Attachment 03c - Plumbing Combined (5 pages).pdf

PDF 2 MB Posted

Attached to
Y1DB--Expand Interventional Radiology Suite Federal contract opportunity
Solicitation number
36C24823R0162
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This document package includes construction drawings, notes, and specifications for a plumbing renovation project at a Department of Veterans Affairs medical facility. The project scope involves demolishing some existing plumbing fixtures and installing new fixtures, relocating some medical gas outlets, and connecting to existing water and drainage systems. Specific items required include new barrier-free lavatories, service sinks, and a scrub sink. The drawings provide demolition plans, renovation plans, isometric diagrams, and construction details. Accompanying notes outline plumbing standards and codes, contractor responsibilities, submittal requirements, and commissioning procedures for anti-scald valves. The solicitation number listed is for expanding an interventional radiology suite.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DB--Expand Interventional Radiology Suite, newest first.
File Type Posted
672-20-107 Third Party Asbestos Monitor Specs (2 pages).pdf PDF
Asbestos Free Areas_IR Suite area (1 page).pdf PDF
672-20-107 Construction SOW Updated 7-21-2023 (4 pages).pdf PDF
36C24823R0162 0001 (RFI Update SOW and Extend Due Date).docx DOCX document
Attachment 08 - Key Personnel Resume Form (1 page).pdf PDF
Attachment 03b - Fire Protection Combined (2 pages).pdf PDF
Attachment 02 - Specifications Part 2 of 2 (749 pages).pdf PDF
Attachment 02 - Specifications Part 1 of 2 (856 pages).pdf PDF
36C24823R0162 Solicitation (BB 672-23-107).docx DOCX document
Attachment 03d - Mechanical Combined (4 pages).pdf PDF
Attachment 13 - Infection Control Guidelines on Construction and Renovation 11B-17-05 (11 pages).pdf PDF
Attachment 12 - Past Performance Survey (3 pages).docx DOCX document
Attachment 09 - Specialized Experience Form (3 pages).pdf PDF
Attachment 06 - Letter of Commitment Key Subcontractors (1 page).pdf PDF
Attachment 05 - Safety or Environmental Violations and Experience Modification Rate EMR Form (1 page).pdf PDF
Attachment 03 - Cover Sheet-G-001 (1 page).pdf PDF
Attachment 04 - Base Offer Price Breakdown (1 Page).xlsx XLSX spreadsheet
Attachment 03a - Architectual Combined (16 pages).pdf PDF
Attachment 01 - Site Plan (1 Page).pdf PDF
Attachment 11 - Past Performance Questionnaire (4 pages).pdf PDF
Attachment 14 - 852.219-75 VA Notice of Limitation on Subcontracting Certificate of Compliance for Services and Construction (JAN 2023) (2 pages).doc DOC document
Attachment 10 - Subcontractor Past Performance Consent Form (1 page).pdf PDF
Attachment 07 - Letter of Commitment for Key Personnel (1 page).pdf PDF
Attachment 03e - Electrical Combined (10 pages).pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

PLUMBING NOTES AND

LEGENDS

P-001

PIPE UP

PIPE DOWN

GCOOR

OR VTR VENT THRU ROOF

EQUIPMENT MARK

POINT OF NEW CONNECTION

DRAWING KEYNOTEX

BALL VALVE

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)

WCO

OR

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RECIRCULATION PIPING

SAN SANITARY PIPING

(E)CW EXISTING COLD WATER

(E)HWR EXISTING HOT WATER RETURN

(E)HW EXISTING HOT WATER PIPING

EXISTING PIPING TO BE REMOVED

(E)SAN EXISTING SANITARY PIPING

V SANITARY VENT PIPING

LIMIT OF DEMOLITION

GRADE CLEAN OUT (1-WAY OR 2-WAY)

PLUMBING LEGEND

PLUMBING ABBREVIATIONS

(E) EXISTING

CO PIPE CLEAN OUT

CTE CONNECT TO EXISTING

CW COLD WATER

DEMO DEMOLISH OR DEMOLITION

DFU DRAINAGE FIXTURE UNITS

ETR EXISTING TO REMAIN

GPM GALLONS PER MINUTE

HW HOT WATER

IBC INTERNATIONAL BUILDING CODE

LAV LAVATORY

S SINK

SAN SANITARY

VTR VENT THROUGH ROOF

W WASTE

WCO WALL CLEAN OUT

WSFU WATER SUPPLY FIXTURE UNITS

1. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND BEGINNING WORK. INSTALLATIONS ARE TO INCLUDE ALL

PLUMBING FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS REQUIRED.

2. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS, STRUCTURE, ELECTRICAL, LIGHTING, AND OTHER PIPING IN THE CEILING SPACE. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER

ABOVE OR BELOW HVAC DUCTWORK, AS COORDINATED WITH THE HVAC CONTRACTOR.

3. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.

4. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES AND EQUIPMENT

SUPPLIES.

5. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING FIXTURES, UNLESS NOTED

OTHERWISE.

6. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES OF ALL PLUMBING FIXTURES PRIOR TO ROUGH-IN.

FURNISH CUT-OUT TEMPLATES, FOR PLUMBING FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL

CONTRACTOR.

7. MAKE PROPER HOT AND COLD WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT

EVEN THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT SHOWN ON DRAWINGS.

8. VERIFY LOCATION OF EXISTING WATER SERVICE AND THE LOCATION/INVERTS OF SANITARY PIPING PRIOR TO

INSTALLATION.

9. CUT AND PATCH CONCRETE AS REQUIRED.

10. IT IS NOT THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND

INSTALLED BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.

11. THE EQUIPMENT ROUGH-IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR EQUIPMENT ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR EQUIPMENT ROUGH-IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THAT CONTRACTOR.

12. CONTRACTOR SHALL SUPPLY TO THE ARCHITECT/ENGINEER THE REQUIRED COPIES OF SHOP DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MATERIALS OR EQUIPMENT CAN BE REVIEWED BEFORE INSTALLATION.

THERE WILL BE NO INSTALLATION UNTIL SHOP DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE

ARCHITECT/ENGINEER.

13. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR BUILDING DIMENSIONS.

14. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, FITTINGS, ETC. REQUIRED TO COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN HAD PROPER

EXAMINATION BEEN MADE.

15. VERIFY SERVICE POINTS AND METERING LOCATIONS FOR PROJECTS WITH LOCAL UTILITIES AND/OR LANDLORD

(DOMESTIC WATER, SANITARY SEWER, GAS, ETC.).

16. THE CONTRACTOR SHALL COOPERATE FULLY AMONG ALL TRADES.

17. ALL ROOF PENETRATIONS FOR ROOF DRAINS AND PLUMBING, GAS, AND REFRIGERANT PIPING SHALL BE MADE IN ACCORDANCE WITH ROOF SYSTEM MANUFACTURER'S GUIDELINES. COORDINATE WITH ARCHITECTURAL DETAILS

AND/OR MANUFACTURER FOR ROOF SYSTEM USED.

18. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0" BEFORE ROOF PENETRATION.

19. INSTALL 1" INSULATION WITH ALL-SERVICE JACKET ON ALL ROOF LEADERS ABOVE CEILING.

20. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH LOCAL REGULATIONS.

21. HOT AND COLD WATER SUPPLY BRANCHES FOR ALL SYSTEMS HAVING QUICK CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTORS INSTALLED AT THE HIGH POINT ON THE END OF EACH BRANCH AND AS

REQUIRED.

22. ALL PIPES HANGING FROM SINGLE VERTICAL RODS / HANGERS SHALL NOT MOVE OR SWAY DURING OPERATION.

SUITABLE LATERAL SUPPORTS OR BRACING SHALL BE USED TO PREVENT SWAY OR MOVEMENT.

23. PROVIDE SHUTOFF BALL VALVES AND DIELECTRIC UNIONS FOR ALL EQUIPMENT HOT AND COLD WATER LINES.

PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT

SUPPLIER FOR EXACT REQUIREMENTS.

24. VERIFY MOUNTING HEIGHTS OF ALL BARRIER FREE FIXTURES WITH ARCHITECTURAL PLANS.

25. PROVIDE COPPER INDIRECT WASTE PIPING REQUIRED FROM EQUIPMENT TO FLOOR DRAINS, OPEN RECEPTACLES, OR FLOOR SINKS. PIPING SHALL COMPLY WITH STATE AND LOCAL CODES. COORDINATE WITH ALL EQUIPMENT SUPPLIERS AND SIZES AS REQUIRED BY PIECE OF EQUIPMENT SERVED. HOLD PIPING TIGHT TO WALL WHERE APPLICABLE. PROPERLY SECURE AS REQUIRED. COORDINATE WITH CASEWORK SUPPLIER FOR MAXIMUM

CLEARANCE UNDER CABINETS.

26. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.

27. INSTALL STORM AND CONDENSATE PIPING WITH MINIMUM SLOPE OF 1/8" PER FOOT. INSTALL SANITARY PIPING LESS THAN 3" AT 1/4" PER FOOT, 3" TO 6" AT 1/8" PER FOOT, AND 8" AND GREATER AT 1/16" PER FOOT. CONTRACTOR

IS RESPONSIBLE FOR PROPER DRAINAGE OF ALL SYSTEMS.

28. ALL FLOOR DRAINS ARE TO BE PROVIDED WITH MINIMUM 3" DRAIN LINES, DEEP SEAL TRAPS, AND AUTOMATIC TRAP PRIMERS. TRAP PRIMERS SHALL BE LOCATED IN A SERVICEABLE LOCATION AND INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. HOLD TOP OF FLOOR DRAINS FLUSH WITH FINISHED FLOOR; SEE

ARCHITECTURAL SHEETS FOR FLOOR SLOPES AND PROPER FINISHED FLOOR ELEVATION.

29. ALL VENT PIPE TO BE COMPATIBLE WITH STRUCTURE, MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT, AND LIGHTING. ALL VTR'S SHALL BE EXTENDED TO A MINIMUM OF 2" ABOVE PARAPET HEIGHT AND

MAINTAINED 10'-0" MINIMUM FROM ALL OUTSIDE AIR INTAKES.

30. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL, ASTM, ASSE, AWWE, AGA AND NFPA AS WELL AS THE MOST

CURRENT ADOPTED VERSION OF THE STATE AND LOCAL CODES.

31. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS, OR SYSTEMS AT CONTRACTOR'S EXPENSE, BEFORE

COMPLETION OF PROJECT.

32. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.

33. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (UNLESS OTHERWISE NOTED). PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC., INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE ACCESSIBLE THEY MUST COMPLY WITH ALL FEDERAL A.D.A. REGULATIONS.

34. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED, FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT.

THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL OWNER ACCEPTANCE OF THE WORK

AND SHALL APPLY TO ALL DEFECTS IN MATERIALS AND WORKMANSHIP OF ANY KIND.

35. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHTGRASPING.

36. ALL BARRIER FREE WATER CLOSET CONTROLS SHALL BE LOCATED ON UNIT TOWARDS WIDE SIDE OF STALL.

VERIFY IF RIGHT OR LEFT SIDE LOCATION.

PLUMBING NOTES GENERAL NOTES

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE

PROVIDED (FURNISHED AND INSTALLED) UNDER THIS CONTRACT. DRAWINGS

SHOULD NOT BE SCALED.

2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER

WHICH THEY SHALL OPERATE AND VERIFY THE EXTENT OF WORK REQUIRED TO

COMPLETE THE WORK UNDER THIS CONTRACT.

3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY

OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT

SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR

INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO

DETERMINE ANY NECESSARY MODIFICATIONS.

4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND

LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY

HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING

DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE

REQUIREMENTS:

· INTERNATIONAL BUILDING CODE (IBC) 2020

· INTERNATIONAL EXISTING BUILDING CODE 2020

· IBC MECHANICAL 2020

· IBC PLUMBING 2020

· IBC ENERGY CONSERVATION 2020

· NFPA 1-2018, THE UNIFORM FIRE CODE

· NFPA 101-2018, THE LIFE SAFETY CODE

· NFPA 51B-2014, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING

AND OTHER HOT WORK

· NFPA 13-2016, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

· NFPA 70-2017, NATIONAL ELECTRICAL CODE

· NFPA 90A-2018, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND

VENTING SYSTEMS.

· NFPA 99-2018, STANDARD FOR HEALTH CARE FACILITIES

· NFPA 241-2013, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION

AND DEMOLITION OPERATIONS.

· ALL APPLICABLE VA DESIGN MANUALS

6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND

CONSTRUCTION WORK.

7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF

WORK UNDER THIS CONTRACT. DISMANTLE AND REASSEMBLE EQUIPMENT AS

NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF INSTALLATION.

8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL

UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED AND AN

UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.

9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART OF THE

TOTAL PROJECT COST.

10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,

CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES

WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L. REQUIREMENTS TO MAINTAIN

THE ASSEMBLY RATING.

11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE

AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND

SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL TIMES DURING

CONSTRUCTION.

12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS

FOR ALL PRODUCTS USED ON PROJECT.

14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE

CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF

CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN

APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION. THE ENGINEER'S

APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF

RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS OR HER SUBMITTAL DATA.

15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN

THREE RING BINDERS AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE

INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS,

CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP DRAWINGS, SPARE PARTS

DATA, ETC. PROVIDE AN INDEX AND ASSOCIATED DIVIDERS.

16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF

CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT

CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE

ALL CONTRACT CHANGES, MODIFICATIONS, AND CLARIFICATIONS. THIS SET ALONG

WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER

AFTER CONSTRUCTION COMPLETION.

17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND

UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED

TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC

IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL

REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND

SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE

OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE

ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE

TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT

AND MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN

CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.

PLUMBING FIXTURE SCHEDULE

FIXTURE

MARK FIXTURE DESCRIPTION

ROUGH-IN PIPE SIZES WATER SUPPLY DURATION

COLD WATER

SUPPLY

HOT WATER

SUPPLY FIXTURE TRAP FIXTURE

DRAIN COLD WATER HOT WATER DRAINAGE

P-418

LAVATORY, BARRIER FREE, WALL HUNG,

20"X18",.VITREOUS CHINA, FAUCET HOLES AS

REQUIRED. 0.5 GPM.PROVIDE WITH ASSE 1070

ANTI-SCALD VALVE. REFER TO SPECIFICATION

SECTION 224000 FOR MORE INFORMATION.

1/2" 1/2" 1 1/4" 2" 0.5 0.5 1

P-505

SERVICE SINK, FLUSHING RIM, WALL HUNG,

24"X20", 2.5 GPM.PROVIDE SERVICE SINK

FAUCET WITH VACUUM BREAKER, INTEGRAL

STOPS, ADJUSTABLE WALL BRACE, AND 3/4"

HOSE THREADED OUTLET. PROVIDE WITH

HOSE, HOSE BRACKET, MOP HANGER, AND

ALUMINUM BUMPERGUARD. REFER TO

SPECIFICATION SECTION 224000 FOR MORE

INFORMATION.

1" 1" 3" 3" 1.5 0.5 2

P-520

SCRUB SINK - 28"X22"X12" DEEP, REFER TO

SPECIFICATION SECTION 224000 FOR MORE

INFORMATION.

1/2" 1/2" 1 1/4" 2" 1 1 1

NOTE: PLUMBING FIXTURES AND FINISHES ARE SELECTED/SPECIFIED BY ARCHITECT/INTERIOR DESIGNER. FURNISH AND INSTALLED BY PLUMBING CONTRACTOR.

X-XXX

RADIOGRAPHIC

CONTROL

A-105

ROOM

HOUSE-

KEEPINGKEEPING

HOUSE-

A-112A-112 A-111A-111

C O R R I D O R

A-104

A-103

57.43n.s.f.

C O

R R

I D

O R

OFFICE

NO.1

OFFICE

NO.2

ULTRASOUND

ROOM NO.1

A V O

A V O

A V O

A V O

BILLING

OFFICE

A-101a

A-101b

A-101c

C-109

A-112a

C O

R R

I D

O R

C

-1ROOM

RECOVERY

HOLDING

R/F ROOM

MULTIPURPOSE

A-102

STORAGE

ASSISTANT

BATHROOM

A-116p

AUTOMATION

OFFICE

A-116q

F.H.

ROOM

READING

SUPERVISOR

OFFICE

I.R.

OFFICE

SCRUBING

AREA

SOILED

LINEN

ROOM

CLEAN

LINEN

ROOM

LOCKER

ROOM

(E) P-501

(E) P-510

(E) 5/8" O

(E) 5/8" MA

(E) 3/4" V

(E) 3/4" MA

(E) 3/4" O

(E) 3/4" V

(E) 1" V

(E) 3/4" O

(E) 3/4" MA

3 4

(E) 3/4" O

(E) 3/4" MA

(E) 1" V

(E) 3/4" O

(E) 3/4" MA

(E) 1" V

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

PLUMBING DEMOLITION PLAN

GENERAL NOTES

A. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS

SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON

EXISTING DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.

FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE VA/COR.

C. ALL EXISTING PIPING TO BE REUSED SHALL BE PRESSURE TESTED,

THOROUGHLY CLEANED, AND SANITIZED TO AVOID POSSIBLE

CONTAMINATION.

D. PLUMBING CONTRACTOR SHALL ENSURE NO DEAD LEGS ARE LEFT IN

ANY PIPING WITHIN THE AREA OF WORK.

E. PLUMBING CONTRACTOR SHALL REVIEW OTHER DISCIPLINES DRAWINGS

AND SHALL DISCONNECT AND MAKE SAFE FOR REMOVAL OF ALL

EQUIPMENT SHOWN TO BE DEMOLISHED.

F. ALL DEMOLISHED EQUIPMENT SHALL BE PRESENTED TO VA FOR

FIRST RIGHT OF REFUSAL

KEYNOTES

1. REMOVE AND DISPOSE OF EXISTING PLUMBING FIXTURE. SANITARY AND

WATER PIPING TO BE CAPPED BACK AT MAIN.

2. REMOVE AND DISPOSE OF EXISTING PLUMBING FIXTURE. TEMPORARILY

CAP PIPING AT WALL.

3. EXISTING MEDICAL GAS OUTLET BOX TO BE RELOCATED. PIPING TO BE

CAPPED AT MAIN. SEE PL100 FOR NEW LOCATIONS.

4. EXISTING 4" SANITARY RISERS.

5. EXISTING MEDICAL GAS VALVE BOX AND ZONE ALARM TO BE PREPARED

FOR RELOCATION.

6. EXISTING PIPING TO REMAIN. PROTECT DURING DEMOLITION AND

CONSTRUCTION.

7. VALVE BOX AND ASSOCIATED PIPING TO BE RELOCATED. SEE PL100 FOR

NEW LOCATION.

X

PD100

RADIOGRAPHIC

ROOM

A-106

CONTROL

A-105

ROOM

HOUSE-

KEEPINGKEEPING

HOUSE-

A-112A-112 A-111A-111

A-104

58.60n.s.f.

77.16n.s.f.

299.00n.s.f.

C O

R R

I D

O R

A V O

A V O

A V O

A V O

C O

R R

I D

O R

C

-1

R/F ROOM

MULTIPURPOSE

ASSISTANT

BATHROOM

A-116p

AUTOMATION

OFFICE

A-116q

F.H.

I.R.

OFFICE

PREP/RECOVERY

PREP/RECOVERY

PREP/RECOVERY

READING

AREA

PREP/RECOVERY

SOILED

LINEN

CATHETERS

SUPPLY

PREP/RECOVERY

SCRUB AREA

NURSE

STATION

LINEN

STORAGE

RECLINERS /

OUTPROCESSING100

ENTRY

C-RENO

CORRIDOR

P-5201

P-418

P-505

(E) 3/4" MA

(E) 3/4" O

(E) 3/4" V

(E) 1" V

(E) 3/4" O

(E) 3/4" MA

(E) 5/8" O

(E) 5/8" MA

(E) 3/4" V

4 4

3" SAN

1" CW

1" HW

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

PLUMBING RENOVATION PLAN

KEYNOTES

1. INSTALL NEW PLUMBING FIXTURE AS INDICATED. CONNECT TO EXISTING

SANITARY, VENT, AND WATER PIPING, MODIFY PIPING AS REQUIRED.

VERIFY SIZE AND LOCATION.

2. CONNECT NEW 3" SANITARY PIPING TO EXISTING PIPING BELOW. FIELD

VERIFY EXACT LOCATION.

3. PROVIDE NEW MEDICAL GAS OUTLET BOX AT EACH PATIENT BED.

CONNECT NEW MEDICAL GAS PIPING TO EXISTING MAINS. FIELD VERIFY

EXACT LOCATIONS.

4. RELOCATED VALVE BOX AND ZONE ALARM.

5. RELOCATED VALVE BOX. EXTEND PIPING AS NECESSARY.

6. CONNECT NEW 1" DOMESTIC HOT AND COLD WATER PIPING TO EXISTING

PIPING. FIELD VERIFY EXACT LOCATION IN FIELD.

7. CONNECT NEW 2" VENT INTO EXISTING. FIELD VERIFY EXACT LOCATION

IN FIELD.

X

PL100

strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

PLUMBING ISOMETRICS

PW301

(E) 3/4" MA

(E) 3/4" O

(E) 3/4" V

(E) 5/8" O

(E) 5/8" MA

(E) 3/4" V

P-505 P-418

3" SAN

1" CW

1" HW

P-505 P-418

2" VENT

strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

PLUMBING DETAILS

P-501

- CPVC PIPING 1" DIAMETER AND SMALLER

SUPPORT MAXIMUM EVERY 3 FT.

- CPVC PIPING 1-1/4" DIAMETER AND LARGER

SUPPORT MAXIMUM EVERY 4 FT.

- TYPE "L" COPPER PIPE 1-1/4" OR SMALLER

SUPPORT MAXIMUM EVERY 6 FT.

- SCHEDULE 40 BLACK STEEL PIPE SUPPORT

MAXIMUM EVERY 12 FT.

DISTANCE BETWEEN SUPPORTS:

PER TABLE 308.5 OF THE FLORIDA

PLUMBING CODE 2017

C-CLAMP PIPE HANGER FOR

TOP ANGLE

3/8" ALL THREAD ROD

ADJUSTABLE SWIVEL

PIPE HANGER RING

BAR JOIST

NTSPIPE HANGER DETAILNTSWATER HAMMER ARRESTOR DETAIL

WATER HAMMER ARRESTOR.

INSTALL PER MANUFACTURERS

RECOMMENDATIONS.

WATER SUPPLY

WATER SUPPLY TO

PLUMBING FIXTURE

WATER HAMMER ARRESTOR.

INSTALL PER MANUFACTURERS

RECOMMENDATIONS.

WATER SUPPLY

WATER SUPPLY TO

PLUMBING FIXTURES

WATER HAMMER

ARRESTOR SIZE

MODEL CONNECTION

DIA

FIXTURE

UNITS

CROSS

REFERENCE

PDI

LF15M2-A 1/2 1-11 A

LF15M2-B 3/4 12-32 B

LF15M2-C 1 33-60 C

LF15M2-D 1 61-113 D

LF15M2-E 1 114-154 E

LF15M2-F 1 155-330 F

SIZING BASED ON WATTS SERIES LF15M2

4 2

NTSP-520 SURGEONS SCRUB SINK DETAIL5

NTSP-505 CLINIC SERVICE SINK ROUGH-IN DETAIL3

A.

B.

C.

D.

E.

F.

G.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

1.

2.

A.

B.

A.

B.

C.

D.

E.

F.

GENERAL REQUIREMENTS FOR ANTI SCALD VALVES (THERMOSTATIC MIXING VALVE):

MEET ASSE REQUIREMENTS FOR WATER TEMPERATURE CONTROL FOR INTEND USE

BE " LEAD FREE" COMPLYING WITH NSF 372 (ASSE 1071 TYPES EXCLUDED)

HAVE CAST BRONZE BODIES WITH CORROSION RESISTANT INTERNAL PARTS PREVENTING SCALE AND BIOFILM BUILD-UP HAVE INTERNAL PARTS ABLE TO WITHSTAND DISINFECTING OPERATIONS OF CHEMICAL AND THERMAL TREATMENT OF WATER

TEMPERATURE UPTO 82.2 DEG C (180 DEG F)

ALLOW EASY TEMPERATURE ADJUSTMENTS TO ALLOW HOT WATER CIRCULATIONS

HAVE INTEGRAL CHECK VALVES WITH SCREENS AND STOP

THE DEVICE SHALL HAVE AN INTEGRAL MEANS OF BYPASS TO ALLOW FOR THERMAL ERADICATION OF THE DOMESTIC HOT WATER

SYSTEM.

INSTALLATION OF THE ANTI-SCALD DEVICE

THE INSTALL SHOULD BE AWARE OF THEIR RESPONSIBILTY AND DUTY OF CARE TO ENSURE ALL ASPECTS OF THE INSTALLATION COMPLY

WITH CURRENT REGUALTIONS AND LEGISLATION.

ANTI-SCALD DEVICE SHOULD BE INSTALLED USING THE APPROPRIATE STANDARD, CODE OF PRACTICE AND LEGISLATION APPLICABLE TO

THE VETERANS HEALTH ADMINISTRATION.

THE ANTI-SCALD DEVICE MUST BE INSTALLED BY A LICENSED PLUMBER.

PRIOR TO INSTALLATION, THE SYSTEM MUST BE CHECKED TO ENSURE THAT THE SYSTEM OPERATING CONDITIONS FALL WITHIN THE RECOMMENDED OPERATING RANGE OF THE DEVICE. VERIFY SUPPLY TEMPERATURES, PRESSURE, RISK ASSESSMENTS, ETC.

THE SUPPLY SYSTEM INTO WHICH THE DEVICE IS TO BE INSTALLED MUST BE THOROUGHLY FLUSHED AND CLEANED TO REMOVE ANY DEBRIS WHICH MAY ACCUMULATE DURING INSTALLATION. FAILURE TO REMOVE DEBRIS WILL RESULT IN POOR PERFORMANCE .

THE DEVICE CAN BE INSTALLED IN ANY POSITION, VERTICALLY OR HORZIONTALLY. ENSURE ACCESS TO THE VALVE IS NOT OBSTRUCTED

FOR FUTURE MAINTENANCE.

HOT AND COLD WATER SUPPLIES MUST BE CONNECTED TO THE DEVICE STRICTLY IN ACCORDANCE WITH THE MARKINGS ON THE DEVICE.

INSTALL PRESSURE REDUCING VALVES AS NEEDED TO ENSURE THE PRESSURE(S) SUPPLIED TO THE DEVICE ARE WITHIN ACCEPTABLE

LIMITS.

ENSURE THE DEVICE COMES COMPLETE WITH CHECK VALVES AT HOT AND COLD INLETS.

THE TEMPERATURE OF THE HOT WATER SUPPLY AT THE POINT OF ENTRY TO THE DEVICE MUST BE A MINIMUM OF 18 DEGREES F HIGHER

THAN THE SET MIXED WATER DISCHARGE TEMPERATURE.

THE DEVICE SHALL BE INSTALLED AND SUPPORTED OR ANCHORED IN PLACE SUCH THAT THE PIPEWORK TO AND FROM THE DEVICE ARE

NOT USED TO SUPPORT THE WEIGHT OF THE DEVICE .

COMISSIONING OF THE ANTI-SCALD DEVICE

UPON COMPLETION OF THE INSTALLATION, THE DEVICE SHOULD BE TESTED AND COMMISSIONED PER PROCEDURE OUTLINED BELOW OR

AS SPECIFIED BY LOCAL AUTHORITY.

THE FOLLOWING INSTRUCTIONS SHOULD BE READ AND CAREFULLY UNDERSTOOD PRIOR TO COMMISSIONING THE DEVICE. ANY ASPECTS OF THE INSTALLATION/SYSTEM WHICH DO NOT COMPLY WITH THE INSTALLATION REQUIREMENTS OR SPECIFICATIONS MUST BE RECTIFIED

PRIOR TO BEGINNING THE COMMISSIONING PROCESS.

ENSURE THAT THE SYSTEM IS THOROUGHLY CLEAN AND FREE FROM DEBRIS.

ENSURE A SUITABLY CALIBRATED AND ACCURATE DIGITAL THERMOMETER IS USED. THE DEVICE IS COMMISSIONED BY

MEASURING THE MIXED WATER TEMPERATURE AT THE OUTLET.

IN ACCORDANCE WITH VHA DIRECTIVE 2009-009 DATED FEBRUARY 2009 AND POLICY MEMORANDUM 00-322 DATED APRIL

17 2016, MIXED WATER TEMPERATURE AT THE OUTLET MAY NOT EXCEED THE FOLLOWING:

FOR SINK TAPS: 110 DEG F

FOR FULL OR PARTIAL IMMERSION FIXTURES: 110 DEG

THE TEMPERATURE AT THE OUTLET OF EACH ANTI-SCALD DEVICE MUST BE SET TAING INTO CONSIDERATION ANY

FLUCTUATIONS WHICH MAY OCCUR WITHIN THE SYSTEM DUE TO SIMULTANEOUS DEMAND.

ONCE THE SUPPLY TEMPERATURE ARE STABILIZED AND THE NORMAL OPERATING CONDITIONS ARE ESTABLISHED, THE DEVICE CAN BE COMMISSIONED. FOLLOW THE SEQUENCE BELOR FOR COMMISSIONING THE DEVICE:

SET THE MIXED WATER DISCHARGE TEMPERATURE AS NEEDED.

MEASURE AND RECORD THE TEMPERATURE OF HOT AND COLD WATER SUPPLIES AT CONNECTIONS TO THE

VALVE.

MEASURE AND RECORD THE TEMPERATURE OF THE WATER DISCHARGING FROM THE LARGEST AND SMALLEST

VOLUME DRAW-OFF POINTS.

PERFORM THE THERMAL SHUT-OFF TEST. ISOLATE THE COLD WATER SUPPLY TO THE DEVICE AND MONITOR THE

MIXED WATER TEMPERATURE. THE OUTLET FLOW SHOULD QUICKLY CEASE FLOWING.

MEASURE AND RECORD THE MAXIMUM MIXED WATER TEMPERATURE. THE TEMPERATURE SHOULD NOT EXCEED

THE TEMPERATURE ALLOWED BY THE APPLICABLE VHA DIRECTIVE ABOVE.

RESTORE THE COLD WATER SUPPLY TO THE VALVE AND MEASURE AND RECORD THE OUTLET MIXED WATER TEMPERATURE AFTER THE MIXED WATER HAS STABILIZED. THE FINAL TEMPERATURE FOUND DURING THIS TEST

SHOULD NOT EXCEED THE PERMITTED VALUES +3 DEG F.

ONCE THE DESIRED TEMPERATURE HAS BEEN REACHED. LOCK ANY ADJUSTMENT CONTROLS ON THE DEVICE.

3. RECORD THE ABOVE INFORMATION IN A COMMISSIONING REPORT AND SUBMIT TO VA COR PRIOR TO FINAL ACCEPTANCE

4. TEMPERATURE OVERRIDE TEST:

PUT EACH ANTI-SCALD VALVE IN BYPASS MODE.

ENSURE HEAT EXCHANGER IS IN THERMAL ERADICATION MODE AND IS DISCHARGING 180F WATER.

ENSURE WATER IS STILL DISCHARGING FROM THE FAUCET. AND TEMPERATURE IS 180F.

PROVIDE AND INSTALL 3/8" O.D. MIXED

WATER CHROME COATED COPPER

TUBING, BEND IN SHAPE AS SHOWN. FLEX

HOSE NOT APPROVED.

PROVIDE AND INSTALL ANTI-SCALD

DEVICE. USE CHROME-PLATED BRASS

COMPRESSION FITTING TO CONNECT 3/8"

O.D. COPPER TUBING TO 1/2" NPT

CONNECTIONS ON DEVICE. COMMISSION

DEVICE PER INSTRUCTION ON SHEET

P-502.

PROVIDE AND INSTALL 3/8" O.D. HW CHROME

COATED COPPER TUBING, BEND IN SHAPE AS

SHOWN. FLEX HOSE NOT APPROVED.

CONNECT TO BRANCH PIPING STUBBED

THRU WALL. EXACT LOCATION OF EACH

STUB-IN MAY VARY FROM SINK TO SINK.

PROVIDE SHUTOFF VALVES IF DEFUNCT

OR DAMAGED DURING INSTALLATION.

PROVIDE AND INSTALL 3/8" O.D.

MIXED WATER CHROME COATED

COPPER TUBING, BEND IN

SHAPE AS SHOWN.

SANITARY LINE AND P-TRAP OF SINK

PROVIDE AND INSTALL ANTI-SCALD

DEVICE. PROPERLY SUPPORT PER

MANUFACTURER'S INSTRUCTIONS.

PROVIDE AND INSTALL 3/8" O.D. HW CHROME

COATED COPPER TUBING, BEND IN SHAPE AS

NEEDED.

CONNECT TO BRANCH PIPING STUBBED

THRU WALL. EXACT LOCATION OF EACH

STUB-IN MAY VARY FROM SINK TO SINK.

PROVIDE SHUTOFF VALVES IF DEFUNCT

OR DAMAGED DURING INSTALLATION.

SINK

FINISHED FLOOR

PROVIDE AND INSTALL CHROME-PLATED

BRASS COMPRESSION FITTING INTO T-

CONNECTOR.

SANITARY LINE AND P-TRAP OF SINK.

PROVIDE AND INSTALL 3/8" O.D. MIXED WATER

CHROME COATED COPPER TUBING, BEND IN

SHAPE AS SHOWN. FLEX HOSE NOT APPROVED.

18" WX24" H ACCESS PANEL ON REAR OF

WALL BEHIND SHOWER CONTROL VALVE

(TYP)

PROVIDE AND INSTALL 1/2" OR 3/4"

HW, CW SUPPLY

PROVIDE AND INSTALL 1/2" OR 3/4"

MIXED WATER SUPPLY PIPE TO

SHOWER CONTROL VALVE

1/2" OR 3/4" CW SUPPLY TO

SHOWER(TYP)

1/2" OR 3/4" HW, CW SUPPLY PIPING TO

FIRST & SECOND FLOORS. SECTION OF

PIPE INSULATION EXPOSED TO ACCESS

PANEL IS ABATED.

PROVIDE AND INSTALL ANTI-SCALD DEVICE

PROPERLY SUPPORT PER MANUFACTURER'S

INSTRUCTIONS.

SHUTOFF VALVES. PROVIDE AND INSTALL IF

DEFUNCT OR DAMAGED DURING

INSTALLATION. (TYP)

SINK FIXTURE

HEIGHT

VARIES

NTSANTI-SCALD DEVICE INSTALLATION DIAGRAMS (TYP)1

P-001 PLUMBING NOTES AND LEGENDS
PD100 PLUMBING DEMOLITION PLAN
PL100 PLUMBING RENOVATION PLAN
PW301 PLUMBING ISOMETRICS
P-501 PLUMBING DETAILS

File details come from the government source that posted it. Updated .