This document package includes plans and specifications for a federal construction project. The solicitation is for relocating nuclear medicine services at the Richard L. Roudebush VA Medical Facility in Indianapolis, Indiana. Work includes renovating existing spaces and relocating equipment to accommodate new PET/CT scanners. The project scope involves demolishing some walls and fixtures, installing new electrical, data, security and medical gas systems, and modifying HVAC. Bids are due by late February 2021, with work to be completed by early 2022. The estimated value is between $1-5 million. The contracting agency is the VA.
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Type B1
RECESSED LED ARCHITECTURAL LAY-IN FIXTURE
HOUSING: DIE-FORMED COLD-ROLLED STEEL. HINGED OPTIC SYSTEM.
SPRING LOADED LATCHES.
FINISH: NON-GLARE HIGH-REFLECTANCE W HITE POW ER COAT
FINISH, PAINTED AFTER FABRICATION.
OPTICS: HIGH TRANSMISSION EXTURDED ACRYLIC LENSES.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 90 CRI.
4000K
CERTIFICATION: UL1598, UL2108, CSA LABEL. EMERGENCY FIXTURES- UL924.
DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED.
DAMP LOCATION LABELED. IC RATING - STANDARD
DIMMING: 0-10VDC 5% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
MANUFACTURER: CREE LIGHTING "CR" SERIES
VARIATIONS: “B1a” 2’ X 4’ 3000 LM, 34 W , NOMINAL “B1b” 2’ X 4’ 4000 LM, 33 W , NOMINAL “B1c” 2’ X 4’ 5000 LM, 50 W , NOMINAL
“B1w” 2’ X 2’ 2000 LM, 22 W , NOMINAL “B1y” 2’ X 2’ 3200 LM, 32 W , NOMINAL
B1
Type B8
LED MRI COMFORT FIXTURE
HOUSING: 0.050” ALUMINUM HOUSING AND DOOR.
FINISH: W HITE POLYESTER POW DER COAT ANTI-MICROBIAL FINISH.
OPTICS: SANITARY DOOR W ITH ACRYLIC 0.175 LENS.
CHOICE OF NATIONAL GEOGRAPHIC IMAGES.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L80, 80 CRI. 4000K
DIMMING: 0-10VDC DIMMING.
VOLTAGE: 120V OR 277V.
VARIATIONS: “B8a” 2’ X 4’ 327 LM, 39 W , NOMINAL
B8
Type F3
RECESSED LED 6” DIAMETER FLUSH LENS DOW NLIGHT FIXTURE
HOUSING: 22 GA. NON-CORROSIVE STEEL PLATFORM. J-BOX W ITH
SNAPON COVER. ACCESSABLE FROM ABOVE AND BELOW
CEILING.
REFLECTOR: ALUMINUM, ALZAK SEMI-DIFFUSE REFLECTOR. SELF-TRIMED.
45DEG BEAM SPREAD.
LAMPS: LED LIGHT SOURCE, 50,000 HOUR RATED AT L70, 80 CRI.
4000K
CERTIFICATION: CSA LABEL. EMERGENCY FIXTURES-UL924.
W ET LOCATION LISTED. W ITH EMERGENCY OPTION, DAMP
LOCATION LISTED. NON-IC RATING
IP65 RATED 16 GA. COLD ROLLED STEEL STAMPINGS. CLEAR
HIGH IMPACT POLYCARBONATE LENS.
DIMMING: 0-10VDC 10% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
MANUFACTURER: CREE LIGHTING "KR" SERIES
VARIATIONS: “F3a” 6” 45DEG 1100 LM, 15 W , NOMINAL “F3b” 6” 45DEG 1500 LM, 19 W , NOMINAL “F3c” 6” 45DEG 2000 LM, 27 W , NOMINAL
F3
Type U2
LED UNDERCABINET FIXTURE
HOUSING: 20 GA STEEL HOUSING.
FINISH: POLYESTER POW DER COAT ANTI-MICROBIAL FINISH. W HITE.
OPTICS: HIGH IMPACT ACRYLIC LENS.
LAMPS: LED LIGHT SOURCE, 4000K
CERTIFICATION: DAMP LOCATION LISTED.
SW ITCHING: W ALL SW ITCH.
LINKS: OPTIONAL LINKING CONNECTOR CORDS.
VOLTAGE: MVOLT 120V - 277V.
VARIATIONS: “UCc” 4’ 2240 LM, 28 W , NOMINAL
UC
Type X1
LED EXIT SIGN
HOUSING: DIE-CAST ALUMINUM BODY. W HITE TEXTURED FINISH.
MOUNTING: UNIVERSAL W ALL, CEILING, END MOUNTING.
LAMPS: LED LIGHT SOURCE, RED STENCIL LETTERS. BREAK OUT CHEVRONS.
CERTIFICATION: DAMP LOCATION LISTED. EMERGENCY FIXTURES-UL924
VOLTAGE: UNIVERSAL 120-277V.
VARIATIONS: “X1” SINGLE FACE EXIT.
“X2” DOUBLE FACE EXIT.
“XO” OPTIONAL W ORDING “X-RAY IN USE”
X2
Type B2
RECESSED LED LENSED LAY-IN FIXTURE
HOUSING: DIE-FORMED COLD-ROLLED STEEL. HINGED OPTIC SYSTEM.
SPRING LOADED LATCHES.
FINISH: HIGH-REFLECTANCE W HITE BAKED ENAMEL FINISH.
OPTICS: HIGH TRANSMISSION EXTURDED ACRYLIC LENSES. A12
PATTERN.
LAMPS: LED LIGHT SOURCE, 60,000 HOUR RATED AT L80, 80 CRI.
4000K
CERTIFICATION: UL1598, UL2108, CSA LABEL. EMERGENCY FIXTURES-UL924.
DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED. DAMP LOCATION
LABELED. IC RATING - STANDARD
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: UNIVERSAL 120-277V.
MANUFACTURER: CREE LIGHTING "C-TR" SERIES
VARIATIONS: “B2b” 2’ X 4’ 4300 LM, 34 W , NOMINAL
B2
Type D1
LED W ALL-MOUNTED VANITY FIXTURE – INDIRECT
HOUSING: EXTRUDED ALUMINUM CHANNEL.FASCIA DIE-FORMED
20 GA. STEEL. 14 GA ENDCAPS HINGED OPTIC SYSTEM.
ANGLED CURVED FASCIA. PERFORATED FRONT.
FINISH: W HITE FINISH.
OPTICS: 96% REFLECTANCE W HITE FINISH. VIRGIN ACRYLIC UV
STABILIZED LENSED DIFFUSER BEHIND PERFORATED FASCIA.
DIFFUSURES: TOP AND BOTTOM FROSTED ACRYLIC DIFFUSERS.
LAMPS: LED LIGHT SOURCE, 100,000 HOUR RATED AT L90, 80 CRI. 4100K
CERTIFICATION: UL1598, CSA LABEL. EMERGENCY FIXTURES-UL924.
DESIGNLIGHTS CONSORTIUM (DLC) QUALIFIED.
DAMP LOCATION LABELED.
DIMMING: 0-10VDC 1% DIMMING.
VOLTAGE: 120V OR 277V.
VARIATIONS: “D1b” 4’ 1400 LM, 18 W , NOMINAL
D1
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:0
A M
E601
LIGHT FIXTURE SCHEDULE
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
BASEMENT
FIRST
FLO OR
ABLNDP3
1600A
AB147
100A
ABLN1
100A
ABLNDP1
400A
ABLN7
100A
ABLN16
100A
ABHN5
100A
ABLN4
100A
ABHCRDP1
400A
ABLCRDP1
400A
ABHCR1
100A
ABLCR1
100A
ABHN1
100A
ABHNDP1
800A
ABT4
500kVA
UNIT SUBSTATION -
AMS1
TRANS.
ABT1
1000kVA
SW GR
AMS1
MV
SW GR ATS-CR1
400A
CRITICAL
ABHEDP1
ATS-CS1
260A
LIFESAFETY
N L
ABT5
112.5 kVA
ABHEDP1
ABHLS3
150A
ABHLS1
100A
ABT6
30 kVA
ABLLS3
100A
ABLLS1
100AUNIT SUBSTATION -
AMS3
TRANS.
FBT3
1000kVA
SW GR
AMS3
MV
SW ABHEQDP1
800A
ATS-EQ1
800A
EQUIPM ENT
E L
N
ABHEQ 1
100A
ABHEQ 4
200A
ABHEQ 7
150A
10KAIC
ABHEQ 9
80A
10KAIC
ABHEQ 8
80A
10KAIC
(NEW )
(NEW )(NEW )
ABNMCC1
600A
TRANS.
FBT2
1000kVA
SW GR
AMS2
MV
SW GR
ABHN6
ABLCR3
100A
(NEW )
GEN-3 GEN-1 GEN-2 MASTER DIST. DIST. DIST.
ABHEDP1
PARALLEL
SW GR
ATS-EQ8
800A
EQUIPM ENT
E
L
N
ABHEQDP2
800A
ABHEQ6
400A
35KAIC
(NEW )
35KAIC
(NEW )
35KAIC
(NEW )
UPS FOR IM S
(SIEMENS
SUPPLIED SYNGO
MI ACQUISITIO N
W ORKPLACE)
EPOEPO
MAIN BREAKER
480Y/277V 3 PH,
80A
480Y/277 VOLTS 3
PHASE, 4 W IRE,
PLUS GRO UND
A
480Y/277V 3 PH,
80A
B
480V, 1 PH, 20A
NCNC
NCNC
XF
C
240V, 1 PH, 25A
UPS FOR SYM BIA
CAMERA SYSTEM
(SIEMENS
SUPPLIED )
BREAKER FOR
SPECT GANTRY
(SIEMENS
SUPPLIED)
LINE
CONNECTIO N
(SIEMENS
SUPPLIED )
BREAKER FOR
CT GANTRY
(SIEMENS
SUPPLIED)
MAIN BREAKER
EPO ABLCR3-31
#14 AW G MAX.
.75"C
PANEL ABHEQ8
PANEL ABHEQ9
B
SPS LCB
MB
XF
C
UPS
#16 AW G /CL2 MAX.
.75"C
EPO
#14 AW G
.75" C
24VDC
X-RAY LIGHT
RELAY BOX
LIGHTING
CIRCUIT DOO R SW ITCH
#16 AW G
.75" C
#16 AW G
.75" C
#12 AW G
.75" C
X-RAYON
W ARNING
LIGHT
EPOEPO
MAIN BREAKER
480Y/277V 3 PH,
200A
480Y/277 VOLTS
3 PHASE,
4 W IRE, PLUS
GROUND
NCNC
NCNC
PO W ER
DISTRIBUTION
CABINET
(SIEMENS
SUPPLIED)
BREAKER EPO
ABLCR3-31
EPO
NC
NC
CT UPS ROO
COM MON POW ER DISTRIBUTION
UNIT (cPDU)(SIEMENS SUPPLIED)
PET UPS
UPS
#6 TO BUILDING
GROUND
CABLE FURNISHED BY
SIEMENS. REFER TO
SIEMENS DRAW ING S FOR
MORE INFORM ATION.
cPDU BREAKER
480Y/277V 3 PH,
150A
HEAT EXCHANGER
CABINET BREAKER
480Y/277V 3 PH, 30A
HEAT EXCHANGER
CABINET (SIEMENS
SUPPLIED)
#14 AW G
.75"C
ABHEQ4
PDC
cPDU
PPS
S
MP
EPO
24VDC
X-RAY LIGHT
RELAY BOX
X-RAY ON
W ARNING LIGHT
LIGHTING
CIRCUIT DOO R SW ITCH
#14 AW G
.75" C
#14 AW G
.75" C
#12 AW G
.75" C
#14 AW G
.75" C
EPOEPO
MAIN BREAKER
480Y/277V 3 PH,
150A
480Y/277 VOLTS
3 PHASE,
4 W IRE, PLUS
GROUND
NCNC
NCNC
PO W ER
DISTRIBUTION
CABINET
(SIEMENS
SUPPLIED)
MAIN BREAKER
EPO ABLCR3-31
EPO
NC
NC
CT UPS ROO
COM MON POW ER DISTRIBUTION
UNIT (SIEMENS SUPPLIED)
PET UPS
UPS
#6 TO BUILDING
GROUND
SIEMENS FURNISHED
CABLES. REFER TO
SIEMENS DRAW INGS
FOR MORE
INFORMATION.
ABHEQ7
#14 AW G
.75" C
EPO
MP
cPDU
PPS
PDC
#14 AW G
.75" C
24VDC
X-RAY LIGHT
RELAY BOX
X-RAY ON
W ARNING LIGHT
LIGHTING
CIRCUIT DOO R SW ITCH
#14 AW G
.75" C
#14 AW G
.75" C
#12 AW G
.75" C
A
480Y/277V 3 PH,
150A
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:0
A M
E701
SINGLE-LINE DIAGRAMS
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
NO SCALEE701
1 ELECTRICAL SINGLE LINE (PARTIAL)
CONDUIT & WIRE SCHEDULE
1 4 - #4, #4GND., 1.25"C MINIMUM SIZE
2 2 - #10, #10 GND., .75"C MINIMUM SIZE
3 4 - #4/0, #4/0GND., 2.5"C MINIMUM SIZE
4 3 - #10, #10GND., 0.75"C MINIMUM SIZE
5 4 - #2/0, 1- #2/0GND., 2"C MINIMUM SIZE
6 2 SETS 4-600 KCMIL, #1/0 GND., 4"C MINIMUM SIZE
7 4-600 KCMIL, #3 GND., 4"C. MINIMUM SIZE
8 12-#14, .75"C. MINIMUM SIZE
PLAN NOTES
1. EXISTING FEED SHALL BE EXTENDED TO THE NEW ABEQ4 PANEL.
REFER TO SHEET EP101.
2. PANEL SHALL BE REPLACED W ITH NEW PANEL FOR PET/CT-1. REFER
TO SHEET EP101 FOR PANEL LOCATION.
3. NEW PANEL FO R PET/CT-2. REFER TO SINGLE LINE DIAGRAM THIS
SHEET FOR FEEDER SIZE.
4. REPLACE SPARE 150A/3P BREAKER W ITH 200A/3P FRAM E BREAKER FOR
FEED TO NEW CT MAIN PANEL.
5. EM ERGENCY POW ER OFF BUTTON W ITH PROTECTIVE COVER. EPO
SHALL BE OF FAIL-SAFE DESIGN W ITH M ECHANICAL LATCHING
MECHANISM. CONTACTS FO R EPO SHALL BE NORMALLY CLOSED.
6. UTILIZE SPARE 800A BREAKER FOR FEED TO ATS-EQ8
7. UTILIZE SPARE CUBICLE IN SECTIO N 2 FOR INSTALLATION OF 800A
BREAKER. PROVIDE BREAKER TO MATCH EXISTING AND PREP EMPTY
CUBICLE AS REQUIRED TO RECEIVE BREAKER.
8. RUN START/CONTROL/MO NITO RING CONDUCTORS TO PARALLING
SW ITCHGEAR. PROVIDE ALL PROGRAMMING AND TESTING AS
REQ UIRED. (SOLE SOURCE TO THE MANUFACTURER)
SCALE: NONE
NM SCAN - SINGLELINE (TYPICAL)
SCALE: NONE
PET/CT 1 POWER SCHEDULE
SCALE: NONE
PET/CT 2 POWER SCHEDULE
GENERAL NOTES
A. REFER TO SITE SPECIFIC DRAW INGS BY SIEMENS PROJECT NUM BERS #
2002344, #2002254, #2002345, AND #200243 FOR ABBREVIATIONS AND
ADDITIONAL INFORMATION.
DMDMDM
DMDM
3 3
DM
DM
OS
OS
OS
OS
OS OS
OSOS
OS
OS
OS
OS
OSOSOS
OS
OS
OS
OS
OS
OS
OS
OS
OS
A
457 3.5
B
C
D
E
F
2.5
1 1 1
1 1
2 2
EX EX EX EX
EXEX
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LOUNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIOACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
EXEX EX EX EX EX EX
EX
EX
EXEX
EX
EXEX
EXEX
EX EX EX EX EX EX
EX
EX
EX EX
EX
EX
EX
EXEX
EX
EX
EX
EX
EX
EX
N
KEY PLAN
GENERAL NOTES - DEMOLITION
A. FOR EXISTING EQUIPM ENT, SUCH AS LIGHTING FIXTURES, W IRING
DEVICES, CONDUITS, ETC., SHOW N ON PLANS TO BE REM OVED,
COMPLETELY CUT/CAP CONDUITS AT THE AREA O F W O RK PERIMETER
AND REMO VE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT
W IRING AT THE OVERCURRENT PRO TECTIVE DEVICE AND REMOVE
W IRING COMPLETELY FROM THE ABANDO NED CONDUITS.
B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED W IRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTO RS PASSING THROUGH RENOVATED AREAS AND
SERVICING UNDISTURBED AREAS.
D. LIGHT FIXTURE NOTED AS EXISTING (EX) SHALL BE SALVAGED,
CLEANED AND STORED FOR REUSE.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:0
A M
ED101
LOWER LEVEL LIGHTING
DEMOLITION PLANGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"ED101
1 LOWER LEVEL LIGHTING DEMOLITION PLAN
PLAN NOTES
1. MAINTAIN DEVICE LOCATION. REMOVE DEVICE TO REPLACE W ITH NEW .
2. SALVAGE LIGHT FIXTURES AND CLEAN FOR REUSE.
N
G F
G F
G F
GF
GF
GF GF
GF
J
J
J J
J
J
J
J
J
F F
F
F F F FF
F
F F
F
FF
F
F F
F
HD
J J
J
HD
F
J N B
N B
J
TV
F
FACP
A
457 3.5
B
C
D
E
F
2.58
ABHEQ4
ABHN1
ABLNDP1
ABLN1
AAUPS
ABLCR1
ABLLS1
ABHLS1 ABHCR1 ABHEQ1
ELECT.
A-B153
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LOUNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIOACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
A-B040
OFFICE
A-B066
AUDITORIU M
N
KEY PLAN
GENERAL NOTES - DEMOLITION
A. FOR EXISTING EQUIPM ENT, SUCH AS LIGHTING FIXTURES, W IRING
DEVICES, CONDUITS, ETC., SHOW N ON PLANS TO BE REM OVED,
COMPLETELY CUT/CAP CONDUITS AT THE AREA O F W O RK PERIMETER
AND REMO VE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT
W IRING AT THE OVERCURRENT PRO TECTIVE DEVICE AND REMOVE
W IRING COMPLETELY FROM THE ABANDO NED CONDUITS.
B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED W IRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTO RS PASSING THROUGH RENOVATED AREAS AND
SERVICING UNDISTURBED AREAS.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:1
A M
ED201
LOW ER LEVEL POW ER AND FIRE
ALARM DEMOLITION PLANSGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"ED201
1 LOWER LEVEL POWER AND FIRE ALARM DEMOLITION PLAN
PLAN NOTES
1. EXISTING EQ UIPMENT CONNECTIONS TO PANEL ABHEQ4 W ITHIN
EQ UIPMENT AND PROCEDURE ROOM SHALL BE REMOVED BACK TO
PANEL.
2. PANEL ABHEQ 4 SHALL BE REMOVED. FEEDER TO PANEL SHALL BE
MAINTAINED AND EXTENDED TO NEW PANEL. REFER TO SHEET EP101.
3. EQ UIPMENT FOR PET / CT SCANNER SHALL BE RELOCATED TO NEW
EQ UIPMENT ROO M FO R SCANNER. ASSO CIATED RACEW AYS SHALL BE
REW ORKED TO NEW LOCATION.
4. FEEDER TO DISTRIBUTIO N PANEL ABHEQDP1 IN ELECTRICAL SW ITCH
GEAR ROO M A-B148 SHALL BE MAINTAINED.
5. DISCONNECT AND REMOVE ELECTRICAL CONNECTION TO COO LING
EQ UIPMENT ASSOCIATED W ITH LOW ER LEVEL PET/CT SCANNER.
EQ UIPMENT LOCATED ON LEVEL B OF PARKING GARAGE.
FACP
ABHEQ5ABLEQ5
TX-ABLEQ-3
ABHNMCC1
1.5"C
4"C
RF30
CONTROL PANEL
A-B148
MECHANICAL
ROOM
N
KEY PLAN
GENERAL NOTES - DEMOLITION
A. FOR EXISTING EQUIPM ENT, SUCH AS LIGHTING FIXTURES, W IRING
DEVICES, CONDUITS, ETC., SHOW N ON PLANS TO BE REM OVED,
COMPLETELY CUT/CAP CONDUITS AT THE AREA O F W O RK PERIMETER
AND REMO VE CONDUIT W ITHIN THE W ORK AREA, DISCONNECT
W IRING AT THE OVERCURRENT PRO TECTIVE DEVICE AND REMOVE
W IRING COMPLETELY FROM THE ABANDO NED CONDUITS.
B. DISCONNECT ALL ABANDONED W IRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED W IRING.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTO RS PASSING THROUGH RENOVATED AREAS AND
SERVICING UNDISTURBED AREAS.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:1
A M
ED202
ENLARGED MECHANICAL ROOM
ELECTRICAL PLAN - DEMOLITIONGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"
LOWER LEVEL ENLARGED MECHANICAL ROOM ELECTRICAL PLAN
PLAN NOTES
1. DISCONNECT AND REMOVE CONNECTION TO FAN BACK TO
MOTOR CONTROL CENTER ABHNM CC1.
2. REM OVE LIGHT FIXTURE. M AINTAIN LIGHTING CIRCUIT FOR
REUSE. REFER TO SHEET EP102.
3. RAISE EMPTY 1.5" CONDUITS TO M ATCH HEIGHT OF THE 4"
CONDUIT FOR CLEARANCE OF NEW AHU. REW O RK CONDUIT
OVER AHU BETW EEN FITTINGS.
4. REM OVE VFD BUCKET FOR SUPPLY AND RETURN FANS FOR
AHU-30.
5. REM OVE SM OKE DETECTOR FRO M DUCTW ORK. PROVIDE
CONTINUITY OF CIRCUIT DURING REMO VAL.
6. REM OVE CIRCUIT BACK TO SOURCE.
7. REM OVE ELECTRICAL CIRCUIT FROM PANEL. MAINTAIN CIRCUIT
FOR REUSE W ITH REPLACEMENT PANEL. COORDINATE W ITH
DIV. 23.
OS
OS
OS
OS
OS OS
OS
DM
D M
OS
D M
DM
OS
O S
D M
D M
OS
DM
D M
DM
DM
OS
D M
D M
D M
3 D M
D M
D M
D M
OS
OS
D M
D M
OS
DM
DM
DM
DM
DM
OS
OS
OS
OS
OS
OS
D M
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OS
DM
D M
D M
OS
D M
OS
OS
OS
DM
DM
DM
DM
D M
D M
OS
D M
D M
DM DM DM DM DM DM
A
457 3.5
B
C
D
E
F
2.58
UCc
B8aB1a
UCc
B1a B8a
B2b B2b
F3c F3c
F3cF3c
F3cF3c
B8aB8a
F3bF3b
F3b F3b
(ETR)
(ETR)
(ETR)
B2b B2b
B2b
B2b
UCc
UCc
UCc
UCc
EX EX EX
B1w
EX
EX
EXEX
B1w
B1w
EX
EX
B1aB1a
UCc
B2b B1y B1y B1y B1y
B1y
B1y
B1y
X1
X2
B1y B1y
B1yB1y
B1y
B1y
B1yB1y
X1 X1
UCc B8a B1a
EX EX
EXEX
EX
EX
B1a
B1aEX EX
EXEX
EX EX
B1y
B1y
B1y
B1a B1a
B1a
B1a
B1a B1a
B1a
B1a
B1y
X1
B1y
B1y
B1y
B1y
X1
X1
B1y B1y
B1y B1y
B1y
B2bB2b
B1a B1a
B8a B8a
B8a B8a
B8aB8a
F3c F3c F3c
F3cF3cF3c
B8a B8a
B8aB8a
B8a B8a
F3c F3c F3c
F3cF3cF3c
F3a
F3a
F3a
F3a
B1a
B1a
B1a
B1a
B1yB1yX1
B1y
B1y
B1y
B1y
B1y
B1y
X1
X1
B1w
B1w
EX
EX
EX
EX EX
B1y B1y
UCc UCc UCc UCc UCc
X1 X1
EX
EX
EX
EX
EX
EX
D1
D1
UCc
UCc
UCc
EXEX
UCc
UCc
UCc
X1
X1
B8a
F3cF3c
F3c
F3c
F3c
F3cF3c
F3c F3c
F3c
F3c
1 1
1 1
1 1
1 1
1 1
1 1
B1w
B1w
1 1
2 2
2 2
2 2
2 2
3 33
1 1
2 1
2 2 2 2
1 3 3
2 2 2 2 2
2 2 2 2 a b a a aa b bb b a a aa c d d d c c e e e f g ab c d c g f e c e c e d c d c a a a b b b b b b a a a a a a a a f f f f ffff f f g g gg g g c a bab c c
F3c
F3c
F3cF3c
F3c
F3c
F3c F3c
2 2
2 2
B8a
B8a
B8a B8a
B8a
B8a ff f f f f ff g g g g g g
B8a
B8a
B8a
B8aB8a b b b gg
3 3 a a a a a b b a b a ab a b b a a b ba c c c c b ab a a b b a c c c c a b c b a c1 b a
ABHN1 - 2
b ab a b a b
1 1 1
EX EX
EX EXEX EX
2 2 2
2 2
UCc
UCc UCc c c c c c c
X0
DS
X0
DS
b
B8a
B8a
3 3
X0
DS
X0
DS
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LOUNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIOACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
A-B043
PATIENT
SAFETY
MANAGER
A-B044
RISK
MANAGER
A-B041
ASSISTANT
LOG
A-B040
OFFICE
A-B066
AUDITORIU M
ab b a b a b a ab ab
N
KEY PLAN
GENERAL NOTES
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES
SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING
PLAN.
B. COORDINATE INSTALLATION OF LIGHTING AND LIG HTING CO NTROLS
W ITH PHASING PLANS. REFER TO ARCHITECTURAL DRAW INGS FOR
PHASING INFORM ATIO N.
C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO M ORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQ UIPMENT GRO UNDING CONDUCTOR.
D. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF
EM ERGENCY AND NO RMAL BRANCH W IRING DEVICES SHALL HAVE
DIVIDERS BETW EEN DEVICES.
E. UNLESS NOTED O THERW ISE ALL NORM AL LIGHTING CIRCUITS ARE
FED FROM PANEL ABHN1, CRITICAL FROM PANEL ABHCR1 AND
LIFESAFETY IS FEED FRO M PANEL ABHLS1.
F. LIGHT FIXTURES INDICATED AS EXISTING (EX) SHALL BE FIXTURES
SALVAGED DURING DEMOLITION.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:1
A M
EL101
LOW ER LEVEL LIGHTING PLAN
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"EL101
1 LOWER LEVEL LIGHTING PLAN
N
PLAN NOTES
1. RELOCATE EXISTING LIGHTING INTO CEILING. REFEED LIGHTING TO
CIRCUIT INDICATED.
G
G F
G F
J
J
J
T P
T P
/G F
T P
T P
GF/TP
G F
/T P
TP
T V
T P
T P
46" MH
RF
MW
GF
GF
T P
T P
TP
TP
TP
M F
D
J
J
TP
TP
T P
T P
T V
GF
G F
GF
G F
46" MH
46" MH
M H
TP
T P T P
TP
T P
/G F
T P
/G
FT
P
T P
TP
T P
E K
G
U C
/R F
A
T P
T P
46" MH
M H
M H
TP
J
TP
TP
TP
T P
TP
T P
T P
T P
J J
J
T P
T P
T P
T P
T P
/G F
TP
T P
T P
J
J46" MH
M H
TP
J
J
J
TP
TP
TP
TP
TP/GF
TP
TP
TP
TP
TP/GF
TP
TP TP
TP
TP/GF
TP
J
U C
/R F
W A
R M
E R
46" MH
46" MH
EPO
E P
O
EPO
E P
O
EPO
EPO
EPO
EPO
EPO
T P
T P
J
J
J
J
T P
TV
J
J
J
J
J
AAP
CC
J
J
J
TV
J
J
J
J
A
457 3.5
B
C
D
E
F
2.589
ABHEQ4
ETR
ETR
ETR
6 6
ABHN1
ABLNDP1
ABLN1
AAUPS
ABLCR1
ABLLS1
ABHLS1 ABHCR1 ABHEQ1
ELECT.
A-B153
ABLN1E
ABLCR3
ABLN7
ABHEQ9
A B
H E
Q
ABHEQ7
X -A
B H
E Q
12 12
1 1
136 13
16,18
14 4
1111 2
29 29
1 1
7 14
8 7
6 6
X -A
B H
E Q
1-EF30B
1717 ACCU-1ACCU-2
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION
A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LOUNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIOACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
INDOOR
UNIT
INDOOR
UNIT
ABLCR3 - 36,38
ABLCR3 - 33,35
ABHCR1
-7,9,11
ABHCR1
-8,10,12
ABHEQ6
ABLN4 ABHN4
A-B016
ELEC
TO ABHEQDP2
IN ELECTRICAL
SW ITCHGEAR A-B140
N
KEY PLAN
GENERAL NOTES
A. CRITICAL CIRCUITS SHOW N SHALL ORIGINATE FROM CRITICAL
PO W ER PANEL ABLCR3.
B. NORMAL CIRCUITS SHOW N SHALL ORIGINATE FROM NORM AL
PO W ER PANEL ABLN1E AND ABLN7.
C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN
THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL
HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING
CONDUCTOR.
D. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND
TYPES OF EMERGENCY AND NORMAL BRANCH W IRING
DEVICES SHALL HAVE DIVIDERS BETW EEN DEVICES.
E. DISTRIBUTIO N PANEL ABHEQDP1 IN ELECTRICAL SW ITCH GEAR
ROOM A-B140.
F. CONTRACTOR SHALL REFER TO SIEM ENS SITE SPECIFIC
DRAW INGS FO R ADDITIO NAL INFORMATION.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:2
A M
EP101
LOWER LEVEL POWER PLAN
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"EP101
1 LOWER LEVEL POWER PLAN
PLAN NOTES
1. BO X MOUNTED TRANSFORMER LOCATED ABOVE THE CEILING TO
CONTRO L SENSOR OPERATED FAUCET O N FIXTURE(S) BELOW . PROVIDE
120V-1PH POW ER IN A JUNCTION BOX ABOVE THE CEILING W IRE TO
RECEPTACLE CIRCUIT IN TOILET ROOM. STUB A 0.75" CONDUIT (FOR LOW
VO LTAGE W IRING) ABOVE THE CEILING AND EXTEND DOW N TO AN
ELECTRICAL W ALL BOX LO CATED BELO W EACH LAVATO RY. REFER TO
DIVISION 22 DRAW INGS. PROVIDE TRANSFORMER AND LOW VOLTAGE
W IRING. COORDINATE ALL W ORK W ITH THE DIVISIO N 22.
2. LOCATION FOR PANEL ABHEQ4. EXTEND FEEDER FOR PANEL ABHEQDP1
TO THIS LOCATION AND CONNECT.
3. REW ORK RACEW AY FOR PET / CT SCANNER TO RELOCATED EQUIPM ENT
IN THIS ROOM .
4. PRO VIDE 20A/120V CONNECTION TO POW ER SUPPLY LOCATED ABOVE
CEILING FOR LOCAL SOUND MASKING SYSTEM.
5. PANEL FOR NEW PET / CT SCANNER EQUIPMENT. FEED FROM ABHEQ DP1.
6. PRO VIDE 20A/120V CONNECTION TO ELECTRIC SECURITY DOOR
HARDW ARE POW ER SUPPLY.
7. REFER TO IMAGING EQUIPM ENT MANUFACTURER DRAW INGS AND
PRO VIDE ALL REQUIRED JUNCTION BOXES, RACEW AYS, ETC.
8. PRO VIDE 20A/480V/3-PHASE CONNECTION TO EXHAUST FAN ON ROOF OF
SECOND FLOOR.
9. PRO VIDE 20A/120V/1-PHASE CONNECTION TO HOOD.
N
39.12 kVA 24.56 kVA (68 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 13.92 kVA 13.64 kVA 11.57 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 1976... -- -- -- 38
35 -- -- -- 1976... 1976... 2 30 A ACCU-1 36
33 ACCU-2 30 A 2 1976... 1400... 1 20 A Receptacle Room... 34
31 EPO'S FOR 4 SCAN... 20 A 1 100 VA 1400... 1 20 A Receptacle Room... 32
29 Receptacle CORRIDO... 20 A 1 900 VA 180 VA 1 20 A HOOD 30
27 AUTODOOR 20 A 1 900 VA 900 VA 1 20 A AUTODOOR 28
25 Receptacle STAFF... 20 A 1 1500... 720 VA 1 20 A Receptacle DOSE... 26
23 Receptacle NM... 20 A 1 360 VA 360 VA 1 20 A Receptacle NM... 24
21 Receptacle NM... 20 A 1 1080... 1080... 1 20 A Receptacle NM... 22
19 Receptacle NM SCAN ... 20 A 1 720 VA 720 VA 1 20 A Receptacle NM SCAN ... 20
17 Receptacle DOSE... 20 A 1 720 VA 720 VA 1 20 A Receptacle DOSE... 18
15 Receptacle HOT LAB... 20 A 1 720 VA 720 VA 1 20 A Receptacle DOSE... 16
13 Receptacle PET / CT 1... 20 A 1 1440... 900 VA 1 20 A Receptacle HOT LAB... 14
11 Receptacle COMBINE... 20 A 1 1080... 1080... 1 20 A Receptacle COMBINE... 12
9 Receptacle Room 3A,... 20 A 1 1080... 1440... 1 20 A Receptacle PET / CT 2... 10
7 WARMER 20 A 1 1500... 1500... 1 20 A UC REFRIGERATOR 8
5 UC REFRIGERATOR 20 A 1 1500... 720 VA 1 20 A Receptacle THYROID... 6
3 Receptacle Room... 20 A 1 1080... 1260... 1 20 A Receptacle CARDIAC... 4
1 Receptacle DOSE... 20 A 1 720 VA 720 VA 1 20 A Receptacle DOSE... 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO
Location: ELEC ROOM A-B025 Mounting: Surface A.I.C. Rating: 22KA
Panel: ABLCR3
40.97 kVA 25.48 kVA (71 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: EXISTING PANEL
Total Load: 14.20 kVA 13.86 kVA 12.90 kVA
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38
35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36
33 Spare 20 A 1 0 VA 1080... 1 20 A Receptacle ETR 34
31 Receptacle 20 A 1 180 VA 720 VA 1 20 A AUTO SENSOR SINK 32
29 Receptacle 20 A 1 1080... 720 VA 1 20 A Receptacle 30
27 Receptacle 20 A 1 900 VA 1260... 1 20 A Receptacle 28
25 MICROWAVE 20 A 1 1500... 1440... 1 20 A Receptacle 26
23 MULTIFUNCTION... 20 A 1 1200... 1220... 1 20 A Receptacle 24
21 Receptacle 20 A 1 1620... 1260... 1 20 A Receptacle 22
19 Receptacle 20 A 1 1400... 1580... 1 20 A Receptacle 20
17 Receptacle 20 A 1 900 VA 1664... -- -- -- 18
15 Receptacle 20 A 1 1220... 1664... 2 20 A Receptacle 16
13 Receptacle 20 A 1 1260... 1080... 1 20 A Receptacle 14
11 Receptacle 20 A 1 1260... 2160... 1 20 A Receptacle 12
9 Receptacle 20 A 1 1080... 1260... 1 20 A Receptacle 10
7 Receptacle 20 A 1 1080... 1440... 1 20 A Receptacle 8
5 Receptacle 20 A 1 1260... 1440... 1 20 A Receptacle 6
3 Receptacle 20 A 1 1620... 900 VA 1 20 A Receptacle 4
1 Receptacle 20 A 1 1440... 1080... 1 20 A Receptacle 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 A Supply From: Enclosure: Type 1 Mains Type: MLO
Location: ELEC ROOM A-B025 Mounting: Surface A.I.C. Rating: 22KA
Panel: ABLN7
295 kVA 295 kVA (355 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 98.33 kVA 98.33 kVA 98.33 kVA
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 -- -- -- 5000... 0 VA 1 20 A Spare 12
9 -- -- -- 5000... 0 VA 1 20 A Spare 10
7 ABHEQ7 150 A 3 5000... 0 VA 1 20 A Spare 8
5 -- -- -- 2416... 2416... -- -- -- 6
3 -- -- -- 2416... 2416... -- -- -- 4
1 ABHEQ8 80 A 3 2416... 2416... 3 80 A ABHEQ9 2
CKT Circuit Description Trip Poles A B C
Poles Trip Circuit Description CKT
Voltage: 480/277 Wye-3PH-4W Mains Rating: 400 A Supply From: ABHEQDP2 Enclosure: Type 1 Mains Type: MCB
Location: ELEC A-B016 Mounting: Surface A.I.C. Rating: 35KA
Panel: ABHEQ6
10. PULL BOX PER VENDOR REQUIREMENTS. REFER TO SITE SPECIFIC
DRAW INGS FO R EXACT LOCATION AND REQUIREM ENTS.
11. DUCT BANK PER VENDOR REQUIREM ENTS. REFER TO SITE SPECIFIC
DRAW INGS FO R EXACT LOCATION AND REQUIREM ENTS.
12. COORDINATE EXACT MOUNTING OF W IREW AY W ITH ARCHITECT AND SITE
SPECIFIC DRAW INGS.
13. ENCLOSED BREAKER FOR TRANSFO RMER. REFER TO SITE SPECIFIC
DRAW INGS FO R EXACT LOCATION AND REQUIREM ENTS.
14. UTILIZE 20A/1P SPARE BREAKER "11" IN PANEL ABLLS1.
15. PRO VIDE 20A/480/3-PHASE CO NNECTIO N FOR EXHAUST FAN ON ROOF.
REFER TO DIV. 23 FO R LOCATION ON ROOF.
16. PRO VIDE LIGHTING PROTECTION ON FAN ENCLOSURE. BO ND #8 BARE
COPPER BOND BETW EEN PRO TECTOR AND EXISTING LIGHTNING
CONDUCTO R O N RO OF. EXOTHERMIC W ELD CONNECTIONS.
17. PRO VIDE 30A/208V/1-PHASE CONNECTION FOR SPLIT SYSTEM. INTERIOR
UNIT SHALL BE FED FROM THE EXTERIOR ACCU. MAKE ALL POW ER AND
CONTRO L CONNECTIONS BETW EEN UNITS. FEED TO ACCU SHALL BE 3 -
#10, 1 - #10 G ND., .75" C. FEED BETW EEN ACCU AND INTERIOR UNIT SHALL
BE 2 #10, 1 - #10 GND., IN .75" C.
18. REFEED EXISTING TO REMAIN DEVICES W ITH CIRCUIT INDICATED.
19. COORDINATE RO UTING O F FEEDERS W ITH OTHER TRADES AND UTILITIES
ABOVE CEILING.
20. FIRESTOP CONDUIT AT W ALL PENETRATION.
ABLCR1
Revisions: Date:
295.00 kVA 52.0 kVA (62.5 A)
TOTAL CONNECTED ESTIMATED DEMAND
NOTES:
5 Space 0.00 kVA -- -- -- -- --
4 Space 0.00 kVA -- -- -- -- --
3 Spare 0.00 kVA -- 3 20 A -- --
2 Spare 0.00 kVA -- 3 20 A -- --
1 ABHEQ6 295.00 kVA 400 A 3 20 A REFER TO SINGLE LINE SHEET E701
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING WIRE SIZE
SEE
NOTE
Feeder Size: Spec. Ref. #:
Voltage: 480/277 Wye-3PH-4W Mains Rating: 800 A
Supply From: Enclosure: Type 1 Mains Type: MCB Location: MECHANICAL ROOM A-B148 Mounting: SURFACE A.I.C. Rating: 35KA
DISTRIBUTION PANEL: ABHEQDP2
200 A
200 A
ABLNDP1
52 kVA (62.5 A)
J
J
S
FACP
S
SD
SD
VFD VFD VFD VFD
VFD
N
KEY PLAN
ABHNMCC1
TX-ABLEQ-3
ABLEQ5 ABHEQ5
1-AC30
1.5"C
4"C
C1a
C1a
C1a
C1a
C1a
C1a
C1a
C1a
C1a
C1a
C1a
C1a
ABHLS1 - 2
ABHLS1 - 2
ABHLS1 - 2
ABHLS1 - 2ABHLS1 - 2
ABHEQ5 - 1
ABHEQ5 - 1 ABHEQ5 - 1
ABHEQ5 - 1ABHEQ5 - 1
ABHEQ5 - 1 ABHEQ5 - 1
1-HCP30
ABHNMCC1
ABHEQ5 - 2,4,6
ABHEQ5 - 3,5,7
ABLEQ5 - 1
ABLEQ5 - 2
A-B148
MECHANICAL
ROOM
1-RF30
7.5 HP
ABHNMCC1
20 HP
20 HP20 HP
20 HP
VFD
VFD
VFD
VFD
VFD
1-CCP30
TO ELEC. SW GR
RM. A-B140
20HP
SUPPLY
FAN
20HP
SUPPLY
FAN
20HP
SUPPLY
FAN
20HP
SUPPLY
FAN
3#4/0,1#4, 2.5"C
SUPPLIED
W ITH 1-AC30
400A DISC.
250A FUSES
TO ABHNM CC1
(SEE PLAN NOTE #5)
10HP
1-RF30
3#10,1#10, .75"C
VFD W ITH
DISC.
TO ABHEQ 5
3#10,1#10, .75"C
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:3
A M
EP102
ENLARGED MECHANICAL ROOM
ELECTRICAL PLANGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"EP102
1 ENLARGED MECHANICAL ROOM ELECTRICAL PLAN
PLAN NOTES
1. INSTALL DUCT SMOKE DETECTO R IN NEW DUCTW ORK .
CONNECT INTO ADDRESSABLE INITIATION CIRCUIT. PROGRAM
SYSTEM TO INCORPORATE NEW DETECTOR.
2. MOUNT C1 FIXTURES AT 9'-0" AFF.
3. EXISTING FIRE ALARM ZONE CONTRO L PANEL FCP-BA.
4. MAKE SINGLE POINT CONNECTION TO 1-AC30 FROM MCC,
ABHNM CC1. PROVIDE FUSED DISCONNECT. COORDINATE
TERMINATIO N W ITH AHU MANUFACTURER.
5. REPLACE VFD BUCKET FOR SF30 W ITH 400A DISCONNECT
BUCKET W ITH 250A THERM AL MAGNETIC CIRCUIT BREAKER.
6. MAKE 20A/120V, 1 PHASE CONNECTION FROM AVAILABLE
CIRCUIT IN PANEL ABLEQ3 FOR AHU LIGHTING AND
RECEPTACLES.
7. MAKE 20A/120V, 1 PHASE CONNECTION FROM AVAILABLE
CIRCUIT IN PANEL ABLEQ3 FOR UV LIGHTS IN AHU.
8. RECO NNECT EXISTING 120V CIRCUIT TO NEW CONTROL PANEL.
9. PRO VIDE 30A, 480V/3P COMBINATION STARTER W ITH START/STOP
CONTACTS AND INDICATOR LIG HTS. COORDINATE W ITH DIVISION
23 BMS CONTROL W IRING TO STOP/START CONTACTS. 3#12, 1#12
GND. IN .75"C.
10. PRO VIDE 20A, 120V CONNECTION TO POW ERED ISOLATION
DAM PERS. COORDINATE FINAL LOCATION W ITH DIVISION 23.
11. PROVIDE REMOTE INDICATOR LIGHT FOR DUCT SM OKE
DETECTOR. MOUNT TO SIDE OF AHU.
12. PRO VIDE 30A/480V-3PHASE CO NNECTIO N FROM AVAILABLE SPARE
IN PANEL "ABHEQ5".
N
SCALE: 12" = 1'-0"
POWER FEED - 1-AC30
SCALE: 12" = 1'-0"
POWER FEED - 1-RF30
Revisions: Date:
ATS ATS ATS ATS
EQ8 ABHEQDP2
AMS 3 AMS 1 AMS 2
TO GBN
ROOM
A-B139
EP402
ENLARGED SW ITCHGEAR ROOM ELECTRICAL PLAN
TO ABHEQ6
13. INSTALL FEEDER ABOVE CEILING. COORDINATE INSTALLATION
W ITH O THER SERVICES BEING INSTLALED IN THIS AREA.
14. ROUTE FEEDER PARALLEL TO EXISTING CONDUIT RUNS AT 11'-2"
TO BOTTOM OF CONDUIT. COORDINATE W ITH O THER TRADES
W ITHIN AREA.
15. FIRESTOP CONDUIT AT W ALL PENETRATION.
16. ROUTE FEEDER PARALLEL TO EXISTING CONDUIT RUNS AT 10'-6"
TO BOTTOM OF CONDUIT. COORDINATE W ITH O THER CONDUIT
RUNS W ITHIN AREA.
17. UTILIZE SOARE 800A BREAKER IN CUBICLE 52-F12 FOR
EM ERGENCY FEED TO ATS-EQ8
18. UTILIZE EMPTY CUBICAL FOR NORMAL FEED TO ATS-EQ8 IN
SECTION 2 OF SUBSTATION AMS3. OUTFIT CUBICAL AS REQUIRED
TO FOR 800A POW ER BREAKER. PROVIDE BREAKER COM PATIBLE
TO EXISTING GE AKD-8 SW ITCHG EAR. BREAKER SHALL HAVE A
SCCR OF 35KAIC.
19. PRO VIDE 800A, 480V, 3-PH-4 W IRE AUTOM ATIC TRANSFER SW ITCH
W ITH BYPASS/ISOLATION SW ITCH. INTEGRATE CONTROLS INTO
THE EXISTING PLC CONTRO L SYSTEM AND PROGRAM UNIT INTO
SYSTEM. PROVIDE AND MOUNT SW ITCH ON 4" CONCRETE
HOUSEKEEPING PAD.
20. INSTALL DISTRIBUTION PANEL ADJACENT TO ATS. COORDINATE
INSTALLATIO N O F CONDUIT W ITH EXISTING CONDUIT RUNS
ABOVE.
SCALE: 1/8" = 1'-0"
17 15
20 14 15
F
F
F
F
F
F
F
F
F
F
F
F
F
F
S
F
F
S
S
F
F
S
S
S
S
S
S
S
F
F
F
S
F
F
S S
F
S
F
F
F
F
F
F
F
F
F
F
F
F
F
FACP
S
S
D DDD
D D
D
F
F
F
F
F
A
457 3.5
B
C
D
E
F
2.58
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LOUNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIOACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
N
KEY PLAN
GENERAL NOTES
A. EXISTING FIRE ALARM DEVICES AND SUPPORTING NETW ORK CABLING
ARE SUPPORTED BY FIRE CONTROL PANEL FCP-BA. REFER TO
LOCATION SHOW N ON EP102.
B. ALL SYSTEM INTEGRATION SHALL BE COMPLETED BY AADCO
(317-781-7680). THIS IS TO INCLUDE SYSTEM TERMINATIONS,
PRO GRAMING AND TESTING.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ ja s u m m e rs .r v t
/2
/2
:1
:3
A M
EY101
LOW ER LEVEL FIRE ALARM PLAN
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 MSG JAS
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"EY101
1 LOWER LEVEL FIRE ALARM PLAN
N
Revisions: Date:
PLAN NOTES
1. BO X MOUNTED TRANSFORMER LOCATED ABOVE THE CEILING TO
CONTRO L SENSOR OPERATED FAUCET O N FIXTURE(S) BELOW . PROVIDE
120V-1PH POW ER IN A JUNCTION BOX ABOVE THE CEILING W IRE TO
RECEPTACLE CIRCUIT IN TOILET ROOM. STUB A 0.75" CONDUIT (FOR LOW
VO LTAGE W IRING) ABOVE THE CEILING AND EXTEND DOW N TO AN
ELECTRICAL W ALL BOX LO CATED BELO W EACH LAVATO RY. REFER TO
DIVISION 22 DRAW INGS. PROVIDE TRANSFORMER AND LOW VOLTAGE
W IRING. COORDINATE ALL W ORK W ITH THE DIVISIO N 22.
2. LOCATION FOR PANEL ABHEQ4. EXTEND FEEDER FOR PANEL ABHEQDP1
TO THIS LOCATION AND CONNECT.
3. REW ORK RACEW AY FOR PET / CT SCANNER TO RELOCATED EQUIPM ENT
IN THIS ROOM .
4. PRO VIDE 20A/120V CONNECTION TO POW ER SUPPLY LOCATED ABOVE
CEILING FOR LOCAL SOUND MASKING SYSTEM.
5. PANEL FOR NEW PET / CT SCANNER EQUIPMENT. FEED FROM ABHEQ DP1.
6. PRO VIDE 20A/120V CONNECTION TO ELECTRIC SECURITY DOOR
HARDW ARE POW ER SUPPLY.
7. REFER TO IMAGING EQUIPM ENT MANUFACTURER DRAW INGS AND
PRO VIDE ALL REQUIRED JUNCTION BOXES, RACEW AYS, ETC.
8. PRO VIDE 20A/480V/3-PHASE CONNECTION TO EXHAUST FAN ON ROOF OF
SECOND FLOOR.
9. PRO VIDE 20A/120V/1-PHASE CONNECTION TO HOOD.
T2
B
T2
DETAIL: B = DETAIL DESIGNATION
T2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
T2 = SHEET W HERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
CONDUIT RUN IN W ALL OR ABOVE CEILING.
CONDUIT RUN IN SLAB OR UNDERGROUND.
CABLE MANAGEMENT SYSTEM PATHW AY.
LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERW ISE.
ABBREVIATIONS
AAP - AREA ALARM PANEL - MEDICAL GAS
ACC - ACCESS
ADJ - ADJUSTABLE
AF - ARC FAULT CIRCUIT INTERRUPTER
AFCI - ARC FAULT CIRCUIT INTERRUPTER
AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM
AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATS - AUTOMATIC TRANSFER SW ITCH
BLDG - BUILD ING
BOE - BOTTOM OF EQUIPMENT
BOT - BOTTOM
BTW N - BETW EEN
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CKT - C IRCUIT
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICERS REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
D - DEPTH
DET - DETAIL
DIA - D IAMETER
DIM - D IMENSION
DIV - D IVISION
DN - DOW N
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL (D IVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATION OR ELEVATOR
EM - EMERGENCY
EQ - EQUAL
EQS - EQUIPMENT SUPPLIER
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EX - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
FCE - FIRE CONTROL EQUIPMENT
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FSC - FIRE SUPPRESSION (D IVISION 21)
FT - FEET
FTG - FOOTING
GC - GENERAL
GF - GROUND FAULT CIRCUIT INTERRUPTER
GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR GOVERNMENT
FURNISHED CONTRACTOR INSTALLED
GFFT - GROUND FAULT FEED THRU
HC - HVAC (DIVISION 23)
HP - HORSE POW ER OR H IGH POINT
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
IN - INCHES
IP - INTERNET PROTOCOL
KEC - KITCHEN EQUIPMENT
L - LENGTH
LBS - POUNDS
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF ITEM
MIN - MIN IMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
NIC - NOT IN CONTRACT
NOM - NOMINAL
NTS - NOT TO SCALE
OD - OUTSIDE D IAMETER
OFCI - OW NER FURNISHED CONTRACTOR INSTALLED
OFOI - OW NER FURNISHED OW NER INSTALLED
PC - PLUMBING (DIVISION 22)
PLBG - PLUMBING
POE - POW ER OVER ETHERNET
PTZ - PAN / TILT / ZOOM
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH-IN
S - SURFACE MOUNTED
SC - SECURITY
SCH - SCHEDULE
SHT - SHEET
SMS - SECURITY MANAGEMENT SYSTEM
SPEC - SPECIFICATIONS
SQ - SQUARE
SS - STAINLESS STEEL
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TC - TECHNOLOGY CONTRACTOR
TEMP - TEMPERATURE
TOE - TOP OF EQUIPMENT
TYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
UTP - UNSHIELDED TW ISTED PAIR
VFD - VARIABLE FREQUENCY DRIVE
VOL - VOLUME
W / - W ITH
W /O - W ITHOUT
W P - W EATHERPROOF
ZVC - ZONE VALVE CABINET
1. ALL CONDUIT SLEEVES THRU W ALLS AND FLOORS, NOT SPECIFICALLY SHOW N ON DRAW INGS BUT REQUIRED FOR COMPLIANT INSTALLATION OF CABLING
SHALL BE PROVIDED AS PART OF THE SCOPE OF W ORK.
2. ALL FIRE STOPPING OF CONDUIT SLEEVES AND CABLE TRAY PENETRATIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE AND THOROUGH COORDINATION OF ALL PATHW AYS BEING PROVIDED. ANY PATHW AYS THAT ARE PROVIDED THAT CAUSE CABLING INSTALLATION TO BE NON-COMPLIANT SHALL BE BROUGHT TO THE ATTENTION OF THE COR PRIOR TO THE
INSTALLATION OF CABLING.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL POW ER REQUIREMENTS W ITHIN THE TECHNOLOGY ROOM(S) PRIOR TO ROUGH-INS AND BUILD-OUT OF EACH TECH ROOM. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING SIGNED-OFF DETAILED COORDINATION DRAW INGS INCLUDING ALL FIRE SUPPRESSION, PLUMBING, HVAC, ELECTRICAL, AND TECHNOLOGY W ORK W ITHIN THE ROOM(S). THE COORDINATION DRAW INGS SHALL SHOW FLOOR PLANS AND W ALL ELEVATIONS INCLUDING ALL TRADES' W ORK W ITHIN THE SPACE(S) PR IOR TO ANY TRADES W ORKING W ITHIN THE
SPACE(S).
5. THE DRAW INGS INDICATE THE QUANTITY, TYPE AND GENERAL LOCATION OF VOICE/DATA/CATV/VIDEO OUTLETS REQUIRED IN EACH SPACE. A FINAL DEVICE LOCATION PLAN FOR EACH SPACE W ILL BE ISSUED PRIOR TO START OF THE INSTALLATION. THE CONTRACTOR SHALL INCLUDE IN THE BID ANY COSTS ASSOCIATED W ITH FINAL DEVICE LOCATIONS AS THERE W ILL BE NO ALLOW ANCE AFTER AW ARD OF CONTRACT.
6. THE CONTRACTOR W ILL PROVIDE THE CABLING PATHW AYS AND POW ER FOR TECHNOLOGY SYSTEMS. THE CONTRACTOR SHALL INCLUDE COST TO W ALK THROUGH EACH BUILDING DURING THE PATHW AY ROUGH-IN PHASE TO VERIFY INSTALLATION W ILL ACCOMMODATE THE CABLING PHASE OF THE
PROJECT.
7. ALL LOW VOLTAGE W IRING ABOVE ACCESSIBLE CEILINGS SHALL BE INSTALLED IN NEW J-HOOK CABLE MANAGEMENT PATHW AYS. W HERE EXISTING CABLETRAY AND/OR J-HOOK PATHW AYS ARE AVAILABLE FOR USE, THE CONTRACTOR MAY REQUEST PERMISSION TO UTILIZE FROM THE COR.
8. ALL W ORK IN PATIENT CARE AREAS SHALL BE DONE IN ACCORDANCE W ITH ALL INFECTION CONTROL AND PATIENT SAFETY STANDARDS AND
REQUIREMENTS.
9. THE CONTRACTOR SHALL REFERENCE ARCHITECTURAL DRAW INGS FOR PROJECT PHASING REQUIREMENTS.
GENERAL NOTES
SECURITY SYMBOLS
CC
1 CCTV SYSTEM CEILING M OUNTED CAM ERA. REFER TO CAMERA SCHEDULE FOR MO UNTING HEIGHT AND
CAMERA SPECIFICATIONS. SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE.
IM DESK MOUNTED INTERCOM MASTER STATION.
CE
PROVIDE INTERFACE FROM CARD ACCESS SYSTEM INTO ELEVATOR CONTROLLER INCLUDING ALL NECESSARY
HARDW ARE, PROGRAMMING AND CABLING AS COORDINATED W ITH ELEVATOR CONTRACTOR.
MD CEILING MOUNTED MOTION DETECTOR.
PB DESK MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE.
JS CCTV SYSTEM REMOTE JOYSTICK/CON TROLLER AN D KEYPAD OPER ATOR'S STATION.
GLASS BREAK.GB
X
PP DESK M OUNTED PANIC/DURESS BUTTON.
SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS
CC
CCTV SYSTEM W ALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. PROVIDE CAMERA, CABLING AND 1-GANG
BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
PS
LOCAL LOW VOLTAGE POW ER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA.
PROVIDE POW ER SUPPLY MOUNTED ABOVE CEILING, LOW VOLTAGE W IRING TO LOCAL CAMERA AND 120V POW ER INTO
LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POW ER SUPPLY.
IC
W ALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERW ISE). PROVIDE INTERCOM, CABLING AND 1-
GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
DM
DOOR POSITION SW ITCH W ITH W IRING. PROVIDE CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR OPENINGS. REFER TO
SECURITY ROUGH-IN DETAILS.
EL
ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE W IR ING AND CONDUIT PATH W AYS FR OM DOOR FRAM E TO COM M ON SM S JUNCTION BOX ABOVE ACC ESSIBLE CEILING. REFER TO SECUR ITY R OUGH-IN
DETAILS.
EM
ELECTRONIC M AG LOCK AND INSTALLATION BY OTHERS. PR OVIDE LOW VOLTAGE W IRING AND CONDUIT PATHW AYS FR OM DOOR FRAM E TO COM M ON SM S JUNCTION BOX ABOVE ACC ESSIBLE CEILING. REFER TO SECUR ITY R OUGH-IN
DETAILS.
ES
ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE W IRING AND CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN DETAILS.
LB
RX
REQU EST TO EXIT SW ITC H IN D OOR HARDW AR E BY OTHERS. PROVIDE LOW VOLTAGE W IRING AND CONDUIT PATH W AYS FR OM DOOR FRAM E TO COM M ON SM S JUNCTION BOX ABOVE ACC ESSIBLE CEILING. REFER TO SECUR ITY R OUGH-IN
DETAILS.
HD
HAN DICAP DOOR OPERATOR M OTOR ASSEM BLY BY OTHERS. PROVIDE LOW VOLTAGE W IR ING, IN TERFACE W ITH SM S AND DOOR ACTUATOR BUTTONS AND 120V POW ER CONN ECTION , AND CON DUIT FR OM DOOR FRAM E TO COM M ON SM S
JUN CTION BOX ABOVE ACCESSIBLE C EILING. REFER TO SECURITY ROUGH-IN DETAILS.
HA
W ALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. PROVIDE ALL LOW VOLTAGE W IR ING, INTERFACE W ITH SMS AND DOOR MOTOR AND BOX AS REQUIRED BY SYSTEM MANUFACTURER W ITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY
ROUGH-IN DETAILS.
HO
FA
W ALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN W ITH POW ER SUPPLY INSTALLED BY OTHERS. PROVIDE LOW VOLTAGE W IRING FROM POW ER SUPPLY TO HOLD OPEN AND INTERFACE W ITH SMS AND 120V POW ER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. SUBSCRIPT "FA" INDICATES DEVICES POW ERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE
ALARM SYSTEM REQUIRED FOR DOOR RELEASE. REFER TO SECURITY ROUGH-IN DETAILS.
CR
W ALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE CARD READER, CABLING AND 1-GANG BOX W ITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-
IN DETAILS.
CR EL
ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED W ITH ELEVATOR CONTRACTOR. W IRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE W ITH ELEVATOR CONTROLLER AND SMS, COORDINATE W ITH ELEVATOR CONTRACTOR.
REFER TO SECURITY ROUGH-IN DETAILS.
KC
W ALL MOUNTED COMBINATION KEYPAD/CARDREADER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE DEVICE, CABLING AND 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING.
K W ALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERW ISE). PROVIDE KEYPAD, CABLING AND 1-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING.
MD
W ALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERW ISE). PROVIDE MOTION DETECTOR, W ALL MOUNT HARDW ARE, CABLING AND 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
PP W
W ALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERW ISE). PROVIDE BUTTON, CABLING AND 1-GANG
BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
X W ALL MOUNTED SECURITY SYSTEM W IRING OUTLET MOUNTED BELOW COUNTER TOP. PROVIDE GROMMETED FACEPLATE, SECURITY SYSTEM CABLING AND 2-GANG BOX W ITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE
ACCESSIBLE CEILING.
CM
W ALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERW ISE). PROVIDE JACK, FACEPLATE, CABLING AND 1-GANG BOX W ITH 1" CONDUIT TO ABOVE CORRIDOR CEILING.
MIC
CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. PROVIDE MICROPHONE, CABLING AND 1-GANG BOX
MOUNTED IN CEILING.
BR
W ALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERW ISE). PROVIDE READER, CABLING AND 2-GANG BOX W ITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING. REFER TO SECURITY ROUGH-IN
DETAILS.
X
X
MD
PB W
W ALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERW ISE). PROVIDE
BUTTON, CABLING AND 1-GANG BOX W ITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING.
ELECTRONIC LATCH BOLT MONITORING. HARDW ARE AND INSTALLATION BY OTHERS. PROVIDE LOW VOLTAGE W IRING AND CONDUIT PATHW AYS FROM DOOR FRAME TO COMMON…
This is the start of the file's text. The full file is on GovTribe.