This notice is for a federal contract solicitation for the NMCP Gravesite Expansion and New Bathroom Project #899-030 at the National Memorial Cemetery of the Pacific in Honolulu, Hawaii. The solicitation will be issued on or around July 15, 2021 as an Invitation for Bid with an estimated value between $5,000,000 to $10,000,000. This is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses under NAICS code 237990. Firms must be registered in the System for Award Management and Vendor Information Pages databases and have the Certified Veteran Enterprise seal to be considered. The point of contact is Auvorie Benson and questions may not be submitted by telephone. Amendments will be posted online only so offerors must check the website and acknowledge all amendments.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEGEND
EXISTING ASPHALT PAVEMENT
REMOVE ASPHALT PAVEMENT
REMOVE CONCRETE PAVEMENT
REMOVE PAVERS
REMOVE CURB & GUTTER
REMOVE WATERLINE
REMOVE SANITARY SEWER
REMOVE UNDERGROUND ELECTRIC
REMOVE UNDERGROUND COMMUNICATION
CONSTRUCTION LIMITS
SILT FENCE
BIO-ROLL
FULL DEPTH SAWCUT
REMOVE TREE
REMOVE SIGN
REMOVE HYDRANT
TREE PROTECTION FENCE
KEY NOTES
REMOVE EXISTING PUBLIC RESTROOM AND ALL ASSOCIATED
INFRASTRUCTURE AND UTILITY LINES
REMOVE DOMESTIC WATERMAIN
REMOVE SANITARY SEWER
REMOVE UNDERGROUND ELECTRIC LINE
REMOVE STORM MANHOLE STRUCTURE
REMOVE SANITARY MANHOLE STRUCTURE
CAP AND ABANDON UTILITY LINE IN-PLACE
REMOVE SIGN AND ASSOCIATED CONCRETE FOOTING AND BASE
FULL DEPTH
REMOVE FLOWER WATERING STATION
REMOVE BOLLARDS AND ASSOCIATED CONCRETE FOOTING AND
BASE FULL DEPTH
FULL DEPTH SAW-CUT TO OCCUR AT NEAREST PAVING JOINT
OUTSIDE THE LIMIT OF WORK
PROTECT AND RE-INSTALL MONUMENT (TYP.)
REMOVE BENCH AND ASSOCIATED CONCRETE FOOTING AND BASE
FULL DEPTH
REMOVE RETAINING WALL AND ASSOCIATED CONCRETE FOOTING
AND BASE FULL DEPTH
TRANSPLANT EXISTING PALMS. SEE LP SERIES FOR ADDITIONAL
INFORMATION
PROTECT EXISTING SECTION MARKER TO REMAIN
Geotechnical Engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h y c i v i l c a d f i l e s b i d d o c s s h e e t s d a d d a l t d e m o d w g e d i t m t o l k k i n n s a v e d
A
M p l o t
P
M
Office of Design and Construction Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
899CM3030
JULY 15, 2021
HONOLULU, HAWAII
BIDDING DOCUMENTS
BIDDING DOCUMENTS
Date:
Mechanical, Electrical, Technology & Structural Engineering:
IMEG, Inc.
623 26th Avenue Rock Island, IL 61201
(309) 788-0673 Wade Ross
Irrigation Engineering
EC Design Group, Ltd 400 5th St.
West Des Moines, IA 50265
(515) 225-6365 Erik Christiansen
Cost Estimating, Scheduling, Value Engineering
Leland Saylor Associates 1777 Oakland Blvd #103 Walnut Creek, CA 94596
(310) 207-6900 Tommy Vest
Kokua Geotech, LLC 94-974 Pakela St., Suite 109 Waipahu, HI 96797
(808) 397-6974 Tim (Xiaobin) Lin
BASE BID
07/15/21
EXP. 04/30/22
OF 138
N
D-301
MTEH
DEMOLITION NOTES
1. ALL CONSTRUCTION SHALL COMPLY WITH RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEER UNLESS DIRECTED OTHERWISE. ( SEE GEOTECHNICAL REPORT BY KOKUA
GEOTECHNICAL, LLC DATED JUNE 23, 2020)
2. EXISTING ASPHALT, CONCRETE, AND CONCRETE CURB TO BE REMOVED AND DISPOSED OF OFFSITE. DISPOSE OF ACCORDING TO LOCAL AND STATE POLLUTION REGULATION
STANDARDS.
3. CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS AND DISPOSAL CERTIFICATIONS.
4. NOTIFY COR OF ANY DISCREPANCIES PRIOR TO BEGINNING DEMOLITION WORK.
5. ALL EXISTING BURIED UTILITY LINE LOCATIONS ARE APPROXIMATE ONLY. CONTRACTOR IS RESPONSIBLE FOR FIELD LOCATION EXISTING UTILITIES PRIOR TO EXCAVATION, DEMOLITION
OR RECONNECTION. CONTRACTOR SHALL VERIFY BURIED UTILITY LOCATIONS WITH "811" UNDERGROUND UTILITIES LOCATION CENTER.
6. CONTRACTOR TO COORDINATE WITH COR, UTILITY COMPANIES AND CITY FOR TEMPORARY UTILITY CONNECTION/DISCONNECTS.
7. INSTALL SILT FENCE ON ALL DOWN SLOPE AREAS PER SWPPP PLANS AND ADJUST AND/OR REINSTALL AS NECESSARY FOR PAVEMENT REMOVALS. SEE EROSION CONTROL PLAN FOR
DETAILS.
8. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL NECESSARY CONSTRUCTION PERMITS TO CARRY OUT THE ENTIRE PROJECT. PERMITS SHALL BE IN-PLACE PRIOR TO BEGINNING ANY
CONSTRUCTION ACTIVITIES. NOTIFY APPROPRIATE UTILITY COMPANIES OF ANY AND ALL PROPOSED WORK.
PUBLIC RESTROOM - DEMOLITION PLAN
SCALE: 1" = 10'
PUBLIC RESTROOM - DEMOLITION
PLAN
I
N
N
E
R
D
I
V
N
O
R
T
H
OUTER DRIVE NORTH
EXISTING COLUMBARIA COURT 13
REMOVE ELECTRIC HANDHOLE
0 20' 40'
VICINITY MAP
65 137
FULL DEPTH ASPHALT PAVEMENT
RECONSTRUCTION
EXISTING ASPHALT PAVEMENT
NEW CONCRETE PAVEMENT
EXISTING CONCRETE PAVEMENT
NEW CURB AND GUTTER
INTERMENT SECTION LIMITS
CONSTRUCTION LIMITS
KEY NOTES
NEW ROLL CURB. SEE DETAIL 5/CD101
NEW PEDESTRIAN CONCRETE PAVEMENT. SEE DETAIL 1/CD101
NEW ASPHALT PAVEMENT. SEE DETAIL 2/CD101
NEW VERTICAL CURB. SEE DETAIL 7/CD101
NEW CONCRETE VALLEY GUTTER. SEE DETAIL 8/CD101
PROTECT MEMORIAL PAVERS TO REMAIN
VERTICAL CURB TO ROLL CURB/ VALLEY GUTTER/ FLUSH CURB
TRANSITION. SEE DETAIL 11/CD101
ROLL CURB TO CONCRETE VALLEY GUTTER & VERTICAL CURB
TRANSITION. SEE DETAIL 12/CD101
FLUSH CURB. SEE DETAIL 4/CD101
ROLL CURB TO FLUSH CURB/ VALLEY GUTTER. SEE DETAIL 13/CD101
HANDICAP STALL. SEE DETAIL 5/CD102
LANDSCAPE CURB. SEE DETAIL 8/CD101
FULL DEPTH SAW-CUT
PEDESTRIAN CROSSWALK. SEE DETAIL 1/CD103
PEDESTRIAN CROSSWALK. SEE DETAIL 2/CD103
NEW RETAINING WALL. SEE STRUCTURAL
NEW FLOWER WATERING STATION. SEE DETAIL 1/LS107
MILL & OVERLAY ASPHALT PAVEMENT. SEE DETAIL 3/CD101
NEW WHEEL STOP. SEE DETAIL 8/CD103
0+00
1+00
2+00
3+00
B P
0+00
B P
P
T
P
C
0+00
1+00
2+00
3+00
B P
SAW-CUT
Station=1+48.45
POINT OF INTERSECTION
OUTER DRIVE= STA. 1+58.58
INNER DRIVE= STA. 0+00.00
Geotechnical Engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h y c i v i l c a d f i l e s d d o c s s h e e t s a d d a l t s i t e d i t m t o l k k i n v e d o t
P
M
Office of Design and Construction Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
899CM3030
JULY 15, 2021
HONOLULU, HAWAII
BIDDING DOCUMENTS
BIDDING DOCUMENTS
Date:
Mechanical, Electrical, Technology & Structural Engineering:
IMEG, Inc.
623 26th Avenue Rock Island, IL 61201
(309) 788-0673 Wade Ross
Irrigation Engineering
EC Design Group, Ltd 400 5th St.
West Des Moines, IA 50265
(515) 225-6365 Erik Christiansen
Cost Estimating, Scheduling, Value Engineering
Leland Saylor Associates 1777 Oakland Blvd #103 Walnut Creek, CA 94596
(310) 207-6900 Tommy Vest
Kokua Geotech, LLC 94-974 Pakela St., Suite 109 Waipahu, HI 96797
(808) 397-6974 Tim (Xiaobin) Lin
BASE BID
07/15/21
EXP. 04/30/22
OF 138
C-301
PUBLIC RESTROOM - SITE PLAN
SITE PLAN NOTES
PUBLIC RESTROOM - SITE PLAN
SCALE: 1" = 10'
0 20' 40'
MTEH
N
R
9.6'
NEW PUBLIC RESTROOM
9.0'
1. ALL HANDICAPPED STALLS AND ACCESS RAMPS SHALL COMPLY WITH
CURRENT ADA STANDARDS.
2. CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL NECESSARY
CONSTRUCTION PERMITS TO CARRY OUT THE ENTIRE PROJECT.
PERMITS SHALL BE IN-PLACE PRIOR TO BEGINNING ANY
CONSTRUCTION ACTIVITIES. NOTIFY APPROPRIATE UTILITY
COMPANIES OF ANY AND ALL PROPOSED WORK.
ADD ALT 2 - OUTER DRIVE - HORIZONTAL GEOMETRY - STA. 0+00 - 3+20
SCALE: NTS
OUTER DRIVE NORTH
I
N
N
I
O
R
T
H
R
LEGEND
ADD ALT 2 - INNER DRIVE - HORIZONTAL GEOMETRY - STA. 0+00 - 3+20
SCALE: NTS
R
8.0'8.0'
9.0'
3.9'
ALIGN EDGES OF NEW SIDEWALK WITH EXISTING STAIRS
VICINITY MAP
66 137
LEGEND
KEY NOTES
959.4
TBC 800.1
FL 800.1
TC 800.1
X.X%
CONSTRUCTION LIMITS
SILT FENCE
BIO-ROLL
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
NEW CURB AND GUTTER
INTERMENT SECTION LIMITS
SOIL BORING LOCATION
SLOPE PERCENTAGE ARROW
INLET PROTECTION
TREE PROTECTION
SPOT ELEVATION
FLOW LINE OF CURB
TOP BACK OF CURB
TOP OF CONCRETE
TOP / BOTTOM OF WALL
SILT FENCE. SEE DETAIL 15/CD101
INLET SEDIMENT PROTECTION. SEE DETAIL 16/CD101
BIO-ROLL. SEE DETAIL 17/CD101
PEDESTRIAN RAMP LANDING. MAX 2% SLOPE IN ALL
DIRECTIONS
ADD ADJUSTING RINGS TO EXISTING STRUCTURE TO
MATCH PROPOSED SIDEWALK ELEVATION.
TW 800.1
BW 800.1
0+00
1+00
2+00
3+00
B P
P C
S T
A
D E
S I G
N
S
P E m i h
ME 354.38
ME FL 355.05
TBC 355.20
FL 354.78
TBC 356.55
FL 356.05
ME 357.09
ME FL 349.58
FL 348.80
TBC 349.30
FL 348.04
TBC 348.54
FL 348.11
TBC 348.61
ME FL 357.22
8.2%
ME 340.46
ME 338.45ME 338.45
ME 338.03
ME 337.72
6.4%
TBC 355.00
FL 354.58
C
O
ME 339.41
ME 339.42
TC 338.40
ME 338.21
ME TBC 338.15
ME 338.95
ME 339.33
TBC 339.13
FL 338.63
FL 343.99
TBC 344.04
FL 343.90
TBC 343.94
FL 343.90
TBC 343.94
FL 343.90
TBC 343.94
FL 343.45
TBC 343.95
ME FL 342.03
ME 341.90
ME 343.30
TC 343.99
FL 343.74
TBC 344.24
FL 344.05
TBC 344.55
1.2%
1.5%
344.00
344.00
344.00
344.10
TW 346.53
ME 343.17
ME 341.96
5.3%
FL 342.62
TBC 343.12
TC 342.97
TC 342.97
TC 342.89
344.10
344.10
344.10
344.13
344.02
344.03
344.03
344.07
344.07344.07
344.09
344.09
344.10
344.06
C
O
R 344.01
R 340.80
R 345.35
343.61
343.71
343.81
344.05
343.87
343.88
345.71
344.17
344.00
342.27
343.25
TC 341.99
FL 341.40
TBC 341.90
Geotechnical Engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h y c i v i l c a d f i l e s d d o c s s h e e t s a d d a l t g r a d i n g d i t e h e d m v e d
P o t
P
M
Office of Design and Construction Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
899CM3030
JULY 15, 2021
HONOLULU, HAWAII
BIDDING DOCUMENTS
BIDDING DOCUMENTS
Date:
Mechanical, Electrical, Technology & Structural Engineering:
IMEG, Inc.
623 26th Avenue Rock Island, IL 61201
(309) 788-0673 Wade Ross
Irrigation Engineering
EC Design Group, Ltd 400 5th St.
West Des Moines, IA 50265
(515) 225-6365 Erik Christiansen
Cost Estimating, Scheduling, Value Engineering
Leland Saylor Associates 1777 Oakland Blvd #103 Walnut Creek, CA 94596
(310) 207-6900 Tommy Vest
Kokua Geotech, LLC 94-974 Pakela St., Suite 109 Waipahu, HI 96797
(808) 397-6974 Tim (Xiaobin) Lin
BASE BID
07/15/21
EXP. 04/30/22
OF 138
CG301
PUBLIC RESTROOM - GRADING
PLAN
PUBLIC RESTROOM - GRADING PLAN
SCALE: 1" = 10'
0 10' 20'
MTEH
N
NEW PUBLIC RESTROOM
FFE = 344.1
RETAINING WALL
TOP OF CAP = 346.53
SEE STRUCTURAL FOR DETAILS.
GRADING PLAN NOTES
1. EXISTING TOPOGRAPHIC AND UTILITY INFORMATION PROVIDED BY THE OWNER ON A SURVEY PREPARED BY ANDERSON ENGINEERING. ALL EXISTING BURIED UTILITY LINE LOCATIONS
ARE APPROXIMATE ONLY. CONTRACTOR IS RESPONSIBLE FOR FIELD LOCATING EXITING UTILITIES PRIOR TO EXCAVATION, DEMOLITION OR RECONNECTION. CONTRACTOR SHALL VERIFY
BURIED UTILITY LOCATIONS WITH "811" UNDERGROUND UTILITIES LOCATION CENTER.
2. NOTIFY COR OF ANY DISCREPANCIES PRIOR TO BEGINNING WORK.
0 5' 10'
N
SEE INSET A
INSET A
SCALE: 1" = 5'
NEW PUBLIC RESTROOM
FFE = 344.10
EXISTING STAIRS TO REMAIN.
VICINITY MAP
NEW UNDERGROUND COMMUNICATION
NEW UNDERGROUND ELECTRIC
NEW 6" SANITARY SEWER
NEW 4" DOMESTIC WATERMAIN
NEW 6" IRRIGATION WATERMAIN
WATERMAIN TIE-IN. SEE DETAIL 1/CD102
CAP UTILITY LINE AND SURVEY END POINT FOR FUTURE
SYSTEM UPGRADES
NEW GATE VALVE. SEE DETAIL 5/CD103
NEW 8" DIA. SURFACE DRAIN. SEE DETAIL 4/CD103
NEW ROOF DRAIN DOWNSPOUT CONNECTION. SEE DETAIL
3/CD103
NEW COLUMBARIA FLOWER STRIP CLEANOUT. SEE DETAIL
6/CD103
NEW GREENSPACE CLEANOUT. SEE DETAIL 7/CD103
NEW 4" PVC PERFORATED DRAINTILE
NEW 6" PVC SOLID DRAINTILE
N/A
NEW
" TYPE K COPPER WATER SERVICE
NEW 1" PVC WATERMAIN
LEGEND
NEW UNDERGROUND ELECTRIC
NEW UNDERGROUND COMMUNICATION
NEW 2" DOMESTIC WATERMAIN
NEW 4" DOMESTIC WATERMAIN
NEW
" WATERMAIN SERVICE
NEW 1" PVC WATERMAIN
NEW 6" IRRIGATION WATERMAIN
NEW SANITARY SEWER
NEW WATERMAIN FITTINGS
NEW SANITARY SEWER MANHOLE
NEW STORM SEWER
NEW DRAINTILE
NEW STORM SEWER STRUCTURES
EXISTING SANITARY SEWER MANHOLE
EXISTING STORM SEWER STRUCTURES
EXISTING WATERLINE
INTERMENT SECTION LIMITS
KEY NOTES
W6
W w1 w1
0+00
1+00
2+00
3+00
B P
P C
55 LF 6" SAN @ 4.00%
SMH-03
RIM 340.48
INV 335.73 (6" IN)
INV 335.63 (6" OUT)
L
F
S
SMH-04
RIM 338.15
INV 335.09 (6" IN)
SMH-01
RIM 356.41
INV 349.50 (6" OUT)
INV 349.60 (6" IN)
INV 338.93
INV 337.17
SMH-02
RIM 343.50
INV 337.89 (6" OUT)
INV 337.99 (6" IN)
C
O
W
W
W
W
W
W
W6
W6
W6
W6
W6
W6
W6
W6
W6
W6
C
O
13 LF 6" HDPE ST @ 3.00%
10 LF 6" HDPE ST @ 4.00%
4 LF 4" HDPE ST @ 5.00%
18 LF 6" HDPE ST @ 4.00%
4 LF 4" HDPE ST @ 5.00%
26 LF 6" HDPE ST @ 4.00%
2 LF 6" HDPE ST @ 4.00%
EX. STRUCTURE
RIM 340.00
INV 338.50 (6" IN)
INV 335.2 (12" OUT)
INV 339.55
INV 340.27
2 LF 6" HDPE ST @ 4.00%
INV 340.65
CO-201
RIM 341.27
INV 340.73 (6" OUT)
200 LF 6" PVC SAN @ 5.77%
1+00
2+00
3+00
3+17
9 LF 4" SAN @ 4.00%
25 LF 4" SAN @ 4.00%
CLEAN-OUT
R. 343.45
Geotechnical Engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h y c i v i l c a d f i l e s d d o c s s h e e t s a d d a l t u t i l i t i e s d i t m t o l k k i n v e d o t
P
M
Office of Design and Construction Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
899CM3030
JULY 15, 2021
HONOLULU, HAWAII
BIDDING DOCUMENTS
BIDDING DOCUMENTS
Date:
Mechanical, Electrical, Technology & Structural Engineering:
IMEG, Inc.
623 26th Avenue Rock Island, IL 61201
(309) 788-0673 Wade Ross
Irrigation Engineering
EC Design Group, Ltd 400 5th St.
West Des Moines, IA 50265
(515) 225-6365 Erik Christiansen
Cost Estimating, Scheduling, Value Engineering
Leland Saylor Associates 1777 Oakland Blvd #103 Walnut Creek, CA 94596
(310) 207-6900 Tommy Vest
Kokua Geotech, LLC 94-974 Pakela St., Suite 109 Waipahu, HI 96797
(808) 397-6974 Tim (Xiaobin) Lin
BASE BID
07/15/21
EXP. 04/30/22
OF 138
CU301
PUBLIC RESTROOM - UTILITY PLAN
PUBLIC RESTROOM - UTILITY PLAN
SCALE: 1" = 10'
0 10' 20'
MTEH
N
SHEET NOTES
1. CONTRACTOR TO PROVIDE INLET PROTECTION ON ALL STORM DRAIN INLETS PER DETAILS 16/CD101 AND 19/CD101
2. CONTRACTOR TO COORDINATE WITH COR, UTILITY COMPANIES AND CITY FOR TEMPORARY UTILITY CONNECTION/DISCONNECTS.
3. WATERMAIN SHALL COMPLY WITH INSTALLATION REQUIREMENTS PER LATEST EDITION OF HAWAII WATER SYSTEM STANDARDS.
NEW PUBLIC RESTROOM
45 LF 2" PVC DOMESTIC WATER SERVICE
WATER INV. = 341.40
SEE SHEET CU302 FOR SANITARY PROFILE
VICINITY MAP
BACKFLOW PREVENTER (BFP). SEE SPEC
SECTION 331000. INSTALL IN-GROUND BOX
PER MANUFACTURER'S RECOMMENDATIONS
AND ACCESS REQUIREMENTS.
6 LF CONCRETE JACKET
68 137
NEW UNDERGROUND COMMUNICATION
NEW UNDERGROUND ELECTRIC
NEW 6" SANITARY SEWER
NEW 4" DOMESTIC WATERMAIN
NEW 6" IRRIGATION WATERMAIN
WATERMAIN TIE-IN. SEE DETAIL 1/CD102
CAP UTILITY LINE AND SURVEY END POINT FOR FUTURE
SYSTEM UPGRADES
NEW GATE VALVE. SEE DETAIL 5/CD103
NEW 8" DIA. SURFACE DRAIN. SEE DETAIL 4/CD103
NEW ROOF DRAIN DOWNSPOUT CONNECTION. SEE DETAIL
3/CD103
NEW COLUMBARIA FLOWER STRIP CLEANOUT. SEE DETAIL
6/CD103
NEW GREENSPACE CLEANOUT. SEE DETAIL 7/CD103
NEW 4" PVC PERFORATED DRAINTILE
NEW 6" PVC SOLID DRAINTILE
N/A
NEW
" TYPE K COPPER WATER SERVICE
NEW 1" PVC WATERMAIN
LEGEND
NEW UNDERGROUND ELECTRIC
NEW UNDERGROUND COMMUNICATION
NEW 2" DOMESTIC WATERMAIN
NEW 4" DOMESTIC WATERMAIN
NEW
" WATERMAIN SERVICE
NEW 1" PVC WATERMAIN
NEW 6" IRRIGATION WATERMAIN
NEW SANITARY SEWER
NEW WATERMAIN FITTINGS
NEW SANITARY SEWER MANHOLE
NEW STORM SEWER
NEW DRAINTILE
NEW STORM SEWER STRUCTURES
EXISTING SANITARY SEWER MANHOLE
EXISTING STORM SEWER STRUCTURES
EXISTING WATERLINE
INTERMENT SECTION LIMITS
KEY NOTES
W6
W w1 w1
0+00
1+00
2+00
3+00
3+17
S M
H
R I
I N
V
S
W
I N
V
N
E
S M
H
R
I N
V
S
W
I N
V
N
E
P
S M
H
R
I N
V
N
E
I N
V
S
53 L F
P V
C S
A N
.0 0%
S M
H
R
I N
V
N
Geotechnical Engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h y c i v i l c a d f i l e s d d o c s s h e e t s a d d a l t u t i l i t i e s d i t m t o l k k i n v e d o t
P
M
Office of Design and Construction Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
899CM3030
JULY 15, 2021
HONOLULU, HAWAII
BIDDING DOCUMENTS
BIDDING DOCUMENTS
Date:
Mechanical, Electrical, Technology & Structural Engineering:
IMEG, Inc.
623 26th Avenue Rock Island, IL 61201
(309) 788-0673 Wade Ross
Irrigation Engineering
EC Design Group, Ltd 400 5th St.
West Des Moines, IA 50265
(515) 225-6365 Erik Christiansen
Cost Estimating, Scheduling, Value Engineering
Leland Saylor Associates 1777 Oakland Blvd #103 Walnut Creek, CA 94596
(310) 207-6900 Tommy Vest
Kokua Geotech, LLC 94-974 Pakela St., Suite 109 Waipahu, HI 96797
(808) 397-6974 Tim (Xiaobin) Lin
BASE BID
07/15/21
EXP. 04/30/22
OF 138
CU302
PUBLIC RESTROOM - UTILITY
PROFILE
0 10' 20'
MTEH
N
PUBLIC RESTROOM - SANITARY SEWER PROFILE
SCALE: H 1" = 10' V 1"=5'
EXISTING ELEVATION
PROPOSED ELEVATION
PROPOSED GRADE
EXISTING GROUND
SHEET NOTES
1. CONTRACTOR TO PROVIDE INLET PROTECTION ON ALL STORM DRAIN INLETS PER DETAILS 16/CD101 AND 19/CD101
2. CONTRACTOR TO COORDINATE WITH COR, UTILITY COMPANIES AND CITY FOR TEMPORARY UTILITY CONNECTION/DISCONNECTS.
3. WATERMAIN SHALL COMPLY WITH INSTALLATION REQUIREMENTS PER LATEST EDITION OF HAWAII WATER SYSTEM STANDARDS.
EXISTING 12" STORM
4" PVC DOMESTIC LINE
UNDERGROUND
COMMUNICATIONS
CONCRETE DUCT BANK
VICINITY MAP
6 LF CONCRETE JACKET
69 137
1+00 2+00 3+00
P C
PW
BR
CF
Cr
OJ
OV
PW
C
O
C
O
C O
C
O
C
O
C
O
C
O
CO
TREES CODE QTY COMMON / BOTANICAL NAME CONT CAL REMARKS
Cr 1 SAGO PALM F.S. RELOCATED
CYCAS REVOLUTA
SHRUBS CODE QTY COMMON / BOTANICAL NAME CONT SIZE REMARKS
BR 2 RASPBERRY ICE BOUGAINVILLEA CONT. 5 GAL. 24" HT, 18" SPD. MIN.
BOUGAINVILLEA X 'RASPBERRY ICE'
CF 10 TI PLANT CONT. 3 GAL. 24" HT., MIN.
CORDYLINE FRUTICOSA
Mp2 26 ORANGE JESSAMINE CONT. 3 GAL. 30" HT., 18" SPD. MIN.
MURRAYA PANICULATA
PW 18 WHEELER`S DWARF PITTOSPORUM CONT. 5 GAL. 24" HT., 18" SPD. MIN.
PITTOSPORUM TOBIRA `WHEELER`S DWARF`
WU 20 `AKIA CONT. 3 GAL. 12" HT., 12" SPD.
WIKSTROEMIA UVA-URSI
PERENNIALS CODE QTY COMMON / BOTANICAL NAME CONT SIZE REMARKS
CP 3 SPOTTED CROTON 1 GAL.
CODIAEUM VARIEGATUM 'PICTUM'
GROUND COVERS QTY COMMON / BOTANICAL NAME CONT SPACING REMARKS
Cc2 3,675 SF CELEBRATION BERMUDA GRASS SOD
CYNODON DACTYLON `CELEBRATION`
LC 180 CREEPING LILY TURF 4" POT 18" o.c. PLANT 18" O.C.
LIRIOPE SPICATA
ML 182 LAUA'E IKI FERN 4" POT 18" o.c. PLANT 18" O.C.
MICROSORUM SCOLOPENDRUM 'LAUA'E IKI'
PLANT SCHEDULE RESTROOM
Geotechnical Engineering
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h y l a c a d f i l e s s h e e t s l p c o l u m b a r i a p l a n t i n g a d d a l t e r n a t e d i t j d e i t n r v e d o t
P
M
Office of Design and Construction Services
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions:
1 3 6 0 5 1 s t A v e . N . # 1 0 0 P l y m o u t h , M N 5 5 4 4 1 P 7 6 3 . 4 1 2 . 4 0 0 0 | F 7 6 3 . 4 1 2 . 4 0 9 0 | a e - m n . c o m Anderson Engineering of Minnesota, LLC | Proj # 15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
899CM3030
JULY 15, 2021
HONOLULU, HAWAII
BIDDING DOCUMENTS
BIDDING DOCUMENTS
Date:
Mechanical, Electrical, Technology & Structural Engineering:
IMEG, Inc.
623 26th Avenue Rock Island, IL 61201
(309) 788-0673 Wade Ross
Irrigation Engineering
EC Design Group, Ltd 400 5th St.
West Des Moines, IA 50265
(515) 225-6365 Erik Christiansen
Cost Estimating, Scheduling, Value Engineering
Leland Saylor Associates 1777 Oakland Blvd #103 Walnut Creek, CA 94596
(310) 207-6900 Tommy Vest
Kokua Geotech, LLC 94-974 Pakela St., Suite 109 Waipahu, HI 96797
(808) 397-6974 Tim (Xiaobin) Lin
BASE BID
OF 138
07/15/21
EXP. 06/30/22
RESTROOM PLANTING PLAN
N
0 20' 40'
PUBLIC RESTROOM PLANTING PLAN
SCALE: 1" = 10'
COLUMBARIA 13
INTERMENT SECTION U
DSJD 70
LP300
AE201
AE201
'-4
/4
A B
1' -6
3'
-1
3 3/8" 3 3/8"
1/
4"
8' -5
"H O
LD
5'
-8
3/
8"
'-0
/8
'-3
/4
1/
8"
3/ 8"
1' -8
2' -2
5'
-0
2'-0"
6 5/8"
6 5/8"
WOMENS
MENS
EQUIP
OPNG
'-8
4' -0
EXPOSED CONC SLAB,
SLOPE 1/8"/FT TO DRAIN
AS INDICATED BY SLOPE
DRAINAGE ARROWS, TYP
SS3
SS3
SS5
6'-8"
SS2 A6
A6
SS2
SS3
SS3SS5
SS2
FD
FD
1'-3"
4'-0" 2'-0"
4' -9
1' -9
SS4
SS6SS6
AE601
AE601
XN6
SLOPE FLOOR 1/8"/FT TO
FLOOR DRAIN AS
INDICATED BY SLOPE
DRAINAGE ARROWS, TYP
SLOPE FLOOR 1/8"/FT TO
TO FLOOR DRAIN AS
INDICATED BY SLOPE
DRAINAGE ARROWS, TYP
SS7
2'-4"
SS7
E Q
E Q
AE601
A
LI
G N
14'-6"
1' -6
/4
1' -4
SEE FLOOR PLAN
KEYNOTE 'FL13'
AE201
AE201
AE201
AE201
AE501
A B
WOMENS
MENS
EQUIP
A M
B U
LA
T
O R
Y
3' -0
"C
LR
5' -4
"C
LR
5'-0"CLR
5' -0
"C
LR
2' -1
0" C
LR
HI-LO DRINKING FOUNTAINS
1'-9"
FL1
FL3
FL3
FL4
FL4
FL5
FL5
FL6
AE501 1
FL9
FL9
FL11
FL11
FL12
FL14
FL15
3'-0"
FL14
FL15
10"
FL2
FL2
FL8
FL17
FL18 FL18
FL18
1' -6
1' -0
1'-0"
2'-0"
1' -6
/4
DOWNSPOUT
DOWNSPOUT
AE301
AE301
FL2
FL10
FL2
FL13
GENERAL NOTES
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF CONSTRUCTION
WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY BE
NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL DRAWINGS DUE TO CHANGES
AFFECTING ELECTRICAL, MECHANICAL AND PLUMBING ALONG WITH OTHER SYSTEMS. THIS
INCIDENTAL WORK SHALL BE PART OF THIS CONTRACT, AND ALL TRADES SHALL INSPECT THESE
AREAS, ASCERTAIN WORK REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT
REQUIREMENTS AT NO ADDITIONAL COST.
2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH THE
EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD VERIFY
ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO DEMOLITION AND
CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.
4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND REPAIR ANY
OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.
5. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE FIREPROOFING
SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND FIRE
RATING, AT THE SUBCONTRACTORS EXPENSE.
6. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE WITH
MANUFACTURER.
7. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR EQUIPMENT SHALL
BE VERIFIED WITH THE RESPECTIVE TRADE.
8. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES WITH
TRADES WHICH REQUIRE THEM.
9. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS REQUIRED BY
MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.
10. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY DIFFER FROM
ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.
11. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD BACKING
BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE.
12. ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF MATERIALS / ASSEMBLIES
MEETING THE RATING INDICATED, TERMINATE AT THE DECK ABOVE WITH A TESTED HEAD OF
WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE SEALED WITH A TESTED ASSEMBLY. ALL
SMOKE PARTITIONS SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE PASSAGE OF
SMOKE, TERMINATE AT THE DECK ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL
PENETRATIONS SHALL BE SEALED WITH FIRE CAULK.
13. PROVIDE AND INSTALL ONE COAT HOOK ON THE INTERIOR FACE OF EACH TOILET PARTITION
DOOR. MOUNT HOOK AT 4'-0" AFF, CENTER HORIZONTALLY ON DOOR.
1. REFER TO PROJECT MANUAL SPECIFICATION SECTION 09 60 00 'SCHEDULE FOR FINISHES" FOR
SPECIFIC PRODUCT SELECTION BASIS OF DESIGN AND OTHER REQUIREMENTS
2. FIELD FINISH VENTS, GRILLES, ACCESS PANELS, PLUG STRIPS, TO MATCH SURFACE ON
WHICH THEY OCCUR UNLESS OTHERWISE INDICATED. EXCEPTION: ITEMS WITH FACTORY WHITE
FINISH OCCURRING ON WHITE GYPSUM BOARD CEILING SHALL NOT BE PAINTED. STAINLESS
STEEL ITEMS SHALL NOT BE PAINTED
3. FIELD VERIFY ALL NEW CONDITIONS. NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO
INSTALLATION
4. LOCATE CHANGES IN FLOOR FINISH MATERIAL UNDER CENTERLINE OF CLOSED DOOR UNLESS
OTHERWISE INDICATED
5. PROVIDE CLEAR SILICONE SEALANT AT PERIMETER OF PLUMBING FLOOR DRAINS, CLEAN OUTS, ETC IN RESILIENT AND CERAMIC TILE FLOORS
6. PROVIDE SEALANT TO HORIZONTAL AND VERTICAL INTERIOR CERAMIC TILE CORNERS, COLOR TO
MATCH GROUT COLOR
7. PROVIDE SEALANT AT JOINT BETWEEN COUNTER TOP, BACK OR SIDE SPLASH AND WALLS
8. PROVIDE CLEAR SILICONE SEALANT AT THE BASE OF DOOR FRAME TO RESILIENT AND CT
FLOORING, TYP. SEE PLANS AND ROOM FINISH SCHEDULE FOR FLOOR FINISH LOCATIONS
9. HOLLOW METAL DOORS AND FRAMES TO BE PAINTED PTE-5, UNLESS NOTED OTHERWISE IN THE
ROOM OPENING SCHEDULE
10. CEILING HEIGHTS AND MATERIALS/FINISHES CALLED OUT IN ROOM FINISH SCHEDULE ARE FOR ENTIRE CEILING OR MAJORITY OF THAT ROOM, UNLESS OTHERWISE INDICATED. SEE REFLECTED CEILING PLAN FOR CHANGES IN CEILING MATERIAL AND CEILING HEIGHT. PAINT ALL SURFACES
OF SOFFIT SAME COLOR AS INDICATED
11. COLOR SELECTIONS ARE BASED ON USE OF PRODUCTS INDICATED IN THE PROJECT MANUAL SPECIFICATION. IF MANUFACTURERS OTHER THAN THOSE INDICATED ARE USED, ARCHITECT MAY
REVISE COLOR SELECTIONS OF OTHER FINISHES TO ENSURE PROPER COORDINATION
12. PAINT ALL FIRE EXTINGUISHER CABINETS TO MATCH COLOR OF THE ADJACENT WALLS. WHERE
CABINET IS SPECIFIED TO BE STAINLESS STEEL, DO NOT PAINT.
13. CEILING HEIGHTS ARE MEASURED FROM FINISH FLOOR
14. EXTERIOR EXPOSED CONCRETE FLOOR SURFACE TO FINISHED WITH CS-1 CONCRETE SEALANT, INCLUDING PORTIONS OF FLOOR SLAB BEYOND EXTERIOR WALL FOOTPRINT, TYP
FINISHES - GENERAL NOTES
FLOOR PLAN SYMBOLS
EXISTING WALL TO
REMAIN
WALL
EXISTING DOOR AND
FRAME TO REMAIN
DOOR
INTERIOR BORROWED
LIGHT
101B
101A
8'-0"
DIMENSION LINE,
NOMINAL
8'-0" EXTENDED
DIMENSION LINE,
NOMINAL
AE2111A
INTERIOR ELEVATION
INDICATOR TAG2B
AE2O1
EXTERIOR ELEVATION
INDICATOR TAG
1A
203 EQUIPMENT TAG
100 FLOOR SPOT
ELEVATIONWALL TAG
OFFICE
ROOM NAME AND
NUMBER AE501
1A
DETAIL REFERENCE
TAG
AE2O1
EXTERIOR SECTION
REFERENCE TAG
1A
AE2O1
INTERIOR SECTION
REFERENCE TAG
1A
KEY NOTE
A
GRIDLINE
REVISION TAG
PR01
REVISION CLOUD
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
FP10
B3
CT CERAMIC TILE
CS CONCRETE SEALER
PTE EXTERIOR PAINT
PPT PORCELAIN TILE (FLOOR AND BASE)
RB RESILIENT BASE
S SOLID SURFACE
P PAINT
ROOM FINISH LEGEND &
ABBREVIATIONS
MATERIAL INSTALL
DIRECTION
KEYNOTECORNER GUARD
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
CG
VCTCPT
AF10
FLOOR PLAN KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
FL1 GRAVESITE LOCATOR
FL2 LINE OF ROOF OVERHANG ABOVE
FL3 FRP CLAD TAPERED COLUMN
FL4 EDGE OF CONC SLAB - SEE STRUCT AND CIVIL
FL5 FACADE MATERIAL TRANSITION
FL6
FULLY RECESSED FIRE EXTINGUISHER CABINET, CENTER HORIZONTALLY
ON WING WALL
FL7 NOT USED
FL8 ELEC PANEL WITH INTEGRAL TRANSFORMER; SEE ELEC
FL9 HORIZONTAL WALL-MOUNTED DIAPER CHANGING STATION
FL10 WALL HYDRANT
FL11 PUSH PLATE FOR AUTOMATIC DOOR OPERATOR
FL12 12" X 24" SST SHELF FOR GSL LAPTOP
FL13
REINFORCE WALL WITH ADDITIONAL STEEL STUD BACKING/BLOCKING AS
REQUIRED TO SUPPORT 300 POUND STATIC LOAD AT DRINKING FOUNTAIN.
SEE DETAIL
FL14 PROVIDE (1) GFCI OUTLET AT SIDE OF LAVATORY
FL15 RECESSED COMBO PAPER TOWEL DISPENSER / WASTE RECEPTACLE
FL16 NOT USED
FL17 RETAINING WALL W/ ST-4 STONE CAP - SEE STRUCTURAL
FL18 HORIZONTAL CAP JOINT. REFER TO TYP DETAILS /3 AE301
/12 AE601
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
NO SPRINKLERS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BASE BID
OF 138
C U s e rs
\P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
R
E S
T R
O O
M -R
C
D u q u e
L D
L E
T .r v t
/1
/2
:1
:1
A
M
AE111
RESTROOM FLOOR PLANS
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 BB CM/CD
15785
1/4" = 1'-0"
FIRST FLOOR DIMENSION PLAN
0 4' 8'2'
1/4" = 1'-0"
FIRST FLOOR PLAN
0 4' 8'2'
ROOM FINISH SCHEDULE
NO. NAME
WALL FINISH
FLOOR FINISH BASE FINISH CEILING FINISH REMARKSNORTH EAST SOUTH WEST
101 WOMENS CT-2 CT-3 CT-2 CT-3/CT-8 PPT-1 PPT-4 (COVE) GWB CT-7 BULLNOSE AT WINDOW SILL
102 MENS CT-3 CT-2 CT-3/CT-8 CT-2 PPT-1 PPT-4 (COVE) GWB CT-6 BULLNOSE AT WINDOW SILL
103 EQUIP P-1 P-1 P-1 P-1 CS-1 RB-1 N/A
SS-5 COUNTERTOP/LAVATORY DUPONT CORIAN - WILLOW -
TS-1 METAL TRANSITION STRIP SCHLUTER SYSTEMS SCHIENE STAINLESS STEEL V2A HEIGHT: TBD BY INSTALLER TO MATCH FLOOR HEIGHT
PF-1 TOILET PARTITIONS BRADLEY PHENOLIC CORE W/ FUSED MALAMINE FINISH TO MATCH WILSONART AMBER CHERRY 7919
MISC. FINISHES
GWB-1 GYPSUM BOARD COMPLY W/ SECTION 092900 PAINT P-4 -
CEILINGS
CT-8 CERAMIC WALL TILE DALTILE COLOR WHEEL CLASSIC, MATTE DESERT GRAY 3"X6" INSTALLATION: STACK BOND
CT-7 CERAMIC WALL TILE DALTILE COLOR WHEEL CLASSIC, MATTE ARCHITECTURAL GREY 3"X6" BULLNOSE TRIM
CT-6 CERAMIC WALL TILE DALTILE COLOR WHEEL CLASSIC, MATTE ARCTIC WHITE 3"X6" BULLNOSE TRIM
CT-3 CERAMIC WALL TILE DALTILE COLOR WHEEL CLASSIC, MATTE ARCHITECTURAL GREY 3"X6" INSTALLATION: STACK BOND
CT-2 CERAMIC WALL TILE DALTILE COLOR WHEEL CLASSIC, MATTE ARCTIC WHITE 3"X6" INSTALLATION: STACK BOND
PTE-5 PAINT BENJAMIN MOORE LEVEL 5 EQUESTRIAN GREY (1553) - HOLLOW METAL DOORS AND FRAMES
P-4 PAINT GLIDDEN LEVEL 5 WHITE ON WHITE 30GY 88/014 - CEILING
P-1 PAINT GLIDDEN LEVEL 5 SPIDER'S WEB 90YY73/040 - EQUIP ROOM WALLS
WALLS
RB-1 RESILIENT BASE JOHNSONITE TRADITIONAL VINYL COVED 48 GREY 4"
PPT-4 PORCELAIN TILE DALTILE SANITARY COVE BASE MATCH PPT-1 6" X 12"
BASE
CS-1 CONCRETE, SEALED L&M CONSTRUCTION... SEALHARD CONCRETE SEALER
PPT-1 PORCELAIN TILE DALTILE RECTANGULAR FIELD TILE HAUT MONDE, PF-08 CHOCOLATE 12"X12" INSTALLATION: STRAIGHT GRID
FLOORING
CODE MATERIAL MANUFACTURER STYLE COLOR SIZE REMARKS
(INTERIOR MATERIALS ONLY. REFER TO PLANS AND SPECIFICATIONS FOR EXTERIOR MATERIALS AND FINISHES)
INTERIOR FINISH MATERIALS SCHEDULE
71Revisions: Date: 137
A B
WOMENS
MENS
EQUIP
OPEN TO
STRUCTURE
ABOVE
A F
F S
T -3
8' -8
ALUM COMPOSITE
PLANK CLADDING
SYSTEM
SLOPE UP
1:12
ELEV VARIES
RC3
RC3
RC2
RC1
C
LE
R E
S
TO
R Y
C
LE
R E
S
TO
R Y
4' -0
4'-6"4'-6" 2'-7 3/4"
1' -7
/2
EQ EQ
4' -2
6' -0
6'
-0
6' -0
2'
-2
/2
2'-10"
EQ 4'-0" EQ
4' -0
3'
-6
3' -6
1'
-6
/2
E Q
E Q
8" 8" 8"
REFLECTED CEILING KEYED NOTES
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
RC1 WATER HEATER ON SUSPENDED SHELF, SEE PLUMBING
RC2 THROUGH WALL EXHAUST FAN - SEE MECHANICAL
RC3 2' x 2' ACCESS PANEL, WITH LOCK. CENTER ON LIGHT FIXTURES
REFLECTED CEILING PLAN SYMBOLS
NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN
GBPD CEILING
/ SOFFIT
ACT CEILING
SYSTEM
ACCESS
PANEL
2'-0" x 4'-0" LIGHT
FIXTURE
2'-0" x 2'-0" LIGHT
FIXTURE
PENDANT STRIP
LIGHT FIXTURE
RECESED LIGHT
FIXTURE
MECHANICAL
SUPPLY GRILL
MECHANICAL
RETURN GRILL
WALL SCONCE
LIGHT FIXTURE
MECHANICAL LINEAR
SUPPLY GRILL
CEILING ELEVATION
AND FINISH
9'-0" AFF
ACT
RCP & ROOF GENERAL NOTES
1. GENERAL CONTRACTOR TO COORDINATE ALL CEILING MOUNTED EQUIPMENT SUPPORT
REQUIREMENTS, LOCATIONS, DIMENSIONS, ETC WITH EQUIPMENT SUPPLIER AND OWNER,
PRIOR TO INSTALLATION.
2. ALL CEILING MOUNTED ITEMS SUCH AS LIGHT FIXTURES, GRILLES, SPEAKERS, ETC SHALL BE
LOCATED IN THE CENTER OF GYP BD SOFFITS, UNLESS NOTED OTHERWISE. COORDINATE WITH
MECHANICAL AND ELECTRICAL DRAWINGS.
NC-15.02
WOMENS
MENS
EQUIP
NC-15.01
NC-15.01
Braille
/2
/4
/8
/4
ICON
AREA
TEXT
DOMED BRAILLE
1/32" RAISED TEXT
6"
NC-15
NC-15.02
MEN WOMEN
2"
NC-15.01
NC-15.02
INTERIOR SIGNAGE SCHEDULE
ROOM ROOM NAME SIGN TYPE SIGN
NO. DESIGNATION
2 MENS MEN'S ADA/ABA COMPLIANT RESTROOM NC-15.01
1 WOMENS WOMEN'S ADA/ABA COMPLIANT RESTROOM NC-15.02
WAYFINDING GENERAL NOTES
1. SIGN COMPONENTS TO BE ACRYLIC PLAQUE
2. TACTILE SYMBOL AND TEXT WITH ACCOMPANYING BRAILLE IS REQUIRED
3. TEXT AND BACKGROUND COLORS: REFER TO SPECIFICATION SECTION 09 06 00 SCHEDULE FOR
FINISHES.
4. TYPOGRAPHY AND SIZE: ADA/ABA COMPLIANT HELVETICA BOLD, UPPER CASE, GRADE 2 BRAILLE
5. MOUNTING: DOUBLE SIDED FOAM TAPE OR SILASTIC ADHESIVE
AE201
AE201
A B
AE401
STANDING
SEAM METAL
PANEL ROOFING
SLOPE 1:12
DOWN
2' -3
2'-3" 2'-3"
2' -3
2'-3"
2' -3
2'-3"
2' -3
7' -7
'-8
CONTINUOUS GUTTER
AND DOWNSPOUT
DOWNSPOUT
DOWNSPOUT
7' -7
SLANT BACK ROOF VENTS
COLOR TO MATCH
METAL ROOFING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
NO SPRINKLERS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BASE BID
OF 138
C U s e rs
\P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
R
E S
T R
O O
M -R
C
D u q u e
L D
L E
T .r v t
/1
/2
:1
:2
A
M
AE121
RESTROOM CEILING, ROOF AND
WAYFINDING PLAN
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 BB CM
15785
0 4' 8'2'
1/4" = 1'-0"
REFLECTED CEILING PLAN
0 4' 8'2'
1/4" = 1'-0"
WAYFINDING PLAN
0 4' 8'2'
3" = 1'-0"
SIGNAGE DETAILS
1/2" = 1'-0"
SIGNAGE ELEVATIONS
1/4" = 1'-0"
ROOF PLAN
72Revisions: Date: 137
FIRST FLOOR
0"
AE201
2 3 41
3 EQ PANELS
7'-6"
3 EQ PANELS
7'-6"
ALUMINUM
CLERESTORY WINDOW
GRAVESITE LOCATOR
DUAL HIGH-LOW
WATER FOUNTAIN
BEYOND
SMOOTH STONE TILE
VENEER, ST-3. SEE
DETAIL
MOSS ROCK STONE
VENEER, ST-2
ALUMINUM
CLERESTORY WINDOW
STONE CAP, ST-1
ALUM COMPOSITE PLANK
CLADDING SYSTEM AT UNDERSIDE
OF SLOPED OVERHANG
FRP CLAD TAPERED
COLUMN, TYP OF 2
RECESS
T/O WINDOW OPNG
8'-8"
ALUMINUM FASCIA
STONE CAP, ST-1
ON PARTIAL
HEIGHT WALL
7' -2
B/O BEARING JOIST
9'-0"
/3 AE201
AE201
STONE CAP, ST-4
ON RETAINING
WALL
MOSS ROCK STONE
VENEER, ST-2
AE301
1'-4"
AE201
FIRST FLOOR
0"
AE201A B
METAL FASCIA
MOSS ROCK STONE
VENEER, ST-2
B/O BEARING JOIST
9'-0"
THROUGH WALL
EXHAUST FAN
(BEYOND)
- SEE MECHANICAL
CONTINUOUS GUTTER
DOWNSPOUT
PRECAST CONCRETE
SPLASH
FIRST FLOOR
0"
AE201
234 1
AE401
MOSS ROCK STONE
VENEER, ST-2
METAL FASCIA
B/O BEARING JOIST
9'-0"
STANDING SEAM
METAL PANEL ROOF
RETAINING WALL W/
STONE CAP, ST-4
EXHAUST FAN -
SEE MECHANICAL
PTE-5
AE301
1/2" TYP CAP JOINT (+/- 1/8")
SEE SEALANT DETAIL
S/S TRIM W/ DRIP
EDGE
1'-6" 1/2"
3'-9 1/2"1/2"
/3 AE301GUTTER AND DOWNSPOUT
SEE CIVIL DETAIL 3/CD103 FOR
DOWNSPOUT CONNECTION
TO STORM NETWORK DETAIL
GRADE LINE
FIRST FLOOR
0"
AE201
AB
STONE CAP, ST-1
MOSS ROCK STONE
VENEER, ST-2
HOLLOW METAL
DOOR AND FRAME
PTE-5
METAL FASCIA
FRP CLAD TAPERED
COLUMN, TYP OF 2
B/O BEARING JOIST
9'-0"
RETAINING WALL
- SEE STRUCTURAL
EXHAUST FAN
- SEE MECHANICAL
PTE-5
STONE CAP, ST-1
MOSS ROCK STONE
VENEER, ST-2
2"
3"
4'-0"1/2" TYP CAP JOINT
(+/- 1/8")
4'-0"
AE301
TYP
4"
4" GUTTER
STEPPED FOUNDATION
LEDGE TO FOLLOW SLOPE
HOSE BIB AT 2'-6"
ABOVE FINISHED FLOOR
PROVIDE 12" X 12" SMOOTH
STONE TILE VENEER ST-3
CENTERED AT HOSE BIB
LOCATION
FIRST FLOOR
0"
AE201
A B
MENS
COLUMN BEYOND
344.20
353.20
T/O SLAB - COL 13
-3'-4 51/64"
EXISTING
COLUMBARIUM
B/O BEARING JOIST
9'-0"
9' -0
"J O
IS
T
B E
A R
IN
G
(L O
W P
O
IN
T
8' -0
"C E
IL
IN
G H
T
(H
IG
H T
P O
IN
T
8' -9
/2
"C E
IL
IN
G H
T
AE401
AE301
REINFORCE WALL WITH ADDITIONAL
STEEL STUD BACKING/BLOCKING AS
REQUIRED TO SUPPORT 300 POUND
STATIC LOAD AT DRINKING FOUNTAIN
FIRST FLOOR
0"
AE2012 3 41
EQUIP
MENS
WOMENS
B/O BEARING JOIST
9'-0"
RETAINING WALL
CLAD W/
MOSS ROCK STONE
VENEER, ST-2
AE601
AE601
AE601
AE301
4 TYP
AE301
AE301
1' -0
1'
-6
1' -0
1'
-0
1' -6
8"
1' -0
1'
-6
NOTE: PROVIDE
1. BUTT JOINT AT TILE CONNECTIONS, MAXIMUM
1/8" GAP BETWEEN TILES
2. VEIN PATTERN OF STONE SHALL RUN IN
HORIZONTAL DIRECTION
VARY BASE TILE WIDTHS FROM 6" TO
2'-0" AT 2" INCREMENTS
B A
S E
RANDOM PATTERN STONE TILE, ST-3
WALL CLADDING. 18" HIGH TILE BAND
VARIES IN WIDTH FROM 6" TO 2'-6" AT 6"
INCREMENTS. VERTICAL JOINTS WILL
NOT ALIGN WITH TILE BAND DIRECTLY
ABOVE AND BELOW.
RANDOM PATTERN STONE TILE, ST-3
WALL CLADDING. 8" AND 1'-0" HIGH TILE
BANDS VARY IN WIDTH FROM 6" TO 2'-6"
AT 6" INCREMENTS. VERTICAL JOINTS
WILL NOT ALIGN WITH TILE BAND
DIRECTLY ABOVE AND BELOW.
9' -2
FIRST FLOOR
0"
AE401
B/O BEARING JOIST
9'-0"
SEALANT
GSL FLANGE
STONE VENEER, ST-3
PREFINISHED METAL
FLASHING
RO WITH GSL MANUFACTURER
VERIFY
RECESS
2' -1
/2
R O
W
IT
H G
S L
M A
N U
F A
C T
U R
E R
V E
R
IF
Y
T/O WDW R.O.
8'-8"
FIRST FLOOR
0"
STEEL COLLAR
FLASHING WITH CONCEALED
FASTENERS
TAPERED FRP CLAD COLUMN
CHANGE IN RADIUS POINT
BACKER ROD AND
CONTINUOUS SEALANT AT
BASE
CONCRETE SLAB
AE201
AE201
AE201
ALUMINUM COMPOSITE PLANK
CLADDING SYSTEM
JOINT LINES (TYP)
1/4" WIDE VERTICAL JOINT -
APPLY CONTINUOUS SEALANT
BEAD TO FILL EXPOSED JOINT -
SEE MFR RECOMMENDATIONS
2' -9
'-2
T
O
/4
V A
R
IE
S W
/ S
LO
P E
D F
IN
IS
H E
D C
E
IL
IN
G
3/ 4"
J O
IN
T
FRP COLUMN
CLADDING
4" x 4" STRUCTURAL
STEEL COLUMN -
SEE STRUCTURAL
FRP COLUMN
CLIPS AS
REQUIRED
9" OD
COLUMN GRID, TYPSEE ADDITIONAL TYP
NOTES ON DETAIL
/8 AE201
ALUMINUM COMPOSITE
PLANK CEILING
CLADDING SYSTEM,
SCRIBE TO FIT
5/
8"
4" x 4" STRUCTURAL
STEEL TUBE COLUMN
FRP COLUMN CLADDING
FRP COLUMN CLIPS, TYP,
MIN 1/8" THICK
GALVANIZED STEEL BENT
PLATES, SECURED TO
COL AS REQUIRED. SIZE
VARIES
1'-4" OD
CONCEALED FASTENERS -
PROVIDE PLUG TO MATCH
TEXTURE AND FINISH OF
SEALANT JOINT
COLUMN GRID, TYP
5/
8"
4" x 4" STRUCTURAL
STEEL TUBE COLUMN
FRP COLUMN CLADDING
FRP COLUMN CLIPS
AS REQUIRED
1'-0" OD
FRP COLUMN COVER
JOINT, TYP
COLUMN GRID, TYP
SEE ADDITIONAL TYP
NOTES ON DETAIL
/8 AE201
5/
8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
NO SPRINKLERS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BASE BID
OF 138
C U s e rs
\P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
R
E S
T R
O O
M -R
C
D u q u e
L D
L E
T .r v t
/1
/2
:2
:1
A
M
AE201
RESTROOM EXT ELEVATIONS AND
BUILDING SECTIONS
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 BB CM/CD
15785
1/4" = 1'-0"
NORTH ELEVATION
1/4" = 1'-0"
WEST ELEVATION
1/4" = 1'-0"
SOUTH ELEVATION
1/4" = 1'-0"
EAST ELEVATION
1/4" = 1'-0"
BUILDING SECTION - TRANSVERSE
1/4" = 1'-0"
BUILDING SECTION - LONGITUDINAL
1/2" = 1'-0"
TYPICAL CLADDING PATTERN AT STONE TILE VENEER ST-3
1/2" = 1'-0"
GRAVE SITE LOCATOR ELEVATION
1/2" = 1'-0"
FRP COLUMN ELEVATION
1" = 1'-0"
FRP - COLUMN CLAD HEAD DETAIL
1" = 1'-0"
FRP - COLUMN CLAD DET @ MID
1" = 1'-0"
FRP - COLUMN CLAD FOOT DETAIL
73Revisions: Date: 137
FIRST FLOOR
0"
B
AE301
NATURAL STONE
RETAINING WALL CAP
MOSS ROCK VENEER
CAST-IN-PLACE
CONCRETE WALL -
SEE STRUCTURAL
DRIP SLOT
1'-6"
EQ
EQ
1"
R 1/2"
SS7
2'-4"
STEPPED LEDGE
2" -3
T.O. SLAB (ELEV VARIES)
1/ 2"
PEAK
EQ EQ
AE301
DRIP SLOT
SEALANT AND BACKER ROD
MONOLITHIC FOUNDATION
SEE STRUCTURAL
GRADE
SS DRIP FLASHING
HORIZONTAL WEEPS AT
3'-0" ON CENTER
BASE AND SCRATCH
COATS
LATH/NET COMBINATION
MESH DRAINAGE PLANE
AND METAL LATH
WATERPROOFING
MEMBRANE
JOINT TOLERANCE
NATURAL STONE
WALL CAP
SECTION VIEW: BETWEEN WALL CAPS
SECTION VIEW: BETWEEN RETAINING WALL CAPS AND VENEER
1/2"TYPSEALANT W/
BACKER ROD
TOP OF WALL, SUBSTRATE
TO VARY BY PARTITION
TYPE. REFER TO FLOOR
PLANS FOR PARTITION
TYPE
WEEP VENT (3/4" - 1" WIDE
MAX) EVERY 3'-0" ALONG
HORIZONTAL JOINT
BACKER ROD & SEALANT
NATURAL STONE
WALL CAP
MOSS ROCK VENEER
TOP OF WALL, SUBSTRATE
TO VARY BY PARTITION
TYPE. REFER TO FLOOR
PLANS FOR PARTITION
TYPE
TYP
1/2"
4"
EXTEND WATERPROOFING
MEMBRANES OVER TOP OF PARTIAL
HEIGHT/RETAINING WALL
METAL LATH
1/ 4"
5/8" TILE CEMENT
BD SHEATHING
OVER METAL
STUD FRAMING
BACKER ROD &
SEALANT
1/ 2"
CONTINUOUS
DRIP SLOT. DO NOT
EXTEND TO VISIBLE
ENDPOINTS, HOLD
BACK 1" TYP
NATURAL STONE CAP
1/ 2"
SEALANT AND BACKER ROD WITH
HORIZONTAL WEEP VENTS AT 3'-0" O.C.
CAP SETTING ON WALL W/ VENEER
SET STONE IN NON SHRINK
GROUT BED
3/ 8"
1/2"
1/4"
1/2"
VENEER
CONTINUOUS SELF ADHESIVE EPDM
MEMBRANE OVER TOP OF WALL
ASSEMBLY
MOSS ROCK WALL
ASSEMBLY
SEALANT
STEEL COLUMN
SEE STRUCTURAL
STONE TILE WALL ASSEMBLY
SEALANT AND BACKER ROD
AT TRANSITION OF MOSS ROCK
AND STONE TILE VENEERS
SS5
SS4
A
3/ 8"
2"
5/ 8"
STONE TILE WALL ASSEMBLY
RECESSED
FIRE EXTINGUISHER
CABINET
/2
STEEL COLUMN
SEE STRUCTURAL
SEALANT AND BACKER ROD
AT TRANSITION OF MOSS
ROCK AND STONE TILE
VENEERS
MOSS ROCK WALL
ASSEMBLY
SS4
SS5
STANDING SEAM METAL ROOF
WATERPROOF MEMBRANE
5/8" PLYWOOD SHEATHING
- SEE STRUCTURAL
METAL GUTTER
1X MOISTURE RESISTANT
FASCIA BOARD
ALUMINUM FASCIA
4" METAL DOWNSPOUT
METAL SUSPENSION
FRAMING
ALUMINUM COMPOSITE
PLANK CLADDING SYSTEM
OUTRIGGER SEE PLAN AND
STRUCTURAL
SEE STRUCTURAL FRAMING PLAN
ROOF OVERHANG
STANDING SEAM
RAKE TRIM
ALUMINUM FASCIA
DRIP EDGE
STANDING SEAM
PANEL
5/8" PLYWOOD SHEATHING
SEE STRUCTURAL
1X MOISTURE RESISTANT
FASCIA BOARD
JOIST FRAMING
SEE STRUCTURAL
METAL SUSPENSION
FRAMING
ALUMINUM COMPOSITE
PLANK CLADDING SYSTEM
WATERPROOFING
MEMBRANE
MOSS STONE VENEER
MORTAR
METAL LATH
SUSPENDED GYPSUM
BOARD CEILING
STANDING SEAM ROOF
PANEL
OUTRIGGER SEE PLAN
AND STRUCTURAL
5/8" PLYWOOD SHEATHING
ALUMINUM COMPOSITE PLANK
CLADDING SYSTEM
METAL SUSPENSION FRAMING
WATERPROOF MEMBRANE
PROVIDE SMOOTH FACE MOSS ROCK
SURFACE ALONG SOFFIT EDGE
SEALANT JOINT
SEALANT JOINT
FIRST FLOOR
0"
MORTAR
SEALANT JOINT
FOUNDATION WALL
BASE AND SCRATCH COATS
CONCRETE SLAB
SEE STRUCTURAL
5/8" GLASS MAT WATER RESISTANT
GYPSUM BACKER BOARD
MOSS STONE VENEER
6 5/8"
CONCRETE CURB
VAPOR PERMEABLE AIR
BARRIER
1' -0
COVE BASE TILE
THIN SET PORCELAIN
TILE FLOOR
GRADE ELEVATION VARIES
STEPPED FOUNDATION LEDGE
SS DRIP FLASHING
MORTAR JOINT WITH BACKER ROD
AND SEALANT
HORIZONTAL WEEPS AT 3'-0" ON
CENTER
LATH/NET COMBINATION MESH
DRAINAGE PLANE AND METAL LATH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
NO SPRINKLERS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BASE BID
OF 138
C U s e rs
\P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
R
E S
T R
O O
M -R
C
D u q u e
L D
L E
T .r v t
/1
/2
:3
:2
A
M
AE301
RESTROOM EXTERIOR DETAILS
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 BB CM/CD
15785
1 1/2" = 1'-0"
SECTION AT RETAINING WALL
6" = 1'-0"
SEALANT JOINT CAP DETAILS, TYP
6" = 1'-0"
HORIZONTAL JOINT AT STONE CAP, TYP
3" = 1'-0"
FLOOR PLAN DETAIL AT NORTH WALL EDGE
3" = 1'-0"
FLOOR PLAN DETAIL AT WALL EDGE
3" = 1'-0"
STANDING SEAM ROOF DETAIL AT GUTTER
3" = 1'-0"
STANDING SEAM ROOF RAKE DETAIL
3" = 1'-0"
WALL/ROOF CONNECTION
3" = 1'-0"
WALL/SLAB CONNECTION
74Revisions: Date: 137
NO SUBSCRIPT
EXTEND ENTIRE
PARTITION TO
UNDERSIDE OF
STRUCTURE
FLOOR
CEILING
BOTTOM
OF FLOOR
OR DECK
(D) SUBSCRIPT
EXTEND STUDS TO
DECK, EXTEND
GYPSUM BOARD TO 6"
ABOVE HIGHEST
ADJACENT CEILING
6"
(C) SUBSCRIPT
EXTEND ENTIRE
PARTITION TO 6"
ABOVE HIGHEST
ADJACENT CEILING
6"
(U) SUBSCRIPT
EXTEND ENTIRE
PARTITION TO
UNDERSIDE OF
CEILING
(X'-X") SUBSCRIPT
INDICATES FINISHED
PARTITION HEIGHT
IN
S
U B
S C
R
IP
T
H E
IG
H
T A
S
IN
D
IC
A T
E D
GENERAL NOTES:
1. FOR PARTITIONS WITH UNEQUAL LAYERS OF GYPSUM BOARD ON EACH SIDE, THE SIDE OF THE PARTITION WITH
THE TAG INDICATES WHERE THE EXTRA LAYER(S) OF GYPSUM BOARD ARE TO BE INSTALLED. REFER TO
PARTITION TYPES FOR MORE INFORMATION
2. DIMENSIONS TO METAL STUD PARTITIONS ARE MEASURED TO FINISH FACE UNLESS NOTED OTHERWISE
3. SUBSCRIPTS MAY BE USED WITH ANY PARTITION TYPE
3'-0"UCD
A6
(1 ) LAYER 5/8" GYPSUM BOARD
EACH SIDE
6" METAL STUD FRAMING
STC 46
7 1/4"
XN6
(1 ) LAYER 5/8" GYPSUM
BOARD
6" METAL STUD FRAMING
6 5/8"
SOUND ATTENUATION
INSULATION
1. SEE LIFE SAFETY PLAN FOR REQUIRED PARTITION FIRE RATINGS.
2. DIMENSIONS TO METAL STUD PARTITION ARE MEASURED TO FINISH FACE OF PARTITION UNLESS
NOTED OTHERWISE
3. THE DIMENSION SHOWING THE LOCATION OF A DOOR FRAME IN GYPSUM BOARD WALLS IS TO
THE INSIDE OF THE DOOR FRAME (DOOR OPENING). PROVIDE 4" TYPICAL DIMENSION IF NO
DIMENSION IS SHOWN.
4. SOUND ATTENUATING INSULATION MEANS GLASS FIBER OR MINERAL WOOL BATTS OR BLANKETS BEARING THE UL LABEL FOR FIRE RESISTANCE. VERIFY TYPE AND DENSITY (PCF) WITH FIRE
TEST NUMBER SHOWN ON PARTITION TYPE.
5. FOR PARTITION HEIGHTS SEE PARTITION TAG LEGEND AND TAG SUBSCRIPTS ON PLANS.
6. FOR PARTITION TYPES WITH GYPSUM BOARD ON ONE SIDE ONLY, INSTALL GYPSUM BOARD ON
ROOM SIDE, UNLESS NOTED OR DETAILED OTHERWISE.
7. PROVIDE 1/2" DEFLECTION SPACE AT THE TOP OF STUDS AT ALL PARTITIONS EXTENDING TO
STRUCTURE, UNLESS NOTED OTHERWISE.
8. BULKHEAD FRAMING SHALL EXTEND TO UNDERSIDE OF STRUCTURE WITH DIAGONAL STUD
FRAMING BRACES AT 4'-0" ON CENTER (2 BRACES MINIMUM) WITH GYPSUM BOARD EXTENDING 6"
ABOVE CEILING MINIMUM, UNLESS NOTED OTHERWISE.
9. GENERAL CONTRACTOR SHALL PROVIDE AND COORDINATE ALL IN-WALL BLOCKING FOR WALL
MOUNTED CASEWORK AND EQUIPMENT SUPPLIED BY THIS CONTRACT, OWNER FURNISHED OR
BY VENDORS. CONTRACTORS OPTION TO PROVIDE 3/4" FIRE TREATED PLYWOOD (PRESERVATIVE
TREATED ON EXTERIOR WALLS) OR SHEET METAL BLOCKING FOR WALL MOUNTED EQUIPMENT,
CASEWORK, DOOR STOPS, ACCESSORIES, ETC, UNLESS NOTED OTHERWISE.
10. IN WET AREAS SUCH AS BUT NOT LIMITED TO JANITOR CLOSETS, ETC, USE TILE BACKER BOARD BEHIND THE CERAMIC TILE AND EXTEND TO 2'-0" BEYOND ALL SIDES OF THE PLUMBING FIXTURE.
IN DOUBLE LAYER WALLS WHERE THE TILE BACKER BOARD IS INSTALLED OVER A BASE LAYER OF
GYPSUM BOARD, APPLY A WATER BARRIER (BUILDING WRAP) NOT A VAPOR RETARDER, OVER
THE BASE LAYER OF GYPSUM BOARD.
11. IN WET AREAS SUCH AS SOILED UTILITY ROOMS, JANITOR CLOSETS, ETC, USE 5/8" WATER
RESISTANT GYPSUM BOARD.
PARTITION GENERAL NOTES:
1iSS2 1iSS3
WALL ASSEMBLY
THIN SET STONE TILE
VAPOR PERMEABLE AIR BARRIER
5/8" GYP SHEATHING
6" STEEL STUDS
5/8" GLASS MAT WATER
RESISTANT GYPSUM BACKER BOARD
WALL ASSEMBLY
1 3/4 - 2" MOSS ROCK STONE
MORTAR BED BASE AND SCRATCH COATS
COMBINATION MESH DRAINAGE PLANE AND
METAL LATH
VAPOR PERMEABLE AIR BARRIER
5/8" GYP SHEATHING
6" STEEL STUDS
5/8" GLASS MAT WATER
RESISTANT GYPSUM BACKER BOARD
1iSS5 1iSS6
WALL ASSEMBLY
THIN SET STONE TILE
VAPOR PERMEABLE AIR BARRIER
5/8" GYP SHEATHING
6" STEEL STUDS
1iSS4
WALL ASSEMBLY
(FROM EXTERIOR TO INTERIOR)
1 3/4" - 2" MOSS ROCK STONE MORTAR
BED BASE AND SCRATCH COATS
COMBINATION MESH DRAINAGE PLANE
AND METAL LATH
WATERPROOFING MEMBRANE CIP CONCRETE
WATERPROOFING MEMBRANE COMBINATION
MESH DRAINAGE PLANE AND METAL LATH
MORTAR BED BASE AND SCRATCH COATS
1 3/4" - 2" MOSS ROCK STONE.
1iSS7
1"5/8"
1"5/8"
1" 5/8"
WALL ASSEMBLY
1 3/4 - 2" MOSS ROCK STONE
MORTAR BED BASE AND SCRATCH COATS
COMBINATION MESH DRAINAGE PLANE
AND METAL LATH
VAPOR PERMEABLE AIR BARRIER
5/8" GYP SHEATHING
6" STEEL STUD
3/4" 2" 1 3/4"-1/2"+/-1/8"
5/8" 3/4" 2" 1 3/4"-1/2"+/-1/8"
5/8"
3/4" 2" 1 3/4"-1/2"+/-1/8"
5/8"
INTERIOR EXTERIOR
(FILL SIDE)
2" 1 3/4"-
3/4" 1/2"
+/-1/8"3/4"2" 1/2"1 3/4"-
+/-1/8"
WALL ASSEMBLY
1 3/4 - 2" MOSS ROCK STONE
MORTAR BED BASE AND SCRATCH COATS
COMBINATION MESH DRAINAGE PLANE
AND METAL LATH
VAPOR PERMEABLE AIR BARRIER
5/8" GYP SHEATHING
6" STEEL STUD
5/8" GYP SHEATHING
VAPOR PERMEABLE AIR BARRIER
THIN SET STONE TILE
SS2
METAL STUD BOX SILL
2X PRESSURE TREATED WOOD
BLOCKING, ALL SIDES; CUT TO FIT
2X PRESSURE TREATED
WOOD BLOCKING, ALL SIDES,
CUT TO FIT
METAL STUD BOX HEADER
SS2
BACKER ROD AND SEALANT
BACKER ROD AND
SEALANT
GRAVESITE LOCATOR
FLANGE
VAPOR PERMEABLE AIR BARRIER
WRAP DOWN INT WALL 4" MIN
4"
GRAVESITE LOCATOR, OFOI
PRE-FINISHED METAL SILL
FLASHING W/ DRIP EDGE - LAP OVER
VAPOR PERMEABLE AIR BARRIER
EXTEND INTO WALL 4" MIN
GRAVESITE LOCATOR
FLANGE
4"
CONTINUOUS BACKER
ROD AND SEALANT
AROUND TOP AND SIDES
OF GSL FLANGE
LAP SHEET
VAPOR PERMEABLE
AIR BARRIER
AROUND BLOCKING
TO 4" VERTICALLY AT
INTERIOR SIDE
6" METAL STUDS @ 12" OC UNDER
GRAVESITE LOCATOR
4"
GUSSET SUPPORT
AE401
6 5/8"
SS2
MITERED CORNER
CONTINUE SMOOTH STONE TILE
VENEER TO UNDERSIDE OF
SOFFIT. REFERENCE TYPICAL
CLADDING PATTERN DETAIL
3/AE201 FOR INTENT OF TILE
JOINT SPACING
SS2
8" 8" 8"
RECESSED LIGHT FIXTURE
WHERE INDICATED ON THE
REFLECTED CEILING PLAN
METAL STUD BOX HEADER
TILE JOINT, TYP GRAVESITE LOCATOR
FLANGE
GRAVESITE LOCATOR,
OFOI
2X PRESSURE TREATED
WOOD BLOCKING, ALL SIDES
BACKER ROD AND SEALANT EXTEND VAPOR PERMEABLE
AIR BARRIER THROUGH
OPENING
BACKER ROD AND SEALANT
A
6 5/8" STRUCTURAL STEEL TUBE,
SLOPED IN LINE W/ 1:12 ROOF
STRUCTURE SLOPE - SEE
STRUCTURAL
FRP COLUMN COVER
COLUMN CENTERLINE
ALUMINUM COMPOSITE
PLANK CLADDING SYSTEM
5/8" PLYWOOD SHEATHING
METAL SUSPENSION
FRAMING
ROOF JOIST - SEE
STRUCTURAL
STANDING SEAM METAL ROOF
WATERPROOFING MEMBRANE
OUTRIGGER - SEE
STRUCTURAL
STEEL COL, SEE
STRUCTURAL
SEALANT
METAL TRACK -
SEE STRUCTURAL
1/8" STEEEL COLLAR FLASHING
3/8" REVEAL AROUND TOP
OF COLUMN
3/8"
5/ 8"
1 1/2"
3/ 8"
3/ 8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTS
NO SPRINKLERS
Office of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Geolabs, Inc.
2006 Kalihi St
Honolulu, HI 96819
(808)913-5150
Robin Kim
BASE BID
OF 138
C U s e rs
\P u b lic \D o c u m e n ts
\R e v it P ro je c ts
\1
R
E S
T R
O O
M -R
C
D u…