Tab 10 Amendment 004 Attachment RFI 016 - Limited Hazmat Survey Report.pdf

PDF 2 MB Posted

Attached to
Nix Federal Building & Courthouse Renovation Project
Solicitation number
47PD0120R0027
Issued by

About this file

This solicitation is for renovation services at the Robert N.C. Nix Federal Building in Philadelphia. General Services Administration seeks to renovate approximately 47,000 square feet of former Post Office space on the first floor and mezzanine level. Renovations will be guided by plans and specifications prepared by Mills & Schnoering Architect Engineer dated April 10, 2020. The six-story masonry building houses the U.S. Bankruptcy Courts, U.S. Immigration and Customs Enforcement, U.S. District Courts, and Executive Office of Immigration Review. Interested offerors should attend the pre-proposal conference call on May 5, 2020 or register with the contracting officer representative. Proposals must be submitted by May 29, 2020 at 4:00pm Eastern time.

View the file

Other files

File Type Posted
Tab 10 Amendment 0010 SF30 2020 06 11.pdf PDF
Tab 10 Amendment 0010 Attachment RFI Log 2020 06 11.pdf PDF
Tab 10 Amendment 009 SF30 2020 06 09.pdf PDF
Tab 10 Amendment 009 Attachment RFI Log 2020 06 08.pdf PDF
Tab 10 Amendment 009 Attachment TY 600 and TY 610.pdf PDF
Tab 10 Amendment 008 RFI Log 2020 06 05x.pdf PDF
Tab 10 Amendment 008 SF30 2020 06 05.pdf PDF
Tab 10 Amendment 008 RFI Log 2020 06 05.pdf PDF
Tab 10 Amendment 008 M and S spec and drwg changes memo 2020 06 03.pdf PDF
Tab 10 Amendment 008 revised sf1442 2020 2020 06 05.pdf PDF
Tab 10 Amendment 007 Questionnaire.pdf PDF
Tab 10 Amendment 007 SF30 2020 05 28.pdf PDF
Tab 10 Amendment 006 SF30 2020 05 27.pdf PDF
Tab 10 Amendment 006 Attachment RFI Log Revised 2020 05 26.pdf PDF
Tab 10 Amendment 006 Attachment Block H - Air Handlers 2020 05 27.pdf PDF
Tab 10 Amendment 006 Attachment RFI Log 62 Vault Constr 2020 05 26.pdf PDF
Tab 10 Amendment 005 SF30 2020 05 20.pdf PDF
Tab 10 Amendment 005 Attachment RFI Log Revised 2020 05 20.pdf PDF
Tab 10 Amendment 004 Attachment RFI 006 - Design Phase Commissioning Report.pdf PDF
Tab 10 Amendment 004 SF30 2020 05 15.pdf PDF
Tab 10 Amendment 004 Attachment RFI 016 - Supplemental Asbestos Survey Report - Floor survey.pdf PDF
Tab 10 Amendment 004 Attachment RFI Log 2020 05 15.pdf PDF
Tab 10 Amendment 003 SF30 2020 05 12.pdf PDF
Tab 10 Amendment 002 info Pre-Bid Conf Attendence 2020 05 05.pdf PDF
Tab 10 Amendment 002 SF30 2020 05 06.pdf PDF
Tab 10 Amendment 002 info Blank ROCAL Sheet.xlsx XLSX spreadsheet
Tab 10 Amendment 002 info Vendor Training Manual.pdf PDF
Tab 10 Amendment 002 info Project Standards and Finishes March 2020 (1).pdf PDF
Tab 10 Amendment 002 info Blank CIW Form.docx DOCX document
Tab 09 Agenda 2020 05 05.pdf PDF
Tab 10 Amendment 0001 Photos Block E - Interior Loading Dock 35.pdf PDF
Tab 10 Amendment 0001 SF30 2020 05 01.pdf PDF
Tab 10 Amendment 0001 Photos Video - Interior Workspace and Warehouse.mp4 MP4 file
Tab 10 Amendment 0001 Photos Block C - Side Office Area 33.pdf PDF
Tab 10 Amendment 0001 Photos Block F - Bulk Mail Area 42.pdf PDF
Tab 10 Amendment 001 RFI Log 2020 05 01.xlsx XLSX spreadsheet
Tab 10 Amendment 0001 Photos Block B - Lobby 35.pdf PDF
Tab 10 Amendment 0001 Photos Block A - External 50.pdf PDF
Tab 10 Amendment 0001 Photos Block D - Inside Transaction Windows 52.pdf PDF
Tab 10 Amendment 0001 Photos Block G - Mezzanine 29.pdf PDF
Tab 10 Amendment 0001 Photos Video - Public Lobby.mp4 MP4 file
Tab 05 Wage Rate at Solicitation 2020 04 17.pdf PDF
Tab 10 Reps and Certs 2020 03 11.pdf PDF
Tab 10 sf1442 w sol 2020 2020 04 17.pdf PDF
Tab 02 Drawings Final CD 2020 04 10.pdf PDF
Tab 10 Solicitation 2020 04 17.pdf PDF
Tab 10 Agreement 2020 04 17.pdf PDF
Tab 02 Specifications Final CD 2020 04 10.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LIMITED HAZMAT SURVEY REPORT

For

Exterior Ramp Entrance Project

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Prepared For:

Mills + Schnoering Architects, LLC

200 Forrestal Road, Suite 3A Princeton, NJ, 08540

Prepared By:

Langan Engineering and Environmental Services, Inc.

30 South 17th Street, Suite 1300

Philadelphia, PA 19103

Vijay Patel

Senior Associate

July 18, 2019

Langan Project No. 270054302

Limited Hazmat Survey Report

Exterior Ramp Entrace Project

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

TABLE OF CONTENTS

Page No.

ACRONYMS

EXECUTIVE SUMMARY

PROJECT INFORMATION:

1.0 INTRODUCTION

2.0 SITE DESCRIPTION

3.0 HAZMAT FINDINGS

3.1 Terminology

3.2 Survey Methodology

3.3 Files Reviewed

4.0 OBSERVATIONS AND FINDINGS

4.1 Asbestos-Containing Materials

4.2 Lead Based paint

4.3 PCB in Caulk

5.0 CONCLUSIONS AND RECOMMENDATION

5.1 Asbestos Containing Materials

5.2 Lead Based Paint

5.3 PCB in Caulk

6.0 LIMITATIONS, EXCEPTIONS AND ASSUMPTIONS

TABLES

Table 1 Summary of Asbestos Survey Findings

Table 2 Lead based paint XRF Screening Data

Table 3 Summary of Caulk Sample PCB Analysis Results

DRAWINGS

ASL-1 Asbestos Sampling Locations

LSL-1 XRF Lead Containing Paint Sampling Locations

APPENDICES

Appendix A Laboratory Test Results and Chain of Custody Documentations (Asbestos)

Appendix B Laboratory Test Results and Chain of Custody Documentations (PCB)

Appendix C Langan’s Certifications and Laboratory Accreditations

Appendix D June 2016 ACM Report by EA Engineering, Science, and Technology, Inc.

ACRONYMS

USEPA United States Environmental Protection Agency

AHERA Asbestos Hazard Emergency Response Act

OSHA Occupational Safety and Health Administration

CAA Clean Air Act

CFR Code of Federal Regulation

EPA United States Environmental Protection Agency

HEPA High Efficiency Particulate Air

HUD United States Department of Housing and Urban Development

NESHAPS National Standards for Hazardous Air Pollutants

RCRA Resource Conservation and Recovery Act

PLM Polarized Light Microscopy

TEM Transmission Electron Microscopy

ACM Asbestos-Containing Materials

LBP Lead-Based Paint

PCB Polychlorinated Biphenyls (PCB)

SF Square Feet

LF Linear Feet

CY Cubic Yard mg/cm2 Milligrams per square centimeter

XRF X-ray Fluorescence

AAS Atomic Absorption Spectrometry

TCLP Toxicity Characteristic Leaching Procedure

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302

EXECUTIVE SUMMARY

Langan Engineering and Environmental Services, Inc. (Langan) has prepared this limited hazardous materials (Hazmat) survey report for the Exterior Ramp Entrance Project at the Robert

N.C. Nix Federal Building, 900 Market Street, Philadelphia, Pennsylvania. The survey was limited to the north and south revolving door entrances on the 9th Street and side door entrance on the

Market Street of the subject building. The objective of this Hazmat Survey was to identify the presence/absence of asbestos-containing materials (ACM), lead-based paint (LBP), and

Polychlorinated Biphenyls (PCB) containing caulk in the spaces surveyed.

PROJECT INFORMATION:

Client Name:

Mills + Schnoering

Architects, LLC Survey Dates: June 5, 2019

Professional’s

Project #:

270054302 Construction Dates: 1937

Professional’s

Project Manager:

Vijay Patel No. Buildings: 1

Phone No.: 973-560-4983 No. of Stories: 7 plus Penthouse

Email: vpatel@langan.com Estimated Area

Surveyed:

62,500 rentable square feet (RSF)

Property Address: 2905-2935 North 16th Street Basement: Full

Property Town, County, State:

Philadelphia, PA 19132 Property Use: Government Offices

The following summarizes the Hazmat findings for the spaces surveyed:

Asbestos-Containing Materials (ACM)

Asbestos was not detected in the suspect materials identified in spaces surveyed. Refer to

Table 1 for a detailed summary of asbestos survey findings.

Lead Containing Paint (LCP)

As per 40 CFR Part 745, TSCA, Title IV (Lead Exposure Reduction), the term ‘‘lead-based paint’’ means paint or other surface coatings that contain lead in excess of 1.0 milligrams per centimeter squared (mg/cm2) or 0.5 percent by weight. Based on the XRF screening data, the paint on the tested building components was noted to contain lead below of 1.0 mg/cm2.

Overall, the paint on building components was observed in fair to good condition.. Refer to

Table 2 for the XRF screening data.

PCB in Caulk

Three (3) composite bulk samples of homogeneous suspect caulking were collected from the building and submitted for PCB analysis. PCBs were either not detected or the concentrations were less than 50 parts per million (PPM), and therefore, no remediation actions are necessary.

Test results are summarized in Table 3.

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302

1.0 INTRODUCTION

Langan Engineering and Environmental Services, Inc. (Langan) has prepared this limited hazardous materials (Hazmat) survey report for the Exterior Ramp Entrance Project at the Robert N.C. Nix Federal Building, 900 Market Street, Philadelphia, Pennsylvania. The survey was limited to the north and south revolving door entrances on the 9th Street and side door entrance on the Market Street of the subject building.

The remainder of this Report presents our observations, findings, laboratory test results of samples collected, plans showing sampling locations, and an itemized inventory of hazmat identified in the building.

2.0 SITE DESCRIPTION

The Robert N. C. Nix, Sr. Federal Building is located at the southwest corner of Ninth and Market Streets in downtown Philadelphia. It is situated on a rectangular lot measuring approximately 2 acres in size and encompassing nearly half of a city block.

The lot is bounded by Market Street to the north, Ninth Street to the east, and Chestnut

Street to the south. An alley on the west side of the property provides access from

Market Street to the building's loading dock. The building is constructed of steel reinforced concrete foundations and masonry constructed in 1937 with approximately

80,000 square feet of footprint.

3.0 HAZMAT FINDINGS

3.1 Terminology

Suspect Asbestos-Containing Materials

Asbestos was used in certain types of construction and building materials. Until a material is examined using light microscopy or a similar technique, the building material is considered as a suspect asbestos-containing material. A few examples of these materials include floor tiles, ceiling panels, thermal system insulation, fireproofing insulation, roofing materials, etc. Any suspect ACM of unknown asbestos content (that is not tested) should be handled as if it were an asbestos containing material.

Asbestos–Containing Material

A material with an asbestos concentration greater than one percent by weight is considered to be asbestos-containing by the United States Environmental Protection

Agency (USEPA). Thus, a material which contains asbestos in concentrations greater than 1% by weight is considered as “Positive” while materials that do not contain asbestos or asbestos is detected in concentrations less than one percent by weight are considered as “Negative”.

Friable Asbestos–Containing Material

A friable material is one that can be easily crumbled, pulverized, or reduced to powder by hand or mechanical pressure. This characteristic of a building material is directly

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302 linked to the potential of the material to release asbestos fibers into the air.

Non-friable Asbestos–Containing Material

Materials that are organically bound normally fall into this category as long as they are in good condition. Some of the materials, which would be defined as non-friable material, include floor tiles, roofing materials, mastic, etc.

3.2 Survey Methodology

Asbestos-Containing Materials

The asbestos survey was conducted in accordance with the United States

Environmental Protection Agency (EPA) protocol outlined in the EPA publication

“Asbestos in Buildings”. Suspect ACM was visually identified during a room-by-room, floor-by-floor survey of the building. Suspect ACM was categorized into various homogeneous materials and types, and sampled and analyzed for asbestos content.

Sampling and analysis was conducted in accordance with the EPA protocol 600/M4-82-

020 per 40 CFR 763. Samples collected were properly packaged in individual containers, sealed, catalogued, and chain-of-custody documentation was completed. Quantities of suspect materials were recorded and observations such as physical condition and friability of the materials were also noted.

Lead-Based Paint

A Heuresis Pb200i X-Ray Fluorescence (XRF) Spectrum Analyzer was used to inspect the subject buildings to identify lead concentrations in painted surfaces. The Heuresis

Pb200i analyzer uses a cobalt 57 radioactive source and an advanced solid-state radiation detector to generate an x-ray fluorescence spectrum of a painted surface.

During the analysis, the intensity of the x-rays is converted by the instrument’s internal software into an estimate of the concentration of lead in the substance being analyzed.

The results are interpreted as concentrations of lead in milligrams per square centimeter. This device is a field-screening tool, used to collect multiple readings in a short period of time. The method of measurement is based on spectrometric analysis of lead x-ray fluorescence within a controlled depth of interrogation. The reading is an estimate of lead content in all layers of paint. The results are displayed in milligrams per square centimeter (mg/cm2).

PCB in Caulk

The PCB survey involved a visual examination building spaces affected by the scope of work and sampling of suspect caulking materials. Composite samples of the caulking materials were collected from the building and submitted for PCB analysis. Samples were analyzed using EPA method 8082.

As per USEPA Code of Federal Regulations (40 CFR 761.3) any product which contains

PCB concentration of greater than 50 PPM is considered as PCB containing material.

Any product which contains <50 PPM PCB is considered a non-PCB product.

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302

3.3 Files Reviewed

Prior to our site visit, we reviewed the June 2016 Asbestos Report for the building prepared by EA Engineering, Science, and Technology, Inc., PBC (EA). The following are the finding documented in this report.

ACM or Presumed ACM (PACM):

Decorative plaster in 1st floor lobby (PACM)

9-inch brown mottled floor tiles

Mastic associated with 9-inch brown mottled floor tiles

Non-ACM:

Wall plaster

Ceiling plaster

Gypsum board

Gypsum board joint compound

Grout associated with ceramic wall and floor tiles

Grout/caulk between window frame and wall, gray

Fire packing

2’x2’ Ceiling tiles with pinholes and fissures

2’x4’ Ceiling tiles with pinholes and divots in a circular pattern

2’x4’ Ceiling tiles with pinholes and texture

12-inch square gray floor tiles with blue swirls

Mastic associated with 12-inch square gray floor tiles with blue swirls

Duct putty (Gray)

White seam sealant on fiberglass pipe insulation

Wooden fire door insulation

4.0 OBSERVATIONS AND FINDINGS

4.1 Asbestos-Containing Materials

The field survey of the subject building spaces was conducted on June 5, 2019 by

Langan’s Sanjay Patel. Suspect materials observed during the survey were documented, assessed, quantified, and sampled as necessary. Bulk samples of the suspect ACM were analyzed using the Polarized Light Microscopy (PLM) analytical methodology in accordance with 40CFR 763 and NESHAP regulations. The samples were analyzed by AmeriSci Richmond (AmeriSci) of Midlothian, Virginia. AmeriSci laboratory is accredited by the American Industrial Hygiene Association (AIHA) and

National Voluntary Laboratory Program (NVLAP).

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302

The survey was limited to the following building spaces:

North and south revolving entrance doors on the 9th street

Corner of alley and Market Street side entrance door

A detailed summary of asbestos survey findings is provided in Table 1. Refer to

Appendix A for the analytical test results and chain of custody documentation. Sampling locations are depicted on Drawings ASL-1.

4.2 Lead Based paint

The LBP screening was conducted on June 5, 2019 by Langan’s Sanjay Patel, a

Pennsylvania State Certified lead inspector. The locations screened primarily consisted of paint on walls, and door components. A total of ten (1) painted locations were screened for LBP during the survey.

As per 40 CFR Part 745, TSCA, Title IV (Lead Exposure Reduction), the term ‘‘lead-based paint’’ means paint or other surface coatings that contain lead in excess of 1.0 milligrams per centimeter squared (mg/cm2) or 0.5 percent by weight. Based on the XRF screening data, the paint on the following building components was identified to contain lead in excess of 1.0 mg/cm2:

Overall, the paint on building components was observed in fair to good condition. A summary of XRF screening data is provided in Table 2.

4.3 PCB in Caulk

Three (3) composite bulk samples of homogeneous suspect caulking were collected from the subject building spaces and submitted for PCB analysis. Samples were analyzed using EPA method 8082. PCBs were either not detected or the concentrations were less than 50 parts per million (PPM). Test results are summarized in Table 3.

5.0 CONCLUSIONS AND RECOMMENDATION

5.1 Asbestos Containing Materials

Asbestos containing materials were not identified in the spaces surveyed, and therefore, no abatement actions are necessary.

5.2 Lead Based Paint

Based on the XRF screening data and comparison of the results to 40 CFR Part 745, TSCA, Title IV, the paint on tested building components was identified to contain lead below of 1.0 mg/cm2. Refer to Table 2 for the XRF screening data.

Although the EPA defines lead based paint as paint having lead concentrations equal or greater than 1.0 mg/cm2, the Occupational Safety and Health Administration (OSHA)

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302 considers any concentration of lead in paint to be lead containing paint. Regardless of the lead concentrations in paint, the contractor shall comply with 29 CFR 1926.62, OSHA regulations, and take precautionary measures for dust control and limit employee exposure to lead dust during the renovations.

Painted surfaces that would be impacted by planned activities such as drilling, cutting, scrapping, etc. and create dust should be properly addressed by following safe work practices, good housekeeping procedures and/or following proper abatement procedures. Grinding and sanding of paint without HEPA filter exhaust, open flame gas fired torch, unconfined abrasive blasting, and chemical strippers containing methylene chloride or other human carcinogenic chemicals are not recommended.

The Federal Resource Conservation and Recovery Act (RCRA) regulation governs the handling, transportation, and disposal of hazardous materials. Every demolition/renovation debris generator has the responsibility to determine whether the debris exhibits one or more of the characteristic wastes listed in subpart C of 40 CFR

Part 261. In the case of demolition debris, lead in LBP is a characteristic waste, and therefore, it is the responsibility of the renovation/demolition debris generator to characterize the waste prior to its disposal and, if found to be hazardous waste as defined by Federal Statutes, to be properly handled and disposed.

Metal objects painted with LBP are exempt from disposal regulations applicable to lead, provided they are properly recycled. All metal objects that are painted with LBP should be sent to a certified recycling facility.

5.3 PCB in Caulk

PCBs were either not detected in caulking samples or the concentrations were less than 50 parts per million (PPM), and therefore, no abatement actions are necessary.

Refer to Table 3 for the summary of caulking sample PCB analysis results.

6.0 LIMITATIONS, EXCEPTIONS AND ASSUMPTIONS

Opinions and recommendations presented in this report apply to site conditions and features as they existed at the time of Langan’s site visit, and those reasonably foreseeable. They cannot necessarily apply to conditions and features of which Langan is unaware and has not had the opportunity to evaluate.

Any suspect building material that is not listed in this report must be assumed to be

ACM and treated as such unless otherwise confirmed by laboratory testing.

The conclusions presented in this report are professional opinions based solely upon

Langan’s visual observations of accessible areas, laboratory test data and current regulatory requirements. These conclusions are intended exclusively for the purpose stated herein, at the site indicated, and for the project indicated.

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

Langan Project No. 270054302

It is important to recognize that even the most comprehensive scope of services may fail to detect all asbestos containing materials that may be associated with the property.

Langan cannot, therefore, act as insurers and cannot “certify” that all asbestos containing materials associated with the property have been identified, and no expressed or implied representation or warranty is included or intended in our report, except that our services were performed, within the limits prescribed by our client, with the customary thoroughness and competence of our profession.

\\langan.com\data\ARL\data3\270054302\Project Data\_Discipline\Hazmat\2019-06-05 Site Visit - Entrance Ramps Survey\2019-07-18 - Limited Hazmat Survey Report.doc

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

TABLES

Material Sample

ID

Location Notes/Comments

Terrazzo Floor TF-1 Near 9th Street and

Market Street entrances Non-ACM -- -- -- -- --

Mortar associted with stones MM-1 9th Street - North and south revolving door Non-ACM -- -- -- -- --

Caulking associated with door -

Exterior

EDC-1

Near 9th Street and

Market Street entrance doors

Non-ACM -- -- -- -- --

Caulking associated with door -

Interior

IDC-1

Market Street side entrance door Non-ACM -- -- -- -- --

Caulking associated with wall/concrete/stone joints

CWJC-1

Near 9th Street and

Market Street entrances Non-ACM -- -- -- -- --

2 ND = “None Detected” – Asbestos not detected in sampled material.

A material with asbestos content greater than one percent (>1.0%) is considered as an asbestos-

Non-ACM

Table -1 - SUMMARY OF ASBESTOS SURVEY FINDINGS

Robert N.C. Nix, Sr. Federal Building, 900 Market Street Philadelphia, PA

Survey Results

Estimated

Quantity

Affected by

Scope of

Work

Project Name: Action Level: 1.0 mg/cm

Survey Date: Total Assays Reported: 171

Survey Component Substrate Color Test Location Total Lead Results Condition Comments

ID# mg/cm

1 0.8

2 1

3 1.1 ---

4 Wall Plaster White Market Street Side 0.8 Negative Good ---

5 Wall Plaster White Market Street Side 0.7 Negative Good ---

6 Wall Plaster White Market Street Side 0.9 Negative Fair ---

7 Door Metal Coffee Market Street Side -0.1 Negative Fair ---

8 Door Frame Metal Coffee Market Street Side 0.2 Negative Fair ---

9 Door Frame Metal Coffee Market Street Side 0.1 Negative Fair ---

10 Door Metal Coffee 9th Street Side 0 Negative Fair ---

11 Door Frame Metal Coffee 9th Street Side 0.1 Negative Fair ---

12 Door Metal Coffee 9th Street Side -0.1 Negative Fair ---

13 Door Frame Metal Coffee 9th Street Side 0 Negative Fair ---

14 1 ---

15 1

16 1

NEGATIVE = Negative Lead Result

POSITIVE = Positive Lead Result

DAILY CALIBRATIONS

Date: 1/17/2018

Calibration Check

Good

Calibration

Calibration

Calibration

Table -2 - XRF SCREENING RESULTS

Robert N.C. Nix, Sr. Federal Building, 900 Market Street Philadelphia, PA

Site

Address:

Robert N.C. Nix, Sr. Federal Building, 900 Market Street Philadelphia, PA

9th Street and Market Street Entrance Ramp

1/17/2018

Calibration

Calibration

Calibration

PCB-1016 ND mg/Kg (PPM) 930 // 0.93

PCB-1221 ND mg/Kg (PPM) 930 // 0.93

PCB-1232 ND mg/Kg (PPM) 930 // 0.93

PCB-1242 ND mg/Kg (PPM) 930 // 0.93

PCB-1248 ND mg/Kg (PPM) 930 // 0.93

PCB-1254 ND mg/Kg (PPM) 930 // 0.93

PCB-1260 ND mg/Kg (PPM) 930 // 0.93

PCB-1262 ND mg/Kg (PPM) 930 // 0.93

PCB-1268 ND mg/Kg (PPM) 930 // 0.93

PCB-1016 ND mg/Kg (PPM) 410 // 0.41

PCB-1221 ND mg/Kg (PPM) 410 // 0.41

PCB-1232 ND mg/Kg (PPM) 410 // 0.41

PCB-1242 ND mg/Kg (PPM) 410 // 0.41

PCB-1248 ND mg/Kg (PPM) 410 // 0.41

PCB-1254 1.2 mg/Kg (PPM) 410 // 0.41

PCB-1260 ND mg/Kg (PPM) 410 // 0.41

PCB-1262 ND mg/Kg (PPM) 410 // 0.41

PCB-1268 ND mg/Kg (PPM) 410 // 0.41

PCB-1016 ND mg/Kg (PPM) 690 // 0.69

PCB-1221 ND mg/Kg (PPM) 690 // 0.69

PCB-1232 ND mg/Kg (PPM) 690 // 0.69

PCB-1242 ND mg/Kg (PPM) 690 // 0.69

PCB-1248 ND mg/Kg (PPM) 690 // 0.69

PCB-1254 ND mg/Kg (PPM) 690 // 0.69

PCB-1260 ND mg/Kg (PPM) 690 // 0.69

PCB-1262 ND mg/Kg (PPM) 690 // 0.69

PCB-1268 ND mg/Kg (PPM) 690 // 0.69

ND or <50 mg/Kg (PPM) ---------------------= Non-PCB

>50 mg/Kg (PPM) ---------------------= PCB Containing

Table -4 - SUMMARY OF CAULK SAMPLE PCB ANALYSES RESULTS

Robert N.C. Nix, Sr. Federal Building, 900 Market Street Philadelphia, PA

Material Sample

ID #

Sample Location Parameter Results Units Reporting Level

Approximate

Quantities of PCB

Caulk

PCB Caulk

Locations

Caulking associated with door - Interior

IDC-1

Market Street - Side door entrance

0 LF

Caulking associated with door - Exterior

EDC-1

9th Street and Market Street

Entrences

0 LF

Caulking associated with wall/concrete/stone joints

CWJC-1

9th Street and Market Street

Entrences

0 LF

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

DRAWINGS

L a n g a n

250066701

10/18/2018

ASL- 1

SP

Basement

GENERAL NOTES:

1. THIS SKETCH IS PROVIDED TO SHOW APPROXIMATE LOCATIONS OF

ASBESTOS SAMPLING . THE ACTUAL LAYOUT OF THE BUILDING MAY

BE DIFFERENT THAN SHOWN. ALSO, THE SKETCH IS NOT TO SCALE,

AND THEREFORE, THE PLAN SHALL NOT BE USED FOR ANY OTHER

PURPOSES.

9TH STREET - SOUTH ENTRANCE

9TH STREET - NORTH ENTRANCE

MARKET STREET ENTRANCE

900 Market Street

Philadelphia, PA spatel Callout

CWJC-1-A

spatel Callout

IDC-1-B

spatel Callout

TF-1-B

spatel Callout

TF-1-A

spatel Callout

IDC-1-A

spatel Callout

EDC-1-A

spatel Callout

EDC-1-B

spatel Callout

MOR-1-A

spatel Callout

CWJC-1-B

spatel Callout

MOR-1-B

L a n g a n

4 5

7,8

10, 12, GENERAL NOTES:

1. THIS SKETCH IS PROVIDED TO SHOW APPROXIMATE LOCATIONS OF

LCP SCREENING . THE ACTUAL LAYOUT OF THE BUILDING MAY BE

DIFFERENT THAN SHOWN. ALSO, THE SKETCH IS NOT TO SCALE, AND

THEREFORE, THE PLAN SHALL NOT BE USED FOR ANY OTHER

PURPOSES.

270054302

07/01/2019900 Market Street, Philadelphia, PA

LSL- 1

SP

9TH STREET - SOUTH ENTRANCE

9TH STREET - NORTH ENTRANCE

MARKET STREET ENTRANCE

XRF

SCREENING

LOCATION

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

APPENDIX A

Laboratory Test Results and Chain of Custody Documentations (Asbestos)

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

APPENDIX B

Laboratory Test Results and Chain of Custody Documentations (PCB)

Sample Information Custody Information Matrix:

Location Code:

Rush Request:

P.O.#:

Collected by:

Received by:

Analyzed by:

CAULK

LANGANNJ

Standard

06/05/19

LB

see "By" below

SP

Laboratory Data

EDC-1

Phoenix ID: CD30343

06/10/19 10:32

Parameter Result

RL/

PQL Units Date/Time By Reference

FOR: Attn: Vijay Patel Langan Engineering & Environmental Svcs 300 Kimball Drive 4th Floor Parsippany NJ 07054

Analysis Report June 12, 2019

Date Time

SDG ID: GCD30343

Client ID:

Project ID: 270054302 ROBERT NIX FEDERAL BLDG., RAMP

Dilution

587 East Middle Turnpike, P.O.Box 370, Manchester, CT 06045 Tel. (860) 645-1102 Fax (860) 645-0823

Environmental Laboratories, Inc.

CompletedCaulk Extraction for PCB 06/10/19 XX/KL SW3540C

PCB (Soxhlet SW3540C) NDPCB-1016 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1221 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1232 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1242 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1248 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1254 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1260 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1262 930 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1268 930 06/11/19 SC SW8082Aug/Kg 1

QA/QC Surrogates

69% DCBP 06/11/19 SC 30 - 150 %% 1

54% DCBP (Confirmation) 06/11/19 SC 30 - 150 %% 1

50% TCMX 06/11/19 SC 30 - 150 %% 1

45% TCMX (Confirmation) 06/11/19 SC 30 - 150 %% 1

Ver 1

EDC-1

Phoenix I.D.: CD30343

Client ID:

270054302 ROBERT NIX FEDERAL BLDG., RAMPProject ID:

Parameter Result

RL/

PQL Units Date/Time By ReferenceDilution

Comments:

Results are reported on an ``as received`` basis, and are not corrected for dry weight.

All soils, solids and sludges are reported on a dry weight basis unless otherwise noted in the sample comments.

Phyllis Shiller, Laboratory Director June 12, 2019

If you are the client above and have any questions concerning this testing, please do not hesitate to contact Phoenix Client Services at ext.200.

The contents of this report cannot be discussed with anyone other than the client listed above without their written consent.

Reviewed and Released by: Rashmi Makol, Project Manager

RL/PQL=Reporting/Practical Quantitation Level (Equivalent to NELAC LOQ, Limit of Quantitation) ND=Not Detected at RL/PQL BRL=Below Reporting Level L=Biased Low QA/QC Surrogates: Surrogates are compounds (preceeded with a %) added by the lab to determine analysis efficiency. Surrogate results(%) listed in the report are not "detected" compounds.

Location Code:

Rush Request:

P.O.#:

Collected by:

Received by:

Analyzed by:

CAULK

LANGANNJ

Standard

06/05/19

LB

see "By" below

SP

Laboratory Data

IDC-1

Phoenix ID: CD30344

06/10/19 10:32

Parameter Result

RL/

PQL Units Date/Time By Reference

FOR: Attn: Vijay Patel Langan Engineering & Environmental Svcs 300 Kimball Drive 4th Floor Parsippany NJ 07054

Analysis Report June 12, 2019

Date Time

SDG ID: GCD30343

Client ID:

Project ID: 270054302 ROBERT NIX FEDERAL BLDG., RAMP

Dilution

587 East Middle Turnpike, P.O.Box 370, Manchester, CT 06045 Tel. (860) 645-1102 Fax (860) 645-0823

Environmental Laboratories, Inc.

CompletedCaulk Extraction for PCB 06/10/19 XX/KL SW3540C

PCB (Soxhlet SW3540C) NDPCB-1016 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1221 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1232 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1242 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1248 410 06/11/19 SC SW8082Aug/Kg 1

1200PCB-1254 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1260 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1262 410 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1268 410 06/11/19 SC SW8082Aug/Kg 1

QA/QC Surrogates

63% DCBP 06/11/19 SC 30 - 150 %% 1

48% DCBP (Confirmation) 06/11/19 SC 30 - 150 %% 1

54% TCMX 06/11/19 SC 30 - 150 %% 1

47% TCMX (Confirmation) 06/11/19 SC 30 - 150 %% 1

IDC-1

Phoenix I.D.: CD30344

Client ID:

270054302 ROBERT NIX FEDERAL BLDG., RAMPProject ID:

Parameter Result

RL/

PQL Units Date/Time By ReferenceDilution

Comments:

Results are reported on an ``as received`` basis, and are not corrected for dry weight.

All soils, solids and sludges are reported on a dry weight basis unless otherwise noted in the sample comments.

Phyllis Shiller, Laboratory Director June 12, 2019

If you are the client above and have any questions concerning this testing, please do not hesitate to contact Phoenix Client Services at ext.200.

The contents of this report cannot be discussed with anyone other than the client listed above without their written consent.

Reviewed and Released by: Rashmi Makol, Project Manager

RL/PQL=Reporting/Practical Quantitation Level (Equivalent to NELAC LOQ, Limit of Quantitation) ND=Not Detected at RL/PQL BRL=Below Reporting Level L=Biased Low QA/QC Surrogates: Surrogates are compounds (preceeded with a %) added by the lab to determine analysis efficiency. Surrogate results(%) listed in the report are not "detected" compounds.

Location Code:

Rush Request:

P.O.#:

Collected by:

Received by:

Analyzed by:

CAULK

LANGANNJ

Standard

06/05/19

LB

see "By" below

SP

Laboratory Data

EWJC-1

Phoenix ID: CD30345

06/10/19 10:32

Parameter Result

RL/

PQL Units Date/Time By Reference

FOR: Attn: Vijay Patel Langan Engineering & Environmental Svcs 300 Kimball Drive 4th Floor Parsippany NJ 07054

Analysis Report June 12, 2019

Date Time

SDG ID: GCD30343

Client ID:

Project ID: 270054302 ROBERT NIX FEDERAL BLDG., RAMP

Dilution

587 East Middle Turnpike, P.O.Box 370, Manchester, CT 06045 Tel. (860) 645-1102 Fax (860) 645-0823

Environmental Laboratories, Inc.

CompletedCaulk Extraction for PCB 06/10/19 XX/KL SW3540C

PCB (Soxhlet SW3540C) NDPCB-1016 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1221 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1232 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1242 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1248 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1254 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1260 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1262 690 06/11/19 SC SW8082Aug/Kg 1 NDPCB-1268 690 06/11/19 SC SW8082Aug/Kg 1

QA/QC Surrogates

85% DCBP 06/11/19 SC 30 - 150 %% 1

60% DCBP (Confirmation) 06/11/19 SC 30 - 150 %% 1

51% TCMX 06/11/19 SC 30 - 150 %% 1

46% TCMX (Confirmation) 06/11/19 SC 30 - 150 %% 1

EWJC-1

Phoenix I.D.: CD30345

Client ID:

270054302 ROBERT NIX FEDERAL BLDG., RAMPProject ID:

Parameter Result

RL/

PQL Units Date/Time By ReferenceDilution

Comments:

Results are reported on an ``as received`` basis, and are not corrected for dry weight.

All soils, solids and sludges are reported on a dry weight basis unless otherwise noted in the sample comments.

Phyllis Shiller, Laboratory Director June 12, 2019

If you are the client above and have any questions concerning this testing, please do not hesitate to contact Phoenix Client Services at ext.200.

The contents of this report cannot be discussed with anyone other than the client listed above without their written consent.

Reviewed and Released by: Rashmi Makol, Project Manager

RL/PQL=Reporting/Practical Quantitation Level (Equivalent to NELAC LOQ, Limit of Quantitation) ND=Not Detected at RL/PQL BRL=Below Reporting Level L=Biased Low QA/QC Surrogates: Surrogates are compounds (preceeded with a %) added by the lab to determine analysis efficiency. Surrogate results(%) listed in the report are not "detected" compounds.

QA/QC Data

Parameter Blk Blank RL

MS

MSD

MS

RPD

QA/QC Report June 12, 2019

587 East Middle Turnpike, P.O.Box 370, Manchester, CT 06045 Tel. (860) 645-1102 Fax (860) 645-0823

Environmental Laboratories, Inc.

SDG I.D.: GCD30343

LCS

LCSD

LCS

RPD

Rec

Limits

RPD

Limits

QA/QC Batch 482566 (ug/Kg), QC Sample No: CD26756 10X (CD30343, CD30344, CD30345)

Polychlorinated Biphenyls

PCB-1016 ND 116 114 1.7 40 - 140 30170

PCB-1221 ND 40 - 140 30170

PCB-1232 ND 40 - 140 30170

PCB-1242 ND 40 - 140 30170

PCB-1248 ND 40 - 140 30170

PCB-1254 ND 40 - 140 30170

PCB-1260 ND 120 123 2.5 40 - 140 30170

PCB-1262 ND 40 - 140 30170

PCB-1268 ND 40 - 140 30170

% DCBP (Surrogate Rec) 138 143 138 3.6 30 - 150 30%

% DCBP (Surrogate Rec) (Confirm 134 148 147 0.7 30 - 150 30

% TCMX (Surrogate Rec) 120 127 125 1.6 30 - 150 30%

% TCMX (Surrogate Rec) (Confirm 121 131 129 1.5 30 - 150 30

A LCS and LCS Duplicate were performed instead of a matrix spike and matrix spike duplicate.

Comment:

MS - Matrix Spike Phyllis Shiller, Laboratory Director

If there are any questions regarding this data, please call Phoenix Client Services at extension 200.

June 12, 2019 MS Dup - Matrix Spike Duplicate

RPD - Relative Percent Difference LCS - Laboratory Control Sample

LCSD - Laboratory Control Sample Duplicate

NC - No Criteria Intf - Interference

Sample Criteria Exceedances ReportWednesday, June 12, 2019

Acode Phoenix Analyte CriteriaResult RLSampNo Analysis

UnitsCriteria

GCD30343 - LANGANNJCriteria: None

RL

Criteria

State: PA

$PCB_SOXR PCB-1254 10001200 410 ug/KgCD30344 PA / Requested PCB RL / 1000

Phoenix Laboratories does not assume responsibility for the data contained in this exceedance report. It is provided as an additional tool to identify requested criteria exceedences. All efforts are made to ensure the accuracy of the data (obtained from appropriate agencies). A lack of exceedence information does not necessarily suggest conformance to the criteria. It is ultimately the site professional's responsibility to determine appropriate compliance.

Analysis Comments June 12, 2019

587 East Middle Turnpike, P.O.Box 370, Manchester, CT 06045 Tel. (860) 645-1102 Fax (860) 645-0823

Environmental Laboratories, Inc.

SDG I.D.: GCD30343

The following analysis comments are made regarding exceptions to criteria not already noted in the Analysis Report or QA/QC Report: None.

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

APPENDIX C

Langan’s Certifications and Laboratory Accreditations

AIHA Laboratory Accreditation Programs, LLC 3141 Fairview Park Drive, Suite 777, Falls Church, VA 22042 USA main +1 703-846-0736 fax +1 703-207-8558 Twitter: @AIHA_LAP_LLC

R3 04/18/2014

July 31, 2017

Laboratory ID: 102843

Tonya Williams - Kassim America Science Team New York, Inc. Dba AmeriSci New York 117 East 30th Street New York, NY 10016

Dear Ms. Williams - Kassim:

AIHA Laboratory Accreditation Programs, LLC (AIHA-LAP, LLC) has approved an extension to your laboratory’s current certificate of accreditation in the Industrial Hygiene Laboratory Accreditation Program (IHLAP). This extension will expire on September 01, 2017. Remember that your laboratory must maintain proficiency per Policy Module 6 in order for the new certificate to be issued.

Your laboratory remains an accredited laboratory in IHLAP. Please keep a copy of this letter with your expired certificate.

If you have questions or concerns, please feel free to contact Drake McGregor, Laboratory Accreditation Specialist at (703) 846-0739.

Sincerely, Cheryl O. Morton Managing Director

3141 Fairview Park Drive, Suite 777, Falls Church, VA 22042 USA main +1 703-846-0736 fax +1 703-207-8558 Twitter: @AIHA_LAP_LLC

R3 05/05/2015

September 30, 2015

Laboratory ID: 102843

Tonya Williams-Kassim America Science Team New York, Inc. Dba AmeriSci New York 117 East 30th Street New York, NY 10016

Dear Ms. Williams-Kassim:

Congratulations! The AIHA Laboratory Accreditation Programs (AIHA-LAP), LLC’s Analytical Accreditation Board (AAB) has approved America Science Team New York, Inc. Dba AmeriSci New York as an accredited Industrial Hygiene laboratory.

Accreditation documentation includes the IHLAP accreditation certificate, scope of accreditation document and a copy of the current AIHA-LAP, LLC license agreement (if your completed agreement is not on file at AIHA-LAP, LLC). The accreditation symbol has been designed for use by all AIHA-LAP, LLC accredited laboratories. If your laboratory chooses to use the symbol in its advertising the laboratory’s accreditation, you must complete and return the AIHA-LAP, LLC license agreement to a Laboratory Accreditation Specialist. Once submitted, an electronic copy of the accreditation symbol will be sent to you. Please inform us if your laboratory does not wish to use the symbol in advertising.

Laboratory accreditation shall be maintained by continued compliance with IHLAP requirements (see Policy Modules 2B and 6), which includes proficient participation in AIHA-LAP, LLC approved proficiency testing, demonstration of competency, or round robin program as indicated on the AIHA-LAP “Approved PT and Round Robin” webpage, its associated Scope/PT table, and as required in Policy Module 6, for all Fields of Testing (FoTs) for which the laboratory is accredited. An accredited laboratory that wishes to expand into a new FoT must submit an updated accreditation application to AIHA-LAP, LLC for review by the AAB.

Any changes in ownership, laboratory location, personnel, FoTs/Methods, or significant procedural changes shall be reported to AIHA-LAP, LLC in writing within twenty (20) business days of the change.

The accreditation certificate is the property of AIHA-LAP, LLC and must be returned to us should your laboratory withdraw or be removed from the IHLAP.

Again, congratulations. If you have any questions, please contact Lauren Schnack, Laboratory Accreditation Specialist, at (703) 846-0716.

Sincerely, Managing Director acknowledges that

America Science Team New York, Inc. Dba AmeriSci New York 117 East 30th Street, New York, NY 10016

Laboratory ID: 102843 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs (AIHA-LAP), LLC accreditation to the ISO/IEC 17025:2005 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:

LABORATORY ACCREDITATION PROGRAMS

INDUSTRIAL HYGIENE Accreditation Expires: 08/01/2017 ENVIRONMENTAL LEAD Accreditation Expires:

ENVIRONMENTAL MICROBIOLOGY Accreditation Expires:

FOOD Accreditation Expires:

UNIQUE SCOPES Accreditation Expires:

Specific Field(s) of Testing (FoT)/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2005 and AIHA-LAP, LLC requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA- LAP, LLC website (www.aihaaccreditedlabs.org) for the most current Scope.

Gerald Schultz, CIH Chairperson, Analytical Accreditation Board

Managing Director, AIHA Laboratory Accreditation Programs, LLC

Revision 14: 03/26/2014 Date Issued: 09/30/2015 http://www.aihaaccreditedlabs.org/

Effective: 04/10/2015 102843_Scope_IHLAP_2015_09_30

SCOPE OF ACCREDITATION

America Science Team New York, Inc. Dba AmeriSci New York Laboratory ID: 102843 117 East 30th Street, New York, NY 10016 Issue Date: 09/30/2015

The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory’s current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.

Industrial Hygiene Laboratory Accreditation Program (IHLAP)

Initial Accreditation Date: 04/01/2001

A complete listing of currently accredited Industrial Hygiene laboratories is available on the AIHA-LAP, LLC website at: http://www.aihaaccreditedlabs.org

IHLAP Scope Category

Field of Testing (FoT) (FoTs cover all relevant

IH matrices)

Technology sub-type/ Detector

Published Reference Method/Title of In-house Method

Method Description or Analyte

(for internal methods only)

Asbestos/Fiber Microscopy Core

Polarized Light Microscopy (PLM) EPA 600/R-93/116

Phase Contrast Microscopy (PCM) NIOSH 7400 http://www.aihaaccreditedlabs.org/

Robert N.C. Nix Federal Building

900 Market Street, Philadelphia, PA

APPENDIX D

June 2016 ACM Report by EA Engineering, Science, and Technology, Inc.