583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part5.pdf
PDF 2 MB Posted
- Solicitation number
- 36C25021B0036
About this file
This solicitation is for renovation services at the Richard L. Roudebush VA Medical Facility in Indianapolis, Indiana. The scope of work includes relocating nuclear medicine services to centralized locations on site. The solicitation number is 36C25021B0036. The agency issuing this opportunity is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. Products and services required include architectural, engineering, and construction services to renovate existing spaces. The total estimated value is between $5 million and $10 million. The response due date is March 15, 2021, with an anticipated award date of April 15, 2021. This is a 100% service-disabled veteran-owned small business set aside.
View the file
Other files
Show 40 more
Latest 50 of 66 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL ABBREVIATIONS
SECTION REFERENCE
DRAWING NUMBER
SHEET LOCATION
DRAWING NUMBER
SHEET
LOCATION
DETAIL REFERENCE
OBJECT
REFERENCED
OBJECT
REFERENCED
X
XXXX
X
XXXX
SCALE: ??
VIEW TITLE
N
NORTH ARROW
EXTENT OF REVISION
REVISION SET
PROJECT BOUNDARY
BEYOND PROJECT BOUNDARY, NIC
DETAIL/DRAWING SCALE
TITLE OF DETAIL/DRAWING
DETAIL/DRAWING NUMBER
SHEET NUMBER
A/C AIR CONDITION
A/E ARCHITECT/ENGINEER
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJACENT, ADJOINING, OR ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINUM
AMP AMPERE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
ARCH ARCHITECT
ASB ASBESTOS
ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION
ASSN ASSOCIATION
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWI ARCHITECTURAL WOODWORKING INSTITUTE
AWS AMERICAN WELDING SOCIETY
BLDG BUILDING
C CELSIUS CHANNEL OR CHANNEL CELSIUS
C TO C CENTER TO CENTER
CAB CABINET
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CL CENTER LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CARBON MONOXIDE, CLEANOUT
CO₂ CARBON DIOXIDE
COMM COMMUNICATION
COMP COMPONENT
COORD COORDINATE
CORR CORRIDOR
CTR CENTER
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
DEMO DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DIM DIMENSION
DN DOWN
E EAST
ELEC ELECTRIC
ELEV ELEVATOR
EPA ENVIRONMENTAL PROTECTION AGENCY
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE
ETC AND SO FORTH OR ET CETERA
EXT EXTERIOR, EXTERNAL, OR EXTINGUISHER
F FAHRENHEIT OR FEMALE
FEC FIRE EXTINGUISHER CABINET
FF&E FURNITURE, FIXTURE, AND EQUIPMENT
FLEX FLEXIBLE
FLR FLOOR
FO FINISHED OPENING
FP FIRE PROTECTION OR FIREPROOF
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FIRE RATING, FIRE RESISTANT, OR FRAME
FT FEET OR FOOT
FURN FURNISH OR FURNITURE
GA GAGE OR GYPSUM ASSOCIATION
GAL GALLON
GC GENERAL CONTRACTOR
GD GUARD
HAZ MAT HAZARDOUS MATERIALS
HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HM HECTOMETER OR HOLLOW METAL
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HSKPG HOUSEKEEPING
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE DIAMETER
ID NO IDENTIFICATION NUMBER
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INTL INTERNATIONAL
JAN JANITOR
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LIN LINEAR
MAX MAXIMUM
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MIC MICROPHONE
MIN MINIMUM MINUTE OR MINUTE MINIMUM
MISC MISCELLANEOUS
mm MILLIMETER
MO MASONRY OPENING OR MOTOR OPERATED
MTL METAL
N NORTH
NA NOT APPLICABLE
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NUMBER
O OXYGEN
OC ON CENTER
OZ OUNCE
PCF POUNDS PER CUBIC FOOT
PLAM PLASTIC LAMINATE
PNEU PNEUMATIC
PREFIN PREFINISH
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PNEUMATIC TUBE, OR PRESSURE TREATED
PVC POLYVINYL CHLORIDE (PLASTIC)
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
RB RESILIENT BASE OR RUBBER BASE
RCP REFLECTED CEILING PLAN
REC RECESSED
RESIL RESILIENT
RFI REQUEST FOR INFORMATION
RM ROOM
RO ROUGH OPENING
RPM REVOLUTIONS PER MINUTE
GENERAL CONSTRUCTION NOTES
1. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING REVIT®
SOFTWARE IN A MICROSOFT WINDOWS ENVIRONMENT. A BUILDING INFORMATION
MODEL (BIM) HAS BEEN DEVELOPED FOR DESIGN COMMUNICATION. THE MODEL
DOES NOT CONTAIN COMPLETE INFORMATION FOR USE IN COST ESTIMATING,
SYSTEMS PERFORMANCE, COORDINATION, SCHEDULING, OR FACILITIES
MANAGEMENT.
2. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING THE
CONSTRUCTION SPECIFICATIONS INSTITUTE'S UNIFORM DRAWING SYSTEM AND THE
NATIONAL CAD STANDARD AS GUIDES.
3. DISCREPANCIES IN THE CONTRACT DOCUMENTS SHALL BE IMMEDIATELY BROUGHT
TO THE ATTENTION OF THE ARCHITECT AND OWNER’S REPRESENTATIVE/COR.
CONTRACTOR SHALL PROVIDE THE HIGHER GRADE OF QUALITY AND/OR GREATER
QUANTITY OF WORK WHEN BIDDING IF A CLARIFICATION CAN NOT BE OBTAINED BY
THE BID DUE DATE.
4. CONTRACTOR IS RESPONSIBLE FOR COORDINATING SCOPE OF WORK WITH
OWNER’S REPRESENTATIVE/COR AND VARIOUS FACILITY PERSONNEL INVOLVED
WITH UTILITY SHUT DOWN, INFECTION CONTROLS, OCCUPANT/EMPLOYEE SAFETY,
ACCESS CONTROL, ETC.
5. ANY INDICATION OF PROJECT LIMITS OR BOUNDARY OF DEMARCATION ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR, THE FULL SCOPE OF THE PROJECT
LIMIT OF BOUNDARY REQUIRES COORDINATION WITH THE DESIGN SCOPE OF WORK
AND ACCESS TO EXISTING UTILITIES FOR TIE IN.
6. DRAWINGS ARE PREPARED FROM FIELD VERIFICATION, EXISTING FACILITY DRAWING
BASE FILES, AND USING DIMENSIONS, CONFIGURATIONS AND DETAILS OF SPECIFIC
MANUFACTURERS AS A BASIS OF DESIGN. CONTRACTOR IS RESPONSIBLE FOR
VERIFICATION OF ACTUAL DIMENSIONS, THE COORDINATION OF THE DETAILS WITH
THE PRODUCTS WHICH ARE PROVIDED PER THE SCOPE OF THE SPECIFICATIONS
AND THE SURROUNDING CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS,
ROUGH-IN DIMENSIONS, CONNECTIONS, AND OVERALL INSTALLATION
REQUIREMENTS.
7. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE ENTIRE SCOPE OF
WORK OUTLINED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE
FOR THE COORDINATION OF ALL SUB-CONTRACTORS AND THE SCOPE OF WORK
THEY PROVIDE. SUB-CONTRACTORS ARE RESPONSIBLE FOR THEIR FULL SCOPE OF
WORK WITHIN THE CONTRACT DOCUMENTS, TRADES ARE NOT SEGMENTED TO ONLY
CERTAIN SHEETS AND SPECIFICATIONS, CROSS COORDINATION IS REQUIRED.
8. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR
UNDERSTANDING INFORMATION OUTLINED IN THE SPECIFICATIONS, KEY NOTES,
GENERAL NOTES, LEGEND, CODES, ETC., PROVIDED IN THE CONTRACT DOCUMENTS.
9. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR PROVIDING
AND MAINTAINING SMOKE/FIRE RATINGS OF NEW CONSTRUCTION AND EXISTING
CONSTRUCTION AS INDICATED ON DRAWINGS. THIS INCLUDES PATCHING
PENETRATIONS IN SHAFTS, WALLS, SLABS AND ROOF. ONLY U.L. APPROVED
METHODS, MATERIALS AND INSTALLATION ARE ACCEPTABLE.
10. MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS SHOW
INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL
CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL MECHANICAL, PLUMBING
AND ELECTRICAL EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL AND
STRUCTURAL DETAILING OF SHAFTS, CHASES, CEILING CONSTRUCTION, ETC.
11. CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IDENTIFIED AND NOT
IDENTIFIED IN THE CONTRACT DOCUMENTS WITH THE EXISTING AND NEW
CONSTRUCTION ELEMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION
BETWEEN THE CONTRACT DOCUMENTS, INSTALLED AND UNINSTALLED
CONSTRUCTION BEFORE THE ORDERING OF MATERIALS AND EQUIPMENT. NOTIFY
ARCHITECT AND OWNER’S REPRESENTATIVE/COR OF ANY DISCREPANCIES OR
MISSING DIMENSIONS.
12. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR GENERAL
ORIENTATION AND CONTEXT ONLY.
13. THE TERM "ALIGN" MEANS TO INSTALL DIFFERENT/SIMILAR COMPONENTS OF
CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.
14. ALL DIMENSIONS INDICATED ARE TO FACE OF EXISTING MEMBERS, FACE OF NEW
STRUCTURAL MEMBERS, FACE OF NEW MASONRY, FACE OF NEW STUDS OR COLUMN
GRID LINES UNLESS NOTED OTHERWISE.
15. FLOOR ELEVATION 100’-0" IS EQUAL TO THE FINISH FLOOR SLAB OF THE EXISTING
SLAB FLOOR CONSTRUCTION UNLESS OTHERWISE NOTED.
16. ROUGH OPENINGS SHALL ALLOW FOR SHIM SPACE.
17. CONTRACTOR TO PROVIDE WORK WHERE DETAILS AND NOTES ARE IDENTIFIED AS
“TYPICAL” OR “SIMILAR” EACH INSTANCE THAT IS THE SAME IN NATURE TO THE
DETAIL, AREA, OR ITEM REFERENCED.
18. PROVIDED WORK SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF DELIVERY, MOUNTING,
INSTALLATION, NECESSARY BLOCKING AND ROUGH-IN.
19. INSTALLED WORK IS THE CONTRACTOR INSTALLING OWNER FURNISHED MATERIALS
AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF MATERIAL
DELIVERY, MOUNTING, INSTALLATION AND ROUGH IN.
20. FURNISHED WORK IS THE CONTRACTOR FURNISHING THE MATERIALS AND
EQUIPMENT TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF
DELIVERY AND ROUGH-IN.
21. ALL PROVIDED WORK SHALL BE WITH NEW MATERIALS UNLESS SPECIFICALLY
CALLED OUT AS SALVAGED OR RELOCATED WITHIN THE CONTRACT DOCUMENTS.
22. ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE
FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND
HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.
23. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL
UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO
UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE
OWNER.
24. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING AND SHORING
REQUIRED DURING CONSTRUCTION.
25. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ADJACENT
CONSTRUCTION, FINISHES, EQUIPMENT, AND TRAVEL ROUTE TO AND FROM THE
CONSTRUCTION SITE. ANY DAMAGE OR UNACCEPTABLE WEAR BY THE
CONSTRUCTION TEAM SHALL BE REPAIRED/REPLACED BY THE CONTRACTOR AT NO
COST TO THE OWNER.
26. IN THE CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT
DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER
QUALITY OF WORK, AS DETERMINED BY THE COR , SHALL BE PROVIDED.
27. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND COORDINATING HARDWARE,
ACCESS CONTROL AND AUTOMATIC OPERATORS ARE PROVIDED WITH COMPLETE
AND COMPATIBLE SYSTEMS REQUIRED FOR THEIR OPERATION. REFER TO DOOR
HARDWARE SCHEDULE, HARDWARE SPECIFICATIONS, AUTOMATIC OPERATOR
SPECIFICATIONS, ACCESS CONTROL SPECIFICATIONS AND ELECTRICAL DRAWINGS.
28. CONTRACTOR SHALL INSTALL SOLID BLOCKING WITHIN PARTITIONS BEHIND ANY
TOILET ACCESSORIES OR CABINETRY. VERIFICATION TO TAKE PLACE PRIOR TO
INSTALLATION OF GYPSUM WALLBOARD.
ARCHITECTURAL SYMBOLS
X
X
XXXX
SHEET LOCATION
VIEW NUMBER
X X
X
SHEET LOCATION
VIEW NUMBER
XXXX
BUILDING SECTION REFERENCE
DRAWING NUMBER
SHEET LOCATION
BUILDING X
XXXX
X
XXXX
ELEVATION REFERENCES
NEW WALL
WALL TO BE
REMOVED
S3A.G
INDICATES STRUCTURAL MATERIAL
INDICATES NOMINAL SIZE
INDICATES STRUCTURE AND FINISH HEIGHTS
INDICATES QUALIFER
EXISTING WALL TO
REMAIN
TEMPORARY IC
BARRIER WALL
CONSTRUCTION
ROOM
ROOM TAG
NEW DOOR
EXISTING DOOR
DEMOLISHED DOOR
SF SQUARE FOOT (FEET)
SIM SIMILAR
S SOUTH
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SPLY SUPPLY
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
STL STEEL
TA TOILET ACCESSORY
T&G TONGUE AND GROOVE
TECH TECHNICAL
TEMP TEMPERATURE OR TEMPORARY
THRES THRESHOLD
THRU THROUGH
TO TOP OF ___
TV TELEVISION
TYP TYPICAL
U HEAT TRANSFER COEFFICIENT
UL UNDERWRITERS LABORATORIES
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VAR VARIES
VIF VERIFY IN FIELD
VOL VOLUME
VOLT VOLTAGE
W/ WITH
W/O WITHOUT
WD WOOD
YD YARD
REVISION TO PLAN CALLOUT
WALLS
DOOR TAG
KEY NOTE TAGS
WALL TAG : REFER TO WALL LEGEND FOR MORE INFORMATION
DOORS
PT-1
A
T
101 EQUIPMENT/FURNITURE TAG
FINISH INDICATION
FRAME / WINDOW
GLAZING1
1 PLAN NOTE
1 DEMOLITION NOTE
ALTERNATE/BID DEDUCT ITEM
KEY NOTE SYMBOLS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C
U s e rs \d c h ri s te n s e n \D o c u m e n ts \1
.1
.0
N u c M e d v d c h ri s te n s e n M
N F
X
.r v t
/2
/2
:5
:0
A
M
AE001
ARCHITECTURAL SYMBOLS AND
ABBREVIATIONSGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 JLG ELB
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
WALL TYPES LEGEND AND GENERAL NOTES
A. ALL WALLS WILL BE WALL TYPS S3C.G UNLESS OTHERWISE NOTED.
B. ALL WALL TYPE INDICATORS REFER TO THIS SHEET UNLESS OTHERWISE
NOTED.
C. REFER TO DIMENSION PLANS FOR PARTITION TYPE LOCATIONS.
PARTITIONS ARE DISTINGUISHED ON PLANS BY SYMBOL DESIGNATION
GRAPHIC DESIGNATION, OR A COMBINATION OF BOTH. NOT ALL
PARTITIONS ON THIS SHEET MAY BE USED. REFER TO PARTITION TYPE
SCHEDULE ON THIS SHEET FOR PARTITIONS USED ON THIS PROJECT.
D. ALL DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD, OR TO FACE
OF EXISTING CONSTRUCTION. REFER TO PARTITION TYPES FOR PARTITION
WIDTH DIMENSIONS.
E. ALL WALL STUDS TO BE 16" O.C. UNLESS OTHERWISE NOTED.
F. REFER TO SPECIFICATIONS AND TO TABLE ON THIS SHEET FOR MINIMUM
STUD GAUGE, MAXIMUM SPACING AND ALLOWABLE LIMITING HEIGHT
DEFLECTION CRITERIA FOR GYPSUM BOARD ASSEMBLIES AND REQUIRED
FINISHES. FOR WALLS WHERE STUDS ARE ATTACHED TO STRUCTURE
ABOVE, PROVIDE CROSS BRACING AS NECESSARY MEETING THE CRITERIA
INDICATED TO ACCOMMODATE THE SPECIFIED DEFLECTION CRITERIA OF
THE WALL.
G. ALL INTERIOR NON-BEARING STUDS TO BE DESIGNED FOR A DEFLECTION
EQUAL TO BUT NOT GREATER THAN L/240, UNLESS FULL HEIGHT FINISH IS
DETERMINED TO BE FRAGILE OR BRITTLE, THEN DEFLECTION TO BE L/360.
EXAMPLES OF FRAGILE FINISHES WOULD INCLUDE BUT NOT LIMITED TO
ANY TYPE OF WALL TILE, PLASTER OR PLASTER SKIM COAT.
H. ALTHOUGH WALL STUD SIZES ARE LISTED ON PLANS AND WALL TYPES, IN
AREAS WHERE STUDS ARE TO EXTEND TO STRUCTURE ABOVE OR HIGH
AREAS, CONTRACTOR TO VERIFY SIZE INDICATED IS ADEQUATE FOR
HEIGHT LISTED. PROVIDE ADEQUATE SIZE STEEL STUD FRAMING AND
NOTIFY ARCHITECT OF ANY DISCREPANCY PRIOR TO FABRICATION OR
INSTALLATION.
I. KING STUDS AT DOOR FRAMES AND WINDOW OPENINGS TO BE 18 GA.
UNLESS OTHERWISE NOTED.
J. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD FOR ALL OTHER WALL
CONSTRUCTION, UNLESS OTHERWISE NOTED.
K. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD IN BULKHEAD CONSTRUCTION.
L. REFER TO LIFE SAFETY PLANS FOR LOCATIONS AND RATINGS OF SMOKE
AND FIRE RATED PARTITIONS. REFERENCE TEST NUMBERS APPLY ONLY TO
PARTITIONS INDICATED TO BE RATED.
M. FIRE RATING TEST NUMBERS ARE FOR UNDERWRITER'S LABORATORIES
(UL) ASSEMBLIES UNLESS OTHERWISE NOTED.
N. FIRE RESISTANT RATED PARTITIONS SHALL EXTEND TO THE INSIDE FACE
OF EXTERIOR SHEATHING, INCLUDING EXTENSIONS THROUGH SOFFITS.
O. SEAL ALL OPENINGS, GAPS, PENETRATIONS, AND JOINTS IN PARTITIONS
TYPES AS FOLLOWS:
a. FIRE RATED PARTITIONS: SEAL IN ACCORDANCE WITH THE
REQUIREMENTS SPECIFIED FOR THROUGH PENETRATION
FIRESTOP SYSTEMS AND FIRE RESISTIVE JOINT SYSTEMS.
b. SMOKE TIGHT PARTITIONS: SEAL COMPLETELY WITH
ELASTOMERIC SEALANT. FOR THE LOCATION AND EXTENT OF
PARTITIONS, DESIGNATED AS "SMOKE TIGHT", REFER TO THE LIFE
SAFETY DRAWINGS.
c. ALL OTHER LOCATIONS: SEAL AS INDICATED AND REQUIRED
ELSEWHERE BY THE CONTRACT DOCUMENTS.
P. INSULATION HEAD CONDITIONS AT FLOOR / ROOF DECK:
a. FIRE RESISTANT RATED PARTITIONS SHALL USE MINERAL WOOL
INSULATION AND APPROPRIATE FIRE RATED SEALANT.
b. NON-RATED PARTITIONS REQUIRING SOUND ATTENUATION SHALL
USE SOUND ATTENUATION BATTS (SAB).
Q. PROVIDE STENCILED IDENTIFICATION FOR RATED PARTITIONS.
R. STC RATING APPLIES WHERE PARTION TAG QUALIFIER INDICATES WITH AN
"i". PROVIDE SOUND ATTENUATION BATTS OF THICKNESS INDICATED ON
SCHEDULE WHERE INDICATED BY QUALIFIER.
S. FOR PARTITIONS WITH STC RATINGS INDICATED SOUND ATTENUATION
BATTS TO EXTEND FULL HEIGHT OF PARTITION UNLESS OTHERWISE
NOTED. FLOOR TRACK TO BE SET IN A CONTINUOUS BED OF SEALANT.
T. WHERE PARTITION TYPE INDICATES SOUND ACOUSTICAL BAT, WITH FINISH
BOARD GOING TO DECK ON ONE SIDE ONLY, PROVIDE VAPOR BARRIER TO
SECURE INSULATION IN PLACE.
U. REFER TO DIMENSIONED PLANS FOR REFERENCE SYMBOLS INDICATING
THE EXTENT OF RADIATION PROTECTION.
V. WHERE RADIATION PROTECTION SCHEDULE INDICATES LEAD LINED
GYPSUM BOARD AT FIRE RESISTANCE RATED ASSEMBLIES, INSTALL PER
UL-U430 (60 MINUTES & 120 MINUTES).
W. PROVIDE 5/8" MOISTURE/MOLD RESISTANT GYPSUM BOARD IN SOILED
ROOMS, BATHROOMS, TOILET ROOMS, ON WALLS BEHIND PLUMBING
FIXTURES, AND IN ALL WET LOCATIONS EXCEPT IN SHOWER AREA.
X. PROVIDE 5/8" CEMENTITIOUS BACKER BOARD BEHIND CERAMIC WALL TILE &
SHOWER AREA. COORDINATE LOCATIONS WITH FINISH WALL PLANS.
Y. PROVIDE CORNER AND END WALL FRAMING AS DETAILED ON AE003.
Z. ALL LEAD LINED PARTITIONS ARE TO BE CONSTRUCTED WITH 18 GA. METAL
STUDS.
WALL TAG LEGEND X#X.#
INDICATES STRUCTURAL MATERIAL
CH = SHAFT WALL
F = FURRING
S = STEEL
M = MASONRY
W = WOOD
INDICATES NOMINAL SIZE
INDICATES STRUCTURE AND
FINISH HEIGHTS
QUALIFIER'S (X-X-X)
G GYPSUM BOARD FINISH
1SB 1 HR RATED SMOKE BARRIER
2SB 2 HR RATED SMOKE BARRIER
1F 1 HR FIRE RATED
2F 2 HR FIRE RATED
i SOUND INSULATION t THERMAL INSULATION
B BULLET RESISTANT
L LEAD LINED
M MESH (STEEL SECURITY MESH)
MR MOIST/MOLD RESISTANT GYPSUM
SP SMOKE PARTITION
TB TILE BACKER CEMENT BOARD
A = STRUCTURE TO DECK, FINISH TO DECK
B = STRUCTURE TO DECK, FINISH ONE SIDE TO DECK
C = STRUCTURE TO DECK, FINISH TO ABOVE CEILING
D = STRUCTURE TO ABOVE CEILING, FINISH TO ABOVE CEILING
P = PARTIAL HEIGHT WALL
U = STRUCTURE TO UNDERSIDE OF CELING, FINISH TO UNDERSIDE OF CEILING
*SEE WALL TYPES FOR PROJECT SPECIFIC CONSTRUCTION
CH
2 1/2" 4" 6"
F 7/8
1 1/2" 2 1/2" 3 5/8"
4" 6" 8" 12"
S
2 1/2" 3 5/8"
4" 6" 8" 12"
M
2 5/8" 3 5/8" 5 5/8" 7 5/8" 11 5/8"
W
3/4"
3 1/2"
5 1/2" 7 1/4" 11 1/4"
" 1 HR FIRE/SMOKE
10'-0" MAX 10'-0" MAX
A. LETTERED STENCILS SHALL BE APPLIED TO EACH SIDE OF RATED PARTITIONS
AT 10'-0" INTERVALS; BUT NO LESS THAN ONCE PER PARTITION LENGTH.
B. USE THE FOLLOWING LANGUAGE FOR STENCILS:
"1 HR FIRE/SMOKE" "1 HR FIRE"
"2 HR FIRE/SMOKE" "2 HR FIRE"
"LIMIT TRANSFER OF SMOKE"
PERMANENT RED PAINT
LETTERING, TYP.
CEILING LINE
STENCILING NOTES
SSMA NON-COMPOSITE STUDS
NOTE:
• TYPICAL LIMITING HEIGHTS-INTERIOR PARTITIONS, L/240 (5 PSF), WITH 5/8"GYPSUM BOARD EACH SIDE.
• PROVIDE DIAGONAL STUD BRACING AT ALL NON FULL HEIGHT INTERIOR PARTITIONS STAGGERED AT 48" O.C. TO DECK ABOVE. PROVIDE
STUD ATTACHMENT TO DECK W/ MIN. SPAN OF 2 DECK FLUTES. BRACING TO BE THE SAME SIZE AND GAUGE AS VERTICAL STUDS.
25 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 6'-11"1-5/8"
24" L/240 6'-0"162S125-18
16" L/240 9'-6"2-1/2"
24" L/240 8'-4"250S125-18
16" L/240 12'-5"3-5/8"
24" L/240 10'-10"362S125-18
16" L/240 13'-9"4"
24" L/240 12'-0"400S125-18
22 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 8'-1"1-5/8"
24" L/240 7'-1"162S125-27
16" L/240 11'-2"2-1/2"
24" L/240 9'-9"250S125-27
16" L/240 14'-6"3-5/8"
24" L/240 12'-8"362S125-27
16" L/240 16'-1"4"
24" L/240 14'-0"400S125-27
20 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 8'-4"1-5/8"
24" L/240 7'-3"162S125-30
16" L/240 11'-7"2-1/2"
24" L/240 10'-1"250S125-30
16" L/240 15'-0"3-5/8"
24" L/240 13'-1"362S125-30
16" L/240 16'-8"4"
24" L/240 14'-7"400S125-30
16" L/240 22'-4"6"
24" L/240 19'-6"600S125-27
16" L/240 23'-1"6"
24" L/240 20'-2"600S125-30
18 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 13'-0"2-1/2"
24" L/240 11'-5"250S125-43
16" L/240 17'-5"3-5/8"
24" L/240 15'-3"362S125-43
16" L/240 18'-10"4"
24" L/240 16'-5"400S125-43
16" L/240 26'-1"6"
24" L/240 22'-10"600S125-43
HIGH PRIORITY PARTITION
GYPSUM BOARD CONTINUES THROUGH
STUD CAVITY OF LOWER WALL
LOWER PRIORITY PARTITION
HIGH PRIORITY CEILING /
ROOF ASSEMBLY
GYPSUM BOARD CONTINUES PAST
TOP OF LOWER WALL
LOWER PRIORITY PARTITION
RATING
3 HOUR ASSEMBLY
2 HOUR ASSEMBLY
1 HOUR ASSEMBLY
SMOKE-RATED ASSEMBLY
NON-RATED ASSEMBLY
PRIORITY
NOTE: LOWER NUMBER, HIGHER PRIORITY
SECTIONPLAN
TOP OF METAL DECK OR CONCRETE
FIRE CAULKING AS REQUIRED BY UL# HWS0001
(BY FRAMING CONTRACTOR)
PACK FLUTES OF DECK WITH FIRE SAFING AS
REQUIRED PER UL# HWS0001
Z-CLIPS 2" WIDTH
BOTTOM OF METAL DECK
LIGHT GAUGE FRAMING DEFLECTION TRAK,
CONFORMING TO UL# HW-D-0060
5/8" TYPE X GYP. BD. EACH SIDE OF STUD
SCRIBED TO DECK UL# U465
METAL STUD
PARALLEL NOTE:
NON-RATED CONSTRUCTION SIMILAR W/O
FIRE SAFING & SCRIBING BYP. BD. TO DECK
6"
TOP OF METAL DECK OR CONCRETE
FIRE CAULKING AS REQUIRED BY UL# HWS0001
(BY FRAMING CONTRACTOR)
PACK FLUTES OF DECK WITH FIRE SAFING AS
REQUIRED PER UL# HWS0001
Z-CLIPS 2" WIDTH
BOTTOM OF METAL DECK
LIGHT GAUGE FRAMING DEFLECTION TRAK,
CONFORMING TO UL# HW-D-0060
5/8" TYPE X GYP. BD. EACH SIDE OF STUD
SCRIBED TO DECK UL# U465
METAL STUD
PERPENDICULAR NOTE:
NON-RATED CONSTRUCTION SIMILAR W/O
FIRE SAFING & SCRIBING BYP. BD. TO DECK
3 HR FIRE RATED
2 HR FIRE RATED
1 HR FIRE RATED
1 HR SMOKE BARRIER
SMOKE PARTITION
2 HR SMOKE BARRIER
3 HR SMOKE BARRIER
WALL RATING LEGEND
WALL TYPES
S2A.G 2 1/2"
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
3 3/4" NA NA NA
COMMENTS
S3A.G 3 5/8" 4 7/8"
NA
NANANANA
S6A.G 6" 7 1/4" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
DEEP LEG SLIP TRACK AT DECK
HOLD GYPSUM BACK FROM DECK FOR
DEFLECTION
S2B.G 2 1/2"
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
3 3/4" NA NA NA
COMMENTS
S3B.G 3 5/8" 4 7/8"
NA
NA34NANA
S6B.G 6" 7 1/4" NA37NANA
3 5/8" 4 7/8" SMOKE PARTITIONNANANA
S6B.SP 6" 7 1/4" NANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
DEEP LEG SLIP TRACK AT DECK
HOLD GYPSUM BACK FROM DECK FOR
DEFLECTION
SMOKE PARTITION
6"
S3B.SP
S2C.G 2 1/2"
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
3 3/4" NA NA NA
COMMENTS
S3C.G 3 5/8" 4 7/8"
NA
NANANANA
S6C.G 6" 7 1/4" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
6"
S2D.G 2 1/2"
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
3 3/4" NA NA NA
COMMENTS
S3D.G 3 5/8" 4 7/8"
NA
NANANANA
S6D.G 6" 7 1/4" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
6"
INSULATION PRESENT WITH QUALIFER (i OR t)
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
INSULATION PRESENT WITH QUALIFER (i OR t)
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
INSULATION PRESENT WITH QUALIFER (i OR t)
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
INSULATION PRESENT WITH QUALIFER (i OR t)
F2D.G 2 1/2"
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
3 1/8" NA NA NA
COMMENTS
F3D.G 3 5/8" 4 1/4"
NA
NANANANA
F6D.G 6" 6 5/8" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
STRUCTURAL DIMENSION
5/8"
FINISH DIMENSION
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
6"
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
INSULATION PRESENT WITH QUALIFER (i OR t)
EXISTING WALL / COLUMN, VIF.
F0D.G 7/8" 1 1/2" NA NA NA
F1D.G 1 1/2" 2 1/8"
HAT CHANNEL @ 24" O.C.
NANANA HAT CHANNEL @ 24" O.C.
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
COMMENTS
S3A.1F 3 5/8" 4 7/8" NA40U4651 HR.
S6A.1F 6" 7 1/4" NA40U4651 HR.
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
DEEP LEG SLIP TRACK AT DECK
HOLD GYPSUM BACK FROM DECK FOR
DEFLECTION
FILL FLUTES OF DECK WITH FIRE SAFING
AT FIRE RATED WALLS
INSULATION PRESENT WITH QUALIFER (i OR t)
S3A.1SB 3 5/8" 4 7/8" NA40U4651 HR.
S6A.1SB 6" 7 1/4" NA40U4651 HR.
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
COMMENTS
S3A.GiL 3 5/8" 4 7/8" SEE PHYSICIST REPORTNANANA
6" 7 1/4" NANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
LEAD LINED 5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
LEAD FLASHING
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
DEEP LEG SLIP TRACK AT DECK
HOLD GYPSUM BACK FROM DECK FOR
DEFLECTION
INSULATION PRESENT WITH QUALIFER (i OR t)
SEE PHYSICIST REPORT
5/8" TYPE X GYP BD
S6A.GiL
STEEL STUDS @ 16" O.C.
RADIATION SIDE NOTE:
SEE PHYSICIST REPORT FOR LEAD
LINED WALL REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C
U s e rs \d c h ri s te n s e n \D o c u m e n ts \1
.1
.0
N u c M e d v d c h ri s te n s e n M
N F
X
.r v t
/2
/2
:5
:1
A
M
AE002
ARCHITECTURAL WALL TYPES
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 JLG PAE, II
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1 1/2" = 1'-0"AE002
1 RATED WALL PRIORITY
SCALE: 1 1/2" = 1'-0"AE002
2 DEFLECTION TRACK
WALL TYPE SCHEDULE
WALL TYPES USED IN THIS PROJECT
F0D.G
F1D.G
F3D.G
F3D.Gi
F6A.Gi
F6A.GiL
F6D.G
F6D.Gi
S3A.1F
S3A.G
S3A.Gi
S3B.SP
S3D.Gi
S6A.Gi
S6A.GiL
ROOM STC SCHEDULE - FGI REQUIREMENTS, AS APPLICABLE
ROOM NUMBER ROOM NAME Remarks STC BOD STC PRV.
ROOM
TYPE/OCC.
A-B01 SOILED UTILITY N/A 40 N/A
A-B002 DOSE ADMIN. ROOM 50 ROOM - 35 CORRIDOR 53 DOSING
A-B003 DOSE ADMIN. ROOM 50 ROOM - 35 CORRIDOR 53 DOSING
A-B004 PET / CT 2 50 ROOM - 35 CORRIDOR 44 SCANNING
A-B004a PET EQUIPMENT ROOM 50 ROOM - 35 CORRIDOR 53 STAFF
A-B005 COMBINED PET CONTROL ROOM 50 ROOM - 35 CORRIDOR 53 STAFF
A-B006 PET / CT 1 50 ROOM - 35 CORRIDOR 53 SCANNIG
A-B006a PET EQUIPMENT ROOM 50 ROOM - 35 CORRIDOR 53 STAFF
A-B007 HOT LAB 50 ROOM - 35 CORRIDOR 53 STAFF
A-B007a RADIOACTIVE WASTE STORAGE N/A 40 N/A
A-B008 DOSE ADMIN. ROOM EXISTING 50 ROOM - 35 CORRIDOR 50 DOSING
A-B009 DOSE ADMIN. ROOM EXISTING 50 ROOM - 35 CORRIDOR 50 DOSING
A-B010 DOSE ADMIN. ROOM EXISTING 50 ROOM - 35 CORRIDOR 50 DOSING
A-B012 DOSE ADMIN. ROOM EXISTING 50 ROOM - 35 CORRIDOR 50 DOSING
A-B013 READING & CONSULTATION 50 ROOM - 35 CORRIDOR 40 CONSULT
A-B014 EQUIP CALIBRATION 35 CORRIDOR 40 N/A
A-B015 STAFF LOUNGE N/A 40 STAFF
A-B016 NM TOILET, PATIENT 45 CORRIDOR 45 TOILET ROOM
A-B017 NM TOILET, PATIENT 45 CORRIDOR 45 TOILET ROOM
A-B018 SUPERVISOR OFFICE 35 CORRIDOR 40 STAFF
A-B019 MSA / SCHEDULING 35 CORRIDOR 40 STAFF
A-B020 OUTPATIENT WAITING 35 CORRIDOR 40 PUBLIC
A-B021 INPATIENT HOLDING NO DOOR N/A N/A PATIENT
A-B022 THYROID UPTAKE 50 ROOM - 35 CORRIDOR 40 PATIENT
A-B023 CARDIAC STRESS TESTING 50 ROOM - 35 CORRIDOR 40 PATIENT
A-B024 PATIENT INTERVIEW ROOM 50 ROOM - 35 CORRIDOR 50 CONSULT
A-B025 ELEC ROOM EXISTING N/A N/A N/A
A-B026 TOILET, STAFF 45 CORRIDOR 45 TOILET ROOM
A-B027 TOILET, STAFF 45 CORRIDOR 45 TOILET ROOM
A-B028 PET TOILET, PATIENT 45 CORRIDOR 45 TOILET ROOM
A-B029 NM CONTROL RM 50 ROOM - 35 CORRIDOR 53 STAFF
A-B029a NM SCAN 1 50 ROOM - 35 CORRIDOR 53 SCANNING
A-B029b NM SCAN 2 50 ROOM - 35 CORRIDOR 53 SCANNING
A-B030 DIGI ROD, MOBILE EQUIPMENT NOT ENCLOSED N/A N/A N/A
A-B031 CLEAN SUPPLY N/A 40 N/A
C-1 STAFF ENTRANCE CORRIDOR 35 CORRIDOR N/A N/A
C-2 NORTH CORRIDOR 35 CORRIDOR N/A N/A
C-3 EAST CORRIDOR 35 CORRIDOR N/A N/A
C-4 SOUTH CORRIDOR 35 CORRIDOR N/A N/A
C-5 WEST CORRIDOR 35 CORRIDOR N/A N/A
C-5A ALCOVE N/A N/A N/A
C-6 CORRIDOR 35 CORRIDOR N/A N/A
C-6a CLOSET N/A N/A N/A
CB-9 CORRIDOR 35 CORRIDOR N/A N/A
CB-10 AUDITORIUM CORRIDOR 35 CORRIDOR N/A N/A
DN
UP
N
KEY PLAN
PROJECT
LOCATION
A
457 3.5
B
C
D
E
F
2.58910
83 SF
LEAD CLERK
A-B023
632 SF
LOG SERVICE
A-B032
139 SF
TRAINING
A-B021
90 SF
ASST CH HIMS
A-B025
94 SF
CHIEF HIMS
A-B024
17 SF
ELEC.
A-B031
206 SF
SEC. / WAITING
A-B030
992 SF
CODING SECTION
A-B026
465 SF
DW-1 CODERS
A-B028
264 SF
STAFF WORK ROOM
A-B003B
100 SF
RECP.
A-B003A
364 SF
WAITING
A-B002
703 SF
CORRIDOR
CB-33
65 SF
TOILET
A-B014
66 SF
TOILET
A-B013
64 SF
PAT. SHOWER &
DEC. SHOWER
A-B012
134 SF
CONTROL
A-B011B
101 SF
READING
A-B011A
106 SF
CLEAN
A-B010
120 SF
UPTAKE
A-B009
83 SF
UPTAKE
A-B008
114 SF
UPTAKE
A-B007
114 SF
UPTAKE
A-B006
123 SF
UPTAKE
A-B005
104 SF
STORAGE
A-B017d
105 SF
SOILED UTILITY
A-B004
517 SF
ROI
A-B017b
91 SF
ROI
A-B017c
180 SF
QSV
A-B017a
120 SF
CHIEF OF SRD
A-B043
210 SF
QSV ICRA
A-B043b
219 SF
QSV
A-B018
124 SF
QSV
A-B018A
111 SF
QSV
A-B034
79 SF
QSV
A-B033C
587 SF
QSV OFFICE
A-B033A
471 SF
FISCAL
A-B036
82 SF
FISCAL
A-B037
84 SF
FISCAL OFFICE
A-B038
125 SF
FISCAL
A-B039
693 SF
CORRIDOR
CB-12
77 SF
OFFICE
A-B028
1050 SF
SCANNING &
TRANSCRIPTION
OFFICE
A-B029
126 SF
EQUIPMENT
A-B011D
454 SF
PET / CT
A-B011C
608 SF
CORRIDOR
CB-00
78 SF
OFFICE
A-B027
D.5
6264 SF
MECHANICAL
A-B148
1302 SF
MECHANICAL
A-B150
240 SF
R.O. EQUIPMENT
A-B151 344 SF
ENG. INTERIOR
DESIGN STORAGE
ROOM
C-B055
143 SF
EMS STORAGE
A-B159
64 SF
TELE. ROOM
B-B051
111213
2092 SF
AUDITORIUM
B-B066
1779 SF
OFFICE
B-B040
153 SF
QCIS
B-B039
234 SF
TEAM ROOM
B-B038
76 SF
RISK MANAGER
B-B044
118 SF
CHIEF QUALITY
MANAGEMENT
B-B045
68 SF
INFECTION
CONTROL MANAGER
B-B046
84 SF
NOURISHMENT
B-B047
152 SF
CHEIF LOG.
B-B042
270 SF
ASSISTANT LOG
B-B041
105 SF
PATIENT SAFETY
MANAGER
B-B043
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C
U s e rs \d c h ri s te n s e n \D o c u m e n ts \1
.1
.0
N u c M e d v d c h ri s te n s e n M
N F
X
.r v t
/2
/2
:5
:4
A
M
AD100
EXISTING LOWER LEVEL FLOOR
PLANGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 JLG DMC
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"AD100
1 EXISTING LOWER LEVEL PLAN
N
DN
UP
DEMOLITION GENERAL NOTES
A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND
REPAIR NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION
SHALL BE PROVIDED. CONTRACTOR SHALL REMOVE EXISTING
IMPROVEMENTS WHETHER OR NOT SPECIFICALLY INDICATED ON THE
DRAWINGS TO FACILITATE THE COMPLETION OF ALL REQUIRED WORK.
CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES AND
ITEMS REQUIRED TO BE REMOVED.
B. REFER TO ARCHITECTURAL SYMBOLS ON SHEET AE001 FOR DEMOLITION
SYSTEMS AND DRAWING NOMENCLATURE.
C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN
UNLESS OTHERWISE NOTED.
D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE
PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO
VERIFY NO UNSAFE OF UNSATISFACTORY CONDITIONS EXIST. SUCH
CONDITIONS SHALL BE RECTIFIED BEFORE WORK MAY PROCEED.
E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE DIMENSION
FLOOR PLAN AE101 AND ENGINEERING DRAWINGS FOR ADDITIONAL
INFORMATION.
F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED
ARE APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF
WORK TO BE REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE
NEW CONSTRUCTION. COORDINATE DEMOLITION WORK WITH DESIGN
INTENT OF NEW CONSTRUCTION TO PROVIDE ADEQUATE AREA FOR THIS
WORK.
G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION
ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHERWISE NOTED, TO
ACCOMMODATE NEW CONSTRUCTION.
H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE
NEW FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH
THAT THE CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE
SMOOTH AND UNDETECTABLE.
I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES
SHALL BE REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES
CAN BE REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE
REPLACED BY CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED
AND PAINTED TO SEAMLESSLY MATCH EXISTING CEILING COLOR
FOLLOWING ABOVE CEILING DEMOLITION ACTIVITY. THIS SHALL INCLUDE
REPAIR TO THE CEILING GRID, SUSPENSION SYSTEM AND ALL ASSOCIATED
ASSEMBLIES AS WELL AS THE REPLACEMENT OF DAMAGED CEILING
PANELS, WITHIN AND BEYOND PROJECT LIMITS.
J. COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND
VENDOR DRAWINGS.
K. WHERE EXISTING FLOOR FINISH IS REMOVED, FLOORING AND ADHESIVE
SHALL BE REMOVED TO PROVIDE A CLEAN FLOOR SLAB. FLOOR SLAB SHALL
BE FILLED/ LEVELED TO PROVIDE A LEVEL FINISH PER NEW FLOORING
MANUFACTURES RECOMMENDATIONS. REFER TO SPECIFICATION 09 05 16.
L. WALLS SHALL BE REMOVED THROUGHOUT PROJECT BOUNDARY UNLESS
OTHERWISE INDICATED.
M. COLUMN WRAPS SHALL BE REMOVED FROM EXISTING COLUMNS
THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE INDICATED.
N. FLOORING AND WALL BASE SHALL BE REMOVED THROUGHOUT PROJECT
BOUNDARY UNLESS OTHERWISE INDICATED.
O. REMOVE WALL MOUNTED ACCESSORIES AND MOUNTING HARDWARE
THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE NOTED.
P. REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED ACCESSORIES
THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE NOTED. REFER TO
PLUMBING PLAN FOR ADDITIONAL INFORMATION.
Q. REMOVE DOOR LEAVES, FRAMES AND HARDWARE THROUGHOUT PROJECT
BOUNDARY UNLESS OTHERWISE NOTED.
R. REMOVE EXISTING WALL PROTECTION, CORNER GUARDS, HANDRAILS AND/
OR GUARDRAILS THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE
NOTED.
S. CONTRACTOR TO REMOVE ALL OFFICE CUBICLES AND FURNITURE
THROUGH PROJECT BOUNDARY UNLESS OTHERWISE NOTED.
DEMOLITION PLAN NOTES
1. REMOVE WALL AND FLOOR MOUNTED CASEWORK.
2. REMOVE INDICATED PORTION OF WALL TO ACCOMMODATE NEW WORK.
3. REMOVE EXISTING SERVICE COUNTER.
4. EXISTING DOOR, FRAME AND HARDWARE TO REMAIN.
5. REMOVE EXISTING SLIDING SERVICE WINDOW AND FRAME IN ITS ENTIRETY.
6. REMOVE EXISTING COUNTERTOP AND PLUMBING FIXTURES.
7. REMOVE EXISTING HANDRAIL AND RUB RAIL COMPLETE.
8. REMOVE ALUMINUM STOREFRONT OPENING AND FRAME.
9. REMOVE EXISTING CHAIR RAIL.
10. EXISTING GRAB BARS TO REMAIN.
11. EXISTING PLUMBING FIXTURES TO REMAIN.
12. EXISTING CASEWORK TO REMAIN.
13. REMOVE EXISTING HANDRAIL AND RUB RAIL. CUT AND RECONFIGURE TO
ACCOMODATE NEW WALL CONFIGURATION. SEE ARCHITECTURAL PLAN.
14. EXISTING HANDRAIL AND RUB RAIL TO REMAIN.
15. EXISTING RECESSED FIRE EXTINGUISHER CABINET TO REMAIN.
16. REMOVE EXISTING WALL MOUNTED FIRE EXTINGUISHER.
17. EXISTING WALL BASE TO REMAIN
18. REMOVE EXISTING EMERGENCY SHOWER
19. PORTION OF EXISTING SLAB TO BE SAWCUT AND REMOVED.
20. REMOVE EXISTING FLOORING
21. REMOVE EXISTING WINDOW
22. EXISTING RAISED CONCRETE PAD
23. PET/CT EQUIPMENT TO BE REMOVED BY VENDOR.
DEMOLITION SYMBOL LEGEND
IMAGE DIRECTION
IMAGE NUMBER
LOCATION OF EXISTING
CONDITION IMAGES, REFER TO
SHEET AD103
N
KEY PLAN
PROJECT
LOCATION
A
3.5
B
C
D
E
F
2.5
7 7
7 7
5' - 0"
3' - 8 1/2" 1' - 4"
3' - 7"
141414 141414
14 14
9'
6' - 1" 5' - 0"
1'
/4
/8
1'
/8
2'
1/ 8"
/8
2'
1/ 2"
9'
/4
5'
3'
1"
5'
1"
6'
8'
/4
27' - 0" 27' - 0" 27' - 0" 27' - 0" 2' - 2" 19' - 0" 41' - 4" 25' - 0" 25' - 0" 25' - 0" 1' - 8"
1'
D.5
111213
'-1
3/
8" 9'
-0
8' -6
/8
9'
-0
'-6
/8
21'-2" 2'-2 1/2" 6' -6
/8
'-3
/8
'-0
/8
'-4
/8
9' -7
/8
23'-8" 11'-0 5/8" 6'-4 7/8" 31'-4 3/4" 9'-4 7/8" 9'-0 1/2"
8' -8
/8
'-4
/8
'-0
/8
'-1
1/ 4"
9' -9
/8
'-3
8' -1
/8
8'
-4
8' -1
/4
'-9
/8
9' -1
3/
4" 4'
-6
/8
'-8
/4
5'
-1
/8
9' -3
/4
10'-10 3/4" 12'-8" 12'-8 7/8" 9'-8 5/8" 6'-4 7/8"
9'-1 1/8" 5'-6 3/8" 19'-9 1/8" 6'-8 7/8"
13'-5 3/8" 12'-6" 8'-8 3/8" 6'-4 7/8"
18'-0 1/2" 16'-8 1/8" 6'-4 7/8"
34'-8 5/8" 6'-4 7/8" 42'-6 1/2" 9'-5 1/4"
19'-3 1/8" 7'-6 7/8" 12'-11" 8'-8 7/8"
21'-2"
9'-10 7/8" 8'-4 7/8"
'-0
'-0
/2
'-3
/8
7'
-3
/2
3/
4"
'-1
3/ 8"
3/
4" 8'
-0
11'-2" 6'-6 3/8" 9'-7" 8'-4 1/2"
26'-10" 12'-11" 18'-9" 17'-5"
12'-6 1/4"
11'-3 7/8" 15'-6 7/8" 4'-6"
'-6
/8
'-7
/8
9' -1
/4
'-2
/8
5' -1
/8
'-5
/8
'-1
1/
4"
'-1
5/
8"
7' -1
7/
8"
1'-0 1/4" 22'-5 5/8" 1'-6 1/8"
12'-3 3/8"
7'-5 3/4" 10'-7 3/8" 1'-8"
'-0
/2
2'
-0
22'-1 1/4" 9'-3 3/4"10 '-2
/8
1'
-9
/8
'-5
/4
'-8
/8
'-6
5'-4 7/8" 7'-6 1/8"
10'-2 1/8"
'-9
/8
'-0
20'-5 1/8" 12'-11" 12'-2 5/8"
6'-9 3/8"
(1)
(2)
(3)
(4)
(5)
(6)
(7)
LEAD CLERK
A-B023
LOG SERVICE
A-B032
TRAINING
A-B021
ASST CH HIMS
A-B025
CHIEF HIMS
A-B024
ELEC.
A-B031
SEC. / WAITING
A-B030
CODING SECTION
A-B026
DW-1 CODERS
A-B028
STAFF WORK ROOM
A-B003B
RECP.
A-B003A
WAITING
A-B002
CORRIDOR
CB-33
TOILET
A-B014
TOILET
A-B013 PAT. SHOWER &
DEC. SHOWER
A-B012
CONTROL
A-B011BREADING
A-B011A
CLEAN
A-B010
UPTAKE
A-B009
UPTAKE
A-B008
UPTAKE
A-B007UPTAKE
A-B006
UPTAKE
A-B005
STORAGE
A-B017d
SOILED UTILITY
A-B004
ROI
A-B017b
ROI
A-B017c
QSV
A-B017a
CHIEF OF SRD
A-B043
QSV ICRA
A-B043b
QSV
A-B018
QSV
A-B018A
QSV
A-B034
QSV
A-B033C
QSV OFFICE
A-B033A
FISCAL
A-B036
FISCAL
A-B037
FISCAL OFFICE
A-B038
FISCAL
A-B039
C O
R R
ID
O
R
C B
-1
OFFICE
A-B028
SCANNING &
TRANSCRIPTION
OFFICE
A-B029
EQUIPMENT
A-B011D
PET / CT
A-B011C
CORRIDOR
CB-00
OFFICE
A-B027
MECHANICAL
A-B148
MECHANICAL
A-B150
R.O. EQUIPMENT
A-B151
ENG. INTERIOR
DESIGN STORAGE
ROOM
C-B055
EMS STORAGE
A-B159
TELE. ROOM
B-B051
2092 SF
AUDITORIUM
B-B066
1779 SF
OFFICE
B-B040
153 SF
QCIS
B-B039
234 SF
TEAM ROOM
B-B038
76 SF
RISK MANAGER
B-B044
118 SF
CHIEF QUALITY
MANAGEMENT
B-B045
68 SF
INFECTION
CONTROL MANAGER
B-B04684 SF
NOURISHMENT
B-B047
152 SF
CHEIF LOG.
B-B042
270 SF
ASSISTANT LOG
B-B041
105 SF
PATIENT SAFETY
MANAGER
B-B043
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C
U s e rs \d c h ri s te n s e n \D o c u m e n ts \1
.1
.0
N u c M e d v d c h ri s te n s e n M
N F
X
.r v t
/2
/2
:5
:5
A
M
AD101
LOWER LEVEL DEMOLITION PLAN
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 JLG ELB
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"AD101
1 LOWER LEVEL DEMOLITION PLAN
N
S
S
S
D
D
DD
DD
D
D
S
S
SS
D
S
D
S
S
1 6 7
1 6
1 6 9 105
10 6
1 6 95
5 6
1 5 6 9 13
1 5 6 9
1 5 6 9 13 7 1 16 17
1 5 6
8 9 13
1 5 6 91 5
6 9
1 5 6 9
16 17
1 5 6 9
16 8
1 5 6 9
16 8
5 6
16 8
1 6
13 16
1 6
13 16
1 5 6
16 9
1 6
1 5 16
1 5
16 6
1 5 6 9
17 8
1 16 17
1 16
6 14
1 16
6 17
1 16 176
6 16
DEMOLITION RCP NOTES
1. REMOVE ACOUSTIC PANEL CEILING ASSEMBLY IN ITS ENTIRETY.
2. EXISTING LIGHT FIXTURES TO REMAIN
3. EXISTING ACOUSTIC PANEL CEILING ASSEMBLY TO REMAIN.
4. EXISTING CEILING DIFFUSERS TO REMAIN.
5. REMOVE EXISTING SPEAKERS.
6. REMOVE AND RELOCATE EXISTING SPRINKLER HEADS. COORDINATE WITH
MECHANICAL DRAWINGS.
7. REMOVE EXISTING EXIT SIGNS
8. REMOVE EXISTING CEILING MOUNTED CAMERAS
9. REMOVE EXISTING SMOKE DETECTORS
10. REMOVE CEILING MOUNTED SIGNAGE
11. REMOVE 36" DIAMETER LIGHT FIXTURE
12. REMOVE CEILING MOUNTED ELECTRICAL OUTLETS
13. REMOVE CEILING MOUNTED ROUTER
14. EXISTING SPRINKLER HEADS TO REMAIN.
15. REMOVE EXISITNG BULKHEAD CONSTRUCTION.
16. REMOVE EXISTING CEILING DIFFUSERS
17. REMOVE EXISTING LIGHT FIXTURES.
18. REMOVE EXISTING PATIENT LIFT - SALVAGE FOR REINSTALLATION.
N
KEY PLAN
PROJECT
LOCATION
2x4 EMERGENCY LIGHT
DEMOLITION RCP LEGEND
2x4 FLUORESCENT LIGHT TO BE DEMOLISHED
1x4 FLUORESCENT LIGHT TO BE DEMOLISHED
36" DIAMETER LIGHT FIXTURE
HVAC RETURN DIFFUSER TO BE DEMOLISHED
HVAC SUPPLY DIFFUSER TO BE DEMOLISHED
S SPEAKER
D SMOKE DETECTOR
2x4 FLUORESCENT LIGHT TO REMAIN
1x4 FLUORESCENT LIGHT TO REMAIN
HVAC RETURN DIFFUSER TO REMAIN
HVAC SUPPLY DIFFUSER TO REMAIN
RECESSED CAN LIGHTING
EXIT LIGHTING
HVAC SUPPLY LINEAR DIFFUSER
MECH / ELEC ITEMS REFER TO MEP SHEETS AS APPLICABLE
PATIENT LIFT
83 SF
LEAD CLERK
A-B023
632 SF
LOG SERVICE
A-B032
139 SF
TRAINING
A-B021
90 SF
ASST CH HIMS
A-B025
94 SF
CHIEF HIMS
A-B024
17 SF
ELEC.
A-B031
206 SF
SEC. / WAITING
A-B030
992 SF
CODING SECTION
A-B026
465 SF
DW-1 CODERS
A-B028
264 SF
STAFF WORK ROOM
A-B003B
100 SF
RECP.
A-B003A
364 SF
WAITING
A-B002
703 SF
CORRIDOR
CB-33
65 SF
TOILET
A-B014
66 SF
TOILET
A-B013
64 SF
PAT. SHOWER &
DEC. SHOWER
A-B012
134 SF
CONTROL
A-B011B
101 SF
READING
A-B011A
106 SF
CLEAN
A-B010
120 SF
UPTAKE
A-B009
83 SF
UPTAKE
A-B008
114 SF
UPTAKE
A-B007
114 SF
UPTAKE
A-B006
123 SF
UPTAKE
A-B005
104 SF
STORAGE
A-B017d
105 SF
SOILED UTILITY
A-B004
517 SF
ROI
A-B017b
91 SF
ROI
A-B017c
180 SF
QSV
A-B017a
120 SF
CHIEF OF SRD
A-B043
210 SF
QSV ICRA
A-B043b
219 SF
QSV
A-B018
124 SF
QSV
A-B018A
111 SF
QSV
A-B034 79 SF
QSV
A-B033C
587 SF
QSV OFFICE
A-B033A
471 SF
FISCAL
A-B036
82 SF
FISCAL
A-B037
84 SF
FISCAL OFFICE
A-B038
125 SF
FISCAL
A-B039
S
F
C O
R R
ID
O
R
C B
-1
77 SF
OFFICE
A-B028
1050 SF
SCANNING &
TRANSCRIPTION
OFFICE
A-B029
126 SF
EQUIPMENT
A-B011D
454 SF
PET / CT
A-B011C
608 SF
CORRIDOR
CB-00
78 SF
OFFICE
A-B027
6264 SF
MECHANICAL
A-B148
1302 SF
MECHANICAL
A-B150
240 SF
R.O. EQUIPMENT
A-B151 344 SF
ENG. INTERIOR
DESIGN STORAGE
ROOM
C-B055
143 SF
EMS STORAGE
A-B159
64 SF
TELE. ROOM
B-B051
2092 SF
AUDITORIUM
B-B066
1779 SF
OFFICE
B-B040
153 SF
QCIS
B-B039
234 SF
TEAM ROOM
B-B038
76 SF
RISK MANAGER
B-B044
118 SF
CHIEF QUALITY
MANAGEMENT
B-B045
68 SF
INFECTION
CONTROL MANAGER
B-B04684 SF
NOURISHMENT
B-B047
152 SF
CHEIF LOG.
B-B042
270 SF
ASSISTANT LOG
B-B041
105 SF
PATIENT SAFETY
MANAGER
B-B043
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C
U s e rs \d c h ri s te n s e n \D o c u m e n ts \1
.1
.0
N u c M e d v d c h ri s te n s e n M
N F
X
.r v t
/2
/2
:5
:0
A
M
AD102
LOWER LEVEL REFLECTED
CEILING DEMOLITION PLANGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA STREET
SUITE 200
INDIANAPOLIS, INDIANA 46202
317.800.6388
HEAPY
1400 W. DOROTHY LANE
DAYTON, OH 45409
937.224.0861
RELOCATE NUCLEAR MEDICINE
SERVICES FOR CENTRALIZED
SERVICES
INDIANAPOLIS, IN
583-20-102
01/28/2021 JLG ELB
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"AD102
1 LOWER LEVEL DEMOLITION REFLECTED CEILING PLAN N
File details come from the government source that posted it. Updated .