Attachment_7_-_Drawings-M0.1-M9.7.pdf

PDF 4 MB Posted

Attached to
Missoula Fire Sciences Lab Mechanical Upgrade Project Federal contract opportunity
Solicitation number
AG-82FT-S-16-0015
Issued by
Department of Agriculture Forest Service Research Service Rocky Mountain Research Station

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

38110 PE

POTCHAK

MATTHEW

A

S

NO

P

I S

S

E F

O R

IG

E

R

NO

M

L

E E R

EN

G

I

ND

E

RET

A

NAT

DAVID

T

C

H

D S

V

T

H

18x12

16 �

X

XX-X

TEMPERATURE SENSOR

CARBON DIOXIDE SENSOR

HUMIDITY SENSOR

WALL SWITCH

SP STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR

VELOCITY SENSOR

THERMOSTAT

HUMIDISTAT

DIFFERENTIAL PRESSURE SENSOR

HVAC CONTROLS LEGEND

AUTOMATIC AIR VENT

MANUAL AIR VENT

AUTOFLOW VALVE

BACKFLOW PREVENTER

BALL VALVE

BUTTERFLY VALVE

CALIBRATED BALANCING VALVE

CHECK VALVE

COMBINATION FLOW CONTROL

VALVE

COMBINATION STRAINER VALVE

SHUT-OFF VALVE

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

HOSE END DRAIN

FLEXIBLE CONNECTOR

FLOW METERING STATION

FLOW SWITCH

GATE VALVE

MULTI-PURPOSE VALVE

PIPE WELL- EMPTY

PRESSURE GAUGE AND COCK

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE SENSOR

PRESSURE SWITCH

PRESSURE/TEMPERATURE PORT

SOLENOID VALVE

STRAINER

STRAINER W/ BLOWOUT

TEMPERATURE SENSOR

THERMOMETER

DRAIN VALVE W/ HOSE THREAD END

CONNECTION

AUTOFLOW VALVE OR MANUAL

BALANCING VALVE

HVAC PIPING SPECIALTIES LEGEND

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

REFRIGERANT LIQUID, SUCTION, & HOT GAS

BYPASS

STEAM- LOW PRESSURE OR ATMOSPHERIC

CONDENSATE

HVAC PIPING SYSTEMS LEGEND

RECTANGULAR DUCTWORK

ROUND DUCTWORK

AIR TERMINAL MARK, CFM, &

NECK SIZE

CEILING SUPPLY DIFFUSER

CEILING RETURN GRILLE

CEILING EXHAUST GRILLE

CEILING SLOT DIFFUSER

FLOOR REGISTER

SIDEWALL DIFFUSER OR GRILLE

VERTICAL TRANSITION-

RECTANGULAR SUPPLY DUCT

VERTICAL TRANSITION-

ROUND SUPPLY DUCT

VERTICAL TRANSITION-

RECTANGULAR RETURN DUCT

VERTICAL TRANSITION-

ROUND RETURN DUCT

VERTICAL TRANSITION-

RECTANGULAR EXHAUST DUCT

VERTICAL TRANSITION-

ROUND EXHAUST DUCT

TURNING VANE

MANUAL VOLUME DAMPER

REMOTE VOLUME DAMPER

MOTORIZED DAMPER

ZONE DAMPER

FIRE DAMPER

SMOKE DAMPER

FIRE/SMOKE DAMPER

CFM NECK

HVAC LEGEND

TEMP. CONTROL GEN'L NOTES

A. THIS PROJECT WILL INCLUDE THE INSTALLATION OF A BUILDING MANAGEMENT

SYSTEM (BMS). SEE SPECIFICATION SECTIONS 230900 "INSTRUMENTATION AND

CONTROL FOR HVAC", 230993 "SEQUENCE OF OPERATIONS FOR HVAC

CONTROLS" FOR ADDITIONAL INFORMATION.

B. IT SHALL BE THE RESPONSIBILITY OF THE TEMPERATURE CONTROLS

CONTRACTOR TO PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND

SOFTWARE NOT SPECIFICALLY REFERRED TO ON THE PLANS OR IN THE

SPECIFICATION TO ACHIEVE THE SEQUENCE OF OPERATIONS DESCRIBED IN

SPECIFICATION SECTION 230993 "SEQUENCE OF OPERATIONS FOR HVAC

CONTROLS".

C. THE GENERAL CONTRACTOR, MECHANICAL CONTRACTORS, AND ELECTRICAL

CONTRACTOR, SHALL PROVIDE ALL LABOR AND INCIDENTAL MATERIALS

REQUIRED TO COORDINATE THE INSTALLATION OF THE BMS.

D. THE TEMPERRATURE CONTROLS CONTRACTOR SHALL HAVE LOCAL

REPRESENTATION, AND SHALL PROVIDE SERVICES TO SET UP THE CONTROL

INTERFACE TO THE SATISFACTION OF THE CONTRACTING OFFICER, AND SHALL

PROVIDE TRAINING TO THE USERS OF THE EQUIPMENT. THE TEMPERATURE

CONTROL CONTRACTOR SHALL PROVIDE UP TO FIVE DAYS OF THESE

SERVICES AFTER THE DATE OF SUBSTANTIAL COMPLETION, EACH SESSION

LASTING UP TO EIGHT HOURS.

E. T.C. CONTRACTOR SHALL COORDINATE THE LOCATIONS AND MOUNTING

HEIGHTS OF ALL SENSORS WITH THE C.O.

PROJECT SPECIFICATIONS

A. ALL WORK ON THE PROJECT SHALL CONFORM TO ALL LOCAL, STATE AND

NATIONAL CODES AND REGULATIONS, INCLUDING BUT NOT LIMITED TO THE

N.F.P.A., N.E.C., U.B.C., I.E.C.C., I.M.C., U.P.C., THE LOCAL UTILITY COMPANIES

AND THE AUTHORITY HAVING JURISDICTION.

B. THE WORK ON THIS PROJECT SHALL CONSIST OF ALL ITEMS, ARTICLES,

MATERIALS, EQUIPMENT, AND LABOR FURNISHED TOGETHER ALONG WITH ALL

INCIDENTAL ITEMS REQUIRED BY GOOD PRACTICE AND WORKMANSHIP TO

PROVIDE A SATISFACTORY, COMPLETE AND FUNCTIONAL SYSTEM IN

ACCORDANCE WITH THE DRAWINGS AT NO ADDITIONAL COST TO THE OWNER.

C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PAY FOR ALL FEES AND

PERMITS REQUIRED FOR WORK UNDER THIS CONTRACT AND UNDER THE

CONTRACTOR'S SUPERVISION BY SUBCONTRACT.

D. MANUFACTURER'S TRADE NAMES AND CATALOG NUMBERS ARE LISTED TO

INDICATE SPECIAL CONDITIONS AND QUALITY OF MATERIALS OR EQUIPMENT

SUPPLIED. ALTERNATIVE EQUIPMENT OR MATERIALS MAY BE SUBMITTED FOR

REVIEW AND APPROVAL DURING THE SUBMITTAL PROCESS.

E. ALL WORK BY THE CONTRACTOR IS SUBJECT TO REVIEW AT ANY TIME BY THE

CONTRACTING OFFICER.

F. ALL WORK TO BE PERFORMED SHALL FIRST BE SCHEDULED AND SUBMITTED TO

THE CONTRACTING OFFICER'S REPRESENTATIVE FOR ACCEPTANCE.

G. SMOKING SHALL NOT BE PERMITTED ANYWHERE IN THIS FACILITY.

H. THE CONTRACTOR SHALL BE CAREFUL NOT TO BLOCK ANY PATHS OF EGRESS

WHILE PERFORMING THE WORK SPECIFIED.

I. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANUP OF ALL MATERIALS

RESULTING FROM THE WORK. CLEANUP SHALL BE PERFORMED TO THE LEVEL

OF ACCEPTANCE OF THE C.O.'S REPRESENTATIVE.

J. THE CONTRACTOR SHALL AND HEREBY DOES WARRANT AND GUARANTEE THAT

ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE OF DEFECTS OF

MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE

OF SUBSTANTIAL COMPLETION.

K. SUBMIT ALL SHOP DRAWINGS FOR ALL EQUIPMENT ASSOCIATED WITH THIS

PROJECT TO THE CONTRACTING OFFICER FOR REVIEW & APPROVAL PRIOR TO

ORDERING ANY EQUIPMENT. ALL MATERIALS AND OR EQUIPMENT SHALL BE NEW

UNLESS STATED OTHERWISE IN THE DESIGN DOCUMENTS.

L. UPON SUBSTANTIAL COMPLETION THE CONTRACTOR SHALL SUBMIT AN

OPERATIONS & MAINTENANCE (O&M) MANUAL OF ALL EQUIPMENT TO THE C.O.

FOR REVIEW & APPROVAL. AFTER RECEIVING APPROVAL FROM, PROVIDE TWO

COPIES TO THE CONTRACTING OFFICER. PROVIDE THE NECESSARY TRAINING

TO THE FACILITIES PERSONNEL REGARDING ALL EQUIPMENT ASSOCIATED WITH

THIS PROJECT.

M. ALL EQUIPMENT & MATERIALS PROVIDED SHALL MEET THE BUY AMERICAN ACT.

HVAC GENERAL NOTES

A. ALL NEW PIPING, DUCTWORK, EQUIPMENT AND INSULATION SHALL BE

INSTALLED IN ACCORDANCE WITH THE 2012 REQUIREMENTS OF THE

INTERNATIONAL MECHANICAL CODE, THE INTERNATIONAL ENERGY

CONSERVATION CODE, AND THE INTERNATIONAL BUILDING CODE.

B. LOCATIONS AND DIMENSIONS OF EXISTING COMPONENTS IDENTIFIED ON THIS

DRAWING ARE APPROXIMATE AND REPRESENT THE BEST AVAILABLE

INFORMATION AT THE TIME OF DESIGN. VERIFY ACTUAL LOCATIONS AND

DIMENSIONS OF EXISTING COMPONENTS IN THE FIELD PRIOR TO ORDERING

NEW EQUIPMENT AND THROUGHOUT THE EXECUTION OF THE WORK FOR

COORDINATION PURPOSES. PROVIDE ALL DEMOLITION WORK, NECESSARY

FITTINGS, OFFSETS AND TRANSITIONS, AND OTHER COMPONENTS AS REQUIRED

FOR A COMPLETE AND FUNCTIONAL INSTALLATION OF NEW SYSTEMS AT NO

ADDITIONAL COST TO THE C.O.

C. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW

EXACT LOCATIONS AND SIZES OF ALL EXISTING DUCTWORK, PIPING, SYSTEMS

AND EQUIPMENT UNLESS SPECIFICALLY DIMENSIONED. THE CONTRACTOR IS

RESPONSIBLE FOR VERIFICATION OF ACTUAL CONDITIONS AND LOCATIONS IN

THE FIELD, AND TO MAKE ADJUSTMENTS ACCORDINGLY. SEEK THE C.O.'S

APPROVAL PRIOR TO MAKING ANY ADJUSTMENTS THAT MAY AFFECT THE

ORIGINAL DESIGN INTENT OR SPECIFIED PERFORMANCE.

D. IT IS NOT THE INTENT OF THESE DRAWINGS TO GRAPHICALLY REPRESENT ALL

OF THE WORK REQUIRED FOR A COMPLETE INSTALLATION IN EVERY RESPECT.

THE PURPOSE OF THESE PLANS IS TO INDICATE THE INTENDED SIZES,

APPROXIMATE LOCATION AND ROUTING OF MAJOR COMPONENTS.

E. EXAMINE AND REFER TO ALL ARCHITECTURAL, STRUCTURAL, ELECTRICAL,

MECHANICAL, PLUMBING, FIRE PROTECTION AND SITE / CIVIL DRAWINGS FOR

CONSTRUCTION CONDITIONS WHICH MAY AFFECT THE CONTRACTOR'S WORK.

INSPECT THE EXISTING FACILITIES FOR VERIFICATION OF EXISTING CONDITIONS

AND SYSTEMS WHICH MAY HAVE AN EFFECT ON WORK PRIOR TO SUBMISSION

OF BID.

F. IT IS ABSOLUTELY NECESSARY TO COORDINATE WITH ALL TRADES INVOLVED TO

ELIMINATE CONFLICTS IN LOCATION OF DUCTS, PIPES, CONDUITS, DIFFUSERS,

SENSORS AND ALL OTHER EQUIPMENT THROUGHOUT THIS PROJECT BEFORE

FINAL PLACEMENT OF MATERIALS. REFER TO ARCHITECTURAL, STRUCTURAL,

MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS AND FIRE PROTECTION

SHOP DRAWINGS FOR ADDITIONAL DETAILS NECESSARY FOR COORDINATION.

G. THE CONTRACTOR IS TO PROVIDE MATERIALS, LABOR, TRANSPORTATION,

TOOLS, PERMITS, FEES, INSPECTIONS, UTILITIES AND INCIDENTALS NECESSARY

FOR THE COMPLETE INSTALLATION OF THE WORK INDICATED AND DESCRIBED

IN THESE CONTRACT DOCUMENTS.

H. THE CONTRACTOR SHALL PROVIDE ANY ADDITIONAL DETAILS INCLUDING

MATERIALS OR SPECIAL CONSTRUCTION REQUIRED IN ORDER TO COMPLETE

THE PROPER INSTALLATION OF THE SPECIFIED SYSTEMS & EQUIPMENT.

I. ALL EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB, AND FIRMLY ANCHORED IN

LOCATIONS INDICATED. OBSERVE MANUFACTURER'S INSTALLATION

INSTRUCTIONS AND RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT

PRODUCTS SERVE THEIR INTENDED FUNCTION.

J. FOLLOW THE MANUFACTURE'S WRITTEN INSTALLATION INSTRUCTIONS FOR

ROUTING COMBUSTION AIR AND FLUE PIPING, INCLUDING FOR SEPARATE

TERMINATION THROUGH THE WALL OR ROOF. FOLLOW ALL SAFETY

INSTRUCTIONS.

K. PROVIDE SEISMIC BRACING OF ALL EQUIPMENT, PIPING, AND DUCTWORK AS

REQUIRED BY LOCAL CODES. SEE SPECIFICATION SECTION 230548 FOR MORE

INFORMATION.

L. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL FIRE AND/OR

SMOKE BARRIERS, PARTITIONS, & WALLS, SUCH AS BETWEEN THE A & B WING,

AND ANY OTHER FIRE / SMOKE SEPARATION WITHIN THE BUILDING, AS DEFINED

BY THE ARCHITECTURAL CODE PLAN WITH A UL LISTED FIRE AND/OR SMOKE

STOP SYSTEM.

M. ALL MATERIAL IN A PLENUM RATED SPACE SHALL HAVE A FLAME SPREAD NOT

EXCEEDING 25 AND A SMOKE DEVELOPMENT RATING NOT EXCEEDING 50.

N. PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF EQUIPMENT,

VALVES, DAMPERS, AND DEVICES INSTALLED ABOVE NON-REMOVABLE CEILINGS.

O. ALL ELEMENTS PENETRATING BUILDING ENVELOPE COMPONENTS SUCH AS

ROOF AND WALL ASSEMBLIES SHALL BE SEALED WEATHER AND WATER TIGHT.

P. ALL NEW PIPING SHALL BE IDENTIFIED WITH SETON SETMARK PIPE MARKERS,

LETTERED TO MATCH EXISTING AND MARKED AT A MAXIMUM OF EVERY 25 FT.

ALL NEW VALVES SHALL BE IDENTIFIED WITH BRASS OR ALUMINUM VALVE TAGS.

Q. PROVIDE PIPE GUIDES, ANCHORS, EXPANSION JOINTS, AND HANGERS PER

MANUFACTURER'S RECOMMENDATIONS.

R. ALL PIPING WALL PENETRATIONS SHALL HAVE A CHROME ESCUTCHEON PLATE.

ALL SOLDER TO BE LEAD-FREE TYPE.

S. VERIFY THE LOCATION OF ALL THERMOSTATS, HUMIDITSTATS, AND SENSORS

WITH THE CONTRACTING OFFICER PRIOR TO INSTALLATION. INSTALL

THERMOSTATS & HUMIDISTATS PER ADA REQUIREMENTS.

T. U.N.O., ALL DUCT WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE

LATEST REQUIREMENTS OF SMACNA DUCT WORK CONSTRUCTION MANUALS,

MINIMUM GAUGE OF 24, GALVANIZED STEEL. DUCTWORK SHALL BE AIRTIGHT

(5% LEAKAGE). ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL BE

SEALED. FABRICATE ELBOWS WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES

THE DUCT WIDTH IN THE PLANE OF THE TURN; AND FABRICATE TO INCLUDE

FACTORY MANUFACTURED TURNING VANES IN ELBOWS WHERE SHORTER

RADIUS IS NECESSARY. SEE DUCT MATERIAL SCHEDULE & SPECS.

U. PROVIDE FLEX CONNECTIONS FROM ALL DUCT WORK TO EQUIPMENT

CONNECTIONS ON THIS PROJECT. FLEXIBLE DUCT SHALL NOT BE USED IN PLACE

OF ELBOWS.

V. THE MECHANICAL CONTRACTOR SHALL PROVIDE THE OWNER'S

REPRESENTATIVE WITH UP TO 16 HOURS OF TRAINING TO ENSURE PROPER

OPERATION AND MAINTENANCE OF THE SYSTEMS. REFER TO DIV. 1

SPECIFICATIONS

W. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,

WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK DEPICTED IN

THESE DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING OF

HOLES TO THE SATISFACTION OF THE CONTRACTING OFFICER.

X. PROVIDE INSULATED MOUNTING SPACERS FOR ALL TEMPERATURE & HUMIDITY

SENSORS AND T-STATS & H-STATS MOUNTED ON EXTERIOR WALLS.

COMMISSIONING GEN'L NOTES

A. A THIRD-PARTY COMMISSIONING AGENT (CxA) SHALL BE HIRED BY THE

CONTRACTING OFFICER FOR THIS PROJECT. AS PART OF THIS CONTRACT, THE

MECHANICAL CONTRACTOR & T & B CONTRACTOR SHALL ABIDE BY ALL

REQUESTS MADE BY THE COMMISSIONING AGENT TO ACHIEVE THE SPECIFIED

CONTROL POINTS AND SEQUENCE OF OPERATIONS WITH NO ADDITIONAL

CHARGES TO THE OWNER. THE MECHANICAL CONTRACTOR SHALL OBTAIN

APPROVAL FROM THE C.O. PRIOR TO ANY MODIFICATIONS, ALTERATIONS OR

CHANGES TO ANY MECHANICAL OR ELECTRICAL SYSTEM.

HVAC DEMO GENERAL NOTES

A. IT IS THE INTENT OF THIS PROJECT TO DEMOLISH PORTIONS OF THE EXISTING

MECHANICAL SYSTEMS. ALL UTILITY OUTAGES MUST BE SUBMITTED FOR

APPROVAL TO THE CONTRACTING OFFICER WITHIN 14 DAYS OF THE NOTICE TO

PROCEED.

B. U.N.O. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, & PIPING SHOWN AS

HATCHED AND NOTED FOR DEMOLITION SHALL BE DEMOLISHED. EXISTING

MECHANICAL EQUIPMENT SHOWN UNHATCHED AND NOT NOTED FOR

DEMOLITION IS TO REMAIN UNCHANGED.

C. PRESENT ALL DEMOLISHED EQUIPMENT TO THE CONTRACTING OFFICER FOR

SALVAGE. REMOVE ANY UNWANTED EQUIPMENT FROM SITE.

D. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING OF FLOORS,

WALLS, CEILINGS, AND ROOFS TO PERFORM THE REQUIRED WORK DEPICTED IN

THESE DOCUMENTS.

E. COORDINATE WITH THE GENERAL CONTRACTOR TO PATCH AND REPAIR THE

FLOORS, ROOF AND WALLS ASSOCIATED WITH THE MECHANICAL DEMOLITION.

THE CONTRACTOR IS RESPONSIBLE FOR ALL PATCHING OF HOLES TO THE

SATISFACTION OF THE CONTRACTING OFFICER.

F. THIS SITE CONTAINS ASBESTOS, LEAD PAINT, MERCURY, AND PCB'S. ANY

EQUIPMENT BEING REMOVED CONTAINING THESE MATERIALS MUST BE

DISPOSED LEGALLY. ALL ASBESTOS ABATEMENT WILL BE REQUIRED BY THE

GENERAL CONTRACTOR, REFER TO REPORTS FOR ADDITIONAL INFORMATION.

FREEZE PROTECTION NOTES

A. THE MECHANICAL CONTRACTOR SHALL FILL THE NEW HYDRONIC SYSTEMS

WITH THE FOLLOWING SOLUTION:

• NEW HEATING HOT WATER SYSTEM: 40% PROPYLENE GLYCOL & 60%

DISTILLED WATER - GLYCOL SHALL INCLUDE CORROSION INHIBITORS.

B. HEATING HOT WATER SYSTEMS WITH BOILERS THAT HAVE ALUMINUM HEAT

EXCHANGERS SHALL USE HERCULES CRYO-TEK 100 / AL PROPYLENE GLYCOL

OR APPROVED EQUAL PRODUCT.

C. SEE SPECIFICATION SECTION 232113 FOR ADDITIONAL CHEMICAL TREATMENT

REQUIREMENTS.

TEST AND BALANCE NOTES

A. A COMPLETE AIR AND WATER SYSTEM TEST AND BALANCE (T&B) SHALL BE

PERFORMED BY A NEBB OR AABC CERTIFIED T&B CONTRACTOR FOR ALL NEW

AND MODIFIED DEVICES & SYSTEMS. MECHANICAL CONTRACTOR SHALL MODIFY

EQUIPMENT AS DIRECTED BY THE T&B CONTRACTOR TO ACHIEVE DESIGN

PARAMETERS WITH NO EXTRA COST TO THE OWNER. A T&B REPORT SHALL BE

PREPARED AND SUBMITTED TO THE O.C. THE REPORT SHALL INCLUDE ALL AIR &

WATER FLOW READINGS, ALL TEMPERATURE AND PRESSURE SETPOINTS, AND

ALL ELECTRICAL CONDITIONS FOR ALL DEVICES. REPORT SHALL ALSO VERIFY

PROPER SEQUENCE OF OPERATION FOR THE ENTIRE CONTROL SYSTEM.

INSTALL ADDITIONAL MANUAL VOLUME DAMPERS AND BALANCING VALVES AS

REQUIRED.

B. SEE SPECIFICATION SECTION 230593 "TESTING, ADJUSTING, & BALANCING FOR

HVAC" FOR MORE INFORMATION.

GENERAL SYMBOLS LEGEND

SYMBOL DESCRIPTION

KEY NOTE SYMBOL

TERMINATION POINT OF DEMOLITION WORK

POINT OF CONNECTION TO EXISTING WORK

HATCH DENOTES EQUIPMENT OR DUCTWORK TO BE DEMOLISHED

EQUIPMENT TAG

SECTION

DETAIL

DP

ALTERNATE

NUMBER ALTERNATE DESCRIPTION ADD OR DEDUCT EQUIPMENT AFFECTED

1 EXPERIMENTAL COOLING ADD CU-A1

2 ABA RESTROOM ADD EF-A2, EM1

3 MZ AHU UPGRADE TO VAV ADD AHU-A2, CU-A2, CD-A13 THROUGH CD-A17

4 SMOKE EXHAUST STACK ADD SEF-A1

5 SMOKE ACCUMULATION EXHAUST ADD SEF-A2

6 VCT ABATEMENT ADD COORDINATE WITH G.C. & C.O.

7 LV TUNNEL DOOR MOTOR ACCESS ADD CONTROLS, LV TUNNEL OVERHEAD DOOR

8 DESTRATIFICATION FANS ADD DSF-A1 & A2, DSF-$

9 HEATER ALTERNATE ADD ECUH-B6 & B7, HWCH-B2

10 AIR CONDITIONING EQUIPMENT

SMOKE EXHAUST ADD SEF-A3, L-A4, CD-A11

11 (D) RECEIVING 101A CMU WALLS ADD COORDINATE WITH G.C. & C.O.

12 SUPPLY-TO-RELIEF BYPASS DAMPER ADD CD-A8

PROJECT ALTERNATE SCHEDULE

M

M

X X

X X

SECTION

DRAWING #

DETAIL

DRAWING #

MECHANICAL ABBREVIATIONS

ABA ARCHITECTURAL BARRIERS ACT

AC ALTERNATING CURRENT (OR) AIR CONDITIONING

AHU AIR HANDLING UNIT

AI ANALOG INPUT

ADJ ADJUSTABLE

AO ANALOG OUTPUT

A.S. ATMOSPHERIC STEAM

AV AIR VENT OR ANALOG VALUE

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

B.D.D. BACKDRAFT DAMPER

BI BINARY INPUT

BMS BUILDING MANAGEMENT SYSTEM

BO BINARY OUTPUT

BOD BASIS OF DESIGN

BTU/HR BRITISH THERMAL UNITS PER HOUR

BV BINARY VALUE

C COMMON

CD CONDENSATE DRAIN (OR ) CONTROL DAMPER

CFM CUBIC FEET PER MINUTE

C.O. CONTRACTING OFFICER

CxA COMMISSIONING AUTHORITY / AGENT

(D) DEMOLISH / DEMOLITION

DDC DIRECT DIGITAL CONTROL

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CUH CABINET UNIT HEATER

DSF DESTRATIFICATION FAN

(E) EXISTING

EA EXHAUST AIR / EACH

EAT ENTERING AIR TEMPERATURE

E.C. ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ESP EXTERNAL STATIC PRESSURE

EWH ELECTRIC WALL HEATER

EWT ENTERING WATER TEMPERATURE

(F) FUTURE

FPM FEET PER MINUTE

F.S. FAR SIDE

FTR FINNED TUBE RADIATION

G.C. GENERAL CONTRACTOR

H HUMIDITY

HGB HOT GAS BYPASS

HV HIGH VELOCITY

HW S/R HOT WATER SUPPLY/RETURN

HWP HOT WATER PUMP

IN INCHES

IN WG INCHES WATER GAUGE

LAT LEAVING AIR TEMPERATURE

LPS LOW PRESSURE STEAM

LV LOW VELOCITY

LWT LEAVING WATER TEMPERATURE

M.C. MECHANICAL CONTRACTOR

MBH THOUSANDS OF BTU/HR

MZ MULTI-ZONE

(N) NEW

NC NORMALLY CLOSED

NG NATURAL GAS

NO NORMALLY OPEN

N.S. NEAR SIDE

N.T.S. NOT TO SCALE

OA OUTDOOR AIR

O&M OPERATIONS & MAINTENANCE

P/E PNEUMATIC / ELECTRIC

PG PROPYLENE GLYCOL

PSIG POUNDS PER SQUARE INCH (GAUGE)

RA RETURN AIR

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

SA SUPPLY AIR

SAM STEAM ABSORPTION MANIFOLD

SEF SMOKE EXHAUST FAN

SG (ATMOSPHERIC) STEAM GENERATOR

T TEMPERATURE

T.C. TEMPERATURE CONTROL

T.B.D. TO BE DETERMINED

TSP TOTAL STATIC PRESSURE

T-STAT THERMOSTAT

TYP. TYPICAL

U.N.O. UNLESS NOTED OTHERWISE

UV UNIT VENTILATOR

V VELOCITY

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

VUV VERTICAL UNIT VENTILATOR

0 1 2 3 4 5 6 7 8 9 10 inches

PROJECT NO:

DESIGNED

CADD

TECH. REVIEW

DATE

SUB SHEET NO. DRAWING NO.

PKG.

NO.

SHEET

OF

TITLE OF SHEET

REVISIONS

15044.10

FIRE SCIENCES LABORATORY

MECHANICAL UPGRADES

USFS / ROCKY MOUNTAIN RESEARCH STATION

5775 US HIGHWAY 10 W

MISSOULA, MT 59808

AG-0343-C-13-0017

AG-03R6-D-15-0211

795.16.16C O N S T R U C T

IO

N D O C U M E N T S

PKG 1

M0.1

MECH NOTES & LEGENDS

JTW

DMP

DMP

JTW

Ø

MATTHEW

A

S

NO

P

I S

S

E F

O R

IG

E

R

NO

M

L

E E R

EN

G

I

ND

E

RET

A

NAT

DAVID

AIR-COOLED CONDENSING UNIT SCHEDULE

MARK BASE BID OR ALTERNATE SERVES MANUFACTURER MODEL NUMBER CAPACITY

(MBH)

EER

REFRIGERANT SUCTION

TEMPERATURE COOLING STAGES CONDENSER

FANS

UNIT PHYSICAL DATA

ADDITIONAL

DETAILSAHRI DESIGN LENGTH TOP

(IN)

LENGTH BASE

(IN)

WIDTH

(IN)

HEIGHT

(IN)

WEIGHT

(LBS)

CU-A1 ALTERNATE 1 AHU-A1 AAON CNA-105 1,169 12.9 21 R-410A 40°F 2 VARIABLE SPEED 8 152 152 142 104 5,905 SEE BELOW

CU-A2 BASE BID OR ALT. 3 AHU-A2 AAON CFA-025 282.5 - 11.2 R-410A 44°F 1 VAR. + 1 ON/OFF 4 91 58.25 61.25 62 1,519 SEE BE LOW

CU-B1 BASE BID (E) B WING MZ

AHU AAON CFA-050 566.7 - 11.5 R-410A 44°F 1 VAR. + 1 ON/OFF 4 120 .5 104.5 82.25 68.5 2,547 SEE BELOW

ACCESSORIES (ALL UNITS U.N.O.):

1. TIME DELAY RELAY

2. EVAP. FREEZE T-STAT

3. CYCLE PROTECTOR

4. THERMOSTATIC EXP. VALVE (HARD SHUT OFF)

5. FILTER / DRYER

6. HIGH & LOW PRESSURE SWITCH.

7. LIQUID LINE SOLENOID VALVE.

8. SINGLE-POINT POWER CONNECTION W/ NON-FUSED

DISCONNECT.

9. CU-A1 ONLY: SUCTION PRESSURE TRANSDUCER ON

EACH REFRIGERANT SYSTEM.

LOW AMBIENT ACCESSORIES:

1. WINTER START CONTROL

2. CRANKCASE HEATER

3. START ASSIST CAPACITOR

4. LOW AMBIENT PRESSURE SWITCH

5. LOW AMBIENT CONTROLLER

CONTROLS:

1. CU-A1 (EXPERIMENTAL COOLING ALTERNATE): DDC CONTROLS.

2. CU-A2 (BASE BID): (E) PNEUMATIC CONTROL SYSTEM SHALL ENABLE COOLING SIGNAL

INPUT TO DDC. PROVIDE P/E SWITCH TO SEND LOW VOLTAGE ENABLE SIGNAL TO DDC AT 9

PSI PNEUMATIC PRESSURE. DDC SHALL OUTPUT CONTROL SIGNAL(S) TO STAGE AND

MODULATE COMPRESSORS AS REQUIRED.

3. CU-A2 (VAV AHU ALTERNATE): DDC CONTROLS.

4. CU-B1 (BASE BID): (E) PNEUMATIC CONTROL SYSTEM SHALL ENABLE COOLING SIGNAL

INPUT TO DDC. PROVIDE P/E SWITCH TO SEND LOW VOLTAGE ENABLE SIGNAL TO DDC AT 9

PSI PNEUMATIC PRESSURE. DDC SHALL OUTPUT CONTROL SIGNAL(S) TO STAGE AND

MODULATE COMPRESSORS AS REQUIRED.

5. SEE SPEC. SECTION 230993 "INSTRUMENTATION & CONTROL FOR HVAC," SEQUENCE OF

OPERATION, & DDC CONTROL POINTS LIST.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER ELEC.

DATA.

CUSTOM AIR HANDLING UNIT SCHEDULE

MARK MANUFACTURER

OPERATING

WEIGHT

(LBS)

FILTERS

SUPPLY FAN(S) DX COOLING COIL (R-410A) HOT WATER HEATING COIL ATMOSPHERIC STEAM HUMIDIFICATION

RETURN

FANTYPE

NO. OF

FANS

HP

(EACH) MAX CFM MIN CFM

TSP

(IN

WG)

ROWS

AIRFLOW

(CFM)

AIR ∆P

(IN WG)

VELOCITY

(FPM)

CAPACITY (MBH) ENTERING

AIR

LEAVING

AIR ALTERNATE

OUTDOOR

UNIT

ROWS MBH

WATERSIDE AIRSIDE

NO. OF

SAMs MATERIAL CFM LB/HR

WIDTH

(IN)

HEIGHT

(IN)

DEPTH

(IN)

ABSORPTION

DISTANCE

(IN)

HEADER INLET

DIAMETER

(IN)

AIR ∆P

(IN WG)

ENTERING

AIR

LEAVING

AIR

TYPE

AIR ∆P

(IN WG) TOTAL SENSIBLE

DB

(°F)

WB

(°F)

DB

(°F)

WB

(°F)

WORKING

FLUID GPM

∆P

(FT WC)

EWT

(°F)

LWT

(°F) CFM

∆P

(FT WG)

VELOCITY

(FPM)

EAT

(°F)

LAT

(°F)

DB

(°F) RH %

DB

(°F) RH %

AHU-A1 TEMTROL 23,931 2" MERV 8 0.63

PLENUM

ARRAY 4W x 3H 7.5 75,000 2,000 4.8 6

48,400 0.56 375.0 1,008.4 687 57.7 52.3 43.3 43.2

CU-A1 2

3,912 40%

PROPYLENE

GLYCOL

280 6.51 160 129.9

48,000 0.15 380 15 90

INSULATED

STAINLESS STEEL

48,400 999 168 103.5 9.5

9.8

0.05 90 4 90 20

NONE

75,000 0.79 500 963.9 963.9 93 64 79.2 59.5 4,600 75,000 0.29 589 15 71.8 75,000 1,175 - 0.15 71.8 7.2 71.8 28

ACCESSORIES:

1. RETURN DUCT SMOKE DETECTOR OMITTED.

2. PROVIDE SNAP-IN FILTER ACCESS FROM THE AIR INLET OF THE CABINET, A NEW FILTER SET AT THE COMPLETION OF CONSTRUCTION, AND (2) COMPLETE SETS

OF SPARE FILTERS.

3. PROVIDE INSULATED CABINET.

4. PROVIDE VIBRATION ISOLATION PER SPEC. SECTION 230548.

5. PROVIDE HSS6"X6"x5/16" STEEL FRAME (PERPENDICULAR) AT 2'-0" O.C. MAX. ANCHOR AT CORNERS TO EXISTING CONCRETE W/ 5/8" DIAMETER EPOXY BOLT W/

4"x4"x1/4"x0'-4" CLIP ANGLES. CONTRACTOR TO FULLY COORDINATE WITH STRUCTURAL ENGINEER OF RECORD, UNIT MANUFACTURER & VIBRATION & SEISMIC REQUIREMENTS DURING THE SHOP DRAWING PROCESS PRIOR TO FABRICATION. COORDINATE NEW PLATFORM TO MAINTAIN EXISTING PENETRATION

THROUGH FLOOR.

6. PROVIDE OUTWARD HINGED, GASKETED ACCESS DOOR, 2.5' W x 5' H IN INLET PLENUM IMMEDIATELY UPSTREAM OF UNIT FOR FILTER ACCESS, TYP. 2.

7. PROVIDE 6" STEEL TUBE CABINET BASE.

8. PROVIDE DRAIN PANS & CD CONNECTIONS FOR DX, HUMIDIFIER, & SA PLENUM SECTIONS.

9. PROVIDE INDIVIDUAL P-TRAPS FOR DX COIL DRAIN (2"), HUMIDIFIER SECTION DRAIN (2"), SUPPLY PLENUM DRAIN (2"), AND INDIVIDUAL SAMS (3/4"). SEE DETAILS.

FAN DATA:

1. PROVIDE INDIVIDUALLY CONTROLLED VFD FOR EACH SUPPLY FAN, TYP. 12.

2. B.O.D.: SIEMENS BT300 FS4 W/ H/O/A & DISCONNECT. BYPASS NOT

REQUIRED. TYP. 12.

HEATING DATA:

1. SCHEDULED PERFORMANCE IS BASED ON A WATER AND

PG MIXTURE OF 40%.

2. PROVIDE 3-WAY MODULATING CONTROL VALVE BY T.C.

CONTRACTOR. SEE 9/M9.2

ELECTRICAL DATA:

1. SEE MEP COORDINATION SCHEDULE FOR STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

2. PROVIDE 115 VOLT CONVENIENCE OUTLET. (FACTORY WIRED, ELEC. CONTR.

TO CONNECT)

3. PROVIDE VAPOR-PROOF 23W COMPACT FLR LIGHT IN ALL ACCESSIBLE

SECTIONS OF AHU. (FACTORY WIRED, ELEC. CONTR. TO CONNECT), TYP. 3.

CONTROLS DATA:

1. SEE SPEC. SECTION 230900 “INSTRUMENTATION AND CONTROL FOR HVAC”

FOR MORE INFORMATION.

2. PROVIDE TERMINAL STRIP FOR DIRECT CONNECTION TO DDC CONTROLS.

3. SEE SEQUENCE OF OPERATION SPEC. SECTION 230993, DIAGRAMS, &

CONTROL POINTS LIST.

COOLING DATA:

1. REFRIGERANT: R-410A

2. SEE CU-A1 SCHEDULE FOR CONDENSER.

3. PROVIDE STAINLESS STEEL DRAIN PAN.

4. TOP TWO COIL SECTIONS SHALL BE CIRCUITED

TOGETHER & BOTTOM TWO COIL SECTIONS SHALL BE

CIRCUITED TOGETHER.

5. SIZE & ROUTE REFRIGERANT PIPING PER

MANUFACTURER'S RECOMMENDATIONS.

ACCESSORIES:

1. RETURN DUCT SMOKE DETECTOR FURNISHED BY ELEC. CONTR., INSTALLED BY MECH. CONTR. AND WIRED BY ELEC. CONTR. SEE PLANS FOR LOCATION.

2. PROVIDE VIBRATION ISOLATION PER SPEC. SECTION 230548.

3. PROVIDE 4"X4"x5/16" STEEL FRAME W/ INTERMEDIATE MEMBERS WELDED TO FRAME (PERPENDICULAR) AT 2'-0" O.C. MAX. ANCHOR CORNERS TO EXISTING

CONCRETE W/ 5/8" DIAMETER EPOXY BOLT W/ 4"x4"x1/4"x0'-4" CLIP ANGLES. CONTRACTOR TO FULLY COORDINATE WITH STRUCTURAL ENGINEER OF RECORD, UNIT MANUFACTURER & VIBRATION & SEISMIC REQUIREMENTS DURING THE SHOP DRAWING PROCESS PRIOR TO FABRICATION.

4. PROVIDE NEW MERV 8 PRE-FILTERS AT COMPLETION OF CONSTRUCTION PLUS (1) COMPLETE SPARE SET.

5. PROVIDE MIN. R-13 INSULATED CABINET.

6. PROVIDE 1-1/2" CONDENSATE DRAIN W/ P-TRAP BY P.C. TERMINATE W/ AIR GAP AT NEW INDIRECT DRAIN.

CONTROLS:

1. SEE SPEC SECTION 230993 FOR SEQUENCE OF

OPERATION AND CONTROL POINTS ETC.

2. PROVIDE LOW-VOLTAGE OUTDOOR AIR, RETURN, & RELIEF

DAMPERS & ACTUATORS INTEGRAL TO AHU TO BE WIRED

& CONTROLLED BY T.C. CONTRACTOR.

3. FULL ECONOMIZER COOLING MODE WITH POWER RELIEF.

4. PROVIDE CHANGEOVER CONTROL BY T.C. ACCORDING TO

MAJORITY OF ZONE VOTING. SEE 5/M9.6.

ALTERNATE 3 - VAV AHU: COMFORT AIR HANDLING UNIT SCHEDULE

MARK MANUFACTURER MODEL

NUMBER

OPERATING

WEIGHT

(LBS)

OUTSIDE AIR PRE-FILTERS

SUPPLY FAN RETURN FAN DX COOLING COIL (R-410A) HOT WATER HEATING COIL

TYPE MAX

CFM ESP (IN WG) HP ELEC VFD TYPE MAX CFM ESP (IN WG) HP ELEC VFD ROWS AIR ∆P

(IN WG)

VELOCITY

(FPM)

CAPACITY (MBH) ENTERING AIR LEAVING AIR

OUTDOOR UNITROWS MBH

WATERSIDE AIRSIDE

MIN CFM MAX CFM TYPE

AIR ∆P

(IN WG) TOTAL SENSIBLE DB (°F) WB (°F) DB (°F) WB (°F)

WORKING

FLUID GPM ∆P (FT WC) EWT (°F) LWT (°F) CFM ∆P (IN WG)

VELOCITY

(FPM) EAT (°F) LAT (°F)

AHU-A2 DAIKIN CAH017GDGC 3,667 1,350 8,000 MERV 8 0.65 PLENUM 8,000 3.5 15.0 460 V / 3 PH / 60 HZ YES PLENUM 8,000 2.0 5.0 460 V / 3 PH / 60 HZ YES 4 0.84 478 250.8 185.2 78.5 64 54.6 52.9 CU-A2 2 228.0 40%

PROPYLENE

GLYCOL

15.9 1.0 160 129.1 4,000 0.19 250 38 96.8

NOTES:

1. FOR ALL CONDENSING UNITS, PROVIDE VARIABLE SPEED DIGITAL SCROLL COMPRESSOR FOR FULLY

MODULATING STAGE(S) WHERE SCHEDULED.

2. MOUNT CU-A1 & A2 ON CONCRETE PADS ON ROOF.

3. MOUNT CU-B1 ON CONCRETE PAD ON GRADE.

4. DESIGN OA CONDITIONS FOR CU-A1: 57.7°F DB / 52.3° F WB.

5. DESIGN OA CONDITIONS FOR ALL OTHER: 95°F DB / 64° F WB.

3. CU-A1 & A2: PROVIDE 4"X4"x5/16" STEEL FRAME W/ INTERMEDIATE MEMBERS WELDED TO FRAME

(PERPENDICULAR) AT 2'-0" O.C. MAX. ANCHOR CORNERS TO EXISTING CONCRETE W/ 5/8" DIAMETER EPOXY BOLT W/ 4"x4"x1/4"x0'-4" CLIP ANGLES. CONTRACTOR TO FULLY COORDINATE WITH STRUCTURAL ENGINEER OF RECORD, UNIT MANUFACTURER & VIBRATION & SEISMIC REQUIREMENTS DURING THE

SHOP DRAWING PROCESS PRIOR TO FABRICATION.

4. CU-B1: PROVIDE 6" CONCRETE HOUSEKEEPING PAD WITH #4 REBAR @12" O.C. IN EACH DIRECTION.

PLACE REBAR AT A DEPTH OF 3" (MIDDLE OF PAD).

NOTES:

1. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, INCLUDING AHU CABINET DIMENSIONS BEFORE ORDERING COILS.

2. SIZE & ROUTE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.

4. PROVIDE VIBRATION ISOLATION PER SPEC. SECTION 230548.

5. PROVIDE 6" CONCRETE HOUSEKEEPING PAD WITH #4 REBAR @12" O.C. IN EACH DIRECTION. PLACE REBAR AT A DEPTH OF 3"

(MIDDLE OF PAD).

CONTROLS:

1. SEE SPEC SECTION 230993 FOR SEQUENCE OF OPERATION AND CONTROL POINTS.

2. SEE CONTROL DIAGRAM 13/M9.6

3. PROVIDE DISCHARGE AIR TEMPERATURE SENSOR FOR ANALOG INPUT TO DDC.

EXISTING PNEUMATIC CONTROL SYSTEM SHALL ENABLE COOLING AT 9 PSI. PROVIDE

P/E SWITCH AS REQUIRED. SEE AIR-COOLED CONDENSING UNIT SCHEDULE.

BASE BID: MULTI-ZONE AHU DX COOLING COIL SCHEDULE

MARK SERVES MANUFACTURER

MODEL

NUMBER

OPERATING

WEIGHT

(LBS)

FINNED DIMENSIONS (E) FAN DX COOLING COIL (R-410A)

ASSOCIATED

OUTDOOR UNITLENGTH (IN) HEIGHT (IN) DEPTH (IN) MAX CFM ROWS AIR ∆P

(IN WG)

VELOCITY

(FPM)

CAPACITY (MBH) ENTERING AIR LEAVING AIR

TOTAL SENSIBLE DB (°F) WB (°F) DB (°F) WB (°F)

CC-A2 (E) A WING MZ AHU DAIKIN 5EJ1204C 225 73.25 33.0 8.5 6,400 4 0.89 495.5 218.5 184.1 85.0 65.0 55.3 53.0 CU-A2

BASE BID

CC-B1 (E) B WING MZ AHU DAIKIN 5EJ1404B 465 111.25 42.0 8.5 18,000 4 0.96 664.6 456.1 390.0 78.6 62.8 56.3 53.7 CU-B1

CONTROLS:

1. SEE SPEC SECTION 230900 FOR SEQUENCE OF OPERATION AND CONTROL POINTS.

2. PROVIDE 2-WAY MODULATING CONTROL VALVE BY T.C. CONTRACTOR, SEE 11/M9.2.

3. PROVIDE FREEZE-STAT. SEE CONTROL DIAGRAM 13/M9.6

4. PROVIDE DISCHARGE AIR TEMPERATURE SENSOR FOR ANALOG INPUT TO DDC. EXISTING PNEUMATIC CONTROL

SYSTEM SHALL ENABLE HEATING AT 8 PSI. PROVIDE P/E SWITCH AS REQUIRED.

BASE BID: MULTI-ZONE AHU HOT WATER HEATING COIL SCHEDULE

MARK SERVES MANUFACTURER MODEL

NUMBER

OPERATING WEIGHT

(LBS)

FINNED DIMENSIONS HOT WATER HEATING COIL

LENGTH

(IN)

HEIGHT

(IN)

DEPTH

(IN) ROWS MBH

WATERSIDE AIRSIDE

WORKING

FLUID GPM ∆P (FT WC) EWT (°F) LWT (°F) CFM ∆P (IN WG) VELOCITY

(FPM)

EAT

(°F) LAT (°F)

HWC-A2 (E) A WING MZ AHU DAIKIN 5WH1103B 97 75.75 15.0 6.0 3 283.9

40%

PROPYLENE

GLYCOL

20.1 11.2 160 129.5 6,400 1.18 1,181.5 50 95.8

NOTES:

1. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, INCLUDING AHU CABINET DIMENSIONS BEFORE ORDERING COILS.

ELECTRICAL DATA :

1. SEE MEP COORDINATION SCHEDULE FOR STARTER/DISCONNECT AND ALL OTHER ELEC. DATA.

2. PROVIDE 115 VOLT CONVENIENCE OUTLET. (FACTORY WIRED, ELEC. CONTR. TO CONNECT)

3. PROVIDE LIGHT IN ALL ACCESSIBLE SECTIONS OF AHU (TYP. 6). LIGHTS SHALL BE FACTORY-WIRED TO A JUNCTION BOX ON THE EXTERIOR OF THE CABINET. E.C. TO CONNECT TO JUNCTION BOX.

0 1 2 3 4 5 6 7 8 9 10 inches

PROJECT NO:

DESIGNED

CADD

TECH. REVIEW

DATE

SUB SHEET NO. DRAWING NO.

PKG.

NO.

SHEET

OF

TITLE OF SHEET

REVISIONS

15044.10

FIRE SCIENCES LABORATORY

MECHANICAL UPGRADES

USFS / ROCKY MOUNTAIN RESEARCH STATION

5775 US HIGHWAY 10 W

MISSOULA, MT 59808

AG-0343-C-13-0017

AG-03R6-D-15-0211

795.16.16C O N S T R U C T

IO

N D O C U M E N T S

PKG 1

M0.2

MECH SCHEDULES

JTW

DMP

DMP

JTW 22

MATTHEW

A

S

NO

P

I S

S

E F

O R

IG

E

R

NO

M

L

E E R

EN

G

I

ND

E

RET

A

NAT

DAVID

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR STARTER/DISCONNECT AND ALL OTHER

ELEC. DATA.

CONTROL:

1. PROVIDE LINE-VOLTAGE-INPUT TO WALL-MOUNTED ROTARY SPEED

CONTROLLER & LOW VOLTAGE CONTROL SIGNAL OUTPUT. SEE DETAIL 13/M9.5.

2. PROVIDE MANUAL OVERRIDE CONTROL AT WALL-MOUNTED HAND / AUTO / OFF

SWITCH. "HAND" MODE SHALL ENABLE MANUAL SPEED CONTROL.

3. FAN SHALL BE CONTROLLED BY LIGHTS IN CORRESPONDING ROOMS. DIV. 26

SHALL PROVIDE CONTROLS. COORDINATE W/ DIV. 26 FOR INSTALLATION.

4. PROVIDE INTERLOCK TO INTAKE CONTROL DAMPER IN BOTH AUTO & HAND

MODES. SEE PLANS FOR LOCATIONS.

5. PROVIDE WALL-MOUNTED SPEED CONTROLLER.

6. PROVIDE DDC INTERFACE.

7. PROVIDE VFD

8. PROVIDE INTERLOCK (OVERRIDABLE) TO AHU-A1 FOR ROOM-NEUTRAL

MAKE-UP AIR.

9. SEE DETAIL 14/M9.5.

NOTES:

1. PROVIDE MAIN CABLE, STABILIZATION CABLE, AND ATTACHMENT HARDWARE BY MANUFACTURER AS REQUIRED.

SUPPORT FROM ROOF SLAB & HANG BELOW (E) SA PREFORATED GRILLE.

2. PROVIDE BIRD SCREEN, PRE-WIRED NEMA1 DISCONNECT, INTEGRAL 2-POSITION LINE VOLTAGE MOTORIZED

DAMPER INTERLOCKED W/ FAN, WALL-MOUNTED SPEED CONTROLLER & SIDEWALL GRILLE BY FAN

MANUFACTURER.

3. MOUNT IN VERTICAL CONFIGURATION. PROVIDE GRAVITY B.D.D. & DISCONNECT, & ROOF CAP BY MANUFACTURER. PROVIDE PIPE PORTAL, CURB, & FLASHING SYSTEM BY RPS OR APPROVED EQUAL. SEE DETAIL 1/M9.1.

4. PROVIDE BIRD SCREEN, PRE-WIRED NEMA1 DISCONNECT, INTEGRAL 2-POSITION LINE-VOLTAGE MOTORIZED

DAMPER INTERLOCKED W/ FAN, CURB, SPEED CONTROLLER AND DRAIN PAN.

5. PROVIDE PREWIRED DISCONNECT, MDSG GALVANIZED 2-POSITION LINE-VOLTAGE MOTORIZED DAMPER INTERLOCKED WITH FAN, UL LISTED TO OPERATE CONTINUOUSLY AT 500°F W/ HIGH TEMPERATURE PAINT, HIGH TEMPERATURE BEARINGS, HIGH TEMPERATURE OSHA BELT GUARD W/ COVER, SHAFT COOLER, NO ALUMINUM

CONSTRUCTION, MOTOR HEAT SHIELD AS REQUIRED BY FAN MANUFACTURER.

6. PROVIDE PREWIRED NEMA3 DISCONNECT, GALVANIZED 14" CURB, GALVANIZED 2-POSITION LINE-VOLTAGE MOTORIZED DAMPER INTERLOCKED WITH FAN, UL LISTED TO OPERATE CONTINUOUSLY AT 500°F W/ HIGH TEMPERATURE PAINT, HIGH TEMPERATURE BEARINGS, SHAFT COOLER, NO ALUMINUM CONSTRUCTION, MOTOR

HEAT SHIELD AS REQUIRED BY FAN MANUFACTURER.

HVAC FAN SCHEDULE

MARK BASE BID OR ALTERNATE AREA SERVED MANUF. MODEL

NUMBER CFM SOUND E.S.P.

(IN WG) DRIVE TYPE MOUNTING WEIGHT

(LBS) CONTROL NOTES

DSF-A1 ALTERNATE 8 BURN CHAMBER ZOO FANS H60 1,200 38.8 dBA 0 DIRECT DESTRATIFICATION

MAIN CABLE &

STABILIZATION TETHER 23 1, 2, 5, 6 1

DSF-A2 ALTERNATE 8 BURN CHAMBER ZOO FANS H60 1,200 38.8 dBA 0 DIRECT DESTRATIFICATION

MAIN CABLE &

STABILIZATION TETHER 23 1, 2, 5, 6 1

EF-A1 BASE BID

BOILER ROOM

EXHAUST COOK 101W15DH 600 8.4 SONES 0.4 DIRECT CENTRIFUGAL SIDEWALL 38 2, 4, 5, 6, 9 2

EF-A2 ALTERNATE 2

RESTROOM AND

JANITOR EXHAUST COOK GN-186 200 4.5 SONES 0.25 DIRECT CENTRIFUGAL INLINE 16 3 3

EF-A3 BASE BID MECHANICAL

PENTHOUSE EXHAUST COOK 120C15D 1,200 9.7 0.35 DIRECT CENTRIFUGAL

DOWNBLAST ROOF 67 2, 4, 5, 6, 9 4

SEF-A1 ALTERNATE 4

BURN CHAMBER

EXHAUST STACK COOK 330 CPS-A 17,500 71 dBA 0.75 BELT

CW / SWSI

CENTRIFUGAL

ROOF UTILITY SET ON

PAD 1176 6, 7, 8 5

SEF-A2 ALTERNATE 5

BURN CHAMBER

SMOKE

ACCUMULATION

COOK 300 ACSC 10,000 68 dBA 0.75 BELT CENTRIFUGAL

UPBLAST ROOF CURB 581 6, 8 6

SEF-A3 ALTERNATE 10

AIR CONDITIONING

EQUIPMENT EXHAUST COOK 100ACSC 900 13.9 SONES 0.5 BELT

CENTRIFUGAL

UPBLAST ROOF CURB 99 2, 4, 5, 6, 9 6 LOUVER SCHEDULE

MARK

BASE BID OR

ALT. MANF. MODEL NUMBER SIZE TYPE FUNCTION MAX CFM MOUNTING FREE AREA (FT2)

FREE AREA VELOCITY

(FPM)

∆P

(IN WG) NOTES

L-A1 BASE BID RUSKIN ELF6350DMP 204"x84" STATIONARY LOUVER OUTDOOR AIR INTAKE FOR AHU-A1 75,000 WALL 78.64 954 0.13 SEE BELOW L-A2 ALT. 3 RUSKIN ELF6350DMP 72"x32" STATIONARY LOUVER OUTDOOR AIR INTAKE FOR AHU-A2 8,000 WALL 9.47 845 0.10 SEE BELOW L-A3 ALT. 3 RUSKIN ELF6350DMP 72"x32" STATIONARY LOUVER RELIEF AIR FOR AHU-A2 8,000 WALL 9.47 845 0.10 SEE BELOW L-A4 ALT. 10 RUSKIN ELF6350DMP 18"x24" STATIONARY LOUVER OUTDOOR AIR INTAKE FOR SEF-A3 900 WALL 1.53 589 0.05 SEE BELOW L-A5 BASE BID RUSKIN ELF6350DMP 14"x24" STATIONARY LOUVER OUTDOOR AIR INTAKE FOR EF-A1 600 WALL 1.15 523 0.04 SEE BELOW L-A6 BASE BID RUSKIN ELF6350DMP 24"x24" STATIONARY LOUVER OUTDOOR AIR INTAKE FOR EF-A3 1,200 WALL 2.1 571 0.05 SEE BELOW

NOTES:

1. 6" DEPTH LOUVER.

2. DRAINABLE LOUVER.

3. CONTRACTING OFFICER TO SELECT COLOR.

4. PROVIDE BIRD SCREEN & EXTENDED SILL.

5. SEE CONTROL DAMPER SCHEDULE.

NOTES:

1. APPROXIMATE OVERALL SIZE IS SCHEDULED. FIELD-VERIFY ALL SIZES & CONDITIONS BEFORE ORDERING.

2. PROVIDE MULTIPLE SECTIONS, ACTUATORS, & LINKAGE AS REQUIRED TO ACHIEVE TOTAL SIZE.

3. PROVIDE END SWITCH TO VERIFY POSITION. SEE SPECIFICATIONS FOR SEQUENCE OF OPERATION AND CONTROL POINTS LIST.

4. PROVIDE DUCT TRANSITIONS TO DAMPER AND/OR MOUNTING SLEEVE AS REQUIRED FOR EACH INSTANCE.

5. PROVIDE ACTUATOR(S) FOR EACH DAMPER TO APPLY THE TORQUE NECESSARY FOR THE SPECIFIC INSTALLATION PER THE MANUFACTURER'S

RECOMMENDATIONS. U.N.O., THE T.C. CONTRACTOR SHALL PROVIDE LOW OR LINE VOLTAGE POWER (CONTRACTOR'S OPTION) & LOW VOLTAGE CONTROL.

6. ALTERNATE 3 - VAV AHU: OUTDOOR AIR, RETURN AIR, & RELIEF AIR DAMPERS ARE SUPPLIED INTEGRAL TO AHU-A2 BY THE M.C., AND SHALL BE SUPPLIED

WITH POWER & LOW VOLTAGE CONTROL BY THE T.C. CONTRACTOR.

7. INTEGRATE CONTROL OF (E) DAMPERS SCHEDULED INTO THE NEW DDC SYSTEM. PROVIDE (N) LINKAGE, ELECTRONIC ACTUATORS, POWER, END-SWITCHES, &

CONTROLS AS REQUIRED. PROVIDE (N) BLADE & JAMB SEALS TO MATCH TEMPERATURE RATING & PERFORMANCE OF (E) MATERIALS. REPAIR OR REPLACE

(E) BLADES OR OTHER COMPONENTS AS REQUIRED. CONTRACTOR SHALL GUARANTEE FUNCTIONING PERFORMANCE OF (E) DAMPERS AS OUTLINED IN THESE DOCUMENTS FOR A PERIOD OF ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION.

CONTROL DAMPER SCHEDULE

MARK BASE, ALT.,

OR (E) MANF. MODEL NUMBER SIZE TYPE FUNCTION MAX CFM MOUNTING CONTROL NOTES

CD-A1 BASE RUSKIN CD40x2 17'-0" x 7'-0" TWO-ROW, OPPOSED BLADE, LOW-LEAKAGE, INSULATED

OUTDOOR AIR INTAKE

FOR AHU-A1

75,000 WALL MODULATING,

FAIL-CLOSED SEE BELOW

CD-A2 (E) - - 10'-0" x 10'-0" VERIFY IN FIELD

LOW VELOCITY WIND

TUNNEL ISOLATION 75,000

DUCT IN-LINE

BELOW ROOF

TWO-POSITION,

FAIL-OPEN SEE BELOW

CD-A3 (E) - - 5'-0" x 5'-0" VERIFY IN FIELD HIGH VELOCITY WIND

TUNNEL ISOLATION 75,000 DUCT IN-LINE

BELOW ROOF

TWO-POSITION,

FAIL-OPEN SEE BELOW

CD-A4 BASE RUSKIN CD60 3'-0" x 2'-6" OPPOSED BLADE, LOW-LEAKAGE

BURN CHAMBER

RECIRCULATION 30,000 DUCT ABOVE

FLOOR

MODULATING,

FAIL-OPEN SEE BELOW

CD-A5 BASE RUSKIN CD60 17'-0" x 4'-0" OPPOSED BLADE, LOW-LEAKAGE

WIND TUNNEL

COMMON

RECIRCULATION

75,000 WALL MODULATING,

FAIL-OPEN SEE BELOW

CD-A6 BASE RUSKIN CD60 17'-0" x 4'-0" OPPOSED BLADE, LOW-LEAKAGE SMOKE RELIEF DAMPER 75,000 WALL MODULATING, FAIL-OPEN SEE BELOW

CD-A7 (E) - - 40'-0" x 2'-6" VERIFY IN FIELD SUPPLY AIR PLENUM 75,000 WALL MODULATING, FAIL

LAST POSITION SEE BELOW

CD-A8 ALT. 12 RUSKIN CD60 30'-0" x 1'-0"

OPPOSED BLADE,

LOW-LEAKAGE

SUPPLY TO RELIEF

BYPASS 30,000 PLENUM

MODULATING,

FAIL-CLOSED SEE BELOW

CD-A9 (E) - - 11'-0" x 8'-0" VERIFY IN FIELD FLUE STACK SMOKE

EXHAUST 17,500 ROOF

VENTILATOR

MODULATING, FAIL

LAST POSITION SEE BELOW

CD-A10 BASE RUSKIN CD60 14"x24" OPPOSED BLADE, LOW-LEAKAGE

BOILER ROOM INTAKE

LOUVER 600 WALL TWO-POSITION,

FAIL-CLOSED SEE BELOW

CD-A11 ALT. 10 RUSKIN CD60 18"x24"

OPPOSED BLADE,

LOW-LEAKAGE

AIR CONDITIONING

EQUIPMENT INTAKE

LOUVER

900 WALL

TWO-POSITION,

FAIL-CLOSED SEE BELOW

CD-A12 BASE RUSKIN CD60 24"x24" OPPOSED BLADE, LOW-LEAKAGE

MECHANICAL LOFT

INTAKE LOUVER 1,200 WALL TWO-POSITION,

FAIL-CLOSED SEE BELOW

CD-A13 ALT. 3 RUSKIN CD60 14"x12" OPPOSED BLADE, LOW-LEAKAGE VAV SA ZONE 1 1,240 DUCT MODULATING, FAIL

LAST POSITION SEE BELOW

CD-A14 ALT. 3 RUSKIN CD60 20"x12"

OPPOSED BLADE,

LOW-LEAKAGE VAV SA ZONE 2 1,590 DUCT

MODULATING, FAIL

LAST POSITION SEE BELOW

CD-A15 ALT. 3 RUSKIN CD60 24"x12" OPPOSED BLADE, LOW-LEAKAGE VAV SA ZONE 3 2,460 DUCT MODULATING, FAIL

LAST POSITION SEE BELOW

CD-A16 ALT. 3 RUSKIN CD60 14"x12"

OPPOSED BLADE,

LOW-LEAKAGE VAV SA ZONE 4 905 DUCT

MODULATING, FAIL

LAST POSITION SEE BELOW

CD-A17 ALT. 3 RUSKIN CD60 10"x8" OPPOSED BLADE, LOW-LEAKAGE VAV SA ZONE 5 205 DUCT MODULATING, FAIL

LAST POSITION SEE BELOW

ELECTRICAL DATA:

SEE MEP COORDINATION

SCHEDULE FOR

STARTER/DISCONNECT AND ALL

OTHER ELEC. DATA.

ACCESSORIES:

1. PROVIDE 2-STAGE INTEGRAL THERMOSTAT, TRANSFORMER, AND RELAYS AS REQUIRED FOR LOW VOLTAGE CONTROL.

2. PROVIDE INTEGRAL DISCONNECT SWITCH AND THERMAL OVERLOADS.

3. PROVIDE SUMMER FAN SWITCH AND PERMANENT WASHABLE FILTERS.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER ELEC.

DATA.

ELECTRIC UNIT HEATER SCHEDULE

MARK

BASE BID

OR ALT. AREA SERVED MANUF. TYPE MODEL NUMBER kW STAGES CFM

DIMENSION

FINISH MOUNTING RETURN SUPPLY NOTESLENGTH

(IN)

DEPTH

(IN)

HEIGHT

(IN)

ECUH-B1 BASE BID 1ST FLOOR WOMENS BRASCH CABINET BCUH3305 5 2 250 33" 9.5" 25"

POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

ECUH-B2 BASE BID 1ST FLOOR MENS BRASCH CABINET BCUH3305 5 2 250 33" 9.5" 25" POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

ECUH-B3 BASE BID 1ST FLOOR SHPG &

RCVG BRASCH CABINET BCUH3305 5 2 250 33" 9.5" 25" POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

ECUH-B4 BASE BID 2ND FLOOR WOMENS BRASCH CABINET BCUH3305 5 2 250 33" 9.5" 25" POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

ECUH-B5 BASE BID 2ND FLOOR MENS BRASCH CABINET BCUH3305 5 2 250 33" 9.5" 25" POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

ECUH-B6 ALT. 9 2ND FLOOR STOCK RM BRASCH CABINET BCUH3305 5 2 250 33" 9.5" 25"

POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

ECUH-B7 ALT. 9 2ND FLOOR PASSAGE BRASCH CABINET BCUH4610 10 2 500 46" 9.5" 25" POWDER

COAT

VERTICAL/

FLOOR FRONT BOTTOM FRONT TOP SEE BELOW

DUCT MATERIAL SCHEDULE

DESCRIPTION SHAPE APPLICATION MATERIAL PRESSURE CLASS INSULATION JACKET R-VALUE ADDITIONAL DETAILS

GENERAL & COMFORT APPLICATIONS

SUPPLY AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 4" WRAP FACTORY APPLIED R-5 SEE BELOW

SUPPLY AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 4" WRAP FACTORY APPLIED R-5 SEE BELOW

RETURN AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

RETURN AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

EXHAUST AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

EXHAUST AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-5 SEE BELOW

OUTSIDE AIR RECTANGULAR INDOOR - CONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

OUTSIDE AIR ROUND INDOOR - CONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

5' LENGTH MAX - SUPPLY ONLY ROUND INDOOR - CONDITIONED FLEX 2" INTEGRAL FACTORY APPLIED R-5 SEE BELOW

ALL DUCTWORK IN UNCONDITIONED SPACE RECTANGULAR INDOOR - UNCONDITIONED SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

ALL DUCTWORK IN UNCONDITIONED SPACE ROUND INDOOR - UNCONDITIONED SPIRAL SHEET METAL 2" WRAP FACTORY APPLIED R-8 SEE BELOW

ALL EXTERIOR DUCTWORK RECTANGULAR EXTERIOR SHEET METAL 2" WRAP FIELD APPLIED EXTERIOR R-8 SEE BELOW

ALL EXTERIOR DUCTWORK ROUND EXTERIOR SPIRAL SHEET METAL 2" WRAP FIELD APPLIED EXTERIOR R-8 SEE BELOW

HIGH TEMPERATURE & SMOKE EXHAUST APPLICATIONS

ALL AHU-A1 DUCT EXCEPT AS NOTED BELOW RECTANGULAR INDOOR - CONDITIONED WELDED - STEEL (16 GA) OR STAINLESS STEEL (18 GA) SEE BELOW WRAP FACTORY APPLIED R-8 SEE BELOW

ALL AHU-A1 DUCT EXCEPT AS NOTED BELOW ROUND INDOOR - CONDITIONED WELDED - STEEL (16 GA) OR STAINLESS STEEL (18 GA) SEE BELOW WRAP FACTORY APPLIED R-8 SEE BELOW

SMOKE EXHAUST - INTERIOR & EXTERIOR RECTANGULAR SMOKE EXHAUST WELDED - STEEL (16 GA) OR STAINLESS STEEL (18 GA) SEE BELOW EXTERNAL FIRE WRAP SEE BELOW N/A SEE BELOW

SMOKE EXHAUST - INTERIOR & EXTERIOR ROUND SMOKE EXHAUST WELDED - STEEL (16 GA) OR STAINLESS STEEL (18 GA) SEE BELOW EXTERNAL FIRE WRAP SEE BELOW N/A SEE BELOW

WIND TUNNEL RECIRCULATION - EXTERIOR RECTANGULAR WIND TUNNEL RECIRC. WELDED - STEEL (16 GA) OR STAINLESS STEEL (18 GA) SEE BELOW WRAP FIELD APPLIED EXTERIOR R-8 SEE BELOW

WIND TUNNEL RECIRCULATION - EXTERIOR ROUND WIND TUNNEL RECIRC. WELDED - STEEL (16 GA) OR STAINLESS STEEL (18 GA) SEE BELOW WRAP FIELD APPLIED EXTERIOR R-8 SEE BELOW

HIGH TEMPERATURE & SMOKE EXHAUST DUCT NOTES:

1. ALL DUCTWORK TO AND FROM AHU-A1 INCLUDING OUTDOOR AIR, SUPPLY AIR, RETURN AIR, RELIEF AIR & TUNNEL RECIRCULATION DUCTWORK, SHALL BE CONSIDERED HIGH TEMPERATURE

APPLICATION.

2. HIGH TEMPERATURE & SMOKE EXHAUST DUCT SHALL BE MADE A CONTINUOUS LIQUID-TIGHT

WELD. DUCTWORK SHALL BE SLOPED AT 2% DOWN TOWARD THE NEAREST ACCESS POINT FOR

CLEANOUT.

3. SMOKE EXHAUST SHALL BE INSULATED W/ 2HR FIRE RESISTANT 3M OR EQUAL, UL LISTED W/

INTEGRAL JACKET.

FACTORY-APPLIED JACKET:

ALL SERVICE JACKETS (ASJ) SHALL BE FOIL SCRIM KRAFT (FSK). SEAL SEAMS

W/ FSK ADHESIVE TAPE ACCORDING TO SPECIFICATIONS.

FIELD-APPLIED EXTERIOR JACKET:

PROVIDE EXTERIOR ALUMINUM JACKET RATED FOR OUTDOOR USE. (POLYGUARD,

ALUMAGUARD 60 OR APPROVED EQUAL). SEE SPECIFICATIONS.

MINIMUM REQUIREMENTS (U.N.O.):

1. PROVIDE SEISMIC BRACING OF ALL DUCTWORK AS REQUIRED BY LOCAL CODES.

2. ALL SHEET METAL DUCTWORK SHALL BE A MINIMUM OF 24 GAGE GALVANIZED STEEL.

3. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED PER SMACNA GUIDELINES.

4. SEAL AND INSULATE ALL DUCTWORK PER 2012 I.E.C.C.

5. INSULATE EXHAUST DUCTWORK FROM EXTERIOR TERMINATION TO ISOLATION

DAMPER, BUT NO LESS THAN WITHIN 15 FT OF PENETRATION THROUGH BUILDING

ENVELOPE.

AIR TERMINAL SCHEDULE

MARK MODULE SIZE NECK SIZE FUNCTION TYPE

PERFORMANCE DATA AT MAX CFM BASIS OF DESIGN

MOUNTING MATERIAL FINISH ADDITIONAL DETAILS

MAX CFM ∆P (IN WG) THROW (FT) VELOCITY

(FPM) MAX NC MANF. MODEL

NUMBER PATTERN

EG-1 DUCT SIZE + 1-3/4" SEE PLANS EXHAUST EXHAUST GRILLE 100 0.02 - 274 - KRUEGER S80 3/4" FIXED 35°

DEFLECTION SURFACE STEEL STANDARD SEE BELOW

EG-2

DUCT HEIGHT +

1-3/4"

DUCT WIDTH + 1-1/2"

SEE PLANS EXHAUST EXHAUST GRILLE 300 0.114 - 500 - TITUS SF8 PERFORATED

FACE DUCT-MOUNTED ALUMINUM STANDARD SEE BELOW

RG-1 DUCT SIZE + 1-3/4" SEE PLANS RETURN RETURN GRILLE 900 0.04 - 436 21 KRUEGER S80

3/4" FIXED 35°

DEFLECTION DUCT-MOUNTED STEEL STANDARD SEE BELOW

NOTES:

1. PROVIDE TRANSITION FROM DUCT SIZE SHOWN ON PLANS TO NECK OF AIR TERMINAL AS REQUIRED.

2. PROVIDE MANUAL VOLUME DAMPER ON EACH BRANCH DUCT TO BALANCE TO AIRFLOWS SHOWN ON PLANS.

3. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING TYPES, AND COORDINATE MOUNTING OF EACH INSTANCE AS REQUIRED

4. SUBMITTAL DATA SHALL INCLUDE N.C., THROW, VELOCITY, PRESSURE DROP, AND ALL PHYSICAL & INSTALLATION DATA.

5. FOR EG-2, PROVIDE RADIUS END-CAP TO MATCH DUCT DIAMETER.

0 1 2 3 4 5 6 7 8 9 10 inches

PROJECT NO:

DESIGNED

CADD

TECH. REVIEW

DATE

SUB SHEET NO. DRAWING NO.

PKG.

NO.

SHEET

OF

TITLE OF SHEET

REVISIONS

15044.10

FIRE SCIENCES LABORATORY

MECHANICAL UPGRADES

USFS / ROCKY MOUNTAIN RESEARCH STATION

5775 US HIGHWAY 10 W

MISSOULA, MT 59808

AG-0343-C-13-0017

AG-03R6-D-15-0211

795.16.16C O N S T R U C T

IO

N D O C U M E N T S

PKG 1

M0.3

MECH SCHEDULES CONTINUED

JTW

DMP

JTW 23

MATTHEW

A

S

NO

P

I S

S

E F

O R

IG

E

R

NO

M

L

E E R

EN

G

I

ND

E

RET

A

NAT

DAVID

PIPE MATERIAL SCHEDULE

SYSTEM MATERIAL SIZES INSULATION THICKNESS** ADDITIONAL DETAILS

REFRIGERANT PIPING 'ACR' COPPER ALL 11/2" ARMAFLEX ON ALL LINES SEE BELOW

CONDENSATE PIPING TYPE "L"COPPER ALL NONE SEE BELOW

HOT WATER SUPPLY & RETURN 'L' COPPER / STEEL

(SEE SPECS FOR SIZES)

<=11/2" 11/2" WRAP WITH ASJ

SEE BELOW

>11/2" 2" WRAP WITH ASJ

STEAM PIPING BLACK STEEL 'SCHEDULE 40'

<=11/2" 11/2" WRAP SEE BELOW

>11/2" 3" WRAP SEE BELOW

PIPE MATERIAL REMARKS:

1. PROVIDE SEISMIC BRACING OF PIPING AS REQUIRED BY LOCAL CODES.

2 NO PLASTIC PIPING IS ALLOWED IN AIR PLENUMS. INSULATION IN PLENUMS MUST BE PLENUM-RATED.

3. ANY CONNECTIONS THAT ARE DISSIMILAR METALS SHALL REQUIRE DIELECTRIC COUPLING.

** BASED ON INSULATION HAVING A CONDUCTIVITY (K) NOT EXCEEDING 0.27 BTU PER INCH/H*FT^2*DEG F

HOT WATER UNIT HEATER SCHEDULE

MARK AREA SERVED MANF. MODEL NUMBER WEIGHT (LB) GPM

FAN HEATING COIL

ADDITIONAL

DETAILSCFM HP MBH

EWT

(°F)

LWT

(°F)

∆P

(FT W.C.) WORKING FLUID

HWUH-A1 BURN CHAMBER STERLING HS-240 143 10.3 3,500 1/3 96 160 130 0.5 40% PROPYLENE GLYCOL SEE BELOW

HWUH-A2 BURN CHAMBER STERLING HS-240 143 10.3 3,500 1/3 96 160 130 0.5 40% PROPYLENE GLYCOL SEE BELOW

HWUH-A3 BOILER ROOM STERLING HS-240 143 10.3 3,500 1/3 96 160 130 0.5 40% PROPYLENE GLYCOL SEE BELOW

HWUH-A4 AIR CONDITIONING EQUIPMENT STERLING HS-240 143 10.3 3,500 1/3 96 160 130 0.5 40% PROPYLENE GLYCOL SEE BELOW

HWUH-A5 3RD FLOOR MECHANICAL

PENTHOUSE STERLING HS-240 143 10.3 3,500 1/3 96 160 130 0.5 40% PROPYLENE GLYCOL SEE BELOW

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER

ELEC. DATA.

ACCESSORIES:

1. ALL STANDARD ACCESSORIES

2. FOUR-POINT CEILING SUSPENSION KIT

OR WALL BRACKET. SEE PLANS FOR

LOCATIONS.

3. TOTALLY ENCLOSED FAN MOTOR

NOTES:

1. SELECTIONS MADE AT 60°F EAT, 160°F EWT, AND A 30° F HW ∆T.

2. SEE DETAIL 11/M9.2 FOR PIPING CONNECTION.

CONTROLS:

1. DDC CONTROLS. SEE DETAIL 13/M9.7

2. PROVIDE DISCONNECT, LOW-TO-LINE VOLTAGE RELAY, WALL-MOUNTED FAN

SPEED CONTROLLER, & MODULATING CONTROL VALVE BY T.C. CONTRACTOR.

3. SEE CONTROL POINTS LIST & SEQUENCE OF OPERATION.

CONDENSING BOILER SCHEDULE

MARK INPUT (MBH) OUTPUT (MBH)

AHRI

THERMAL

EFFICIENCY

TYPE MANF. MODEL NUMBER COMB. AIR VENT TURNDOWN

GAS

CONNECTION

(TRANSITION AS REQ'D)

WORKING FLUID WET WEIGHT

(LBS)

ADDITIONAL

DETAILS

B-A1 2,500 2,300 92.0% FIRE-TUBE LOCHINVAR CREST FBN2500 8" 9" 20:1 2" 40% PROPYLENE GLYCOL 3652 SEE BELOW

B-A2 2,500 2,300 92.0% FIRE-TUBE LOCHINVAR CREST FBN2500 8" 9" 20:1 2" 40% PROPYLENE GLYCOL 3652 SEE BELOW

NOTES:

1. PROVIDE STANDARD OPTION FOR ZERO CLEARANCE TO COMBUSTIBLES.

2. PROVIDE 4" HOUSEKEEPING PAD 6" WIDER THAN EACH BOILER.

3. BOILERS SHALL BE SEALED COMBUSTION. CONTRACTOR SHALL PROVIDE PIPING

FOR AIR & FLUE TO EXTERIOR PER MANUFACTURER'S RECOMMENDATIONS. SEE

PLANS.

4. PROVIDE HIGH AND LOW GAS PRESSURE SWITCHES WITH MANUAL RESET.

PROVIDE REGULATOR AS REQUIRED & VENT TO EXTERIOR.

5. SUPPLY CONDENSATE NEUTRALIZATION KITS BY BOILER MANUFACTURER TO P.C.

P.C. SHALL ROUTE CONDENSATE PIPING TO NEAREST FLOOR DRAIN, TYP. 2.

COORDINATE W/ P.C.

6. BOILERS MUST BE ASME CSD-1 COMPLIANT TO INTERRUPT FUEL & POWER SUPPLY

TO UNIT.

7. PROVIDE SELKIRK HEATFAB SAF-T VENT CI PLUS DOUBLE-WALL VENT SYSTEM, UL

1738 LISTED FOR CONDENSING APPLIANCES, OR APPROVED EQUAL.

CONTROLS:

1. PROVIDE DDC GATEWAY, OA TEMPERATURE SENSOR, AND MOTORIZED ISOLATION

VALVES FOR VARIABLE PRIMARY PUMPING CONFIGURATION.

2. PROVIDE ADJUSTABLE HIGH LIMIT W/ MANUAL RESET.

3. PROVIDE LOW WATER CUTOFF W/ MANUAL RESET & TEST.

4. PROVIDE COMBUSTION AIR PROVING SWITCH.

5. SEE CONTROL DIAGRAM ON 5/M9.\7.

6. USER SHALL BE CAPABLE OF OVERRIDING HWS TEMPERATURE & RESET SCHEDULE.

SEE POINTS LIST.

7. PROVIDE WALL-MOUNTED ASME CSD-1 MANUAL EMERGENCY SHUT-DOWN SWITCH

INSIDE EXIT DOORS FROM BOILER ROOM TO EXTERIOR, TYP. 2. COORDINATE WITH

P.C. & E.C. TO CLOSE GAS VALVE WITH SWITCH AS REQUIRED.

ELECTRICAL DATA :

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER

ELEC. DATA.

PUMP SCHEDULE

MARK SYSTEM MANUFACTURER MODEL NUMBER TYPE WORKING FLUID FLOW RATE (GPM) HEAD LOSS (FT) MOTOR SPEED (RPM) IMPELLER DIA. (IN) VARIABLE SPEED ADDITIONAL DETAILS

HWP-1 HOT WATER TACO FI 2510C

BASE-MOUNTED,

END-SUCTION 40% PROPYLENE GLYCOL 162.5 50 1750 7 VFD SEE BELOW

HWP-2 HOT WATER TACO FI 2510C BASE-MOUNTED,

END-SUCTION 40% PROPYLENE GLYCOL 162.5 50 1750 7 VFD SEE BELOW

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER ELEC. DATA.

REMARKS:

1. PROVIDE 4" CONCRETE HOUSEKEEPING PAD UNDER EACH PUMP

2. PROVIDE VFD BY T.C. CONTRACTOR, TYP. 2. MOUNT VFD'S WHERE ACCESSABLE ON WALL OR ON (E) VERTICAL SUPPORTS FOR CONDENSATE RECEIVER

TANK.

3. E.C. SHALL PROVIDE CONDUIT AND WIRING BETWEEN PANELBOARD AND VFD, AND BETWEEN VFD AND MOTOR. COORDINATE W/ E.C.

4. PUMPS SHALL BE CONTRILLED BY DDC. SEE POINTS LIST & SEQUENCE OF OPERATION.

5. SEE CONNECTION DETAILS ON M9.3 & CONTROL DIAGRAM ON M9.7.

EXPANSION TANK SCHEDULE

MARK MANUFACTURER MODEL NUMBER TYPE WORKING FLUID

DIMENSIONS

PRESSURE RAITING (PSI) ADDITIONAL DETAILS

ACCEPTANCE VOLUME(GAL) HEIGHT (IN) DIAMETER (IN)

ET-A1 TACO CA140-125 VERTICAL BLADDER 40% PROPYLENE GLYCOL 37 40-1/8" 20" 125 ASME CONSTRUCTION

AIR/DIRT SEPARATOR SCHEDULE

MARK MANF. MODEL NUMBER TYPE MAX FLUID FLOW RATE

(GPM) WORKING FLUID TANK DIMENSIONS DRY WEIGHT (LBS) APPROX. OPERATING WEIGHT

(LBS) ADDITIONAL DETAILS

AS-A1 TACO 4905ADH-125 TANK - HIGH VELOCITY 686 40% PROPYLENE GLYCOL 57-1/2" H x 20" DIA. 225 907 ASME CONSTUCTION

AUTOMATIC GLYCOL FEEDER SCHEDULE

MARK MANUFACTURER MODEL NUMBER TANK VOLUME (GAL) PUMP GPM @ 100 PSI WEIGHT (LBS) ADDITIONAL DETAILS

GLF-A1 GENERAL TREATMENT PRODUCTS GP55-E4-1 55 1/3 HP 1.3 148 SEE BELOW

NOTES:

1. PROVIDE LOCKABLE NEMA 4X CONTROL PANEL AND ELECTRICAL DISCONNECT.

2. PROVIDE DRY CONTACTS TO ALARM DDC IN THE EVENT OF LOW LEVEL & TO ALLOW FOR MONITORING OF "HAND" STATUS.

SEE POINTS LIST.

3. PROVIDE PUMP H/O/A SWITCH, AUTOMATIC PUMP PRESSURE SWITCH, & LOW LEVEL FLOAT & PUMP SHUT-OFF SWITCH.

4. PROVIDE PRESSURE RELIEF VALVE, CHECK VALVE, & STRAINER BY UNIT MANUFACTURER.

5. SEE M9.3 & M9.6 FOR DETAILS & CONTROL DIAGRAMS.

ELECTRICAL DATA:

SEE MEP COORDINATION SCHEDULE FOR

STARTER/DISCONNECT AND ALL OTHER

ELEC. DATA.

NOTES:

1. PROVIDE AIR VENT AT TOP OF TANK AND SEPERATE FLUSH VALVE.

2. PROVIDE 2" MANUAL BLOWDOWN VALVE AT BASE OF TANK W/ HOSE THREAD END.

3. PROVIDE LIFTING LUGS. MOUNT IN-LINE. SUPPORT FROM FLOOR & BRACE FROM WALL AS REQUIRED.

GAS-FIRED STEAM GENERATOR SCHEDULE

MARK SERVES MANUF. MODEL

NUMBER

GAS INPUT STEAM OUTPUT

WEIGHT (LB) NOTESMAX

(MBH) IGNITION VENT/ FLUE

SIZE

MAX

(LB/HR)

MIN

(LB/HR) PRESSURE OUTLET

DIA.

SG-A1 SAM-A1

IN AHU-A1 NORTEC GSTC-400 560 HOT SURFACE 5" 420 25 ATMOSPHERIC 4" 992 ALL BELOW

SG-A2 SAM-A2

IN AHU-A1 NORTEC GSTC-400 560 HOT SURFACE 5" 420 25 ATMOSPHERIC 4" 992 ALL BELOW

SG-A3

SAM-A3

IN AHU-A1 NORTEC GSTC-400 560 HOT SURFACE 5" 420 25 ATMOSPHERIC 4" 992 ALL BELOW

NOTES:

1. PROVIDE APPLIANCE REGULATOR AS REQUIRED TO SUPPLY GAS PRESSURE IN MANUFACTURER'S ACCEPTABLE RANGE: 4.5-9.0 IN W.C.

2. PROVIDE MOUNTING STAND BY UNIT MANUFACTURER AND BOLT STAND TO FLOOR OF MECHANICAL LOFT.

3. PROVIDE WALL-MOUNTED DISCONNECT SWITCH FOR EACH UNIT.

4. PROVIDE STAINLESS STEEL HEAT…