9- Elec Tech FA BID Drawing 657-20-101JB (16 Pages) 5 28 2021 .pdf

PDF 11 MB Posted

Attached to
Z2DA--657-20-101JB FCA-Renovate Space for Whole Health Clinic
Solicitation number
36C25522R0058
Issued by

About this file

This document provides details for a federal solicitation for renovations to space for a Whole Health Clinic. Solicitation number 36C25522R0058 was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 to renovate space for a Whole Health Clinic. The solicitation seeks bids for electrical technical drawings and related work. The response due date is not specified in the provided file, which contains 16 pages of electrical technical drawings for the project. No other salient details regarding pricing terms, set asides, award dates or incumbent contractors are included in the file.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

L L

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BYPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DED DEDICATED CIRCUIT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BDGYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK

AREA, FOR THE STARTING POINT OF THE CALCULATIONS.

METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS

USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED THE

RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH CIRCUIT CONDUCTORS.

METHOD OF VOLTAGE DROP CALCULATIONS

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

CLNG: CEILING MOUNTED

EM: EMERGENCY "RED"

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE

EQUIPMENT CONNECTION

AS

NOTED

E

208V DUPLEX RECEPTACLE18"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

2' X 2' RECESSED DIRECT/INDIRECT TROFFER

2' X 4' RECESSED DIRECT/INDIRECT TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY

VS: VACANCY SENSOR, DUAL TECHNOLOGY

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

48"

CENTER

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE

LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

OS

OS

LS

DOUBLE DRUM ACRYLIC PENDANT LIGHT---

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:0

A

M

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES

ELECTRICAL GENERAL NOTES

ELECTRICAL SYMBOL LEGENDLIGHTING SYMBOL LEGEND

DocuSign Envelope ID: E51FD6FD-9E75-48EE-A27B-857B4471886E

5/25/2021

F

S

F

S

F

S

S D

S D

SD

SD

DD

DD

F

S

F

S

SD

F

F P

F P

10.1

8.1

A.1 A.2 A.3 B C C.1 D.1 D.2

E F G H J K M N O P Q

R R.1 R.2 S T U V V.1 V.2 V.3

U.1T.2T.1R.3

LL

C.2B.2B.1A.4

D

PANEL 'EC2B'

PANEL '1-L23'

A

EXAM

2E25A

EXAM

2E25

OFFICE

2E23

WAITING

ROOM

2E26

OFFICE

2E27

OFFICE

2E22

TOILET

2E22A

TOILET

2E28

EXAM

2E29

TOILET

2E25B TOILET

2E24

EXAM

2E21

OFFICE

2E20

CHASE

CH-E-1

OFFICE

2CO5

STORAGE

2CO6

ELEVATOR

NO. 2

E2

OFFICE

2CO8

OFFICE

2CO9

CONFERENCE

ROOM

2CO7

OFFICE

2CO3

THERAPY

2CO2

OFFICE

2CO4

CORRIDOR

H210

STAIR

S201

HAC

2E01

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:1

A

M

ED101

SECOND FLOOR ELECTRICAL

DEMOLITION PLAN

2 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

NORTH

0 84 16

Scale: 3/32" = 1'-0"

SECOND FLOOR ELECTRICAL DEMOLITION PLAN

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

A. CONTRACTOR SHALL BE RESPONSIBLE FOR

TRACING AND IDENTIFYING ALL CIRCUITS AND

CONDUITS THAT ORIGINATE, PASS THROUGH,

OR TERMINATE IN THE AREA OF WORK.

DEMOLISH ALL CIRCUITS THAT ARE NO

LONGER IN USE. MAINTAIN CIRCUIT

CONTINUITY TO ALL CIRCUITS WHICH ARE

NOT COMPLETELY REMOVED.

B. CONTRACTOR TO DISCONNECT AND REMOVE

ELECTRICAL CONNECTION TO OUTLETS,

RECEPTACLES, HVAC EQUIPMENT AND OTHER

ELECTRICAL DEVICES. REMOVE

CONDUCTORS AND CONDUIT BACK TO

PANELBOARD SERVICING EQUIPMENT OR TO

THE POINT WHERE OTHER REMAINING LOADS

ARE CONNECTED. MARK ANY ABANDONED

OVERCURRENT PROTECTION DEVICE AS

"SPARE (UNUSED)".

C. CONTRACTOR SHALL REMOVE ALL

ELECTRICAL CONDUIT, CABLE, WIRING

DEVICE, JUNCTION BOXES, FITTINGS, AND

RELATED ITEMS FROM ALL PORTIONS OF THE

AREA OF WORK INCLUDING WALL, CEILING,

AND FLOORS. THIS SHALL BE FOR ALL WALLS,

EVEN WALLS NOT SUBJECT FOR REMOVAL.

D. FOR ELECTRICAL CIRCUITS BEING

DEMOLISHED REMOVE BOXES, CONDUIT AND

CONDUCTORS BACK TO SOURCE, INCLUDING

THOSE CONCEALED WITHIN WALLS, LEAVING

NO ABANDONED ITEMS.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING HOLE SHALL BE

PATCHED/REPAIRED TO MAINTAIN THE

RATING OF THE ASSEMBLY.

F. CONSTRUCTION IS TO BE PERFORMED WHILE

LEAVING WORK AREAS OF OTHER PHASES

ACTIVE TO THE GREATEST EXTENT POSSIBLE.

NOTIFY COR IF ANY WORK IS REQUIRED THAT

WILL CROSS MULTIPLE PHASES OF THE WORK

AREA PRIOR TO PERFORMING THE WORK.

G. CONTRACTOR TO DISCONNECT FIXTURES

AND STORE FOR FUTURE USE.

1 AREA OF DEMOLITION.

2 AREA BEING REMEDIATED IN SEPARATE

PROJECT BY OTHERS.

10.1

8.1

A.1 A.2 A.3 B C C.1 D.1 D.2

E F G H J K M N O P Q

R R.1 R.2 S T U V V.1 V.2 V.3

U.1T.2T.1R.3

LL

C.2B.2B.1A.4

D

A

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:1

A

M

ED102

SECOND FLOOR LIGHTING

DEMOLITION PLAN

3 10AB

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 3/32" = 1'-0"

SECOND FLOOR LIGHTING DEMOLITION PLAN

NORTH

0 84 16

A. CONTRACTOR SHALL BE RESPONSIBLE FOR

TRACING AND IDENTIFYING ALL CIRCUITS AND

CONDUITS THAT ORIGINATE, PASS THROUGH,

OR TERMINATE IN THE AREA OF WORK.

DEMOLISH ALL CIRCUITS THAT ARE NO

LONGER IN USE. MAINTAIN CIRCUIT

CONTINUITY TO ALL CIRCUITS WHICH ARE

NOT COMPLETELY REMOVED.

B. CONTRACTOR TO DISCONNECT AND REMOVE

ELECTRICAL CONNECTION TO OUTLETS,

RECEPTACLES, HVAC EQUIPMENT AND OTHER

ELECTRICAL DEVICES. REMOVE

CONDUCTORS AND CONDUIT BACK TO

PANELBOARD SERVICING EQUIPMENT OR TO

THE POINT WHERE OTHER REMAINING LOADS

ARE CONNECTED. MARK ANY ABANDONED

OVERCURRENT PROTECTION DEVICE AS

"SPARE (UNUSED)".

C. CONTRACTOR SHALL REMOVE ALL

ELECTRICAL CONDUIT, CABLE, WIRING

DEVICE, JUNCTION BOXES, FITTINGS, AND

RELATED ITEMS FROM ALL PORTIONS OF THE

AREA OF WORK INCLUDING WALL, CEILING,

AND FLOORS. THIS SHALL BE FOR ALL WALLS,

EVEN WALLS NOT SUBJECT FOR REMOVAL.

D. FOR ELECTRICAL CIRCUITS BEING

DEMOLISHED REMOVE BOXES, CONDUIT AND

CONDUCTORS BACK TO SOURCE, INCLUDING

THOSE CONCEALED WITHIN WALLS, LEAVING

NO ABANDONED ITEMS.

E. WHERE CONDUIT IS REMOVED FROM AN

EXISTING RATED ASSEMBLY NOT SUBJECT TO

DEMOLITION, THE REMAINING HOLE SHALL BE

PATCHED/REPAIRED TO MAINTAIN THE

RATING OF THE ASSEMBLY.

F. CONSTRUCTION IS TO BE PERFORMED WHILE

LEAVING WORK AREAS OF OTHER PHASES

ACTIVE TO THE GREATEST EXTENT POSSIBLE.

NOTIFY COR IF ANY WORK IS REQUIRED THAT

WILL CROSS MULTIPLE PHASES OF THE WORK

AREA PRIOR TO PERFORMING THE WORK.

G. CONTRACTOR TO REMOVE AND DISPOSE OF

ALL DEVICES SHOWN UNLESS NOTED

OTHERWISE.

1 FIXTURES IN THIS AREA ARE TO BE

DISCONNECTED AND STORED FOR REUSE IN

THE PROJECT.

GFI

DED

GFI

DED

AC

GFI

DED

AC

GFI

DED

AC

GFI

DED

36"

36"36" 60"

GFI

GFI GFI

D D

60" 60" DD

G

FI

G

FI

45"

45"

CLNG

CLNG

CLNG

CLNG

CLNG

CLNG

60"

J

J

J

GFI

DED

G

FI

36"36" 60"

36"36" 60"

36"36" 60"

GFI

GFI

G

FI

G

FI

GFI

GFI

G

FI

GFI

GFI

GFI AC

GFI

AC

GFI

GFI

GFI

GFI

36" 36"

GFI

G

FI

J

D D

DDDD DD

D D

10.1

8.1

K M N O P Q

R R.1 R.2 S T U V V.1 V.2 V.3

(TYP.)

(TYP.)

1 (TYP.)

PANEL '1-EC2B'

PANEL '1-L23'

'1-L23'- 1

'1-EC2B'- 1

'1-L23'- 2

'1-EC2B'- 2

'1-L23'- 3

'1-EC2B'- 3

'1-EC2B'- 4

'1-EC2B'- 5

OFFICE

2C02A

OFFICE

2C02B

OFFICE

2C04A

OFFICE

2C04B'1-L23'- 27

'1-L23'- 22

'1-L23'- 24

'1-L23'- 29

'1-L23'- 5

'1-L23'- 6

'1-L23'- 7

'1-L23'- 8

'1-L23'- 9

'1-L23'- 10

'1-L23'- 11'1-L23'- 14

'1-L23'- 13

'1-EC2B'- 9

'1-L23'- 15

'1-L23'- 18

'1-L23'- 19

'1-L23'- 23

'1-L23'- 20

'1-L23'- 25

'1-L23'- 26

'1-L23'- 31

'1-L23'- 28

'1-EC2B'- 6

'1-EC2B'- 17

'1-EC2B'- 11

'1-L23'- 12

'1-EC2B'- 12

'1-L23'- 27

HAC

2E01

CONSULT

2E20

OIT

2C10

OPEN OFFICE

2C09

OPEN OFFICE

2C08

MEN'S RESTROOM

2C07A

WOMEN'S RESTROOM

2C07B OFFICE

2C06

PROVIDER OFFICE

2C05

COPY AREA

2E23

OFFICE

2E24

GROUP ROOM 1A

2E26A

CLASSROOM

2E28

RECEPTION

2E22

WAITING

2E21

CLASSROOM

2E27

GROUP ROOM 2A

2E25A

CORRIDOR

H205

CORRIDOR

H202

CORRIDOR

H207

ELEV LOBBY

H206

STORAGE

2E26C

OFFICE

2C03

EXAM

2C01B

WAITING

2C01

RECEPTION

2C01A

CORRIDOR

H203

STORAGE

2E25C

STAIR S201

H208

ELEV_

H209

GROUP ROOM 1B

2E26B

GROUP ROOM 2B

2E25B

CORRIDOR

H204

MATCH LINE MATCH LINE

1 / EP101 1 / EP101

'1-EC2B'- 14

'1-EC2B'- 16

'1-EC2B'- 21

'1-L23'- 49

'1-L23'- 4

ADO

ADO

'1-L23'- 17

'1-L23'- 16

'1-L23'- 21

'1-L23'- 51

'1-EC2B'- 29

'1-EC2B'- 31,33

'1-EC2B'- 28,30

'1-L23'- 60

'1-EC2B'- 32

FAC

H210

'1-L23'- 71

EP101

P R R.1 R.2 T U V V.1 V.2 V.3

U.1T.2T.1R.3

'1-L23'- 33

PAT TLT

2E03

CONSULT

2E18

CONSULT

2E19

PAT TLT

2E02

CORRIDOR

H201

CORRIDOR

H202

OFFICE

2C04B

'1-L23'- 30

'1-L23'- 35

'1-L23'- 32

'1-L23'- 37

'1-L23'- 34

'1-L23'- 36

'1-L23'- 41

'1-L23'- 38

'1-L23'- 43

'1-L23'- 40

'1-L23'- 45

'1-L23'- 42

'1-L23'- 47

'1-L23'- 44

'1-EC2B'- 7

'1-EC2B'- 10

(TYP.)

'1-EC2B'- 8

ACUPUNCTURE

2E10

MEDITATION

2E11

MASSAGE

2E12

ACUPUNCTURE

2E09

CLEAN UTILITY

2E08

EXAM

2E13

MEDS

2E14

SOILED

2E07

CHIRO EXAM

2E06

CHIRO EXAM

2E15

CHIRO EXAM

2E05

CHIRO EXAM

2E16

CONSULT

2E17

CONSULT

2E04

PAT TLT

2E03

CONSULT

2E18

CONSULT

2E19

PAT TLT

2E02

CONSULT

2E20

CORRIDOR

H201

OFFICE

2C04B

MATCH LINEMATCH LINE

2 / EP101 2 / EP101

'1-EC2B'- 15

'1-EC2B'- 20

'1-EC2B'- 23

'1-EC2B'- 22

'1-EC2B'- 25

'1-EC2B'- 24

'1-EC2B'- 27

'1-EC2B'- 26

'1-EC2B'- 18

ADO

'1-EC2B'- 19

FAC

H210

'1-EC2B'- 39

'1-EC2B'- 34

'1-EC2B'- 35

'1-EC2B'- 36

'1-EC2B'- 37

'1-EC2B'- 38

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:3

A

M

EP101

ENLARGED SECOND FLOOR POWER

PLANS

4 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

NORTH SECOND FLOOR POWER PLAN

Scale: 1/8" = 1'-0"

SOUTH SECOND FLOOR POWER PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

1 CEILING MOUNTED EXPOSED DUPLEX

RECEPTACLE.

2 FLOOR BOX DUPLEX RECEPTACLE WITH IT

CONNECTION.

3 SEE SHEETS E-601, E-602 & E-603 FOR

INFORMATION ON FEEDER SIZING AND PANEL

SCHEDULES.

4 ELECTRICAL PANEL FACES SHALL BE SENT

OUT TO BE PROFESSIONALLY

POWDERCOATED/BAKED. COLOR IS TO BE

COORDINATED WITH THE ARCHITECTURAL

CONTRACTOR.

5 ALL RECEPTACLES TO BE MOUNTED 24" AFF.

A. ALL RECEPTACLE CONDUCTORS ARE 2-12

AWG, 1-12 AWG EG IN 3/4" CONDUIT MINIMUM

UNLESS NOTED OTHERWISE.

B. COORDINATE LOCATION AND ELECTRICAL

REQUIREMENTS OF ALL MECHANICAL AND

PLUMBING EQUIPMENT WITH MECHANICAL

AND PLUMBING CONTRACTORS.

C. COORDINATE EQUIPMENT WITH

ARCHITECTURAL & INTERIORS EQUIPMENT

PLANS AND SCHEDULES.

D. ELECTRICAL CONTRACTOR SHALL FOLLOW

SITE LOCK-OUT/TAG-OUT GUIDELINES TO DE-

ENERGIZE EQUIPMENT.

E. ALL RECEPTACLES SHALL HAVE THEIR

SOURCE PANEL AND CIRCUIT NUMBER

INDICATED ON THEIR FACEPLATE.

Scale: 1/4" = 1'-0"

ENLARGED POWER PLAN NORTH - FAC ROOM

OS OS OS OS OS OS

OS

OS

OS

OS

OS

OS

OS

O S

O S

O S

O S

OS OS

OS

O S

OS

O S

O S

O S

O S

O S

O S

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

O S

OS

O S

O S

O S

OS

O S

O S

O S

O S

O S

O S

O S

O S

O S

OS

OS

OS

10.1

8.1

K M N O P Q

R R.1 R.2 S T U V V.1 V.2 V.3

A1

A1

A1

A1

A1 A1 A1 A1

A1A1A1A1

A1

A1 A1 A1 A1

A1

A1

A1

A1 A1

A1 A1 A1

A1A1A1

A1

A1

A1 A1 A1

A1A1

A1

A1 A1 A1

A1A1

A1

A1 A1 A1

A1A1

A1

A1

A1

A1 A1

A1

A1 A1

A1A1

A1 A1 A1

A1 A1 A1

A1

A1

A1

A1

A1 A1

A1 A1

A1 A1

A1

A1

A1 A1

A1

A1 A1

A1 A1

B

B

B

X

X

X

X

X

A1

A1

A1 A1

A1

A1

A1

A1

A1A1

A1

A1

B

B

A1

A1

A1

X

MATCH LINE MATCH LINE

1 / EL101 1 / EL101

EM EM EM EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

A2

A2

A2

A2

A2

A2

EM EMA2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A1 A1 A1 A1 A1

A1A1A1

A1

A1

A1

A1

A1

A1 A1

G

G

G G G

N

(TYP.)

H H

H

H

H H

EM

1-L23 - 65 1-L23 - 65

1-L23 - 65

1-L23 - 62

A2

1-L23 - 64

1-L23 - 66

1-L23 - 67

FEM

P R R.1 R.2 T U V V.1 V.2 V.3

U.1T.2T.1R.3

A1

A1 A1

A1 A1

A1 A1

A1

A1

A1 A1

A1 A1

A1 A1

A1

A1

A1 A1

A1 A1A1

A1 A1

A1A1

A1

A1

A1

A1

A1

A1

A1

A1

A1 A1

A1

A1

A1 A1

A1

A1

A1 A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1 A1

A1

A1A1

A1 A1

A1 A1

X

MATCH LINEMATCH LINE

2 / EL101 2 / EL101

EM

EM

EM

EM

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

1-L23 - 67

1-L23 - 68

1-L23 - 68

1-L23 - 64

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:3

A

M

EL101

ENLARGED SECOND FLOOR LIGHTING

PLANS

5 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

NORTH SECOND FLOOR LIGHTING PLAN

Scale: 1/8" = 1'-0"

SOUTH SECOND FLOOR LIGHTING PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

A. ALL LIGHTING CONDUCTORS SHALL BE 2-12

AWG, 1-12 AWG EG IN 3/4" CONDUIT UNLESS

NOTED OTHERWISE:

a. RUNS LESS THAN 150' SHALL BE MINIMUM

2-12 AWG, 1-12 AWG EG IN 3/4" CONDUIT.

b. RUNS 150'-250' SHALL BE MINIMUM 2-10

AWG, 1-10 AWG EG IN 3/4" CONDUIT.

c. RUNS GREATER THAN 250' SHALL BE

MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4"

CONDUIT.

B. VERIFY COMPATIBILITY OF ALL LIGHTING

CONTROLS WITH THE LED DRIVERS TO BE

CONTROLLER.

C. FIXTURES ANNOTATED WITH 'EM' INDICATE

EMERGENCY LIGHTING FOR PATH OF EGRESS.

EXIT SIGNS ARE TO BE CIRCUITED TO THE

SAME CIRCUIT. LIGHTS ARE CIRCUITED TO

PANEL 1-EC2B. SEE PANEL SCHEDULE ON

SHEET E-601 FOR MORE INFORMATION.

1 REUSE AND REINSTALL 2X4 FIXTURES FROM

DEMO FIXTURES STORED. CONTRACTOR TO

PROVIDE AND INSTALL LIGHTS IN EXCESS OF

THOSE STORED FROM DEMOLITION PHASE.

J

J

J J

J

J J

J

J

J

J

J

J

J

J

J

J

J M

M

M

M

MM

M

M

M M

M

M M

M M

M

M

M

J

J

JJ

J

J

J

J

M

J

M

J

M

MM

J

J

J

M J

J

J

J

J

J

J J

J

J J

J

J

JM

M

M

M

M M

M

M

M

M

M

M

M

M M

M

J

J

J

J

HAC

2E01

CONSULT

2E20

OFFICE

2C02B

OIT

2C10

OPEN OFFICE

2C09

OPEN OFFICE

2C08

MEN'S RESTROOM

2C07A

WOMEN'S RESTROOM

2C07B

OFFICE

2C06

PROVIDER OFFICE

2C05

COPY AREA

2E23

OFFICE

2E24

GROUP ROOM 1A

2E26A

CLASSROOM

2E28

RECEPTION

2E22

WAITING

2E21

CLASSROOM

2E27

GROUP ROOM 2A

2E25A

CORRIDOR

H205

CORRIDOR

H202

CORRIDOR

H207 ELEV LOBBY

H206

OFFICE

2C02A

OFFICE

2C04A

STORAGE

2E26C

OFFICE

2C03

OFFICE

2C04B

EXAM

2C01B

WAITING

2C01

RECEPTION

2C01A

CORRIDOR

H203

STORAGE

2E25C

STAIR S201

H208

ELEV_

H209

GROUP ROOM 1B

2E26B

GROUP ROOM 2B

2E25B

CORRIDOR

H204

FCU-2C02B

FCU-2C02A

FCU-2C03

FCU-2C04A

FCU-2C04B

FCU-C209 FCU-2C08

FCU-2C05

FCU-2C06

FCU-2E21

FCU-2E20

FCU-2E19

FCU-2E23

FCU-2E25B

FCU-2E25A

FCU-2E26B

FCU-2E26A

FCU-2E27

FCU-2E28

FCU-2E24

1 TYP

MATCH LINE MATCH LINE

1 / EM101 1 / EM101

1-CWRP-1

FCU-H204

'1-L23'- 55

'1-L23'- 48

'1-L23'- 56

'1-L23'- 53

'1-L23'- 46

'1-L23'- 57

'1-L23'- 50

FCU-H205

'1-L23'- 52

'1-L23'- 58

'1-L23'- 63

'1-L23'- 63

FCU-H210

ACUPUNCTURE

2E10

MEDITATION

2E11

MASSAGE

2E12

ACUPUNCTURE

2E09

CLEAN UTILITY

2E08

EXAM

2E13

MEDS

2E14

SOILED

2E07

CHIRO EXAM

2E06

CHIRO EXAM

2E15

CHIRO EXAM

2E05

CHIRO EXAM

2E16

CONSULT

2E17

CONSULT

2E04

PAT TLT

2E03

CONSULT

2E18

CONSULT

2E19

PAT TLT

2E02

HAC

2E01

CONSULT

2E20

CORRIDOR

H201

CORRIDOR

H202

OFFICE

2C04B

FCU-2C04B

FCU-2E19

FCU-2E17FCU-2E04

FCU-2E16

FCU-2E05

FCU-2E06

FCU-2E15

FCU-2E14

FCU-2E13

FCU-2E08

FCU-2E09

FCU-2E12

FCU-2E11

FCU-2E10

FCU-2E18

MATCH LINEMATCH LINE

2 / EM101 2 / EM101

'1-L23'- 59

'1-L23'- 52

'1-L23'- 54

'1-L23'- 61

HU-2E08

'1-L23'- 69

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:4

A

M

EM101

SECOND FLOOR MECHANICAL POWER

PLAN

6 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

SECOND FLOOR MECHANICAL POWER PLAN

NORTH

0 4 8 16

1 3/4" LFMC FROM SINGLE POLE

MOTORSWITCH TO MECHANICAL LOAD.

2 1 120V SINGLE PHASE POWER FOR 24

POWER SOURCE FOR PLUMBING FIXTURES.

Scale: 1/8" = 1'-0"

SECOND FLOOR MECHANICAL POWER PLAN

NORTH

0 4 8 16

A. ALL CONDUCTORS ARE 2-12 AWG, 1-12 AWG

EG IN 3/4" CONDUIT MINIMUM UNLESS NOTED

OTHERWISE.

B. COORDINATE LOCATION AND ELECTRICAL

REQUIREMENTS OF ALL MECHANICAL AND

PLUMBING EQUIPMENT WITH MECHANICAL

AND PLUMBING CONTRACTORS.

C. COORDINATE EQUIPMENT WITH

ARCHITECTURAL & INTERIORS AND

MECHANICAL EQUIPMENT PLANS AND

SCHEDULES.

D. ELECTRICAL CONTRACTOR SHALL FOLLOW

SITE LOCK-OUT/TAG-OUT GUIDELINES TO DE-

ENERGIZE EQUIPMENT.

E. ALL RECEPTACLES SHALL HAVE THEIR

SOURCE PANEL AND CIRCUIT NUMBER

INDICATED ON THEIR FACEPLATE.

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)

WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF

OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.

(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL

ELECTRICAL METALLIC TUBING

D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS

PIPING MAY BE USED:

1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

OMEGA FLEX INC

2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

TITEFLEX CORP

A BUNDY CO

3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

WARD MFG INC

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT

LOCATION ON BOTH SIDES OF WALL.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN

WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.

THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,

*BEARING THE UL CLASSIFICATION MARKING

SYSTEM NO.W-L-1001

JUNE 15, 2005

F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)

T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

MAX PIPE OR

CONDUIT DIAM

IN. (mm)

1 (25)

1 (25)

4 (102)

6 (152)

12 (305)

F RATING

HR

1 OR 2

3 OR 4

1 OR 2

3 OR 4

1 OR 2

T RATING

HR

0+, 1 OR 2

3 OR 4

SECTION A-A

1B

1A

3A

A

LUMINAIRE MANUFACTURER'S

EARTHQUAKE CLIP, (4) PER

FIXTURE AT CORNERES. ATTACH

WITH SHEET METAL SCREW

FIXTURE WHIP

FROM JUNCTION

BOX

(6FT. LONG MAX.)

LUMINAIRE. REFER TO

SCHEDULE

ARCHITECTURAL

CEILING GRID

LUMINAIRE. REFER

TO SCHEDULE

ACOUSTICAL CEILING

TILE (TYP)

3 TWIST

MINIMUM (TYP)

LUMINAIRE

SUSPENSION WIRES

(#10 MIN)

ATTACHED TO

STRUCTURE

(TYP EA. CORNER)

CEILING HANGER

WIRE, TYP.

WIRE TIE OR

SCREW BAR

HANGER TO

ARCHITECTURAL

CEILING GRID TYP.

ARCHITECTURAL

CEILING GRID RECESSED CAN

LUMINAIRE

RECESSED CAN

LUMINAIRE

ARCHITECTURAL CEILING GRID

ACOUSTICAL

CEILING TILE

(TYP)

LUMINAIRE

BAR HANGERS

LUMINAIRE SUSPENSION

WIRE REFER TO

SPECIFICATION SECTION 26

51 00

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING

INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING

HARDWARE.

FIXTURE WHIP FROM

JUNCTION BOX (6'

[1829MM] LONG MAX

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

HANGER WIRE AND MOUNTING

CHANNEL ATTACHED TO

STRUCTURE. REFER TO

SPECIFICATION SECTION 26 51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

WIRE TIE THROUGH

MOUNTING CHANNEL

& CROSS BEAM, TYP.

ARCHITECTURAL

CEILING GRID

ACOUSTICAL CEILING

TILE, TYP.

ARCHITECTURAL

CEILING GRID

1/4" SCREW

JUNCTION BOX

LOCKING SQUARE

WASHER & NUT

FIXTURE WHIP FROM JUNCTION

BOX (6' [1829MM] LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING

INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING

HARDWARE.

SPRING NUT

CONDUIT FITTING

JUNCTION BOX

(SIZE AS

REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

BEAM

CLAMP,

TYP.

CONDUIT

TRAPEZE PER

SD260533-03, TYP. CONDUIT,

TYP.

STEEL

EXPANSION

ANCHOR

STRUCTURAL MEMBER

(BEAM , JOIST, ETC.), TYP.

SEISMIC OR

EXPANSION

JOINT. FIELD

VERIFY

ACTUAL

CONDITIONS &

LOCATIONS.

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

PROVIDE 127MM (5") OF SLACK AT

MIDPOINT BETWEEN TWO END OF

FLEXIBLE GALVANIZED STEEL

CONDUIT. PROVIDE GREEN INSULATED

COPPER EQUIPMENT GROUNDING

CONDUCTOR WITH FLEXIBLE CONDUIT.

914mm

(3'-0") MAX

PROVIDE EXTRA

CABLE TO MAKE

COMPLETE LOOP

AROUND BOX

PERIMETER

GENERAL NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUITS SMALLER THAN 76MM (3").

BOX S0E CONNECTOR

CEILING

4X4 BOX WITH COVER

STRAIN RELIEF

CONNECTOR 3 CORD #12 S0E CORD

NEMA L25-30FEMALE

MALE

CHAIN

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:4

A

M

E-501

ELECTRICAL DETAILS

7 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

Scale: No Scale

UL PENETRATION DETAIL W-L-1001

Scale: No Scale

LUMINAIRE MOUNTING - LAY-IN CEILING

Scale: No Scale

DOWNLIGHT MOUNTING - LAY-IN CEILING

Scale: No Scale

EXIT SIGN MOUNTING - LAY-IN CEILING

Scale: No Scale

CONDUIT EXPANSION JOINT CROSSING - FLEXIBLE

CONDUIT

Scale: No Scale

CHAIN HUNG FIXTURE

LUMINAIRE SCHEDULE

A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE

FOR MISMATCHED OR INACCURATE PART NUMBERS.

B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH COR.

C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE

SUBMITTALS.

D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH

THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.

E. WHERE EMERGENCY LIGHTING IS SHOWN ON DRAWING INCLUDE "EM LED" TO CATALOG NUMBER.

GENERAL NOTES:

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:5

:4

A

M

E-601

ELECTRICAL SCHEDULES

8 10KG

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

DAS

TYPE DESCRIPTION MOUNTING LAMP BALLAST/DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER

A1 2' X 2' DIRECT/INDIRECT TROFFER; WITH

CURVED SMOOTH CENTER DIFFUSER

LED; 3800

LUMENS; 80

CRI; 4000K

0-10V DIMMABLE TO 5%

LED DRIVER

120.00 V 38 W PHILLIPS DAYBRITE 2-EV-G-38L-840-2-DS-UN

V-DIM (EMLED) (E)

A2 2' X 4' DIRECT/INDIRECT TROFFER; WITH

CURVED SMOOTH CENTER DIFFUSER

LED; 4800

LUMENS; 80

CRI; 4000K

0-10V DIMMABLE TO 5%

DRIVER

120.00 V 36 W PHILLIPS DAYBRITE DFR 2X4 LED42 40K DIM

OSDL PHIL

B 6" DIAMETER DIMMABLE LED MEDIUM WIDE

DISTRIBUTION DOWNLIGHT WITH CLEAR

REFLECTOR & FLANGE AND MATTE-DIFFUES

FINISH

RECESSED

GRID

LED; 1000

LUMENS; 83

CRI; 4000K

0-10V DIMMABLE TO 5%

LED DRIVER

120.00 V 27 W VICATO SPECTRUM

LTG

RFDO6LEDXT20L35KDS1

01CB24MWGLX

F 4' LINEAR LED INDUSTRIAL STRIP LIGHT WITH

LENS

CHAIN

SUSPEND

LED; 4000

LUMENS; 80

CRI; 3000K

ELECTRONIC LED DRIVER 120.00 V 40 W PHILLIPS DAYBRITE FSS-4-4-L-830-UNV-DIM

G DECORATIVE PENDANT; BLACK FINISH; AQUA

BLOWN GLASS DIFFUSER

PENDANT LED; 1000

LUMENS; 90

CRI; 3500K

0-10V DIMMABLE LED

DRIVER

120.00 V 14 W BRUCK LIGHTING BOBO 3 LLED 35K 90 971

BK PBK

H 4" DIAMETER ADJUSTABLE LENSED WALL

WASH DOWNLIGHT

RECESSED

GRID

LED; 1500

LUMENS; 80

CRI; 3500K

0-10V DIMMABLE TO 1%

LED DRIVER

120.00 V 20 W KIRLIN LRR-04022-1500L-120-D1-

MFL

N 30" DECORATIVE DOUBLE ACRYLIC DRUM PENDANT LED; 4460

LUMENS; 80

CRI; 4000K

0-10V DIMMABLE LED

DRIVER

120.00 V 35 W BROWNLEE 2608-NT-C37-SSM-40K-DT

R

X CONTEMPORARY LED DOUBLE FACED EXIT

SIGN WITH WHITE PLASTIC HOUSING,\ RED

LETTERS, AND CHEVRON ARROWS AS

SHOWN ON PLANS.

UNIVERSAL LED --- 120.00 V 6 W EXITRONIX BARRON

LTGGRP

VEXUBPWBWHUSAVEPA

MCB SHALL BE FITTED WITH TERMINALS CAPABLE OF ACCEPTING 500kCMIL CONDUCTORS.

Notes:

LIGHTING (GENERAL) 7.37 kVA 125.00% 9.22 kVA

LIGHTING 0.01 kVA 125.00% 0.01 kVA Total Est. Demand: 107 A

RECEPTACLES (DEDICATED) 0.84 kVA 100.00% 0.84 kVA Total Conn.: 129 A

RECEPTACLES (GENERAL) 30.42 kVA 66.44% 20.21 kVA Total Est. Demand: 38.72 kVA

MOTOR/HVAC 7.97 kVA 105.96% 8.45 kVA Total Conn. Load: 46.61 kVA

Other 0.00 kVA 0.00% 0.00 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 139 A 113 A 144 A

Total Load: 16.31 kVA 13.50 kVA 16.80 kVA

83 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 84

81 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 82

79 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 80

77 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 78

75 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 76

73 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 74

71 OFFICE 2C03 FUTURE PRINTER 20 A 1 0.18 0.00 1 20 A SPARE 72

69 HUMIDIFIER RM 2E07 20 A 1 1.90 0.00 1 20 A SPARE 70

67 LIGHTING - S CORRIDOR, RESTROOMS & HAC 20 A 1 0.59 1.94 1 20 A LIGHTING - EXAM ROOMS 68

65 LIGHTING - OFFICES 20 A 1 1.67 1.44 1 20 A LIGHTING - GROUP & CLASS ROOMS 66

63 GROUP ROOMS SINK FIXTURES 20 A 1 0.10 1.06 1 20 A LIGHTING - WAITING AND CONSULT ROOMS 64

61 FCUs - ACUPUNCTURE, MASSAGE,... 20 A 1 0.80 0.67 1 20 A LIGHTING - WEST CORRIDOR & RESTROOMS 62

59 FCUs - CONSULT ROOMS AND CHIRO EXAM... 20 A 1 0.80 0.72 1 20 A OFFICE 2C03 RCPT 60

57 FCUs - OFFICES AND RESTROOMS 20 A 1 0.32 0.16 1 20 A WATER FOUNTAIN/BOTTLE FILLER H207 58

55 FCUs - OPEN OFFICES, WEST OFFICES 20 A 1 0.64 0.05 1 20 A COLD WATER RECIRC PUMP 56

53 FCUs - CLASSROOMS & GROUP ROOM 1 20 A 1 0.64 0.48 1 20 A FCUs - CHIRO EXAM, SOILED, MEDS RMS 54

51 OFFICE 2C08 RCPT 20 A 1 0.54 0.48 1 20 A FCUs - CONSULT ROOMS AND PATIENT... 52

49 OFFICE 2C09 RCPT 20 A 1 1.08 0.64 1 20 A FCUs - OFFICES & CORRIDOR 50

47 ACCUPUNCTURE RM 2E10 RCPT 20 A 1 0.54 0.96 1 20 A FCUs - GROUP ROOM 2, CORRIDOR,... 48

45 ACCUPUNCTURE RM 2E09 RCPT 20 A 1 0.54 0.30 1 20 A RESTROOM FIXTURES 46

43 CHIRO EXAM RM 2E06 RCPT 20 A 1 0.54 0.54 1 20 A MEDITATION RM 2E11 RCPT 44

41 MEDS ROOM 2E14 RCPT 20 A 1 0.54 0.54 1 20 A MASSAGE RM 2E12 RCPT 42

39 CHIRO EXAM RM 2E16 RCPT 20 A 1 0.54 1.08 1 20 A SOILED & CLEAN UTILITY RMS 2E07 & 2E08... 40

37 CONSULT RM 2E04 RCPT 20 A 1 1.08 0.54 1 20 A EXAM RM 2E13 RCPT 38

35 CONSULT RM 2E18 RCPT 20 A 1 1.08 0.72 1 20 A CHIRO EXAM RM 2E15 RCPT 36

33 HAC & RESTROOMS RCPT 20 A 1 0.54 0.54 1 20 A CHIRO EXAM RM 2E05 RCPT 34

31 WAITING ROOM RCPT 20 A 1 0.90 1.08 1 20 A CONSULT RM 2E17 RCPT 32

29 OFFICE 2C06 RCPT 20 A 1 0.72 1.08 1 20 A CONSULT RM 2E19 RCPT 30

27 OFFICES 2C02A & 2C02B RCPT 20 A 1 0.72 0.72 1 20 A CONSULT RM 2E20 RCPT 28

25 CLASSROOM 2E27 RCPT 20 A 1 1.08 0.54 1 20 A WAITING ROOM RCPT 26

23 CLASSROOM 2E27 RCPT 20 A 1 1.08 0.54 1 20 A OFFICE 2C05 RCPT 24

21 GROUP ROOM 1B 2E25B RCPT 20 A 1 0.72 0.72 1 20 A OFFICES 2C04A & 2C04B RCPT 22

19 GROUP ROOM 1A 2E26A RCPT 20 A 1 0.90 0.54 1 20 A CLASSROOM 2E28 RCPT 20

17 CLASSROOM 2E27 RCPT 20 A 1 0.54 0.90 1 20 A GROUP ROOM 2B 2E25B RCPT 18

15 COPY AREA RCPT 20 A 1 0.36 0.18 1 20 A GROUP ROOM 2A 2E25A RCPT 16

13 RECEPTION COPIER RCPT 20 A 1 0.18 0.18 1 20 A RECEPTION SHREDDER RCPT 14

11 OFFICE 2E24 RCPT 20 A 1 0.72 0.54 1 20 A RECEPTION RCPT 12

9 OFFICE 2C03 COPIER 20 A 1 0.18 0.36 1 20 A RESTROOMS 2C07 RCPT 10

7 OFFICE 2C03 MICROWAVE 20 A 1 0.18 0.18 1 20 A OFFICE 2C03 KITCHEN AREA RCPT 8

5 OFFICE 2C03 REFRIGERATOR 20 A 1 0.18 0.18 1 20 A OFFICE 2C03 KITCHEN AREA RCPT 6

3 OFFICE 2C09 RCPT 20 A 1 0.90 0.54 1 20 A OFFICE 2C08 RCPT 4

1 OFFICE 2C03 RCPT 20 A 1 0.72 0.72 1 20 A OFFICE 2C03 RCPT 2

CKT Circuit Description Trip Poles

A B C A B C

Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA1 MCB Rating:

Mounting: RECESSED Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: Volts: 120/208 A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: 1-L23

Notes:

LIGHTING (GENERAL) 0.78 kVA 125.00% 0.97 kVA Total Est. Demand: 58 A

RECEPTACLE (DEDICATED) 4.99 kVA 100.00% 4.99 kVA Total Conn.: 65 A

Power 2.00 kVA 100.00% 2.00 kVA Total Est. Demand: 20.88 kVA

RECEPTACLES (DEDICATED) 0.36 kVA 100.00% 0.36 kVA Total Conn. Load: 23.25 kVA

RECEPTACLES (GENERAL) 15.12 kVA 83.08% 12.56 kVA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 69 A 74 A 55 A

Total Load: 8.00 kVA 8.66 kVA 6.59 kVA

41 SPARE 20 A 1 0.00 0.00 1 20 A SPARE 42

39 FAC RM H210 SERVICE RCPT 20 A 1 0.36 0.00 1 20 A SPARE 40

37 PAGING AMPLIFIER - RM H210 20 A 1 0.18 0.18 1 20 A CCTV EQUIPMENT - RM H210 38

35 PACS PANEL - RM H210 20 A 1 0.18 0.18 1 20 A NAC PANEL - RM H210 36

33 1.25 0.18 1 20 A NURSE CALL EQUIPMENT CABINET - RM H210 34

IT RACK #2 RM 2C10 RCPT 20 A 2

1.25 0.50 1 20 A NURSE CALL EQUIPMENT CABINET - RM 2C10 32

29 SERVICE RECEPTACLES IT RM 2C10 20 A 1 0.72 1.25 30

27 MASSAGE RM 2E12 RCPT 20 A 1 0.58 1.25

2 20 A IT RACK #1 RM 2C10 RCPT

25 ACCUPUNCTURE RM 2E10 RCPT 20 A 1 0.58 0.58 1 20 A EXAM RM 2E13 RCPT 26

23 CHIRO EXAM RM 2E06 RCPT 20 A 1 0.58 0.58 1 20 A MEDITATION RM 2E11 RCPT 24

21 CONSULT RM 2E20 RCPT 20 A 1 0.36 0.58 1 20 A ACCUPUNCTURE RM 2E09 RCPT 22

19 CHIRO EXAM RM 2E15 RCPT 20 A 1 0.58 0.58 1 20 A CHIRO EXAM RM 2E05 RCPT 20

17 CHECK-IN KIOSK RCPT 20 A 1 0.36 0.58 1 20 A CHIRO EXAM RM 2E16 RCPT 18

15 AUTOMATIC DOOR OPENER CORRIDOR H202 20 A 1 0.50 0.72 1 20 A RECEPTION WORKSTATIONS & 2E24 RCPT 16

13 EMERGENCY LIGHTING 20 A 1 0.78 1.00 1 20 A AUTOMATIC DOOR OPENER CORRIDOR H204. 14

11 OFFICE 2C04A, 2C04B, 2C05, 2C06 RCPT 20 A 1 0.72 0.36 1 20 A OFFICES 2C02A & 2C02B RCPT 12

9 RECEPTION WORKSTATIONS RCPT 20 A 1 0.72 0.36 1 20 A CORRIDOR RCPT 10

7 MED ROOM 2E14 RCPT 20 A 1 0.18 0.18 1 20 A MED RM 2E14 MEDICATION DISPENSER RCPT 8

5 CORRIDOR RCPT 20 A 1 0.54 0.54 1 20 A CORRIDOR RCPT 6

3 OFFICE 2C09 RCPT 20 A 1 0.90 0.90 1 20 A OFFICE 2C08 RCPT 4

1 OFFICE 2C03 RCPT 20 A 1 0.72 0.72 1 20 A OFFICE 2C03 RCPT 2

CKT Circuit Description Trip Poles

A B C A B C

Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA1 MCB Rating:

Mounting: RECESSED Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type: MLO

Location: Volts: 120/208 A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: 1-EC2B

225 A

MCB

1-PANEL-L23

208.0 V

225.0 A

CBL1-PANEL-L23

88.0 ft

1 per phase

500 kcmil

Copper

SPARE

ECB

TO 1-ATS1-LSA TO 1-ATS1-EDP25 TO 1-ATS1-EMDP TO 1-ATS1-CDP

TO 1-ATS1-ELEV-WEST

TO 1-ATS1-ELEV-EAST

5.0 ft

1 per phase

4/0 AWG

Copper

208.0 V

100.0 A

CUTLER-HAMMER

DG

100.0 A

208.0 V

0.0 A

208.0 V

0.0 A

WESTINGHOUSE

HLB

400.0 A

WESTINGHOUSE

HKB

200.0 A

WESTINGHOUSE

HKB

200.0 A

CUTLER-HAMMER

HCA

225.0 A

CUTLER-HAMMER

HCA

225.0 A

CUTLER-HAMMER

DA

400.0 A

HJD

350.0 A

CUTLER-HAMMER

DA

400.0 A

CUTLER-HAMMER

DA

400.0 A

WESTINGHOUSE

NB

700.0 A

CUTLER-HAMMER

LD

600.0 A

WESTINGHOUSE

HKB

250.0 A

WESTINGHOUSE

FDB

100.0 A

CUTLER-HAMMER

LSB-E

400.0 A

CUTLER-HAMMER

KDB

400.0 A

WESTINGHOUSE

HKB

250.0 A

WESTINGHOUSE

HJD

250.0 A

CUTLER-HAMMER

LSB-E

400.0 A

WESTINGHOUSE

FD

100.0 A

CUTLER-HAMMER

HKD

300.0 A

CUTLER-HAMMER

LSB-E

400.0 A

WESTINGHOUSE

HLA

400.0 A

50.0 ft

1 per phase

500 kcmil

Copper

177.0 ft

1 per phase

500 kcmil

Copper

72.0 ft

1 per phase

350 kcmil

Copper

76.0 ft

1 per phase

2 AWG

Copper

50.0 ft

2 per phase

3/0 AWG

Copper

338.0 ft

1 per phase

3/0 AWG

Copper

88.0 ft

1 per phase

3/0 AWG

Copper

50.0 ft

1 per phase

500 kcmil

Copper

50.0 ft

1 per phase

500 kcmil

Copper

50.0 ft

1 per phase

2 AWG

Copper

50.0 ft

1 per phase

300 kcmil

Copper

100.0 ft

1 per phase

8 AWG

Copper

50.0 ft

2 per phase

350 kcmil

Copper

50.0 ft 1 per phase 300 kcmil

Copper

50.0 ft

1 per phase

300 kcmil

Copper

208.0 V

225.0 A

50.0 ft

1 per phase

300 kcmil

Copper

208.0 V

225.0 A

270.0 ft

1 per phase

250 kcmil

Copper

208.0 V

200.0 A

258.0 ft

1 per phase

250 kcmil

Copper

208.0 V

225.0 A

230.0 ft

1 per phase

2 AWG

Copper

CUTLER-HAMMER

EB

100.0 A

208.0 V

225.0 A

174.0 ft

1 per phase

2/0 AWG

Copper

GE

THQD

225.0 A

208.0 V

200.0 A

50.0 ft

1 per phase

2/0 AWG

Copper

291.0 ft

1 per phase

600 kcmil

Copper

NumMotors 1

Total 7.5 hp

50.0 ft

1 per phase

6 AWG

Copper

SIEMENS

HBL

70.0 A

NumMotors 1

Total 15 hp

50.0 ft

1 per phase

2 AWG

Copper

SIEMENS

HBL

100.0 A

NumMotors 1

Total 7.5 hp

50.0 ft

1 per phase

6 AWG

Copper

SIEMENS

HBL

70.0 A

SIEMENS

HBL

100.0 A

208.0 V

400.0 A

NumMotors 1

Total 3 hp

50.0 ft

1 per phase

10 AWG

Copper

SIEMENS

HBL

40.0 A

208.0 V

100.0 A

50.0 ft

1 per phase

4 AWG

Copper

CUTLER-HAMMER

EB

60.0 A

208.0 V

400.0 A

CUTLER-HAMMER

LSB-E

400.0 A

208.0 V

225.0 A

208.0 V

225.0 A

136.0 ft

1 per phase

3/0 AWG

Copper

208.0 V

225.0 A

NumMotors 1

Total 10 hp

50.0 ft

1 per phase

8 AWG

Copper

CUTLER-HAMMER

EB

30.0 A

3.0 ft

1 per phase

2 AWG

Copper

NumMotors 1

Total 30 hp

55.0 ft

1 per phase

1 AWG

Copper

SIEMENS

NGB

125.0 A

NumMotors 1

Total 30 hp

52.0 ft

1 per phase

1 AWG

Copper

SIEMENS

NGB

125.0 A

208.0 V

250.0 A

SIEMENS

HQJ2H

225.0 A

50.0 ft

1 per phase

250 kcmil

Copper

55.0 ft

1 per phase

250 kcmil

Copper

45.0 ft

1 per phase

2 AWG

Copper

208.0 V

225.0 A

208.0 V

100.0 A

208.0 V

225.0 A

5.0 ft

1 per phase

350 kcmil

Copper

208.0 V

400.0 A

CUTLER-HAMMER

LSB-E

400.0 A

208.0 V

100.0 A

186.0 ft

1 per phase

8 AWG

Copper

C…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .