This is a pre-solicitation notice for an invitation for bid to provide gravesite expansion and new bathroom construction at the National Memorial Cemetery of the Pacific in Honolulu, Hawaii. The solicitation number is 36C78621B0012 and will be issued on or around July 15, 2021. The acquisition type is an IFB with a magnitude between $5-10 million. The NAICS code is 237990 and the size standard is $36.5 million. This is a 100% set-aside for verified Service-Disabled Veteran-Owned Small Businesses. Firms must be registered in SAM, VIP, and CVE to be eligible for award. Offers will only be accepted from verified SDVOSBs. The point of contact is Auvorie Benson via email. Amendments will be posted to Contract Opportunities and firms must acknowledge all amendments.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
S
SD
GENERAL ELECTRICAL AND TECHNOLOGY EQUIPMENT SCHEDULE
A1
E
E
OC
D
K
HUBBELL
LEVITON
PASS & SEYMOUR
COOPER
ALL SWITCH, RECEPTACLE, AND OUTLET COLORS SHALL BE VERIFIED WITH ARCHITECT,
UNLESS INDICATED OTHERWISE.
1 DEVICE
COLOR
HUBBELL
LEVITON
PASS & SEYMOUR
COOPER
ALL SWITCHES, RECEPTACLES, AND OUTLETS SHALL BE COMPLETE WITH #302 STAINLESS
STEEL COVERPLATES IN FINISHED SPACES WHERE WALLS ARE FINISHED; #302 STAINLESS
STEEL COVERPLATES IN UNFINISHED SPACES FOR FLUSH BOXES; AND GALVANIZED STEEL
COVERPLATES IN UNFINISHED SPACES FOR SURFACE MOUNTED BOXES. WHERE SEVERAL
DEVICES ARE GANGED TOGETHER, THE COVER PLATE SHALL BE OF THE GANGED STYLE FOR
THE NUMBER OF DEVICES USED.
2 COVER
PLATES
HUBBELL HBL1221
LEVITON 1221-2
PASS & SEYMOUR PS20AC1
COOPER AH2221
SWITCH, SINGLE POLE, SINGLE THROW, 120/277 VOLT, 20 AMP. TOGGLE HANDLE, MAINTAINED
CONTACT, SIDE AND BACK WIRED,
HUBBELL HBL1221L
LEVITON 1221-2L
PASS & SEYMOUR
PS20AC1-L
COOPER AH2221L
SWITCH, KEY LOCK TYPE, SINGLE POLE, SINGLE THROW, 120/277 VOLT 20 AMP MAINTAINED
CONTACT, SIDE AND BACK WIRED, PROVIDE KEY TO OWNER,
WATT STOPPER
DT 300 SERIES
HUBBELL INC.
OMNI-DT2000 OR
ATD2000C
GREENGATE OAC-DT
LEVITON OSC##-MOW
OCCUPANCY SENSOR, CEILING MOUNTED 360 DEGREE, DUAL TECHNOLOGY PASSIVE
INFRARED/ULTRASONIC FREQUENCY GREATER THAN 40 KHz, DUAL SENSING VERIFICATIONS
(REQUIRES BOTH TECHNOLOGIES TO ACTIVATE), EITHER TECHNOLOGY MAINTAINS ON
STATUS, INTEGRATED AMBIENT LIGHT LEVEL SENSOR (2-200 FC RANGE), ADJUSTABLE
SENSITIVITY AND TIME DELAY, INTEGRATED ISOLATED RELAY CONTACT, 5 YEAR WARRANTY.
SENSOR SHALL CONTROL ALL CIRCUITS IN AREA, UNLESS NOTED OTHERWISE. INITIAL
SETTINGS: TIME DELAY 10 MINUTES, AMBIENT SENSOR 40FC. CONTRACTOR SHALL SUBMIT
MANUFACTURER SUPPLIED SENSOR COVERAGE DRAWING FOR SHOP DRAWING REVIEW.
PARAGON CW-201-70
TORK 2107
INTERMATIC K4236
PHOTOCELL, 120/277 VOLT, 1800 V.A. RATED, SINGLE POLE, SINGLE THROW CONTACT,
WEATHERPROOF AND CORROSION PROOF ENCLOSURE. MOUNT FACING NORTH. U.L. LISTED.
PC
9 HUBBELL
GFTR20/RW57300
LEVITON
GFWT2/5977-CL
PASS & SEYMOUR
2097TRWR/WIUC10-C
COOPER WRSGF20/WIU-1
RECEPTACLE, GROUND FAULT DUPLEX, WEATHER RESISTANT, WEATHERPROOF
COVERPLATE, 125 VOLT, 20 AMP, 3 WIRE GROUNDING TYPE, N.E.M.A. 5-20R. TEST AND RESET
BUTTONS IN IMPACT RESISTANT THERMOPLASTIC FACE, NEMA 3R RATED WHILE IN USE, CAST
ALUMINUM, NON-LOCKING, STANDARD DEPTH, VERTICAL MOUNT.
W
REFER TO SPECIFICATIONSELECTRICAL CONNECTION TO EQUIPMENT AND MOTORS, SIZE PER N.E.C. COORDINATE
REQUIREMENTS WITH CONTRACTOR FURNISHING EQUIPMENT OR MOTOR. REFER TO
SPECIFICATIONS AND GENERAL INSTALLATION NOTES FOR TERMINATIONS TO MOTORS.
RECEPTACLE, DUPLEX, 125 VOLT, 20 AMP,3 WIRE GROUNDING TYPE, N.E.M.A.
5-20R, IMPACT RESISTANT THERMOPLASTIC FACE, STEEL BACK STRAP.
HUBBELL 5352A
LEVITON 5362-S
PASS & SEYMOUR 5362
COOPER 5352
HUBBELL GF20L
LEVITON GFNT2
PASS & SEYMOUR 2097
COOPER SGF20
RECEPTACLE, GROUND FAULT DUPLEX, 125 VOLT, 20 AMP, 3 WIRE GROUNDING
TYPE, N.E.M.A. 5-20R. TEST AND RESET BUTTONS IN IMPACT RESISTANT
THERMOPLASTIC FACE.
13 SQUARE D 7440
MINI-POWER ZONE
GENERAL ELECTRIC
CUTLER-HAMMER
SIEMENS
PACKAGED POWER PANELBOARD, CONSISTING OF A PRIMARY BREAKER, 25 KVA DRY TYPE
TRANSFORMER, SECONDARY PROTECTION AND A 240/120 VOLT, 1 PHASE PANELBOARD.
SURFACE MOUNT NEMA 3R ENCLOSURE, GROUND BUS, REFER TO SCHEDULES FOR SIZE AND
CONFIGURATION, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
'MPC-1'
19 FIBER OPTIC SPLICE CASE FOR EXTERIOR USE. PROVIDES UP TO (3) FIBER ENTRANCE PORTS
FOR FIBER SPLICING OF UP TO 36 SINGLE FUSION SPLICES AND 72 WITH AN EXPANDED
OPTION. INCLUDES MOUNTING IN HANDHOLES, LOCK-TAPE SEALING SYSTEM, PERMANENT
NEOPRENE GASKET SYST.
PERFORMED LINE PRODUCTS
COYOTE RUNT CLOSURE KIT
OR PRE-APPROVED EQUAL.
SC-FSC-1
18 WALL MOUNTED SPLICE HOUSING. ACCOMMODATES EITHER 16 0.2" (TYPE 2S OR 2R) OR 11 0.4"
(TYPE 4S OR 4R) SPLICE TRAYS. FRONT LOCKING DOOR, SLIDE OUT RAILS TO FACILITATE
FRONT ACCESS. DIMENSION:13.5" X 22.5" X 2.5" (H X W XD).
PROVIDE WITH CLAMP AND GROUNDING.
CORING SPLICE HOUSING
WSH-16SPT SPLICE TRAY
M67-112
OR PRE-APPROVED EQUAL.
SC-FDC-1
ALLIED TELESIS
MMC200-SERIES
20 COPPER TO FIBER MINI MEDIA AND RATE CONVERTER. FIXED SC/ST/LC OR SFP (100MB OR
1000MB) OPTICS. 12VDC POWER SUPPLY AND POWER CONSUMPTION IS 140mA@12VTYPICAL.
WALL MOUNTABLE USING MMCWLMT. VIRTUAL LAN SUPPORT. THE TWISTED-PAIR COPPER
PORT HAS AN RJ-45 CONNECTOR SUPPORTING EITHER 100MBPS OR 1000MBPS.
REFER TO SPECIFICATIONS FOR FIBER TYPE AND MORE INFORMATION.
SC-MEDIA-1
HUBBELL/QUAZITE
PG2436BB18
PG2436HAOO
CARSON INDUSTRIES
H SERIES
ARMORCAST
HIGHLINE PRODUCTS
SYNERTECH
HANDHOLE, COMPOSITE POLYMER CONCRETE BODY AND COVER. STAINLESS STEEL
HARDWARE. BOLTED NON-SKID COVER RATED FOR 10,000 LB. DESIGN LOAD OCCASIONAL
NON-DELIBERATE VEHICULAR TRAFFIC. STACK UNITS TO ACHIEVE DEPTH SHOWN ON PLANS.
UNITS IN LANDSCAPED AREAS SHALL BE GREEN IN COLOR. 48"W, 48"L, 36"D OR DIMENSIONS
AS SHOWN ON PLANS.
10 HH-#
ITEM
NO.
SYMBOL DESCRIPTION APPROVED MANUFACTURERS
THE SYMBOLS AND THE EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING
SYSTEM.
CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO
MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE
DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD
COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.
15 JOHNSON CONTROLS -
SIMPLEX
NOTIFIER BY HONEYWELL
SIEMENS FIRE SAFETY
EDWARDS - EST
FIRE ALARM CONTROL PANEL, ADDRESSABLE SYSTEM, FEATURING INTERFACE WITH ANALOG
SENSING INITIATING DEVICES, EXPANDABLE MODULAR DESIGN, MICROPROCESSOR BASED
ELECTRONICS, 120 VAC OPERATION, SURFACE MOUNT. REFER TO SPECIFICATIONS FOR
COMPLETE REQUIREMENTS.
FAP-1
SMOKE DETECTOR, ADDRESSABLE, ANALOG PHOTOELECTRIC SENSOR, 24 VDC, 2-PIECE
DESIGN, LOW-PROFILE MOUNTING BASE WITH MULTI-FUNCTION LED INDICATOR, COMPLETE
WITH MOUNTING HARDWARE AND BACKBOX.
17 JOHNSON CONTROLS -
SIMPLEX
NOTIFIER BY HONEYWELL
SIEMENS FIRE SAFETY
EDWARDS - EST
JOHNSON CONTROLS -
SIMPLEX
NOTIFIER BY HONEYWELL
SIEMENS FIRE SAFETY
EDWARDS - EST
FIRE ALARM CEILING AUDIO/VISUAL NOTIFICATION APPLIANCE, ELECTRONIC HORN
WITH SELECTABLE CONTINUOUS OR TEMPORAL TONE, SELECTABLE SOUND OUTPUT,
AND HIGH-INTENSITY STROBE, WHITE HOUSING WITH RED LETTERING OR PICTOGRAM,
SEMI-FLUSH CEILING MOUNT, 24 VDC.
CANDELA RATINGS: A1=15, A3=30, A7=75, A9=95, AH=115, AS=177. CANDELA
RATING SHALL BE VISIBLE FROM THE OUTSIDE OF THE DEVICE.
11 GROVE CONCRETE
UTILITY CONCRETE
PRODUCTS, LLC
HARTFORD CONCRETE
PRODUCTS
OR APPROVED EQUAL
MANHOLE, CONCRETE BODY AND COVER. TYPE 20,000 LB. DESIGN LOAD OCCASIONAL
NON-DELIBERATE VEHICULAR TRAFFIC. 8'W X 10'L . ACCESSORIES PER THE SPECIFICATIONS.
REFER TO DETAIL 8/E500.
MH-#
HUBBELL/QUAZITE
B14363636M
CARSON INDUSTRIES
ARMORCAST
HIGHLINE PRODUCTS
SYNERTECH
21 HANDHOLE COMPOSITE POLYMER CONCRETE BODY AND COVER. STAINLESS STEEL
HARDWARE BOLTED NON-SKID COVER RATED FOR 15,000LB. DESIGN LOAD OCCASIONAL
NON-DELIBERATE VEHICULAR TRAFFIC. STACK UNITS TO ACIEVE DEPTH SHOWN ON PLANS.
UNITS IN LANDSCAPED AREAS SHALL BE GREEN IN COLOR. “COMMUNICATIONS” LOGO ON
HANHOLE COVER. CONTRACTOR SHALL FIELD VERIFY QUANTITY AND LOCATIONS. PW-HH-1 =
36”X36"X36”(WXLXH).
PW-HH-1
14 SQUARE D 7440
MINI-POWER ZONE
GENERAL ELECTRIC
CUTLER-HAMMER
SIEMENS
OUTDOOR RATED PACKAGED POWER PANELBOARD, CONSISTING OF A PRIMARY
BREAKER, 5 KVA DRY TYPE TRANSFORMER, SECONDARY PROTECTION AND A
240/120 VOLT, 1 PHASE PANELBOARD. WALL MOUNT NEMA 3R ENCLOSURE,
GROUND BUS, REFER TO SCHEDULES FOR SIZE AND CONFIGURATION, REFER TO
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
'MPC-2'
LEVITON 1000 SERIES
#10240-2W
W/R9120-5 MODHOPPER
22 SUBMETER FOR EXISTING FACILITY ADVANCED METERING SYSTEM. 120/240V, 200A RATED.
SURFACE MOUNT ENCLOSURE. PROVIDE ETHERNET CONNECTION FROM BUILDING
TECHNOLOGY SERVICE. PROVIDE WIRELESS MODBUS/PULSE TRANSCEIVER. PROVIDE ALL
NECESSARY PROGRAMMING TO INCORPORATE NEW METER INTO EXISTING METER SYSTEM.
SM-1
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UNO UNLESS NOTED OTHERWISE
GFI GROUND FAULT INTERRUPTER
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET E600.
3. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND
OPERATES FROM EMERGENCY BATTERY UPON LOSS OF POWER.
4. INDICATES CONTINUATION TO MATCHING MARKER NUMBER ON ANOTHER SHEET,
REFER TO ADJACENT KEYED NOTED FOR SHEET NUMBER FOR CONTINUATION.
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
H MOUNT ORIENTED HORIZONTALLY
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
E#
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN
EACH PHASE.
3. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
4. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
5. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS
SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN
GRILLE.
6. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
7. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
9. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF
ANY WELDERS ASSIGNED TO THE JOB.
10. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
ELECTRICAL INSTALLATION NOTES:
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
T101
SIM
DETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
SIM
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
LINE TYPE AND TAG KEY:
SECURITY CONTRACTORS.C.
CIVIL CONTRACTORC.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
CONSTRUCTION MANAGERC.M.
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
TECHNOLOGY
WADE ROSS
WADE ROSS
MATT SNYDER
JAYSON STICKROD
DESCRIPTION: PERSON:
BUILDING CODE: IBC 2012 EDITION
FIRE CODE: IFC 2012 EDITION
PLUMBING CODE: IPC 2012 EDITION
MECHANICAL CODE: IMC 2012 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2017 EDITION
LIFE SAFETY CODE: NFPA 101 CURRENT EDITION
ENERGY CONSERVATION CODE: IECC 2015
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
1. THE LOCATION OF THE CONDUIT, HAND HOLES AND/OR MAINTENANCE HOLES SHOWN ARE
APPROXIMATE LOCATIONS. FIELD VERIFY THE LOCATION OF ALL UTILITIES PRIVATE AND/OR
PUBLIC PRIOR TO THE INSTALLATION OF THE COMPONENT. FIELD COORDINATE THE FINAL
LOCATION WITH THE OWNER AND ENGINEER PRIOR TO INSTALLATION.
2. POTHOLING TO LOCATE EXISTING UNDERGROUND UTILITIES, IF APPLICABLE, SHALL BE
INCLUDED IN THE CONTRACTOR'S BID. CONTRACTOR IS RESPONSIBLE FOR FINAL
PLACEMENT OF HAND HOLES AND/OR MAINTENANCE HOLES AND SHALL NOTIFY THE
ENGINEER OF FINAL LOCATIONS PRIOR TO INSTALLATION.
3. HAND HOLES AND/OR MAINTENANCE HOLES SHALL BE CONSTRUCTED SO THAT THE TOP OF
THE FRAME WILL BE FLUSH WITH THE GROUND LINE.
4. REMOVAL AND REPLACEMENT OF THE EXISTING UNDERGROUND UTILITIES THAT ARE
REQUIRED TO COMPLETE THE INSTALLATION SHALL BE INCLUDED IN THE CONTRACTOR'S
BID
5. CONTRACTOR SHALL INCLUDE IN THEIR BID ANY REMOVAL AND REPLACEMENT OF EXISTING
SIDEWALK, PAVEMENT, GRASS, SHRUBS, TREES, ETC. THAT WILL BE IMPACTED BY THE
INSTALLATION OF THE NEW CONDUITS SHOWN ON THE DRAWINGS. IF TREES ARE
REQUIRED TO BE REMOVED THE CONTRACTOR SHALL CONTACT THE OWNER AND DISCUSS
OPTIONS PRIOR TO CUTTING DOWN ANY TREE OR SHRUB OVER 5' IN HEIGHT.
6. NO ADDITIONAL COST SHALL BE APPROVED FOR PLACING CONDUITS DEEPER THAN
REQUIRED MINIMUM DEPTH TO AVOID EXISTING UNDERGROUND UTILITIES.
7. PROVIDE A MINIMUM OF 25'-0" SLACK LOOP WITHIN EACH HAND HOLES AND/OR
MAINTENANCE HOLES. SLACK LOOP SHALL BE SECURE SO COPPER OR FIBER IS NOT
RESTING ON EARTH AFTER FINAL INSTALLATION.
TECHNOLOGY OUTSIDE PLANT NOTES
ELECTRICAL SHEET INDEX
E000 ELECTRICAL AND TECHNOLOGY COVERSHEET
E001 OVERALL ELECTRICAL SITE PLAN
E002 PARTIAL ELECTRICAL SITE PLAN
E003 PARTIAL ELECTRICAL SITE PLAN
E004 PARTIAL ELECTRICAL SITE PLAN
E005 TECHNOLOGY SITE PLAN
E006 TECHNOLOGY SITE PLAN
E111 FLOOR PLANS - ELECTRICAL AND TECHNOLOGY
E400 ELECTRICAL ONE-LINE DIAGRAM
E500 ELECTRICAL AND TECHNOLOGY DETAILS
GRAND TOTAL: 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BIDDING DOCUMENTS
Services
OF 138
Project Director
BASE BID
C R e v it L o c a l F ile s \M
E P
.1
P A
C
IF
IC
N
A T
IO
N
A L
C E
M E
T E
R Y
C
M a tt h e w .D
.S n y d e r.
rv t
/2
/2
:0
:5
P
M
E000
ELECTRICAL AND TECHNOLOGY
COVERSHEET
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU. HAWAII
899CM3030
JULY 15, 2021 JRV SAC
15785
NMCP
REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
INTERIOR CORRELATED COLOR TEMPERATURE 3500K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
EXTERIOR CORRELATED COLOR TEMPERATURE 4000/4100K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF
DESIGN.
VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE
MOUNTING HEIGHTS.
DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)
DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE
0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC
(TYPE) DRIVER:
PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED
P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED
FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER
CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE
CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED
(MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP
CFSA - COLOR-FINISH SELECTION BY ARCHITECT [DESIGN SPECIFIC BLANKS]
PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION)
FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR
RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC
RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE
FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE
FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR
(DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC
LED LUMINAIRE SCHEDULE
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATT LED DRIVER
APPROVED MANUFACTURERL W H DIA.
ANSI
WATT
S PER TYPE QTY
ABSOLUTE
LUMENS
(MIN) VOLTS TYPE
F1 48" LINEAR LED, COLD-ROLLED STEEL
HOUSING, FLAT DIFFUSE LENS, FINISH
SELECTION BY ARCHITECT.
O CL 4'-0" 3 7/16" 2
23/32"
35 W FIX LED 1 5000 120 V LITHONIA
CLXL485000LMSEFFDLMVOLT35K8
0CRI
METALUX 4SNLED
WILLIAMS 75S4
F2 OPEN RECESSED DOWNLIGHT, GALVANIZED
STEEL HOUSING, POLYCARBONATE LENS,
WIDE DISTRIBUTION, FINISH SELECTION BY
ARCHITECT.
O RE 7 9/16" 4" 20 W FIX LED 1 2000 120 V GOTHAM
EVO435/20ARWDLSSMVOLT
HALO HC4
LITHONIA LDN4
F2A SAME AS F2 EXCEPT WITH 1000 LUMENS
PACKAGE.
O RE 7 9/16" 4" 9 W FIX LED 1 1000 120 V GOTHAM
EVO435/10ARWDLSSMVOLT
HALO HC4
LITHONIA LDN4
F2AE SAME AS F2A EXCEPT WITH MINIMUM 300
LUMENS EMERGENCY BATTERY PACK.
O RE 7 9/16" 4" 9 W FIX LED 1 1000 120 V GOTHAM
EVO435/10ARWDLSSMVOLTEL
HALO HC4
LITHONIA LDN4
F2E SAME AS F2 EXCEPT WITH MINIMUM 600
LUMENS EMERGENCY BATTERY PACK.
O RE 7 9/16" 4" 20 W FIX LED 1 2000 120 V GOTHAM
EVO435/20ARWDLSSMVOLTEL
HALO HC4
LITHONIA LDN4
F3 3' VANITY LIGHT, ACRYLIC DIFFUSER, FINISH
SELECTION BY ARCHITECT. MOUNT AT 7' 0"
AFF.
O WL 3'-0" 2
13/16"
4 7/16" 34 W FIX LED 1 2050
3000K
120 V LITHONIA
FMVCCL36INMVOLT30K90CRI
OXYGEN FUGIT VANITY 3-5013-XX
VISA VOILA CV4146
LIGHTING SEQUENCE OF OPERATION
NOTES:
1.{L##} DENOTES THE LIGHTING SEQUENCE OF OPERATIONS FOR THIS SPACE.
2.a = SWITCH DESIGNATION FOR LIGHTING CONTROL.
PLAN ID LIGHTING SWITCHED
{LS1} Sequence: Switched lights are controlled in this space.
ON: The lights turn on using switches.
OFF: The lights turn off using switches.
{LS2} Sequence: Switched lights are controlled in this space.
ON: The lights turn on using switches or upon occupancy.
OFF: The lights turn off using switches or after the space has been vacant for 15 minutes, the lights will automatically turn off via an occupancy sensor.
Emergency Sequence: If normal power fails life safety (SE) lights will remain on via an integral emergency battery pack.
{LS3} Sequence: Switched lights are controlled in the space.
ON: The lights turn on automatically via outdoor photocell when insufficient daylight is available.
OFF:The lights will turn off via outdoor photocell when sufficient daylight is available.
Emergency Sequence: If normal power fails life safety (SE) lights will remain on via an integral emergency battery pack.
CIRCUIT KEY NOTES: H=LOCK ON
TOTAL ESTIMATED DEMAND CURRENT: 17.42 A
TOTAL CONNECTED CURENT: 17.42 A
Lighting 350 VA TOTAL ESTIMATE DEMAND LOAD: 4.18 kVA
Power 1600 VA TOTAL CONNECTED LOAD: 4.18 kVA
HVAC 791 VA
LOAD CLASSIFICATION CONNECTED LOAD
TOTALS
LOAD SUMMARY
Total Amps: 16.66 19.84
Total Load: 2.00 kVA 2.38 kVA
-- MPC-1-17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE MPC-1-18 --
-- MPC-1-15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE MPC-1-16 --
-- MPC-1-13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE MPC-1-14 --
-- MPC-1-11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE MPC-1-12 --
-- MPC-1-9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE MPC-1-10 --
MPC-1-7 HVAC - EF-2 20 A 1 12 12 12 0.12 0.2 12 12 12 1 20 A Other - FAP-1 MPC-1-8 *H
MPC-1-5 Recept. - GRAVESITE LOCATOR 20 A 1 12 12 12 0.18 0.67 12 12 12 1 20 A HVAC - EF-1 MPC-1-6
MPC-1-3 Power - AUTODOOR 20 A 1 12 12 12 0.8 1.26 12 12 12 1 20 A Receptacles MPC-1-4
MPC-1-1 Lighting 20 A 1 12 12 12 0.35 0.8 12 12 12 1 20 A Power - AUTODOOR MPC-1-2
K E
Y CKT NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B
WIRE
SIZE
H N G
OCPD
P AMPS LOAD DESCRIPTION CKT NO.
K E Y
NOTES:
METER: N/A
SPD: N/A SCCR: 18,000
LOCATION: EQUIP 3 WIRE: 3
FED FROM: EXISTING 75KVA TRANSFORMER GROUND BUS PHASE: 1
ENCLOSURE: BOLT-ON SOLID NEUTRAL VOLTS: 120/240 Single
MOUNTING: SURFACE MAIN: 125 A MCB
MPC-1
Revisions: Date:
Addendum 1 8/27/21
09/14/21
OC
OC
{LS1}
{LS2}
{LS2}
{LS3}
{LS3}
E
E
E
E
PP
P P
P P
P P
SD
SD
SD
A1
A1
A1
PC
1'
J
H
G
-1
F1 /MPC-1-1 /a
F2
MPC-1-1
a
K/a
K/a
D
D
F3 /MPC-1-1 /a
F2AE /MPC-1-1 /a/SE
F2A /MPC-1-1 /a
F3 /MPC-1-1 /a
F2E
MPC-1-1
SE
F2
MPC-1-1
F2E
MPC-1-1
SE
F2A
MPC-1-1
F2E
MPC-1-1
SE
F2A /MPC-1-1 /a
MPC-1
F2A /MPC-1-1 /a
F2A /MPC-1-1 /a
F2A /MPC-1-1 /a
F2A /MPC-1-1 /a
F2A /MPC-1-1 /a
F2A /MPC-1-1 /a
F2AE /MPC-1-1 /a/SE
F2A /MPC-1-1 /a
F2A /MPC-1-1 /a
WOMENS
MENS
EQUIP
1'
J
H
G
-1
A/MPC-1-4
A/MPC-1-4
GROUND ROD. REFER TO 1/E400 FOR
MORE INFORMATION (TYP. OF 2). REFER
TO 2/E500 FOR GROUND GRID DETAIL.
EF-1
MPC-1-6
EF-2/MPC-1-7
GRAVESITE LOCATOR
MPC-1-5
W/MPC-1-4
W
MPC-1-4
AUTODOOR
MPC-1-2
AUTODOOR
MPC-1-3
MPC-1
MPC-1-4
MPC-1-4
MPC-1-4
FAP-1
MPC-1-8
E4
SM-1
1'
J
H
G
-1
1'
J
H
G
-1
2" CONDUIT FROM NEW FIBER
CABINET. REFER TO SITE PLAN
1/E005 FOR CONTINUATION.
WOMENS
MENS
EQUIP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BIDDING DOCUMENTS
Services
OF 138
Project Director
BASE BID
C R e v it L o c a l F ile s \M
E P
.1
P A
C
IF
IC
N
A T
IO
N
A L
C E
M E
T E
R Y
C
M a tt h e w .D
.S n y d e r.
rv t
/2
/2
:1
:0
P
M
E111
FLOOR PLANS - ELECTRICAL AND
TECHNOLOGY
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU. HAWAII
899CM3030
JULY 15, 2021 JRV SAC
15785
NMCP
N O R
HT
1/4" = 1'-0"
FIRST FLOOR PLAN - LIGHTING
N O R
HT
1/4" = 1'-0"
FIRST FLOOR PLAN - POWER
N O R
HT
1/4" = 1'-0"
ROOF PLAN - ELECTRICAL
N O R
HT
1/4" = 1'-0"
FIRST FLOOR PLAN - TECHNOLOGY
SHEET NOTES:
1. REFER TO E000 FOR GENERAL ELECTRICAL
NOTES, ELECTRICAL INSTALLATION NOTES,
GENERAL ELECTRICAL EQUIPMENT SCHEDULE
AND VIEW KEY.
2. REFER TO E000 FOR LUMAINIRE SCHEDULE
AND PANEL SCHEDULES.
3. {L##} INDICATES THE SEQUENCE OF
OPERATION FOR SPACE. REFER TO SHEET
E000 FOR LIGHTING SEQUENCE OF
OPERATION.
KEYNOTES:
1. MOUNT EXTERIOR PHOTOCELL AT ROOF
LEVEL. REFER TO 3/E500 FOR PHOTOCELL
MOUNTING DETAIL.
2. INSTALL AND WIRE TWO PUSH PADS
(PROVIDED BY G.C.) FOR EACH OPENER.
COORDINATE PUSH PAD LOCATIONS WITH
ARCHITECTURAL DRAWINGS.
3. THE OUTLET NEEDS TO BE MOUNTED WITHIN
4'-0" OF THE LOCATOR OPENING.
4. REFER TO 4/E500 FOR ADDITIONAL
CONNECTIVITY REQUIREMENTS. COORDINATE
WITH THE RESIDENT ENGINEER (RE),
ARCHITECT, AND ENGINEER ON THE LAYOUT
OF THE ROOM AND THE PLACEMENT OF THE
EQUIPMENT FOR REVIEW PRIOR TO
INSTALLATION.
5. REFER TO 2/E003 FOR CIRCUIT LINE
CONTINUATION FROM MATCHING MARKER
FROM COLUMBARIUM COURT 13 EXISTING
TRANSFORMER.
6. EXHAUST FAN EF-1 IS GOING TO BE CONTROL
VIA WALL SWITCH OF THE EQUIP 103. REFER
TO 1/E111 FOR WALL SWITCH LOCATION.
7. EXHAUST FAN EF-2 IS GOING TO BE CONTROL
VIA WALL SWITCH OF THE MENS 102. REFER
TO 1/E111 FOR WALL SWITCH LOCATION.
NO SPRINKLERS
Revisions: Date:
Addendum 1 8/27/21
N E
U T
R A
L
GROUND
3#1/0 IN 2" C. IN CONCRETE
ENCASED DUCTBANK
125A MCB SEC.
120/240V, 1-PHASE, 3W
18,000 SCCR
4.18KVA
#6 GROUNDING ELECTRODE
CONDUCTOR
EFFECTIVELY GROUNDED
BUILDING STEEL
CONNECT TO METALLIC
WATER MAIN, WITHIN 5'-0" OF
WATER SERVICE ENTRANCE.
WM
PROVIDE JUMPER ACROSS
WATER METER
REMOVABLE LINK
#6 GROUNDING
ELECTRODE CONDUCTOR
CONCRETE ENCASED
ELECTRODE. NEC 250.52
BOND TO MINIMUM OF 20'
OF 1/2" REINFORCING
BAR.
3/4" DIA. x 10'-0" COPPER
GROUND ROD. TOP OF
ROD SHALL BE 12" BELOW
GRADE. (TYP.)
20'-0"
'MPC-1'
100A MCB PRI.
480V, 1-PHASE, 3W
18,000 SCCR
EXISTING UTILITY
PRIMARY SERVICE
EXISTING PRIMARY
METERING
EXISTING MAINTENANCE
FACILITY BUILDING
EXISTING
COLUMBARIUM
COURT 13 PANEL
EXISTING 75KVA
TRANSFORMER
12.47KV:480V
480V, 3P, 3W240V, 1P, 3W
MH
EXISTING 1002
ADMIN BUILDING
EXISTING 150KVA
TRANSFORMER
MH
EXISTING ELECTRICAL MANHOLE #1
'MPC-1'
'MPC-1'
25KVA
480/277:120/240V
EXISTING PUMP
HOUSE PANEL
EXISTING 112.5KVA
TRANSFORMER
MH
EXISTING ELECTRICAL MANHOLE #2
MH
EXISTING ELECTRICAL MANHOLE #3
MH
EXISTING 15KVA
TRANSFORMER
12.47KV:240V
EXISTING ELECTRICAL MANHOLE #4
MH
MH-1
NEW ELECTRICAL MANHOLE
(2) 5" EMPTY CONDUITS IN DUCTBANK
REFER TO E002 AND E003
FOR REQUIRED TESTING
MH-1
NEW ELECTRICAL MANHOLE
1 2
M
SM-1
200A 240V SPLIT
CORE SENSORS AT
TRANSFORMER
SECONDARY, AND
15/2P BREAKER IN
PANEL SECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BIDDING DOCUMENTS
Services
OF 138
Project Director
BASE BID
C R e v it L o c a l F ile s \M
E P
.1
P A
C
IF
IC
N
A T
IO
N
A L
C E
M E
T E
R Y
C
M a tt h e w .D
.S n y d e r.
rv t
/2
/2
:1
:0
P
M
E400
ELECTRICAL ONE-LINE DIAGRAM GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU. HAWAII
899CM3030
JULY 15, 2021 JRV SAC
15785
NMCP
NO SCALE
ONE-LINE DIAGRAM
Revisions: Date:
Addendum 1 8/27/21
KEYNOTES:
1. REFER TO 1/E004 FOR MANHOLE LOCATION
MH-1 NEAR THE EXISTING MEMORIAL
BUILDING.
2. REFER TO 1/E004 FOR MANHOLE MH-1
LOCATION AT COLUMBARIA COURT 14.
| E000 - ELECTRICAL AND TECHNOLOGY COVER SHEET |
| E111 - FLOOR PLANS - ELECTRICAL AND TECHNOLOGY |
| E400 - ELECTRICAL ONE-LINE DIAGRAM |
File details come from the government source that posted it. Updated .