This pre-solicitation notice announces an upcoming invitation for bid for gravesite expansion and new bathroom construction at the National Memorial Cemetery of the Pacific in Honolulu, Hawaii. The solicitation will be issued on or around July 15, 2021 for a construction project with a value between $5-10 million. The NAICS code is 237990 and the business size standard is $36.5 million. This opportunity is a 100% set-aside for verified Service-Disabled Veteran-Owned Small Businesses. Interested offerors must be registered in the System for Award Management and Vendor Information Pages databases. The administrative contracting officer may be contacted via email for any questions. Amendments will be posted online rather than distributed via mail. Offerors must acknowledge all amendments.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SW#
SW#
1. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ENGINEER, NOR THE PRESENCE OF THE
ENGINEER OR THEIR EMPLOYEES AND SUBCONSULTANTS AT THE CONSTRUCTION SITE,
SHALL RELIEVE THE CONTRACTOR AND ANY OTHER ENTITY OF THEIR OBLIGATIONS,
DUTIES AND RESPONSIBILITIES INCLUDING BUT NOT LIMITED TO, CONSTRUCTION MEANS,
METHODS, SEQUENCE, TECHNIQUES OR PROCEDURES NECESSARY FOR PERFORMING,
SUPERINTENDING OR COORDINATING ALL PORTIONS OF THE CONSTRUCTION WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ANY HEALTH OR SAFETY
PRECAUTIONS REQUIRED BY ANY REGULATORY AGENCIES. THE ENGINEER AND THEIR
PERSONNEL HAVE NO AUTHORITY TO EXERCISE ANY CONTROL OVER ANY
CONSTRUCTION CONTRACTOR OR OTHER ENTITY OR THEIR EMPLOYEES IN CONNECTION
WITH THEIR WORK OR ANY HEALTH OR SAFETY PRECAUTIONS. THE CONTRACTOR IS
SOLELY RESPONSIBLE FOR THE JOBSITE SAFETY. THE ENGINEER AND THE ENGINEER’S
CONSULTANTS SHALL BE MADE ADDITIONAL INSUREDS UNDER THE CONTRACTOR’S
GENERAL LIABILITY INSURANCE POLICY.
2. ALL DRAWINGS AND SPECIFICATIONS ARE CONSIDERED TO BE A PART OF THE CONTRACT
DOCUMENTS. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND
COORDINATION OF ALL DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF
CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT PRIOR TO THE START OF CONSTRUCTION SO A CLARIFICATION CAN BE
ISSUED. ANY WORK PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY
CODE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN
EXPENSE AND AT NO EXPENSE TO THE OWNER, ARCHITECT, OR STRUCTURAL ENGINEER
OF RECORD. (SEOR)
3. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
4. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT
OF NEW WORK.
5. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
6. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
7. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
8. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
9. THE CONTRACT DOCUMENTS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE
CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE
AND SAFETY OF WORKMEN DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE,
BUT NOT BE LIMITED TO, BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, ETC. OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL
ENGINEER SHALL NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND
DOES NOT IN ANY WAY RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE
ABOVE.
10. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
11. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
12. NO HOLES, NOTCHES, BLOCKOUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
13. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, EACH BIDDER SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS,
TEMPORARY CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE
BID SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK WITHIN THE EXISTING
CONDITIONS.
GENERAL
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
IBC 2018
ASCE/SEI 7-16
ACI 318-14
AISC 360-16
AWS D1.1
AISI S100
NDS-18 AND SDPWS-15
2. RISK CATEGORY II
3. SEISMIC:
SEISMIC DESIGN CATEGORY D
IMPORTANCE FACTOR 1.0
SOIL CLASSIFICATION PER
GEOTECHNICAL REPORT D
SS 0.579 g S1 0.169 g Sds 0.516 g Sd1 0.255 g
SEISMIC FORCE RESISTING SYSTEM LIGHT-FRAMED WALLS SHEATHED
WITH WOOD PANELS
R 6.5 Cd 4.0
ΩO 3.0
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
BASE SHEAR, STRENGTH LEVEL V = CS x W = 0.079 x 31.4 = 2.48 KIPS,
4. WIND:
BASIC WIND SPEED 150 MPH
IMPORTANCE FACTOR 1.0
EXPOSURE CLASS D
MWFRS DESIGN PRESSURE 80 PSF STRENGTH LEVEL
NET ROOF UPLIFT PRESSURE 66 [LC: 0.9DL + 1.0WL]
C&C DESIGN PRESSURE PER APPLICABLE BUILDING CODE
5. LIVE LOADS:
TYPICAL FLOOR 100 PSF
TYPICAL ROOF 20 PSF
6. SNOW:
GROUND SNOW ZERO PSF
7. ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE BUILDING IN THE COMPLETED
STRUCTURE IS PROVIDED BY SHEAR WALLS IN EACH ORTHOGONAL DIRECTION.
REFER TO PLANS FOR LOCATIONS. THE ROOF SHEATHING SERVES AS HORIZONTAL
DIAPHRAGM DISTRIBUTING THE LATERAL WIND AND SEISMIC FORCES TO THE
VERTICAL LATERAL ELEMENTS WHICH IN TURN CARRY THE LOAD TO THE BUILDING
FOUNDATIONS.
DESIGN CRITERIA AND LOADS
1. RESTROOM FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT
DATED JUNE 23, 2020 BY KOKUA GOEOTECH LLC. REPORT IS ON FILE WITH THE
ARCHITECT. COLUMBARIUM FOUNDATION DESIGN IS BASED ON THE
GEOTECHNICAL REPORT DATED MAY 21, 2012 BY GEOLABS, INC.
2. SOIL PROPERTIES PER THE GEOTECHNICAL REPORT:
ALLOWABLE NET SOIL BEARING PRESSURE:
FOOTINGS 3000 PSF
EQUIVALENT FLUID PRESSURE 40 PCF UNRESTRAINED WALLS
60 PCF RESTRAINED WALLS
ACTIVE PRESSURE 40 PSF/FT, DRAINED
AT REST PRESSURE 60 PSF/FT, DRAINED
PASSIVE PRESSURE 300 PSF/FT OF DEPTH
COEFFICIENT OF FRICTION 0.35
3. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED.
4. EXTREME CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT
TO EXISTING STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE
FOUNDATIONS, WALLS, SLABS, UTILITIES, ETC.
EARTHWORK
3. BAR SPLICES SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. ALL
SPLICES SHALL BE CLASS 'B' AS DEFINED IN ACI 318. IF SPLICE LENGTH IS NOT
GIVEN ON THE DRAWINGS, PROVIDE LAP LENGTH (IN INCHES) AS FOLLOWS:
LAP LENGTHS ASSUME CLEAR SPACING BETWEEN BARS OF 2 BAR DIAMETERS, AND
A MINIMUM COVER OF 1 BAR DIAMETER. FOR DEVELOPMENT LENGTHS, DIVIDE BY
1.3. TOP BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 1'-0" OF
FRESH CONCRETE BELOW.
CAST-IN-PLACE CONCRETE
1. CONCRETE STRENGTHS SHALL CONFORM TO:
2. DRYPACK SHALL BE 1:3-1/2 PORTLAND CEMENT TO SAND WITH A MINIMUM 28-DAY
STRENGTH OF 7000 PSI.
3. SLAB ON GRADE CONSTRUCTION:
LOCATE SAW CUT CONTROL JOINTS ALONG COLUMN LINES WITH INTERMEDIATE
JOINTS SPACED PER THE TABLE BELOW, UNO. SLAB PANELS SHALL HAVE A
MAXIMUM LENGTH TO WIDTH RATIO OF 1.5:1. PROVIDE ADDITIONAL CONTROL
JOINTS AT ALL RE-ENTRANT CORNERS.
4. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ASSURE
PROPER DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS,
NOTCHES, EDGES OF WALLS/GRADE BEAMS AND PIERS.
5. UNO, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS OR COLUMNS.
6. NOTIFY THE ARCHITECT/STRUCTURAL ENGINEER 48 HOURS MINIMUM PRIOR TO
ALL POURS.
POST-INSTALLED ANCHORS
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS.
ACCEPTABLE ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY
AND CONFIGURATION MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY
AND CONFIGURATION. ANY ALTERNATES ARE TO BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW. INSTALL IN ACCORDANCE WITH
MANUFACTURER’S WRITTEN INSTRUCTIONS. BELOW SUMMARIZES EACH ANCHOR
TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
EXPANSION ANCHORS
THREADED SCREW ANCHORS
3. ADHESIVE ANCHORS: SHALL CONSIST OF DEFORMED REINFORCING BARS OR
ASTM A193 GRADE B7 RODS, HEAVY DUTY NUTS AND WASHERS AND A TWO
COMPONENT STRUCTURAL ADHESIVE. WHERE ANCHORING INTO HOLLOW
MASONRY, A SCREEN TUBE SHALL BE PROVIDED.
STEEL
1. STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:
WIDE FLANGE SHAPES ASTM A992 Fy = 50 KSI OTHER ROLLED SHAPES ASTM A36 Fy = 36 KSI PIPE SECTIONS ASTM A53, GR B Fy = 35 KSI HSS SECTIONS, SQ/RECT ASTM A500, GR B Fy = 46 KSI BASE AND CONNECTION PLATES ASTM A36 Fy = 36 KSI ANCHOR RODS ASTM F1554, GR 36 Fy = 36 KSI HIGH STRENGTH BOLTS ASTM F3125, GR A325 Fv = 120 KSI HIGH STRENGTH TWIST-OFF BOLTS ASTM F3125, GR F1852 Fv = 120 KSI
HEAVY HEX NUTS ASTM A563
WASHERS ASTM F436
ELECTRODES FOR ARC WELDING AWS 5.1, E70XX
2. HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH AISC
“SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS”.
REFER TO DETAILS FOR BOLT SIZE AND MATERIAL ASTM DESIGNATION.
3. USE TENSION-CONTROL, “TWIST-OFF”, BOLTS FOR ALL HIGH STRENGTH BOLTS
REQUIRING FULL TENSION AS INDICATED ON THE DRAWINGS.
4. ALL HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM F3125, GRADE A325N, UNO.
5. STANDARD BOLT HOLES IN STEEL SHALL BE 1/16 INCH LARGER IN DIAMETER THAN
NOMINAL SIZE OF BOLT USED, UNO.
6. BOLTS IN SLOTTED HOLES SHALL BE LOCATED IN THE CENTER OF THE HOLE
AFTER FIELD ASSEMBLY IS COMPLETE, UNLESS DETAILED OTHERWISE.
7. WELD LENGTHS INDICATED ON THE DRAWINGS ARE THE NET EFFECTIVE LENGTH
REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE,
USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC 360, SECTION J2.4
8. FIELD CONNECTIONS SHALL BE WELDED OR BOLTED. SHOP CONNECTIONS SHALL
BE WELDED, UNO. WELDS INDICATED WITH A SHOP WELD SYMBOL MAY BE MADE
IN THE FIELD WITH THE APPROVAL OF THE STRUCTURAL ENGINEER. LOCATIONS
OF ALL FIELD WELDS SHALL BE CLEARLY SHOWN ON THE SHOP DRAWINGS.
WELDS SHALL BE DESIGNED TO BE FULLY EQUIVALENT IN STRENGTH TO BOLTED
CONNECTIONS DETAILED TO MINIMIZE BENDING IN THE CONNECTION.
9. REFER TO DRAWINGS FOR DETAIL OF DECK OPENINGS. REFER TO
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS, ETC. FOR EXACT
SIZE, LOCATION, AND COUNT OF REQUIRED OPENINGS.
10. CUTS, HOLES, OPENINGS, ETC., REQUIRED IN STRUCTURAL STEEL MEMBERS FOR
THE WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS.
BURNING OF HOLES AND CUTS IN THE FIELD SHALL NOT BE ALLOWED, EXCEPT BY
WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER. NO HOLES SHALL
BE CUT IN STRUCTURAL STEEL BY OTHER TRADES UNLESS SHOWN ON
STRUCTURAL DRAWINGS OR APPROVED IN WRITING BY THE STRUCTURAL
ENGINEER.
COLD-FORMED STEEL FRAMING (CFSF) SYSTEM
1. COLD-FORMED STRUCTURAL STUDS SHALL CONFORM TO THE FOLLOWING
STANDARDS:
ROLLED SECTIONS, CONNECTION MATERIAL, AND STIFFENER PLATES
18 GAUGE AND THINNER ASTM A653, GR 33 Fy = 33 KSI 16 GAUGE AND THICKER ASTM A653, GR 50 Fy = 50 KSI
CONNECTION MATERIAL >3/16" ASTM A36 Fy = 36 KSI ANCHOR RODS ASTM F1554, GR 36 Fy = 36 KSI BOLTS ASTM A307 Fv = 10 KSI
HOT-DIP COATING ASTM A924, G60
ELECTRO-PLATE COATING ASTM A591
ALUMINUM-ZINC COATING ASTM A792, GR 40
INSTALLATION ASTM C955 AND ASTM C1007
ELECTRODES FOR ARC WELDING AWS 5.1, E60XX
2. STRUCTURAL CFSF IS PERFORMANCE SPECIFIED. DESIGN INFORMATION
INCLUDED IN THESE DOCUMENTS IS TO BE CONSIDERED A GUIDELINE FOR
BIDDING PURPOSES ONLY. STUD DEPTH IS REQUIRED TO MEET THOSE INDICATED
ON THE PLANS. CONNECTION DETAILS ARE ONLY AN INDICATION OF SUGGESTED
SUPPORT AND SLIP JOINT ORIENTATION. GAUGE, SECTION, MATERIAL, BRACING,
CONNECTIONS, STIFFENERS, AND SIMILAR DETAILS ARE THE RESPONSIBILITY OF
THE MANUFACTURER BASED ON LOADS GIVEN ON THE PLANS AND
SPECIFICATIONS.
3. PROVIDE TRACKS, BLOCKING, HEADERS, CLIP ANGLES, BRIDGING, SHOES,
REINFORCEMENTS, FASTENERS AND ACCESSORIES TO PROVIDE A COMPLETE
STEEL FRAME SYSTEM IN ACCORDANCE WITH MANUFACTURER’S
RECOMMENDATIONS.
4. TRACK SHALL BE THE SAME SIZE AND GAUGE AS THE STUD.
5. UNIFORM BEARING SURFACE SHALL BE PROVIDED WITH A MAXIMUM 1/4 INCH GAP
BETWEEN BOTTOM TRACK AND THE FOUNDATION OR SLAB. IT SHALL BE
ACCOMPLISHED BY THE USE OF LOAD BEARING SHIMS AND/OR GROUT PROVIDED
BETWEEN THE UNDERSIDE OF THE WALL BOTTOM TRACK AND THE TOP OF THE
FOUNDATION OR SLAB AT EACH STUD.
6. UNLESS OTHERWISE NOTED, ATTACH MATERIALS BY BOLTING OR SCREW
FASTENERS.
A. SCREW CONNECTIONS:
1) SCREWS LARGER THAN SPECIFIED MAY BE USED, PROVIDED THE
MINIMUM SPACING AND EDGE DISTANCE REQUIREMENTS ARE MET.
2) SCREWS SHALL BE FULLY DRIVEN AND HAVE A MINIMUM PENETRATION
OF THREE THREADS THROUGH THE LAST MATERIAL JOINED.
3) SCREWS SHALL HAVE A PROTECTIVE COATING COMPLYING WITH
RECOGNIZED DESIGN STANDARDS FOR THE PROJECT ENVIRONMENTAL
CONDITIONS.
B. BOLT CONNECTIONS:
1) BOLTS SHALL MEET OR EXCEED THE REQUIREMENTS OF ASTM A307 AND
SHALL BE INSTALLED WITH NUTS AND WASHERS AT SPACING PER
RECOGNIZED DESIGN STANDARD.
7. UNLESS INDICATED OTHERWISE ON THE DRAWINGS OR IN SHEAR WALL PANELS,
FASTEN GYPSUM BOARD WITH #6 x 1” BUGLE HEAD SCREWS AT 12” OC AT ALL
SUPPORTS AND EDGES.
8. WEB CRIPPLING BASED ON MINIMUM 10” UNPUNCHED STEEL AT BOTH ENDS.
WOOD
1. SHEATHING
A. SHALL CONFORM TO:
ROOF SHEATHING, FLAT 5/8" THICK; 24/16 APA SPAN RATING
SHEAR WALL SHEATHING SEE SHEAR WALL SCHEDULE
WALL SHEATHING 1/2" THICK
B. REFER TO TYPICAL DETAILS AND WALL SCHEDULES FOR FASTENING
REQUIREMENTS. WHERE NOT NOTED, PROVIDE 6d NAILS AT 6” OC ALONG ALL
EDGES AND AT 12” OC AT INTERMEDIATE SUPPORTS.
C. ALL SHEATHING WHICH IS EXPOSED TO OUTDOOR APPLICATIONS SHALL BE
EXTERIOR TYPE. SHEATHING EXPOSED TO WEATHER ONLY DURING
CONSTRUCTION SHALL BE EXPOSURE 1. ALL WOOD STRUCTURAL PANELS SHALL
CONFORM TO 2303.1.4 AND WHEN USED IN HORIZONTAL DIAPHRAGM AND
VERTICAL SHEAR WALLS SHALL BE FIVE-PLY MINIMUM.
D. WHERE ORIENTED STRAND BOARD SHEATHING IS USED HORIZONTALLY, REMOVE
AND REPLACE IF SHEATHING REMAINS WET FOR EXTENDED PERIODS OF TIME
WHEREBY REDUCING THE STIFFNESS.
BAR
SIZE
#3
OTHER
TOP
3000 PSI CONCRETE
OTHER
TOP
4000 PSI CONCRETE
#4 29 38 25 33
#5 36 47 31 41
#6 43 56 37 49
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
CONCRETE HILTI KWIK BOLT TZ [ESR-1917]
DEWALT POWER STUD+ SD2 [ESR-2502]
RED HEAD TRUBOLT+ [ESR-2427]
SIMPSON STRONG BOLT 2 [ESR-3037]
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
CONCRETE DEWALT POWER SCREW-BOLT+ [ESR-3889]
SIMPSON TITEN HD [ESR-2713]
HILTI KWIK HUS-EZ [ESR-3027]
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
CONCRETE
DEWALT AC 200+ [ESR-4027]
SIMPSON SET-3G [ESR-4057]
HILTI HIT-HY 200 [ESR-3187]
INTENDED USE
28-DAY
STRENGTH (PSI)
MAX W/C
RATIO
A/E SLUMP
FOOTINGS
FOUNDATIONS
SLAB-ON-GRADE
UNLESS NOTED OTHERWISE
0.45
0.5
0.45
0.45
N/A
N/A
N/A
N/A
1"-4"
4"-6"
1"-4"
1"-4"
THICKNESS
(IN)
MAX JOINT
SPACING (FT)
5 13
6 15
15. SHOP DRAWINGS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
16. SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DO NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS AND
SPECIFICATIONS.
REINFORCING STEEL
1. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL
CONFORMING TO THE FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR60 Fy = 60 KSI WELDED WIRE REINFORCING ASTM A1064 Fy = 65 KSI
2. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE
OUTERMOST REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3"
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2"
#5 BARS OR SMALLER 1 1/2"
STRUCTURAL SYMBOL LIST
NOT ALL SYMBOLS MAY APPLY
SYMBOL: DESCRIPTION:
FLOOR OPENING
SLAB DEPRESSION
REVISION TRIANGLE - NUMBER
INDICATES REVISION NUMBER
TOP OF STEEL FRAMING ELEVATION
ABOVE ELEVATION +0' - 0"
BEAM BEARING ON COLUMN
COLUMN BEARING ON BEAM
COLUMN BEARING ON CONCRETE PIER
SHEAR WALL CALLOUT
STEP IN FOOTING
(+16' - 3")
-1"
SHEAR WALL HOLDOWN, TYP
SHEAR WALL LENGTH, TYP
S
STRUCTURAL ABBREVIATION KEY
WWR
VERT
UNO
TYP
TEMP
T&B
STIFF
SIM
REQD
REINF
R
PSI
PSF
PCF
OH
OC
NTS
NIC
MIN
MECH
MAX
LLV
LLH
LL
LB
K, KIP
INT
IN
HORIZ
GALV
f'c
EXT
EXP
(E)
EW
EQUIP
EQ
ELEC
EL
EF
EA
DL
CONT
CONC
CMU
CLR
CFSF
BP
B.O.
ARCH
EOD
VIF
VWA
WELDED WIRE REINFORCING
VERTICAL
UNLESS NOTED OTHERWISE
TYPICAL
TEMPERATURE
TOP AND BOTTOM
STIFFENER
SIMILAR
REQUIRED
REINFORCING, -MENT, -ED
RADIUS
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
POUNDS PER CUBIC FOOT
OPPOSITE HAND
ON CENTER
NOT TO SCALE
NOT IN CONTRACT
MINIMUM
MECHANICAL
MAXIMUM
LONG LEG VERTICAL
LONG LEG HORIZONTAL
LIVE LOAD
POUND
KILOPOUND (1,000 POUNDS)
INTERIOR
INCH
HORIZONTAL
GALVANIZED
CONCRETE COMPRESSIVE STRENGTH
EXTERIOR
EXPANSION
EXISTING
EACH WAY
EQUIPMENT
EQUAL
ELECTRICAL
ELEVATION
EACH FACE
EACH
DEAD LOAD
CONTINUOUS
CONCRETE
CONCRETE MASONRY UNIT
CLEAR
COLD FORM STEEL FRAMING
BASE PLATE
BOTTOM OF
ARCHITECT, -URE, -URAL
DIAMETER
AT
NUMBER OR POUNDS
EDGE OF DECK
DEGREE
VERIFY IN FIELD
VERIFY WITH ARCHITECTURAL DRAWINGS
bf BEAM FLANGE WIDTH
LSV
LSH
LONG SIDE VERTICAL
LONG SIDE HORIZONTAL
Ø
ABBR: DESCRIPTION:
BOTT BOTTOM
CL CENTERLINE
DIA DIAMETER
DIM DIMENSION
GA GAGE OR GAUGE
HSB HIGH STRENGTH BOLT
LONG LONGITUDINAL
PLF POUNDS PER LINEAR FOOT
SP SPACE(S)
SPEC SPECIFICATION(S)
W/ WITH
B.N. BOUNDARY NAILING
E.N. EDGE NAILING
F.N. FIELD NAILING
T.O. TOP OF
FOUNDATION PREPARATION
CONCRETE AND CONCRETE PLACEMENT
VERIFY MATERIALS BELOW SHALLOW FOOTINGS ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.
VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL.
PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS.
REVIEW OF PROPOSED MIX DESIGN AND SUPPORTING TEST RESULTS.
X
X
X
X
XINSPECTION OF FABRICATORS AND DURING FABRICATION.
INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, AND PLACEMENT.
C O
N T
IN
U
O U
S
P E
R
IO
D
IC
REFERENCED
STANDARD
IBC
REFERENCE
X
VERIFYING USE OF REQUIRED DESIGN MIX. X ACI 318: CH. 19, 26.4.3, 26.4.4
PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
ASTM C172, ASTM C31,
ACI 318: 26.4, 26.12
X
INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES. ACI 318: 26.5
INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES.
X
ACI 318: 26.5.3 - 26.5.5X
1904.1, 1904.2, 1908.2, 1908.3
1908.10
1908.6, 1908.7, 1908.8
1908.9
VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING PLACEMENT AND COMPACTION OF COMPACTED FILL. X
PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT THE SITE HAS BEEN PROPERLY PREPARED.
1704.2
1908.4ACI 318: Ch. 20, 25.2, 25.3,
26.6.1 - 26.6.3
XINSPECT ANCHORS CAST IN CONCRETE.
X
INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED. X ACI 318: 26.11.1.2(b)
ACI 318: 17.8.2
X ACI 318: 17.8.2.4
STEEL DECK
SDI - QA / QC STANDARD FOR STEEL DECK INSTALLATION
INSPECTION TASKS PRIOR TO DECK PLACEMENT
DOCUMENT ACCEPTANCE OR REJECTION OF DECK AND DECK ACCESSORIES
VERIFY COMPLIANCE OF MATERIALS (DECK AND ALL DECK ACCESSORIES) WITH CONSTRUCTION DOCUMENTS, INCLUDING
PROFILES, MATERIAL PROPERTIES, AND BASE METAL THICKNESS
INSPECTION ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS.
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN ROW ABOVE. X ACI 318: 17.8.2
O - OBSERVE THESE ITEMS ON AN INTERMITTENT BASIS
P - PERFORM THESE TASKS PRIOR TO FINAL ACCEPTANCE FOR EACH ITEM OR ELEMENT.
INSPECTION TASKS AFTER DECK PLACEMENT
VERIFY COMPLIANCE OF DECK AND ALL DECK ACCESSORIES INSTALLATION WITH CONSTRUCTION DOCUMENTS
VERIFY COMPLIANCE OF DECK MATERIALS ARE REPRESENTED BY THE MILL CERTIFICATIONS THAT COMPLY WITH THE
CONSTRUCTION DOCUMENTS
DOCUMENTS ACCEPTANCE OR REJECTION OF INSTALLATION OF DECK AND DECK ACCESSORIES
INSPECTION TASKS PRIOR TO MECHANICAL FASTENING
MANUFACTURER INSTALLATION INSTRUCTIONS ARE AVAILABLE FOR MECHANICAL FASTENERS
PROPER TOOLS ARE AVAILABLE FOR FASTENERS INSTALLATION
PROPER STORAGE FOR MECHANICAL FASTENERS
INSPECTION TASKS DURING MECHANICAL FASTENING
FASTENERS ARE POSITIONED AS REQUIRED
FASTENERS ARE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS
INSPECTION TASKS AFTER MECHANICAL FASTENING
CHECKING SPACING, TYPE, AND INSTALLATION OF SUPPORT FASTENERS
CHECK SPACING, TYPE, AND INSTALLATION OF SIDELAP FASTENERS
CHECK SPACING, TYPE, AND INSTALLATION OF PERIMETER FASTENERS
VERIFY REPAIR ACTIVITIES
DOCUMENTS ACCEPTANCE OR REJECTION OF MECHANICAL FASTENERS
INSPECTION TASKS FOR SEISMIC RESISTANCE
FOR STRUCTURES IN SEISMIC DESIGN CATEGORY C, D, E, OR F, INSPECT DIAPHRAGMS THAT ARE PART OF THE SEISMIC LOAD RESISTING SYSTEM
P
P
P
P
PP
O
O
O
O
O
P
P
P
P
P
P
STRUCTURAL COMPONENT TESTING AND INSPECTION
1. THE FOLLOWING TESTING AND INSPECTION OF STRUCTURAL COMPONENTS IS REQUIRED AS DETAILED IN CHAPTER 17 OF THE 2018 INTERNATIONAL BUILDING CODE (IBC) AND PROJECT SPECIFICATIONS.
2. SEE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING AND ELECTRICAL SPECIFICATIONS FOR TESTING AND INSPECTION REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. WORK PERFORMED ON THE PREMISES OF A FABRICATOR APPROVED BY THE BUILDING OFFICIAL PER SECTION 1704.2.5.1 OF CHAPTER 17 OF THE 2018 INTERNATIONAL BUILDING CODE NEED NOT BE TESTED AND INSPECTED PER THE TABLE BELOW. THE FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE THAT THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS TO THE BUILDING OFFICIAL AND THE ARCHITECT AND ENGINEER OF RECORD.
DUTIES OF THE SPECIAL INSPECTION AGENCY (IBC CHAPTER 17):
A. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE ARCHITECT AND THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK. THE TABLE BELOW SHALL SERVE AS A GUIDELINE FOR THE SCOPE OF THE TESTING AND INSPECTION PROGRAM.
B. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND INSPECTION PROGRAM.
C. FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT, THE ENGINEER OF RECORD AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE COMPLETED AND
FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
D. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION AGENCY'S KNOWLEDGE, IN CONFORMANCE WITH THE
APPROVED PLANS AND SPECIFICATIONS.
WELDING PROCEDURE SPECIFICATIONS (WPSS) AVAILABLE P
AISC 360 - CHAPTER N: STRUCTURAL STEEL QUALITY ASSURANCE
O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS.
P - PERFORM THESE TASKS FOR EACH WELDED JOINT MEMBER.
INSPECTION TASKS PRIOR TO WELDING
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE P
MATERIAL IDENTIFICATION (TYPE / GRADE) O
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
• JOINT PREPARATION
• DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
• BACKING TYPE AND FIT (IF APPLICABLE)
O
CONFIGURATION AND FINISH OF ACCESS HOLES O
O
INSPECTION TASKS DURING WELDING
USE OF QUALIFIED WELDERS
CONTROL AND HANDLING OF WELDING CONSUMABLES
• PACKAGING
• EXPOSURE CONTROL
O
O
NO WELDING OVER CRACKED TACK WELDS O
ENVIRONMENTAL CONDITIONS
• WIND SPEED WITHIN LIMITS
• PRECIPITATION AND TEMPERATURE
O
WPS FOLLOWED
• SETTINGS ON WELDING EQUIPMENT
• TRAVEL SPEED
• SELECTED WELDING MATERIALS
• SHIELDING GAS TYPE / FLOW RATE
• PREHEAT APPLIED
• INTERPASS TEMPERATURE MAINTAINED (MIN. / MAX.)
• PROPER POSITION (F,V,H,OH)
O
WELDING TECHNIQUES
• INTERPASS AND FINAL CLEANING
• EACH PASS WITHIN PROFILE LIMITATIONS
• EACH PASS MEETS QUALITY REQUIREMENTS
O
INSPECTION TASKS AFTER WELDING
WELDS CLEANED O
SIZE, LENGTH, AND LOCATION OF WELDS P
WELDS MEETS VISUAL ACCEPTANCE CRITERIA
• CRACK PROHIBITION
• WELD / BASE-METAL FUSION
• CRATER CROSS SECTION
• WELD PROFILES
• WELD SIZE
• UNDERCUT
• POROSITY
P
ARC STRIKES P
K-AREA: WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 INCHES OF THE WELD
P
BACKING REMOVED AND WELD TABS REMOVED AND FINISHED (IF REQUIRED) P
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER P
REPAIR ACTIVITIES P
FIT-UP OF FILLET WELDS
• DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTSOffice of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Kokua Geotech, LLC.
94-974 Pakela St. Suite 109
Waipahu, HI 96797
(808)397-6974
Tim (Xiaobin) Lin
Project Director
BASE BID
Dwg of
C R e v it L o c a l F ile s \S
.1
P
A C
IF
IC
N A
T
IO
N A
L C
E M
E T
E R
Y C
M e h u lk u m a r.
V .N a k ra n i.
rv t
/1
/2
:0
:4
P
M
STRUCTURAL GENERAL NOTES
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 JOHGOE PRIPAN
15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
S-001 99 138Revisions: Date:
SW2
(13' - 0")
S W
(3
SW1
(7' - 6")
SW1
(7' - 6")
OPEN-GRADED GRAVEL
VAPOR RETARDER - SEE SPECS
NOTES:
1. REFERENCE SPECIFICATIONS FOR MATERIAL AND COMPACTION REQUIREMENTS.
2. COMPACT ALL FILL MATERIAL TO 90% OF THE MAXIMUM DRY DENSITY PER ASTM D1557.
3. VAPOR RETARDER TO MEET ASTM E1745, CLASS A AND BE NOT LESS THAN 15 MILS THICK.
4. SCARIFY THE SUBGRADE SOILS TO A DEPTH OF 10 INCHES, MOISTURE CONDITION THE
SOILS TO AT LEAST 2% ABOVE THE OPTIMUM MOISTURE CONTENT AND COMPACT TO A
MINIMUM 90% RELATIVE COMPACTION.
SLAB ON GRADE - SEE PLAN
REINFORCING - SEE PLAN
/3 t)
S E
E P
L A
N T
H
IC
K N
E S
S t)
STRUCTURAL FILL MATERIAL
SUBGRADE - NOTE 4
SAWCUT JOINT WITHIN
24 HOURS OF CONCRETE
PLACEMENT
SLAB ON GRADE
SEE PLAN
t/
M
IN
IM
U
M
1/4"
S E
E P
L A
N T
H
IC
K N
E S
S t)
NOTE:
1. SEE CAST-IN-PLACE CONCRETE GENERAL NOTES
CONCERNING LOCATION OF JOINTS.
S E
E P
L A
N T
H
IC
K N
E S
S
TOOLED RADIUS
2' - 6"
#4 @ 18" OC
C L R 1' - 0"
#4 CONT @ 12" OC
GRADE
M
IN
SLAB ON GRADE
SEE PLAN
STEEL COLUMN
SEE PLAN
2' - 0"
SEE PLAN SEE PLAN
S E
E P
L A
N T
H
IC
K N
E S
S
A.1A
#4 STIRRUPS @ 18" OC
#4 SIDE BAR, EACH FACE
(3) #4 CONT TOP
AND BOTTOM
GRADE
SLAB - SEE PLAN
#10 SCREW EACH
FLANGE, TYP
BOTTOM TRACK
TYPICAL
STUDS - SEE
PLAN FOR
SPACING
DOUBLE
STUDS AT
OPENING, TYP
CONCRETE
CURB
A B
/4
/8
4" SLAB ON GRADE
REINFORCED WITH 6x6 -
W1.4xW1.4 WWR
A.1
H SS4x4x1/4BP1
H SS4x4x1/4
BP1
3 3/8" 6 5/8"
14' - 6"
NOTES:
1. SEE 2 AND 3/SB101 FOR TYPICAL SLAB ON GRADE CONSTRUCTION DETAILS.
2. CF2.0 INDICATES 2'-0" WIDE x 2'-0" DEEP CONTINUOUS FOOTING. 5/SB101 FOR MORE
INFORMATION.
3. BP1 INDICATES BASE PLATE. SEE 1/SF102.
4. SLOPE FLOOR SLAB TO FLOOR DRAINS, COORDINATE WITH ARCH AND MECH DRAWINGS.
5. SEE SB101 FOR SHEAR WALL AND HOLDOWN SCHEDULES.
6. AT DOOR OPENINGS, HOLD CURB BACK 3" FOR CFSF WALL STUDS TO EXTEND TO SLAB
ON GRADE. COORDINATE DOOR OPENING LOCATIONS WITH ARCH. SEE 6/SB101 FOR
MORE INFORMATION.
7. COORDINATE CONCRETE CURB LOCATIONS WITH ARCH DRAWINGS.
KEYNOTES:
1. HSS5x5x5/16 WITH 3/16" CAP PLATE. T.O. COLUMN IS ( +6' - 2"). SEE 12/SB101 FOR BOTTOM
CONNECTION. CFSF CONNECTION TO COLUMN BY CFSF DESIGNER.
2. HSS5x5x5/16 WITH 3/16" CAP PLATE. T.O. COLUMN IS ( +6' - 8"). SEE 12/SB101 FOR BOTTOM
CONNECTION. CFSF CONNECTION TO COLUMN BY CFSF DESIGNER.
T.O. SLAB EL (+0' - 0")
T.O. SLAB
EL (+0' - 0")
T.O. SLAB
EL (+0' - 0 5/8")
SB101
SB101
EXPOSED CONCRETE
SLAB TO SLOPE AS
INDICATED BY SLOPE
ARROWS, TYP
SB101
SB101
TYP
SB101
TYP
/8
W A
L L
SB101
SB101
C F
.0
3"
/4
2' - 0"
1' - 5 3/4"
?1 ?1
?1
?1
?1?1
?1
EL ( -0' - 1")
T.O. SLAB
EL ( +0' - 0")
T.O. SLAB
EL ( +0' - 0")
T.O. SLAB
EL ( +0' - 1")
T.O. SLAB
EL ( +0' - 0")
T.O. SLAB
EL ( -0' - 1")
T.O. SLAB
/8
C F
.0
8" WALL
SB101
STEP FOOTING UP AT
INTERIOR FOOTING, TYP
SB101
SIM
S
S
STEEL STUD WALL
SEE PLAN
SLAB ON GRADE
SEE PLAN
AT SHEAR WALLS, SEE SCHEDULE
FOR BOTTOM TRACK ATTACHMENT.
AT BEARING WALLS, PROVIDE HILTI X-
U 0.145"Ø POWDER ACTUATED
FASTENER WITH 1 1/4" EMBED @ 8" OC
(1) #10 TEK SCREW
EACH SIDE
NOTES:
1. CENTER THICKENED SLAB ABOUT WALL. SEE
ARCHITECTURAL DRAWINGS FOR WALL LOCATIONS.
6"
CONCRETE CURB
T Y
P
2' - 0"
#4 STIRRUPS @ 18" OC
#4 SIDE BAR, EACH FACE
(3) #4 CONT TOP
AND BOTTOM
#4 DOWELS CENTERED IN
CURB @ 18" OC. PROVIDE
180 DEG HOOK ON TOP
(2) #4 CONT
S E
E P
L A
N T
H
IC
K N
E S
S
C L R
M
IN
6 5/8"
CONCRETE
CURB
STEEL STUD WALL
SEE PLAN
AT SHEAR WALLS, SEE SCHEDULE FOR
BOTTOM TRACK ATTACHMENT. AT
BEARING WALLS, PROVIDE HILTI X-U
0.145"Ø POWDER ACTUATED
FASTENER WITH 1 1/4" EMBED @ 8" OC
(1) #10 TEK SCREW
EACH SIDE
NOTES:
1. SEE 4/SB101 FOR ADDITIONAL INFORMATION.
2. T.O. LEDGE TO BE 2" TO 3" ABOVE GRADE.
SEE ARCH.
#4 DOWELS CENTERED IN
CURB @ 18" OC. PROVIDE
180 DEG HOOK ON TOP
(2) #4 CONT
A T
S
IM
GRADE
EL (NOTE 2)
T.O. LEDGE
3 1/2"
1' - 0"
S E
E P
L A
N T
H
IC
K N
E S
S
C L R
1' - 0"
2" CLREL ( +1' - 11 1/2" )
T.O. WALL 3 1/2" SEE PLAN
#4 @ 12" OC
(3) #4 CONT
NOTES:
1. SEE 4/SB101 FOR ADDITIONAL INFORMATION.
2. T.O. LEDGE TO BE 2" TO 3" ABOVE GRADE. SEE CIVIL.
GRADE
EL ( NOTE 2)
T.O. LEDGE
S E
E P
L A
N T
H
IC
K N
E S
S
C L R
1' - 0"
EL ( +1' - 11 1/2" )
T.O. WALL
#4 @ 12" OC
(3) #4 CONT
NOTES:
1. SEE 4/SB101 FOR ADDITIONAL INFORMATION.
2. T.O. LEDGE TO BE 2" TO 3" ABOVE GRADE. SEE CIVIL.
2" CLR
B
SEE PLAN
M
IN
GRADE
3 1/2"
EL (NOTE 2)
T.O. LEDGE
BACK TO BACK
BRACE FRAME END
POST- SEE PLAN
HOLD DOWN
SEE SCHEDULE
BOTTOM TRACKT.O. SLAB OR
CURB
HOLDOWN ANCHOR
SEE SCHEDULE
S-111
CONCRETE
CURB WHERE
SHOWN
OPENING
NOTE:
1. ANCHOR EMBEDMENT IS IN SLAB / FOOTING. CONCRETE CURB DOES NOT
APPLY FOR EMBEDMENT DEPTH.
P E
R S
C H
E D
U L E
A N
C H
O R
E M
B E
D M
E N
T
S E
E P
L A
N T
H
IC
K N
E S
S
C L R
1' - 0"
M
IN
6 5/8"
CONCRETE
CURB
STEEL COLUMN
SEE PLAN
SEE DETAIL 4/SB101
FOR REMAINDER OF
INFORMATION
(3) #4 CONT
PL3/4"x6 5/8 x 0'-10"
(2) #4 DOWELS (A706) AT
EACH SIDE @ 8" OC
CENTERED ON PLATE.
PROVIDE 180 DEG HOOK
ON BOTTOM. FULL PEN
WELD TO PLATE.
SEE PLAN
1/4
(2) #4 DOWELS AT EACH FACE
@ 8" OC CENTERED ON
COLUMN. PROVIDE 180 DEG
HOOK ON TOP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTSOffice of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Kokua Geotech, LLC.
94-974 Pakela St. Suite 109
Waipahu, HI 96797
(808)397-6974
Tim (Xiaobin) Lin
Project Director
BASE BID
Dwg of
C R e v it L o c a l F ile s \S
.1
P
A C
IF
IC
N A
T
IO
N A
L C
E M
E T
E R
Y C
M e h u lk u m a r.
V .N a k ra n i.
rv t
/1
/2
:0
:4
P
M
RESTROOM BUILDING
FOUNDATION PLAN - STRUCTURAL
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 JOHGOE PRIPAN
15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
SB101
3/4" = 1'-0"
TYPICAL SLAB SECTION
2 3/4" = 1'-0"
TYPICAL CONTROL JOINT
3 3/4" = 1'-0"
TYPICAL EDGE OF SLAB DETAIL
3/4" = 1'-0"
FOUNDATION DETAIL
5 3/4" = 1'-0"
BEARING WALL TRACK ANCHORAGE DETAIL
N O R
HT
1/4" = 1'-0"1
RESTROOM BUILDING - FOUNDATION PLAN
3/4" = 1'-0"
FOUNDATION DETAIL
3/4" = 1'-0"
FOUNDATION DETAIL
3/4" = 1'-0"
FOUNDATION DETAIL
10 3/4" = 1'-0"
FOUNDATION DETAIL
1" = 1'-0"
HOLDOWN ANCHORAGE DETAIL
3/4" = 1'-0"
FOUNDATION DETAIL
NO SPRINKLERS
100 138Revisions: Date: 137
CFSF JOIST - SEE PLAN
SHEATHING
SEE PLAN
#12 SCREW @ 6" OC.
SHEATHING TO BLOCKING AND
BLOCKING TO TOP TRACK
STEEL STUD WALL
SEE PLAN
SEE PLAN
16 GA FULL
DEPTH BLOCKING
CFSF JOIST, TYP
SHEATHING
SEE PLAN
STEEL STUD WALL
SEE PLAN
SEE PLAN
OUTRIGGER
SEE PLAN
#12 SCREW @ 6" OC.
SHEATHING TO BLOCKING AND
BLOCKING TO TOP TRACK
16 GA FULL
DEPTH BLOCKING
A B
2' - 3" 14' - 6" 2' - 3"
/8
/4
/8
A.1
H
H1
H
H
H
H1
HSS6x6x3/8
6" CFSF JOISTS
@ 16" OC
EL ( +9' - 0" )
T.O. WALL
6" CFSF JOISTS
@ 16" OC
SF102
SF101
SF101
SF101
SF101
SF101
SF1013
SF101
SF101
NOTES:
1. ROOF SHEATHING IS 5/8" PLYWOOD, UNO. SEE 3/SF102 FOR FASTENING REQUIREMENTS.
2. EXTERIOR WALL SYSTEM: 6" CFSF @ 16" OC (MAX). FINAL DESIGN BY CFSF DESIGNER. SEE
GENERAL NOTES AND SPECIFICATIONS FOR MORE INFORMATION.
3. H1 AND H2 INDICATE CFSF HEADER IN WALL OPENING. FINAL DESIGN BY CFSF DESIGNER.
SEE GENERAL NOTES AND SPECIFICATIONS FOR MORE INFORMATION.
6" CFSF
OUTRIGGERS
@ 16" OC
6" CFSF
OUTRIGGERS
@ 16" OC
6" CFSF
OUTRIGGERS
@ 16" OC
6 5/8"
1"
12"
ROOF SLOPE
KEYNOTES:
1. SKYLIGHT - COORDINATE SIZE AND LOCATION WITH ARCH.
2. CFSF BLOCKING FOR TOILET PARTITION SUPPORT. GC TO PROVIDE LOADS FROM SELECTED PARTITION SUPPLIER FOR CFSF DESIGNER. COORDINATE QUANTITY AND LOCATION WITH ARCH LAYOUT AND
PARTITION SUPPLIER. PARTITION SUPPORT CONNECTION TO CFSF BLOCKING BY GC.
3. ROOF FRAMING CONCEPT SHOWN REQUIRES EDGE TRACK FRAMING TO SUPPORT OUTRIGGERS OVER
WING WALL. CFSF DESIGNER TO ADJUST FRAMING LAYOUT AS NEEDED FOR THEIR DESIGN.
4. CFSF DESIGNER TO INCLUDE STONE CAP WEIGHT IN DESIGN OF WING WALL STUDS. COORDINATE
WEIGHT OF CAP WITH SUPPLIER.
SPACE CFSF AT 18" OC
AT SKYLIGHT. REDUCE
ADJACENT SPACING FOR
AVERAGE OF 16" OC
SPACE CFSF AT 18" OC
AT SKYLIGHT. REDUCE
ADJACENT SPACING FOR
AVERAGE OF 16" OC
6" CFSF
OUTRIGGERS
@ 16" OC
( +10' - 7 7/16")
TYP
HOLDOWN SCHEDULE
NOTES:
1. BASIS OF DESIGN IS SIMPSON STRONG-TIE. SUBSTITUTIONS REQUIRE WRITTEN AUTHORIZATION FROM STRUCTURAL ENGINEER.
2. SEE FOR DETAILS.
MARK MODEL NO. SCREW
CONNECTION
TO POST
HOLDOWN
POST
ANCHOR ROD
DIAMETER
(IN)
MATERIAL
EMBEDMENT
"E" (IN)
S/HD8S (17) #14 (2) 600S162-54 7/8" F1554 - GR36 10"
REMARKS
SB101
COLD FORM SHEAR WALL SCHEDULE
NOTES:
1. SHEATHING SHALL BE PLYWOOD ONLY.
2. SEE SF102 FOR TYPICAL SHEAR WALL CONSTRUCTION DETAILS.
3. ALL PANEL EDGES ARE TO BE BLOCKED. EDGE BLOCKING TO BE PROVIDED BY THE COLD FORM SUPPLIER.
4. SEE PLAN FOR HOLDOWN ANCHOR AND POST SIZE.
5. USE #10 SCREW IF STUDS ARE 16 GAUGE OR THICKER.
6. WALL BOTTOM TRACK TO HAVE 1 1/4" LEG AND MATCH GAUGE OF STUDS.
MARK
THICKNESS
GRADE SPAN
RATING
APA RATED SHEATHING
PANEL FASTENER SIZE
AND SPACING
SIZE EDGE FIELD
FRAMING SIZE
AT ADJOINING
PANEL
EDGES, MIN
BOTTOM TRACK
ANCHORS AT CONCRETE
SIZE AND
SPACING
EMBEDMENT
(IN)
REMARKSALLOWABLE
SHEAR
CAPACITY
(PLF)
1/2" NOMINAL STRUCTURAL 1 32/16 700 1 1/2" HILTI X-U PAF @ 6" OC 1 1/4" -
1/2" NOMINAL STRUCTURAL 1 32/16 500 1 1/2" (1) HILTI X-U PAF @ 8" OC 1 1/4" -
HILTI X-PN 37 G3 MX @ 4" 12"
HILTI X-PN 37 G3 MX @ 6" 12"
EL (SEE PLAN)
T.O. STEEL
STEEL BEAM
SEE PLAN
SHEATHING
SEE PLAN
CFSF JOIST
SEE PLAN
CONT TRACK. SIZE AND
ATTACHMENTS BY CFSF
DESIGNER
SEE PLAN
OUTRIGGER
SEE PLAN
NOTE:
1. HSS IS ROTATED WITH ROOF SLOPE (1 V TO 12 H).
FLAT STRAP ON TOP AND
BOTTOM - AS NEEDED BY
CFSF DESIGNER
SHEATHING
SEE PLAN
#12 SCREW @ 6" OC.
SHEATHING TO BLOCKING AND
BLOCKING TO TOP TRACK
CFSF JOIST
SEE PLAN
STEEL STUD WALL
SEE PLAN
16 GA FULL
DEPTH BLOCKING
SHEATHING
SEE PLAN
#12 SCREW @ 6" OC
SHEATHING TO JOIST AND
JOIST TO TOP TRACK
CFSF JOIST
SEE PLAN
STEEL STUD WALL
SEE PLAN
CONNECTION BY
CFSF DESIGNER
CFSF JOIST
SEE PLAN
BLOCKING AS
NEEDED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTSOffice of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Kokua Geotech, LLC.
94-974 Pakela St. Suite 109
Waipahu, HI 96797
(808)397-6974
Tim (Xiaobin) Lin
Project Director
BASE BID
Dwg of
C R e v it L o c a l F ile s \S
.1
P
A C
IF
IC
N A
T
IO
N A
L C
E M
E T
E R
Y C
M e h u lk u m a r.
V .N a k ra n i.
rv t
/1
/2
:0
:5
P
M
RESTROOM BUILDING FRAMING
PLAN - STRUCTURAL
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 JOHGOE PRIPAN
15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
SF101
3/4" = 1'-0"
JOIST BEARING AT STUD WALL
2 3/4" = 1'-0"
JOIST PARALLEL TO STUD WALL
N O R
HT
1/4" = 1'-0"1
RESTROOM BUILDING - FRAMING PLAN
1 1/2" = 1'-0"
FRAMING DETAIL
1 1/2" = 1'-0"
FRAMING DETAIL
5 1 1/2" = 1'-0"
FRAMING DETAIL
NO SPRINKLERS
101 138Revisions: Date:
1/4
4 SIDES
3/4" BASE PLATE
3/4"Ø ANCHOR ROD
WITH 9" EMBED USING
ADHESIVE ANCHOR
PER S-001, TYP
STEEL COLUMN
SEE PLAN
1 1/2" TYP 1 1/2" TYP
EL (SEE PLAN)
T.O. STEEL
STEEL BEAM
SEE PLAN
CAP PLATE:
PL1/2"x5" x 0'-8"
STEEL COLUMN
SEE PLAN
3/16
STAGGER JOINT
FACE OF GRAIN
EDGE OF SHEET JOINT
TO BE CL OF FRAMING
OR BLOCKING
EDGE FASTENING: HILTI X-PN
G3 MX FASTENERS @ 3" OC
TYP, UNO
BOUNDARY FASTENING :
HILTI X-PN G3 MX FASTENERS
@ 3" OC TYP, UNO
FIELD FASTENING :
HILTI X-PN G3 MX @ 9" OC
REPRESENTATIVE OF
4' - 0" x 8' - 0" SHEET, TYP
(MIN DIM OF ANY SHEET = 24")
3/8" MIN EDGE DISTANCE
AT BLOCKING, TYP
SEE PLAN FOR FRAMING SIZE AND SPACING
1 1/2" WIDE CFSF BLOCKING, TYP
T Y
P
S H
E A
T H
IN
G
S
E E
P L A
N
F.N.
TYP
E.N.
TYP
E.N.
TYP
SILL PLATE,
TYP
E.N.HOLDOWN ANCHOR
SEE FOUNDATION
PLAN AND DETAIL
E.N.
"X
F.N.
BLOCKING
CONTACT STRUCTURAL
ENGINEER IF VENTS
OCCURS AT BLOCKING
BEFORE PLACING
VENTS
E.N.
"X" "X/2"
"X /2
"X
BLOCKING
NOTES:
A. STRUCTURAL SHEATHING:
1. FOR SHEATHING TYPE (PLYWOOD, RATED SHEATHING, ETC.), SEE
FRAMING PLANS AND SHEAR WALL SCHEDULE.
2. USE 4' - 0" x 8' - 0" MINIMUM SIZE SHEATHING WHEREVER POSSIBLE AND
STAGGER ADJACENT HORIZONTAL JOINTS IN ALL CASES AS SHOWN.
3. MINIMUM DIMENSION OF ANY PIECE OF SHEATHING SHALL BE 2' - 0".
4. LEAVE A 1/8" GAP BETWEEN ALL PIECES OF SHEATHING AT EACH STUD
AND BLOCKING WHERE SHEATHING SPLICE OCCURS TYP.
B. NAILING:
1. E.N. = EDGE NAILING F.N. = FIELD NAILING
2. 'X' REPRESENTS THE SPACING OF NAILS. SIZE OF NAILS AND SPECIFIC
SPACING ARE SHOWN ON SCHEDULE.
3. THE MINIMUM EDGE DISTANCE FOR FASTENING OF SHEATHING SHALL
BE: 1/2" FOR #10, 3/8" FOR #8.
4. MINIMUM STUDS AND BLOCKING SIZES AT SHEATHING SPLICES SHALL
BE PER SHEAR WALL SCHEDULE.
5. ALL EDGE NAILING SHALL BE STAGGERED AT ADJOINING PANEL EDGES.
SEE TYPICAL SHEAR PANEL ELEVATION.
C. GENERAL:
1. SEE SHEAR WALL SCHEDULE FOR ADDITIONAL REQUIREMENTS.
OPEN
SB101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTSOffice of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Kokua Geotech, LLC.
94-974 Pakela St. Suite 109
Waipahu, HI 96797
(808)397-6974
Tim (Xiaobin) Lin
Project Director
BASE BID
Dwg of
C R e v it L o c a l F ile s \S
.1
P
A C
IF
IC
N A
T
IO
N A
L C
E M
E T
E R
Y C
M e h u lk u m a r.
V .N a k ra n i.
rv t
/1
/2
:0
:5
P
M
RESTROOM BUILDING FRAMING
DETAILS
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 JOHGOE PRIPAN
15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
SF102
1" = 1'-0"
BASE PLATE (BP1) DETAIL
1 3/4" = 1'-0"
FRAMING DETAIL
3/8" = 1'-0"
TYPICAL ROOF SHEATHING DETAIL
3/4" = 1'-0"
SINGLE STORY SHEAR WALL ELEVATION
NO SPRINKLERS
102 138Revisions: Date:
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
F R
O N
T
B A
C K
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
FRONT
BACK
F R
ON
T
B A C
K
1 1
2A
4A
4 3A
9A
RETAINING WALL
PER 2/SS103
RETAINING WALL
PER 3/SS103 SIM
RETAINING WALL
PER 3/SS103
RETAINING WALL
PER 3/SS103 SIM
RETAINING WALL
PER 5/SS103
RETAINING WALL
PER 3/SS103 SIM
RETAINING WALL
PER 5/SS103 SIM
RETAINING WALL
PER 5/SS103 SIM
LOCATION OF
RETAINING WALL
CHANGE
RETAINING WALL
PER 1/SS103
RETAINING WALL
PER 1/SS103 SIM
RETAINING WALL
PER 5/SS103
BASE BID SCOPEBASE BID SCOPE.
FOR OPTION 1 SCOPE
CHANGES PER SS200
SCOPE MATCHLINE
4B
NOTES:
1. SEE L AND LC-SHEETS FOR MORE INFORMATION.
2. SEE 10/SS101 FOR FOOTING STEP DETAIL. COORDINATE STEP
LOCATIONS WITH GRADING PLAN TO MAINTAIN MINIMUM 1'-6"
GRADE ABOVE TOP OF FOOTINGS.
3. SEE 2/SS100 FOR SITE PREPARATION AT COLUMBARIUM.
KEYNOTES:
1. SINGLE SIDED COLUMBARIUM RETAINING WALL - SEE 1/SS101.
2. CONCRETE WALL. SEE 9/SS101. AT 2A, SEE 8/SS101.
3. SINGLE SIDED COLUMBARIUM WALL - SEE 5/SS101. AT 3A, SEE
4/SS103.
4. STAIRS. SEE 6/SS101. AT 4A, SEE 6/SS103 FOR WALL AT SIDES OF
STAIRS. AT 4B, SEE 7/SS103 FOR WALL AT SIDES OF STAIRS.
5. OFFSET DOUBLE SIDED COLUMBARIUM RETAINING WALL - SEE
2/SS101.
6. CONCRETE WALL. SEE 7/SS101.
7. DOUBLE SIDED COLUMBARIUM END WALL PIER - SEE 1/SS102.
8. DOUBLE SIDED COLUMBARIUM MIDDLE WALL PIER - SEE 2/SS102.
9. SINGLE SIDED COLUMBARIUM END WALL PIER - SEE 3/SS102.
AT 9A, SEE 8/SS101 FOR PERPENDICULAR WALL INFORMATION.
10. SINGLE SIDED COLUMBARIUM MIDDLE WALL PIER - SEE 4/SS102.
11. SINGLE SIDED COLUMBARIUM END WALL PIER. SEE 5/SS102.
12. SINGLE SIDED COLUMBARIUM END WALL PIER. SEE 6/SS102.
13. SINGLE SIDED COLUMBARIUM MIDDLE WALL PIER. SEE 7/SS102.
14. SINGLE SIDED COLUMBARIUM MIDDLE WALL PIER. SEE 8/SS102.
15. SINGLE SIDED COLUMBARIUM END WALL PIER. SEE 9/SS102.
N O
T E
3' - 0" 3' - 0"
COLUMBARIUM
FOUNDATION
FINISH GRADE
CONTRACTOR TO
DETERMINE SLOPE
NOTES:
1. COORDINATE LENGTH OF COLUMBARIUM EXCAVATION WITH CIVIL AND LANDSCAPE DRAWINGS.
2. GEOTECHNICAL REPORT INDICATES APPROXIMATELY 1'-0" TO 3'-0" OF OF SANDY SILT ON TOP OF
VOLCANIC TUFF IN AREA OF COLUMBARIUM. AT A MINIMUM, OVER-EXCAVATION SHALL EXTEND
DOWN TO NATIVE VOLCANIC TUFF. TUFF REMOVAL MAY BE REQUIRED FOR FOUNDATION DESIGN
DEPTHS.
3. PLACE ACCEPTABLE STRUCTURAL FILL UNDER THE FOOTINGS IN LOOSE LIFTS OF ABOUT 8 INCHES TO ACHIEVE REQUIRED ELEVATIONS. EACH LIFT SHALL BE MOISTURE CONDITIONED TO ABOVE THE
OPTIMUM MOISTURE CONTENT AND COMPACTED TO AT LEAST 90% RELATIVE COMPACTION.
4. SEE GEOTECHNICAL REPORT FOR USCS CLASSIFICATION FOR ACCEPTABLE STRUCTURAL FILL
MATERIAL AND GENERAL FILL MATERIAL. ALL MATERIAL TO BE APPROVED AND COMPACTION
OBSERVED BY GEOTECHNICAL ENGINEER TO VERIFY THE ADEQUACY OF THE COMPACTION EFFORT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTSOffice of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Kokua Geotech, LLC.
94-974 Pakela St. Suite 109
Waipahu, HI 96797
(808)397-6974
Tim (Xiaobin) Lin
Project Director
BASE BID
Dwg of
C R e v it L o c a l F ile s \S
.1
P
A C
IF
IC
N A
T
IO
N A
L C
E M
E T
E R
Y C
M e h u lk u m a r.
V .N a k ra n i.
rv t
/1
/2
:0
:5
P
M
COLUMBARIUM COURT PLAN
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 JOHGOE PRIPAN
15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
SS100
N O R
HT
3/32" = 1'-0"1
COLUMBARIUM COURT PLAN - BASE BID
NO SCALE
COLUMBARIUM PAD SITE PREPARATION
2 SCHEMATIC
103 138Revisions: Date:
6"
3"
NOTE 1
3"
EL (SEE LC SHEETS)
T.O. STEM WALL
EL (SEE PLAN ON SS102)
T.O. LEDGE
EL (SEE PLAN ON SS102)
T.O. LEDGE
EL (SEE PLAN ON SS102)
T.O. PIER
HORIZONTAL: #4 @ 12"
OC, EACH FACE. PROVIDE
CORNER BARS OR U-
BARS MATCHING BAR
SIZE AND SPACING. BARS
ARE TIES AS INDICATED
ON PLANS ON SS102
VERTICAL:
#6 @ 12" OC, EACH FACE
SEE SECTIONS ON
THIS SHEET FOR BARS
DOWELS: MATCH VERTICAL
BAR SIZE AND SPACING
SEE SECTIONS ON
THIS SHEET FOR BARS
NOTE:
1. DIMENSION VARIES - SEE LC SHEETS.
GRADE
SEE CIVIL
MATCH VERTICAL AND
HORIZONTAL BAR SIZE
AND SPACING
C L R
EL (SEE LC SHEETS)
T.O. STEMWALL
(4) #5 CONT
#5 @ 12" OC
3' - 0"
VERTICAL:
#5 @ 12" OC, EACH FACE
HORIZONTAL:
#5 @ 12" OC, EACH FACE
#5 @ 12" OC
3" 1' - 9"
(3) #5 CONT
N O
T E
FRONT OF COLUMBARIUM
PROVIDE STD
90 DEG HOOK
GRADE
SEE CIVIL
NOTE:
1. DIMENSION VARIES - SEE LC SHEETS.
M
IN
5' - 0"
EQ 3' - 10" EQ
#5 @ 8" OC
VERTICAL:
#5 @ 8" OC
#5 @ 12" OC
VERTICAL:
#5 @ 8" OC
VERTICAL:
#5 @ 8" OC
1' - 9" 2' - 1"
1 1/2" CLR
C L R
(6) #5 CONT
HORIZONTAL:
#5 @ 12" OC,
EACH FACE, TYP
0", TYP
T.O. 3H UNIT STEM WALL
EL (SEE LC SHEETS)
T.O. 5H UNIT STEM WALL
GRADE
SEE CIVIL
#5 CONT
STD 90 DEG
HOOK, TYP
GRADE
SEE CIVIL
#4 @ 18" OC,
EACH WAY
NOTE:
1. SEE ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION ON
RISE, RUN, FINISH AND EMBED ITEMS.
(2) #4 CONT
#4 NOSING
BAR, TYP
1/2" TOOLED EDGE OR
CAST IRON NOSING
C L R
1' - 0"
1" TYP
TYP
1" CLR
T Y
P
C
L R
M
IN
" S
L A
B
" C
LR
SLAB ON GRADE
SEE LC SHEETS
#4 @ 24" OC,
EACH WAY
6' - 6"
#4 CONT
VERTICAL:
#5 @ 12" OC
#5 @ 12" OC
DOWELS TO MATCH
VERTICAL BAR SIZE
AND SPACING. TYP
VERTICAL:
#6 @ 12" OC
1' - 3"
/2
2" CLR
C L R
#6 @ 12" OC
HORIZONTAL:
#5 @ 12" OC,
EACH FACE
3' - 0"
#5 @ 12" OC
ROUGHEN JOINT
TO 1/4" AMPLITUDE
HORIZONTAL:
#5 @ 12" OC
#4 @ 12" OC
WITH STD HOOK 1' - 11"
GRADE
SEE CIVIL
VERTICAL:
#5 @ 12" OC
C L A
S S
B S
P L
IC
E
0" TYP
(MIN)
1' - 0"
UNDERDRAIN
SEE 2/LD109
BACKFILL BEHIND
WALL WITH ON
SITE COMPACTED
FILL SEE SPEC
1' - 0" WIDE MIN FREE
DRAINING GRAVEL
SEE SPEC FOR
GRADATION
EL (SEE LC SHEETS)
T.O. STEM WALL
3"
NOTE 1
3"
EL (SEE LC SHEETS)
T.O. STEM WALL
EL (SEE PLAN ON SS102)
T.O. LEDGE
NO LEDGE AT SIM
EL (SEE PLAN ON SS102)
T.O. PIER
HORIZONTAL: #4 @ 12" OC,
EACH FACE. PROVIDE
CORNER BARS MATCHING
BAR SIZE AND SPACING. BARS
ARE TIES AS INDICATED ON
PLANS ON SS102
VERTICAL:
#6 @ 12" OC, EACH FACE
SEE SECTIONS ON
THIS SHEET FOR BARS
DOWELS: MATCH VERTICAL
BAR SIZE AND SPACING
SEE SECTIONS ON THIS
SHEET FOR BARS
NOTE:
1. DIMENSION VARIES - SEE LC SHEETS.
MATCH VERTICAL AND
HORIZONTAL BAR SIZE
AND SPACING
3"
EL (SEE LC SHEETS)
T.O. LEDGE
NOTE:
1. CONNECT CONCRETE WALL OR STAIRS WITH 2'-6" x 2'-6"
DOWELS THAT MATCH HORIZONTAL BAR SIZE AND SPACING
OR EMBED 2'-6" LONG DOWELS 4" WITH EPOXY ADHESIVE.
2' - 0"
9"
EL (SEE LC SHEETS)
T.O. WALL
3"
CONCRETE
WALL OR STAIRS
NOTE 1
(3) #4 CONT
#4 @ 24" OC
TOP OF FOOTING TO BE A
MINIMUM OF 2'-0" BELOW
FINISH GRADE
DOWELS - MATCH VERTICAL
BAR SIZE AND SPACING
HORIZONTAL:
#4 @ 12" OC, EACH FACE
VERTICAL:
#6 @ 12" OC, EACH FACE
M
IN
EL (SEE LC SHEETS)
T.O. FOOTING
4' - 0"
3" 9"
HORIZONTAL:
#5 @ 12" OC
SITE PAVING - SEE CIVIL
SLEEVE AND RAILING - SEE
LANDSCAPE DRAWINGS. SET
RAILING WITH FLOWABLE
NON-SHRINK GROUT. SEE
SPECS FOR MORE
INFORMATION
PROVIDE (3) #4
CONTINUOUS AT TOP
#5 @ 12" OC
VERTICAL:
#5 @ 12" OC,
1' - 0"
#5 @ 12" OC
#5 @ 12" OC
CLR
2"
GRADE
SEE CIVIL
3"
SEE LC SHEETS FOR
LEDGE INFORMATION
VENEER - SEE
LC SHEETS
1' - 0"
HORIZONTAL:
#5 @ 12" OC
SLAB ON GRADE
SEE LC SHEETS
SLEEVE AND RAILING - SEE
LANDSCAPE DRAWINGS. SET
RAILING WITH FLOWABLE
NON-SHRINK GROUT. SEE
SPECS FOR MORE
INFORMATION
PROVIDE (3) #4
CONTINUOUS AT TOP
VERTICAL:
#4 @ 12" OC,
M
IN
1' - 0"
GRADE
SEE CIVIL
SEE LC SHEETS FOR
LEDGE INFORMATION 3"
VENEER - SEE
LC SHEETS
FOOTING
REINFORCING
MATCH FOOTING
REINFORCING
FOUNDATION
WALL
EL (SEE PLAN)
T.O. FOOTING
EL (SEE PLAN)
T.O. FOOTING
GENERAL NOTES
LAP SPLICE PER
THICKNESS
SAME AS FOOTING
3" CLR, TYP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BIDDING DOCUMENTSOffice of Design and Construction
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Mechanical, Electrical, Technology & Structural
Engineering:
IMEG, Inc.
623 26th Avenue
Rock Island, IL 61201
(309) 788-0673
Wade Ross
BIDDING DOCUMENTS
Irrigation Engineering:
EC Design Group, Ltd
400 5th St.
West Des Moines, IA 50265
(515)225-6365
Erik Christiansen
Cost Estimating, Scheduling, Value Engineering:
Leland Saylor Associates
1777 Oakland Blvd #103
Walnut Creek, CA 94596
(310)207-6900
Tommy Vest
Geotechnical Engineering:
Kokua Geotech, LLC.
94-974 Pakela St. Suite 109
Waipahu, HI 96797
(808)397-6974
Tim (Xiaobin) Lin
Project Director
BASE BID
Dwg of
C R e v it L o c a l F ile s \S
.1
P
A C
IF
IC
N A
T
IO
N A
L C
E M
E T
E R
Y C
M e h u lk u m a r.
V .N a k ra n i.
rv t
/1
/2
:0
:5
P
M
STRUCTURAL SITE PLANS AND
SECTIONS
HONOLULU, HAWAII
899CM3030
JULY 15, 2021 JOHGOE PRIPAN
15785
NMCP
GRAVESITE EXPANSION AND
CEMETERY IMPROVEMENTS
SS101
3/4" = 1'-0"
COLUMBARIUM END SECTION
3/4" = 1'-0"
SINGLE SIDED
COLUMBARIUM SECTION
1" = 1'-0"
OFFSET DOUBLE SIDED COLUMBARNIUM SECTION
3/4" = 1'-0"
TYPICAL STAIR ON GRADE DETAIL
3/4" = 1'-0"
SINGLE SIDED
COLUMBARIUM RETAINING WALL
1 3/4" = 1'-0"
COLUMBARIUM MIDDLE SECTION
3/4" = 1'-0"
FOUNDATION SECTION
7 3/4" = 1'-0"
FOUNDATION SECTION
3/4" = 1'-0"
FOUNDATION SECTION
9 3/4" = 1'-0"
TYPICAL STEPPED FOOTING DETAIL
104 138Revisions: Date:
3" NOTE 2 3"
N O
T E
T Y
P
NOTE 2 NOTE 23' - 10"
EQ EQ
EL (SEE LC SHEETS)
T.O. CONCRETE PIER
EL (SEE LC SHEETS)
T.O. LEDGE
EL (SEE LC SHEETS)
T.O. LEDGE
EL (SEE LC SHEETS)
T.O. 5H UNIT STEM WALL
EL (SEE LC SHEETS)
T.O. FOOTING
NOTES:
1. COORDINATE WALL LENGTH WITH LC SHEETS.
2. DIMENSION VARIES - SEE LC SHEETS.
SS101
SS101
PIER IS ADJACENT TO STAIRS OR
PERPENDICULAR WALL. SEE 6 OR
7/SS101 FOR DOWELS TO WALL
SEE 3/SS101 FOR
REINFORCEMENT.
EL ( +2' - 9" )
T.O. 3H UNIT STEM WALL
ABOVE 5H UNIT
STEM WALL
EL (SEE LC SHEETS)
T.O. CONCRETE PIER
EL (SEE LC SHEETS)
T.O. LEDGE
EL (SEE LC SHEETS)
T.O. LEDGE
EL (SEE LC SHEETS)
T.O. STEM WALL
EL (SEE LC SHEETS)
T.O. FOOTING
NOTES:
1. COORDINATE WALL LENGTH WITH LC SHEETS.
2. PLAN IS SIMILAR AT INTERMEDIATE PIERS.
3. DIMENSION VARIES - SEE LC SHEETS.
3" NOTE 3 3"
N O
T E
T Y
P
EQ EQ
SS101
SS101
3" 1' - 9" NOTE 3
FRONT OF COLUMBARIUM
AT LOCATIONS WHERE PIER IS
ADJACENT TO STAIRS OR
PERPENDICULAR WALL, SEE 6 OR
7/SS101 FOR DOWELS TO WALL.
SEE 3/SS101 FOR
REINFORCEMENT.
E Q
E Q
3"
3"
E Q
2' - 1"
1' - 9"
E Q
SEE 4/SS101 FOR
REINFORCEMENT.
CROSS TIES:
#4 @ 12" OC
EL (SEE LC SHEETS)
T.O. 5H UNIT STEM WALL
EL (SEE LC SHEETS)
T.O. LEDGE
EL (SEE LC SHEETS)
T.O. FOOTING
EL (SEE LC SHEETS)
T.O. CONCRETE PIER
EL ( +2' - 9" )
T.O. 3H UNIT STEM WALL
ABOVE 5H UNIT STEM WALL
EL (SEE LC SHEETS)
T.O. LEDGE
SS101
SS101
SS101
SIM
EL (SEE LC SHEETS)
T.O. 3H UNIT STEM WALL
EL (SEE LC SHEETS)
T.O. LEDGE
EL (SEE LC SHEETS)
T.O. FOOTING
EL (SEE LC SHEETS)
T.O. CONCRETE PIER
1' - 9"
3…