This is a summary of a solicitation notice for Solicitation 75H701-23-R-00048 Peach Springs Sprinkler System, HVAC, and Communication Cabling project. The scope of work is for a contractor to replace an existing failed dry-pipe sprinkler system with a new wet-pipe sprinkler system, replace HVAC units beyond their useful lives, and replace outdated communication cabling with current technology at the Peach Springs Health Center in Peach Springs, Arizona. The period of performance is 365 calendar days from notice to proceed. The magnitude of construction is estimated between $1,000,000 to $5,000,000. A site visit will be detailed in the solicitation. A single firm fixed price contract will be awarded using lowest price technically acceptable evaluation criteria in accordance with FAR Part 36 procedures. Registration in SAM is required to be considered for award. The solicitation will be posted on the website for download, with no hard copies available.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
A00002
N/A
KELLY J. BRITTON
Project: PH23CR01C9, Peach Springs Sprinkler System, HVAC, and Communication Cabling
1. The purpose of Amendment A00002 is to incorporate the following changes;
a. Pre-Proposal Inquiries 23 and 24, dated June 5, 2023, 1 page
b. Add Attachment J01k - Dental Equipment Electrical Requirements, 7 pages
2. All other terms and conditions of this solicitation remain unchanged.
Indian Health Service Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104
75H701-23-R-00048
PH23CR01C9
1 9
06/06/2023
05/08/2023
Amendment of Solicitation Amendment A00002 under Solicitation 75H701-23-R-00048 Project PH23CR01C9, Peach Springs Sprinkler System, HVAC, and Communication Cabling
INDIAN HEALTH SERVICE
DIVISION OF ENGINEERING
SERVICE
PRE-PROPOSAL INQUIRIES
Solicitation 75H701-23-R-00048
PROJECT:
Peach Springs Sprinkler System, HVAC, and Communication Cabling
LOCATION: Peach Springs, AZ
PROJECT NO: PH23CR01C9
DOCUMENT
OWNER: Kelly Britton PHONE: 602-364-5081 DOCUMENTS:
DATE: 6/6/2023 DEPARTMENT: IHS/PAO/DFE
Item No.
Reference Drawing, Spec, Page COMMENTS POC IHS Approved Response
Amendment A00002 dated 06/06/2023
23. The proposed location of the dental swing space is South of the existing trailers. There is not enough elevation difference to facilitate drainage into the existing sewer manhole. We propose setting the dental swing space to the East of the designated area so that the facility can sit at a higher elevation. A concrete walkway can be added between the trailer and the asphalted surface. Is this acceptable?
Groh The IHS lease ends at the pavement. We cannot move the building east, off the IHS leased land.
24. What are the amperage requirements for the dental equipment?
Groh The relevant pages from the equipment installation guides are provided in Attachment J01jk – Dental Equipment Electrical Requirements.
A-dec Regulatory Information, Specifications, and Warranty
Frequency (Hz)
Voltage Range
(VAC)
Maximum (Amps)
24 VDC Power Supply/LED light 50-60 100-240 1.25
24 VDC Power Supply (small)/cabinets 50-60 100-240 1.6
24 VDC Power Supply (large)/cabinets 50-60 100-240 2.5
24 VDC Power Supply (60W)/carts 50-60 100-240 1.6
25W Power Supply 50-60 100/110-120/220-240 0.3/0.3/0.15
80W Power Supply 50-60 100/110-120/220-240 0.9/0.8/0.4
300W Power Supply 50-60 100/110-120/220-240 3.1/2.8/1.4
Dental Furniture
Preference Collection® 60 120 20
Preference ICC® 50-60 100-120 15
ICV 50-60 110-120/220-240 0.5/0.5
A-dec Inspire Cabinet Models 591, 592, 593, 594, and 595
50-60 100-120 20
A-dec Inspire Cabinet Model 391 47-63 100-240 0.45
A-dec Inspire Distribution Box 50-60 100-240 10 Duplex output = 7 Amps max.
A-dec Inspire Power Box 50-60 100-240 10
Simulator 41L/41pro/42L/42pro 50-60 100/110-120/220-240 10/10/5 Duplex output = 7 Amps max.
Bitewing X-Ray Viewer 50-60 24 0.5
Monitor Mounts Performer 880X,381, 382, 482, 581, 584, 585, 586, and 587
50-60 100-240 10
NOTE
Electrical Rating
Frequency (Hz)
Voltage Range
(VAC)
(Amps)
A-dec 200 and Performer 8000
50-60 100/110-120/220-240 Input = 10/10/10 Duplex output = 10 Amps max.
Chair circuit board output = 2 Amps max.
Chair pump typical = 4/4/2
A-dec 311, A-dec 411, and A-dec 511 (chair rating includes optional chair-powered modules)
50-60 100/110-120/220-240 Input = 10/10/10 Duplex output = 10 Amps max.
511 Chair power supply = 4 Amps max.
Chair pump typical = 4/4/2
Systems with 300W Power Supply, including: A-dec 200, Performer 8100/8200/8500, 2671/2615, 2561/2562, 4631/4635, 3072, 7004, and A-dec 342.
50-60 100/110-120/220-240 Input = 3.1/2.8/1.4 Output with optional duplex on 2671/2615, 2561/2562
= 7 Amps max.
3420 Pac 1 Field and Institutional Units, N57D Bench Control, N74 M.O.M.
50-60 100-240 1.6
(Low Voltage
A-dec 200 Chair-Mount 50-60 12.1/17 5.5
(Mains Voltage)
A-dec 573L Post-Mount, A-dec 374L, 574L Cabinet- Mount, A-dec 375L, 575L Wall-Mount, A-dec 376L, 576L Ceiling-Mount, and A-dec 377L, 577L Track- Mount; A-dec 378L, 578L Universal Single
50-60 100-240 1.25
A-dec 578L Universal Dual 50-60 100-240 2.5
(Low Voltage)
A-dec 371L/372L/571L/572L Chair-Mount, A-dec 378L, 578L Stationary/In-Bench Simulator
50-60 16-24 (AC or DC) 1.5
J01k - Dental Equipment Electrical Requirements
AS10 AS12 AS21 AS22 AS30 AS40 AS50 AS70 AS100
Note 1: Install a buck or boost transformer if actual facility service is above or below the supply voltage fluctuation of ±10% of nominal voltage ratings listed, install a buck/boost transformer with the corresponding part number as shown below.
Nominal Supply Voltage (VAC, see note) 120 220 120 220 220 220 220 220 3 220
Maximum Current (Amps) 8 4 15 8 8 12 16 24 20
Minimum Panel Breaker Rating (Amps) 20 10 20 20 20 20 20 40 30
Minimum Wire Size (AWG) 12 16 12 12 12 12 12 8 10
Maximum Watts 864 792 1,620 1,584 1,584 2,376 3,168 4,752 3,960
BTU/hr @ 50% 1,473 1,350 2,201 2,701 2,701 4,051 5,401 8,201 6,752
BTU/hr @ 75% 2,210 2,026 4,143 4,051 4,051 6,077 8,102 12,153 N/A
Note 2: The 220 volt 3-phase, 4.6 KVa transformer is not available from Air Techniques.
Buck/Boost Transformer Air Techniques Part No. and Size
67006
2.5 KVa
67002
3.9 KVa
67006
2.5 KVa
67002
3.9 KVa
67002
3.9 KVa
67002
3.9 KVa
67002
3.9 KVa
67000-1
7.8 KVa
4.6 KVa
N/A
Site Requirements
All AirStar compressors comply with NFPA 99C level 3 requirements
Electrical Connections
AS50 and AS70 Electrical Connections
L1
L2
GND
WHITE
GREEN
BLACK
WHITE
BLACK
GREEN
HARD WIRED
CONNECTED
AIRSTAR MODELS
AS50 & AS70
AS100 3-Phase Electrical Connections
BLUE
L1
L2
GND
L3
GREEN
BLACK
RED
RED
BLACK
BLUE
GREEN
HARD WIRED
CONNECTED
AIRSTAR MODEL
AS100
24V Circuit Connections
AirStar Electrical Connection
Interconnect Cable
Yellow 2
Brown 4
Orange 3
See Note 3
Future Use
Remote Panel
Yellow 2 Brown 4 Orange 3
White
White
See Note 4
Connection without
24V Switch
4 BRN3 ORG
2 YEL
Notes:
1. Use 18 Gauge, 4 conductor, interconnect cable between the
AirStar unit and Remote Switch Panel.
When any 24V circuit exceeds 150 feet, use #16 AWG.
2. As shown, 3 conductors of the 24V circuit cable from each compressor connect via the user-supplied interconnect cable.
3. The fourth conductor of interconnect cable to be used for future equipment options/enhancements.
4. Leave with factory connection, without a 24V Switch, or connect the associated interconnect cable directly to remote switch.
Please note that one switch is used for each compressor.
Pressure Switch
From Electrical Box
3 ORN
YEL
BRN
BLU
BLK
BRN
YEL
BLK
BRN
BLU
ORN
To Remote Panel
YELORN
ORN
YEL
AirStar is a trademark of Air Techniques, Inc. 2009 Air Techniques, Inc. • PN 87104 Rev. P May 2021 www.air techniques.com
Corporate Headquarters
1295 Walt Whitman Road Melville, New York 11747- 3062
Phone: 800-247-8324 Fax: 888-247-8481
Product Specifications - Dimensions
AS10 AS12 AS21 AS22 AS30 AS40 AS50 AS70 AS100
Input Voltage Phase 1 1 1 1 1 1 1 1 3
System Power
HP
(kW)
0.75 (0.56)
0.75 (0.56)
1.5 (1.1)
1.5 (1.1)
1.5 (1.1)
2.25 (1.68)
3.0 (2.2)
4.5 (3.4)
4.8 (3.6)
Nominal Supply Voltage VAC 120 220 120 220 220 220 220 220 220
Frequency Hz 60 60 60 60 60 60 60 60 60
Maximum Current Amps 8 4 15 8 8 12 16 24 20
Maximum Simultaneous Air Users 2 2 3 3 4 6 8 12 15
System Output Flow Rate at
80 PSI CFM 2.5 2.5 5.0 5.0 5.0 7.5 10.0 15.0 20.0
Maximum Pump-up Time
0-115 PSI (M:SS) 2:55 2:55 3:10 3:10 3:10 1:40 2:50 2:40 2:30
Maximum Recovery Time
85-115 PSI (M:SS) 0:48 0:48 0:47 0:47 0:47 0:34 0:42 0:40 0:30
Tank Size US Gal.
(ft3)
(0.8)
(0.8)
(1.6)
(1.6)
(1.6)
(1.6)
(2.7)
(4.0)
(4.0)
Shipping Weight lbs.
(Approximate)
No Sound Cover With Sound Cover
N/A
N/A
Dimensions in.
(See note.)
No Sound Cover
H W D
28.50 25.00 19.75
28.50 25.00 19.75
30.50 29.00 20.00
30.50 29.00 20.00
30.50 29.00 20.00
30.50 32.50 20.00
33.50 35.50 20.50
35.00 47.75 21.75
34.50 46.00 24.50
With Sound Cover H W D
30.00 25.00 22.50
30.00 25.00 22.50
32.00 31.00 22.25
32.00 31.00 22.25
32.00 31.00 22.25
32.25 33.25 22.50
33.50 36.50 22.75
36.00 51.00 29.50
N/A N/A N/A
Description Model
Note: Height measured without leveling feet for all units with or without sound cover.
Speci cations & Site Requirements
Model QT 2 115V QT 2 230V
Maximum Number of Users 4 4
Phase 1 1
Horsepower (kW) 1.0 (0.7) 1.0 (0.7)
Voltage Rating (Minimum/Maximum)
104/127
208/253
Frequency (Hz) 60 60
Breaker Rating Size (Recommended Amps) 20 15
Full Load Amps 9.0 4.5
Fusetron Size (Recommended) FRN-25 FRN-8
THHN Wire Size (AWG) 12 12
BTU/HR (Heat Released to Room) 1,082 1,082
Sound Levels (dBA) 71 71
Operating Temperature (Min/Max) 32°F/104°F
Operating Relative Humidity Range 0-95%, No Condensing Moisture
Shipping/Transport Temperature (Min/Max) -20°F/165°F
Operating Atmospheric Pressure Range 63-105 kPa
DentalEZ 2500 Highway 31 South Bay Minette, AL 36507
Phone: 866-DTE-INFO Fax: 251-937-0461 www.dentalez.com
PN: 7565-049A
November, 2019
Bulldog® QT Dry VacuumPreinstallation Guide
Product Dimensions* Bulldog QT 15-Gallon Otter Tank Bulldog & 15-Gallon Otter Tank Stacked
Nominal Width 21" (533 mm) 25" (635 mm) 25" (635 mm)
Nominal Depth 17" (432 mm) 19" (483 mm) 19" (483 mm)
Nominal Height 28" (711 mm) 24" (610 mm) 44" (1,118 mm)
Nominal Height with S-Type Exhaust Filter
48" (1,219 mm) N/A 67" (1,702 mm)
Drain Valve Centerline to Floor N/A 8" (203 mm) 8" (203 mm)
*Add 6" (155 mm) to each dimension for working space.
Conforms to:
ANSI/AAMI STD ES60601
Certi ed to:
CAN/CSA STD C22.2 NO. 60601-1
ETL CLASSIFIED
4007136
7 Technical data
51774-IMG rev 13 Instrumentarium Dental
7 Technical data
7.1 Technical specifications
Manufacturer: Instrumentarium Dental, PaloDEx Group Oy, Nahkelantie 160 FI-04300 Tuusula, FINLAND
Manufacturer’s Quality System: In accordance with ISO13485 and ISO9001 standard
Environmental Management System:
In accordance with ISO 14001 standard
Conformity to standards: IEC 60601-1
IEC 60601-1-4
IEC 60601-1-3
IEC 60601-2-7
IEC 60601-2-28
IEC60601-2-65
CAN/CSA –C22.2 No. 601-1-M90 CE models marked according to the Medical Device Directive 93/
42/ EEC
Product Name FOCUS Type Intraoral X-ray unit
UNIT DATA
Protection against electric shock
Class I
Degree of protection Type B Protection against the ingress of liquids
IP20
Mode of operation Continuous operation with intermittent loading
Power supply Mains connection, plug or fixed Software version 3.0 or higher
X-RAY GENERATOR
Generator type Constant potential Nominal power 490 W High voltage DC Supply frequency 100-200 kHz Number of phases 1 Reference current time product 7 mAs (70 kV, 7 mA, 1 s) Lowest current time product 0.14 mAs (70 kV, 7 mA, 0.02 s) Coefficient of variation of DAP < 0,05
32 Instrumentarium Dental
DENTAL CARE UNIT MOUNT MODEL FOCUS
Horizontal arm length 330 mm (from axl to axl), 418 mm (total length) Generator module length 500 mm Horizontal arm shaft diameter 32 mm Main cable length 5230 mm
(measured from generator module to the scissors arm)
TUBE HEAD ASSEMBLY
Tube head assembly type FOCUS Tube type Toshiba D-0711SB or Kailong KL
21 SB or equivalent Max. tube voltage 60 or 70 kV Max. tube current 7 mA Max. electric output 490 W (70kV; 7mA) Reference axis Runs axially with the cone Target angle 16 degrees Focal spot 0.7 mm
(according to IEC 60336/2005) Nominal anode input power 940 W Max. symmetrical radiation field
60 mm at a 200 mm focal length
Total filtration 2,0 mm Al (70 kV) Inherent filtration 1,5 mm Al (70 kV) Fixed additional filtration 1,0 mm Al (70 kV) Max. anode heat content 7 kJ Maximum X-ray tube assembly heat content
140 kJ
Maximum continuous heat dissipation of the X-ray tube head assembly
19 W
ELECTRICAL CONNECTIONS
Nominal mains voltage 115 VAC +/- 10%
230 VAC +/- 10%
Input power frequency 60 Hz
50 Hz Nominal current 7.63A
3.55A Mains fuse, slow blow 6.25AT Apparent resistance of supply mains
0.68
Power consumption 816 VA / 230 VAC
877 VA / 115 VAC
US/Canada mains connector type
115 V / NEMA 6-15P or similar
Power supply cords type H05VV5-F / AWG 14 (UL 2587)
51774-IMG rev 13 Instrumentarium Dental
Nominal Shortest Irradiation Time 0.02 S Exposure Time Range 0.02 - 3.2 S Exposure Time Range In Aec Mode 0.02- 1.6 S
BEAM LIMITING DEVICE
Cone dimensions Round: 60 mm
Rectangular: 35 x 45 mm
PHYSICAL MEASURES AND AMBIENT TEMPERATURES:
Focal length (Standard/Long) 229 mm (9 inches) /
305 mm (12 inches) Installation Standard wall mount Optional base for free standing unit Height x Width x Depth (mm) Unit: 1059 mm x 279 mm x 946/
1096/1346 mm Tube head assembly: 112 mm x 260 mm x 201 mm
Weight Unit: approximately 30 kg (66 pounds) Tube head assembly:
approximately 4.5 kg (10 pounds)
Type and length of the cable of the remote exposure switch
Length approximately 10 m (32.5 feet), RJ-45 plug at both ends (8 wires)
Transportation and Storage -40°...+70°C (-40F...+158F), RH 10...100%
Operating environment +10°...+40°C (+50F...+104F), RH max. 70%, 700 – 1060 mbar