Amendment_3_260902-SubmersibleLevelTransmitter-20110512.doc

DOC document 117 KB Posted

Attached to
Construction of Cascade Lakes National Scenic Byway Welcome Station
Solicitation number
AG-04GG-S-14-0002
Issued by

About this file

Amendment 3 - Submersible Level Transmitter

View the file

Other files

File Type Posted
Amendment_5_Septic_Site_Eval_F-24008.pdf PDF
Amendment_5_narrative.docx DOCX document
Amendment_5_SF-30.doc DOC document
Amendment_4_Well_Location.pdf PDF
Amendment_4_DetailScheduleItems.xlsx XLSX spreadsheet
Amendment_4_SF-30.doc DOC document
Amendment_4_8-20.docx DOCX document
Amendment_3_Interior_Finishes_Schedule.pdf PDF
Amendment_3_260573-OvercurentProtectiveDeviceCoordinationStudy.docx DOCX document
Amendment_3_specs_for_hydroseeding_and_soil_prep.docx DOCX document
Amendment_3_Addendum.docx DOCX document
Amendment_3_DeschutesDoubleGateLayout2014.pdf PDF
Amendment_3_260900-ControlsAnd_instrumentation-20140806.doc DOC document
Amendment_3_DetailScheduleItems.xlsx XLSX spreadsheet
Amendment_3_Bid_Bond_Form_SF_24.pdf PDF
Amendment_3_SF-30.doc DOC document
Amendment_2_DetailScheduleItems.xlsx XLSX spreadsheet
Amendment_2_EFS_1.pdf PDF
Amendment_2_7th_Mountain_Pit.pdf PDF
Amendment_2_USFS_CLWS_IFS-1.pdf PDF
Amendment_2_8-4.docx DOCX document
3.Welcome_St_All_Dwgs_in_Order.pdf PDF
5.Technical_Evaluation_Questionnaire.docx DOCX document
6.Fire_Clauses.pdf PDF
7.Welcome_Station_Wage_Rates_OR25_dvb.mht MHT file
4.Welcome_Station_Bidders_Packet2.docx DOCX document
2.WelcomeStAllSpecs0718.pdf PDF
1.Welcome_Station_RFP.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA Forest Service Project Specifications

SECTION 260902

submersible level (pressure) transducer INFO Subject \* MERGEFORMAT

SUBJECT \* MERGEFORMAT

1. Part 1 - General

1.01 description

A. This submersible pressure transducer shall be suitable for continuous submergence in either water or domestic sewage. The connection Junction box may have up to 100% RH condensing atmosphere.

1.02 Submittals

A. Submit shop drawings and equipment catalog data and manufacturer's installation operating and maintenance instructions for approval of the following items in accordance with Section 260010.

B. Provide both hard copy and manufacturers original PDF files with submittals in electronic form.

1.03 References

A. 260010 - General Technical Provisions.

B. 260050 - Basic Methods and Materials

2. PART 2 - PRODUCTS

2.01 submersible Pressure Transducer Specification

A. Range:

0 – 10 PSIG = 23.1 feet of water.

B. Overload:

Proof Pressure: 2 times FS

C. Burst Pressure:

35 times FS

D. Materials Contacting Media:

Transducer: 17 – 4 Stainless Steel

E. Cable:

FDA Approved Material in contact with water

F. Weight with 32’ Cable:

20 oz.

G. Electrical:

Input: 7 – 35 VDC

H. Output:

4 – 20 mA

I. Supply Sensitivity:

0.01%FS/Volt

J. Max. Loop Resistance:

(Vs-7) x 50 Ohms

K. Insulation Resistance:

> 1000 M Ohms at 50 VDC

L. Approvals:

CE and UL

M. Intrinsic safety:

For sewage applications, sensor shall be ETL approved Intrinsically Safe for Class 1, Groups C and D

1. Intrinsically safe transducer shall be suitable for use in conjunction with Gems Barrier P/N 195318.

2. Entity parameters are: Voc=28VDC, Isc=89mA, Ca=1.1microfarads, La=35.7microHenrys

N. Performance:

1. Accuracy: 0.15% (Includes hysteresis, non-linearity and repeatability)

2. Long Term Drift: 0.2% FS/year (non-cumulative)

3. Zero Tolerance: 0.1% of span

4. Span Tolerance: 0.1% of span

5. There shall be no allowance in design for zero and span adjustments

6. Strain gages in sensor should be produced by CVD process

7. Thermal Error: 1% FS Typical with “B” accuracy option

8. Compensated Temp: -5F to 180F

9. Operating Temp: -5F to 125F with Immersible Cable

10. Pressure Port: G1/8 female (others available)

11. Vibration: 35g peak, 5 to 2000 Hz

12. Acceleration: 100g in any direction. 0.032%FS/g for 15 psi decreasing logarithmically to 0.0007% FS/g for 6000 psi

13. Shock: Withstands free fall to IEC 68-2-32 procedure 1

14. Transducers should meet the requirements for CE marking as detailed in EN50082-2 for susceptibility. Test methods are defined in the following test procedures:

EN61000-4-2 Electrostatic Discharge

+/- 4kV contact discharge

+/- 8kV air discharge

EN61000-4-4 Fast Burst Transients

+/- 2kV 2 minutes

O. Accessories:

1. Potable water and Intrinsically Safe designs shall be compatible for use with Gems transient protector, P/N 195319.

2. Provide Moisture protection of vent tube for potable water or Intrinsically Safe transducer shall be accomplished using a desiccant dryer tube, Gems P/N 195316. Provide one spare desiccant dryer tube for each transducer.

P. For Potable Water:

1. Provide Gems Sensors Inc. Model 2600BGF1509M3GBxxx transducer with 32 feet of cable. Analog pressure level transducer with special 0 – 10 PSIG range and FDA approved material covering 38 feet of the cable. Verify cable lenth required prior to order with actual distance to tank.

Q. Manufacturer

1. Transducer and accessories supplied by Gems Sensors Inc., 1 Cowles Road, Plainville, CT 06062

2. Rep Ewing Foley

3. PART 3 - EXECUTION

3.01 installation & testing

A. Install sensor in water tank or sewage tank as shown on drawings. Tighten compression cord grip carefully to avoid damage to sensor cable.

B. Minimum bending radius of cable: 6”

C. Install vent tube to moisture trap with tube end down to keep free moisture from entering vent tube.

D. Install vent tube moisture trap, transient voltage surge suppressor, control cable lightning arrestors as shown on drawings.

E. Provide nameplates for all equipment in sensor connection J box as per 16010.

F. Test sensor by putting plastic electrical tape at one-foot intervals from the bottom of the sensor and immersing the sensor in water at one foot intervals and recording the current (4-20MA) up to the maximum depth of the liquid in the tank installed. Verify that resultant current meets accuracy specification above. Replace any unit not meeting specification; re-test until accuracy specification is met. Utilize a 4-1/2 digit Fluke multi-meter or equal for testing. See 16010 for complete testing requirements.

END OF SPECIFICATIONS

Pressure transducer, 32’ Cord with breather tube, 4-20MA 2 Wire submersible pressure transmitter 0-10psi = 23.1’ head water UL & CE recognized

1/8” NPT Fitting

Desiccant dryer tube

Dessicant tube, lightning protectors TVSS unit mounted in Nema 43X J box at water tank

End of Section