01-General Drawing 657-20-101JB (6 Pages) 5 28 2021 .pdf
PDF 4 MB Posted
- Solicitation number
- 36C25522R0058
About this file
This document package includes construction drawings and specifications for a renovation project at a VA medical center. The project scope involves renovating approximately 11,300 square feet of space to create a new whole health clinic on the second floor of an existing outpatient treatment facility. Key details include:
-
The project will install new walls, doors, flooring, mechanical and electrical systems, and finishes to convert existing exam rooms and offices into a new whole health clinic with classrooms, consultation rooms, waiting areas, and support spaces. Infection control barriers and provisions will be required during construction.
-
Applicable codes and standards include the 2018 editions of the International Building, Plumbing, Mechanical and Energy codes, as well as the 2017 NFPA 70, 2018 NFPA 101, 2010 ADA standards, and VA design guides. Construction type is mixed non-rated with sprinklers.
-
Drawings provide demolition plans, new construction layouts, life safety egress details, and architectural, structural, mechanical, plumbing and electrical drawings. Specifications cover infection control measures and barrier requirements.
-
The related federal contract opportunity is solicitation number 36C25522R0058 for the renovation work. The soliciting agency is the VA Veterans Health Administration VISN 15.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
PROJECT SITE MAP PROJECT LOCATION MAP
PROJECT IMAGE
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/2
/2
:5
:4
P
M
G-001
COVER
1 6RR
RENOVATE SPACE FOR
WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
MAY 28, 2021
BID DOCUMENTS
657-20-101JB19-335
RENOVATE SPACE FOR WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
VA PROJECT #: 657-20-101JB
TJS
APOGEE PROJECT #: 19-335
DRAWING LIST
ABATEMENT
HA100 FIRST FLOOR - LEAD ABATEMENT PLAN 1 5
HA101 SECOND FLOOR - FLOORING ABATEMENT PLAN 2 5
HA102 SECOND FLOOR - TSI AND OTHER ACM ABATEMENT PLAN 3 5
HA103 SECOND FLOOR - LEAD ABATEMENT PLAN 4 5
HA104 SECOND FLOOR - CEILING ABATEMENT PLAN 5 5
FIRE PROTECTION
FX001 FIRE PROTECTION GENERAL INFORMATION 1 3
FD101 SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN 2 3
FX101 SECOND FLOOR FIRE PROTECTION PLAN 3 3
PLUMBING
P-001 PLUMBING GENERAL INFORMATION 1 8
PD101 SECOND FLOOR WASTE/VENT DEMOLITION PLAN 2 8
PD102 SECOND FLOOR DOMESTIC WATER/MEDICAL GAS DEMOLITION PLAN 3 8
PP101 SECOND FLOOR DOMESTIC WATER PLAN 4 8
PW101 SECOND FLOOR DRAIN, WASTE, AND VENT PLAN 5 8
P-501 PLUMBING DETAILS 6 8
P-901 SANITARY AND VENT PIPE RISERS 7 8
P-902 DOMESTIC PIPE RISERS 8 8
MECHANICAL
M-001 MECHANICAL GENERAL INFORMATION 1 9
MD101 SECOND FLOOR MECHANICAL DEMOLITION PLAN 2 9
MD102 SECOND FLOOR MECHANICAL PIPING DEMOLITION PLAN 3 9
MH101 SECOND FLOOR HVAC PLAN 4 9
MP101 SECOND FLOOR MECHANICAL PIPING PLAN 5 9
M-301 MECHANICAL SECTIONS 6 9
M-501 MECHANICAL DETAILS 7 9
M-502 MECHANICAL DETAILS 8 9
M-601 MECHANICAL SCHEDULES 9 9
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 10
ED101 SECOND FLOOR ELECTRICAL DEMOLITION PLAN 2 10
ED102 SECOND FLOOR LIGHTING DEMOLITION PLAN 3 10
EP101 ENLARGED SECOND FLOOR POWER PLANS 4 10
EL101 ENLARGED SECOND FLOOR LIGHTING PLANS 5 10
EM101 SECOND FLOOR MECHANICAL POWER PLAN 6 10
E-501 ELECTRICAL DETAILS 7 10
E-601 ELECTRICAL SCHEDULES 8 10
E-602 SINGLE LINE DIAGRAM - PANEL 1-L23 9 10
E-603 SINGLE LINE DIAGRAM - PANEL 1-EC2B 10 10
TECHNOLOGY
T-001 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 1 4
TK101 ENLARGED SECOND FLOOR TECHNOLOGY PLAN 2 4
T-401 TECHNOLOGY ENLARGED PLANS & DETAILS 3 4
T-501 TECHNOLOGY DETAILS 4 4
FIRE ALARM
FA001 FIRE ALARM GENERAL NOTES, SYMBOL LEGEND, AND RISER 1 2
FA101 SECOND FLOOR FIRE ALARM PLAN 2 2
DRAWING LIST
GENERAL
G-001 COVER 1 6
GI101 GENERAL INFORMATION AND ICRA ANALYSIS 2 6
GI102 ICRA DETAILS 3 6
GI103 ENLARGED SECOND FLOOR ICRA PLAN 4 6
LS101 SECOND FLOOR OVERALL LIFE SAFETY PLAN 5 6
LS102 ENLARGED SECOND FLOOR LIFE SAFETY PLAN 6 6
STRUCTURAL
S-001 GENERAL NOTES AND DESIGN LOADS 1 4
SD101 SECOND FLOOR FRAMING DEMOLITION PLAN 2 4
S-101 SECOND FLOOR FRAMING PLAN 3 4
S-301 SECTIONS 4 4
ARCHITECTURAL
A-001 ARCHITECTURAL SYMBOLS, PARTITION TYPES, ABBREVIATIONS AND NOTES 1 14
A-002 LOGISTICS SITE PLAN 2 14
AD101 OVERALL SECOND FLOOR DEMOLITION PLAN 3 14
AD102 ENLARGED SECOND FLOOR DEMOLITION PLAN 4 14
ADC112 ENLARGED SECOND FLOOR REFLECTED CEILING DEMOLITION PLAN 5 14
A-101 OVERALL SECOND FLOOR PLAN 6 14
A-102 ENLARGED SECOND FLOOR PLAN 7 14
AC111 OVERALL SECOND FLOOR REFLECTED CEILING PLAN 8 14
AC112 ENLARGED SECOND FLOOR REFLECTED CEILING PLAN 9 14
AC113 ENLARGED CEILING SECTIONS 10 14
A-401 ENLARGED PLANS AND ENLARGED CEILING PLANS 11 14
A-501 PLAN DETAILS 12 14
A-502 PLAN DETAILS AND FLOOR TRANSITIONS 13 14
A-601 DOOR SCHEDULE, ELEVATIONS AND DETAILS 14 14
INTERIORS
I-001 FINISH SCHEDULE AND GENERAL NOTES 1 19
I-101 SECOND FLOOR FINISH PLAN 2 19
I-121 SECOND FLOOR FLOOR PATTERN PLAN 3 19
I-131 SECOND FLOOR WALL PROTECTION PLAN 4 19
I-141 SECOND FLOOR SIGNAGE FLOOR PLAN 5 19
I-201 CASEWORK ELEVATIONS 6 19
I-202 CASEWORK DETAILS 7 19
I-401 INTERIOR ELEVATIONS 8 19
I-402 INTERIOR ELEVATIONS 9 19
I-411 OVERALL EQUIPMENT FLOOR PLAN 10 19
I-421 ENLARGED EQUIPMENT PLANS 11 19
I-422 ENLARGED EQUIPMENT PLANS 12 19
I-423 ENLARGED EQUIPMENT PLANS 13 19
I-424 ENLARGED EQUIPMENT PLANS 14 19
I-431 ENLARGED RESTROOMS AND ELEVATIONS 15 19
I-432 ENLARGED RESTROOMS AND ELEVATIONS 16 19
I-601 EQUIPMENT SCHEDULE 17 19
I-602 EQUIPMENT SCHEDULE 18 19
I-611 SIGNAGE SCHEDULE 19 19
PROJECT LOCATION
NORTH
PROJECT LOCATION
NORTH
DocuSign Envelope ID: 16222EA7-D798-4CC7-9C06-921DD28D6352
5/26/2021
WALL SECTION
SYMBOL
INTERIOR ELEVATION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED DETAIL CALLOUT
ROOM DESIGNATION
SYMBOL
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL GRAPHIC SCALE
DETAIL #
PAGE #
DETAIL #
PAGE #
TRUE NORTH ARROW
A8.1
EXTERIOR ELEVATION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
ROOM
NAME
101A
NORTH
0 4 8 16
THE FOLLOWING SYSTEMS ARE A DESIGN/BUILD RESPONSIBILITY OF THE CONTRACTOR
OR PRODUCT MANUFACTURER AND WILL REQUIRE THE DEFERRED SUBMITTAL OF
DESIGN WORK TO THE VA FOR PLAN REVIEW AND PERMITTING:
1. FIRE SPRINKLER SYSTEMS
2. FIRE ALARM SYSTEMS
1-1/2"
DIAMETER
GRAB BAR
TOILET
TISSUE
DISPENSER
SANITARY
NAPKIN
DISPOSAL
TOILET
FIXTURE
TOILET
FIXTURE
TOILET
TISSUE
DISPENSER
1-1/2"
DIAMETER
GRAB BAR
EXPOSED
PLUMBING AT
BARRIER
FREE
LAVATORIES
SHALL BE
INSULATED.
LEVER OPERATING
CONTROLLED
SOAP DISPENSER
NOTE: SINKS IN COUNTERS TO BE
MOUNTED WITH RIM NO MORE
THAN 2'-10" HIGH AND WITH AT
LEAST 2'-3" KNEE CLEARANCE.
CLEAR
ACCESSIBLE TOILET PAPER TOWEL DISPENSER/
WASTE RECEPTICLE
TYPICAL ACCESSIBLE
CLEARANCE AT LAVATORY
TYPICAL ACCESSIBLE
LAVATORY AND MIRROR
1'-3" 1'-3"
M
IN
M A
X
M
A X
M
A X6
A
.F .F
5'-0" CLEAR
3'-0" 6"
3'-0"
" 3
1'-0" 3'-6"
2'-4"
5'-0" CLEAR
MIN
8"
MAX
6"
M
IN9
M
IN
M
IN
M A
X
17" MIN
TYPICAL URINAL
MOUNTING
CLEAR
15"
CLEAR
15"
"3
M
A X
W H
E R
E H
.C
A C
C E
S S
R E
Q 'D
OF DOOR WIDTH WHEN
ON WALL BEYOND
DOOR
CLOCK
NURSE
CALL
DOME
LIGHT
CLOCK OUTLET
TELEVISION
OUTLET
WALL MOUNTED TVCOAT RACK / COAT HOOK CLOCK & NURSE CALL DEVICES
HAND DRYER
T
Y P
M A
X
F O
R S
T A
N D
IN
G
O
.C
TELEVISION
OUTLET
F O
R S
E A
T E
D
O
.C
WALL MOUNTED TACKBOARD
AND MARKERBOARD
WALL MOUNTED LECTURE UNIT
BOARD
PAPER TOWEL
DISPENSER
2'-0" AT SIDEWALLS
AT COUNTER SINKS
1'-6" AT SIDEWALLS
AT LAVATORY
4'-0" MAX TO
HIGHEST OPERABLE
POINT - IF FIRE
EXTINGUISHER
OVER 40 LBS
3'-6" MAX HT.
FIRE EXTINGUISHER
CABINET
ELECTRICAL CABINET
DUPLEX
OUTLET
SWITCH
THERMOSTAT
TELEPHONE
OR DATA
OUTLET
FIRE ALARM
PULL
INTERCOM
STATION
DUPLEX
OUTLET
COMPUTER
TERMINAL
MOP BASIN
MOP SHELF
TYPICAL JANITORS CLOSET
FIRE ALARM
CHIME WITH
VISUAL
ALARM LIGHT
FIRE ALARM
PULL STATION
FIRE ALARM
ANNUNCIATOR
FIRE ALARM
INTERCOM
STATION
INTERCOM
MASTER
STATION
INTERCOM
WALL
OUTLET
INTERCOM STATION
WALL PROTECTION
BUMPERGUARD
HANDRAIL
OR DOOR FRAME
3" TO CORNERGUARD
CORNERGUARD
DRINKING FOUNTAIN
WHEELCHAIR ACCESSIBLE
(CANTILEVERED STYLE)
17" - 19"
8" MIN
9" MIN
6" MAX
M
IN
T O
P O
F S
P O
U T
' M
A X
DIAPER CHANGING
STATION
M
IN
M A
X
MISC. WALL DEVICES
/8
T O
B O
T T
O M
O F
R
E F
L E
C T
IV
E
S
U R
F A
C E
O F
M
IR
R
O R
1'-6"
TOWEL BAR
ACCESSIBLE
ROBE/COAT HOOK
ROBE/COAT
HOOK
TOILET ACCESSORIES
6"
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/2
/2
:5
:4
P
M
GI101
GENERAL INFORMATION AND ICRA
ANALYSIS
2 6RR
RENOVATE SPACE FOR
WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
MAY 28, 2021
BID DOCUMENTS
657-20-101JB19-335
TS
GENERAL SYMBOL LEGEND
DEFERRED SUBMITTALS
STANDARD MOUNTING HEIGHTS
PLASTIC WINDOW
SWIVEL CASTERS
WITH TWO
LOCKING BRAKES
MOBILE CART
A D
J U
S T
A B
L E
H E
IG
H
T
HEPA NEGATIVE
AIR UNIT
EXISTING WALL
EXISTING CEILING
FLEX DUCT
ICRA, ILSM, FIRE WATCH AND
MISC. FORMS
ILSM SIGNAGE
INTERIM LIFE SAFETY MEASURES IN EFFECT FOR THE
RENOVATE SPACE FOR WHOLE HEALTH, BUILDING 1
• THIS EXIT IS CLOSED AND LEADS TO A
CONSTRUCTION AREA
• PLEASE USE ALTERNATE EXITS AS MARKED
FORMS CONTAINER
TO BE CLEAR
PLASTIC
1'-5"
OUTSIDE OF BUILDING
WEEKLY CHANGED HEPA
FILTER
HEPA NEGATIVE
AIR UNIT
WEEKLY CHANGED (OR MORE AS
NEEDED) PRE FILTER
FIRE RATED PLYWOOD
F L E
X D
U C
T
SUPPLY DUCTS EITHER KEEP
RUNNING OR COVER WHEN
RUNNING TO KEEP DUST OUT.
TAPE ALL SERVICES
TO PROTECT AGAINST
CONTAMINATION
A
O
V
FIRE EXTINGUISHER ON PORTABLE
FLOOR BRACKET (ILSM MAY REQUIRE
MORE THAN ONE)
SUSPENDED PLASTIC ZIPPER
WALL CURTAIN BARRIER
6 MIL PLASTIC
TEMPORARY DIGITAL MANOMETER FOR NEGATIVE
PRESSURE MONITORING OUTSIDE OF ICRA BARRIER
FOR VA'S INSPECTION. INDICATOR SHALL BE AT -0.01
OR GREATER (VERIFY DAILY). IF NOT, VERIFY ALL
OPENINGS, SUCH AS DOOR CLOSED, AND/OR
CHANGE OUT NEGATIVE AIR PRE-FILTER.
PROVIDE STICKY MAT, DRY MAT, WET MAT
(CHANGED END OF SHIFT
OR MORE IF NECESSARY
TO MAINTAIN CLEANLINESS)
PROVIDE WIPES AND SPRAY FOR WET MAT
POST ICRA ILSM FIRE
INSPECTION SHEETS
CONTAINER VISIBLE TO
PUBLIC
COVER ALL RETURNS AT THE
GRATE/DIFFUSERS
OPTIONAL EXHAUST DUCTS
(COVER THE GRATES AND THE DIFFUSERS)
GI102
E
DOOR OPENING
VENT TO OUTSIDE
ROUTE TO BE
APPROVED BY COR.
FIRE PULL STATION WITH AUDIO/
VISUAL
ILSM SIGNAGE
GI102
ICRA BARRIER, SEE PLANS FOR
TYPE AND LOCATION
HEATED DETECTOR CUT-OFF
BASIS OF DESIGN: HEPA
NEGATIVE AIR UNIT INTEGRAL
WITH EDGEGUARD BARRIER
SYSTEM.
FIRE RATED PLYWOOD (TEMP.
REMOVE GLASS PANEL)
EXISTING WINDOW FRAME
TYPE A OR C ICRA
BARRIER, SEE PLANS
FOR TYPE AND
LOCATION
TYPE B OR D ICRA
BARRIER, SEE
PLANS FOR TYPE
AND LOCATION
EXISTING CEILING
EXISTING CONCRETE SLAB FLOORING
FINISHED FLOORING TO BE
KEPT CLEAN. FLOORS NOT
BEING REPLACED MUST BE
PROTECTED. COVER WITH
ROSIN PAPER/ FIRE RATED
PLYWOOD.
WHEN WORKING ABOVE
CEILING WITH BARRIERS
THAT TERMINATE AT
CEILING, PROVIDE PLASTIC
ENCLOSURE IN PLENUM
SPACE.
3 5/8" INSULATED WALL WITH
16 GAUGE METAL STUDS @
16" O.C. WALL TO EXTEND TO
UNDERSIDE OF DECK
5/8" FIRE RESISTANT GYPSUM
BOARD - BOTH SIDES
EXISTING CEILING SYSTEM
BASE - TO MATCH
EXISTING AREA
EXISTING FLOOR
UNDERSIDE OF EXISTING
DECK
C E
IL
IN
G H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
W A
L L
H E
IG
H
T V
A R
IE
S
F
IE
L D
V E
R
IF
Y
4 7/8"
5/8" FIRE RESISTANT GYPSUM
BOARD - BOTH SIDES
EXISTING CEILING SYSTEM
BASE - TO MATCH
EXISTING AREA
EXISTING FLOOR
UNDERSIDE OF EXISTING
DECK
C E
IL
IN
G H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
/2
4 7/8"
3 5/8" 16 GAUGE METAL
STUDS @ 16" O.C. WALL TO
EXTEND TO UNDERSIDE OF
DECK
A B
3 5/8" INSULATED WALL WITH
16 GAUGE METAL STUDS @
16" O.C. (2) LAYERS 5/8"
GYPSUM BOARD EACH SIDE.
WALL TO EXTEND TO
UNDERSIDE OF DECK
5/8" FIRE RESISTANT GYPSUM
BOARD - BOTH SIDES
EXISTING CEILING SYSTEM
BASE - TO MATCH
EXISTING AREA
EXISTING FLOOR
UNDERSIDE OF EXISTING
DECK
C E
IL
IN
G H
E
IG
H T
V A
R
IE
S F
IE
L D
V E
R
IF
Y
W A
L L
H E
IG
H
T V
A R
IE
S
F
IE
L D
V E
R
IF
Y
6 1/8"
C
FIRE RESISTANT SEALANT,
BOTH SIDES
FIRE RESISTANT SEALANT,
BOTH SIDES
FIRE RESISTANT SEALANT,
BOTH SIDES
1-HR RATED AND SMOKE RATED
U.L. DESIGN NO. U404
SMOKE RATED 2-HR RATED AND
SMOKE RATED
U.L. DESIGN NO. U404 D
PLASTIC SHEET BARRIER
NON RATED
PLASTIC SHEET
BARRIER
EXISTING WALL
ASSEMBLY
EXISTING CEILING
BOTTOM SEALING
RUNNER
TOP SEALING
RUNNER
SUPPORT POLES,
QUANTITY PER
MANUF.
RECOMMENDATIONS
REQU.
AS
A. THE CONTRACTOR SHALL NOT HAUL DEBRIS
THROUGH PATIENT-CARE AREAS WITHOUT PRIOR
APPROVAL OF THE COR AND THE MEDICAL CENTER.
B. ACTIVITY HAZARD RISK CLASSIFICATIONS OF CLASS
I OR CLASS II SHALL REQUIRE APPROVAL BY THE
FACILITY SAFETY MANAGER AND CONTRACTING
OFFICER REPRESENTATIVE BEFORE BEGINNING
ANY CONSTRUCTION WORK. HAZARD RISK
CLASSIFICATIONS OF CLASS III OR IV SHALL
REQUIRE A PERMIT BEFORE BEGINNING ANY
CONSTRUCTION WORK. INFECTION CONTROL
PERMITS WILL BE ISSUED BY THE FACILITY SAFETY
MANAGER AND CONTRACTING OFFICER
REPRESENTATIVE.
C. INFECTION CONTROL PERMITS SHALL BE POSTED
OUTSIDE THE APPROPRIATE CONSTRUCTION AREA.
MORE THAN ONE PERMIT MAY BE ISSUED, AS WORK
IS LOCATED IN MULTIPLE AREAS.
D. THE REQUIRED INFECTION CONTROL PRECAUTIONS
ARE AS FOLLOWS:
CLASS 1:
• NOTIFY THE COR.
• EXECUTE WORK USING METHODS TO MINIMIZE
RAISING DUST FROM CONSTRUCTION OPERATIONS.
• CEILING TILES: IMMEDIATELY REPLACE ANY CEILING
TILES DISPLACED FOR VISUAL INSPECTION.
• UPON COMPLETION: CLEAN WORK AREA, AND
NOTIFY COR.
CLASS 2:
• NOTIFY THE COR.
• PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE
DUST FROM DISPERSING INTO ATMOSPHERE SUCH
AS WET METHODS OR TOOL MOUNTED DUST
COLLECTORS.
• WATER MIST WORK SURFACES TO CONTROL DUST
WHILE CUTTING.
• SEAL UNUSED DOORS WITH PAINTERS TAPE.
• BLOCK OFF AND SEAL AIR VENTS.
• REMOVE OR ISOLATE HVAC SYSTEM IN AREAS
WHERE WORK IS BEING PERFORMED.
• UPON COMPLETION: WIPE WORK SURFACES WITH
CLEANER/ DISINFECTANT. CONTAIN CONSTRUCTION
WASTE BEFORE TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
CLASS 3:
DURING CONSTRUCTION WORK:
• OBTAIN PERMIT FROM THE COR.
• REMOVE OR ISOLATE HVAC SYSTEM IN AREA
WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
• COMPLETE ALL CRITICAL BARRIERS TO SEAL AREA
FROM NON-WORK AREA OR IMPLEMENT CONTROL
CUBE METHOD (CART WITH PLASTIC COVERING AND
SEALED CONNECTION TO WORK SITE WITH HEPA
VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS. INSTALL CONSTRUCTION
BARRIERS AND CEILING PROTECTION CAREFULLY,
OUTSIDE OF NORMAL WORK HOURS.
• MAINTAIN NEGATIVE AIR PRESSURE, 0.01 INCHES OF
WATER GAUGE, WITHIN WORK SITE UTILIZING HEPA
EQUIPPED AIR FILTRATION UNITS AND
CONTINUOUSLY MONITORED WITH A DIGITAL
DISPLAY, RECORDING AND ALARM INSTRUMENT,
WHICH MUST BE CALIBRATED ON INSTALLATION,
MAINTAINED WITH PERIODIC CALIBRATION AND
MONITORED BY THE CONTRACTOR.
• CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED CONTAINERS.
• COVER TRANSPORT RECEPTACLES OR CARTS.
TAPE COVERING UNLESS SOLID LID.
UPON COMPLETION:
• DO NOT REMOVE BARRIERS FROM WORK AREA
UNTIL COMPLETED PROJECT THOROUGHLY
CLEANED, AND IS INSPECTED BY THE CONTRACTING
OFFICER REPRESENTATIVE AND BY THE VA
ENVIRONMENTAL SERVICES DEPARTMENT.
• REMOVE CONSTRUCTION BARRIERS AND CEILING
PROTECTION CAREFULLY TO MINIMIZE SPREADING
OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION, OUTSIDE OF NORMAL WORK
HOURS.
• VACUUM WORK AREA WITH HEPA FILTERED
VACUUMS.
• WET MOP AREA WITH CLEANER/DISINFECTANT.
• UPON COMPLETION, RESTORE HVAC SYSTEM
WHERE WORK WAS PERFORMED.
• RETURN PERMIT TO THE COR.
CLASS 4:
DURING CONSTRUCTION WORK:
• OBTAIN PERMIT FROM THE COR.
• ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS
BEING DONE TO PREVENT CONTAMINATION OF
DUCT SYSTEM.
• COMPLETE ALL CRITICAL BARRIERS TO SEAL AREA
FROM NON-WORK AREA OR IMPLEMENT CONTROL
CUBE METHOD (CART WITH PLASTIC COVERING AND
SEALED CONNECTION TO WORK SITE WITH HEPA
VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS. INSTALL CONSTRUCTION
BARRIERS AND CEILING PROTECTION CAREFULLY,
OUTSIDE OF NORMAL WORK HOURS.
• MAINTAIN NEGATIVE AIR PRESSURE, 0.01 INCHES OF
WATER GAUGE, WITHIN WORK SITE UTILIZING HEPA
EQUIPPED AIR FILTRATION UNITS AND
CONTINUOUSLY MONITORED WITH A DIGITAL
DISPLAY, RECORDING AND ALARM INSTRUMENT,
WHICH MUST BE CALIBRATED ON INSTALLATION,
MAINTAINED WITH PERIODIC CALIBRATION AND
MONITORED BY THE CONTRACTOR.
• SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES.
• CONSTRUCT ANTEROOM AND REQUIRE ALL
PERSONNEL TO PASS THROUGH THIS ROOM SO
THEY CAN BE VACUUMED USING A HEPA VACUUM
CLEANER BEFORE LEAVING WORK SITE OR THEY
CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE
REMOVED EACH TIME THEY LEAVE WORK SITE.
• ALL PERSONNEL ENTERING WORK SITE ARE
REQUIRED TO WEAR SHOE COVERS. SHOE COVERS
MUST BE CHANGED EACH TIME THE WORKER EXITS
THE WORK AREA.
UPON COMPLETION:
• DO NOT REMOVE BARRIERS FROM WORK AREA
UNTIL COMPLETED PROJECT THOROUGHLY
CLEANED, AND IS INSPECTED BY THE CONTRACTING
OFFICER REPRESENTATIVE.
• REMOVE CONSTRUCTION BARRIERS AND CEILING
PROTECTION CAREFULLY TO MINIMIZE SPREADING
OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION, OUTSIDE OF NORMAL WORK
HOURS.
• CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED CONTAINERS.
• COVER TRANSPORT RECEPTACLES OR CARTS.
TAPE COVERING UNLESS SOLID LID.
• VACUUM WORK AREA WITH HEPA FILTERED
VACUUMS.
• AREA TO BE CLEANED/DISINFECTED PER VA
ENVIRONMENTAL SERVICES GUIDELINES AS
COORDINATED BY THE COR.
• UPON COMPLETION, RESTORE HVAC SYSTEM
WHERE WORK WAS PERFORMED.
• RETURN PERMIT TO THE COR.
TYPE "A" DOOR -
WHERE INDICATED ON PLANS, IN ALL TYPE "A" INFECTION CONTROL
BARRIERS, USE A FLUSH 3'-0"x7'-0" SOLID CORE WOOD DOOR WITH 45 MINUTE
RATING. DOORS TO BE IN HOLLOW METAL DOOR FRAME AND USE DOOR
HARDWARE SET HW-4A. SEE SPECIFICATIONS FOR DOOR HARDWARE.
TYPE "B" DOOR -
WHERE INDICATED ON PLANS, IN ALL TYPE "B" INFECTION CONTROL
BARRIERS, USE A FLUSH 3'-0"x7'-0" SOLID CORE WOOD DOOR . DOORS TO BE
IN HOLLOW METAL DOOR FRAME AND USE DOOR HARDWARE SET HW-4. SEE
SPECIFICATIONS FOR DOOR HARDWARE.
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/2
/2
:5
:5
P
M
GI102
ICRA DETAILS
3 6RR
RENOVATE SPACE FOR
WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
MAY 28, 2021
BID DOCUMENTS
657-20-101JB19-335
TJS
Scale: 1/2" = 1'-0"
ICRA MOBILE CONTAINMENT CART
Scale: 6" = 1'-0"
ILSM SIGNAGE
Scale: 1/2" = 1'-0"
GENERAL ICRA CONSTRUCTION PLAN LAYOUT
Scale: 1/2" = 1'-0"
SECTION AT ICRA CONSTRUCTION PLAN
Scale: 3/4" = 1'-0"
ICRA BARRIER WALL TYPES
ICRA DOOR LEGEND
2E28
CLASSROOM
2E23
COPY AREA 2E24
OFFICE
2E21
WAITING
2E22
RECEPTION
2E02
PAT TLT
2E01
HAC
2E19
CONSULT
2E20
CONSULT
2C06
OFFICE
2C05
PROVIDER
OFFICE
2C02B
OFFICE
2C10
OIT
2C09
OPEN OFFICE
2C08
OPEN OFFICE
2C07B
WOMEN'S
RESTROOM
2C07A
MEN'S
RESTROOM
2E27
CLASSROOM
GROUP
ROOM 2A
2E25A
GROUP
ROOM 1A
2E26A
2C02A
OFFICE
2C03
OFFICE
2C04A
OFFICE
2C04B
OFFICE
H203
CORRIDOR
H205
CORRIDOR
H207
CORRIDOR
2E26C
STORAGE
STORAGE
2E25C
ELEV_
2 2
3 3
3 3
3 3
AREA OF ROOF BELOW
326 SF
GROUP
ROOM 1B
364 SF
GROUP
ROOM 2B
H208
STAIR S201
MATCH LINE
/1 LS102
MATCH LINE
/1 LS102
CAPACITYCLR
STAIR
EXIT
32" 106
FAC
H210
EXAM
2C11
PHONE CLO.
2C11A
IRM
2C10A
WAITING
2C01
RECEPTION
2C01A
EXAM
2C01B
2E11
MEDITATION
2E12
MASSAGE
2E13
EXAM
2E14
MEDS
2E15
CHIRO EXAM
2E16
CHIRO EXAM
2E17
CONSULT
2E10
ACUPUNCTURE
2E09
ACUPUNCTURE
2E08
CLEAN UTILITY
2E07
SOILED
2E06
CHIRO EXAM
CHIRO
EXAM
2E05
2E04
CONSULT
2E03
PAT TLT
2E02
PAT TLT
2E01
HAC
2E18
CONSULT
2E19
CONSULT
2E20
CONSULT
2C04B
OFFICE
H201
CORRIDOR
3 3
/2 LS102/2 LS102
MATCH LINE MATCH LINE
SCOPE OF CONSTRUCTION
ICRA BARRIER LEGEND
LINE REPRESENTS DIAGRAMMED
LOCATION OF ICRA BARRIERS
EXISTING WALL
NEW WALL
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RATED
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs#
S S S S
© COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/2
/2
:2
:4
P
M
GI103
ENLARGED SECOND FLOOR ICRA PLAN
4 6RR
RENOVATE SPACE FOR
WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
MAY 28, 2021
BID DOCUMENTS
657-20-101JB19-335
TJS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
ENLARGED SECOND FLOOR ICRA PLAN - NORTH
NORTH
0 4 8 16
Scale: 1/8" = 1'-0"
ENLARGED SECOND FLOOR ICRA PLAN - SOUTH
NORTH
0 4 8 16
SCOPE OF WORK LEGEND
1 PROVIDE "TYPE A" HARD WALL INFECTION
CONTROL BARRIER THIS LOCATION.
2 WALK OFF MAT THIS LOCATION.
3 USE PORTABLE HEPA FILTRATION UNIT, VENT TO
EXTERIOR WHEN WORKING THIS AREA.
4 PROVIDE "TYPE D" SHEET PLASTIC BARRIER THIS
LOCATION.
5 LINE OF SOFFIT ABOVE.
6 PROVIDE "TYPE B" BARRIER THIS LOCATION.
WALL LEGEND
DocuSign Envelope ID: 68BB6621-FDF1-40A6-A543-2A241B61CB44
S SS
A
A.3 B C C.1 D.1
D.2
E F G H J K M N O P Q
R
R.2 S T U V
V.3U.1T.2T.1R.3
LL
C.2B.2B.1A.4
10.1
A
A
B
C
E
D
D
STAIRS
ELEV.
STAIRSSTAIRS
STAIRS
ELEV.
/2 LS102
/1 LS102
/2 LS102
/1 LS102
371 SF
CLASSROOM
294 SF
CLASSROOM
353 SF
GROUP
ROOM 1A
327 SF
GROUP
ROOM 2A
100 SF
OFFICE
94 SF
COPY
AREA
317 SF
WAITING
187 SF
RECEPTION
338 SF
OPEN
OFFICE
296 SF
OPEN
OFFICE
701 SF
OFFICE
111 SF
OFFICE
96 SF
OFFICE
97 SF
OFFICE
102 SF
OFFICE
135 SF
MEN'S
RESTROOM
162 SF
WOMEN'S
RESTROOM
135 SF
OFFICE
117 SF
PROVIDER
OFFICE
755 SF
CORRIDOR
112 SF
CONSULT
68 SF
HAC
100 SF
PAT TLT
98 SF
CONSULT
97 SF
CONSULT
86 SF
PAT TLT
149 SF
CONSULT
103 SF
CONSULT
128 SF
CHIRO
EXAM
157 SF
CHIRO
EXAM
136 SF
CHIRO
EXAM
134 SF
CHIRO
EXAM
106 SF
SOILED
101 SF
MEDS
107 SF
EXAM
133 SF
CLEAN
UTILITY
128 SF
ACUPUNCTURE
122 SF
MASSAGE
128 SF
MEDITATION
142 SF
ACUPUNCTURE
STAIR CAN BE USED FOR
CONTRACTOR ACCESS. MATERIAL
AND LARGE TOOL TRANSPORT TO
BE DONE OFF PEAK HOURS
ELEVATOR CAN BE USED FOR
CONTRACTOR ACCESS. MATERIAL AND
LARGE TOOL TRANSPORT TO BE DONE
OFF PEAK HOURS. PROTECT INTERIOR
OF ELEVATOR CAB AT ALL TIMES.
CONTRACTOR ACCESS
AT GROUND LEVEL
CONTRACTOR
MATERIAL ACCESS AT
GROUND LEVEL, OFF
PEAK HOURS ONLY.
CAPACITYCLR
STAIR
EXIT
38" 126
CAPACITYCLR
STAIR
EXIT
32" 106FAC
H210
EGRESS WIDTH
(per IBC 1005.3.1)
COMMON PATH OF TRAVEL
(per IBC Table 1006.2.1)
EXIT ACCESS TRAVEL
(per IBC TABLE 1017.2)
DEAD-END CORRIDOR
(NFPA 101A, CH. 8)
STAIR 1 EXIT DOORS =
75"/(0.30) = 249 PPL
STAIR 2 EXIT DOOR =
41"/(0.30) = 136 PPL
70'-0" MAXIMUM
100'-0" ALLOWED
179'-6" MAXIMUM DISTANCE
300'-0" ALLOWED
COMPLIANT PER NFPA 101A
WORKSHEET 8.6.1
OCCUPANT LOAD
(per IBC TABLE 1004.1 and NFPA 7.3.1.2)
TOTAL BUILDING
81,064 GSF/150 = 541 PPL
SECOND FLOOR -
25,611 GSF/150 = 171 PPL
RENOVATED AREA -
11,318 GSF/150 = 76 PPL
GROSS BUILDING AREA
(OUTSIDE FACE WALLS)
81,064 SF
GROSS MEASURED AREA
(INTERIOR FACE WALLS)
79,895 SF
REQUIRED # OF EXITS
(NFPA 101A, CH. 8)
REQUIRED DISTANCE
BETWEEN EXITS
FLOOR
FLOOR AREAS (per TABLE 506.2):
EXISTING NEW TOTAL
0 SF
AREA TOTAL = 81,064 SF
AREA ALLOWED = 112,500 SF
FIRST 29,842 SF
EGRESS INFORMATION
BUILDING HEIGHT = 3 STORIES + BASEMENT - < 85'-0"
EXSTING BUILDING
ALLOWABLE HEIGHT = 6 STORIES - 85'-0"
AREA AND HEIGHT REQUIREMENTS:
SERVICE SINKS
X
PLUMBING CODE REVIEW
MALEFIXTURE FEMALE
X
DRINKING FOUNTAINS
LAVATORIES
URINALS
WATER CLOSETS
X X
X X
X
X
29,842 SF
0 SFSECOND 25,611 SF25,611 SF
0 SFTHIRD 25,611 SF25,611 SF
0 SFBASEMENT 25,611 SF25,611 SF
COMPLIANT PER NFPA 101A
WORKSHEET 8.6.1
COMPLIANT PER NFPA 101A
WORKSHEET 8.6.1
NET RENOVATED AREA = 10,880 SF
GROSS RENOVATED AREA = 11,318 SF
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE RATED
SCOPE OF CONSTRUCTION
EGRESS PATH
EGRESS PATH TAG
EGRESS PATH TAG - COMMON PATH
EGRESS IDENTIFICATION
XXX
XXX
FHC
FEC
FBC
CAPACITYCLR
EXTERIOR
EXIT
XX" ###
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS
CAPACITY
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
FIRE BLANKET CABINET
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/2
/2
:2
:4
P
M
LS101
SECOND FLOOR OVERALL LIFE SAFETY
PLAN
5 6RR
RENOVATE SPACE FOR
WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
MAY 28, 2021
BID DOCUMENTS
657-20-101JB19-335
TJS
PROPOSED USE:
APPLICABLE CODES:
GENERAL CODE INFORMATION:
NEW CONSTRUCTION
RENOVATION (EXISTING BUILDING)
CONSTRUCTION TYPE:
MIXED CONSTRUCTION
SPRINKLERED
MEZZANINE
MIXED OCCUPANCY
PRIMARY OCCUPANCY:
SECONDARY OCCUPANCY:
PROJECT NAME:
PROJECT ADDRESS:
OWNER OR AGENT:
OUTPATIENT TREATMENT
TYPE II-B
BUSINESS
2018 International Building Code
2018 International Plumbing Code
2018 International Energy Conservation Code 2018 International Mechanical Code 2018 NFPA 101 Life Safety Code 2017 NFPA 70 National Electrical Code
2010 ADA Code 2018 NFPA 101 Life Safety Code
VA Design Guide Architectural Manual 2014 August 01
ASHRAE 90.1-2016
2010 ADA Standards for Accessible Design
RENOVATE SPACE FOR WHOLE HEALTH
1 JEFFERSON BARRACKS DR., ST
LOUIS, MO 63125
ST LOUIS VA JEFFERSON BARRACKS
CODE INFORMATION
EGRESS PATH "A"
PATH ID LENGTH
A 16' - 0"
A (COMMON) 45' - 10"
TOTAL PATH LENGTH 61' - 10"
EGRESS PATH "B"
PATH ID LENGTH
B (COMMON) 57' - 0"
TOTAL PATH LENGTH 57' - 0"
EGRESS PATH "C"
PATH ID LENGTH
C 138' - 4 1/4"
TOTAL PATH LENGTH 138' - 4 1/4"
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
NORTH
0 84 16
Scale: 3/32" = 1'-0"
OVERALL SECOND FLOOR LIFE SAFETY PLAN
EGRESS PATH "D"
PATH ID LENGTH
D 21' - 0 1/32"
D (COMMON) 39' - 8 13/16"
TOTAL PATH LENGTH 60' - 8 27/32"
EGRESS PATH "E"
PATH ID LENGTH
E (COMMON) 68' - 3 1/4"
TOTAL PATH LENGTH 68' - 3 1/4"
WALL RATING LEGEND
SCOPE OF WORK LEGEND
LIFE SAFETY LEGEND
CAPACITYCLR
STAIR
EXIT
32" 106
S SS
P
R
R.2 T V
V.3U.1T.2T.1R.3
CAPACITYCLR
STAIR
EXIT
41" 136
CAPACITYCLR
STAIR
EXIT
34" 113
/2 LS102/2 LS102
MATCH LINE MATCH LINE
ACUPUNCTURE
2E09
ACUPUNCTURE
2E10
MEDITATION
2E11
MASSAGE
2E12
EXAM
2E13
CLEAN
UTILITY
2E08
MEDS
2E14
SOILED
2E07
CHIRO
EXAM
2E06
CHIRO
EXAM
2E15
CHIRO
EXAM
2E16
CHIRO
EXAM
2E05
CONSULT
2E17
CONSULT
2E04
CONSULT
2E18
PAT TLT
2E03
PAT TLT
2E02
CONSULT
2E19
HAC
2E01
CONSULT
2E20
OFFICE
2C04A
STAIR
S201
H208
A
A
B
B
FEC
FEC
FEC
FHC
J K M N O P Q
R R.2 S T U V V.3
10.1
8.1
CAPACITYCLR
STAIR
EXIT
41" 136
CAPACITYCLR
STAIR
EXIT
34" 113
MATCH LINE
MATCH LINE
/1 LS102 /1 LS102
HAC
2E01
CONSULT
2E20
OFFICE
2C02A
OFFICE
2C02B
OFFICE
2C03
OPEN
OFFICE
2C08
OPEN
OFFICE
2C09
MEN'S
RESTROOM
2C07A WOMEN'S
RESTROOM
2C07B
OFFICE
2C06
PROVIDER
OFFICE
2C05
OFFICE
2C04A
OFFICE
2C04B
STAIR
S201
H208
WAITING
2E21
RECEPTION
2E22
OFFICE
2E24COPY
AREA
2E23
CORRIDOR
H203
ELEV
LOBBY
H206
CORRIDOR
H207
GROUP
ROOM 2A
2E25A
GROUP
ROOM 1A
2E26A
CORRIDOR
H205
CLASSROOM
2E27
CLASSROOM
2E28
C
E
D
D
B
E
FEC
FEC
FEC
FEC
CAPACITYCLR
STAIR
EXIT
32" 106
OIT
2C10
FAC
H210
RECEPTION
2C01A
WAITING
2C01
EXAM
2C01B
STAIR
S202
OFFICE
2C29
EXAM
2C11
PHONE CLO.
2C11A
OPTICAL
SHOP
2C12
WAITING
ALCOVE
H205A
IRM
2C10A
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE RATED
EGRESS WIDTH
(per IBC 1005.3.1)
COMMON PATH OF TRAVEL
(per IBC Table 1006.2.1)
EXIT ACCESS TRAVEL
(per IBC TABLE 1017.2)
DEAD-END CORRIDOR
(NFPA 101A, CH. 8)
STAIR 1 EXIT DOORS =
75"/(0.30) = 249 PPL
STAIR 2 EXIT DOOR =
41"/(0.30) = 136 PPL
70'-0" MAXIMUM
100'-0" ALLOWED
179'-6" MAXIMUM DISTANCE
300'-0" ALLOWED
COMPLIANT PER NFPA 101A
WORKSHEET 8.6.1
OCCUPANT LOAD
(per IBC TABLE 1004.1 and NFPA 7.3.1.2)
TOTAL BUILDING
81,064 GSF/150 = 541 PPL
SECOND FLOOR -
25,611 GSF/150 = 171 PPL
RENOVATED AREA -
11,318 GSF/150 = 76 PPL
GROSS BUILDING AREA
(OUTSIDE FACE WALLS)
81,064 SF
GROSS MEASURED AREA
(INTERIOR FACE WALLS)
79,895 SF
REQUIRED # OF EXITS
(NFPA 101A, CH. 8)
REQUIRED DISTANCE
BETWEEN EXITS
FLOOR
FLOOR AREAS (per TABLE 506.2):
EXISTING NEW TOTAL
0 SF
AREA TOTAL = 81,064 SF
AREA ALLOWED = 112,500 SF
FIRST 29,842 SF
EGRESS INFORMATION
BUILDING HEIGHT = 3 STORIES + BASEMENT - < 85'-0"
EXSTING BUILDING
ALLOWABLE HEIGHT = 6 STORIES - 85'-0"
AREA AND HEIGHT REQUIREMENTS:
SERVICE SINKS
X
PLUMBING CODE REVIEW
MALEFIXTURE FEMALE
X
DRINKING FOUNTAINS
LAVATORIES
URINALS
WATER CLOSETS
X X
X X
X
X
29,842 SF
0 SFSECOND 25,611 SF25,611 SF
0 SFTHIRD 25,611 SF25,611 SF
0 SFBASEMENT 25,611 SF25,611 SF
COMPLIANT PER NFPA 101A
WORKSHEET 8.6.1
COMPLIANT PER NFPA 101A
WORKSHEET 8.6.1
NET RENOVATED AREA = 10,880 SF
GROSS RENOVATED AREA = 11,318 SF
SCOPE OF CONSTRUCTION
EGRESS PATH
EGRESS PATH TAG
EGRESS PATH TAG - COMMON PATH
EGRESS IDENTIFICATION
XXX
XXX
FHC
FEC
FBC
CAPACITYCLR
EXTERIOR
EXIT
XX" ###
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS
CAPACITY
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
FIRE BLANKET CABINET
NEW WALL, SEE
WALL TYPES
NEW DOOR, SEE
DOOR SCHEDULE
NEW TOILET NEW SINK
EXISTING
WALL
EXISTING
DOOR
1151 Kildaire Farm Rd.
Suite 120 Raleigh, NC 27511 www.acg-pa.com (919)858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com (843)875-3637Project Mgr: Alex Kramer (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
JOHN A. JURGIEL & ASSOCIATES, INC.
123 N. Main Street (636)757-3060 St. Charles, MO. 63301 Jurgiel.com
JURGIEL
JOHN A. JURGIEL & ASSOCIATES, INC.
/2
/2
:2
:5
P
M
LS102
ENLARGED SECOND FLOOR LIFE
SAFETY PLAN
6 6RR
RENOVATE SPACE FOR
WHOLE HEALTH
1 JEFFERSON BARRACKS DR.,
ST LOUIS, MO 63125
MAY 28, 2021
BID DOCUMENTS
657-20-101JB19-335
TJS
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
ENLARGED SECOND FLOOR LIFE SAFETY PLAN - SOUTH
Scale: 1/8" = 1'-0"
ENLARGED SECOND FLOOR LIFE SAFETY PLAN - NORTH
NORTH
0 4 8 16
NORTH
0 4 8 16
WALL RATING LEGEND
EGRESS PATH "A"
PATH ID LENGTH
A 16' - 0"
A (COMMON) 45' - 10"
TOTAL PATH LENGTH 61' - 10"
EGRESS PATH "B"
PATH ID LENGTH
B (COMMON) 57' - 0"
TOTAL PATH LENGTH 57' - 0"
EGRESS PATH "C"
PATH ID LENGTH
C 138' - 4 1/4"
TOTAL PATH LENGTH 138' - 4 1/4"
EGRESS PATH "D"
PATH ID LENGTH
D 21' - 0 1/32"
D (COMMON) 39' - 8 13/16"
TOTAL PATH LENGTH 60' - 8 27/32"
EGRESS PATH "E"
PATH ID LENGTH
E (COMMON) 68' - 3 1/4"
TOTAL PATH LENGTH 68' - 3 1/4"
PROPOSED USE:
APPLICABLE CODES:
GENERAL CODE INFORMATION:
NEW CONSTRUCTION
RENOVATION (EXISTING BUILDING)
CONSTRUCTION TYPE:
MIXED CONSTRUCTION
SPRINKLERED
MEZZANINE
MIXED OCCUPANCY
PRIMARY OCCUPANCY:
SECONDARY OCCUPANCY:
PROJECT NAME:
PROJECT ADDRESS:
OWNER OR AGENT:
OUTPATIENT TREATMENT
TYPE II-B
BUSINESS
2018 International Building Code
2018 International Plumbing Code
2018 International Energy Conservation Code 2018 International Mechanical Code 2018 NFPA 101 Life Safety Code 2017 NFPA 70 National Electrical Code
2010 ADA Code 2018 NFPA 101 Life Safety Code
VA Design Guide Architectural Manual 2014 August 01
ASHRAE 90.1-2016
2010 ADA Standards for Accessible Design
RENOVATE SPACE FOR WHOLE HEALTH
1 JEFFERSON BARRACKS DR., ST
LOUIS, MO 63125
ST LOUIS VA JEFFERSON BARRACKS
CODE INFORMATION
SCOPE OF WORK LEGEND
LIFE SAFETY LEGEND
CONSTRUCTION LEGEND
0 10050 200
NORTH
PLAN
| 01-General |
| Sheets |
| G-001 - COVER |
| GI101 - GENERAL INFORMATION AND ICRA ANALYSIS |
| GI102 - ICRA DETAILS |
| GI103 - ENLARGED SECOND FLOOR ICRA PLAN |
| LS101 - SECOND FLOOR OVERALL LIFE SAFETY PLAN |
| 20210526_Fixed_1_G_and_2_L_sheets |
| Sheets |
| GI103 - ENLARGED SECOND FLOOR ICRA PLAN |
| LS101 - SECOND FLOOR OVERALL LIFE SAFETY PLAN |
| LS102 - ENLARGED SECOND FLOOR LIFE SAFETY PLAN |
File details come from the government source that posted it. Updated .