7-Plumb Bid Drawing 657-20-101JB (8 Pages) 5 28 2021 .pdf

PDF 3 MB Posted

Attached to
Z2DA--657-20-101JB FCA-Renovate Space for Whole Health Clinic
Solicitation number
36C25522R0058
Issued by

About this file

This document package includes plans and specifications for a plumbing renovation project at a VA medical center. The project involves demolishing and replacing waste, vent, and domestic water piping on the second floor to renovate space for a new whole health clinic. The package provides demolition plans, new construction plans, plumbing fixture schedules, general notes, specifications and construction details. Key project details include demolishing existing piping and installing new sanitary drainage, vent, and domestic water systems to support plumbing fixtures in the renovated clinic spaces. The project will connect to existing infrastructure and must carefully coordinate shutdowns and tie-ins to maintain medical center operations.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ANNOTATION ABBREVIATIONS

PLUMBING ABBREVIATIONS

3-WAY CONTROL VALVE

ANGLE GATE VALVE

ANGLE GLOBE VALVE

BALANCING/SHUTOFF VALVE

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

CALIBRATED BALANCING VALVE

CONTROL VALVE

EXPANSION VALVE

GATE VALVE

GLOBE VALVE

QUICK OPEN VALVE

SAFETY RELIEF VALVE

SOLENOID VALVE

BACKFLOW PREVENTER

ECCENTRIC REDUCER

CONCENTRIC REDUCER

FLOW ARROW

HOSE BIBB / SILLCOCK

VACUUM RELIEF VALVE

GAS COCK

PLUG VALVE

PLUMBING SYMBOLS

PRESSURE REDUCING VALVE (WATER)

PRESSURE REGULATOR (GAS)

PIPE ANCHOR

PIPE GUIDES

WALL CLEANOUT

SUSPENDED CLEANOUT

WCO

WYE STRAINER

WYE STRAINER W/DRAIN VALVE

FLOOR DRAIN - ROUND OR SQUARE

FLOOR CLEANOUT - ROUND OR SQUARE

PIPE CAP

PIPE TURNING DOWN

PIPE TURNING UP

TEE UP

TEE DOWN

DROP AND RUN

DROP AND TURN

TEE OFF TOP

TEE OFF BOTTOM

CROSS AND RISER

PLAN 90° ELBOW

PIPE TEE

PIPE UNION

FLEXIBLE PIPE CONNECTOR

WATER METER

PUMP

AUTOMATIC AIR VENT

PRESSURE SWITCH

PRESSURE GAUGE

THERMOMETER

FLOW SWITCH

TEMPERATURE SWITCH

OR

OR

CO

PIPE SLOPE ARROW

F

P

T

M

DCWR

DHW

PIPING SYSTEM

NG NATURAL GAS

ST STORM

OFD OVERFLOW STORM DRAIN

SAN SANITARY WASTE

N NITROGEN

N2O NITROUS OXIDE

O OXYGEN

MV MEDICAL VACUUM

V SANITARY VENT

DCW DOMESTIC COLD WATER

DOMESTIC CW RECIRCULATION

DOMESTIC HOT WATER

PLUMBING SYMBOLS

ANNOTATION SYMBOLS

(E)EXISTING

NEW KEYNOTE

DEMO KEYNOTE

NEW BOLD TEXT INDICATES NEW ITEM

TEXT INDICATES EXISTING ITEM

PLUMBING EQUIPMENT DESIGNATION

DETAIL OR SECTION MARK

SHOWN ON DRAWING

DETAIL MODULE NUMBER

CONNECT TO EXISTING

LIMITS OF DEMOLITION

P-###

DHWR DOMESTIC HW RECIRCULATION

PLUMBING GENERAL NOTES

PLUMBING DEMOLITION GENERAL NOTES

1. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR REGARDING CONFLICTS BEFORE

PROCEEDING WITH WORK.

2. REMOVED ITEMS REMAIN PROPERTY OF GOVERNMENT UNTIL COR DETERMINES THAT THEY ARE NOT REQUIRED. REMOVE FROM SITE ITEMS NOT BEING RETAINED BY GOVERNMENT OR REINSTALLED AS PART OF

THIS WORK.

3. DO NOT DISTURB ITEMS NOT INDICATED FOR DEMOLITION.

4. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION. COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTORS FOR ANY MECHANICAL OR ELECTRICAL ITEMS THAT NEED TO BE

RELOCATED, REMOVED OR ADJUSTED IN ORDER TO PERFORM PLUMBING WORK.

5. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING OR NEW ADJACENT

CONDITIONS.

6. COORDINATE DEMOLITION WITH COR. SUBMIT SHUTDOWN PLAN AND SCHEDULE TO COR FOR REVIEW AND APPROVAL. COORDINATE ANY REQUIRED SHUTDOWNS WITH THE COR A MINIMUM OF THREE (3) WEEKS IN

ADVANCE.

7. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION. REPAIR UTILITIES AND SERVICES

DAMAGED AT NO ADDITIONAL COST TO THE GOVERNMENT.

8. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE WORK.

9. SAWCUT CONCRETE FLOOR AS REQUIRED FOR DEMOLITION WORK INDICATED. COORDINATE WITH NEW PLUMBING AND WORK OF OTHER TRADES. PATCH AND REPAIR FLOOR AFTER PLUMBING WORK IS COMPLETE.

1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL/FEDERAL CODES AND APPLICABLE

VA STANDARDS.

2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTRUCTIONS.

3. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE

GRADE FOR THE PURPOSES INTENDED.

4. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS ARE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY

AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.

5. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR

EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.

6. PROVIDE A PISTON-TYPE WATER HAMMER ARRESTOR WHERE INDICATED ON DETAIL ON SHEET P-501 AND WHERE REQUIRED BY SPECIFICATION SECTION 22 11 00. SIZE PER MANUFACTURER’S RECOMMENDATIONS.

7. SANITARY DRAINAGE PIPING INDICATED IS LOCATED BELOW FLOOR SLAB OR WITHIN WALLS UNLESS NOTED OTHERWISE. SANITARY VENT PIPING INDICATED IS ABOVE THE CEILING OR WITHIN WALLS UNLESS NOTED

OTHERWISE.

8. SUPPORT PIPING SYSTEM AS REQUIRED BY APPLICABLE LOCAL, STATE, AND NATIONAL/FEDERAL CODES

ALONG WITH SPECIFICATIONS, VA STANDARDS AND MANUFACTURER'S RECOMMENDATIONS.

9. FIRESTOP AND SEAL PIPING PENETRATIONS THROUGH WALLS AND FLOORS EQUAL TO THE RATING OF

WALLS AND FLOORS.

10. TEST PLUMBING SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND NATIONAL CODES AND

APPLICABLE VA STANDARDS.

11. COORDINATE PLUMBING PIPING WITH WORK OF OTHER DISCIPLINES.

12. DISINFECT DOMESTIC WATER SYSTEM IN ACCORDANCE WITH APPLICABLE LOCAL, STATE, AND

NATIONAL/FEDERAL CODES AND APPLICABLE VA STANDARDS.

13. PROVIDE SHUT OFF VALVES AT BRANCH PIPING TO FIXTURES.

14. COORDINATE PLUMBING WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION. COORDINATE ROUTING

OF PIPING WITH EXISTING CONDITIONS.

15. PROVIDE ALL NECESSARY OFFSETS, TEES, ELBOWS, ETC. FOR A COMPLETE AND COORDINATED WORKING PLUMBING SYSTEM. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND

ARRANGEMENT OF PIPING SYSTEMS.

16. CONTRACTOR SHALL COORDINATE ANY PLUMBING SYSTEM REQUIRED SHUTDOWN WITH THE COR THREE (3)

WEEKS IN ADVANCE.

17. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH PLUMBING WORK OF THIS

CONTRACT, UNLESS NOTED OTHERWISE.

18. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF

PROJECT.

19. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.

20. DO NOT INSTALL PIPES ABOVE TELECOM OR ELECTRICAL EQUIPMENT.

A/E ARCHITECT/ENGINEER

AC ABOVE CEILING

AD AREA DRAIN

AFF ABOVE FINISHED FLOOR

AG AIR GAP

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

AFG ABOVE FINISHED GRADE

ASD ADJUSTABLE SPEED DRIVE

ASHRAE AMERICAN SOCIETY HEATING,

REGRIGERATING, AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

BAS BUILDING AUTOMATION SYSTEM

BF BELOW FLOOR

BFP BACKFLOW PREVENTER

BG BELOW GRADE

BH BOOSTER HEATER

BHP BREAK HORSEPOWER

BJ BETWEEN JOISTS

BOP BOTTOM OF PIPE

BSP BLACK STEEL PIPE

BT BATHTUB

BTUH BRITISH THERMAL UNITS PER HOUR

C CELSIUS

CF COMBINATION FIXTURE

CGA COMPRESSED GAS ASSOCIATION

CI CAST IRON

CLG CIELING

CO CLEANOUT

COND CONDENSATE

CP CONDENSATE PUMP

CS CLINICAL SINK

CV CONTROL VALVE

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DF DRINKING FOUNTAIN

DI DEIONIZED WATER

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

EC ELECTRICAL CONTRACTOR

EL ELEVATION

EMCS ENERGY MONOSERRAT AND CENTRAL

SYSTEM

EPA ENVIRONMENTAL PROTECTION

AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWS EYEWASH STATION

EX EXISTING

F FAHRENHEIT

FA FROM ABOVE

FB FROM BELOW

FBO FURNISHED BY OTHERS

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT (HOSE)

CONNECTION

FL FIRE LINE

FLR FLOOR

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FU FIXTURE UNITS

G GALLON

GC GENERAL CONTRACTOR

GCO GRADE CLEANOUTS

GD GARBAGE DISPOSAL

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED WATER HEATER

H&CW HOT AND COLD WATER

HB HOSE BIBB (INTERIOR)

HD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS HAND SINK

HST HOT WATER STORAGE TANK

(DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HYD HYDRANT

ICW INDUSTRIAL COLD WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

KW KILOWATT

KWHR KILOWATT-HOUR

L/S LITER PER SECOND

LA LABORATORY AIR

LAV LAVATORY

LBS/HR POUNDS PER HOUR

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH THOUSANDS OF BTU PER HOUR

MC MECHANICAL CONTRACTOR

MED MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MH MANHOLE

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SINK BASIN

MV MEDICAL VACUUM

N2 NITROGEN

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OR OPERATING ROOM

OVFL OVERFLOW

PA PACAL

PC PLUMBING CONTRACTOR

PD PRESSURE DROP

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAUGE

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH

ATMOSPHERE

PSIG POUNDS PER SQUARE INCH GAUGE

PTRV PRESSURE TEMPERATURE RELIEF

VALVE

PW POTABLE WATER

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RO REVERSE OSMOSIS

RWL RAIN WATER LEADER

SAN SANITARY SEWER

SCFM STANDARD CUBIC FOOT/MIN

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT SQUARE FOOT

SS STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

TCV TEMPERATURE CONTROL VALVE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TDL TEMPERATURE DIFFERENTIAL

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

UPC UNIFORM PLUMBING CODE

V SANITARY VENT

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAUGE

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

WHD WALL HYDRANT

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

YCO YARD CLEANOUT

YH YARD HYDRANT

CIRCUIT SETTER VALVE

NG

ST

OFD

SAN

N

N2O

O

MV

V

LA MEDICAL LAB AIRLA

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:5

A

M

P-001

PLUMBING GENERAL INFORMATION

1 8JT/SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

PLUMBING LOAD SUMMARY

MARK DESCRIPTION QUANTITY DFU EACH DFU

CW WSFU

EACH

CW WSFU

HW WSFU

EACH HW WSFU

TOTAL WSFU

EACH TOTAL WSFU

P-103 WATER CLOSET, FLUSH VALVE, WALL MOUNT, PUBLIC 6 4 24 10 60 0 0 10 60

P-204 URINAL, WASHOUT, LOW 1 4 2 3 3 0 0 3 3

P-408 LAVATORY, WALL MOUNT, WRIST BLADES, PUBLIC 12 1 12 1.5 18 1.5 18 2 24

P-418 LAVATORY, WALL MOUNT, SENSOR, PUBLIC 3 1 3 1.5 4.5 1.5 4.5 2 6

P-420 SOLID SURFACE INTEGRAL LAVATORY FAUCET, SENSOR, PUBLIC. 4 1 4 1.5 6 1.5 6 2 8

P-502 SERVICE SINK, TERRAZO MOP 1 2 2 3 3 3 3 4 4

P-528 SINK, COUNTER MOUNT, SINGLE COMPARTMENT, CORROSION-RESISTANT STEEL 2 3 6 1.5 3 1.5 3 2 4

P-604 ELECTRIC WATER COOLER 1 4 0.5 10 0.25 0 0 10 0.25

30 53.5 97.75 34.5 109.25

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION QUANTITY WASTE PIPE VENT PIPE

COLD

WATER HOT WATER

WRIST BLADE

HANDLES

ELECTRIC

SENSOR REMARKS

FD-D FLOOR DRAIN, TYPE D 5 3" - - - - -

P-103 WATER CLOSET, FLUSH VALVE, WALL MOUNT, PUBLIC 6 4" 2" 1" - - YES WATER CLOSET, FLUSH VALVE, WALL MOUNT, PUBLIC

P-204 URINAL, WASHOUT, LOW 1 2" 1 1/2" 3/4" - - YES URINAL, WASHOUT, LOW

P-408 LAVATORY, WALL MOUNT, WRIST BLADES, PUBLIC 12 2" 1 1/2" 3/8" 3/8" YES NO LAVATORY, WALL MOUNT, WRIST BLADES, PUBLIC

P-418 LAVATORY, WALL MOUNT, SENSOR, PUBLIC 3 2" 1 1/2" 3/8" 3/8" NO YES LAVATORY, WALL MOUNT, SENSOR, PUBLIC

P-420 SOLID SURFACE INTEGRAL LAVATORY FAUCET, SENSOR,

PUBLIC.

4 2" 1 1/2" 3/8" 3/8" NO YES FAUCET.

P-502 SERVICE SINK, TERRAZO MOP 1 3" 1 1/2" 1/2" 1/2" NO NO SERVICE SINK, TERRAZO MOP

P-528 SINK, COUNTER MOUNT, SINGLE COMPARTMENT,

CORROSION-RESISTANT STEEL

2 2" 1 1/2" 3/8" 3/8" NO NO SINK, COUNTER MOUNT, SINGLE COMPARTMENT, CORROSION-RESISTANT STEEL

P-604 ELECTRIC WATER COOLER 1 1 1/2" 1 1/2" 3/8" - - YES ELECTRIC WATER COOLER

P-708 EMERGENCY EYE AND FACE WASH, WALL MOUNT 1 2" 1 1/2" 3/4" 3/4'' - - EMERGENCY EYE AND FACE WASH, WALL MOUNT

P-812 WATER SUPPLY BOX 2 - - 1/2" - - - WATER SUPPLY BOX

TP-1 TRAP PRIMER 3 - - 1/2" - - - ELECTRONIC TRAP PRIMER.

PLUMBING RECIRCULATION PUMP SCHEDULE

MARK LOCATION SYSTEM TYPE

PERFORMANCE

MIN % EFF R.P.M.

SPEED

CONTROL

ELECTRICAL

REMARKSFLOW HEAD FT TEMPERATURE HP PHASE VOLTAGE

1-CWRP-1 BUILDING 1, CORRIDOR H204 DOMESTIC COLD WATER

RETURN

CARTRIDGE 1 GPM 4.0 50 °F 70 3250 CONSTANT 1/40 1 115 1, 2, 3, 4

REMARKS:

1. INSTALL PER MANUFACTURER'S INSTRUCTIONS.

2. PUMP SHALL HAVE STAINLESS STEEL CASING, UNION CONNECTION AND PANEL MOUNT TAPPINGS.

3. PUMP SHALL HAVE INTEGRAL CHECK VALVE.

4. PUMP SHALL OPERATE CONTINIOUSLY.

DocuSign Envelope ID: 5031BAE7-940A-4160-ADF6-B089AC0BA15C

5/26/2021

HAC

2E01

P

R.3 T.1 T.2 U.1

R T U V

4'' SAN DN

4'' V UP

2'' SAN DN

4'' V

4'' V UP

2'' V UP

2'' SAN DN &

2'' V UP

4'' SAN UP & DN

4'' SAN DN

TO 1ST FLR,

4'' V UP

4'' V UP TO

3RD FLR

2'' V UP

4'' V UP

4'' SAN DN TO BASEMENT

4'' V UP

4'' SAN DN

2'' V UP

2'' V UP

4'' SAN1

4'' SAN DN TO BASEMENT

4" SAN

MATCH LINE MATCH LINE

/2 PD101 /2 PD101

4'' SAN DN TO 1ST FLR

IN 1ST FLR CLG

4'' SAN DN TO BASEMENT

IN 1ST FLR CEILING

EXAM

2E25A

EXAM

2E25

OFFICE

2E23

WAITING

ROOM

2E26

OFFICE

2E27

OFFICE

2E22

TOILET

2E22A

TOILET

2E28

EXAM

2E29

TOILET

2E25B TOILET

2E24

EXAM

2E21

OFFICE

2E20

CHASE

CH-E-1

OFFICE

2CO5

STORAGE

2CO6

ELEVATOR

NO. 2

E2

OFFICE

2CO8

OFFICE

2CO9

CONFERENCE

ROOM

2CO7

OFFICE

2CO3

THERAPY

2CO2

OFFICE

2CO4

CORRIDOR

H210

STAIR

S201

HAC

2E01

WAITING

2C01

RECEPTION

2C01A

EXAM

2C01B

IRM

2C10A

4'-0 1/2"

OIT

2C10

8.1

K M N P Q

R S T U V

2" V

2'' V UP 4'' SAN DN

4'' V UP

4'' SAN DN

4'' SAN DN

2'' V UP

4'' SAN DN

2'' SAN,

1-1/2'' V

2'' V UP

4'' SAN DN, 2'' V UP

2'' SAN DN

2'' V UP

1 1/2" SAN

1 1/2" SAN

3" SAN

1 1/2" SAN

4" SAN

3" SAN

3" SAN

1-1/2'' SAN AND 1-1/2'' V

1-1/2'' SAN DN

AND 1-1/2'' V UP

2" V

4'' SAN

4'' SAN

4'' SAN 4'' SAN

2'' V

4'' SAN UP

EX. 3'' SAN

EX. SAN

MATCH LINE MATCH LINE

/1 PD101/1 PD101

EX.'' SAN

STACK TO

REMAIN

EX. 2'' V IN 1ST FLR CLG

EX. 2'' V DN TO BASEMENT

2'' V FROM 1ST FLR CLG TO 3RD FLR

1 1/2" V

1 1/2" SAN

1 1/2" V

1 1/2" SAN

EX. 4'' V

UP TO

REMAIN

EX. 2'' V TO REMAIN

EX. 4'' V TO REMAIN

EX. 3'' SAN TO REMAIN

3'' SAN DN TO REMAIN

4" SAN 4

S A N

4" SAN

4" SAN

EX. 2"V UP

TO REMAIN

EX. 2"V UP TO

REMAIN

EX. 2'' V UP TO

3RD FLR TO REMAIN

4'' SAN FROM 3RD FLR TO REMAIN

EX. SAN IN 2ND FLR

CLG TO REMAIN

EX. 4'' SAN IN 2ND FLR CLG

TO REMAIN

EX. 3'' SAN IN 2ND FLR

CLG TO REMAIN

4'' SAN IN

2ND FLR CLG

TO REMAIN

EX. 2'' V UP

TO REMAIN

EX. 4'' SAN IN 2ND FLR CLG TO REMAIN

EX. 2'' VENT RISER FROM 1ST FLR

10 13

1. DEMOLITION WORK SHALL BE PERFORMED

SUCH THAT ALL PIPES, HANGERS,

SUPPORTS, AND VALVES IN SCOPE ARE

REMOVED COMPLETELY TO MAINS. REMOVE

ALL ITEMS TO ENSURE NOTHING IS

ABANDONED IN PLACE.

2. COORDINATE DEMOLITION WITH NEW

CONSTRUCTION SUCH THAT SERVICE

OUTSIDE OF AREA OF WORK IS

UNINTERRUPTED.

3. UNLESS OTHERWISE NOTED, SANITARY

PIPING SHOWN IS LOCATED IN FIRST FLOOR

CEILING AND VENT PIPING IS LOCATED IN

SECOND FLOOR CEILING.

4. PROVIDE TEMPORARY SUPPORTS FOR ALL

EXISTING UTILITIES SHOWN TO REMAIN IN

ORDER TO PERFORM THE WORK SHOWN ON

THE ‘HA’ SERIES DRAWINGS. ONCE THE ‘HA’

SERIES WORK IS COMPLETED, REMOVE THE

TEMPORARY SUPPORTS AND SUPPORT THE

UTILITIES IN ACCORDANCE WITH THE

DRAWINGS AND SPECIFICATIONS.

5. FIRESTOP AT NEW AND EXISTING

PENETRATIONS THROUGH FIRE-RATED

WALL, FLOOR AND CEILING ASSEMBLIES.

PROVIDE SMOKE SEALING AT NEW AND

EXISTING PENETRATIONS THROUGH SMOKE-

RATED WALL, FLOOR AND CEILING

ASSEMBLIES. COMPLY WITH DIVISION 07

SPECIFICATIONS. WHERE A PIPE OR OTHER

ELEMENT PENETRATING A FIRE- AND/OR

SMOKE-RATED ASSEMBLY IS DEMOLISHED,

PATCH/REPAIR THE ASSEMBLY TO MATCH

THE FIRE AND/OR SMOKE RATING.

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:0

A

M

PD101

SECOND FLOOR WASTE/VENT

DEMOLITION PLAN

2 8SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

SOUTH WASTE/VENT DEMOLITION PLAN

Scale: 1/8" = 1'-0"

NORTH WASTE/VENT DEMOLITION PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

1 DEMOLISH ABANDONED SANITARY PIPE

COMPLETE.

2 DEMOLISH SINK/LAVATORY AND ASSOCIATED

SANITARY AND VENT PIPING BACK TO MAINS

AND CAP IF MAINS SERVE FIXTURES OUTSIDE

AREA OF WORK.

3 DEMOLISH SINK AND ASSOCIATED SANITARY

PIPING BACK TO MAIN AND CAP. DEMOLISH

VENT PIPING BACK TO STACK AND PREPARE

FOR NEW CONNECTION IN SECOND FLOOR

CEILING.

4 DEMOLISH VENT/SANITARY PIPING BACK TO

HEADER/STACK AFTER VERIFYING

VENT/SANITARY PIPE DOES NOT SERVE ANY

FIXTURES OUTSIDE AREA OF WORK.

5 SANITARY VENT UP/DOWN TO REMAIN.

6 DEMOLISH 2'' VENT UP AND 2'' SANITARY

DOWN THE CHASE. PREPARE FOR NEW VENT

CONNECTION.

7 DEMOLISH SANITARY BACK TO FIRST FLOOR

CEILING. PREPARE FOR NEW CONNECTION.

8 DEMOLISH SHOWER DRAIN AND ASSOCIATED

WASTE AND VENT PIPING BACK TO THE

MAINS AND CAP IF MAINS SERVE FIXTURES

OUTSIDE AREA OF WORK.

9 DEMOLISH WATER CLOSET AND ASSOCIATED

WASTE AND VENT PIPING BACK TO MAINS

AND CAP IF MAINS SERVE FIXTURES OUTSIDE

AREA OF WORK.

10 DEMOLISH FLOOR DRAIN AND ASSOCIATED

WASTE PIPING BACK TO MAIN AND CAP.

11 DEMOLISH 2'' VENT IN FIRST FLOOR CEILING

TO POINT INDICATED. PREPARE TO

REROUTE.

12 DEMOLISH 2'' VENT IN CHASE FROM FIRST

FLOOR CEILING TO SECOND FLOOR CEILING.

PREPARE FOR NEW CONNECTION IN SECOND

FLOOR CEILING.

13 VERIFY LOCATION OF EXISTING SANITARY

AND VENT.

14 DEMOLISH SANITARY PIPING TO POINT

INDICATED AND PREPARE FOR NEW

CONNECTION. DEMOLISH VENT PIPING IN

WALL AND CAP IN SECOND FLOOR CEILING.

15 DEMOLISH SANITARY TEE. PREPARE FOR

NEW CONNECTION.

16 DEMOLISH 3'' ACID WASTE RISER FROM FIRST

FLOOR CEILING TO SECOND FLOOR CEILING

AFTER NEW OFFSET PIPING IS INSTALLED.

17 DEMOLISH 2'' VENT RISER FROM FIRST

FLOOR CEILING TO SECOND FLOOR CEILING.

PREPARE TO REROUTE.

18 EXISTING TO REMAIN.

EXAM

2E25A

EXAM

2E25

OFFICE

2E23

WAITING

ROOM

2E26

OFFICE

2E27

OFFICE

2E22

TOILET

2E22A

TOILET

2E28

EXAM

2E29

TOILET

2E25B TOILET

2E24

EXAM

2E21

OFFICE

2E20

CHASE

CH-E-1

OFFICE

2CO5

STORAGE

2CO6

ELEVATOR

NO. 2

E2

OFFICE

2CO8

OFFICE

2CO9

CONFERENCE

ROOM

2CO7

OFFICE

2CO3

THERAPY

2CO2

OFFICE

2CO4

CORRIDOR

H210

STAIR

S201

HAC

2E01

WAITING

2C01

RECEPTION

2C01A

EXAM

2C01B

IRM

2C10A

OIT

2C10

3" DCW

1" DHWR

2" DHW

1/2" DCW

1/2" DHW

2" DHW

1" DHWR

3" DCW

3" DCW

1" DHWR

2" DHW

8.1

K M N P Q

R S T U V

3/4'' DCW TO LAV ON THIRD FLR

3/4'' DHWR UP AND DN TO REMAIN

1'' DHW UP AND DN TO REMAIN

1 1/4'' DCW UP AND DN TO REMAIN

1" O

3/4" O

1" O

1/2" DHW

1/2" DCW

1/2" DCW

1/2" DHW

1 1/4" DCW

1 1/4" DHW

3/4" DCW

3/4" DHW

1 1/2" DCW

3/4" DHW

3/4" DHWR

3/4" LA

1" O

1/2" N

1" O

2'' DCW UP & DN

1 1/4'' DHW UP & DN

1 1/4'' DHW UP & DN

3/4" DHWR

3/4" DHW

3/4" DCW

3/4" DCW

1/2" DHW

/1 PD102/1 PD102

MATCH LINEMATCH LINE

EXISTING TO REMAIN

EXISTING TO REMAIN

EXISTING TO REMAIN

IN 1ST FLR CEILING

FROM BASEMENT

UP FROM 1ST FLR CEILING

TO 2ND FLR CEILING

UP TO 3RD FLR

UP TO 3RD FLR

EXISTING TO REMAIN

EXISTING TO REMAIN

HAC

2E01

P

R.3 T.1 T.2 U.1

R T U V

1/2" DHWR

1/2" DHW

3/4" DCW

1/2" DHWR

1/2" DHW

3/4" DCW

3/4'' DHWR UP

1 1/4'' DHW UP

2'' DCW UP

1/2'' DHW UP

3/4'' DCW UP

1 1/2'' DCW UP

3/4'' DCW UP

1/2'' DHW UP

1'' MV UP

1'' MV UP

1'' MV UP

3/4'' G UP

1'' LA UP

3/4" DHWR

1 1/4" DHW

2" DCW

MATCH LINE MATCH LINE

/2 PD102 /2 PD102

1. DEMOLITION WORK SHALL BE PERFORMED

SUCH THAT ALL PIPES, HANGERS,

SUPPORTS, AND VALVES IN SCOPE ARE

REMOVED COMPLETELY TO MAINS. REMOVE

ALL ITEMS TO ENSURE NOTHING IS

ABANDONED IN PLACE.

2. NO DEAD ENDS SHALL REMAIN. DEMOLISH

PIPING TO WITHIN TWO PIPE DIAMETERS OF

THE BRANCH, RISER, OR MAIN AND CAP.

FIELD VERIFY THE LOCATIONS OF THE

MAINS, BRANCHES, OR RISERS SERVING

THE AREA. WORK ON FLOORS BELOW WILL

BE REQUIRED.

3. COORDINATE DEMOLITION WITH NEW

CONSTRUCTION SUCH THAT SERVICE

OUTSIDE OF AREA OF WORK IS

UNINTERRUPTED.

4. UNLESS OTHERWISE NOTED, DOMESTIC

WATER PIPING SHOWN IS LOCATED IN

SECOND FLOOR CEILING.

5. PROVIDE TEMPORARY SUPPORTS FOR ALL

EXISTING UTILITIES SHOWN TO REMAIN IN

ORDER TO PERFORM THE WORK SHOWN ON

THE ‘HA’ SERIES DRAWINGS. ONCE THE ‘HA’

SERIES WORK IS COMPLETED, REMOVE THE

TEMPORARY SUPPORTS AND SUPPORT THE

UTILITIES IN ACCORDANCE WITH THE

DRAWINGS AND SPECIFICATIONS.

6. FIRESTOP AT NEW AND EXISTING

PENETRATIONS THROUGH FIRE-RATED

WALL, FLOOR AND CEILING ASSEMBLIES.

PROVIDE SMOKE SEALING AT NEW AND

EXISTING PENETRATIONS THROUGH SMOKE-

RATED WALL, FLOOR AND CEILING

ASSEMBLIES. COMPLY WITH DIVISION 07

SPECIFICATIONS. WHERE A PIPE OR OTHER

ELEMENT PENETRATING A FIRE- AND/OR

SMOKE-RATED ASSEMBLY IS DEMOLISHED,

PATCH/REPAIR THE ASSEMBLY TO MATCH

THE FIRE AND/OR SMOKE RATING.

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:2

A

M

PD102

SECOND FLOOR DOMESTIC

WATER/MEDICAL GAS DEMOLITION

PLAN

3 8JT/SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

Scale: 1/8" = 1'-0"

NORTH DOMESTIC WATER/MEDICAL GAS DEMOLITION PLAN

NORTH

0 4 8 16

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

1 DEMOLISH SINK/LAVATORY AND

ASSOCIATED DOMESTIC HOT AND COLD

WATER BACK TO MAINS AND CAP.

2 DEMOLISH WATER CLOSET AND

ASSOCIATED DOMESTIC COLD WATER BACK

TO MAINS AND CAP.

3 REMOVE DCW, DHW, AND DHWR INCLUDING

FITTINGS, INSULATION, AND HANGERS BACK

TO FLOOR RISER AND CAP.

4 DEMOLISH DOMESTIC COLD AND HOT

WATER SUPPLY AND HOT WATER RETURN

PIPING IN CHASE AND IN FIRST FLOOR

CEILING. PREPARE TO REROUTE PIPING IN

THE FIRST FLOOR CEILING. PIPING FROM

BASEMENT TO REMAIN.

5 DEMOLISH MEDICAL OXYGEN PIPE AND

ASSOCIATED VALVE BOX BACK TO MAIN AND

CAP.

6 DEMOLISH SHOWER VALVE AND

ASSOCIATED DOMESTIC COLD AND HOT

WATER BACK TO MAINS AND CAP.

7 DEMOLISH SINK/LAVATORY AND

ASSOCIATED DOMESTIC HOT AND COLD

WATER COMPLETE.

8 DEMOLISH WATER CLOSET AND

ASSOCIATED DOMESTIC COLD WATER

COMPLETE.

9 DEMOLISH SHOWER AND ASSOCIATED

DOMESTIC COLD AND HOT WATER

COMPLETE.

10 VERIFY LOCATION OF EXISTING DOMESTIC

WATER PIPING.

11 EXISTING TO REMAIN.

Scale: 1/8" = 1'-0"

SOUTH DOMESTIC WATER/MEDICAL GAS DEMOLITION PLAN

NORTH

0 4 8 16

8.1

M N P Q

R S T U V

EXAM

2C01B

OFFICE

2C02A

OFFICE

2C02B

OFFICE

2C03

OFFICE

2C04A

OFFICE

2C04B

MEN'S RESTROOM

2C07A

WOMEN'S RESTROOM

2C07B

CORRIDOR

H207

OPEN OFFICE

2C08

OPEN OFFICE

2C09

OIT

2C10

OFFICE

2C06

PROVIDER OFFICE

2C05

ELEV_

H209

ELEV LOBBY

H206

STAIR S201

H208

HAC

2E01

CONSULT

2E20

WAITING

2E21

CORRIDOR

H202

CORRIDOR

H203

RECEPTION

2E22

CORRIDOR

H203

COPY AREA

2E23

OFFICE

2E24

GROUP ROOM 2B

2E25BCORRIDOR

H204

CORRIDOR

H205

STORAGE

2E26C

STORAGE

2E25C

CLASSROOM

2E28

CLASSROOM

2E27

GROUP ROOM 1B

2E26B

P-528

P-420

P-420

P-204

P-103

P-103 P-420

P-420

P-408

P-408

P-502

3/4'' DHWR UP AND DN

1'' DHW UP AND DN

1 1/4'' DCW UP AND DN

3/4" DCWR

3/4" DHWR

3/4" DHW

3/4" DCW

2" DCW

3/4" DHW

3/4" DHWR

1 1/2" DCW 1 1/2" DCW

2" DCW

1" DHW

3/4" DHW

3/4" DHWR

1-CWRP-1

EX. 1-1/4'' DHW,

1-1/4'' DCW,

DHWR

EX. 2'' DCW,

1'' DHW,

DHWR

EX. 1-1/2'' DCW,

1-1/4'' DHW,

3/4'' DHWR

2'' DCW UP & DN

1 1/4'' DHW UP & DN

1 1/4'' DHW UP & DN

1'' DHW

3/4'' DHWR

1-1/2'' DCW

3/4" DCW

3/4" DHW

3/4" DHWR

GROUP ROOM 1A

2E26A

GROUP ROOM 2A

2E25A

MATCH LINE MATCH LINE

/1 PP101 /1 PP101

IN 1ST FLR CEILING

IN 2ND FLR CEILING

UP IN WALL

WHA-B

P-103

1 1/2" DCW

WHA-B

0.2 GPM

0.2 GPM

0.4 GPM

0.4 GPM

3/4" 2" 1 1/2"

P-812

P-812

1/2"

1/2'' DCW DN TO

WATER BOX

AND SINK

1/2"

3/4" DCW

3/4" DHW

TP-1

P-604

3/8" DCW

1/2'' DCW IN

1ST FLR CLG

R.3 T.1 T.2 U.1

R T U V

CONSULT

2E20STAIR S201

H208

HAC

2E01

PAT TLT

2E02

PAT TLT

2E03

CONSULT

2E19

CONSULT

2E18

CONSULT

2E04

CONSULT

2E17

CHIRO EXAM

2E05

CHIRO EXAM

2E16

CHIRO EXAM

2E06

CHIRO EXAM

2E15

SOILED

2E07

MEDS

2E14

CLEAN UTILITY

2E08

EXAM

2E13

ACUPUNCTURE

2E09

MASSAGE

2E12

ACUPUNCTURE

2E10

MEDITATION

2E11

CORRIDOR

H201

CORRIDOR

H202

P-502

P-418

P-418

P-103

P-103

P-408

P-408

P-528

P-408

P-408

P-408

P-408

P-418

P-408

P-408

P-708

3/4" DHWR

1" DCW1" DHW

3/4" DHW

3/4" DCW

3/4" DHWR

3/4" DHW

3/4" DCW

3/4'' DCW UP

1/2'' DHW UP

1 1/2" DCW

1 1/4" DHW

3/4" DHWR

3/4" DHWR

3/4" DHWR

3/4" DHWR

1/2" DHWR

1/2" DHW

3/4" DCW

3/4" DHWR

1 1/4" DHW

2" DCW

3/4" DCW

3/4" DHW

1 1/4" DHW

1 1/2" DCW

/2 PP101 /2 PP101

MATCH LINEMATCH LINE

WHA-B

0.2 GPM

0.5 GPM

0.2 GPM

0.2 GPM

0.3 GPM

/4

1"

3/4"

1 1/2"

/4

3/4"

P-408

3/4" DHW

1/2" DCW

P-408

1 1/2" DCW

1" DHW

1/2" DCW

TP-1

TP-1

1/2'' DCW IN 1ST FLR CLG

1/2'' DCW IN 1ST FLR CLG

1/2'' DCW IN 1ST FLR CLG

3/4" 1/2" 3/4"

1. UNLESS OTHERWISE NOTED, DOMESTIC

PIPING SHOWN IS LOCATED IN SECOND

FLOOR CEILING.

2. FIRESTOP AT NEW AND EXISTING

PENETRATIONS THROUGH FIRE-RATED

WALL, FLOOR AND CEILING ASSEMBLIES.

PROVIDE SMOKE SEALING AT NEW AND

EXISTING PENETRATIONS THROUGH SMOKE-

RATED WALL, FLOOR AND CEILING

ASSEMBLIES. COMPLY WITH DIVISION 07

SPECIFICATIONS. WHERE A PIPE OR OTHER

ELEMENT PENETRATING A FIRE- AND/OR

SMOKE-RATED ASSEMBLY IS DEMOLISHED,

PATCH/REPAIR THE ASSEMBLY TO MATCH

THE FIRE AND/OR SMOKE RATING.

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:3

A

M

PP101

SECOND FLOOR DOMESTIC WATER

PLAN

4 8JT/SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

Scale: 1/8" = 1'-0"

SECOND FLOOR DOMESTIC WATER PLAN

NORTH

0 4 8 16

1 1/2'' DCW/DHW DOWN IN WALL TO

BACK-TO-BACK LAVATORIES.

2 3/4'' DCW/DHW TO EMERGENCY FIXTURE

MIXING VALVE.

3 INSTALL BALANCING VALVE ASSEMBLY PER

DETAIL ON SHEET P-501. BALANCE FLOW

RATE AS INDICATED ON PLAN.

4 WATER BOX OUTLET FOR ICE MAKER.

BOTTOM OF BOX SHALL BE INSTALLED 18''

ABOVE FINISHED FLOOR.

5 WATER BOX OUTLET FOR COFFEE MAKER.

BOTTOM OF BOX SHALL BE INSTALLED 3'-4''

ABOVE FINISHED FLOOR.

6 1/2" DCW DOWN TO TRAP PRIMER TP-1

CONNECTION. EXTEND 1/2" DCW IN FIRST

FLOOR CEILING FROM TRAP PRIMER TO

FLOOR DRAIN FD-D.

7 OFFSET 2" DHW, 1 1/2 " DCW, AND 3/4" DWHR

FROM FIRST FLOOR CEILING UP IN WALL AND

RECONNECT TO RISERS UP TO THIRD

FLOOR.

8 1/2'' DCW IN 1ST FLOOR CEILING FROM TP-1

TO FLOOR SINK DRAIN.

9 EXISTING TO REMAIN.

10 EXTEND 1/2" DCW TO HUMIDIFIER AND

TRANSITION TO HUMIDIFIER INLET

CONNECTION.

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

SECOND FLOOR DOMESTIC WATER PLAN

NORTH

0 4 8 16

8.1

K M N P Q

R S T U V

OPEN OFFICE

2C09

OPEN OFFICE

2C08

MEN'S RESTROOM

2C07A

WOMEN'S RESTROOM

2C07B

CORRIDOR

H207

OFFICE

2C04A

OFFICE

2C04B

OFFICE

2C03

OFFICE

2C02A

OFFICE

2C02B

WAITING

2C01

RECEPTION

2C01A

EXAM

2C01B

OIT

2C10

CLASSROOM

2E28

CLASSROOM

2E27

CORRIDOR

H205

GROUP ROOM 1A

2E26A

GROUP ROOM 2A

2E25A

CORRIDOR

H203

COPY AREA

2E23

OFFICE

2E24

WAITING

2E21

WAITING

2E21

CONSULT

2E20STAIR S201

H208

CORRIDOR

H202

OFFICE

2C06

PROVIDER OFFICE

2C05

ELEV_

H209

EX. 4" WASTE

STACK

EX. 2"V UP

EX. 4" WASTE

STACK

EX. 2"V UP

4'' WCO

4'' WCO

4" SAN

FD-D

FD-D

2" SAN

1 1/2" V

EX. 3'' VENT RISER

EX. 2'' FROM 1ST FLR

2" SAN

3'' SAN DN TO

BASEMENT 1 1/2" V

4" SAN

1 1/2" V

EX. 4'' V UP

EX. 2'' V UP

EX. 4'' SAN DN

EX. 4'' SAN DN

EX. 4'' SAN DN TO BASEMENT

EX. 3'' SAN

EX. SAN

2" SAN

2" SAN

P-408

P-408

P-502

P-103

P-420

P-420

P-103

P-204

P-420

P-420

P-528

GROUP ROOM 1B

2E26B

GROUP ROOM 2B

2E25B

RECEPTION

2E22

2" V

4'' SAN

EX.'' SAN

STACK

EX. 2'' V IN 1ST FLR CLG

EX. 2'' V DN TO BASEMENT

2'' V IN 2ND FLR CEILING

2" V

IN 2ND FLR CHASE

4" SAN

IN 1ST FLR CLG

IN 1ST FLR CLG

IN 2ND FLR CHASE

2" V

2" V

2" V

4" SAN

3" SAN

EX. 2''V UP

EX. 2'' V

P-103

IN 1ST FLR CLG

IN 2ND FLR CLG

UP TO 2ND FLR CLG

4" SAN

EX. 2'' V

UP TO 3RD

FLR

4'' SAN FROM 3RD FLR

IN 2ND FLR CLG

4" SAN

EX. 4'' SAN IN 2ND FLR CLG

EX. 4'' SAN IN 2ND FLR CLG

EX. 3'' SAN IN 2ND FLR CLG

EX. 4'' SAN IN 2ND FLR CLG

IN 1ST FLR CLG

4'' SAN IN

2ND FLR CLG

EX. 2''

V UP

EX. 4'' SAN IN 2ND FLR CLG

EX. SAN IN 1ST FLR CLG

IN 1ST FLR CLG

IN 1ST FLR CLG

/1 PW101/1 PW101

MATCH LINE MATCH LINE

IN 1ST FLR CLG

IN 2ND FLR CEILING

2" V

3"

1 1/2" V

P-604

2" SAN

R.3 T.1 T.2 U.1

R T U V

HAC

2E01

PAT TLT

2E02 CONSULT

2E19

PAT TLT

2E03

CONSULT

2E04

CONSULT

2E18

CONSULT

2E17

CHIRO EXAM

2E16

CHIRO EXAM

2E05

CHIRO EXAM

2E06

CHIRO EXAM

2E15

SOILED

2E07

MEDS

2E14

CLEAN UTILITY

2E08

EXAM

2E13

ACUPUNCTURE

2E09

MASSAGE

2E12

MEDITATION

2E11

ACUPUNCTURE

2E10

4" V

1 1/2" V

2" SAN

2" SAN

1 1/2"

V

1 1/2" V

2" SAN2" SAN

2" V

4" V

4" V

4" SAN

2" V

3" SAN

1 1/2" V

2" SAN

FCO

2" V

2" SAN

4'' V UP

2'' SAN DN

4'' V

4'' V UP

EX. 4'' SAN DN

4'' SAN DN, 4'' V UP

4'' V UP

2'' V UP

4'' V UP

4'' SAN DN

4'' V UP

2'' V UP

2'' V UP

3" SAN

2" SAN

2" SAN

FD-D

1 1/2" V

1 1/2" V

FCO

2" V

2" SAN

2" SAN

1 1/2" V

P-103

P-103

P-502

P-418

P-418

P-408

P-408

P-528

P-408

P-408

P-408

P-408

P-708

P-418

P-408

P-408

2" SAN

2" SAN

4" SAN

EX. 4'' SAN DN TO BASEMENT

4" SAN

MATCH LINE MATCH LINE

/2 PW101 /2 PW101

4" SAN

1 1/2" V

IN 1ST FLR CLG

IN 1ST FLR CLG

IN 1ST FLR CLG

IN 1ST FLR CLG

IN 1ST FLR CLG

IN 1ST FLR CLG

2" SAN

1 1/2" V

IN 1ST FLR CLG

4'' SAN DN TO BASEMENT

P-408

P-408

2"

13 3"

4"FD-D

FD-D

3"

3"

1. UNLESS OTHERWISE NOTED, SANITARY

PIPING SHOWN IS LOCATED IN FIRST FLOOR

CEILING AND VENT PIPING IS LOCATED IN

SECOND FLOOR CEILING.

2. FIRESTOP AT NEW AND EXISTING

PENETRATIONS THROUGH FIRE-RATED

WALL, FLOOR AND CEILING ASSEMBLIES.

PROVIDE SMOKE SEALING AT NEW AND

EXISTING PENETRATIONS THROUGH SMOKE-

RATED WALL, FLOOR AND CEILING

ASSEMBLIES. COMPLY WITH DIVISION 07

SPECIFICATIONS. WHERE A PIPE OR OTHER

ELEMENT PENETRATING A FIRE- AND/OR

SMOKE-RATED ASSEMBLY IS DEMOLISHED,

PATCH/REPAIR THE ASSEMBLY TO MATCH

THE FIRE AND/OR SMOKE RATING.

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

# KEY NOTES:

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RATED

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs#

S S S S

© COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:4

A

M

PW101

SECOND FLOOR DRAIN, WASTE, AND

VENT PLAN

5 8JT/SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

Scale: 1/8" = 1'-0"

NORTH DRAIN, WASTE, AND VENT PLAN

NORTH

0 4 8 16

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

1 CONNECT NEW 2" SANITARY TO EXISTING 4"

SANITARY STACK.

2 CONNECT 4'' SANITARY TO EXISTING 4''

SANITARY STACK IN FIRST FLOOR CEILING.

3 CONNECT 2 1/2'' VENT TO EXISTING 4'' VENT

ABOVE CEILING.

4 CONNECT NEW 2'' VENT TO EXISTING 2'' VENT

ABOVE CEILING.

5 CONNECT NEW 1 1/2'' VENT AND 2'' VENT TO

EXISTING 4'' VENT ABOVE CEILING.

6 REROUTE 3" ACID WASTE STACK LATERALLY

ABOVE FIRST FLOOR CEILING, TURN UP INTO

NEW CHASE.

7 NEW 3" ACID WASTE LINE ABOVE SECOND

FLOOR CEILING, RECONNECT TO EXISTING

STACK.

8 INSTALL NEW OFFSET 3" ACID WASTE PIPING

PRIOR TO DEMOLISHING EXISTING.

9 CONNECT NEW 2'' SANITARY FROM

LAVATORIES TO EXISTING 4'' SANITARY IN

FIRST FLOOR CEILING.

10 2'' SANITARY FROM LAVATORY/SINK DOWN TO

FLOOR BELOW. 1 1/2'' VENT UP TO ABOVE

CEILING. PROVIDE ONE WALL CLEANOUT

ABOVE LAVATORY RIM AS SHOWN ON P-501,

DETAIL 3 AND 10.

11 3'' SANITARY FROM SINK DOWN TO FLOOR

BELOW. 1 1/2'' VENT UP TO ABOVE CEILING.

12 4'' SANITARY FROM WATER CLOSET(S) DOWN

TO FLOOR BELOW. 2'' VENT UP TO ABOVE

CEILING.

13 2'' SANITARY FROM LAVATORIES DOWN TO

FLOOR BELOW. 1 1/2'' VENT UP TO ABOVE

CEILING. PROVIDE ONE WALL CLEANOUT

ABOVE LAVATORY RIM AS SHOWN ON P-501,

DETAIL 3 AND 10.

14 4'' SANITARY FROM A GROUP OF FIXTURES

DOWN TO FLOOR BELOW. 2'' VENT UP TO

ABOVE CEILING.

15 2'' SANITARY FROM EMERGENCY EYE/FACE

WASH DOWN TO FLOOR BELOW. 1 1/2'' VENT

UP TO ABOVE CEILING.

16 INSTALL NEW OFFSET 2" VENT PIPING.

17 2'' SANITARY UP TO FLOOR CLEANOUT.

18 2" SAN FROM WATER COOLER P-204 DOWN

TO FIRST FLOOR CEILING. 1 1/2" VENT UP AND

CONNECT IN SECOND FLOOR CEILING.

19 EXISTING TO REMAIN.

Scale: 1/8" = 1'-0"

SOUTH DRAIN, WASTE, AND VENT PLAN

NORTH

0 4 8 16

MINIMUM 16 GAGE GALVANIZED

STEEL PLATE 12"x48" [300x1200mm] MIN. SECURED TO

A MIN. 4 STUDS PER LAVATORY

TYP. 1/8" 1/4"

TYP. [3mm] [6mm]

1/4" [6mm] MOLLY BOLT HOLLOW WALL

ANCHOR (1 EA. SIDE OF LAV)

PLAN

STEEL WALL PLATE

WALL ANCHOR

STUDS

STEEL HANGER BY LAV MFGR

AA

FOR FIXTURE

HEIGHT SEE

ARCHITECTURAL

DRAWINGS

MIN. 5 1/4"

[131mm] GALV/

MACHINE BOLTS

WELDED TO PLATE

MIN. (3) 1/4"

[6mm] MACHINE

BOLTS W/ DOUBLE

LOCK NUTS ON

BACK SIDE

SECTION A

[9 m m

T O

F L O

O R

V A

R

IE

S

1" STOP

FINISHED

FLOOR

FINISHED

WALL

SENSOR

MANUAL

OVER-RIDE

BUTTON

REFER TO

ARCHITECTURAL

PLANS FOR

FIXTURE HEIGHT

/2

/2

2 3/4" 4 3/4"

2 1/4"

C/L OF

FIXTURE

/2

NOTE:

PROVIDE 24 VOLT

TRANSFORMER

FAUCET

LAMINAR FLOW

CONTROL DEVICE

FINISHED

FLOOR

ESCUTCHEON

LOOSE

KEY STOP

F O

R F

IX

T

U R

E H

E

IG

H T

S S

E

A

R C

H

IT

E C

T U

R A

L D

R A

W

IN

G S 1

/4

TRAP PARALLEL

TO WALL

WALL MOUNTED

THERMOSTATIC

MIXING VALVE

3/8" FLEX TO HW

ON FAUCET

OFFSET WASTE

8"

1 1/2'' VENT. SEE PLANS FOR

CONTINUATION.

2'' WALL CLEANOUT

WITH CHROME

PLATED COVER

2'' SANITARY. SEE

PLANS FOR

CONTINUATION.

2'' SANITARY

QUICK CLOSING

VALVE

WATER HAMMER ARRESTOR

ISOLATION VALVE

OUTLET

PROVIDE ACCESS

DOOR TO ALLOW FOR

ACCESS TO WATER

HAMMER ARRESTOR

HOT OR COLD WATER

RETURN PIPING

SWING TYPE

CHECK VALVE

BALANCING

VALVE

RETURN PIPING

HOT OR COLD WATER

BALL VALVE (TYP OF TWO)

FINISHED

FLOOR

REFER TO

ARCHITECTURAL

PLANS FOR

FIXTURE HEIGHT

FINISHED

WALL

CARRIER

1" STOP

/2

4 3/4"

C/L OF

FIXTURE

SENSOR

MANUAL

OVER-RIDE

BUTTON

2 3/4"

INSTALL PER PDI STANDARDS AND

MANUFACTURER'S INSTRUCTIONS.

PROVIDE WHA AT ALL QUICK

CLOSING VALVES.

IF BRANCH IS GREATER THAN

20' LONG, PROVIDE ANOTHER

WHA IN MIDDLE, EACH SIZED

FOR HALF THE FIXTURE UNITS

IF HORIZONTAL BRANCH IS LESS

THAN 20' LONG, PROVIDE ONE

WHA AT END OF LINE

HOT OR COLD WATER SUPPLY

WATER HAMMER

ARRESTER (TYP)

WHA-A

WHA-B

WHA-C

WHA-D

WHA-E

WHA-F

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

1-11

12-32

33-60

61-113

114-154

154-330 FIXTURE WITH QUICK

CLOSING VALVE (TYP)

PDI

SIZE

PIPE

SIZE

FIXTURE

UNIT LOAD

ACCESSIBLE

MAINTENANCE

SHUTOFF (TYP)

NOM. SIZE (IN.)

PIPE (FT.)

TUBING (FT.)

5 FT

THRU 3/4

1 1 1/4

1 1/2

HANGER ROD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR

LOW TEMPERATURE

PIPE)

PROVIDE HIGH

COMPRESSIVE

STRENGTH

INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION SHIELD AT

HANGER

WELD

SADDLE

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE

SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE

SPECIFICATIONS

1/2" DIA. HANGER RODS WITH 36"

MAX. SPACING ON EACH CHANNEL

BAND

1-5/8" 12 GAUGE CHANNEL

OR 2" x 2" x 1/4" ANGLE

NOTES:

SEE SPECIFICATIONS FOR

DETAILED HANGER

REQUIREMENTS. SIDE VIEW TRAPEZE HANGER

FOR UP TO 1000 LB. UNIFORM

LOAD

1" MAX.

PROVIDE INSULATION SHIELD &

INSERT FOR ALL PIPING (8" MIN.)

2 2 1/2 3 4 5 6 8 10 12

11 12 14 16 17 19 22 23

9 10 12 13 14 16 - -

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE

MAXIMUM PIPE/TUBING SUPPORT SPACING

FAUCET SEE

SPECIFICATIONS

LAMINAR FLOW

CONTROL DEVICE

TRAP PARALLEL TO WALL

FINISHED

FLOOR

ESCUTCHEON

LOOSE

KEY STOP

F O

R F

IX

T

U R

E H

E

IG

H T

S S

A

R C

H

IT

E C

T U

R A

L D

R A

W

IN

G S 1

/4

8"

WALL MOUNTED

THERMOSTATIC

MIXING VALVE

3/8" FLEX TO FAUCET

OFFSET WASTE

J-BOX WITH TRANSFORMER OR PLUG-IN ON

DUPLEX RECEPTACLE. SHOWN FOR

REFERENCE ONLY. COORDINATE WITH

ELECTRICAL CONTRACTOR.

1 1/2'' VENT. SEE PLANS FOR

CONTINUATION.

2'' WALL CLEANOUT

WITH CHROME

PLATED COVER

2'' SANITARY

2'' SANITARY. SEE

PLANS FOR

CONTINUATION.

1-1/2" P-TRAP

WITH CLEANOUT

SOLID SURFACE

INTEGRAL

LAVATORY

FINISHED FLOOR

THERMOSTATIC MIXING

VALVE

HOT & COLD WATER

CONNECTIONS

HOT & COLD WATER

CONNECTIONS TO FAUCET

SEE ARCHITECTURAL

PLANS AND PLUMBING

SPECIFICATIONS FOR

DIMENSIONS

SENSOR

OPERATED

FAUCET SEE

SPECIFICATIONS

NOTE: COUNTER IS SHOWN FOR

REFERENCE ONLY.

COORDINATE INSTALLATION

WITH THE COUNTER PROVIDED.

1-1/2" P-TRAP

WITH CLEANOUT

WRIST OPERATED

DECK MOUNT

GOOSENECK FAUCET

COUNTER

MOUNT SINK

FINISHED FLOOR

THERMOSTATIC MIXING

VALVE

HOT & COLD WATER

CONNECTIONS

HOT & COLD WATER

CONNECTIONS TO FAUCET

SEE ARCHITECTURAL

PLANS AND PLUMBING

SPECIFICATIONS FOR

DIMENSIONS

NOTE: COUNTER IS SHOWN FOR

REFERENCE ONLY.

COORDINATE INSTALLATION OF

SINK WITH THE COUNTER

PROVIDED.

TYP. PIPE SUPPORTS

(SEE SPECIFICATIONS)

TYPICAL PRESSURE GAUGE

AND GAUGE COCK

COLD WATER CIRCULATION PUMP.

SEE EQUIPMENT SCHEDULE

(PUMP MOTORS SHALL BE INSTALLED

SO THAT MOTOR IS IN A HORIZONTAL

POSITION)

1/2" FLEXIBLE ELECTRICAL CONDUIT

FROM AQUASTAT TO PUMP BY

ELECTRICAL CONTRACTOR

THERMOMETER

TO POWER SOURCE. SEE

'E' SERIES DRAWINGS.

TYPICAL SHUT-OFF VALVE

CHECK VALVE

TYPICAL DIELECTRIC UNION COLD WATER CIRCULATION LINE

FROM BUILDING SYSTEM

DRAIN IN BOTTOM

OF BASIN

MOP BASIN ON FLOOR

WALL

FAUCET LOCATED BETWEEN

36" AND 42" ABOVE FLOOR

1/2'' DCW TO TRAP PRIMER

ASSEMBLY

FROM COLD

WATER MAIN

TRAP PRIMER

VALVE LOCATED

INSIDE WALL CAVITY

PROVIDE LOCKABLE

ACCES DOOR

DISTRIBUTION UNIT FOR

MULITPLE INSTALLATIONS

WALL

VENT PIPING

LOCATED IN WALL

FINISHED FLOOR

COPPER PIPING PASSING THRU

CONCRETE SLAB SHALL BE PROTECTED

BY A PROTECTIVE SHEATING OR

WRAPPING TO PERVENT CORROSION

TO THE COPPER

PROVIDE TRAP PRIMER

CONNECTION ADAPTER SO

THAT TRAP PRIMER LINES

CAN BE ROUTED BELOW

SLAB OR IN FLOOR BELOW

CEILING SPACE FROM

VALVE TO DRAIN

FLOOR DRAIN OR FLOOR SINK

SEE FLOOR PLANS FOR

DRAIN LOCATIONS

WASTE PIPE

TO MAIN

JUCTION-BOX FOR TRANSFORMER

CODE ALLOWED DISTANCE

NO MORE THAN

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:4

A

M

P-501

PLUMBING DETAILS

6 8JT/SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

Scale: No Scale

LAVATORY MOUNTING DETAIL

Scale: No Scale

WATER CLOSET WALL HUNG DETAIL-SENSOR OPERATED

Scale: No Scale

TYPICAL WHEELCHAIR LAVATORY DETAIL

Scale: No Scale

WATER HAMMER ARRESTOR DETAIL

Scale: No Scale

HOT/COLD WATER BALANCING VALVE STATION DETAIL

Scale: No Scale

URINAL MOUNTING DETAIL - SENSOR OPERATED

Scale: No Scale

WATER HAMMER ARRESTOR SCHEDULE AND INSTALLATION

Scale: No Scale

PIPE HANGER

Scale: No Scale

LAVATORY WITH MIXING VALVE -SENSOR OPERATED DETAIL

Scale: No Scale

SENSOR OPERATED SOLID SURFACE INTEGRAL LAVATORY

Scale: No Scale

COUNTER MOUNTED SINK

Scale: No Scale

COLD WATER RECIRCULATION PUMP DETAIL

Scale: No Scale

MOP BASIN

Scale: No Scale

FLOOR DRAIN & TRAP PRIMER DETAIL

3" AW

2" SAN

2"

2" 2"

2"

1 1/2" 1 1/2"

1 1/2" 1 1/2"

1 1/2"

3" 2"

1 1/2"

1 1/2"

2"

/2

/2

2"

/2

/2

2"

4"

3"

1 1/2"

2"

1 1/2"

2"

1 1/2"

2"

P-408

P-408

P-408

P-408

P-528

P-708

P-408

P-418 P-408

P-408

P-408

P-418

P-418

P-103

P-103

P-502

P-528

P-420 P-420

P-204

P-103

P-420

P-420 P-103

P-408

P-408

FD-D FD-D

FD-D

4" SAN

S A N

S A N

S A N

V

S A N

V

S A N

V

V

S A N

S A N

S A N

V

V 3 S A N

AW

V

S A N

S A N

S A N

V

S A N

VS

A N 4"

S A N

S A N

S A N

S A N

2"

2"

2"

4"

2"

2"

2"

CO

S A N

S A N

S A N

4" V

S A N

4" V

4" V

4"

4"

4"

2"

3"

P-812

P-812

P-103

P-408

P-408

2"

FD-D

FD-D

FCO

P-604

2"

1 1/2"

TP-1

TP-1

TP-1

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:5

A

M

P-901

SANITARY AND VENT PIPE RISERS

7 8SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

Scale: No Scale

SANITARY AND VENT PIPE RISERS

FCO

4'' WCO

4'' WCO

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

2" 3/4"

3/4"

2"

1 1/2"

1 1/2"

1"

3/4"

3/4"

3/4" 3/4" 3/4"

3/4"

1" 1"

1 1/2" 1 1/4"

3/4"

1 1/4"

1 1/2"

3/4"

3/4" DCW

3/4" DHW

1" 3/4"

3/4"

P-528 P-420

P-420 P-204

P-103

P-420 P-420

P-103

P-408

P-408

3/4"

P-408

P-408

P-408

P-528

P-708

P-418

P-408

P-408

P-408

P-408

P-103

P-103

P-418

P-418

P-502

3/4" 3/4" 1 1/2"

3/4" 1"

1 1/4"

1/

1"

1 1/4"

1 1/4"

3/4"

3/4"

1 1/4"

1 1/4"

WHA-B

WHA-B

WHA-B

3/4" 3/4"

1 1/2"

3/4"

1 1/2"

3/4"3/4"

3/4"

1"

3/4" 3/4"

3/4"

3/4" 3/4"

3/4" 3/4"

1 1/2"

2" 3/4"1-CWRP-1

3/4"

3/4"

3/4"

1/2"

1/2"

1/2" 1/2"

P-812

P-812

2"

3/4"

P-408P-408

P-408

1 1/2"

1"

P-103 P-604

TP-1

TP-1

TP-1

1151 Kildaire Farm Rd.

Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420

108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)

Joint Venture An Alliance for Success

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC

JOHN A. JURGIEL & ASSOCIATES, INC.

123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com

JURGIEL

JOHN A. JURGIEL & ASSOCIATES, INC.

/2

/2

:2

:5

A

M

P-902

DOMESTIC PIPE RISERS

8 8SM

RENOVATE SPACE FOR

WHOLE HEALTH

1 JEFFERSON BARRACKS DR.,

ST LOUIS, MO 63125

MAY 28, 2021

BID DOCUMENTS

657-20-101JB19-335

RCM/PLH

Scale: No Scale

DOMESTIC WATER RISERS

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

Sheets
FX001 - FIRE PROTECTION GENERAL INFORMATION
FD101 - SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN
FX101 - SECOND FLOOR FIRE PROTECTION PLAN
P-001 - PLUMBING GENERAL INFORMATION
PD101 - SECOND FLOOR WASTE/VENT DEMOLITION PLAN
PD102 - SECOND FLOOR DOMESTIC WATER/MEDICAL GAS DEMOLITION PLAN
PP101 - SECOND FLOOR DOMESTIC WATER PLAN
PW101 - SECOND FLOOR DRAIN, WASTE, AND VENT PLAN
P-501 - PLUMBING DETAILS
P-901 - SANITARY AND VENT PIPE RISERS
P-902 - DOMESTIC PIPE RISERS
2021-05-26T07:57:25-0700
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .