583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part24.pdf

PDF 5 MB Posted

Attached to
Z1DA--Renovate Nuclear Med 583-20-102 (VA-21-00037478)
Solicitation number
36C25021B0036
Issued by

About this file

This set of documents includes construction drawings and specifications for a project to relocate nuclear medicine services at the Richard L. Roudebush VA Medical Facility in Indianapolis, Indiana. The project involves renovating space in the basement and on the first floor, including demolishing existing HVAC systems, ductwork, piping, air terminals and other mechanical equipment to prepare for new installations. Detailed drawings show plans for demolishing and installing HVAC, plumbing and medical gas systems. Schedules provide specifications for new air handling units, fans, air terminals, pumps and other mechanical equipment. The opportunity is solicited through the Department of Veterans Affairs with a solicitation number of 36C25021B0036 and project number 583-20-102. The renovation aims to centralize nuclear medicine services at the Indianapolis facility.

View the file

Other files

File Type Posted
Amendment A00006.docx DOCX document
Amendment A00006 RFI Responses.docx DOCX document
Amendment 36C25021B0036 A00005.pdf PDF
A00004- Corrected Statement of Work.pdf PDF
Amendment 36C25021B0036 A00004.pdf PDF
A00004 - RFI Responses.docx DOCX document
A0004 - 08 71 00 - Door Hardware.pdf PDF
A00004 - 10 25 13 - Patient Bed Service Walls.pdf PDF
A00004 - Door Schedule.pdf PDF
Amendment 36C25021B0036 A00003.pdf PDF
Amendment A00002.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
A0001 - RFI 1 ShieldingReportComplete.pdf PDF
A0001 - RFI 2- GC101.pdf PDF
A0001 - RFI Responses.docx DOCX document
Amendment A0001.docx DOCX document
A0001 - RFI 4- Door Schedule.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part18.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part23.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part22.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part11.pdf PDF
Specifications.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part21.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part13.pdf PDF
Wage Determination.txt TXT text file
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part15.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part4.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part20.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part8.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part6.pdf PDF
36C25021B0036 Solicitation Document.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part11.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part2.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part3.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

KEY PLAN

A

457 3.5

B

C

D

E

F

2.589

OH

OH

OH

OH

A-B020

OUTPATIENT

WAITING

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LO UNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIO ACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:2

:3

A M

FX101

LOWER LEVEL PLAN - FIRE

SUPPRESSIONGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

NOTES

1 LIMITS OF RENOVATED AREA REQUIRING EXISTING SPRINKLER

SYSTEM MODIFICATIONS. MODIFICATIONS INCLUDE, BUT ARE NOT

LIMITED TO, REPLACING ALL SPRINKLER HEADS AND BRANCH PIPING

TO CONFORM TO NEW ARCHITECTURAL LAYOUT AS NECESSARY.

2 ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE

LOCATED IN THIS ROOM.

3 LOCATION OF PATIENT LIFT, NO SPRINKLERS SHALL BE LOCATED

BETWEEN RAILS, BELOW MOVEABLE LIFT RAIL OR MOTOR.

GENERAL NOTES

A. REFER TO SHEET FX001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.

B. EXISTING CORRIDORS AND/ OR ROO MS TO REMAIN OPERATIONAL AT ALL

TIM ES DURING BUSINESS HOURS. AUTOM ATIC SPRINKLER SYSTEM(S)

SHALL BE MAINTAINED IN FULLY OPERATIONAL CONDITION (PER NFPA 241,

SPRINKLER SYSTEMS W ILL BE OPERATIONAL, BUT IM PAIRED W HILE CEILINGS

ARE REMOVED). SPRINKLER SYSTEM MAY BE TAKEN OFF-LINE FOR UP TO

8 HOURS, AS REQUIRED, TO MAKE MODIFICATIONS/ CONNECTIONS

TO EXISTING SYSTEM.

N

SCALE: 1/8" = 1'-0"FX101

1 LOWER LEVEL PLAN - FIRE SUPPRESSION

Revisions: Date:

GENERAL NOTES

A ALL PIPING IS ABO VE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN

EXPOSED STRUCTURE AREAS), UNLESS OTHERW ISE NOTED.

B REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES

AND PIPELINE DEVICES NO T INDICATED ON THE FLOOR PLAN.

C ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION W ITH ALL

TRADES IS CRITICAL, PRIOR TO INSTALLATION OF ANY W ORK.

D LOCATIONS AND SIZES O F EXISTING PIPING HAVE BEEN DETERMINED

FROM A REVIEW OF EXISTING DRAW INGS AND/OR SITE INSPECTIO N,

W HERE POSSIBLE. FIELD VERIFICATION OF EXACT LOCATIONS,

ELEVATIONS, INVERTS, SIZES, DIRECTION OF FLOW , ETC. SHALL BE

REQ UIRED PRIOR TO BEGINNING NEW W ORK.

E ALL PIPING SHALL BE REM OVED BACK TO W ITHIN TW O PIPE DIAMETERS

OF ACTIVE MAINS AND CAPPED, OR REMOVED BACK TO POINTS OF

CONNECTION OF NEW W O RK. INACCESSIBLE PIPING, W HERE SO NOTED,

TO BE ABANDONED SHALL BE DISCO NNECTED FROM ACTIVE MAINS AND

CAPPED OR PLUGGED IN CONCEALED LOCATIONS. ALL EXISTING PIPING,

EQ UIPMENT, FIXTURES, ETC., SHOW N ON REMOVAL PLAN(S) SHALL BE

REM OVED. THE MAJORITY OF THE W ORK TO BE REMOVED IS SHOW N.

REM OVE ALL INCIDENTAL AND/OR ABANDONED PIPING ETC., THAT M AY NOT

BE SHOW N BUT IS ASSO CIATED W ITH THE REMOVAL W ORK.

F NEW CO NNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAM E SIZE

AS THE EXISTING PIPING UNLESS OTHERW ISE NOTED.

G ALL REMOVED MATERIAL AND EQUIPMENT SO DESIGNATED BY THE

GOVERNMENT, SHALL BE TURNED OVER AND PLACED W HERE DIRECTED.

ALL MATERIAL AND EQUIPMENT, W HICH THE O W NER DOES NO T W ISH TO

RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTO R

RESPONSIBLE FOR THE REMOVAL.

H REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING

REQ UIREMENTS.

I ANY RENO VATION W ORK REQUIRED "OUTSIDE" OF THE

BO UNDARIES/ EXTENTS OF A SPECIFIC PHASE OF W ORK (OR

TEMPO RARY CONSTRUCTIO N W ALLS SHALL BE BID AS "NIGHT W ORK"

AND SHALL BE AS DIRECTED BY THE COR.

J ALL CORE DRILLS AND PIPE EXTENSIONS THRU THE EXISTING

STRUCTURAL FLOOR SLAB O R STRUCTURAL W ALL SHALL BE X-RAYED

TO DETERMINE THE EXACT LOCATION OF THE "REBARS" IN THE

STRUCTURAL SLAB. DO NOT CUT THE LO W ER (BOTTOM REBARS) IN

THE STRUCTURAL FLOOR SLAB.

K W ORKING ON EXISTING FLO ORS W ITH NO /LIM ITED ARCHITECTURAL

SCO PE, THE CONTRACTO R SHALL PRO VIDE ALL REQ UIRED

FLOOR/ W ALL PROTECTION (AS REQUIRED) AND REPLACE ANY

DAM AGED CEILING TILES W ITH NEW . RETURN AREA BACK TO ORIGINAL

CONDITION UPON COMPLETION OF W O RK.

L REFER TO ARCHITECTURAL FIRE RATED PARTITION PLAN(S) FOR

LOCATIONS AND FIRE RATINGS O F NEW AND EXISTING W ALL

ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES

SHALL BE PROTECTED AND/ OR FIRE STOPPED AS REQUIRED TO

MAINTAIN FIRE RATINGS INDICATED. COORDINATE W ITH ALL TRADES

TO ENSURE FIRE RATED PENETRATION REQ UIREMENTS AND DETAILS

ARE MET.

M ANNULAR SPACE O F ALL PIPE & OTHER SIMILAR PENETRATIONS OF

FIRE RATED ASSEM BLIES SHALL BE FIRE STOPPED. IN ADDITION,

PENETRATIONS THROUGH 0-HO UR RATED W ALLS & FLO OR SHALL

BE SEALED TO RETARD THE PASSAGE OF SM OKE.

N PHASING : REFER TO ARCHITECTURAL DRAW INGS FOR AN O UTLINE OF

PRO JECT PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS

MAY BE INCLUDED THROUGHOUT THIS DRAW ING SET.

O BID ITEM S: REFER TO ARCHITECTURAL DRAW ING AND SPECIFICATION

SECTION 01 00 00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES

DESCRIBING BID ITEM DETAILS MAY BE INCLUDED THROUGHOUT THIS

DRAW ING SET.

P. SUPPLY PIPING SHALL BE MINIM UM 0.5” SIZE. MEDICAL VACUUM AND

W ASTE ANESTHESIA GAS DISPOSAL PIPING SHALL BE M INIMUM 0.75" SIZE.

Q. ALL MEDICAL G AS SYSTEM INSTALLERS SHALL BE CERTIFIED TO THE

REQ UIREMENTS O F ASSE 6010. ALL MEDICAL GAS SYSTEM VERIFIERS

SHALL BE CERTIFIED TO THE REQUIREM ENTS OF ASSE 6030.

R MEDICAL GAS AND VACUUM SYSTEM INSTALLATION AND VERIFICATION

SHALL COMPLY W ITH THE REQUIREM ENTS OF NFPA 99, G AS AND

VACUUM SYSTEMS, 2018 EDITION.

A1

P1 P1OR

A1

OH

P2

B

P2

GENERAL FLOOR PLAN NOTES

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

P2 = SHEET W HERE DETAIL IS LOCATED

FIRE SUPPRESSIO N HAZARD CLASSIFICATIO N AND HAZARD

CLASSIFICATIO N G ROUP

SECTION: 1 = SECTION DESIGNATION

P2 = SHEET W HERE DETAIL IS LOCATED

EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES.

REFER TO SCHEDULES.

EQUIPMENT, DEVICE, O R PLUMBING FIXTURE MARK. LETTER

DESIGNATIONS REFER TO SCHEDULES.

CONNECT TO EXISTING

PLAN NO TE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N

UNLESS NOTED OTHERW ISE.

DETAIL NO TE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

"UP TO" SYMBOL (ITEM ON FLO OR ABO VE)

10" 10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOE: 3' - 0"

BOE: 0' - 6"

APPROXIM ATE DIMENSIO N ABOVE FINISHED FLO OR TO TOP OR

BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO

CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE

PIPING SYMBOLS

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE

NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBO W DOW N

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

D

R

SPECIALTY GAS SYMBOLS

AIR OUTLET - LAB TYPE

VC

VC

CARBON DIOXIDE OUTLET - HOSPITAL TYPE

MEDICAL AIR OUTLET - HO SPITAL TYPE

MEDICAL VACUUM INLET - HOSPITAL TYPE

NITROGEN OUTLET - HOSPITAL TYPE

NITROUS OXIDE OUTLET - HOSPITAL TYPE

OXYGEN O UTLET - HOSPITAL TYPE

W AGD INLET - HOSPITAL TYPE

NATURAL GAS OUTLET - LAB TYPE

VACUUM OUTLET - LAB TYPE

VACUUM CLEANING STATION - W ALL

VACUUM CLEANING STATION - FLOOR

PIPING DESIGNATIONS

DOMESTIC COLD W ATER

DOMESTIC HOT W ATER

DOMESTIC HOT W ATER RETURN

EXISTING PIPE TO REMAIN

EXISTING PIPE TO BE REMO VED

HOT W ATER PIPE (140 DEGS. F.)

HOT W ATER PIPE (180 DEGS. F.)

HOT W ATER RETURN PIPE (140 DEGS. F.)

HOT W ATER RETURN PIPE (180 DEGS. F.)

ARGON PIPE

COMPRESSED AIR PIPE

MEDICAL CARBON DIOXIDE PIPE

COMBINATION FIRE SUPPRESSION AND DOMESTIC

W ATER SERVICE

DIESEL FUEL PIPE

SPRINKLER PIPE (DRY)

FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)

FIRE SERVICE

FUEL OIL FLO W LINE

FUEL OIL GAUGE LINE

FUEL OIL RETURN LINE

FUEL OIL SUPPLY LINE

NATURAL G AS PIPE

GARAGE DRAINAGE PIPE

GAS SERVICE

HYDROG EN PIPE

HELIUM PIPE

MEDICAL INSTRUMENT AIR PIPE

KITCHEN W ASTE PIPE

LABORATO RY COMPRESSED AIR PIPE

LABORATORY VENT PIPE

LABORATORY VACUUM PIPE

LABORATORY W ASTE PIPE

MEDICAL NITROGEN PIPE

MEDICAL COMPRESSED AIR PIPE

MEDICAL-SURGICAL VACUUM PIPE

GASOLINE PIPE (NON-LEAD)

MEDICAL NITROUS OXIDE PIPE

NON-POTABLE

MEDICAL OXYG EN PIPE

(OVERFLOW ) SECONDARY STORM DRAINAGE PIPE

PROPANE GAS PIPE

PUMP DISCHARGE PIPE

PRE-ACTION / DELUGE SPRINKLER PIPE

PURE W ATER PIPE

SPRINKLER PIPE (W ET)

SANITARY DRAINAGE PIPE

SOFT COLD W ATER

SPRINKLER DRAIN PIPE

STORM DRAINAGE PIPE

FUEL TANK VENT PIPE

TRAP PRIMER DISCHARGE PIPE

TEMPERED W ATER PIPE

SANITARY SEW ER VENT

W ASTE ANESTHESIA GAS DISPOSAL PIPE

W ATER SERVICE

LV

140R

180R

AR

CA

CO2

CW S

DF

DS

F

FS

FOF

FOG

FOR

FOS

G

GD

GS

H2

HE

IA

IV

IW

LA

LV

LW

N2

MA

MV

NG

NO

NPW

O2

OD

P

PD

PS

PW

S

SAN

SCW

SD

STM

T

TP

TW

V

W AGD

W S

INDIRECT VENT PIPE

INDIRECT W ASTE PIPE

K

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS

FOR REQUIRED TYPE BASED ON

APPLICATIO NS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUG E OR THERMOM ETER

UNION

CLEANO UT

STRAINER

STRAINER W ITH A BLOW DOW N VALVE AND

HOSE CONNECTION

DRAIN VALVE W ITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER W ITH P/T

PLUG IN AND OUT

EXPANSION JOINT

PRESSURE REGULATING VALVE

SAFETY RELIEF VALVE. PIPE DISCHARGE AIR

GAPPED TO FLOOR DRAIN UNLESS NOTED

OTHERW ISE.

PRESSURE AND TEMPERATURE TEST PLUG

TRAP PRIMER

VACUUM GAUGE W ITH STOP

CLEANOUT TO GRADE OR FINISHED FLOOR

END CAP

MIXING FAUCET

PLUG

HOSE BIB

W ALL HYDRANT

PLUG VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE O N RISER

V

VB

TP

CO

COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO

SPECIFICATIONS FO R REQ UIRED TYPE BASED ON APPLICATIONS)

BALL VALVE, BUTTERFLY VALVE, GATE VALVE

VALVES AND FITTINGS

SOLENOID VALVE

S

P/T PRESSURE AND TEMPERATURE SAFETY RELIEF

VALVE. PIPE DISCHARGE AIR G APPED TO FLOO R

DRAIN UNLESS NOTED OTHERW ISE.

W ATER METERM

ACID VENT PIPEAV

ACID W ASTE PIPEAW

ABBREVIATIONS

AAP - AREA ALARM PANEL (MEDICAL G AS)

AC - AIR COM PRESSOR OR AIR CONDITIO NER

ACC - ACCESS

ACCU - AIR COO LED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADB - ACID DILUTION BASIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

AR - AIR RECEIVER OR ARGON

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

AV - ACID VENT

AW - ACID W ASTE

BDD - BACK DRAFT DAMPER

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BT - BATHTUB

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

BTW N - BETW EEN

CA - COM PRESSED AIR

CB - CATCH BASIN

CBD - COUNTER BALANCED BACKDRAFT DAM PER

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CFM - CUBIC FEET PER MINUTE

CHS - CHILLED W ATER SUPPLY

CHR - CHILLED W ATER RETURN

CI - CAST IRON

CK - CLINICAL SINK

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - M EDICAL CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CS - CLINICAL SINK OR COLD SOFT W ATER

CTR - CENTER

CU - COPPER

CW - COLD W ATER

CW S - COM BINATION W ATER SERVICE

OR CONDENSER W ATER SUPPLY

CW R - CONDENSER W ATER RETURN

D - DEPTH OR DRAIN LINE

DD - DECK DRAIN

DET - DETAIL

DF - DRINKING FOUNTAIN OR W ATER COOLER

OR DIESEL FUEL

DFU - DRAINAGE FIXTURE UNIT

DI - DEIO NIZED W ATER

DIA - DIAM ETER

DIM - DIM ENSION

DN - DOW N

DS - DOW N SPOUT OR SPRINKLER (DRY)

DT - PERFORATED DRAIN TILE

DW G - DRAW ING

EA - EACH

EC - ELECTRICAL (DIVISIO N 26)

EEW - EMERG ENCY EYE W ASH

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATO R

EQ - EQUAL

EQUIP - EQUIPM ENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

ES - EMERG ENCY SHO W ER

EQS - EQUIPM ENT SUPPLIER

EW C - ELECTRICAL W ATER COOLER

EXH - EXHAUST AIR

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER

MAIN)

FCE - FIRE CONTROL EQUIPMENT

FCO - FLOOR CLEANO UT

FD - FLOOR DRAIN

FDC - FIRE DEPARTMENT CO NNECTIO N

FDV - FIRE DEPARTMENT VALVE

FF - FINISHED FLOOR ELEVATION

FHC - FIRE HOSE CABINET

FLR - FLOOR

FM - FORCE MAIN

FOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL GAUGE

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT O N TOP

FPM - FEET PER M INUTE

FR - FIRE RISER

FS - FLOOR SINK OR FIRE SERVICE

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

G - G AS OR NATURAL G AS

GA - G AUG E

GAL - G ALLON

GALV - G ALVANIZED

GC - G ENERAL TRADES

GD - G ARAG E DRAINAGE

GPM - G ALLONS PER M INUTE

GS - G AS SERVICE

GW - G REASE W ASTE

H2 - HYDROGEN

HB - HO SE BIBB

HC - HVAC (DIVISIO N 23)

HD - HUB DRAIN

HE - HELIUM

HG - REFRIGERANT HOT GAS

HP - HO RSEPOW ER O R HIGH POINT

HPC - HIGH PRESSURE CONDENSATE RETURN

HPS - HIGH PRESSURE STEAM SUPPLY

HPW - HIGH PURITY W ATER

HPW R - HIGH PURITY W ATER RETURN

HR - HO SE REEL

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING , AND AIR

CONDITIONING

HW - HO T W ATER

HW R - HEATING HOT W ATER RETURN

HW S - HEATING HOT W ATER SUPPLY

IA - M EDICAL INSTRUMENT AIR

ID - INSIDE DIAMETER

INV - INVERT ELEVATIO N

IN - INCHES

IV - INDIRECT VENT

IW - INDIRECT W ASTE

JS - JANITOR SINK

K - KITCHEN W ASTE

KEC - KITCHEN EQUIPMENT

L - LENGTH

LA - LABORATORY COMPRESSED AIR

LAV - LAVATORY

LBS - POUNDS

LCW - LABORATORY COLD W ATER

LEC - LABORATORY EQUIPMENT

LHW - LABORATORY HOT W ATER

LHW R - LABORATORY HOT W ATER RETURN

LPC - LOW PRESSURE CONDENSATE RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LV - LABORATORY VACUUM OR LABORATO RY

VENT

LW - LABORATORY W ASTE

MA - M EDICAL COM PRESSED AIR

MAP - M ASTER ALARM PANEL (MEDICAL GAS)

MAX - M AXIMUM

MB - M OP BASIN

MC - M ECHANICAL (DIVISIO N 23)

MEZZ - M EZZANINE

MFR - M ANUFACTURER

MH - M ANHOLE

MIN - M INIMUM OR M INUTE

MISC - M ISCELLANEOUS

MTD - M OUNTED

MTG - M OUNTING

MPC - M EDIUM PRESSURE CO NDENSATE RETURN

MPS - M EDIUM PRESSURE STEAM SUPPLY

MU - W ATER MAKE-UP

MV - M EDICAL SURGICAL VACUUM

N2 - M EDICAL NITROGEN

N/C - NO RMALLY CLOSED

NG - G ASO LINE (NON-LEAD)

NIC - NO T IN CONTRACT

N/O - NO RMALLY OPEN

NO - M EDICAL NITROUS OXIDE

NOM - NO MINAL

NPW - NO N-PO TABLE W ATER

NPT - NATIONAL PIPE THREAD

NTS - NO T TO SCALE

O2 - MEDICAL OXYGEN

OA - OUTDOOR AIR

OD - OUTSIDE DIAMETER OR O VERFLOW

DRAIN

OFCI - OW NER FURNISHED CONTRACTOR

INSTALLED

OFOI - OW NER FURNISHED OW NER

INSTALLED

P - PROPANE GAS

PC - PLUMBING (DIVISION 22) OR PUMPED

CONDENSATE RETURN

PD - PUMP DISCHARGE OR PARAPET DRAIN

PIV - POST INDICATOR VALVE

PLBG - PLUMBING

PS - PRE-ACTION/DELUGE SPRINKLER

PRESS - PRESSURE

PRV - PRESSURE REG ULATING VALVE

PSF - POUNDS PER SQ UARE FOOT

PSI - POUNDS PER SQ UARE INCH

PSV - PRESSURE SUSTAINING VALVE

PSIG - POUNDS PER SQ UARE INCH GAUGE

PW - PURE W ATER

RA - RETURN AIR

RAD - RADIUS

RCP - REINFORCED CONCRETE PIPE

RD - ROOF DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS W ATER SUPPLY

ROR - REVERSE OSMOSIS W ATER RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

RV - RELIEF VALVE

S - SPRINKLER (W ET)

SA - SHOCK ARRESTO R OR SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD W ATER

SD - SPRINKLER DRAIN OR SUBSOIL DRAIN

SH - SHOW ER

SHT - SHEET

SK - SINK

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SS - SANITARY STACK (SOIL OR W ASTE) OR

STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

T - FUEL TANK VENT

TD - TRENCH DRAIN

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQ UIPMENT

TOF - TOP OF FOO TING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TF - TRAP FILLER

TP - TRAP PRIMER OR TRAP PRIMER

DISCHARGE

TW - TEMPERED W ATER

TYP - TYPICAL

UR - URINAL

UNO - UNLESS NO TED OTHERW ISE

V - VENT OR SANITARY SEW ER VENT

VAC - VACUUM

VC - VACUUM CLEANING

VCV - VACUUM CLEANING VALVE

VE - VACUUM EXHAUST

VEL - VELOCITY

VIB - VALVE IN BOX

VOL - VOLUME

VP - VACUUM PUMP

VS - VENT STACK

VTR - VENT THRO UGH RO OF

VR - VENT RISER

W / - W ITH

W /O - W ITHOUT

W - W ASTE

W AGD - W ASTE ANESTHESIA GAS DISPO SAL

W C - W ATER CLO SET

W CO - W ALL CLEANOUT

W H - W ALL HYDRANT OR W ATER HEATER

W IV - W ALL INDICATO R VALVE

W S - W ATER SERVICE

YCO - YARD CLEANOUT

ZVC - ZONE VALVE CABINET

PIPE RISER

NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS. ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT NECESSARILY BE USED ON THIS PROJECT.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:3

:4

A M

P001

LEGEND, INDEX AND GENERAL

NOTESGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

INDEX OF DRAWINGS - PLUMBING

SHEET NUMBER SHEET NAME

P001 LEGEND, INDEX AND GENERAL NOTES

PD101 PARTIAL LOWER LEVEL PLAN - REMOVALS

PL100 PARTIAL UNDERSLAB PLAN - DRAINAGE

PL101 PARTIAL LOWER LEVEL PLAN - DRAINAGE

PP101 PARTIAL LOWER LEVEL PLAN - DISTRIBUTION

PG101 PARTIAL LOWER LEVEL PLAN - MEDICAL GAS

P601 SCHEDULES & DETAILS

P901 SOIL, WASTE & VENT DIAGRAM

CO

A

457 3.5

B

C

D

E

F

2.5

1ZVC-

3MED GAS OUTLETS -

- MED GAS OUTLETS

ZVC - 1

6"

4"

2" 1.25"

1.25"

2" 2"

0.75"

2" 2"0.75"

1.25" - MV

0.75" - MA

0.

M A

1.

M V

1 .25" - O2 1.25" - G

0.75" - MV

0.5" - O2

0.5" - MA

D H

W R

D H

W R

D H

W R

D H

W

D H

W D

C W

DHW

DCW

DHW

2" - V

0.75" - MA

0.75" - O2

1.25" - MV

3" - V

3"

V

VENT RISER UP

3"

V

3"

V

SK

ES

SK

SK

SKSK

SK

SK

5 5

N

KEY PLAN

GENERAL NOTES

A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:4

:2

A M

PD101

PARTIAL LOWER LEVEL PLAN -

REMOVALSGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"PD101

1 PARTIAL LOWER LEVEL PLAN - REMOVALS

NOTES

1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.

2 REMOVE EXISTING FIXTURE AND ALL EXTRANEOUS DOMESTIC WATER

PIPING BACK TO WITHIN TWO (2) PIPE DIAMETERS OF ACTIVE MAIN AND

CAP OR TO POINT-OF-CONNECTION WITH NEW WORK. REMOVE ALL

EXTRANEOUS SANITARY DRAIN AND VENT PIPING BACK TO ACTIVE

MAIN AND CAP OR BACK TO POINT-OF-CONNECTION WITH NEW WORK.

CAP PIPING IN WALLS WHERE WALLS ARE TO REMAIN OR ABOVE

CEILING OR BELOW FLOOR SLAB WHERE WALLS ARE TO BE REMOVED.

NO PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.

3 REMOVE MEDICAL GAS OUTLETS AND PIPING BACK TO ACTIVE MAIN

OR POINT-OF-CONNECTION WITH NEW WORK.

4 REMOVE EXISTING DHW/ DHWR PIPING AS SHOWN. DHW/ DHWR

PIPING TO BE REVISED AS SHOWN ON NEW WORK PLAN.

5 REMOVE FIXTURE OR ITEM OF EQUIPMENT (TYPE AS INDICATED) AND

REPLACE WITH NEW FIXTURE IN THE (SAME OR APPROXIMATE)

LOCATION. REFER TO NEW WORK PLANS.

A

457 3.5

B

C

D

E

F

2.5

2" - SAN

3"

S A

N

4"

S A

N

4" - SAN

2"

S A

N STM

STM

S T

M

S A

N

1 1

2 2

2 2

P531(2)

P528

P520

P520

4" DS

CAP

CO 1

P528

FD-C

CAP

SKSK

CO 1

CO

CO

CO

CO

P114

FD-C

P114

2" VR

FD-C

P421

P421

SK

P520

P520

CAP

CO1

CO1

FD

FD

FD

LAV

W C

W C

LAV

2"

W C

P531

P528

1.5" VR

N

KEY PLAN

GENERAL NOTES

A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:4

:5

A M

PL100

PARTIAL UNDERSLAB PLAN -

DRAINAGEGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"PL100

1 PARTIAL UNDERSLAB PLAN - DRAINAGE

NOTES

1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.

2 PIPING LOCATED IN GRADE BELOW FLOOR SLAB.

3 SAW CUT AND TRENCH EXISTING FLOOR SLAB TO ACCOMMODATE

NEW SANITARY PIPING. PROVIDE BEDDING, BACKFILL AND

COMPACTION PER SPECIFICATIONS. PATCH CONCRETE FLUSH TO

FINISHED FLOOR AND RESURFACE TO MATCH ADJACENT FLOOR SLAB.

CO

CO

CO

A

457 3.5

B

C

D

E

F

2.5

V

P421

P114

FD-C

P114

FD-C

P421

P520

P520

VV

V

V

V

V

V

V

VVV

P520

P520

P707

FD-C

CAP

CAP

P528

P528 P528

P528

V

P528P531P531

P531

P531

P811

P528

1.5" VR

CO

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION

A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LO UNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIO ACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

V

V

VR

V

V

N

KEY PLAN

GENERAL NOTES

A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.

A

3.5

B

C

D

2.5

D.5

A

3.5

B

C

D

2.5

VTR

V

3" VR

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:4

:1

A M

PL101

PARTIAL LOWER LEVEL PLAN -

DRAINAGEGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"PL101

1 PARTIAL LOWER LEVEL PLAN - DRAINAGE

NOTES

1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.

2 PROVIDE NEW FIXTURE (TYPE AS INDICATED) AT THE SAME LOCATION

AS EXISTING FIXTURE. EXTEND NEW PIPING AND CONNECT TO

EXISTING ROUGH-IN TO BE RE-USED/ RE-WORKED TO SERVE NEW

FIXTURE.

3 RISE VENT LINE WITHIN NEW CHASE.

N

Revisions: Date:

SCALE: 1/8" = 1'-0"PL101

2 PARTIAL FIRST FLOOR PLAN - DRAINAGE

TP

TP

A

457 3.5

B

C

D

E

F

2.5

1.5"

2"

0.5"

0.5"

2"

2"

1"

0.75"

0.75"

1"

1"

2"

0.5"

2"

P707

P421

P114

P114

P421

P520

P520

P520

P520

P811

P528

P528

P528

P528

1"

FD-C

P528

FD-C

0.75"

1"

P531

P531 P531

3 3

2"1" 2"2" 2" 1.5"

1.25"

1"

1"

0.5"

2"

2" P531

P528

0.5"

2" 2"

0.75"

P601 A

6 A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION

A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LO UNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIO ACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

0.5"

0.5"

N

KEY PLAN

GENERAL NOTES

A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:4

:3

A M

PP101

PARTIAL LOWER LEVEL PLAN -

DISTRIBUTIONGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"PP101

1 LOWER LEVEL SUPPLY PLAN

NOTES

1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.

2 PROVIDE 2” FULL SIZE DCW MANIFOLD ENTIRE LENGTH OF PLUMBING

CHASE / WALL AND SERVE EACH FIXTURE INDIVIDUALLY FROM

MANIFOLD.

3 PROVIDE NEW FIXTURE (TYPE AS INDICATED) AT THE SAME LOCATION

AS EXISTING FIXTURE. EXTEND NEW PIPING AND CONNECT TO

EXISTING ROUGH-IN TO BE RE-USED/ RE-WORKED TO SERVE NEW

FIXTURE.

4 LOCATE EMERGENCY MIXING VALVE ABOVE CEILING.

5 ADJUST EXISTING BALANCING VALVE AS REQUIRED TO BALANCE

SYSTEM.

6 MAKE DCW CONNECTION FROM SUPPLY BOX TO REFRIGERATOR.

457 3.5

B

C

D

E

F

2.58

0.75" - MA

1.25" - MV

1.25"

0.75" 0.75"

0.75"0.5"

0.5"

1ZVC -

1ZVC -

0.

M A

1.

M V

ZVC

1.25"

0.5"

0.5"

1" 0.5"

0.5"

1.25"

0.5"0.5"

1.25"

0.75"

0.75"

MA

MV

O2

0.75" - MV

0.5" - MA0.5" - O2

0.5"

0.5"

0.75"

0.75"

0.5" 0.5"

0.5" 0.5"

0.75"

O2

MA MV

0.75" 0.5" 0.5"

1" 1.25" 0.75" 0.5"

0.5"

1.25"

O

1.25"

1"

O2

MV

MA

O2

MV

MA O2

1.25" 0.75"0.75"

0.75"

0.5"

0.5"

0.5"

0.5" 0.75"

0.5" 0.5" 0.75"

0.75"

0.5"

0.5"

0.75"

0.5"

0.5"

MV

MA O2

O2

MV

MA

SENSORS

SENSORS

AAP

SENSORS

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LO UNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIO ACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

N

KEY PLAN

GENERAL NOTES

A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIO NS & INDEX OF DRAW INGS.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:4

:4

A M

PG101

PARTIAL LOWER LEVEL PLAN -

MEDICAL GASGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"PG101

1 PARTIAL LOWER LEVEL PLAN - MEDICAL GAS

NOTES

1 EXISTING PIPING, FIXTURE OR PIECE OF EQUIPMENT TO REMAIN.

TRAP PRIMER, W ITH DISTRIBUTION

UNIT W HEN SERVING MULTIPLE

DRAINS. LOCATE ABOVE CEILING

IN FINISHED AREAS.

0.5''SUPPLY SHALL BE

OFF TO P OF MAIN

COLD W ATER MAIN

T P

T P

W ALL

FINISHED CEILING

W HERE APPLICABLE

FLO OR DRAINS

FLOOR

TP

PIPING TO FLOOR DRAINS

SHALL BE RUN BELO W FLOOR,

UNLESS NO TED OTHERW ISE.

INSTALL PIPING CONCEALED

IN W ALL IN FINISHED AREAS.

INSTALL PIPING TIGHT TO W ALL

SURFACE IN UNFINISHED AREAS.

NOTE:

1 REFER TO FLOO R PLANS FOR REQ UIRED NUMBER O F

VALVES, VALVE SERVICES AND SIZES AT EACH INDIVIDUAL LOCATION.

VACUUM GAUGE

PRESSURE

GAUGE, TYPICAL

MEDICAL GAS O R VACUUM

PIPING TO/FROM STATION

INLETS AND OUTLETS

SYSTEM AND SERVICE

AREA LABEL, TYPICAL

MEDICAL GAS O R VACUUM

PIPING TO/FROM

DISTRIBUTION SYSTEM

MIN. 45 DEG REES

BRANCH OR RUNOUT

TO STATION OUTLET,

INLET O R SPECIAL STATION

MAIN OR BRANCH PIPING

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:3

:5

A M

P601

SCHEDULES & DETAILS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

FIXTURE SCHEDULE

SYMBOL

MOUNTING

HEIGHT DESCRIPTION

FLOW FIXTURE UNITS SUPPLY WASTE & VENT

REMARKSGPM GPF DRAINS

WATER

COLD HOT TEPID OUTLET VENT DIRECT INDIRECTCOLD HOT

P114 FLOOR SET WATER CLOSET/ BARIATRIC/ FLOOR SET 1.6 4 10 2" MANUAL/ FLUSH VALVE

P421 FLOOR SET LAVATORY/ BARIATRIC/ PEDESTAL 1.5 1 0.5 0.5 0.5" 0.5" 1.25" 1.5" FAUCET BY CHICAGO OR APPROVED EQUAL/ MANUAL/ GOOSENECK

SPOUT/ T'STATIC MIXING VALVE/

P520 36" TO RIM SINK/ SCRUB/ WALL HUNG/ SENSOR CONTROL/ 1.5 2 2 2 0.5" 0.5" 1.25" 1.5" HARD WIRED/ SENSOR OPERATED/ GOOSENECK SPOUT/ T'STATIC

MIXING VALVE

P528 C'TOP SINK/ SST/ SINGLE COMP'T/ 21" x 22"/ 1.5 2 2 2 0.5" 0.5" 1.5" 1.5" FAUCET BY CHICAGO OR APPROVED EQUAL/ MANUAL/ GOOSENECK

SPOUT/ T'STATIC MIXING VALVE

P531 C'TOP SINK/ SST/ INTEGRAL TO COUNTER 1.5 2 2 2 0.5" 0.5" 1.5" 1.5" FAUCET BY CHICAGO OR APPROVED EQUAL/ MANUAL/ GOOSENECK

SPOUT/ T'STATIC MIXING VALVE

P707 FLOOR SET EMERGENCY SHOWER AND EYE AND FACE WASH 1.25" 1.25" 1.5"

P811 48" WATER SUPPLY BOX/ COFFEE MAKER AND ICE MAKER 2 1 1 0.5" PROVIDE FLEXIBLE CONNECTOR TO EQUIPMENT

DRAIN SCHEDULE

SYMBOL DESCRIPTION

BODY STRAINER / GRATE TOP FINISH

C.I. S.S. C.R. BRASS RD. SQ. ADJUST. FLAT RECESS DOME

NICKLE

BRONZE C.I. C.R. S.S.

FD-C 3" LIGHT DUTY/ DOUBLE DRAINAGE/ VANDAL RESISTANT (TYPE C)/ TRAP PRIMER CONNECTION ● ● ● ●

SCALE: NONE

TRAP PRIMER

A

SCALE: NONE

MEDICAL GAS ZONE VALVE CABINET

B

SCALE: NONE

BRANCH TAKE-OFF PIPING - MEDICAL GAS

C

1.25" 3" 4"

1.5"

1.5"

1.5"

1.5"

1.5"

CO

CO

P520

P520

P421

P421

P520

P520

P114

P114

FD-C

FD-C

FD-C

CAP

L LVL

P531

P531

P531

P528

P528

P528

P528

P528

2"

1.5"

3"

2"

2"

2"

1.5"

3"

3"

3"

2"

3"

2"

3"3"

4"

4"

4"

1.

5"

3"

2"

2"

2"

2"

1.5"

4"

4"

1.

5"

4"

1.5"

1.5"

3"

3"

2"

1.5"

4"

4"

3"

3"4"

4"

3" 2"

3"

CO

CAP

CAP

CAP

CAP

P531

2"

3" 3"

1.5"

L LVL

2"

2"

P528

2"

2"

2"

2"

2"

4"

L LVL

L LVL

L LVL

L LVL

3"

3"

3"

2"

3"

1.5"

1.

5"

2"

1ST FLR

4" VTR

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

C

B

IM

\M o d e l\

-0

-M E

P -C e n tr a l_ a b n o rm a n

.r v t

/2

/2

:0

:1

A

M

P901

SOIL, WASTE & VENT DIAGRAM

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 DPB ABN

BID DOCUMENTS

FULLY SPRINKLERED

SOIL, WASTE & VENT DIAGRAM

NOTE: ALL SYMBOLS AND ABBREVIATIONS

ARE SUBJECT TO MODIFICATIONS

ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS

MIGHT NOT NECESSARILY BE USED ON

THIS PROJECT.

ABBREVIATIONS

AC - AIR COM PRESSOR OR AIR CONDITIO NER

ACCU - AIR COO LED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOO R

AFG - ABOVE FINISHED GRADE

AFMS - AIR FLOW MEASURING STATION

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATC - AUTOMATIC TEMPERATURE CO NTRO L

(SYNO NYMOUS W ITH BAS)

BAS - BUILDING AUTOMATION SYSTEM

BDD - BACK DRAFT DAM PER

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

CBD - COUNTER BALANCED BACKDRAFT

DAMPER

CFCI - CONTRACTOR FURNISHED CONTRACTO R

INSTALLED

CFM - CUBIC FEET PER MINUTE

CHS - CHILLED W ATER SUPPLY

CHR - CHILLED W ATER RETURN

CHGR - CHILLED W ATER GLYCO L SOLUTION

RETURN

CHGS - CHILLED W ATER GLYCO L SOLUTION

SUPPLY

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CTR - CENTER

CU - COPPER

CW - COLD W ATER

CW R - CONDENSER W ATER RETURN

CW S - CONDENSER W ATER SUPPLY

D - DRAIN LINE

DB - DRY BULB

DDC - DIRECT DIGITAL CONTROLS

DI - DEIO NIZED W ATER

DIA - DIAM ETER

DIM - DIMENSION

DN - DOW N

DW G - DRAW ING

EA - EACH OR EXHAUST AIR

EAT - ENTERING AIR TEMPERATURE

EC - ELECTRICAL CONTRACTOR (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATO R

EQUIP - EQUIPM ENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

EQS - EQUIPM ENT SUPPLIER

EW T - ENTERING W ATER TEM PERATURE

EXH - EXHAUST

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

FD - FLOOR DRAIN

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FOB - FLAT O N BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL G AUG E

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT O N TOP

FPM - FEET PER M INUTE

FSC - FIRE SUPPRESSION CONTRACTO R

(DIVISION 21)

FT - FEET

FTG - FOOTING

G - GAS OR NATURAL GAS

GA - GAUG E

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES CONTRACTOR

GPM - GALLONS PER M INUTE

HB - HOSE BIBB

HC - HVAC CONTRACTOR (DIVISION 23)

HD - HUB DRAIN

HG - REFRIGERANT HOT GAS

HP - HORSEPOW ER

HPC - HIGH PRESSURE CONDENSATE RETURN

HPS - HIGH PRESSURE STEAM SUPPLY

HR - HOUR

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING, AND AIR

CONDITIONING

HW - HOT W ATER

HW R - HEATING HOT W ATER RETURN

HW S - HEATING HOT W ATER SUPPLY

ID - INSIDE DIAM ETER

INV - INVERT ELEVATION

IN - INCHES

KEC - KITCHEN EQUIPMENT

CONTRACTOR

L - LENGTH

LAT - LEAVING AIR TEMPERATURE

LAV - LAVATORY

LBS - POUNDS

LPC - LOW PRESSURE CONDENSATE

RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LW T - LEAVING W ATER TEMPERATURE

MAX - M AXIMUM

MDD - M OTORIZED DAM PER

MEZZ - M EZZANINE

MFR - M ANUFACTURER

MH - M ANHOLE

MIN - M INIMUM OR MINUTE

MISC - M ISCELLANEOUS

MTD - M OUNTED

MTG - M OUNTING

MPC - M EDIUM PRESSURE CONDENSATE

RETURN

MPS - M EDIUM PRESSURE STEAM

SUPPLY

MU - W ATER MAKE-UP

N/C - NORMALLY CLOSED

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NOM - NOM INAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTDOO R AIR

OBD - OPPOSED BLADE DAM PER

OD - OUTSIDE DIAMETER

OFCI - OW NER FURNISHED

CONTRACTOR INSTALLED

OFOI - OW NER FURNISHED OW NER

INSTALLED

P - PROPANE GAS

PC - PLUMBING CONTRACTOR

(DIVISION 22)

OR PUMPED CO NDENSATE

RETURN

PLBG - PLUMBING

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FO OT

PSI - POUNDS PER SQUARE INCH

PSIG - POUNDS PER SQUARE INCH

GAUGE

RA - RETURN AIR

RAD - RADIUS

RCP - REFLECTED CEILING PLAN

RD - ROO F DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS W ATER

SUPPLY

ROR - REVERSE OSMOSIS W ATER

RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

S - SPRINKLER (W ET)

SA - SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD W ATER

SHT - SHEET

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SRV - SAFETY RELIEF VALVE

SS - STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL O R STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TYP - TYPICAL

UNO - UNLESS NOTED OTHERW ISE

V - VENT

VAC - VACUUM

VEL - VELOCITY

VIB - VALVE IN BO X

VOL - VOLUME

VTR - VENT THROUGH ROOF

VR - VENT RISER

W / - W ITH

W /O - W ITHO UT

W B - W ET BULB

W CO - W ALL CLEANOUT

GENERAL FLOOR PLAN NOTES

PLAN NO TE. APPLIES ONLY TO THE SHEET W HICH IT IS SHO W N

UNLESS NOTED OTHERW ISE.

DETAIL NO TE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

A1

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER

DESIGNATIONS REFER TO SCHEDULES.

H1 H1OR

EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO

SCHEDULES.

H2

B

H2

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

H2 = SHEET W HERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

H2 = SHEET W HERE DETAIL IS LOCATED

1 "UP TO" SYMBOL (ITEM ON FLO OR ABO VE)

APPROXIM ATE DIMENSIO N ABOVE FINISHED FLOO R TO TOP OR

BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE

10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOD: 8' - 10"

BOD: 7' - 2"

20x20

20x20

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR

BOTTOM OF DUCTW ORK, UNLESS NOTED OTHERW ISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE

OF PIPE, UNLESS NOTED OTHERW ISE

DL-1

UC-X DOOR UNDERCUT. X = HEIGHT O F UNDERCUT IN INCHES; 0.75 INCH

UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.

DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.

CONNECT TO EXISTING

HVAC PIPING DESIGNATIONS

CHILLED W ATER SUPPLY PIPECHS

CONDENSER W ATER SUPPLY PIPECW S

CONDENSER W ATER RETURN PIPECW R

DRAIN LINE. PITCH IN DIRECTION INDICATEDD

HEATING HOT W ATER SUPPLY PIPEHW S

HEATING HOT W ATER RETURN PIPEHW R

W ATER MAKE-UP PIPEMU

VENT PIPEV

REFRIGERANT LIQ UID LINERL

REFRIGERANT SUCTION LINERS

EXPANSION TANK PIPEET

REFRIGERANT HOT GAS LINEHG

LOW PRESSURE CONDENSATE RETURN PIPELPC

LOW PRESSURE STEAM SUPPLY PIPELPS

MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC

MEDIUM PRESSURE STEAM SUPPLY PIPEMPS

PUMPED CONDENSATE RETURN PIPEPC

HIGH PRESSURE CONDENSATE RETURN PIPEHPC

HIGH PRESSURE STEAM SUPPLY PIPEHPS

STEAM SUPPLY PIPE - NUM BER INDICATES P.S.I.G .10

MISC SYMBOLS

DUCTWORK SYMBOLS

ROUND BRANCH DUCTW ORKCONICAL

FITTING

ACOUSTIC

FITTING

ACOUSTIC

FITTING

ADAD

D

R R

D

RECTANGULAR BRANCH DUCTW ORK

SQUARE TEE W ITH TURNING VANES

NOTE: ALL SQUARE ELBOW S IN

RECTANGULAR AND ROUND / OVAL

DUCTW ORK SHALL BE PROVIDED W ITH

TURNING VANES. REFER TO

SPECIFICATIONS FOR ADDITIONAL DETAILS.

EXISTING DUCTW ORK TO REMOVED

RETURN AIR, RELIEF AIR, OR TRANSFER AIR

DUCTW ORK. (UP AND DO W N) RADIUSED

OR SQUARE W ITH TURNING VANES.

SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.

(UP AND DO W N) RADIUSED OR SQUARE

W ITH TURNING VANES.

EXHAUST AIR DUCTW ORK. (UP AND

DOW N) RADIUSED OR SQUARE W ITH

TURNING VANES.

RECTANGULAR AND ROUND / OVAL

DUCTW ORK RISE / DRO P W ITH 90° RADIUSED

OR SQUARE ELBOW S AND TURNING VANES.

RADIUS ELBOW

90° SQUARE ELBOW (W ITH TURNING VANES)

NOTE: ALL SQUARE ELBOW S IN

RECTANGULAR AND ROUND DUCTW ORK

SHALL BE PROVIDED W ITH TURNING VANES.

ACCESS DOOR OR PANEL

DUCTW ORK RISE IN DIRECTION O F AIR

FLO W

DUCTW ORK DROP IN DIRECTION OF

AIR FLO W

DUCTW ORK W ITH ACOUSTICAL LINER.

LISTED DUCT SIZES ARE INSIDE CLEAR

DIMENSIO NS.

RECTANGULAR ROUND / OVAL

FLEXIBLE DUCTW ORK

FLEXIBLE CONNECTION

DUCTW ORK CONSTRUCTED OF

SPECIAL M ATERIAL AS NOTED

DIRECTION OF PITCH

RECTANGULAR DUCTW ORK

DIMENSIONS (W x H)26x20

ROUND DUCTW ORK DIM ENSIONS (D IA)26ø

OVAL DUCTW ORK DIMENSIONS (W x H)26x20 OV

DUCTWORK DEVICE SYMBOLS

W ALL OR DUCTW O RK M OUNTED AIR DEVICE. SG1 = DESIGNATION

(REFER TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION

SIZE (IN INCHES). 300 = REQUIRED CFM. 9'-0" = M OUNTING HEIGHT

FROM FLOOR TO BO TTOM O F GRILLE.

A3 10ø

MANUAL BALANCING DAMPER W ITH LO CKING DEVICE

BDD = BACK DRAFT DAM PER

CBD = COUNTER-BALANCED BACK DRAFT DAM PER

SD = SMOKE DAMPER

FS = COMBINATION FIRE - SMO KE DAMPER

MDD = MOTORIZED DAMPER

AFMS = AIR FLOW MEASURING STATION

DUCT MOUNTED SMOKE DETECTOR. COORDINATE LO CATIO N.

HUMIDITY SENSOR - DUCT M OUNTED

SG1

20x12

BOG: 9'-0"

XXX

A-D

XX

H

SD

SP

AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR

DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS).

10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR

DEVICE DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S.

AIR DEVICE SHOW N IS 2-W AY SIDE THROW . METHOD OF

IDENTIFICATION ALSO APPLIES TO O THER CEILING MOUNTED AIR

DEVICES.

FIRE DAMPER

A = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)

D OR S = DYNAMIC OR STATIC

STATIC PRESSURE SENSOR - DUCT MO UNTED

C

CARBON DIOXIDE SENSOR - DUCT MO UNTED

S

TEMPERATURE SENSOR - DUCT M OUNTED

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS

FOR REQUIRED TYPE BASED ON

APPLICATIO NS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUG E OR THERMOM ETER

COMBINATION SHUTOFF AND BALANCING

VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

BALL VALVE

BUTTERFLY VALVE

GATE VALVE

VALVES AND FITTINGS

DOUBLE LINE SINGLE LINE

10"

TOE: 3' - 0"

BOE: 0' - 6"

CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR

CHILLED W ATER GLYCOL SO LUTION SUPPLY PIPECHGS

CHILLED W ATER RETURN PIPECHR

SQUARE THROAT / RADIUS HEEL

FITTINGS NOT ACCEPTABLE

PIPING SYMBOLS

DOUBLE LINE SINGLE LINE

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTIO N (NO TE:

BULLHEAD TEE'S ARE NOT

PERMITTED)

DIRECTION OF PITCH

DROP

ELBO W DOW N

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

DD

RR

PIPE RISER

RADIUS'D BRANCH

RADIUS'D TEE

EXISTING DUCTW ORK TO REMAIN

UNLESS NOTED OTHERW ISE ON

DRAW INGS, 15° MAX FOR DIVERGING, 30°

MAX FOR CONVERGING TRANSITION

EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED

OTHERW ISE.

SPACE TEMPERATURE SENSO R / THERMOSTAT. W HEN W ALL M OUNTED, MOUNTING

HEIGHT 46" TO M EET ADA REQUIREMENTS. W HEN MO UNTED NEXT TO W ALL SW ITCH

COORDINATE W ITH ARCHITECT.

T

DP

DIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO

MEET ADA REQUIREM ENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH CO ORDINATE W ITH

ARCHITECT.

H

HUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO M EET ADA

REQUIREMENTS. W HEN M OUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA

REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.

C

CO

CARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET

ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH

ARCHITECT.

TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO M EET ADA

REQUIREMENTS. W HEN M OUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH

ARCHITECT.

S

S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM .

STATIC PRESSURE SENSOR.SP

STRAINER W ITH A BLOW DOW N VALVE AND

HOSE CONNECTION

DRAIN VALVE W ITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER W ITH P/T

PLUG IN AND OUT

EXPANSION JOINT

MANUAL AIR VENT

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE

2 PO RT AUTOMATIC CONTROL VALVE

3 PO RT AUTOMATIC CONTROL VALVE

QUICK OPENING M ANUAL VALVE

VACUUM BREAKER

NEEDLE VALVE

PRESSURE AND TEMPERATURE TEST PLUG

VACUUM GAUGE W ITH STOP

END CAP

GLOBE VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE O N RISER

A

M

M

N

V

VB

SOLENOID VALVE

S

SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE

DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS

NOTED OTHERW ISE. FOR STEAM SYSTEMS PIPE

DISCHARGE TO OUTDOORS.

W ATER METERM

PRESSURE GAUG E W ITH COCK AND SIPHON LOO P

BI-METALIC STEAM TRAP AND DRIP ASSEMBLY

THERMODYNAMIC STEAM TRAP AND DRIP

ASSEMBLY

INVERTED BUCKET STEAM TRAP AND DRIP

ASSEMBLY

FLOAT AND THERMOSTATIC STEAM TRAP

AND DRIP ASSEM BLY

THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY

BM

TD

IB

FT

TS

FLO W METER

F

UNION

CLEANO UT

STRAINER

AUTOMATIC PRESSURE INDEPENDENT

CONTROL VALVE

M

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:4

:0

A M

M001

LEGEND, INDEX, AND GENERAL

NOTESGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

SHEET LIST - MECHANICAL

SHEET NUMBER SHEET NAME

M402 ENLARGED MECHANICAL ROOM HVAC PLAN

M403 PARTIAL SIXTH FLOOR HVAC ROOF PLANS

M404 HVAC ISOMETRIC VIEWS

M501 HVAC DETAILS

M502 HVAC DETAILS

M503 HVAC DETAILS

M504 HVAC DETAILS

M505 HVAC DETAILS

M600 HVAC CONTROL SCHEMATICS

M601 HVAC CONTROL SCHEMATICS

M602 HVAC CONTROL SCHEMATICS

SHEET LIST - MECHANICAL

SHEET NUMBER SHEET NAME

M001 LEGEND, INDEX, AND GENERAL NOTES

M002 HVAC SCHEDULES

M003 HVAC SCHEDULES

M004 HVAC SCHEDULES

MD101 LOWER LEVEL HVAC DEMOLITION PLAN

MH101 LOWER LEVEL HVAC DUCTWORK PLAN

MH102 FIRST FLOOR HVAC DUCTWORK PLAN

MH103 ROOF LEVEL HVAC DUCTWORK PLAN

MP101 LOWER LEVEL HVAC PIPING PLAN

M401 ENLARGED MECHANICAL ROOM HVAC DEMOLITION PLAN

GENERAL NOTES

27. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LOCATION OF CEILING DIFFUSERS, REGISTERS, AND GRILLES.

28. W ATER PIPE CONNECTIONS TO AIR HEATING AND COO LING COILS SHALL

BE MADE TO PROVIDE COUNTER FLOW BETW EEN W ATER AND AIR.

29. W ALL TYPE EXHAUST REG ISTERS NOTED AS "BR" O N DRAW INGS ARE TO

BE INSTALLED W ITH BOTTOM OF REG ISTERS SEVEN INCHES ABOVE FINISHED

FLOOR.

30. W HERE DUCTS O R PIPES ARE REMOVED THRU W ALL/FLOOR/ROOF THAT IS

TO REMAIN, PATCH W ALL/FLOO R/RO OF OPENING TO MATCH EXISTING W HERE

OPENING IS NO T RE-USED.

31. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERW ISE

NOTED.

32. ALL CUTTING AND PATCHING REQUIRED FOR THIS PROJECT SHALL BE

INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE DISTURBED UNDER

THIS W ORK TO MATCH EXISTING.

33. IN GENERAL, KEEP DUCT AND PIPING MAINS NEXT TO UNDERSIDE O F

STRUCTURE.

34. ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEM S

NOT DESIRED BY THE VA SHALL BE REMOVED FROM THE PREMISES AND

DISPO SED OF PROPERLY BY THE CONTRACTOR.

35. THE CONTRACT DRAW INGS ARE NOT INTENDED TO SHOW EVERY

VERTICAL OR HORIZONTAL OFFSET W HICH M AY BE NECESSARY TO COMPLETE

THE SYSTEMS. CO ORDINATE W O RK IN ADVANCE W ITH ALL OTHER TRADES

AND REPORT IMMEDIATELY ANY DIFFICULTIES W HICH CAN BE ANTICIPATED.

36. FIELD VERIFY EXISTING CONDITIO NS, INCLUDING DUCT, PIPE AND

EQ UIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO PERFORMING W ORK.

37. HEPA FILTERED EXHAUST IS REQUIRED TO MAINTAIN A MINIMUM OF 0.01"

W .G. NEGATIVE PRESSURE IN CONSTRUCTION AREAS. COO RDINATE W ITH

GENERAL CONTRACTOR AND THE COR.

38. ALL ABANDONED EXTRANEO US PIPING , DUCTW ORK, SUPPORTS,

CONTRO LS, ETC. SHALL BE REMOVED.

39. TERMINATE PIPING AND DUCTW ORK BELOW FLOO RS, ABOVE CEILINGS,

ETC., IN CONCEALED SPACES. ALL CUTTING AND PATCHING SHALL MATCH

EXISTING FINISHES.

40. W HERE CONTROL DEVICES ARE REMOVED, PNEUM ATIC LINES SHALL BE

REM OVED BACK TO MAIN AND CAPPED; AND CONTROL W IRING AND CONDUIT

SHALL BE REMOVED BACK TO SOURCE.

41. ALL EXISTING DUCTW ORK, PIPING, EQUIPMENT, CO NTRO LS, ETC. SHOW N

ON REM OVAL PLAN(S) SHALL BE REMOVED. THE MAJORITY OF W ORK TO BE

REM OVED IS SHOW N. REMOVE ALL INCIDENTAL AND/O R ABANDONED

DUCTW ORK, PIPING, ETC. THAT MAY NOT BE SHOW N BUT IS ASSOCIATED W ITH

THE REMOVAL W ORK.

42. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING,

SERVICING, M AINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY

ACCESSIBLE BY PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON

PERM ANENT PLATFORMS, W ITHOUT THE USE OF PORTABLE LADDERS.

EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: ALL TYPES OF

VALVES, FILTERS AND STRAINER, TRANSMITTERS, CONTROL DEVICES, ETC.

43. W HERE EXISTING HVAC UTILITIES IN SERVICE W ILL BE DISRUPTED DURING

THE CONSTRUCTION OF THIS PROJECT, THIS W ORK SHALL BE PERFORMED ON

W EEKENDS OR W EEK NIGHTS. DOW NTIM E SHALL BE KEPT TO A MINIM UM, AND

SHALL BE COORDINATED AND SCHEDULED W ELL IN ADVANCE W ITH THE COR.

44. W HEN NEW SUPPLY AND RETURN AIR DUCTS ARE CONNECTED TO

EXISTING DUCTW ORK, CLEAN BOTH NEW AND EXISTING DUCTW ORK BY

MOPPING AND VACUUM CLEANING INSIDE AND OUTSIDE BEFORE OPERATION.

CLEANING OF EXISTING DUCTW ORK SHALL BE LIM ITED TO THE IMMEDIATE

AREA W ITHIN REACH OF THE OPEN END OF THE DUCT.

45. RUNOUT PIPING TO TERM INAL UNITS SHALL BE 0.75” SIZE UNLESS

OTHERW ISE NOTED. REFER TO AIR TERMINAL UNIT SCHEDULE(S).

46. APPROXIMATE ELEVATIONS NOTED ON FLOOR PLANS ARE TO THE BOTTOM

OF DUCTS AND EQUIPMENT, AND TO THE CENTER OF PIPES.

47. REFER TO ELECTRICAL DRAW INGS FOR VARIABLE SPEED MOTOR

CONTRO LLERS ASSOCIATED W ITH MECHANICAL EQUIPMENT.

48. ALL INSULATED DUCTW ORK AND PIPING SHALL HAVE DAM PER/VALVE

HANDLE EXTENSIONS.

49. CONTROL CONTRACTORS RESPONSIBILITES ARE LISTED IN SPECIFICATION

SECTION 23 09 23, SECTIO N 1.1.

50. SME DIVISION 26 AND 27 W O RK IS SHOW N ON DIVISIO N 23 DRAW INGS.

W ORK INCLUDES 120V POW ER CIRCUITRY, BREAKERS, VFD'S, DISCONNECTS,

VO ICE/DATA OUTLETS, CONDUIT, ETC. DIV 26/27 CONTRACTOR TO

COORDINATE ALL REQ UIREMENTS CLOSELY W ITH DIV 01 AND DIV 23

CONTRACTORS.

51. EXTEND POW ER, CO MMUNICATIONS, SIGNAL, AND OTHER W IRING

REQ UIRED TO ACCOM PLISH THE SPECIFIED STRATEGIES AND OBJECTIONS

FROM NEW M ETERS AND…