583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part25.pdf

PDF 5 MB Posted

Attached to
Z1DA--Renovate Nuclear Med 583-20-102 (VA-21-00037478)
Solicitation number
36C25021B0036
Issued by

About this file

This solicitation is for renovation services at the Richard L. Roudebush VA Medical Facility in Indianapolis, Indiana. The scope of work involves relocating the nuclear medicine department and centralizing services. Key details include renovating approximately 12,000 square feet of existing space in the basement level and providing new HVAC, electrical, and plumbing systems. The estimated cost is between $5-10 million. The solicitation number is 36C25021B0036 and the opportunity was posted by the Department of Veterans Affairs VHA VISN 10 network. The response due date is April 15, 2022.

View the file

Other files

File Type Posted
Amendment A00006.docx DOCX document
Amendment A00006 RFI Responses.docx DOCX document
Amendment 36C25021B0036 A00005.pdf PDF
A00004- Corrected Statement of Work.pdf PDF
Amendment 36C25021B0036 A00004.pdf PDF
A00004 - RFI Responses.docx DOCX document
A0004 - 08 71 00 - Door Hardware.pdf PDF
A00004 - 10 25 13 - Patient Bed Service Walls.pdf PDF
A00004 - Door Schedule.pdf PDF
Amendment 36C25021B0036 A00003.pdf PDF
Amendment A00002.pdf PDF
Site Visit Sign-in Sheet.pdf PDF
A0001 - RFI 1 ShieldingReportComplete.pdf PDF
A0001 - RFI 2- GC101.pdf PDF
A0001 - RFI Responses.docx DOCX document
Amendment A0001.docx DOCX document
A0001 - RFI 4- Door Schedule.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part18.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part23.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part22.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part11.pdf PDF
Specifications.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part21.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part13.pdf PDF
Wage Determination.txt TXT text file
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part15.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part4.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part20.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part5.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part8.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part10.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part7.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part12.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part6.pdf PDF
36C25021B0036 Solicitation Document.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part11.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part14.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part16.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part24.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-2_Part9.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part1.pdf PDF
583-20-102 Relocate Nuclear Medicine Drawing SetPart-1_01_Part2.pdf PDF
Show 40 more

Latest 50 of 66 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A

3.5

B

C

D

2.5

D.5

A

3.5

B

C

D

2.5

A

B

C

D

D.5

9.A

9.9 9.8 9.7 9.6

1 .5

.4

2.5

3.5

10ø

1 4

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:2

A M

MH102

FIRST FLOOR HVAC DUCTWORK

PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"

PARTIAL FIRST FLOOR HVAC DUCTWORK PLAN

GENERAL NOTES

PLAN NOTES

A. REFER TO SHEET M001 FOR LEGEND, INDEX, AND GENERAL NOTES.

1. DUCT SHALL BE 2-HO UR FIRE W RAPPED FROM PENETRATION OF FIRST FLOOR

SLAB TO PENETRATION OF SECO ND FLOOR ROOF.

2. DUCT DOW N TO LEVEL BELO W . REFER TO M H101 FO R CO NTINUATION DOW N.

3. DUCT UP THROUGH SECOND FLOOR ROOF. REFER TO MH103 FOR

CONTINUATIO N UP.

4. RADIOISOTOPE HO OD EXHAUST DUCT SHALL BE CO NSTRUCTED OF W ELDED

316L STAINLESS STEEL. TO MINIMIZE HOT W ORK IN EMERGENCY CARE SUITE,

PRE-FABRICATE DUCTW O RK SHOW N AS MUCH AS POSSIBLE FOR

INSTALLATIO N. REFER TO ARCHITECTURAL SHEET AE104 FOR DESCRIPTION

OF PHASING, TEMPORARY BARRIERS, AND MAXIMUM TIME AVAILABLE FOR

COMPLETION OF W ORK ON THIS SHEET.

Revisions: Date:

B

C

D

D.5

E

F

E.5

9.A

9.10 9.9 9.8 9.7 9.6

1 .5

E.7

E.1

.4

2.5

3.5

1-EF30B

ø

14ø ø

10ø

UP

UP

MH103

B01A - 7 -

SEVENTH FLOOR

183' - 1 1/4"

B01A - 2 - SECOND

FLOOR

111' - 11"

B01A - 3 - THIRD

FLOOR

INTERSTITIAL

123' - 11"

B01A - 4 - FOURTH

FLOOR

133' - 11"

B01A - 5 - FIFTH

FLOOR

INTERSTITIAL

146' - 11"

B01A - 6 - SIXTH

FLOOR

158' - 5 1/4"

B01A - 7 -

SEVENTH FLOOR

169' - 5 1/4"

B01A - 8 - EIGHTH

FLOOR

181' - 4 1/4"

B01A - 9 - ROOF

195' - 4 1/4"

10-PH FLOOR

205' - 4 1/4"

D D.5 E

T.O. ENTRANCE

CANOPY PARAPET

166' - 1 3/4"

ENTRANCE

CANOPY ROOF

162' - 1 3/4"

B01A - 5 - FIFTH

FLOOR CORE

146' - 6 1/4"

B01A - 3 - THIRD

FLOOR CORE

122' - 11"

B01A - 2 - SECOND

FLOOR

125' - 7"

B01A - 9 - ROOF

209' - 0 1/4"

B01A - 3 - THIRD

FLOOR CORE

136' - 7"

1-EF30B

14ø

14ø

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:3

A M

MH103

ROOF LEVEL HVAC DUCTWORK

PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"

PARTIAL ROOF LEVEL HVAC DUCTWORK PLAN

GENERAL NOTES

PLAN NOTES

A. REFER TO SHEET M001 FOR LEGEND, INDEX, AND GENERAL NOTES.

1. DUCT DOW N TO LEVEL BELO W . REFER TO M H102 FO R CO NTINUATION DOW N.

PRO VIDE M ANUFACTURED DUCT RO OF CURB FOR DUCT PENETRATION.

2. RADIOISOTOPE HO OD EXHAUST DUCT SHALL BE CO NSTRUCTED OF W ELDED

316L STAINLESS STEEL. DUCTW ORK RUNNING ACROSS THE ROOF SHALL BE

SUPPORTED AT INTERVALS RECO MMENDED BY SMACNA FOR THE

APPLICATION.

SCALE: 1/8" = 1'-0"

EXHAUST DUCTWORK ELEVATION

T

T T

T

T

T

T

T

T

T

T

T

TTTTT

T

T

TT

T T

T

T

T

T

T

T

T

H H

T

T

A

457 3.5

B

C

D

E

F

2.5

TU-30-22

TU-30-24

TU-30-25

TU-30-25

TU-30-26

TU-30-27

TU-30-04

TU-30-10

TU-30-21

TU-30-20

TU-30-19

TU-30-28

TU-30-23

TU-30-29

TU-30-31

TU-30-30

TU-30-30

TU-30-29

TU-30-17

TU-30-18

TU-30-12

TU-30-12

TU-30-18

TU-30-09

TU-30-08

TU-30-03

TU-30-02

TU-30-01

TU-30-05 TU-30-07

TU-30-06

TU-30-13

TU-30-14

TU-30-15

TU-30-16

TU-30-31

TU-30-16

TU-30-11

TU-30-17

TU-30-23

TU-30-26

TU-30-27

TU-30-28

TU-30-05

TU-30-06

TU-30-07

TU-30-09

TU-30-01 TU-30-02

TU-30-08

TU-30-03

TU-30-04

TU-30-10

TU-30-21

TU-30-20

TU-30-19

TU-30-11

ACV-30-04

ACV-30-10

ACV-30-20

ACV-30-25

ACV-30-24

ACV-30-26

ACV-30-27

ACV-30-28

ACV-30-29

ACV-30-30

ACV-30-31ACV-30-15ACV-30-14ACV-30-13

ACV-30-11

ACV-30-09

2"

2"1.

5"

1.5"

2" 2"

2" 2"

1" 1"

1"

1"

1" 1"

1.

5"

2"

2" 1.

5" 2"

2" 2"

2" 2"

2" 1.25"

H W

S

HW R

HW S

H W

S H

W R

HW R

H W

S H

W R

H W

S H

W R

1" 1"

1" 1"

1"

4"

1.

PET/CT

CHILLER 1

PET/CT

CHILLER 2

1.25"

1.

1.

0.75"

AC-1

ACCU-1

D 0.5"

AC-2

AC-2

ACCU-2

AC-1

0.5"D

5 5

RPM

RPM

RPM

RPMRPMRPM

RPM

RPM

RPM

ACV-30-12 ACV-30-17

ACV-30-18

TU-30-15

TU-30-14

TU-30-13

A-B005

COMBINED

PET

CONTROL

ROOM

A-B007

HOT LAB

A-B008

DOSE

ADMIN.

ROOM

A-B009

DOSE

ADMIN.

ROOM

A-B010

DOSE

ADMIN.

ROOM

A-B013

READING &

CONSULTATION

A-B012

DOSE

ADMIN.

ROOM

A-B014

EQUIP

CALIBRATION A-B01

SOILED

UTILITY

A-B026

TOILET,

STAFF

A-B027

TOILET,

STAFF

A-B028

PET

TOILET,

PATIENT

A-B029a

NM SCAN 1

A-B029

NM

CONTROL

RM

A-B016

NM TOILET,

PATIENT

A-B017

NM TOILET,

PATIENT

A-B018

SUPERVISOR

OFFICE

A-B020

OUTPATIENT

WAITING

CB-9

CORRIDOR

CB-10

AUDITORIUM

CORRIDOR

A-B025

ELEC

ROOM

A-B004a

PET

EQUIPMENT

ROOM

A-B004

PET / CT 2

A-B002

DOSE

ADMIN.

ROOM

A-B003

DOSE

ADMIN.

ROOM

A-B006a

PET

EQUIPMENT

ROOM

A-B024

PATIENT

INTERVIEW

ROOM

A-B023

CARDIAC

STRESS

TESTING

A-B021

INPATIENT

HOLDING

A-B022

THYROID

UPTAKE

C-5A

ALCOVE

A-B030

DIGI ROD,

MOBILE

EQUIPMENT

A-B031

CLEAN

SUPPLY

A-B029b

NM SCAN 2

C-6a

CLOSET

C-2

NORTH

CORRIDOR

A-B006

PET / CT 1

A-B019

MSA /

SCHEDULING

A-B015

STAFF

LO UNGE

1A

PATIENT

EDUCATION

KIOSK

3A

HOLDING

BAY 1

3B

HOLDING

BAY 2

A-B007a

RADIO ACTIVE

WASTE

STORAGE

3C

HOLDING

BAY 3

C-5

WEST

CORRIDOR

C-4

SOUTH

CORRIDOR

C-6

CORRIDOR

C-3

EAST

CORRIDOR

C-1

STAFF

ENTRANCE

CORRIDOR

A-B039

QCIS

A-B038

TEAM

ROOM

N

KEY PLAN

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:4

A M

MP101

LOW ER LEVEL HVAC PIPING PLAN

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

GENERAL NOTES

PLAN NOTES

A. REFER TO SHEET M001 FOR LEGEND, INDEX, AND GENERAL NOTES.

B. REFER TO ARCHITECTURAL DRAW INGS FOR PHASING OF W ORK.

1. PRO VIDE LINE SIZE SHUTOFF VALVE IN APPROXIMATE LO CATIO N SHOW N.

2. ROUTE COOLING CONDENSATE DRAIN PIPING DOW N TO FLOOR DRAIN.

3. REFRIG ERANT PIPES SHO W N SINGLE LINE FOR CLARITY. COORDINATE

ACTUAL SIZE AND QUANTITY OF PIPES W ITH EQUIPMENT MANUFACTURER.

4. PRO VIDE W ALL MOUNTING BRACKET/FRAME FOR CONDENSING UNIT

INSTALLATIO N. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCES AND

INSTALL PER MANUFACTURER'S INSTRUCTIONS.

5. AIR-COOLED CHILLER FOR PET/CT EQUIPM ENT (BY OTHERS). INSTALL PER

MANUFACTURER'S RECOMMENDATIONS - REFER TO SIEMENS DRAW INGS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS. CHILLED W ATER PIPING

SHALL BE COPPER - PROVIDE HO SE ADAPTERS AS REQUIRED.

6. ROUTE CHILLED W ATER PIPING TO INDOOR HEAT EXCHANGER CABINET (BY

OTHERS). REFER TO SIEMENS DRAW INGS FOR ADDITIONAL INFORMATION AND

REQ UIREMENTS.

SCALE: 1/8" = 1'-0"

LOWER LEVEL HVAC PIPING PLAN

F

PRS

FD

5 4

7 7

M 402

/3

O

V

/3

O V

26/18 OV

22x14 x3 x3

72x30 ø ø

17/12 OV

4"

4"

0 .75" -

8" - CHS

8" - CHR

x1

/2

O

V x2

10" - SCW

4" -

4" -

2.5" - HW S

4" - HW R

4" - HW R

2.

5"

H

W S

3" - MPS

4" - HW S

6" - MPS

6"

M P

S

3" - MPS

2" - LPS

10" - SCW

4" - HW S

4" - HW R

1" - MPC

2" - MPS

x2 x3

14x12 x1 x1

18x12

26x12 20x12

1" - MPC

F

F.3

G

F.4

G.6

F.5

F.8

G.5

G.4

F.3.1

F.8.5

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:4

:2

A M

M401

ENLARGED MECHANICAL ROOM

HVAC DEMOLITION PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

GENERAL NOTES

PLAN NOTES

A. REFER TO SHEET M001 FOR LEGEND, INDEX, AND GENERAL NOTES.

B. REFER TO ARCHITECTURAL DRAW INGS FOR PHASING OF W ORK.

1. REM OVE EXISTING AIR HANDLING UNIT AND ASSO CIATED CONTROLS AND ACCESSORIES.

2. REM OVE EXISTING DUCTW ORK, ACCESSORIES, AND SUPPORTS BACK TO APPROXIM ATE

LOCATION SHOW N. CAP AND SEAL DUCT IN PREPARATION FOR NEW W ORK.

3. REM OVE EXISTING RETURN FAN AND ASSOCIATED SUPPORTS, CONTROLS, AND

ACCESSORIES.

4. EXISTING PIPING TO REM AIN.

5. EXISTING DUCTW ORK TO REMAIN.

6. EXISTING AIR HANDLING UNIT TO REMAIN.

7. EXISTING AIR COMPRESSO R AND ASSOCIATED PIPING, ACCESSORIES, AND SUPPORTS

TO REMAIN.

8. EXISTING AIR STORAGE TANK AND ASSOCIATED PIPING, ACCESSORIES, AND SUPPORTS

TO REMAIN.

9. EXISTING AIR TERMINAL UNIT TO REMAIN.

10. EXISTING COIL PUM P TO REMAIN.

11. REM OVE EXISTING COIL PUMP AND ASSOCIATED CO NTRO LS AND ACCESSORIES.

12. REM OVE EXISTING PIPING BACK TO APPROXIMATE LO CATIO N SHOW N.

13. EXISTING FIRE DAMPER TO REMAIN.

14. EXISTING STORM RISER TO REMAIN,

15. REM OVE EXISTING AIR HANDLING UNIT CONTROL PANEL.

16. REM OVE EXISTING OUTSIDE AIR DUCT AND CO NTRO L DAMPER.

17. REM OVE EXISTING RETURN AIR CONTROL DAMPER.

18. EXISTING STEAM PRESSURE REDUCEING STATION TO REMAIN.

19. EXISTING RELIEF AIR DUCTW ORK RISER TO SIXTH FLOOR ROOF TO REM AIN.

20. EXISTING STEAM CONDENSATE PUMP AND FLASH TANK TO REMAIN.

SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM HVAC DEMOLITION PLAN

S D

S D

F

FD

AREAW ELL

M 402

1-RF30

1-AC30

8" - CHS

8" - CHR

6"

C H

R

6"

C H

S

2"

LP

S

6"

M P

S

3" - MPS

x1

S A x1 ø x 3 x3 ø x3

60x30

1-HCP30

x2

30x10 26/18 OV

26x12 x1

/2

O

V

1-AC29

4" - HW R

2.5" - HW S

2" - MPS

4" - HW R

10" - SCW

4" - HW S

20x20 x2 x3

14x12

16x12

3" - MPS

4" - HW R

18x12

10" - SCW

4" - HW R

4" - HW S

4" - HW R

3" - MPS

2" - LPS

1" - MPC

x2 x2 x2

/2

O

V x1

1-PRS30

1-CCP30

2" - MPS

1" - MPC

2.5" - HW S

2.5" - HW S

4" - HW R

B-D B-D

0.75" - LPC

F

F.3

G

F.4

G.6

F.5

F.8

G.5

G.4

F.3.1

F.8.5

3" - HW S

MDD 17

60x26 x2

LOW ER LEVEL

PLAN

100' - 0" x2

B01A - 2 - SECOND

FLOOR

111' - 11"

B01A - 1 - FIRST

FLOOR

100' - 0"

B01A - 0 -

BASEMENT

86' - 4"

B01A - SUB

BASEMENT

82' - 4"

B W ING-FLOOR

89' - 0"

B01A - GARAGE

LEVEL A

99' - 0"

B01A - GARAGE

LEVEL B

701' - 5"

B01A - GARAGE

LEVEL C

691' - 5"

B W ING-ROOF

104' - 6"

B01A - 2 - SECOND

FLOOR

125' - 7"

FIRST FLOOR

HVAC DUCTW ORK

PLAN

113' - 8"

2' MIN.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:4

:2

A M

M402

ENLARGED MECHANICAL ROOM

HVAC PLANGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM HVAC PLAN

GENERAL NOTES

PLAN NOTES

A. REFER TO SHEET M001 FOR LEGEND, INDEX, AND GENERAL NOTES.

B. REFER TO ARCHITECTURAL DRAW INGS FOR PHASING OF W ORK.

1. AIR HANDLING UNT. REFER TO SCHEDULE ON SHEET M 002 AND DETAIL O N

SHEET M506.

2. PRO VIDE AREAW ELL PENETRATIONS TO ACCOM MODATE O UTDOO R AIR AND

RELIEF AIR DUCTW ORK. EXISTING OUTDOOR AIR OPENING SHALL BE CAPPED

W ITH SHEET METAL. SEAL W ATERTIGHT AND INSULATE AS FOR OUTDOOR AIR

DUCTW ORK.

3. PRO VIDE DDC CONTROL PANEL FOR 1-AC30 AND RELATED EQUIPM ENT.

4. EXISTING STEAM PRESSURE REDUCING STATION AND ASSOICATED PIPING.

5. EXISTING STRUCTURAL COLUM N. COO RDINATE AIR HANDLING UNIT ACCESS

AND CLEARANCES.

6. MODIFY EXISTING CONCRETE HOUSEKEEPING PAD TO ACCOMMODATE AIR

HANDLING UNIT.

7. CALIBRATE EXISTING VAV BOX TO DELIVER 850 CFM.

8. CALIBRATE EXISTING VAV BOX TO DELIVER 1500 CFM.

9. CHECK VALVE, REFER TO CO IL PIPING DETAILS.

10. EXISTING AREAW ELL STEEL GRATING. CUT OPENING IN EXISTING GRATING TO

INSTALL RELIEF DUCT. PROVIDE DUCT SUPPORTS AS REQUIRED.

11. PRO VIDE NEW PIPING TO RELOCATE EXISTING M AINS OUT OF THE W AY O F THE

AIR HANDLING UNIT. COORDINATE SYSTEM SHUTDOW NS W ELL IN ADVANCE

W ITH THE COR.

12. EXISTING STEAM CONDENSATE PUM P AND FLASH TANK. CO NNECT STEAM

CONDENSATE PIPING TO EXISTING FLASH TANK AND PROVIDE UNION AND

SHUTOFF VALVE AT CO NNECTIO N.

13. APPROXIMATE LOCATION FOR VFD'S: FOUR (4) AHU SUPPLY FAN DRIVES AND

ONE (1) RETURN FAN DRIVE. THE SUPPLY FAN VFD'S SHALL BE PROVIDED BY

THE AIR HANDLING UNIT M ANUFACTURER, REFER TO SPECIFICATIONS.

MAINTAIN CODE REQUIRED CLEARANCES.

14. EXISTING FLOOR DRAIN.

15. INSTALL RETURN FAN SUCH THAT THE M OTO R/BELT ENCLOSURE IS

ACCESSIBLE FRO M THE TOP OF THE AHU CASING. PRO VIDE SPRING HANGER

VIBRATION ISOLATORS SUITABLE FOR THE APPLICATIO N.

16. PRO VIDE 0.5" ALUMINUM W IRE MESH TO COVER DUCT OPENING.

17. AUTOM ATIC RELIEF AIR DAM PER INSTALLED REMOTELY IN DUCTW ORK.

18. MINIMUM / MAXIMUM OUTSIDE AIR DAM PERS / AIRFLOW STATIONS SHALL BE

DUCTED SEPARATELY TO A COMMON PLENUM OPENING IN EXISTING

AREAW ELL. APPROX. SIZE O F OUTSIDE AIR PLENUM = 78" x 52". COORDINATE

W ITH AIR HANDLING UNIT MANUFACTURER TO DETERMINE EXACT SIZE AND

ELEVATION.

SCALE: 1/4" = 1'-0"

RELIEF AIR AREAWELL SECTION

4 8x 36 ø

36x5036x44 36x38

G

G.6

F.8

101112

G.5

G.4

F.8.5

M 403 ø

3 6x4 4

3 6x3 8

4 8x 36 ø

44x28

1-EF30A

36x50 7

G

G.6

F.8

101112

G.5

G.4

F.8.5 ø 42ø x4 x4

1 4x 14 x1

12ø ø

12x12 ø x1

1-EF118

1-EF119

1-EF116

1-RF33B

1-RF29

1-EF32

1-EF120

1-EF126

1-EF129

1-EF125 1-EF131

1-EF115

B01A - 7 -

SEVENTH FLOOR

183' - 1 1/4"

B01A - 6 - SIXTH

FLOOR

158' - 5 1/4"

B01A - 7 -

SEVENTH FLOOR

169' - 5 1/4"

GG.6 F.8

T.O. ENTRANCE

CANOPY PARAPET

166' - 1 3/4"

ENTRANCE

CANOPY ROOF

162' - 1 3/4"

F.8.5 x5

44x28

34ø ø

MDD

1-EF30A

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:4

:3

A M

M403

PARTIAL SIXTH FLOOR HVAC

ROOF PLANSGUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"

PARTIAL SIXTH FLOOR ROOF HVAC DEMOLITION PLAN

SCALE: 1/8" = 1'-0"

PARTIAL SIXTH FLOOR HVAC ROOF PLAN

GENERAL NOTES

PLAN NOTES

A. REFER TO SHEET M001 FOR LEGEND, INDEX, AND GENERAL NOTES.

1. EXISTING EXHAUST FAN AND ASSOCIATED DUCTW ORK TO REM AIN.

2. EXISTING RELIEF AIR LO UVER TO REMAIN.

3. EXISTING DUCTW ORK TO REMAIN.

4. REM OVE EXISTING RELIEF AIR DUCT FROM ELBOW TO CONNECTION TO RELIEF

AIR LOUVER. CAP AND SEAL LOUVER SHEET METAL PLENUM AT FORM ER

DUCT CONNECTION LOCATION. EXISTING 38x54 RISER TO REMAIN.

5. PRO VIDE STEEL CHANNEL ISOLATIO N BASE FOR FAN W ITH SPRING

ISOLATORS.

6. EXHAUST STACK, REFER TO DETAIL ON SHEET M505.

7. PRO VIDE DUCT TRANSITION FRO M 36x50 TO 44x28 IN EXISTING DUCT RISER.

PENETRATE AREAW AY ROO F ABOVE W ITH W EATHERPROO F DUCT ROOF

CURB. ELBO W DOW N TO RO OF LEVEL AS SHOW N W ITH 90 DEG RADIUS ELLS

(3 TOTAL). ROOF PENETRATION SHALL BE PATCHED AND SEALED TO MAINTAIN

THE INTEGRITY OF THE EXISTING RO OFING SYSTEM.

SCALE: 1/4" = 1'-0"

EXHAUST DUCT SECTION

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:1

A M

M404

HVAC ISOMETRIC VIEWS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

SCALE:

ROOF PLAN ISOMETRIC

1-EF30B

14Ø

GENERAL NOTES

PLAN NOTES

A. ALL ROOF AND W ALL DUCT SUPPORTS AND FASTENERS SHALL BE

CONSTRUCTED OF THE SAME MATERIAL AS THE DUCT IT IS SUPPORTING.

1. DUCTW ORK ABOVE ROOF SHALL BE SUPPORTED W ITH DUCTW ORK SUPPO RTS

SECURED TO ROOF DECT BELOW PER SM ACNA STANDARDS ON ROOF CURBS

FLASHED TO ROO F. VERIFY FINAL QUANTITIES REQUIRED IN KEEPING W ITH

SM ACNA STANDARDS FO R M AINTAIN ING MAX. ALLOW ABLE DEFLECTIONS

BETW EEN SUPPORTS. ROUTE DUCTS AS LOW AS POSSIBLE, BUT NO LOW ER

THAN 18" FROM BOTTOM OF DUCT TO FINISHED ROOF SURFACE.

2. DUCTW ORK RISERS ON EXTERIOR W ALL SHALL BE SUPPORTED W ITH POSITIVE

ATTACHMENT TO BUILDING SURFACE. SUPPORTS SHALL BE SELECTED AND

DESIG NED FOR THE EXPECTED LOADING, AND SHALL BE INSTALLED SUCH

THAT THE BUILDING ENVELOPE REM AINS CO NTINUO US.

3. EXTERIO R BUILDING SURFACE IS CURTAINW ALL W ITH A CO MBINATION OF

INSULATING (1") SPANDREL AND VISION GLASS PANELS.

4. EXTERIO R BUILDING SURFACE IS CURTAINW ALL W ITH A CO MBINATION OF

PRECAST CONCRETE PANELS AND INSULATING (1") SPANDREL AND VISION

GLASS PANELS.

5. EXTERIO R BUILDING SURFACE IS MASONRY W ALL W ITH MORTAR JOINTS.

6. INSTALL RADIOISOTOPE FUME HOOD EXHAUST FAN ON EQUIPM ENT RAILS

W ITH SPRING VIBRATION ISOLATORS. FAN SUPPORTS SHALL BE INTEGRATED

INTO THE EXISTING ROOFING SYSTEM. SUPPORT STACK PER SMACNA AND

MANUFACTURER'S RECOMMENDATIONS.

SUPPLY DUCT

4 3 4 5 4

CEILING CEILING DIFFUSER

1. SQ UARE-TO-ROUND ADAPTER IF DIFFUSER NECK IS

SQ UARE. CONNECT ADAPTOR TO DIFFUSER. SEAL

TO AIR DEVICE, SEAL CLASS A. INSULATE ADAPTO R

AND EXPOSED BACKSIDE SURFACES OF AIR DEVICE.

2. INSULATED FLEXIBLE DUCT SAM E DIAM ETER AS

BRANCH DUCT , 5 FT. M AXIMUM TOTAL LENGTH

PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT

LEAST 90% O F FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH

MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.

INTEG RAL INSULATION GUARD SLEEVE REQ UIRED

FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL

INSULATION, AND EXTENDED DAM PER SHAFT AND

HANDLE W ITH STAND-O FF TO ACCOMMODATE

EXTERNAL INSULATIO N.

4. DUCT STRAP HANGER. ATTACH TO STRUCTURE.

5. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE

DUCT IS LONGER THAN 4 FT.

6. MINIMUM CENTERLINE RADIUS EQUAL TO DUCT

DIAMETER.

7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS

DIFFUSER INLET UNLESS NOTED OTHERW ISE.

8. FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED W ITH

NYLO N BANDING PER MANUFACTURER'S

INSTRUCTIO NS.

9. A RADIUS'D SHEET METAL ELBOW MAY BE USED IN

LIEU OF A FLEXIBLE ELBO W SUPPORT W HEN

CONNECTED DIRECTLY TO AIR DEVICE.

10. CEILING T-BAR SUPPORT (FOR LAY-IN

APPLICATIONS). COORDINATE AND VERIFY T-BAR

TYPE FOR COMPATIBILITY W ITH DIFFUSER.

NOTES

CEILING CEILING DIFFUSER

2 6 4 1

SUPPLY DUCT

1. SHEET METAL BOX W ITH SAME INTERNAL OR EXTERNAL INSULATION AS MAIN

SUPPLY DUCT, 2" LARGER EACH DIRECTION THAN DIFFUSER NECK, W ITH

ADAPTOR CONNECTION TO DIFFUSER. CONNECT PLENUM TO DIFFUSER. SEAL

BO X AND ADAPTOR TO AIR DEVICE, SEAL CLASS A. INSULATE ADAPTOR AND

BACKSIDE SURFACES OF AIR DEVICE.

2. INSULATED FLEXIBLE DUCT SAM E DIAM ETER AS BRANCH DUCT , 5 FT.

MAXIMUM TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT

LEAST 90% O F FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH M ANUAL DAMPER. DAM PER

SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR

TAP FITTING TO M AIN DUCT W ITH INTERNAL INSULATION, AND EXTENDED

DAM PER SHAFT AND HANDLE W ITH STAND-OFF TO ACCOMMODATE EXTERNAL

INSULATION.

4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER.

5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SAM E SIZE AS DIFFUSER INLET UNLESS

NOTED OTHERW ISE.

8. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE AND

VERIFY T-BAR TYPE FOR COM PATIBILITY W ITH DIFFUSER.

NOTES

CEILING SLOT DIFFUSER

SUPPLY DUCT

5 3

2 6 4 1

1. SLOT DIFFUSER ASSEMBLY AND PLENUM W ITH SAME INTERNAL OR EXTERNAL

INSULATION AS MAIN SUPPLY DUCT. CONNECT PLENUM TO DIFFUSER. SEAL PLENUM TO

DIFFUSER, SEAL CLASS A. INSULATE BACKSIDE SURFACES OF DIFFUSER.

2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH DUCT , 5 FT. MAXIMUM

TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY

EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER SHAFT IN

HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQ UIRED FOR TAP FITTING TO

MAIN DUCT W ITH INTERNAL INSULATION, AND EXTENDED DAMPER SHAFT AND HANDLE

W ITH STAND-OFF TO ACCOM MODATE EXTERNAL INSULATION.

4. SPIN-IN TAP FITTING SIM ILAR TO EXCEPT NO DAM PER.

5. DUCT STRAP HANG ER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS DIFFUSER INLET UNLESS NOTED

OTHERW ISE.

8. CEILING T-BAR SUPPO RT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-BAR

TYPE FOR COMPATIBILITY W ITH DIFFUSER.

NOTES

CEILING

5 3

2 6 4 1

1. LINEAR DIFFUSER W ITH SHOP FABRICATED SHEET METAL PLENUM W ITH SAME

INTERNAL OR EXTERNAL INSULATION AS MAIN SUPPLY DUCT. CONNECT PLENUM TO

DIFFUSER. SEAL PLENUM TO DIFFUSER, SEAL CLASS A. INSULATE BACKSIDE

SURFACES OF DIFFUSER.

2. INSULATED FLEXIBLE DUCT SAME DIAMETER AS BRANCH DUCT , 7 FT. MAXIMUM

TOTAL LENGTH PER AIR DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF

FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH MANUAL DAMPER. DAMPER

SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP

FITTING TO MAIN DUCT W ITH INTERNAL INSULATIO N, AND EXTENDED DAM PER SHAFT

AND HANDLE W ITH STAND-OFF TO ACCOM MODATE EXTERNAL INSULATION.

4. SPIN-IN TAP FITTING SIM ILAR TO EXCEPT NO DAM PER.

5. DUCT STRAP HANG ER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS DIFFUSER INLET UNLESS

NOTED OTHERW ISE.

8. CEILING T-BAR SUPPO RT (FOR LAY-IN APPLICATIONS). COORDINATE AND VERIFY T-

BAR TYPE FOR COMPATIBILITY W ITH DIFFUSER.

NOTES

SUPPLY DUCT

ROUND SHEETM ETAL BRANCH DUCT

BRANCH CFM RD. DUCT SIZE

0 TO 80 CFM 6"D

81 TO 120 CFM 7"D

121 TO 200 CFM 8"D

401 TO 700 CFM 12"D

701 TO 1000 CFM 14"D

201 TO 400 CFM 10"D

CEILING RETURN OR EXHAUST

GRILLE

55 3 57 6

102RETURN OR EXHAUST DUCT

1. SHEET METAL PLENUM, FULL SIZE O F GRILLE NECK,

MINIMUM 6" TALL W ITH SAM E INTERNAL OR EXTERNAL

INSULATION AS RETURN O R EXHAUST DUCT.

CONNECT TO GRILLE. SEAL PLENUM AND

CONNECTION TO GRILLE, SEAL CLASS A.

2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH

DUCT , 5 FT. MAXIMUM TOTAL LENGTH PER AIR

DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90%

OF FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH

MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.

INTEG RAL INSULATION GUARD SLEEVE REQUIRED

FOR TAP FITTING TO MAIN DUCT W ITH INTERNAL

INSULATION. EXTENDED DAM PER SHAFT AND HANDLE

W ITH STAND-OFF REQUIRED FO R EXTERNALLY

INSULATED DUCTW ORK.

4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO

DAM PER.

5. DUCT STRAP HANGER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE

DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SIZE AS

INDICATED IN ADJACENT SCHEDULE UNLESS NOTED

OTHERW ISE ON PLANS.

8. CEILING T-BAR SUPPORT (FOR LAY-IN

APPLICATIONS). COORDINATE AND VERIFY T-BAR

TYPE FOR COMPATIBILITY W ITH GRILLE.

9. MINIMUM CENTERLINE RADIUS EQ UAL TO DUCT

DIAMETER.

10. FLEXIBLE DUCT ELBOW SUPPORT, INSTALLED W ITH

NYLO N BANDING PER MANUFACTURER'S

INSTRUCTIONS.

11. A RADIUS'D SHEET METAL ELBO W MAY BE USED IN

LIEU OF A FLEXIBLE ELBOW SUPPORT W HEN

CONNECTED DIRECTLY TO AIR DEVICE.

NOTES

ROUND SHEETMETAL BRANCH DUCT

BRANCH CFM RD. DUCT SIZE

0 TO 80 CFM 6"D

81 TO 120 CFM 7"D

121 TO 200 CFM 8"D

401 TO 700 CFM 12"D

701 TO 1000 CFM 14"D

201 TO 400 CFM 10"D

RETURN OR EXHAUST DUCT

CEILING

RETURN OR

EXHAUST GRILLE

625735

1. SHEET METAL PLENUM, FULL SIZE OF GRILLE NECK,

MINIMUM 4" TALLER THAN DUCT RUNOUT SIZE, W ITH

SAM E INTERNAL OR EXTERNAL INSULATION AS

RETURN OR EXHAUST DUCT, CONNECT TO GRILLE.

SEAL PLENUM AND CONNECTION TO GRILLE, SEAL

CLASS A.

2. FLEXIBLE DUCT, SAME DIAMETER AS BRANCH

DUCT , 5 FT. MAXIMUM TOTAL LENGTH PER AIR

DEVICE. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF

FULLY EXTENDED LENGTH.

3. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE W ITH

MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL.

INTEGRAL INSULATIO N G UARD SLEEVE REQUIRED FOR

TAP FITTING TO M AIN DUCT W ITH INTERNAL

INSULATION. EXTENDED DAM PER SHAFT AND HANDLE

W ITH STAND-OFF REQ UIRED FOR EXTERNALLY

INSULATED DUCTW ORK.

4. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO

DAM PER.

5. DUCT STRAP HANG ER. ATTACH TO STRUCTURE.

6. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE

DUCT IS LONGER THAN 4 FT.

7. ROUND SHEET METAL BRANCH DUCT, SIZE AS

INDICATED IN ADJACENT SCHEDULE UNLESS NO TED

OTHERW ISE ON PLANS.

8. CEILING T-BAR SUPPO RT (FOR LAY-IN APPLICATIONS).

COORDINATE AND VERIFY T-BAR TYPE FOR

COMPATIBILITY W ITH GRILLE.

NOTES

6" M

A X

CEILING RETURN OR EXHAUST

GRILLE

3 1 3 2 3

RETURN OR EXHAUST DUCT

1. 45 DEGREE STATIC BOOT AND M ANUAL DAMPER. INTEGRAL

INSULATION GUARD SLEEVE REQUIRED W HEN MAIN DUCT HAS

INTERNAL INSULATIO N. EXTENDED DAMPER SHAFT AND HANDLE

W ITH STAND-OFF REQUIRED FO R EXTERNALLY INSULATED

DUCTW ORK.

2. SHEET METAL DUCT, SIZE AS NOTED ON PLANS.

3. DUCT STRAP HANGER.

4. STATIC BOOT SIMILAR TO EXCEPT NO DAMPER.

5. SHEET METAL DUCT, FULL SIZE O F GRILLE NECK SIZE. CONNECT

AND SEAL DUCT TO GRILLE, SEAL CLASS A.

6. FLEXIBLE DUCT CONNECTOR.

7. CEILING T-BAR SUPPORT (FOR LAY-IN APPLICATIONS). COORDINATE

AND VERIFY T-BAR TYPE FOR COMPATIBILITY W ITH GRILLE.

NOTES

GENERAL NOTES

NOTES

A. FIRE DAMPERS SHALL BE UL LABELED.

B. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM TO NFPA 90A, SMACNA AND M ANUFACTURER'S

INSTRUCTIO NS.

C. DETAILS SHOW INSTALLATION OF FIRE DAMPER IN W ALL. DAMPER INSTALLATION IN FLOOR SIMILAR. COO RDINATE

REQ UIRED ACCESS LOCATIONS.

D. INSULATE RETAINING ANGLES FOR SYSTEMS REQUIRED TO BE INSULATED.

1. FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. VERTICAL MOUNT, GRAVITY DROP; HORIZONTAL MOUNT, SPRING LOADED TO CLO SE. REFER TO SPECS FO R VELOCITY LIMITATIONS OF EACH TYPE. REFER TO

DRAW INGS FO R STATIC OR DYNAMIC REQUIREM ENTS.

• TYPE "A" - BLADES STORED IN AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.

• TYPE "B" - BLADES STORED O UT OF AIR STREAM . RECTANGULAR, RO UND O R O VAL DUCT CONNECTION.

• TYPE "C" - HIGH VELO CITY TYPE, BLADES STORED OUT OF AIR STREAM. RECTANGULAR, ROUND OR OVAL DUCT

CONNECTION.

• TYPE "D" - HIGH VELO CITY CENTER PIVOTED MULTI-BLADE. RECTANGULAR, ROUND OR OVAL DUCT CONNECTION.

• TYPE "R" - HORIZONTAL CEILING RADIATION TYPE.

• TYPE "AA", "BB", "CC", "DD" - SAME AS "A", "B", "C", "D", EXCEPT RATED FOR 3-HRS.

2. SHEET METAL W ALL SLEEVE, SAM E M ATERIAL AS DUCT (EXCEPT GALVANIZED SHEET M ETAL FOR FIBERG LASS DUCT).

SHEET METAL GAUG E PER SMACNA. USE EXTENDED HEAVY GAUGE SLEEVES W HEN INSTALLED CO NDITION REQUIRES.

3. DUCT/SLEEVE CONNECTIO N. BREAKAW AY TYPE SHOW N. CO NNECTIO N M AY BE RIG ID TYPE IF ALLOW ED BY CO DE

AUTHORITY.

4. RETAINING ANG LE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MINIM UM OVERLAP OF W ALL OPENING. LONGER LEG M AY BE REQUIRED TO ATTAIN REQUIRED O VERLAP. BOLT, SCREW OR TACK W ELD TO W ALL SLEEVE. SPACING OF FASTENERS

PER SMACNA.

5. DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATIONS.

6. CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE.

7. HIGH VELOCITY DUCT COUPLING.

DUCT EXTENSION

AT TOP OF DAMPER

DUCT

1TYPE "B" -

FIRE RATED

W ALL O R

PARTITION

3" MIN3" MIN

4 4

ROUND/OVAL DUCT

TYPE "C" -1

2 4

8 5

2 3 6 4 9

TO AIR DEVICES

MAIN SUPPLY DUCT

1. CONICAL SPIN-IN BRANCH TAP FITTING, STRAIGHT

SIDE. INTEGRAL INSULATION GUARD SLEEVE

REQ UIRED FOR TAP FITTING TO MAIN SUPPLY DUCT

W ITH INTERNAL INSULATION.

2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS

AIR TERMINAL UNIT INLET SIZE UNLESS NOTED

OTHERW ISE.

3. INSULATED FLEXIBLE DUCT. MAXIM UM LENGTH OF

4 FT. M INIMUM LENGTH O F 4 IN. STRETCH FLEXIBLE

DUCT TO 90% OF FULLY EXTENDED LENGTH.

4. AIR TERMINAL UNIT.

5. MINIMUM FOUR HANGER RODS FO R UNIT (CORNER

PO INTS). ATTACH TO STRUCTURE.

6. TRANSITION W HEN REQUIRED.

7. MINIMUM STRAIGHT LENGTH OF DUCT SHALL BE

TERMINAL UNIT MANUFACTURER'S REQUIRED

LENGTH, BUT AT LEAST 3 TIM ES UNIT INLET

DIAMETER.

8. DUCT HANGER. ATTACH TO STRUCTURE.

9. DUCT SHALL BE FULL SIZE OF UNIT OUTLET

UNLESS NOTED OTHERW ISE ON FLOOR PLANS.

10. REHEAT COIL W HEN SPECIFIED. REFER TO COIL

DETAIL.

NOTES

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:1

A M

M501

HVAC DETAILS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

CEILING DIFFUSER DUCT CONNECTION

CEILING DIFFUSER DUCT CONNECTION

SLOT DIFFUSER DUCT CONNECTION

LINEAR DIFFUSER DUCT CONNECTION

RETURN/EXHAUST GRILLE DUCT CONNECTION

RETURN/EXHAUST GRILLE DUCT CONNECTION

RETURN/EXHAUST GRILLE DUCT CONNECTION

FIRE DAMPER NOTES

FIRE DAMPER TYPE "B"

FIRE DAMPER TYPE "C"

AIR TERMINAL UNIT DUCT CONNECTION

LAG SCREW

W OO D NAILER

4"x4"x1/4"

STEEL

PLATE

INSULATION

ROOFING

CONCRETE DECK

1. PROVIDE COUNTER-FLASHING.

2. HEAVY GAUGE CONTINUOUS SUPPORT

EXTENDS 6" BEYOND LAST EQUIPMENT

LEG. SCREW ATTACHMENT TO DECK.

3. M INIMUM 12 INCHES.

4. EXPANSION LAGS TO DECK.

5. 18 / 24 / 36 INCH HIG H INSULATED STEEL

CURB.

NOTES

AIR FLOW

AIR

FLO W

IR

LO

W

TURNING VANES

SEE FLOOR PLAN FOR

SPLIT DIM ENSION

MAIN

SUPPLY

DUCT

MANUAL VOLUME

DAMPER

SUPPLY REGISTER

ON BRANCH DUCT

SQUARE ELBOW SHOW N

PROVIDE ROUND ELBOW

W HEN SHOW N ON PLANS

AIR FLOW

IR

LO

W

W /4 OR 4"

MIN.

MAIN SUPPLY DUCT

MANUAL VOLUM E DAMPER

BRANCH DUCT

W

BRANCH DUCT TAKE-OFF

PLAN VIEW

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% O F THE MAIN DUCT CFM , AND UP TO 40% W HEN THE M AIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE

USED IN ALL OTHER CASES

BRANCH

DUCT

PLAN VIEW

W

W /4 OR 4" MIN.

PROVIDE MANUAL VO LUM E

DAMPER AT EACH BRANCH DUCT

MAIN EXHAUST OR

RETURN AIR FLOW

45 DEG.

A

IR

F L

O W

A IR FLOW

AIR FLOW

E Q

U

IP

M E

N T

AIR FLOW

TYPICAL DUCTW ORK

TRANSITION W ITH EQUIPMENT

M OUNTED IN DUCT PLAN OR

SIDE VIEW

TYPICAL DUCTW ORK

TRANSITION PLAN OR SIDE

VIEW

NOTE:

A. UNLESS OTHERW ISE INDICATED ON PLANS, M AXIMUM ANGLES SHO W N SHALL APPLY.

B. TRANSITION ANGLES IN AND OUT OF FANS SHALL BE 50% OF THO SE SHOW N ABOVE.

AIR FLOW

30 DEG. MAX

60 DEG.

MAX.

30 DEG .

M AX.

CONCENTRIC TRANSITIONS UNLESS

SHOW N OTHERW ISE ON PLANS

1. CONICAL SPIN-IN BRANCH TAP FITTING, STRAIGHT

SIDE. INTEGRAL INSULATION GUARD SLEEVE

REQ UIRED FOR TAP FITTING TO MAIN

EXHAUST/RETURN DUCT.

2. ROUND SHEET METAL BRANCH DUCT, SAME SIZE AS

AIR CO NTROL VALVE OUTLET SIZE UNLESS NOTED

OTHERW ISE. REFER TO DETAIL SCHEDULED FO R

DUCT RUNOUT SIZE REQUIRED FOR MULTI-VALVE

INSTALLATIO N.

3. EXHAUST/RETURN AIR CO NTROL VALVE.

4. CABLE SUPPO RTS. ATTACH TO STRUCTURE.

5. TRANSITION W HEN NEEDED.

6. 6" W IDE 22 GAUGE DRAW BAND W ITH 5/16" THICK x

3/4" W IDE DUCTMATE DM 440 GASKET TAPE

(BUTYL RUBBER TAPE) INSTALLED PER VALVE

MANUFACTURE'S INSTRUCTIONS.

7. SO UND ATTENUATOR, IF REQUIRED.

8. PRO VIDE M ULTI-VALVE DUCT TRANSITION FOR

MULTI-VALVE INSTALLATIO N.

9. STRAP HANGER. ATTACH TO STRUCTURE.

NOTES

1 5 6 3 8

FROM EXHAUST OR

RETURN DEVICES

RETURN DUCT

AIR CONTROL MULTI-VALVE RUNOUT SIZE

BRANCH CFM RD. DUCT SIZE

886 TO 1200 CFM 12"D

1201 TO 1780 CFM 14"D

1781 TO 2140 CFM 16"D

2141 TO 3630 CFM 24"X16" RECT.

INSULATION

DUCT

GASKET

INSULATION

SECTION "A-A"

CASING

GASKET

HANDLE INSIDE

INSULATION

FLEXIBLE

W ASHER

FACTO RY

FABRICATED

LATCH

SECTION "B-B"

NOTES:

1. LATCHES SHALL BE OF THE W EDGE TYPE TO CLOSE DO ORS

TIG HTLY

2. HINGES O N THE ACCESS DO ORS SHALL HAVE NON-CORRO SIVE

PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS DOOR

ACCESS PANEL

MAX. DUCT DIA.

INCHES [M M]

QUANTITY / SIZE

INCHES [MM]

MAX. LO AD

LBS. [MM]

MAX. SPACING

INCHES [MM]

26 [650] ONE 1 [25] x 22 GA. STRAP 260 [119] 144 [3600]

36 [900] ONE 1 [25] x 18 GA. STRAP 420 [190] 144 [3600]

50 [1250] ONE 1 [25] x 16 GA. STRAP 700 [317] 144 [3600]

60 [1500] TW O 3/8 [10] DIA. RODS 1320 [598] 144 [3600]

84 [2100] 2500 [1133] 144 [3600]TW O 1/2 [13] DIA. RODS

HANGER STRAPS OR RODS

NOTE:

TABULATED DATA FROM SM ACNA

ALLOW S FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LO AD.

LOAD RATED

FASTENERS

BAND OF SAM E

SIZE AS HANGER

STRAP

50" [1250m m] DIA.

AND UNDER

HANGER RODSS

BAND

OVER 50"

[1250m m] DIA.

MOTORSHAFT

TYPICAL STRUCTURAL

STEEL MEMBER

FOR EQUIPMENT

DRIVEN

EQUIPMENT

NUMBER OF ISOLATION

UNITS AS REQUIRED

SECTION A-A

TYPE "B"

W ELDED STEEL BASE

REINFORCING BARS

ANCHOR

BOLT

SLEEVE

STRUCTURAL

STEEL FRAME

SPRING

ISOLATOR

DRIVEN

EQUIPMENT

ALL W ELDED

STEEL FRAMEW ORK

MOTORSHAFT

TYPICAL STRUCTURAL

STEEL MEMBER FOR

EQUIPMENT

NUMBER OF ISOLATION

UNITS AS REQUIRED

TYPE "1"

CONCRETE INERTIA BASE

DUCT RISER - SEE FLOOR

PLANS FOR SIZES

EXTEND ANGLE 3"

[75mm ] BEYO ND DUCT

FLOOR

SEAL HOLE W ITH FIREPRO OFING

MATERIAL AFTER DUCT INSTALLATION

SHEET METAL SCREW S 4"

[100mm ] ON CENTER

1-1/2" x 1/2"x1/8" [40x40x3m m]

ANGLE INSTALL ON BO TH LONG

DIMENSIO N SIDES OF DUCT. FOR

DUCTS OVER 60" [1500mm] USE 2"x2"x1/8" [50x50x3mm] ANGLE

HOLE IN STRUCTURAL FLOOR

DUCT RISER

0.5 INCH W G [125Pa] TO 2 INCHES W G [500Pa] DUCT RISER SUPPORT

2 INCHES W G [500Pa] TO 4 INCHES W G [1000Pa] DUCT RISER SUPPO RT

DUCT RISER - SEE FLOOR

PLANS FOR DETAILS

2"x2"x1/4" [50x50x6mm]

ANGLE INSTALL ON BOTH LONG

DIMENSIO N SIDES OF DUCT

SEAL HOLE W ITH FIREPRO OFING

MATERIAL AFTER DUCT INSTALLATION

HOLE IN STRUCTURAL FLOOR

DUCT RISER

FLOOR

ARRANGE RISER SO

REINFORCER TRANSVERSE JOINT

IS AT RISER SUPPORT POINT

NOTE:

ALL DUCTW ORK RISERS W HICH ARE RUN EXPO SED, SUCH AS THRU ATTIC FLOORS

AND FAN ROO M FLOORS SHALL BE PROVIDED W ITH A 3" [75mm] HIGH CONCRETE

CURB AROUND OPENING FOR DUCT.

ALL THREAD

ROD. MINIMUM

3/8" [10mm] DIA.

GALVANIZED ANGLE

IRON OR EQUIVALENT

STRENGTH CHANNEL

INSULATION

NOTE:

1. PRO VIDE BRACING TO LIMIT THE AMPLITUDE OF W ALL VIBRATION AND W ALL

DEFLECTION TO SPECIFIED MAXIMUMS.

2. MINIMUM BRACING REQUIREMENTS:

MAXIM UM DUCT W IDTH

INCHES [mm]

UP TO 26 [650]

27 [675] TO 40 [1000]

41 [1000] TO 60 [1500]

61 [1500] TO 72 [1800]

MAXIMUM SIZE ANG LE

INCHES [mm]

NONE

1-1/2x1-1/2x3/1/16 [40x40x7] 2x2x3/16 [50x50x7] 2x2x3/16 [50x50x7]

MAXIMUM SPACING

INCHES [mm]

NONE

72 [1800] 48 [1200] 24 [600]

3. INSULATION: FOR COLD DUCTS INSULATE BRACES AND PROVIDE VAPOR BARRIER.

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:2

A M

M502

HVAC DETAILS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

ROOF EQUIPMENT SUPPORT

SUPPLY DUCTWORK TAKE-OFFS

EXHAUST OR RETURN BRANCH DUCTWORK

DUCTWORK TRANSITIONS

EXHAUST AIR CONTROL VALVE DUCT CONNECTION

ACCESS PANEL AND DOOR DETAIL

ROUND DUCT HANGERS

VIBRATION ISOLATION BASES

DUCT RISER SUPPORTS

SCALE: 1" = 1'-0"

FLAT OVAL DUCT HANGERS

4" MIN

14" MIN

20" MIN

NOTES

1. AIR HANDLING UNIT/CASING.

2. HUMIDIFIER SUPPORTS PER AHU AND HUMIDIFIER

MANUFACTURER'S INSTRUCTIONS.

3. BLANKED OFF AREA IF REQUIRED BY THE HUMIDIFIER

MANUFACTURER. LOCATION OF HUMIDIFIER SHALL BE

COORDINATED WITH AIR HANDLER MANUFACTURER,

SUCH THAT THE BLANK OF AREAS DON'T AFFECT

AIRFLOW ON OTHER COMPONENTS. BLANK OFFS

SHALL BE MINIMUM 18 GAUGE STAINLESS STEEL.

4. AHU BASE RAIL AND CURB.

5. STEAM DISTRIBUTORS. VERTICAL SHOWN, HORIZONTAL

SIMILAR. SPACING, QUANTITIES, ETC... PER EQUIPMENT DATA.

6. INCREASE INSTALLATION DIMENSIONS IF REQUIRED BY

HUMIDIFIER MANUFACTURER.

7. FULL SIZE DIRT LEG, BUT MINIMUM 0.75" SIZE, WITH DRAIN

VALVE AND HOSE CONNECTION.

8. SECOND CONDENSATE RETURN CONNECTION WHEN

RQEUIRED BY HUMIDIFIER MANUFACTURER. PIPE

INDEPENDENTLY SAME AS ONE SHOWN, TRAP DISCHARGE TO

CONDENSATE RETURN MAIN.

9. SLEEVE AND FOAM AIR TIGHT ALL PIPING PENETRATIONS.

PROVIDE STAINLESS STEEL ESCUTCHEONS FOR NEAT

APPEARANCE.

10. REFER TO HUMIDIFIER PIPING DETAIL.

FLOOR

SUPPLY HEADER

CONDENSATE HEADER

10 3

NOTES

"a"

1. STEAM DISTRIBUTORS. SPACING, QUANTITIES, ETC.

PER EQUIPMENT DATA.

2. F&T STEAM TRAP WHEN HUMIDIFIER MOUNTED IN

DUCTWORK ABOVE CEILINGS. BUCKET TRAP WHEN

MOUNTED IN EXPOSED AREAS SUCH AS MECHANICAL

ROOMS.

3. MOUNT STEAM SIDE STRAINER SUCH THAT STRAIN IS

ON ITS SIDE IN A HORIZONTAL POSITION.

4. AUTOMATIC MODULATING CONTROL VALVE FURNISHED

BY HUMIDIFIER MANUFACTURER, PROVIDE MULTIPLE VALVE

WHEN SPECIFIED.

5. AUTOMATIC 2-POSITION CONTROL VALVE, BY HUMIDIFIER

MANUFACTURER.

6. LINE SIZE AUTOMATIC 2-POSITION CONTROL VALVE

FOR SEASONAL OR SAFETY SHUT-OFF.

7. EXTEND CONDENSATE RETURN PER PLANS.

8. TEMPERATURE SWITCH.

9. TUBULETS PERPENDICULAR TO AIRFLOW.

10. SHUT-OFF VALVE.

11. WHEN DIMENSION "A" EXCEEDS 10 LINEAR FEET,

PROVIDE DRIP LEG AND TRAP ASSEMBLY PER ABOVE.

REFER TO TYPICAL

STEAM DRIP ASSEMBLY

TO CONDENSATE

RETURN MAIN

REFER TO BELOW FOR

HUMIDIFIER PIPING

STEAM SUPPLY MAIN

CONDENSATE RETURN MAIN

STEAM SUPPLY MAIN

1. STEAM MAIN (30 PSIG AND BELOW ).

2. INVERTED BUCKET TRAP W ITH BIMETALLIC

THERMAL ELEM ENT FOR AIR REMOVAL, 0.75" SIZE

UNLESS NOTED O THERW ISE.

3. COLLECTING POCKET AND DIRT LEG SAME SIZE AS

MAIN.

4. LENGTH FROM INVERT OF MAIN TO DRAIN PIPE, 1.5

x MAIN DIAMETER, 8" MINIMUM .

5. CONDENSATE RETURN, FULL SIZE OF TRAP

DISCHARGE, 0.75" MINIMUM .

6. 0.75" DRAIN VALVE W ITH HOSE CONNECTION.

7. 0.75" TEST VALVE AND DRAIN W ITH HOSE

CONNECTION.

NOTES

3 6 7

IB

4" M

IN

P

P

5 1

8 22

1. PUM P W ITH FLANGED CONNECTIONS.

2. SPRING HANG ER.

3. TURNBUCKLE ADJUSTMENT.

4. BALANCING VALVE, SIZED FOR 3 TO 5 FT. HD.

W PD AT FULL PUMP GPM. PROVIDE REDUCERS

IN AND OUT. FOR PUMPS FITTED W ITH AN

ADJUSTABLE FREQ UENCY MOTOR CONTROLLER

LEAVE THE BALANCING VALVE FULL OPEN.

5. REDUCER W HEN PUMP CONNECTION SIZE

DIFFERS FROM PIPE SIZE.

6. LEAVE SPACE TO ALLOW M OTOR TO BE PULLED.

7. DRAIN VALVE W ITH HOSE CO NNECTIO N.

8. PRESSURE GAUGE W ITH INTERCONNECTING

PIPING AND VALVES.

TYPICAL - - TYPICAL

NOTES

2"

2" 3"

3"

3"

3"

2"

STEAM

MAIN

0.75"

N.C. N.C.

0.75"

V D

1. MINIMUM 10 PIPE DIAMETERS.

2. 0.75" DRIP ASSEM BLY W ITH INVERTED BUCKET TRAP W ITH

BIMETALLIC THERM AL ELEMENT FOR AIR REMOVAL. REFER

TO TYPICAL DETAIL.

3. 0.75" DRIP ASSEM BLY W ITH INVERTED BUCKET TRAP W ITH

BIMETALLIC THERM AL ELEMENT FOR AIR REMOVAL. REFER

TO TYPICAL DETAIL.

4. STEAM SIDE STRAINERS SHALL BE MOUNTED W ITH THE

STRAINER INSTALLED ON ITS SIDE IN A HORIZONTAL

PO SITION, TYPICAL.

5. 1" GLO BE VALVE IN EMERGENCY BYPASS.

6. PRESSURE SENSING LINE W ITH NEEDLE VALVE.

7. 0.75" DRAIN VALVE.

8. EXTEND TO CONDENSATE RETURN SYSTEM AS SHOW N ON

DRAW INGS.

9. SAFETY RELIEF VALVE SET AT __ PSIG. SIZE TO RELIEVE

FULL CAPACITY OF PRESSURE REDUCING VALVE O R

BYPASS VALVE (W HICH EVER IS GREATER) AT AN INLET

PRESSURE EQUAL TO THE SAFETY RELIEF VALVE SETTING

OF THE INCOMING STEAM SYSTEM.

10. DRIP PAN ELBOW ASSEMBLY. EXTEND DRAIN LINE TO

FLOOR DRAIN.

11. VENT PIPE SHALL BE MINIMUM 1 PIPE SIZE LARGER THAN

INLET, AND EXTENDED TO THE OUTDOORS PER ASME AND

AS SHOW N ON THE DRAW INGS. INCREASE PIPE SIZE IF

DETERMINED BY SRV SUPPLIER THAT VENT PRESSURE

DROP EXCEEDS THE ALLOW ABLE BACK PRESSURE.

12. STEAM PRESSURE REDUCING VALVE W ITH PILOT AND

RELATED CONTRO L TUBING. REFER TO EQUIPMENT DATA

FOR CAPACITY AND OTHER SIZING INFORM ATION.

13. MOISTURE SEPARATOR AND 0.50" DRIP ASSEMBLY W ITH __

TRAP.

FOB

FOB

NOTES

HANGER ROD

INSULATION (VAPO R

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

PROVIDE HIGH COM PRESSIVE

STRENGTH INSULATION (9 PSF M IN.

DENSITY) UNDER INSULATION SHIELD

INSULATION SHEILD

AT HANGER

W ELD

SADDLE

ADJUSTABLE CLEVIS HANG ER TYPE 1 -

SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 -

SEE SPECIFICATIONS

PROVIDE INSULATION SHEILD

& INSERT FOR ALL PIPING

(200mm [8"] M IN.)

15m m [½"] DIA.

HANGER RODS W ITH

900mm [36"] MAX.

SPACING ON EACH

CHANNEL

BAND

43m m [1-⅝ "] 12 GAUGE CHANNEL O R 50x50x6.4mm [2"x2"x¼"] ANGLE m m [1

M

A X

S IDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000lb.] UNIFORM LOAD

[1]

[1¼]

THRU 20

[THRU ¾]

[1½]

[2½]

[2]

[3]

[4]

[5]

[6]

[10]

[10]

[12]

[14]

[16]

[18]

[20]

[24]NOM. SIZE

[7]

[7]

[7]

[9]

[11]

[10]

[12]

[14]

[16]

[17]

[19]

[22]

[23]

[25]

[27]

[28]

[30]

[32]PIPE

[6]

[7]

[5]

[8]

[9]

[8]

[10]

[12]

[13]

[14]

[16]

-TUBING

mm

[IN]

mm

[FT]

mm

[FT]

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

MAXIMUM PIPE/TUBING SUPPO RT SPACING

NOTE:

SEE SPECIFER FOR DETAILED HANGER REQUIREM ENTS

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:2

A M

M503

HVAC DETAILS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

30 PSIG AND LOWER STEAM DRIP ASSEMBLY

PIPE MOUNTED PUMP

SINGLE STAGE STEAM PRESSURE REDUCING STATION

(DUAL PUMPS SHOWN, SINGLE PUMP SIMILAR)

AHU STEAM INJECTION HUMIDIFIER

HUMIDIFIER PIPING DETAIL

PIPE HANGERS

1. LOCATE STRAINER W ITH BLOW -DO W N VALVE AND HOSE

CONNECTION AT LOW POINT OF COIL PIPING.

2. PIPE REDUCER IF REQUIRED.

3. FULL RUN-OUT PIPE SIZE.

4. INSULATE FIRST 6" NEXT TO COIL.

5. MINIMUM 18" LONG BRAIDED STAINLESS STEEL FLEXIBLE

PIPE CONNECTOR.

6. MAXIMUM DISTANCE FROM SUPPLY AND RETURN SHUT-

OFF VALVES TO COIL IS 48".

7. FACTORY ASSEMBLED PIPING PACKAG E (OPTIONAL).

8. LINE SIZE START-UP/FLUSHING BYPASS.

9. OPTION 2 MAY ONLY BE USED W ITH A FACTORY PIPING

PACKAGE THAT IS FACTORY MO UNTED RIGIDLY TO THE

TERM INAL UNIT.

10. PIPING SAM E SIZE AS AUTO CONTROL VALVE O R CO IL

CONNECTION, W HICHEVER IS LARGER.

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING

UNLESS NOTED OTHERW ISE.

B. REFER TO AIR TERM INAL UNIT SCHEDULE FOR AUTOMATIC

CONTROL VALVE SIZE.

C. REFER TO SPECIFICATIO NS FOR DEVICES NOT TO BE

INSULATED. INSULATED DEVICES SHALL INCLUDE EXTENDED

NECKS, SHAFTS, ETC... SO THEY ARE ACCESSIBLE ABO VE THE

INSULATION.

HW R

HW S

M

COIL

5 23

NOTES

GENERAL NOTES

18" MIN

48" MAX

18" MIN

N.C.

HW R

HW S

M

COIL

6" MIN

48" MAX

6" MIN

2N.C.

OPTION 1

OPTION 2 9

1. LOCATE STRAINER W ITH BLOW -DOW N VALVE AND HOSE

CONNECTION AT LOW POINT OF CO IL PIPING .

2. PIPE REDUCER IF REQUIRED.

3. FULL RUN-OUT PIPE SIZE.

4. INSULATE FIRST 6" NEXT TO COIL.

5. MINIMUM 18" LONG BRAIDED STAINLESS STEEL FLEXIBLE

PIPE CONNECTOR.

6. MAXIMUM DISTANCE FROM SUPPLY AND RETURN SHUT-

OFF VALVES TO COIL IS 48".

7. UNION OR SCREW ED VALVE FITTING.

8. TRUE "T" FITTING (NOT A PORT OFF AN ACCESSORY).

9. FACTORY ASSEMBLED PIPING PACKAGE (OPTIONAL).

10. LINE SIZE START-UP FLUSHING BYPASS.

11. OPTIO N 2 MAY ONLY BE USED W ITH A FACTORY PIPING

PACKAGE THAT IS FACTORY MOUNTED RIGIDLY TO THE

TERMINAL UNIT.

12. PIPING SAM E SIZE AS AUTO CONTROL VALVE OR COIL

CONNECTION, W HICHEVER IS LARGER.

A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING

UNLESS NOTED O THERW ISE.

B. REFER TO AIR TERM INAL UNIT SCHEDULE FOR AUTOMATIC

CONTRO L VALVE SIZE. VERIFY VALVE PORTING AND

CONNECT PIPING TO PROPER PORTS, PER

MANUFACTURER'S RECOMMENDATIONS.

C. REFER TO SPECIFICATIONS FOR DEVICES NOT TO BE

INSULATED. INSULATED DEVICES SHALL INCLUDE

EXTENDED NECKS, SHAFTS, ETC... SO THEY ARE

ACCESSIBLE ABO VE THE INSULATION.

HW R

HW S

COIL

5 2

M

NOTES

GENERAL NOTES

18" MIN

48" MAX

18" MIN

3N.C.

HW R

HW S

COIL

M

6" MIN

48" MAX

6" MIN

N.C. 10

OPTION 1

OPTION 2 11

1. AUTOM ATIC TW O-PO RT CONTROL

VALVE. NORMALLY OPEN THRU COIL.

2. 0.5" DRAIN VALVE.

3. PIPE REDUCER IF COIL CONNECTION

DIFFERS FROM PIPE SIZE.

4. LEAVE W IDE OPEN UNLESS NEEDED

TO EVENLY DISTRIBUTE FLOW THRU

COILS OR TO BALANCE PUMP GPM .

5. COIL RECIRCULATING PUMP.

A. ALL PIPING SHALL BE FULL SIZE OF MAIN

RUN-OUT PIPING UNLESS NOTED

OTHERW ISE. BRANCH PIPING TO EACH

COIL ONE SIZE SMALLER THAN M AIN RUN-

OUT PIPING , BUT NO SMALLER THAN CO IL

CONNECTION SIZE.

B. REFER TO AIR HANDLING UNIT SCHEDULE

FOR AUTOMATIC CONTROL VALVE SIZE.

H W

S

H W

R

AIR

FLOW

AIR

FLOW

M

NOTES

GENERAL NOTES

1. AUTOM ATIC TW O -PO RT CONTROL VALVE.

NORMALLY CLOSED THRU COIL.

2. 0.5" DRAIN VALVE.

3. PIPE REDUCER IF COIL CONNECTION

DIFFERS FROM PIPE SIZE.

4. DRAIN PAN.

5. DRAIN PIPE, SAME SIZE AS PAN

CONNECTION, W ITH DEEP SEAL TRAP.

REFER TO CONDENSATE DRAIN PIPING

DETAIL.

6. LEAVE W IDE OPEN UNLESS NEEDED TO

EVENLY DISTRIBUTE FLOW THRU COILS.

7. COOLING COIL BO OSTER PUMP. REFER

TO INLINE PUMP DETAIL.

8. BALANCING VALVE, SIZED FOR 3 TO 5 FT.

HD. W PD AT FULL PUMP GPM. PROVIDE

REDUCERS IN AND OUT. FO R PUM PS

FITTED W ITH AN ADJUSTABLE

FREQUENCY M OTOR CONTROLLER

LEAVE THE BALANCING VALVE FULL

OPEN.

9. SHUT-OFF, CHECK AND BALANCING

VALVES MAY BE COMBINED INTO A

SINGLE TRIPLE DUTY VALVE (OPTIONAL).

A. ALL PIPING SHALL BE FULL SIZE O F MAIN RUN-

OUT PIPING UNLESS NOTED OTHERW ISE.

BRANCH PIPING TO EACH COIL ONE SIZE

SMALLER THAN MAIN RUN-OUT PIPING, BUT NO

SMALLER THAN COIL CO NNECTION SIZE.

B. REFER TO AIR HANDLING UNIT SCHEDULE FOR

AUTOM ATIC CONTROL VALVE SIZE.

C H

R

C H

S

AIR

FLOW

AIR

FLOW

M

D

3 6

NOTES

GENERAL NOTES8

BLOW -THRU UNIT

DRAW -THRU UNIT

1. DRAIN PIPE, SAME SIZE AS UNIT DRAIN PAN

CONNECTIO N.

2. VERIFY REQUIRED HEIGHT FOR DRAIN PIPE AND

TRAP INSTALLATION. PROVIDE ADDITIO NAL BEAMS

OR BACK-TO-BACK CHANNELS UNDER UNIT, IF

REQ UIRED, TO ATTAIN REQUIRED HEIGHT.

3. TEE W ITH CLEANOUT PLUG.

4. 1" CENTERLINE-TO-CENTERLINE DIMENSION.

5. CENTERLINE-TO-CENTERLINE DIMENSION NOT

LESS THAN SUPPLY FAN T.S.P. (INCH W .G.) + 1/2

INCH.

6. CENTERLINE-TO-CENTERLINE DIMENSION NOT

LESS THAN SUPPLY FAN T.S.P. (INCH W .G.) + 1 INCH.

7. CENTERLINE-TO-CENTERLINE DIMENSION SHALL BE

50% OF DIMENSIO N FOUND IN ABOVE.

8. CONCRETE HOUSEKEEPING PAD.

NOTES

FLO OR DRAIN

A.H. UNIT

A.H. UNIT

FLO OR DRAIN

P: 937-224-0861 www.heapy.com

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Departm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

PROJECT NO. 2019-05201

D a y d a ta

\H e a p y D o c u m e n ts

\l d ri c h te r\

M y D o c u m e n ts \2

-0

-M E

P -C e n tr a l_ ld ri c h te r.

rv t

/2

/2

:5

:3

A M

M504

HVAC DETAILS

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

SUITE 200

INDIANAPOLIS, INDIANA 46202

317.800.6388

HEAPY

1400 W. DOROTHY LANE

DAYTON, OH 45409

937.224.0861

RELOCATE NUCLEAR MEDICINE

SERVICES FOR CENTRALIZED

SERVICES

INDIANAPOLIS, IN

583-20-102

01/28/2021 JPR LDR

BID DOCUMENTS

FULLY SPRINKLERED

AIR TERMINAL UNIT REHEAT COIL/DUCT HEATING COIL

AIR TERMINAL UNIT REHEAT COIL/DUCT HEATING COIL

A.H. UNIT HOT WATER COILS

A.H. UNIT CHILLED WATER COILS

AIR HANDLING UNIT DRAIN PIPING-FLOOR MOUNTED

NOTES

1. 15" M ERV 11 BAG TYPE PRE-FILTERS.

2. SUPPLY FAN ARRAY (4 FANS TOTAL).

3. BAROM ETRIC FAN INLET DAM PERS (4).

4. UVG I LIG HTS.

5. AIR BLENDER MOTORIZED BYPASS DAM PER.

6. RETURN AIR OPENING (78" x 30") W ITH UL555C SMOKE

RATED RETURN AIR ISOLATION DAMPER.

7. MAX. OUTDOOR AIR MEASURING IAQ DAMPERS (17,000

CFM ).

8. MIN. OUTSIDE AIR M EASURING IAQ DAM PERS (15,000 CFM).

9. SUPPLY AIR OPENING (86" x 30") W ITH UL555C SM OKE

RATED SUPPLY AIR ISO LATION DAMPER.

10. SERVICE RECEPTICLE.

11. SUPPLY FAN VFDs, ONE PER FAN.

12. COOLING COILS.

13. HUMIDIFIER HEADER ASSEMBLY AND DISPERSION TUBES.

REFER TO SCHEDULE.

14. STAINLESS STEEL DRAIN PAN.

15. PRE-HEATING COILS.

16. AIR BLENDERS. REFER TO SCHEDULE.

17. 12" M ERV 14 HIGH EFFICIENCY CARTRIDG E TYPE FINAL

FILTERS.

18. VAPOR TIGHT LED LIGHTING FIXTURE (TYPICAL).

19. PRO VIDE M ECHANISM FO R M OTOR REMOVAL THROUGH

AHU ACCESS DOOR. COMPONENTS SHALL BE DESIGNED

TO REMO VE FAN EQUIPMENT THROUGH STANDARD SIZE

ACCESS DOOR.

20. AHU ACCESS DOOR W ITH VIEW ING W INDOW (TYPICAL).

21. AHU INTERNAL LIGHT SW ITCH.

22. 6" CONCRETE HO USEKEEPING PAD.

23. W ET SECTIONS OF AIR HANDLING UNIT SHALL BE

CONSTRUCTED OF 304 STAINLESS STEEL.

GENERAL NOTES

A. UNIT SHALL BE DESIGNED AND SHIPPED AS A KIT FO R

KNO CKDOW N ASSEM BLY ON-SITE.

B. COORDINATE ACCESS DOOR LOCATIONS AND COIL

PULL ACCESS W ITH EXISTING STRUCTURAL CO LUM NS

IN MECHANICAL ROO M. APPROXIMATE COLUMN

LOCATIONS ARE SHOW N ON DRAW INGS - VERIFY AND

COORDINATE UNIT LAYOUT TO MAINTAIN REQUIRED

FIT AND CLEARANCES.

C. REFER TO AHU SCHEDULE ON DRAW INGS AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

D. OVERALL UNIT D IMENSIONS SHOW N SHALL BE

MAINTAINED.

4 12 13 15 117 16

MECH. ROOM FLOOR

132"

111"

432"

FAN DISCHARGE VIEW FAN INLET VIEW

NOTES

1 DUCT MO UNTED MOTORIZED ISOLATION DAMPER.

2 ROOF SUPPORT CURBS, 24" HIG H. FLASH INTO ROOFING SYSTEM.

3 EXHAUST STACK, SAME MATERIAL AS SYSTEM DUCTW ORK. PRIM E AND PAINT.

4 FLEX CONNECTION.

5 BLIND FLANG E CONNECTION, SLOPED TO DRAIN OUTLET.

6 3/4" PVC DRAIN OUTLET TO SPILL ONTO CONCRETE SPLASH BLOCK OR NEARBY ROOF DRAIN .

7 GUY W IRES PER SMACNA.

8 TRANSITION DUCT STACK TO ALLOW LAST 2'…