J01j - Hydrant Flow Tests.pdf

PDF 1 MB Posted

Attached to
Peach Springs Sprinkler System, HVAC, and Communication Cabling
Solicitation number
75H701-23-R-00048
Issued by

About this file

This document provides details for a federal construction solicitation notice and opportunity. The solicitation is for a firm fixed price contract to replace the existing failed dry-pipe sprinkler system with a new wet-pipe sprinkler system, replace HVAC units beyond their useful lives, and replace outdated communication cabling with current technology at the Peach Springs Health Center located in Peach Springs, Arizona. The period of performance is 365 calendar days from notice to proceed. The construction magnitude is estimated between $1,000,000 to $5,000,000. A site visit will be detailed in the solicitation. The solicitation will use a request for proposal process with a lowest price technically acceptable evaluation. The Department of Health and Human Services Indian Health Service is the contracting agency.

View the file

Other files

File Type Posted
B04 Pre-Proposal Inquiries (23R00048).pdf PDF
Amendment A00006 75H701-23-R-00048 2023.06.20.pdf PDF
Amendment A00005 75H701-23-R-00048 2023.06.15.pdf PDF
Amendment A00004 75H701-23-R-00048 2023.06.12.pdf PDF
Amendment A00003 75H701-23-R-00048 2023.06.11.pdf PDF
J02 - WD AZ20230026 Mod 2 2023.06.09.pdf PDF
J01k - Dental Equipment Electrical Requirements.pdf PDF
Pre-Proposal Inquiries (23R00048).pdf PDF
Amendment A00002 75H701-23-R-00048 2023.06.06.pdf PDF
B04 Pre-Proposal Inquiries (23R00048).pdf PDF
J01g - ICRA Template.pdf PDF
Amendment A00001 75H701-23-R-00048 2023.06.01.pdf PDF
J01a - Project Drawings.pdf PDF
J06 - Past Performance Questionnaire.docx DOCX document
B01 RFP 23-R-00048 PS Sprinkler Final.pdf PDF
J04 - 2023 Exemption Letter for a Qualifying Hospital.pdf PDF
J05 - Company Specialized Experience Form Construction.docx DOCX document
J02 - WD AZ20230026 Mod 1 2023.02.03.pdf PDF
J04a - AZ Form 5000HC-TPT Healthcare Exemption Certificate.pdf PDF
J01d - PSHC Fire Sprinkler Record Drawings.pdf PDF
J01g - ICRA Template.docx DOCX document
J01 - SOW - PS Sprinkler Project 2023.04.13.pdf PDF
J01f - Existing GFE to Move to Swing Space.pdf PDF
J01i - Electrical Panel Photos.pdf PDF
J01b - PSHC - Original As-built Drawings.pdf PDF
J01c - PSHC IPC- Record Drawings.pdf PDF
J03 - Self Performed Calculation Sheet (Construction).docx DOCX document
J01e - Dental Swing Space Needs.pdf PDF
J01h - Dental Clinic photos.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5/30/23, 8:17 AM Hydrant Details https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina/Resources/Hydrant/Edit/a3429227-e2eb-ea11-80e5-001dd8b7228b 1/2

Hydrant Testing

Hydrant Info

Active Status

Sort Order 0

Hydrant ID 190024

Hydrant Type Dry

Color yellow

Cap Color yellow

Dome Color yellow

Barrel Color yellow

Make

Model

Year

Ownership Public

Name Of Owner

Phone Number Of Owner

Hydrant Location

Location 930 Hualapai Way

Cross Street Canyon View

Latitude 35.538203

Longitude -113.420599

Shift B Shift

Section Or District 1

Agency Location Station 141 (141)

Parcel Number

Key Map

Map Tile

Hydrant Properties

Main Size (in)

Number of Outlets 3

Elevation (ft)

Barrel Size (in)

Outlet Size (in)

Direction To Open Counter-Clockwise

Flow Properties

Date Last Tested 08/20/2020

Tested By Joshua Paddock

Leaks Present

Out of Service

Next Test Date mm/dd/yyyy

Repair Needed

Back More Sa

Yes No

Yes No

Yes No

Yes No

Hydrants

BradInboxHualapai N... Incidents Resources Tools Community

Attachment J01j - Hydrant Flow Tests

Peach Springs Sprinkler System, HVAC, and Communication Cabling Page 1 of 6 https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina

5/30/23, 8:17 AM Hydrant Details https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina/Resources/Hydrant/Edit/a3429227-e2eb-ea11-80e5-001dd8b7228b 2/2

Tested Outlet Diameter (in)

2.5

Coefficient (0.7 - 0.99) 0.98

Pitot pressure (psi) 5

Calculated GPM 408.686

Discharge Opening (in) 2.5

Static pressure (psi) 60

Residual pressure (psi) 15

Calculated GPM @ 20psi

383.502

Remarks Proper cap red

Special Instructions

Attachment J01j - Hydrant Flow Tests

Peach Springs Sprinkler System, HVAC, and Communication Cabling Page 2 of 6

5/30/23, 8:15 AM Hydrant Details https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina/Resources/Hydrant/Edit/98fe2aa4-dfeb-ea11-80e5-001dd8b7228b… 1/2

Hydrant Testing

Hydrant Info

Active Status

Sort Order 0

Hydrant ID 190017

Hydrant Type Dry

Color yellow

Cap Color Red

Dome Color yellow

Barrel Color yellow

Make

Model

Year

Ownership Public

Name Of Owner

Phone Number Of Owner

Hydrant Location

Location 533 Juniper

Cross Street Oak

Latitude 35.539386

Longitude -113.418361

Shift B Shift

Section Or District 1

Agency Location Station 141 (141)

Parcel Number

Key Map

Map Tile

Hydrant Properties

Main Size (in)

Number of Outlets 3

Elevation (ft)

Barrel Size (in)

Outlet Size (in)

Direction To Open Counter-Clockwise

Flow Properties

Date Last Tested 04/15/2023

Tested By Joshua Paddock

Leaks Present

Out of Service

Next Test Date mm/dd/yyyy

Repair Needed

Back More Sa

Yes No

Yes No

Yes No

Yes No

Hydrants

BradInboxHualapai N... Incidents Resources Tools Community

Attachment J01j - Hydrant Flow Tests

Peach Springs Sprinkler System, HVAC, and Communication Cabling Page 3 of 6

5/30/23, 8:15 AM Hydrant Details https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina/Resources/Hydrant/Edit/98fe2aa4-dfeb-ea11-80e5-001dd8b7228b… 2/2

Tested Outlet Diameter (in)

2.5

Coefficient (0.7 - 0.99) 0.9

Pitot pressure (psi) 18

Calculated GPM 712.127

Discharge Opening (in) 2.5

Static pressure (psi) 50

Residual pressure (psi) 30

Calculated GPM @ 20psi

886.435

Remarks ldh gasket needs to be replaced

Proper cap color Green.

Special Instructions

Peach Springs Sprinkler System, HVAC, and Communication Cabling Page 4 of 6

5/30/23, 8:16 AM Hydrant Details https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina/Resources/Hydrant/Edit/bdb58c0d-e0eb-ea11-80e5-001dd8b7228b 1/2

Hydrant Testing

Hydrant Info

Active Status

Sort Order 0

Hydrant ID 190018

Hydrant Type Dry

Color yellow

Cap Color Orange

Dome Color yellow

Barrel Color yellow

Make

Model

Year

Ownership Public

Name Of Owner

Phone Number Of Owner

Hydrant Location

Location 937 Oak Street

Cross Street Juniper Way

Latitude 35.539416

Longitude -113.419346

Shift B Shift

Section Or District 1

Agency Location Station 141 (141)

Parcel Number

Key Map

Map Tile

Hydrant Properties

Main Size (in)

Number of Outlets 3

Elevation (ft)

Barrel Size (in)

Outlet Size (in)

Direction To Open Counter-Clockwise

Flow Properties

Date Last Tested 04/15/2023

Tested By Patrick Lowry

Leaks Present

Out of Service

Next Test Date mm/dd/yyyy

Repair Needed

Back More Sa

Yes No

Yes No

Yes No

Yes No

Hydrants

BradInboxHualapai N... Incidents Resources Tools Community

Attachment J01j - Hydrant Flow Tests

Peach Springs Sprinkler System, HVAC, and Communication Cabling Page 5 of 6

5/30/23, 8:16 AM Hydrant Details https://www.imagetrendelite.com/Elite/Organizationkingmanarea/Agencyhualapaina/Resources/Hydrant/Edit/bdb58c0d-e0eb-ea11-80e5-001dd8b7228b 2/2

Tested Outlet Diameter (in)

2.5

Coefficient (0.7 - 0.99) 0.98

Pitot pressure (psi) 17

Calculated GPM 753.58

Discharge Opening (in) 2.5

Static pressure (psi) 55

Residual pressure (psi) 20

Calculated GPM @ 20psi

753.58

Remarks

Proper cap color green.

Special Instructions

Peach Springs Sprinkler System, HVAC, and Communication Cabling Page 6 of 6

File details come from the government source that posted it. Updated .