH SIDE, DOOR PROVIDED WITH

BOTH CLOSER AND LATCH

X > 8"4

" M

IN

(B)

PUSH SIDE

" M

IN

18" MIN

X > 8"

(A)

PULL SIDE

24" MIN

" M

IN

(D)

STOP OR LATCH APPROACH

22 MIN

m in

(C)

POCKET OR HINGE APPROACH

(B)

SIDE APPROACH

M

IN

m in

(A)

FRONT APPROACH

202A

A101

1Ref

Re f

1 Ref

Re f

A101

Ref

1Re f

1 Re f

Ref

ROOM NAME

150 SF

1t

1i

A101

SIM

A101

SIM

A101

SIM

Building Elevation Tag

Interior Elevation Tag

Building Section Tag

Wall Section Tag

Detail Tag

General Symbol Legend

Room Tag

ADA Approved Turning Space

Spot Elevation

Door Tag (See Door Schedule)

Window Tag (See Window Schedule)

Wall/Storefront Tag (See Wall/Storefront Schedule)

Revision Tag (See Revision Schedule)

X Specific Note Tag

Electric Water Cooler (See Plumbing)

Fire Extinguisher Cabinet

How do we tag these in a legend so they will look the same as on a plan???

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

T3.0

TYPICAL

MOUNTING

HEIGHTS &

CLEARANCES

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1/2" = 1'-0"T3.0

TYPICAL MOUNTING HEIGHTS

UNLESS NOTED OTHERWISE

3/8" = 1'-0"T3.0

2 ADA DOOR SWINGS

903 SF

B (CONCENTRATED)

C O

M M

O N P

AT

H

EXIT ACCESS DIAGONAL

43' - 1 5/8"

(1 /3

D

IA

G O

N A L

M

IN

IM

U M

EX

IT

A C C

ES

S D

IS

TA

N C E

/8

EXIT TRAVEL DISTANCE

161'

FEC

873 SF

B (ASSEMBLY - FIXED

SEATING)

781 SF

B (IT)

816 SF

B (IT)

102 SF

B (IT)

95 SF

B (IT)

137 SF

B (IT)

173 SF

B (IT)

401 SF

B (IT)

709 SF

B (MECHANICAL)

1371 SF

B (CONCENTRATED)

171 SF

B (STORAGE) 139 SF

B (IT)

2571 SF

B (EQUIPMENT)

1300 SF

B (EQUIPMENT)

1330 SF

B (EQUIPMENT)

1 3

LINE OF

MEZZANINE

ABOVE

3 33

1236 SF

B (CONCENTRATED)

315 SF

B (CONCENTRATED)

401 SF

B - GENERAL

459 SF

B (CONCENTRATED)

4490 SF

B - GENERAL

HANDICAP ACCESSIBLE EXIT LOCATION

EXIT TRAVEL PATH

FIRE EXTINGUISHER CABINETFEC

ELECTRIC WATER COOLER - SEE PLUMBINGEWC

EMERGENCY EXIT SIGNAGE

SYMBOLS LEGEND

BUSINESS OCCUPANCY - IT

BUSINESS OCCUPANCY - STORAGE /

MECHANICAL / EQUIPMENT

BUSINESS OCCUPANCY - ASSEMBLY

BUSINESS OCCUPANCY - GENERAL

BUSINESS OCCUPANCY - CONCENTRATED

SMOKE PARTITION

REQUIRED ONE HOUR FIRE RATED WALL

CONSTRUCTION (UL DESIGN # U419)

OPEN TO BELOW

3.

FIRE RATED WALL CONSTRUCTION TO EXTEND FROM TRUE FLOOR TO

UNDERSIDE OF MECHANICAL MEZZANINE

FIRE RATED WALL CONSTRUCTION TO EXTEND FROM TRUE FLOOR OF

MECHANICAL MEZZANINE TO UNDERSIDE OF TRUE ROOF ABOVE

SPECIFIC NOTE KEY

3 SMOKE PARTITION / FIRE RATED WALL CONSTRUCTION TO EXTEND

FROM TRUE FLOOR TO UNDERSIDE OF TRUE ROOF ABOVE. SEE PLAN

FOR LOCATION OF SMOKE PARTITION VERSUS FIRE RATED WALL

CONSTRUCTION.

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

LS1.0

LIFE SAFETY

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

3/32" = 1'-0"LS1.0

1 LIFE SAFETY PLAN

Applicable Codes:

Building Code..............UFC 1-200-01 / 2015 INTERNATIONAL

BUILDING CODE

Structural Code...........UFC 3-301-01 Plumbing Code............UFC 3-420-01 Mechanical Code.........UFC 3-401-01 Fire Code..................UFC 3-600-01 Electrical Code...........UFC 3-501-01 Energy Code..............UFC 1-200-02 Accessibility Code......2010 ADA STANDARDS Life Safety Code........UFC 3-600-01

IBC Chapter 3 and UFC 3-600-01 Occupancy & Use:

NFPA 101 Chapter 6:

• See Legend on Life Safety Plan

IBC Chapter 4 - Special Detailed Requirements:

• NOT APPLICABLE

IBC Chapter 5 - General Building Heights & Areas:

• Construction Type = II - B, SPRINKLED

• Allowable Building Height (PER TABLE 504.3)

75 FEET ABOVE GRADE PLANE

• Allowable Number of Stories Above Grade Plane (PER TABLE 504.4)

4 STORIES ABOVE GRADE PLANE

• Tabular Building Area (PER TABLE 506.2)

92,000 SQUARE FEET

• Frontage Increase Formula PER 506.3

I=(F/P -0.25)W/30 = (625/625-0.25)30/30 = 0.75

• Allowable Building Area (PER SECTION 506.2)

92,000 + (23,000*.75)=109,250 Actual Building area = 18,806 sf

• Fire Separation Requirements (Per Table 508.4)

NOT APPLICABLE

• Incidental Use Areas (PER TABLE 509) See occupancy table.

IBC Chapter 6 Types of Construction:

• Construction Type: II - B

• Fire Ratings (PER TABLE 601) as Follows (Except where noted otherwise) Primary Structural Frame.............................. 0 HOUR Bearing Walls (Interior & Exterior)...................0 HOUR Non-Bearing Walls and Paritions (Interior)........0 HOUR Floor Construction and Secondary Members...0 HOUR Roof Construction and Secondary Members....0 HOUR

• Required Fire Rating (Per Table 602)

NO FIRE SEPARATION REQUIRED, FIRE SEPARATION DISTANCE

IS GREATER THAN 10'

UFC 3-600-01(replaces IBC Chapter 9) - Fire Protection Systems:

• SECTION 9-1 - EMERGENCY VEHICLE ACCESS

1. Facility REQUIRES one means of all-weather emergency vehicle ground access in accordance with 9-1.1

2. Facility REQUIRES aerial apparatus access in accordance with 9-1.2

• SECTION 9-2 - FIRE FLOW FOR FACILITIES

1. Fire Flow for sprinkler system is provided in accordance with 9-2.1

• SECTION 9-3 - SERVICE MAINS AND LATERALS

1. Fire hydrants are provided in accordance with 9-3.5.8 A. Hydrants are spaced at 300 ft maximum

• SECTION 9-5 - FIRE PUMPS

1. A fire pump IS NOT required to meet fire protection demand

• SECTION 9-7 - AUTOMATIC SPRINKLER SYSTEMS

1. Per 9-7.2.1, an automatic sprinkler system IS required

• SECTION 9-10 - STANDPIPE SYSTEMS

1. Per 9-10, a standpipe system IS NOT required

• SECTION 9-17 - PORTABLE FIRE EXTINGUISHERS

1. Per 9-17.1, portable fire extinguishers ARE NOT required

2. Fire extinguishers are provided, see plans for locations

NFPA CHAPTER 8 and UFC 3-600-01- Fire and Smoke Protection Features:

• Maximum Exterior Wall Openings (PER IBC SECTION 705)

Fire Separation: Degree of Opening Protection: Allowable Area:

GREATER THAN 30 FT UNPROTECTED, SPRINKLERED , (UP, S) NO LIMIT

• Fire Walls (PER SECTION 706) No fire walls are present within the scope of the project

• Shaft Enclosure (PER 8.6.5) No shaft enclosure is present

• Opening Protectives (Per 8.3.4) Type of Assembly Assembly Rating Required Opening Protection (Door/Sidelite)

CORRIDOR NA NA

• Concealed Spaces (Per 8.6.11) Not Applicable

• See Legend on Life Safety Plan for Applicable UL Assemblies to be provided.

IBC Chapter 8, UFC 3-600-01, NFPA 101 - Interior Finishes:

• Finish Material Rating Requirements (Per NFPA 101)

BUSINESS (CHAPTER 38)

Exits and Exit Access Corridors

Interior Wall and Ceiling Finish - CLASS A OR B (38.3.3.2.1) Interior Floor Finish - CLASS I OR CLASS II (38.3.3.3.2)

Areas other than Exits and Exit Access Corridors Interior Wall and Ceiling Finish - CLASS A, B, OR C (38.3.3.2.2)

NFPA Chapter 7 (replaces IBC Chapter 10) - Means of Egress:

• Occupancy Load (PER TABLE 7.3.1.2):

See Occupancy Table

• Egress Capacity Sizing (PER TABLE 7.3.3.1)

See Code Calculations Table(s) See life safety plan for individual room egress analysis

• Minimum Stair Width (PER SECTION 7.3.3.1) See Code Calculations Table(s)

• Number of Means of Egress (PER SECTION 7.4.1) Total Number of Exits Required

Business Occupancy (CHAPTER 38)

GROUND FLOOR - 2 EXITS REQUIRED

Storage Occupancy (CHAPTER 42)

GROUND FLOOR - 1 EXITS REQUIRED

• Common Path of Egress Travel Distance Business Occupancy (CHAPTER 38)

100 ft per 38.2.5.3.1 Other (CHAPTER 7)

Mechanical Equipment Rooms, Boiler Rooms, and Furnace Rooms - 100 ft per 7.12.1

NFPA Chapter 7 (Continued)

• Exit Access Travel Distance

Business Occupancy (CHAPTER 38) 300 FT per 38.2.6.3 See life saftey plan for exit access travel distance

• Corridors Occupancy Type (B) requires:

NO FIRE RATING REQUIRED FOR

CORRIDOR WALLS

See life saftey Plan for locations of rated corridors

Minimum Corridor Width Business Occupancy (CHAPTER 38) 44 inches per 38.2.3.2

Dead End Corridors Business Occupancy (CHAPTER 38)

Maximum of 50 feet per 38.2.5.2.1

GROUND FLOOR PLAN CODE...

Name

Egress Calculations

Area Occupancy

Factor

Total Occupant

Load

Req. Stair Egress Width

Req. Width Other Egress Components

B (ASSEMBLY - FIXED SEATING) 873 SF 18 SF 49 14.66 9.77

B (CONCENTRATED) 4284 SF 50 SF 86 25.70 17.14

B (EQUIPMENT) 5200 SF 500 SF 11 3.12 2.08

B (IT) 2643 SF 300 SF 9 2.64 1.76

B (MECHANICAL) 709 SF 500 SF 2 0.43 0.28

B (STORAGE) 171 SF 500 SF 1 0.10 0.07

B - GENERAL 4891 SF 100 SF 49 14.67 9.78

18771 SF 207 61.32 40.88

PLUMBING FIXTURE CALCULATIONS

Name Male

Occupancy Female

Occupancy

Plumbing Fixture Calculations Water Closets

Required Lavatories Required

Drinking Fountains

Req.Men Women Male Female.

B - GENERAL 22 6 1.10 0.30 1.10 0.30 0.37

3/32" = 1'-0"LS1.0

2 MECHANICAL MEZZANINE PLAN

THIS PLAN IS FOR REFERENCE ONLY - SEE A2.1 FOR ROOM NAMES / NUMBER

PLUMBING FIXTURES HAVE BEEN CALCULATED BASED UPON UFC 3-420-01 USING THE MAXIMUM UTA

OCCUPANCY RATE OF 27 OCCUPANTS IN ACCORDANCE WITH ANGETL 15-01-00.

Rev. Description Date

NOTE 1

NOTE 1:

- OCCUPANCY LOAD OF 49

ESTABLISHED FOR ASSEMBLY

AREAS WITH FIXED SEATING

EXISTING BUILDING 1104

FAKZ999088

FAKZ162109

EXISTING TREES TO

REMAIN

F-35 SIMULATOR BUILDING

NEW BASE SUPPLY COMPLEX

COMM

BUILDING

PER

IM

ETER

R

O A D

L2.1

TYP

REMOVABLE BOLLARDS

BD

BD

BD

BD

BD

BD

BD

BD

MECHANICAL

UNIT - SEE

MECHANICAL

BD

BD

BD

BD

BD

L2.0

Sim

EXISTING

NEW PAVING - SEE CIVIL

L2.0

REMOVABLE BOLLARD STORAGE SLEEVES

L2.0

Sim

L2.1

Sim

MECHANICAL

UNITS - SEE

MECHANICAL

CHILLED WATER PIPING -

PENETRATE CONCRETE SLAB A

MINIMUM OF 3' AWAY FROM

FACADE

ORNAMENTAL

FENCE GATE

ORNAMENTAL

FENCE GATE

PROVIDE HORIZONTAL CHAIN LINK FABRIC AND FENCE POSTS

AS REQUIRED TO COVER MECHANICAL YARD. COORDINATE

HEIGHT AND POST SPACING WITH CHILLER MANUFACTURER

LEGEND

NOT IN SCOPE -

REFER TO FAKZ999088

AND FAKZ162109

AREA TO RECEIVE GRASS

SEED/SOD - REFER TO

ALTERNATES

ASPHALT- SEE CIVIL

STAMPED CONCRETE BAND-

SEE CIVIL

BRICK PAVERS- SEE CIVIL

CONCRETE PAVING- SEE CIVIL

BOLLARDS - SEE L2.0BD

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

L1.0

BASE BID

LANDSCAPE SITE

PLAN

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1" = 20'-0"L1.0

1 BASE BID SITE PLAN

EXISTING BUILDING 1104

FAKZ999088

FAKZ162109

EXISTING TREES TO

REMAIN

F-35 SIMULATOR BUILDING

NEW BASE SUPPLY COMPLEX

COMM

BUILDING

PER

IM

ETER

R

O A D

L2.1

TYP

MECHANICAL

UNITS - SEE

MECHANICAL

CHILLED WATER PIPING -

PENETRATE CONCRETE SLAB A

MINIMUM OF 3' AWAY FROM

FACADE

REMOVABLE BOLLARDS

BD

BD

BD

BD

BD

BD

BD

BD

MECHANICAL

UNIT - SEE

MECHANICAL

BD

BD

BD

BD

BD

REMOVABLE BOLLARD STORAGE SLEEVES

L2.1

L2.1

Sim

L2.1

Sim

L2.0

Sim

L2.1

Sim

EXISTING

NEW PAVING - SEE CIVIL

L2.0

L2.0

Sim

L2.1

Sim

ORNAMENTAL

FENCE GATE

ORNAMENTAL

FENCE GATE

PROVIDE HORIZONTAL CHAIN LINK FABRIC AND FENCE POSTS

AS REQUIRED TO COVER MECHANICAL YARD. COORDINATE

HEIGHT AND POST SPACING WITH CHILLER MANUFACTURER

SAUCER MAGNOLIA - TYPICAL -

SEE PLANTING SCHEDULE

LEGEND

NOT IN SCOPE -

REFER TO FAKZ999088

AND FAKZ162109

AREA TO RECEIVE GRASS

SEED/SOD - REFER TO

ALTERNATES

CONCRETE PAVERS

ASPHALT- SEE CIVIL

CONCRETE PAVING- SEE CIVIL

CONCRETE EDGE BAND- SEE CIVIL

BOLLARDS - SEE L2.0BD

SPECIFIC NOTES

1 PROVIDE CAST STONE BENCH WITH WOOD BACKLESS

SEAT - SEE ENLARGED PLAN AND SECTION

2 BENCH - EQUAL TO PARALLEL 42 BY LANDSCAPE

FORMS - 67" LEFT OR RIGHT UNIT AS REQUIRED BY

LAYOUT

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

L1.1

LANDSCAPE SITE

PLAN - BID

OPTION

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1" = 20'-0"L1.1

1 SITE PLAN - BID OPTION

REFER TO CIVIL

WIDTH VARIES

REFER TO CIVIL

VARIES

STAMPED CONCRETE BORDER CURB

S

EE

C

IV

IL

LIME-STABILIZED SUBGRADE

EXISTING SUBGRADE

ALTERNATE BASE BID

CONCRETE PAVER

BASE

EXPANSION JOINT

LIME-STABILIZED

SUBGRADE

EXISTING SUBGRADE

PAVERS (SEE SPECS)

SAND LEVELING BED

CONCRETE BORDER CURB

EXPANSION JOINT

CONCRETE PAVING

CONCRETE

24"24"

EQ EQ

1'-3"

'-1

'-0

0' -1

'-6

0'

-3

SOLID CONCRETE FILL. PROVIDE STEEL CAP. WELD ON TOP

6" DIAMETER STEEL POST SET IN CONCRETE

CONCRET

E

COMPACTED FILL

CONCRETE

SEE CIVIL

PLAN

SECTION

PAINT COLOR AS APPROVED BY ARCHITECT.

PLAN

SECTION

PAINT COLOR AS APPROVED BY ARCHITECT. PROVIDE ADDITIONAL

SLEEVES FOR BOLLARD STORAGE - SEE PLAN FOR LOCATION

EQ EQ

1'-6"

0' -1

4'

-0

0' -1

3' -0

0'

-3

PROVIDE STEEL CAP. WELD ON TOP

6" DIAMETER STEEL POST

SET IN CONCRETE

PAVING - SEE CIVIL

COMPACTED FILL

CONCRETE

REMOVABLE BOLLARD

STEEL PIPE SLEEVE

HINGE SLEEVE COVER - SEE SPECS

1. BOTANICAL AND COMMON NAMES SHALL CONFIRM WITH "HORTUS THIRD".

2. PLANTS SHALL BE ADJUSTED ON THE SITE TO AVOID CONFLICTS WITH UNDERGROUND UTILITIES, SURFACE

DRAINAGE WAYS, AND EXTERIOR LIGHTING STANDARDS. ADJUSTMENT SHALL BE APPROVED PRIOR TO

PLANTING

3. PINE BARK MULCH IN SHRUB BEDS, GROUND COVER BEDS, AND ON TREE PITS SHALL BE PINE BARK MULCH

(4") AND SHALL COVER THE AREA BETWEEN SHRUBS.

4. PLANT MIX FOR ALL PLANTINGS SHALL BE AS DETAILED IN SPECIFICATIONS.

5. PLANT MATERIALS SHALL BE NURSERY-GROWN, ROOT-PRUNED, STOCK CONFORMED TO ANSI Z.60.1

STANDARDS OF NURSERY STOCK.

6. INSPECTIONS AT PLACE OF GROWTH SHALL NOT IMPAIR THE RIGHT OF REJECTION AT SITE.

7. REMOVE ALL SOIL AND VEGETATION TO A DEPTH OF 9" IN AREAS TO RECEIVE SHRUBS OR GROUND COVERS

AND REPLACE WITH SOIL MIX.

8. DO NOT INJURE ROOT SYSTEM OF EXISTING TREES.

9. VERIFY EXACT NUMBER AND LOCATIONS OF ALL PLANTINGS WITH ARCHITECT.

10. SOD - PROVIDE AS SHOWN IN SPECIFICATIONS.

11. IF ANY EXISTING TO REMAIN PLANTINGS OR TREES ARE DISTURBED, DISTRESSED, OR DIE - CONTRACTOR TO

REPLACE BY MATCHING EXISTING PLANTS.

12. LANDSCAPER NOTE EXISTING SOIL CONDITIONS IN GEOTECHNICAL REPORT IN SPECIFICATIONS AND MAKE

SITE VISIT TO BECOME FAMILIAR WITH EXISTING SOIL CONDITIONS.

13. LANDSCAPER TO VERIFY EXISTING GRADES. CONSULT WITH ARCHITECT BEFORE INSTALLATION OF ANY TREES, SHRUBS, OR GROUND COVERS.

14. ON EXTERIOR LANDSCAPE WALLS PROVIDE A MINIMUM OF 2'-0" UNLESS NOTED OTHERWISE BELOW

FINISHED GRADE TO THE TOP OF CONCRETE FOOTINGS; WHERE NOT SHOWN ON STRUCTURAL. PRIOR TO PLACEMENT OF CONCRETE FOUNDATIONS, PROVIDE ARCHITECT AND OWNER WITH WRITTEN APPROVAL FROM THE OWNERS TESTING AGENT THAT THE SOIL MEETS THE REQUIREMENTS OF THE GEOTECHNICAL REPORT FOR APPLICABLE LOADING. UNLESS NOTED OTHERWISE, THE BEARING CAPACITY UNDER ALL LANDSCAPE

WALLS AND COLUMNS SHALL BE A MINIMUM 1,500 PSF.

LANDSCAPING NOTES:

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

L2.0

LANDSCAPE

DETAILS

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1 1/2" = 1'-0"L2.0

TYPICAL CONCRETE WALK

WITH INTERIOR BRICK

1" = 1'-0"L2.0

4 BOLLARD DETAIL

1" = 1'-0"L2.0

5 REMOVABLE BOLLARD DETAIL

PLANTING SCHEDULE

QUANTITY UNITS COMMON NAME BOTANICAL NAME CALIPER HEIGHT SPREAD

ROOTBALL

(CONTAINER) SPACING COMMENTS

6 EA SAUCER MAGNOLIA MAGNOLIA XOULANGIANA 3" 12' - 14' 4' - 5' 24" STRONG CONTROL LEADER

EQUAL TO LANDSCAPE FORMS UNIVERSE

SYSTEM BACKLESS (25" AND 71" UNITS)

CASTSTONE BENCH EQUAL TO

SOCRATES BY LANDSCAPE FORMS

PAVERS - SEE SPECS

SAND LEVELING BED

CONCRETE PAVING

BASE - SEE CIVIL

LIME-STABILIZED SUBGRADE

INSTALL 6" OF TOPSOIL, LANDSCAPE

FABRIC, AND MULCH AT ALL PLANTER

BEDS - TYPCAL

L2.1

Sim

EQUAL TO LANDSCAPE FORMS

UNIVERSE SYSTEM BACKLESS

BENCH (25" OR 71")

EQUAL TO LANDSCAPE FORMS

SOCRATES 95" CAST STONE

BENCH IN BEIGE COLOR (5 TOTAL)

INSTALL 6" OF TOPSOIL, LANDSCAPE

FABRIC, AND MULCH AT ALL PLANTER

BEDS - TYPCAL

EQUAL TO ROCKCAST SL200

STAINLESS STEEL PINS

GROUT-FILLED 8" CMU

WEEP

TERMINATION BAR AND SEALANT

MORTAR NET

METAL DRIP EDGE

12" GROUT-FILLED CMU

CAST STONE

WEEP

TERMINATION BAR AND SEALANT

MORTAR NET

METAL DRIP EDGE

GROUT FILL

FINISH GRADE - SEE CIVIL

PEJ

CONCRETE PAVING -

SEE CIVIL

SEE STRUCTURAL

BRICK

C O

O

RD

IN

AT

E W

IT

H C

H

IL

ER

M

AN

U

FA

C

TU

R

ER

EPOXY COATING

EPOXY PAINT

4" CMU

EQUAL TO ROCKCAST CO100

STAINLESS STEEL THROUGH WALL FLASHING WITH

3/4" HEMMED DRIP EDGE (BOTH SIDES) , SET IN

FULL BED OF SEALANT

0' - 0 7/8" 0' - 0 7/8"

SLOPE

CHAIN LINK FENCE POST(S) AS REQUIRED TO

SUPPORT HORIZONTAL CHAIN LINK ENCLOSURE

OF MECHANICAL YARD

TOP POST AND FENCE FABRIC AS REQUIRED

0' - 1"0' - 1"

EQ EQ

WRAP BRICK AROUND JAMBS (TYPICAL)

GATES - PROVIDE DIAGONAL BRACING AS REQUIRED

HEAVY DUTY HINGES BY GATE MANUFACTURER

SLIDE BOLT BY GATE MANUFACTURER

CANE BOLT BY GATE MANUFACTURER

RECESSED STRIKE EMBEDDED IN CONCRETE (TYPICAL)

0' - 5" 0' - 5"

SEE PLAN

L2.1

Sim

5"x5"x3/8" STEEL TUBE, FILL

WITH CONCRETE

1/2" PEJ, ALL SIDES

PAVING - SEE CIVIL

SLOPE TOP OF CONCRETE AWAY

FROM STEEL TUBE

STONE CAP INSTALL SEALANT AT ALL WALL

CAP JOINTS

WRAP BRICK AROUND JAMBS

0' - 4" 0' - 4"

SEE STRUCTURAL WHERE FOOTINGS OCCUR AT

FULL HEIGHT COLUMNS

4" FENCE SLAT

4"X4"X1/4" GATE FRAMING

" M

IN

TURNBUCKLE

14 GA. WIRE

2X4 STAKE (GRAY)

SET BALL 1/3 HIGHER

THAN EXISTING GRADE

PINE BARK MULCH

PLANT MIX

EXISTING GRADE

PLANT PIT SHALL BE

6" WIDER THAN BALL

PLANT MIX

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

L2.1

LANDSCAPE SITE

PLAN DETAILS

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1" = 1'-0"L2.1

RAISED PLANTER SECTION -

BID OPTION

1/4" = 1'-0"L2.1

ENLARGED RAISED PLANTER

PLAN

1" = 1'-0"L2.1

10 MECHANICAL SCREEN

1/2" = 1'-0"L2.1

DECORATIVE FENCE GATE

ELEVATION

1" = 1'-0"L2.1

9 DECORATIVE FENCE SECTION

1/16" = 1'-0"L2.1

TYPICAL TREE PLANTING

DETAIL1

A5.2

A5.3

1203 SF

SIM

356 SF

SERVER

182 SF

IOS

58 SF

COMM

68 SF

VEST

417 SF

B/DB

1203 SF

SIM

361 SF

SERVER

220 SF

IOS

61 SF

VEST

432 SF

B/DB

1203 SF

SIM

357 SF

SERVER

220 SF

IOS

78 SF

COMM

45 SF

VEST

798 SF

MASS B/DB

1202 SF

SIM

357 SF

SERVER

74 SF

COMM

40 SF

VEST

459 SF

B/DB

443 SF

HELMET

719 SF

REPAIRS

325 SF

PATCH PANEL

601 SF

OPEN OFFICE

(CLASSSIFIED)

156 SF

CARPET TILE

158 SF

SECURITY SUPPLY

ROOM

644 SF

MECH/ELEC

63 SF

SPRINKLER

151 286 SF

BREAK ROOM

151 SF

OFFICE

151 SF

OFFICE

60 SF

JAN

72 SF

MAN TRAP

110 SF

COMM

194 SF

WOMEN'S

283 SF

MEN'S

PR

IN

TE

RS

S U

PP

LI

ES

217 SF

IOS

639 SF

OPEN OFFICE

(UNCLASS)

TV

L O

C

KA

B

LE

LO

C

KE

R S

TV

S C H

ED

U

LE

M O

V

AB

LE

S

TC

W

AL

L

UPS UPS UPSUPS

82 SF

187TH COMM/

STRG

314 SF

CARPET TILE

273 SF

HALL

238 SF

ENTRY OVERHANG

112 SF

COMM

37 SF

A/V

A6.1

A5.2

A5.3

A9.2

A9.2

A5.3

Sim

A5.3

A5.3

A5.2

A5.4

A5.4

Sim

A5.3

Sim

A5.3

Sim

A5.3

106a

5 6

64 SF

ENTRY

831 SF

HALL

72 SF

HALL

101 SF

HALL

160 SF

HALL

112 SF

HALL

109 SF

HALL

40 SF

VEST

106b

120 121

130 124

133 127

128a

129134

135a

128c135c140c147c

128b135b

146 141

140a

139145

147a

143148B

148A 150

140b147b

151 152 108

A5.5

A7.1

A5.1

A5.1

A5.1

1 7 1

DS DS DS

DS

DS

DSDSDSDSDSDSDS

DS

DS

DS

DS

5' - 6"

OP.OP.OP.

OP.

A6.3

CHILLER - SEE

MECHANCIAL

CHILLER - SEE

MECHANCIAL

DS DS

DS

DS

DS

A5.5

Sim ___________ 3

A5.5

Sim

A2.9

A2.9

A2.9

A2.9

A2.9

A3.6

FLOOR PLAN LEGEND

NOTE: SEE A9.2 FOR EXTENTS OF ACCESS FLOORING

INTERIOR SAPF PERIMETER MEETING ICD 705, STC-50

SAPCA PERIMETER MEETING ICD 705, STC-50

EXTERIOR SAPF PERIMETER MEETING ICD 705, STC-50

SPECIFIC NOTE LEGEND

1 ACCESS LADDER - COORDINATE LOCATION WITH ALL

MECHANICAL, ELECTRICAL, AND PLUMBING FIXTURES

DOWNSPOUTDS

DOOR TAG

SECTION/DETAIL TAG

X

AX.X

CURTAIN WALL/STOREFRONT TAG

202A

1i

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.1

FIRST FLOOR PLAN

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1/8" = 1'-0"A2.1

1 FIRST FLOOR PLAN

ALL FURNITURE SHOWN ON PLAN IS NOT INCLUDED IN CONTRACT AND IS PROVIDED FOR GENERAL INFORMATION ONLY. ALL FURNITURE SHADED IN GRAY IS FURNITURE PROVIDED/INSTALLED BY LOCKHEED MARTIN AS PART OF THE FMS INSTALLATION.

1 5

5 7

BB

DD

EE

FF

AA

C C

2 6 9 1511

GG

0' - 11 1/4"22' - 11 1/2"22' - 11 1/2"22' - 11 1/2"22' - 11 1/2"23' - 3 3/4"23' - 3 3/4"22' - 7"22' - 7" 0' - 11 1/4"

2' - 6" 2' - 6"

2' - 6" 2' - 6"

3' - 1" 4' - 4"

FROM CL OF ROOM

5' - 7"

FOR CL OF ROOM'

5' - 7"

7' - 1 3/4"

1' - 11 3/4"

8' - 3 1/4" 7' - 11 1/2"

4' - 4 1/2"

8' - 3 1/4" 8' - 3 1/4"4' - 9"7' - 7 1/4"

CLEAR INTERIOR

15' - 0"

CLEAR INTERIOR

15' - 0"

1 1

6' - 10"

3' - 8" 3' - 8"

" 9

CLEAR INTERIOR

15' - 0"

CLEAR INTERIOR

15' - 0"

7' - 4"

14' - 5 1/4" 15' - 11 3/4"

1 2

6' - 10"

3' - 8" 3' - 8"

"9

CLEAR INTERIOR

15' - 0"

CLEAR INTERIOR

15' - 0"

3' - 8" 3' - 8"

6' - 10"

" 9

FROM CL OF ROOM

5' - 7"

15' - 3" 15' - 2"

2' - 6" 2' - 6"

/4

/4

/4

8' - 3 1/4"

1' - 7 1/4"

7' - 8 3/4"

/4

2' - 9 3/4"

8' - 10 3/4" 6' - 3 1/2" 4' - 11 3/4"

4' - 3 1/2"

6' - 10"

3' - 8" 3' - 8"

"9

CLEAR INTERIOR

15' - 0 3/4"

CLEAR INTERIOR

15' - 0"

FROM CL OF ROOM

5' - 7"

/2

7' - 2" 4' - 10"5' - 10 1/2"

4' - 2"

/4

/2

/2

/4

/4

/4

/4

/4

12' - 10 3/4"

/4

3' - 0"

2' - 6" 2' - 6"

14' - 7 3/4"

0' - 11 1/4"8' - 6 3/4"22' - 11 1/2"22' - 11 1/2"22' - 11 1/2"23' - 3 3/4"12' - 10 3/4"10' - 5"13' - 4 1/4"9' - 2 3/4"18' - 3"2' - 8"1' - 8"

5' - 11 1/2"10' - 7 3/4"4' - 1"4' - 8 1/2"

2' - 6"6' - 10 1/4" 0' - 8 1/4"0' - 7 1/4"

13' - 8 1/4" 1' - 3 3/4"

/4

/4

/4

/4

/4

/2

/4

/4

/4

/4

/4

/2

/4

/2

2' - 1 1/4"

0' - 4 3/4"

2' - 6" 7' - 6 1/4"3' - 10 3/4" 0' - 5 1/2" 0' - 8 1/4"3' - 4 3/4"

/2

4' - 1 3/4"

5' - 8 1/4"

2' - 6"

0' - 3 1/4"

5' - 9 3/4"

/4

1' - 2 3/4"

5' - 0 1/2" 6' - 1 1/4" 8' - 7 1/2"

2' - 0 1/4"

/4

/4

2' - 6"

7' - 10 3/4" 3' - 11 3/4"

3' - 2"

3' - 6"3' - 0"

0' - 7 3/4"

10' - 1"

/2

0' - 3 1/4"

/4

7' - 6"7' - 6"7' - 6" 7' - 6"7' - 6"7' - 6"7' - 6"7' - 6"

CENTER OF FMS DOME

CENTER OF FMS DOME

CENTER OF FMS DOME

CENTER OF FMS DOME

/4

2' - 10 3/4"

7' - 10"

/2

/4

AS REQUIRED BY MANUFACTURER

/4

0' - 9 1/4"

/2

4' - 10 1/2"

/2

/2

/2

2' - 0 1/4"

2' - 4 3/4"AS REQUIRED BY MANUFACTURER

13' - 1"

SPECIFIC NOTES:

1 SUPPLY AIR ROUGH IN LOCATION FOR FMS - SEE MECHANICAL

2 RETURN AIR ROUGH IN LOCATION FOR FMS - SEE MECHANICAL

3 SIGNAL TRENCH LOCATION - SEE STRUCTURAL

4 POWER TRENCH LOCATION - SEE STRUCTURAL

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.1D

DIMENSION PLAN

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1/8" = 1'-0"A2.1D

1 DIMENSION PLAN

GENERAL NOTES:

1. WALL DIMENSIONS ARE TAKEN FROM CENTER LINE OF EXTERIOR AND INTERIOR WALLS

A2.3

A2.3

A2.3

A8.2

1. PROVIDE 36" x 6'-8" CASED OPENING IN WALL

2. PROVIDE STC RATED DOOR ASSEMBLY - SEE DOOR SCHEDULE

3. HOLD PLYWOOD DECK +/- 6" OFF SPPF WALL - REFER TO 2/A2.3

2.

2.

4. INSPECTION PLATFORM ACCESSED BY SECURITY PERSONNEL VIA LADDER IN THIS LOCATION

4.

4.4.

16' - 0"

OPEN TO

BELOW

17' - 8 3/4"

17' - 8 3/4"

17' - 8 3/4"

17' - 8 3/4"

FROM EDGE OF MEZZ.

6' - 0"

M102

M101

3 3

17' - 8 3/4"

4 4

HOIST BEAM ABOVE - SEE STRUCTURAL

11' - 3 1/2"

A2.3

A2.3

A2.3

Sim

A2.3

Sim

5. FIXED LADDER FOR MEZZANINE ACCESS - SEE DETAIL 6/A2.3

6. FIXED LADDER FOR ROOF ACCESS - SEE DETAIL 7/A2.7

7. RAISE SHEETROCK WALL TO 23'-6" IN THIS AREA

ATU 1A

ATU 1B & BF-1 STACKED

BF-2BF-3

ATU 3A

ATU 3B

ATU 2AATU 2B

ATU 4B

ATU 4A

16' - 0"

7 7

A2.37

MEZZANINE LEGEND

PREFABRICATED CATWALK SYSTEM

FIRE RESISTANT 3/4" T & G PLYWOOD DECK

CONCRETE MEZZANINE - SEE STRUCTURAL

INDICATES SAPF PERIMETER WALLS

INDICATES SAPCA WALLS

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.2

MEZZANINE PLAN

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1/8" = 1'-0"A2.2

1 MEZZANINE PLAN

3/4" T.&G. PLYWOOD

BATT INSULATION -

COMPLETELY FILL WALL CAVITY

SAPCA PERIMETER WALL

SEAL ALL PENETRATIOSN IN

SECURE WALLS IN

ACCORDANCE WITH ICD 705

REQUIREMENTS.

12"x1 5/8" 12 GAUGE

COLD FORMED METAL

STUDS AT 12" O.C.

3 5/8" METAL STUD AND

GWB - DESIGN TO RESIST

50 LBS PER LINEAR FOOT

DISTRIBUTED LOAD AND

200 LBS CONCENTRATED

LOAD PER SECTION

1607.8 OF IBC 2015

DOOR -M102 - SEE DOOR SCHEDULE

LADDER EXTENSION ( LATCH SIDE ONLY)

24' - 2"

PREFABRICATED LADDER - SEE SPECS

TO CL

7" MIN

UNISTRUT MIDRAIL

UNISTRUT HANDRAIL

PREFABRICATED CATWALK SYSTEM VERTICAL RAILS

PREFABRICATED CATWALK SYSTEM TOP RAIL

FRAMING AS REQUIRED TO SUSPEND CATWALK SYSTEM

PRAFABIRCATED METAL STUD TRUSSES - SEE STRUCTURAL

GYPSUM WALLBOARD

METAL STUD FRAMING

GYPSUM WALLBOARD

3' - 0"

" M

A X

" M

A X

" M

IN

" M

A X

" M

IN

" M

IN

BRACE TO STRUCTURE ABOVE AS REQUIRED

ABOVE

COORD. LOCATION

WITH STRUCTURE

3 5/8" METAL STUD -

DESIGN TO RESIST 50 LBS

PER LINEAR FOOT

DISTRIBUTED LOAD AND

200 LBS CONCENTRATED

LOAD PER SECTION 1607.8

OF IBC 2015.

STEEL BEAM - SEE

STRUCTURAL (PAINT)

3/4" FIRE RESISTANT

T&G. PLYWOOD

12"x1 5/8" 12 GAUGE

COLD FORMED METAL

STUDS AT 12" O.C.

SEAL ALL PENETRATIONS IN

SECURE WALLS IN

ACCORDANCE WITH ICD 705

REQUIREMENTS

SAPF

PERIMETER

WALL

3 1/2" MINIMUM BATT

INSULATION

14' - 3 1/4"

0' - 6"

2' - 6"

SAPCA PERIMETER WALL

" M

A X

" M

A X

RIGID CORNER BEAD

BATT INSULATION -

FILL WALL CAVITY

COMPLETELY

GYPSUM WALLBOARD

METAL STUD FRAMING

METAL STUD FRAMING

LIGHT FIXTURE - SEE

ELECTRICAL

GYPSUM WALLBOARD

METAL STUD FRAMING

GYPSUM WALLBOARD

BATT INSULATION - FILL

WALL CAVITY COMPLETELY

DUCTWORK CONCEALED

IN BULKHEAD - SEE

MECHANICAL

GYPSUM WALLBOARD

GYPSUM WALLBOARD

(PAINT WITH PT-5)

SEAL ALL PENETRATIONS

IN SECURE WALL IN

ACCORDANCE WITH ICD

705 REQUIREMENTS

GYPSUM WALLBOARD

(PAINT WITH PT-5)

GYPSUM WALLBOARD

(PAINT WITH PT-3)

19' - 6" TYPICAL. RAISE TO 23'-6" WHERE NEEDED ON PLAN.

WALL TYPE A6 - EXTEND TO

ROOF DECK ABOVE

CEILING - SEE REFLECTED CEILING

PLAN

PREFABRICATED METAL STUD TRUSSES - SEE

STRUCTURAL

UNISTRUT CATWALK SYSTEM TOP RAIL

FRAMING AS REQUIRED TO SUSPEND

CATWALK BETWEEN TRUSSES

UNISTRUT CATWALK SYSTEM VERTICAL SUPPORT

UNISTRUT HANDRAIL

BRACE TO STRUCTURE ABOVE AS REQUIRED

" M

A X

" M

A X

" M

IN

3' - 0"

UNISTRUT MIDRAIL

METAL GRATING

TOE KICK - 4" TALL MIN.

UNISTRUT CATWALK SYSTEM BOTTOM RAIL

STRUCTURE ABOVE

COORD. EXACT

LOCATION W/

VARIES

VARIES

SEE MEZZANINE PLAN

SEE STRUCTURAL

SAPCA PERIMETER WALL

PROVIDE ADDITIONAL METAL STUD FRAMING AT

STRUCTURAL FRAMING EMBEDDED IN SECURE WALLS.

TWO LAYERS OF SHEETROCK MUST BE CONTINUOUS

FROM CONCRETE FLOOR TO METAL ROOF DECK. FILL

STUD FRAMING FULL OF INSULATION

STEEL BEAM - SEE STRUCTURAL

C

LE

A R

" M

AX

" M

IN

C

LE

A R

" M

AX

1-1/2" STEEL PIPE RAIL

1-1/2"" STEEL PIPE UPRIGHT @ 36" O.C.

EDGE ANGLE - SEE STRUCTURAL

STEEL PLATE (6"X6") - WELD TO EDGE ANGLE

AND TOP FLANGE OF BEAM AT FASCIA FLANGES

STEEL HANDRAIL FASCIA FLANGE - WELD TO PLATE

JOIST SEAT - SEE STRUCTURAL

BEAM - SEE STRUCTURAL

2" x 4" RAILS SPACED TO ALLOW

24" CLEAR BETWEEN RAILS

1" ROUND STEEL RUNGS -

CORRUGATED, KNURLED, OR

CRIMPED - EQUAL SPACING NOT

TO EXCEED 12" O.C. (NOT LESS

THAN 10" O.C.)

LADDER BRACKET - FASTEN AS

REQUIRED TO STRUCTURE

TOP RUNG LEVEL WITH LANDING

EXPANSION BOLT TO FLOOR AND

MEZZANINE AS REQUIRED

" M

IN

2' - 0"

BRACE AS REQUIRED

A2.3 ___________ 36" 36"

HASP FOR PAD LOCK

FLUSH BOLT - PROVIDE STEEL PLATE

FOR MOUNTING BOLT TO GATE

STEEL PLATE - WELD TO EDGE ANGLE AND

BEAM FLANGE AT EACH FASCIA PLATE

FASCIA FLANGE

STEEL PLATE AND FLUSH BOLT

RECEIVER - WELD TO EDGE ANGLE

STEEL PIPE RAILING

EDGE ANGLE - SEE STRUCTURAL

CONTINUOUS HINGE

BEAM - SEE STRUCTURAL

CENTER GATE ON HOIST BEAM ABOVE

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.3

MEZZANINE

DETAILS

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1" = 1'-0"A2.3

1 INSPECTION PLATFORM DETAIL

1" = 1'-0"A2.3

HALLWAY INSPECTION

PLATFORM

1" = 1'-0"A2.3

3 TYPICAL CATWALK DETAIL

1 1/2" = 1'-0"A2.3 4 Section 54

1" = 1'-0"A2.3

5 MEZZANINE RAILING DETAIL

3/4" = 1'-0"A2.3

6 ACCESS LADDER DETAIL

1/2" = 1'-0"A2.3

ELEVATION OF RAILING AT

GATE

4" / 1'-0"

4"

1' -0

4" / 1'-0"

4"

1' -0

4"

1' -0

4" / 1'-0"4" / 1'-0"

1/ 2"

1'

-0

1/2" / 1'-0" 1/2" / 1'-0"

A2.7

A2.6

A2.6

A2.7

A2.7

Sim

A2.6

Sim

A2.6

Sim

A2.7

Sim

A2.6

Sim

A2.6

Sim

A2.6

Sim

A2.6

Sim

A2.7

Sim

A2.7

Sim

A2.7

A2.6

Sim

A2.6 ___________ 4

A2.6

A2.5 1 Sim

1 M MIN

EQ

1 M MIN

EQ

1 M MIN

EQ

GPS GPS GPS GPS

VTR

A5.3

Sim

A5.3

A5.3

A5.3

Sim

A5.3

Sim

A5.5

Sim

A5.2

A5.4

Sim

A5.4

Sim

A5.1

Sim

A5.3

Sim

A5.3

A5.3

A5.3

Sim

A5.2

A5.1

A5.2

A5.1

Sim

DS DS DS DS DS DS DS

DS

DS

DS

DS

DS DS

DS

DS

DS

DS

DS DS DS DS DS DS

DS

1. ROUTE DOWNSPOUT ALONG LOW ROOF AND DISCHARGE TO

UNDERGROUND STORM SYSTEM AT SOUTH SIDE OF LOW ROOF.

SPECIFIC NOTES:

1. LOCATE ALL PENETRATIONS THROUGH METAL

ROOF PANELS AT MIDPOINT IN ROOF PANEL.

GENERAL NOTES:

1.

ROOF PLAN LEGEND

STANDING SEAM METAL ROOF

MEMBRANE ROOF

BUILDING OUTLINE

GPS ANTENNA SUPPORT - SEE ELECTRICAL AND DETAIL

VENT THROUGH ROOF - SEE PLUMBING AND DETAILVTR

GPS /5 A2.5

/4 A2.5

DS

DOWNSPOUT

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.4

ROOF PLAN

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1/8" = 1'-0"A2.4 1 Roof Level

NEW CLAMPING RING & SEALANT

TPO COATED METAL

PLUMBING BOOT

HEAT WELD NEW TPO MEMBRANES

IN THESE LOCATIONS

TPO MEMBRANE

COVER BOARD

VENT - SEE PLUMBING

NEW TPO

TERMINATION

C O

O R

. W

IT

H T

PO

M

AN

U

FA

C

TU

R

ER

" M

IN

RIGID INSULATION

METAL DECK2

A5.2

1/ 2"

1'

-0

1/2" / 1'-0"

MEMBRANE ROOF

DS

DS

SLOPE GUTTER ALONG TOP OF LOW ROOF.

TURN GUTTER DOWN ON SOUTH SIDE OF

LOW ROOF - CONNECT DOWNSPOUT TO

UNDERGROUND STORM DRAINAGE SYSTEM.

SILICONE SEALANT AROUND CUT OF BOOT

EPDM RUBBER PIPE FLASHING

BUTYL TAPE BENEATH BASE AND

POLYURETHANE FILLET

METAL ROOF PANEL

SELF ADHERED ROOF UNDERLAYMENT

RIGID INSULATION

METAL ROOF DECK

VENT - SEE PLUMBING

INSTALL PER MANUFACTURER'S

REQUIREMENTS AND WARRANTY

REQUIREMENTS FOR ROOF SYSTEM

SILICONE SEALANT AROUND CUT OF BOOT

EPDM RUBBER PIPE FLASHING

BUTYL TAPE BENEATH BASE AND

POLYURETHANE FILLET

METAL ROOF PANEL

SELF ADHERED ROOF UNDERLAYMENT

RIGID INSULATION

METAL ROOF DECK

2" O.D. HOT-DIPPED GALVANIZED STEEL PIPE -

PAINT TO MATCH ROOF

INSTALL PER MANUFACTURER'S

REQUIREMENTS AND WARRANTY

REQUIREMENTS FOR ROOF SYSTEM

6"X6"X1/4" HOT DIPPED

GALVANIZED STEEL PLATE

WELDED TO ROOF DECK

AND PIPE. DRILL HOLE AS

REQUIRED FOR CABLE

PASS-THROUGH

HOT-DIPPED GALVANIZED STEEL PIPE CAP

(TYPICAL)- PAINT TO MATCH ROOF. OMIT WHERE

ELBOW IS PROVIDED

HOT-DIPPED GALVANIZED STEEL 180 DEGREE

ELBOW (REQUIRED AT ONE GPS PIPE )- PAINT TO

MATCH ROOF

WATERPROOF CABLE GROMET - SIZE AS REQUIRED

A S R

EQ

U

IR

ED

T

O M

O U N T

G

PS

A B O

V E

R

ID

G E

O F

R O

O F

SEAL CABLE PENETRATION

INSTALL PIPE IN CENTER OF PANEL TO

ALLOW BASE OF RUBBER ROOF BOOT

TO LAY FLAT ON PANEL

NOT TO

SCALE

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.5

ROOF DETAILS

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

1 1/2" = 1'-0"A2.5

PLUMBING VENT DETAIL

THROUGH MEMBRANE ROOF

1/8" = 1'-0"A2.5

1 LOW ROOF PLAN

1 1/2" = 1'-0"A2.5

PLUMBING ROOF VENT

THROUGH STANDING SEAM

ROOF

1 1/2" = 1'-0"A2.5

GPS ANTENNA SUPPORT

DETAIL

1 1/2" = 1'-0"A2.5

TYPICAL STANDING SEAM

ROOF PENETRATION

TRI-BEAD TAPE SEALER

DECK SCREW PER

MANUFACTURER REQ.

SELF-DRILLER W/ WASHER

@4" O.C. (MAX)

HIP FLASHING

PROVIDE WATERPROOF END

COMPONENT (TYP)

SELF ADHERED

ROOF

UNDERLAYMENT

BEARING PLATE

ZEE CLOSURE

URETHANE SEALANT

INSULATION

METAL ROOF

DECK

STANDING

SEAM METAL

ROOF PLANEL

ROOF CLIP AND

BEARING PLATE

PREFABRICATED METAL STUD

TRUSSES - SEE STRUCTURAL

INSTALL ALL ACCESSORIES AND COMPONENTS AS REQUIRED

BY MANUFACTURER TO ACHIEVE ALL SPECIFIED WARRANTIES

VALLEY TRIM

URETHANE SEALANT

(BETWEEN PANEL RIBS)

SPECIAL LOW

EAVE PLATE

PANCAKE HEAD

SELF-DRILLER

SUPPORT

PLATE

METAL ROOF

DECK

RIGID

INSULATION

TRIPLE BEAD TAPE SEALER

METAL ROOF PANEL

SELF ADHERED

ROOF

UNDERLAYMENT

INSTALL ALL ACCESSORIES AND COMPONENTS AS REQUIRED

BY MANUFACTURER TO ACHIEVE ALL SPECIFIED WARRANTIES

AS REQUIRED BY MANUFACTURER

TOS

20' - 9 1/2"

D

STANDING SEAM METAL ROOF

SELF ADHERED ROOF UNDERLAYMENT

RIGID INSULATION

ROOF DECK- SEE STRUCTURAL

METAL FLASHING ( SEAM INTO STANDING SEAM JOINT ASSEMBLY)

METAL COUNTER FLASHING

SEALANT

ROOF CLIP

JACK TRUSS - SEE STRUCTURAL

A2.7 2 Sim

GUTTER - SEE SPECS

PREFINISHED SHEET METAL FASCIA

BACKER ROD W/ SEALANT

PREFABRICATED METAL STUD TRUSSES - SEE STRUCT.

SPRAY FOAM IN WALL CAVITY

CUT SHEATHING AND SHEETROCK TO FIT ROOF DECK PROFILE. INSTALL

ACOUSTIC SEALANT BETWEEN ROOF DECK AND SHEATHING/GYPSUM.

FILL VOID ABOVE STUD TRACK WITH SPRAY FOAM INSULATION.

METAL CLOSURE TRIM

METAL SOFFIT PANELS

STEEL BEAM WITH PLATE - SEE STRUCTURAL

STANDARD BRICK

D

STANDING SEAM METAL ROOF

RIGID INSULATION

ROOF DECK- SEE STRUCTURAL

SELF ADHERED ROOF UNDERLAYMENT

RIGID INSULATION

ROOF DECK- SEE STRUCTURAL

GUTTER - SEE SPECS

PREFINISHED SHEET METAL FASCIA

PREFABRICATED METAL STUD TRUSSES - SEE

STRUCTURAL

SHEATHING

STANDING SEAM METAL ROOF

SELF ADHERED ROOF UNDERLAYMENT

METAL SOFFIT PANELS

AIR BARRIER

PREFABRICATED METAL STUD TRUSSES - SEE

STRUCTURAL

BACKER ROD W/ SEALANT

METAL CLOSURE TRIM

A2.7 2 Sim

SHEET METAL PANELS WITH FLAT SEAM JOINTS

LAP AIR BARRIER OVER SELF-ADHERED ROOF UNDERLAYMENT

CONTINUOUS CLEAT

SHEET METAL COUNTERFLASHING WITH LOCK CLEAT

SHEET METAL FLASHING - SEAM INTO ROOF PANEL

SHEATHING

Sheet Number

Sheet Title

Project Title

M on tg om er y

D ot ha n

W W

W .S

SL

A

R C

H .C

O M

(M ) 3

. 2

. 5

(D

) 3

. 7

. 5

Job Number

Date

Drawn By

Checked By

A

RC

H

IT

E

CT

U

RE

IN

TE

RI

O R

D E

SI

G

N

A2.6

ROOF DETAILS

F-

S im ul at or F ac ili ty

7T

H F

W , D

A N

N E

LL

Y

FI

E

LD

, M

O N

TG

O

M E

RY

, A

L

18049

1 NOVEMBER 2020

JLJ/NF/NJ

DCD

3" = 1'-0"A2.6 1 Section 49

3" = 1'-0"A2.6 2 Section 48

1 1/2" = 1'-0"A2.6 3 Detail 1

1 1/2" = 1'-0"A2.6 4 Detail 2

PREFABRICATED METAL STUD

TRUSSES - SEE STRUCTURAL

COVER BOARD

RIGID INSULATION

ROOF DECK- SEE STRUCTURAL

TPO ROOFING MEMBRANE

STEEL ANGLE - SEE STRUCTURAL

P.T. WOOD BLOCKING AS REQUIRED

ES-1 RATED EDGE METAL

BACKER ROD W/ SEALANT

COMPOSITE METAL WALL PANELS

CONTINUOUS INSULATION CHANNEL

RIGID INSULATION

AIR BARRIER

SHEATHING

METAL STUD FRAMING

SPRAY FOAM INSULATION

GUTTER - SEE SPECS

AIR BARRIER

ROOF DECK- SEE STRUCTURAL

RIGID INSULATION

SELF ADHERED ROOF UNDERLAYMENT

STANDING SEAM METAL ROOF

SHEET METAL CLEAT - WRAP

UNDERLAYMENT OVER ALL FASTENERS (TYP)

PREFINISHED FLASHING W/ DRIP

GUTTER STRAP

SEALANT

SELF ADHERED UNDERLAYMENT

AIR BARRIER

SHEET METAL CLEAT - WRAP AIR BARRIER

OVER ALL FASTENERS (TYP)

SPRAY FOAM INSULATION

SHEET METAL CLEAT - WRAP AIR BARRIER

OVER ALL FASTENERS (TYP)

SHEATHING

/2

STEEL EDGE PLATE - SEE STRUCTURAL

F

PREFABRICATED METAL STUD TRUSSES - SEE

STRUCTURAL

SPRAY FOAM INSULATION

SHEATHING

METAL SOFFIT PANELS

METAL CLOSURE TRIM

BACKER ROD W/ SEALANT

METAL CLOSURE TRIM

METAL WALL PANELS

CONTINUOUS INSULATION CHANNEL

RIGID INSULATION

TERMINATION BAR & SEALANT - SEE FLASHING DETAIL

METAL CLOSURE TRIM

BACKER ROD W/ SEALANT - PROVIDE TUBE WEEPS @

32" O.C.

METAL COUNTERFLASHING

TERMINATION BAR & SEALANT - SEE FLASHING DETAIL

METAL FLASHING

GYPSUM WALLBOARD

COVER BOARD

TPO BASE FLASHING WELDED TO ROOF MEMBRANE

TPO…