Electrical General Addendum 3 for Wanship Fire Station 23 Dorm Addition and Interior Remodel
This is an Addendum 3 electrical design document for the North Summit Fire District's Wanship Fire Station 23 dorm addition and interior remodel project located at 2000 South Hoytsille Road, Coalville, Utah 84017. The project involves electrical system installation for a fire station renovation and requires the electrical contractor to provide complete and operable electrical systems in strict accordance with local, state, and national codes. The scope includes lighting design, power distribution, fire alarm integration, data/telecom infrastructure, roof penetration seals, and coordination with mechanical and architectural trades. The electrical system must be tested and confirmed for proper operation prior to project closeout. The mandatory pre-proposal site visit is scheduled for August 27, 2026, with questions due by September 2, 2026 at 2:00 p.m. MT, and proposals due by September 4, 2026 at noon MT. The document includes detailed electrical general notes, lighting control sequences compliant with IECC 2021, and power distribution specifications indicating a new total electrical load of 27,254 VA or 113.6 amperes at 125 percent of existing demand plus new loads.
The electrical design incorporates copper THHN/THWN-2 conductors rated at 600 volts, EMT conduit in interior dry locations, PVC conduit underground with GRC elbows, and equipment listed by nationally recognized testing agencies. Specifications require all conduit to be supported by industry-standard methods, with flexible conduit limited to fixture and equipment connections not exceeding 72 inches. The contractor must coordinate with equipment suppliers, mechanical contractors, and the architect regarding device placement, thermostats, HVAC service receptacles, and emergency lighting connections to unswitched circuit legs. All penetrations through fire-rated assemblies require fire-stopping materials, and roof penetrations must include boots sealed per roof warranty specifications. The electrical contractor is responsible for maintaining continuity to existing equipment during any removals and replacing any damaged wiring to existing devices while bringing them back to full operational status.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 3-Attachment C Cost Sheet.xlsx | XLSX spreadsheet | |
| 9-20250120 111534.jpg | JPG image | |
| 4-Attachment E.pdf | ||
| 12-Award Justification.pdf | ||
| 6-Attachment A Standard Terms and Conditions GOODS AND SERVICES.docx | DOCX document | |
| 5-Attachment B2 - Westnet plans.pdf | ||
| 2-Staiton 23 RFP.pdf | ||
| 1-Attachment D Technical Evaluation Scoring Sheet.xlsx | XLSX spreadsheet | |
| 10-Pre-proposal Mtg Attendance Log ADA (1).docx | DOCX document | |
| 7-Attachmetn B - Fire Station 23 Rev. 08.19.26.pdf | ||
| 11-000 U3P Courtesy Posting Closed.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
alt ar ch ite ct ur e
1445 w. 8660 s.
west jordan, utah 84088 www.altarchitecture-ut.com
ANDY TONGISH 801-865-0633
TIT
LE
PR
O
JE
C
T
C
LIE
NT
AD
DR
ES
S
NO. DATE DESCRIPTION
SHEET
REVISIONS
6/
/2
2:
:0
PM
E000
CONSULTING ENGINEERS, INC.
2332 West 12600 South, Suite F | Riverton, UT 84065
(801) 566-0503 www.rmceut.com Project #
ROCKY MOUNTAIN
25042
BT / TG
BK
2/20/2025
1 04/10/26 SMOKE DETECTOR
25-001
W
AN
SH
IP
FI
RE
ST
AT
IO
N
NO
RT
H
SU
M M
IT
FIR
E
DE
PA
RT
M
EN
T
SO
UT
H
HO
YT
SV
ILL
E
RO
AD
C O
AL
VI
LL
E, U
TA
H
RE
G
IS
TE
RE
D PROFESS I ONAL ENG
I NEER
STATE OF UTAH
No. 7945859-2202
DAVID W.
STEWARD
2 07/29/26 ADD3
GENERAL NOTES:
1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND THE SPECIFICATIONS ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT DOCUMENTS, AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION, OR CONFLICT EXIST IN EITHER THE PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING THEIR BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIERS SHALL SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS INCLUSIVE OF THE ORIGINAL BID. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE, THE CONTRACTOR SHALL TEST AND CONFIRM ITS PROPER OPERATION. ANY INCOMPLETE SYSTEM SHALL BE MADE
COMPLETE AND OPERABLE PRIOR TO PROJECT CLOSEOUT.
2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE GREATER THAN SPECIFIED AND/OR
DIMENSIONED ON THE PLANS.
3. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS, AND LABOR FOR THE CONNECTIONS OF
ALL EQUIPMENT SHOWN ON THE PLANS - ARCHITECTURAL, MECHANICAL, ETC.
4. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH THE MOST RECENT LOCAL, STATE, AND NATIONAL CODES. IF AT ANY TIME DURING OR AFTER CONSTRUCTION SOMETHING IS FOUND TO BE INSTALLED IN
VIOLATION OF THESE CODES LISTED ABOVE, IT SHALL BE CORRECTED BY THE CONTRACTOR.
5. WHERE A RACEWAY ENTERS A BUILDING OR STRUCTURE FROM THE OUTSIDE, IT SHALL BE SEALED AS PER NEC 225.27.
6. ALL ELECTRICAL EQUIPMENT THAT IS LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING OR MAINTENANCE WHILE ENERGIZED SHALL BE FIELD OR FACTORY LABELED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS PER NEC 110.16. THE LABEL SHALL ALSO CONTAIN THE MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE THE FAULT CURRENT CALCULATIONS WERE PERFORMED AS PER NEC 110.24.
7. EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS PURPOSE AND TO IDENTIFY THE
CIRCUIT SOURCE THAT SUPPLIES THE DISCONNECTING MEANS PER NEC 110.22.
8. ALL EQUIPMENT PROVIDED BY THE EC SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE
CONDITIONS AND SPACE THAT EQUIPMENT IS BEING INSTALLED WITHIN.
9. THE EC SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE EC SHALL GROUND THE ELECTRICAL
SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.
10. CONDUIT LAYOUTS SHOWN ON THE PLANS ARE DIAGRAMMATIC, NOT INDICATING THE ROUTING REQUIRED. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT, BUILDING STRUCTURE, AND OTHER POTENTIAL OBSTRUCTIONS.
11. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.
12. THE EC SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY STANDARD METHODS AND PRACTICES. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE APPLICATION.
13. MINIMUM SIZE CONDUIT SHALL BE 3/4" UNO. CONDUIT INSTALLED WITHIN THE BUILDING IN DRY LOCATIONS WITHIN WALL, CEILINGS, OR EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE SHALL BE EMT WITH STEEL SET SCREW FITTINGS. IN EXTERIOR LOCATIONS (EXCEPT FOR THE SERVICE ENTRANCE) THE CONDUIT SHALL BE EMT WITH COMPRESSION GLAND TYPE FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH. 40) WITH GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN DIRECT CONTACT WITH THE SOIL.
14. FLEXIBLE CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR SEAL-TITE CONDUIT SHALL NOT BE
GREATER THAN 72 INCHES.
15. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB RATED NYLON PULL CORD.
16. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS, WALLS, ETC.), THEY SHALL BE
APPROVED BY THE INSPECTING OFFICER (INSPECTOR).
17. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120VAC BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12 (CU,THHN) + 1#12 (CU,THHN) GND IN 3/4" EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10 (CU,THHN) FOR BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 125' TO ACCOMMODATE FOR VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES, AND NOTES ON DRAWINGS FOR ALL OTHER
BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.
18. CONDUCTORS SHALL BE COPPER, 600VAC RATED, TYPE THHN/THWN-2 UNO. CONDUCTORS UP TO #10AWG SHALL
BE SOLID AND CONDUCTORS #8AWG OR LARGER SHALL BE STRANDED.
19. METAL CLAD CABLING MAY BE USED BETWEEN DEVICES SUCH AS LIGHTING, RECEPTACLES, SWITCHES, ETC.
UNLESS OTHERWISE REQUIRED BY THE NEC. HOME RUNS SHALL BE INSTALLED IN CONDUIT. MC CABLE SHALL
NOT BE INSTALLED EXPOSED.
20. EC SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, AND UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FROM THE PREMISES.
21. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED WITH THE ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL
BE MADE TO CONCEAL WIRING METHODS.
22. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND
CAULK, PUTTY, STRIP AND SHEET FORMS, DOW CORNING 3-6548 SILICONE RTV FOAM.
23. COORDINATE LOCATION OF WALL MOUNTED DEVICES WITH CABINETRY AND OTHER WALL OBSTRUCTIONS.
COORDINATE CEILING MOUNTED DEVICES WITH CEILING OBSTRUCTIONS. ANY DEVICES THAT NEED TO BE RELOCATED MUST BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER PRIOR TO ROUGH-IN FOR NEW
LOCATION.
24. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE PLACEMENT OF ALL DEVICES INSTALLED WITHIN THE CEILING SUCH AS LIGHTING, SPEAKERS, FIRE SPRINKLERS, SMOKE/HEAT DETECTORS, ETC.
ANY EXISTING DEVICES THAT NEED TO BE RELOCATED IN ORDER TO ACCOMMODATE NEW
CONSTRUCTION/REMODEL MUST BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER PRIOR TO
ROUGH-IN FOR RESOLUTION AND FURTHER DIRECTION.
25. WHERE THE PREMISES WIRING SYSTEM HAS BRANCH CIRCUITS SUPPLIED FROM MORE THAN ONE NOMINAL VOLTAGE, EACH UNGROUNDED CONDUCTOR OF A BRANCH CIRCUIT SHALL BE IDENTIFIED BY PHASE OR LINE AND BY SYSTEM VOLTAGE CLASS AT ALL TERMINATION, CONNECTION, AND SPLICE POINTS. IDENTIFICATION MEANS
SHALL BE POSTED AT EACH BRANCH CIRCUIT PANELBOARD.
ALL CONDUCTORS SHALL BE COLOR-CODED AS FOLLOWS:
PHASE 208/120 480/277
PHASE A BLACK BROWN
PHASE B RED ORANGE
PHASE C BLUE YELLOW
NEUTRAL WHITE WHITE
GROUND GREEN GREEN
REMODEL NOTES:
26. THE EC SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE EXISTING POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED. VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BRANCH
CIRCUIT BREAKERS AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.
27. THE EC SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELECOM ROOM FROM WHICH NEW TELE/DATA OUTLETS WILL BE FED. VERIFY EXISTING PATCH PANEL SPACES AND PROVIDE NEW PATCH PANELS AS
NECESSARY TO LAND/TERMINATE NEW TELECOM CABLING.
28. THE EC SHALL MAINTAIN ELECTRICAL CONTINUITY TO REMAINING EQUIPMENT WHEN ANY EXISTING ELECTRICAL
EQUIPMENT IS REMOVED.
29. ALL DEVICES NOT SHOWN ON PLANS ARE EXISTING TO REMAIN IN PLACE AND FUNCTIONAL. IN THE EVENT THAT WIRING TO AN EXISTING DEVICE IS DAMAGED, WIRING MUST BE REPLACED AND DEVICE BROUGHT BACK TO FULL
OPERATION.
LIGHTING NOTES:
30. ALL BATTERY POWERED OR CONTINUOUS BURN LUMINAIRES SHOWN ON THE PLANS, SUCH AS EXIT LIGHTS, NIGHT LIGHTS, OR EMERGENCY LIGHTS, SHALL BE CONNECTED TO THE UN-SWITCHED LEG OF THE LIGHTING CIRCUIT
FEEDING THAT AREA.
31. LUMINAIRES INSTALLED IN THE MECHANICAL ROOM SHALL BE PLACED SO THAT ALL EQUIPMENT IS ADEQUATELY
ILLUMINATED AFTER THE MECHANICAL EQUIPMENT IS IN PLACE.
32. ALL LUMINAIRES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND NOT THE CEILING GRID OR OTHER
NONSTRUCTURAL MEMBERS.
33. TO MAINTAIN CONSISTENT LIGHT QUALITY, FOR ANY ONE LAMP TYPE SUPPLIED, LAMPS SHALL BE OF THE SAME MANUFACTURER, SURFACE TEMPERATURE, COLOR RENDERING INDEX, LAMP EFFICACY, LUMEN OUTPUT, AND
STARTING CHARACTERISTICS FOR ALL INSTALLED.
34. LIGHT FIXTURES INSTALLED IN DAMP OR WET LOCATIONS SHALL BE UL LISTED FOR INSTALLATION IN THE PROPER ENVIRONMENT. CARE SHOULD BE TAKEN TO ENSURE THAT DIFFUSERS AND LENSES ARE APPROPRIATE FOR THEIR INSTALLED USE AND PREMATURE DISCOLORATION WILL NOT RESULT DUE TO EXPOSURE TO UV LIGHT, CHEMICALS, OR OTHER CONDITIONS.
35. ELECTRICAL CONTRACTOR SHALL PROVIDE LIGHTING CONTROL SHOP DRAWINGS WITH ELECTRICAL SUBMITTAL
FOR REVIEW.
POWER NOTES:
36. ALL PANELBOARDS AND SWITCHBOARDS SHALL BE PERMANENTLY MARKED TO INDICATE EACH DEVICE OR
EQUIPMENT WHERE THEIR POWER ORIGINATES AS PER NEC 408.4B.
37. ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS OR CABINETS AND SHALL MOVE THE PANELS IF REJECTED BY AN INSPECTOR. IF CLEARANCE
IS NOT POSSIBLE, THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.
38. WIRING DEVICES SHALL HAVE A NYLON COVER PLATE. COLOR SHALL BE COORDINATED WITH ARCHITECT.
EXTERIOR OUTLETS SHALL HAVE CAST COVERS WITH FLIP TYPE LIDS UNO.
39. EC SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS PRIOR TO ROUGH-IN. THE EC SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE EQUIPMENT SUPPLIER. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE EC WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE EC'S EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE OF EQUIPMENT AND ADDITIONAL
COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.
40. EC SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS. REFER TO MECHANICAL DRAWINGS FOR THE
LOCATION OF THERMOSTATS.
41. EC SHALL PROVIDE A 20AMP, 120VAC RECEPTACLE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT PER NEC 210.63. RECEPTACLE SHALL BE OF THE GROUND FAULT CIRCUIT INTERRUPTING TYPE, INSTALLED WITHIN A CAST METAL BOX, AND WITHIN 25' OF ALL
REQUIRED EQUIPMENT.
DATA/TELECOM NOTES:
42. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ROUGH-IN ONLY FOR THE TELECOM/CAT6 SYSTEMS. THIS SHALL CONSIST OF A FOUR SQUARE DEVICE MOUNTING BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING SPACE OR TO THE CEILING SPACE ABOVE IF OPEN. CABLING, JACKS, FACEPLATES, TESTING AND TERMINATIONS SHALL BE
PROVIDED AND INSTALLED BY OTHERS.
ROOF NOTES:
43. ELECTRICAL CONTRACTOR TO INSTALL A ROOF JACK (BOOT) FOR ALL CONDUIT PENETRATIONS THROUGH THE ROOF. ALL ROOF PENETRATION SEALS SHALL BE IN ACCORDANCE WITH THE ROOF WARRANTY AND BE COMPLETELY SEALED WITH ROOF ADHESIVE. UTILIZE PROPER CLAMPING METHODS TO SEAL BOOT AROUND
CONDUIT.
ELECTRICAL GENERAL NOTES
ELECTRICAL
GENERAL SHEET
ELECTRICAL SHEET INDEX
E000 ELECTRICAL GENERAL SHEET
E101 LIGHTING PLAN
E201 POWER PLAN
E601 ELECTRICAL SCHEDULES
J JUNCTION BOX SURFACE
WALL JUNCTION BOX 18" UNO
FLOOR JUNCTION BOX FLOOR
DISCONNECT SWITCH - NON-FUSED 60" UNO 4
DISCONNECT SWITCH - FUSED 4
COMBINATION MAGNETIC STARTER / DISCONNECT
MOTOR STARTER
CONTACTOR
MOTOR SURFACE
METER - PLAN VIEW
PUSH BUTTON SWITCH 48" TO TOP
EMERGENCY POWER SHUTOFF SWITCH
PANELBOARD - SURFACE MOUNTED 78" TO TOP
PANELBOARD - RECESSED 78" TO TOP
TRANSFORMER - PLAN VIEW
TELEPHONE TERMINAL BOARD
J
J
F
WALL
WALL
PAD/FLOOR
DISCONNECT SWITCH - SHUNT TRIP 4
60" UNO
60" UNO
60" UNO
60" UNO
60" UNO
48" TO TOP
CIRCUIT BREAKER
MCB PANEL - ONE-LINE
MLO PANEL - ONE-LINE
CURRENT TRANSFORMER
CT ENCLOSURE - ONE-LINE
TRANSFORMER - ONE-LINE
PAD MOUNT XFMR - ONE-LINE
METER - ONE-LINE
FUSED SWITCH
GROUND
OH RISER CABLE/WIRE SIZE TAG
M
XXX
AUTOMATIC TRANSFER SWITCH GROUND SLEEVE - ONE-LINE
FUSED DISCONNECT - ONE-LINE
XXXA
XXXA
XP
XX
X X
KEYED NOTE TAG
MECH/ELEC. EQUIPMENT TAG
OTHER EQUIPMENT TAG
X
ABBREVIATIONS
AFCI - ARC FAULT CKT INTERRUPTER
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
AIC - AMPS INTERRUPTING CAPACITY
AL - ALUMINUM
ATS - AUTOMATIC TRANSFER SWITCH
BC - BARE COPPER
BFC - BELOW FINISHED CEILING
BFG - BELOW FINISHED GRADE
CKT - CIRCUIT
CND. OR C. - CONDUIT
CLG - INSTALLED IN CEILING
C.R. - CORD REEL
CT - CURRENT TRANSDUCER
CU - COPPER
(E) - EXISTING TO REMAIN
EC - ELECTRICAL CONTRACTOR
EM - EMERGENCY
(F) - FUTURE
FACP - FIRE ALARM CONTROL PANEL
FLA - FULL LOAD AMPS
FVNR - FULL VOLTAGE NON REVERSING
GC - GENERAL CONTRACTOR
GFCI - GROUND FAULT CKT INTERRUPTER
GND - GROUND
HP - HORSEPOWER
IG - ISOLATED GROUND
KW - KILOWATTS
LCP - LIGHTING CONTROL PANEL
LTG - LIGHTING
LV - LOW VOLTAGE
MC - MECHANICAL CONTRACTOR
MCA - MINIMUM CIRCUIT AMPS
MCB - MAIN CIRCUIT BREAKER
MCC - MOTOR CONTROL CENTER
MDP - MAIN DISTRIBUTION PANEL
MLO - MAIN LUGS ONLY
MOCP - MAX. OVERCURRENT PROTECTION
(N) - NEW
NIC - NOT IN CONTRACT
NEC - NATIONAL ELECTRICAL CODE
NFPA - NATIONAL FIRE PROT. ASSN.
NL - NIGHT LIGHT
NR - NOT REQUIRED
NTS - NOT TO SCALE
PC - PLUMBING CONTRACTOR
PH - PHASE
PNL - PANEL
POC - POINT OF CONNECTION
POS - POINT OF SALE
(R) - RELOCATED
REC - RECEPTACLES
RMC - RIGID METAL CONDUIT
SCBA - SELECT COLOR BY ARCHITECT
SCA - SHORT CIRCUIT AMPERES
SES - SERVICE ENTRANCE SWITCHGEAR
SPD - SURGE PROTECTIVE DEVICE
TL - TWIST LOCK
TTB - TELEPHONE TERMINAL BOARD
TR - TAMPER RESISTANT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VA - VOLT/AMPS
VIF - VERIFY IN FIELD
VR - VANDAL RESISTANT
WP - WEATHERPROOF
WU - FURNISHED WITH UNIT
XFMR - TRANSFORMER
NOTES
WIRING / CONDUIT UNDERGROUND/FLOOR WIRING
CONDUIT TURNED UP CONDUIT TURNED DOWN
CIRCUIT HOME RUN TO PANEL: # OF ARROWHEADS INDICATE # OF CIRCUITS
(SEPARATE NEUTRAL PER CIRCUIT). BOTH EX. INCLUDE AN EQUIP. GROUND.
1. SEE LIGHT FIXTURE SCHEDULE FOR TYPE, MOUNTING, AND OTHER SPECIFICS.
2. CONNECT EMERGENCY AND/OR EXIT LIGHTS TO THE UNSWITCHED SIDE OF THE AREA
LIGHTING BRANCH CIRCUIT.
3. ARROW DENOTES EXIT DIRECTION.
4. USE HEAVY DUTY FOR 480 VOLT.
5. PROVIDE RACEWAY WITH OUTLETS 12" ON CENTER UNO.
6. MOUNT SWITCH AT DOOR JAM PER MANUFACTURER'S INSTRUCTIONS.
7. PROVIDE UL LISTED DEVICE TO BE USED WITH THE FIRE ALARM PANEL/SYSTEM OR
PROVIDE A MONITOR MODULE TO CONNECT INTO FIRE ALARM SYSTEM.
X
EXXX
DETAIL/VIEW REFERENCE TAG
DETAIL/VIEW NUMBER
SHEET NUMBER
STEP LIGHT FIXTURE WALL 1
LIGHT BOLLARD SURFACE 1
TIMER SWITCH - 30 MINUTEST
GROUND MOUNTED / IN-GRADE LIGHT FIXTURE GROUND 1
PILOT LIGHT SWITCHSP
LIGHT FIXTURE - SURFACE OR RECESSED SEE DRAWINGS 1
EMERGENCY LIGHT FIXTURE - SURFACE OR RECESSED SEE DRAWINGS 1, 2
EMERGENCY LIGHT FIXTURE - OPEN STRIP
LIGHT FIXTURE - CEILING MOUNTED CEILING 1
LIGHT FIXTURE - PENDANT / CHANDELIER CEILING 1
LIGHT FIXTURE - DOWNLIGHT CEILING 1
LIGHT FIXTURE - WALL WASH DOWNLIGHT CEILING 1
LIGHT FIXTURE - WALL MOUNTED WALL 1
LIGHT FIXTURE - WALL BRACKET WALL 1
TRACK LIGHTING SURFACE 1
EXIT SIGN - WALL MOUNT WALL
EXIT SIGN - CEILING MOUNT CEILING
EXIT SIGN W/ EMERGENCY HEADS - WALL MOUNT WALL
EXIT SIGN W/ EMERGENCY HEADS - CEILING MOUNT CEILING
DUAL HEAD EMERGENCY LIGHT FIXTURE WALL 1, 2
POLE LIGHT FIXTURE POLE 1
PHOTO-ELECTRIC CELL WITH RELAY SURFACE 1
OCCUPANCY / VACANCY SENSOR - CEILING MOUNT CEILING 1
CURRENT LIMITING DEVICE SURFACE 1
TIME CLOCK - 7 DAY 60"
WALL OCCUPANCY / VACANCY SENSOR SWITCH 48" TO TOP
SINGLE POLE SWITCH
THREE WAY SWITCH
FOUR WAY SWITCH
DIMMER SWITCH
LOW VOLTAGE SWITCH
EM
PC
CL
TC
SOS
S S3 S4
SD
SLV
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
LIGHT FIXTURE - OPEN STRIP 1
1, 2
SEE DRAWINGS
SEE DRAWINGS
EMERGENCY LIGHT FIXTURE - WALL MOUNTED WALL 1, 2
EMERGENCY LIGHT FIXTURE - WALL BRACKET WALL 1, 2
EMERGENCY LIGHT FIXTURE - DOWNLIGHT CEILING 1, 2
48" TO TOP
48" TO TOP
48" TO TOP
48" TO TOP
48" TO TOP
48" TO TOP
48" TO TOP
SINGLE POLE KEYED SWITCH
MULTI-OUTLET METAL SURFACE RACEWAY 44" UNO 5
SK
SINGLE/SIMPLEX OUTLET, 20A, 120VAC
THERMAL OVERLOAD SWITCH
DUPLEX OUTLET, 20A, 120VAC 18" UNO
DUPLEX OUTLET, 20A, 120VAC - GFCI
DUPLEX OUTLET - SPLIT WIRED
DUPLEX OUTLET - ISOLATED GROUND
DUPLEX OUTLET WITH USB-A & USB-C PORTS
DUPLEX OUTLET - OCCUPANCY SENSOR CONTROLLED
DUPLEX OUTLET, 20A, 120VAC - CEILING CEILING
DUPLEX OUTLET, 20A, 120VAC - FLOOR FLOOR
FOURPLEX OUTLET, 20A, 120VAC
FOURPLEX OUTLET, 20A, 120VAC - GFCI
FOURPLEX OUTLET - ISOLATED GROUND
FOURPLEX OUTLET, 20A, 120VAC - CEILING CEILING
FOURPLEX OUTLET, 20A, 120VAC - FLOOR FLOOR
APPLIANCE OUTLET - 208/240V SINGLE PHASE
APPLIANCE OUTLET - 208/480V 3-PHASE
TELEPHONE OUTLET
DATA OUTLET
DUAL TELEPHONE/DATA OUTLET
CABLE TELEVISION OUTLET
DUAL TELEPHONE/DATA OUTLET - FLOOR FLOOR
STH
OS
CEILING DATA OUTLET/ WIRELESS ACCESS POINT CEILING
DATA OUTLET - FLOOR FLOOR
2-POLE SWITCHS2
48" TO TOP
48" TO TOP
48" TO TOP
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
18" UNO
ELECTRICAL SYMBOL SCHEDULE
SYMBOL DESCRIPTION MOUNTING NOTES
EL
EC
TR
IC
AL
G
EN
ER
AL
SH
EE
T
FIRE ALARM HORN 7' - 6"
FIRE ALARM STROBE 7' - 6"
FIRE ALARM HORN STROBE 7' - 6"
WATERFLOW GONG 7' - 6"
FIRE ALARM DUAL ACTION MANUAL PULL STATION 4' - 0"
FIRE ALARM ADDRESSABLE CONTROL RELAY
FIRE ALARM MONITOR MODULE
FIRE ALARM CONTROL PANEL 6' - 6" TO TOP
FIRE ALARM ANNUNCIATOR PANEL 4' - 0"
PHOTOELECTRIC SMOKE DETECTOR
RATE OF RISE/HEAT DETECTOR
CARBON MONOXIDE DETECTOR
DUCT SMOKE DETECTOR 6
FIRE SMOKE DAMPER
FIRE RISER TAMPER SWITCH
FIRE RISER FLOW SWITCH
ELECTROMAGNETIC DOOR HOLDER 2' - 0"
CO
AR
F
MM
F
T
SURFACE
SURFACE
SURFACE
DUCT
REF.REF.
DL
S D S D
S D
S D
S O S
S O S
S 3
EM
EMX
1 1
EX
EX
EM
M-10
DL
DL DL
DL DL
DL DL
DL DL
DL DL
S 3 a a a a
EXISTING
PANEL 'M'
EXISTING
SUB PANEL
'S'
M-12 S 3
S3
HBHBHB
HB HB
HB
HB
HBHB
EM
EM
EM
EM
EM
EM EX
DL DLDL
DL
DL
DL
DL
DL
DLDL
S3
S3 b b b b b b b b b
DLDL
3 3
S O S3
DL
DLDL
DLDL
a a
DLDLDLDL
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
alt ar ch ite ct ur e
1445 w. 8660 s.
west jordan, utah 84088 www.altarchitecture-ut.com
ANDY TONGISH 801-865-0633
TIT
LE
PR
O
JE
C
T
C
LIE
NT
AD
DR
ES
S
NO. DATE DESCRIPTION
SHEET
REVISIONS
6/
/2
2:
:0
PM
E101
CONSULTING ENGINEERS, INC.
2332 West 12600 South, Suite F | Riverton, UT 84065
(801) 566-0503 www.rmceut.com Project #
ROCKY MOUNTAIN
25042
BT / TG
BK
2/20/2025
1 04/10/26 SMOKE DETECTOR
25-001
W
AN
SH
IP
FI
RE
ST
AT
IO
N
NO
RT
H
SU
M M
IT
FIR
E
DE
PA
RT
M
EN
T
SO
UT
H
HO
YT
SV
ILL
E
RO
AD
C O
AL
VI
LL
E, U
TA
H
RE
G
IS
TE
RE
D PROFESS I ONAL ENG
I NEER
STATE OF UTAH
No. 7945859-2202
DAVID W.
STEWARD
2 07/29/26 ADD3
E101
1 LIGHTING PLAN
SCALE: 1/4" = 1'-0"
N
GENERAL NOTES
KEYED NOTES#
A. CONNECT ALL EMERGENCY AND EXIT LIGHT FIXTURES TO
THE UNSWITCHED SIDE OF THE LIGHTING BRANCH CIRCUIT.
LIGHT FIXTURES WITH EMERGENCY DRIVERS SHALL BE
NORMALLY SWITCHED WITH THE AREA LIGHTING, BUT HAVE
THEIR EMERGENCY DRIVERS CONNECTED AHEAD OF THE
LIGHT SWITCH OR LIGHTING CONTROL PANEL RELAY.
FIXTURES WILL REMAIN ON FOR NOT LESS THAN 90 MINUTES
IN CASE OF POWER LOSS.
B. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS THAT
CONDUIT IS TO BE INSTALLED WITHIN WALLS AND ABOVE
CEILINGS CONCEALED WHERE POSSIBLE.
C. COORDINATE MOUNTING HEIGHTS OF ALL PENDANT AND
WALL MOUNTED LIGHT FIXTURES WITH ARCHITECTURAL
ELEVATIONS.
D. VERIFY FIXTURE DIMMING CONTROLS AND PROVIDE
NECESSARY WIRING AND DEVICES REQUIRED FOR DIMMING
OPERATION.
E. CONCEAL ALL FIXTURE DRIVERS IN ACCESSIBLE CEILING
SPACE OUT OF DIRECT VIEW.
F. FOR OPEN CEILING AREAS WITH OCCUPANCY CONTROLS EC
IS TO INSTALL OCCUPANCY SENSORS AT A LEVEL EQUAL TO
OR LOWER THAN AREA DUCT WORK TO ENSURE OCCUPANCY
SENSOR COVERAGE.
1. PROVIDE A WALL MOUNT DUAL TECH TWO POLE OCC.
SENSOR FOR RESTROOM LIGHT AND FAN CONTROL.
(SENSOR SWITCH #WSX PDT 2P OR EQUIVALENT).
2. EXTERIOR EGRESS LIGHTING TO REMAIN.
3. PROVIDE VACANCY SENSORS FOR AUTO OFF FUNCTION
ONLY. GROUP ROOM, BEDROOM, AND KITCHEN LIGHTS
SHOULD NOT COME ON WITH MOTION.
LTG CTRL SEQUENCE OF OPERATION
LIGHTING AND CONTROLS ARE DESIGNED TO MEET IECC 2021.
OCCUPANCY SENSORS WILL CONTROL LIGHTING IN RESTROOMS
AND GROUP ROOM.
DAYLIGHT ZONES EXEMPT FROM AUTOMATIC CONTROL
REQUIREMENTS PER IECC 2021 405.2.4 (1) (LESS THAN 150W
KITCHEN AUTOMATIC LIGHTING CONTROLS NOT REQUIRED PER
(C405.2.2 - EXCEPTION 3 (SPACES WHERE AUTOMATIC
SHUTOFF WOULD ENDANGER OCCUPANT SAFETY).
LIGHTING PLAN
LIG
HT
IN
G
P
LA
N
REF.REF.
TYP.
DS
DS
DS
HP
F WP
J 3
EXISTING
PANEL 'M'
EXISTING
SUB PANEL
'S'
TO HP-1
TO HP-1
TO HP-1
S-8
M-41
M-39
S-5,7
J 3
J 3
48"
DOOR
M-22
DOOR
M-20
DOOR
M-18
M-35
M-4
5 5
APPLIANCE
CONTROLLER
DEVICE
ALERT
END
POINT
PM UPS
M-6
M-15
APPLIANCE
RESET
BUTTON
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
alt ar ch ite ct ur e
1445 w. 8660 s.
west jordan, utah 84088 www.altarchitecture-ut.com
ANDY TONGISH 801-865-0633
TIT
LE
PR
O
JE
C
T
C
LIE
NT
AD
DR
ES
S
NO. DATE DESCRIPTION
SHEET
REVISIONS
6/
/2
2:
:0
PM
E201
CONSULTING ENGINEERS, INC.
2332 West 12600 South, Suite F | Riverton, UT 84065
(801) 566-0503 www.rmceut.com Project #
ROCKY MOUNTAIN
25042
BT / TG
BK
2/20/2025
1 04/10/26 SMOKE DETECTOR
25-001
W
AN
SH
IP
FI
RE
ST
AT
IO
N
NO
RT
H
SU
M M
IT
FIR
E
DE
PA
RT
M
EN
T
SO
UT
H
HO
YT
SV
ILL
E
RO
AD
C O
AL
VI
LL
E, U
TA
H
RE
G
IS
TE
RE
D PROFESS I ONAL ENG
I NEER
STATE OF UTAH
No. 7945859-2202
DAVID W.
STEWARD
2 07/29/26 ADD3
POWER PLAN
E201
1 POWER PLAN
SCALE: 1/4" = 1'-0"
N
PO
W
ER
P
LA
N
GENERAL NOTES
KEYED NOTES
1. PROVIDE COMBINATION SMOKE/CO DETECTORS IN
SLEEPING AREAS.
2. CONNECT TO AREA LIGHTING CIRCUIT.
3. PROVIDE 24 VDC CONNECTION TO FIRST-IN DORM REMOTE.
COORDINATE WITH EQUIPMENT SUPPLIER FOR EXACT
REQUIREMENTS.
4. PROVIDE ALL NECESSARY CONDUIT AND WIRING FOR THE
GARAGE DOOR PUSHBUTTON CONTROL SWITCH AND
RED/GREEN STOP LIGHTS. COORDINATE GARAGE DOOR
INSTALLATION REQUIREMENTS WITH THE GARAGE DOOR
INSTALLER.
5. PROVIDE 2" DATA CONDUIT FOR 2 ANTENNAS FROM UNDER
THE EVE ON THE NORTH END OF THE BUILDING TO THE
FURNACE ROOM.
A. PROVIDE TAMPER RESISTANT OUTLETS IN ALL ROOMS IN
SCOPE OF WORK.
B. ITEMS SHOWN LIGHT ARE EXISTING TO REMAIN.
C. SMOKE/CO DETECTORS IN SLEEPING AREAS SHALL HAVE
LOW FREQUENCY SOUNDER BASES.
D. PROVIDE RACEWAY AND BOXES FOR WESTNET ALERT
SYSTEM PER WESTNET PLANS.
E. PROVIDE NEW GFCI BREAKERS TO PROTECT CIRCUITS AS
INDICATED IN PANEL SCHEDULE M.
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
alt ar ch ite ct ur e
1445 w. 8660 s.
west jordan, utah 84088 www.altarchitecture-ut.com
ANDY TONGISH 801-865-0633
TIT
LE
PR
O
JE
C
T
C
LIE
NT
AD
DR
ES
S
NO. DATE DESCRIPTION
SHEET
REVISIONS
6/
/2
2:
:0
PM
E601
CONSULTING ENGINEERS, INC.
2332 West 12600 South, Suite F | Riverton, UT 84065
(801) 566-0503 www.rmceut.com Project #
ROCKY MOUNTAIN
25042
BT / TG
BK
2/20/2025
1 04/10/26 SMOKE DETECTOR
25-001
W
AN
SH
IP
FI
RE
ST
AT
IO
N
NO
RT
H
SU
M M
IT
FIR
E
DE
PA
RT
M
EN
T
SO
UT
H
HO
YT
SV
ILL
E
RO
AD
C O
AL
VI
LL
E, U
TA
H
RE
G
IS
TE
RE
D PROFESS I ONAL ENG
I NEER
STATE OF UTAH
No. 7945859-2202
DAVID W.
STEWARD
2 07/29/26 ADD3
ELECTRICAL
SCHEDULES
EL
EC
TR
IC
AL
SC
HE
DU
LE
S
KEYED NOTES
1. PANEL SCHEDULES SHOW NEW LOADS ONLY. HIGHEST
DEMAND FROM LAST 12 MONTHS OF UTILITY BILLS WAS
13.876kW. PER NEC 220.87 LOAD IS TO BE 125% OF EXISTING
DEMAND PLUS THE NEW LOADS. NEW TOTAL LOAD IS
27,254VA OR 113.6A.
| Sheets and Views |
| 1 25042 - E000 - General Sheet - E000 |
| 2 25042 - E101 - Lighting - E101 |
| 3 25042 - E201 - Power - E201 |
| 5 25042 - E601 - Schedules - E601 |