583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part26.pdf

PDF 4 MB Posted

Attached to
Z1DA--Renovate Nuclear Med 583-20-102 (VA-21-00037478)
Solicitation number
36C25021B0036
Issued by

About this file

This document package includes plans and specifications for a federal construction project. The solicitation is for relocating nuclear medicine services at the Richard L. Roudebush VA Medical Facility in Indianapolis, Indiana. Work includes renovating existing spaces and relocating equipment to accommodate new PET/CT scanners. The project scope involves demolishing some walls and fixtures, installing new electrical, data, security and medical gas systems, and modifying HVAC. Bids are due by late February 2021, with work to be completed by early 2022. The estimated value is between $1-5 million. The contracting agency is the VA.

View the file

Other files

File Type Posted
Amendment A00006.docx DOCX document
Amendment A00006 RFI Responses.docx DOCX document
Amendment 36C25021B0036 A00005.pdf PDF
A00004- Corrected Statement of Work.pdf PDF
Amendment 36C25021B0036 A00004.pdf PDF
A00004 - RFI Responses.docx DOCX document
A0004 - 08 71 00 - Door Hardware.pdf PDF
A00004 - 10 25 13 - Patient Bed Service Walls.pdf PDF
A00004 - Door Schedule.pdf PDF
Amendment 36C25021B0036 A00003.pdf PDF
Amendment A00002.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
A0001 - RFI 1 ShieldingReportComplete.pdf PDF
A0001 - RFI 2- GC101.pdf PDF
A0001 - RFI Responses.docx DOCX document
Amendment A0001.docx DOCX document
A0001 - RFI 4- Door Schedule.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part18.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part23.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part22.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part11.pdf PDF
Specifications.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part21.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part13.pdf PDF
Wage Determination.txt TXT text file
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part15.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part4.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part20.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part8.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part6.pdf PDF
36C25021B0036 Solicitation Document.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part11.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part24.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part2.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Type B1

RECESSED LED ARCHITECTURAL LAY-IN FIXTURE

HOUSING: DIE-FORMED COLD-ROLLED STEEL. HINGED OPTIC SYSTEM.

SPRING LOADED LATCHES.

FINISH: NON-GLARE HIGH-REFLECTANCE W HITE POW ER COAT

FINISH, PAINTED AFTER FABRICATION.

OPTICS: HIGH TRANSMISSION EXTURDED ACRYLIC LENSES.

LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 90 CRI.

4000K

CERTIFICATION: UL1598, UL2108, CSA LABEL. EMERGENCY FIXTURES- UL924.

DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED.

DAMP LOCATION LABELED. IC RATING - STANDARD

DIMMING: 0-10VDC 5% DIMMING.

VOLTAGE: UNIVERSAL 120-277V.

MANUFACTURER: CREE LIGHTING "CR" SERIES

VARIATIONS: “B1a” 2’ X 4’ 3000 LM, 34 W , NOMINAL “B1b” 2’ X 4’ 4000 LM, 33 W , NOMINAL “B1c” 2’ X 4’ 5000 LM, 50 W , NOMINAL

“B1w” 2’ X 2’ 2000 LM, 22 W , NOMINAL “B1y” 2’ X 2’ 3200 LM, 32 W , NOMINAL

B1

Type B8

LED MRI COMFORT FIXTURE

HOUSING: 0.050” ALUMINUM HOUSING AND DOOR.

FINISH: W HITE POLYESTER POW DER COAT ANTI-MICROBIAL FINISH.

OPTICS: SANITARY DOOR W ITH ACRYLIC 0.175 LENS.

CHOICE OF NATIONAL GEOGRAPHIC IMAGES.

LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 80 CRI. 4000K

DIMMING: 0-10VDC DIMMING.

VOLTAGE: 120V OR 277V.

VARIATIONS: “B8a” 2’ X 4’ 327 LM, 39 W , NOMINAL

B8

Type F3

RECESSED LED 6” DIAMETER FLUSH LENS DOW NLIGHT FIXTURE

HOUSING: 22 GA. NON-CORROSIVE STEEL PLATFORM. J-BOX W ITH

SNAPON COVER. ACCESSABLE FROM ABOVE AND BELOW

CEILING.

REFLECTOR: ALUMINUM, ALZAK SEMI-DIFFUSE REFLECTOR. SELF-TRIMED.

45DEG BEAM SPREAD.

LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L70, 80 CRI.

4000K

CERTIFICATION: CSA LABEL. EMERGENCY FIXTURES-UL924.

W ET LOCATION LISTED. W ITH EMERGENCY OPTION, DAMP

LOCATION LISTED. NON-IC RATING

IP65 RATED 16 GA. COLD ROLLED STEEL STAMPINGS. CLEAR

HIGH IMPACT POLYCARBONATE LENS.

DIMMING: 0-10VDC 10% DIMMING.

VOLTAGE: UNIVERSAL 120-277V.

MANUFACTURER: CREE LIGHTING "KR" SERIES

VARIATIONS: “F3a” 6” 45DEG 1100 LM, 15 W , NOMINAL “F3b” 6” 45DEG 1500 LM, 19 W , NOMINAL “F3c” 6” 45DEG 2000 LM, 27 W , NOMINAL

F3

Type U2

LED UNDERCABINET FIXTURE

HOUSING: 20 GA STEEL HOUSING.

FINISH: POLYESTER POW DER COAT ANTI-MICROBIAL FINISH. W HITE.

OPTICS: HIGH IMPACT ACRYLIC LENS.

LAMPS: LED LIGHT SOURCE, 4000K

CERTIFICATION: DAMP LOCATION LISTED.

SW ITCHING: W ALL SW ITCH.

LINKS: OPTIONAL LINKING CONNECTOR CORDS.

VOLTAGE: MVOLT 120V - 277V.

VARIATIONS: “UCc” 4’ 2240 LM, 28 W , NOMINAL

UC

Type X1

LED EXIT SIGN

HOUSING: DIE-CAST ALUMINUM BODY. W HITE TEXTURED FINISH.

MOUNTING: UNIVERSAL W ALL, CEILING, END MOUNTING.

LAMPS: LED LIGHT SOURCE, RED STENCIL LETTERS. BREAK OUT CHEVRONS.

CERTIFICATION: DAMP LOCATION LISTED. EMERGENCY FIXTURES-UL924

VOLTAGE: UNIVERSAL 120-277V.

VARIATIONS: “X1” SINGLE FACE EXIT.

“X2” DOUBLE FACE EXIT.

“XO” OPTIONAL W ORDING “X-RAY IN USE”

X2

Type B2

RECESSED LED LENSED LAY-IN FIXTURE

HOUSING: DIE-FORMED COLD-ROLLED STEEL. HINGED OPTIC SYSTEM.

SPRING LOADED LATCHES.

FINISH: HIGH-REFLECTANCE W HITE BAKED ENAMEL FINISH.

OPTICS: HIGH TRANSMISSION EXTURDED ACRYLIC LENSES. A12

PATTERN.

LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.

4000K

CERTIFICATION: UL1598, UL2108, CSA LABEL. EMERGENCY FIXTURES-UL924.

DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED. DAMP LOCATION

LABELED. IC RATING - STANDARD

DIMMING: 0-10VDC 1% DIMMING.

VOLTAGE: UNIVERSAL 120-277V.

MANUFACTURER: CREE LIGHTING "C-TR" SERIES

VARIATIONS: “B2b” 2’ X 4’ 4300 LM, 34 W , NOMINAL

B2

Type D1

LED W ALL-MOUNTED VANITY FIXTURE – INDIRECT

HOUSING: EXTRUDED ALUMINUM CHANNEL.FASCIA DIE-FORMED

20 GA. STEEL. 14 GA ENDCAPS HINGED OPTIC SYSTEM.

ANGLED CURVED FASCIA. PERFORATED FRONT.

FINISH: W HITE FINISH.

OPTICS: 96% REFLECTANCE W HITE FINISH. VIRGIN ACRYLIC UV

STABILIZED LENSED DIFFUSER BEHIND PERFORATED FASCIA.

DIFFUSURES: TOP AND BOTTOM FROSTED ACRYLIC DIFFUSERS.

LAMPS: LED LIGHT SOURCE, 100,000 HOUR RATED AT L90, 80 CRI. 4100K

CERTIFICATION: UL1598, CSA LABEL. EMERGENCY FIXTURES-UL924.

DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED.

DAMP LOCATION LABELED.

DIMMING: 0-10VDC 1% DIMMING.

VOLTAGE: 120V OR 277V.

VARIATIONS: “D1b” 4’ 1400 LM, 18 W , NOMINAL

D1

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:0

A M

E601

LIGHT FIXTURE SCHEDULE

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

BASEMENT

FIRST

FLO OR

ABLNDP3

1600A

AB147

100A

ABLN1

100A

ABLNDP1

400A

ABLN7

100A

ABLN16

100A

ABHN5

100A

ABLN4

100A

ABHCRDP1

400A

ABLCRDP1

400A

ABHCR1

100A

ABLCR1

100A

ABHN1

100A

ABHNDP1

800A

ABT4

500kVA

UNIT SUBSTATION -

AMS1

TRANS.

ABT1

1000kVA

SW GR

AMS1

MV

SW GR ATS-CR1

400A

CRITICAL

ABHEDP1

ATS-CS1

260A

LIFESAFETY

N L

ABT5

112.5 kVA

ABHEDP1

ABHLS3

150A

ABHLS1

100A

ABT6

30 kVA

ABLLS3

100A

ABLLS1

100AUNIT SUBSTATION -

AMS3

TRANS.

FBT3

1000kVA

SW GR

AMS3

MV

SW ABHEQDP1

800A

ATS-EQ1

800A

EQUIPM ENT

E L

N

ABHEQ 1

100A

ABHEQ 4

200A

ABHEQ 7

150A

10KAIC

ABHEQ 9

80A

10KAIC

ABHEQ 8

80A

10KAIC

(NEW )

(NEW )(NEW )

ABNMCC1

600A

TRANS.

FBT2

1000kVA

SW GR

AMS2

MV

SW GR

ABHN6

ABLCR3

100A

(NEW )

GEN-3 GEN-1 GEN-2 MASTER DIST. DIST. DIST.

ABHEDP1

PARALLEL

SW GR

ATS-EQ8

800A

EQUIPM ENT

E

L

N

ABHEQDP2

800A

ABHEQ6

400A

35KAIC

(NEW )

35KAIC

(NEW )

35KAIC

(NEW )

UPS FOR IM S

(SIEMENS

SUPPLIED SYNGO

MI ACQUISITIO N

W ORKPLACE)

EPOEPO

MAIN BREAKER

480Y/277V 3 PH,

80A

480Y/277 VOLTS 3

PHASE, 4 W IRE,

PLUS GRO UND

A

480Y/277V 3 PH,

80A

B

480V, 1 PH, 20A

NCNC

NCNC

XF

C

240V, 1 PH, 25A

UPS FOR SYM BIA

CAMERA SYSTEM

(SIEMENS

SUPPLIED )

BREAKER FOR

SPECT GANTRY

(SIEMENS

SUPPLIED)

LINE

CONNECTIO N

(SIEMENS

SUPPLIED )

BREAKER FOR

CT GANTRY

(SIEMENS

SUPPLIED)

MAIN BREAKER

EPO ABLCR3-31

#14 AW G MAX.

.75"C

PANEL ABHEQ8

PANEL ABHEQ9

B

SPS LCB

MB

XF

C

UPS

#16 AW G /CL2 MAX.

.75"C

EPO

#14 AW G

.75" C

24VDC

X-RAY LIGHT

RELAY BOX

LIGHTING

CIRCUIT DOO R SW ITCH

#16 AW G

.75" C

#16 AW G

.75" C

#12 AW G

.75" C

X-RAYON

W ARNING

LIGHT

EPOEPO

MAIN BREAKER

480Y/277V 3 PH,

200A

480Y/277 VOLTS

3 PHASE,

4 W IRE, PLUS

GROUND

NCNC

NCNC

PO W ER

DISTRIBUTION

CABINET

(SIEMENS

SUPPLIED)

BREAKER EPO

ABLCR3-31

EPO

NC

NC

CT UPS ROO

COM MON POW ER DISTRIBUTION

UNIT (cPDU)(SIEMENS SUPPLIED)

PET UPS

UPS

#6 TO BUILDING

GROUND

CABLE FURNISHED BY

SIEMENS. REFER TO

SIEMENS DRAW ING S FOR

MORE INFORM ATION.

cPDU BREAKER

480Y/277V 3 PH,

150A

HEAT EXCHANGER

CABINET BREAKER

480Y/277V 3 PH, 30A

HEAT EXCHANGER

CABINET (SIEMENS

SUPPLIED)

#14 AW G

.75"C

ABHEQ4

PDC

cPDU

PPS

S

MP

EPO

24VDC

X-RAY LIGHT

RELAY BOX

X-RAY ON

W ARNING LIGHT

LIGHTING

CIRCUIT DOO R SW ITCH

#14 AW G

.75" C

#14 AW G

.75" C

#12 AW G

.75" C

#14 AW G

.75" C

EPOEPO

MAIN BREAKER

480Y/277V 3 PH,

150A

480Y/277 VOLTS

3 PHASE,

4 W IRE, PLUS

GROUND

NCNC

NCNC

PO W ER

DISTRIBUTION

CABINET

(SIEMENS

SUPPLIED)

MAIN BREAKER

EPO ABLCR3-31

EPO

NC

NC

CT UPS ROO

COM MON POW ER DISTRIBUTION

UNIT (SIEMENS SUPPLIED)

PET UPS

UPS

#6 TO BUILDING

GROUND

SIEMENS FURNISHED

CABLES. REFER TO

SIEMENS DRAW INGS

FOR MORE

INFORMATION.

ABHEQ7

#14 AW G

.75" C

EPO

MP

cPDU

PPS

PDC

#14 AW G

.75" C

24VDC

X-RAY LIGHT

RELAY BOX

X-RAY ON

W ARNING LIGHT

LIGHTING

CIRCUIT DOO R SW ITCH

#14 AW G

.75" C

#14 AW G

.75" C

#12 AW G

.75" C

A

480Y/277V 3 PH,

150A

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:0

A M

E701

SINGLE-LINE DIAGRAMS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

NO SCALEE701

1 ELECTRICAL SINGLE LINE (PARTIAL)

CONDUIT & WIRE SCHEDULE

1 4 - #4, #4GND., 1.25"C MINIMUM SIZE

2 2 - #10, #10 GND., .75"C MINIMUM SIZE

3 4 - #4/0, #4/0GND., 2.5"C MINIMUM SIZE

4 3 - #10, #10GND., 0.75"C MINIMUM SIZE

5 4 - #2/0, 1- #2/0GND., 2"C MINIMUM SIZE

6 2 SETS 4-600 KCMIL, #1/0 GND., 4"C MINIMUM SIZE

7 4-600 KCMIL, #3 GND., 4"C. MINIMUM SIZE

8 12-#14, .75"C. MINIMUM SIZE

PLAN NOTES

1. EXISTING FEED SHALL BE EXTENDED TO THE NEW ABEQ4 PANEL.

REFER TO SHEET EP101.

2. PANEL SHALL BE REPLACED W ITH NEW PANEL FOR PET/CT-1. REFER

TO SHEET EP101 FOR PANEL LOCATION.

3. NEW PANEL FO R PET/CT-2. REFER TO SINGLE LINE DIAGRAM THIS

SHEET FOR FEEDER SIZE.

4. REPLACE SPARE 150A/3P BREAKER W ITH 200A/3P FRAM E BREAKER FOR

FEED TO NEW CT MAIN PANEL.

5. EM ERGENCY POW ER OFF BUTTON W ITH PROTECTIVE COVER. EPO

SHALL BE OF FAIL-SAFE DESIGN W ITH M ECHANICAL LATCHING

MECHANISM. CONTACTS FO R EPO SHALL BE NORMALLY CLOSED.

6. UTILIZE SPARE 800A BREAKER FOR FEED TO ATS-EQ8

7. UTILIZE SPARE CUBICLE IN SECTIO N 2 FOR INSTALLATION OF 800A

BREAKER. PROVIDE BREAKER TO MATCH EXISTING AND PREP EMPTY

CUBICLE AS REQUIRED TO RECEIVE BREAKER.

8. RUN START/CONTROL/MO NITO RING CONDUCTORS TO PARALLING

SW ITCHGEAR. PROVIDE ALL PROGRAMMING AND TESTING AS

REQ UIRED. (SOLE SOURCE TO THE MANUFACTURER)

SCALE: NONE

NM SCAN - SINGLELINE (TYPICAL)

SCALE: NONE

PET/CT 1 POWER SCHEDULE

SCALE: NONE

PET/CT 2 POWER SCHEDULE

GENERAL NOTES

A. REFER TO SITE SPECIFIC DRAW INGS BY SIEMENS PROJECT NUM BERS #

2002344, #2002254, #2002345, AND #200243 FOR ABBREVIATIONS AND

ADDITIONAL INFORMATION.

DMDMDM

DMDM

3 3

DM

DM

OS

OS

OS

OS

OS OS

OSOS

OS

OS

OS

OS

OSOSOS

OS

OS

OS

OS

OS

OS

OS

OS

OS

A

457 3.5

B

C

D

E

F

2.5

1 1 1

1 1

2 2

EX EX EX EX

EXEX

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LOUNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIOACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

EXEX EX EX EX EX EX

EX

EX

EXEX

EX

EXEX

EXEX

EX EX EX EX EX EX

EX

EX

EX EX

EX

EX

EX

EXEX

EX

EX

EX

EX

EX

EX

N

KEY PLAN

GENERAL NOTES - DEMOLITION

A. FOR EXISTING EQUIPM ENT, SUCH AS LIGHTING FIXTURES, W IRING

DEVICES, CONDUITS, ETC., SHOW N ON PLANS TO BE REM OVED,

COMPLETELY CUT/CAP CONDUITS AT THE AREA O F W O RK PERIMETER

AND REMO VE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT

W IRING AT THE OVERCURRENT PRO TECTIVE DEVICE AND REMOVE

W IRING COMPLETELY FROM THE ABANDO NED CONDUITS.

B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED W IRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTO RS PASSING THROUGH RENOVATED AREAS AND

SERVICING UNDISTURBED AREAS.

D. LIGHT FIXTURE NOTED AS EXISTING (EX) SHALL BE SALVAGED,

CLEANED AND STORED FOR REUSE.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:0

A M

ED101

LOWER LEVEL LIGHTING

DEMOLITION PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"ED101

1 LOWER LEVEL LIGHTING DEMOLITION PLAN

PLAN NOTES

1. MAINTAIN DEVICE LOCATION. REMOVE DEVICE TO REPLACE W ITH NEW .

2. SALVAGE LIGHT FIXTURES AND CLEAN FOR REUSE.

N

G F

G F

G F

GF

GF

GF GF

GF

J

J

J J

J

J

J

J

J

F F

F

F F F FF

F

F F

F

FF

F

F F

F

HD

J J

J

HD

F

J N B

N B

J

TV

F

FACP

A

457 3.5

B

C

D

E

F

2.58

ABHEQ4

ABHN1

ABLNDP1

ABLN1

AAUPS

ABLCR1

ABLLS1

ABHLS1 ABHCR1 ABHEQ1

ELECT.

A-B153

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LOUNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIOACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

A-B040

OFFICE

A-B066

AUDITORIU M

N

KEY PLAN

GENERAL NOTES - DEMOLITION

A. FOR EXISTING EQUIPM ENT, SUCH AS LIGHTING FIXTURES, W IRING

DEVICES, CONDUITS, ETC., SHOW N ON PLANS TO BE REM OVED,

COMPLETELY CUT/CAP CONDUITS AT THE AREA O F W O RK PERIMETER

AND REMO VE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT

W IRING AT THE OVERCURRENT PRO TECTIVE DEVICE AND REMOVE

W IRING COMPLETELY FROM THE ABANDO NED CONDUITS.

B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED W IRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTO RS PASSING THROUGH RENOVATED AREAS AND

SERVICING UNDISTURBED AREAS.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:1

A M

ED201

LOW ER LEVEL POW ER AND FIRE

ALARM DEMOLITION PLANSGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"ED201

1 LOWER LEVEL POWER AND FIRE ALARM DEMOLITION PLAN

PLAN NOTES

1. EXISTING EQ UIPMENT CONNECTIONS TO PANEL ABHEQ4 W ITHIN

EQ UIPMENT AND PROCEDURE ROOM SHALL BE REMOVED BACK TO

PANEL.

2. PANEL ABHEQ 4 SHALL BE REMOVED. FEEDER TO PANEL SHALL BE

MAINTAINED AND EXTENDED TO NEW PANEL. REFER TO SHEET EP101.

3. EQ UIPMENT FOR PET / CT SCANNER SHALL BE RELOCATED TO NEW

EQ UIPMENT ROO M FO R SCANNER. ASSO CIATED RACEW AYS SHALL BE

REW ORKED TO NEW LOCATION.

4. FEEDER TO DISTRIBUTIO N PANEL ABHEQDP1 IN ELECTRICAL SW ITCH

GEAR ROO M A-B148 SHALL BE MAINTAINED.

5. DISCONNECT AND REMOVE ELECTRICAL CONNECTION TO COO LING

EQ UIPMENT ASSOCIATED W ITH LOW ER LEVEL PET/CT SCANNER.

EQ UIPMENT LOCATED ON LEVEL B OF PARKING GARAGE.

FACP

ABHEQ5ABLEQ5

TX-ABLEQ-3

ABHNMCC1

1.5"C

4"C

RF30

CONTROL PANEL

A-B148

MECHANICAL

ROOM

N

KEY PLAN

GENERAL NOTES - DEMOLITION

A. FOR EXISTING EQUIPM ENT, SUCH AS LIGHTING FIXTURES, W IRING

DEVICES, CONDUITS, ETC., SHOW N ON PLANS TO BE REM OVED,

COMPLETELY CUT/CAP CONDUITS AT THE AREA O F W O RK PERIMETER

AND REMO VE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT

W IRING AT THE OVERCURRENT PRO TECTIVE DEVICE AND REMOVE

W IRING COMPLETELY FROM THE ABANDO NED CONDUITS.

B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED W IRING.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTO RS PASSING THROUGH RENOVATED AREAS AND

SERVICING UNDISTURBED AREAS.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:1

A M

ED202

ENLARGED MECHANICAL ROOM

ELECTRICAL PLAN - DEMOLITIONGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"

LOWER LEVEL ENLARGED MECHANICAL ROOM ELECTRICAL PLAN

PLAN NOTES

1. DISCONNECT AND REMOVE CONNECTION TO FAN BACK TO

MOTOR CONTROL CENTER ABHNM CC1.

2. REM OVE LIGHT FIXTURE. M AINTAIN LIGHTING CIRCUIT FOR

REUSE. REFER TO SHEET EP102.

3. RAISE EMPTY 1.5" CONDUITS TO M ATCH HEIGHT OF THE 4"

CONDUIT FOR CLEARANCE OF NEW AHU. REW O RK CONDUIT

OVER AHU BETW EEN FITTINGS.

4. REM OVE VFD BUCKET FOR SUPPLY AND RETURN FANS FOR

AHU-30.

5. REM OVE SM OKE DETECTOR FRO M DUCTW ORK. PROVIDE

CONTINUITY OF CIRCUIT DURING REMO VAL.

6. REM OVE CIRCUIT BACK TO SOURCE.

7. REM OVE ELECTRICAL CIRCUIT FROM PANEL. MAINTAIN CIRCUIT

FOR REUSE W ITH REPLACEMENT PANEL. COORDINATE W ITH

DIV. 23.

OS

OS

OS

OS

OS OS

OS

DM

D M

OS

D M

DM

OS

O S

D M

D M

OS

DM

D M

DM

DM

OS

D M

D M

D M

3 D M

D M

D M

D M

OS

OS

D M

D M

OS

DM

DM

DM

DM

DM

OS

OS

OS

OS

OS

OS

D M

OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

DM

D M

D M

OS

D M

OS

OS

OS

DM

DM

DM

DM

D M

D M

OS

D M

D M

DM DM DM DM DM DM

A

457 3.5

B

C

D

E

F

2.58

UCc

B8aB1a

UCc

B1a B8a

B2b B2b

F3c F3c

F3cF3c

F3cF3c

B8aB8a

F3bF3b

F3b F3b

(ETR)

(ETR)

(ETR)

B2b B2b

B2b

B2b

UCc

UCc

UCc

UCc

EX EX EX

B1w

EX

EX

EXEX

B1w

B1w

EX

EX

B1aB1a

UCc

B2b B1y B1y B1y B1y

B1y

B1y

B1y

X1

X2

B1y B1y

B1yB1y

B1y

B1y

B1yB1y

X1 X1

UCc B8a B1a

EX EX

EXEX

EX

EX

B1a

B1aEX EX

EXEX

EX EX

B1y

B1y

B1y

B1a B1a

B1a

B1a

B1a B1a

B1a

B1a

B1y

X1

B1y

B1y

B1y

B1y

X1

X1

B1y B1y

B1y B1y

B1y

B2bB2b

B1a B1a

B8a B8a

B8a B8a

B8aB8a

F3c F3c F3c

F3cF3cF3c

B8a B8a

B8aB8a

B8a B8a

F3c F3c F3c

F3cF3cF3c

F3a

F3a

F3a

F3a

B1a

B1a

B1a

B1a

B1yB1yX1

B1y

B1y

B1y

B1y

B1y

B1y

X1

X1

B1w

B1w

EX

EX

EX

EX EX

B1y B1y

UCc UCc UCc UCc UCc

X1 X1

EX

EX

EX

EX

EX

EX

D1

D1

UCc

UCc

UCc

EXEX

UCc

UCc

UCc

X1

X1

B8a

F3cF3c

F3c

F3c

F3c

F3cF3c

F3c F3c

F3c

F3c

1 1

1 1

1 1

1 1

1 1

1 1

B1w

B1w

1 1

2 2

2 2

2 2

2 2

3 33

1 1

2 1

2 2 2 2

1 3 3

2 2 2 2 2

2 2 2 2 a b a a aa b bb b a a aa c d d d c c e e e f g ab c d c g f e c e c e d c d c a a a b b b b b b a a a a a a a a f f f f ffff f f g g gg g g c a bab c c

F3c

F3c

F3cF3c

F3c

F3c

F3c F3c

2 2

2 2

B8a

B8a

B8a B8a

B8a

B8a ff f f f f ff g g g g g g

B8a

B8a

B8a

B8aB8a b b b gg

3 3 a a a a a b b a b a ab a b b a a b ba c c c c b ab a a b b a c c c c a b c b a c1 b a

ABHN1 - 2

b ab a b a b

1 1 1

EX EX

EX EXEX EX

2 2 2

2 2

UCc

UCc UCc c c c c c c

X0

DS

X0

DS

b

B8a

B8a

3 3

X0

DS

X0

DS

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LOUNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIOACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

A-B043

PATIENT

SAFETY

MANAGER

A-B044

RISK

MANAGER

A-B041

ASSISTANT

LOG

A-B040

OFFICE

A-B066

AUDITORIU M

ab b a b a b a ab ab

N

KEY PLAN

GENERAL NOTES

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES

SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING

PLAN.

B. COORDINATE INSTALLATION OF LIGHTING AND LIG HTING CO NTROLS

W ITH PHASING PLANS. REFER TO ARCHITECTURAL DRAW INGS FOR

PHASING INFORM ATIO N.

C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO M ORE THAN

THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQ UIPMENT GRO UNDING CONDUCTOR.

D. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF

EM ERGENCY AND NO RMAL BRANCH W IRING DEVICES SHALL HAVE

DIVIDERS BETW EEN DEVICES.

E. UNLESS NOTED O THERW ISE ALL NORM AL LIGHTING CIRCUITS ARE

FED FROM PANEL ABHN1, CRITICAL FROM PANEL ABHCR1 AND

LIFESAFETY IS FEED FRO M PANEL ABHLS1.

F. LIGHT FIXTURES INDICATED AS EXISTING (EX) SHALL BE FIXTURES

SALVAGED DURING DEMOLITION.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:1

A M

EL101

LOW ER LEVEL LIGHTING PLAN

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"EL101

1 LOWER LEVEL LIGHTING PLAN

N

PLAN NOTES

1. RELOCATE EXISTING LIGHTING INTO CEILING. REFEED LIGHTING TO

CIRCUIT INDICATED.

G

G F

G F

J

J

J

T P

T P

/G F

T P

T P

GF/TP

G F

/T P

TP

T V

T P

T P

46" MH

RF

MW

GF

GF

T P

T P

TP

TP

TP

M F

D

J

J

TP

TP

T P

T P

T V

GF

G F

GF

G F

46" MH

46" MH

M H

TP

T P T P

TP

T P

/G F

T P

/G

FT

P

T P

TP

T P

E K

G

U C

/R F

A

T P

T P

46" MH

M H

M H

TP

J

TP

TP

TP

T P

TP

T P

T P

T P

J J

J

T P

T P

T P

T P

T P

/G F

TP

T P

T P

J

J46" MH

M H

TP

J

J

J

TP

TP

TP

TP

TP/GF

TP

TP

TP

TP

TP/GF

TP

TP TP

TP

TP/GF

TP

J

U C

/R F

W A

R M

E R

46" MH

46" MH

EPO

E P

O

EPO

E P

O

EPO

EPO

EPO

EPO

EPO

T P

T P

J

J

J

J

T P

TV

J

J

J

J

J

AAP

CC

J

J

J

TV

J

J

J

J

A

457 3.5

B

C

D

E

F

2.589

ABHEQ4

ETR

ETR

ETR

6 6

ABHN1

ABLNDP1

ABLN1

AAUPS

ABLCR1

ABLLS1

ABHLS1 ABHCR1 ABHEQ1

ELECT.

A-B153

ABLN1E

ABLCR3

ABLN7

ABHEQ9

A B

H E

Q

ABHEQ7

X -A

B H

E Q

12 12

1 1

136 13

16,18

14 4

1111 2

29 29

1 1

7 14

8 7

6 6

X -A

B H

E Q

1-EF30B

1717 ACCU-1ACCU-2

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION

A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LOUNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIOACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

INDOOR

UNIT

INDOOR

UNIT

ABLCR3 - 36,38

ABLCR3 - 33,35

ABHCR1

-7,9,11

ABHCR1

-8,10,12

ABHEQ6

ABLN4 ABHN4

A-B016

ELEC

TO ABHEQDP2

IN ELECTRICAL

SW ITCHGEAR A-B140

N

KEY PLAN

GENERAL NOTES

A. CRITICAL CIRCUITS SHOW N SHALL ORIGINATE FROM CRITICAL

PO W ER PANEL ABLCR3.

B. NORMAL CIRCUITS SHOW N SHALL ORIGINATE FROM NORM AL

PO W ER PANEL ABLN1E AND ABLN7.

C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN

THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL

HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING

CONDUCTOR.

D. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND

TYPES OF EMERGENCY AND NORMAL BRANCH W IRING

DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.

E. DISTRIBUTIO N PANEL ABHEQDP1 IN ELECTRICAL SW ITCH GEAR

ROOM A-B140.

F. CONTRACTOR SHALL REFER TO SIEM ENS SITE SPECIFIC

DRAW INGS FO R ADDITIO NAL INFORMATION.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:2

A M

EP101

LOWER LEVEL POWER PLAN

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"EP101

1 LOWER LEVEL POWER PLAN

PLAN NOTES

1. BO X MOUNTED TRANSFORMER LOCATED ABOVE THE CEILING TO

CONTRO L SENSOR OPERATED FAUCET O N FIXTURE(S) BELOW . PROVIDE

120V-1PH POW ER IN A JUNCTION BOX ABOVE THE CEILING W IRE TO

RECEPTACLE CIRCUIT IN TOILET ROOM. STUB A 0.75" CONDUIT (FOR LOW

VO LTAGE W IRING) ABOVE THE CEILING AND EXTEND DOW N TO AN

ELECTRICAL W ALL BOX LO CATED BELO W EACH LAVATO RY. REFER TO

DIVISION 22 DRAW INGS. PROVIDE TRANSFORMER AND LOW VOLTAGE

W IRING. COORDINATE ALL W ORK W ITH THE DIVISIO N 22.

2. LOCATION FOR PANEL ABHEQ4. EXTEND FEEDER FOR PANEL ABHEQDP1

TO THIS LOCATION AND CONNECT.

3. REW ORK RACEW AY FOR PET / CT SCANNER TO RELOCATED EQUIPM ENT

IN THIS ROOM .

4. PRO VIDE 20A/120V CONNECTION TO POW ER SUPPLY LOCATED ABOVE

CEILING FOR LOCAL SOUND MASKING SYSTEM.

5. PANEL FOR NEW PET / CT SCANNER EQUIPMENT. FEED FROM ABHEQ DP1.

6. PRO VIDE 20A/120V CONNECTION TO ELECTRIC SECURITY DOOR

HARDW ARE POW ER SUPPLY.

7. REFER TO IMAGING EQUIPM ENT MANUFACTURER DRAW INGS AND

PRO VIDE ALL REQUIRED JUNCTION BOXES, RACEW AYS, ETC.

8. PRO VIDE 20A/480V/3-PHASE CONNECTION TO EXHAUST FAN ON ROOF OF

SECOND FLOOR.

9. PRO VIDE 20A/120V/1-PHASE CONNECTION TO HOOD.

N

39.12 kVA 24.56 kVA (68 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Load: 13.92 kVA 13.64 kVA 11.57 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 1976... -- -- -- 38

35 -- -- -- 1976... 1976... 2 30 A ACCU-1 36

33 ACCU-2 30 A 2 1976... 1400... 1 20 A Receptacle Room... 34

31 EPO'S FOR 4 SCAN... 20 A 1 100 VA 1400... 1 20 A Receptacle Room... 32

29 Receptacle CORRIDO... 20 A 1 900 VA 180 VA 1 20 A HOOD 30

27 AUTODOOR 20 A 1 900 VA 900 VA 1 20 A AUTODOOR 28

25 Receptacle STAFF... 20 A 1 1500... 720 VA 1 20 A Receptacle DOSE... 26

23 Receptacle NM... 20 A 1 360 VA 360 VA 1 20 A Receptacle NM... 24

21 Receptacle NM... 20 A 1 1080... 1080... 1 20 A Receptacle NM... 22

19 Receptacle NM SCAN ... 20 A 1 720 VA 720 VA 1 20 A Receptacle NM SCAN ... 20

17 Receptacle DOSE... 20 A 1 720 VA 720 VA 1 20 A Receptacle DOSE... 18

15 Receptacle HOT LAB... 20 A 1 720 VA 720 VA 1 20 A Receptacle DOSE... 16

13 Receptacle PET / CT 1... 20 A 1 1440... 900 VA 1 20 A Receptacle HOT LAB... 14

11 Receptacle COMBINE... 20 A 1 1080... 1080... 1 20 A Receptacle COMBINE... 12

9 Receptacle Room 3A,... 20 A 1 1080... 1440... 1 20 A Receptacle PET / CT 2... 10

7 WARMER 20 A 1 1500... 1500... 1 20 A UC REFRIGERATOR 8

5 UC REFRIGERATOR 20 A 1 1500... 720 VA 1 20 A Receptacle THYROID... 6

3 Receptacle Room... 20 A 1 1080... 1260... 1 20 A Receptacle CARDIAC... 4

1 Receptacle DOSE... 20 A 1 720 VA 720 VA 1 20 A Receptacle DOSE... 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO

Location: ELEC ROOM A-B025 Mounting: Surface A.I.C. Rating: 22KA

Panel: ABLCR3

40.97 kVA 25.48 kVA (71 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: EXISTING PANEL

Total Load: 14.20 kVA 13.86 kVA 12.90 kVA

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 1080... 1 20 A Receptacle ETR 34

31 Receptacle 20 A 1 180 VA 720 VA 1 20 A AUTO SENSOR SINK 32

29 Receptacle 20 A 1 1080... 720 VA 1 20 A Receptacle 30

27 Receptacle 20 A 1 900 VA 1260... 1 20 A Receptacle 28

25 MICROWAVE 20 A 1 1500... 1440... 1 20 A Receptacle 26

23 MULTIFUNCTION... 20 A 1 1200... 1220... 1 20 A Receptacle 24

21 Receptacle 20 A 1 1620... 1260... 1 20 A Receptacle 22

19 Receptacle 20 A 1 1400... 1580... 1 20 A Receptacle 20

17 Receptacle 20 A 1 900 VA 1664... -- -- -- 18

15 Receptacle 20 A 1 1220... 1664... 2 20 A Receptacle 16

13 Receptacle 20 A 1 1260... 1080... 1 20 A Receptacle 14

11 Receptacle 20 A 1 1260... 2160... 1 20 A Receptacle 12

9 Receptacle 20 A 1 1080... 1260... 1 20 A Receptacle 10

7 Receptacle 20 A 1 1080... 1440... 1 20 A Receptacle 8

5 Receptacle 20 A 1 1260... 1440... 1 20 A Receptacle 6

3 Receptacle 20 A 1 1620... 900 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 1440... 1080... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO

Location: ELEC ROOM A-B025 Mounting: Surface A.I.C. Rating: 22KA

Panel: ABLN7

295 kVA 295 kVA (355 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Total Load: 98.33 kVA 98.33 kVA 98.33 kVA

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16

13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14

11 -- -- -- 5000... 0 VA 1 20 A Spare 12

9 -- -- -- 5000... 0 VA 1 20 A Spare 10

7 ABHEQ7 150 A 3 5000... 0 VA 1 20 A Spare 8

5 -- -- -- 2416... 2416... -- -- -- 6

3 -- -- -- 2416... 2416... -- -- -- 4

1 ABHEQ8 80 A 3 2416... 2416... 3 80 A ABHEQ9 2

CKT Circuit Description Trip Poles A B C

Poles Trip Circuit Description CKT

Voltage: 480/277 Wye-3PH-4W Mains Rating: 400 A Supply From: ABHEQDP2 Enclosure: Type 1 Mains Type: MCB

Location: ELEC A-B016 Mounting: Surface A.I.C. Rating: 35KA

Panel: ABHEQ6

10. PULL BOX PER VENDOR REQUIREMENTS. REFER TO SITE SPECIFIC

DRAW INGS FO R EXACT LOCATION AND REQUIREM ENTS.

11. DUCT BANK PER VENDOR REQUIREM ENTS. REFER TO SITE SPECIFIC

DRAW INGS FO R EXACT LOCATION AND REQUIREM ENTS.

12. COORDINATE EXACT MOUNTING OF W IREW AY W ITH ARCHITECT AND SITE

SPECIFIC DRAW INGS.

13. ENCLOSED BREAKER FOR TRANSFO RMER. REFER TO SITE SPECIFIC

DRAW INGS FO R EXACT LOCATION AND REQUIREM ENTS.

14. UTILIZE 20A/1P SPARE BREAKER "11" IN PANEL ABLLS1.

15. PRO VIDE 20A/480/3-PHASE CO NNECTIO N FOR EXHAUST FAN ON ROOF.

REFER TO DIV. 23 FO R LOCATION ON ROOF.

16. PRO VIDE LIGHTING PROTECTION ON FAN ENCLOSURE. BO ND #8 BARE

COPPER BOND BETW EEN PRO TECTOR AND EXISTING LIGHTNING

CONDUCTO R O N RO OF. EXOTHERMIC W ELD CONNECTIONS.

17. PRO VIDE 30A/208V/1-PHASE CONNECTION FOR SPLIT SYSTEM. INTERIOR

UNIT SHALL BE FED FROM THE EXTERIOR ACCU. MAKE ALL POW ER AND

CONTRO L CONNECTIONS BETW EEN UNITS. FEED TO ACCU SHALL BE 3 -

#10, 1 - #10 G ND., .75" C. FEED BETW EEN ACCU AND INTERIOR UNIT SHALL

BE 2 #10, 1 - #10 GND., IN .75" C.

18. REFEED EXISTING TO REMAIN DEVICES W ITH CIRCUIT INDICATED.

19. COORDINATE RO UTING O F FEEDERS W ITH OTHER TRADES AND UTILITIES

ABOVE CEILING.

20. FIRESTOP CONDUIT AT W ALL PENETRATION.

ABLCR1

Revisions: Date:

295.00 kVA 52.0 kVA (62.5 A)

TOTAL CONNECTED ESTIMATED DEMAND

NOTES:

5 Space 0.00 kVA -- -- -- -- --

4 Space 0.00 kVA -- -- -- -- --

3 Spare 0.00 kVA -- 3 20 A -- --

2 Spare 0.00 kVA -- 3 20 A -- --

1 ABHEQ6 295.00 kVA 400 A 3 20 A REFER TO SINGLE LINE SHEET E701

CKT

CIRCUIT

DESCRIPTION

APPROX.

CONNECTED

LOAD

FRAME

SIZE POLES

TRIP

SETTING WIRE SIZE

SEE

NOTE

Feeder Size: Spec. Ref. #:

Voltage: 480/277 Wye-3PH-4W Mains Rating: 800 A

Supply From: Enclosure: Type 1 Mains Type: MCB Location: MECHANICAL ROOM A-B148 Mounting: SURFACE A.I.C. Rating: 35KA

DISTRIBUTION PANEL: ABHEQDP2

200 A

200 A

ABLNDP1

52 kVA (62.5 A)

J

J

S

FACP

S

SD

SD

VFD VFD VFD VFD

VFD

N

KEY PLAN

ABHNMCC1

TX-ABLEQ-3

ABLEQ5 ABHEQ5

1-AC30

1.5"C

4"C

C1a

C1a

C1a

C1a

C1a

C1a

C1a

C1a

C1a

C1a

C1a

C1a

ABHLS1 - 2

ABHLS1 - 2

ABHLS1 - 2

ABHLS1 - 2ABHLS1 - 2

ABHEQ5 - 1

ABHEQ5 - 1 ABHEQ5 - 1

ABHEQ5 - 1ABHEQ5 - 1

ABHEQ5 - 1 ABHEQ5 - 1

1-HCP30

ABHNMCC1

ABHEQ5 - 2,4,6

ABHEQ5 - 3,5,7

ABLEQ5 - 1

ABLEQ5 - 2

A-B148

MECHANICAL

ROOM

1-RF30

7.5 HP

ABHNMCC1

20 HP

20 HP20 HP

20 HP

VFD

VFD

VFD

VFD

VFD

1-CCP30

TO ELEC. SW GR

RM. A-B140

20HP

SUPPLY

FAN

20HP

SUPPLY

FAN

20HP

SUPPLY

FAN

20HP

SUPPLY

FAN

3#4/0,1#4, 2.5"C

SUPPLIED

W ITH 1-AC30

400A DISC.

250A FUSES

TO ABHNM CC1

(SEE PLAN NOTE #5)

10HP

1-RF30

3#10,1#10, .75"C

VFD W ITH

DISC.

TO ABHEQ 5

3#10,1#10, .75"C

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:3

A M

EP102

ENLARGED MECHANICAL ROOM

ELECTRICAL PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"EP102

1 ENLARGED MECHANICAL ROOM ELECTRICAL PLAN

PLAN NOTES

1. INSTALL DUCT SMOKE DETECTO R IN NEW DUCTW ORK .

CONNECT INTO ADDRESSABLE INITIATION CIRCUIT. PROGRAM

SYSTEM TO INCORPORATE NEW DETECTOR.

2. MOUNT C1 FIXTURES AT 9'-0" AFF.

3. EXISTING FIRE ALARM ZONE CONTRO L PANEL FCP-BA.

4. MAKE SINGLE POINT CONNECTION TO 1-AC30 FROM MCC,

ABHNM CC1. PROVIDE FUSED DISCONNECT. COORDINATE

TERMINATIO N W ITH AHU MANUFACTURER.

5. REPLACE VFD BUCKET FOR SF30 W ITH 400A DISCONNECT

BUCKET W ITH 250A THERM AL MAGNETIC CIRCUIT BREAKER.

6. MAKE 20A/120V, 1 PHASE CONNECTION FROM AVAILABLE

CIRCUIT IN PANEL ABLEQ3 FOR AHU LIGHTING AND

RECEPTACLES.

7. MAKE 20A/120V, 1 PHASE CONNECTION FROM AVAILABLE

CIRCUIT IN PANEL ABLEQ3 FOR UV LIGHTS IN AHU.

8. RECO NNECT EXISTING 120V CIRCUIT TO NEW CONTROL PANEL.

9. PRO VIDE 30A, 480V/3P COMBINATION STARTER W ITH START/STOP

CONTACTS AND INDICATOR LIG HTS. COORDINATE W ITH DIVISION

23 BMS CONTROL W IRING TO STOP/START CONTACTS. 3#12, 1#12

GND. IN .75"C.

10. PRO VIDE 20A, 120V CONNECTION TO POW ERED ISOLATION

DAM PERS. COORDINATE FINAL LOCATION W ITH DIVISION 23.

11. PROVIDE REMOTE INDICATOR LIGHT FOR DUCT SM OKE

DETECTOR. MOUNT TO SIDE OF AHU.

12. PRO VIDE 30A/480V-3PHASE CO NNECTIO N FROM AVAILABLE SPARE

IN PANEL "ABHEQ5".

N

SCALE: 12" = 1'-0"

POWER FEED - 1-AC30

SCALE: 12" = 1'-0"

POWER FEED - 1-RF30

Revisions: Date:

ATS ATS ATS ATS

EQ8 ABHEQDP2

AMS 3 AMS 1 AMS 2

TO GBN

ROOM

A-B139

EP402

ENLARGED SW ITCHGEAR ROOM ELECTRICAL PLAN

TO ABHEQ6

13. INSTALL FEEDER ABOVE CEILING. COORDINATE INSTALLATION

W ITH O THER SERVICES BEING INSTLALED IN THIS AREA.

14. ROUTE FEEDER PARALLEL TO EXISTING CONDUIT RUNS AT 11'-2"

TO BOTTOM OF CONDUIT. COORDINATE W ITH O THER TRADES

W ITHIN AREA.

15. FIRESTOP CONDUIT AT W ALL PENETRATION.

16. ROUTE FEEDER PARALLEL TO EXISTING CONDUIT RUNS AT 10'-6"

TO BOTTOM OF CONDUIT. COORDINATE W ITH O THER CONDUIT

RUNS W ITHIN AREA.

17. UTILIZE SOARE 800A BREAKER IN CUBICLE 52-F12 FOR

EM ERGENCY FEED TO ATS-EQ8

18. UTILIZE EMPTY CUBICAL FOR NORMAL FEED TO ATS-EQ8 IN

SECTION 2 OF SUBSTATION AMS3. OUTFIT CUBICAL AS REQUIRED

TO FOR 800A POW ER BREAKER. PROVIDE BREAKER COM PATIBLE

TO EXISTING GE AKD-8 SW ITCHG EAR. BREAKER SHALL HAVE A

SCCR OF 35KAIC.

19. PRO VIDE 800A, 480V, 3-PH-4 W IRE AUTOM ATIC TRANSFER SW ITCH

W ITH BYPASS/ISOLATION SW ITCH. INTEGRATE CONTROLS INTO

THE EXISTING PLC CONTRO L SYSTEM AND PROGRAM UNIT INTO

SYSTEM. PROVIDE AND MOUNT SW ITCH ON 4" CONCRETE

HOUSEKEEPING PAD.

20. INSTALL DISTRIBUTION PANEL ADJACENT TO ATS. COORDINATE

INSTALLATIO N O F CONDUIT W ITH EXISTING CONDUIT RUNS

ABOVE.

SCALE: 1/8" = 1'-0"

17 15

20 14 15

F

F

F

F

F

F

F

F

F

F

F

F

F

F

S

F

F

S

S

F

F

S

S

S

S

S

S

S

F

F

F

S

F

F

S S

F

S

F

F

F

F

F

F

F

F

F

F

F

F

F

FACP

S

S

D DDD

D D

D

F

F

F

F

F

A

457 3.5

B

C

D

E

F

2.58

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LOUNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIOACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

N

KEY PLAN

GENERAL NOTES

A. EXISTING FIRE ALARM DEVICES AND SUPPORTING NETW ORK CABLING

ARE SUPPORTED BY FIRE CONTROL PANEL FCP-BA. REFER TO

LOCATION SHOW N ON EP102.

B. ALL SYSTEM INTEGRATION SHALL BE COMPLETED BY AADCO

(317-781-7680). THIS IS TO INCLUDE SYSTEM TERMINATIONS,

PRO GRAMING AND TESTING.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ ja s u m m e rs .r v t

/2

/2

:1

:3

A M

EY101

LOW ER LEVEL FIRE ALARM PLAN

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 MSG JAS

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"EY101

1 LOWER LEVEL FIRE ALARM PLAN

N

Revisions: Date:

PLAN NOTES

1. BO X MOUNTED TRANSFORMER LOCATED ABOVE THE CEILING TO

CONTRO L SENSOR OPERATED FAUCET O N FIXTURE(S) BELOW . PROVIDE

120V-1PH POW ER IN A JUNCTION BOX ABOVE THE CEILING W IRE TO

RECEPTACLE CIRCUIT IN TOILET ROOM. STUB A 0.75" CONDUIT (FOR LOW

VO LTAGE W IRING) ABOVE THE CEILING AND EXTEND DOW N TO AN

ELECTRICAL W ALL BOX LO CATED BELO W EACH LAVATO RY. REFER TO

DIVISION 22 DRAW INGS. PROVIDE TRANSFORMER AND LOW VOLTAGE

W IRING. COORDINATE ALL W ORK W ITH THE DIVISIO N 22.

2. LOCATION FOR PANEL ABHEQ4. EXTEND FEEDER FOR PANEL ABHEQDP1

TO THIS LOCATION AND CONNECT.

3. REW ORK RACEW AY FOR PET / CT SCANNER TO RELOCATED EQUIPM ENT

IN THIS ROOM .

4. PRO VIDE 20A/120V CONNECTION TO POW ER SUPPLY LOCATED ABOVE

CEILING FOR LOCAL SOUND MASKING SYSTEM.

5. PANEL FOR NEW PET / CT SCANNER EQUIPMENT. FEED FROM ABHEQ DP1.

6. PRO VIDE 20A/120V CONNECTION TO ELECTRIC SECURITY DOOR

HARDW ARE POW ER SUPPLY.

7. REFER TO IMAGING EQUIPM ENT MANUFACTURER DRAW INGS AND

PRO VIDE ALL REQUIRED JUNCTION BOXES, RACEW AYS, ETC.

8. PRO VIDE 20A/480V/3-PHASE CONNECTION TO EXHAUST FAN ON ROOF OF

SECOND FLOOR.

9. PRO VIDE 20A/120V/1-PHASE CONNECTION TO HOOD.

T2

B

T2

DETAIL: B = DETAIL DESIGNATION

T2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

T2 = SHEET W HERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

CONDUIT RUN IN W ALL OR ABOVE CEILING.

CONDUIT RUN IN SLAB OR UNDERGROUND.

CABLE MANAGEMENT SYSTEM PATHW AY.

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERW ISE.

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SW ITCH

BLDG - BUILD ING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTW N - BETW EEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - C IRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICERS REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - D IAMETER

DIM - D IMENSION

DIV - D IVISION

DN - DOW N

DW G - DRAW ING

EA - EACH

EC - ELECTRICAL (D IVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EX - EXISTING

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION (D IVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT

FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC (DIVISION 23)

HP - HORSE POW ER OR H IGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

IP - INTERNET PROTOCOL

KEC - KITCHEN EQUIPMENT

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM

MIN - MIN IMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE D IAMETER

OFCI - OW NER FURNISHED CONTRACTOR INSTALLED

OFOI - OW NER FURNISHED OW NER INSTALLED

PC - PLUMBING (DIVISION 22)

PLBG - PLUMBING

POE - POW ER OVER ETHERNET

PTZ - PAN / TILT / ZOOM

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY CONTRACTOR

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

UTP - UNSHIELDED TW ISTED PAIR

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W / - W ITH

W /O - W ITHOUT

W P - W EATHERPROOF

ZVC - ZONE VALVE CABINET

1. ALL CONDUIT SLEEVES THRU W ALLS AND FLOORS, NOT SPECIFICALLY SHOW N ON DRAW INGS BUT REQUIRED FOR COMPLIANT INSTALLATION OF CABLING

SHALL BE PROVIDED AS PART OF THE SCOPE OF W ORK.

2. ALL FIRE STOPPING OF CONDUIT SLEEVES AND CABLE TRAY PENETRATIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE AND THOROUGH COORDINATION OF ALL PATHW AYS BEING PROVIDED. ANY PATHW AYS THAT ARE PROVIDED THAT CAUSE CABLING INSTALLATION TO BE NON-COMPLIANT SHALL BE BROUGHT TO THE ATTENTION OF THE COR PRIOR TO THE

INSTALLATION OF CABLING.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL POW ER REQUIREMENTS W ITHIN THE TECHNOLOGY ROOM(S) PRIOR TO ROUGH-INS AND BUILD-OUT OF EACH TECH ROOM. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING SIGNED-OFF DETAILED COORDINATION DRAW INGS INCLUDING ALL FIRE SUPPRESSION, PLUMBING, HVAC, ELECTRICAL, AND TECHNOLOGY W ORK W ITHIN THE ROOM(S). THE COORDINATION DRAW INGS SHALL SHOW FLOOR PLANS AND W ALL ELEVATIONS INCLUDING ALL TRADES' W ORK W ITHIN THE SPACE(S) PR IOR TO ANY TRADES W ORKING W ITHIN THE

SPACE(S).

5. THE DRAW INGS INDICATE THE QUANTITY, TYPE AND GENERAL LOCATION OF VOICE/DATA/CATV/VIDEO OUTLETS REQUIRED IN EACH SPACE. A FINAL DEVICE LOCATION PLAN FOR EACH SPACE W ILL BE ISSUED PRIOR TO START OF THE INSTALLATION. THE CONTRACTOR SHALL INCLUDE IN THE BID ANY COSTS ASSOCIATED W ITH FINAL DEVICE LOCATIONS AS THERE W ILL BE NO ALLOW ANCE AFTER AW ARD OF CONTRACT.

6. THE CONTRACTOR W ILL PROVIDE THE CABLING PATHW AYS AND POW ER FOR TECHNOLOGY SYSTEMS. THE CONTRACTOR SHALL INCLUDE COST TO W ALK THROUGH EACH BUILDING DURING THE PATHW AY ROUGH-IN PHASE TO VERIFY INSTALLATION W ILL ACCOMMODATE THE CABLING PHASE OF THE

PROJECT.

7. ALL LOW VOLTAGE W IRING ABOVE ACCESSIBLE CEILINGS SHALL BE INSTALLED IN NEW J-HOOK CABLE MANAGEMENT PATHW AYS. W HERE EXISTING CABLETRAY AND/OR J-HOOK PATHW AYS ARE AVAILABLE FOR USE, THE CONTRACTOR MAY REQUEST PERMISSION TO UTILIZE FROM THE COR.

8. ALL W ORK IN PATIENT CARE AREAS SHALL BE DONE IN ACCORDANCE W ITH ALL INFECTION CONTROL AND PATIENT SAFETY STANDARDS AND

REQUIREMENTS.

9. THE CONTRACTOR SHALL REFERENCE ARCHITECTURAL DRAW INGS FOR PROJECT PHASING REQUIREMENTS.

GENERAL NOTES

SECURITY SYMBOLS

CC

1 CCTV SYSTEM CEILING M OUNTED CAM ERA. REFER TO CAMERA SCHEDULE FOR MO UNTING HEIGHT AND

CAMERA SPECIFICATIONS. SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE.

IM DESK MOUNTED INTERCOM MASTER STATION.

CE

PROVIDE INTERFACE FROM CARD ACCESS SYSTEM INTO ELEVATOR CONTROLLER INCLUDING ALL NECESSARY

HARDW ARE, PROGRAMMING AND CABLING AS COORDINATED W ITH ELEVATOR CONTRACTOR.

MD CEILING MOUNTED MOTION DETECTOR.

PB DESK MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE.

JS CCTV SYSTEM REMOTE JOYSTICK/CON TROLLER AN D KEYPAD OPER ATOR'S STATION.

GLASS BREAK.GB

X

PP DESK M OUNTED PANIC/DURESS BUTTON.

SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS

CC

CCTV SYSTEM W ALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. PROVIDE CAMERA, CABLING AND 1-GANG

BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.

PS

LOCAL LOW VOLTAGE POW ER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA.

PROVIDE POW ER SUPPLY MOUNTED ABOVE CEILING, LOW VOLTAGE W IRING TO LOCAL CAMERA AND 120V POW ER INTO

LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POW ER SUPPLY.

IC

W ALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERW ISE). PROVIDE INTERCOM, CABLING AND 1-

GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.

DM

DOOR POSITION SW ITCH W ITH W IRING. PROVIDE CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR OPENINGS. REFER TO

SECURITY ROUGH-IN DETAILS.

EL

ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE W IR ING AND CONDUIT PATH W AYS FR OM DOOR FRAM E TO COM M ON SM S JUNCTION BOX ABOVE ACC ESSIBLE CEILING. REFER TO SECUR ITY R OUGH-IN

DETAILS.

EM

ELECTRONIC M AG LOCK AND INSTALLATION BY OTHERS. PR OVIDE LOW VOLTAGE W IRING AND CONDUIT PATHW AYS FR OM DOOR FRAM E TO COM M ON SM S JUNCTION BOX ABOVE ACC ESSIBLE CEILING. REFER TO SECUR ITY R OUGH-IN

DETAILS.

ES

ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE W IRING AND CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN DETAILS.

LB

RX

REQU EST TO EXIT SW ITC H IN D OOR HARDW AR E BY OTHERS. PROVIDE LOW VOLTAGE W IRING AND CONDUIT PATH W AYS FR OM DOOR FRAM E TO COM M ON SM S JUNCTION BOX ABOVE ACC ESSIBLE CEILING. REFER TO SECUR ITY R OUGH-IN

DETAILS.

HD

HAN DICAP DOOR OPERATOR M OTOR ASSEM BLY BY OTHERS. PROVIDE LOW VOLTAGE W IR ING, IN TERFACE W ITH SM S AND DOOR ACTUATOR BUTTONS AND 120V POW ER CONN ECTION , AND CON DUIT FR OM DOOR FRAM E TO COM M ON SM S

JUN CTION BOX ABOVE ACCESSIBLE C EILING. REFER TO SECURITY ROUGH-IN DETAILS.

HA

W ALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. PROVIDE ALL LOW VOLTAGE W IR ING, INTERFACE W ITH SMS AND DOOR MOTOR AND BOX AS REQUIRED BY SYSTEM MANUFACTURER W ITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY

ROUGH-IN DETAILS.

HO

FA

W ALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN W ITH POW ER SUPPLY INSTALLED BY OTHERS. PROVIDE LOW VOLTAGE W IRING FROM POW ER SUPPLY TO HOLD OPEN AND INTERFACE W ITH SMS AND 120V POW ER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. SUBSCRIPT "FA" INDICATES DEVICES POW ERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE

ALARM SYSTEM REQUIRED FOR DOOR RELEASE. REFER TO SECURITY ROUGH-IN DETAILS.

CR

W ALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE CARD READER, CABLING AND 1-GANG BOX W ITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-

IN DETAILS.

CR EL

ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED W ITH ELEVATOR CONTRACTOR. W IRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE W ITH ELEVATOR CONTROLLER AND SMS, COORDINATE W ITH ELEVATOR CONTRACTOR.

REFER TO SECURITY ROUGH-IN DETAILS.

KC

W ALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE DEVICE, CABLING AND 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING.

K W ALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERW ISE). PROVIDE KEYPAD, CABLING AND 1-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING.

MD

W ALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERW ISE). PROVIDE MOTION DETECTOR, W ALL MOUNT HARDW ARE, CABLING AND 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.

PP W

W ALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERW ISE). PROVIDE BUTTON, CABLING AND 1-GANG

BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.

X W ALL MOUNTED SECURITY SYSTEM W IRING OUTLET MOUNTED BELOW COUNTER TOP. PROVIDE GROMMETED FACEPLATE, SECURITY SYSTEM CABLING AND 2-GANG BOX W ITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE

ACCESSIBLE CEILING.

CM

W ALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERW ISE). PROVIDE JACK, FACEPLATE, CABLING AND 1-GANG BOX W ITH 1" CONDUIT TO ABOVE CORRIDOR CEILING.

MIC

CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. PROVIDE MICROPHONE, CABLING AND 1-GANG BOX

MOUNTED IN CEILING.

BR

W ALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE READER, CABLING AND 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN

DETAILS.

X

X

MD

PB W

W ALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERW ISE). PROVIDE

BUTTON, CABLING AND 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.

ELECTRONIC LATCH BOLT MONITORING. HARDW ARE AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE W IRING AND CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON…

This is the start of the file's text. The full file is on GovTribe.