Addendum_Architectural Spec.pdf
PDF 15 MB Posted
- Attached to
- Z2DA--EHRM Upgrades - White River Junction, VT
- Solicitation number
- 36C77626R0092
About this file
This document is an Architectural Specifications addendum for the EHRM Infrastructure Upgrades project at the White River Junction, Vermont Department of Veterans Affairs Medical Center. The project involves improving, reconfiguring, expanding, and renovating existing spaces across 21 buildings (Buildings 1, 2, 4, 6, 7, 8, 9, 28, 31, 37, 39, 44, 65, 66, 67, 88, and T58-T63) to create new telecommunication rooms. The design team includes SPEES Design Build (23830 Pacific Highway S., Suite 300, Kent, WA 98032) as the primary architect/engineer for structural, mechanical, plumbing, and electrical disciplines, with WSP USA, Inc. (33301 9th Avenue South, Federal Way, WA 98003-2600) providing civil engineering support.
The specifications detail construction requirements including installation of 3/4-inch fire-retardant treated plywood on walls for telecommunications equipment mounting, new doors and frames, anti-static flooring coatings, resilient rubber base installation, and new semi-recessed fire extinguisher cabinets in each telecommunications room. All work must comply with NFPA 101 life safety codes, VA Infection Control Risk Assessment (ICRA) protocols (VHA 2023-1.0), and existing fire rating standards. The project incorporates phased construction with multiple sections requiring coordination with the VA Contracting Officer's Representative (COR) for room closures and data wiring completion. Contractors must conduct pre-bid site visits, field-verify all existing conditions, coordinate with all trades, and ensure high-quality workmanship with specifications superseding drawings in case of conflicts. The project is set-aside for Service-Disabled Veteran-Owned Small Business (SDVOSB) concerns, with the solicitation closing date of August 6, 2026, under solicitation number 36C77626R0092, issued by the Department of Veterans Affairs Technology Acquisition Center.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
DESIGN TEAM
STRUCTURAL
MECHANICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
CIVIL
WSP USA, INC.
33301 9TH AVENUE SOUTH
FEDERAL WAY, WA 98003-2600
PHONE: (206) 431-2300
PLUMBING
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
ELECTRICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
PHONE: (206) 590-2118
WSP USA, INC.
33301 9TH AVENUE SOUTH
FEDERAL WAY, WA 98003-2600
PHONE: (206) 431-2300
PROJECT INFORMATION
STATE:
COUNTY:
JURISDICTION:
OWNER:
CODE ANALYSIS
PROJECT DESCRIPTION
THE PROPOSED DESIGN SHALL IMPROVE,
RECONFIGURE, EXPAND AND RENOVATE
EXISTING SPACES FOR NEW
TELECOMMUNICATION ROOMS.
APPLICABLE BUILDING
BUILDING 1, 2, 4, 6, 7, 8, 9, 28, 31,
37, 39, 44, 65, 66, 67, 88, T58, T59, T60, T61, T62 and T63.
ICRA CLASS REQUIREMENTS
REQUIREMENTS DEPENDENT ON
EACH INDIVIDUAL ROOM LOCATION.
VERMONT
WINDSOR
DEPARTMENT OF VETERANS
AFFAIRS
GENERAL NOTES
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO DRAWINGS &
SPECIFICATIONS.
2. SPECIFICATIONS SHALL SUPERSEDE DRAWINGS IN THE CASE OF ANY CONFLICTING INFORMATION.
BRING TO THE AWARENESS OF, AND VERIFY WITH VA COR PRIOR TO PROCEEDING.
3. THE CONTRACTOR AND ANY SUBCONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND PROJECT REQUIREMENTS PRIOR TO SUBMITTING A BID OR BEGINNING WORK. NO ALLOWANCES WILL BE MADE ON BEHALF OF THE CONTRACTOR OR SUB-CONTRACTORS FOR FAILURE
TO VISIT THE SITE.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT
IMMEDIATELY TO THE ATTENTION OF THE COR.
5. ALL WORK SHALL BE PERFORMED WITH A HIGH-LEVEL OF WORKMANSHIP.
6. THE CONTRACTOR SHALL VERIFY ALL PRODUCT TYPES AND QUANTITIES DURING SITE WALK
THROUGH, PRIOR TO PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
7. THE CONTRACTOR SHALL VERIFY AND COORDINATE WITH ALL INSTALLERS TO ENSURE COMPLIANCE
WITH THE CONTRACT DOCUMENTS.
BLDG 065
BLDG 039
BLDG T-063
BLDG 088
BLDG 002
BLDG 001
BLDG 066
BLDG 009
BLDG 031
BLDG 067
BLDG 028
BLDG 044
BLDG 004
BLDG T-059
BLDG 006
BLDG 007
BLDG T-061
BLDG T-062
BLDG T-058
BLDG T-060
BLDG 08
BLDG 08A
BLDG 037
EXIST. BUILDINGS & FACILITIES TO REMAIN
(NOT INCLUDED WITHIN THE SCOPE OF THIS
PROJECT)
EXIST. BUILDINGS WITHIN THE SCOPE OF
THIS PROJECT
ARCHITECTURAL SITE PLAN KEY
GENERAL ARCHITECTURAL SITE PLAN NOTES:
1. SEE CIVIL DRAWINGS FOR ALL SITE WORK &
UTILITY LOCATIONS & DETAIL.
2. ARCHITECTURAL SITE PLAN IS ONLY FOR
IDENTIFICATION OF BUILDINGS INCLUDED IN THE
SCOPE OF THIS PROJECT.
VAMC, WHITE RIVER JUNCTION, VT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:2
:4 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
S
IT
E
C
I_ S
D B
.r v t
G-001
COVER PAGE
TH OB
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
JUNCTION
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
EHRM INFRASTRUCTURE UPGRADES
VAMC, WHITE RIVER JUNCTION, VT
PROJECT #: 405-22-700
1" = 160'-0"
SITE PLAN
NTS
LOCATION MAP
TRUE
NORTH
TRUE
NORTH
Revisions: Date:
ADDENDUM PRE-BID RFI 1 07/28/2026
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
GENERAL NOTES
1. CONTRACTOR TO LEAVE FIRE RATING STAMP UNPAINTED &
VISIBLE ON NEW INSTALLED F.R.T. PLYWD. PANELS.
2. PROVIDE NEW 3/4" F.R.T. PLYWD. ON WALLS WHERE
INDICATED ON PLANS. PAINT PER FINISH SCHED. & INSTALL
PER DTL. 3/AE421.
3. REFER TO DETAIL 1-5/AE421 FOR A TYP. T.R. OR M.C.R.
ROOM INTERIOR ELEVATION.
4. INSTALL VERT. STUD OR HORIZ. BLOCKING @ ALL G.W.B.
EDGES.
5. ALL PRODUCTS & WALL FINISHES TO MATCH EXIST. OR
ADJACENT FINISHES U.N.O.
EXIST. SUSPENDED CEILING TO REMAIN
ON CORRIDOR SIDE TYP.- U.N.O.
EXIST. UNDERSIDE OF
STRUCTURE ABOVE.
EXIST. WALL TO
REMAIN
INSTALL NEW DOOR &
JAMB AS INDICATED
ON PLANS & DETAILS.
LENGTH VARIES LENGTH VARIES
REPAINT FULL HEIGHT FROM SUSPENDED CEILING
TO FINISH FLOOR WHERE DOOR/FRAME ARE TO BE
INSTALLED NEW OR MODIFIED.
EXIST. WALL TO
REMAIN
LENGTH VARIES
DEMOLISH EXIST.
SUSPENDED CEILING AS
INDICATED ON RCP- TYP.
EXIST. OR PROPOSED
NEW WALL FINISH
PAINTED PER FINISH
SCHED.-TYP.
-INSTALL PLYWD. TYP.
DTL. PER LOCATIONS
AS SHOWN ON THE
PLANS
CONT. RUBBER BASE- TYP.
DEMOLISH EXIST. SUSPENDED
CEILING AS INDICATED ON DEMO RCP-
TYP.
INSTALL 4'X8'X3/4" AC GRADE FIRE RETARDANT
PLYWOOD WITH A-SIDE OUT APPLIED OVER WALL
FOR MOUNTING OF TELECOMMUNICATIONS EQUIP.
INSTALL FULL HEIGHT 8'-0" PANELS FROM 6" A.F.F.
TO 8'-6" A.F.F. CHAMFER EDGES 1/8".
ON METAL STUD WALL.
- SELF TAPPING HEX/ PAN HEAD 1/4" DIA.
SHEET METAL SCREWS WITH THREAD EMBED
INTO EXISTING STUDS (SCREWS TO
BE CENTERED ON STUD) W/ FLAT WASHER.
-18" OR 24" O.C. TYP. EDGES
-(STAGGER @ ABUTTING PLYWD. EDGES)
-24" O.C. TYP. IN PLYWD. FIELD
ON WOOD STUD WALL
- 1/4"⌀ HEX/ PAN HEAD LAG SCREWS WITH 2"
EMBED INTO EXISTING STUDS (SCREWS TO BE
CENTERED ON STUD) W/ FLAT WASHER.
-18" OR 24" O.C. TYP. EDGES
-(STAGGER @ ABUTTING PLYWD. EDGES)
-24" O.C. TYP. IN PLYWD. FIELD
ON CMU WALL
- HILTI KWIK HUS-EZ SCREW ANCHORS 3/8"⌀
WITH 3" MIN. EMBEDMENT INTO EXISTING
CONCRETE (MINIMUM F'c = 3000 psi)
-18" OR 24" O.C. TYP. EDGES
-(STAGGER @ ABUTTING PLYWD. EDGES)
-24" O.C. TYP. IN PLYWD. FIELD
OR
- 5/16"⌀ BOLTS WITH SPRING NUTS OR EQUAL
LOCK WASHER.
-18" OR 24" O.C. TYP.
-(STAGGER @ ABUTTING PLYWD. EDGES)
-24" O.C. TYP. IN PLYWD. FIELD
EXPOSED WALL FINISH PAINTED WHITE (P-01)- TYP.
CONT. RUBBER BASE- TYP.
PAINT EXIST. WALL TO
NEAREST INSIDE &/ OR
OUTSIDE CORNERS- TYP.
INSTALL NEW DOOR
& JAMB OR INFILL
WALL AS INDICATED
ON PLANS
CONTRACTOR TO LEAVE FIRE RATING STAMP UNPAINTED,
COVER STAMP BEFORE PAINTING. REMOVE COVER AFTER PAINT.PROVIDE NEW 3/4" F.R.T. PLYWD.
ON WALLS WHERE INDICATED
ON PLANS. PAINT PER FINISH
SCHED. & INSTALL PER DTL.
3/AE421.
EXTERIOR TR/ MCR ELEV. - TYP. ELEV. @ ENTRY DOOR
N.T.S.
INTERIOR TR/ MCR ELEV. - TYP. ELEV. @ ENTRY DOOR
N.T.S.
INTERIOR ELEVATION - TYP. TR OR MCR F.R.T. PLYWOOD
N.T.S.
TYPICAL TR WALL - PLAN VIEW
N.T.S.
FIRE STAMP UNPAINTED DETAIL
N.T.S.
EXIST. UNDERSIDE OF
STRUCTURE ABOVE.
REQ.'D FROM CORRIDOR
A.B.A. PUSH/ PULL COMPLIANT
CORRIDOR OR
OTHER ROOM
EXTERIOR TO THE
T.R. OR M.C.R.
INTERIOR TO T.R. OR
M.C.R.
DOOR OUTSWING TO
CORRIDOR OR
OTYJHER SPACE
FROM T.R. OR M.C.R.
U.N.O.
PREFER FROM T.R. OR M.C.R.
A.B.A. PUSH/ PULL COMPLIANT
PAINT EXIST. WALL TO
NEAREST INSIDE &/ OR OUTSIDE CORNERS- TYP.
CONT. RUBBER BASE- TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:0
:0 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
G
E N
S
H E
E T
S
S D
B .r v t
AE421
INTERIOR ELEVATIONS, TR PLAN VIEW &
WINDOW DETAIL
TH/OB ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
Revisions: Date:
ADDENDUM PRE-BID RFI 1 07/28/2026
A B C D E F G H I J K L M N O P Q R
S T U V W
PHASE 1:
CONTRACTOR TO COMPLETE THE WORK
OF THIS TR & ASSOCIATED DATA
DROPS. COMPLETE ONE SECTION AT
A TIME AS DIRECTED BY THE VA'S COR.
SECTION 1A:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES & AVAILABILITY
TO COMPLETE DATA WIRING IN THIS AREA.
SECTION 1B:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES & AVAILABILITY
TO COMPLETE DATA WIRING IN THIS AREA.
HC OUT-PAT
C LOW II
ADJACENT
AREA 3
ADJACENT
AREA 1
ADJACENT
AREA 4
ADJACENT
AREA 2
ACTIVITY AREA
AREA ABOVE
AREA BELOW
ADJ. AREA 1
ADJ. AREA 2
ADJ. AREA 3
ADJ. AREA 4
AFFECTED AREA ASSESSMENT TABLE
TR - 10A
X-RAY/READING ROOM
STAIR
N/A
STORAGE
CORRIDOR
N/A
TO
BUILDING 31
BUILDING 39
543 SF
EXAM/
TREATMENT
184 SF
EXAM/
TREATMENT
2A
173 SF
KITCHEN/MISC
195 SF
VAN DRIVER
LOUNGE
OFFICE
77 SF
WALK-IN
REFR.
7F
187 SF
MORGUE
185 SF
MORGUE
7A
411 SF
MORGUE
7B
141 SF
LOCKER RM
7C
127 SF
LOCKER RM
7E
300 SF
ELECTRICAL
340 SF
ELEC RM
9A
215 SF
MECH RM
9B
145 SF
STORAGE
9C
182 SF
CORRIDOR
222 SF
STAIR
S-B-1
142 SF
TR
10A
314 SF
STORAGE
314 SF
DAV OFFICE
47 SF
HAC
35 SF
TELECOM
21A
618 SF
MECH
15 82 SF
MECH
16A
380 SF
OFFICE
216 SF
STAIR
S-B-3
1231 SF
CONFINED
SPACE
113 SF
22A
164 SF
OFFICE
18A
772 SF
EXAM/TREATMENT
738 SF
PROSTHETICS
67 SF
OFFICE
238 SF
OFFICE
186 SF
OFFICE SECY
23A
40 SF
CLOSET
665 SF
CORRIDOR
C-B-3
239 SF
STAIR
S-B-2
714 SF
CORRIDOR
655 SF
CORRIDOR
95 SF
TOILET
18B
32 SF
TOILET
18C
33 SF
STORAGE
18E
18 SF
STORAGE
18D
18 SF
ELECTRICAL
68 SF
WAITING RM
84 SF
BATH/
SHOWER
2B
88 SF
FEMALE
TOILET
123 SF
MALE TOILET
121 SF
STORAGE
421 SF
STORAGE/
EQUIPMENT
1A
NEW SEMI-RECESSED FEC. NEW 10 POUND
CLEAN AGENT FIRE EXTINGUISHER. SEE
DETAIL 3/A-601.
FEC
ELEVATOR
ELEVATOR
CLASS I
CLASS II
4. LEVEL OF ICRA CONTROL PRECAUTIONS
-SEE ICRA-(VHA 2023-1.0- TABLE 4 LEVEL ICRA & CONTROL
PRECAUTIONS & TABLE 5 REQ. ICRA BY LEVEL OF PRECAUTIONS)
3. PATIENT RISK CATEGORY
-SEE ICRA-(VHA 2023-1.0- TABLE 3 PATIENT RISK CATEGORY)
LOW RISK NON-PATIENT CARE AREAS
MEDIUM RISK PATIENT CARE SUPPORT AREAS
HIGH RISK PATIENT CARE AREAS
HIGHEST RISK PROCEDURAL, INVASIVE, STERILE
SUPPORT & HIGHLY COMPROMISED
PATIENT CARE AREAS.
2. CONSTRUCTION, RENOVATION &/OR MAINTENANCE CATEGORY
-SEE ICRA-(VHA 2023-1.0- TABLE 1 CONSTRUCTION, RENOVATION,
&/OR ACTIVITY CATEGORY)
INSPECTION & FACILITY UPKEEP
GENERAL MAINTENANCE & REPAIR
SMALL-SCALE CONSTRUCTION,
RENOVATION, OR MAINTENANCE
LARGE-SCALE CONSTRUCTION,
RENOVATION, OR MAINTENANCE
A
B
C
D
OFFICE
D HIGH + IV
OCCUPANCY CLASS. PER NFPA 101
CONSTRUCTION, RENOVATION &/OR
MAINTENANCE CATEGORY
PATIENT RISK CATEGORY
LEVEL OF INFECTION CONTROL
1. OCCUPANCY CLASSIFICATION
- NFPA 101 (2021) 6.1
HEALTHCARE IN-PATIENT
HEALTHCARE OUT-PATIENT
RESIDENTIAL
INFECTION CONTROL RISK ASSESMENT (ICRA) NOTES
ICRA/ PHASING PLAN KEY
MERCANTILE
BUSINESS
STORAGE
5. ICRA REQUIREMENTS BY LEVEL OF PRECAUTIONS
-SEE ICRA-(VHA 2023-1.0- TABLE 2 AFFECTED AREA ASSESSMENT)
LOW, MEDIUM, HIGH or HIGH +
I, II, III or IV
AREA ABOVE
AREA BELOW
AREA ADJACENT 1
AREA ADJACENT 2
AREA ADJACENT 3
AREA ADJACENT 4
6. MIN. INFECTION PREVENTION & CONTROL REQ. UPON
COMPLETION
-SEE ICRA-(VHA 2023-1.0- TABLE 6 MIN. INFECTION PREVENTION &
CONTROL REQ. UPON COMPLETION OF ACTIVITY)
CONTRACTOR NOTE- CONTROLS DEFINED BELOW, SHALL BE
DEEMED COMPLETE, UPON COMPLETION OF THE ACTIVITY &
APPROVED INSPECTION BY THE VA PRIOR TO TERMINATING
MEASURES DEFINED IN- (VHA 2023-1.0- TABLE 5 REQUIRED ICRA BY
LEVEL OF PRECAUTIONS)
A, B, C or D
LEVEL I-II LEVEL III-IV
HC IN-PAT, HC OUT-PAT, RES, MERC,
BUS, STOR, ETC. or OTHER OCCUPANCY
CHANGE NOTED PER BELOW-
(EXIST.) HC IN-PAT to (PROP.) STOR.
CLASS III
CLASS IV
ACTIVITY AREA
AREA ABOVE
AREA BELOW
ADJ. AREA 1
ADJ. AREA 2
ADJ. AREA 3
ADJ. AREA 4
AFFECTED AREA ASSESSMENT TABLE
TR / TE or MCR
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
PROPOSED TR/ TE LOCATION
ICRA PHASING LINE
EXIST. FIRE EXTINGUISHER (NO CABINET)
EXIST. FIRE EXTINGUISHER CABINET
PROPOSED FIRE EXTINGUISHER CABINET
XFEC
FEC
XFE
KEY AREA SHOWN
PROJECT
NORTH
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:3
:1 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001AS100
BLDG 001-LVL 00-PHASING PLN
TH/OB RB / ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
3/32" = 1'-0"
BUILDING 001 - LEVEL 00 - PHASING PLAN
0' 2' 4' 8' 16'
PROJECT
NORTH
KEY PLAN
RATED BOUNDARY KEY
Revisions: Date:
A B C D E F G H I J K L M N O P Q R
S T U V W
PHASE 1:
CONTRACTOR TO COMPLETE THE WORK OF THIS
TR & ASSOCIATED DATA DROPS. COMPLETE ONE
SECTION AT A TIME AS DIRECTED BY THE VA'S COR.
SECTION 1A:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES & AVAILABILITY
TO COMPLETE DATA WIRING IN THIS AREA.
SECTION 1B:
CONTRACTOR TO COORDINATE WITH VA
FOR ROOM CLOSURES & AVAILABILITY TO
COMPLETE DATA WIRING IN THIS AREA.
HC OUT-PAT
D LOW III
ADJACENT
AREA 3
ADJACENT
AREA 1
ADJACENT
AREA 4
ADJACENT
AREA 2
ACTIVITY AREA
AREA ABOVE
AREA BELOW
ADJ. AREA 1
ADJ. AREA 2
ADJ. AREA 3
ADJ. AREA 4
AFFECTED AREA ASSESSMENT TABLE
TR-331
N/A
OFFICE
N/A
ENTRANCE ROOM A
CORRIDOR
FEMALE TOILET
226 SF
X-RAY RM
213 SF
AUDIOLOGY/
ENT/EYE/DENTAL
200 SF
OFFICE
PHYSICIAN
137 SF
EXAM
303A
189 SF
EXAM
123 SF
EXAM
127 SF
EXAM
123 SF
OPTICAL
SHOP
122 SF
CHIEF
(OPTOMETRY
OFFICE
155 SF
EXAM
73 SF
STORAGE
30943 SF
SOILED
132 SF
EXAM/TREATMENT
RM
129 SF
EXAM/TREATMENT
RM
122 SF
EXAM/TREATMENT
RM
134 SF
EXAM/TREATMENT
RM
313A
87 SF
EXAM
313B
148 SF
EXAM
148 SF
EXAM
155 SF
WAITING RM
315A
136 SF
EXAM/TREATMENT
RM
89 SF
DARK RM
64 SF
OFFICE
318B
206 SF
EXAM
318A
148 SF
EXAM/TREATMENT
RM
225 SF
STAIR
S-3-1
141 SF
MALE TOILET
135 SF
FEMALE
TOILET
75 SF
LAB
289 SF
OFFICE
325 HOUSEKEEPING
CLOSET
37 SF
TEL CLOSET
96 SF
TELECOM
356 SF
OFFICE
128 SF
TR
189 SF
OFFICE SECY
139 SF
ELEC. ROOM
'A'
333 160 SF
FEMALE
TOILET
232 SF
COMPUTER
ROOM
133 SF
MALE TOILET
163 SF
CHIEF
123 SF
OFFICE
STAFF
339A
127 SF
OFFICE
339B
150 SF
EXAM
195 SF
OFFICE
PHYSICIAN
182 SF
WAITING
14 SF
ELECTRICAL
CLOSET
308A
637 SF
CORRIDOR
244 SF
STAIR
S-3-2
497 SF
CORRIDOR
534 SF
CORRIDOR
33 SF
TOILET
330A
75 SF
ELEVATOR
72 SF
ELEVATOR
20 SF
Room
NRN-BB
229 SF
OFFICE
324A
HC OUT-PAT
C MED III
ACTIVITY AREA
AREA ABOVE
AREA BELOW
ADJ. AREA 1
ADJ. AREA 2
ADJ. AREA 3
ADJ. AREA 4
AFFECTED AREA ASSESSMENT TABLE
MCR 336A
N/A
CORRIDOR, STAIR, COMP RM
N/A
N/A
N/A
PHRMCY, EXAM RMS, LAB, TOILETS, STO & OFFICES
ADJACENT
AREA 1
ADJACENT
AREA 2
ADJACENT
AREA 3
ADJACENT
AREA 4
PHASE 2:
CONTRACTOR TO COMPLETE THE WORK OF THIS
TR & ASSOCIATED DATA DROPS. COMPLETE ONE
SECTION AT A TIME AS DIRECTED BY THE VA'S COR.
XFEC
EXISTING FEC. REPLACE EXISTING FE WITH
NEW 10 POUND CLEAN AGENT EXTINGUISHER
THAT MEETS OR EXCEEDS THE ABC RATING
AND SIZE OF EXISTING EXTINGUISHER.
217 SF
STAIR
S-3-3
676 SF
CORRIDOR
C-3-4
21 SF
ELEC CL.
KEY AREA SHOWN
PROJECT
NORTH
CLASS I
CLASS II
4. LEVEL OF ICRA CONTROL PRECAUTIONS
-SEE ICRA-(VHA 2023-1.0- TABLE 4 LEVEL ICRA & CONTROL
PRECAUTIONS & TABLE 5 REQ. ICRA BY LEVEL OF PRECAUTIONS)
3. PATIENT RISK CATEGORY
-SEE ICRA-(VHA 2023-1.0- TABLE 3 PATIENT RISK CATEGORY)
LOW RISK NON-PATIENT CARE AREAS
MEDIUM RISK PATIENT CARE SUPPORT AREAS
HIGH RISK PATIENT CARE AREAS
HIGHEST RISK PROCEDURAL, INVASIVE, STERILE
SUPPORT & HIGHLY COMPROMISED
PATIENT CARE AREAS.
2. CONSTRUCTION, RENOVATION &/OR MAINTENANCE CATEGORY
-SEE ICRA-(VHA 2023-1.0- TABLE 1 CONSTRUCTION, RENOVATION,
&/OR ACTIVITY CATEGORY)
INSPECTION & FACILITY UPKEEP
GENERAL MAINTENANCE & REPAIR
SMALL-SCALE CONSTRUCTION,
RENOVATION, OR MAINTENANCE
LARGE-SCALE CONSTRUCTION,
RENOVATION, OR MAINTENANCE
A
B
C
D
OFFICE
D HIGH + IV
OCCUPANCY CLASS. PER NFPA 101
CONSTRUCTION, RENOVATION &/OR
MAINTENANCE CATEGORY
PATIENT RISK CATEGORY
LEVEL OF INFECTION CONTROL
1. OCCUPANCY CLASSIFICATION
- NFPA 101 (2021) 6.1
HEALTHCARE IN-PATIENT
HEALTHCARE OUT-PATIENT
RESIDENTIAL
INFECTION CONTROL RISK ASSESMENT (ICRA) NOTES
ICRA/ PHASING PLAN KEY
MERCANTILE
BUSINESS
STORAGE
5. ICRA REQUIREMENTS BY LEVEL OF PRECAUTIONS
-SEE ICRA-(VHA 2023-1.0- TABLE 2 AFFECTED AREA ASSESSMENT)
LOW, MEDIUM, HIGH or HIGH +
I, II, III or IV
AREA ABOVE
AREA BELOW
AREA ADJACENT 1
AREA ADJACENT 2
AREA ADJACENT 3
AREA ADJACENT 4
6. MIN. INFECTION PREVENTION & CONTROL REQ. UPON
COMPLETION
-SEE ICRA-(VHA 2023-1.0- TABLE 6 MIN. INFECTION PREVENTION &
CONTROL REQ. UPON COMPLETION OF ACTIVITY)
CONTRACTOR NOTE- CONTROLS DEFINED BELOW, SHALL BE
DEEMED COMPLETE, UPON COMPLETION OF THE ACTIVITY &
APPROVED INSPECTION BY THE VA PRIOR TO TERMINATING
MEASURES DEFINED IN- (VHA 2023-1.0- TABLE 5 REQUIRED ICRA BY
LEVEL OF PRECAUTIONS)
A, B, C or D
LEVEL I-II LEVEL III-IV
HC IN-PAT, HC OUT-PAT, RES, MERC,
BUS, STOR, ETC. or OTHER OCCUPANCY
CHANGE NOTED PER BELOW-
(EXIST.) HC IN-PAT to (PROP.) STOR.
CLASS III
CLASS IV
ACTIVITY AREA
AREA ABOVE
AREA BELOW
ADJ. AREA 1
ADJ. AREA 2
ADJ. AREA 3
ADJ. AREA 4
AFFECTED AREA ASSESSMENT TABLE
TR / TE or MCR
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
OCC. CLASS. NFPA 101
PROPOSED TR/ TE LOCATION
ICRA PHASING LINE
EXIST. FIRE EXTINGUISHER (NO CABINET)
EXIST. FIRE EXTINGUISHER CABINET
PROPOSED FIRE EXTINGUISHER CABINET
XFEC
FEC
XFE
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:3
:3 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001AS103
BLDG 001-LVL 03-PHASING PLN
TH/OB RB / ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
3/32" = 1'-0"
BUILDING 001 - LEVEL 03 - PHASING PLAN
PROJECT
NORTH
KEY PLAN
0' 2' 4' 8' 16'
RATED BOUNDARY KEY
Revisions: Date:
IC
R
A
E F
1 2
NEW WALL CLR.
11' - 0"
STEP #1
MAT
STEP #1
MAT
S T
E P
M A
T
S T
E P
T
TEMP. POLYETHYLENE
ACCESS POINT
A/E RECOMMENDS FIRST PRIORITY TO BE
INSTALLATION OF NEW DOOR & INFILL EXIST.
WALL PREFERABLY AFTER BUSINESS HOURS
OR AS COORDINATED W/ VA C.O.R. TO
MINIMIZE F.L.S. IMPACT & OCCUPANTS DURING
PRIME OPERATING HOURS.
CONTRACTOR TO FINISH
AS REQ'D BY
C O
N T
R A
C T
O R
T O
F
IN
IS
H
A S
R E
Q 'D
B Y
D
IR
E C
T E
D P
E R
A .H
.J
M
IN
T
E M
P
C O
R R
ID
O
R W
ID
T
H
DEMO FLOOR PLAN NOTES
1. TEMPORARY DOORS MAY BE USED DURING PHASING & WHERE USED THEY ARE REQ'D TO MATCH THE EXIST.
WALL ASSEMBLY'S FIRE RATINGS/DOOR OPENING PENETRATION RATING & PER NFPA 101.
2. REFER TO SHEET AS101 FOR TYP. TEMP. CONSTRUCTION BARRIERS. DESIGNATIONS FOR LEVEL II ICRA USE 4/AS101, FOR LEVEL III ICRA USE 5/AS101 & FOR LVL IV ICRA USE 6/AS101. G.W.B./ MTL. STUD TEMPORARY WALLS ARE TO BE USED IN LIEU OF POLYETHELENE SHOWN IN THE ENLARGED PLAN DETAILS THIS SHEET, WHEN NOTED AS SUCH ON THE PLANS OR WHEN THE DURATION OF TEMP. BARRIER MEETS CRITERIA AS
NOTED ON AS101 OR AS INDICATED ON THE AS102 TABLE 5 PRECAUTION REQ'D.
TEMP. POLYETHYLENE
ACCESS POINT
REMOVE EXIST. CARPET
FLOOR SYSTEM
E F
REMOVE EXIST.
A.C.T. CLG. SYSTEM
SEE ELEC. FOR EXIST.
EQUIP. TO DEMO.
E F
314 SF
STORAGE
222 SF
STAIR
S-1
665 SF
CORRIDOR
C-B-3
314 SF
DAV OFFICE
142 SF
TR
10A
A
11' - 0" (CLR.)
/4
(E
X
IS
T
01a
10'X10' TR
FORM FACTOR
NEW
FLOORING
EXISTING
FLOORING
IN
-0
.3
NEW SEMI-RECESSED FEC.
NEW 10 POUND CLEAN AGENT
FIRE EXTINGUISHER. SEE
DETAIL 3/A-601.
SEE TELECOM
FOR NEW EQUIP.
IN-03.01-01
FLOOR PLAN NOTES
1. WHEN 'FORM FACTOR' OR OTHER EXCEPTIONS ARE NOTED ON DRAWINGS- DESIGNER IS REFERRING TO EXCEPTIONS NOT MEETING THE VA O.I.T.C. PLANNING GUIDES FOR MINIMUM CLEARANCES OR OTHER DESIGN CRITERIA. VA HAS ACCEPTED THESE EXCEPTIONS & NOTATION IS INCLUDED TO NOTIFY THE VA
ON THESE DOCUMENTS. THERE IS NO ACTION REQ,'D OF THE CONTRACTOR.
E F
314 SF
STORAGE
10222 SF
STAIR
S-1
314 SF
DAV OFFICE
665 SF
CORRIDOR
C-B-3
142 SF
TR
10A
O.T.S.
SEE ELEC. FOR
NEW EQUIP.
SEE MECH. FOR
NEW EQUIP.
DEMO ABUTTING CLG. SYSTEM ADJACENT NEW
WALLS &/ OR BRACING. PATCH & REPAIR EXIST.
CLG. SYSTEMS TO BLEND W/ NEW MODIFIED CLG.'S.
SEE ELEC. FOR
NEW EQUIP.
462 SF
STORAGE
665 SF
CORRIDOR
C-B-3
314 SF
DAV OFFICE
222 SF
STAIR
S-1
462 SF
STORAGE
665 SF
CORRIDOR
C-B-3
314 SF
DAV OFFICE
222 SF
STAIR
S-1
ENLARGED AREA
KEY AREA SHOWN
PROJECT
NORTH
TO DEMOLISH
X X
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH
EXISTING WALL TO REMAIN
EXISTING LIGHTS TO DEMOLISH
NEW LIGHTS (SEE ELECTRICAL DRAWINGS)
NEW WALL
(F.R.T. PLYWD. WHERE INDICATED)
(F.R.T. PLYWD. WHERE INDICATED)
( + ) POSITIVE PRESSURE
CONSTRUCTION ZONE,
(--) NEGATIVE PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MAT
HEPA EQUIPPED EXHAUST
POLYETHYLENE SHEETING
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
IC
R
A
00-00-00
NEW SIGNAGE (SEE SIGNAGE SCHEDULE)
NEW CONCRETE (SEE STRUCT. DRAWINGS)
(ACCESS POINT)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:3
:3 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001A-400
BLDG 001-LVL 00-DEMO, FLR PLNS & RCPS
TH ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
3/16" = 1'-0"
RM 10 - DEMO FLOOR PLAN
PROJECT
NORTH
3/16" = 1'-0"
RM 10 - DEMO RCP
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
3/16" = 1'-0"
RM 10A - FLOOR PLAN
3/16" = 1'-0"
RM 10A - RCP
1 DEMO. EXIST. BASE. REMOVE EXIST. ADHESIVE & PREPARE
FOR NEW BASE.
2 DEMO EXIST. FLOOR FIN. TO EXPOSE SUBSURFACE FLOOR
STRUCT. REMOVE ANY EXIST. SEALER, TOPPING OR BONDING
SUBSTANCE. PREPARE SUBFLOOR IN ACCORD. WITH NEW
FLOORING MANUFACT. FINISH PREPARATION REQUIREMENTS.
3 DEMO. PORTION OF EXIST. WALL. PREPARE FOR NEW DOOR &
FRAME.
4 PREPARE WALL FOR INSTALLATION OF NEW FEC.
5 DEMO EXIST. CLG. SYSTEM INCLUDING SUPPORTING WIRES,
CLIPS, PERIMETER WALL ANGLES & ALL OTHER COMPONENTS.
EXPOSE CLG. O.T.S. ABV.
6 CONSTRUCT NEW WALL. PATCH & PAINT TO MATCH EXIST.
7 INSTALL NEW DOOR & FRAME.
8 INSTALL F.R.T. PLYWD. OVER WALLS AS NEEDED- PER TYP.
DTL. 3/AE421- TYP.
9 INSTALL NEW RESILIENT RUBBER BASE @ ROOM PERIM. W/
SEALANT @ THE BTTM.
10 APPLY ANTI-STATIC COATING TO EXPOSED FLOOR. PROVIDE
VINYL REDUCER STRIP @ EXIST. FLOORING TRANSITION.
11 CONTRACTOR COORD. ROUTING & TERMINATION OF
TEMPORARY VENTILATION & PRESSURIZATION IN
ACCORDANCE W/ SPEC. REQ. & IN COORD. W/ VA C.O.R. &
EXIST. SITE CONDITION CONSTRAINTS.
KEY PLAN
SHEET GENERAL NOTES
1. ALL NEW PRODUCTS & FINISHED SURFACES ARE TO MATCH
EXIST. ADJACENT PRODUCTS & FINISHED SURFACES U.N.O.
2. PATCH & REPAIR FINISHES & FIRE RATINGS OF WALLS,
FLOORS & CEILINGS, TO MATCH EXIST. ADJACENT SURFACES,
WHERE MECH., PLUMBING, ELEC. & TELECOM. ITEMS ARE
DEMO'D.
3. PROTECT FINISHES IN ROOMS ADJACENT TO WORK AREAS &
DO NOT ALTER AREAS & ITEMS NOT INCLUDED IN THE SCOPE.
4. CONTRACTOR IS TO LEAVE FIRE RATING STAMP UNPAINTED &
VISIBLE ON THE NEW INSTALLED F.R.T. PLYWD. SEE DETAIL
5/AE421.
5. REFER TO SHEETS AS101, AS102 & AS103 FOR ICRA REQ. &
TEMP. CONST. BARRIER DETAILS REF. FROM PHASING &
ENLARGED PLANS.
6. PATCH & REPAIR CEILINGS, WALLS & FLOORS WHERE TEMP.
CONST. BARRIERS ARE CONSTRUCTED & REMOVED.
7. PATCH & REPAIR EXIST. CLG. GRID & A.C.T./ G.W.B. CLG.
WHERE NEW WALLS ARE TO BE INSTALLED.
8. PATCH & REPAIR G.W.B. WHERE DOORS ARE DEMO.'D & NEW
DOORS ARE TO BE INSTALLED.
9. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR EXIST. EQUIP., & IT'S ASSOCIATED CONDUIT, WIRE, OR
PIPING IS TO BE DEMO'D OR ARE INTENDED TO REMAIN.
ARCH. SHEET SYMBOLSSHEET KEYNOTES
10. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR LOCATION & SIZE OF PROPOSED NEW EQUIP., & IT'S
ASSOCIATED CONDUIT, WIRE, OR PIPING.
11. WHERE TEMP. POLYETHYLENE CONST. BARRIERS ARE
INSTALLED, THEY ARE TO BE FULLY TAPED @ THE PERIM. OF
THE ENCLOSURE TO CONTROL WORK AREA PRESSURIZATION
& DUST MIGRATION. UPKEEP TAPED PERIM.
12. WHERE WALLS ENCLOSING T.R.'S DO NOT EXTEND FULLY TO
THE UNDERSIDE OF THE STRUCTURE ABV., CONTRACTOR IS
TO PROVIDE TEMP. POLYETHYLENE BARRIER AS NEEDED IN
CONST. SEQUENCING & ALSO FINAL PERMANENT G.W.B.
ENCLOSURE FROM THE TOP OF EXIST. DISCONTINUOUS
WALLS TO THE UNDERSIDE OF STRUCTURE ABV.
13. CONTRACTOR IS RESPONSIBLE FOR MEANS & METHODS, FOR
SECURING THE WORK AREA/ JOB SITE W/ TEMP. LOCKABLE
BARRIER DURING & AFTER CONST. WORK HOURS. WHERE
NEW OR EXIST. DOORS ARE UTILIZED FOR THIS PURPOSE
THEY ARE TO BE COVERED W/ A PROTECTIVE SURFACE TO
PREVENT FINISH DAMAGE.
14. REFER TO SHEET KEYNOTES, SHEET GENERAL NOTES, ARCH.
SHEET SYMBOLS THIS SHEET, FOR NOTES & SYMBOLS
APPLICABLE TO THE WORK AREA SHOWN.
Revisions: Date:
F
NEW WALL CLR.
10' - 0"
STEP #1
MAT
STEP #1
MAT
S T
E P
T
S T
E P
T
SEAL DOOR DURING
CONSTRUCTION.
A/E RECOMMENDS FIRST PRIORITY TO BE
INSTALLATION OF NEW DOOR & INFILL EXIST.
WALL PREFERABLY AFTER BUSINESS HOURS OR
AS COORDINATED W/ VA C.O.R. TO MINIMIZE F.L.S.
IMPACT & OCCUPANTS DURING PRIME OPERATING
HOURS.
DEMO FLOOR PLAN NOTES
1. TEMPORARY DOORS MAY BE USED DURING PHASING & WHERE USED THEY ARE REQ'D TO MATCH THE EXIST.
WALL ASSEMBLY'S FIRE RATINGS/DOOR OPENING PENETRATION RATING & PER NFPA 101.
2. REFER TO SHEET AS101 FOR TYP. TEMP. CONSTRUCTION BARRIERS. DESIGNATIONS FOR LEVEL II ICRA USE 4/AS101, FOR LEVEL III ICRA USE 5/AS101 & FOR LVL IV ICRA USE 6/AS101. G.W.B./ MTL. STUD TEMPORARY WALLS ARE TO BE USED IN LIEU OF POLYETHELENE SHOWN IN THE ENLARGED PLAN DETAILS THIS SHEET, WHEN NOTED AS SUCH ON THE PLANS OR WHEN THE DURATION OF TEMP. BARRIER MEETS CRITERIA AS
NOTED ON AS 101 OR AS INDICATED ON THE AS102 TABLE 5 PRECAUTION REQ'D.
REMOVE EXIST. VCT
FLOOR SYSTEM
CONTRACTOR TO FINISH
AS REQ'D BY
C O
N T
R A
C T
O R
T O
F
IN
IS
H
A S
R E
Q 'D
B Y
D
IR
E C
T E
D P
E R
A .H
.J
M
IN
T
E M
P
C O
R R
ID
O
R W
ID
T
H
TEMP. POLYETHYLENE
ACCESS POINT
TEMP. POLYETHYLENE
ACCESS POINT
F
O.T.S.
REMOVE EXIST. A.C.T.
CLG. SYSTEM
SEE ELEC. FOR EXIST.
EQUIP. TO DEMO.
SEE ELEC. FOR EXIST.
EQUIP. TO DEMO.
F
129 SF
TR
112 SF
OFFICE
230 SF
RECEPTION,
FILES
657 SF
CORRIDOR
179 862 SF
CORRIDOR
C-1-1
369 SF
FILE RM
10' - 0" (CLR.)
/4
(E X
IS
T
01a
01b
10'x10' TR
FORM FACTOR
E X
IS
T
IN
G
L O
O R
IN
G
NEW
FLOORING
IN-01.31
NEW SEMI-RECESSED FEC.
NEW 10 POUND CLEAN AGENT
FIRE EXTINGUISHER. SEE
DETAIL 3/A-601.
SEE TELECOM
FOR NEW EQUIP.
9 10
R E
U S
E E
X
IS
T
FLOOR PLAN NOTES
1. WHEN 'FORM FACTOR' OR OTHER EXCEPTIONS ARE NOTED ON DRAWINGS- DESIGNER IS REFERRING TO EXCEPTIONS NOT MEETING THE VA O.I.T.C. PLANNING GUIDES FOR MINIMUM CLEARANCES OR OTHER DESIGN CRITERIA. VA HAS ACCEPTED THESE EXCEPTIONS & NOTATION IS INCLUDED TO NOTIFY THE VA
ON THESE DOCUMENTS. THERE IS NO ACTION REQ,'D OF THE CONTRACTOR.
F
129 SF
TR
369 SF
FILE RM
230 SF
RECEPTION,
FILES
657 SF
CORRIDOR
O.T.S.
112 SF
OFFICE
SEE ELEC. FOR
NEW EQUIP. SEE MECH. FOR
NEW EQUIP.
DEMO ABUTTING CLG. SYSTEM ADJACENT
NEW WALLS &/ OR BRACING. PATCH &
REPAIR EXIST. CLG. SYSTEMS TO BLEND
W/ NEW MODIFIED CLG.'S.
SEE ELEC. FOR
NEW EQUIP.
114 SF
IRM VOICE/DATA
RM
126 SF
OFFICE
230 SF
RECEPTION,
FILES
369 SF
FILE RM
657 SF
CORRIDOR
114 SF
IRM VOICE/DATA
RM
126 SF
OFFICE
230 SF
RECEPTION,
FILES
369 SF
FILE RM
657 SF
CORRIDOR
ENLARGED AREA
KEY AREA SHOWN
PROJECT
NORTH
TO DEMOLISH
X X
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH
EXISTING WALL TO REMAIN
EXISTING LIGHTS TO DEMOLISH
NEW LIGHTS (SEE ELECTRICAL DRAWINGS)
NEW WALL
(F.R.T. PLYWD. WHERE INDICATED)
(F.R.T. PLYWD. WHERE INDICATED)
( + ) POSITIVE PRESSURE
CONSTRUCTION ZONE,
(--) NEGATIVE PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MAT
HEPA EQUIPPED EXHAUST
POLYETHYLENE SHEETING
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
IC
R
A
00-00-00
NEW SIGNAGE (SEE SIGNAGE SCHEDULE)
NEW CONCRETE (SEE STRUCT. DRAWINGS)
(ACCESS POINT)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:3
:4 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001A-401
BLDG 001-LVL 01-DEMO, FLR PLNS & RCPS
TH ME/OB
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
1/4" = 1'-0"
RM 112, 113 - DEMO FLOOR PLAN
PROJECT
NORTH
1/4" = 1'-0"
RM 112, 113 - DEMO RCP
PROJECT
NORTH
1/4" = 1'-0"
RM 113 - FLOOR PLAN
1/4" = 1'-0"
RM 113 - RCP
PROJECT
NORTH
PROJECT
NORTH
1 DEMO. EXIST. DOOR & FRAME. PREPARE FOR NEW DOOR &
FRAME.
2 DEMO. EXIST. WALL. PATCH EXPOSED ADJ. SURFACES TO
MATCH EXIST.
3 DEMO EXIST. FLOOR FIN. TO EXPOSE SUBSURFACE FLOOR
STRUCT. REMOVE ANY EXIST. SEALER, TOPPING OR BONDING
SUBSTANCE. PREPARE SUBFLOOR IN ACCORD. WITH NEW
FLOORING MANUFACT. FINISH PREPARATION REQUIREMENTS.
4 DEMO. EXIST. BASE. REMOVE EXIST. ADHESIVE & PREPARE
FOR NEW BASE.
5 PREPARE WALL FOR INSTALLATION OF NEW FEC.
6 DEMO EXIST. CLG. SYSTEM INCLUDING SUPPORTING WIRES,
CLIPS, PERIMETER WALL ANGLES & ALL OTHER COMPONENTS.
EXPOSE CLG. O.T.S. ABV.
7 CONSTRUCT NEW WALL. PATCH & PAINT TO MATCH EXIST.
8 INFILL WALL, PATCH & PAINT TO MATCH EXIST.
9 INSTALL NEW RESILIENT RUBBER BASE @ ROOM PERIM. W/
SEALANT @ THE BTTM.
10 APPLY ANTI-STATIC COATING TO EXPOSED FLOOR. PROVIDE
VINYL REDUCER STRIP @ EXIST. FLOORING TRANSITION.
11 INSTALL NEW DOOR & FRAME.
12 INSTALL F.R.T. PLYWD. OVER WALLS AS NEEDED- PER TYP.
DTL. 3/AE421- TYP.
13 CONTRACTOR COORD. ROUTING & TERMINATION OF
TEMPORARY VENTILATION & PRESSURIZATION IN
ACCORDANCE W/ SPEC. REQ. & IN COORD. W/ VA C.O.R. &
EXIST. SITE CONDITION CONSTRAINTS.
KEY PLAN
SHEET GENERAL NOTES
1. ALL NEW PRODUCTS & FINISHED SURFACES ARE TO MATCH
EXIST. ADJACENT PRODUCTS & FINISHED SURFACES U.N.O.
2. PATCH & REPAIR FINISHES & FIRE RATINGS OF WALLS,
FLOORS & CEILINGS, TO MATCH EXIST. ADJACENT SURFACES,
WHERE MECH., PLUMBING, ELEC. & TELECOM. ITEMS ARE
DEMO'D.
3. PROTECT FINISHES IN ROOMS ADJACENT TO WORK AREAS &
DO NOT ALTER AREAS & ITEMS NOT INCLUDED IN THE SCOPE.
4. CONTRACTOR IS TO LEAVE FIRE RATING STAMP UNPAINTED &
VISIBLE ON THE NEW INSTALLED F.R.T. PLYWD. SEE DETAIL
5/AE421.
5. REFER TO SHEETS AS101, AS102 & AS103 FOR ICRA REQ. &
TEMP. CONST. BARRIER DETAILS REF. FROM PHASING &
ENLARGED PLANS.
6. PATCH & REPAIR CEILINGS, WALLS & FLOORS WHERE TEMP.
CONST. BARRIERS ARE CONSTRUCTED & REMOVED.
7. PATCH & REPAIR EXIST. CLG. GRID & A.C.T./ G.W.B. CLG.
WHERE NEW WALLS ARE TO BE INSTALLED.
8. PATCH & REPAIR G.W.B. WHERE DOORS ARE DEMO.'D & NEW
DOORS ARE TO BE INSTALLED.
9. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR EXIST. EQUIP., & IT'S ASSOCIATED CONDUIT, WIRE, OR
PIPING IS TO BE DEMO'D OR ARE INTENDED TO REMAIN.
ARCH. SHEET SYMBOLSSHEET KEYNOTES
10. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR LOCATION & SIZE OF PROPOSED NEW EQUIP., & IT'S
ASSOCIATED CONDUIT, WIRE, OR PIPING.
11. WHERE TEMP. POLYETHYLENE CONST. BARRIERS ARE
INSTALLED, THEY ARE TO BE FULLY TAPED @ THE PERIM. OF
THE ENCLOSURE TO CONTROL WORK AREA PRESSURIZATION
& DUST MIGRATION. UPKEEP TAPED PERIM.
12. WHERE WALLS ENCLOSING T.R.'S DO NOT EXTEND FULLY TO
THE UNDERSIDE OF THE STRUCTURE ABV., CONTRACTOR IS
TO PROVIDE TEMP. POLYETHYLENE BARRIER AS NEEDED IN
CONST. SEQUENCING & ALSO FINAL PERMANENT G.W.B.
ENCLOSURE FROM THE TOP OF EXIST. DISCONTINUOUS
WALLS TO THE UNDERSIDE OF STRUCTURE ABV.
13. CONTRACTOR IS RESPONSIBLE FOR MEANS & METHODS, FOR
SECURING THE WORK AREA/ JOB SITE W/ TEMP. LOCKABLE
BARRIER DURING & AFTER CONST. WORK HOURS. WHERE
NEW OR EXIST. DOORS ARE UTILIZED FOR THIS PURPOSE
THEY ARE TO BE COVERED W/ A PROTECTIVE SURFACE TO
PREVENT FINISH DAMAGE.
14. REFER TO SHEET KEYNOTES, SHEET GENERAL NOTES, ARCH.
SHEET SYMBOLS THIS SHEET, FOR NOTES & SYMBOLS
APPLICABLE TO THE WORK AREA SHOWN.
Revisions: Date:
IC
R
A
H I
J K
NEW WALL CLR.
10' - 0"
STEP #1
MAT
S T
E P
T
S T
E P
T
A/E RECOMMENDS FIRST PRIORITY TO BE
INSTALLATION OF NEW DOOR & INFILL EXIST. WALL
PREFERABLY AFTER BUSINESS HOURS OR AS
COORDINATED W/ VA C.O.R. TO MINIMIZE F.L.S.
IMPACT & OCCUPANTS DURING PRIME OPERATING
HOURS.
STEP #3
MAT
STEP #3
MAT
CONTRACTOR TO PROVIDE FLOOR COVERING
PROTECTION THRU THE DURATION OF CONSTRUCTION
IN WORK AREA. REPLACE ADJACENT FLOORING TO
MATCH EXISTING, OR PROVIDE NEW IN ENTIRE ROOM IF
MATCHING NOT AVAILABLE
REMOVE EXIST.
VCT FLOOR
SYSTEM.
CONTRACTOR TO FINISH
AS REQ'D BY
SEAL DOOR DURING
CONSTRUCTION
STEP #1
MAT
C O
N T
R A
C T
O R
T O
F
IN
IS
H
A S
R E
Q 'D
B Y
TEMP.
POLYETHYLENE
ACCESS POINT
TEMP. POLYETHYLENE
ACCESS POINT
D
IR
E C
T E
D P
E R
A .H
.J
M
IN
T
E M
P
C O
R R
ID
O
R W
ID
T
H
H I J K
REMOVE EXIST.
A.C.T. CLG. SYSTEM.
REMOVE EXIST.
A.C.T. CLG. SYSTEM.
SEE ELEC. FOR EXIST.
EQUIP. TO DEMO.
SEE ELEC. FOR
EXIST. EQUIP.
TO REMAIN.
H I J K
245 SF
CLERK
178 SF
TR
267 SF
LAB
202A
110 SF
OFFICE STAFF
259C
110 SF
OFFICE
RESIDENT
259B
O.T.S.
SEE ELEC. FOR
NEW EQUIP.
SEE MECH. FOR
NEW EQUIP.
SEE ELEC. FOR
NEW EQUIP.
DEMO ABUTTING CLG. SYSTEM ADJACENT NEW
WALLS &/ OR BRACING. PATCH & REPAIR EXIST.
CLG. SYSTEMS TO BLEND W/ NEW MODIFIED
CLG.'S.
H I J K
245 SF
CLERK
178 SF
TR
267 SF
LAB
202A
110 SF
OFFICE STAFF
259C
110 SF
OFFICE
RESIDENT
259B
358 SF
PORCH
432 SF
CORRIDOR C-2-1
10' - 0" (CLR.)
01b
01a
10'x10' TR
FORM FACTOR
01b
(E X
IS
T
EXISTING
FLOORING
NEW
FLOORING
SEE TELECOM
FOR NEW EQUIP.
REUSE EXIST.
PATCH FLOOR WHERE
WALLS ARE REMOVED.
FINISH TO MATCH EXISTING.
PROVIDE CONTIN. BEAD OF SILICONE
CAULK @ BTTM. OF RUBBER BASE,
FOR FULL LENGTH OF WET WALL.
- INTENDED AS WATER MIGRATION
MITIGATION IF PLUMBING WALL LEAK
OCCURS.
347 SF
CLERK
77 SF
LAB STORAGE
215 SF
LAB
202A
44 SF
STORAGE
201A
432 SF
CORRIDOR C-2-1
358 SF
PORCH
14S
110 SF
OFFICE STAFF
259C
110 SF
OFFICE
RESIDENT
259B
844 SF
CORRIDOR
C-2-3
347 SF
CLERK
77 SF
LAB STORAGE
215 SF
LAB
202A
44 SF
STORAGE
201A
432 SF
CORRIDOR C-2-1
358 SF
PORCH
14S
110 SF
OFFICE
RESIDENT
259B
844 SF
CORRIDOR
C-2-3
ENLARGED AREA
KEY AREA SHOWN
PROJECT
NORTH
TO DEMOLISH
X X
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH
EXISTING WALL TO REMAIN
EXISTING LIGHTS TO DEMOLISH
NEW LIGHTS (SEE ELECTRICAL DRAWINGS)
NEW WALL
(F.R.T. PLYWD. WHERE INDICATED)
(F.R.T. PLYWD. WHERE INDICATED)
( + ) POSITIVE PRESSURE
CONSTRUCTION ZONE,
(--) NEGATIVE PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MAT
HEPA EQUIPPED EXHAUST
POLYETHYLENE SHEETING
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
IC
R
A
00-00-00
NEW SIGNAGE (SEE SIGNAGE SCHEDULE)
NEW CONCRETE (SEE STRUCT. DRAWINGS)
(ACCESS POINT)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:3
:4 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001A-402
BLDG 001-LVL 02-DEMO, FLR PLNS & RCPS
TH ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
1/4" = 1'-0"
RM 200, 201 - DEMO FLOOR PLAN
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
PROJECT
NORTH
1/4" = 1'-0"
RM 200, 201 - DEMO RCP
1/4" = 1'-0"
RM 201 - RCP
1/4" = 1'-0"
RM 201 - FLOOR PLAN
1 DEMO. EXIST. DOOR & FRAME.
2 DEMO. EXIST. WALL. PATCH EXPOSED ADJ. SURFACES TO
MATCH EXIST.
3 DEMO EXIST. FLOOR FIN. TO EXPOSE SUBSURFACE FLOOR
STRUCT. REMOVE ANY EXIST. SEALER, TOPPING OR BONDING
SUBSTANCE. PREPARE SUBFLOOR IN ACCORD. WITH NEW
FLOORING MANUFACT. FINISH PREPARATION REQUIREMENTS.
4 DEMO. PORTION OF EXIST. WALL. PREPARE FOR NEW DOOR &
FRAME.
5 DEMO EXIST. CLG. SYSTEM INCLUDING SUPPORTING WIRES,
CLIPS, PERIMETER WALL ANGLES & ALL OTHER COMPONENTS.
EXPOSE CLG. O.T.S. ABV.
6 INSTALL NEW DOOR & FRAME.
7 CONSTRUCT NEW WALL. PATCH & PAINT TO MATCH EXIST.
8 INSTALL F.R.T. PLYWD. OVER WALLS AS NEEDED- PER TYP.
DTL. 3/AE421- TYP.
9 INSTALL NEW RESILIENT RUBBER BASE @ ROOM PERIM. W/
SEALANT @ THE BTTM.
10 APPLY ANTI-STATIC COATING TO EXPOSED FLOOR. PROVIDE
VINYL REDUCER STRIP @ EXIST. FLOORING TRANSITION.
11 INFILL WALL, PATCH & PAINT TO MATCH EXIST.
12 INSTALL PHYSICAL SECURITY @ INT. OF EXIST. WIN.-PER DTL.
1/A603.
13 INSTALL NEW BASE TO MATCH EXIST. ON AFFECTED ROOM.
14 CONSTRUCT NEW CLG. TO MATCH EXIST.
15 CONTRACTOR COORD. ROUTING & TERMINATION OF
TEMPORARY VENTILATION & PRESSURIZATION IN
ACCORDANCE W/ SPEC. REQ. & IN COORD. W/ VA C.O.R. &
EXIST. SITE CONDITION CONSTRAINTS.
SHEET GENERAL NOTES
KEY PLAN
1. ALL NEW PRODUCTS & FINISHED SURFACES ARE TO MATCH
EXIST. ADJACENT PRODUCTS & FINISHED SURFACES U.N.O.
2. PATCH & REPAIR FINISHES & FIRE RATINGS OF WALLS,
FLOORS & CEILINGS, TO MATCH EXIST. ADJACENT SURFACES,
WHERE MECH., PLUMBING, ELEC. & TELECOM. ITEMS ARE
DEMO'D.
3. PROTECT FINISHES IN ROOMS ADJACENT TO WORK AREAS &
DO NOT ALTER AREAS & ITEMS NOT INCLUDED IN THE SCOPE.
4. CONTRACTOR IS TO LEAVE FIRE RATING STAMP UNPAINTED &
VISIBLE ON THE NEW INSTALLED F.R.T. PLYWD. SEE DETAIL
5/AE421.
5. REFER TO SHEETS AS101, AS102 & AS103 FOR ICRA REQ. &
TEMP. CONST. BARRIER DETAILS REF. FROM PHASING &
ENLARGED PLANS.
6. PATCH & REPAIR CEILINGS, WALLS & FLOORS WHERE TEMP.
CONST. BARRIERS ARE CONSTRUCTED & REMOVED.
7. PATCH & REPAIR EXIST. CLG. GRID & A.C.T./ G.W.B. CLG.
WHERE NEW WALLS ARE TO BE INSTALLED.
8. PATCH & REPAIR G.W.B. WHERE DOORS ARE DEMO.'D & NEW
DOORS ARE TO BE INSTALLED.
9. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR EXIST. EQUIP., & IT'S ASSOCIATED CONDUIT, WIRE, OR
PIPING IS TO BE DEMO'D OR ARE INTENDED TO REMAIN.
ARCH. SHEET SYMBOLSSHEET KEYNOTES
10. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR LOCATION & SIZE OF PROPOSED NEW EQUIP., & IT'S
ASSOCIATED CONDUIT, WIRE, OR PIPING.
11. WHERE TEMP. POLYETHYLENE CONST. BARRIERS ARE
INSTALLED, THEY ARE TO BE FULLY TAPED @ THE PERIM. OF
THE ENCLOSURE TO CONTROL WORK AREA PRESSURIZATION
& DUST MIGRATION. UPKEEP TAPED PERIM.
12. WHERE WALLS ENCLOSING T.R.'S DO NOT EXTEND FULLY TO
THE UNDERSIDE OF THE STRUCTURE ABV., CONTRACTOR IS
TO PROVIDE TEMP. POLYETHYLENE BARRIER AS NEEDED IN
CONST. SEQUENCING & ALSO FINAL PERMANENT G.W.B.
ENCLOSURE FROM THE TOP OF EXIST. DISCONTINUOUS
WALLS TO THE UNDERSIDE OF STRUCTURE ABV.
13. CONTRACTOR IS RESPONSIBLE FOR MEANS & METHODS, FOR
SECURING THE WORK AREA/ JOB SITE W/ TEMP. LOCKABLE
BARRIER DURING & AFTER CONST. WORK HOURS. WHERE
NEW OR EXIST. DOORS ARE UTILIZED FOR THIS PURPOSE
THEY ARE TO BE COVERED W/ A PROTECTIVE SURFACE TO
PREVENT FINISH DAMAGE.
14. REFER TO SHEET KEYNOTES, SHEET GENERAL NOTES, ARCH.
SHEET SYMBOLS THIS SHEET, FOR NOTES & SYMBOLS
APPLICABLE TO THE WORK AREA SHOWN.
DEMO FLOOR PLAN NOTES
1. TEMPORARY DOORS MAY BE USED DURING PHASING & WHERE USED THEY ARE REQ'D TO MATCH THE EXIST.
WALL ASSEMBLY'S FIRE RATINGS/DOOR OPENING PENETRATION RATING & PER NFPA 101.
2. REFER TO SHEET AS101 FOR TYP. TEMP. CONSTRUCTION BARRIERS. DESIGNATIONS FOR LEVEL II ICRA USE 4/AS101, FOR LEVEL III ICRA USE 5/AS101 & FOR LVL IV ICRA USE 6/AS101. G.W.B./ MTL. STUD TEMPORARY WALLS ARE TO BE USED IN LIEU OF POLYETHELENE SHOWN IN THE ENLARGED PLAN DETAILS THIS SHEET, WHEN NOTED AS SUCH ON THE PLANS OR WHEN THE DURATION OF TEMP. BARRIER MEETS CRITERIA AS
NOTED ON AS 101 OR AS INDICATED ON THE AS102 TABLE 5 PRECAUTION REQ'D.
FLOOR PLAN NOTES
1. WHEN 'FORM FACTOR' OR OTHER EXCEPTIONS ARE NOTED ON DRAWINGS- DESIGNER IS REFERRING TO EXCEPTIONS NOT MEETING THE VA O.I.T.C. PLANNING GUIDES FOR MINIMUM CLEARANCES OR OTHER DESIGN CRITERIA. VA HAS ACCEPTED THESE EXCEPTIONS & NOTATION IS INCLUDED TO NOTIFY THE VA
ON THESE DOCUMENTS. THERE IS NO ACTION REQ,'D OF THE CONTRACTOR.
Revisions: Date:
P Q R
S
A/E RECOMMENDS FIRST PRIORITY TO BE INSTALLATION OF NEW
DOOR & INFILL EXIST. WALL PREFERABLY AFTER BUSINESS HOURS
OR AS COORDINATED W/ VA C.O.R. TO MINIMIZE F.L.S. IMPACT &
OCCUPANTS DURING PRIME OPERATING HOURS.
STEP #1
MAT
2 311 2 3
REMOVE EXIST. VCT
FLOOR SYSTEM
STEP #1
MAT
STEP #2
MAT
STEP #3
MAT
D
IR
E C
T E
D P
E R
A .H
.J
M
IN
T
E M
P
C O
R R
ID
O
R W
ID
T
H
C O
N T
R A
C T
O R
T O
F
IN
IS
H
A S
R E
Q 'D
B Y
CONTRACTOR TO FINSH
AS REQ'D BY
TEMP. POLYETHYLENE
ACCESS POINT TEMP. POLYETHYLENE
ACCESS POINT
P Q R S
4 4
REMOVE EXIST.
A.C.T. CLG. SYSTEM.
SEE ELEC. FOR EXIST.
EQUIP. TO DEMO.
P Q R S
139 SF
ELEC. ROOM 'A'
160 SF
FEMALE TOILET
189 SF
OFFICE SECY
534 SF
CORRIDOR
± 10' - 7" (EXIST.)
10'x10' TR FORM
FACTOR
01b
128 SF
TR
01b
± 9' - 10 3/4" (EXIST.)
N E
W
O
O R
IN
G
E X
IS
T
O
O R
IN
G
56 6
SEE TELECOM FOR NEW
EQUIP.
REUSE EXIST.
REUSE EXIST.
P Q R S
139 SF
ELEC. ROOM 'A'
160 SF
FEMALE TOILET
534 SF
CORRIDOR
O.T.S.
O.T.S.128 SF
TR
189 SF
OFFICE SECY
SEE ELEC. FOR
NEW EQUIP. SEE ELEC. FOR
NEW EQUIP.
SEE ELEC. FOR
NEW EQUIP.
139 SF
OFFICE
189 SF
OFFICE SECY
160 SF
FEMALE TOILET
534 SF
CORRIDOR
14E
129 SF
SOCIAL WORKER
OFFICE
139 SF
OFFICE
189 SF
OFFICE SECY
332 160 SF
FEMALE TOILET
534 SF
CORRIDOR
14E
129 SF
SOCIAL WORKER
OFFICE
ENLARGED AREA
KEY AREA SHOWN
PROJECT
NORTH
TO DEMOLISH
X X
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH
EXISTING WALL TO REMAIN
EXISTING LIGHTS TO DEMOLISH
NEW LIGHTS (SEE ELECTRICAL DRAWINGS)
NEW WALL
(F.R.T. PLYWD. WHERE INDICATED)
(F.R.T. PLYWD. WHERE INDICATED)
( + ) POSITIVE PRESSURE
CONSTRUCTION ZONE,
(--) NEGATIVE PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MAT
HEPA EQUIPPED EXHAUST
POLYETHYLENE SHEETING
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
IC
R
A
00-00-00
NEW SIGNAGE (SEE SIGNAGE SCHEDULE)
NEW CONCRETE (SEE STRUCT. DRAWINGS)
(ACCESS POINT)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0 /2
:3
:5 a m
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001A-403a
BLDG 001-LVL 03-DEMO, FLR PLNS & RCPS
TH ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
1/4" = 1'-0"
RM 331-333 - DEMO FLOOR PLAN
PROJECT
NORTH
1/4" = 1'-0"
RM 331-333 - DEMO RCP
PROJECT
NORTH
1/4" = 1'-0"
RM 331-333 - FLOOR PLAN
PROJECT
NORTH
1/4" = 1'-0"
RM 331-333 - RCP
PROJECT
NORTH
1 DEMO. EXIST. DOOR & FRAME.
2 DEMO EXIST. FLOOR FIN. TO EXPOSE SUBSURFACE FLOOR
STRUCT. REMOVE ANY EXIST. SEALER, TOPPING OR BONDING
SUBSTANCE. PREPARE SUBFLOOR IN ACCORD. WITH NEW
FLOORING MANUFACT. FINISH PREPARATION REQUIREMENTS.
3 DEMO. EXIST. BASE. REMOVE EXIST. ADHESIVE & PREPARE
FOR NEW BASE.
4 DEMO EXIST. CLG. SYSTEM INCLUDING SUPPORTING WIRES,
CLIPS, PERIMETER WALL ANGLES & ALL OTHER COMPONENTS.
EXPOSE CLG. O.T.S. ABV.
5 INFILL WALL, PATCH & PAINT TO MATCH EXIST.
6 INSTALL NEW DOOR & FRAME.
7 INSTALL NEW RESILIENT RUBBER BASE @ ROOM PERIM. W/
SEALANT @ THE BTTM.
8 APPLY ANTI-STATIC COATING TO EXPOSED FLOOR. PROVIDE
VINYL REDUCER STRIP @ EXIST. FLOORING TRANSITION.
9 INSTALL F.R.T. PLYWD. OVER WALLS AS NEEDED- PER TYP.
DTL. 3/AE421- TYP.
10 INSTALL PHYSICAL SECURITY @ INT. OF EXIST. WIN.-PER DTL.
1/A603.
11 CONTRACTOR COORD. ROUTING & TERMINATION OF
TEMPORARY VENTILATION & PRESSURIZATION IN
ACCORDANCE W/ SPEC. REQ. & IN COORD. W/ VA C.O.R. &
EXIST. SITE CONDITION CONSTRAINTS.
KEY PLAN
SHEET GENERAL NOTES
1. ALL NEW PRODUCTS & FINISHED SURFACES ARE TO MATCH
EXIST. ADJACENT PRODUCTS & FINISHED SURFACES U.N.O.
2. PATCH & REPAIR FINISHES & FIRE RATINGS OF WALLS,
FLOORS & CEILINGS, TO MATCH EXIST. ADJACENT SURFACES,
WHERE MECH., PLUMBING, ELEC. & TELECOM. ITEMS ARE
DEMO'D.
3. PROTECT FINISHES IN ROOMS ADJACENT TO WORK AREAS &
DO NOT ALTER AREAS & ITEMS NOT INCLUDED IN THE SCOPE.
4. CONTRACTOR IS TO LEAVE FIRE RATING STAMP UNPAINTED &
VISIBLE ON THE NEW INSTALLED F.R.T. PLYWD. SEE DETAIL
5/AE421.
5. REFER TO SHEETS AS101, AS102 & AS103 FOR ICRA REQ. &
TEMP. CONST. BARRIER DETAILS REF. FROM PHASING &
ENLARGED PLANS.
6. PATCH & REPAIR CEILINGS, WALLS & FLOORS WHERE TEMP.
CONST. BARRIERS ARE CONSTRUCTED & REMOVED.
7. PATCH & REPAIR EXIST. CLG. GRID & A.C.T./ G.W.B. CLG.
WHERE NEW WALLS ARE TO BE INSTALLED.
8. PATCH & REPAIR G.W.B. WHERE DOORS ARE DEMO.'D & NEW
DOORS ARE TO BE INSTALLED.
9. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR EXIST. EQUIP., & IT'S ASSOCIATED CONDUIT, WIRE, OR
PIPING IS TO BE DEMO'D OR ARE INTENDED TO REMAIN.
ARCH. SHEET SYMBOLSSHEET KEYNOTES
10. REFER TO MECH., PLUMBING, ELEC. & TELECOM. DRAWINGS
FOR LOCATION & SIZE OF PROPOSED NEW EQUIP., & IT'S
ASSOCIATED CONDUIT, WIRE, OR PIPING.
11. WHERE TEMP. POLYETHYLENE CONST. BARRIERS ARE
INSTALLED, THEY ARE TO BE FULLY TAPED @ THE PERIM. OF
THE ENCLOSURE TO CONTROL WORK AREA PRESSURIZATION
& DUST MIGRATION. UPKEEP TAPED PERIM.
12. WHERE WALLS ENCLOSING T.R.'S DO NOT EXTEND FULLY TO
THE UNDERSIDE OF THE STRUCTURE ABV., CONTRACTOR IS
TO PROVIDE TEMP. POLYETHYLENE BARRIER AS NEEDED IN
CONST. SEQUENCING & ALSO FINAL PERMANENT G.W.B.
ENCLOSURE FROM THE TOP OF EXIST. DISCONTINUOUS
WALLS TO THE UNDERSIDE OF STRUCTURE ABV.
13. CONTRACTOR IS RESPONSIBLE FOR MEANS & METHODS, FOR
SECURING THE WORK AREA/ JOB SITE W/ TEMP. LOCKABLE
BARRIER DURING & AFTER CONST. WORK HOURS. WHERE
NEW OR EXIST. DOORS ARE UTILIZED FOR THIS PURPOSE
THEY ARE TO BE COVERED W/ A PROTECTIVE SURFACE TO
PREVENT FINISH DAMAGE.
14. REFER TO SHEET KEYNOTES, SHEET GENERAL NOTES, ARCH.
SHEET SYMBOLS THIS SHEET, FOR NOTES & SYMBOLS
APPLICABLE TO THE WORK AREA SHOWN.
DEMO FLOOR PLAN NOTES
1. TEMPORARY DOORS MAY BE USED DURING PHASING & WHERE USED THEY ARE REQ'D TO MATCH THE EXIST.
WALL ASSEMBLY'S FIRE RATINGS/DOOR OPENING PENETRATION RATING & PER NFPA 101.
2. REFER TO SHEET AS101 FOR TYP. TEMP. CONSTRUCTION BARRIERS. DESIGNATIONS FOR LEVEL II ICRA USE 4/AS101, FOR LEVEL III ICRA USE 5/AS101 & FOR LVL IV ICRA USE 6/AS101. G.W.B./ MTL. STUD TEMPORARY WALLS ARE TO BE USED IN LIEU OF POLYETHELENE SHOWN IN THE ENLARGED PLAN DETAILS THIS SHEET, WHEN NOTED AS SUCH ON THE PLANS OR WHEN THE DURATION OF TEMP. BARRIER MEETS CRITERIA AS
NOTED ON AS 101 OR AS INDICATED ON THE AS102 TABLE 5 PRECAUTION REQ'D.
FLOOR PLAN NOTES
1. WHEN 'FORM FACTOR' OR OTHER EXCEPTIONS ARE NOTED ON DRAWINGS- DESIGNER IS REFERRING TO EXCEPTIONS NOT MEETING THE VA O.I.T.C. PLANNING GUIDES FOR MINIMUM CLEARANCES OR OTHER DESIGN CRITERIA. VA HAS ACCEPTED THESE EXCEPTIONS & NOTATION IS INCLUDED TO NOTIFY THE VA
ON THESE DOCUMENTS. THERE IS NO ACTION REQ,'D OF THE CONTRACTOR.
Revisions: Date:
T U V W
1217 SF
DATA CENTER
336A
113 SF
OFFICE
336K534 SF
CORRIDOR
217 SF
STAIR
S-3-3
147 SF
TELEPHONE
CLOSET
336J
995 SF
COMPUTER RM
336I
232 SF
COMPUTER
ROOM
NEW TEMPORARY
WALLS & DOORS
UP 0
E X
IS
T
R
A M
P
/2
01c
01c
01c
01c
01c
01c 01c
01c
01c
01c
1' - 1"
0' - 0"
1' - 1"
1' - 2"
1' - 2"
01c
01a
21 SF
CLOSET
SEE MECH. &
TELECOM. FOR NEW
EQUIP.
SEE TELECOM. FOR
EXIST. EQUIP. TO REMAIN
SEE ELEC. FOR
EXIST. EQUIP. TO
REMAIN
SEE ELEC. FOR EXIST.
EQUIP. TO REMAIN
SEE ELEC. FOR
EXIST. EQUIP. TO
REMAIN
001A-403j
DN
A L
IG
N
336B.1
001A-403j
SEE SHEET
001A-403g FOR
HANDRAIL
LOCATIONS
T U V W
1217 SF
DATA CENTER
336A
113 SF
OFFICE
336K
534 SF
CORRIDOR
217 SF
STAIR
S-3-3
O.T.S.
995 SF
COMPUTER RM
336I
147 SF
TELEPHONE
CLOSET
336J
232 SF
COMPUTER
ROOM
O.T.S.
O.T.S.
O.T.S.
NEW TEMPORARY
WALLS AND DOORS
SEE ELEC. &
MECH. FOR NEW
EQUIP. BLW.
SEE ELEC. &
MECH. FOR NEW
EQUIP. BLW.
SEE MECH. FOR
NEW EQUIP.
SEE MECH. FOR
EXIST. EQUIP. TO
REMAIN
SEE MECH. FOR
EXIST. EQUIP. TO
REMAIN
001A-403j
SEE ELEC. FOR
NEW EQUIP. SEE ELEC. FOR
NEW EQUIP.
SEE ELEC. FOR
NEW EQUIP.
SEE ELEC. FOR
NEW EQUIP.
ENLARGED AREA
KEY AREA SHOWN
PROJECT
NORTH
TO DEMOLISH
X X
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
EXISTING WALL TO DEMOLISH
EXISTING WALL TO REMAIN
EXISTING LIGHTS TO DEMOLISH
NEW LIGHTS (SEE ELECTRICAL DRAWINGS)
NEW WALL
(F.R.T. PLYWD. WHERE INDICATED)
(F.R.T. PLYWD. WHERE INDICATED)
( + ) POSITIVE PRESSURE
CONSTRUCTION ZONE,
(--) NEGATIVE PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONSTRUCTION TACKY MAT
HEPA EQUIPPED EXHAUST
POLYETHYLENE SHEETING
FIRE WALL (2 HOUR MINIMUM)
1 HOUR FIRE BARRIER
2 HOUR FIRE BARRIER
SMOKE PARTITION
IC
R
A
00-00-00
NEW SIGNAGE (SEE SIGNAGE SCHEDULE)
NEW CONCRETE (SEE STRUCT. DRAWINGS)
(ACCESS POINT)
CORNER GUARDS AND WALL PROTECTION
HANDRAIL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E: ARCHITECT
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE: ARCHITECTURE
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/5
/2
:4
:2
P M
A u to d e s k D o c s /4
-2
-7
V
A V
T W h it e
R iv e r
J u n c ti o n E
H R
M
IU
/V A
W R
A
R S
D B
.r v t
001A-403c
BLDG 001-DATA CENTER-ENLARGED PHASE 01
PROP. FLR PLN & RCP
TH ME
100% CONSTRUCTION
DOCUMENTS
01/16/2026
405-22-700EHRM INFRASTRUCTURE
UPGRADES - WHITE RIVER
VA VT WHITE RIVER JUNCTION
163 VETERANS DR, WHITE RIVER JUNCTION, VT 05009
1/4" = 1'-0"
DATA CENTER - PHASE 01 FLOOR PLAN
1/4" = 1'-0"
DATA CENTER - PHASE 01 RCP
1 CONSTRUCT NEW RAISED FLOOR WITH ANTI-STATIC FLOOR
FINISH.
2 CONSTRUCT NEW WALL.
3 INSTALL NEW DOOR & FRAME.
PROJECT
NORTH
PROJECT
NORTH
SHEET GENERAL NOTES
KEY PLAN
1. ALL NEW PRODUCTS & FINISHED SURFACES ARE TO MATCH
EXIST. ADJACENT PRODUCTS & FINISHED SURFACES U.N.O.
2. PATCH & REPAIR FINISHES & FIRE RATINGS OF WALLS,
FLOORS & CEILINGS, TO MATCH EXIST. ADJACENT SURFACES,
WHERE MECH., PLUMBING, ELEC. & TELECOM. ITEMS ARE
DEMO'D.
3. PROTECT FINISHES IN ROOMS ADJACENT TO WORK AREAS &
DO NOT ALTER AREAS & ITEMS NOT INCLUDED IN THE SCOPE.
4. CONTRACTOR IS TO LEAVE FIRE RATING STAMP UNPAINTED &
VISIBLE ON THE NEW INSTALLED F.R.T. PLYWD. SEE DETAIL
5/AE421.
5. REFER TO SHEETS AS101, AS102 & AS103 FOR ICRA REQ. &
TEMP. CONST. BARRIER DETAILS REF. FROM PHASING &
ENLARGED PLANS.
6. PATCH & REPAIR CEILINGS, WALLS & FLOORS WHERE TEMP.
CONST. BARRIERS ARE CONSTRUCTED & REMOVED.
7. PATCH & REPAIR EXIST. CLG. GRID & A.C.T./ G.W.B. CLG.
WHERE NEW WALLS ARE TO BE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .