This document provides details on a federal contract opportunity for repair work on a medical training facility. The solicitation number is W50S6Y24B0001 and is being issued by the Department of the Army Florida Army National Guard for repair of Medical Training Facility Building 1002B. Attached to the opportunity is a 15MB PDF file containing drawings and plans for the building in Volume 1 with an effective date of September 30, 2022. Interested parties should review the drawings and specifications to understand the full scope of repair work required on the medical training facility building. The response due date and anticipated award date are not provided in this document.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
C
B
A
1 2 3 4 5 6
Date:
Proj. No.:
PLOT DATE/TIME:
www.Jacobs.com
Drawing No.:
D ra w in g T it le
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
J a c o b s E n g in e e ri n g G ro u p I n c
A
L L R
IG
H
T S
R E
S E
R V
E D
D S
G N
D R
C H
K A
P V
D
A P
V D
B Y
R E
V
IS
IO
N
D A
T E
N O
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
14300 Fang Road Jacksonville international airport, Florida 32218
Contract Number
LSGA112024
T Y
P E
B -3
F
IN
A L D
E S
IG
N
S U
B M
IT
T
A L
S
E P
T E
M B
E R
200 S. Orange Avenue, Suite 900 Orlando, Florida 32801
PH.: 407-903-5001
PRELIM
IN
ARY
NO
T F
O R C
O
NSTRUCTIO
N
Florida Architectural Corporation License #AAC001790 Florida Engineering Certificate Authorization #2822
Mark Alden Johnson, AIA State of Registration: FLORIDA Registration Number: 96440
9/27/2022 4:29:55 PM BIM 360://US FL_D3457500_FLANG_Emergency Repair Medical Training Facility Building 1002B/FLANG_BLDG1002B_ARCH_V20.rvt
09/30/2022
D3457500
G-001
E m e rg e n c y /R e p a ir M e d ic a l T ra in in g
B u ild in g
B
M J O
H N
S O
N M
J O
H N
S O
N M
H
E S
T E
R M
J O
H N
S O
N
C O
V E
R S
H E
E T
BASE CIVIL ENGINEERING
14300 FANG ROAD, JACKSONVILLE INTERNATIONAL AIRPORT, FLORIDA 32218-7933
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
PROJECT NAME:
ADDRESS:
CONTRACT NUMBER:
PROJECT NUMBER:
200 S. ORANGE AVENUE, SUITE 900
ORLANDO, FLORIDA 32801
EMERGENCY/REPAIR MEDICAL TRAINING, BLDG. 1002B
14300 FANG ROAD, BUILDING 1002B
LSGA112024
D3457500
VICINITY MAP : LOCATION MAP :
AERIAL PHOTO OF BUILDING 1002
PARTIAL SITE WITH HAUL ROUTE
1002B
1002A
1002C
STAGING
LOADING
RAMP
SECURITY
STATION
FA
N G
D R
IV
E
ENGINEERING
CONTRACTOR SHALL CONFIRM HAUL ROUTE AND STAGING
LOCATION WITH COR PRIOR TO START OF CONSTRUCTION
TERRELL ROAD
F A
N G
D R
IV
E
L E
M T
U R
N E
R R
O A
SHEET NUMBERING SYSTEM
A-210
DISCIPLINE DESIGNATOR:
G - GENERAL
LS - LIFE SAFETY
C - CIVIL
L - LANDSCAPE
S - STRUCTURAL
A - ARCHITECTURE
I - INTERIORS
F - FIRE PROTECTION
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
T - TELECOMMUNICATIONS
SHEET DISCIPLINE DESIGNATOR
SHEET TYPE DESIGNATOR
SHEET NUMBER WITHIN SERIES
SHEET TYPE DESIGNATOR:
0 - GENERAL (SYMBOLS, LEGEND, NOTES, ETC.)
1 - PLANS (HORIZONTAL VIEWS AND COMBINATION LAN AND PROFILE)
2 - ELEVATIONS AND PROFILES (VERTICAL VIEWS)
3 - SECTIONS (SECTIONAL VIEWS, CROSS SECTIONS, ETC.)
4 - LARGE SCALE VIEWS (SCALED UP REPRODUCTIONS OF PLANS,
ELEVATIONS, OR SECTIONS THAT ARE NOT DETAILS).
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - USER DEFINED
8 - USER DEFINED
9 - 3D REPRESENTATIONS (ISOMETRICS, PERSPECTIVES, PHOTOGRAPHS)
D
C
B
A
1 2 3 4 5 6
Date:
Proj. No.:
PLOT DATE/TIME:
www.Jacobs.com
Drawing No.:
D ra w in g T it le
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
J a c o b s E n g in e e ri n g G ro u p I n c
A
L L R
IG
H
T S
R E
S E
R V
E D
D S
G N
D R
C H
K A
P V
D
A P
V D
B Y
R E
V
IS
IO
N
D A
T E
N O
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
14300 Fang Road Jacksonville international airport, Florida 32218
Contract Number
LSGA112024
T Y
P E
B -3
F
IN
A L D
E S
IG
N
S U
B M
IT
T
A
P
T E
M B
E R
200 S. Orange Avenue, Suite 900 Orlando, Florida 32801
PH.: 407-903-5001
PRELIM
IN
ARY
NO
T F
O R C
O
NSTRUCTIO
N
Florida Architectural Corporation License #AAC001790 Florida Engineering Certificate Authorization #2822
Mark Alden Johnson, AIA State of Registration: FLORIDA Registration Number: 96440
9/28/2022 4:23:54 PM BIM 360://US FL_D3457500_FLANG_Emergency Repair Medical Training Facility Building 1002B/FLANG_BLDG1002B_ARCH_V20.rvt
09/30/2022
D3457500
G-002
E m e rg e n c y /R e p a ir M e d ic a l T ra in in g
B u ild in g
B
M J O
H N
S O
N M
J O
H N
S O
N M
H
E S
T E
R M
J O
H N
S O
N
S H
E E
T I N
D E
X
INDEX OF DRAWINGS
NUMBER NAME
MECHANICAL
M-001 MECHANICAL GENERAL NOTES AND SYMBOLS
M-002 MECHANICAL GENERAL NOTES AND SYMBOLS
M-101 FIRST FLOOR DEMOLITION PLAN - HVAC
M-201 FIRST FLOOR PLAN - HVAC
M-301 HVAC SECTIONS
M-401 HVAC ENLARGED PLANS
M-501 HVAC DETAILS
M-502 HVAC DETAILS
M-503 HVAC DETAILS
M-504 HVAC DETAILS
M-601 HVAC SCHEDULES
M-801 BAS CONTROL DIAGRAMS
M-802 CONTROL POINTS SCHEDULE INSTRUCTIONS
M-803 CONTROL DIAGRAMS
M-804 CONTROL DIAGRAMS
M-805 CONTROL DIAGRAMS
M-806 POINT SCHEDULE
M-807 POINT SCHEDULE
M-808 SEQUENCE OF OPERATION
ELECTRICAL
E-001 ELECTRICAL LEGEND, ABBRIEVIATIONS AND GENERAL NOTES
E-002 ELECTRICAL LEGEND, ABBRIEVIATIONS AND GENERAL NOTES
ED101 ELECTRICAL DEMOLITION PLAN
ES101 ELECTRICAL SITE PLAN
EL101 LIGHITNG PLAN
EP101 POWER PLAN
EP102 VAV POWER PLAN
E-401 ENLARGED ELECTRICAL PLANS
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-601 ELECTRICAL SINGLE LINE DIAGRAM
E-602 ELECTRICAL GROUNDING RISER DIAGRAM
E-701 FEEDER AND LIGHTING FIXTURE SCHEDULES
E-702 PANEL SCHEDULES
E-703 PANEL SCHEDULES
E-704 ELECTRICAL SCHEDULES
TELECOMMUNICATIONS
T-001 COMMUNICATIONS SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
TS101 COMMUNICATIONS SITE PLAN
TD101 COMMUNICATIONS - DEMOLITION PLAN
T-101 COMMUNICATIONS PLAN
T-201 RACK AND WALL ELEVATIONS
T-202 TV MONITOR ELEVATIONS
T-401 ENLARGED PLANS
T-501 OUTLET DETAILS
T-502 OUTLET INSTALLATION DETAILS
T-503 CABLE TRAY DETAILS
T-504 CONDUIT AND CABLE TRAY DETAILS
T-505 GROUNDING AND BONDING DETAILS
T-601 VOICE AND DATA ONE-LINE DIAGRAM
T-602 ONE-LINE DIAGRAMS
INDEX OF DRAWINGS
NUMBER NAME
GENERAL
G-001 COVER SHEET
G-002 SHEET INDEX
LS101 LIFE SAFETY FLOOR PLAN
STRUCTURAL
S-001 STRUCTURAL GENERAL NOTES AND WIND PRESSURES
S-501 STRUCTURAL DETAILS
ARCHITECTURAL
A-001 ABBREVIATIONS, SYMBOLS AND GENERAL NOTES
A-002 MOUNTING HEIGHTS
A-003 EXTERIOR BUILDING IMAGES
AD100 FLOOR PLAN - DEMOLITION
A-101 FIRST FLOOR PLAN
A-102 FIRST FLOOR PLAN - DIMENSIONS AND STC RATINGS
A-103 FIRST FLOOR EQUIPMENT PLAN
A-104 REFLECTED CEILING PLAN
A-201 EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-401 ENLARGED PLANS
A-501 PLAN DETAILS, CEILING DETAILS
A-502 PARTITION TYPES, STC RATINGS
A-601 DOOR SCHEDULE
A-602 DOOR, FRAME, AND WINDOW TYPES AND DETAILS
A-603 PRECAST DOOR AND WINDOW DETAILS
A-604 PLASTER/CMU DOOR, WINDOW AND LOUVER DETAILS
INTERIORS
I-101 FLOOR FINISH PLAN
I-102 SIGNAGE PLAN
I-201 INTERIOR ELEVATIONS
I-501 MILLWORK DETAILS
I-502 MILLWORK DETAILS
I-601 FINISH SCHEDULE AND FINISH DETAILS
I-602 ROOM FINISH SCHEDULE
I-607 SIGNAGE SCHEDULE
I-608 SIGNAGE DETAILS
FIRE PROTECTION
FA001 FIRE ALARM AND MASS NOTIFICATION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
FA101 FIRE ALARM AND MASS NOTIFICATION CEILING PLAN
FA501 FIRE ALARM AND MASS NOTIFICATION DETAILS
FS001 FIRE SUPPRESSION GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
FS002 FIRE SUPPRESSION SITE PLAN
FS101 FIRE SUPPRESSION FLOOR PLAN
FS501 FIRE SUPPRESSION DETAILS
PLUMBING
P-001 GENERAL NOTES, LEGENDS, AND ABBREVIATIONS
P-101 LEVEL 1 - PLUMBING - EXISTING/DEMO
P-201 LEVEL 1 - PLUMBING - DOMESTIC SUPPLY PLAN
P-202 LEVEL 1 - PLUMBING - DWV
P-203 ROOF - PLUMBING - PLAN
P-204 PLUMBING ENLARGED PLANS
P-501 DETAILS
P-502 DETAILS
P-503 DETAILS
P-601 SCHEDULES
P-701 PLUMBING ISOMETRIC DIAGRAMS
P-803 CONTROLS
WH
R
EF
CP
13/
09/
SCA
LE:
0,5
SC
AL
E 1, PR
IN
TE
R
PO
W
ER
CO
RD
IN
LE
T
9,4
14,9 4")
358,1 (14,1")
136,2 (5,36")
0-6 0 E
LE
CTR
O
NI
C
VIT
AL
SI
G
NS
M O
BI
LE
STA
ND
A .V
2/
1/2
S
CAL
E:
.5
:15
EQ
SP
ACE
22.0000
3.2428
7.9990
.1325
2.8200
CP
13/
09/
SCA
LE:
0,5
SC
AL
E 1, PR
IN
TE
R
PO
W
ER
CO
RD
IN
LE
T
9,4
14,9 4")
358,1 (14,1")
136,2 (5,36")
0-6 0 E
LE
CTR
O
NI
C
VIT
AL
SI
G
NS
M O
BI
LE
STA
ND
A .V
2/
1/2
S
CAL
E:
.5
:15
EQ
SP
ACE
22.0000
3.2428
7.9990
.1325
2.8200
CP150
2013/09/09 SCALE:0,500
SCALE
1,000
PRINTER
POW
ER CORD INLET
379,42 (14,94")
358, 1 ( 14,1")
136, 2 ( 5, 36")
0-6 0 E
LE
CTR
O
NI
C
VIT
AL
SI
G
NS
M O
BI
LE
STA
ND
A .V
2/
1/2
S
CAL
E:
.5
:1 5
EQ
SP
ACE
22.0000
3.2428
7.9990
.1325
2.8200
CP150
2013/09/09 SCALE:0,500
SCALE
1,000
PRINTER
POW
ER CORD INLET
379,42 (14,94")
358, 1 ( 14,1")
136, 2 ( 5, 36")
0-6 0 E
LE
CTR
O
NI
C
VIT
AL
SI
G
NS
M O
BI
LE
STA
ND
A .V
2/
1/2
S
CAL
E:
.5
:1 5
EQ
SP
ACE
22.0000
3.2428
7.9990
.1325
2.8200
FB1 FB1FB1
FB1 FB1FB1
FB
FB
FB
FB
FB
FB1 FB1FB1
FB
FB
FB
FB1 FB1FB1
FB1 FB1FB1
FB1 FB1FB1
FB1 FB1FB1
FB
FB
1 FB1
FB
FB
FB1 FB1FB1
FB1 FB1FB1
FB
FB
FB1
FB1 A
B
C
D
1 2 3 4 5 6
CC
BB
AA
2.4
3.6
B'
0.2
0.2
0.2
0.2
OFFICE
OFFICE
OFFICE
OPEN OFFICE
OPEN OFFICE
CONFERENCE
CLASSROOM
SIM RM.
STORAGE
OFFICE
BREAK RM.
OFFICE
OFFICE
OFFICE
OPEN OFFICE
LAB STOR BIO
ENV
EQUIP.
CLINICAL LAB
M. TOILET
PHARMACY
F. TOILET
M. SHOWER
J. CLO.
STORAGE
F. SHOWER
COMM.
ELECT.
CORRIDOR
MECH.
EXAM RM.
EXAM RM.
EXAM RM.
EXAM RM.
EXAM RM.
EXAM RM.
OPEN OFFICE
OPEN OFFICE
DENTAL EXAM.
DENTAL EXAM.
OPEN OFFICE
EXAM RM.
OFFICE
OFFICE
114WAITING
OFFICE
FA CLO.
VESTIBULE
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
STO.
OPEN OFFICE
CORRIDOR
OFFICE
L
F
F
L
C P
TD
CP = 43
TD = 85
C P
TD = 80
OPEN OFFFICE
0.2
GENERAL NOTES
1. ENSURE THE CONTINUITY AND MAINTAIN THE PRIORITY OF RATED ASSEMBLIES THAT ARE
INDICATED.
2. PROVIDE THROUGH PENETRATION FIRE STOPPING SYSTEM AT ALL PENETRATIONS THROUGH
RATED PARTITIONS. WHERE A PARTITION IS INDICATED TO BE FIRE RATED, PROVIDE A THROUGH
PENETRATION FIRE STOPPING SYSTEM CONSTRUCTED IN STRICT COMPLIANCE WITH THE FIRE
TEST DESIGN (TESTED AND COMPATIBLE WITH LEVEL OF RATING INDICATED) AT ALL
PENETRATIONS. IF NO TEST IS REFERENCED, PROVIDE AN INDUSTRY RECOGNIZED FIRE TEST
APPLICABLE TO THE PARTITION TYPE. SYSTEMS MUST BE COMPATIBLE WITH PARTITION
CONSTRUCTION. REFER TO DISCIPLINE DRAWINGS FOR PENETRATION LOCATIONS.
3. PROVIDE CONTINUOUS SEALANT AT TOPS AND BOTTOMS OF ALL SMOKE PARTITIONS AND AT ALL
PENETRATIONS THROUGH SMOKE PARTITIONS COMPATIBLE WITH THE PARTITION AND ALLOWING
FOR STRUCTURAL MOVEMENT.
4. REFER TO FIRE ALARM AND MASS NOTIFICATION, FIRE PROTECTION, AND ELECTRICAL FOR
LOCATION OF FIRE ALARM NOTIFICATION, MANUAL PULL STATIONS, AND EXIT SIGNAGE.
5. FOR EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS REFER TO ELECTRICAL.
6. PORTABLE FIRE EXTINGUISHERS MUST BE INSTALLED IN ACCORDANCE WITH NFPA 10.
7. INSTALL FIRE EXTINGUISHER SIGN AT FIRE EXTINGUISHER.
LEGEND
A.
B.
C.
D.
E.
F.
G.
USE (OCCUPANT LOAD FACTOR IN SQFT/PERSON)
BUSINESS (150 GROSS)
ASSEMBLY
F DENOTES FIXED SEATING (NUMBER OF CHAIRS)
L DENOTES LESS CONCENTRATED (15 NET)
MECHANICAL/ELECTRICAL/STORAGE (500 GROSS)
FIRE RESISTANCE RATING
1 HOUR FIRE RESISTANCE
(BARRIER)
TRAVEL DISTANCE (MEASURED IN FEET)
MAXIMUM PERMITTED
BUSINESS: 300 FEET
COMMON PATH (MEASURED IN FEET)
MAXIMUM PERMITTED
BUSINESS: 100 FEET
DEAD END CORRIDOR (MEASURED IN FEET)
MAXIMUM PERMITTED
BUSINESS: 50 FEET
EGRESS CAPACITY
W = EXIT CAPACITY FACTOR
(IN/PERSON)
X = OCCUPANTS USING EXIT
(PERSONS)
Y = EXIT CAPACITY (PERSONS)
Z = EXIT CLEAR WIDTH (IN)
FIRE EXTINGUISHER
W
Z
X
Y
CP = XX
TD = XX
DE = XX
XX
XX
XX
X
KEYNOTE
1. TOTAL BUSINESS USE OCCUPANT LOAD
FB1 FB1 FB1
D
C
B
A
1 2 3 4 5 6
Date:
Proj. No.:
PLOT DATE/TIME:
www.Jacobs.com
Drawing No.:
Pr oj ec t T itl e:
D ra w in g Ti tle
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Ja co bs
E ng in ee rin g
G ro up In c.
A
LL
R
IG
H
TS
R
ES
ER
V
ED
D
SG
N D
R C
H K
AP
VD
AP
VD
BY
R
EV
IS
IO
N
D
AT
E N
O
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
14300 Fang Road Jacksonville international airport, Florida 32218
Contract Number
LSGA112024
TY
PE
B -3
F
IN
AL
D
ES
IG
N S
U
BM
IT
TA
L
SE
PT
EM
BE
R
0, 200 S. Orange Avenue, Suite 900 Orlando, Florida 32801
PH.: 407-903-5001
PRELIMINARY
NOT FOR CONSTRUCTION
Florida Architectural Corporation License #AAC001790 Florida Engineering Certificate Authorization #2822
Jeffrey C. McLaughlin, PE State of Registration: FLORIDA Registration Number: 71830
H
EA
D Q
U A
R
TE
R S
-1
A
M
ED
. C
LI
N
IC
B
R
EN
O
VA
TI
O
N D
IN
IN
G
C
PLAN
NORTH
KEY PLAN - NEW
1" = 60'
9/27/2022 3:22:08 PM BIM 360://US FL_D3457500_FLANG_Emergency Repair Medical Training Facility Building 1002B/FLANG_BLDG1002B_FPRO_V20.rvt
09/30/2022
D3457500
LS101
Em er ge nc y/ R ep ai r M ed ic al
T ra in in g Bu ild in g
B
JC
M
D
PF
JA
B
Ap pr ov er
LI
FE
S
AF
ET
Y
FL
O
O R
P
LA
N
1/8" = 1'-0"D1 LIFE SAFETY FLOOR PLAN
0 4' 8' 16'
A. GENERAL BUILDING AND DESIGN CODES:
1. THE FLORIDA BUILDING CODE 2020.
2. ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES, THE LATEST EDITION ADOPTED BY GOVERNING CODE.
3. AISC MANUAL OF STEEL CONSTRUCTION AND CODE OF STANDARD
PRACTICE, THE LATEST EDITION ADOPTED BY GOVERNING CODES.
4. ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE,
THE LATEST EDITION ADOPTED BY GOVERNING CODES.
5. TMS 402 BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR
MASONRY STRUCTURES, THE LATEST EDITION ADOPTED BY GOVERNING
CODES.
6. UFC 1-200-01, GENERAL BUILDING REQUIREMENTS, WITH CHANGE 1,
OCTOBER1, 2020.
7. UFC 3-301-01, STRUCTURAL ENGINEERING, OCTOBER 1, 2019.
8. UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS,
WITH CHANGE 1, AUGUST 19, 2020.
B. DESIGN LOADS:
1. DEAD LOADS
a. ROOF DEAD LOADS 20 PSF (INCLUDING SELF-WEIGHT OF MATERIALS)
2. LIVE LOADS
a. ROOF LIVE LOADS 20 PSF
b. REDUCTION OF LIVE LOADS:
1. LIVE LOADS HAVE BEEN REDUCED IN DESIGNS USING THE
STANDARD PROCEDURE FROM THE BUILDING CODE.
3. WIND LOADS:
a. ULTIMATE DESIGN WIND SPEED (3 SECOND GUST) – 124 MPH
b. NOMINAL DESIGN WIND SPEED (3-SECOND GUST) – 96 MPH
c. BUILDING RISK CATEGORY: II
d. WIND EXPOSURE CATEGORY: C
e. ENCLOSURE CLASSIFICATION: ENCLOSED
f. INTERNAL PRESSURE COEFFICIENT - GCpi = +/- 0.18
g. REFER TO COMPONENTS AND CLADDING DIAGRAMS AND PRESSURE
TABLES ON THIS SHEET.
4. RAIN LOADS:
a. 100-YEAR 1-HOUR RAINFALL INTENSITY: 4.5 IN/HOUR
b. DESIGN RAIN LOAD: 0 PSF
C. SPECIFICATIONS ARE PART OF THE CONSTRUCTION DOCUMENTS AND MUST
BE USED IN CONJUNCTION WITH THE DRAWINGS. WHERE CONFLICTS EXIST IN
THE STRUCTURAL CONTRACT DOCUMENTS, THE STRICTEST OF ALL
REQUIREMENTS AS INDICATED BY THE STRUCTURAL ENGINEER OF RECORD
SHALL GOVERN.
D. VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO BEGINNING WORK
OR FABRICATING MATERIALS. NOTIFY ARCHITECT/ENGINEER OF
DISCREPANCIES BEFORE PROCEEDING WITH ANY PHASE OF WORK.
CONTRACTOR SHALL ENSURE THAT EXISTING AND ADJACENT BUILDINGS AND
PROPERTY ARE NOT DAMAGED DURING CONSTRUCTION. VERIFY THE
LOCATION OF CHASES, INSERTS, OPENINGS, SLEEVES, FINISHES,
DEPRESSIONS, PADS, AND WALL OPENINGS.
E. CONTRACTOR SHALL SHORE ALL EXISTING CONSTRUCTION WHEREVER
EXISTING SUPPORTS ARE REMOVED TO ALLOW FOR THE INSTALLATION OF
NEW CONSTRUCTION WORK. SHORING DESIGN SHALL BE THE RESPONSIBILITY
OF THE CONTRACTOR AND THEIR ENGINEER.
F. VERIFY THE LOCATION OF CHASES, INSERTS, OPENINGS, SLEEVES, FINISHES,
DEPRESSIONS, PADS, AND WALL OPENINGS.
G. DO NOT SCALE DRAWINGS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS.
H. DETAIL LABELS CONTAINING "TYPICAL”, OR “TYP” ON DRAWINGS APPLY TO
SITUATIONS OCCURRING ON THE PROJECT THAT ARE THE SAME OR SIMILAR
TO THOSE SPECIFICALLY DETAILED. SUCH DETAILS APPLY WHETHER OR NOT
DETAILS ARE REFERENCED AT EACH LOCATION. NOTIFY ENGINEER OF
CONFLICTS REGARDING APPLICABILITY OF "TYPICAL DETAILS".
I. THE STRUCTURE, IN ITS FINAL AND COMPLETED STATE, HAS BEEN DESIGNED
FOR THE LOADS IDENTIFIED WITHIN THESE STRUCTURAL DRAWINGS. THE
CONTRACTOR SHALL ENSURE THAT THE STRUCTURE IS NOT OVERLOADED
DURING THE CONSTRUCTION PROCESS. CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING THE ADEQUACY OF THE AS-BUILT STRUCTURE
TO SUPPORT ANY APPLIED CONSTRUCTION LOADING, INCLUDING BUT NOT
LIMITED TO THOSE DUE TO VEHICLES, EQUIPMENT, MATERIAL
HANDLING/STORAGE, SHORING, RESHORING, OR ANY OTHER ITEMS NOT
ENUMERATED RELATED TO CONSTRUCTION ACTIVITIES. THE CONTACTOR
SHALL SUBMIT CALCULATIONS SIGNED AND SEALED BY AN ENGINEER IN THE
STATE OF THE PROJECT THAT VALIDATE THE ADEQUACY OF THE AS-BUILT
SYSTEM FOR ANY PROPOSED LOADS IN EXCESS OF THOSE NOTED IN THESE
DRAWINGS.
J. THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF
CONSTRUCTION. PROVIDE ALL MEASURES REQUIRED TO PROTECT THE
STRUCTURE, WORKMEN, AND OTHER PERSONS DURING CONSTRUCTION;
INCLUDING BUT NOT LIMITED TO BRACING, SHORING FOR CONSTRUCTION
EQUIPMENT, SHORING FOR THE BUILDING, FORMS, AND SCAFFOLDING,
SHORING OF RETAINING WALLS, AND OTHER TEMPORARY SUPPORTS AS
REQUIRED.
K. PRINCIPAL OPENINGS THROUGH THE FRAMING ARE SHOWN ON DRAWINGS.
EXAMINE THE DRAWINGS OF ALL OTHER PROJECT DISCIPLINES FOR ANY
REQUIRED OPENINGS AND PROVIDE FRAMING OR REINFORCEMENT AS
REQUIRED FOR THOSE OPENINGS WHETHER EXPLICITLY SHOWN ON THE
STRUCTURAL DRAWINGS OR NOT. VERIFY SIZE AND LOCATION OF OPENINGS
WITH THE RELEVANT DISCIPLINE SUBCONTRACTORS. DEVIATIONS FROM THE
OPENINGS SHOWN ON THE STRUCTURAL DRAWINGS MUST BE APPROVED
PRIOR TO IMPLEMENTING THE CHANGES. SUBMIT ALL ANTICIPATED OPENINGS
THROUGH THE STRUCTURE TO THE ENGINEER OF RECORD FOR REVIEW.
L. DO NOT CUT OR DRILL THROUGH EXISTING REINFORCING OR TENDONS. X-RAY
TO LOCATE REINFORCING OR CABLE TENDONS AT LOCATIONS REQUIRING
CUTTING OR CORING PRIOR TO START OF CONSTRUCTION. SUBMIT
REINFORCEMENT LOCATION IN CONFLICT WITH DRAWINGS FOR ARCHITECT
AND ENGINEER REVIEW.
GENERAL NOTES
A. PROVIDE STRUCTURAL STEEL OF THE FOLLOWING ASTM DESIGNATIONS
UNLESS OTHERWISE NOTED:
1. M- AND S-SHAPES, CHANNELS AND ANGLES – ASTM A36
2. HIGH STRENGTH BOLTS (SLIP CRITICAL JOINTS FOR ALL BRACES WHERE
SPECIFIED) – ASTM F3125 GRADE A325 OR ASTM F3125 GRADE F1852
3. HARDENED STEEL WASHERS – ASTM F436
4. HEAVY HEX NUTS – ASTM A563
B. WELD MINIMUM SIZE AND STRENGTH
1. PROVIDE MINIMUM SIZE OF FILLET WELDS AS SPECIFIED IN TABLE J2.4 OF
THE AISC MANUAL.
2. PROVIDE MINIMUM EFFECTIVE THROAT THICKNESS OF PARTIAL
PENETRATION GROOVE WELDS AS SPECIFIED IN TABLE J2.3 OF THE AISC
MANUAL.
3. DEVELOP THE FULL TENSILE STRENGTH OF THE MEMBER ELEMENT JOINED
ON ALL SHOP AND FIELD WELDS UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
STRUCTURAL STEEL NOTES
B. WELD MINIMUM SIZE AND STRENGTH
1. WHERE CONNECTIONS ARE NOTED ON DRAWINGS AS MOMENT
CONNECTIONS AND REACTIONS ARE NOT PROVIDED, PROVIDE WELDS TO
DEVELOP FULL PLASTIC FLEXURAL CAPACITY OF THE LESSER MEMBER.
2. PROVIDE ELECTRODES FOR FIELD OR SHOP WELDING THAT CONFORM TO
AWS D1.1 CLASS E70XX.
C. PROVIDE BOLTS, NUTS, AND WASHERS THAT ARE HOT DIP GALVANIZED
ACCORDING TO ASTM A153, CLASS C WHEN USED TO CONNECT STEEL
ELEMENTS THAT ARE HOT DIP GALVANIZED AFTER FABRICATION.
D. STEEL FABRICATION
1. FABRICATE AND ASSEMBLE STRUCTURAL MEMBERS/ASSEMBLIES IN SHOP
TO GREATEST EXTENT POSSIBLE.
2. CAMBER OF STRUCTURAL STEEL MEMBERS IS INDICATED ON THE
DRAWINGS. WHERE POSSIBLE, CAMBER OF BEAMS TO BE APPLIED BY
COLD BEND PROCESS. CAMBERS INDICATED ON DRAWINGS ARE INTENDED
TO BE FINAL CAMBERS AT TIME OF ERECTION.
3. SPLICING OF STRUCTURAL STEEL MEMBERS IS PROHIBITED WITHOUT
PRIOR APPROVAL BY THE ENGINEER OF RECORD.
4. BE RESPONSIBLE FOR ALL ERRORS OF DETAILING ON THE SHOP
DRAWINGS, ERRORS IN FABRICATION, AND THE CORRECT FITTING OF
STRUCTURAL STEEL MEMBERS.
E. CONFORM TO THE AISC CODE OF STANDARD PRACTICE FOR ERECTION
TOLERANCES. FIELD MODIFICATION TO STRUCTURAL STEEL IS PROHIBITED
WITHOUT PRIOR APPROVAL BY THE ENGINEER OF RECORD.
F. CLEAN STEEL OF RUST, LOOSE MILL SCALE, AND OTHER FOREIGN MATERIALS
WHERE REQUIRED FOR FABRICATION, FITTING UP, OR WELDING.
G. DO NOT CUT STRUCTURAL STEEL MEMBERS FOR THE WORK OF OTHER
TRADES WITHOUT PRIOR REVIEW AND APPROVAL OF THE ENGINEER OF
RECORD.
H. EXAMINE THE ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR OTHER
ITEMS THAT REQUIRE HOT-DIP GALVANIZATION.
I. FURNISH STEEL SHOP DRAWINGS FOR ARCHITECT'S AND STRUCTURAL
ENGINEER'S REVIEW PRIOR TO FABRICATION. INCLUDE WELDING
PROCEDURES, TESTING PROGRAMS FOR WELDING AND HIGH STRENGTH
BOLTING, COATING MATERIAL, AND ERECTION SEQUENCE ON SHOP
DRAWINGS. SHOP DRAWINGS SUBMITTED WITHOUT COMPLETE DESIGN
CALCULATIONS WHERE APPLICABLE WILL NOT BE REVIEWED. WHERE
PREDESIGNED CONNECTIONS ARE TAKEN DIRECTLY FROM TABLES IN THE AISC
MANUAL, CALCULATIONS NEED NOT BE SUBMITTED PROVIDED CONNECTION
DESIGN CONDITIONS PRECISELY MATCH THOSE ASSUMPTIONS IN THE AISC
MANUAL. CONNECTION SPECIALTY ENGINEER IS RESPONSIBLE FOR ENSURING
AISC MANUAL TABULAR CONNECTIONS MEET THE PRESCRIBED LIMITATIONS.
STRUCTURAL STEEL NOTES CONTINUED
STRUCTURAL MASONRY NOTES
A. REINFORCED MASONRY WORK AND MATERIALS TO BE IN ACCORDANCE WITH
THE BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES TMS 402.
B. REINFORCED MASONRY TO CONFORM TO THE SPECIFICATIONS FOR MASONRY
STRUCTURES TMS 602 (WITH THE EXCEPTIONS NOTED IN JOB
SPECIFICATIONS).
C. PROVIDE CONCRETE MASONRY UNITS (CMU) OF NORMAL WEIGHT (125 PCF
MINIMUM), CONFORMING TO THE LATEST EDITION OF ASTM C90. LAY UNITS IN
RUNNING BOND UNLESS OTHERWISE NOTED.
D. PROVIDE PORTLAND CEMENT/LIME MASONRY MORTAR MEETING THE
REQUIREMENTS OF TYPE M OR S PER ASTM C270. PROVIDE MORTAR WITH A
MINIMUM COMPRESSIVE STRENGTH OF 1,800 PSI AT 28 DAYS.
E. PROVIDE MASONRY GROUT WITH MINIMUM 28-DAY COMPRESSIVE STRENGTH
OF 3,000 PSI TESTED IN ACCORDANCE WITH ASTM C1019. GROUT TO MEET THE
MINIMUM REQUIREMENTS SPECIFIED IN ASTM C476.
F. PROVIDE MASONRY ASSEMBLAGES WITH MINIMUM SPECIFIED MASONRY
COMPRESSIVE STRENGTH (f'm) OF 2,500 PSI, AS ESTABLISHED BY THE UNIT-
STRENGTH METHOD OR PRISM TESTING (UNIT STRENGTH ON NET AREA SHALL
BE 2,000 PSI).
G. PROVIDE CONCRETE MASONRY UNITS IN ACCORDANCE WITH ASTM C426
LIMITS FOR DRYING SHRINKAGE OF CONCRETE BLOCKS.
H. PROVIDE VERTICAL REINFORCEMENT IN CMU WALLS AS SHOWN IN DRAWINGS.
FILL THE REINFORCED CELLS SOLIDLY WITH GROUT. MAXIMUM HEIGHT OF
GROUT POURS TO BE AS PER ACI 530, TABLE 1.20.1.
I. PROVIDE HORIZONTAL JOINT REINFORCING IN WALLS AT 16 INCHES ON
CENTER VERTICAL SPACING. SPACE JOINT REINFORCEMENT AT 8 INCHES ON
CENTER IN PARAPETS OR CANTILEVERED WALLS. LAP SPLICE ENDS A MINIMUM
OF 12 INCHES AT SPLICES. PROVIDE PRE-FABRICATED T- AND L-SHAPED UNITS
AT WALL INTERSECTIONS AND CORNERS. JOINT REINFORCING SHALL BE HOT-
DIP GALVANIZED LADDER TYPE CONFORMING TO ASTM A1064, WITH THE SIZES
PER BELOW:
• 8" NOMINAL WIDTH WALLS: 9 GAGE DIAMETER (W1.7)
J. MINIMUM REINFORCEMENT OF MASONRY UNITS SHALL BE (1)-#5 VERTICAL AT
48”, (1)-#5 VERTICAL AT EACH CORNER, (1)-#5 VERTICAL AT EACH SIDE OF
OPENINGS UP TO 12’-0” WIDE AND (2)-#5 VERTICAL AT EACH SIDE OF OPENINGS
LARGER THAN 12’-0” WIDE. REFER TO THE DRAWINGS FOR REINFORCING
REQUIREMENTS ABOVE THE MINIMUMS LISTED HEREIN.
K. LAY HOLLOW UNITS WITH FULL MORTAR COVERAGE ON HORIZONTAL AND
VERTICAL FACE SHELLS. PROVIDE FULL MORTAR COVERAGE FOR WEBS WHEN
ADJACENT TO GROUTED CELLS.
L. ALIGN VERTICAL CELLS TO BE FILLED WITH GROUT TO PROVIDE CONTINUOUS
UNOBSTRUCTED VERTICAL CELLS. REMOVE OVERHANGING MORTAR OR
OTHER OBSTRUCTION AND DEBRIS FROM THE INSIDES OF SUCH CELL WALLS.
PROVIDE GROUT WITH 8 INCH SLUMP AND CONSOLIDATE BY MEANS OF HAND
TAMPING TO ENSURE COMPLETE FILLING OF CELLS.
M. INSTALL ANCHORS, ACCESSORIES, AND OTHER ITEMS TO BE BUILT IN AS WORK
PROGRESSES.
N. LAP SPLICE VERTICAL REINFORCING MINIMUM OF 48 BAR DIAMETERS OR 24
INCHES, WHICHEVER IS GREATER. POSITION LAPS SUCH THAT THEY DO NOT
OCCUR THROUGH INTERSECTING BOND BEAMS.
O. PERFORM CUTTING AND FITTING OF MASONRY WITH MASONRY SAWS
PROVIDING CUT FINISHED UNITS.
P. CELLS AT OR BELOW FINISHED GRADE ARE TO BE GROUTED SOLID.
A. INSTALL ANCHORS IN ACCORDANCE WITH CURRENT ICC-ES REPORT FOR THE
ANCHOR AND PER THE MANUFACTURER'S PRINTED INSTALLATION
INSTRUCTIONS.
B. INSTALL ANCHORS PERPENDICULAR TO THE FACE OF CONCRETE. DEVIATION
FROM PERPENDICULAR GREATER THAN 10 DEGREES, OR GREATER THAN
PERMITTED BY THE MANUFACTURER, WILL NOT BE ACCEPTABLE. PROVIDE
BEVELED WASHERS AS REQUIRED TO PROVIDE COMPETENT BEARING OF THE
FASTENER.
C. CREATE A TEMPLATE AT EACH ANCHOR CONNECTION LOCATION PRIOR TO
FABRICATING HOLES IN CONNECTION PLATES. MAKE TEMPLATE BY LOCATING
EXISTING REBAR WITH A PACHOMETER, GROUND-PENETRATING RADAR, PILOT
HOLES, OR THROUGH OTHER METHODS APPROVED BY THE ENGINEER OF
RECORD. NOTIFY ENGINEER OF RECORD WHERE CONFLICTS ARE FOUND FOR
EVALUATION.
D. DRILL HOLES TO DEPTH AND DIAMETER RECOMMENDED BY THE
MANUFACTURER. DO NOT ENLARGE OR REDIRECT HOLES ALONG LENGTH OF
ANCHOR.
E. DRILL HOLES IN A CONTINUOUS OPERATION. BLOW DUST FROM THE HOLE PER
THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
F. FILL ABANDONED HOLES WITH EPOXY GROUT AND DO NOT RE-USE HOLE
LOCATIONS UNLESS APPROVED BY THE ENGINEER OF RECORD. DO NOT
INSTALL ANCHORS ADJACENT TO ABANDONED HOLES WITHIN 1 EMBEDMENT
LENGTH OF THE ANCHOR TO BE INSTALLED IN ANY DIRECTION.
G. TIGHTEN NUTS AGAINST SMOOTH WASHERS TO THE MINIMUM TORQUE
RECOMMENDED BY THE MANUFACTURER.
H. PROVIDE STANDARD HOLES IN CONNECTION PLATES (EXCEPT AT BASE PLATES
WITH WELDED WASHERS) UNLESS NOTED OTHERWISE IN THE DRAWINGS.
I. AT MASONRY WALLS WITH POST-INSTALLED ANCHORS, COORDINATE
LOCATION TO OCCUR WITHIN GROUTED CELLS OR OTHERWISE ENSURE CELLS
ARE GROUTED PRIOR TO INSTALLATION OF ANCHORS. IT SHALL NOT BE
ACCEPTABLE TO INSTALL ANCHORS INTO HEAD JOINTS OF MASONRY UNLESS
DOUBLE OPEN-ENDED BLOCKS OR DOUBLE STRETCHER BLOCKS HAVE BEEN
PROVIDED WITH ENDS GROUTED SOLID. ENSURE MINIMUM EDGE DISTANCES
TO BLOCK AND HEAD JOINTS ARE MAINTAINED IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
J. EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS
SHALL CONSIST OF THE FOLLOWING ANCHOR TYPES AS PROVIDED BY HILTI,
INC (USED AS BASIS OF DESIGN) OR AN APPROVED EQUAL.
1. ANCHORAGE TO CONCRETE:
a. HILTI HIT-HY 200-R ADHESIVE ANCHORING SYSTEM.
b. MINIMUM 1/2" DIAMETER, HILTI HAS STANDARD THREADED ROD
CONFORMING TO ISO898 CLASS 5.8, GRADE 36, OR #5 REBAR
CONFORMING TO ASTM A615, GRADE 60.
c. MINIMUM EMBEDMENT = 3".
2. ANCHORAGE TO HOLLOW AND GROUT FILLED MASONRY:
a. HILTI HIT-HY 270 ADHESIVE ANCHORING SYSTEM.
b. MINIMUM 1/2" DIAMETER HILTI HAS STANDARD THREADED ROD
CONFORMING TO ISO 898 CLASS 5.8, GRADE 36.
c. MINIMUM EMBEDMENT = 2".
POST-INSTALLED ANCHOR NOTES
ASCE 7-16 ROOF DESIGN PRESSURES
NOTES:
1. WIND PRESSURES USED FOR THE DESIGN OF COMPONENTS AND CLADDING ARE SHOWN IN THE ADJACENT TABLES. PRESSURES ARE CALCULATED
USING ASCE 7-16 AND ARE ULTIMATE, FACTORED LOADS (LRFD). FOR ALLOWABLE LOAD PRESSURES, REFER TO THE LOAD COMBINATIONS IN ASCE 7-16
FOR APPROPRIATE LOAD REDUCTION FACTORS.
2. WIDTH OF END ZONE/EDGE/CORNER STRIPS (a): 15'-0", UNO
3. COMPONENT AND CLADDING PRESSURES ACT NORMAL TO THE SURFACE. POSITIVE PRESSURES ACT TOWARDS A GIVEN SURFACE AND NEGATIVE
PRESSURES ACT AWAY FROM A GIVEN SURFACE.
4. DESIGN PRESSURE FOR COMPONENTS AND CLADDING ELEMENTS SHALL NOT BE LESS THAN 16 PSF IN EITHER DIRECTION NORMAL TO THE SURFACE.
5. THE EFFECTIVE WIND AREA IS THE SPAN LENGTH MULTIPLIED BY AN EFFECTIVE WIDTH THAT NEED NOT BE LESS THAN ONE-THIRD OF THE SPAN
LENGTH. FOR CLADDING FASTENERS, THE EFFECTIVE WIND AREA SHALL NOT BE GREATER THAN THE AREA TRIBUTARY TO THE INDIVIDUAL FASTENER
IN QUESTION.
DESIGN WIND PRESSURE (PSF)
TRIB AREA
(SQ FT)
1 2e 2r
+26.5 -44.5
+22.9 -44.5
+18.1 -39.4
+16.0 -35.5
+16.0 -35.5
+26.5 -59.6
+22.9 -54.7
+18.1 -48.3
+16.0 -43.4
+16.0 -38.5
ASCE 7-16 WALL DESIGN PRESSURES
DESIGN WIND PRESSURE (PSF)
TRIB AREA
(SQ FT)
4 5
+35.5 -38.5
+33.9 -36.9
+31.8 -34.8
+30.2 -33.2
+26.5 -29.5
+26.5 -77.6
+22.9 -70.0
+18.1 -59.9
+16.0 -52.2
+16.0 -44.5
+26.5 -59.6
+22.9 -54.7
+18.1 -48.3
+16.0 -43.4
+16.0 -38.5
+35.5 -47.6
+33.9 -44.4
+31.8 -40.1
+30.2 -36.9
+26.5 -29.5
COMPONENTS AND CLADDING PRESSURES
0.6h a
2e
2r
ROOF PLAN DIAGRAM WALL ELEVATION DIAGRAM
2e
2r2e 2e1 1 a a a a a a a
5 4 5 a a a a h
D
C
B
A
1 2 3 4 5 6
Date:
Proj. No.:
PLOT DATE/TIME:
www.Jacobs.com
Drawing No.:
D ra w in g T it le
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
J a c o b s E n g in e e ri n g G ro u p I n c
A
L L R
IG
H
T S
R E
S E
R V
E D
D S
G N
D R
C H
K A
P V
D
A P
V D
B Y
R E
V
IS
IO
N
D A
T E
N O
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
14300 Fang Road Jacksonville international airport, Florida 32218
Contract Number
LSGA112024
T Y
P E
B -3
F
IN
A L D
E S
IG
N
S U
B M
IT
T
A L
S E
P T
E M
B E
R
200 S. Orange Avenue, Suite 900 Orlando, Florida 32801
PH.: 407-903-5001
PRELIM
IN
ARY
NO
T F
O R C
O
NSTRUCTIO
N
Florida Architectural Corporation License #AAC001790 Florida Engineering Certificate Authorization #2822
Brett E. Rowan, PE State of Registration: FLORIDA Registration Number: 77608
9/27/2022 2:48:16 PM BIM 360://US FL_D3457500_FLANG_Emergency Repair Medical Training Facility Building 1002B/FLANG_BLDG1002B_STRUC_V20.rvt
09/30/2022
D3457500
S-001
E m e rg e n c y /R e p a ir M e d ic a l T ra in in g
B u ild in g
B
S B
A P
T
IS
T A
S B
A P
T
IS
T A
B R
O W
A N
B R
O W
A N
S T
R U
C T
U R
A L G
E N
E R
A L N
O T
E S
A N
D W
IN
D
P R
E S
S U
R
8" CMU INFILL WALL TO MATCH
EXISTING WALL THICKNESS
#5 DOWELS TO MATCH VERTICAL
REINFORCEMENT, TYPICAL TOP AND BOTTOM.
DRILL AND EPOXY ANCHOR REBAR INTO
GROUT FILLED CELL WITH 6" MIN EMBED
T Y
P
IC
A L
M
IN
L A
P
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATIONS, DIMENSIONS, AND WALL FINISH.
2. PROVIDE #5 VERTICAL REINFORCEMENT AT EACH
END OF NEW INFILL WALL AND AT 48" ON CENTER IN
GROUT FILLED CELLS. PROVIDE HORIZONTAL JOINT
REINFORCEMENT AT 16" ON CENTER VERTICALLY.
3. DOWEL VERTICAL REINFORCEMENT INTO EXISTING
TURNDOWN SLAB AT DOOR OPENINGS.
4. AT PARTIAL INFILL WINDOWS, GROUT FILL NEW
WINDOW SILL CELLS AND PROVIDE (2) #5
HORIZONTAL, DOWEL OR HOOK INTO JAMB AS
REQUIRED.
SEE NOTE 2
EXISTING 8" CMU WALL, TYPICAL
EXISTING TIE BEAM
EXISTING WALL FOUNDATION
ROUGH OPENING, REFER TO
ARCHITECTURAL DRAWINGS. SAW
CUT NEW OPENING FOR NEW
DOOR/WINDOW. MAXIMUM CLEAR
OPENING WIDTH 4'-0"
DRILL AND EPOXY DOWEL OF SIZE TO
MATCH VERTICAL REINFORCEMENT
INTO EXISTING TIE BEAM WITH 6"
MINIMUM EMBEDMENT, TYPICAL
GROUT FILL JAMB CELLS ADJACENT
TO NEW OPENING AND PROVIDE (1)
#5 BAR
GROUT FILL LINTEL CELLS ABOVE
NEW OPENING AND PROVIDE (2) #5
NEW L5x5x5/16 STEEL LINTEL ON
INTERIOR FACE WITH 1/2" DIAMETER
HILTI HIT-HY 270 ADHESIVE ANCHORS
(BASIS OF DESIGN) AT 2'-0" MAXIMUM
SPACING CENTERED ON VERTICAL
LEG WITH 4" EDGE DISTANCE AND 2"
EMBEDMENT. PROVIDE A MINIMUM
OF (3) ANCHORS. INSTALL BEFORE
REMOVAL OF EXISTING CMU. SAW
CUT ALONG EXISTING CMU JOINT
FOR NEW STEEL LINTEL
INSTALLATION, TYPICAL BOTH ENDS
GROUT FILL CELLS AND PROVIDE (2)
#5 AT BOTTOM OF NEW WINDOW
OPENINGS. SEE NEW SLAB ON
GRADE DETAIL FOR NEW DOOR
OPENINGS
EXISTING CMU WALL
MIN BRG
8"
T Y
P
IC
A L
L A
P
DRILL AND EPOXY DOWEL OF SIZE TO
MATCH VERTICAL REINFORCEMENT
INTO EXISTING FOUNDATION WITH 6"
MINIMUM EMBEDMENT, TYPICAL EXISTING GRADE
BEAM, VERIFY IN FIELD
ROUGH OPENING, REFER
TO ARCHITECTURAL
DRAWINGS. SAW CUT
NEW OPENING FOR NEW
DOOR/WINDOW.
MAXIMUM CLEAR
OPENING WIDTH 7'-0"
NEW L5x5x5/16 STEEL
LINTEL ON ONE SIDE OF
WALL. COPE ANGLE
HORIZONTAL LEG AT BOTH
ENDS AT OPENING EXTENTS
EXISTING PRECAST NON-
LOAD BEARING WALL
TYP
6" 1/2" DIAMETER HIT-HY 200-R
ADHESIVE ANCHORS (BASIS
OF DESIGN) AT 2'-0" MAXIMUM
SPACING CENTERED ON
VERTICAL LEG WITH 4"
MINIMUM EDGE DISTANCE
AND 3" EMBEDMENT. PROVIDE
A MINIMUM OF (3) ANCHORS 1/2" EXPASION JOINT
CMU BEYOND
NEW SIDEWALK, REFER
TO ARCHITECTURAL
DRAWINGS
NEW 4" CONCRETE SLAB AT NEW EXTERIOR
DOOR OPENINGS WITH #4 AT 16" OC (3 MIN)
TERMINATED IN STANDARD HOOK. DRILL
AND EPOXY ANCHOR INTO EXISTING SLAB
WITH 6" MIN EMBEDMENT
#4 DOWELS AT 16" OC (3 MIN) TERMINATED IN
STANDARD HOOK. DRILL AND EPOXY ANCHOR INTO
GROUT FILLED CELLS WITH 6" MIN EMBEDMENT
(1) #4 CONTINUOUS, EXTEND 6" BEYOND
OPENING ON EACH SIDE AND DRILL AND
EPOXY ANCHOR INTO GROUT FILLED CELLS
15 MIL VAPOR RETARDER
EXISTING CMU WALL,
VERIFY IN FIELD
PREPARED SUB-GRADE
EXISTING INTERIOR CONCRETE SLAB
1' - 6"
NEW 4" CONCRETE SLAB AT NEW
INTERIOR DOOR OPENING REINFORCED
WITH 6x6-W1.4xW1.4 WWR. PLACE
REINFORCEMENT 1 1/2" CLEAR FROM TOP
PRECAST WALL BEYOND
#4x1'-0" DOWELS AT 2'-0" ON
CENTER. DRILL AND EPOXY
DOWELS WITH 6" EMBEDMENT
INTO EXISTING CONCRETE SLAB
#5 AT 48" ON CENTER
(3) #5 CONTINUOUS. DRILL AND EPOXY #5
DOWELS INTO EXISTING GRADE BEAM ON
EACH SIDE OF OPENING WITH 6"
EMBEDMENT
15 MIL VAPOR RETARDER
PREPARED SUB-GRADE
EXISTING INTERIOR
CONCRETE SLAB, TYPICAL
6" 6" #3 @ 12" DOWELS DRILLED
AND EPOXIED INTO SLAB
ALL AROUND PAD
ROUGHEN SURFACE AND APPLY
A BONDING AGENT PRIOR TO
PLACING PAD
12"
24"
24" #4 CONT AT PERIMETER
WITH #4 AT EACH CORNER
REINF, REFER
TO SCHED
3/4" CHAMFER
NOTES:
1. CONFIRM REQUIRED SIZE AND LOCATION OF ALL HOUSEKEEPING PADS WITH EQUIPMENT MANUFACTURER'S PRIOR TO PLACEMENT OF CONCRETE.
PROVIDE PADS AS REQUIRED, WHETHER SHOWN ON STRUCTURAL DRAWINGS OR NOT.
2. WHERE REQUIRED, COORDINATE HOUSEKEEPING PAD WITH ARCH AND MECHANICAL SO PENETRATIONS ARE PLACED BEFORE CONCRETE IS POURED.
3. ANCHOR EQUIPMENT PADS PER MFR RECOMMENDATIONS OR DESIGN, INCREASE PAD DIMENSIONS AS REQUIRED FOR ANCHOR POINTS
4. WHERE PADS HAVE RE-ENTRANT CORNERS, PROVIDE (1)-#4x4'-0" DIAGONAL BAR CENTERED ON CORNER IN EACH LAYER OF REINFORCEMENT
REFER TO PLAN, NOTE 1
't
C O
V E
R
T Y
P
/2
C L
R
T
Y P
DOWELS
3" TYP AT
THICKNESS
UP TO 6"
>6" TO 8"
>8" TO 12"
>12" TO 16"
EQUIP PAD REINFORCING SCHEDULE
WWR4x4-W4xW4 OR #4 AT 18" EW
WWR4x4-W6xW6 OR #4 AT 12" EW
#4 AT 18" EW, TOP AND BOT
#4 AT 12" EW, TOP AND BOT
REINFORCEMENT
NEW 4" CONCRETE SLAB REINFORCED
WITH 6x6-W1.4xW1.4 WWR. PLACE
REINFORCEMENT 1 1/2" CLEAR FROM TOP
#4x1'-0" DOWELS AT 2'-0" ON
CENTER AROUND PERIMETER OF
NEW SLAB. DRILL AND EPOXY
DOWELS WITH 6" EMBEDMENT
INTO EXISTING CONCRETE SLAB
15 MIL VAPOR RETARDER
PREPARED SUB-GRADE
EXISTING INTERIOR
CONCRETE SLAB, TYPICAL
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR FLOOR FINISHES.
2. REFER TO ARCHITECTURAL AND PLUMBING DRAWINGS FOR
PATCHING LOCATIONS.
E Q
E Q
D
C
B
A
1 2 3 4 5 6
Date:
Proj. No.:
PLOT DATE/TIME:
www.Jacobs.com
Drawing No.:
D ra w in g T it le
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
J a c o b s E n g in e e ri n g G ro u p I n c
A
L L R
IG
H
T S
R E
S E
R V
E D
D S
G N
D R
C H
K A
P V
D
A P
V D
B Y
R E
V
IS
IO
N
D A
T E
N O
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
14300 Fang Road Jacksonville international airport, Florida 32218
Contract Number
LSGA112024
T Y
P E
B -3
F
IN
A L D
E S
IG
N
S U
B M
IT
T
A L
S E
P T
E M
B E
R
200 S. Orange Avenue, Suite 900 Orlando, Florida 32801
PH.: 407-903-5001
PRELIM
IN
ARY
NO
T F
O R C
O
NSTRUCTIO
N
Florida Architectural Corporation License #AAC001790 Florida Engineering Certificate Authorization #2822
Brett E. Rowan, PE State of Registration: FLORIDA Registration Number: 77608
9/27/2022 2:48:17 PM BIM 360://US FL_D3457500_FLANG_Emergency Repair Medical Training Facility Building 1002B/FLANG_BLDG1002B_STRUC_V20.rvt
09/30/2022
D3457500
S-501
E m e rg e n c y /R e p a ir M e d ic a l T ra in in g
B u ild in g
B
S B
A P
T
IS
T A
S B
A P
T
IS
T A
B R
O W
A N
B R
O W
A N
S T
R U
C T
U R
A L D
E T
A
IL
S
3/4" = 1'-0"C2
CMU INFILL WALL
3/8" = 1'-0"C1
OPENING AT CMU WALL
3/8" = 1'-0"C4
OPENING AT PRECAST WALL
3/4" = 1'-0"C5
NEW SLAB AT CMU DOOR OPENING
1" = 1'-0"D2
NEW SLAB AT PRECAST DOOR OPENING
1" = 1'-0"D3
TYPICAL MECHANICAL EQUIPMENT PAD
1" = 1'-0"D1
TYPICAL SLAB PATCHING DETAIL
DRAWING ABBREVIATIONS
A ---------------------
A LABEL CLASS A DOOR
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AESS ARCHITECTURAL EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
B ---------------------
B LABEL CLASS B DOOR
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BOS BOTTOM OF STEEL
BOT BOTTOM
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CATW CATWALK
CAV CAVITY
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CI CONTINUOUS INSULATION
CJ CONTROL JOINT
CL CENTER LINE / COLUMN LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLR COLOR
CMU CONCRETE MASONRY UNIT
CDR CARD READER
COL COLUMN
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONT CONTINUE
COORD COORDINATE
COR CONTRACTING OFFICER'S REPRESENTATIVE
CORR CORRIDOR
CR CONTROL ROOM
CS CAST STONE
CTR CENTER
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ENTR ENTRANCE
EQ EQUAL
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FGL FIBERGLASS
FIN FINISH
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLG FLOORING
FLR FLOOR
FO FACE OF
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
G ---------------------
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GUT GUTTER
GYP BD GYPSUM BOARD
H ---------------------
HB HOSE BIBB
HDW HARDWARE
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HSS HOLLOW STRUCTURAL SECTION
HSRU HIGH-SPEED ROLL-UP
HT HEIGHT
I ---------------------
IBC INTERNATIONAL BUILDING CODE
ICBP INSULATED COMPOSITE BACKUP PANEL
IMP INSULATED METAL PANEL
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KPL KICKPLATE
L ---------------------
LAV LAVATORY
LBS POUND
LF LINEAR FEET (FOOT)
LIN LINEAR
LOC LOCATION
LR LOW ROOF
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFY
MTG MOUNTING
MTL METAL
MVBL MOVABLE
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PBD PARTICLEBOARD
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PL PROPERTY LINE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTN PARTITION
PWR POWER
Q --------------------
QTY QUANTITY
R --------------------
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE REFER
REC RECESSED
REC RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TD TRENCH DRAIN
TE TRANSPORTER ENCLOSURE
TEL TELEPHONE
TEMP TEMPORARY
TFF TOP OF FINISH FLOOR
THK THICKNESS
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TO TOP OF
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TYP TYPICAL
U --------------------
UNO UNLESS NOTED OTHERWISE
V --------------------
VIF VERIFY IN FIELD
W --------------------
WD WOOD
WP WORK POINT
CONCRETE/ PRECAST
CONCRETE
SOIL
CMU
STONE
FIBERGLASS BATT
INSULATION
EXPANDED POLYSTYRENE
RIGID INSULATION
EXTRUDED POLYSTYRENE
RIGID INSULATION
POLYISOCYANURATE RIGID
INSULATION / SEMI RIGID
MINERAL WOOL
GYPSUM BOARD
EXTERIOR GYPSUM
SHEATHING
EXTERIOR CEMENT BOARD
COATED GLASS MAT
WATER RESISTANT GYP BD
PLYWOOD
COVER BOARD
MATERIALS
30 MIN SMOKE RATED
FIRE RATED PARTITION LEGEND:
WOOD
ANNOTATION CALLOUTS/DRAWING SYMBOLS
INTERIOR
ELEVATION
A-101
1 SIM
Name
Elevation
A101
SIM
A101
Ref
A101
Ref
SHEET NUMBER WHERE
SECTION/DETAIL IS DRAWN
EXTERIOR
ELEVATION
SHEET NUMBER WHERE
SECTION/DETAIL IS DRAWN
SECTION
SHEET NUMBER WHERE
SECTION/DETAIL IS DRAWN
ENLARGED PLAN,
BLOW-UP DETAIL
SHEET NUMBER WHERE
SECTION / DETAIL IS DRAWN
FLOOR LEVEL
AND NAME
SHEET
KEYNOTE
1i
PLAN NORTH
Room
Rm_Occupancy
150 SF
A
1i
Room name
ROOM NAME
/ NUMBER
WINDOW TYPE
WALL TYPE
GRID / COLUMN LINE
DESIGNATOR
EQUIPMENT
NUMBER
DOOR NUMBER
REVISION TAG
NORTH ARROW W/ TRUE
NORTH INDICATION
ROOM OCCUPANCY
& AREA
INFILL PANEL TYPE
CEILING SYMBOLS LEGEND
2' X 2' ACT
CEILING
4' X 4' ACT
CEILING
2 X 2 LIGHT
FIXTURE
2 X 4 LIGHT
FIXTURE
FLUORESCENT
LIGHT
RETURN AIR
GRILLE
SUPPLY AIR
GRILLE
EXHAUST AIR
GRILLE
EXIT LIGHT - CEILING
1 HR FIRE
2 HR FIRE
VAPOR BARRIER
GYPSUM BOARD
CEILING
SAFETY: CONSTRUCTION ACTIVITIES AND THE COMPLETED CONSTRUCTION OF THE PROJECT SHALL COMPLY WITH ALL APPLICABLE SUBPARTS OF THE CURRENT OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA) REGULATIONS 29, CODE OF FEDERAL REGULATIONS (CFR) 1910 AND 1926, AND THE CURRENT
VERSION OF THE EM-385-1-1 SAFETY AND HEALTH REQUIREMENTS MANUAL.
PREVENT DAMAGE: COORDINATE ALL WORK WITH WEATHER CONDITIONS AND TEMPORARY MEASURES TO
ENSURE THAT BUILDINGS REMAIN WATERTIGHT AT ALL TIMES.
DAMAGE: DAMAGE TO THE EXISTING BUILDINGS, GOVERNMENT PROPERTY, OR GOVERNMENT EMPLOYEE
PROPERTY CAUSED BY THE CONTRACTOR SHALL BE IMMEDIATELY REPORTED TO THE COR. SUCH
DAMAGES SHALL BE REPAIRED OR THE DAMAGED ITEMS REPLACED WITH THE SAME PER GOVERNMENT
DIRECTION, AND AT NO COST TO THE GOVERNMENT OR GOVERNMENT EMPLOYEES.
BUILDING AND LIFE SAFETY CODES: THE COMPLETED CONSTRUCTION OF THE PROJECT SHALL COMPLY WITH THE CODES & REGULATIONS LISTED BELOW; AS WELL AS APPLICABLE FEDERAL, STATE, LOCAL AND
DEPOT/BASE REGULATIONS:
GOVERNMENT PUBLICATIONS:
UNIFIED FACILITIES CRITERIA:
• UFC 1-200-01, GENERAL BUILDING REQUIREMENTS
• UFC 3-101-01 ARCHITECTURE
• UFC 3-120-10 INTERIOR DESIGN
NON-GOVERNMENT PUBLICATIONS:
• IBC, INTERNATIONAL BUILDING CODE
• NFPA 101 LIFE SAFETY CODE
• OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
• ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS
WORK PLANNING AND PHASING: PLANNING OF CONSTRUCTION ACTIVITIES SHALL BE COMPLETE IN ALL REGARDS. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND THE REQUIREMENTS OF THE WORK IN SUCH DETAIL THAT PHASING AND WORK PLANS ACCOMMODATE ALL CONDITIONS AND WORK IN A MANNER ACCEPTABLE TO THE COR, AND AS REQUIRED TO PROTECT THE BUILDING WITHIN THE AFFECTED
AREA. OBTAIN A DIG PERMIT FROM PUBLIC WORKS.
CONTRACTOR VERIFICATION: ALL DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO BUILDING NEW WORK OR FABRICATING WORK TO BE INSTALLED TO ENSURE THAT ALL WORK IS FULLY COORDINATED. IF DISCREPANCIES ARE DISCOVERED BETWEEN FIELD CONDITIONS
AND DRAWINGS, OR BETWEEN DRAWINGS OF OTHER DISCIPLINES, REPORT SUCH TO THE COR
IMMEDIATELY. DEVELOP A RESOLUTION TO EACH POSSIBLE CONFLICT AS APPROVED BY THE COR PRIOR
TO PROCEEDING WITH THE IMPACTED WORK.
WATERTIGHT ASSURANCE: MAINTAIN WATERTIGHT CONDITIONS OVER ALL PORTIONS OF THE BUILDING.
COORDINATE ALL WORK WITH THE COR TO ASSURE THAT NO INTERRUPTIONS TO THE GOVERNMENT'S
ACTIVITIES OCCUR WITHOUT THE COR'S PRIOR WRITTEN APPROVAL.
MANUFACTURER'S DIRECTION: ALL WORK SHALL COMPLY WITH MANUFACTURER'S INSTALLATION
DIRECTIONS FOR EACH PRODUCT OR MATERIAL IF CONFLICTS ARISE BETWEEN PROJECT REQUIREMENTS AND MANUFACTURER'S DIRECTIONS, THE CONTRACTOR IS TO REPORT SUCH TO THE COR IMMEDIATELY.
DEVELOP RESOLUTION TO EACH POSSIBLE CONFLICT AS APPROVED BY THE COR PRIOR TO PROCEEDING
WITH THE IMPACTED WORK.
SHOP DRAWINGS: SUBMISSIONS SHALL INCLUDE THE COMPLETION OF ALL FIELD VERIFICATION PRIOR TO THE PREPARATION OF THE SUBMITTALS. COR OR A/E CANNOT FIELD VERIFY CONDITIONS FOR THE CONTRACTOR. COR OR A/E REVIEW OF SHOP DRAWINGS AND RELATED SUBMISSIONS ASSUMES THAT THE CONTRACTOR HAS ACCOUNTED FOR THE FIELD CONDITIONS IN THE SUBMISSIONS. COR OR A/E APPROVAL
IS NOT VALIDATION THAT FIELD CONDITIONS ARE ADDRESSED.
CLEAN UP: THE CONTRACTOR SHALL PROVIDE DAILY CLEANUP OF ALL CONSTRUCTION DEBRIS AS APPROVED BY THE COR. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OF ALL DEBRIS OFF OF THE DEPOTS AND FOR PROVIDING APPROVED DUMPSTER. THE CONTRACTOR SHALL PROVIDE A MINIMUM
OF 75% RECYCLING OF ALL DEMO AND CONSTRUCTION WASTE TO THE APPROPRIATE FACILITY.
DESIGN DRAWINGS: THE CONTRACTOR IS TO UNDERSTAND ALL DRAWINGS COMPLETELY. EACH ASPECT OF THE WORK MAY BE INDICATED ON ONE DISCIPLINE OR INDICATED ON MULTIPLE DISCIPLINES. REVIEW ALL INFORMATION FROM ALL DISCIPLINES AND COMPLETELY FIELD VERIFY ALL CONDITIONS BEFORE
IMPACTING EXISTING CONDITIONS OR PROVIDING NEW WORK.
DRAWINGS SCALES: THE CONTRACTOR MAY NOT SCALE THE DRAWINGS. ALL INFORMATION ON THE DRAWINGS WHETHER DIMENSIONED, OR NOT, IS TO BE FIELD VERIFIED BY THE CONTRACTOR BEFORE
COMMENCING THE WORK AND BEFORE PROCURING OR FABRICATING WORK TO BE INSTALLED.
CONTRACTOR'S FIELD VERIFICATION IS TO BE INCORPORATED INTO ALL SUBMITTALS PRIOR TO
SUBMISSION.
ANY OF THE SYMBOLS / MATERIAL REFERENCED ON THIS DRAWING MAY OR MAY NOT OCCUR AS A PART OF
THIS PROJECT AND ARE PROVIDED FOR REFERENCE ONLY.
DIFFERENT FLOOR MATERIALS SHALL MEET UNDER THE CENTERLINE OF DOORS UNLESS OTHERWISE
NOTED. REFER TO DETAILS ON A-602.
SIGNAGE SHALL BE MOUNTED ON LATCH SIDE OF DOORS WHERE SCHEDULED; REFER TO SIGNAGE
DETAILS .
REFER TO STRUCTURAL FOR SELECT DEMOLITION, NEW WALL REINFORCING, FLOOR SLAB PATCHING, ETC.
AND ADDITIONAL INFORMATION.
GENERAL CONTRACTOR SHALL COORDINATE REQUIRED BLOCKING AND SPECIFIC LOCATIONS OF ALL WALL MOUNTED EQUIPMENT, FIXTURES AND FURNISHING LOCATIONS WITH THE CONTRACTING OFFICE PRIOR TO
CONSTRUCTION, INCLUDING GOVT. PROVIDED AND INSTALLED.
REFER TO THE PROJECT MANUAL FOR GENERAL CONTRACT REQUIREMENTS AND SPECIFICATIONS.
FLOOR ELEVATIONS REFERENCED ARE TO TOP OF CONCRETE SLABS. FINISH FLOORING IS INSTALLED ON
TOP OF THE FLOOR ELEVATION. FOR RECESSED FLOORS AND CURBS REFER TO STRUCTURAL.
NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO SPECIFIC DETAILS ARE INDICATED, CONSTRUCTION SHALL CONFORM TO SIMILAR
WORK ON THE PROJECT.
EQUIPMENT LOCATIONS INDICATED ON ARCHITECTURAL DRAWINGS ARE FOR REFERENCE ONLY.
EQUIPMENT LOCATIONS SHALL BE COORDINATED WITH UTILITIES INDICATED ON CIVIL, MECHANICAL, FIRE
PROTECTION, ELECTRICAL, AND EQUIPMENT DRAWINGS.
WHILE CARE HAS BEEN TAKEN TO COORDINATE MECHANICAL AND ELECTRICAL PENETRATIONS WITH ARCHITECTURAL WORK, CONTRACTOR IS RESPONSIBLE FOR FRAMING MODIFICATIONS AND PATCHING
REQUIRED WHETHER SPECIFICALLY SHOWN OR NOT.
GENERAL CONTRACTOR SHALL PROVIDE CONTINUOUS VAPOR RETARDER TO MAINTAIN MOISTURE BARRIER AND THERMAL ENVELOPE AT ALL NEW WALLS AND FLOOR SLAB PATCHES, WHETHER NOTED ON DETAILS
OR NOT.
THE CONTRACTOR SHALL REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR THE GENERAL INTENDED LAYOUTS OF MECHANICAL, ELECTRICAL, CABLE TRAY, FIRE SUPPRESSION SYSTEMS AS THEY
OCCUR WITHIN THE FINISHED CEILING SYSTEM.
THE CONTRACTOR SHALL VERIFY FINISHED FLOOR ELEVATIONS ON EACH SIDE OF NEW WALL OPENING PENETRATIONS BETWEEN BUILDING 1002A, 1002B (PART 1 & PART 2). ANY DEVIATIONS IN HEIGHT GREATER
THAN 3/8" SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT.
UNLESS OTHERWISE NOTED LOCATE THE EDGE OF DOOR JAMBS 4 INCHES OFF OF THE FINISHED FACE OF
ADJACENT GYPSUM BOARD PARTITION AND 8" AT CMU PARTITION
GENERAL NOTES
STC 45 PARTITION
STC 50 PARTITION
SOUND RATED PARTITION LEGEND:
RECESSED
CAN LIGHT
EXIT LIGHT - WALL
SECURITY CAMERA
TELECOM - SPEAKER
FP - ALARM STROBE
TELECOM - WAP
D
C
B
A
1 2 3 4 5 6
Date:
Proj. No.:
PLOT DATE/TIME:
www.Jacobs.com
Drawing No.:
D ra w in g T it le
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
J a c o b s E n g in e e ri n g G ro u p I n c
A
L L R
IG
H
T S
R E
S E
R V
E D
D S
G N
D R
C H
K A
P V
D
A P
V D
B Y
R E
V
IS
IO
N
D A
T E
N O
125th FIGHTER WING
FLORIDA AIR NATIONAL GUARD
14300 Fang Road Jacksonville international airport, Florida 32218
Contract Number
LSGA112024
T Y
P E
B -3
F
IN
A L D
E S
IG
N
S U
B M
IT
T
A
P
T E
M B
E R
200 S. Orange Avenue, Suite 900 Orlando, Florida 32801
PH.: 407-903-5001
PRELIM
IN
ARY
NO
T F
O R C
O
NSTRUCTIO
N
Florida Architectural Corporation License #AAC001790 Florida Engineering Certificate Authorization #2822
Mark Alden Johnson, AIA State of Registration: FLORIDA Registration Number: 96440
9/27/2022 4:28:24 PM BIM 360://US FL_D3457500_FLANG_Emergency Repair Medical Training Facility Building 1002B/FLANG_BLDG1002B_ARCH_V20.rvt
09/30/2022
D3457500
A-001
E m e rg e n c y /R e p a ir M e d ic a l T ra in in g
B u ild in g
B
M J O
H N
S O
N M
J O
H N
S O
N M
H
E S
T E
R M
J O
H N
S O
N
A B
B R
E V
IA
T
IO
N
S
S Y
M B
O L S
A N
D G
E N
E R
A L
N O
T
GRAB BAR, STAINLESS STEEL 18" LONG (VERTICAL)
GRAB BAR, STAINLESS STEEL 36" LONG
SOAP DISPENSER
COAT / TOWEL HOOK
SHELF - LARGE AT 48" AFF
SHELF - SMALL AT 48" AFF
FOLD UP SHOWER SEAT
SHOWER ROD, CURTAIN AND HOOKS
MOP RACK / UTILITY SHELF
PAPER TOWEL DISPENSER / WASTE RECEPTACLE - LARGE
PAPER TOWEL DISPENSER / WASTE RECEPTACLE - SMALL
910 SANITARY NAPKIN DISPOSAL
BOBRICK - MODEL B-6806 X 18
BOBRICK - MODEL B-6806 X 36
BRADLEY 6542 SURFACE MOUNTED
BRADLEY - MODEL SA35
BRADLEY - MODEL 7512 - 36
BRADLEY - MODEL 756 - 24
BRADLEY - MODEL 9569
BRADLEY - MODEL 9539, 9537 AND 9540
BRADLEY - MODEL 9933
BRADLEY - MODEL 3565 - SURFACE-MOUNTED; PAPER TOWEL DISPENSER (TYPICAL)
BRADLEY - MODEL 3251-11 - SURFACE-MOUNTED; PAPER TOWEL DISPENSER
BRADLEY - MODEL 4722-15 - SURFACE-MOUNTED
FRAMED MIRROR - 24" WIDE X 36" HIGH AT 40" AFF BRADLEY - MODEL 780-2436-2
TOILET TISSUE DISPENSER - SURFACE MOUNTED BOBRICK - MODEL B-4288 MULTI ROLL SURFACE MOUNTED908
NOTE: MODEL NUMBERS INDICATED ARE BASIS OF DESIGN ONLY AND
ARE NOT INTENDED TO LIMIT OTHER ACCEPTABLE MANUFACTURERSRESTROOM ACCESSORIES
TOILET SEAT COVER DISPENSER - SURFACE MOUNTED BOBRICK - MODEL B-221 SURFACE MOUNTED909
GRAB BAR, STAINLESS STEEL 42" LONG BOBRICK - MODEL B-6806 X 42
GRAB BAR, STAINLESS STEEL SHOWER 'L' BOBRICK - MODEL B-6861
918 FRAMED MIRROR - 24" WIDE X 72" HIGH AT 12" AFF BRADLEY - MODEL 780-2472-2
C7 SS SPECIMEN PASS THRU BOBRICK - MODEL B-505
SEAT WALLSIDEBACKCONTROL WALLSIDE WALL BACK WALL
DUAL DRINKING FOUNTAINSACCESSIBLE DRINKING FOUNTAIN
NOTE: IN TRANSFER SHOWERS, THRESHOLDS SHALL BE FLUSH OR BEVELED WITH A
MAXIMUM EDGE HEIGHT OF 1/2-INCH, AND A MAXIMUM SLOPE OF 50%. THRESHOLDS IN
ROLL-IN SHOWER STALLS SHALL BE LEVEL WITH THE ADJACENT CLEAR SPACE.
STANDARD SHOWER STALL
HANDICAP TRANSFER SHOWER STALL
ELECTRICAL
OUTLET
NOTE: MAX HEIGHT TO OPERABLE
PART OF TOILET ACCESSORIES IS 40"
STANDARD MOUNTING HEIGHTS AND ADA /…