A0004 - 08 71 00 - Door Hardware.pdf

PDF 218 KB Posted

Attached to
Z1DA--Renovate Nuclear Med 583-20-102 (VA-21-00037478)
Solicitation number
36C25021B0036
Issued by

About this file

This document package includes specifications for a federal construction project to renovate nuclear medicine services at the Richard L. Roudebush VA Medical Center in Indianapolis, Indiana. The specifications cover door hardware requirements including hinges, locks, exit devices, closers, signage and other hardware. Key details include hardware set numbers and descriptions for over 30 doors, finish specifications, installation and warranty requirements. Electrified hardware, access control system components and detailed operation narratives are also specified for various secured doors.

View the file

Other files

File Type Posted
Amendment A00006.docx DOCX document
Amendment A00006 RFI Responses.docx DOCX document
Amendment 36C25021B0036 A00005.pdf PDF
A00004- Corrected Statement of Work.pdf PDF
Amendment 36C25021B0036 A00004.pdf PDF
A00004 - RFI Responses.docx DOCX document
A00004 - 10 25 13 - Patient Bed Service Walls.pdf PDF
A00004 - Door Schedule.pdf PDF
Amendment 36C25021B0036 A00003.pdf PDF
Amendment A00002.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
A0001 - RFI 1 ShieldingReportComplete.pdf PDF
A0001 - RFI 2- GC101.pdf PDF
A0001 - RFI Responses.docx DOCX document
Amendment A0001.docx DOCX document
A0001 - RFI 4- Door Schedule.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part18.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part23.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part22.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part11.pdf PDF
Specifications.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part21.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part13.pdf PDF
Wage Determination.txt TXT text file
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part15.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part4.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part20.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part8.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part6.pdf PDF
36C25021B0036 Solicitation Document.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part11.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part24.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part2.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part3.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Richard L. Roudebush VA Medical Center 11-01-19

Relocate Nuclear Medicine Services for Centralized Services Bid Documents

583-20-102 January 6, 2021

08 71 00-1

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

A. Door hardware and related items necessary for complete installation and operation of doors.

B. Drawings and general provisions of the Contract, including General and

Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 RELATED WORK

A. Caulking: Section 07 92 00 JOINT SEALANTS.

B. Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11

13, HOLLOW METAL DOORS AND FRAMES, Section 08 42 29.23, SLIDING

AUTOMATIC ENTRANCES, Section 08 71 13, AUTOMATIC DOOR OPERATORS, Section 13 49 00, RADIATION PROTECTION, Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.

C. Painting: Section 09 91 00, PAINTING.

D. Electrical: Division 26, ELECTRICAL.

E. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

A. All hardware shall comply with UFAS, (Uniform Federal Accessible

Standards) unless specified otherwise.

B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).

C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.

D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

E. The following items shall be of the same manufacturer, except as otherwise specified:

08 71 00-2

1. Mortise locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

4. Exit devices.

5. Floor closers.

1.4 WARRANTY

A. Automatic door operators shall be subject to the terms of FAR Clause

52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

3. Twenty five years for manual surface door closer bodies.

4. Five years for motorized electric latch retraction exit devise

5. Two years for electromechanical door hardware.

1.5 MAINTENANCE MANUALS

A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section

01 33 23. Submit 2 final copies of the final approved schedules to VAMC

Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).

B. Hardware Schedule: Prepare and submit hardware schedule in the following form:

Hardware

Item

Quantity Size Reference

Publication

Type No.

Finish Mfr.

Name and

Catalog

No.

Key

Control

Symbols

UL Mark

(if fire rated and listed)

ANSI/BHMA

Finish

Designation

08 71 00-3

C. Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers

Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

E. Keying Schedule: Prepared under the supervision of the COR, separate schedule detailing final keying instructions for locksets and cylinders in writing. Include keying system explanation, door numbers, key set symbols, hardware set numbers and special instructions. Owner to approve submitted keying schedule prior to the ordering of permanent cylinders.

1.7 DELIVERY AND MARKING

A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to

Contracting Officer’s Representative (COR) for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. These items shall remain on file in Contracting

Officer’s Representative (COR)'s office until all other similar items have been installed in project, at which time the Contracting Officer’s

Representative (COR) will deliver items on file to Contractor for installation in predetermined locations on the project.

B. Inventory door hardware on receipt and provide secure lock-up and shelving for door hardware delivered to Project site. Do not store electronic access control hardware, software or accessories at Project site without prior authorization.

08 71 00-4

C. Tag each item or package separately with identification related to the final Door Hardware Schedule and include basic installation instructions with each item or package.

D. Deliver, as applicable, permanent keys, cylinders, cores, access control credentials, software and related accessories directly to Owner via registered mail or overnight package service. Instructions for delivery to the Owner shall be established at the "Keying Conference".

1.8 PREINSTALLATION MEETING

A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and

Hardware Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols.

Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

B. Keying: All cylinders shall be keyed into existing Grand Master Key

System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 6 pin type. Keying information shall be furnished at a later date by the Contracting Officer’s Representative (COR).

C. Keying: A new Great Grandmaster key shall be established for this project. The key system shall be small format (Best size and profile)

08 71 00-5 removable core type as previously described. The key blanks shall be protected by a utility patent with a minimum seven years remaining on the patent from the start of construction, and protected by contract-controlled distribution. The manufacturer shall furnish code pattern listings in both paper and electronic formats so keys may be reproduced by code.; provide electronic format in file type required by project’s key control software. The manufacturer shall design the new key system with the capacity to rekey the existing system and provide for 25 percent expansion capability beyond this requirement. Submit a keying chart for approval showing proposed keying layout and listing expansion capacity.

1. Keying information will be furnished to the Contractor by the

Contracting Officer’s Representative (COR).

2. Supply information regarding key control of cylinder locks to manufacturers of equipment having cylinder type locks. Notify

Contracting Officer’s Representative (COR) immediately when and to whom keys or keying information is supplied. Return all such keys to the Contracting Officer’s Representative (COR).

1.10 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

B. American Society for Testing and Materials (ASTM):

F883-04.................Padlocks

E2180-07................Standard Test Method for Determining the

Activity of Incorporated Antimicrobial Agent(s)

In Polymeric or Hydrophobic Materials

C. American National Standards Institute/Builders Hardware Manufacturers

Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Locks and Latches

A156.3-08...............Exit Devices, Coordinators, and Auto Flush

Bolts

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

08 71 00-6

A156.6-05...............Architectural Door Trim

A156.8-05...............Door Controls-Overhead Stops and Holders

A156.12-05 .............Interconnected Locks and Latches

A156.13-05..............Mortise Locks and Latches Series 1000

A156.14-07 .............Sliding and Folding Door Hardware

A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical

A156.16-08..............Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Pivots

A156.18-06..............Materials and Finishes

A156.21-09..............Thresholds

A156.22-05..............Door Gasketing and Edge Seal Systems

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.31-07 .............Electric Strikes and Frame Mounted Actuators

A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Frames

D. National Fire Protection Association (NFPA):

80-10...................Fire Doors and Other Opening Protectives

101-09..................Life Safety Code

E. Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

PART 2 - PRODUCTS

2.1 BUTT HINGES

A. Hinges: ANSI/BHMA A156.1 certified butt hinges with number of hinge knuckles and other options as specified in the Door Hardware Sets.

1. Quantity: Provide the following hinge quantity:

a. Two Hinges: For doors with heights up to 60 inches.

b. Three Hinges: For doors with heights 61 to 90 inches.

c. Four Hinges: For doors with heights 91 to 120 inches.

d. For doors with heights more than 120 inches, provide 4 hinges, plus 1 hinge for every 30 inches of door height greater than

120 inches.

08 71 00-7

2. Hinge Size: Provide the following, unless otherwise indicated, with hinge widths sized for door thickness and clearances required:

a. Widths up to 3’0”: 4-1/2” standard or heavy weight as specified.

b. Sizes from 3’1” to 4’0”: 5” standard or heavy weight as specified.

3. Hinge Weight and Base Material: Unless otherwise indicated, provide the following:

a. Interior Doors: Standard weight, steel, ball bearing or oil impregnated bearing hinges unless Hardware Sets indicate heavy weight.

4. Hinge Options: Comply with the following:

a. Non-removable Pins: Provide set screw in hinge barrel that, when tightened into a groove in hinge pin, prevents removal of pin while door is closed; for the all out-swinging lockable doors.

C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 DOOR CLOSING DEVICES

A. All door closers specified herein shall meet or exceed the following criteria:

1. General: Door closers to be from one manufacturer, matching in design and style, with the same type door preparations and templates regardless of application or spring size. Closers to be non-handed with full sized covers including installation and adjusting information on inside of cover.

2. Standards: Closers to comply with UL-10C for Positive Pressure Fire

Test and be U.L. listed for use of fire rated doors.

3. Cycle Testing: Provide closers which have surpassed 15 million cycles in a test witnessed and verified by UL.

4. Size of Units: Comply with manufacturer's written recommendations for sizing of door closers depending on size of door, exposure to weather, and anticipated frequency of use. Where closers are indicated for doors required to be accessible to the physically handicapped, provide units complying with ANSI ICC/A117.1.

08 71 00-8

5. Closer Arms: Provide heavy duty, forged steel closer arms unless otherwise indicated in Hardware Sets.

6. Closers shall not be installed on exterior or corridor side of doors; where possible install closers on door for optimum aesthetics.

7. Closer Accessories: Provide door closer accessories including custom templates, special mounting brackets, spacers and drop plates as required for proper installation. Provide through-bolt and security type fasteners as specified in the hardware sets.

2.3 POWER TRANSFER DEVICES

A. Electrified Quick Connect Transfer Hinges: Provide electrified transfer hinges with Molex™ standardized plug connectors and sufficient number of concealed wires (up to 12) to accommodate the electrified functions specified in the Door Hardware Sets. Connectors plug directly to through-door wiring harnesses for connection to electric locking devices and power supplies. Wire nut connections are not acceptable.

B. Concealed Quick Connect Electric Power Transfers: Provide concealed wiring pathway housing mortised into the door and frame for low voltage electrified door hardware. Furnish with Molex™ standardized plug connectors and sufficient number of concealed wires (up to 12) to accommodate the electrified functions specified in the Door Hardware

Sets. Connectors plug directly to through-door wiring harnesses for connection to electric locking devices and power supplies. Wire nut connections are not acceptable.

C. Electric Door Wire Harnesses: Provide electric/data transfer wiring harnesses with standardized plug connectors to accommodate up to twelve

(12) wires. Connectors plug directly to through-door wiring harnesses for connection to electric locking devices and power supplies. Provide sufficient number and type of concealed wires to accommodate electric function of specified hardware. Provide a connector for through-door electronic locking devices and from hinge to junction box above the opening. Wire nut connections are not acceptable. Determine the length required for each electrified hardware component for the door type, size and construction, minimum of two per electrified opening.

08 71 00-9

2.4 DOOR STOPS AND HOLDERS

A. General: Door stops and holders to be of type and design as specified below or in the Hardware Sets.

B. Door Stops and Bumpers: ANSI/BHMA A156.16, Grade 1 certified door stops and wall bumpers. Provide wall bumpers, either convex or concave types with anchorage as indicated, unless floor or other types of door stops are specified in Hardware Sets. Do not mount floor stops where they will impede traffic. Where floor or wall bumpers are not appropriate, provide overhead type stops and holders.

C. Overhead Door Stops and Holders: ANSI/BHMA A156.6, Grade 1 certified overhead stops and holders to be surface or concealed types as indicated in Hardware Sets. Track, slide, arm and jamb bracket to be constructed of extruded bronze and shock absorber spring of heavy tempered steel.

Provide non-handed design with mounting brackets as required for proper operation and function.

2.5 CYLINDERS AND KEYING

A. General: Cylinder manufacturer to have minimum (10) years experience designing secured master key systems and have on record a published security keying system policy.

B. Cylinders: Original manufacturer cylinders complying with the following:

1. Mortise Type: Threaded cylinders with rings and cams to suit hardware application.

2. Rim Type: Cylinders with back plate, flat-type vertical or horizontal tailpiece, and raised trim ring.

3. Bored-Lock Type: Cylinders with tailpieces to suit locks.

4. Mortise and rim cylinder collars to be solid and recessed to allow the cylinder face to be flush and be free spinning with matching finishes.

5. Keyway: Match Facility Restricted Keyway.

C. Permanent Cores: Manufacturer's standard; finish face to match lockset;

complying with the following:

1. Interchangeable Cores: Core insert, removable by use of a special key; usable with other manufacturers' cylinders.

D. Permanent Cores: Match standard. Reference Division 01 for material required under project. Installation to be included under Division 08

"Door Hardware" base bid package.

08 71 00-10

1. Interchangeable Cores: Core insert, removable by use of a special key; usable with other manufacturers' cylinders.

E. Keying System: Each type of lock and cylinders to be factory keyed.

1. Conduct specified "Keying Conference" to define and document keying system instructions and requirements.

2. Furnish factory cut, nickel-silver large bow permanently inscribed with a visual key control number as directed by Owner.

3. Existing System: Field verify and key locks to match Owner's existing system.

F. Key Quantity: Provide the following minimum number of keys:

1. Change Keys per Cylinder: Two (2)

2. Master Keys (per Master Key Level/Group): Five (5).

3. Construction Keys (where required): Ten (10).

4. Construction Control Keys (where required): Two (2).

5. Permanent Control Keys (where required): Two (2).

G. Construction Keying: Provide construction master keyed cylinders.

H. Construction Keying: Provide temporary keyed construction cores.

I. Key Registration List (Bitting List):

1. Provide keying transcript list to COR in the proper format for importing into key control software.

2. Provide transcript list in writing or electronic file as directed by the COR.

2.6 LOCKS AND LATCHES

A. Strikes: Provide manufacturer's standard strike with strike box for each latch or lock bolt, with curved lip extended to protect frame, finished to match door hardware set, unless otherwise indicated, and as follows:

1. Flat-Lip Strikes: For locks with three-piece antifriction latchbolts, as recommended by manufacturer.

2. Extra-Long-Lip Strikes: For locks used on frames with applied wood casing trim.

3. Aluminum-Frame Strike Box: Provide manufacturer's special strike box fabricated for aluminum framing.

4. Double-lipped strikes: For locks at double acting doors. Furnish with retractable stop for rescue hardware applications.

B. Standards: Comply with the following:

1. Strikes for Mortise Locks and Latches: BHMA A156.13.

2. Strikes for Bored Locks and Latches: BHMA A156.2.

08 71 00-11

3. Strikes for Auxiliary Deadlocks: BHMA A156.36.

4. Dustproof Strikes: BHMA A156.16.

C. In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Locksets, Grade 1 (Heavy Duty): ANSI/BHMA A156.13, Series

1000, Operational Grade 1 certified. Locksets are to be manufactured with a corrosion resistant steel case and be field-reversible for handing without disassembly of the lock body.

2.7 ELECTROMECHANICAL LOCKS

A. Electromechanical Mortise Locksets, Grade 1 (Heavy Duty): Subject to same compliance standards and requirements as mechanical mortise locksets, electrified locksets to be of type and design as specified below.

1. Electrified Lock Options: Where indicated in the Hardware Sets, provide electrified options including: outside door lock/unlock trim control, latchbolt and lock/unlock status monitoring, deadbolt monitoring, and request-to-exit signaling. Support end-of-line resistors contained within the lock case. Unless otherwise indicated, provide electrified locksets standard as fail secure.

2.8 ELECTRIC STRIKES

A. ANSI/ BHMA A156.31 Grade 1.

B. General: Use fail-secure electric strikes at fire-rated doors.

2.9 KEYS

A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.10 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

A. Door Protective Trim

08 71 00-12

1. General: Door protective trim units to be of type and design as specified below or in the Hardware Sets.

2. Size: Fabricate protection plates (kick, armor, or mop) not more than 2" less than door width (LDW) on stop side of single doors and

1” LDW on stop side of pairs of doors, and not more than 1" less than door width on pull side. Coordinate and provide proper width and height as required where conflicting hardware dictates. Height to be as specified in the Hardware Sets.

3. Where plates are applied to fire rated doors with the top of the plate more than 16” above the bottom of the door, provide plates complying with NFPA 80. Consult manufacturer’s catalog and template book for specific requirements for size and applications.

4. Protection Plates: ANSI/BHMA A156.6 certified protection plates

(kick, armor, or mop), fabricated from the following:

a. Stainless Steel: 300 grade, 050-inch thick.

5. Options and fasteners: Provide manufacturer's designated fastener type as specified in the Hardware Sets. Provide countersunk screw holes.

2.11 EXIT DEVICES

A. General Requirements: All exit devices specified herein shall meet or exceed the following criteria:

1. At doors not requiring a fire rating, provide devices complying with NFPA 101 and listed and labeled for "Panic Hardware" according to UL305. Provide proper fasteners as required by manufacturer including sex nuts and bolts at openings specified in the Hardware

Sets.

2. Where exit devices are required on fire rated doors, provide devices complying with NFPA 80 and with UL labeling indicating "Fire Exit

Hardware". Provide devices with the proper fasteners for installation as tested and listed by UL. Consult manufacturer’s catalog and template book for specific requirements.

3. Except on fire rated doors, provide exit devices with hex key dogging device to hold the pushbar and latch in a retracted position. Provide optional keyed cylinder dogging on devices where specified in Hardware Sets.

4. Devices must fit flat against the door face with no gap that permits unauthorized dogging of the push bar. The addition of filler strips

08 71 00-13 is required in any case where the door light extends behind the device as in a full glass configuration.

5. Energy Efficient Design: Provide lock bodies which have a holding current draw of 15mA maximum, and can operate on either 12 or 24 volts. Locks are to be field configurable for fail safe or fail secure operation.

6. Electromechanical Options: Subject to same compliance standards and requirements as mechanical exit devices, electrified devices to be of type and design as specified in hardware sets. Include any specific controllers when conventional power supplies are not sufficient to provide the proper in rush current.

7. Lever Operating Trim: Where exit devices require lever trim, furnish manufacturer's heavy duty escutcheon trim with threaded studs for thru-bolts.

a. Lock Trim Design: As indicated in Hardware Sets, provide finishes and designs to match that of the specified locksets.

b. Where function of exit device requires a cylinder, provide a cylinder (Rim or Mortise) as specified in Hardware Sets.

8. Vertical Rod Exit Devices: Where surface or concealed vertical rod exit devices are used at interior openings, provide as less bottom rod (LBR) unless otherwise indicated. Provide dust proof strikes where thermal pins are required to project into the floor.

9. Narrow Stile Applications: At doors constructed with narrow stiles, or as specified in Hardware Sets, provide devices designed for maximum 2” wide stiles.

10. Dummy Push Bar: Nonfunctioning push bar matching functional push bar.

11. Rail Sizing: Provide exit device rails factory sized for proper door width application.

12. Through Bolt Installation: For exit devices and trim as indicated in Door Hardware Sets.

B. Conventional Push Rail Exit Devices (Heavy Duty): ANSI/BHMA A156.3, Grade 1 certified panic and fire exit hardware devices furnished in the functions specified in the Hardware Sets. Exit device latch to be stainless steel, pullman type, with deadlock feature.

2.12 FLUSH BOLTS (AUTOMATIC)

08 71 00-14

A. Flush Bolts and Surface Bolts: ANSI/BHMA A156.3 and A156.16, Grade 1, certified.

1. Flush bolts to be furnished with top rod of sufficient length to allow bolt retraction device location approximately six feet from the floor.

2. Furnish dust proof strikes for bottom bolts.

3. Surface bolts to be minimum 8” in length and U.L. listed for labeled fire doors and U.L. listed for windstorm components where applicable.

4. Provide related accessories (mounting brackets, strikes, coordinators, etc.) as required for appropriate installation and operation.

2.13 COMBINATION PUSH AND PULL PLATES

A. Door Push Plates and Pulls: ANSI/BHMA A156.6 certified door pushes and pulls of type and design specified in the Hardware Sets. Coordinate and provide proper width and height as required where conflicting hardware dictates.

1. Push/Pull Plates: Minimum .050 inch thick, size as indicated in hardware sets, with beveled edges, secured with exposed screws unless otherwise indicated.

2. Door Pull and Push Bar Design: Size, shape, and material as indicated in the hardware sets. Minimum clearance of 2 1/2-inches from face of door unless otherwise indicated.

3. Offset Pull Design: Size, shape, and material as indicated in the hardware sets. Minimum clearance of 2 1/2-inches from face of door and offset of 90 degrees unless otherwise indicated.

4. Fasteners: Provide manufacturer's designated fastener type as indicated in Hardware Sets.

2.14 MISCELLANEOUS HARDWARE

A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):

Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

B. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers

Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated

08 71 00-15 frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors.

Provide 4 mutes or silencers for frames for each Dutch type door.

Provide 2 mutes for each edge of sliding door which would contact door frame.

2.15 DIGITAL ELECTRONIC CYLINDERS AND KEYS

A. Digital Cylinders: Provide original manufacturer cylinders to meet the following minimum requirements:

1. Provide cylinders to retrofit into new or existing hardware without modifications. Provide cylinders and keys with integral power without the need for wires or electricity.

2. Provide electronic access control functions for rim, mortise, or key-in-lever cylinder types, and auxiliary locks (deadbolts, padlocks, cam locks) as specified in the hardware sets listed under

Part 3.

3. Communications between cylinder/key/software are AES encrypted.

4. Provide system compatibility with small format interchangeable core cylinder systems.

5. Cylinders to provide access control functions with non-volatile system programming allowing loss of battery life to retain key access rights, and/or audit records.

6. 2000 audit events stored in cylinder.

7. Electronic only cylinder powered by the key.

B. Digital Keys: Provide original manufacturer keys to meet the following minimum requirements:

1. Single, multi-function keys perform all user, administrative, and core removal operations.

2. Key and cylinder shall be designed for use on interior and exterior with an operating temperature of -40 Degrees F to 140 Degrees F.

3. One piece stainless steel with hardened tip.

4. Provide keys which are bundled with individual wall outlet chargers and USB cables.

5. Up to 1800 openings per charge.

6. Keys automatically power down when left in the cylinder.

7. Access 16,000 cylinders maximum.

8. Audit 10,000 events maximum.

08 71 00-16

9. All programming done at key.

C. Programming Stations: Provide stations for the programming and charging of keys. Provide the necessary cables and system dongles for full operation.

1. Provide one desktop programming station.

D. Digital Electronic Cylinder System Software: Provide digital cylinder manufacturer's original management software supporting the following features:

1. Provide web hosted Basic version of the software.

2. Product management by the system software with the following provisions:

a. Deactivate lost or stolen keys.

b. User schedules set uniquely for each key holder.

c. Full audit reports.

d. Physical access to the key is not required.

3. Software access protected by password and unique system authorization key.

2.16 ARCHITECTURAL SEALS

A. General: Thresholds, weatherstripping, and gasket seals to be of type and design as specified below or in the Hardware Sets. Provide continuous weatherstrip gasketing on exterior doors and provide smoke, light, or sound gasketing on interior doors where indicated. At exterior applications provide non-corrosive fasteners and elsewhere where indicated.

B. Smoke Labeled Gasketing: Assemblies complying with NFPA 105 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for smoke control ratings indicated, based on testing according to UL 1784.

1. Provide smoke labeled perimeter gasketing at all smoke labeled openings.

C. Fire Labeled Gasketing: Assemblies complying with NFPA 80 that are listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction, for fire ratings indicated, based on testing according to UL-10C.

08 71 00-17

1. Provide intumescent seals as indicated to meet UL10C Standard for

Positive Pressure Fire Tests of Door Assemblies, and NPFA 252, Standard Methods of Fire Tests of Door Assemblies.

D. Sound-Rated Gasketing: Assemblies that are listed and labeled by a testing and inspecting agency, for sound ratings indicated.

E. Replaceable Seal Strips: Provide only those units where resilient or flexible seal strips are easily replaceable and readily available from stocks maintained by manufacturer.

2.17 ELECTRONIC ACCESSORIES

A. Power Supplies: Provide Nationally Recognized Testing Laboratory Listed

12VDC or 24VDC (field selectable) filtered and regulated power supplies.

Include battery backup option with integral battery charging capability in addition to operating the DC load in event of line voltage failure.

Provide the least number of units, at the appropriate amperage level, sufficient to exceed the required total draw plus 50% for the specified electrified hardware and access control equipment.

2.18 FINISHES

A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.

B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

C. Miscellaneous Finishes:

1. Hinges --interior doors: 652 or 630.

2. Pivots: Match door trim.

3. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

4. Cover plates for floor hinges and pivots: 630.

5. Other primed steel hardware: 600.

D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.

E. Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.

08 71 00-18

Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.

2.19 BASE METALS

A. Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to Contracting Officer’s

Representative (COR) for approval.

B. Hardware Heights from Finished Floor:

1. Exit devices centerline of strike (where applicable) 1024 mm (40-

5/16 inches).

2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).

3. Deadlocks centerline of strike 1219 mm (48 inches).

4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.

5. Centerline of door pulls to be 1016 mm (40 inches).

6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.

7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.

8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.

3.2 INSTALLATION

A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. Where

08 71 00-19 closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws.

B. Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

D. Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by

Contracting Officer’s Representative (COR). Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.

E. Hinges Required Per Door:

Door Description Number butts

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm

(7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less

2 butts

Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts

F. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.

All fastenings exposed to weather shall be of nonferrous metal.

G. After locks have been installed; show in presence of Contracting

Officer’s Representative (COR) that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and

08 71 00-20 above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the Contracting Officer’s Representative (COR) for his records.)

Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

H. Install each item of mechanical and electromechanical hardware and access control equipment to comply with manufacturer's written instructions and according to specifications.

1. Installers are to be trained and certified by the manufacturer on the proper installation and adjustment of fire, life safety, and security products including: hanging devices; locking devices;

closing devices; and seals.

I. Retrofitting: Install door hardware to comply with manufacturer's published templates and written instructions. Where cutting and fitting are required to install door hardware onto or into surfaces that are later to be painted or finished in another way, coordinate removal, storage, and reinstallation of surface protective trim units with finishing work specified in Division 9 Sections. Do not install surface-mounted items until finishes have been completed on substrates involved.

J. Thresholds: Set thresholds for exterior and acoustical doors in full bed of sealant complying with requirements specified in Division 7 Section

"Joint Sealants."

3.3 FINAL INSPECTION

A. Installer to provide letter to COR that upon completion, installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of COR.

08 71 00-21

3.5 HARDWARE SETS

A. Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.

B. Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.

C. Manufacturer’s Abbreviations: The manufacturers listed below are a basis of design only. An approved equal may be substituted.

1. MK - McKinney

2. PE - Pemko

3. GS - ASSA ABLOY Glass Solutions

4. RF - Rixson

5. RO - Rockwood

6. SA - SARGENT

7. AD - Adams Rite

8. MC - Medeco

9. RU - Corbin Russwin

10. NO - Norton

11. BM - Besam

12. SU - Securitron

13. LU - Lund Equipment Co

14. OT - Other

D. Door Hardware Schedule: The manufacturers listed below are a basis of design only. An approved equal may be substituted.

ELECTRIC HARDWARE ABBREVIATIONS LEGEND:

ADO = Automatic Door Operator

EMCH = Electro-Mechanical Closer-Holder

MHO = Magnetic Hold-Open (wall- or floor-mounted)

08 71 00-22

Hardware Sets

Set: HW-1A

Doors: 39

3 Hinge TA2714 (NRP and size as required)

US26D MK 087100

1 Passage Latch 8215 LNL US32D SA 087100

1 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

3 Silencer 608 RO 087100

Set: HW-15

Doors: OMIT 25, 27, A-B019, A-B023

1 Track System W60 x Length Required PE 087100

2 Pull RM2214-24 Mtg-Type 5HD

(Back to Back)

US32D RO 087100

Set: HW-16

Doors: A-B004, A-B029a, A-B029b

1 SFIC Rim Cylinder Housing 3_ tailpiece to suit US32D SA 087100

1 Cylinder type as required 626 RU 087100

All Hardware Provided By

Door Supplier

Set: HW-16A

Doors: A-B005a, A-B006

1 SFIC Rim Cylinder Housing 3_ tailpiece to suit US32D SA 087100

1 Card Reader By Security Supplier

All Hardware Provided By

Door Supplier

OMIT

Set: HW-17

Doors: A-B008, A-B009, A-B010, A-B025, A-B026, A-B027, A-B028

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Existing Hardware To Remain

08 71 00-23

Notes: Door is Push/Push. No Locking function.

OMIT

Set: HW-18

Doors: A-B011C-I

1 XT Key EA-100178 XT Slim Line Key MC 087100

1 XT Key Charger 94-0307 MC 087100

1 XT Install/Control Key EA-100174 MC 087100

1 XT Install Key EA-100173 MC 087100

1 Programming Station EA-100109 MC 087100

Set: HW-2B

Doors: A-B016, A-B017

1 Double Acting Hinge DSHP01C x Length Required PE 087100

1 Privacy Lock 49 8265 LNL US32D SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Mop Plate K1050 - 10" X 1" LDW high

BEV CSK

US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

1 Emergency Stop ERS_C-NOTCH x HT x Hand PE 087100

1 Coat Hook RM801 US26D RO 087100

Set: HW-3

Doors: A-B015, A-B020, A-B021, A-B024

3 Hinge (heavy weight) T4A3786 (NRP and size as required)

US26D MK 087100

1 Office/Entry Lock 70 8205 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

Set: HW-3A

Doors: A-B005, A-B013, A-B014, A-B022 required)

US26D MK 087100

08 71 00-24

1 Office/Entry Lock 70 8205 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

1 Silencer 608 RO 087100

Set: HW-3B

Doors: A-B004b

1 Pivot Set L147 626 RF 087100

1 Intermediate Pivot ML19 626 RF 087100

Office/Entry Lock (lead lined)

70 74 8205 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

Set: HW-3C

Doors: A-B002, A-B003

Office/Entry Lock (lead lined)

70 74 8205 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

Set: HW-3D

Doors: A-B012 required)

1 Office/Entry Lock 70 8205 LNL US32D SA 087100

08 71 00-25

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

1 Gasketing S88D (Head & Jambs) PE 087100

Set: HW-4G

Doors: A-B004a, A-B006a

2 Pivot Set L147 626 RF 087100

2 Intermediate Pivot ML19 626 RF 087100

Self Latching Flush Bolt

Set 2845 / 2945 (As Required) US26D RO 087100

1 Dust Proof Strike 570 US26D RO 087100

1 Classroom Lock (lead lined) 70 74 8237 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surf Overhead Stop 10-X36 630 RF 087100

1 Wall Stop 403 (or) 441CU (As

Required)

2 Silencer 608 RO 087100

Set: HW-5A

Doors: A-B007a

1 Storeroom Lock (lead lined) 70 74 8204 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

Set: HW-5G

Doors: A-B011 required)

US26D MK 087100

1 Storeroom Lock 70 8204 LNL US32D SA 087100

08 71 00-26

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

Set: HW-5H

Doors: A-B031 required)

US26D MK 087100

1 Storeroom Lock 70 8204 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

Set: HW-SH-3

Doors: A-B018, A-B029

1 Hinge (heavy weight) T4A3786 QC12 US26D MK 087100

2 Hinge (heavy weight) T4A3786 (NRP and size as required)

US26D MK 087100

Electrified Mortise Lock

(fail secure) 70 NAC-82271-24v LNL US32D SA 087100

08 71 00-27

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

3 Silencer 608 RO 087100

1 Card Reader By Security Supplier

1 ElectroLynx Harness QC-C**** x Length Required MK 087100

1 ElectroLynx Harness QC-C1500P MK 087100

1 Power Supply BPS (Size & Type as

Required)

SU 087100

1 Wiring Diagram Elevation and Point to

Point as Specified

OT

Notes: System Operational Narrative:

• Door normally closed and secure.

• Access by valid credential presentation unlocking Lockset lever on the secure side for a pre-determined time limit and then relocking.

• Egress always free for immediate exit. Request-to-Exit sensor integrated into the lockset allows exit without alarm condition.

• Door position switch integrated into the lockset provides open/closed monitoring to both access control system and intrusion alarm service.

• Outside lever trim remains locked (fail secure) in event of power loss.

Key override cylinder for emergency access.

Set: HW-SH-3A

Doors: A-B007

1 Electrified Inter Pivot EFML19 QC 626 RF 087100

Electrified Mortise Lock

(fail secure/lead lined)

70 74 NAC-82271 LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

3 Silencer 608 RO 087100

1 Card Reader By Security Supplier

1 ElectroLynx Harness QC-C**** x Length Required MK 087100

1 ElectroLynx Harness QC-C1500P MK 087100

1 Power Supply BPS (Size & Type as

Required)

SU 087100

1 Wiring Diagram Elevation and Point to

• Access by valid credential presentation unlocking Lockset lever on the

08 71 00-28 secure side for a pre-determined time limit and then relocking.

• Egress always free for immediate exit. Request-to-Exit sensor integrated into the lockset allows exit without alarm condition.

• Door position switch integrated into the lockset provides open/closed monitoring to both access control system and intrusion alarm service.

Set: HW-SH-3B

Doors: 9B, CB-9

1 Hinge (heavy weight) T4A3786 QC12 US26D MK 087100

2 Hinge (heavy weight) T4A3786 (NRP and size as required)

US26D MK 087100

Electrified Mortise Lock

(fail secure) 70 NAC-82271-24v LNL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

1 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

1 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

1 Gasketing S88D (Head & Jambs) PE 087100

1 Card Reader By Security Supplier

1 ElectroLynx Harness QC-C**** x Length Required MK 087100

1 ElectroLynx Harness QC-C1500P MK 087100

1 Power Supply BPS (Size & Type as

Required)

SU 087100

1 Wiring Diagram Elevation and Point to

• Access by valid credential presentation unlocking Lockset lever on the secure side for a pre-determined time limit and then relocking.

• Egress always free for immediate exit. Request-to-Exit sensor integrated into the lockset allows exit without alarm condition.

• Door position switch integrated into the lockset provides open/closed monitoring to both access control system and intrusion alarm service.

Set: HW-SH-7

Doors: A-B020a

6 Hinge (heavy weight) required)

08 71 00-29

Fire Rated SVR Exit Device

(LBR, EL-Trim Fail Sec., RX)

12 55 NB8774-24v ETL US32D SA 087100

Fire Rated SVR Exit Device

(LBR, EO, RX)

12 55 NB8710 EO US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

2 Surface Closer (Tri-Pack) 281 UO (Reg or P/A Arm as required)

EN SA 087100

2 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

2 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

1 Gasketing S88D (Head & Jambs) PE 087100

1 Astragal S771C x Door Height PE 087100

2 Harness Adaptor 52-2946 SA

2 Electric Power Transfer EL-CEPT SU 087100

1 Card Reader By Security Supplier

2 ElectroLynx Harness QC-C**** x Length Required MK 087100

2 ElectroLynx Harness QC-C1500P MK 087100

1 Power Supply BPS (Size & Type as

Required)

SU 087100

1 Wiring Diagram Elevation and Point to

• Access by valid credential presentation releasing the exit trim lever at the active leaf for a pre-determined time limit and then relocking.

• Egress always free for immediate manual exit. Request-to-Exit sensor allows exit without alarm condition.

• Exit Device Trim is fail safe and will remain secured in event of power loss or remote signal. Key override at the active leaf cylinder for emergency access.

Set: HW-SH-8

Doors: 9A, 9C required)

US26D MK 087100

Fire Rated SVR Exit Device

(LBR, EO,RX, ELR)

12 55 56 NB8710 EO US32D SA 087100

Fire Rated SVR Exit Device

(LBR, STRM, RX, ELR)

12 55 56 70 NB8706 ETL US32D SA 087100

1 SFIC Core EA-100108 Medeco XT SFIC MC 087100

2 Auto Operator w/actuators

SW100 Series Auto Operator and required actuators

(Supplied and installed by

Section 087113 supplier

BM

2 Kick Plate K1050 10" X 2" LDW BEV CSK US32D RO 087100

08 71 00-30

2 Wall Stop 403 (or) 441CU (As

Required)

US26D RO 087100

1 Gasketing S88D (Head & Jambs) PE 087100

1 Astragal S771C x Door Height PE 087100

2 Harness Adaptor 52-2946 SA

2 Electric Power Transfer EL-CEPT SU 087100

1 Card Reader By Security Supplier

2 ElectroLynx Harness QC-C**** x Length Required MK 087100

2 ElectroLynx Harness QC-C1500P MK 087100

1 Power Supply BPS (Size & Type as

Required)

SU 087100

1 Wiring Diagram Elevation and Point to

• Access by valid credential presentation retracting the exit latch at both doors and activating the auto operator actuator switch on the secure side of the opening for a pre-determined time limit and then relocking.

• Egress always free for immediate manual exit. Request-to-Exit sensor allows exit without alarm condition.

• Auto Operator Egress from the unsecure side, pressing the auto operator actuator switch on the unsecure side will momentarily retract the exit latches at both doors and activate the auto operators to open both doors to allow for auto operator egress.

• Exit Devices are fail safe and will remain secured in event of power loss or remote signal. Key override at the active leaf cylinder for emergency access.

Set: HW-SH-9

Doors: A-B020b required)

US26D MK 087100

Self Latching Flush Bolt

Set 2845 / 2945 (As Required) US26D…