This set of documents includes construction drawings and specifications for a project to relocate nuclear medicine services at the Richard L. Roudebush VA Medical Facility in Indianapolis, Indiana. The project involves renovating space in the basement and on the first floor, including demolishing existing HVAC systems, ductwork, piping, air terminals and other mechanical equipment to prepare for new installations. Detailed drawings show plans for demolishing and installing HVAC, plumbing and medical gas systems. Schedules provide specifications for new air handling units, fans, air terminals, pumps and other mechanical equipment. The opportunity is solicited through the Department of Veterans Affairs with a solicitation number of 36C25021B0036 and project number 583-20-102. The renovation aims to centralize nuclear medicine services at the Indianapolis facility.
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
KEY PLAN
A
457 3.5
B
C
D
E
F
2.589
OH
OH
OH
OH
A-B020
OUTPATIENT
WAITING
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LO UNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIO ACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:2
:3
A M
FX101
LOWER LEVEL PLAN - FIRE
SUPPRESSIONGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
NOTES
1 LIMITS OF RENOVATED AREA REQUIRING EXISTING SPRINKLER
SYSTEM MODIFICATIONS. MODIFICATIONS INCLUDE, BUT ARE NOT
LIMITED TO, REPLACING ALL SPRINKLER HEADS AND BRANCH PIPING
TO CONFORM TO NEW ARCHITECTURAL LAYOUT AS NECESSARY.
2 ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE
LOCATED IN THIS ROOM.
3 LOCATION OF PATIENT LIFT, NO SPRINKLERS SHALL BE LOCATED
BETWEEN RAILS, BELOW MOVEABLE LIFT RAIL OR MOTOR.
GENERAL NOTES
A. REFER TO SHEET FX001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.
B. EXISTING CORRIDORS AND/ OR ROO MS TO REMAIN OPERATIONAL AT ALL
TIM ES DURING BUSINESS HOURS. AUTOM ATIC SPRINKLER SYSTEM(S)
SHALL BE MAINTAINED IN FULLY OPERATIONAL CONDITION (PER NFPA 241,
SPRINKLER SYSTEMS W ILL BE OPERATIONAL, BUT IM PAIRED W HILE CEILINGS
ARE REMOVED). SPRINKLER SYSTEM MAY BE TAKEN OFF-LINE FOR UP TO
8 HOURS, AS REQUIRED, TO MAKE MODIFICATIONS/ CONNECTIONS
TO EXISTING SYSTEM.
N
SCALE: 1/8" = 1'-0"FX101
1 LOWER LEVEL PLAN - FIRE SUPPRESSION
Revisions: Date:
GENERAL NOTES
A ALL PIPING IS ABO VE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN
EXPOSED STRUCTURE AREAS), UNLESS OTHERW ISE NOTED.
B REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES
AND PIPELINE DEVICES NO T INDICATED ON THE FLOOR PLAN.
C ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION W ITH ALL
TRADES IS CRITICAL, PRIOR TO INSTALLATION OF ANY W ORK.
D LOCATIONS AND SIZES O F EXISTING PIPING HAVE BEEN DETERMINED
FROM A REVIEW OF EXISTING DRAW INGS AND/OR SITE INSPECTIO N,
W HERE POSSIBLE. FIELD VERIFICATION OF EXACT LOCATIONS,
ELEVATIONS, INVERTS, SIZES, DIRECTION OF FLOW , ETC. SHALL BE
REQ UIRED PRIOR TO BEGINNING NEW W ORK.
E ALL PIPING SHALL BE REM OVED BACK TO W ITHIN TW O PIPE DIAMETERS
OF ACTIVE MAINS AND CAPPED, OR REMOVED BACK TO POINTS OF
CONNECTION OF NEW W O RK. INACCESSIBLE PIPING, W HERE SO NOTED,
TO BE ABANDONED SHALL BE DISCO NNECTED FROM ACTIVE MAINS AND
CAPPED OR PLUGGED IN CONCEALED LOCATIONS. ALL EXISTING PIPING,
EQ UIPMENT, FIXTURES, ETC., SHOW N ON REMOVAL PLAN(S) SHALL BE
REM OVED. THE MAJORITY OF THE W ORK TO BE REMOVED IS SHOW N.
REM OVE ALL INCIDENTAL AND/OR ABANDONED PIPING ETC., THAT M AY NOT
BE SHOW N BUT IS ASSO CIATED W ITH THE REMOVAL W ORK.
F NEW CO NNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAM E SIZE
AS THE EXISTING PIPING UNLESS OTHERW ISE NOTED.
G ALL REMOVED MATERIAL AND EQUIPMENT SO DESIGNATED BY THE
GOVERNMENT, SHALL BE TURNED OVER AND PLACED W HERE DIRECTED.
ALL MATERIAL AND EQUIPMENT, W HICH THE O W NER DOES NO T W ISH TO
RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTO R
RESPONSIBLE FOR THE REMOVAL.
H REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING
REQ UIREMENTS.
I ANY RENO VATION W ORK REQUIRED "OUTSIDE" OF THE
BO UNDARIES/ EXTENTS OF A SPECIFIC PHASE OF W ORK (OR
TEMPO RARY CONSTRUCTIO N W ALLS SHALL BE BID AS "NIGHT W ORK"
AND SHALL BE AS DIRECTED BY THE COR.
J ALL CORE DRILLS AND PIPE EXTENSIONS THRU THE EXISTING
STRUCTURAL FLOOR SLAB O R STRUCTURAL W ALL SHALL BE X-RAYED
TO DETERMINE THE EXACT LOCATION OF THE "REBARS" IN THE
STRUCTURAL SLAB. DO NOT CUT THE LO W ER (BOTTOM REBARS) IN
THE STRUCTURAL FLOOR SLAB.
K W ORKING ON EXISTING FLO ORS W ITH NO /LIM ITED ARCHITECTURAL
SCO PE, THE CONTRACTO R SHALL PRO VIDE ALL REQ UIRED
FLOOR/ W ALL PROTECTION (AS REQUIRED) AND REPLACE ANY
DAM AGED CEILING TILES W ITH NEW . RETURN AREA BACK TO ORIGINAL
CONDITION UPON COMPLETION OF W O RK.
L REFER TO ARCHITECTURAL FIRE RATED PARTITION PLAN(S) FOR
LOCATIONS AND FIRE RATINGS O F NEW AND EXISTING W ALL
ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES
SHALL BE PROTECTED AND/ OR FIRE STOPPED AS REQUIRED TO
MAINTAIN FIRE RATINGS INDICATED. COORDINATE W ITH ALL TRADES
TO ENSURE FIRE RATED PENETRATION REQ UIREMENTS AND DETAILS
ARE MET.
M ANNULAR SPACE O F ALL PIPE & OTHER SIMILAR PENETRATIONS OF
FIRE RATED ASSEM BLIES SHALL BE FIRE STOPPED. IN ADDITION,
PENETRATIONS THROUGH 0-HO UR RATED W ALLS & FLO OR SHALL
BE SEALED TO RETARD THE PASSAGE OF SM OKE.
N PHASING : REFER TO ARCHITECTURAL DRAW INGS FOR AN O UTLINE OF
PRO JECT PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS
MAY BE INCLUDED THROUGHOUT THIS DRAW ING SET.
O BID ITEM S: REFER TO ARCHITECTURAL DRAW ING AND SPECIFICATION
SECTION 01 00 00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES
DESCRIBING BID ITEM DETAILS MAY BE INCLUDED THROUGHOUT THIS
DRAW ING SET.
P. SUPPLY PIPING SHALL BE MINIM UM 0.5” SIZE. MEDICAL VACUUM AND
W ASTE ANESTHESIA GAS DISPOSAL PIPING SHALL BE M INIMUM 0.75" SIZE.
Q. ALL MEDICAL G AS SYSTEM INSTALLERS SHALL BE CERTIFIED TO THE
REQ UIREMENTS O F ASSE 6010. ALL MEDICAL GAS SYSTEM VERIFIERS
SHALL BE CERTIFIED TO THE REQUIREM ENTS OF ASSE 6030.
R MEDICAL GAS AND VACUUM SYSTEM INSTALLATION AND VERIFICATION
SHALL COMPLY W ITH THE REQUIREM ENTS OF NFPA 99, G AS AND
VACUUM SYSTEMS, 2018 EDITION.
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
FIRE SUPPRESSIO N HAZARD CLASSIFICATIO N AND HAZARD
CLASSIFICATIO N G ROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES.
REFER TO SCHEDULES.
EQUIPMENT, DEVICE, O R PLUMBING FIXTURE MARK. LETTER
DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NO TE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N
UNLESS NOTED OTHERW ISE.
DETAIL NO TE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLO OR ABO VE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIM ATE DIMENSIO N ABOVE FINISHED FLO OR TO TOP OR
BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO
CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE
PIPING SYMBOLS
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE
NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBO W DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
CARBON DIOXIDE OUTLET - HOSPITAL TYPE
MEDICAL AIR OUTLET - HO SPITAL TYPE
MEDICAL VACUUM INLET - HOSPITAL TYPE
NITROGEN OUTLET - HOSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN O UTLET - HOSPITAL TYPE
W AGD INLET - HOSPITAL TYPE
NATURAL GAS OUTLET - LAB TYPE
VACUUM OUTLET - LAB TYPE
VACUUM CLEANING STATION - W ALL
VACUUM CLEANING STATION - FLOOR
PIPING DESIGNATIONS
DOMESTIC COLD W ATER
DOMESTIC HOT W ATER
DOMESTIC HOT W ATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMO VED
HOT W ATER PIPE (140 DEGS. F.)
HOT W ATER PIPE (180 DEGS. F.)
HOT W ATER RETURN PIPE (140 DEGS. F.)
HOT W ATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC
W ATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLO W LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL G AS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROG EN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN W ASTE PIPE
LABORATO RY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY W ASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYG EN PIPE
(OVERFLOW ) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE W ATER PIPE
SPRINKLER PIPE (W ET)
SANITARY DRAINAGE PIPE
SOFT COLD W ATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED W ATER PIPE
SANITARY SEW ER VENT
W ASTE ANESTHESIA GAS DISPOSAL PIPE
W ATER SERVICE
LV
140R
180R
AR
CA
CO2
CW S
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
W AGD
W S
INDIRECT VENT PIPE
INDIRECT W ASTE PIPE
K
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS
FOR REQUIRED TYPE BASED ON
APPLICATIO NS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUG E OR THERMOM ETER
UNION
CLEANO UT
STRAINER
STRAINER W ITH A BLOW DOW N VALVE AND
HOSE CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T
PLUG IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERW ISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE W ITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
W ALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE O N RISER
V
VB
TP
CO
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO
SPECIFICATIONS FO R REQ UIRED TYPE BASED ON APPLICATIONS)
BALL VALVE, BUTTERFLY VALVE, GATE VALVE
VALVES AND FITTINGS
SOLENOID VALVE
S
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF
VALVE. PIPE DISCHARGE AIR G APPED TO FLOO R
DRAIN UNLESS NOTED OTHERW ISE.
W ATER METERM
ACID VENT PIPEAV
ACID W ASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL G AS)
AC - AIR COM PRESSOR OR AIR CONDITIO NER
ACC - ACCESS
ACCU - AIR COO LED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID W ASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTW N - BETW EEN
CA - COM PRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAM PER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED W ATER SUPPLY
CHR - CHILLED W ATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - M EDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT W ATER
CTR - CENTER
CU - COPPER
CW - COLD W ATER
CW S - COM BINATION W ATER SERVICE
OR CONDENSER W ATER SUPPLY
CW R - CONDENSER W ATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DET - DETAIL
DF - DRINKING FOUNTAIN OR W ATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DI - DEIO NIZED W ATER
DIA - DIAM ETER
DIM - DIM ENSION
DN - DOW N
DS - DOW N SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL (DIVISIO N 26)
EEW - EMERG ENCY EYE W ASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATO R
EQ - EQUAL
EQUIP - EQUIPM ENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERG ENCY SHO W ER
EQS - EQUIPM ENT SUPPLIER
EW C - ELECTRICAL W ATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER
MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANO UT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CO NNECTIO N
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT O N TOP
FPM - FEET PER M INUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
G - G AS OR NATURAL G AS
GA - G AUG E
GAL - G ALLON
GALV - G ALVANIZED
GC - G ENERAL TRADES
GD - G ARAG E DRAINAGE
GPM - G ALLONS PER M INUTE
GS - G AS SERVICE
GW - G REASE W ASTE
H2 - HYDROGEN
HB - HO SE BIBB
HC - HVAC (DIVISIO N 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HO RSEPOW ER O R HIGH POINT
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY W ATER
HPW R - HIGH PURITY W ATER RETURN
HR - HO SE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING , AND AIR
CONDITIONING
HW - HO T W ATER
HW R - HEATING HOT W ATER RETURN
HW S - HEATING HOT W ATER SUPPLY
IA - M EDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATIO N
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT W ASTE
JS - JANITOR SINK
K - KITCHEN W ASTE
KEC - KITCHEN EQUIPMENT
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD W ATER
LEC - LABORATORY EQUIPMENT
LHW - LABORATORY HOT W ATER
LHW R - LABORATORY HOT W ATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATO RY
VENT
LW - LABORATORY W ASTE
MA - M EDICAL COM PRESSED AIR
MAP - M ASTER ALARM PANEL (MEDICAL GAS)
MAX - M AXIMUM
MB - M OP BASIN
MC - M ECHANICAL (DIVISIO N 23)
MEZZ - M EZZANINE
MFR - M ANUFACTURER
MH - M ANHOLE
MIN - M INIMUM OR M INUTE
MISC - M ISCELLANEOUS
MTD - M OUNTED
MTG - M OUNTING
MPC - M EDIUM PRESSURE CO NDENSATE RETURN
MPS - M EDIUM PRESSURE STEAM SUPPLY
MU - W ATER MAKE-UP
MV - M EDICAL SURGICAL VACUUM
N2 - M EDICAL NITROGEN
N/C - NO RMALLY CLOSED
NG - G ASO LINE (NON-LEAD)
NIC - NO T IN CONTRACT
N/O - NO RMALLY OPEN
NO - M EDICAL NITROUS OXIDE
NOM - NO MINAL
NPW - NO N-PO TABLE W ATER
NPT - NATIONAL PIPE THREAD
NTS - NO T TO SCALE
O2 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR O VERFLOW
DRAIN
OFCI - OW NER FURNISHED CONTRACTOR
INSTALLED
OFOI - OW NER FURNISHED OW NER
INSTALLED
P - PROPANE GAS
PC - PLUMBING (DIVISION 22) OR PUMPED
CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REG ULATING VALVE
PSF - POUNDS PER SQ UARE FOOT
PSI - POUNDS PER SQ UARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQ UARE INCH GAUGE
PW - PURE W ATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS W ATER SUPPLY
ROR - REVERSE OSMOSIS W ATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (W ET)
SA - SHOCK ARRESTO R OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD W ATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOW ER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR W ASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQ UIPMENT
TOF - TOP OF FOO TING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER
DISCHARGE
TW - TEMPERED W ATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NO TED OTHERW ISE
V - VENT OR SANITARY SEW ER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THRO UGH RO OF
VR - VENT RISER
W / - W ITH
W /O - W ITHOUT
W - W ASTE
W AGD - W ASTE ANESTHESIA GAS DISPO SAL
W C - W ATER CLO SET
W CO - W ALL CLEANOUT
W H - W ALL HYDRANT OR W ATER HEATER
W IV - W ALL INDICATO R VALVE
W S - W ATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS. ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT NECESSARILY BE USED ON THIS PROJECT.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:3
:4
A M
P001
LEGEND, INDEX AND GENERAL
NOTESGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
INDEX OF DRAWINGS - PLUMBING
SHEET NUMBER SHEET NAME
P001 LEGEND, INDEX AND GENERAL NOTES
PD101 PARTIAL LOWER LEVEL PLAN - REMOVALS
PL100 PARTIAL UNDERSLAB PLAN - DRAINAGE
PL101 PARTIAL LOWER LEVEL PLAN - DRAINAGE
PP101 PARTIAL LOWER LEVEL PLAN - DISTRIBUTION
PG101 PARTIAL LOWER LEVEL PLAN - MEDICAL GAS
P601 SCHEDULES & DETAILS
P901 SOIL, WASTE & VENT DIAGRAM
CO
A
457 3.5
B
C
D
E
F
2.5
1ZVC-
3MED GAS OUTLETS -
- MED GAS OUTLETS
ZVC - 1
6"
4"
2" 1.25"
1.25"
2" 2"
0.75"
2" 2"0.75"
1.25" - MV
0.75" - MA
0.
M A
1.
M V
1 .25" - O2 1.25" - G
0.75" - MV
0.5" - O2
0.5" - MA
D H
W R
D H
W R
D H
W R
D H
W
D H
W D
C W
DHW
DCW
DHW
2" - V
0.75" - MA
0.75" - O2
1.25" - MV
3" - V
3"
V
VENT RISER UP
3"
V
3"
V
SK
ES
SK
SK
SKSK
SK
SK
5 5
N
KEY PLAN
GENERAL NOTES
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:4
:2
A M
PD101
PARTIAL LOWER LEVEL PLAN -
REMOVALSGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"PD101
1 PARTIAL LOWER LEVEL PLAN - REMOVALS
NOTES
1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.
2 REMOVE EXISTING FIXTURE AND ALL EXTRANEOUS DOMESTIC WATER
PIPING BACK TO WITHIN TWO (2) PIPE DIAMETERS OF ACTIVE MAIN AND
CAP OR TO POINT-OF-CONNECTION WITH NEW WORK. REMOVE ALL
EXTRANEOUS SANITARY DRAIN AND VENT PIPING BACK TO ACTIVE
MAIN AND CAP OR BACK TO POINT-OF-CONNECTION WITH NEW WORK.
CAP PIPING IN WALLS WHERE WALLS ARE TO REMAIN OR ABOVE
CEILING OR BELOW FLOOR SLAB WHERE WALLS ARE TO BE REMOVED.
NO PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
3 REMOVE MEDICAL GAS OUTLETS AND PIPING BACK TO ACTIVE MAIN
OR POINT-OF-CONNECTION WITH NEW WORK.
4 REMOVE EXISTING DHW/ DHWR PIPING AS SHOWN. DHW/ DHWR
PIPING TO BE REVISED AS SHOWN ON NEW WORK PLAN.
5 REMOVE FIXTURE OR ITEM OF EQUIPMENT (TYPE AS INDICATED) AND
REPLACE WITH NEW FIXTURE IN THE (SAME OR APPROXIMATE)
LOCATION. REFER TO NEW WORK PLANS.
A
457 3.5
B
C
D
E
F
2.5
2" - SAN
3"
S A
N
4"
S A
N
4" - SAN
2"
S A
N STM
STM
S T
M
S A
N
1 1
2 2
2 2
P531(2)
P528
P520
P520
4" DS
CAP
CO 1
P528
FD-C
CAP
SKSK
CO 1
CO
CO
CO
CO
P114
FD-C
P114
2" VR
FD-C
P421
P421
SK
P520
P520
CAP
CO1
CO1
FD
FD
FD
LAV
W C
W C
LAV
2"
W C
P531
P528
1.5" VR
N
KEY PLAN
GENERAL NOTES
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:4
:5
A M
PL100
PARTIAL UNDERSLAB PLAN -
DRAINAGEGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"PL100
1 PARTIAL UNDERSLAB PLAN - DRAINAGE
NOTES
1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.
2 PIPING LOCATED IN GRADE BELOW FLOOR SLAB.
3 SAW CUT AND TRENCH EXISTING FLOOR SLAB TO ACCOMMODATE
NEW SANITARY PIPING. PROVIDE BEDDING, BACKFILL AND
COMPACTION PER SPECIFICATIONS. PATCH CONCRETE FLUSH TO
FINISHED FLOOR AND RESURFACE TO MATCH ADJACENT FLOOR SLAB.
CO
CO
CO
A
457 3.5
B
C
D
E
F
2.5
V
P421
P114
FD-C
P114
FD-C
P421
P520
P520
VV
V
V
V
V
V
V
VVV
P520
P520
P707
FD-C
CAP
CAP
P528
P528 P528
P528
V
P528P531P531
P531
P531
P811
P528
1.5" VR
CO
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION
A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LO UNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIO ACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
V
V
VR
V
V
N
KEY PLAN
GENERAL NOTES
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.
A
3.5
B
C
D
2.5
D.5
A
3.5
B
C
D
2.5
VTR
V
3" VR
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:4
:1
A M
PL101
PARTIAL LOWER LEVEL PLAN -
DRAINAGEGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"PL101
1 PARTIAL LOWER LEVEL PLAN - DRAINAGE
NOTES
1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.
2 PROVIDE NEW FIXTURE (TYPE AS INDICATED) AT THE SAME LOCATION
AS EXISTING FIXTURE. EXTEND NEW PIPING AND CONNECT TO
EXISTING ROUGH-IN TO BE RE-USED/ RE-WORKED TO SERVE NEW
FIXTURE.
3 RISE VENT LINE WITHIN NEW CHASE.
N
Revisions: Date:
SCALE: 1/8" = 1'-0"PL101
2 PARTIAL FIRST FLOOR PLAN - DRAINAGE
TP
TP
A
457 3.5
B
C
D
E
F
2.5
1.5"
2"
0.5"
0.5"
2"
2"
1"
0.75"
0.75"
1"
1"
2"
0.5"
2"
P707
P421
P114
P114
P421
P520
P520
P520
P520
P811
P528
P528
P528
P528
1"
FD-C
P528
FD-C
0.75"
1"
P531
P531 P531
3 3
2"1" 2"2" 2" 1.5"
1.25"
1"
1"
0.5"
2"
2" P531
P528
0.5"
2" 2"
0.75"
P601 A
6 A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION
A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LO UNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIO ACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
0.5"
0.5"
N
KEY PLAN
GENERAL NOTES
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:4
:3
A M
PP101
PARTIAL LOWER LEVEL PLAN -
DISTRIBUTIONGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"PP101
1 LOWER LEVEL SUPPLY PLAN
NOTES
1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.
2 PROVIDE 2” FULL SIZE DCW MANIFOLD ENTIRE LENGTH OF PLUMBING
CHASE / WALL AND SERVE EACH FIXTURE INDIVIDUALLY FROM
MANIFOLD.
3 PROVIDE NEW FIXTURE (TYPE AS INDICATED) AT THE SAME LOCATION
AS EXISTING FIXTURE. EXTEND NEW PIPING AND CONNECT TO
EXISTING ROUGH-IN TO BE RE-USED/ RE-WORKED TO SERVE NEW
FIXTURE.
4 LOCATE EMERGENCY MIXING VALVE ABOVE CEILING.
5 ADJUST EXISTING BALANCING VALVE AS REQUIRED TO BALANCE
SYSTEM.
6 MAKE DCW CONNECTION FROM SUPPLY BOX TO REFRIGERATOR.
457 3.5
B
C
D
E
F
2.58
0.75" - MA
1.25" - MV
1.25"
0.75" 0.75"
0.75"0.5"
0.5"
1ZVC -
1ZVC -
0.
M A
1.
M V
ZVC
1.25"
0.5"
0.5"
1" 0.5"
0.5"
1.25"
0.5"0.5"
1.25"
0.75"
0.75"
MA
MV
O2
0.75" - MV
0.5" - MA0.5" - O2
0.5"
0.5"
0.75"
0.75"
0.5" 0.5"
0.5" 0.5"
0.75"
O2
MA MV
0.75" 0.5" 0.5"
1" 1.25" 0.75" 0.5"
0.5"
1.25"
O
1.25"
1"
O2
MV
MA
O2
MV
MA O2
1.25" 0.75"0.75"
0.75"
0.5"
0.5"
0.5"
0.5" 0.75"
0.5" 0.5" 0.75"
0.75"
0.5"
0.5"
0.75"
0.5"
0.5"
MV
MA O2
O2
MV
MA
SENSORS
SENSORS
AAP
SENSORS
A-B005
COMBINED
PET
CONTROL
ROOM
A-B007
HOT LAB
A-B008
DOSE
ADMIN.
ROOM
A-B009
DOSE
ADMIN.
ROOM
A-B010
DOSE
ADMIN.
ROOM
A-B013
READING &
CONSULTATION
A-B012
DOSE
ADMIN.
ROOM
A-B014
EQUIP
CALIBRATION A-B01
SOILED
UTILITY
A-B026
TOILET,
STAFF
A-B027
TOILET,
STAFF
A-B028
PET
TOILET,
PATIENT
A-B029a
NM SCAN 1
A-B029
NM
CONTROL
RM
A-B016
NM TOILET,
PATIENT
A-B017
NM TOILET,
PATIENT
A-B018
SUPERVISOR
OFFICE
A-B020
OUTPATIENT
WAITING
CB-9
CORRIDOR
CB-10
AUDITORIUM
CORRIDOR
A-B025
ELEC
ROOM
A-B004a
PET
EQUIPMENT
ROOM
A-B004
PET / CT 2
A-B002
DOSE
ADMIN.
ROOM
A-B003
DOSE
ADMIN.
ROOM
A-B006a
PET
EQUIPMENT
ROOM
A-B024
PATIENT
INTERVIEW
ROOM
A-B023
CARDIAC
STRESS
TESTING
A-B021
INPATIENT
HOLDING
A-B022
THYROID
UPTAKE
C-5A
ALCOVE
A-B030
DIGI ROD,
MOBILE
EQUIPMENT
A-B031
CLEAN
SUPPLY
A-B029b
NM SCAN 2
C-6a
CLOSET
C-2
NORTH
CORRIDOR
A-B006
PET / CT 1
A-B019
MSA /
SCHEDULING
A-B015
STAFF
LO UNGE
1A
PATIENT
EDUCATION
KIOSK
3A
HOLDING
BAY 1
3B
HOLDING
BAY 2
A-B007a
RADIO ACTIVE
WASTE
STORAGE
3C
HOLDING
BAY 3
C-5
WEST
CORRIDOR
C-4
SOUTH
CORRIDOR
C-6
CORRIDOR
C-3
EAST
CORRIDOR
C-1
STAFF
ENTRANCE
CORRIDOR
A-B039
QCIS
A-B038
TEAM
ROOM
N
KEY PLAN
GENERAL NOTES
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:4
:4
A M
PG101
PARTIAL LOWER LEVEL PLAN -
MEDICAL GASGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"PG101
1 PARTIAL LOWER LEVEL PLAN - MEDICAL GAS
NOTES
1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.
TRAP PRIMER, W ITH DISTRIBUTION
UNIT W HEN SERVING MULTIPLE
DRAINS. LOCATE ABOVE CEILING
IN FINISHED AREAS.
0.5''SUPPLY SHALL BE
OFF TO P OF MAIN
COLD W ATER MAIN
T P
T P
W ALL
FINISHED CEILING
W HERE APPLICABLE
FLO OR DRAINS
FLOOR
TP
PIPING TO FLOOR DRAINS
SHALL BE RUN BELO W FLOOR,
UNLESS NO TED OTHERW ISE.
INSTALL PIPING CONCEALED
IN W ALL IN FINISHED AREAS.
INSTALL PIPING TIGHT TO W ALL
SURFACE IN UNFINISHED AREAS.
NOTE:
1 REFER TO FLOO R PLANS FOR REQ UIRED NUMBER O F
VALVES, VALVE SERVICES AND SIZES AT EACH INDIVIDUAL LOCATION.
VACUUM GAUGE
PRESSURE
GAUGE, TYPICAL
MEDICAL GAS O R VACUUM
PIPING TO/FROM STATION
INLETS AND OUTLETS
SYSTEM AND SERVICE
AREA LABEL, TYPICAL
MEDICAL GAS O R VACUUM
PIPING TO/FROM
DISTRIBUTION SYSTEM
MIN. 45 DEG REES
BRANCH OR RUNOUT
TO STATION OUTLET,
INLET O R SPECIAL STATION
MAIN OR BRANCH PIPING
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:3
:5
A M
P601
SCHEDULES & DETAILS
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
FIXTURE SCHEDULE
SYMBOL
MOUNTING
HEIGHT DESCRIPTION
FLOW FIXTURE UNITS SUPPLY WASTE & VENT
REMARKSGPM GPF DRAINS
WATER
COLD HOT TEPID OUTLET VENT DIRECT INDIRECTCOLD HOT
P114 FLOOR SET WATER CLOSET/ BARIATRIC/ FLOOR SET 1.6 4 10 2" MANUAL/ FLUSH VALVE
P421 FLOOR SET LAVATORY/ BARIATRIC/ PEDESTAL 1.5 1 0.5 0.5 0.5" 0.5" 1.25" 1.5" FAUCET BY CHICAGO OR APPROVED EQUAL/ MANUAL/ GOOSENECK
SPOUT/ T'STATIC MIXING VALVE/
P520 36" TO RIM SINK/ SCRUB/ WALL HUNG/ SENSOR CONTROL/ 1.5 2 2 2 0.5" 0.5" 1.25" 1.5" HARD WIRED/ SENSOR OPERATED/ GOOSENECK SPOUT/ T'STATIC
MIXING VALVE
P528 C'TOP SINK/ SST/ SINGLE COMP'T/ 21" x 22"/ 1.5 2 2 2 0.5" 0.5" 1.5" 1.5" FAUCET BY CHICAGO OR APPROVED EQUAL/ MANUAL/ GOOSENECK
SPOUT/ T'STATIC MIXING VALVE
P531 C'TOP SINK/ SST/ INTEGRAL TO COUNTER 1.5 2 2 2 0.5" 0.5" 1.5" 1.5" FAUCET BY CHICAGO OR APPROVED EQUAL/ MANUAL/ GOOSENECK
SPOUT/ T'STATIC MIXING VALVE
P707 FLOOR SET EMERGENCY SHOWER AND EYE AND FACE WASH 1.25" 1.25" 1.5"
P811 48" WATER SUPPLY BOX/ COFFEE MAKER AND ICE MAKER 2 1 1 0.5" PROVIDE FLEXIBLE CONNECTOR TO EQUIPMENT
DRAIN SCHEDULE
SYMBOL DESCRIPTION
BODY STRAINER / GRATE TOP FINISH
C.I. S.S. C.R. BRASS RD. SQ. ADJUST. FLAT RECESS DOME
NICKLE
BRONZE C.I. C.R. S.S.
FD-C 3" LIGHT DUTY/ DOUBLE DRAINAGE/ VANDAL RESISTANT (TYPE C)/ TRAP PRIMER CONNECTION ● ● ● ●
SCALE: NONE
TRAP PRIMER
A
SCALE: NONE
MEDICAL GAS ZONE VALVE CABINET
B
SCALE: NONE
BRANCH TAKE-OFF PIPING - MEDICAL GAS
C
1.25" 3" 4"
1.5"
1.5"
1.5"
1.5"
1.5"
CO
CO
P520
P520
P421
P421
P520
P520
P114
P114
FD-C
FD-C
FD-C
CAP
L LVL
P531
P531
P531
P528
P528
P528
P528
P528
2"
1.5"
3"
2"
2"
2"
1.5"
3"
3"
3"
2"
3"
2"
3"3"
4"
4"
4"
1.
5"
3"
2"
2"
2"
2"
1.5"
4"
4"
1.
5"
4"
1.5"
1.5"
3"
3"
2"
1.5"
4"
4"
3"
3"4"
4"
3" 2"
3"
CO
CAP
CAP
CAP
CAP
P531
2"
3" 3"
1.5"
L LVL
2"
2"
P528
2"
2"
2"
2"
2"
4"
L LVL
L LVL
L LVL
L LVL
3"
3"
3"
2"
3"
1.5"
1.
5"
2"
1ST FLR
4" VTR
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
C
B
IM
\M o d e l\
-0
-M E
P -C e n tr a l_ a b n o rm a n
.r v t
/2
/2
:0
:1
A
M
P901
SOIL, WASTE & VENT DIAGRAM
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 DPB ABN
BID DOCUMENTS
FULLY SPRINKLERED
SOIL, WASTE & VENT DIAGRAM
NOTE: ALL SYMBOLS AND ABBREVIATIONS
ARE SUBJECT TO MODIFICATIONS
ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS
MIGHT NOT NECESSARILY BE USED ON
THIS PROJECT.
ABBREVIATIONS
AC - AIR COM PRESSOR OR AIR CONDITIO NER
ACCU - AIR COO LED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOO R
AFG - ABOVE FINISHED GRADE
AFMS - AIR FLOW MEASURING STATION
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
ATC - AUTOMATIC TEMPERATURE CO NTRO L
(SYNO NYMOUS W ITH BAS)
BAS - BUILDING AUTOMATION SYSTEM
BDD - BACK DRAFT DAM PER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
CBD - COUNTER BALANCED BACKDRAFT
DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTO R
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED W ATER SUPPLY
CHR - CHILLED W ATER RETURN
CHGR - CHILLED W ATER GLYCO L SOLUTION
RETURN
CHGS - CHILLED W ATER GLYCO L SOLUTION
SUPPLY
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
CTR - CENTER
CU - COPPER
CW - COLD W ATER
CW R - CONDENSER W ATER RETURN
CW S - CONDENSER W ATER SUPPLY
D - DRAIN LINE
DB - DRY BULB
DDC - DIRECT DIGITAL CONTROLS
DI - DEIO NIZED W ATER
DIA - DIAM ETER
DIM - DIMENSION
DN - DOW N
DW G - DRAW ING
EA - EACH OR EXHAUST AIR
EAT - ENTERING AIR TEMPERATURE
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATO R
EQUIP - EQUIPM ENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
EQS - EQUIPM ENT SUPPLIER
EW T - ENTERING W ATER TEM PERATURE
EXH - EXHAUST
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
FD - FLOOR DRAIN
FF - FINISHED FLOOR ELEVATION
FLR - FLOOR
FOB - FLAT O N BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL G AUG E
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT O N TOP
FPM - FEET PER M INUTE
FSC - FIRE SUPPRESSION CONTRACTO R
(DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUG E
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GPM - GALLONS PER M INUTE
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HG - REFRIGERANT HOT GAS
HP - HORSEPOW ER
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HR - HOUR
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR
CONDITIONING
HW - HOT W ATER
HW R - HEATING HOT W ATER RETURN
HW S - HEATING HOT W ATER SUPPLY
ID - INSIDE DIAM ETER
INV - INVERT ELEVATION
IN - INCHES
KEC - KITCHEN EQUIPMENT
CONTRACTOR
L - LENGTH
LAT - LEAVING AIR TEMPERATURE
LAV - LAVATORY
LBS - POUNDS
LPC - LOW PRESSURE CONDENSATE
RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LW T - LEAVING W ATER TEMPERATURE
MAX - M AXIMUM
MDD - M OTORIZED DAM PER
MEZZ - M EZZANINE
MFR - M ANUFACTURER
MH - M ANHOLE
MIN - M INIMUM OR MINUTE
MISC - M ISCELLANEOUS
MTD - M OUNTED
MTG - M OUNTING
MPC - M EDIUM PRESSURE CONDENSATE
RETURN
MPS - M EDIUM PRESSURE STEAM
SUPPLY
MU - W ATER MAKE-UP
N/C - NORMALLY CLOSED
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NOM - NOM INAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOO R AIR
OBD - OPPOSED BLADE DAM PER
OD - OUTSIDE DIAMETER
OFCI - OW NER FURNISHED
CONTRACTOR INSTALLED
OFOI - OW NER FURNISHED OW NER
INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR
(DIVISION 22)
OR PUMPED CO NDENSATE
RETURN
PLBG - PLUMBING
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FO OT
PSI - POUNDS PER SQUARE INCH
PSIG - POUNDS PER SQUARE INCH
GAUGE
RA - RETURN AIR
RAD - RADIUS
RCP - REFLECTED CEILING PLAN
RD - ROO F DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS W ATER
SUPPLY
ROR - REVERSE OSMOSIS W ATER
RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
S - SPRINKLER (W ET)
SA - SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD W ATER
SHT - SHEET
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SRV - SAFETY RELIEF VALVE
SS - STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL O R STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
V - VENT
VAC - VACUUM
VEL - VELOCITY
VIB - VALVE IN BO X
VOL - VOLUME
VTR - VENT THROUGH ROOF
VR - VENT RISER
W / - W ITH
W /O - W ITHO UT
W B - W ET BULB
W CO - W ALL CLEANOUT
GENERAL FLOOR PLAN NOTES
PLAN NO TE. APPLIES ONLY TO THE SHEET W HICH IT IS SHO W N
UNLESS NOTED OTHERW ISE.
DETAIL NO TE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
A1
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER
DESIGNATIONS REFER TO SCHEDULES.
H1 H1OR
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
H2
B
H2
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
H2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION
H2 = SHEET W HERE DETAIL IS LOCATED
1 "UP TO" SYMBOL (ITEM ON FLO OR ABO VE)
APPROXIM ATE DIMENSIO N ABOVE FINISHED FLOO R TO TOP OR
BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE
10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOD: 8' - 10"
BOD: 7' - 2"
20x20
20x20
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR
BOTTOM OF DUCTW ORK, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE
OF PIPE, UNLESS NOTED OTHERW ISE
DL-1
UC-X DOOR UNDERCUT. X = HEIGHT O F UNDERCUT IN INCHES; 0.75 INCH
UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.
DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.
CONNECT TO EXISTING
HVAC PIPING DESIGNATIONS
CHILLED W ATER SUPPLY PIPECHS
CONDENSER W ATER SUPPLY PIPECW S
CONDENSER W ATER RETURN PIPECW R
DRAIN LINE. PITCH IN DIRECTION INDICATEDD
HEATING HOT W ATER SUPPLY PIPEHW S
HEATING HOT W ATER RETURN PIPEHW R
W ATER MAKE-UP PIPEMU
VENT PIPEV
REFRIGERANT LIQ UID LINERL
REFRIGERANT SUCTION LINERS
EXPANSION TANK PIPEET
REFRIGERANT HOT GAS LINEHG
LOW PRESSURE CONDENSATE RETURN PIPELPC
LOW PRESSURE STEAM SUPPLY PIPELPS
MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC
MEDIUM PRESSURE STEAM SUPPLY PIPEMPS
PUMPED CONDENSATE RETURN PIPEPC
HIGH PRESSURE CONDENSATE RETURN PIPEHPC
HIGH PRESSURE STEAM SUPPLY PIPEHPS
STEAM SUPPLY PIPE - NUM BER INDICATES P.S.I.G .10
MISC SYMBOLS
DUCTWORK SYMBOLS
ROUND BRANCH DUCTW ORKCONICAL
FITTING
ACOUSTIC
FITTING
ACOUSTIC
FITTING
ADAD
D
R R
D
RECTANGULAR BRANCH DUCTW ORK
SQUARE TEE W ITH TURNING VANES
NOTE: ALL SQUARE ELBOW S IN
RECTANGULAR AND ROUND / OVAL
DUCTW ORK SHALL BE PROVIDED W ITH
TURNING VANES. REFER TO
SPECIFICATIONS FOR ADDITIONAL DETAILS.
EXISTING DUCTW ORK TO REMOVED
RETURN AIR, RELIEF AIR, OR TRANSFER AIR
DUCTW ORK. (UP AND DO W N) RADIUSED
OR SQUARE W ITH TURNING VANES.
SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.
(UP AND DO W N) RADIUSED OR SQUARE
W ITH TURNING VANES.
EXHAUST AIR DUCTW ORK. (UP AND
DOW N) RADIUSED OR SQUARE W ITH
TURNING VANES.
RECTANGULAR AND ROUND / OVAL
DUCTW ORK RISE / DRO P W ITH 90° RADIUSED
OR SQUARE ELBOW S AND TURNING VANES.
RADIUS ELBOW
90° SQUARE ELBOW (W ITH TURNING VANES)
NOTE: ALL SQUARE ELBOW S IN
RECTANGULAR AND ROUND DUCTW ORK
SHALL BE PROVIDED W ITH TURNING VANES.
ACCESS DOOR OR PANEL
DUCTW ORK RISE IN DIRECTION O F AIR
FLO W
DUCTW ORK DROP IN DIRECTION OF
AIR FLO W
DUCTW ORK W ITH ACOUSTICAL LINER.
LISTED DUCT SIZES ARE INSIDE CLEAR
DIMENSIO NS.
RECTANGULAR ROUND / OVAL
FLEXIBLE DUCTW ORK
FLEXIBLE CONNECTION
DUCTW ORK CONSTRUCTED OF
SPECIAL M ATERIAL AS NOTED
DIRECTION OF PITCH
RECTANGULAR DUCTW ORK
DIMENSIONS (W x H)26x20
ROUND DUCTW ORK DIM ENSIONS (D IA)26ø
OVAL DUCTW ORK DIMENSIONS (W x H)26x20 OV
DUCTWORK DEVICE SYMBOLS
W ALL OR DUCTW O RK M OUNTED AIR DEVICE. SG1 = DESIGNATION
(REFER TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION
SIZE (IN INCHES). 300 = REQUIRED CFM. 9'-0" = M OUNTING HEIGHT
FROM FLOOR TO BO TTOM O F GRILLE.
A3 10ø
MANUAL BALANCING DAMPER W ITH LO CKING DEVICE
BDD = BACK DRAFT DAM PER
CBD = COUNTER-BALANCED BACK DRAFT DAM PER
SD = SMOKE DAMPER
FS = COMBINATION FIRE - SMO KE DAMPER
MDD = MOTORIZED DAMPER
AFMS = AIR FLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR. COORDINATE LO CATIO N.
HUMIDITY SENSOR - DUCT M OUNTED
SG1
20x12
BOG: 9'-0"
XXX
A-D
XX
H
SD
SP
AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR
DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS).
10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR
DEVICE DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S.
AIR DEVICE SHOW N IS 2-W AY SIDE THROW . METHOD OF
IDENTIFICATION ALSO APPLIES TO O THER CEILING MOUNTED AIR
DEVICES.
FIRE DAMPER
A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)
D OR S = DYNAMIC OR STATIC
STATIC PRESSURE SENSOR - DUCT MO UNTED
C
CARBON DIOXIDE SENSOR - DUCT MO UNTED
S
TEMPERATURE SENSOR - DUCT M OUNTED
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS
FOR REQUIRED TYPE BASED ON
APPLICATIO NS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUG E OR THERMOM ETER
COMBINATION SHUTOFF AND BALANCING
VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGS
DOUBLE LINE SINGLE LINE
10"
TOE: 3' - 0"
BOE: 0' - 6"
CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR
CHILLED W ATER GLYCOL SO LUTION SUPPLY PIPECHGS
CHILLED W ATER RETURN PIPECHR
SQUARE THROAT / RADIUS HEEL
FITTINGS NOT ACCEPTABLE
PIPING SYMBOLS
DOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTIO N (NO TE:
BULLHEAD TEE'S ARE NOT
PERMITTED)
DIRECTION OF PITCH
DROP
ELBO W DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PIPE RISER
RADIUS'D BRANCH
RADIUS'D TEE
EXISTING DUCTW ORK TO REMAIN
UNLESS NOTED OTHERW ISE ON
DRAW INGS, 15° MAX FOR DIVERGING, 30°
MAX FOR CONVERGING TRANSITION
EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED
OTHERW ISE.
SPACE TEMPERATURE SENSO R / THERMOSTAT. W HEN W ALL M OUNTED, MOUNTING
HEIGHT 46" TO M EET ADA REQUIREMENTS. W HEN MO UNTED NEXT TO W ALL SW ITCH
COORDINATE W ITH ARCHITECT.
T
DP
DIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO
MEET ADA REQUIREM ENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH CO ORDINATE W ITH
ARCHITECT.
H
HUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO M EET ADA
REQUIREMENTS. W HEN M OUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA
REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
C
CO
CARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET
ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH
ARCHITECT.
TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO M EET ADA
REQUIREMENTS. W HEN M OUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH
ARCHITECT.
S
S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM .
STATIC PRESSURE SENSOR.SP
STRAINER W ITH A BLOW DOW N VALVE AND
HOSE CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T
PLUG IN AND OUT
EXPANSION JOINT
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
2 PO RT AUTOMATIC CONTROL VALVE
3 PO RT AUTOMATIC CONTROL VALVE
QUICK OPENING M ANUAL VALVE
VACUUM BREAKER
NEEDLE VALVE
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE W ITH STOP
END CAP
GLOBE VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE O N RISER
A
M
M
N
V
VB
SOLENOID VALVE
S
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE
DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS
NOTED OTHERW ISE. FOR STEAM SYSTEMS PIPE
DISCHARGE TO OUTDOORS.
W ATER METERM
PRESSURE GAUG E W ITH COCK AND SIPHON LOO P
BI-METALIC STEAM TRAP AND DRIP ASSEMBLY
THERMODYNAMIC STEAM TRAP AND DRIP
ASSEMBLY
INVERTED BUCKET STEAM TRAP AND DRIP
ASSEMBLY
FLOAT AND THERMOSTATIC STEAM TRAP
AND DRIP ASSEM BLY
THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
BM
TD
IB
FT
TS
FLO W METER
F
UNION
CLEANO UT
STRAINER
AUTOMATIC PRESSURE INDEPENDENT
CONTROL VALVE
M
P: 937-224-0861 www.heapy.com
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
PROJECT NO. 2019-05201
D a y d a ta
\H e a p y D o c u m e n ts
\l d ri c h te r\
M y D o c u m e n ts \2
-0
-M E
P -C e n tr a l_ ld ri c h te r.
rv t
/2
/2
:4
:0
A M
M001
LEGEND, INDEX, AND GENERAL
NOTESGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 JPR LDR
BID DOCUMENTS
FULLY SPRINKLERED
SHEET LIST - MECHANICAL
SHEET NUMBER SHEET NAME
M402 ENLARGED MECHANICAL ROOM HVAC PLAN
M403 PARTIAL SIXTH FLOOR HVAC ROOF PLANS
M404 HVAC ISOMETRIC VIEWS
M501 HVAC DETAILS
M502 HVAC DETAILS
M503 HVAC DETAILS
M504 HVAC DETAILS
M505 HVAC DETAILS
M600 HVAC CONTROL SCHEMATICS
M601 HVAC CONTROL SCHEMATICS
M602 HVAC CONTROL SCHEMATICS
SHEET LIST - MECHANICAL
SHEET NUMBER SHEET NAME
M001 LEGEND, INDEX, AND GENERAL NOTES
M002 HVAC SCHEDULES
M003 HVAC SCHEDULES
M004 HVAC SCHEDULES
MD101 LOWER LEVEL HVAC DEMOLITION PLAN
MH101 LOWER LEVEL HVAC DUCTWORK PLAN
MH102 FIRST FLOOR HVAC DUCTWORK PLAN
MH103 ROOF LEVEL HVAC DUCTWORK PLAN
MP101 LOWER LEVEL HVAC PIPING PLAN
M401 ENLARGED MECHANICAL ROOM HVAC DEMOLITION PLAN
GENERAL NOTES
27. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LOCATION OF CEILING DIFFUSERS, REGISTERS, AND GRILLES.
28. W ATER PIPE CONNECTIONS TO AIR HEATING AND COO LING COILS SHALL
BE MADE TO PROVIDE COUNTER FLOW BETW EEN W ATER AND AIR.
29. W ALL TYPE EXHAUST REG ISTERS NOTED AS "BR" O N DRAW INGS ARE TO
BE INSTALLED W ITH BOTTOM OF REG ISTERS SEVEN INCHES ABOVE FINISHED
FLOOR.
30. W HERE DUCTS O R PIPES ARE REMOVED THRU W ALL/FLOOR/ROOF THAT IS
TO REMAIN, PATCH W ALL/FLOO R/RO OF OPENING TO MATCH EXISTING W HERE
OPENING IS NO T RE-USED.
31. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERW ISE
NOTED.
32. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE
INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER
THIS W ORK TO MATCH EXISTING.
33. IN GENERAL, KEEP DUCT AND PIPING MAINS NEXT TO UNDERSIDE O F
STRUCTURE.
34. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEM S
NOT DESIRED BY THE VA SHALL BE REMOVED FROM THE PREMISES AND
DISPO SED OF PROPERLY BY THE CONTRACTOR.
35. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW EVERY
VERTICAL OR HORIZONTAL OFFSET W HICH M AY BE NECESSARY TO COMPLETE
THE SYSTEMS. CO ORDINATE W O RK IN ADVANCE W ITH ALL OTHER TRADES
AND REPORT IMMEDIATELY ANY DIFFICULTIES W HICH CAN BE ANTICIPATED.
36. FIELD VERIFY EXISTING CONDITIO NS, INCLUDING DUCT, PIPE AND
EQ UIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO PERFORMING W ORK.
37. HEPA FILTERED EXHAUST IS REQUIRED TO MAINTAIN A MINIMUM OF 0.01"
W .G. NEGATIVE PRESSURE IN CONSTRUCTION AREAS. COO RDINATE W ITH
GENERAL CONTRACTOR AND THE COR.
38. ALL ABANDONED EXTRANEO US PIPING , DUCTW ORK, SUPPORTS,
CONTRO LS, ETC. SHALL BE REMOVED.
39. TERMINATE PIPING AND DUCTW ORK BELOW FLOO RS, ABOVE CEILINGS,
ETC., IN CONCEALED SPACES. ALL CUTTING AND PATCHING SHALL MATCH
EXISTING FINISHES.
40. W HERE CONTROL DEVICES ARE REMOVED, PNEUM ATIC LINES SHALL BE
REM OVED BACK TO MAIN AND CAPPED; AND CONTROL W IRING AND CONDUIT
SHALL BE REMOVED BACK TO SOURCE.
41. ALL EXISTING DUCTW ORK, PIPING, EQUIPMENT, CO NTRO LS, ETC. SHOW N
ON REM OVAL PLAN(S) SHALL BE REMOVED. THE MAJORITY OF W ORK TO BE
REM OVED IS SHOW N. REMOVE ALL INCIDENTAL AND/O R ABANDONED
DUCTW ORK, PIPING, ETC. THAT MAY NOT BE SHOW N BUT IS ASSOCIATED W ITH
THE REMOVAL W ORK.
42. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING,
SERVICING, M AINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY
ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON
PERM ANENT PLATFORMS, W ITHOUT THE USE OF PORTABLE LADDERS.
EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF
VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.
43. W HERE EXISTING HVAC UTILITIES IN SERVICE W ILL BE DISRUPTED DURING
THE CONSTRUCTION OF THIS PROJECT, THIS W ORK SHALL BE PERFORMED ON
W EEKENDS OR W EEK NIGHTS. DOW NTIM E SHALL BE KEPT TO A MINIM UM, AND
SHALL BE COORDINATED AND SCHEDULED W ELL IN ADVANCE W ITH THE COR.
44. W HEN NEW SUPPLY AND RETURN AIR DUCTS ARE CONNECTED TO
EXISTING DUCTW ORK, CLEAN BOTH NEW AND EXISTING DUCTW ORK BY
MOPPING AND VACUUM CLEANING INSIDE AND OUTSIDE BEFORE OPERATION.
CLEANING OF EXISTING DUCTW ORK SHALL BE LIM ITED TO THE IMMEDIATE
AREA W ITHIN REACH OF THE OPEN END OF THE DUCT.
45. RUNOUT PIPING TO TERM INAL UNITS SHALL BE 0.75” SIZE UNLESS
OTHERW ISE NOTED. REFER TO AIR TERMINAL UNIT SCHEDULE(S).
46. APPROXIMATE ELEVATIONS NOTED ON FLOOR PLANS ARE TO THE BOTTOM
OF DUCTS AND EQUIPMENT, AND TO THE CENTER OF PIPES.
47. REFER TO ELECTRICAL DRAW INGS FOR VARIABLE SPEED MOTOR
CONTRO LLERS ASSOCIATED W ITH MECHANICAL EQUIPMENT.
48. ALL INSULATED DUCTW ORK AND PIPING SHALL HAVE DAM PER/VALVE
HANDLE EXTENSIONS.
49. CONTROL CONTRACTORS RESPONSIBILITES ARE LISTED IN SPECIFICATION
SECTION 23 09 23, SECTIO N 1.1.
50. SME DIVISION 26 AND 27 W O RK IS SHOW N ON DIVISIO N 23 DRAW INGS.
W ORK INCLUDES 120V POW ER CIRCUITRY, BREAKERS, VFD'S, DISCONNECTS,
VO ICE/DATA OUTLETS, CONDUIT, ETC. DIV 26/27 CONTRACTOR TO
COORDINATE ALL REQ UIREMENTS CLOSELY W ITH DIV 01 AND DIV 23
CONTRACTORS.
51. EXTEND POW ER, CO MMUNICATIONS, SIGNAL, AND OTHER W IRING
REQ UIRED TO ACCOM PLISH THE SPECIFIED STRATEGIES AND OBJECTIONS
FROM NEW M ETERS AND…