8-25042 - Wanship Fire Station 23 - ADD3.pdf

PDF 2 MB Posted

Attached to
GJ27-18 North Summit Fire District Fire Station 23 Dorm Addition and Interior Remodel
Solicitation number
GJ27-18
Issued by
Summit County, Utah

About this file

Electrical General Addendum 3 for Wanship Fire Station 23 Dorm Addition and Interior Remodel

This is an Addendum 3 electrical design document for the North Summit Fire District's Wanship Fire Station 23 dorm addition and interior remodel project located at 2000 South Hoytsille Road, Coalville, Utah 84017. The project involves electrical system installation for a fire station renovation and requires the electrical contractor to provide complete and operable electrical systems in strict accordance with local, state, and national codes. The scope includes lighting design, power distribution, fire alarm integration, data/telecom infrastructure, roof penetration seals, and coordination with mechanical and architectural trades. The electrical system must be tested and confirmed for proper operation prior to project closeout. The mandatory pre-proposal site visit is scheduled for August 27, 2026, with questions due by September 2, 2026 at 2:00 p.m. MT, and proposals due by September 4, 2026 at noon MT. The document includes detailed electrical general notes, lighting control sequences compliant with IECC 2021, and power distribution specifications indicating a new total electrical load of 27,254 VA or 113.6 amperes at 125 percent of existing demand plus new loads.

The electrical design incorporates copper THHN/THWN-2 conductors rated at 600 volts, EMT conduit in interior dry locations, PVC conduit underground with GRC elbows, and equipment listed by nationally recognized testing agencies. Specifications require all conduit to be supported by industry-standard methods, with flexible conduit limited to fixture and equipment connections not exceeding 72 inches. The contractor must coordinate with equipment suppliers, mechanical contractors, and the architect regarding device placement, thermostats, HVAC service receptacles, and emergency lighting connections to unswitched circuit legs. All penetrations through fire-rated assemblies require fire-stopping materials, and roof penetrations must include boots sealed per roof warranty specifications. The electrical contractor is responsible for maintaining continuity to existing equipment during any removals and replacing any damaged wiring to existing devices while bringing them back to full operational status.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT #:

DRAWN BY:

CHECKED BY:

ISSUED:

alt ar ch ite ct ur e

1445 w. 8660 s.

west jordan, utah 84088 www.altarchitecture-ut.com

ANDY TONGISH 801-865-0633

TIT

LE

PR

O

JE

C

T

C

LIE

NT

AD

DR

ES

S

NO. DATE DESCRIPTION

SHEET

REVISIONS

6/

/2

2:

:0

PM

E000

CONSULTING ENGINEERS, INC.

2332 West 12600 South, Suite F | Riverton, UT 84065

(801) 566-0503 www.rmceut.com Project #

ROCKY MOUNTAIN

25042

BT / TG

BK

2/20/2025

1 04/10/26 SMOKE DETECTOR

25-001

W

AN

SH

IP

FI

RE

ST

AT

IO

N

NO

RT

H

SU

M M

IT

FIR

E

DE

PA

RT

M

EN

T

SO

UT

H

HO

YT

SV

ILL

E

RO

AD

C O

AL

VI

LL

E, U

TA

H

RE

G

IS

TE

RE

D PROFESS I ONAL ENG

I NEER

STATE OF UTAH

No. 7945859-2202

DAVID W.

STEWARD

2 07/29/26 ADD3

GENERAL NOTES:

1. THE ELECTRICAL SYSTEMS DEFINED BY THESE PLANS AND THE SPECIFICATIONS ARE TO BE CONSTRUCTED AS COMPLETE AND OPERABLE SYSTEMS AND SHALL BE BID WITH THIS INTENT. THE CONTRACTOR SHALL VISIT THE SITE, READ ALL THE RELEVANT DOCUMENTS, AND BECOME FAMILIAR WITH THE TYPE OF CONSTRUCTION AND WORK TO BE ACCOMPLISHED. SHOULD ANY ERROR, OMISSION, OR CONFLICT EXIST IN EITHER THE PLANS OR SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING BEFORE SUBMITTING THEIR BID PRICE SO A CHANGE CAN BE ISSUED IN A PRE-BID ADDENDUM. OTHERWISE, THE CONTRACTOR AND/OR EQUIPMENT SUPPLIERS SHALL SUPPLY THE PROPER MATERIALS AND LABOR TO INSTALL COMPLETE AND OPERABLE SYSTEMS INCLUSIVE OF THE ORIGINAL BID. WHEN EACH ELECTRICAL SYSTEM IS COMPLETE, THE CONTRACTOR SHALL TEST AND CONFIRM ITS PROPER OPERATION. ANY INCOMPLETE SYSTEM SHALL BE MADE

COMPLETE AND OPERABLE PRIOR TO PROJECT CLOSEOUT.

2. THE ARCHITECTURAL AND MECHANICAL PLANS ARE CONSIDERED A PART OF THE ELECTRICAL DOCUMENTS SO FAR AS ANY ELECTRICAL ITEMS THEY MAY CONTAIN. THE ELECTRICAL CONTRACTOR SHALL REFER TO AND COORDINATE WITH THEM. NO EXTRA COST SHALL BE ALLOWED FOR FAILURE TO COORDINATE THE CONTRACT DOCUMENTS WITH OTHER TRADES AND/OR IF EQUIPMENT DIMENSIONS ARE GREATER THAN SPECIFIED AND/OR

DIMENSIONED ON THE PLANS.

3. THE ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT, MATERIALS, AND LABOR FOR THE CONNECTIONS OF

ALL EQUIPMENT SHOWN ON THE PLANS - ARCHITECTURAL, MECHANICAL, ETC.

4. THIS PROJECT IS TO BE INSTALLED IN STRICT ACCORDANCE WITH THE MOST RECENT LOCAL, STATE, AND NATIONAL CODES. IF AT ANY TIME DURING OR AFTER CONSTRUCTION SOMETHING IS FOUND TO BE INSTALLED IN

VIOLATION OF THESE CODES LISTED ABOVE, IT SHALL BE CORRECTED BY THE CONTRACTOR.

5. WHERE A RACEWAY ENTERS A BUILDING OR STRUCTURE FROM THE OUTSIDE, IT SHALL BE SEALED AS PER NEC 225.27.

6. ALL ELECTRICAL EQUIPMENT THAT IS LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING OR MAINTENANCE WHILE ENERGIZED SHALL BE FIELD OR FACTORY LABELED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS PER NEC 110.16. THE LABEL SHALL ALSO CONTAIN THE MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE THE FAULT CURRENT CALCULATIONS WERE PERFORMED AS PER NEC 110.24.

7. EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS PURPOSE AND TO IDENTIFY THE

CIRCUIT SOURCE THAT SUPPLIES THE DISCONNECTING MEANS PER NEC 110.22.

8. ALL EQUIPMENT PROVIDED BY THE EC SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, AND BE PROPERLY INSTALLED FOR THE

CONDITIONS AND SPACE THAT EQUIPMENT IS BEING INSTALLED WITHIN.

9. THE EC SHALL INSTALL A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT RUN. CONDUIT SHALL NOT BE USED AS AN EQUIPMENT GROUNDING CONDUCTOR. THE EC SHALL GROUND THE ELECTRICAL

SYSTEM IN ACCORDANCE WITH LOCAL AND NATIONAL CODES.

10. CONDUIT LAYOUTS SHOWN ON THE PLANS ARE DIAGRAMMATIC, NOT INDICATING THE ROUTING REQUIRED. THE EC SHALL ROUTE THE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION AND SHALL COORDINATE WITH DUCTWORK, PIPING, EQUIPMENT, BUILDING STRUCTURE, AND OTHER POTENTIAL OBSTRUCTIONS.

11. THE CONTRACTOR SHALL ALLOW THE MOVEMENT, BEFORE ROUGH-IN, OF ANY ELECTRICAL PANEL, DEVICE, LUMINAIRE, ETC. A DISTANCE OF 10 FEET WITHOUT REQUIRING ADDITIONAL COST TO THE PROJECT.

12. THE EC SHALL SECURE ALL CONDUIT TO THE STRUCTURE AS IT IS SET IN PLACE USING INDUSTRY STANDARD METHODS AND PRACTICES. TO ASSURE ALL DEVICES ARE RIGIDLY SET, THE ELECTRICAL CONTRACTOR SHALL SECURE ALL DEVICE BOXES WITH BRACKETS, HANGERS, ETC. DESIGNED FOR THE APPLICATION.

13. MINIMUM SIZE CONDUIT SHALL BE 3/4" UNO. CONDUIT INSTALLED WITHIN THE BUILDING IN DRY LOCATIONS WITHIN WALL, CEILINGS, OR EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE SHALL BE EMT WITH STEEL SET SCREW FITTINGS. IN EXTERIOR LOCATIONS (EXCEPT FOR THE SERVICE ENTRANCE) THE CONDUIT SHALL BE EMT WITH COMPRESSION GLAND TYPE FITTINGS. UNDERGROUND CONDUIT SHALL BE PVC (SCH. 40) WITH GRC ELBOWS AND RISERS WRAPPED IN CORROSION RESISTANT MATERIALS WHERE IN DIRECT CONTACT WITH THE SOIL.

14. FLEXIBLE CONDUIT SHALL BE LIMITED TO CONNECTIONS TO LIGHT FIXTURES AND FINAL CONNECTIONS TO MOTORS OR OTHER EQUIPMENT SUBJECT TO VIBRATION. LENGTHS OF FLEXIBLE OR SEAL-TITE CONDUIT SHALL NOT BE

GREATER THAN 72 INCHES.

15. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL EMPTY CONDUITS WITH 200LB RATED NYLON PULL CORD.

16. BEFORE ANY ELECTRICAL CONDUIT, BOXES, ETC. ARE COVERED (FLOOR, CEILINGS, WALLS, ETC.), THEY SHALL BE

APPROVED BY THE INSPECTING OFFICER (INSPECTOR).

17. WHERE WIRE SIZE IS NOT SHOWN ON THE DRAWINGS FOR 20A, 120VAC BRANCH CIRCUITS, THE CIRCUIT SHALL CONSIST OF 2#12 (CU,THHN) + 1#12 (CU,THHN) GND IN 3/4" EMT CONDUIT. THIS WIRE SIZE SHALL BE INCREASED TO #10 (CU,THHN) FOR BRANCH CIRCUITS WITH OVERALL LENGTHS EXCEEDING 125' TO ACCOMMODATE FOR VOLTAGE DROP. REFER TO EQUIPMENT SCHEDULES, FEEDER SCHEDULES, AND NOTES ON DRAWINGS FOR ALL OTHER

BRANCH CIRCUIT AND FEEDER WIRE/CONDUIT SIZING.

18. CONDUCTORS SHALL BE COPPER, 600VAC RATED, TYPE THHN/THWN-2 UNO. CONDUCTORS UP TO #10AWG SHALL

BE SOLID AND CONDUCTORS #8AWG OR LARGER SHALL BE STRANDED.

19. METAL CLAD CABLING MAY BE USED BETWEEN DEVICES SUCH AS LIGHTING, RECEPTACLES, SWITCHES, ETC.

UNLESS OTHERWISE REQUIRED BY THE NEC. HOME RUNS SHALL BE INSTALLED IN CONDUIT. MC CABLE SHALL

NOT BE INSTALLED EXPOSED.

20. EC SHALL CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FINGER PRINTS, FOREIGN MATTER, PAINT, DIRT, GREASE, AND UN-NEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FROM THE PREMISES.

21. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS FOR ALL DEVICES TO BE FLUSH MOUNTED AND CONDUIT/CABLING INSTALLED CONCEALED WITHIN WALLS/CEILINGS. IN AREAS WHERE CONDUIT MUST BE INSTALLED EXPOSED IT SHALL BE COORDINATED WITH THE ARCHITECT AND/OR ENGINEER. ALL EFFORTS SHALL

BE MADE TO CONCEAL WIRING METHODS.

22. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND

CAULK, PUTTY, STRIP AND SHEET FORMS, DOW CORNING 3-6548 SILICONE RTV FOAM.

23. COORDINATE LOCATION OF WALL MOUNTED DEVICES WITH CABINETRY AND OTHER WALL OBSTRUCTIONS.

COORDINATE CEILING MOUNTED DEVICES WITH CEILING OBSTRUCTIONS. ANY DEVICES THAT NEED TO BE RELOCATED MUST BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER PRIOR TO ROUGH-IN FOR NEW

LOCATION.

24. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO COORDINATE PLACEMENT OF ALL DEVICES INSTALLED WITHIN THE CEILING SUCH AS LIGHTING, SPEAKERS, FIRE SPRINKLERS, SMOKE/HEAT DETECTORS, ETC.

ANY EXISTING DEVICES THAT NEED TO BE RELOCATED IN ORDER TO ACCOMMODATE NEW

CONSTRUCTION/REMODEL MUST BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER PRIOR TO

ROUGH-IN FOR RESOLUTION AND FURTHER DIRECTION.

25. WHERE THE PREMISES WIRING SYSTEM HAS BRANCH CIRCUITS SUPPLIED FROM MORE THAN ONE NOMINAL VOLTAGE, EACH UNGROUNDED CONDUCTOR OF A BRANCH CIRCUIT SHALL BE IDENTIFIED BY PHASE OR LINE AND BY SYSTEM VOLTAGE CLASS AT ALL TERMINATION, CONNECTION, AND SPLICE POINTS. IDENTIFICATION MEANS

SHALL BE POSTED AT EACH BRANCH CIRCUIT PANELBOARD.

ALL CONDUCTORS SHALL BE COLOR-CODED AS FOLLOWS:

PHASE 208/120 480/277

PHASE A BLACK BROWN

PHASE B RED ORANGE

PHASE C BLUE YELLOW

NEUTRAL WHITE WHITE

GROUND GREEN GREEN

REMODEL NOTES:

26. THE EC SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE EXISTING POWER PANELS FROM WHICH NEW CIRCUITS ARE BEING FED. VERIFY EXISTING BRANCH CIRCUIT BREAKERS AND PROVIDE NEW BRANCH

CIRCUIT BREAKERS AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.

27. THE EC SHALL COORDINATE AND CONFIRM THE EXACT LOCATION OF THE TELECOM ROOM FROM WHICH NEW TELE/DATA OUTLETS WILL BE FED. VERIFY EXISTING PATCH PANEL SPACES AND PROVIDE NEW PATCH PANELS AS

NECESSARY TO LAND/TERMINATE NEW TELECOM CABLING.

28. THE EC SHALL MAINTAIN ELECTRICAL CONTINUITY TO REMAINING EQUIPMENT WHEN ANY EXISTING ELECTRICAL

EQUIPMENT IS REMOVED.

29. ALL DEVICES NOT SHOWN ON PLANS ARE EXISTING TO REMAIN IN PLACE AND FUNCTIONAL. IN THE EVENT THAT WIRING TO AN EXISTING DEVICE IS DAMAGED, WIRING MUST BE REPLACED AND DEVICE BROUGHT BACK TO FULL

OPERATION.

LIGHTING NOTES:

30. ALL BATTERY POWERED OR CONTINUOUS BURN LUMINAIRES SHOWN ON THE PLANS, SUCH AS EXIT LIGHTS, NIGHT LIGHTS, OR EMERGENCY LIGHTS, SHALL BE CONNECTED TO THE UN-SWITCHED LEG OF THE LIGHTING CIRCUIT

FEEDING THAT AREA.

31. LUMINAIRES INSTALLED IN THE MECHANICAL ROOM SHALL BE PLACED SO THAT ALL EQUIPMENT IS ADEQUATELY

ILLUMINATED AFTER THE MECHANICAL EQUIPMENT IS IN PLACE.

32. ALL LUMINAIRES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND NOT THE CEILING GRID OR OTHER

NONSTRUCTURAL MEMBERS.

33. TO MAINTAIN CONSISTENT LIGHT QUALITY, FOR ANY ONE LAMP TYPE SUPPLIED, LAMPS SHALL BE OF THE SAME MANUFACTURER, SURFACE TEMPERATURE, COLOR RENDERING INDEX, LAMP EFFICACY, LUMEN OUTPUT, AND

STARTING CHARACTERISTICS FOR ALL INSTALLED.

34. LIGHT FIXTURES INSTALLED IN DAMP OR WET LOCATIONS SHALL BE UL LISTED FOR INSTALLATION IN THE PROPER ENVIRONMENT. CARE SHOULD BE TAKEN TO ENSURE THAT DIFFUSERS AND LENSES ARE APPROPRIATE FOR THEIR INSTALLED USE AND PREMATURE DISCOLORATION WILL NOT RESULT DUE TO EXPOSURE TO UV LIGHT, CHEMICALS, OR OTHER CONDITIONS.

35. ELECTRICAL CONTRACTOR SHALL PROVIDE LIGHTING CONTROL SHOP DRAWINGS WITH ELECTRICAL SUBMITTAL

FOR REVIEW.

POWER NOTES:

36. ALL PANELBOARDS AND SWITCHBOARDS SHALL BE PERMANENTLY MARKED TO INDICATE EACH DEVICE OR

EQUIPMENT WHERE THEIR POWER ORIGINATES AS PER NEC 408.4B.

37. ELECTRICAL CONTRACTOR SHALL CONFIRM MINIMUM CODE (NEC) WORKING CLEARANCE BEFORE INSTALLING ANY ELECTRICAL PANELS OR CABINETS AND SHALL MOVE THE PANELS IF REJECTED BY AN INSPECTOR. IF CLEARANCE

IS NOT POSSIBLE, THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY IN WRITING.

38. WIRING DEVICES SHALL HAVE A NYLON COVER PLATE. COLOR SHALL BE COORDINATED WITH ARCHITECT.

EXTERIOR OUTLETS SHALL HAVE CAST COVERS WITH FLIP TYPE LIDS UNO.

39. EC SHALL COORDINATE WITH EQUIPMENT SUPPLIERS ON THE EXACT LOCATIONS OF ALL EQUIPMENT AND ELECTRICAL CONNECTIONS PRIOR TO ROUGH-IN. THE EC SHALL MAKE THE FINAL CONNECTION TO ALL EQUIPMENT UNLESS OTHERWISE DIRECTED BY THE EQUIPMENT SUPPLIER. OBTAIN FROM SUPPLIERS ALL WIRING DIAGRAMS FOR EQUIPMENT PRIOR TO ANY ROUGH-IN. TO ASSURE THAT PROPER CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY THE EC WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT THE EC'S EXPENSE. PROVIDE COPIES OF WIRING DIAGRAMS WITHIN EACH PIECE OF EQUIPMENT AND ADDITIONAL

COPIES WITH THE OPERATION AND MAINTENANCE MANUALS.

40. EC SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR TO PROVIDE CONDUIT AND DEVICE MOUNTING BOXES FOR THERMOSTATS AND OTHER MECHANICAL CONTROLS. REFER TO MECHANICAL DRAWINGS FOR THE

LOCATION OF THERMOSTATS.

41. EC SHALL PROVIDE A 20AMP, 120VAC RECEPTACLE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT PER NEC 210.63. RECEPTACLE SHALL BE OF THE GROUND FAULT CIRCUIT INTERRUPTING TYPE, INSTALLED WITHIN A CAST METAL BOX, AND WITHIN 25' OF ALL

REQUIRED EQUIPMENT.

DATA/TELECOM NOTES:

42. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ROUGH-IN ONLY FOR THE TELECOM/CAT6 SYSTEMS. THIS SHALL CONSIST OF A FOUR SQUARE DEVICE MOUNTING BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING SPACE OR TO THE CEILING SPACE ABOVE IF OPEN. CABLING, JACKS, FACEPLATES, TESTING AND TERMINATIONS SHALL BE

PROVIDED AND INSTALLED BY OTHERS.

ROOF NOTES:

43. ELECTRICAL CONTRACTOR TO INSTALL A ROOF JACK (BOOT) FOR ALL CONDUIT PENETRATIONS THROUGH THE ROOF. ALL ROOF PENETRATION SEALS SHALL BE IN ACCORDANCE WITH THE ROOF WARRANTY AND BE COMPLETELY SEALED WITH ROOF ADHESIVE. UTILIZE PROPER CLAMPING METHODS TO SEAL BOOT AROUND

CONDUIT.

ELECTRICAL GENERAL NOTES

ELECTRICAL

GENERAL SHEET

ELECTRICAL SHEET INDEX

E000 ELECTRICAL GENERAL SHEET

E101 LIGHTING PLAN

E201 POWER PLAN

E601 ELECTRICAL SCHEDULES

J JUNCTION BOX SURFACE

WALL JUNCTION BOX 18" UNO

FLOOR JUNCTION BOX FLOOR

DISCONNECT SWITCH - NON-FUSED 60" UNO 4

DISCONNECT SWITCH - FUSED 4

COMBINATION MAGNETIC STARTER / DISCONNECT

MOTOR STARTER

CONTACTOR

MOTOR SURFACE

METER - PLAN VIEW

PUSH BUTTON SWITCH 48" TO TOP

EMERGENCY POWER SHUTOFF SWITCH

PANELBOARD - SURFACE MOUNTED 78" TO TOP

PANELBOARD - RECESSED 78" TO TOP

TRANSFORMER - PLAN VIEW

TELEPHONE TERMINAL BOARD

J

J

F

WALL

WALL

PAD/FLOOR

DISCONNECT SWITCH - SHUNT TRIP 4

60" UNO

60" UNO

60" UNO

60" UNO

60" UNO

48" TO TOP

CIRCUIT BREAKER

MCB PANEL - ONE-LINE

MLO PANEL - ONE-LINE

CURRENT TRANSFORMER

CT ENCLOSURE - ONE-LINE

TRANSFORMER - ONE-LINE

PAD MOUNT XFMR - ONE-LINE

METER - ONE-LINE

FUSED SWITCH

GROUND

OH RISER CABLE/WIRE SIZE TAG

M

XXX

AUTOMATIC TRANSFER SWITCH GROUND SLEEVE - ONE-LINE

FUSED DISCONNECT - ONE-LINE

XXXA

XXXA

XP

XX

X X

KEYED NOTE TAG

MECH/ELEC. EQUIPMENT TAG

OTHER EQUIPMENT TAG

X

ABBREVIATIONS

AFCI - ARC FAULT CKT INTERRUPTER

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

AIC - AMPS INTERRUPTING CAPACITY

AL - ALUMINUM

ATS - AUTOMATIC TRANSFER SWITCH

BC - BARE COPPER

BFC - BELOW FINISHED CEILING

BFG - BELOW FINISHED GRADE

CKT - CIRCUIT

CND. OR C. - CONDUIT

CLG - INSTALLED IN CEILING

C.R. - CORD REEL

CT - CURRENT TRANSDUCER

CU - COPPER

(E) - EXISTING TO REMAIN

EC - ELECTRICAL CONTRACTOR

EM - EMERGENCY

(F) - FUTURE

FACP - FIRE ALARM CONTROL PANEL

FLA - FULL LOAD AMPS

FVNR - FULL VOLTAGE NON REVERSING

GC - GENERAL CONTRACTOR

GFCI - GROUND FAULT CKT INTERRUPTER

GND - GROUND

HP - HORSEPOWER

IG - ISOLATED GROUND

KW - KILOWATTS

LCP - LIGHTING CONTROL PANEL

LTG - LIGHTING

LV - LOW VOLTAGE

MC - MECHANICAL CONTRACTOR

MCA - MINIMUM CIRCUIT AMPS

MCB - MAIN CIRCUIT BREAKER

MCC - MOTOR CONTROL CENTER

MDP - MAIN DISTRIBUTION PANEL

MLO - MAIN LUGS ONLY

MOCP - MAX. OVERCURRENT PROTECTION

(N) - NEW

NIC - NOT IN CONTRACT

NEC - NATIONAL ELECTRICAL CODE

NFPA - NATIONAL FIRE PROT. ASSN.

NL - NIGHT LIGHT

NR - NOT REQUIRED

NTS - NOT TO SCALE

PC - PLUMBING CONTRACTOR

PH - PHASE

PNL - PANEL

POC - POINT OF CONNECTION

POS - POINT OF SALE

(R) - RELOCATED

REC - RECEPTACLES

RMC - RIGID METAL CONDUIT

SCBA - SELECT COLOR BY ARCHITECT

SCA - SHORT CIRCUIT AMPERES

SES - SERVICE ENTRANCE SWITCHGEAR

SPD - SURGE PROTECTIVE DEVICE

TL - TWIST LOCK

TTB - TELEPHONE TERMINAL BOARD

TR - TAMPER RESISTANT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VA - VOLT/AMPS

VIF - VERIFY IN FIELD

VR - VANDAL RESISTANT

WP - WEATHERPROOF

WU - FURNISHED WITH UNIT

XFMR - TRANSFORMER

NOTES

WIRING / CONDUIT UNDERGROUND/FLOOR WIRING

CONDUIT TURNED UP CONDUIT TURNED DOWN

CIRCUIT HOME RUN TO PANEL: # OF ARROWHEADS INDICATE # OF CIRCUITS

(SEPARATE NEUTRAL PER CIRCUIT). BOTH EX. INCLUDE AN EQUIP. GROUND.

1. SEE LIGHT FIXTURE SCHEDULE FOR TYPE, MOUNTING, AND OTHER SPECIFICS.

2. CONNECT EMERGENCY AND/OR EXIT LIGHTS TO THE UNSWITCHED SIDE OF THE AREA

LIGHTING BRANCH CIRCUIT.

3. ARROW DENOTES EXIT DIRECTION.

4. USE HEAVY DUTY FOR 480 VOLT.

5. PROVIDE RACEWAY WITH OUTLETS 12" ON CENTER UNO.

6. MOUNT SWITCH AT DOOR JAM PER MANUFACTURER'S INSTRUCTIONS.

7. PROVIDE UL LISTED DEVICE TO BE USED WITH THE FIRE ALARM PANEL/SYSTEM OR

PROVIDE A MONITOR MODULE TO CONNECT INTO FIRE ALARM SYSTEM.

X

EXXX

DETAIL/VIEW REFERENCE TAG

DETAIL/VIEW NUMBER

SHEET NUMBER

STEP LIGHT FIXTURE WALL 1

LIGHT BOLLARD SURFACE 1

TIMER SWITCH - 30 MINUTEST

GROUND MOUNTED / IN-GRADE LIGHT FIXTURE GROUND 1

PILOT LIGHT SWITCHSP

LIGHT FIXTURE - SURFACE OR RECESSED SEE DRAWINGS 1

EMERGENCY LIGHT FIXTURE - SURFACE OR RECESSED SEE DRAWINGS 1, 2

EMERGENCY LIGHT FIXTURE - OPEN STRIP

LIGHT FIXTURE - CEILING MOUNTED CEILING 1

LIGHT FIXTURE - PENDANT / CHANDELIER CEILING 1

LIGHT FIXTURE - DOWNLIGHT CEILING 1

LIGHT FIXTURE - WALL WASH DOWNLIGHT CEILING 1

LIGHT FIXTURE - WALL MOUNTED WALL 1

LIGHT FIXTURE - WALL BRACKET WALL 1

TRACK LIGHTING SURFACE 1

EXIT SIGN - WALL MOUNT WALL

EXIT SIGN - CEILING MOUNT CEILING

EXIT SIGN W/ EMERGENCY HEADS - WALL MOUNT WALL

EXIT SIGN W/ EMERGENCY HEADS - CEILING MOUNT CEILING

DUAL HEAD EMERGENCY LIGHT FIXTURE WALL 1, 2

POLE LIGHT FIXTURE POLE 1

PHOTO-ELECTRIC CELL WITH RELAY SURFACE 1

OCCUPANCY / VACANCY SENSOR - CEILING MOUNT CEILING 1

CURRENT LIMITING DEVICE SURFACE 1

TIME CLOCK - 7 DAY 60"

WALL OCCUPANCY / VACANCY SENSOR SWITCH 48" TO TOP

SINGLE POLE SWITCH

THREE WAY SWITCH

FOUR WAY SWITCH

DIMMER SWITCH

LOW VOLTAGE SWITCH

EM

PC

CL

TC

SOS

S S3 S4

SD

SLV

1, 2, 3

1, 2, 3

1, 2, 3

1, 2, 3

LIGHT FIXTURE - OPEN STRIP 1

1, 2

SEE DRAWINGS

SEE DRAWINGS

EMERGENCY LIGHT FIXTURE - WALL MOUNTED WALL 1, 2

EMERGENCY LIGHT FIXTURE - WALL BRACKET WALL 1, 2

EMERGENCY LIGHT FIXTURE - DOWNLIGHT CEILING 1, 2

48" TO TOP

48" TO TOP

48" TO TOP

48" TO TOP

48" TO TOP

48" TO TOP

48" TO TOP

SINGLE POLE KEYED SWITCH

MULTI-OUTLET METAL SURFACE RACEWAY 44" UNO 5

SK

SINGLE/SIMPLEX OUTLET, 20A, 120VAC

THERMAL OVERLOAD SWITCH

DUPLEX OUTLET, 20A, 120VAC 18" UNO

DUPLEX OUTLET, 20A, 120VAC - GFCI

DUPLEX OUTLET - SPLIT WIRED

DUPLEX OUTLET - ISOLATED GROUND

DUPLEX OUTLET WITH USB-A & USB-C PORTS

DUPLEX OUTLET - OCCUPANCY SENSOR CONTROLLED

DUPLEX OUTLET, 20A, 120VAC - CEILING CEILING

DUPLEX OUTLET, 20A, 120VAC - FLOOR FLOOR

FOURPLEX OUTLET, 20A, 120VAC

FOURPLEX OUTLET, 20A, 120VAC - GFCI

FOURPLEX OUTLET - ISOLATED GROUND

FOURPLEX OUTLET, 20A, 120VAC - CEILING CEILING

FOURPLEX OUTLET, 20A, 120VAC - FLOOR FLOOR

APPLIANCE OUTLET - 208/240V SINGLE PHASE

APPLIANCE OUTLET - 208/480V 3-PHASE

TELEPHONE OUTLET

DATA OUTLET

DUAL TELEPHONE/DATA OUTLET

CABLE TELEVISION OUTLET

DUAL TELEPHONE/DATA OUTLET - FLOOR FLOOR

STH

OS

CEILING DATA OUTLET/ WIRELESS ACCESS POINT CEILING

DATA OUTLET - FLOOR FLOOR

2-POLE SWITCHS2

48" TO TOP

48" TO TOP

48" TO TOP

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

18" UNO

ELECTRICAL SYMBOL SCHEDULE

SYMBOL DESCRIPTION MOUNTING NOTES

EL

EC

TR

IC

AL

G

EN

ER

AL

SH

EE

T

FIRE ALARM HORN 7' - 6"

FIRE ALARM STROBE 7' - 6"

FIRE ALARM HORN STROBE 7' - 6"

WATERFLOW GONG 7' - 6"

FIRE ALARM DUAL ACTION MANUAL PULL STATION 4' - 0"

FIRE ALARM ADDRESSABLE CONTROL RELAY

FIRE ALARM MONITOR MODULE

FIRE ALARM CONTROL PANEL 6' - 6" TO TOP

FIRE ALARM ANNUNCIATOR PANEL 4' - 0"

PHOTOELECTRIC SMOKE DETECTOR

RATE OF RISE/HEAT DETECTOR

CARBON MONOXIDE DETECTOR

DUCT SMOKE DETECTOR 6

FIRE SMOKE DAMPER

FIRE RISER TAMPER SWITCH

FIRE RISER FLOW SWITCH

ELECTROMAGNETIC DOOR HOLDER 2' - 0"

CO

AR

F

MM

F

T

SURFACE

SURFACE

SURFACE

DUCT

REF.REF.

DL

S D S D

S D

S D

S O S

S O S

S 3

EM

EMX

1 1

EX

EX

EM

M-10

DL

DL DL

DL DL

DL DL

DL DL

DL DL

S 3 a a a a

EXISTING

PANEL 'M'

EXISTING

SUB PANEL

'S'

M-12 S 3

S3

HBHBHB

HB HB

HB

HB

HBHB

EM

EM

EM

EM

EM

EM EX

DL DLDL

DL

DL

DL

DL

DL

DLDL

S3

S3 b b b b b b b b b

DLDL

3 3

S O S3

DL

DLDL

DLDL

a a

DLDLDLDL

PROJECT #:

DRAWN BY:

CHECKED BY:

ISSUED:

alt ar ch ite ct ur e

1445 w. 8660 s.

west jordan, utah 84088 www.altarchitecture-ut.com

ANDY TONGISH 801-865-0633

TIT

LE

PR

O

JE

C

T

C

LIE

NT

AD

DR

ES

S

NO. DATE DESCRIPTION

SHEET

REVISIONS

6/

/2

2:

:0

PM

E101

CONSULTING ENGINEERS, INC.

2332 West 12600 South, Suite F | Riverton, UT 84065

(801) 566-0503 www.rmceut.com Project #

ROCKY MOUNTAIN

25042

BT / TG

BK

2/20/2025

1 04/10/26 SMOKE DETECTOR

25-001

W

AN

SH

IP

FI

RE

ST

AT

IO

N

NO

RT

H

SU

M M

IT

FIR

E

DE

PA

RT

M

EN

T

SO

UT

H

HO

YT

SV

ILL

E

RO

AD

C O

AL

VI

LL

E, U

TA

H

RE

G

IS

TE

RE

D PROFESS I ONAL ENG

I NEER

STATE OF UTAH

No. 7945859-2202

DAVID W.

STEWARD

2 07/29/26 ADD3

E101

1 LIGHTING PLAN

SCALE: 1/4" = 1'-0"

N

GENERAL NOTES

KEYED NOTES#

A. CONNECT ALL EMERGENCY AND EXIT LIGHT FIXTURES TO

THE UNSWITCHED SIDE OF THE LIGHTING BRANCH CIRCUIT.

LIGHT FIXTURES WITH EMERGENCY DRIVERS SHALL BE

NORMALLY SWITCHED WITH THE AREA LIGHTING, BUT HAVE

THEIR EMERGENCY DRIVERS CONNECTED AHEAD OF THE

LIGHT SWITCH OR LIGHTING CONTROL PANEL RELAY.

FIXTURES WILL REMAIN ON FOR NOT LESS THAN 90 MINUTES

IN CASE OF POWER LOSS.

B. IT IS THE INTENT OF THE CONSTRUCTION DOCUMENTS THAT

CONDUIT IS TO BE INSTALLED WITHIN WALLS AND ABOVE

CEILINGS CONCEALED WHERE POSSIBLE.

C. COORDINATE MOUNTING HEIGHTS OF ALL PENDANT AND

WALL MOUNTED LIGHT FIXTURES WITH ARCHITECTURAL

ELEVATIONS.

D. VERIFY FIXTURE DIMMING CONTROLS AND PROVIDE

NECESSARY WIRING AND DEVICES REQUIRED FOR DIMMING

OPERATION.

E. CONCEAL ALL FIXTURE DRIVERS IN ACCESSIBLE CEILING

SPACE OUT OF DIRECT VIEW.

F. FOR OPEN CEILING AREAS WITH OCCUPANCY CONTROLS EC

IS TO INSTALL OCCUPANCY SENSORS AT A LEVEL EQUAL TO

OR LOWER THAN AREA DUCT WORK TO ENSURE OCCUPANCY

SENSOR COVERAGE.

1. PROVIDE A WALL MOUNT DUAL TECH TWO POLE OCC.

SENSOR FOR RESTROOM LIGHT AND FAN CONTROL.

(SENSOR SWITCH #WSX PDT 2P OR EQUIVALENT).

2. EXTERIOR EGRESS LIGHTING TO REMAIN.

3. PROVIDE VACANCY SENSORS FOR AUTO OFF FUNCTION

ONLY. GROUP ROOM, BEDROOM, AND KITCHEN LIGHTS

SHOULD NOT COME ON WITH MOTION.

LTG CTRL SEQUENCE OF OPERATION

LIGHTING AND CONTROLS ARE DESIGNED TO MEET IECC 2021.

OCCUPANCY SENSORS WILL CONTROL LIGHTING IN RESTROOMS

AND GROUP ROOM.

DAYLIGHT ZONES EXEMPT FROM AUTOMATIC CONTROL

REQUIREMENTS PER IECC 2021 405.2.4 (1) (LESS THAN 150W

KITCHEN AUTOMATIC LIGHTING CONTROLS NOT REQUIRED PER

(C405.2.2 - EXCEPTION 3 (SPACES WHERE AUTOMATIC

SHUTOFF WOULD ENDANGER OCCUPANT SAFETY).

LIGHTING PLAN

LIG

HT

IN

G

P

LA

N

REF.REF.

TYP.

DS

DS

DS

HP

F WP

J 3

EXISTING

PANEL 'M'

EXISTING

SUB PANEL

'S'

TO HP-1

TO HP-1

TO HP-1

S-8

M-41

M-39

S-5,7

J 3

J 3

48"

DOOR

M-22

DOOR

M-20

DOOR

M-18

M-35

M-4

5 5

APPLIANCE

CONTROLLER

DEVICE

ALERT

END

POINT

PM UPS

M-6

M-15

APPLIANCE

RESET

BUTTON

PROJECT #:

DRAWN BY:

CHECKED BY:

ISSUED:

alt ar ch ite ct ur e

1445 w. 8660 s.

west jordan, utah 84088 www.altarchitecture-ut.com

ANDY TONGISH 801-865-0633

TIT

LE

PR

O

JE

C

T

C

LIE

NT

AD

DR

ES

S

NO. DATE DESCRIPTION

SHEET

REVISIONS

6/

/2

2:

:0

PM

E201

CONSULTING ENGINEERS, INC.

2332 West 12600 South, Suite F | Riverton, UT 84065

(801) 566-0503 www.rmceut.com Project #

ROCKY MOUNTAIN

25042

BT / TG

BK

2/20/2025

1 04/10/26 SMOKE DETECTOR

25-001

W

AN

SH

IP

FI

RE

ST

AT

IO

N

NO

RT

H

SU

M M

IT

FIR

E

DE

PA

RT

M

EN

T

SO

UT

H

HO

YT

SV

ILL

E

RO

AD

C O

AL

VI

LL

E, U

TA

H

RE

G

IS

TE

RE

D PROFESS I ONAL ENG

I NEER

STATE OF UTAH

No. 7945859-2202

DAVID W.

STEWARD

2 07/29/26 ADD3

POWER PLAN

E201

1 POWER PLAN

SCALE: 1/4" = 1'-0"

N

PO

W

ER

P

LA

N

GENERAL NOTES

KEYED NOTES

1. PROVIDE COMBINATION SMOKE/CO DETECTORS IN

SLEEPING AREAS.

2. CONNECT TO AREA LIGHTING CIRCUIT.

3. PROVIDE 24 VDC CONNECTION TO FIRST-IN DORM REMOTE.

COORDINATE WITH EQUIPMENT SUPPLIER FOR EXACT

REQUIREMENTS.

4. PROVIDE ALL NECESSARY CONDUIT AND WIRING FOR THE

GARAGE DOOR PUSHBUTTON CONTROL SWITCH AND

RED/GREEN STOP LIGHTS. COORDINATE GARAGE DOOR

INSTALLATION REQUIREMENTS WITH THE GARAGE DOOR

INSTALLER.

5. PROVIDE 2" DATA CONDUIT FOR 2 ANTENNAS FROM UNDER

THE EVE ON THE NORTH END OF THE BUILDING TO THE

FURNACE ROOM.

A. PROVIDE TAMPER RESISTANT OUTLETS IN ALL ROOMS IN

SCOPE OF WORK.

B. ITEMS SHOWN LIGHT ARE EXISTING TO REMAIN.

C. SMOKE/CO DETECTORS IN SLEEPING AREAS SHALL HAVE

LOW FREQUENCY SOUNDER BASES.

D. PROVIDE RACEWAY AND BOXES FOR WESTNET ALERT

SYSTEM PER WESTNET PLANS.

E. PROVIDE NEW GFCI BREAKERS TO PROTECT CIRCUITS AS

INDICATED IN PANEL SCHEDULE M.

PROJECT #:

DRAWN BY:

CHECKED BY:

ISSUED:

alt ar ch ite ct ur e

1445 w. 8660 s.

west jordan, utah 84088 www.altarchitecture-ut.com

ANDY TONGISH 801-865-0633

TIT

LE

PR

O

JE

C

T

C

LIE

NT

AD

DR

ES

S

NO. DATE DESCRIPTION

SHEET

REVISIONS

6/

/2

2:

:0

PM

E601

CONSULTING ENGINEERS, INC.

2332 West 12600 South, Suite F | Riverton, UT 84065

(801) 566-0503 www.rmceut.com Project #

ROCKY MOUNTAIN

25042

BT / TG

BK

2/20/2025

1 04/10/26 SMOKE DETECTOR

25-001

W

AN

SH

IP

FI

RE

ST

AT

IO

N

NO

RT

H

SU

M M

IT

FIR

E

DE

PA

RT

M

EN

T

SO

UT

H

HO

YT

SV

ILL

E

RO

AD

C O

AL

VI

LL

E, U

TA

H

RE

G

IS

TE

RE

D PROFESS I ONAL ENG

I NEER

STATE OF UTAH

No. 7945859-2202

DAVID W.

STEWARD

2 07/29/26 ADD3

ELECTRICAL

SCHEDULES

EL

EC

TR

IC

AL

SC

HE

DU

LE

S

KEYED NOTES

1. PANEL SCHEDULES SHOW NEW LOADS ONLY. HIGHEST

DEMAND FROM LAST 12 MONTHS OF UTILITY BILLS WAS

13.876kW. PER NEC 220.87 LOAD IS TO BE 125% OF EXISTING

DEMAND PLUS THE NEW LOADS. NEW TOTAL LOAD IS

27,254VA OR 113.6A.

Sheets and Views
1 25042 - E000 - General Sheet - E000
2 25042 - E101 - Lighting - E101
3 25042 - E201 - Power - E201
5 25042 - E601 - Schedules - E601

File details come from the government source that posted it. Updated .