About this file

This document outlines a federal contract opportunity for facility renovations, improvements, and repairs at the Baltimore National Cemetery. The solicitation number is 36C78622B0001 and is being issued by the Department of Veterans Affairs National Cemetery Administration. The contract calls for exterior facility renovations, improvements, and repairs at the Baltimore National Cemetery, with a period of performance through 2023. Offerors are required to submit responses by the specified due date to be considered for the award, which is anticipated to be issued prior to the expiration date.

View the file

Other files

File Type Posted
Award Notice -Baltimore Nalt Cem- 36C78622C0019.pdf PDF
A0009 Baltimore Nalt Cem (36C78622B0001).pdf PDF
09 96 00 High Performance Epoxy Coatings (Baltimore Nalt Cem).pdf PDF
VITRUAL BID OPENING IFB (FY-22) BALTIMORE NALT CEM - PO 802CM3023 (05 Jan 2022).pdf PDF
PART 1-GENERAL (Baltimore Nalt Cem).pdf PDF
A0010 Baltimore Nalt Cem - 36C78622B0001.pdf PDF
092216 Non Structural Metal Framing (Baltimore Nalt Cem).pdf PDF
A0008 Baltimore Nalt Cem (36C78622B0001).pdf PDF
HAZMAT_Investigation_BNC_Final v2 -updated Appendix E.pdf PDF
Grille Ceilings.pdf PDF
RFI Question and Answers (Baltimore Nalt Cem) 14 Dec 2021.pdf PDF
Attachment 1 (52.228-1 Bid Guarantee).pdf PDF
A0007 Baltimore Nalt Cem - 36C78622B0001.pdf PDF
A0006 Baltimore Nalt Cem (36C78622B0001).pdf PDF
Amendment A0002 Baltimore Nalt Cem 36C78622B0001.pdf PDF
Amendment (A0005) Baltimore Nalt Cem (36C78622B0001).pdf PDF
A0004 Baltimore Nalt Cem (36C78622B0001) Vendor Portal Instructions.pdf PDF
Amendment (A0001) Baltimore Nalt Cem (36C78622B0001) 25 Oct 2021.pdf PDF
Amendment A0003 Baltimore Nalt Cem - 36C78622B0001 27 Oct 2021.pdf PDF
802CM3023 Baltimore SOW Construction.pdf PDF
COVID Safety Protocols for Federal Contractors FY-22.pdf PDF
802CM3023 BNC Dwg BK02.pdf PDF
802CM3023 BNC Dwg BK01.pdf PDF
802CM3023 BNC Specs BK02.pdf PDF
Sub-Contracting Limitation Attachment Certification.pdf PDF
802CM3023 BNC HAZARDOUS MATERIALS REPORT.pdf PDF
802CM3023 BNC Dwg BK04.pdf PDF
802CM3023 BNC Specs BK01.pdf PDF
Sub-Contraction POLICY 819 Contractor Certification Doc.pdf PDF
Copy of IFB-Contractor Cost Estimate Worksheet Baltimore Nalt Cem.xlsx XLSX spreadsheet
DAVIS BACON WD BALTIMORE COUNTY MD.pdf PDF
802CM3023 BNC Dwg BK03.pdf PDF
802CM3023 BNC GEOTECHNICAL REPORT.pdf PDF
36C78622B0001.docx DOCX document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECOND FLOOR PLAN - POWER

SCALE: 1/4"= 1'-0"

DN

DN

GAS WATER HEATER

PLAN NOTES:#

1. 20A, 120V-1Ø CONNECTION FOR GAS WATER HEATER.

2. 20A, 12OV-1Ø CONNECTION FOR GAS FURNACE.

3. 15A, 208V-1Ø CONNECTION FOR HEAT EXCHANGER.

4. INSTALL IN SAME LOCATION.

HE-1

(B-35,37)

FURN F-3

(B-19)

FURN F-2

(B-17)

(B-13)1

FURN F-1

(B-15)2

P

B-20

E-122-AM

SECOND FLOOR PLAN POWER

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SET

Admin-Maint. Bldg

VOLTS: 120/208

LOCATION:

CKTS: 42

LUGS: MCB

AMPS: 400

WIRE: 3

PHASE: 1

MTG: SURFACE

PANEL:

23 24

14.514.1 8.7

8.7

NO.

CIR.

REMARKS

ØBØA

<LOAD>

POLE

ØA

CIR.

NO. POLE

<LOAD>

ØB

REMARKS

20 20

20 20

FEED: BOTTOM/TOP

'B'

STORAGE

PANEL 'C' GARAGE

EF-1

SPARE

GAS WATER HEATER

0.5

0.5

VOLTS: 120/208

LOCATION:

CKTS: 42

LUGS: MCB

AMPS: 400

WIRE: 3

PHASE: 1

MTG: SURFACE

PANEL:

23 24

10.210.3 5.1

4.3

NO.

CIR.

REMARKS

ØBØA

<LOAD>

POLE

ØA

CIR.

NO. POLE

<LOAD>

ØB

REMARKS

20 20

20 20

FEED: BOTTOM/TOP

'A'

STORAGE

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

RECEPTS

REFRIG

REFRIG

ICE MAKER

I.T. RECEPT

INFO-SCREEN

1.1 1.1

1.1 1.1

1.1 1.1

1.1 1.1

1.1 1.1

1.1 1.1

1.1 1.1

1.1 0.5

0.5 1.0

1.0 1.0

SPARE

LIGHTING

LIGHTING

LIGHTING

LIGHTING

LIGHTING

LIGHTING

EXTERIOR LTG

EXIT/EM LTG

LTG - 2ND FLR

LTG - 2ND FLR

EXIST. LTG - 2ND FLR

EXIST. LTG - 2ND FLR

EXIT/EM LTG - 2ND FLR0.3

1.0

1.0 0.7

0.7

0.7 0.7

0.7 0.7

0.7 0.7

1.0 0.5

LIGHT FIXTURE SCHEDULE

MOUNTINGTYPE LAMPS REMARKS

NOMINAL

DIMENSION

MFGR & CAT NO. OR

ACCEPTABLE EQUIVALENTWATTS

RECESSA LED 30 2' x 2'

B

C

D

E

F

FX

G

H

J

K

RECESS

SURF

SURF

PEND

WALL

WALL

SURF

PEND

WALL

WALL

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

8"

ROUND

4'

6"

ROUND

2'

TRACE LITE

#LPA22-30-35KV

2' x 2' RECESSED LED FLAT PANEL

SPECTRUM

#SP8ES-24L-35/AR8ES-SG-WF

TRACE LITE

#SLS-4-40-C

ROYAL PACIFIC

#8556-W-90-3K

SPECTRUM

#WS1210GV-15L-35K-EX-TF2

TRACE LITE

#WLZ7-3-4K-BR-PC-RDC5-MWI-MW

TRACE LITE

#WLZ7-3-4K-BR-PC-BB

SPECTRUM

#C0606GV-15L-35K-EX-FS-TSG-SM-MW

SPECTRUM

#C0606GV-15L-35K-EX-FS-TSG-PM-MW

SPECTRUM

#C1216UDGV-15L-15L-35K-EX-TSG-

SO-WM5-MW

ROYAL PACIFIC

#4907-BN-24

8" ROUND LED RECESSED DOWNLIGHT

4' LED STRIP

6" ROUND LED SURFACE FIXTURE

LED PENDANT RLM FIXTURE

LED EXTERIOR WALL PACK WITH

BUILT-IN PHOTOCELL

LED EXTERIOR WALL PACK WITH

BUILT-IN PHOTOCELL AND EMERG

BATTERY PACK

LED SURFACE MOUNTED ROUND

CYLINDER

LED PENDANT MOUNTED ROUND

CYLINDER

LED WALL MOUNTED ROUND CYLINDER

WITH UP/DOWN LIGHT

2' LED WALL MOUNTED OVER-MIRROR

LIGHT

EM

X

X1

WALL

UNIV

UNIV

LED

LED

LED

EXTRONIX

#LED-95-WH

EXTRONIX

#QXT-G-WB-WH

EXTRONIX

#QCRS-U-WH

LED EMERGENCY WALL PACK

LED EXIT LIGHT WITH EMERGENCY WALL

PACK GREEN LETTERS

LED COMBO EXIT/EMERGENCY LIGHT

GREEN LETTERS

FURN F-1

FURN F-2

FURN F-3

0.5 0.5

0.5

HE-1

CU-2

2.5

2.5

46.0 KVA (221 AMPS)

CU-1

CU-3

3.8

1.9 3.8

1.9

AM-GRH-1

AM-GRH-2

AM-GRH-3

EXIST. ENERGY MONITOR

RACK PDU

RACK UPS

BACKBOARD RECEPT

BACKBOARD RECEPT

0.5 0.5

0.5 0.5

1.0 1.0

1.0 1.0

29.9 KVA (83 AMPS)

SPARE

SPARE

EXIST. GARAGE DOOR OPENER

EXIST. GARAGE DOOR OPENER

EXIST. GARAGE DOOR OPENER

1.5 1.5

1.5

1. EXISTING FEEDERS AND PANELS SHOWN X'ED OUT SHALL BE REMOVED.

2. 3-#500MCM, 1-#1/0 GND IN A 3-1/2"C.

3. 3-#3, 1-#8 GND IN A 1-1/2"C.

4. 3-#8, 1-#8 GND IN A 3/4"C.

ONE-LINE DIAGRAM NOTES:

M

EXIST. A-1

(TO REMOVE)

EXIST. A-2

(TO REMOVE)

100A 2P

EXIST. 'G'

(TO REMOVE)

50A 2P

EXIST. SUB-PANEL

(TO REMOVE)

NEW PANEL 'A' NEW PANEL 'B'

400A 2P

100/2

100A 2P

NEW PANEL 'C'

ONE-LINE DIAGRAM

NO SCALE:

L RECESS LED 32 12"

ROUND

SPECTRUM

#SP12ES-32L-35/AR12ES-SG-WF

12" ROUND LED RECESSED DOWNLIGHT

POWER LOGIC PANEL

SMOKE DET

1.0 0.5

40A 2P

PANEL 'POL'

E-201-AM

FIRST FLOOR PLAN

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

Admin-Maint. Bldg

FLOOR PLAN - LIGHTING

'C''C''C'

'C''C''C'

'C''C''C'

P

P

2 2 2 2

'C''C''C'

'C'

'C''C''C' 'C'

'C''C''C' 'C'

P

P

4 4 4

1. REMOVE EXISTING 4' FLUORESCENT STRIP FIXTURES. REMOVE EXISTING SURFACE

CONDUIT AND WIRE COMPLETE BACK TO THE PANEL. INSTALL NEW TYPE 'C' 4' LED STRIP

FIXTURES BACK IN EXISTING LOCATIONS AFTER CEILING IS PAINTED. CONNECT TO NEW

CIRCUITS SHWON. INSTALL BRANCH CIRCUITS IN SURFACE MOUNTED CONDUIT. PAINT

CONDUIT TO MATCH CEILING.

2. REMOVE EXISTING EXTERIOR WALL PACK AND INSTALL NEW TYPE 'F' WALL PACK IN SAME

LOCATION AFTER NEW WOOD TRIM HAS BEEN INSTALLED.

3. REMOVE EXISTING SMOKE DETECTOR. INSTALL NEW 120V SELF-CONTAINED

PHOTOELECTRIC SMOKE DETECTOR IN SAME LOCATION AFTER CEILING IS PAINTED.

4. DISCONNECT EXISTING UNIT HEATER. REMOVE EXISTING WIRING BACK TO THE PANEL.

INSTALL BLANK COVER PLATE OVER ROUGH-IN LOCATION.

5. SEE POWER SHEET FOR DEMOLITION OF EXISTING PANELS.

PLAN NOTES:#

'F' C-5 'F' C-5 'F' C-5 'F' C-5

C-1 C-1 C-1

C-1 C-1 C-1

C-1 C-1 C-1

C-14 C-14 C-14 C-14

C-3 C-3 C-3 C-3

C-3 C-3 C-3 C-3

C-3 C-3 C-3 C-3

NEW PANEL 'C'5

EXIST. HEATER PANEL

(TO BE REMOVED)

NEW PANEL 'POL'

E-111-GS

FLOOR PLAN - LIGHTING

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

Garage - Storage

VOLTS: 120/208

LOCATION:

CKTS: 30

LUGS: MCB

AMPS: 100

WIRE: 3

FEED: BOTTOM/TOP

PHASE: 1

MTG: SURFACE

PANEL:

23 24

3.12.8 5.7 5.8

NO.

CIR.

REMARKS

ØBØA

<LOAD>

POLE

ØA

CIR.

NO. POLE

<LOAD>

ØB

REMARKS

'C'

GARAGE

NEW LTS SMALL BAY

NEW LTS LARGE BAY

EXIST. GAS SHED (POL)

EXIST. GAR DOOR MOTOR

EXIST. GAR DOOR MOTOR

EXIST. WATER MON.

0.7 0.6

0.6 1.0

1.5 1.5

1.0

NEW EXT. LTS

SPARE

EXIST. RECEPTS

EXIST. RECEPTS

EXIST. RECEPTS

EXIST. GAR. DOOR MOTOR

EXIST. GAR. DOOR MOTOR

0.0 1.1

1.1 1.1

1.5 1.5

SMOKE DET.

GRH-1

GRH-2

GRH-3

GRH-4

GRH-5

SPARE

PANEL 'POL'

SPARE

SPARE

SPARE

FLOOR PLAN - ELECTRICAL

SCALE: 1/4"= 1'-0"

1. DELETE TWO (2) EXISTING PANELS AND PANEL FEEDERS COMPLETE. EXTEND EXISTING

BRANCH CIRCUITS TO NEW PANEL THAT ARE TO REMAIN.

2. INSTALL NEW PANEL 'C' IN EXISTING PANEL LOCATION. EXTEND EXISTING BRANCH

CIRCUITS TO THIS LOCATION AND CONNECT TO NEW CIRCUIT BREAKERS IN THIS PANEL.

3. DELETE EXISTING OVERHEAD SERVICE ENTRANCE CABLING FROM GARAGE TO POL

BUILDING.

4. DELETE EXISTING OVERHEAD SERVICE ENTRANCE CABLING FROM GARAGE TO

ADMINISTRATION/MAINTENANCE BUILDING.

5. 20A, 120V-1Ø CONNECTION FOR GAS RADIANT HEATER.

6. DELETE EXISTING WEATHER HEAD PATCH ALL WALL/ROOF PENETRATIONS. WEATHER

AND WATERPROOF. REMOVE ALL OVERHAED CABLING BACK TO ADMIN BUILDING.

7. REMOVE LL FEEDERS COMPLETE FROM WEATHERHEAD TO HEATER PANEL.

8. PROVIDE SHUNT-TRIP MAIN CIRCUIT BEAKER IN NEW PANEL 'POL' AND CONNECT TO

PUSH-BUTTON SHUT-OFF WITCH ON POL BUILDING.

PLAN NOTES:#

NEW PANEL 'C'

GS-GRH-1

(C-16) 5

GS-GRH-2

(C-18) 5

GS-GRH-3

(C-20) 5

GS-GRH-4

(C-22) 5

GS-GRH-5

(C-24)5

A. RECONNECT ALL EXISTING EQUIPMENT TO NEW PANEL 'C'. EXTEND EXISTING BRANCH

CIRCUITS TO NEW PANEL. SEE PANEL SCHEDULE FOR ALL EXISTING EQUIPMENT TO BE

RECONNECTED.

GENERAL NOTES:

0.5 0.5

0.5 0.5

0.5 0.5

17.4 KVA (72.5 AMPS)

VOLTS: 120/208

LOCATION:

CKTS: 12

LUGS: MCB

AMPS: 40

WIRE: 3

FEED: BOTTOM

PROVIDE:

PHASE: 1

MTG: SURFACE

PANEL:

0.60.6 1.0 0.0

NO.

CIR.

REMARKS

ØBØA

<LOAD>

POLE

ØA

CIR.

NO. POLE

<LOAD>

ØB

REMARKS

20 20

'POL'

GARAGE

SHUNT-TRIP MAIN

GAS PUMP

DIESEL PUMP

SPARE

SPARE

SPARE

SPARE

LEAK DETECTOR

SPARE

SPARE

SPARE

SPARE

SPARE

0.6

0.6

2.2KVA (9.0 AMPS)

20SPARE

20SPARE

20SPARE

20SPARE

20SPARE

0.6 1.6

NEW PANEL 'POL'

8 EXIST. HEATER PANEL

(TO BE REMOVED AND ASSOCIATED WEATHERHEAD)

E-121-GS

FLOOR PLAN - ELECTRICAL

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

Garage - Storage

TP#

P-5

TP#

P-6

MATCHLINE - SHEE SHEET B-100

SITE PLAN - ELECTRICAL

SCALE: 1"= 10'-0"

NEW PANEL 'B'

NEW PANEL 'A'

NEW PANEL 'C'3

ADMIN. BLDG

GARAGE

STORAGE BLDG

POL BLDG

UNDERGROUND

TO POL BLDG

LODGE

1. NEW UNDERGROUND FEEDER TO PANEL 'C'. CONTRACTOR SHALL CHANNEL AND PATCH

EXISTING DRIVE AS NECESSARY FOR INSTALLATION OF NEW FEEDER. SEE ONE-LINE

DIAGRAM.

2. REMOVE EXISTING WEATHERHEAD FOR OVERHEAD SERVICE TO GARAGE. REMOVE ALL

EXISTING OVERHEAD CABLING.

3. SEE POL BUILDING PLAN AND NEW CONCRETE PAD PLAN FOR ADDITIONAL INFORMATION.

KEYED PLAN NOTES:#

A. REMOVE ALL OVERHEAD SERVICE CABLES BETWEEN ADMINISTRATION BUILDING AND

GARAGE STORAGE BUILDING AND BETWEEN GARAGE STORAGE BUILDING AND POL

BUILDING. REMOVE ALL ASSOCIATED WEATHERHEADS AND EQUIPMENT.

B. CONTRACTOR SHALL DISCONNECT EXISTING FUEL PUMPS. REMOVE ALL EXISTING

BRANCH CIRCUIT CONDUIT, WIRE AND CONTROLS. REMOVE EXISTING WIRING BACK TO

THE PANEL. ALSO REMOVE EXISTING CARD READER AND ASSOCIATED BRANCH CIRCUIT

CONDUIT AND WIRE.

C. SEE NEW PANEL 'C' SCHEDULE FOR BRANCH CIRCUIT FEEDERS AND CIRCUITS.

GENERAL DEMOLITION NOTES:

NEW PANEL

'POL'

ES-100

SITE PLAN - ELECTRICAL

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

342 343

CO

MB

B

B B

BB

BB

B

GIS MONUMENT

FP

FP

CO

EST-100

SITE PLAN - ELECTRICAL TEMPORARY

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SET

SITE PLAN - ELECTRICAL TEMPORARY

SCALE: 1"= 50'-0"

1. TAP EXISTING BUILDING SERVICE AND INSTALL TEMPORARY WEATHERHEAD ON SIDE OF

BUILDING FOR TEMPORARY POWER.

2. INSTALL TEMPORARY WOODEN POWER POLES AS NECESSARY FOR FEEDS TO TEMPORARY

STAFF TRAILERS AND RESTROOMS TRAILERS. POLES SHALL BE 24' LONG, 6' BELOW GRADE

AND 18" ABOVE GRADE.

3. 200A, 208V-1Ø CONNECTION TO TEMPORARY OFFICE TRAILER.

4. 60A, 208V-1Ø CONNECTION TO TEMPORARY RESTROOM TRAILER.

5. 60A, 208V-1Ø CONNECTION TO TEMPORARY STAFF TRAILER.

6. 2-#3/0, 1-#2 GROUND OVERHEAD CABLES TO TEMPORARY TRAILER.

7. 2-#6, 1-#6 GROUND OVERHEAD CABLES TO TEMPORARY RESTROOM TRAILER.

8. 2-#6, 1-#6 GROUND OVERHEAD CABLES TO TEMPORARY TRAILER.

9. INSTALL NEW FIBER OPTIC CABLE OVERHEAD FOR TEMPORARY FEED TO TEMPORARY

OFFICE TRAILER. TAP EXISTING INCOMING FIBER OPTIC SERVICE. RUN CABLES OVERHEAD

BETWEEN NEW TEMPORARY POLES.

PLAN NOTES:

MAINTENANCE

GARAGE

(TYP.)

ADMINISTRATION

BUILDING

(TYP.)

STAFF

TRAILER

RESTROOM

TRAILER

OFFICE

TRAILER

LODGE BASEMENT ELECTRICAL DEMOLITION PLAN

LODGE BASEMENT ELECTRICAL REVISED PLAN

SCALE: 1/4"= 1'-0"

1. 1. DISCONNECT EXISTING GAS BOILER. EXISTING BRANCH CIRCUIT SHALL REMAIN TO

FEED NEW BOILER.

2. 20A, 120V-1Ø CONNECTION FO NEW GAS BOILER. CONNECT TO EXISTING BRANCH CIRCUIT

THAT FEEDS EXISTING BOILER. EXTEND EXISTING BRANCH CIRCUIT AS NECESSARY.

PLAN NOTES:#

NEW BOILER LB-1

E-111-LG

FLOOR PLAN - LIGHTING

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

Lodge

FLOOR PLAN -

WEST ELEVATION ELECTRICAL

SCALE: 1/4"= 1'-0"

SOUTH ELEVATION ELECTRICAL

SCALE: 1/4"= 1'-0"

EAST ELEVATION ELECTRICAL

SCALE: 1/4"= 1'-0"

NORTH ELEVATION ELECTRICAL

SCALE: 1/4"= 1'-0"

EXIST. EMERGENCY

PUSH-BUTTON

SHUT-OFF SWITCH

EXIST. LEAK

DETECTOR ALARM

EXIST. PULL BOX6

TO NEW PANEL 'POL'8

TO NEW PANEL 'C'8

EXIST. WEATHERHEAD4EXIST. WEATHERHEAD4

1. EXISTING LEAK DETECTOR ALARM TO REMAIN. CONNECT TO NEW 20A, 120V-1Ø CIRCUIT IN

NEW PANEL 'POL'. PROVIDE LEAK DETECTION FOR BOTH NEW GAS TANKS (POL-2)

2. EXISTING EMERGENCY PUSH-BUTTON SHUT-OFF SWITCH TO REMAIN. CONNECT TO MAIN

CIRCUIT BREAKER IN NEW PANEL 'POL' TO SHUT-OFF PANEL.

3. EXISTING WATER MONITORING PANEL TO REMAIN. CONNECT TO NEW 20A-1P C.B. IN NEW

PANEL 'C'.

4. EXISTING WEATHERHEAD TO BE REMOVED. REMOVE ALL OVERHEAD WIRING BACK TO

GARAGE BUILDING. REMOVE EXISTING WOOD POLE ALONG BUILDING.

5. CONTRACTOR SHALL RUN NEW BRANCH CIRCUIT WIRING IN EXISTING CONDUIT ALONG

WALL.

6. EXISTING PULL BOX TO REMAIN.

7. CONTRACTOR SHALL INSTALL NEW PULL BOX TO RUN NEW BRANCH CIRCUIT WIRING.

8. CONTRACTOR SHALL CHANNEL AND PATCH EXISTING ASPHALT AS NECESSRY TO INSTALL

NEW BRANCH CIRCUIT FEEDERS. ALSO BURY FEEDER UNDER EXISTING CURB. DO NOT

CHANNEL AMD PATCH EXISTING CONCRETE.

PLAN NOTES:#

E-111-FS

FLOOR PLAN - LIGHTING

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

Flammable Storage

FUEL TANK PAD ELECTRICAL

GROUND ROD

EXP

EXP

POL-1 POL-3

3 GROUND ROD

FUEL TANK PAD SECTION

SCALE: 1/4"= 1'-0"

EXP

EXP

1. CONTRACTOR SHALL CONNECT FUEL PUMPS PER MANUFACTURERS RECOMMENDATIONS

AND ALL APPLICABLE CODES PERTAINING TO GAS PUMP INSTALLATION.

2. CONTRACTOR SHALL GROUND EACH GAS TANK PER N.E.C.

3. CONTRACTOR SHALL COORDINATE CONCRETE PAD PENENTRATIONS WITH G.C. POURING

PAD.

4. CONTRACTOR SHALL DISCONNECT EXISTING PUMPS. PUMPS WILL BE REMOVED AND

RE-INSTALLED ON NEW FUEL TANKS BY OTHERS. CONTRACTOR SHALL REMOVE EXISTING

BRANCH CIRCUIT CONDUIT AND WIRE COMPLETE BACK TO EXISTING PANEL.

PLAN NOTES:#

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SET

E-111-FT

FLOOR PLAN - LIGHTING

Fuel Tank

ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING,

MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE BY

PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS,

WITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE,

BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES, FILTERS AND STRAINERS,

TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION

WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT

DOCUMENTS TO COR FOR RESOLUTIONS.

INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING MECHANICAL

EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND DUCTWORK WAS OBTAINED

FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY FIELD OBSERVATION, HOWEVER,

ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE, CERTAIN INFORMATION CONCERNING

THE LOCATION OF THE EXISTING MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING,

PLUMBING AND DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S)

AND DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT HAS

BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER, ALL EXISTING

WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS

OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN

THESE PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE

ENGINEER FOR VERIFICATION AND/OR CORRECTION.

1. PLUMBING CONTRACT DRAWINGS ARE IN PART DIAGRAMMATIC, COVERING THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF THE EQUIPMENT, PIPING, ETC., AND THE APPROXIMATE SIZE OF EQUIPMENT AND MATERIALS. THE CONTRACTOR SHALL FOLLOW THESE DRAWINGS IN LAYING OUT THE PLUMBING WORK. PLUMBING CONTRACTOR SHALL CONSULT GENERAL, SPRINKLER, HEATING/VENTILATING/AIR CONDITIONING CONTRACTOR AND ELECTRICAL DRAWINGS TO FAMILIARIZE HIMSELF WITH THAT WORK AND TO

VERIFY THE SPACES IN WHICH THE PLUMBING WORK WILL BE INSTALLED.

2. BECAUSE OF THE NATURE AND SCALE OF THE DRAWINGS, CERTAIN BASIC PLUMBING ITEMS SUCH AS UNIONS, FITTINGS, ELBOWS, ETC., MAY NOT BE SHOWN. WHERE SUCH ITEMS ARE REQUIRED BY OTHER SECTIONS OF THE SPECIFICATIONS, OR WHERE THEY ARE REQUIRED BY THE NATURE OF THE WORK OR BY CODES AND REGULATIONS, THEY SHALL BE FURNISHED AND INSTALLED AT NO ADDITIONAL COST TO THE OWNER. THE DRAWINGS INDICATE GENERAL LOCATIONS OF PIPING, EQUIPMENT, DUCTWORK AND SIMILAR. THE EXACT LOCATION TO

BE DETERMINED BY THE CONTRACTOR TO BEST FIT THE LAYOUT OF THE JOB.

3. ALL EQUIPMENT SHALL BE TIGHTLY COVERED AND PROTECTED AGAINST DIRT, WATER, AND CHEMICAL OR MECHANICAL INJURY OR THEFT.

PLUMBING FIXTURES SHALL BE COVERED WITH HEAVY PAPER COVERINGS AFTER INSTALLATION AND SHALL BE THOROUGHLY CLEANED

AFTER COMPLETION OF THE PROJECT.

4. ALL MATERIALS SUCH AS VALVES, FITTINGS, PIPING, EQUIPMENT, PUMPS, COILS, ETC., SHALL BE PROPERLY PROTECTED, AND ALL PIPING OPENINGS SHALL BE TEMPORARILY CLOSED BY THE CONTRACTOR FOR THE WORK UNDER HIS CHARGE, ON A DAILY BASIS, AT THE END OF EACH WORKING DAY, SO AS TO PREVENT OBSTRUCTION AND DAMAGE. THE ABOVE REQUIREMENTS ARE MANDATORY.

5. THE CONTRACTOR SHALL SEE THAT ALL MATERIALS, INSTALLATION AND WORKMANSHIP IS PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF ALL FEDERAL APPLICABLE CODES, LAWS, OR ORDINANCES OF THE STATE OF VIRGINIA, AND FEDERAL AND STATE ENVIRONMENTAL PROTECTION REGULATIONS, STATE ENERGY CODES AND UTILITY REGULATORY AGENCIES.

6. ALL WORK SHALL BE FURTHER PERFORMED IN ACCORDANCE WITH THE NATIONAL BOARD OF FIRE UNDERWRITERS, THE PLUMBING AND BUILDING CODES, NATIONAL ELECTRICAL CODE, THE OCCUPATIONAL SAFETY AND HEALTH ACT, THE AMERICAN GAS ASSOCIATION, AND ALL SUCH OTHER SPECIFIC CODES AS MAY BE REFERRED TO IN THE INDIVIDUAL SECTIONS OF THE SPECIFICATIONS.

7. PIPE SIZES SHOWN ON THE DRAWINGS ARE THE MINIMUM SIZES ALLOWED REGARDLESS OF THE CODE MINIMUM, EXCEPT WHEN THE CODE

MINIMUM SIZE IS LARGER THAN THAT SHOWN.

8. THE CONTRACTOR SHALL MAINTAIN A CURRENT SET OF CONTRACT PRINTS ON THE CONSTRUCTION SITE AT ALL TIMES, ON WHICH HE SHALL ACCURATELY RECORD THE ACTUAL INSTALLATION OF ALL PLUMBING WORK. AS WORK PROGRESSES, MARK CHANGES MADE WHETHER RESULTING FROM JOB CONDITIONS, ADDENDA, FORMAL CHANGE ORDERS OR OTHER INSTRUCTIONS ISSUED BY THE ENGINEER.

9. THE PLUMBING CONTRACTOR SHALL INDICATE PROGRESS BY COLORING IN VARIOUS PIPES, FIXTURES, AND ASSOCIATED APPURTENANCES

EXACTLY AS THEY ARE ERECTED AND INSTALLED.

10. MARK ALL PIPE SIZES AND LOCATIONS DURING CONSTRUCTION. ALSO, MARK LOCATIONS OF ALL VALVES AND VARIOUS EQUIPMENT, APPARATUS, AND ASSOCIATED APPURTENANCES AS ERECTED WEEKLY DURING CONSTRUCTION.

11. AT THE COMPLETION OF THE JOB THESE PRINTS, INCORPORATING CHANGES, ADDENDA AND ADDED DATA NOTED ON MARKED-UP PRINTS, INCLUDING DIMENSIONED LOCATIONS OF UNDERGROUND PIPING BEYOND LIMITS OF BUILDING, SHALL BE SUBMITTED TO THE ENGINEER FOR FINAL REVIEW AND COMMENT. THE PRINTS WILL BE RETURNED WITH APPROPRIATE COMMENTS AND RECOMMENDATIONS. THESE CORRECTED PRINTS TOGETHER WITH CORRELATED PRINTS INDICATING ALL THE REVISIONS, ADDITIONS AND DELETIONS OF WORK, SHALL

FORM THE BASIS FOR PREPARING A SET OF RECORD DRAWINGS.

12. WHERE PIPING, AND OTHER PLUMBING APPURTENANCES PASS THROUGH FIRE PARTITIONS, FIRE WALLS, OR FLOORS, INSTALL A FIRE-STOP THAT PROVIDES AN EFFECTIVE BARRIER AGAINST THE SPREAD OF FIRE, SMOKE AND GASES. FIRE-STOP MATERIAL SHALL BE UL APPROVED, PACKED TIGHT AND COMPLETELY FILL CLEARANCES BETWEEN RACEWAYS AND OPENINGS. FLOOR, EXTERIOR WALL, AND ROOF SEALS SHALL ALSO BE MADE WATERTIGHT AS APPROVED BY THE ADMINISTRATIVE AUTHORITY.

13. ARRANGE AND INSTALL PIPING APPROXIMATELY AS INDICATED, STRAIGHT, PLUMB AND AS DIRECT AS POSSIBLE. FORM RIGHT ANGLES OR PARALLEL LINES WITH BUILDING WALLS. KEEP PIPES CLOSE TO WALLS, PARTITIONS AND CEILINGS, OFFSETTING ONLY WHERE NECESSARY TO FOLLOW WALLS AND AVOID INTERFERENCE WITH OTHER MECHANICAL ITEMS. LOCATE GROUPS OF PIPES PARALLEL TO EACH OTHER;

SPACE THEM AT A DISTANCE TO PERMIT ACCESS FOR SERVICING VALVES.

14. PIPING SHALL BE PITCHED TO POINTS OF DRAINAGE WITH CONSTANT UNIFORM SLOPE.

15. INSTALL HORIZONTAL PIPING AS HIGH AS POSSIBLE WITHOUT SAGS OR HUMPS.

16. WHERE CHANGES IN PIPE SIZES OCCUR, USE ONLY REDUCING FITTINGS.

17. FOR DRAINAGE PIPING CHANGES IN DIRECTION, USE LONG SWEEP WHERE POSSIBLE, OTHERWISE, SHORT SWEEP 1/4 BENDS, OR COMBINATION WYE AND 1/8 BENDS; USE SANITARY TEE BRANCHES ONLY FOR HORIZONTAL BRANCHES DISCHARGING TO STACKS.

18. WATER SUPPLY TO ALL FIXTURES AND CONTAINERS SHALL BE SO INSTALLED AS TO PREVENT POSSIBLE BACK SIPHONAGE OF POLLUTED WATER. ALL SUPPLIES SHALL BE EITHER ABOVE THE FLOOD RIM OF THE FIXTURE OR SEPARATED FROM THE DRAINAGE END BY MEANS OF

AN APPROVED VACUUM BREAKERS.

19. PROVIDE PIPING AND FIXTURE TRAPS. CONNECT TO FIXTURES AND OTHER EQUIPMENT INDICATED OR SPECIFIED AS REQUIRING SOIL, WASTE, DRAIN AND VENT FACILITIES.

20. LAY ALL PIPING TRUE TO LINE AND GRADE, FIT ENDS TOGETHER, MATCH SO THAT SEWER OR DRAIN WILL HAVE SMOOTH AND UNIFORM INSERT. FOLLOW LOCATIONS AND ELEVATIONS AT SITE. AS THE PIPE LAYING PROGRESSES, CLEAR PIPE INTERIOR OF CEMENT, DIRT, AND OTHER FOREIGN MATERIALS. DURING WORK STOPPAGE PERIODS, PROVIDE EFFECTIVE PLUGS OR COVERS FOR OPEN ENDS OF PIPE AND

DRAINS.

21. PROVIDE CLEANOUTS WHERE INDICATED AND AT INTERVALS OF 100' OR AS REQUIRED BY LOCAL PLUMBING CODE AND WHERE REQUIRED AT CHANGES OF DIRECTIONS OF SOIL AND WASTE STACKS. INSTALL CLEANOUTS SO AS TO BE ACCESSIBLE FOR EASY REMOVAL AND TO PROVIDE CLEARANCE FOR RODDING. CLEANOUTS SHALL BE THE SAME SIZE AS PIPE SERVED EXCEPT THAT NO CLEANOUT NEED BE

LARGER THAN FOUR INCHES.

22. EXTEND VENT PIPES 12 INCHES ABOVE ROOF AND 10FT MINIMUM AWAY FROM ANY FRESH AIR INTAKES.

23. SANITARY VENT PIPING SHALL BE GRADED SO THAT THE AIRFLOW TO THE OUTSIDE WILL BE CONTINUOUSLY UPWARD AND SO THAT NO

LOW POINTS WILL BE DRAINED.

24. MAKE TIGHT CONNECTION BETWEEN WATER CLOSET FLANGES AND EARTHENWARE FIXTURE BY MEANS OF AN APPROVED MOLDED WAX

RING OR SETTING COMPOUND AND BOLTING.

25. VENTS: PROVIDE FLASHING FOR STACKS PASSING THROUGH ROOF. MAKE WATER-TIGHT AT ROOF WITH 4 LB. SHEET LEAD; EXTEND INTO ROOFING FELTS AT LEAST 24" FROM PIPES. EXTEND LEAD COLLAR UP AROUND OUTSIDE AND TURN DOWN INSIDE VENTS AT THE TOP.

LOCATE VENT THROUGH ROOF 10FT MINIMUM AWAY FROM ANY FRESH AIR INTAKE.

26. ALL PLUMBING FIXTURES AND PIPING IS TO BE LISTED BY AN APPROVED LISTING AND TESTING AGENCY AND PROPERLY LABELED.

27. COORDINATE ALL LOCATIONS, SIZES, AND ELEVATIONS OF ALL SLEEVES THROUGH WALLS, BEAMS, SLABS AND FOOTING WITH STRUCTURAL AND ARCHITECTURAL DRAWINGS. ALL PIPES SLEEVING THROUGH FOOTINGS SHALL HAVEA SLEEVE DIAMETER OF TWO PIPE SIZES OVER THE PIPE PASSING THROUGH THE FOOTING. NO PIPE TO BE PLACED THROUGH FOOTING UNLESS APPROVED BY THE STRUCTURAL

ENGINEER.

28. FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 POUNDS.

29. DISINFECTION OF POTABLE WATER SYSTEM SHALL COMPLY WITH THE LOCAL AND THE FEDERAL PLUMBING CODE.

30. HUNG WASTE PIPING SHALL BE STRUCTURALLY SUPPORTED AS TIGHT AS POSSIBLE BELOW THE STRUCTURAL BEAMS TOGAIN MORE HEAD SPACE AS IT PITCH TOWARDS THE LOWEST POINT TO KEEP WASTE PIPING WITHIN THE CEILING SPACE.

P-001-AM

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETPLUMBING SCHEDULES AND DETAILS -

ADMINISTRATION BUILDING

ADMINISTRATION

P-002-AM

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETPLUMBING SCHEDULES AND DETAILS -

ADMINISTRATION BUILDING

HALL

M

EN

R R

ST

O

RA

G

E

HALL

ST

O

RA

G E

OFFICE

HALL

LOBBY

W O

M

EN

R R

OFFICE

OFFICE

FURNACE

ROOM

STAFF RRBREAK

ROOM

ST

AI

R

GARAGE

UTILITY

CLOSET

GARAGEGARAGE

FIRST FLOOR MECHANICAL DEMOLITION PLAN -

ADMINISTRATION BUILDING

EXISTING WATER SERVICE DETAIL

NO SCALE:

PD-101-AM

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETFIRST FLOOR PLUMBING DEMOLITION

PLAN - ADMINISTRATION BUILDING

REF

UP

REF

ICE

MAKER

M O

NI

TO

R

SCALE: 1/4"= 1'-0"

FIRST FLOOR MECHANICAL REVISED PLAN -

ADMINISTRATION BUILDING

P-101-AM

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETFIRST FLOOR WASTE REVISED PLAN -

ADMINISTRATION BUILDING

REF

REF

ICE

MAKER

M O

NI

TO

R

ADMIN FIRST FLOOR PIPING REVISED PLAN

SCALE: 1/4"= 1'-0"

P-201-AM

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETFIRST FLOOR PLUMBING REVISED

PLAN - ADMINISTRATION BUILDING

DN

ADMIN SECOND FLOOR MECHANICAL REVISED PLAN

SCALE: 1/4"= 1'-0"

P-202-AM

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETSECOND FLOOR PLUMBING REVISED

PLAN - ADMINISTRATION BUILDING

PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS,

WITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE,

BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES, FILTERS AND STRAINERS,

TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION

WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT

DOCUMENTS TO COR FOR RESOLUTIONS.

INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING MECHANICAL

EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND DUCTWORK WAS OBTAINED

FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY FIELD OBSERVATION, HOWEVER,

ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE, CERTAIN INFORMATION CONCERNING

THE LOCATION OF THE EXISTING MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING,

PLUMBING AND DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S)

AND DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT HAS

BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER, ALL EXISTING

WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS

OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN

THESE PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE

ENGINEER FOR VERIFICATION AND/OR CORRECTION.

1. PLUMBING CONTRACT DRAWINGS ARE IN PART DIAGRAMMATIC, COVERING THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF THE EQUIPMENT, PIPING, ETC., AND THE APPROXIMATE SIZE OF EQUIPMENT AND MATERIALS. THE CONTRACTOR SHALL FOLLOW THESE DRAWINGS IN LAYING OUT THE PLUMBING WORK. PLUMBING CONTRACTOR SHALL CONSULT GENERAL, SPRINKLER, HEATING/VENTILATING/AIR CONDITIONING CONTRACTOR AND ELECTRICAL DRAWINGS TO FAMILIARIZE HIMSELF WITH THAT WORK AND TO

VERIFY THE SPACES IN WHICH THE PLUMBING WORK WILL BE INSTALLED.

2. BECAUSE OF THE NATURE AND SCALE OF THE DRAWINGS, CERTAIN BASIC PLUMBING ITEMS SUCH AS UNIONS, FITTINGS, ELBOWS, ETC., MAY NOT BE SHOWN. WHERE SUCH ITEMS ARE REQUIRED BY OTHER SECTIONS OF THE SPECIFICATIONS, OR WHERE THEY ARE REQUIRED BY THE NATURE OF THE WORK OR BY CODES AND REGULATIONS, THEY SHALL BE FURNISHED AND INSTALLED AT NO ADDITIONAL COST TO THE OWNER. THE DRAWINGS INDICATE GENERAL LOCATIONS OF PIPING, EQUIPMENT, DUCTWORK AND SIMILAR. THE EXACT LOCATION TO

BE DETERMINED BY THE CONTRACTOR TO BEST FIT THE LAYOUT OF THE JOB.

3. ALL EQUIPMENT SHALL BE TIGHTLY COVERED AND PROTECTED AGAINST DIRT, WATER, AND CHEMICAL OR MECHANICAL INJURY OR THEFT.

PLUMBING FIXTURES SHALL BE COVERED WITH HEAVY PAPER COVERINGS AFTER INSTALLATION AND SHALL BE THOROUGHLY CLEANED

AFTER COMPLETION OF THE PROJECT.

4. ALL MATERIALS SUCH AS VALVES, FITTINGS, PIPING, EQUIPMENT, PUMPS, COILS, ETC., SHALL BE PROPERLY PROTECTED, AND ALL PIPING OPENINGS SHALL BE TEMPORARILY CLOSED BY THE CONTRACTOR FOR THE WORK UNDER HIS CHARGE, ON A DAILY BASIS, AT THE END OF EACH WORKING DAY, SO AS TO PREVENT OBSTRUCTION AND DAMAGE. THE ABOVE REQUIREMENTS ARE MANDATORY.

5. THE CONTRACTOR SHALL SEE THAT ALL MATERIALS, INSTALLATION AND WORKMANSHIP IS PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF ALL FEDERAL APPLICABLE CODES, LAWS, OR ORDINANCES OF THE STATE OF VIRGINIA, AND FEDERAL AND STATE ENVIRONMENTAL PROTECTION REGULATIONS, STATE ENERGY CODES AND UTILITY REGULATORY AGENCIES.

6. ALL WORK SHALL BE FURTHER PERFORMED IN ACCORDANCE WITH THE NATIONAL BOARD OF FIRE UNDERWRITERS, THE PLUMBING AND BUILDING CODES, NATIONAL ELECTRICAL CODE, THE OCCUPATIONAL SAFETY AND HEALTH ACT, THE AMERICAN GAS ASSOCIATION, AND ALL SUCH OTHER SPECIFIC CODES AS MAY BE REFERRED TO IN THE INDIVIDUAL SECTIONS OF THE SPECIFICATIONS.

7. PIPE SIZES SHOWN ON THE DRAWINGS ARE THE MINIMUM SIZES ALLOWED REGARDLESS OF THE CODE MINIMUM, EXCEPT WHEN THE CODE

MINIMUM SIZE IS LARGER THAN THAT SHOWN.

8. THE CONTRACTOR SHALL MAINTAIN A CURRENT SET OF CONTRACT PRINTS ON THE CONSTRUCTION SITE AT ALL TIMES, ON WHICH HE SHALL ACCURATELY RECORD THE ACTUAL INSTALLATION OF ALL PLUMBING WORK. AS WORK PROGRESSES, MARK CHANGES MADE WHETHER RESULTING FROM JOB CONDITIONS, ADDENDA, FORMAL CHANGE ORDERS OR OTHER INSTRUCTIONS ISSUED BY THE ENGINEER.

9. THE PLUMBING CONTRACTOR SHALL INDICATE PROGRESS BY COLORING IN VARIOUS PIPES, FIXTURES, AND ASSOCIATED APPURTENANCES

EXACTLY AS THEY ARE ERECTED AND INSTALLED.

10. MARK ALL PIPE SIZES AND LOCATIONS DURING CONSTRUCTION. ALSO, MARK LOCATIONS OF ALL VALVES AND VARIOUS EQUIPMENT, APPARATUS, AND ASSOCIATED APPURTENANCES AS ERECTED WEEKLY DURING CONSTRUCTION.

11. AT THE COMPLETION OF THE JOB THESE PRINTS, INCORPORATING CHANGES, ADDENDA AND ADDED DATA NOTED ON MARKED-UP PRINTS, INCLUDING DIMENSIONED LOCATIONS OF UNDERGROUND PIPING BEYOND LIMITS OF BUILDING, SHALL BE SUBMITTED TO THE ENGINEER FOR FINAL REVIEW AND COMMENT. THE PRINTS WILL BE RETURNED WITH APPROPRIATE COMMENTS AND RECOMMENDATIONS. THESE CORRECTED PRINTS TOGETHER WITH CORRELATED PRINTS INDICATING ALL THE REVISIONS, ADDITIONS AND DELETIONS OF WORK, SHALL

FORM THE BASIS FOR PREPARING A SET OF RECORD DRAWINGS.

12. WHERE PIPING, AND OTHER PLUMBING APPURTENANCES PASS THROUGH FIRE PARTITIONS, FIRE WALLS, OR FLOORS, INSTALL A FIRE-STOP THAT PROVIDES AN EFFECTIVE BARRIER AGAINST THE SPREAD OF FIRE, SMOKE AND GASES. FIRE-STOP MATERIAL SHALL BE UL APPROVED, PACKED TIGHT AND COMPLETELY FILL CLEARANCES BETWEEN RACEWAYS AND OPENINGS. FLOOR, EXTERIOR WALL, AND ROOF SEALS SHALL ALSO BE MADE WATERTIGHT AS APPROVED BY THE ADMINISTRATIVE AUTHORITY.

13. ARRANGE AND INSTALL PIPING APPROXIMATELY AS INDICATED, STRAIGHT, PLUMB AND AS DIRECT AS POSSIBLE. FORM RIGHT ANGLES OR PARALLEL LINES WITH BUILDING WALLS. KEEP PIPES CLOSE TO WALLS, PARTITIONS AND CEILINGS, OFFSETTING ONLY WHERE NECESSARY TO FOLLOW WALLS AND AVOID INTERFERENCE WITH OTHER MECHANICAL ITEMS. LOCATE GROUPS OF PIPES PARALLEL TO EACH OTHER;

SPACE THEM AT A DISTANCE TO PERMIT ACCESS FOR SERVICING VALVES.

14. PIPING SHALL BE PITCHED TO POINTS OF DRAINAGE WITH CONSTANT UNIFORM SLOPE.

15. INSTALL HORIZONTAL PIPING AS HIGH AS POSSIBLE WITHOUT SAGS OR HUMPS.

16. WHERE CHANGES IN PIPE SIZES OCCUR, USE ONLY REDUCING FITTINGS.

17. FOR DRAINAGE PIPING CHANGES IN DIRECTION, USE LONG SWEEP WHERE POSSIBLE, OTHERWISE, SHORT SWEEP 1/4 BENDS, OR COMBINATION WYE AND 1/8 BENDS; USE SANITARY TEE BRANCHES ONLY FOR HORIZONTAL BRANCHES DISCHARGING TO STACKS.

18. WATER SUPPLY TO ALL FIXTURES AND CONTAINERS SHALL BE SO INSTALLED AS TO PREVENT POSSIBLE BACK SIPHONAGE OF POLLUTED WATER. ALL SUPPLIES SHALL BE EITHER ABOVE THE FLOOD RIM OF THE FIXTURE OR SEPARATED FROM THE DRAINAGE END BY MEANS OF

AN APPROVED VACUUM BREAKERS.

19. PROVIDE PIPING AND FIXTURE TRAPS. CONNECT TO FIXTURES AND OTHER EQUIPMENT INDICATED OR SPECIFIED AS REQUIRING SOIL, WASTE, DRAIN AND VENT FACILITIES.

20. LAY ALL PIPING TRUE TO LINE AND GRADE, FIT ENDS TOGETHER, MATCH SO THAT SEWER OR DRAIN WILL HAVE SMOOTH AND UNIFORM INSERT. FOLLOW LOCATIONS AND ELEVATIONS AT SITE. AS THE PIPE LAYING PROGRESSES, CLEAR PIPE INTERIOR OF CEMENT, DIRT, AND OTHER FOREIGN MATERIALS. DURING WORK STOPPAGE PERIODS, PROVIDE EFFECTIVE PLUGS OR COVERS FOR OPEN ENDS OF PIPE AND

DRAINS.

21. PROVIDE CLEANOUTS WHERE INDICATED AND AT INTERVALS OF 100' OR AS REQUIRED BY LOCAL PLUMBING CODE AND WHERE REQUIRED AT CHANGES OF DIRECTIONS OF SOIL AND WASTE STACKS. INSTALL CLEANOUTS SO AS TO BE ACCESSIBLE FOR EASY REMOVAL AND TO PROVIDE CLEARANCE FOR RODDING. CLEANOUTS SHALL BE THE SAME SIZE AS PIPE SERVED EXCEPT THAT NO CLEANOUT NEED BE

LARGER THAN FOUR INCHES.

22. EXTEND VENT PIPES 12 INCHES ABOVE ROOF AND 10FT MINIMUM AWAY FROM ANY FRESH AIR INTAKES.

23. SANITARY VENT PIPING SHALL BE GRADED SO THAT THE AIRFLOW TO THE OUTSIDE WILL BE CONTINUOUSLY UPWARD AND SO THAT NO

LOW POINTS WILL BE DRAINED.

24. MAKE TIGHT CONNECTION BETWEEN WATER CLOSET FLANGES AND EARTHENWARE FIXTURE BY MEANS OF AN APPROVED MOLDED WAX

RING OR SETTING COMPOUND AND BOLTING.

25. VENTS: PROVIDE FLASHING FOR STACKS PASSING THROUGH ROOF. MAKE WATER-TIGHT AT ROOF WITH 4 LB. SHEET LEAD; EXTEND INTO ROOFING FELTS AT LEAST 24" FROM PIPES. EXTEND LEAD COLLAR UP AROUND OUTSIDE AND TURN DOWN INSIDE VENTS AT THE TOP.

LOCATE VENT THROUGH ROOF 10FT MINIMUM AWAY FROM ANY FRESH AIR INTAKE.

26. ALL PLUMBING FIXTURES AND PIPING IS TO BE LISTED BY AN APPROVED LISTING AND TESTING AGENCY AND PROPERLY LABELED.

27. COORDINATE ALL LOCATIONS, SIZES, AND ELEVATIONS OF ALL SLEEVES THROUGH WALLS, BEAMS, SLABS AND FOOTING WITH STRUCTURAL AND ARCHITECTURAL DRAWINGS. ALL PIPES SLEEVING THROUGH FOOTINGS SHALL HAVEA SLEEVE DIAMETER OF TWO PIPE SIZES OVER THE PIPE PASSING THROUGH THE FOOTING. NO PIPE TO BE PLACED THROUGH FOOTING UNLESS APPROVED BY THE STRUCTURAL

ENGINEER.

28. FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 POUNDS.

29. DISINFECTION OF POTABLE WATER SYSTEM SHALL COMPLY WITH THE LOCAL AND THE FEDERAL PLUMBING CODE.

30. HUNG WASTE PIPING SHALL BE STRUCTURALLY SUPPORTED AS TIGHT AS POSSIBLE BELOW THE STRUCTURAL BEAMS TOGAIN MORE HEAD SPACE AS IT PITCH TOWARDS THE LOWEST POINT TO KEEP WASTE PIPING WITHIN THE CEILING SPACE.

P-001-GS

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETGENERAL NOTES AND DETAILS

- GARAGE STORAGE

GARGAE STORAGE

GARAGE STORAGE FIRST FLOOR PLUMBING PLAN

GAS ENTRY DETAIL

NO SCALE:

P-101-GS

Project Number

Drawing Number

Project Title

Location: Baltimore National Cemetery 5501 Frederick Avenue, Baltimore, MD 21228

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT OF RECORD

ARCHITURA CORPORATION

9880 Westpoint Drive, Suite #400 Indianapolis, IN 46256-3384

PH: (317) 348-1000

POC: Michael Conly, AIA, NCARB, President

CONSULTANTS

321 4 5 6 7 8 9 10

802-CM 3023

Project Director

07.02.2021 D.H. M.V.Revisions: Date:

FACILITY RENOVATION, IMPROVEMENTS AND

REPAIRS

Office of Construction and Facilities Management

LICENSE #19379

EXP. 03.15.2020

CIVIL/STRUCTURAL ENGINEER

KCI Technologies Inc.

(302) 731-9176

MEP ENGINEER

Design-Aire Engineering 317-464-9090

LANDSCAPE ARCHITECT

Pashek + MTR, Ltd.

412-321-6362

IRRIGATION DESIGNER

Aqua Engineering, Inc.

(970) 372-6104

BID SETFIRST FLOOR PLUMBING PLAN -

GARAGE STORAGE

GARGAE STORAGE

PERSONS STANDING AT FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS,

WITHOUT THE USE OF PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE,

BUT ARE NOT LIMITED TO: ALL TYPES OF VALVES, FILTERS AND STRAINERS,

TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION

WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT

DOCUMENTS TO COR FOR RESOLUTIONS.

INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING MECHANICAL

EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING, PLUMBING AND DUCTWORK WAS OBTAINED

FROM ORIGINAL DESIGN DRAWINGS AND/OR CURSORY FIELD OBSERVATION, HOWEVER,

ACTUAL "ASBUILT" DRAWINGS WERE NOT AVAILABLE, CERTAIN INFORMATION CONCERNING

THE LOCATION OF THE EXISTING MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT, PIPING,

PLUMBING AND DUCTWORK HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT LOCATION(S)

AND DIRECTION OF FLOW OF ALL EXISTING WORK IS UNKNOWN. REASONABLE EFFORT HAS

BEEN MADE TO ACCURATELY DEPICT THE EXISTING CONDITIONS, HOWEVER, ALL EXISTING

WORK MUST BE VERIFIED IN THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS

OF FLOW, DEPTH, SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN

THESE PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE

ENGINEER FOR VERIFICATION AND/OR CORRECTION.

1. PLUMBING CONTRACT DRAWINGS ARE IN PART DIAGRAMMATIC, COVERING THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF THE EQUIPMENT, PIPING, ETC., AND THE APPROXIMATE SIZE OF EQUIPMENT AND MATERIALS. THE CONTRACTOR SHALL FOLLOW THESE DRAWINGS IN LAYING OUT THE PLUMBING WORK. PLUMBING CONTRACTOR SHALL CONSULT GENERAL, SPRINKLER, HEATING/VENTILATING/AIR CONDITIONING CONTRACTOR AND ELECTRICAL DRAWINGS TO FAMILIARIZE HIMSELF WITH THAT WORK AND TO

VERIFY THE SPACES IN WHICH THE PLUMBING WORK WILL BE INSTALLED.

2. BECAUSE OF THE NATURE AND SCALE OF THE DRAWINGS, CERTAIN BASIC PLUMBING ITEMS SUCH AS UNIONS, FITTINGS, ELBOWS, ETC., MAY NOT BE SHOWN. WHERE SUCH ITEMS ARE REQUIRED BY OTHER SECTIONS OF THE SPECIFICATIONS, OR WHERE THEY ARE REQUIRED BY THE NATURE OF THE WORK OR BY CODES AND REGULATIONS, THEY SHALL BE FURNISHED AND INSTALLED AT NO ADDITIONAL COST TO THE OWNER. THE DRAWINGS INDICATE GENERAL LOCATIONS OF PIPING, EQUIPMENT, DUCTWORK AND SIMILAR. THE EXACT LOCATION TO

BE DETERMINED BY THE CONTRACTOR TO BEST FIT THE LAYOUT OF THE JOB.

3. ALL EQUIPMENT SHALL BE TIGHTLY COVERED AND PROTECTED AGAINST DIRT, WATER, AND CHEMICAL OR MECHANICAL INJURY OR THEFT.

PLUMBING FIXTURES SHALL BE COVERED WITH HEAVY PAPER COVERINGS AFTER INSTALLATION AND SHALL BE THOROUGHLY CLEANED

AFTER COMPLETION OF THE PROJECT.

4. ALL MATERIALS SUCH AS VALVES, FITTINGS, PIPING, EQUIPMENT, PUMPS, COILS, ETC., SHALL BE PROPERLY PROTECTED, AND ALL PIPING OPENINGS SHALL BE TEMPORARILY CLOSED BY THE CONTRACTOR FOR THE WORK UNDER HIS CHARGE, ON A DAILY BASIS, AT THE END OF EACH WORKING DAY, SO AS TO PREVENT OBSTRUCTION AND DAMAGE. THE ABOVE REQUIREMENTS ARE MANDATORY.

5. THE CONTRACTOR SHALL SEE THAT ALL MATERIALS, INSTALLATION AND WORKMANSHIP IS PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF ALL FEDERAL APPLICABLE CODES, LAWS, OR ORDINANCES OF THE STATE OF VIRGINIA, AND FEDERAL AND STATE ENVIRONMENTAL PROTECTION REGULATIONS, STATE ENERGY CODES AND UTILITY REGULATORY AGENCIES.

6. ALL WORK SHALL BE FURTHER PERFORMED IN ACCORDANCE WITH THE NATIONAL BOARD OF FIRE UNDERWRITERS, THE PLUMBING AND BUILDING CODES, NATIONAL ELECTRICAL CODE, THE OCCUPATIONAL SAFETY AND HEALTH ACT, THE AMERICAN GAS ASSOCIATION, AND ALL SUCH OTHER SPECIFIC CODES AS MAY BE REFERRED TO IN THE INDIVIDUAL SECTIONS OF THE SPECIFICATIONS.

7. PIPE SIZES SHOWN ON THE DRAWINGS ARE THE MINIMUM SIZES ALLOWED REGARDLESS OF THE CODE MINIMUM, EXCEPT WHEN THE CODE

MINIMUM SIZE IS LARGER THAN THAT SHOWN.

8. THE CONTRACTOR SHALL MAINTAIN A CURRENT SET OF CONTRACT PRINTS ON THE CONSTRUCTION SITE AT ALL TIMES, ON WHICH HE SHALL ACCURATELY RECORD THE ACTUAL INSTALLATION OF ALL PLUMBING WORK. AS WORK PROGRESSES, MARK CHANGES MADE WHETHER RESULTING FROM JOB CONDITIONS, ADDENDA, FORMAL CHANGE ORDERS OR OTHER INSTRUCTIONS ISSUED BY THE ENGINEER.

9. THE PLUMBING CONTRACTOR SHALL INDICATE PROGRESS BY COLORING IN VARIOUS PIPES, FIXTURES, AND ASSOCIATED APPURTENANCES

EXACTLY AS THEY ARE ERECTED AND INSTALLED.

10. MARK ALL PIPE SIZES AND LOCATIONS DURING CONSTRUCTION. ALSO, MARK LOCATIONS OF ALL VALVES AND VARIOUS EQUIPMENT, APPARATUS, AND ASSOCIATED APPURTENANCES AS ERECTED WEEKLY DURING CONSTRUCTION.

11. AT THE COMPLETION OF THE JOB THESE PRINTS, INCORPORATING CHANGES, ADDENDA AND ADDED DATA NOTED ON MARKED-UP PRINTS, INCLUDING DIMENSIONED LOCATIONS OF UNDERGROUND PIPING BEYOND LIMITS OF BUILDING, SHALL BE SUBMITTED TO THE ENGINEER FOR FINAL REVIEW AND COMMENT. THE PRINTS WILL BE RETURNED WITH APPROPRIATE COMMENTS AND RECOMMENDATIONS. THESE CORRECTED PRINTS TOGETHER WITH CORRELATED PRINTS INDICATING ALL THE REVISIONS, ADDITIONS AND DELETIONS OF WORK, SHALL

FORM THE BASIS FOR PREPARING A SET OF RECORD DRAWINGS.

12. WHERE PIPING, AND OTHER PLUMBING APPURTENANCES PASS THROUGH FIRE PARTITIONS, FIRE WALLS, OR FLOORS, INSTALL A FIRE-STOP THAT PROVIDES AN EFFECTIVE BARRIER AGAINST THE SPREAD OF FIRE, SMOKE AND GASES. FIRE-STOP MATERIAL SHALL BE UL APPROVED, PACKED TIGHT AND COMPLETELY FILL CLEARANCES BETWEEN RACEWAYS AND OPENINGS. FLOOR, EXTERIOR WALL, AND ROOF SEALS SHALL ALSO BE MADE WATERTIGHT AS APPROVED BY THE ADMINISTRATIVE AUTHORITY.

13.