This package of documents includes mechanical drawings and details to expand an interventional radiology suite for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8. The drawings show the existing conditions, demolition plan, renovation plan, and mechanical details. Key details include relocating ceiling diffusers and thermostats, demolishing other diffusers and grilles, and extending ductwork and wiring as needed. Mechanical specifications cover requirements for duct installation and supports, insulation, equipment connections, testing and balancing, controls, and other aspects of the project. The federal solicitation is to expand the interventional radiology suite in support of Veterans Affairs healthcare services.
View the file
Other files for this federal contract opportunity
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL NOTES AND
LEGENDS
M-001
NEW THERMOSTAT
POINT OF NEW CONNECTION
X DRAWING NOTE
U 1" DOOR UNDERCUT
END CAP
INDICATES SUPPLY AIRFLOW
INDICATES RETURN AIRFLOW
UP DUCT UP
DN DUCT DOWN
- EQUIPMENT MARK
FIRE DAMPER
MANUAL BALANCING DAMPER
EXHAUST
RETURN OR TRANSFER
RECTANGULAR DUCT
(INSIDE DIMENSIONS: WIDTH x DEPTH)AxB
EXISTING DUCT
(INSIDE DIMENSIONS: WIDTH x DEPTH)AxB
EXISTING FLEX-DUCT
EXISTING DUCT TO BE REMOVED
EXISTING RETURN
EXISTING EXHAUST
SUPPLY
EXISTING SUPPLY
(E) EXISTING
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFM AIRFLOW MEASURING DEVICE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ATU AIR TERMINAL UNIT
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOS BOTTOM OF STRUCTURE
BTUH BRITISH THERMAL UNIT PER HOUR
CCV COOLING CONTROL VALVE
CD CEILING SUPPLY AIR DIFFUSER
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CG CEILING GRILLE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
COR CONTRACTING OFFICER'S REPRESENTATIVE
CTE CONNECT TO EXISTING
CU CONDENSING UNIT
CV CONSTANT AIR VOLUME
DD DUCT MOUNTED SMOKE DETECTOR
DIA DIAMETER
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EWT ENTERING WATER TEMPERATURE
FBC FLORIDA BUILDING CODE 2017
FCU FAN COIL UNIT
FD FIRE DAMPER
FMC FLORIDA MECHANICAL CODE 2017
FO FLAT OVAL
FPM FEET PER MINUTE
FSD COMBINATION FIRE SMOKE DAMPER
FT FEET
G GAS / GRILLE
GPM GALLONS PER MINUTE
HCV HEATING CONTROL VALVE
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HP HORSEPOWER
IBC INTERNATIONAL BUILDING CODE
IN INCH
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MBTUH 1,000 BTUH
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVERCURRENT PROTECTION
MUA MAKE UP AIR
NC NEW CONNECTION / NOISE CRITERIA
NG NATURAL GAS
OA OUTSIDE AIR
OAL OUTSIDE AIR LOUVER
OBD OPPOSED BLADE DAMPER
PTAC PACKAGED TERMINAL AIR CONDITIONING
RA RETURN AIR
RG RETURN AIR GRILLE
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SF SQUARE FEET
SR SUPPLY AIR REGISTER
TAB TEST AND BALANCE
TOD TOP OF DUCT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
WG WATER GAUGE
ABBREVIATIONS
LIMIT OF DEMOLITION
FLEX-DUCT
ROUND DUCT
(INSIDE DIMENSIONS: DIAMETER)AØ
45° BRANCH TAKE-OFF FITTING
MECHANICAL LEGEND
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE
PROVIDED (FURNISHED AND INSTALLED) UNDER THIS CONTRACT. DRAWINGS
SHOULD NOT BE SCALED.
2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER
WHICH THEY SHALL OPERATE AND VERIFY THE EXTENT OF WORK REQUIRED TO
COMPLETE THE WORK UNDER THIS CONTRACT.
3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY
OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT
SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR
INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO
DETERMINE ANY NECESSARY MODIFICATIONS.
4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND
LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY
HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING
DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.
5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE
REQUIREMENTS:
· INTERNATIONAL BUILDING CODE (IBC) 2020
· INTERNATIONAL EXISTING BUILDING CODE 2020
· IBC MECHANICAL 2020
· IBC PLUMBING 2020
· IBC ENERGY CONSERVATION 2020
· NFPA 1-2018, THE UNIFORM FIRE CODE
· NFPA 101-2018, THE LIFE SAFETY CODE
· NFPA 51B-2014, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING
AND OTHER HOT WORK
· NFPA 13-2016, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
· NFPA 70-2017, NATIONAL ELECTRICAL CODE
· NFPA 90A-2018, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND
VENTING SYSTEMS.
· NFPA 99-2018, STANDARD FOR HEALTH CARE FACILITIES
· NFPA 241-2013, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION
AND DEMOLITION OPERATIONS.
· ALL APPLICABLE VA DESIGN MANUALS
6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND
CONSTRUCTION WORK.
7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF
WORK UNDER THIS CONTRACT. DISMANTLE AND REASSEMBLE EQUIPMENT AS
NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF INSTALLATION.
8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL
UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED AND AN
UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.
9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART OF THE
TOTAL PROJECT COST.
10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,
CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES
WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L. REQUIREMENTS TO MAINTAIN
THE ASSEMBLY RATING.
11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE
AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND
SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL TIMES DURING
CONSTRUCTION.
12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.
13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS
FOR ALL PRODUCTS USED ON PROJECT.
14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE
CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF
CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN
APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION. THE ENGINEER'S
APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF
RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS OR HER SUBMITTAL DATA.
15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN
THREE RING BINDERS AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE
INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS,
CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP DRAWINGS, SPARE PARTS
DATA, ETC. PROVIDE AN INDEX AND ASSOCIATED DIVIDERS.
16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF
CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT
CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE
ALL CONTRACT CHANGES, MODIFICATIONS, AND CLARIFICATIONS. THIS SET ALONG
WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER
AFTER CONSTRUCTION COMPLETION.
17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND
UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED
TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC
IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL
REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND
SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE
OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE
TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT
AND MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN
CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.
GENERAL NOTESMECHANICAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF FIELD CONDITIONS PRIOR TO BEGINNING WORK AND ORDERING EQUIPMENT, AND FOR COORDINATING NEW EQUIPMENT DIMENSIONS AND MEANS AND METHODS FOR
INSTALLATION WITH FIELD CONDITIONS.
2. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH SUBMITTED EQUIPMENT TO ENSURE ALL INLET/OUTLET CONNECTIONS COORDINATE WITH FIELD INSTALLED DUCTWORK AND MAKE ANY NECESSARY DUCT MODIFICATIONS
TO ENSURE PROPER OPERATION OF MECHANICAL EQUIPMENT.
3. SUBMITTALS SHALL MEET SCHEDULED DESIGN CHARACTERISTICS, INCLUDING BUT NOT LIMITED TO CFMS, EAT(DB/WB), ESP, CAPACITIES, VOLTAGES/PHASES, MCA/MOCP, SONES, ETC.
4. ALL DUCT CONSTRUCTION, INSTALLATION, AND SUPPORTS ARE TO COMPLY WITH LATEST EDITION OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE DUCT. ALL DUCTWORK SHALL BE 2" PRESSURE
CLASS UNLESS OTHERWISE NOTED.
5. INSULATE ALL DUCTWORK ACCORDING TO SPECIFICATIONS.
6. ALL WALL-MOUNTED THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE INSTALLED AT AN ELEVATION OF 48" ABOVE FINISHED FLOOR TO THE TOP UNLESS OTHERWISE NOTED ON DRAWINGS. LOCATION OF WALL-MOUNTED THERMOSTATS SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION OF THERMOSTATS SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER OR REPRESENTATIVE IN
THE FIELD.
7. ALL SUPPLY AIR DIFFUSERS SHALL BE 4-WAY THROW UNLESS NOTED OTHERWISE. CONTRACTOR SHALL PAINT INSIDE EACH RETURN GRILLE'S PLENUM AND DUCT CONNECTION FLAT BLACK TO CONCEAL CONNECTION.
COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES AND FIRE SPRINKLER HEADS. PRIOR TO INSTALLATION, THE CONTRACTOR IS TO REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR ACTUAL
FINAL LOCATIONS OF AIR DEVICES.
8. DIFFUSERS/GRILLES SHALL NEVER BE INSTALLED ON SURFACE OF ACOUSTICAL LAY-IN TILE. ALL DIFFUSERS/GRILLES IN LAY-IN CEILINGS SHALL BE LAY-IN PANEL MOUNT. REFER TO SCHEDULE. GYPSUM BOARD
SURFACE MOUNT DIFFUSERS SHALL NOT BE BEVEL MOUNT.
9. CONTRACTOR SHALL COORDINATE DIFFUSER/GRILLE LOCATIONS WITH STRUCTURE IN EXPOSED SITUATIONS IN ORDER TO ENSURE AIR IS NOT DIRECTLY SUPPLIED OR RETURNED OVER STRUCTURE OR OTHER TRADE COMPONENTS SUCH AS FIRE SPRINKLER PIPING, PLUMBING PIPING, ETC., CAUSING DUST ACCUMULATION.
DUCTWORK ALONG WITH DIFFUSER/GRILLE LOCATIONS SHALL BE INSTALLED SYMMETRICALLY WITH ANY ADJACENT DUCTWORK/GRILLES. CENTER DIFFUSERS/GRILLES BETWEEN STRUCTURAL MEMBERS WHERE DUCTWORK AND STRUCTURAL MEMBERS ARE EXPOSED. CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL
INSTALLATION APPEARANCE AND SHALL MAKE APPROPRIATE CHANGES WHERE DIRECTED BY
ARCHITECT/ENGINEER AT THEIR OWN EXPENSE WHERE ITEMS ARE NOT INSTALLED PER ABOVE STANDARDS.
10. CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE REPORT BY AN AABC OR NEBB CERTIFIED AGENCY. THIS REPORT MUST BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO THE FINAL INSPECTION.
THE CONTRACTOR MUST ALSO PROVIDE ALL REPORTS REQUIRED BY THE SPECIFICATION. OUTDOOR TEMPERATURE (DB); OUTSIDE AIR (DB/WB & CFM); SUPPLY AIR AT UNIT DISCHARGE (DB/WB & CFM); RETURN AIR {MIXED} (DB/WB & CFM); LEAVING COIL (DB/WB); DIFFUSER/GRILLE (DB/WB); EQUIPMENT (EWT/LWT); EQUIPMENT (EAT/LAT); EQUIPMENT (GPM); EQUIPMENT (PRESSURES). OUTSIDE AIR CFM SHALL BE MEASURED DIRECTLY AND
NOT CALCULATED FROM THE DIFFERENCE BETWEEN SUPPLY AIR CFM AND RETURN AIR CFM.
11. CONTRACTOR SHALL MAKE NECESSARY ADJUSTMENTS DURING TEST AND BALANCE AS REQUIRED TO ENSURE EQUIPMENT IS OPERATING WITHIN 10% OF THE SPECIFIED CRITERIA. THIS INCLUDES, BUT IS NOT LIMITED TO, ADJUSTING BELTS, SHEAVES, PULLEYS, AND IMPELLERS.
12. ALL AIR HANDLING UNITS SHALL BE MECHANICALLY ATTACHED TO OTHER AIR DISTRIBUTION SYSTEM COMPONENTS. AIR HANDLING UNITS LOCATED OUTSIDE THE CONDITIONED SPACE SHALL BE SEALED USING APPROVED CLOSURE SYSTEMS CONFORMING TO THE APPROVED CLOSURE AND MECHANICAL APPLICATION
REQUIREMENTS OF FLORIDA BUILDING CODE.
13. ALL DUCTWORK MUST BE INSTALLED 6" AWAY FROM ANY FIRE RATED WALL TO FACILITATE INSPECTION.
14. WHEN DUCTWORK IS INSTALLED 12 FT. OR MORE ABOVE THE FINISHED FLOOR, WRITE DUCT SIZES IN LARGE FONT ON THE BOTTOM OF DUCTWORK, SUCH THAT DUCT SIZES CAN BE OBSERVED AT FLOOR LEVEL WITHOUT THE NEED
OF A LADDER OR MEASUREMENTS.
15. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL TRADES INSTALLATION SCHEDULES. FIXED WORK SUCH AS DUCTWORK AND PLUMBING SHALL BE INSTALLED PRIOR TO ANY TRADE WORK THAT CAN BE EASILY RELOCATED OR OFFSET SUCH AS ELECTRICAL CONDUITS, SMALL WATER LINES, ETC. IDEALLY DUCTWORK SHALL BE INSTALLED
FIRST.
16. PROVIDE A FIRE DAMPER AT EVERY DUCT PENETRATION OF A FIRE-RATED WALL OR CEILING, WHETHER SHOWN ON DRAWINGS OR NOT. ALL FIRE DAMPERS SHALL BE DYNAMIC TYPE WITH BLADES OUTSIDE AIRSTREAM, UNLESS
NOTED OTHERWISE.
17. PROVIDE FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS AT EVERY LOCATION WHERE REQUIRED BY SECTION 607.5 OF THE IBC-MECHANICAL, WHETHER SHOWN ON DRAWINGS OR NOT. PROVIDE PROPER DAMPER ACTUATION IN ACCORDANCE WITH SECTION 607.3.3 OF THE IBC-MECHANICAL. PROVIDE ACCESS AND
IDENTIFICATION IN ACCORDANCE WITH SECTION 607.4 OF THE IBC-MECHANICAL.
18. WHERE SMOKE OR COMBINATION FIRE/SMOKE DAMPERS ARE REQUIRED, THE ELECTRICAL OR FIRE ALARM CONTRACTOR (MECHANICAL CONTRACTOR TO COORDINATE) SHALL PROVIDE 120V POWER AND ENSURE PROPER OPERATION UPON ACTIVATION. PROVIDE PROPER DAMPER ACTUATION IN ACCORDANCE WITH SECTION 607.3.3.2
OF THE FBC-MECHANICAL.
19. PROVIDE SMOKE DAMPERS FOR ALL SYSTEMS WITH DESIGN CAPACITY GREATER THAN 15,000 CFM TO ISOLATE AIR HANDLING UNIT FROM THE REMAINDER OF THE SYSTEM ON BOTH THE SUPPLY AND RETURN SIDE, UNLESS THE AIR HANDLING UNIT IS LOCATED ON THE FLOOR IT SERVES AND SERVES ONLY THAT FLOOR, OR UNLESS THE AIR HANDLING UNIT IS LOCATED ON THE ROOF AND SERVES ONLY THE FLOOR IMMEDIATELY BELOW THE ROOF.
20. PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY AIR DUCT, DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY BRANCH CONNECTIONS, FOR ALL SYSTEMS HAVING A DESIGN CAPACITY GREATER THAN 2,000 CFM.
21. PROVIDE DUCT SMOKE DETECTORS WHERE REQUIRED BY SECTION 606.2 AND 607.3.3.2 OF THE IBC-MECHANICAL.
LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION ONLY. FINAL PLACEMENT OF DETECTORS IN DUCTWORK SHALL MEET THE REQUIREMENTS OF THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE A PRESSURE DIFFERENTIAL TEST AND MANUFACTURER'S TEST KIT. A COPY OF ALL TEST DATA SHALL BE MADE AVAILABLE AT FINAL INSPECTION.
PROVIDE A READILY ACCESSIBLE DUCT ACCESS DOOR FOR INSPECTING AND SERVICING EACH DETECTOR.
PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN INACCESSIBLE LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR A U.L. LABEL. MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL DETECTOR WITHIN THE DUCTWORK. ELECTRICAL OR FIRE ALARM CONTRACTOR (MECHANICAL CONTRACTOR TO COORDINATE) SHALL PROVIDE 120V POWER AND ENSURE PROPER OPERATION FOR EACH DETECTOR. OTHER THAN IN MECHANICAL SMOKE CONTROL SYSTEMS, UPON ACTIVATION, THE ASSOCIATED AIR DISTRIBUTION SYSTEM SHALL SHUT DOWN AND A SUPERVISORY SIGNAL SHALL BE GENERATED PER SECTION 606.4 OF THE
FBC-MECHANICAL.
22. PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES (FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE RATING OF THE ASSEMBLY.
23. INTENT OF MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS. CONTRACTOR IS TO VISIT THE SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK, AND PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS, AND TO COORDINATE WITH ELECTRICAL, PLUMBING, AND FIRE PROTECTION SUBCONTRACTORS, BEFORE ANY
CONSTRUCTION WORK.
24. FLEXIBLE AND RIGID ROUND DUCT TAKE-OFFS FOR DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER NECK.
MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 5'-0".
25. INSTALL DUCTWORK AS HIGH AS POSSIBLE, TIGHT TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
COORDINATE DUCT ELEVATIONS WITH RAIN LEADERS, WATER PIPING, SANITARY DRAINS, AND MAJOR ELECTRICAL
CONDUITS.
26. CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL, STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES REQUIRED TO INSTALL AND ADEQUATELY SUPPORT MECHANICAL EQUIPMENT AND COMPONENTS IN A MANNER WHICH WILL NOT OVERLOAD BUILDING STRUCTURE. CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND
SERVICEABILITY.
27. CONTRACTOR SHALL INSTALL MOTORIZED OUTSIDE AIR DAMPERS FOR ALL AIR HANDLING EQUIPMENT. AIR HANDLING UNITS SHALL HAVE AN EQUIVALENT OR BETTER OF RUSKIN "CD50" DAMPER, WHICH SHALL MODULATE
PER 24V ACTUATOR MECHANICALLY WIRED. ALL DAMPERS SHALL CLOSE UPON UNIT SHUTDOWN.
28. PROVIDE A TRAP IN ALL CONDENSATE PIPING LOCATED AT THE AIR HANDLING EQUIPMENT. INSULATE ALL CONDENSATE LINES WITH 1/2" CLOSED CELL FOAM INSULATION. ALL PIPING EXPOSED TO EXTERNAL ELEMENTS
SHALL BE JACKETED WITH UV STABILIZED PVC OR ALUMINUM SHEETING.
29. PROVIDE A 4" HIGH CONCRETE HOUSEKEEPING PAD UNDER ALL MECHANICAL EQUIPMENT, UNLESS NOTED
OTHERWISE. PADS SHALL BE 4" LARGER THAN EQUIPMENT ON ALL SIDES.
30. ALL UNDERGROUND PIPING SHALL HAVE A MINIMUM 3'-0" OF COVER, UNLESS NOTED OTHERWISE.
31. IT IS THE RESPONSIBILITY OF THE MECHANICAL INSTALLER TO PATCH AND REPAIR ANY DUCT OPENINGS WHICH RESULT FROM THE RELOCATION OR ELIMINATION OF ANY EXISTING AIR DEVICES. THE PATCH IS TO BE OF A SIMILAR MATERIAL TO THE REPAIRED DUCT AND TO BE SEALED IN ACCORDANCE WITH SMACNA STANDARDS.
32. AIR HANDLING EQUIPMENT WARRANTIES SHALL BE EQUAL TO OR EXCEED WARRANTY OF SCHEDULED EQUIPMENT, UNLESS NOTED OTHERWISE.
33. PROVIDE SEISMIC RESTRAINTS FOR DUCTWORK AND PIPING CONFORMING TO THE LATEST EDITION OF THE "SMACNA GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING SYSTEMS."
34. PROVIDE ADDITIONAL DUCTWORK AND PIPING SUPPORTS ON BOTH SIDES AND WITHIN 18" OF EACH FIRE RATED
WALL. DUCTWORK OR PIPING SHALL NOT BE SUPPORTED FROM ANY FIRE RATED WALL.
35. PROVIDE SINGLE WALL TURNING VANES IN ALL RECTANGULAR DUCT ELBOWS WITH ANGLES FROM 45 DEGREES TO 90 DEGREES, EXCEPT FOR TRANSFER AIR ELBOWS. TURNING VANES SHALL BE PROVIDED ACCORDING TO SMACNA
HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE.
36. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS (FREE AREA).
37. CONTRACTOR SHALL COORDINATE ALL INTAKE/EXHAUST LOCATIONS TO ENSURE MINIMUM 10'-0" DISTANCE
BETWEEN ANY INTAKES AND EXHAUSTS, PLUMBING VENTS, RELIEF, ETC.
38. ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS UNLESS INDICATED
OTHERWISE.
39. CONTRACTOR SHALL THOROUGHLY CLEAN AND ENSURE PROPER OPERATION OF ANY EXISTING HVAC EQUIPMENT.
ANY CHANGE TO THE SYSTEM SHALL RESULT IN EQUIPMENT MODIFICATIONS (AS REQUIRED) INCLUDING BUT NOT
LIMITED TO REPLACING MOTORS, VFDS, PULLEYS, SHEAVES, BELTS, ETC.
40. MECHANICAL CONTRACTOR SHALL SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. REFRIGERANT PIPING SHALL BE TYPE "L" COPPER WITH SOLDERED OR BRAZED JOINTS AND 1" CLOSED CELL INSULATION. ALL PIPING EXPOSED TO EXTERNAL ELEMENTS SHALL BE JACKETED WITH UV STABILIZED PVC OR ALUMINUM SHEETING. PRE-CHARGED LINES AND SOLDER ON SHORT 90'S ARE NOT ACCEPTABLE. CONTRACTOR SHALL USE SWEEPING 90'S AT EVERY BEND WITH EXCEPTION OF EQUIPMENT
CONNECTIONS.
41. CONTRACTOR SHALL PROVIDE A PERMANENT/PROFESSIONAL LABEL FOR EACH PIECE OF EQUIPMENT, ASSOCIATED THERMOSTAT(S) AND/OR SENSOR(S).
42. EQUIPMENT LOCATION IDENTIFICATIONS AT CEILINGS: WHERE VALVES, EQUIPMENT SUCH AS VAV BOXES, FANS, ETC., CIRCUIT BREAKERS, OR OTHER ITEMS SUBJECT TO ROUTINE SERVICE, ARE MOUNTED IN A CONCEALED AREA ABOVE A CEILING, THE CEILING MUST BE MARKED WITH A LABEL UNDER THE SERVICED DEVICE. THE LABEL SHALL
CARRY APPROPRIATE IDENTIFICATION TAG.
43. DUCTWORK, DIFFUSERS, REGISTERS, GRILLES, AND OTHER MECHANICAL SYSTEM COMPONENTS SHALL NOT BE
SUPPORTED BY THE CEILING OR CEILING SUSPENSION SYSTEM.
44. METAL DUCTWORK SHALL BE CONNECTED TO MECHANICAL EQUIPMENT WITH FLEXIBLE DUCT CONNECTORS EQUAL TO DURO DYNE "SUPER METAL-FAB" WITH EXCELON FABRIC; "GRIP LOC" SEAM; 24 GAGE METAL TABS. INSULATION
SHALL BE INSTALLED OVER METAL TABS AS TO NOT CAUSE FRICTION ON FABRIC.
45. ALL EXHAUST DUCT WORK SHALL BE NON-INSULATED SHEET METAL, UNLESS NOTED OTHERWISE.
46. ALL FLEXIBLE DUCTS SHALL BE LISTED AND LABELED TO UL 181 AND SHALL BE CLASS 0 OR CLASS 1. FLEXIBLE DUCTS SHALL HAVE A MINIMUM RATED AIR VELOCITY OF 4000 FPM, A MINIMUM POSITIVE PRESSURE RATING OF 4 IN.
WG, AND A MINIMUM NEGATIVE PRESSURE RATING OF 1 IN. WG. ALL FLEXIBLE DUCTS SHALL MEET 2017
INTERNATIONAL BUILDING CODE SECTION 449.3.6.4.
47. CONTRACTOR SHALL SUPPLY PIPE SUPPORTS 4'-0" ON CENTERS FOR REFRIGERANT LINES AND CONDENSATE
LINES. SUPPORTS SHALL BE PER DETAILS.
48. ALL DOOR UNDERCUTS FOR THE PURPOSE OF BALANCING RETURN AIR SHALL BE MINIMUM 1".
49. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF MECHANICAL WORK; REFER TO ELECTRICAL SPECIFICATIONS FOR CONDUIT AND WIRING REQUIREMENTS. COORDINATE WITH ELECTRICAL CONTRACTOR TO ENSURE THAT REQUIRED INTERFACE DEVICES ARE PROVIDED WITH ELECTRICAL COMPONENTS (I.E. FAN SPEED
RHEOSTATS, AUXILIARY CONTACTS, INTERLOCKS, ETC.).
50. ALL EQUIPMENT DISCONNECTS, WHETHER INTERNALLY MOUNTED OR EXTERNALLY MOUNTED, SHALL BE FURNISHED, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. IF EXTERNALLY MOUNTED, PROVIDE DISCONNECTING MEANS AT SAME ELEVATION AS EQUIPMENT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
51. MECHANICAL CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH ELECTRICAL CONTRACTOR BEFORE BIDDING/ORDERING AND INSTALLATION.
52. WHERE MOTOR SPEED CONTROL IS REQUIRED, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE APPROPRIATE METHOD OF SPEED CONTROL. TYPICALLY, SINGLE PHASE MOTORS REQUIRE SPEED CONTROLLERS, AND THREE PHASE MOTORS REQUIRE VFD'S.
nstephenson PE Nicholas P. Stephenson - FL nstephenson Snapshot
RADIOGRAPHIC
CONTROL
A-105
ROOM
HOUSE-
KEEPINGKEEPING
HOUSE-
A-112A-112 A-111A-111
C O R R I D O R
A-104
A-103
57.43n.s.f.
C O
R R
I D
O R
OFFICE
NO.1
OFFICE
NO.2
ULTRASOUND
ROOM NO.1
A V O
A V O
A V O
A V O
BILLING
OFFICE
A-101a
A-101b
A-101c
C-109
A-112a
C O
R R
I D
O R
C
-1ROOM
RECOVERY
HOLDING
R/F ROOM
MULTIPURPOSE
A-102
STORAGE
ASSISTANT
BATHROOM
A-116p
AUTOMATION
OFFICE
A-116q
F.H.
ROOM
READING
SUPERVISOR
OFFICE
I.R.
OFFICE
SCRUBING
AREA
SOILED
LINEN
ROOM
CLEAN
LINEN
ROOM
LOCKER
ROOM
(E) CD
(E) CD
(E) EG
(E) CD
(E) CD
(E) CD
(E) CD
(E) CD
(E) CD
(E) CD
(E) CD
(E) CD
(E) CD
(E) EG
(E) RG
(E) RG
T
T
T
T
T
T
(E) CD
(E) 40"X14"
(E) RG
(E) CD 2
(E) RG 2
(E) RG
(E) 34"X16"
(E) 48"X10"
(E ) 3
2" X1
6"
(E )1
8" X1
2"
(E )2
0" X1
0"
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL DEMOLITION
PLAN
GENERAL NOTES
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN
THESE DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING
EXISTING INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE VA/COR.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO EXISTING
SYSTEM PIPING AND DUCTWORK AND IDENTIFY ALL RISERS AFFECTED.
D. CONTRACTOR TO REMOVE ALL ABANDONED MECHANICAL ITEMS
INCLUDING EQUIPMENT, DUCTWORK, PIPING, VALVES, ACCESSORIES,
ETC. ABOVE THE CEILING WITHIN THE AREA OF WORK, EVEN IF NOT
SHOWN ON DRAWINGS. PROPERLY SEAL ANY OPENINGS CREATED BY
THE REMOVAL OF MECHANICAL ITEMS. COORDINATE WITH VA
PERSONNEL BEFORE THE REMOVAL TO ENSURE ITEM IS ABANDONED.
E. MECHANICAL CONTRACTOR SHALL REVIEW OTHER DISCIPLINES
DRAWINGS AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF
ALL EQUIPMENT SHOWN TO BE DEMOLISHED.
F. ALL DEMOLISHED EQUIPMENT SHALL BE PRESENTED TO VA FOR
FIRST RIGHT OF REFUSAL
KEYNOTES
1. REMOVE EXISTING CEILING DIFFUSER AND PREPARE FOR RELOCATION.
SEE MH100 FOR NEW LOCATION.
2. DEMOLISH EXISTING CEILING DIFFUSER/RETURN GRILLE. CAP
DUCTWORK BACK AT MAIN.
3. THERMOSTAT TO BE RELOCATED AND ASSOCIATED WIRING TO BE
REMOVED. SEE MH100 FOR NEW LOCATION.
X
MD100
nstephenson PE Nicholas P. Stephenson - FL
RADIOGRAPHIC
CONTROL
A-105
ROOM
HOUSE-
KEEPINGKEEPING
HOUSE-
A-112A-112 A-111A-111
A-104
58.60n.s.f.
77.16n.s.f.
299.00n.s.f.
C O
R R
I D
O R
A V O
A V O
A V O
A V O
C O
R R
I D
O R
C
-1
R/F ROOM
MULTIPURPOSE
ASSISTANT
BATHROOM
A-116p
AUTOMATION
OFFICE
A-116q
F.H.
I.R.
OFFICE
PREP/RECOVERY
PREP/RECOVERY
PREP/RECOVERY
READING
AREA
PREP/RECOVERY
SOILED
LINEN
CATHETERS
SUPPLY
PREP/RECOVERY
SCRUB AREA
NURSE
STATION
LINEN
STORAGE
RECLINERS /
OUTPROCESSING100
ENTRY
C-RENO
CORRIDOR
T
T
T
T
(R) EG
850 CFM
(R) CD
225 CFM
(R) CD
225 CFM
(R) CD
50 CFM
(R) CD
40 CFM
(R) CD
60 CFM
(R) RG
40 CFM
T
T
T
T
(E) 40"X14"
(R) RG
60 CFM
(R) RG
40 CFM
(E) 34"X16"
(E) 48"X10"
(E ) 3
2" X1
6"
(E )1
8" X1
2"
(E )2
0" X1
0"
(R) CD
225 CFM
(R) CD
30 CFM
(R) CD
60 CFM
(R) EG
80 CFM
(R) CD
225 CFM
(R) RG
20 CFM
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL RENOVATION
PLAN
KEYNOTES
1. RELOCATED CEILING DIFFUSER. ENSURE PROPER CONNECTION OF FLEX
DUCT TO RELOCATED DIFFUSERS AND EXTEND DUCTWORK AS
NECESSARY. BALANCE TO CFM SHOWN ON PLAN. COORDINATE WITH
OTHER TRADES. TYPICAL.
2. RELOCATED THERMOSTAT. PLACE AT 48" AFF AND EXTEND WIRING AS
NECESSARY.
3. RELOCATED RETURN/EXHAUST GRILLE. ENSURE PROPER CONNECTION
OF NEW DUCTWORK TO EXISTING. COORDINATE WITH OTHER TRADES.
TYP.
X
MH100
nstephenson PE Nicholas P. Stephenson - FL
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL DETAILS
M-501
20° TRANSITION (MAX)
0.25 D (4" MIN. PER SMACNA)
RECTANGULAR DUCT
D
VOLUME DAMPER
CONICAL FITTING WITH LOCKING
TYPE VOLUME DAMPER.
FLEX DUCT OR ROUND SHEET METAL DUCT. FLEX DUCT
MAX. 8'-0" LONG, USE CLAMP TO ATTACH FLEX DUCTS AND
SEAL. SUPPORT DUCT EVERY FOUR FEET FROM
STRUCTURE
1.
D
DUCT DETAILS NTS
PROVIDE VOLUME
DAMPER WHEN SHOWN
ON PLANS
PROVIDE VOLUME
DAMPER WHEN SHOWN
ON PLANS
MAIN SUPPLY DUCT
ADJUSTABLE METAL
ROD OR LINKAGE
TOP REGISTER
MAIN SUPPLY DUCT
BRANCH DUCT
1/4W 4" MIN.
SEE PLAN FOR SPLIT DIMENSION
MAIN SUPPLY
DUCT
TURNING VANES
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON PLANS
SUPPLY REGISTER
OR BRANCH DUCT
PLAN VIEW
AIR SPLIT TYPE DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF
PLAN VIEW
SUPPLY REGISTER TAKE-OFF
SUPPLY DUCT TAKE-OFFS NTS
SUPPORT AS PER
SMACNA STANDARDS
SPIN-IN FITTING WITH BUTTERFLY
DAMPER & 45° EXTRACTOR
ROUND "SNAPLOCK" SHEET METAL OR SPIRAL
LOCKSEAM WITH WRAP INSULATION
(SAME AS DIFFUSER NECK)
FLEXIBLE DUCT: DO NOT SAG
OR KINK, INSULATED,
MAXIMUM 8'-0" LONG (SAME
SIZE AS DIFFUSER NECK)
THREE SHEET METAL
SCREWS THROUGH HELIX OF
FLEXIBLE DUCT, BAND CLAMP
& TAPE
2" WRAP INSULATION:
CUT, FIT & GLUED OVER
CEILING DIFFUSER
CEILING DIFFUSERCEILING
SUPPLY DUCT
SUPPORT STRAP TO PREVENT
SAGS & KINKS
IN FLEX (PER SMACNA)
* FLEXIBLE DUCT SHALL HAVE CONTINUOUS METAL LINER ENCASED BY INSULATING MATERIAL WITH AN OUTER VAPOR JACKET CONFORMING TO UL181 UNLESS THE FLEX DUCT MEETS THE CRITERIA STATED IN 2017 FLORIDA
BUILDING CODE-BUILDING SECTION 449.3.6.4.
CEILING DIFFUSER RUNOUT DETAIL NTS3
nstephenson PE Nicholas P. Stephenson - FL
| M-001 MECHANICAL NOTES AND LEGENDS |
| MD100 MECHANICAL DEMOLITION PLAN |
| MH100 MECHANICAL RENOVATION PLAN |
| M-501 MECHANICAL DETAILS |
File details come from the government source that posted it. Updated .