S06 - HazMat Information - WB.pdf

PDF 7 MB Posted

Attached to
Z1QA--Facility Renovations at the Woodlawn and Bath National Cemeteries.
Solicitation number
36c78620b0009
Issued by

About this file

This solicitation is for facility renovations, improvements, and repairs at the Woodlawn and Bath National Cemeteries. The work includes renovations to the administration buildings at both cemeteries including lighting, power, and mechanical system upgrades. The solicitation is issued by the Department of Veterans Affairs National Cemetery Administration. Responses are due by early June 2020, with award anticipated by late May. Pricing will be fixed-price. The solicitation is unrestricted with no set-asides indicated. Appendices include inspection reports, mechanical demolition plans, lighting/power demolition and new work plans, and plumbing demolition plans to further outline the required scope of work.

View the file

Other files

File Type Posted
S06 - A0003 - Amendment.docx DOCX document
S06 - Amendment 0002.docx DOCX document
A2 - Pre-Bid Walk-Thru Sign In Sheet.PDF PDF
A1 - 803IC3015 Bid Dwgs Bath Bk02A.pdf PDF
S05 - Amendment 0001.docx DOCX document
S02 - 824IC3005 Bid Dwgs Woodlawn Bk09.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk05.pdf PDF
S02 - 824IC3005 - Geotechnical Report - Woodlawn.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk02.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk12.pdf PDF
S02 - Scope of Work Final - Woodlawn-Bath.pdf PDF
S02 - 803IC3015 Bid Specs Bath Bk.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk03.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk01.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk13.pdf PDF
ATTACHMENT 05 - Cost Estimate Worksheet - WB.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk03.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk06.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk07.pdf PDF
P07 - WD - NY20200005 - Woodlawn NC.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk10.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk05.pdf PDF
S02 - 36C786-20-B-0009 - Solicitation.pdf PDF
P07 - WD - NY20200048 - Bath NC.pdf PDF
S02 - 803IC3015 - Geotechnical Report - Bath.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk01.pdf PDF
S02 - 824IC3005 Bid Specs Woodlawn Bk.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk04.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk02.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk07.pdf PDF
S02 - 803IC3015 Bid Dwgs Bath Bk06.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk08.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk11.pdf PDF
S02 - 824IC3005 Bid Dwgs Woodlawn Bk04.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A MENDMENT 1

7820 B Wormans Mill Road, Suite 162, Frederick, Maryland 21701 | 240-529-5406

WFS

Project:

Woodlawn (824IC3005) & Bath (813IC3015) National Cemeteries;

Facility Renovations

Affects Set: Final Construction Documents, 5/22/2020

Date: 8/20/2020

Bath & Woodlawn National Cemeteries, Bidding Q&A Question Response

After Review of the documents it has come to my attention that the refrigeration piping and Natural Gas piping required for the AHU’s in each facility is not shown on the drawings.

Please advise routing and sizing of the pipe required for each system respectively.

Currently with the piping not shown each mechanical contractor could route the piping differently and this creates differences in pricing that creates differences in scope and subsequent differences in pricing.

The gas line has been extended to AHU-1 for Woodlawn, as shown on revised PP-111 riser & floorplan. There is no gas piping for Bath.

For the refrigerant piping, it is not as customary to size and route the refrigerant piping. This is because the pipes are very small and short in length, and the specific pipe sizes are actually determined by the winning equipment manufacturer. Normally this is not something that shows up as a price difference between bidders.

Are pipes to be run in the attic space in both facilities or below the joists in the ceiling space?

Yes, run refrigerant pipes in attic and then drop down inside the wall adjacent pop out adjacent to the condensing unit. Gas pipe is in attic per revised PP-101.

Will the natural gas piping be required to have a secondary containment vent piping if it is run in the attic space?

No.

Is the provided ½” thick insulation on the refrigeration line sets acceptable or does additional insulation need to be provided?

Refrigerant insulation needs to have min R 3.6 insulation per note 15, M-001. Therefore, thickness is not specifically an issue, but it must meet the R value.

Woodlawn National Cemetery, Drawing Revisions

5 AE-102 Deleted Note, potential asbestos containing material (ACM)/pipe wrap in Administration Building crawl space. Subsequent inspection found no ACM. See attachment.

6 ED-101 Deleted Note, potential ACM, as above.

7 EP-101 Deleted Note, potential ACM, as above.

8 ET-101 Deleted Note, potential ACM, as above.

9 MD-101 Deleted Note, potential ACM, as above.

10 PD-101 Deleted Note, potential ACM, as above.

11 PP-111 Deleted Note, potential ACM, as above.

Modified floorplan and riser diagram to indicate attic gas connection of for AHU-1

Attachment: Asbestos Consulting Services-Administration Building Crawlspace 6-12-2020.pdf

T errac on C ons ul tants -N Y, Inc . 15 M arw ay C i rc le R oc hes ter , N ew York 14624

P [ 585] 247 3471 ter rac on. c om

June 12, 2020

Walker Federal Services, LLC

162 B Wormans Mill Road, Suite 7820B

Frederick, Maryland 21701

Attn: Robert Moreno

Principal

P: (240) 529-5406

E: rmoreno@wfsfederal.com

Re: Asbestos Consulting Services

Woodlawn National Cemetery

Administration Building

Crawlspace

1825 Davis Street

Elmira, New York 14901

Terracon Project No. J5207035

Dear Mr. Moreno:

On June 4, 2020, Terracon representative, Mr. Tony Hill, visited the above-referenced site to visually inspect the crawlspace and to collect samples from suspect pipe insulation to determine if they contain asbestos by laboratory analysis prior to their removal and/or replacement. The inspection was conducted pursuant to Terracon’s Proposal number PJ5207035.

REGULATORY REVIEW

Federal

United States Environmental Protection Agency (USEPA) regulation 40 CFR 61.140, National

Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated asbestos-containing building materials be identified, classified and quantified prior to planned disturbances or demolition activities. The Occupational Safety and Health Administration (OSHA) regulates asbestos under OSHA 29 CFR 1910.1101. The

USEPA regulates asbestos use, removal and disposal, while OSHA regulates asbestos exposure to workers.

NESHAP requires that commercial and public buildings be thoroughly inspected for the presence of asbestos-containing materials (ACM) prior to conducting renovation or demolition activities.

Asbestos Consulting Services Woodlawn Nation Cemetery Administration Building Crawlspace

The reconnaissance must assess whether ACM is considered friable or non-friable. Friable

ACM is defined as material containing more than 1% asbestos that, when dry, can be crumbled, pulverized or reduced to powder by hand pressure (i.e. regulated asbestos-containing materials

{RACM}). The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 1 f/cc for a 30-minute excursion limit and 0.1 f/cc for an 8-hour permissible exposure limit. The OSHA standard classifies construction and maintenance activities, which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.

According to EPA and OSHA regulations, an ACM is considered any material or product containing more than one percent (>1%) asbestos. However, OSHA also considers materials that are trace or less than 1% asbestos to be materials of concern. A material of concern is a material, that when disturbed, may emit fiber concentrations greater than 0.1 f/cc.

State / Local

In the State of New York, asbestos abatement activities are regulated by the New York State

Department of Labor (NYSDOL) under the Part 56 of Title 12 of the Official Compilation of

Codes, Rules and Regulations of the State of New York (12 NYCRR Part 56). New York regulations require that any asbestos-related activity conducted in the state be performed by personnel licensed by NYSDOL. NYSDOL 12 NYCRR has instituted nine different certifications for asbestos related activities that include: Handler; Allied Trades; Air Sampling Technician;

Inspector; Operations and Maintenance; Supervisor; Project Designer; Project Monitor; and

Management Planner. The owner or operator must provide the NYSDOL with written notification of planned removal activities at least 10 working days prior to the commencement of a large project (greater than or equal to 160 square feet or 260 linear feet). Removal of ACM must be conducted by a State of New York certified asbestos abatement contractor.

NYSDOL enforces the federal OSHA standard referenced-above.

INSPECTION ACTIVITIES

The inspection was conducted by Mr. Tony Hill, a New York state certified asbestos building inspector (Inspector Certification No. 06-02018). A copy of Mr. Hill’s asbestos inspector certificate is attached as Appendix A. The inspection was conducted in general accordance with the protocols established by EPA regulation 40 CFR 763, the Asbestos Hazard Emergency

Response Act (AHERA).

Visual Assessment

The inspection activities were initiated with visual observation of the accessible interior areas of the crawlspace proposed for renovation to identify homogeneous areas of suspect ACM on the domestic hot and cold water lines. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of

Asbestos Consulting Services Woodlawn Nation Cemetery Administration Building Crawlspace application and are individual to each building surveyed.

Physical Assessment

A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material, which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

Sample Analysis

Bulk samples were not collected during this inspection. Mr. Hill observed all of the pipe insulation in the crawlspace to be insulated with fiberglass which not a suspect ACM.

RECOMMENDATIONS

Based on inspection results, in regard to the hot and cold domestic water piping observed in the crawlspace of the Administration Building, no further sampling or asbestos abatement activities are required for the removal and replacement of the crawlspace domestic hot and cold water piping.

It should be noted that suspect materials, other than those identified during our recent site visit, may exist within the subject building. Should suspect materials other than that which was identified during our recent site visit be uncovered during the renovation process, those materials should be assumed asbestos-containing until sampling and analysis can confirm or refute asbestos-content.

CLOSING

We hope this report is responsive to your needs. Should you have any questions regarding this report, please contact us at (585) 247-3471 or Tony.Hill@Terracon.com.

Sincerely, TERRACON-NY

Tony Hill

Project Scientist

Attachments:

Appendix A – Inspector’s Certification

APPENDIX A

INSPECTOR’S CERTIFICATION

New York State – Department of Labor Division of Safety and Health License and Certificate Unit State Campus, Building 12

Albany, NY 12240

ASBESTOS HANDLING LICENSE

Terracon Consultants - NY, Inc.

Suite 2B 15 Marway Circle

Rochester, NY 14624

FILE NUMBER: 20-216863

LICENSE NUMBER: 216863

LICENSE CLASS: RESTRICTED

DATE OF ISSUE: 05/27/2020

EXPIRATION DATE: 05/31/2021

Duly Authorized Representative – Charles Guzzetta:

This license has been issued in accordance with applicable provisions of Article 30 of the Labor Law of New York State and of the New York State Codes, Rules and Regulations (12 NYCRR Part 56). It is subject to suspension or revocation for a (1) serious violation of state, federal or local laws with regard to the conduct of an asbestos project, or (2) demonstrated lack of responsibility in the conduct of any job involving asbestos or asbestos material.

This license is valid only for the contractor named above and this license or a photocopy must be prominently displayed at the asbestos project worksite. This license verifies that all persons employed by the licensee on an asbestos project in New York State have been issued an Asbestos Certificate, appropriate for the type of work they perform, by the New York State Department of Labor.

Eileen M. Franko, Director SH 432 (8/12) For the Commissioner of Labor

DS

DS

DS

DS

7:

PI

TC

H

7:12 PITCH

7:

PI

TC

H

7:12 PITCH

7:12 PITCH

7:

PI

TC

H

3'-0"

3'- 0"

UNEXCAVATED

EXISTING ACCESS

DOOR IN FLOOR

VENT VENT

VENT

VENTVENTVENT

VENT

VENT

VENT

VENT

LEGEND

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2020, Walker Federal Services, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

803IC3005

IK; FW FW; CL

May 22, 2020

FINAL CONSTRUCTION DOCUMENTS

Amendment 1 8/20/20201

1. REPLACE FLASHING AROUND ALL ROOF PENETRATIONS AND

ROOF BOOTS. ALL FLASHING TO BE MINIMUM 16 OZ. COPPER

AT EXPOSED LOCATIONS AND 10 OZ. MINIMUM AT

CONCEALED LOCATIONS. REFER TO SPECIFICATIONS FOR

DETAILS.

2. VERIFY ALL DIMENSIONS IN FIELD PRIOR TO CONSTRUCTION.

NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO

PROCEEDING WITH THE WORK.

3. DO NOT SCALE DRAWINGS.

4. ALL DIMENSIONS ARE GIVEN TO FINISHED WALL SURFACES

AND SHALL BE CONSIDERED AS CLEAR OPENINGS UNLESS

NOTED OTHERWISE.

5. PREPARE ALL SUBSURFACES PROPERLY BEFORE APPLICATION

OF FINISHES. CONTRACTOR SHALL ASSUME RESPONSIBILITY

FOR SUBSTRATE CONDITIONS WHERE FINISHES ARE APPLIED.

6.

ADMINISTRATION BUILDING

ROOF PLAN AND

CRAWL SPACE PLAN

AE-102

0 2' 4' 8' 12'

1 ROOF PLAN

1/4" = 1'-0"

'ENVIROSLATE' BY 'ENVIROSHAKE' QUALITY ENGINEERED

ROOFING AND UNDERLAYMENT OR EQUAL AS APPROVED BY

COR.

COPPER STANDING SEAM METAL ROOF TO MATCH EXISTING

PROFILE.

5" HALF ROUND 20 OZ. COPPER GUTTERS AND 3"X4" FLUTED

COPPER DOWNSPOUTS MATCHING GUTTER.

REFER TO NOTE 6 BELOW. REMOVE CAP & INSULATION AT

ALL EXISTING VENTS, TYP. TO RESTORE EXISTING VENTS TO

WORKING CONDITION. CAREFULLY CUT INSULATION

AROUND VENTS AND RE-SEAL AROUND NEW HOLE. CLEAN &

REFURBISH EXISTING VENT AND/OR REPLACE AS NECESSARY.

PROTECT ADJACENT BRICKS FROM DAMAGE.

GRAVESITE LOCATOR

COPPER SNOW GUARDS, LAYOUT AND INSTALL PER

MANUFACTURER'S WRITTEN INSTRUCTIONS APPROPRIATE

FOR ROOF TYPE, PITCH, LOADS AND APPLICABLE BUILDING

CODES. REFER TO SPECIFICATIONS FOR DETAILS.

RIDGE VENT

EXISTING BRICK

CHIMNEY AND VENTS

EXISTING GABLE

VENT

EXISTING

GABLE VENT

2 CRAWL SPACE PLAN

1/4" = 1'-0"

04 04

NOTES

07 07

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

DS

DS

DS

RA

M

P

DN

DN

DN

DN

LOUNGE

109 CLOSET

107A

PORCH

109B

ENT. PORCH

104B

CLOSET

102A

CLOSET

110A

CLOSET

109A

CLOSET

108A

HALL

OFFICE

OFFICE

RESTROOM

OFFICE

LOBBY

RESTROOM

UTILITY RM

KITCHEN

K-12185FairfaxFaucetsBrass

S

S S

F L

F L

S

DS

DS

DS

DS

DS

RA

M

P

DN

DN

DN

DN

LOUNGE

109 CLOSET

107A

PORCH

109B

ENT. PORCH

104B

CLOSET

102A

CLOSET

110A

CLOSET

109A

CLOSET

108A

HALL

OFFICE

OFFICE

RESTROOM

OFFICE

LOBBY

RESTROOM

UTILITY RM

KITCHEN

K-12185FairfaxFaucetsBrass

AB

GFI

WP

GFI

WP

GFI

AB

GFI

EXISTING PANEL

AB

S S

SaSb

S

S

1. REMOVE ALL EXISTING ELECTRICAL CONDUIT AND

DEVICES FROM CRAWL SPACE.

2. PATCH AND REPAIR ALL EXISTING PENETRATIONS

FROM THE CRAWL SPACE AFTER DEMOLITION IS

COMPLETE.

DEMOLITION HATCH

EXISTING CEILING FAN

EXISTING LIGHT FIXTURE

EXISTING LIGHT FIXTURE

EXISTING LIGHT FIXTURE

EXISTING LIGHT FIXTURE

EXISTING EXHAUST FAN/LIGHT FIXTUREF

L

EXISTING EXIST SIGN

EXISTING LIGHT FIXTURE

EXISTING LIGHT SWITCHS

EXISTING LIGHT SWITCHS 2

EXISTING LIGHT SWITCHSa

Sb EXISTING LIGHT SWITCH

EXISTING EMERGENCY LIGHT FIXTURE

EXISTING DUPLEX RECEPTACLE

EXISTING ABOVE COUNTER GROUND FAULT

INTERRUPTER DUPLEX RECEPTACLE

AB

GFI

EXISTING WEATHERPROOF GROUND FAULT

INTERRUPTER DUPLEX RECEPTACLE

WP

GFI

EXISTING SPECIAL PURPOSE RECEPTACLE

EXISTING TELECOMMUNICATION DATA DEVICE

EXISTING TELECOMMUNICATION TELEPHONE DEVICE

EXISTING PANELBOARD

LEGEND

NOTES

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

DRAWING NO.

Dwg. Of

© COPYRIGHT 2019, Walker Federal Serivces, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

DRAWING NO.

Dwg. Of

N C A

ATIONAL

EMETERY

DMINISTRATION

N C A

ATIONAL

EMETERY

DMINISTRATION

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

803IC3005

GGG BLP

May 22, 2020

FINAL CONSTRUCTION DOCUMENTS

Amendment 1 8/20/20201

0 2' 4' 8' 12'

1 DEMOLITION FLOOR PLAN - LIGHTING

1/4" = 1'-0" 2 DEMOLITION FLOOR PLAN - POWER

1/4" = 1'-0"

ADMINISTRATION BUILDING

LIGHTING & POWER

DEMOLITION PLANS

ED-101

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

S

DS

DS

DS

REF

K-5016-ETDEXTERC_URINALSVITREOUS CHINA

K-310-4M FINAL TRADITIONAL FAUCET BRASS

LOUNGE

109 CLOSET

107A

PORCH

109B

ENT. PORCH

104B

CLOSET

102A

IT CLOSET

105A

CLOSET

110A

CLOSET

109A

CLOSET

108A

HALL

OFFICE

OFFICE

RESTROOM

OFFICE

LOBBY

RESTROOM

UTILITY RM

KITCHEN

CLOSET

104A

BrassFaucetsFairfaxK-12185

K-3407WELLWORTH LITE 10"TOILET/TWO-PIECE/ELONGATEDVITREOUS CHINA14-15-

K-12185FairfaxFaucetsBrass

LOUNGE

109 CLOSET

107A

PORCH

109B

ENT. PORCH

104B

CLOSET

102A

IT CLOSET

105A

CLOSET

110A

CLOSET

109A

CLOSET

108A

HALL

OFFICE

OFFICE

RESTROOM

OFFICE

LOBBY

RESTROOM

UTILITY RM

KITCHEN

CLOSET

104A

K-12185FairfaxFaucetsBrass

S OS S OS

S O

SS3

S3

S 3

S3

S 3

S O

S

S3

S3

S3

OS

OS

OS

OS

S

DS

DS

DS

DS

DS

REF

K-5016-ET DEXTER C_URINALS VITREOUS CHINA

K-310-4MFINAL TRADITIONAL FAUCETBRASS

LOUNGE

109 CLOSET

107A

PORCH

109B

ENT. PORCH

104B

CLOSET

102A

IT CLOSET

105A

CLOSET

110A

CLOSET

109A

CLOSET

108A

HALL

OFFICE

OFFICE

RESTROOM

OFFICE

LOBBY

RESTROOM

UTILITY RM

KITCHEN

CLOSET

104A

BrassFaucetsFairfaxK-12185

K-3407WELLWORTH LITE 10" TOILET/TWO-PIECE/ELONGATEDVITREOUS CHINA14-15-

K-12185FairfaxFaucetsBrass

AB

GFI

AB

GFI

AB

GFI

AB

GFI

M

M

SM

SM

LOCATED IN

ATTIC ABOVE

CU-1

D

D

E

AA

A A

AAA

A A

B

B

C

C

L L

LL

C

D

D

S

EF-1

AHU-1

EF-1

WH-1

EX1

EX1

EX1

EX1EM

EM

EM

EM

EM

C C

C

TV

PANEL 'B'

S

S

S

S

SC

1. RUN ALL ELECTRICAL CONDUIT AND WIRING THROUGH ATTIC

SPACE. DO NOT USE CRAWL SPACE. EXISTING PENETRATIONS

FROM THE CRAWL SPACE TO BE REPAIRED OR PATCHED AS

PART OF THIS PROJECT.

PROVIDE DEDICATED OUTLET FOR RELOCATED

COPIER.

TV

TV

KEY NOTES

NEW LIGHT FIXTURE

NEW LIGHT FIXTURE

NEW LIGHT FIXTURE

NEW LIGHT FIXTURE

NEW EXIT SIGN

NEW EMERGENCY LIGHT FIXTURE

NEW CEILING MOUNTED OCCUPANCY

SENSOROS

NEW SINGLE POLE SWITCHS

NEW 3-WAY SWITCHS3

NEW WALL MOUNTED OCCUPANCY

SENSOR SWITCHS OS

NEW PANELBOARD

NEW DISCONNECT SWITCH

NEW MOTORM

NEW CONNECTION TO EQUIPMENT

NEW SINGLE PHASE MANUAL MOTOR

SWITCHSM

NEW DUPLEX RECEPTACLE

NEW ABOVE COUNTER GROUND FAULT

INTERRUPTER DUPLEX RECEPTACLE

AB

GFI

NEW DUPLEX RECEPTACLE FOR DIGITAL

DISPLAY

NEW DOUBLE DUPLEX RECEPTACLE

TV

NEW SPECIAL PURPOSE RECEPTACLE

M NEW UTILITY METER

J

J

F S

F S F S F S

F S

F S

F S NEW FIRE ALARM SYSTEM SMOKE

DETECTOR - PHOTOELECTRIC TYPE

B-1

B-2

B-3

B-4

B-5

B-6

B-7

B-8

B-9

B-10

B-11

B-12

B-13

B-14

B-18

B-16

B-15

M

SM

EF-2

B-17

B-19,21

HOMERUN TO PANELBOARD ARROWS

INDICATE NUMBER OF CIRCUITS IN CONDUIT

(3#12 FOR EACH CIRCUIT-3/4"C UNLESS

NOTED OTHERWISE)

SWITCH LEG

SWITCHED CIRCUIT

BRANCH CIRCUIT

B-20

S3

S 3

B-22

B-23

B-23

B-23

B-23

B-23

B-23

B-24

B-25,27

P

B-23

B-26

FACP FIRE ALARM CONTROL PANEL

S

S

S S S

SS

S S S

B

B-23

S

S

R

R

Q Q Q

V

A

ST

T

AB

EXHAUST HOOD

B-28

MICROWAVE

EM

EM

FIREPLACE

B-32

B-29

T

B-26 B-26

B-26

B-26

B-26

B-31

AB

B-14

EM

HEAT TRACE

B-34

LEGEND

NOTES

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

DRAWING NO.

Dwg. Of

© COPYRIGHT 2019, Walker Federal Serivces, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

DRAWING NO.

Dwg. Of

N C A

ATIONAL

EMETERY

DMINISTRATION

N C A

ATIONAL

EMETERY

DMINISTRATION

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

803IC3005

GGG BLP

May 22, 2020

FINAL CONSTRUCTION DOCUMENTS

Amendment 1 8/20/20201

0 2' 4' 8' 12'

1 NEW WORK FLOOR PLAN - LIGHTING

1/4" = 1'-0" 2 NEW WORK FLOOR PLAN - POWER

1/4" = 1'-0"

ADMINISTRATION BUILDING

LIGHTING & POWER PLANS

EP-101

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

S

DS

DS

DS

RA

M

P

DN

DN

KITCHEN

UTILITY RM

RESTROOM

LOBBY

OFFICE

RESTROOM

OFFICE

OFFICE

HALL

CLOSET

108A

CLOSET

109A

CLOSET

110A

CLOSET

102A

ENT. PORCH

104B

PORCH

109B

DN

DN

CLOSET

107A

LOUNGE

1 ADMINISTRATION BUILDING FLOOR DEMO PLAN

1/4" = 1'-0"

ADMINISTRATION BUILDING

TELECOM DEMOLITION PLAN

ET-101

GENERAL NOTES

1. FOR TELECOMMUNICATION SYMBOLS, ABBREVIATIONS AND GENERAL NOTES, SEE

DRAWING ET-001.

2. FOR TELECOMMUNICATION NEW WORK PLANS, SEE DRAWING ET-201.

3. FOR TELECOMMUNICATION DETAILS, SEE DRAWING ET-301.

KEY NOTES

DISCONNECT AND REMOVE EXISTING TELEPHONE AND DATA OUTLETS AS

INDICATED. DEMOLITION SHALL BE COMPLETE INCLUDING GANG BOX, COVER

PLATE AND PULLING WIRING BACK TO SOURCE AND DISPOSAL THEREOF.

DISCONNECT AND RELOCATE EXISTING VERIZON TELECOM MODEM AS SHOWN

ON DRAWING E-201.

PROTECT EXISTING DATA SIGNAL MODEM AND T-1 CABLE FOR RE-USE.

DISCONNECT AND REMOVE EXISTING INTEGRATED SERVICE ROUTER, ETHERNET

NETWORK SWITCH, CONNECTOR PORT, UPS AND ALL WIRING/CONNECTIONS

LOCATED IN IT CLOSET (105A).

FOR CONSTRUCTION SEQUENCE, SEE DRAWING ET-001.

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

FINAL CONSTRUCTION DOCUMENTS

N C A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg. Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2019, Walker Federal Serivces, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

824IC3005

HU UB

May 22, 2020

05/22/2020

Amendment 1 8/20/20201

0 2' 4' 8' 12'

DEMOLITION - TELEPHONE OUTLET

DEMOLITION - DATA OUTLET

DEMOLITION - TELEPHONE AND DATA OUTLET

LEGEND

(TYP.)

(TYP.)

TELECOM

EQUIPMENT

DATA/COMMUNICATION

EQUIPMENT 03

BrassFaucetsFairfaxK-12185

REF

K-5016-ETDEXTERC_URINALSVITREOUS CHINA

NOTES

1. NOT USED.

2. FOR EQUIPMENT SHOWN TO BE REMOVED, PATCH AND SEAL REMAINING WALLS,

FLOORS AND/OR ROOF WORK TO MAINTAIN THAT ELEMENT'S PREVIOUS

INTEGRITY. REFER TO ARCHITECTURAL DRAWINGS & SPECIFICATIONS FOR FURTHER

DEMOLITION REQUIREMENTS.

3. PERFORM ALL WORK ABOVE, BELOW, IMMEDIATELY ADJACENT TO

THEN-OCCUPIED SPACES OUTSIDE OF NORMAL BUSINESS HOURS UNLESS

OTHERWISE AUTHORIZED BY COR.

4. MAINTAIN EXISTING OR PROVIDE NEW UTILITIES, SYSTEMS, AND SERVICES TO

OCCUPIED SPACES AT ALL TIMES. NO OUTAGES ARE PERMITTED DURING NORMAL

BUSINESS HOURS. COORDINATE ALL OUTAGES DURING CHANGE-OVERS BETWEEN

BUILDING AND TEMPORARY SPACES WITH CEMETERY DIRECTOR NOT LESS THAN 7

DAYS IN ADVANCE.

LEGEND

01 REMOVE RADIATOR SYSTEM HEATING BOILER AND ALL ASSOCIATED PIPING AND

ACCESSORIES.

KITCHEN

UTILITY RM

RESTROOM

LOBBY

OFFICE

RESTROOM

OFFICE

OFFICE

LOUNGE

HALL

ENT. PORCH

104B

CLOSET

110A

CLOSET

108A

CLOSET

109A

CLOSET

107A

IT CLOSET

105A

CLOSET

102A

02 RETAIN PORTION OF FLUE 6" UPSTREAM OF CONNECTION TO BRICK CHIMNEY.

03 REMOVE ENTIRE HOT WATER RADIATOR SYSTEM, INCLUDING RADIATORS,

BELOW-FLOOR PIPING, VALVES, CONTROL WIRING, AND ACCESSORIES (AVERAGE HOT

WATER PIPE SIZE =1", PLUS INSULATION).

04 REMOVE FLUE FOR DOMESTIC WATER HEATER.

X

X

X

X

X

X

X

X

X

XX

X X

X

X

X

X

X

X

X

X X

X

X

X

X

X

X X

X

X

X

X

X

X

X X

X

X X

X

X X

X X

X

XXXXX XXX

XXXXX XXX

X

X

X

X

X

X

X X

X X

X X

X

X X

X X

X

X

X

XX

X

X

X

X

X

X

XXX

XX XX

X X X X

X X X X X

X

X

X

X

XX

XX

X X

X

XXXX XX

X X

X X

X X

X

X X

X X

X X

X X

X X

X

X

X

X

X

X X

X X

X X

X

X X

X X

X X

X X

X X

X

X

03 (TYP.)

03 (TYP.)

03(TYP.)

X

X

X

X

X

X06

05 EXISTING GABLE VENT IN ATTIC (WITH LOUVERS).

06 DEMOLISH ATTIC VENTILATION FAN.

07 REMOVE KITCHEN HOOD AND DUCT CONNECTION STUB. EXTERIOR DISCHARGE CAP

WILL STAY (TO BE RECONNECTED TO NEW HOOD).

X

X

X

X

X

08 REMOVE EXISTING FIREPLACE FLUE.

N

C

A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number

Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg.

Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

FINAL CONSTRUCTION DOCUMENTS - ISSUED FOR CONSTRUCTION

N

C

A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number

Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg.

Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2019, Walker Federal Serivces, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

824IC3005

TDF MLP

MAY 22, 2020

0 2 4 8 12

Amendment 1 8/20/20201

MD-101

ADMINISTRATION BUILDING

MECHANICAL

DEMOLITION PLANS

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text Y

AutoCAD SHX Text W

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text X

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text B.

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text U

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text No.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Y

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

05/22/2020

K-5016-ETDEXTERC_URINALSVITREOUS CHINA

NOTES

LEGEND

01 DEMOLISH DOMESTIC WH. PRESERVE GAS PIPING FOR NEW WH. DEMOLISH ALL HW

& CW DOWN STREAM PIPING.

1. NOT USED.

2. ALL BELOW-FLOOR PLUMBING PIPING ON THIS PLAN IS LOCATED IN THE

CRAWL SPACE AREA (APPROX. 36" HIGH) - EXCEPT FOR PIPING IN UTILITY

ROOM 102 AND MOST OF RESTROOM 103, WHICH IS BURIED IN

UNEXCAVATED GRADE.

3. REMOVE ALL EXISTING ABOVE FLOOR PLUMBING FIXTURES AND SANITARY

PIPING. CAP (SEAL TIGHT) ANY PIPE OPENING THAT IS NOT BEING REUSED FOR

NEW WORK.

4. CUT AND PLUG BELOW FLOOR SLAB ALL SANITARY AND VENT PIPING

PENETRATING SLAB.

5. ALL BELOW-FLOOR PLUMBING PIPING ON THIS PLAN IS LOCATED IN THE

CRAWL SPACE AREA (APPROX. 36" HIGH) - EXCEPT FOR PIPING IN UTILITY

ROOM 102 AND MOST OF REST ROOM 103, WHICH IS BURIED IN

UNEXCAVATED GRADE.

6. REMOVE ALL BELOW-SLAB CONCRETE THAT IS DEMOLISHED AND DISPOSE OF

LEGALLY OFF GOVERNMENT PROPERTY.

7. PERFORM ALL WORK ABOVE, BELOW, IMMEDIATELY ADJACENT TO

THEN-OCCUPIED SPACES OUTSIDE OF NORMAL BUSINESS HOURS UNLESS

OTHERWISE AUTHORIZED BY COR.

8. MAINTAIN EXISTING OR PROVIDE NEW UTILITIES, SYSTEMS, AND SERVICES TO

OCCUPIED SPACES AT ALL TIMES. NO OUTAGES ARE PERMITTED DURING

NORMAL BUSINESS HOURS. COORDINATE ALL OUTAGES DURING

CHANGE-OVERS BETWEEN BUILDING AND TEMPORARY SPACES WITH

CEMETERY DIRECTOR NOT LESS THAN 7 DAYS IN ADVANCE.

9. FOR EQUIPMENT SHOWN TO BE REMOVED, PATCH AND SEAL REMAINING

WALLS, FLOORS AND/OR ROOF WORK TO MAINTAIN THAT ELEMENT'S

PREVIOUS INTEGRITY. REFER TO ARCHITECTURAL DRAWING (AND SPECS) FOR

FURTHER DEMOLITION REQUIREMENTS (I.E. DOWELS, PSI, LEVELING MIX,

ETC.).

KITCHEN

UTILITY RM

102 RESTROOM

LOBBY

OFFICE

RESTROOM

OFFICE

OFFICE

LOUNGE

HALL

ENT. PORCH

104B

CLOSET

110A

CLOSET

108A

CLOSET

109A

CLOSET

107A

IT CLOSET

105A

CLOSET

102A

EX. 3" VTR

EX. 2" VTR

EX. 4" SAN

EX. 3" VTR

EX. 1" CWEX. 1.25" GAS

EX. 4" SAN

EX. 2" VTR

G

X X

X X

X X

X X

X

X

X X

X X

X

X X

X

X X X X

X X

X X

X X

X X

X X X X X X X X X X X X X X X X X X X

XX

X X X X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X X X X X

X X

X X

X

X X X X X X X X X X

X

X

XX

X

X X

X X

XX

(TYP.)

X

X X

X

(TYP.)

02 DEMOLISH HEATING SYSTEM BOILER & CAP ITS GAS CONNECTION.

03 DEMOLISH EXISTING HW & CW PIPING IN CRAWL SPACE.

04 EXISTING VENT PIPE IN ATTIC SPACE.

XX

X

XX

X X

05 THIS AREA (ALL OF UTILITY ROOM 102 AND MOST OF RESTROOM 103) IS SLAB ON GRADE.

HOWEVER, NO SANITARY SLAB DEMOLITION IS ANTICIPATED WITHIN THIS ZONE. THE

OTHER PIPE (GAS, WATER, VENT) IS SHOWN TO BE DEMOLISHED, BUT ALL OF THAT PIPE

EXISTS ABOVE THE SLAB (I.E. NO CUTTING REQUIRED TO REMOVE THE PIPE).

N

C

A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number

Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg.

Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

FINAL CONSTRUCTION DOCUMENTS - ISSUED FOR CONSTRUCTION

N

C

A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number

Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg.

Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2019, Walker Federal Serivces, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

824IC3005

TDF MLP

MAY 22, 2020

0 2 4 8 12

Amendment 1 8/20/20201

PD-101

ADMINISTRATION BUILDING

PLUMBING DEMOLITION PLANS

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text Y

AutoCAD SHX Text W

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text X

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text B.

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text U

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text No.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Y

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

K-5016-ETDEXTERC_URINALSVITREOUS CHINA

1 FLOOR PLAN - WATER & GAS

1/4" = 1'-0"

KITCHEN

UTILITY RM

102 RESTROOM

LOBBY

OFFICE

RESTROOM

OFFICE

OFFICE

LOUNGE

HALL

ENT. PORCH

104B

CLOSET

110A

CLOSET

108A

CLOSET

109A

CLOSET

107A

IT CLOSET

105A

CLOSET

102A

CLOSET

104A

2 DOMESTIC WATER RISER DIAGRAM

NO SCALE

1ST FLOOR

ROOF

1ST FLOOR

ROOF

3 NATURAL GAS RISER DIAGRAM

NO SCALE

1ST FLOOR1ST FLOOR

ROOF

EX. 1" CWEX. 1.25" GAS

G

LV-2 UR-2

WC-1

LV-1

WC-1

SK-1

WH

SK-2

GG

1"

1/2"

3/4"

3/4"

3/4"

WH

WH

1/2"

3/4"

3/4"

1"

3/4"3/4"1"

EX. 1" CW

1/2" 1" 1/2"1"1"1/2"

SK-2 SK-1

WC-1 WC-1

UR-2LV-1 LV-2

RANGE

75 MBH

M

EX. 1-1/4" G

G

G

G

G

G

3/4"

40 MBH

1.25"

3/4"

GAS SIZING CRITERIA:

A. GAS PIPING IS SCHEDULE 40 STEEL, EXCEPT FOR FINAL (~36") CONNECTION TO

APPLIANCES WHICH MAY BE CSST.

B. REFER TO APPLIANCE MANUFACTURER'S DATA FOR GAS SIZE RUNOUTS TO

INDIVIDUAL APPLIANCES AND CONNECTION REQUIREMENTS.

C. SIZING CRITERIA (LOW PRESSURE):

--SCHEDULE 40 STEEL

--0.5 INCHES W.C. PRESSURE LOSS

--30' LONGEST LENGTH

--250 CFH TOTAL LOAD

ROOF

G

3/4"

GAS

FIREPLACE

G

3/4"

35 MBH

1" PEX CW BURIED

UNDERGROUND TO TRAILER.

SEE DWG. PP-101 FOR

CONTINUATION.

CEILING CEILING CEILINGCEILING

NOTES

LEGEND

1. INSTALLATION OF NEW COLD WATER PIPE THAT WILL SERVE THE TEMPORARY TRAILER

PRECEDES DEMOLITION.

2. PERFORM ALL WORK ABOVE, BELOW, IMMEDIATELY ADJACENT TO THEN-OCCUPIED

SPACES OUTSIDE OF NORMAL BUSINESS HOURS UNLESS OTHERWISE AUTHORIZED BY

COR.

3. MAINTAIN EXISTING OR PROVIDE NEW UTILITIES, SYSTEMS, AND SERVICES TO

OCCUPIED SPACES AT ALL TIMES. NO OUTAGES ARE PERMITTED DURING NORMAL

BUSINESS HOURS. COORDINATE ALL OUTAGES DURING CHANGE-OVERS BETWEEN

BUILDING AND TEMPORARY SPACES WITH CEMETERY DIRECTOR NOT LESS THAN 7

DAYS IN ADVANCE.

INSTALL INDICATED PORTION OF WATER PIPE BEFORE THE TRAILER ARRIVES

ON SITE. COORDINATE TIME/DATE OF THIS WORK WITH COR. THE WATER

MAY NOT BE TURNED OFF FOR MORE THAN 3 HOURS TO PERFORM THE

INITIAL INSTALLATION OF THE NEW TEE AND VALVE. REMOVE VALVE AND

ALL COMPONENTS DOWNSTREAM WHEN TRAILER IS REMOVED & CAP TEE.

02 1" CW EXPRESS LINE IN ATTIC, DOWN TO CRAWL SPACE, FOR USE WITH

TEMPORARY TRAILER. AT THE END OF THE WORK, AFTER THE TRAILER HAS

BEEN REMOVED, DEMOLISH THIS PORTION OF THE CW PIPE (AND ALL POINTS

DOWNSTREAM WITHIN THE BUILDING).

1"

03 1" CW EXPRESS LINE IN CRAWL SPACE (INSTALL BE THE TRAILER ARRIVES, AND

REMOVE AFTER TRAILER IS REMOVED).

04 1" CW EXPRESS LINE TRANSITIONS IN CRAWL SPACE TO A PEX PIPE, AND TURNS

DOWN BELOW SOIL, SUCH THAT THE PIPE IS AT LEAST 48" BELOW GRADE

(BELOW GRADE AS MEASURED FROM THE EXTERIOR OF THE BUILDING) TO BE

BELOW THE FROST LINE. INSTALL CW LINE BEFORE TRAILER ARRIVES AND

REMOVE THE COPPER-PORTION OF THE 1" EXPRESS LINE WHEN TRAILER IS

REMOVED. CAP AND ABANDON PORTION OF PEX THAT IS BELOW THE SOIL (SEE

NOTES ON PP-101). BEFORE THE LINE IS ABANDONED, DEMOLISH, AT A

MINIMUM, THE TOP 24" OF THE VERTICAL PIPE AND THEN FILL OVER WITH SOIL

AND RE-SEAL CRAWL SPACE FLOOR.

C R

A W

L

S P

A C

E

GRADE

TEMPORARY

TRAILER

1"

1" PEX CW BURIED

UNDERGROUND TO TRAILER.

SEE DWG. PP-101 FOR

CONTINUATION.

05 05

05 PROVIDE INSULATION AND HEAT TRACE FOR THE CW AND HW PIPING IN THE

ATTIC SPACE. CALCULATE THE PRECISE MEASUREMENT OF LENGTH AND SIZE OF

INSULATION AND HEAT TRACE REQUIRED, PER THE ACTUAL INSTALLED

CONDITION. FOR PRICING PURPOSES, THE INSULATION/HEAT TRACE WILL BE

ESTIMATED AT 150 LINEAL FEET OF 3/4" PIPE, USING A HEAT TRACE OF 6

WATTS/FT (I.E. 900 WATTS - 120V/1 - SEE ELECTRICAL DRAWINGS FOR

CIRCUITING DETAILS).

06 THIS AREA (ALL OF UTILITY ROOM 102 AND MOST OF RESTROOM 103) IS SLAB ON

GRADE. ALL SANITARY WORK IN THIS AREA INVOLVES SLAB-CUTTING.

07 PROVIDE 3/4" GAS TO NEW GAS FIREPLACE. FIREPLACE MODEL IS

SUPREME-I30-IFT OR APPROVED EQUAL.

AHU

3/4" G

AHU

100 MBH

3/4"3/4"

N

C

A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number

Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg.

Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

FINAL CONSTRUCTION DOCUMENTS - ISSUED FOR CONSTRUCTION

N

C

A

ATIONAL

EMETERY

DMINISTRATION

Revisions Date

Drawing Title

Approved:

Approved:

Project Title

Building Number

Checked Drawn

Location

Date

Project No.

DRAWING NO.

Dwg.

Of

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A B

C D

E F

A B

C D

E F

© COPYRIGHT 2019, Walker Federal Serivces, LLC

Walker Federal Services, LLC 7820B-162 Wormans Mill Road Frederick, Maryland 21701

WFS

FACILITY RENOVATION,

IMPROVEMENTS, AND

REPAIRS

WOODLAWN NATIONAL CEMETERY

824IC3005

TDF MLP

MAY 22, 2020

0 2 4 8 12

Amendment 1 8/20/20201

PP-111

ADMINISTRATION BUILDING

DOMESTIC & GAS

PLUMBING PLANS

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text V

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text

PRIME CONSULTANT

AutoCAD SHX Text

CONSULTANTS

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text Y

AutoCAD SHX Text W

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text X

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text B.

AutoCAD SHX Text H

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text U

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text No.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Y

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text E

Hard Card Expires 9-20.pdf
Terracon-NY AHL 2020-2021(2).pdf
Sheets and Views
AE-102
Sheets and Views
ET-101
Sheets and Views
MD-101_MECHANICAL DEMO ADMIN PLANS-MD-101
PD-101_PLUMBING DEMO ADMIN PLANS-PD-101
PP-111_PLUMBING WATER-GAS NEW ADMIN PLANS-PP-111
2020-06-19T08:23:01-0400
Hill, Tony J

File details come from the government source that posted it. Updated .