Appendix I.1 20210603 Plants and LOWS Work Orders and Expenses.xlsx

XLSX spreadsheet 336 KB Posted

Attached to
US Coast Guard Base Kodiak Base Operations Support Services
Solicitation number
70Z08423RKODI0001
Issued by

View the file

Other files

File Type Posted
Amendment 0009.pdf PDF
Base Kodiak BOSS Award Fee Plan_Final.pdf PDF
First page of the 1449.pdf PDF
Remaining RFI 6.22.23.xlsx XLSX spreadsheet
Amendment 0008.pdf PDF
Revised Attachment 1 - CLIN Schedule of Prices.xlsx XLSX spreadsheet
Attachment 6- Davis Bacon Act WD AK20230005 5.24.23.pdf PDF
Attachment 5- Davis-Bacon Act WD AK20230001 5.24.23.pdf PDF
Final Request for Information 5.24.23.xlsx XLSX spreadsheet
Attachment 2 - Performance Work Statement 5.24.23.pdf PDF
Final Request for Proposal 70Z08423RKODI0001 5.24.23.pdf PDF
Attachment 1 - CLIN Schedule of Prices 5.23.23.xlsx XLSX spreadsheet
Amendment_0007.pdf PDF
Amendment 0002.pdf PDF
Amendment 0006.pdf PDF
Amendment 0003.pdf PDF
Amendment 0005.pdf PDF
Amendment 0001.pdf PDF
Amendment 0004.pdf PDF
Attachment 2 - Performance Work Statement dated 13-MAR-23.pdf PDF
Revised Request for Proposal 70Z08423RKODI0001 3.20.23.pdf PDF
Request for Information 3.20.23.xlsx XLSX spreadsheet
Preproposal Conf-BOSS Kodiak-22-FEB-2023.pptx PPTX presentation
CBA- signed 4 Mar 2022.pdf PDF
Revised REQUEST FOR PROPOSAL 70Z08423RKODI0001.pdf PDF
BOSS Kodiak Preproposal Conference Schedule.pdf PDF
Attendance Sheet page 2.pdf PDF
Revised Attachment 3 - Past Performance Questionnaire.pdf PDF
Attendance Sheet page 1.pdf PDF
Attachment 4 - Service Contract Act WD 2015-5687.pdf PDF
Attachment 1 - CLIN Schedule of Prices.xlsx XLSX spreadsheet
TE 16.4 Coupon Stations (1).pdf PDF
TE 11.1 Drinking Water Monitoring Program.pdf PDF
TE 10.4 2017 Tsunami Readiness Plan - Final PDF.pdf PDF
Appendix I.3 Historical Fuel Transfers.xls XLS spreadsheet
Appendix C Summary Table of Task Area Deliverables Sections_v1.xlsx XLSX spreadsheet
Attachment 7 - CBA 2022-2024 dated 04 Mar 2022.pdf PDF
Appendix F.3 Example PM Schedule.xlsx XLSX spreadsheet
Appendix H Shore Facilities Inventory 2020.xlsx XLSX spreadsheet
TE 1.2 Mapbook_2021.pdf PDF
TE 16.1 CHP System Description (1).pdf PDF
TE 17.2 Oil Water Separators_May_2021 (1).pdf PDF
Attachment 3 - Past Performance Questionnaire.pdf PDF
Appendix B Government Property.Equipment.and Materials List.xlsx XLSX spreadsheet
Appendix I.2 Hazardous Waste Historical Annual Container and Sampling Costs.pdf PDF
Appendix E Performance Requirements Statement.pdf PDF
Request for Proposal.pdf PDF
TE 18.1 MBIT Report.xls XLS spreadsheet
TE 17.1 Used Oil System Description_May_2021 (1).pdf PDF
TE 19.1 COM Worksheet.xlsx XLSX spreadsheet
Show 40 more

Latest 50 of 72 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHP WTP WWTP Work Order Report

***up to June 3, 2021***
WO#SAM CodeRequestBuilding NameCLINLabor ChargeMaterial ChargeOther ChargeTotal Charge
104-1020410590726CWork order incomplete Troubleshoot and repair MSA LEL gas sensor and unit. This unit monitors the lower explosive level of the atmosphere in the WWTP. SAMs 10560987N2 SEWAGE TREATMENT PLANT BLDG855-0-001$163.42$0.00$0.00$163.42
104-1031610591359CTroubleshoot the electric shop and repair/replace the north end outside entry lightN24 STEAM PLANT BUILDING855-0-001$405.00$31.15$1,031.25$1,467.40
104-1032110591308CCallout 18E0125 Utility Alarm Action: "lo wet well" 2nd pump problem with stick. clean stick, reset alarmN4 SEWAGE LIFT STATION BLDG855-0-012
104-1065110621389CTrouble shoot, repair/replace the contactors on #1 small in plant condensate lift station control switch Labor - 3.0 hours Parts - $90 Down to one switch operating properlyN24 STEAM PLANT BUILDING855-0-001$1,083.84$374.53$0.00$1,458.37
104-1066910621385CRepair cause of fluctuating glycol pressure for AUH-1N2 SEWAGE TREATMENT PLANT BLDG855-0-001$930.38$63.39$0.00$993.77
104-1116510621433CRPL OR RPR THE EXHAUST FLAP ON N24-EEG-01N24A STEAM PLANT EAST ANNEX855-0-001$494.20$0.00$278.43$772.63
104-1124610641034CNo heatN2 SEWAGE TREATMENT PLANT BLDG855-0-001$140.50$0.00$0.00$140.50
104-1126310648871CRepair or Replace Man door to Lift station N6 and replace key core on door handle.N6 SEWAGE LIFT STATION BLDG855-0-001$118.52$0.00$0.00$118.52
104-1126410648872CRepair discharge sample tap of Corrosion Coupon Station at N24 Central Heating Plant.N24 STEAM PLANT BUILDING855-0-001$392.48$18.86$0.00$411.34
104-1126510648873CReplace Red Hat Solenoid Valve on raw water line going to streaming current detectors at N23 WTPN2 SEWAGE TREATMENT PLANT BLDG855-0-001$513.34$0.00$0.00$513.34
104-1134610678907Crepair 20 AMP branch circuit in 120/208 volt distribution panel. The breaker has been faulted and trips out the main breaker disabling all boilers. Investigate working load on panel. (Also, how many amps during normal load are being used) Report Al B.N24 STEAM PLANT BUILDING855-0-001$348.15$35.88$60.00$444.03
104-1297310723824CNo heatN2 SEWAGE TREATMENT PLANT BLDG855-0-001$349.50$31.69$0.00$381.19
104-1299010725743CDiagnose and Repair Electrical Issue on Ultra-Violet Radiation Bank B at N2 WWTP PRI 4N2 SEWAGE TREATMENT PLANT BLDG855-0-001$547.10$0.00$0.00$547.10
104-1301610726193CInvestigate and repair pressure sensor for the instrument air compressor. It is not alternating properly. Est Labor - 8-16hrs PRI 3 Amanda Benton(02/15/2018 08:38)--N24 STEAM PLANT BUILDING855-0-001$881.07$0.00$120.13$1,001.20
104-1306310737321CREPAIR BUSTED PIPEN15 PUMP STATION @ A.HILL855-0-001$230.64$0.00$0.00$230.64
104-1315210773432CNO HOT WATERN2 SEWAGE TREATMENT PLANT BLDG855-0-001$489.30$7.40$0.00$496.70
104-1316310778245CCallout 18E0199 Desc: Oil sheen Dispatched: Blair and WoodN2 SEWAGE TREATMENT PLANT BLDG855-0-001$620.28$0.00$0.00$620.28
104-1335410860824CReplace broken seal on Soda Ash Feed Hopper. Part still needs to be orderedN23 WATER TREATMENT PLANT855-0-001$602.13$0.00$177.94$780.07
104-1349110894815CInspect and repair North Side above instrument air compressor, and south side above the work bench wind damage and water leaks Inspect and repair/replace flashing for the flash tank vent from wind damage.N24 STEAM PLANT BUILDING855-0-001$2,460.39$812.72$0.00$3,273.11
104-1371410894818CReplace leaking valve. FOV-08 (four inch gate) with PEM Valve. Labor - 8hrs Material - $100N24 STEAM PLANT BUILDING855-0-001$492.20$0.00$0.00$492.20
104-1383710905641COperational test of emergency power supply/generator to coincide with KEA outage on 03/28/18 at 0930N23 WATER TREATMENT PLANT855-1-001$1,181.42$0.00$0.00$1,181.42
104-1389110976708CReplace failed condensate pump 1 motor starterN24 STEAM PLANT BUILDING855-0-001$419.21$0.00$142.50$561.71
104-1472011017268CNO HEATN2 SEWAGE TREATMENT PLANT BLDG855-0-001$384.45$0.00$0.00$384.45
104-1474711017291CReplace lock on door to generator room at lift stationN74A GEN BLDG-NEMETZ LIFT STA855-0-026$68.16$334.00$0.00$402.16
104-1490611034881CReplace EZ automation touch screen for microchlor on-site generation systemN23 WATER TREATMENT PLANT855-0-001$207.83$0.00$1,750.17$1,958.00
104-1493311035294CInstall Fluoride Tank Restraint: Stainless Steel 2" x 2" x 3" bracket with 9/16" hole with washers per concrete anchor recommendations. See attached for some examples Or Mc Master-Carr website: https://www.mcmaster.com/#33125t32/=1c63q9o See attached document suggestionsN23 WATER TREATMENT PLANT855-0-001$331.24$0.00$0.00$331.24
104-1511611106617CService M6 coreN74A GEN BLDG-NEMETZ LIFT STA855-0-026$68.16$338.00$0.00$406.16
104-1551011138460CTroubleshoot and repair problems with breaker #13 in lighting panel L1/DP2. Circuit is currently OOC Labor 8+- hours Priority 2 SibrelN24 STEAM PLANT BUILDING855-0-001$383.68$54.67$0.00$438.35
104-1560311149983CReview and annotate any suggested corrections to the Latest WTP draft (to be final 2018 version). *The files will uploaded into ShareFile by COB 03 May 2018 **Submit to the COR all findings before COB on 15 May 2018N23 WATER TREATMENT PLANT855-0-001$439.93$0.00$0.00$439.93
104-1573911159342CChange core N99 on condensate lift station and re-key to R-16MAIN CONDENSATE LIFT STATION855-0-026$74.98$0.00$0.00$74.98
104-1577911167797CTrouble shoot and repair/replace the exterior lights on building with LED's. Several of the current lights are not functioning. Labor 8+/- Materials - unknownN24 STEAM PLANT BUILDING855-0-001$1,361.46$57.71$3,125.00$4,544.17
104-1578011167990COrder and replace the 2.5 flange gate stop valve for the soot blow system on boiler #2. The boiler is functional now, but soot blow system is incapacitated. Root valve on this system will isolate this for replacement otherwise a plant outage will be required. First outage is scheduled for July 11 Labor 7+/- Materials $550 (valve and gaskets)N24 STEAM PLANT BUILDING855-0-001$553.04$0.00$466.61$1,019.65
104-1636711275745CRepair BFP assembly. #1 & 2 failed testing during PM. Estimated 4hours and $300 materialN23 WATER TREATMENT PLANT855-0-001$238.56$0.00$99.85$338.41
104-1662011302630CRepair Life Ring stanchions at the Drain PondN23 WATER TREATMENT PLANT855-0-001$530.81$0.00$0.00$530.81
104-1668911303422CREQUEST A WORK ORDER BE INITIATED TO PURCHASE AND REPLACE LEAKING BOTTOM BLOW VALVES ON PORTABLE BOILER #2. Man hours – 18+ Materials - $2538.05 PLUS SHIPPING FOR PARTSN24 STEAM PLANT BUILDING855-0-001$749.28$82.05$1,780.00$2,611.33
104-1670211305662CRepair and return UV Bank B to 100% operational conditionN2 SEWAGE TREATMENT PLANT BLDG855-0-001$312.26$0.00$0.00$312.26
104-1670311305663CClean fuel tank portable boiler #1N24 STEAM PLANT BUILDING855-0-001$123.55$0.00$0.00$123.55
104-1670411305664CClean fuel tank portable boiler #2N24 STEAM PLANT BUILDING855-0-001$95.61$2.09$0.00$97.70
104-1676911305994CPlease discontinue domestic drinking water production until 1600 tomorrow. Base Kodiak intends on testing the emergency fire valve at N15 tomorrow to transfer approximately 1000 gallons between Aviation Hill water storage tank and the main distribution system. The testing is expected to entail isolation of the emergence valve and actuation without transferring any water, resetting the isolation valves back to the normally open position and then performing the test.N23 WATER TREATMENT PLANT855-0-001$34.92$0.00$0.00$34.92
104-1762011320880CFabricate feeder cord for grindex pump to reach digester, claifier and aerator basins Needed for maintenance within the monthN2 SEWAGE TREATMENT PLANT BLDG855-0-001$405.03$10.60$501.17$916.80
104-1786711417316CInvestigate means to provide a safe/secure space in Women's Locker Room for W/WWTP operator This is to provide a nursing station for mothers. POC returns to work on July 9th and can provide specifics. Approved by cwN2 SEWAGE TREATMENT PLANT BLDG855-0-001$1,374.52$17.46$444.37$1,836.35
104-1787211417345COperating Deck Replace emergency light located above the main door next to roll up garage door on the north-east end of the building Material ? Labor 8+ hours Interior light. Previous emergency lights have been estimated at; Material $100 Labor 1-1.5 hours. FD found inop during inspection.Approved by cwN24 STEAM PLANT BUILDING855-0-001$72.63$19.19$0.00$91.82
104-1804511427896CCALL OUT 18E00324 Chlorine system power fail. Cycling power did not workN23 WATER TREATMENT PLANT855-0-001$412.10$0.00$68.54$480.64
104-1808811438143CDIG PERMIT Dig up and remove MH1 manhole . Remove mixer inline and existing taps saddle. Approx depth 6'N23 WATER TREATMENT PLANT855-0-001$431.02$15.44$0.00$446.46
104-1812111438420CPurchase and replace leaking bottom blow valves on portable boiler #1. Labor: 18+- hours Materials: $2538.05 plus S&HN24 STEAM PLANT BUILDING855-0-001$874.16$0.00$1,780.00$2,654.16
104-1826711445558CPerform annual inspection and maintenance of electrical, control & service panels per OMS-85 Labor 8+- hoursN24 STEAM PLANT BUILDING855-1-001$950.23$0.00$0.00$950.23
104-1859911468505Disable Alarms if they are Non-Functioning -or- Restore Items Functioning / Back Online Repair, Replace, or Disable Constant Alarm Warnings: Allen-Bradley Panelview 1000 -Sulfite Tank Level Low Alarm -Input Out of Range Alarm -Loss of Coms with Auto-stick WSCP Steam Plant MTU -Buskin Lake Pump Station Alarm -Remove Alarm monitoring from the Locked-Out #3 Pump from Alarm SystemN24 STEAM PLANT BUILDING855-1-001$6,511.70$0.00$0.00$6,511.70
104-1860011468507CCallout 18E00330 Chlorine system not producing chlorine due to electrical errorN23 WATER TREATMENT PLANT855-0-001$272.36$0.00$0.00$272.36
104-1878111471759CCallout 18E00334 PLC FailN2 SEWAGE TREATMENT PLANT BLDG855-0-001$417.78$0.00$0.00$417.78
104-1946711579181CDIG PERMIT Install concrete supports by water filters. Need no deeper than 12"N23 WATER TREATMENT PLANT855-0-001$233.57$0.00$0.00$233.57
104-1947611573318CAccept portable boiler from Sitka and write a report of recommended repairs to make it useful to Base and BOSS contractor. Incluse estimated costs to repairN24 STEAM PLANT BUILDING855-0-001$321.12$0.00$0.00$321.12
104-1948911573319CPOST FOR THE UPCOMING BASE WIDE STEAM OUTAGE ON WEDNESDAY AUGUST 15TH.N24 STEAM PLANT BUILDING855-0-001$365.92$0.00$0.00$365.92
104-1950711579276CSecure water/shut down draining in accordance to attached approved utility outage permit Outage to take place August 14 @0800N23 WATER TREATMENT PLANT855-0-001$432.50$0.00$0.00$432.50
104-1954811579200CCallout 18E00356 High Filter differential pressureN23 WATER TREATMENT PLANT855-0-001$116.27$0.00$0.00$116.27
104-1984811590871CRepair/replace manual reset on secondary aqua-stat. This is to correct a discrepancy noted on the state boiler inspection. Mike Fields was present with inspector and will have additional information regarding this repair.N2 SEWAGE TREATMENT PLANT BLDG855-0-001$34.95$84.94$0.00$119.89
104-2051311648978CRemove JP-5 Pipeline Spool from N-24 distribution system. Cap ends of pipelines and properly store Spool.N24 STEAM PLANT BUILDING855-0-001$241.22$0.00$0.00$241.22
104-2052311696043CPlease adjust LED lighting at waste water treatment plant to light only area needed and prevent excessive light pollution into nighttime sky. Excerpt from airport managers email: During an FAA Certification Inspection the FAA had concerns about the intensity of the lights around the Wastewater Plant causing a distraction for pilots landing at night. They are very bright and could lead to an issue. I would like to request that shields be installed or re-positioning of the lights be done in order to keep that light from spilling into the runway environment.N2 SEWAGE TREATMENT PLANT BLDG855-0-001$213.15$0.00$0.00$213.15
104-2059511711303CRepair damaged generator canon type plug at N5 lift stationN5 SEWAGE LIFT STATION BLDG855-0-001$596.85$10.41$0.00$607.26
104-2155611771770CReplace hose on portable boiler #1 & #2, and portable boiler plant #3. Originals are deteriorated and nearing end of useful life. These heat units keeping them dry, warm and in "ready" standby status Labor:4+ hours ; Materials: $1638 + S/HN24 STEAM PLANT BUILDING855-0-001$963.36$3.16$1,446.58$2,413.10
104-2155711771773CPerform a run of portable boiler plant #3 Labor: 40 hrs Involves CHP, Heavy shop (generator), Electric and POLN24 STEAM PLANT BUILDING855-0-001$2,430.32$0.00$34.83$2,465.15
104-2173411854978CTroubleshoot/repair/replace the variable frequency drive/ FD fan on boiler #4 Spoke with Jim Crane Labor: 40+ hrs Should be priority 5N24 STEAM PLANT BUILDING855-1-001$2,061.84$0.00$0.00$2,061.84
104-2176811855206CToyo heater showing EE2 error codeN40 CHEMICAL STORAGE BLDG-WTP855-0-001$139.80$0.00$0.00$139.80
104-2183111872957CReplace 2 light fixtures. Mat $150; Labor 4 hrsLIFT STA-STORM @BLDG 518 (N6)855-0-001$184.74$1.72$80.94$267.40
104-2191611882292CRepair/replace coupon station at the CHP. The one in place has a crack in the piping and needs repair or replacement. Work order to be initiated to the WTP or Pipe. labor: 4+ hrs materials : $450 plus shippingN24 STEAM PLANT BUILDING855-0-001$348.96$0.00$0.00$348.96
104-2191711882295CRepair/rebuild #1 used oil pump seals and bearings as needed. labor: 24+ hrs material: $725.00 plus shipping new coupon station This pump is inoperable at this time.N24 STEAM PLANT BUILDING855-0-001$963.36$0.00$2,660.00$3,623.36
104-2192811882303CProvide a WWTP Operator for Q&A VIP tour of WWTP (N2). 09:30-10:30 on 10/19/2018N2 SEWAGE TREATMENT PLANT BLDG855-0-001$69.63$0.00$0.00$69.63
104-2192911882304CPriority 2. PLC room, SCADA rack Upgrade circuit labeled PLC-UPS CK-5 from what appears to be a 5 amp circuit to a 20 amp circuit. Existing outlet may be reused if it is rated for 20 amps. New circuit needs to be a 20 amp dedicated circuit for the use of a UPS on the SCADA Rack. Field discussions indicate there is room for a spare circuit in the low voltage panel in the electrical room. Existing circuit is under-sized to supply installed equipment, creating a safety hazard.N2 SEWAGE TREATMENT PLANT BLDG855-1-001$138.00$0.00$0.00$138.00
104-2212211892253CReplace worn out quick opening and slow opening bottom blow valves on portable boiler plant #3. survey and compile list of possible replacement parts for the future . This equipment will be needed during a natural disaster. Labor: 16 hrs Material: * 1 slow opening 1.5: BB valve $1176.45 * 2 fast opening 1.5: BB valves: $775 Total:$2,726.17 Recommend PRI 5N24 STEAM PLANT BUILDING855-0-001$927.68$0.00$2,188.53$3,116.21
104-2291811964682C1. Provide a generator during KEA scheduled outage on 11/09/18 by 09:00. 2. Maintain fuel during outage. 3. Upon completion of the outage, return generator set to storage. Outage expected to take 3 hours, from 09:30-12:30 verify generator operates properly upon transfer * Stan Skaw 602-570-0298N5 SEWAGE LIFT STATION BLDG855-1-001$1,069.54$0.00$0.00$1,069.54
104-2296912017729CRepair lift station and bring it back to operation. Downgrade to a Priority 3 if parts are not available locally. Notify COR as to progress. Andrew Christescu, COR 907-654-4385N6 SEWAGE LIFT STATION BLDG855-0-001$1,693.54$58.79$4,713.40$6,465.73
104-2303112039615CELECTRIC SHOP TROUBLE SHOOT ELECTRICAL PROBLEMS WITH #1 BOILER (LOST BOILER AT 0718 THIS MORNING). Man hours – 8 Materials – NOT KNOWN AT THIS TIME RECOMMEND THAT THIS BE ISSUED AS A PRIORITY 2. HAVE ALREADY SPOKE WITH COR (ANDY CHRISTESCU) IN REFERENCE TO THIS. BOILER IS OOC AT THIS TIME.N24 STEAM PLANT BUILDING855-0-001$369.93$0.00$668.78$1,038.71
104-2316812055527CReplace roof access ladder at Tank N9. Ladder has excessive rust through, restore integrity of the ladder and ladder platform.AST-WATER@NEMETZ (N9)855-0-001$35.30$0.00$0.00$35.30
104-2342412072407CCall out 18E00489 King Fisher Utility AlarmN74A GEN BLDG-NEMETZ LIFT STA855-1-025$662.75$0.00$688.63$1,351.38
104-2410412097714CProvide a generator during KEA scheduled outage on 12/07/18 by 12:30. Maintain fuel during outage. Upon completion of the outage, return generator set to storage. verify generator operates properly upon transfer * Stan Skaw 602-570-0298 Outage expected to take 3 hours, from 13:00-16:00N4 SEWAGE LIFT STATION BLDG855-1-001$1,963.64$0.00$0.00$1,963.64
104-2416612187241CProvide a report as to what is required to get the N6 pump station improved enough to be reliable for the next four years.N6 SEWAGE LIFT STATION BLDG855-1-016$167.60$0.00$0.00$167.60
104-2419912190921CRebuild check valves and relief valve in BFP. 3/4" BFP on hose bib. CDS Pipe Shop.N2 SEWAGE TREATMENT PLANT BLDG855-0-001$338.06$0.00$66.96$405.02
104-2425312196575CReplace faulted HMI in SCADA cabinet. standard WO Recommend Pri 2. Approved by cwN23 WATER TREATMENT PLANT855-1-001$595.43$0.00$0.00$595.43
104-2431112212445CRPR INOP TAIL LIGHTS on 248 PB1 Utility TrailerN24 STEAM PLANT BUILDING855-0-015AB$139.58$0.00$0.00$139.58
104-2443112232830Cportable boiler 3 is in alarmN24 STEAM PLANT BUILDING855-0-001$209.37$0.00$0.00$209.37
104-2445012232953CReplace inoperable fixture (EM Light). Beyond repair. FILTER ROOM:109437-104N23 WATER TREATMENT PLANT855-0-001$160.53$83.31$0.00$243.84
104-2445112233046CRepair/replace two bad heaters and inspect boiler at WWTP. out on deck temperature is 55 F. Lab/Office is around 70 degrees but that is ran off of sensors-programming. man hours:8+ materials- possible 2 new heaters.N2 SEWAGE TREATMENT PLANT BLDG855-2-001AA$2,634.63$0.00$0.00$2,634.63
104-2445212233162CRepair/replace filter #1 effluent tyco actuator valve. man hours: 4+ materials- $450 + S/HN2 SEWAGE TREATMENT PLANT BLDG855-1-001$1,774.17$0.00$333.47$2,107.64
104-2446812233190CReplace inoperable fixture (EM Light). Beyond repair. FILTER ROOM:109436-104N23 WATER TREATMENT PLANT855-0-001$153.42$83.31$0.00$236.73
104-2448312239983CN2/ Clarifier Room UH-1 Replace motor that is on the verge of going out and intermittently will not run. UHs 5,7 & 8 Repair UHs that do not run when commanded by thermostat.N2 SEWAGE TREATMENT PLANT BLDG855-1-001$629.47$0.00$0.00$629.47
104-2448412239985CReplace air compressor and clean oil stain from compressorN23 WATER TREATMENT PLANT855-1-001$1,975.93$0.00$1,949.00$3,924.93
104-2449912240053CMechanical Room Clean corrosion and residue on and near WWTP boiler bases. Flexible fuel lines on one North end boiler are damaged by corrosion and replacement appears to be required. Pictures attached. Operations building main Room Investigate cause and repair of water leak at footer to wall interface located at WWTP, operations building east wall near south end past clarifier number 2 behind flam locker (pic attached)N2 SEWAGE TREATMENT PLANT BLDG855-1-001$70.86$0.00$0.00$70.86
104-2451712240278CN-23 Due to aging/obsolete, purchase 2 new Polymer Pumps at N-23 with a set of back-up batteries. Reference: M Walker as agreed upon during our meeting held on 12/12/2018 ADChristescu Contact M Walker for complete scope of work & equipmentN23 WATER TREATMENT PLANT855-1-001$9.32$0.00$0.00$9.32
104-2451912240283CN-2 Remove Moyno Sludge Transfer Pump and add Poratble Gas Pump Replace with new: TSS Sensor (in Aeration Basin) , Level transducer (in Clarifier #1 Polymer Pumps) for the Dewater Press Purchase and enroll 2 new Aerators due to aging of Aerator #3 Reference: M Walker as agreed upon during our meeting held on 12/12/2018 ADChristescu Contact M Walker for complete scope of work & equipmentN2 SEWAGE TREATMENT PLANT BLDG855-1-001$1,962.53$4.40$3,786.98$5,753.91
104-24528CAir compressor has oil blow by needs replacement and oil stain out back needs cleaned up at the same time. Found during quarterly PM Inspect compressor and repair if able and feasable. Approved by cwN23 WATER TREATMENT PLANT855-0-001
104-2454512240963CCall Out 18E00512 Comms lost and tank level lowAST-WATER@AVIATION HILL (N85)855-0-001$104.75$0.00$0.00$104.75
104-2457212242401CRepairing the alarm system/resetting passcodesN23 WATER TREATMENT PLANT855-1-026$1,632.96$0.00$5,927.00$7,559.96
104-2562512252740CReplace # 1 Feed Water Pump with New Pump on Main Feed Water System. As discussed with POC M Amberg. N-23 RPL #1 Feed Water Pump ADChristescuN23 WATER TREATMENT PLANT855-1-001$1,675.03$22.16$5,385.97$7,083.16
104-2569212291690COPERATING DECK REPAIR THE SERVICE AIR COMPRESSOR, IT APPEARS TO BE THE PRESSURE SWITCH. HAVE ELECTRIC SHOP TROUBLE SHOOT. Man hours – 6+ Materials - $???.00 FOR PARTS THE SERVICE AIR COMPRESSOR IS THE BACK-UP FOR THE PLANT INSTRUMENT AIR COMPRESSOR. THIS IS A CRITICAL PIECE OF MACHINERY FOR PLANT OPERATION. WOULD RECOMMEND THIS BE A PRIORITY 2.N24 STEAM PLANT BUILDING855-1-001$284.47$0.00$33.85$318.32
104-2596112416193CRepair lift station pump #1. piping and seal water filter assembly. labor 4+ hrs; material $200N5 SEWAGE LIFT STATION BLDG855-1-001$486.49$0.00$0.00$486.49
104-2664812395892CRepair/replace broken spring and check valve arm on pump #1 at N2 WWTP Lift Station Labor: 4+ hrs & Material $500(springs, gaskets,cotter pin)N2 SEWAGE TREATMENT PLANT BLDG855-1-001$440.24$0.00$252.68$692.92
104-2695812518777CBring an emergency back-up generator to steam plant. Current one is not working properly.N24A STEAM PLANT EAST ANNEX855-1-020$2,228.75$0.00$0.00$2,228.75
104-2709012517488Crepair/replace cracked PVC piping for chlorine pump #2 at N23 WTP. Install pump isolation ball for chlorine pump #1 & #2 so chlorine tank can be directed to either pump during maintenance. labor: 4 + ( plumber & operator) material: $300 ( pvc piping, couplings and vall valves)N23 WATER TREATMENT PLANT855-1-001$910.14$0.00$184.75$1,094.89
104-2770412531246CInstall new fuel level gauge, spill bucket, gauge port, Tee vent and secondary cover. AST #N40 fuel tank. discrepancies found on annual P.M. # 104-26027 Requesting priority 5N40 CHEMICAL STORAGE BLDG-WTP855-1-001$167.79$494.83$0.00$662.62
104-2772512529701CHAVE THE GENERATOR MECHANIC REPLACE THE HEAD BOLT (BLOCK) HEATER ON PORTABLE BOILER PLANT #3. LABOR – 8+ COST - ???N24 STEAM PLANT BUILDING855-1-001$1,010.20$0.00$155.00$1,165.20
104-2774612556952CRepair/Replace Bear Damaged Siding on N-4 building.N4 SEWAGE LIFT STATION BLDG855-1-001$1,798.77$17.64$37.45$1,853.86
104-2789412529700CREPLACE Lift Station N6A: sump pump, electric blower, hour meters, and mercury level switches (with a Flygt MultiTrode and floats.) Man hours – 40+ (combination of electricians, plants mechanic, and ww operators) Materials ~ $ 3800 Total = $5,600+SEWAGE LIFT STATION(N6A)855-2-001$8,668.29$104.13$516.20$9,288.62
104-2824912670809CReplace two EXTERIOR fixtures beyond repair. safety issue for access after dark. mat 500; labor 8 hrsN74A GEN BLDG-NEMETZ LIFT STA855-1-001$881.09$36.86$0.00$917.95
104-2927512808585CProvide access to N-23 WTP at 13:00 today 04/04/19 For representatives from Brechan Enterprises and American Mechanical to collect information for their proposal for the new water line project.N23 WATER TREATMENT PLANT855-1-001$149.06$0.00$0.00$149.06
104-2931712810947CInstall JP-5 Spool at N-24 Day-Tank Priority 4N24 STEAM PLANT BUILDING855-1-001$1,312.33$0.00$0.00$1,312.33
104-2935412827755CProvide answers to the below inquiry: a. Summer treated water temperature, maximum summer flow rate, water pH. b. Winter treated water temperature, maximum winter flow rate, water pH. c. Log inactivation requirement for giardia as specified in the water plant operating permit. d. Maximum allowable chlorine dosage. Disinfection Byproducts Rule: a. Total Organic Carbon content of the water. b. Total Dissolved Organic Carbon. c. Copy of any prior disinfection byproducts potential production study. Email the results by COB 9 April 2019 to: Christescu, Andrew D CIV < Andrew.D.Christescu@uscg.mil> Zeimer, Eric D CIV (Eric.D.Zeimer@uscg.mil)N23 WATER TREATMENT PLANT855-1-001$287.16$0.00$0.00$287.16
104-2936712810974CRepair/replace the over-speed trip on the 500KW Cummins Genset. There is a stand-by generator in place at this time. Recommend PRI 3 labor: 16-30 hrs parts ???N24A STEAM PLANT EAST ANNEX855-1-001$1,397.28$0.00$5,393.22$6,790.50
104-2952012837321CProvide Operator for Q&A tour: North Star Elementary will have a field trip to Base Kodiak on May 3rd for their 1st graders. There are two tour groups - 15 kids plus school chaperones each group. Bus will stay with the WWTP group and when done, swap the kids out and come back to the plant for round 2. We will need to set up two tours with WWTP aprox 20-30 minutes ea. with a 20 minute break in between with Escort for the School Bus to and from the WWTP (twice). Anticipate the start time to be about 9 am / 03 May 2019 Andrew Christescu, COR 654-4385 PLANTS, POL, LOW, JanitorialN2 SEWAGE TREATMENT PLANT BLDG855-1-001$175.36$0.00$0.00$175.36
104-2960112837304CPressure Wash Exterior Surfaces of N9 Water Tank (5,000 sq ft approximately). *Caution; prevent back wash entering the tank through vents/openings.AST-WATER@NEMETZ (N9)855-1-001$2,494.66$0.00$0.00$2,494.66
104-2960212837305CPressure Wash Exterior Surface of N23A Sphere and its supports (12,350 sq ft approximately). *Caution; prevent back wash entering the tank through vents/openings.AST-CHLORINE CONTACT (N23A)855-1-001$332.53$0.00$0.00$332.53
104-2961812834053CN99 Replace offline UPS with an online UPS. The system consistently fails during power outages due to the 8 millisecond interruption of power. This interruption places the automation system ( 1PLC and 3 VFDs) at risk.MAIN CONDENSATE LIFT STATION855-1-001$3,136.71$4.26$0.00$3,140.97
104-3044412889801CRepair slight fuel leak on flange line on MGD at Steam plant. Leak currently contained but needs repairs.N24 STEAM PLANT BUILDING855-1-001$633.36$0.00$0.00$633.36
104-3067212975858Creplace 3 leaking Unit heaters at WWTP. As per shop lead CDS needs to order 3 unit heaters, 3 air outs, miscellanies piping and install new strap on aquastatsN2 SEWAGE TREATMENT PLANT BLDG855-1-001$506.51$0.00$2,414.61$2,921.12
104-3073112990737C***In conjunction w/ MRI 19-046*** Remove signs from N4. Repair rotten trim and reform /replace bent metal siding. Replace weather stripping around door. Once painting is done, attach new "N4" and "Warning" signs to match original.N4 SEWAGE LIFT STATION BLDG855-1-001$1,412.42$194.23$68.95$1,675.60
104-3089112993785CRepair/replace the JB, conduit and other parts as needed on the acuator for the door entry bell at CHP. (advised by electricians that parts needed replacement/repair) Labor: 4hr Material: $575.00N24 STEAM PLANT BUILDING855-1-001$544.00$28.25$0.00$572.25
104-3089912996258CDiagnose/repair air relief/vacuum valve and 2" ball valve on the top of filter #1. cc Electric- turn off heat trace cc POL - plant mechanic will do most of work Labor: 8 hrs Material: $900N23 WATER TREATMENT PLANT855-1-001$1,020.59$0.00$0.00$1,020.59
104-3093112996320CAST fuel tank TK-N24 Install new gauge port cap, lock, and fuel level gauge. Remove broken scully gauge. Remove 1/2” H2O from primary—polish and treat fuel. items required to facilitate monthly inspections and prevent water intrusion.N24 STEAM PLANT BUILDING855-1-001$544.50$160.15$0.00$704.65
104-3110213007038CReplace inop #1 used oil pump. labor: 16+ hrs material $2700 + S/H recommend PRI 3N24 STEAM PLANT BUILDING855-1-001$1,286.24$226.77$2,714.76$4,227.77
104-3192813041575CRepair or replace light fixture on light pole- outside of WWTP- Southwest side of building. Man hours- 4(2 people) Materials- 400N2 SEWAGE TREATMENT PLANT BLDG855-1-001$3,098.72$33.30$112.35$3,244.37
104-3220513041557CRepair or replace emergency/ exit sign combo, existing fixture is working property, but the cover on the face of the fixture is too large and does not snap securely in place in electrical room 109386. 13041557 4 MN2 SEWAGE TREATMENT PLANT BLDG855-1-001$181.98$57.01$0.00$238.99
104-3221913133145CReplace propane pressure proving switch for #3 boiler. Materials: $100 Labor: 2 hours Priority: 4N24 STEAM PLANT BUILDING855-1-001$130.11$0.00$114.41$244.52
104-3227813145646CProvide access and an Operator at WTP (N-23) for Q&A session on new mapping As-Build's. 10 June 2019 @ 09:00 for approximately 1-2 hrs.N23 WATER TREATMENT PLANT855-1-001$7.99$0.00$0.00$7.99
104-3262713163220CChange the electronic security code on the WTP Building Intrusion Alarm: Contact myself or Mike Wood for the new combination.N23 WATER TREATMENT PLANT855-1-026$53.95$0.00$0.00$53.95
104-3265913136256CRepair or replace check valve seal & flange on pump #1 at lift station N6. Man Hours: 8+(Mechanic and operator) Materials: $550 flange/check valve and gasketLIFT STA-STORM @BLDG 518 (N6)855-1-001$248.01$0.00$0.00$248.01
104-3287213172209Trouble shoot and repair stationary generator subsequent to KEA outage failure in generator room 13172209 4 SN24A STEAM PLANT EAST ANNEX855-1-001$7,537.60$0.00$655.45$8,193.05
104-3295513177769CCall out 19E00159 Filter differential H / Low Effluent ChlorineN23 WATER TREATMENT PLANT855-1-001$1,427.70$0.00$0.00$1,427.70
104-3296613177823CReplace current UPS Battery Back-up with a new, bigger one. Current one failed during recent power outage due to being too small. Return to the original size/capacity. The one being used now is incorrect. It sits atop of the old broken one, if specs are needed for how large a battery back-up is needed refer to that one.N23 WATER TREATMENT PLANT855-1-001$2,228.11$0.00$2,947.10$5,175.21
104-3308813187516CPriority One to return one of the pumps to normal operation, downgrade to a Priority 2 for the second pump to be returned to normal operations. Repair or Replace the two water pumps and their associated couplings at the WWTP (N2) one has completely failed and the other is screeching and about to fail. Questions can be addressed to G Kernan as discussed on site today.N2 SEWAGE TREATMENT PLANT BLDG855-1-001$952.08$0.00$1,789.46$2,741.54
104-3310613179759CAdd a lock to the double door chain link fence. This added lock need to have a construction core (green core). This to make access for contractor for adding utility connection power for the wireless antenna to be mounted on the chlorine contact tank on the week of July 4th.N23 WATER TREATMENT PLANT855-1-026$44.96$30.69$0.00$75.65
104-3318313202666CReplace the two obsolete Chlorine Pumps with new pumps. (one pump is in-operable one is erratic, and the critical spare is broken) All three pumps must be identical, 2 installed in the system and the third "critical spare" for the shelf. .N23 WATER TREATMENT PLANT855-1-001$2,240.58$285.50$7,382.24$9,908.32
104-3319313195930CRepair malfunctioning CA610 fluoride detector to restore fluoride injection to the public water system.N23 WATER TREATMENT PLANT855-1-001$113.79$0.00$0.00$113.79
104-3319413195931CRepair chlorine leak at pump #2N23 WATER TREATMENT PLANT855-1-001$113.79$0.00$0.00$113.79
104-3396813245461CRe-calibrate all Allen Bradley PLC'sN24 STEAM PLANT BUILDING855-1-001$93.24$0.00$0.00$93.24
104-3403312999012Troubleshoot and repair/replace Main HMI.scada.N23 WATER TREATMENT PLANT855-1-001$148.13$0.00$0.00$148.13
104-3403413008507CReplace bad SC Controller 200 and DO meter for N2 WWTP Solids Basin. labor: 4+ (elec + WTP) material: $2900N2 SEWAGE TREATMENT PLANT BLDG855-1-001$88.56$0.00$0.00$88.56
104-3403513008508CRepair/replace broken and old UV transmission photometer at N2 lab labor: 1 hr material: $2300N2 SEWAGE TREATMENT PLANT BLDG855-1-001$22.47$0.00$0.00$22.47
104-3404013011922CTroubleshoot, repair & replace problematic graphic display cardN23 WATER TREATMENT PLANT855-1-001$52.79$0.00$0.00$52.79
104-3409213245345CIt is requested that a work order be generated to replace the leaking 2" DI-electric union on the make up water Leslie. Cost: Materials $200.00 Labor: -8 man hours Recommended a priority 5 on this work request.N24 STEAM PLANT BUILDING855-1-001$215.90$0.00$0.00$215.90
104-3414113195932Connect existing float switches and commission back up float system to in fluent wet-well pumps. 13195932 3 SN23 WATER TREATMENT PLANT855-1-001$115.05$0.00$0.00$115.05
104-3419313272439CCONTRACTOR HAS REQUESTED 2 KEYS FOR THE WWTP GATE MG KEY REQUESTING QUICK TURNAROUNDN2 SEWAGE TREATMENT PLANT BLDG855-1-026$45.19$0.00$0.00$45.19
104-3424013295185CLocate the source of the leakage at N6A lift station. Report findings to the Base FE & Env Dept. as to where the excess sanitary is going and scope of repairs.SEWAGE LIFT STATION(N6A)855-1-001$1,299.00$0.00$0.00$1,299.00
104-3451313297667CTroubleshoot & repair alarm panelN24 STEAM PLANT BUILDING855-1-001AB$1,313.84$4,822.00$0.00$6,135.84
104-3451413297672CTroubleshoot & repair Nemtiz N9 water tank SCADAAST-WATER@NEMETZ (N9)855-1-001AB$1,516.48$4,822.00$0.00$6,338.48
104-3454413308959CInstall a new level stick and not allow the station wet well to go above the high wet well mark. We have ordered the required equipment to put the station back into a operation mode that will avoid discharge.SEWAGE LIFT STATION(N6A)855-1-001AA$374.62$0.00$0.00$374.62
104-3482213319385CRemedy the serious concerns with SCADA at the WTP and provide support to correct issues. Communication with the node at Nemetz Tank (N-9) is not communicating.N23 WATER TREATMENT PLANT855-1-001
104-3482313319387Add 2 additional New Hard Drive Back-ups for the WTP & WWTP for increased backup redundancy.N23 WATER TREATMENT PLANT855-1-001AA$10.75$0.00$0.00$10.75
104-3483213319411CHarold of Elcon Engineering is requesting an electrician with tools to help open junction boxes and electrical items at the steam plant for the Replace UST with AST at the Steam Plant Project. POC for Coordination: Leora Houtary at 907-209-4423.N24 STEAM PLANT BUILDING855-1-001AA$543.75$0.00$0.00$543.75
104-3490113311413CREQUEST A WORK ORDER BE INITIATED TO REPLACE THE WORN OUT QUICK OPENING AND SLOW OPENING BOTTOM BLOW VALVES ON BOILER #1 MAN HOURS:-10 MATERIALS: ONE SLOW OPENING 1.5" BB VALVE-$2815.80 TWO FAST OPENING 1.5" BB VALVES- $1684.97 TOTAL=$6185.74N24 STEAM PLANT BUILDING855-1-001AB$428.40$17.68$5,392.26$5,838.34
104-3493613319478CRepair KF alarms discovered during third party assessment. These critical alarms alert to "overflow" sewage or storm OE troubleN6 SEWAGE LIFT STATION BLDG855-1-025$759.65$0.00$0.00$759.65
104-3500313342356CPlace a temporary Construction Core in one of the locks at the Water Meter Building N108 at the Airport. Dustin/Chuck is POC on site. By COB Today 26 July 2019Water Meter Facility #5 & 6 @ Servant Air/NAC855-1-026$27.11$0.00$0.00$27.11
104-3563113342745CCall out 19E00209 Water leaking from inside Meter houseWater Meter Facility #5 & 6 @ Servant Air/NAC855-1-001$225.29$0.00$0.00$225.29
104-3569613405515CConfirm or Deny water leak at or under Meter 5/6 bldg. N108 at the Airport Contact On-site Plumber "Duffy" or Lead "Chuck" for details.Water Meter Facility #5 & 6 @ Servant Air/NAC855-1-001AA$405.56$0.00$0.00$405.56
104-3571813405530CReplace I/O board in 1336VFD *Requesting priority 2*N24 STEAM PLANT BUILDING855-1-001AA$599.45$0.00$0.00$599.45
104-3599413448936CRebuild back flowN23 WATER TREATMENT PLANT855-1-001AA$811.75$4.43$97.18$913.36
104-3611713411323CRepair/replace entry door lightsN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$1,109.05$1,559.27$0.00$2,668.32
104-3613513462420CRemedy cause of heat being on full blastN23 WATER TREATMENT PLANT855-1-001AA$356.23$0.00$0.00$356.23
104-3615213462626CRPL AND RETURN 8 HOSES #1 CLARIFIERN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$240.78$0.00$864.30$1,105.08
104-3615313462628CRPL AND RETURN 8 HOSES #2 CLARIFIERN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$303.34$0.00$864.30$1,167.64
104-3627013468511CIt is requested that the current UV photometer be replaced. The old one no longer works and this portable piece of equipment is mandatory to verify that the UV system at the wwtp is doing it’s job. Part estimate: $3192.05 Labor: 1 hourN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$124.29$0.00$3,192.05$3,316.34
104-3627213468638Creplace a UV ballast on the spare UV system @ wwtp N2. Ballast for the top 2 lights on module 1A bank #3. Also replace pressure relief plug for wipers. **Mandatory for proper wwtp disinfection process. Parts estimate: 2,536.65 Labor: 6 hours Requesting priority 2 for this work requestN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$802.91$0.00$2,639.59$3,442.50
104-3631513490096CProvide certified BFP. Disconnect / Lock Out Tag Out aerator. Remove aerator and then place back basin when work is doneN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$2,211.71$0.00$552.88$2,764.59
104-3639313508916Crepair/replace feeder circuitry or aerator #6 motor to ensure proper dissolved oxygen levels in the aerator basin at N2. This is deemed a priority by WWTP operators to comply with mandated minimum levels.N2 SEWAGE TREATMENT PLANT BLDG855-1-001$1,161.85$0.00$0.00$1,161.85
104-3704113518975CUNIT LIGHT - EMERGENCY LIGHT NOT WORKING 13518975 M 4N23 WATER TREATMENT PLANT855-1-001$142.77$82.82$0.00$225.59
104-3706913589017CRepair cause of belt not rotating on belt pressN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$2,079.35$62.77$0.00$2,142.12
104-3711713590789CRemedy cause of tank not communicating accuratelyN74A GEN BLDG-NEMETZ LIFT STA855-1-001$156.89$0.00$0.00$156.89
104-3713313611664CCorrect electrical malfunction of the electrical outlet that is directly below the Simples 2001 box,, by the phone on the WTP computer desk. Outlet has blue painters-tape over the top plug indicating "Don't Use". Return outlet to proper code & function.N23 WATER TREATMENT PLANT855-1-001$270.07$0.00$0.00$270.07
104-3716313577059CEmergency light #109559 not in working order. Appears to be a dead batteryN24 STEAM PLANT BUILDING855-1-001$115.41$10.01$0.00$125.42
104-3716413577064CEmergency light #109560 not in working order. Appears to be a dead batteryN24 STEAM PLANT BUILDING855-1-001$105.79$10.01$0.00$115.80
104-3716613577065CEmergency light #109561 not in working order. Appears to be a dead batteryN24 STEAM PLANT BUILDING855-1-001$134.64$82.82$0.00$217.46
104-3724313623772CIt is requested that the electricians diagnose/repair the digester aerator #2 at the wastewater treatment plant to return back serviceN2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$2,441.01$8.20$415.00$2,864.21
104-3725613609375CIt is requested that the plumbers fix/replace T on the corrosion coupon station located on the bottom right of the assembly. Labor: 2 Priority: 3AST-WATER@NEMETZ (N9)855-1-001$145.50$0.00$0.00$145.50
104-3731113627370CIt is requested that the air compressor at the waste water plant gets diagnosed.repaired ASAP. The sludge belt press cannot operate without the compressor. Requesting a PRI. 2N2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$568.96$0.00$0.00$568.96
104-3731213627375CIt is requested that the electricians replace sensors for DO and PH probes at the WWTP effluent outfall. New sensors have arrived and wiring diagrams have been printed.N2 SEWAGE TREATMENT PLANT BLDG855-1-001$213.26$0.00$0.00$213.26
104-3735913633457C1) Clean Boiler per the attached annual maintenance excerpt. 2) Provide final flue gas analysis to forrest.l.wallace@uscg.mil. Reason: the PM performed on 22JAN19 (24033) for this boiler identified that the boiler needed to be cleaned and the flue gas readings failed. Per the PM, the stack temperature was 600F which is over the 450 max.N23 WATER TREATMENT PLANT855-1-001AA$369.85$70.93$0.00$440.78
104-3739713634080CAviation Hill Tank (N85) to be filled to 28 feet capacity past seismic safety point of 21 feet for additional capacity during test of the PLC. This can also be done after the test but not after the final PLC change out date of Tuesday 9/24/19. So it may be done before today but could wait until the following Monday. Need work order for the PLC shut down test. This should be done by CDS and will be supported by StanTec since they are on Island this week. Can you place the Work Order for today as discussed in the meeting 9/10/2019 with the Boss Contractor. The test will constist of the following steps: 1. Create the back-up of the programing for the Pump House PLC (StanTec di this step Tuesday) 2. Turn off the PLC (tomorrow at 10am) 3. Place the Pump in (manual Mode) 4. See if the pump can be run without the PLC form the TWP scada system. 5. Run the pump for 1 hour for a test of system integrity 6. Place the PLC back on and run normally 7. Verify that this will all work in this way when the PLC will be changed out next week for final install Per Christescu: Provide a WTP/WWTP Operator for SCADA system upgrades. 09/20 thru 09/27 Perform a Manual “Test Run” of WTP & 559/Pump house; provide the technical/operational assistance to bring down the 559/Pumphouse in an orderly fashion and coordinate the correct flow during the manual run. Coordinate dates & times with POC. Fill Aviation Hill Water Tank N-85 to Maximum Capacity prior to system going off-line, return N-85 to reduced capacity once SCADA system is back to fully operational.N23 WATER TREATMENT PLANT855-1-001AB$7,329.51$0.00$0.00$7,329.51
104-3739913634081CInstall circuit breaker replacement for Pump 1 at the N6A Waste-Water Lift Station. The current circuit breaker has faulted and cannot be reset. This is a critical pump.SEWAGE LIFT STATION(N6A)855-1-001AA$1,389.61$0.00$727.11$2,116.72
104-3740013634082CReplace and program the pump/VFD operator panel.N2 SEWAGE TREATMENT PLANT BLDG855-1-001$320.43$0.00$139.99$460.42
104-3740113634083CProvide Plant/Utilities Operators and Technicians (IT, Electrician, CHP, and WTP/WWWTP) for multiple SCADA hands-on training sessions. 5.16.2.C.4. Attending on-island plant-related training Coordinate with POC times & dates & locations.N23 WATER TREATMENT PLANT855-1-001AA$171.23$0.00$0.00$171.23
104-3745913633482CProvide access and electrician support for Q&A about possible generator replacement on September 25thN2 SEWAGE TREATMENT PLANT BLDG855-1-001$135.97$0.00$0.00$135.97
104-3746113644739CTrouble shoot in-fluent pumps and return to service Requesting a priority 2N2 SEWAGE TREATMENT PLANT BLDG855-1-001$29.68$0.00$0.00$29.68
104-3749313633483Relocate the emergency eyewash/shower station to the chemical storage bay Requesting a PRI. 5 for this work requestN24 STEAM PLANT BUILDING855-1-001AB$7,060.76$235.29$3,104.74$10,400.79
104-3829913758066CT/s and repair cause of heat trace panel not operating sufficientlyN23 WATER TREATMENT PLANT855-1-001AA$940.63$0.00$148.37$1,089.00
104-3845213758704Diagnose/repair the system control center that is not communicating with the wiper control module. Pri 4N2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$2,463.55$0.00$0.00$2,463.55
104-3845313758705CIt is requested that the aluminum slide gate from N2 to be straightened and refabricated to fit in channel(reduce thickness of around perimeter of gate). Priority 3N2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$631.92$0.00$0.00$631.92
104-3845513758713CIt is requested that the BTEX monitor at n2 gets either refurbished or replaced(online monitor for measuring hydrocarbons, displaying negative results).N2 SEWAGE TREATMENT PLANT BLDG855-1-001AB$189.22$0.00$7,066.23$7,255.45
104-3858213784418CRestore power to multiple outletsN23 WATER TREATMENT PLANT855-1-001$209.18$0.00$0.00$209.18
104-3859513644509It is requested that the electricians diagnose/repair the blower and the automatic blower switch located near the lid for the dry well for the lift station N6A Requesting a priory 3SEWAGE LIFT STATION(N6A)855-1-001AA$227.84$0.00$0.00$227.84
104-3859613644510It is requested that the electricians diagnose/repair pump #1 at N6A to return back to service. Pump #1 has no power Requesting a priority 3SEWAGE LIFT STATION(N6A)855-1-001AA$460.21$0.00$0.00$460.21
104-3868213799191CGain modem access via provided password (separate email); verify that the Cisco Switches-Admin Passwords are functional and confirm the ability to change firewall and/or ip addresses through these switches. Have IT dept/J.Mills contact A Christescu for passwords. andrew.d.christescu@uscg.mil 907-654-4385 Report findings to; R.Logan Creelman (Contractor) USCG Civil Engineering Unit Juneau Work#: 907-487-5170 X 6634 Fax#: 907-487-5334 richard.l.creelman@uscg.milN23 WATER TREATMENT PLANT855-1-001AA
104-3958813800802CReplace and calibrate PH sensor/temperature electrode at the water treatment plant. Faulty sensor giving incorrect readings for finished water PH and temperature. Labor: 4 hours Parts: $319.00 + shipping Priority: 4N23 WATER TREATMENT PLANT855-1-001$331.28$0.00$319.00$650.28
104-3962813802007CIt is requested that the lamp assembly in 1720E turbidimeters be replaced on turbidimeters F1, F4, raw water, and finished water. 3 of the lamps are dim and will begin to give false turbidity readings (one of the meters already giving false readings and is not online) Replace loose and faulty wire harness Labor: 4 hours Parts: $265.40 + shipping Priority: 3 13802007 3 SN23 WATER TREATMENT PLANT855-1-001$80.26$0.00$265.40$345.66
104-3963913818442C**19E00315** N6 NOT WORKING NO UTILITY ALARM AT CHP JUST REQUESTED BY OODLIFT STA-STORM @BLDG 518 (N6)855-1-001$205.30$0.00$0.00$205.30
104-3970613828314CN74 Lift Station Priority 4 Pump number 2 historically plugs up within a few hours of being online. Upgrade both Pumps #1 & 2 @ Lift station N74 Retro fit with newer engineered impeller (reference City of Kodiak upgrade) that are designed to not plug as often, contact COR if these are not upgradable. Andrew Christescu, COR Base Kodiak, Public Work 907-654-4385NEMETZ SEW LIFT STA BLDG (N74)855-1-001AB$1,902.22$0.00$3,923.46$5,825.68
104-3971013828318CRPR THE EMERGENCY LIGHT FOUND DURING PM SURVEILLANCEN23 WATER TREATMENT PLANT855-1-001$234.83$82.82$0.00$317.65
104-3975413799186CNeed the following done at N6A. Since the space is a confined entry space, I cannot get into the space easily to verify, and inspect the components in this area. 1. Inspect the mechanical components in the "Dry Well". It is the CG's intention to replace the pumps in the "Dry Well". The pumps are 53 years old, and are well beyond their useful life. The pumps have performed admirably, but the time has come to replace them. We need the nameplate information of the pumps. Please take a picture of the pumps and equipment, in addition to writing down the nameplate information. 2. Exercise the isolation valves, and verify if the valves will or will not fully open and close. 3. Note any other deficiencies in the "Dry Well". Let's get everything that will prohibit the function of the new pumps done the first time. 4. Measure the dimensions of the existing pump, the man-way, and provide drawings/documentation showing findings of deficiencies, measurements, information and pictures. Need to add the following to WO Request #21839 5. I need run times of the existing pumps. 6. Take a Panoramic photos of inside the "Dry-Well", showing all equipment locations. 7. Need the information by Thursday, November 7th. Thanks Roger Bunton, PE U.S. Coast Guard, CEU Juneau Mechanical Engineer DESK: (907) 463-2438 Roger.D.Bunton@USCG.MIL 1379986 S 3SEWAGE LIFT STATION(N6A)855-1-001AA$664.51$0.00$0.00$664.51
104-3982213906857CReturn integrity to the personnel gate main entrance padlock latch. Ref: nuts that secure latch are hand tight // latch with lock can be removed by hand. Repair before COB 04 Nov 2019N23 WATER TREATMENT PLANT855-1-026$90.38$0.00$0.00$90.38
104-3990813833867CIt is requested that a work order be generated to have Zack Berg place a patch (small leak) on the continuous blowdown (CB) header manifold at this time and then to take the necessary measurements, procedure, needed materials, and fabricate a new header manifold. Cost: $3000.00(Schedule 80 piping, unions, nipples, caps, etc.) Labor: -25 man hours Recommend a priority 2 for the path and downgrade to priority 3 for fabrication of the new manifold Requesting a jumbo work orderN24 STEAM PLANT BUILDING855-1-001AB$4,077.46$26.75$855.69$4,959.90
104-3996513939683CAcquire quotes / order rebuild kits for all 4 Paco Pump Seal Pressurizers. Once parts arrive, rebuild all seal pressurizers for proper lubrication distribution to both RAS and both WAS pumps at N2 (wwtp). After parts have been ordered can downgrade the priority. Labor: 8 hours (confined space 2 operators, 4 hours each) Parts: Priority: 2N2 SEWAGE TREATMENT PLANT BLDG855-1-001AA$269.66$45.29$312.66$627.61
104-4000413951293Cdiagnose the Pump #1 fail at Lift Station N5. Pump 1 fail will not clear. This is the main station that pumps everything to the wwtp and runs 24/7.N5 SEWAGE LIFT STATION BLDG855-1-001AA$1,510.98$0.00$0.00$1,510.98