This document is an Addendum No. 3 for a telecommunications infrastructure upgrade project (Project Number 504-21-700) for the Electronic Health Record Modernization (EHRM) at the Amarillo VA Medical Center. The addendum provides detailed revisions to construction drawing documents, specifically focusing on telecommunications infrastructure modifications across multiple buildings. Key changes include reducing existing work area outlets from (3) or (4) ports to (2) new Cat 6a cables, updating cable schedules with a new "PORT-QTY-NEW" column, and correcting data device and circuit schedules for various telecom rooms (TR), particularly in Building 29.

The document covers telecommunications infrastructure for multiple building levels, with each telecom room (TR) having specific details about work area outlets (WAO), port quantities, and expansion capacity. For example, TR #1399 has 284 WAO out of a total 720 WAO available, with 538 total port quantities and a 60.5% expansion capacity. The addendum emphasizes maintaining maximum cable lengths under 328 feet, providing a 10% allowance for new data ports, and ensuring contractors coordinate with the VA Contracting Officer's Representative (COR) for any deviations from the design documents.

View the file

Other files

File Type Posted
36C77624R0084 0015.docx DOCX document
36C77624R0084 0014.docx DOCX document
36C77624R0084 0013.docx DOCX document
Att 28 - 504-21-700.EHRM.Amarillo.Add4.20250401.pdf PDF
PPQ - Amarillo.docx DOCX document
Att 22 - 00 41 13.10 - Construction Estimate Breakdown Template.xlsx XLSX spreadsheet
36C77624R0084 0012.docx DOCX document
RFP 36C77624R0084 3-28-2025.docx DOCX document
Att 1 Construction SOW Revised 504-21-700 - 3-27-25.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
36C77624R0084 0006 SF 30.docx DOCX document
0011 - DBA Wage Rates - Potter County - 3-14-25.pdf PDF
36C77624R0084 0011.pdf PDF
36C77624R0084 0010.docx DOCX document
36C77624R0084 0009.docx DOCX document
36C77624R0084 0008.docx DOCX document
Att 26-504-21-700 EHRM Amarillo.ADD 2-13-25.pdf PDF
36C77624R0084 0007.docx DOCX document
Att 24-504-21-700 EHRM Amarillo.ADD-1.20250128.pdf PDF
Att 25- Amendment 0006-updated RFP 36C77624R0084.docx DOCX document
Att 20-Updated Wage Determ 1-3-25 Potter County TX.pdf PDF
Att 23-S05-Vendor Questions and RFIs Rspns Final.xlsx XLSX spreadsheet
Prebid Site Visit Sign-in 1-6-25 n 1-17-25 combined.pdf PDF
36C77624R0084 0005.docx DOCX document
36C77624R0084 0004.docx DOCX document
36C77624R0084 0003.docx DOCX document
36C77624R0084 0002.docx DOCX document
36C77624R0084 0001.docx DOCX document
Att 13-EHRM Ama IFC Bld26 Bld28 Bld29.zip ZIP file
Att 2-Limitations on Subcont - Constr.pdf PDF
Att 9-EHRM Ama IFC Bld1 Bld4.zip ZIP file
Att 22-Division Cost Breakdown.xlsx XLSX spreadsheet
Att 6- OIT-InfrastrucStdTelecomSpaces-AppxA B07.pdf PDF
Att 19-Asbestos Insp Rpt.zip ZIP file
Att 10-EHRM Ama IFC Bld8.zip ZIP file
Att 1 Construction SOW Prj 504-21-700 11.13.24.pdf PDF
Att 8-Amarillo_EHRM.SPEC.part 2.zip ZIP file
Att 21-PPQ.docx DOCX document
Att 5-504-23-053 EHRM PCRA.pdf PDF
36C77624R0084_1 tradeoffs Final.pdf PDF
Att 20-WD-Amarillo verified 12-17-24.pdf PDF
Att 11-EHRM Ama IFC Bld7 Bld9.zip ZIP file
Att 3-ICRA DRAFT EHRM 12 14 2023 LEVEL 4.pdf PDF
Att 18-EHRM Ama IFC SITE.20241022.zip ZIP file
Att 15-EHRM Ama IFC Bld44 Bld45 Bld46.zip ZIP file
Att 16-EHRM Ama IFC Bld48 Bld49 Bld53.zip ZIP file
Att 12-EHRM Ama IFC Bld10 Bld11 Bld12 Bld14.zip ZIP file
Att 7-Amarillo_EHRM.SPEC.part 1.zip ZIP file
Att 4-EHRM Prj Stnd Compl Memo.pdf PDF
Att 17-EHRM Ama IFC Bld54.zip ZIP file
Show 40 more

Latest 50 of 51 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CVE Verified Service-Disabled Veteran-Owned Small Business

TRIPLE C – THE A&E GROUP

OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE

410 Grand Avenue, Suite 201C � Laramie, Wyoming 82070 � Telephone: (307) 460-2054 � Fax: (307) 460-2053

Addenda

Project: 504-21-700 EHRM Infrastructure Upgrades

Subject: Addenda No. 3

Date: 03/06/2025

Revisions: Construction drawing documents for project 504-21-700 EHRM Infrastructure Upgrades have been revised. In response to Technical Questions, the following additional clarifying information is provided:

1. Existing work area outlets with (3) or (4) existing data ports shall be reduced and provided with

(2) new ports (2) new cat 6a cables. In response to Bidders inquires to clarify the cable quantity, cable schedules located on xxT-700 series sheets are updated to include a “PORT-QTY-NEW” column that identifies the required cable quantity at each WAO location.

2. Appending “DATA DEVICE AND CIRCUIT SCHEDULE” for each TR, “TOTAL PORT QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE” quantities have been updated to reflect the sum of the “PORT-QTY-NEW” column.

3. Building 29: Corrected “DATA DEVICE AND CIRCUIT SCHEDULES”, added Sheet 29T-703, and updated drawing index on 29G-001.

Specification Revisions:

NONE

Drawing Sheet Revisions:

Sheet Number

Revision

Number Description of / Reason for Change

01T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

01T-702 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

01T-703 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

01T-704 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

01T-705 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

04T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

07T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

08T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

09T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

10T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

11T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

12T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

14T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

26T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

28T-701A 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

28T-701B 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

28T-702 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

28T-703 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

28T-704 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

29G-001 02 Added Sheet 29T-703 to Drawing Index.

29T-701 02 Corrected “DATA DEVICE AND CIRCUIT SCHEDULES” and added “PORT-

QTY-NEW” column and updated “TOTAL PORT QUANTITIES” and

“TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

29T-702 02 Corrected “DATA DEVICE AND CIRCUIT SCHEDULES” and added “PORT-

QTY-NEW” column and updated “TOTAL PORT QUANTITIES” and

“TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

29T-703 02 Corrected “DATA DEVICE AND CIRCUIT SCHEDULES” and added “PORT-

QTY-NEW” column and updated “TOTAL PORT QUANTITIES” and

“TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

33T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

34T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

35T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

36T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

44T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

45T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

46T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

48T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

48T-702 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

49T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

53T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

QUANTITIES” and “TOTAL PORT QUANTITIES WITH 10% ALLOWANCE”.

54T-701 02 Added “PORT-QTY-NEW” column and updated “TOTAL PORT

Attachments:

01T-701

01T-702

01T-703

01T-704

01T-705

04T-701

07T-701

08T-701

09T-701

10T-701

11T-701

12T-701

14T-701

26T-701

28T-701A

28T-701B

28T-702

28T-703

28T-704

29G-001

29T-701

29T-702

29T-703

33T-701

34T-701

35T-701

36T-701

44T-701

45T-701

46T-701

48T-701

48T-702

49T-701

53T-701

54T-701

Notes

NONE.

TELECOM ROOM

174 SF

LEGEND

TR #1199 - PROPOSED AREA OF SERVICE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 325 N. Saint Paul Street, Suite 3100 Dallas, TX 75201

MAT PERKINS

469-330-9710

STAMP

UPDATED AND RE-ISSUED FOR CONSTRUCTION 09/18/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 11/02/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 10/25/2024

Au to de sk

D oc s:

//5

-2

1-

EH

R M

In fra st ru ct ur e U pg ra de s at A m ar illo V

AM

C

/5

-2 1-

0.

EH

R

M .A m ar illo .B

.M

EP

.rv t

-0 3-

2:

:5

01T-701

TELECOMMUNICATION SCHEDULES 504-21-700

B01

11/02/2023 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

6010 Amarillo Blvd. West, Amarillo, TX 79106

DATA DEVICE AND CIRCUIT SCHEDULE - TR #1199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING

OUTLET DESIGNATOR -

EXISTING

PORT QTY-

NEW MOUNTING RACK ID

71'

1164-A 3 (V10)(D19 D20) 2 WALL TR01-1199-1

66'

1164-B 4 (ASSUMED) 2 WALL TR01-1199-1

73'

1162-A 4 (1)(2)(3)(4) 2 WALL TR01-1199-1

71'

1162-B 3 (V29)(D57 D58) 2 WALL TR01-1199-1

84'

1160-A 4 (ASSUMED) 2 WALL TR01-1199-1

89'

S2-1-AP-A 1 (AMAAP18-1-5) 1 CLG TR01-1199-1

42'

1A-C4-AP-C 1 (AMAAP22-1-1) 1 CLG TR01-1199-1

52'

1A-C4-AP-B 1 (MOTEM) 1 CLG TR01-1199-1

86'

1A-C4-AP-A 1 (MOTEM) 1 CLG TR01-1199-1

103'

1166-A 1 (TELEPHONE) 1 WALL TR01-1199-1

109'

1166-AP-A 1 (AMAAP23-1-1) 1 CLG TR01-1199-1

73'

1165-B 3 (V1)(D2 D3) 2 WALL TR01-1199-1

71'

1165-AP-A 1 (AMAAP32-1-1) 1 CLG TR01-1199-1

69'

1165-A 3 (UNLABELED) 2 WALL TR01-1199-1

123'

1A-C2-AP-A 1 (AMAAP16-1-1) 1 CLG TR01-1199-1

145'

1134-AP-A 1 (AMAAP24-1-1) 1 CLG TR01-1199-2

154'

1125-A 3 (V24)(D47 D48) 2 WALL TR01-1199-1

168'

1125-B 3 (V25)(D49 D50) 2 WALL TR01-1199-1

152'

1123-AP-A 1 (AMAAP14-1-1) 1 CLG TR01-1199-1

154'

1123-A 4 (1123A)(B27)(D53 D54) 2 WALL TR01-1199-1

157'

1123A-A 3 (9V)(1123A-A)(UNLABELED) 2 WALL TR01-1199-1

147'

1A-C5-AP-D 1 (MODEM) 1 CLG TR01-1199-1

184'

1A-C5-AP-C 1 (SPECTRALINK 1-1-4) 1 CLG TR01-1199-1

193'

1A-C5-AP-B 1 (UNLABELED) 1 CLG TR01-1199-1

162'

1124-B 3 (25V)(85D 86D) 2 WALL TR01-1199-1

164'

1124-AP-A 1 (AMAAP13-1-1) 1 CLG TR01-1199-1

163'

1124-A 3 (UNLABELED)(D51 D52) 2 WALL TR01-1199-1

168'

1120-AP-A 1 (AMAAP12-1-1) 1 CLG TR01-1199-1

229'

1110A-A 3 (UNLABELED)(D095 D096) 2 WALL TR01-1199-1

236'

1110A-B 2 (D113 D114) 2 WALL TR01-1199-1

231'

1110A-AP-A 1 (AMAAP04-1-1) 1 CLG TR01-1199-1

246'

1106A-A 3 (V46)(D91 D92) 2 WALL TR01-1199-1

237'

1106A-B 3 (32V)(100D)(UNLABELED) 2 WALL TR01-1199-1

244'

1106B-A 3 (V33)(D101 D102) 2 WALL TR01-1199-1

246'

1106B-B 3 (31V)(97D 98D) 2 WALL TR01-1199-1

260'

1106-AP-B 1 (AMAAP10-1-1) 1 CLG TR01-1199-1

276'

1106D-A 3 (30V)(95D 96D) 2 WALL TR01-1199-1

281'

1106D-B 3 (29V)(93D 94D) 2 WALL TR01-1199-1

280'

1106E-A 3 (24V)(83D 84D) 2 WALL TR01-1199-1

254'

1106-A 3 (V44)(D87 D88) 2 WALL TR01-1199-1

254'

1107-A 3 (V50)(D99 D100) 2 WALL TR01-1199-1

255'

1107-B 3 (V45)(D89 D90) 2 WALL TR01-1199-1

233'

1106-AP-A 1 (AMAAP11-1-1) 1 CLG TR01-1199-1

238'

1109-A 3 (V51)(D101 D102) 2 WALL TR01-1199-1

239'

1109-B 3 (V47)(D93 D94) 2 WALL TR01-1199-1

239'

1112-A 3 (V034)(D103 D104) 2 WALL TR01-1199-1

221'

1112-B 1 (111.10V) 2 WALL TR01-1199-1

218'

1112-C 3 (1111.8V)(9D 10D) 2 WALL TR01-1199-1

277'

1110A-AP-A 1 (AMAAP011-1-1) 1 CLG TR01-1199-1

277'

1100-A 3 (UNLABELED) 2 WALL TR01-1199-1

248'

1105-A 4 (UNLABELED) 2 WALL TR01-1199-1

253'

1105-AP-A 1 (AMAAP03-1-1) 1 CLG TR01-1199-1

267'

1105-B 3 (V42)(27D 28D) 2 WALL TR01-1199-1

256'

1105-C 3 (15V)(29D 30D) 2 WALL TR01-1199-1

260'

1103-A 3 (V28)(D91 D92) 2 WALL TR01-1199-1

270'

1103-B 3 (V41)(D81 D82) 2 WALL TR01-1199-1

275'

1101-A 3 (V49)(D97 D98) 2 WALL TR01-1199-1

278'

1101-B 3 (V40)(D79 D80) 2 WALL TR01-1199-1

271'

1101-C 3 (V27)(D89 D90) 2 WALL TR01-1199-1

211'

1A-C5-AP-A 1 (AMAAP05-1-1) 1 CLG TR01-1199-1

238'

1114-A 4 (ASSUMED) 2 WALL TR01-1199-1

241'

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

COMMENTS:

CONTRACTOR SHALL NOT EXCEED CABLE TRAY MANUFACTURERS

MAX LOADING CAPACITY BASED ON THE SUPPORT SPAN SPACING

CONTRACTOR SHALL PROVIDE ADDITIONAL SUPPORT AS REQUIRED

TO NOT EXCEED MAXIMUM LOADING CAPACITY.

CONTRACTOR SHALL NOT EXCEED 40 % FILL CAPACITY FOR CABLE

TRAY.

CONTRACTOR SHALL PROVIDE GALVANIZED FINISHES FOR ALL CABLE

TRAY FITTINGS AND ASSOCIATED COMPONENTS.

CABLE TRAY SHALL BE A WIRE MESH SYSTEM IN ACCORDANCE WITH

SPECIFICATION SECTION 27 05 33.

ALL CABLE TRAYS ASSEMBLY SHALL BE PROVIDED BY A SINGLE

MANUFACTURER

CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS SHOWING

PROPOSED ROUTE AND SIZE PRIOR TO BEGINNING WORK AND

PROVIDE CALCULATIONS SHOWING PROPOSED FILL PERCENTAGE

AND LOAD (LBS/FT) WITH SUPPORT SPACING.

CONTRACTOR SHALL PROVIDE SEISMIC BRACING AS REQUIRED BY 13

05 41 AND SUBMIT DETAILS AND CALCULATIONS PRIOR TO

COMMENCING WORK.

CABLE TRAY SHALL BE INSTALLED PER MANUFACTURER'S REQUIRED

INSTALLATION PROCEDURES.

AS A STANDARD, ALL INTER-BUILDING PATHWAYS SHALL HAVE A

MINIMUM OF 20% AVAILABLE CAPACITY AT THE SCHEDULED END OF

THE PROJECT.

CABLE TRAY SCHEDULE

LEVEL ESTIMATED LENGTH

LEVEL 1 537'

LEVEL 2 570'

LEVEL 3 651'

LEVEL 4 570'

LEVEL 5 126'

Grand total 2452'

CABLE TRAY SIZE MAX. # OF CAT 6A CABLES

6"x12" 6"x16" 6"x24"

195 CABLES

292 CABLES

390 CABLES

CABLE TRAY CAPACITY

SCALE: 1/32" = 1'-0"F7

TELECOMMUNICATION PLAN - FIRST

LEVEL - WAO COUNTS - TR #1199

A.

B.

C.

D.

1.

2.

3.

4.

5.

6.

A.

B.

C.

D.

1.

2.

3.

4.

5.

2.1 CABLE TRAY.

Design. Wire basket with tray insert. Maximum 2” x 4” wire mesh construction.

Constructed of round, smooth wire with continuous top side to minimize cable sheath damage.

Finish. Coated to prevent rust.

Size. Cable tray shall be sized to hold the maximum expected cable load at not more than 40% fill and not more than 6” maximum cable depth.

Accessories. Provide and install the following components and accessories as necessary to achieve the design:

Overhead mounting equipment (thread-rod, unistrut, nuts, washers, etc.) suitable for the supporting structural elements.

Tray section splicing hardware.

Tray insert.

Cable waterfalls.

Ground strap kits.

Bend radius limiters.

2.2 FIBER OPTIC CABLE RACEWAY.

Design. Raceway system shall be a modular system of channels, fittings, and brackets, able to be assembled with couplers. Fittings for cable spillout shall maintain a minimum 2” bend radius.

Materials. Raceway shall be constructed of rigid PVC and ABS plastics.

Size. Raceway shall be nominally sized 4”x4”.

Accessories. Provide and install the following components and accessories as necessary to achieve the design:

Overhead mounting equipment (thread-rod, unistrut, nuts, washers, etc.) suitable for the supporting structural elements.

Hinged channel covers.

Raceway section couplers.

Channel corners and intersections.

Spillway fittings.

DATA DEVICE AND CIRCUIT SCHEDULE - TR #1199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING

OUTLET DESIGNATOR -

EXISTING

PORT QTY-

NEW MOUNTING RACK ID

1116-A 3 (V53)(D105 D106) 2 WALL TR01-1199-1

242'

1116-B 2 (UNLABELED) 2 WALL TR01-1199-1

243'

1113-A 2 (UNLABELED) 2 WALL TR01-1199-1

246'

1113-B 3 (1111.4V)(3D 4D) 2 WALL TR01-1199-1

246'

1113-C 3 (1113-A)(1D 2D) 2 WALL TR01-1199-1

255'

1115-D 3 (1105-C)(15D 16D) 2 WALL TR01-1199-1

249'

1115-E 3 (V57)(1105-D)(D113 D114) 2 WALL TR01-1199-1

244'

1115-F 2 (UNLABELED) 2 WALL TR01-1199-1

244'

1115-G 3 (V56)(D111 D112) 2 WALL TR01-1199-1

274'

1115-A 3 (11V)(13D 14D) 2 WALL TR01-1199-1

274'

1115-B 3 (V54)(D107 D108) 2 WALL TR01-1199-1

276'

1115-C 3 (V55)(1105-A)(D109 D110) 2 WALL TR01-1199-1

162'

1136-A 3 (V20)(1136A)(D39 D40) 2 WALL TR01-1199-2

171'

1138-A 3 (V23)(D45 D46) 2 WALL TR01-1199-2

193'

1140-A 3 (V18)(D35 D36) 2 WALL TR01-1199-2

193'

1140-C 3 (V17)(D33 D34) 2 WALL TR01-1199-2

195'

1140-B 2 (UNLABELED) 2 WALL TR01-1199-2

185'

1131-A 1 (UNLABELED) 2 WALL TR01-1199-2

167'

1131B-AP-A 1 (AMAAP25-1-1) 1 CLG TR01-1199-2

190'

1158B-A 4 (12V)(23D 24D) 2 WALL TR01-1199-2

176'

1158B-B 2 (21V)(D41 D42) 2 WALL TR01-1199-2

203'

1156-A 2 (109D 110D) 2 WALL TR01-1199-2

234'

1152-A 4 (V15)(D29 D30) 2 WALL TR01-1199-2

237'

1154-A 3 (V14)(D37 D38) 2 WALL TR01-1199-2

237'

1154-B 3 (V13)(D35 D36) 2 WALL TR01-1199-2

253'

1150-A 4 (ASSUMED) 2 WALL TR01-1199-2

259'

1146-A 1 (V30) 2 WALL TR01-1199-2

270'

1146-B 2 (D59 D60) 2 WALL TR01-1199-2

269'

1146-AP-A 1 (AMASAP28-1-1) 1 CLG TR01-1199-2

275'

1144-A 3 (V35)(UNLABELED) 2 WALL TR01-1199-2

280'

1144-B 3 (V14)(1144A)(D27 D28) 2 WALL TR01-1199-2

278'

1142-A 3 (1142A)(D65 D66) 2 WALL TR01-1199-2

288'

1135-AP-A 1 (AMAAP27-1-1) 1 CLG TR01-1199-2

277'

1137-A 1 (UNLABELED) 2 WALL TR01-1199-2

287'

1137-B 2 (D73 D74) 2 WALL TR01-1199-2

266'

1139-A 1 (V31) 2 WALL TR01-1199-2

264'

1141-A 1 (POKE-THRU FLOOR) 2 FLOOR TR01-1199-2

256'

1141-B 1 (UNLABELED) 2 WALL TR01-1199-2

265'

1141-AP-A 1 (AMAAP29-1-1) 1 CLG TR01-1199-2

253'

1143-A 2 (D68 D67) 2 WALL TR01-1199-2

243'

1143-B 1 (V34) 2 WALL TR01-1199-2

242'

1145-A 2 (D71 D72) 2 WALL TR01-1199-2

252'

1158-A 2 (111.6V)(5D 6D) 2 WALL TR01-1199-2

253'

1158-AP-A 1 (AMAAP03-1-1) 1 CLG TR01-1199-2

223'

S3-1-AP-A 1 (AMAAP33-1-1) 1 CLG TR01-1199-2

244'

1153-A 4 (ASSUMED) 2 WALL TR01-1199-2

249'

1153-B 4 (ASSUMED) 2 WALL TR01-1199-2

250'

1153-C 4 (ASSUMED) 2 WALL TR01-1199-2

241'

1153-D 4 (ASSUMED) 2 WALL TR01-1199-2

239'

1155A-A 4 (ASSUMED) 2 WALL TR01-1199-2

240'

1155A-B 4 (ASSUMED) 2 WALL TR01-1199-2

229'

1155A-C 4 (ASSUMED) 2 WALL TR01-1199-2

232'

1155A-D 4 (ASSUMED) 2 WALL TR01-1199-2

242'

1155-A 3 (TELEPHONE)(1D 2D) 2 WALL TR01-1199-2

243'

1155-B 3 (V3)(D5 D6) 2 WALL TR01-1199-2

250'

1155-C 1 (UNLABELED) 2 WALL TR01-1199-2

240'

1155-AP-A 1 (AMAAP34-1-1) 1 CLG TR01-1199-2

262'

1155-AP-B 1 (AMAAP15-1-1) 1 CLG TR01-1199-2

265'

1155-D 3 (V5)(1155A)(D9 D10) 2 WALL TR01-1199-2

276'

1155C-A 3 (V12)(D23 D24) 2 WALL TR01-1199-2

262'

1155C-B 3 (TELEPHONE)(1D 2D) 1 WALL TR01-1199-2

DATA DEVICE AND CIRCUIT SCHEDULE - TR #1199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING

OUTLET DESIGNATOR -

EXISTING

PORT QTY-

NEW MOUNTING RACK ID

258'

1155C-C 3 (V13)(D25 D26) 2 WALL TR01-1199-2

266'

1155-J 3 (V8)(D15 D16) 2 WALL TR01-1199-2

279'

1155-H 3 (V9)(D17 D18) 2 WALL TR01-1199-2

286'

1155-G 3 (TELEPHONE)(1D 2D) 1 WALL TR01-1199-2

288'

1155-F 3 (18V)(33D 34D) 2 WALL TR01-1199-2

285'

1155-E 3 (V6)(D11 D12) 2 WALL TR01-1199-2

42'

1199-CAM-01 - NEWLY INSTALLED DEVICE,

NOT EXISTING

1 WALL TR01-1199-1

279'

1139-B 2 (D61 D62) 2 WALL TR01-1199-1

261'

1155B-A 3 (TELEPHONE)(1D 2D) 1 WALL TR01-1199-1

263'

1155B-B 2 (UNLABELED) 2 WALL TR01-1199-1

270'

1155B-C 3 (V11)(1155B-A)(D21 D22) 2 WALL TR01-1199-1

271'

1155B-D 2 (112A) 2 WALL TR01-1199-1

269'

1155B-E 3 (7261)(1D 2D) 2 WALL TR01-1199-1

32'

1199-A - NEWLY INSTALLED DEVICE,

NOT EXISTING

2 WALL TR01-1199-1

236'

1111-A 1 (TELEPHONE) 1 WALL TR01-1199-1

Grand total: 137

WAO CAPACITY FOR TR #1199

137 WAO TOTAL

480 WAO AVAILABLE

71.5% EXPANSION CAPACITY

240 TOTAL PORT QUANTITIES

264 TOTAL PORT QUANTITIES WITH 10% ALLOWANCE

1.

2.

3.

4.

5.

6.

7.

8.

9.

CABLING COMMENTS:

MAXIMUM ALLOWABLE CABLE LENGTH SHALL NOT EXCEED 100 METERS / 328 FEET.

WHEREVER POSSIBLE A MAXIMUM OF 260 FEET HAS BEEN UTILIZED TO ALLOW FOR FUTURE EXPANSION/SLACK LOOP.

WHILE ALL POSSIBLE DUE DILIGENCE WAS PERFORMED THE BIDDERS ARE REQUIRED TO PROVIDE A 10% ALLOWANCE FOR NEW DATA PORTS. ALL DEVIATIONS FROM THE DESIGN DOCUMENTS FOR LOCATIONS AND QUANTITIES OF DATA PORTS ARE REQUIRED TO BE VERIFIED BY THE VA COR AND A/E. AS AN EXAMPLE, IF 100 DATA DROPS WERE IDENTIFIED AND DOCUMENTED IN A BUILDING, THE CONTRACTOR SHALL BID 110 DATA DROPS AND CABLE, CONNECTION, TESTING, AND LABELING FOR THAT BUILDING. DURING THE COURSE OF THE INSTALLATION THE CONTRACTOR SHALL IDENTIFY ANY ADDITIONAL DATA PORTS AND ANY DATA DROPS NOT FOUND TO ENSURE THE AGGREGATE SUM IS CAPTURED IN THE RECORD DRAWINGS AND THE OWNER HAS AN ACCURATE COUNT AT THE END OF THE PROJECT.

"PORT QTY" LISTED IN TELECOMMUNICATION SCHEDULES ARE EXISTING AND NEW QUANTITIES.

1-RACK TR SOLUTIONS CAN HOLD UP TO 144 WAO (WORK AREA OUTLETS).

2-RACK TR SOLUTIONS CAN HOLD UP TO 240 WAO (WORK AREA OUTLETS).

3-RACK TR SOLUTIONS CAN HOLD UP TO 480 WAO (WORK AREA OUTLETS).

4-RACK TR SOLUTIONS CAN HOLD UP TO 720 WAO (WORK AREA OUTLETS).

WHEN CABLES ARE SPLIT FOR VOICE, 2 NEW CABLES WILL BE PROVIDED.

KEYNOTES:

EXISTING WORK AREA OUTLETS WITH (3)OR(4)EXISTING DATA PORTS SHALL BE REDUCED AND PROVIDED WITH (2)NEW PORTS (2)NEW CAT 6a CABLES.COORDINATE

WITH OWNER PRIOR TO REDUCTION AT EACH LOCATION.1

Revisions: Date:

2-ADDENDUM 2 03/06/2025

174 SF

LEGEND

TR #2199 - PROPOSED AREA OF SERVICE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 325 N. Saint Paul Street, Suite 3100 Dallas, TX 75201

MAT PERKINS

469-330-9710

STAMP

UPDATED AND RE-ISSUED FOR CONSTRUCTION 09/18/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 11/02/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 10/25/2024

Au to de sk

D oc s:

//5

-2

1-

EH

R M

In fra st ru ct ur e U pg ra de s at A m ar illo V

AM

C

/5

-2 1-

0.

EH

R

M .A m ar illo .B

.M

EP

.rv t

-0 3-

2:

:5

01T-702

TELECOMMUNICATION SCHEDULES 504-21-700

B01

11/02/2023 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

6010 Amarillo Blvd. West, Amarillo, TX 79106

DATA DEVICE AND CIRCUIT SCHEDULE - TR #2199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW PORT QTY - EXISTING

OUTLET DESIGNATOR -

EXISTING PORT QTY- NEW MOUNTING RACK ID

236'

2131-A 3 (UNLABELED) 2 FLOOR TR01-2199-2

248'

2131-B 3 (16C)(16B)(16A)(D295) 2 FLOOR TR01-2199-2

69'

2150-A 3 (V86)(D171)(D172) 2 WALL TR01-2199-1

64'

2150-B 3 (V27)(D314)(D315) 2 WALL TR01-2199-1

59'

2150-AP-A 1 (AMAAP15-1-2) 1 CLG TR01-2199-1

64'

2152-A 4 (ASSUMED) 2 WALL TR01-2199-1

83'

2151-A 3 (V82)(163)(164) 2 WALL TR01-2199-1

91'

2151-B 3 (V140)(D271)(D272) 2 WALL TR01-2199-1

79'

2A-C2-AP-A 1 (AMAAP14-1-2) 1 CLG TR01-2199-1

92'

2149-A 4 (ASSUMED) 2 WALL TR01-2199-1

91'

2149-B 4 (ASSUMED) 2 WALL TR01-2199-1

82'

2149-C 4 (ASSUMED) 2 WALL TR01-2199-1

76'

2113E-A 4 (ASSUMED) 2 WALL TR01-2199-1

71'

2153-A 2 (UNLABELED) 2 WALL TR01-2199-1

72'

2153-B 3 (V87)(D173)(D174) 2 WALL TR01-2199-1

64'

2153-AP-A 1 (AMAAP16-1-2) 1 CLG TR01-2199-1

67'

2153-C 3 (V88)(D175)(UNLABELED) 2 WALL TR01-2199-1

142'

2121-A 3 (V40)(D77)(D79) 2 WALL TR01-2199-1

138'

2121-B 3 (V39)(D79)(D81) 2 WALL TR01-2199-1

158'

2119-A 3 (V25)(D63)(D64) 2 WALL TR01-2199-1

164'

2117-A 3 (V30)(D59)(D60) 2 WALL TR01-2199-1

160'

2117-B 2 (UNLABELED) 2 WALL TR01-2199-1

172'

2115-A 3 (V28)(D55)(D56) 2 WALL TR01-2199-1

169'

2115-B 2 (UNLABELED) 2 WALL TR01-2199-1

164'

2115-AP-A 1 (AMAAP19-1-2) 1 CLG TR01-2199-1

188'

2122-A 3 (V41)(D81)(D82) 2 WALL TR01-2199-1

163'

2120-A 2 (UNLABELED) 2 WALL TR01-2199-1

166'

2120-B 3 (UNLABELED) 2 WALL TR01-2199-1

173'

2120-C 3 (V33)(D65)(D66) 2 WALL TR01-2199-1

172'

2120-D 3 (UNLABELED)(D67)(D68) 2 WALL TR01-2199-1

175'

2120-E 2 (UNLABELED) 2 WALL TR01-2199-1

184'

2120-F 3 (UNLABELED)(D69)(D70) 2 WALL TR01-2199-1

182'

2120-G 3 (V38)(D74)(D76) 2 WALL TR01-2199-1

180'

2120-H 2 (UNLABELED) 2 WALL TR01-2199-1

172'

2120-J 3 (V37)(D73)(D75) 2 WALL TR01-2199-1

164'

2120-K 3 (V36)(D71)(D72) 2 WALL TR01-2199-1

162'

2120-AP-A 1 (AMAAP18-1-2) 1 CLG TR01-2199-1

181'

2118-A 2 (D118)(D119) 2 WALL TR01-2199-1

174'

2118-B 3 (V31)(D61)(D62) 2 WALL TR01-2199-1

196'

2116-A 4 (ASSUMED) 2 WALL TR01-2199-1

262'

2111A-A 3 (V25)(D49)(D50) 2 WALL TR01-2199-1

283'

2111B-A 3 (V48)(D391)(D392) 2 WALL TR01-2199-1

292'

2111C-A 3 (2130.5V)(3D)(4D) 2 WALL TR01-2199-1

286'

2111C-B 3 (V26)(D51)(D52) 2 WALL TR01-2199-1

224'

2111-AP-A 1 (AMAAP26-1-2) 1 CLG TR01-2199-1

283'

2111-A 3 (V27)(D53)(D54) 2 WALL TR01-2199-1

282'

2111-AP-B 1 (AMAAP27-1-2) 1 CLG TR01-2199-1

249'

2111-B 3 (31V)(D325)(D326) 2 WALL TR01-2199-1

247'

2111-C 3 (32V)(D327)(D328) 2 WALL TR01-2199-1

235'

2112E-A 4 (ASSUMED) 2 WALL TR01-2199-1

239'

2112D-A 3 (V21)(D41)(D42) 2 WALL TR01-2199-1

234'

2112D-AP-A 1 (AMAAP24-1-2) 1 CLG TR01-2199-1

235'

211C-AP-A 1 (AMAAP25-1-2) 1 CLG TR01-2199-1

250'

2112C-A 3 (V20)(D3)(D4) 2 WALL TR01-2199-1

238'

2112B-A 3 (V39)(D37)(D38) 2 WALL TR01-2199-1

228'

2112A-A 3 (V18)(D35)(D36) 2 WALL TR01-2199-1

228'

2112A-B 3 (10)(TELEPHONE)(1D)(2D) 1 WALL TR01-2199-1

226'

2112A-C 3 (UNLABELED)(D543) 2 WALL TR01-2199-1

246'

2110-A 3 (V16)(D31)(D32) 2 WALL TR01-2199-1

249'

2108-A 3 (V14)(D27)(D28) 2 WALL TR01-2199-1

252'

2108-B 3 (V38)(D33)(D34) 2 WALL TR01-2199-1

261'

2106-A 3 (V12)(D23)(D24) 2 WALL TR01-2199-1

261'

2106-B 3 (34V)(D331)(D332) 2 WALL TR01-2199-1

264'

2104-A 3 (V10)(D19)(D20) 2 WALL TR01-2199-1

SCALE: 1/32" = 1'-0"F7

TELECOMMUNICATION PLAN -

SECOND LEVEL - WAO COUNTS - TR

#2199

DATA DEVICE AND CIRCUIT SCHEDULE - TR #2199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW PORT QTY - EXISTING

OUTLET DESIGNATOR -

EXISTING PORT QTY- NEW MOUNTING RACK ID

269'

2104-B 3 (V9)(D17)(D18) 2 WALL TR01-2199-1

279'

2102-A 4 (ASSUMED) 2 WALL TR01-2199-1

288'

2102-B 4 (ASSUMED) 2 WALL TR01-2199-1

297'

2102A-A 4 (ASSUMED) 2 WALL TR01-2199-1

281'

2102A-B 4 (ASSUMED) 2 WALL TR01-2199-1

283'

2100-A 3 (V1)(D1)(D2) 2 WALL TR01-2199-1

291'

2101-A 3 (V4)(D7)(D8) 2 WALL TR01-2199-1

279'

2103-A 3 (V23)(D306)(D308) 2 WALL TR01-2199-1

283'

2103-B 3 (V8)(D15)(D16) 2 WALL TR01-2199-1

269'

2105-A 3 (V11)(D21)(D22) 2 WALL TR01-2199-1

259'

2107-A 3 (V43)(D25)(D26) 2 WALL TR01-2199-1

256'

2107-B 3 (31V)(D325)(D326) 2 WALL TR01-2199-1

257'

2109-A 3 (31V)(D325)(D326) 2 WALL TR01-2199-1

120'

2A-C1-AP-C 1 (AMAAP13-1-2) 1 CLG TR01-2199-2

152'

2123-A 3 (V42)(D83)(D84) 2 WALL TR01-2199-2

147'

2123-B 3 (V43)(D85)(D86) 2 WALL TR01-2199-2

162'

2125-A 4 (2130.2V)(270)(269) 2 WALL TR01-2199-2

154'

2125-B 3 (V46)(D91)(D92) 2 WALL TR01-2199-2

157'

2125-C 3 (V47)(D93)(D94) 2 WALL TR01-2199-2

159'

2125-AP-A 1 (AMAAP11-1-2) 1 CLG TR01-2199-2

170'

2126A-A 3 (V44)(D87)(D88) 2 WALL TR01-2199-2

175'

2126A-B 2 (UNLABELED) 2 WALL TR01-2199-2

180'

2126A-C 2 (UNLABELED) 2 WALL TR01-2199-2

181'

2126-A 3 (V48)(D95)(D96) 2 WALL TR01-2199-2

186'

2126-B 4 (V49)(D97)(D98) 2 WALL TR01-2199-2

187'

2126-C 3 (6V)(D289)(D290) 2 WALL TR01-2199-2

171'

2126-D 1 (UNLABELED) 2 WALL TR01-2199-2

165'

2126-E 3 (V51)(D101)(D102) 2 WALL TR01-2199-2

152'

2126-AP-A 1 (AMAAP12-1-2) 1 CLG TR01-2199-2

174'

2126-F 3 (39)(UNLABELED) 2 WALL TR01-2199-2

176'

2126-G 3 (V50)(D99)(D100) 2 WALL TR01-2199-2

186'

2126-H 3 (7V)(D291)(D292) 2 WALL TR01-2199-2

169'

2126-J 3 (V54)(D107)(D108) 2 WALL TR01-2199-2

165'

2126-K 2 (UNLABELED) 2 WALL TR01-2199-2

185'

2128-A 3 (19V)(B298)(B299) 2 WALL TR01-2199-2

197'

2128-B 3 (V32)(UNLABELED) 2 WALL TR01-2199-2

191'

2128-C 3 (V53)(D105)(D106) 2 WALL TR01-2199-2

189'

2128-AP-A 1 (AMAAP10-1-2) 1 CLG TR01-2199-2

245'

2132A-A 4 (ASSUMED) 2 WALL TR01-2199-2

241'

2132A-B 3 (V76)(D151)(D152) 2 WALL TR01-2199-2

253'

2132B-A 3 (V77)(D153)(D154) 2 WALL TR01-2199-2

251'

2132-A 3 (29V)(D318)(D319) 2 WALL TR01-2199-2

271'

2132-B 3 (V74)(D147)(D148) 2 WALL TR01-2199-2

260'

2132-AP-B 1 (AMAAP01-1-2) 1 CLG TR01-2199-2

300'

2132C-A 4 (UNLABELED) 2 WALL TR01-2199-2

291'

2132C-B 3 (V138)(UNLABELED) 2 WALL TR01-2199-2

288'

2132D-A 3 (UNLABELED) 2 WALL TR01-2199-2

284'

2132-C 3 (UNLABELED) 2 WALL TR01-2199-2

293'

2132-D 3 (V135)(D269)(D272) 2 WALL TR01-2199-2

255'

2132-AP-C 1 (AMAAP03-1-2) 1 CLG TR01-2199-2

261'

2132-E 4 (ASSUMED) 2 WALL TR01-2199-2

223'

2132-AP-A 1 (AMAAP02-1-2) 1 CLG TR01-2199-2

287'

2132E-A 4 (ASSUMED) 2 WALL TR01-2199-2

277'

2132E-B 3 (D160)(D159) 2 WALL TR01-2199-2

257'

2131-C 3 (DATA)(CONSOLE LAPTOP) 2 WALL TR01-2199-2

266'

2131-D 4 (PHONES) 1 WALL TR01-2199-2

188'

2A-C1-AP-A 1 (AMAAP23-1-2) 1 CLG TR01-2199-2

130'

2A-C1-AP-B 1 (AMAAP17-1-2) 1 CLG TR01-2199-1

237'

2A-C3-AP-A 1 (AMAAP22-1-2) 1 CLG TR01-2199-1

230'

2A-C1-AP-D 1 (AMAAP04-1-2) 1 CLG TR01-2199-2

257'

2147-A 3 (UNLABELED)(D322)(D323) 2 WALL TR01-2199-2

246'

2147-B 2 (UNLABELED) 2 WALL TR01-2199-2

245'

2147-C 3 (V58)(D115)(D116) 2 WALL TR01-2199-2

233'

2147A-A 2 (UNLABELED) 2 WALL TR01-2199-2

DATA DEVICE AND CIRCUIT SCHEDULE - TR #2199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW PORT QTY - EXISTING

OUTLET DESIGNATOR -

EXISTING PORT QTY- NEW MOUNTING RACK ID

237'

2147A-B 3 (V57)(D113)(D114) 2 WALL TR01-2199-2

238'

2133-A 3 (V60)(D119)(D120) 2 WALL TR01-2199-2

238'

2133-B 2 (UNLABELED) 2 WALL TR01-2199-2

243'

2137-A 1 (V59) 2 WALL TR01-2199-2

248'

2137-B 3 (41V)(B342)(B343) 2 WALL TR01-2199-2

255'

2139-AP-A 1 (AMAAP07-1-2) 1 CLG TR01-2199-2

256'

2139-A 3 (31V)(D325)(D326) 2 WALL TR01-2199-2

265'

2141-A 3 (49V)(D393)(D394) 2 WALL TR01-2199-2

274'

2141-B 3 (V67)(D133)(D134) 2 WALL TR01-2199-2

274'

2143-A 4 (ASSUMED) 2 WALL TR01-2199-2

286'

2143-B 4 (ASSUMED) 2 WALL TR01-2199-2

288'

2143-C 4 (ASSUMED) 2 WALL TR01-2199-2

280'

2143-D 4 (ASSUMED) 2 WALL TR01-2199-2

284'

2145-A 3 (22V)(D304)(D305) 2 WALL TR01-2199-2

297'

2145-B 3 (45V)(D350)(D351) 2 WALL TR01-2199-2

287'

2145-AP-A 1 (AMAAP05-1-2) 1 CLG TR01-2199-2

280'

2142-A 1 (D324) 2 WALL TR01-2199-2

289'

2142-B 3 (V71)(D141)(D143) 2 WALL TR01-2199-2

276'

2142-C 3 (TELEPHONE)(1)(2) 1 WALL TR01-2199-2

277'

2140-A 4 (ASSUMED) 2 WALL TR01-2199-2

282'

2140-B 4 (ASSUMED) 2 WALL TR01-2199-2

283'

2140-C 4 (ASSUMED) 2 WALL TR01-2199-2

270'

2140-D 4 (ASSUMED) 2 WALL TR01-2199-2

252'

2138-A 3 (44V)(D347)(D348) 2 WALL TR01-2199-2

268'

2138-B 3 (V66)(D131)(D132) 2 WALL TR01-2199-2

262'

2138-C 3 (43V)(D346)(D347) 2 WALL TR01-2199-2

252'

2136-A 4 (ASSUMED) 2 WALL TR01-2199-2

264'

2136-B 4 (ASSUMED) 2 WALL TR01-2199-2

261'

2136-C 4 (ASSUMED) 2 WALL TR01-2199-2

246'

2136-D 4 (ASSUMED) 2 WALL TR01-2199-2

239'

2134-A 3 (V72)(D142)(D144) 2 WALL TR01-2199-2

253'

2134-B 2 (UNLABELED) 2 WALL TR01-2199-2

234'

2134-C 3 (V61)(D121)(D122) 2 WALL TR01-2199-2

242'

2134-AP-A 1 (AMAAP08-1-2) 1 CLG TR01-2199-2

41'

2199-CAM-01 - NEWLY INSTALLED DEVICE,

NOT EXISTING

2 WALL TR01-2199-1

34'

2199-A - NEWLY INSTALLED DEVICE,

NOT EXISTING

2 WALL TR01-2199-1

Grand total: 164

1.

2.

3.

4.

5.

6.

7.

8.

9.

CABLING COMMENTS:

MAXIMUM ALLOWABLE CABLE LENGTH SHALL NOT EXCEED 100 METERS / 328 FEET.

WHEREVER POSSIBLE A MAXIMUM OF 260 FEET HAS BEEN UTILIZED TO ALLOW FOR FUTURE EXPANSION/SLACK LOOP.

WHILE ALL POSSIBLE DUE DILIGENCE WAS PERFORMED THE BIDDERS ARE REQUIRED TO PROVIDE A 10% ALLOWANCE FOR NEW DATA PORTS. ALL DEVIATIONS FROM THE DESIGN DOCUMENTS FOR LOCATIONS AND QUANTITIES OF DATA PORTS ARE REQUIRED TO BE VERIFIED BY THE VA COR AND A/E. AS AN EXAMPLE, IF 100 DATA DROPS WERE IDENTIFIED AND DOCUMENTED IN A BUILDING, THE CONTRACTOR SHALL BID 110 DATA DROPS AND CABLE, CONNECTION, TESTING, AND LABELING FOR THAT BUILDING. DURING THE COURSE OF THE INSTALLATION THE CONTRACTOR SHALL IDENTIFY ANY ADDITIONAL DATA PORTS AND ANY DATA DROPS NOT FOUND TO ENSURE THE AGGREGATE SUM IS CAPTURED IN THE RECORD DRAWINGS AND THE OWNER HAS AN ACCURATE COUNT AT THE END OF THE PROJECT.

"PORT QTY" LISTED IN TELECOMMUNICATION SCHEDULES ARE EXISTING AND NEW QUANTITIES.

1-RACK TR SOLUTIONS CAN HOLD UP TO 144 WAO (WORK AREA OUTLETS).

2-RACK TR SOLUTIONS CAN HOLD UP TO 240 WAO (WORK AREA OUTLETS).

3-RACK TR SOLUTIONS CAN HOLD UP TO 480 WAO (WORK AREA OUTLETS).

4-RACK TR SOLUTIONS CAN HOLD UP TO 720 WAO (WORK AREA OUTLETS).

WHEN CABLES ARE SPLIT FOR VOICE, 2 NEW CABLES WILL BE PROVIDED.

KEYNOTES:

EXISTING WORK AREA OUTLETS WITH (3)OR(4)EXISTING DATA PORTS SHALL BE REDUCED AND PROVIDED WITH (2)NEW PORTS (2)NEW CAT 6a CABLES.COORDINATE

WITH OWNER PRIOR TO REDUCTION AT EACH LOCATION.1

Revisions: Date:

2-ADDENDUM 2 03/06/2025

WAO CAPACITY FOR TR #2199

164 WAO TOTAL

480 WAO AVAILABLE

65.8% EXPANSION CAPACITY

302 TOTAL PORT QUANTITIES

332 TOTAL PORT QUANTITIES WITH 10% ALLOWANCE

171 SF

LEGEND

TR #3199 - PROPOSED AREA OF SERVICE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 325 N. Saint Paul Street, Suite 3100 Dallas, TX 75201

MAT PERKINS

469-330-9710

STAMP

UPDATED AND RE-ISSUED FOR CONSTRUCTION 09/18/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 11/02/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 10/25/2024

Au to de sk

D oc s:

//5

-2

1-

EH

R M

In fra st ru ct ur e U pg ra de s at A m ar illo V

AM

C

/5

-2 1-

0.

EH

R

M .A m ar illo .B

.M

EP

.rv t

-0 3-

2:

:0

01T-703

TELECOMMUNICATION SCHEDULES 504-21-700

B01

11/02/2023 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

6010 Amarillo Blvd. West, Amarillo, TX 79106

SCALE: 1/32" = 1'-0"F7

TELECOMMUNICATION PLAN - THIRD

LEVEL - WAO COUNTS - TR #3199

DATA DEVICE AND CIRCUIT SCHEDULE - TR #3199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING OUTLET DESIGNATOR - EXISTING PORT QUANTITIES - NEW MOUNTING RACK ID

68'

3768-A 6 (95-V)(96-V)(C-27-D)(D-27-D)(C31)(C32) 2 WALL TR01-3199-1

55'

3768-B 5 (3738)(97-V)(98-V)(C-28-D)(D-28-D)(C33) 2 WALL TR01-3199-1

46'

3768-AP-A 1 (AMAAP13-1-3) 1 CLG TR01-3199-1

74'

3A-C3-AP-J 1 (MODEM) 1 CLG TR01-3199-1

87'

3A-C3-AP-H 1 (AMAAP15-1-3) 1 CLG TR01-3199-1

76'

3770-A 4 (ASSUMED) 2 WALL TR01-3199-1

90'

3770-B 4 (ASSUMED) 2 WALL TR01-3199-1

80'

S2-3-AP-A 1 (AMAAP16-1-3) 1 CLG TR01-3199-1

102'

3A-C3-AP-G 1 (MODEM) 1 CLG TR01-3199-1

127'

3A-C4-AP-A 1 (MODEM) 1 CLG TR01-3199-1

158'

3726-A 4 (ASSUMED) 2 WALL TR01-3199-1

159'

3726-B 4 (ASSUMED) 2 WALL TR01-3199-1

152'

3726-C 4 (ASSUMED) 2 WALL TR01-3199-1

139'

3726-D 4 (ASSUMED) 2 WALL TR01-3199-1

148'

3A-C4-AP-B 1 (AMAAP10-1-3) 1 CLG TR01-3199-1

151'

3A-C4-AP-C 1 (SPECTRALINK 1-3-1) 1 CLG TR01-3199-1

140'

3A-C4-A 3 (IDF 3738)(D35)(D36) 2 WALL TR01-3199-1

159'

3A-C4-B 3 (3738)(40V)(B37)(B38) 2 WALL TR01-3199-1

162'

3A-C4-AP-D 1 (MODEM) 1 CLG TR01-3199-1

138'

3781-A 1 (IDF 3837)(3727) 2 WALL TR01-3199-1

153'

3781-B 1 (38V)(EXT. 3731) 2 WALL TR01-3199-1

147'

3781-C 2 (B11)(B12) 2 WALL TR01-3199-1

138'

3781-D 2 (IDF 3738) 2 WALL TR01-3199-1

173'

3723-A 4 (ASSUMED) 2 WALL TR01-3199-1

189'

3723-B 4 (ASSUMED) 2 WALL TR01-3199-1

187'

3723-C 4 (ASSUMED) 2 WALL TR01-3199-1

178'

3723-D 4 (ASSUMED) 2 WALL TR01-3199-1

177'

3724-A 4 (ASSUMED) 2 WALL TR01-3199-1

184'

3724-B 4 (ASSUMED) 2 WALL TR01-3199-1

174'

3724-C 4 (ASSUMED) 2 WALL TR01-3199-1

166'

3724-D 4 (ASSUMED) 2 WALL TR01-3199-1

197'

3720-A 3 (4V)(D144)(D143) 2 WALL TR01-3199-1

235'

3707-A 1 (3738)(100-V) 2 WALL TR01-3199-1

251'

3705-A 1 (3738)(99-V) 2 WALL TR01-3199-1

279'

3701-A 2 (C41)(C42) 2 WALL TR01-3199-1

268'

3701-B 4 (UNLABELED) 2 WALL TR01-3199-1

244'

3704-A 2 (C39)(C40) 2 WALL TR01-3199-1

265'

3702-A 1 (D-22-D) 2 WALL TR01-3199-1

276'

3702-B 1 (3738)(81-V)(82-V)(C-20-D)(D-20-D) 2 WALL TR01-3199-1

272'

3702-C 1 (3738)(83-V)(84-V)(C-21-D)(D-21-D) 2 WALL TR01-3199-1

270'

3700-A 4 (3738)(850-V)(86-V)C-22-D) 2 WALL TR01-3199-1

273'

3700-B 6 (D32)(D33)(D34)(D35)(D36)(D37) 2 WALL TR01-3199-1

296'

3700-C 4 (87-V)(88-V)(C-23-D)(D-23-D) 2 WALL TR01-3199-1

288'

3700-D 3 (D29)(D30)(D31) 2 WALL TR01-3199-1

305'

3700-E 4 (3738)(89V)(90V)(C-24-D)(D-24-D) 2 WALL TR01-3199-1

282'

3700-F 4 (UNLABELED) 2 WALL TR01-3199-1

277'

3700-G 6 (D38)(D39)(D40)(D41)(D42)(D43) 2 WALL TR01-3199-1

248'

3710-A 4 (3738)(79-V)(80-V)(C-19-D)(D-19-D) 2 WALL TR01-3199-1

234'

3712-A 4 (3738)(75-V)(76-V)(C-17-D)(D-17-D) 2 WALL TR01-3199-1

231'

3712-B 4 (3738)(77-V)(78-V)(C-18-D)(D-18-D) 2 WALL TR01-3199-1

231'

3A-C6-AP-A 1 (AMAAP31-1-3) 1 CLG TR01-3199-1

229'

3714-A 4 (3738)(67-V)(68-V)(C-13-D)(D-13-D) 2 WALL TR01-3199-1

240'

3714-B 4 (ASSUMED) 2 WALL TR01-3199-1

247'

3714-C 4 (3738)(69-V)(70-V)(C-14-D)(D-14-D) 2 WALL TR01-3199-1

231'

3714-D 4 (3738)(73-V)(74-V)(C-16-D)(D-16-D) 2 WALL TR01-3199-1

256'

3709-A 4 (3738)(43-V)(44-V)(C-01-D)(D-01-D) 2 WALL TR01-3199-1

258'

3709-B 4 (3738)(45-V)(46-V)(C-02-D)(D-02-D) 2 WALL TR01-3199-1

247'

KEYPAD 4 (KEYPAD) 1 WALL TR01-3199-1

273'

3716-A 4 (3738)(65-V)(66-V)(C-12-D)(D-12-D) 2 WALL TR01-3199-1

262'

3711-A 4 (3738)(47-V)(48-V)(C-03-D)(D-03-D) 2 WALL TR01-3199-1

262'

DATA DEVICE AND CIRCUIT SCHEDULE - TR #3199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING OUTLET DESIGNATOR - EXISTING PORT QUANTITIES - NEW MOUNTING RACK ID

3711-B 4 (3738)(49-V)(50-V)(C-04-D)(D-04-D) 2 WALL TR01-3199-1

273'

3713-A 4 (3738)(51-V)(52-V)(C-05-D)(D-05-D) 2 WALL TR01-3199-1

272'

3713-B 4 (3738)(53-V)(54-V)(C-06-D)(D-06-D) 2 WALL TR01-3199-1

298'

3715-A 4 (3738)(57-V)(58-V)(C-08-D)(D-08-D) 2 WALL TR01-3199-1

285'

3715-B 4 (3738)(59-V)(60-V)(C-09-D)(D-09-D) 2 WALL TR01-3199-1

273'

3715-C 4 (3738)(61-V)(62-V)(C-10-D)(D-10-D) 2 WALL TR01-3199-1

284'

3715-AP-A 1 (AMAAP08-1-3) 1 CLG TR01-3199-1

284'

3718-A 4 (UNLABELED) 2 WALL TR01-3199-1

281'

3718-AP-A 1 (AMAAP09-1-3) 1 CLG TR01-3199-1

123'

3728-A 1 (PHONE) 1 WALL TR01-3199-2

126'

3728-B 4 (IDF 3738)(28V)(29V)(B19)(B20) 2 WALL TR01-3199-2

128'

3728-C 4 (IDF 3738)(30V)(31V)(B21)(B22) 2 WALL TR01-3199-2

125'

3782-A 1 (IDF 3738)(33V) 2 WALL TR01-3199-2

137'

3783-A 4 (43V)(C33)(C29)(C30) 2 WALL TR01-3199-2

132'

3783-B 2 (C37)(C38) 2 WALL TR01-3199-2

134'

3731-A 4 (ASSUMED) 2 WALL TR01-3199-2

122'

3A-C3-AP-F 1 (AMAAP30-1-3) 1 CLG TR01-3199-2

146'

3784-A 4 (ASSUMED) 2 WALL TR01-3199-2

158'

3784-B 4 (ASSUMED) 2 WALL TR01-3199-2

156'

3784-C 4 (ASSUMED) 2 WALL TR01-3199-2

158'

3784-D 4 (ASSUMED) 2 WALL TR01-3199-2

132'

3A-C3-AP-E 1 (MODEM) 1 CLG TR01-3199-2

155'

3734-A 4 (ASSUMED) 2 WALL TR01-3199-2

163'

3734-B 4 (ASSUMED) 2 WALL TR01-3199-2

162'

3734-C 4 (ASSUMED) 2 WALL TR01-3199-2

141'

3734-D 4 (ASSUMED) 2 WALL TR01-3199-2

181'

3735-A 1 (IDF 3837)(3735) 2 WALL TR01-3199-2

187'

3735-B 1 (IDF 3837)(26V)(EXT. 3738) 2 WALL TR01-3199-2

171'

3735-C 2 (IDF 3738)(A17)(A18) 2 WALL TR01-3199-2

184'

3737-AP-A 1 (UNLABELED) 1 CLG TR01-3199-2

170'

3A-C3-AP-D 1 (MODEM) 1 CLG TR01-3199-2

184'

3736-A 2 (A11)(A12) 2 WALL TR01-3199-2

182'

3736-B 1 (3736) 2 WALL TR01-3199-2

185'

3736-C 1 (25V)(EXT. 3746) 2 WALL TR01-3199-2

178'

3736-D 2 (A13)(A14) 2 WALL TR01-3199-2

180'

3736-AP-A 1 (AMAAP18-1-3) 1 CLG TR01-3199-2

190'

3A-C3-AP-C 1 (MODEM) 1 CLG TR01-3199-2

233'

3741-A 4 (41V)(B39)(B40)(B41) 2 WALL TR01-3199-2

226'

3741-B 4 (IDF 3738)(22V)(23V)(B1)(B23) 2 WALL TR01-3199-2

255'

3745-A 1 (3745) 2 WALL TR01-3199-2

270'

3745-B 1 (EXT. 3751) 2 WALL TR01-3199-2

261'

3745-C 2 (A21)(A22) 2 WALL TR01-3199-2

252'

3745-D 2 (A19)(A20) 2 WALL TR01-3199-2

292'

3747-A 4 (ASSUMED) 2 WALL TR01-3199-2

221'

3747-B 4 (ASSUMED) 2 WALL TR01-3199-2

303'

3749-B 4 (ASSUMED) 2 WALL TR01-3199-2

304'

3749-C 4 (ASSUMED) 2 WALL TR01-3199-2

297'

3751-A 2 (IDF 3738)(A31)(A32) 2 WALL TR01-3199-2

305'

3751-B 1 (17V)(EXT. 3755) 2 WALL TR01-3199-2

305'

3751-C 2 (IDF 3738)(3751) 2 WALL TR01-3199-2

296'

3751-D 1 (IDF 2728)(A33)(A34) 2 WALL TR01-3199-2

272'

3A-C1-AP-A 1 (AMAAP21-1-3) 1 CLG TR01-3199-2

282'

3A-C1-A 4 (IDF 3738)(B25)(B26) 2 WALL TR01-3199-2

276'

3753-A 4 (18V)(19V)(B23)(B24) 2 WALL TR01-3199-2

271'

3753-B 1 (OMNICELL) 2 WALL TR01-3199-2

273'

3753-C 4 (20V)(21V)(D27)(D28) 2 WALL TR01-3199-2

240'

3A-C1-AP-B 1 (MODEM) 1 CLG TR01-3199-2

205'

3A-C3-AP-B 1 (AMAAP29-1-3) 1 CLG TR01-3199-2

242'

3755-AP-A 1 (AMAAP23-1-3) 1 CLG TR01-3199-2

223'

3A-C3-AP-A 1 (MODEM) 1 CLG TR01-3199-2

252'

3750-A 4 (IDF 3738)(10V)(11V)(A47)(A48) 2 WALL TR01-3199-2

DATA DEVICE AND CIRCUIT SCHEDULE - TR #3199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING OUTLET DESIGNATOR - EXISTING PORT QUANTITIES - NEW MOUNTING RACK ID

237'

3750-AP-A 1 (AMAAP24-1-3) 1 CLG TR01-3199-2

256'

3740-A 4 (IDF 3738)(08V)(09V)(A9)(A10) 2 WALL TR01-3199-2

240'

S3-3-AP-A 1 (AMAAP28-1-3) 1 CLG TR01-3199-2

275'

3742-A 4 (ASSUMED) 2 WALL TR01-3199-2

289'

3742-B 4 (ASSUMED) 2 WALL TR01-3199-2

292'

3742-C 4 (ASSUMED) 2 WALL TR01-3199-2

277'

3742-D 4 (ASSUMED) 2 WALL TR01-3199-2

270'

3748-A 4 (IDF 3738)(04V)(05V)(B33)(B34) 2 WALL TR01-3199-2

267'

3748-B 1 (OMNICELL) 2 WALL TR01-3199-2

271'

3748-C 4 (02V)(03V)(B29)(B30) 2 WALL TR01-3199-2

272'

3A-C2-A 2 (IDF 3738)(B31)(B32) 2 WALL TR01-3199-2

269'

3A-C2-AP-A 1 (AMAAP26-1-3) 1 CLG TR01-3199-2

289'

3746-A 4 (ASSUMED) 2 WALL TR01-3199-2

302'

3746-B 4 (ASSUMED) 2 WALL TR01-3199-2

307'

3746-C 4 (ASSUMED) 2 WALL TR01-3199-2

300'

3746-D 4 (ASSUMED) 2 WALL TR01-3199-2

42'

3199-CAM-01 - NEWLY INSTALLED DEVICE, NOT

EXISTING

1 WALL TR01-3199-1

244'

3747-C 4 (ASSUMED) 2 WALL TR01-3199-1

294'

3744-A 4 (ASSUMED) 2 WALL TR01-3199-2

299'

3744-B 4 (ASSUMED) 2 WALL TR01-3199-2

297'

3744-C 4 (ASSUMED) 2 WALL TR01-3199-2

275'

3744-D 4 (ASSUMED) 2 WALL TR01-3199-2

284'

3749-A 4 (ASSUMED) 2 WALL TR01-3199-2

34'

3199-A - NEWLY INSTALLED DEVICE, NOT

EXISTING

2 WALL TR01-3199-1

Grand total: 145

WAO CAPACITY FOR TR #3199

145 WAO TOTAL

480 WAO AVAILABLE

69.8% EXPANSION CAPACITY

261TOTAL PORT QUANTITIES

287 TOTAL PORT QUANTITIES WITH 10% ALLOWANCE

1.

2.

3.

4.

5.

6.

7.

8.

9.

CABLING COMMENTS:

MAXIMUM ALLOWABLE CABLE LENGTH SHALL NOT EXCEED 100 METERS / 328 FEET.

WHEREVER POSSIBLE A MAXIMUM OF 260 FEET HAS BEEN UTILIZED TO ALLOW FOR FUTURE EXPANSION/SLACK LOOP.

WHILE ALL POSSIBLE DUE DILIGENCE WAS PERFORMED THE BIDDERS ARE REQUIRED TO PROVIDE A 10% ALLOWANCE FOR NEW DATA PORTS. ALL DEVIATIONS FROM THE DESIGN DOCUMENTS FOR LOCATIONS AND QUANTITIES OF DATA PORTS ARE REQUIRED TO BE VERIFIED BY THE VA COR AND A/E. AS AN EXAMPLE, IF 100 DATA DROPS WERE IDENTIFIED AND DOCUMENTED IN A BUILDING, THE CONTRACTOR SHALL BID 110 DATA DROPS AND CABLE, CONNECTION, TESTING, AND LABELING FOR THAT BUILDING. DURING THE COURSE OF THE INSTALLATION THE CONTRACTOR SHALL IDENTIFY ANY ADDITIONAL DATA PORTS AND ANY DATA DROPS NOT FOUND TO ENSURE THE AGGREGATE SUM IS CAPTURED IN THE RECORD DRAWINGS AND THE OWNER HAS AN ACCURATE COUNT AT THE END OF THE PROJECT.

"PORT QTY" LISTED IN TELECOMMUNICATION SCHEDULES ARE EXISTING AND NEW QUANTITIES.

1-RACK TR SOLUTIONS CAN HOLD UP TO 144 WAO (WORK AREA OUTLETS).

2-RACK TR SOLUTIONS CAN HOLD UP TO 240 WAO (WORK AREA OUTLETS).

3-RACK TR SOLUTIONS CAN HOLD UP TO 480 WAO (WORK AREA OUTLETS).

4-RACK TR SOLUTIONS CAN HOLD UP TO 720 WAO (WORK AREA OUTLETS).

WHEN CABLES ARE SPLIT FOR VOICE, 2 NEW CABLES WILL BE PROVIDED.

KEYNOTES:

EXISTING WORK AREA OUTLETS WITH (3)OR(4)EXISTING DATA PORTS SHALL BE REDUCED AND PROVIDED WITH (2)NEW PORTS (2)NEW CAT 6a CABLES.COORDINATE

WITH OWNER PRIOR TO REDUCTION AT EACH LOCATION.1

Revisions: Date:

2-ADDENDUM 2 03/06/2025

171 SF

LEGEND

TR #4199 - PROPOSED AREA OF SERVICE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 325 N. Saint Paul Street, Suite 3100 Dallas, TX 75201

MAT PERKINS

469-330-9710

STAMP

UPDATED AND RE-ISSUED FOR CONSTRUCTION 09/18/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 11/02/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 10/25/2024

Au to de sk

D oc s:

//5

-2

1-

EH

R M

In fra st ru ct ur e U pg ra de s at A m ar illo V

AM

C

/5

-2 1-

0.

EH

R

M .A m ar illo .B

.M

EP

.rv t

-0 3-

2:

:0

01T-704

TELECOMMUNICATION SCHEDULES 504-21-700

B01

11/02/2023 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

6010 Amarillo Blvd. West, Amarillo, TX 79106

SCALE: 1/32" = 1'-0"F7

TELECOMMUNICATION PLAN -

FOURTH LEVEL - WAO COUNTS - TR

#4199

DATA DEVICE AND CIRCUIT SCHEDULE - TR #4199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW PORT QTY - EXISTING

OUTLET DESIGNATOR -

EXISTING PORT QUANTITIES - NEW MOUNTING RACK ID

51'

4165-A 3 (D265)(D266)(133) 2 WALL TR01-4199-1

66'

4164-A 4 (ASSUMED) 2 WALL TR01-4199-1

69'

4164-AP-A 1 (AMAAP12-1-4) 1 CLG TR01-4199-1

74'

4163-A 3 (V4)(D7)(D8) 2 WALL TR01-4199-1

84'

4163-B 4 (ASSUMED) 2 WALL TR01-4199-1

71'

4163-C 3 (V5)(D9)(D10) 2 WALL TR01-4199-1

71'

4163-D 3 (UNLABELED) 2 WALL TR01-4199-1

63'

4163-E 1 (2335) 2 WALL TR01-4199-1

80'

4161-A 3 (V3)(D5)(D6) 2 WALL TR01-4199-1

89'

4159-A 3 (V1)(D1)(D2) 2 WALL TR01-4199-1

83'

4159-B 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-1

47'

4162-A 4 (ASSUMED) 2 WALL TR01-4199-1

55'

4162-B 3 (V8)(D15)(D16) 2 WALL TR01-4199-1

80'

4160-A 3 (V7)(D13)(D14) 2 WALL TR01-4199-1

75'

4160-B 3 (UNLABELED)(D356)(D357) 2 WALL TR01-4199-1

78'

C4-1-AP-B 1 (AMAAP14-1-4) 1 CLG TR01-4199-1

137'

4173-A 4 (D477) 2 WALL TR01-4199-1

121'

4173-B 3 (UNLABELED)(255)(256) 2 WALL TR01-4199-1

138'

4126A-A 3 (V122)(243)(244) 2 WALL TR01-4199-1

141'

4126B-AP-A 1 (AMAAP11-1-4) 1 CLG TR01-4199-1

154'

4126B-A 3 (V121)(241)(242) 2 WALL TR01-4199-1

162'

4124-A 1 (D239) 2 WALL TR01-4199-1

170'

4175-A 3 (V119)(237)(238) 2 WALL TR01-4199-1

189'

4176-A 3 (V118)(235)(236) 2 WALL TR01-4199-1

190'

4122-A 4 (ASSUMED) 2 WALL TR01-4199-1

193'

4122-B 4 (ASSUMED) 2 WALL TR01-4199-1

193'

4122-C 4 (ASSUMED) 2 WALL TR01-4199-1

181'

4122-D 4 (ASSUMED) 2 WALL TR01-4199-1

139'

4123-AP-A 1 (AMAAP10-1-4) 1 CLG TR01-4199-1

142'

4123-A 3 (4129.5V)(251)(252) 2 WALL TR01-4199-1

144'

4123-B 2 (UNLABELED) 2 WALL TR01-4199-1

142'

4123A-A 4 (OMNICELL) 2 WALL TR01-4199-1

160'

4121-A 3 (V137)(D271)(D272) 2 WALL TR01-4199-1

159'

4121-B 3 (D267)(D268)(A35) 2 WALL TR01-4199-1

149'

4121-C 3 (UNLABELED) 2 WALL TR01-4199-1

178'

4119-A 3 (4119A)(D216)(D215) 2 WALL TR01-4199-1

287'

4100-A 3 (UNLABELED) 2 WALL TR01-4199-1

224'

4003-A 2 (UNLABELED) 2 WALL TR01-4199-1

227'

4003-B 2 (UNLABELED) 2 WALL TR01-4199-1

229'

4003-C 4 (UNLABELED) 2 WALL TR01-4199-1

231'

4003-D 3 (UNLABELED) 2 WALL TR01-4199-1

229'

4107-A 3 (V95)(UNLABELED) 2 WALL TR01-4199-1

254'

4114A-A 4 (ASSUMED) 2 WALL TR01-4199-1

257'

4114A-B 4 (ASSUMED) 2 WALL TR01-4199-1

254'

4114A-C 4 (ASSUMED) 2 WALL TR01-4199-1

259'

4115A-A 2 (D368)(V185) 2 WALL TR01-4199-1

260'

4115A-B 4 (ASSUMED) 2 WALL TR01-4199-1

274'

4115-A 2 (UNLABELED) 2 WALL TR01-4199-1

264'

C4-7-A 1 (UNLABELED) 2 WALL TR01-4199-1

268'

4114-A 4 (V132)(D261)(D262) 2 WALL TR01-4199-1

260'

4114-B 3 (UNLABELED) 2 WALL TR01-4199-1

251'

4114-C 2 (UNLABELED) 2 WALL TR01-4199-1

272'

4116-A 3 (V72)(D183)(D184) 2 WALL TR01-4199-1

299'

4116-B 3 (V142)(D334)(D345) 2 WALL TR01-4199-1

286'

4116-C 2 (D336)(D337) 2 WALL TR01-4199-1

266'

4116-D 2 (D188)(D189)(D190) 2 WALL TR01-4199-1

145'

4130-A 3 (V9)(D17)(D18) 2 WALL TR01-4199-2

137'

4130-B 3 (V10)(D19)(D20) 2 WALL TR01-4199-2

152'

4132-A 3 (V18)(D35)(D36) 2 WALL TR01-4199-2

161'

4132-B 4 (ASSUMED) 2 WALL TR01-4199-2

153'

4132-C 3 (V20)(D39)(D40) 2 WALL TR01-4199-2

134'

C4-1-AP-A 1 (AMAAP15-1-4) 1 CLG TR01-4199-2

173'

DATA DEVICE AND CIRCUIT SCHEDULE - TR #4199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW PORT QTY - EXISTING

OUTLET DESIGNATOR -

EXISTING PORT QUANTITIES - NEW MOUNTING RACK ID

4134-A 3 (V21)(D41)(D42) 2 WALL TR01-4199-2

143'

4125-A 4 (ASSUMED) 2 WALL TR01-4199-2

151'

4125-B 3 (V11)(D21)(D22) 2 WALL TR01-4199-2

137'

4125-C 2 (UNLABELED) 2 WALL TR01-4199-2

135'

4125-D 3 (V12)(D23)(D24) 2 WALL TR01-4199-2

172'

4134-B 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

172'

4134A-A 2 (D482)(D483) 2 WALL TR01-4199-2

197'

4136-A 3 (V25)(D49)(D50) 2 WALL TR01-4199-2

191'

4136-B 3 (V24)(D47)(D48) 2 WALL TR01-4199-2

185'

4136-AP-A 1 (AMAAP17-1-4) 1 CLG TR01-4199-2

175'

4127-A 1 (D58) 2 WALL TR01-4199-2

175'

4129-A 3 (V17)(D33)(D34) 2 WALL TR01-4199-2

183'

4129-B 3 (V15)(D29)(D30) 2 WALL TR01-4199-2

176'

4129-AP-A 1 (AMAAP16-1-4) 1 CLG TR01-4199-2

244'

4146-A 4 (V37)(D93)(D94) 2 WALL TR01-4199-2

238'

4146-B 2 (UNLABELED) 2 WALL TR01-4199-2

256'

4142-A 3 (V51)(D101)(D102) 2 WALL TR01-4199-2

255'

4142-B 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

264'

4142-C 3 (V136)(D270A)(D270) 2 WALL TR01-4199-2

273'

4140-A 3 (V52)(D103)(D104) 2 WALL TR01-4199-2

275'

4138-A 3 (V54)(D107)(D108) 2 WALL TR01-4199-2

291'

4138-B 3 (V55)(D109)(D110) 2 WALL TR01-4199-2

287'

4138-C 3 (D369)(D370)(V188)(4138-3) 2 WALL TR01-4199-2

284'

4138-D 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

281'

4138-AP-A 1 (AMAAP19-1-4) 1 CLG TR01-4199-2

290'

4131-A 4 (V57)(D113)(D114) 2 WALL TR01-4199-2

282'

4131-B 4 (ASSUMED) 2 WALL TR01-4199-2

286'

4133-A 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

295'

4133-B 3 (127-2)(TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

288'

4133-C 3 (V58)(D115)(D116) 2 WALL TR01-4199-2

289'

4133-AP-A 1 (AMAAP18-1-4) 1 CLG TR01-4199-2

281'

4135-A 3 (V61)(D121)(D122) 2 WALL TR01-4199-2

281'

4135-B 3 (V60)(D119)(D120) 2 WALL TR01-4199-2

267'

4137-A 3 (UNLABELED)(D125)(D126) 2 WALL TR01-4199-2

239'

4139-A 3 (D371)(D372)(V4139-3) 2 WALL TR01-4199-2

255'

4139-B 3 (V64)(D127)(D128) 2 WALL TR01-4199-2

246'

4139-C 4 (ASSUMED) 2 WALL TR01-4199-2

244'

4141-A 4 (ASSUMED) 2 WALL TR01-4199-2

233'

4141-B 3 (v49)(D297)(D298) 2 WALL TR01-4199-2 227'

4141-C 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

231'

4148-A 2 (UNLABELED) 2 WALL TR01-4199-2

241'

4148-B 3 (V147)(D354)(D355) 2 WALL TR01-4199-2

257'

4148-C 3 (V148)(D352)(D353) 2 WALL TR01-4199-2

242'

4148-AP-A 1 (AMAAP21-1-4) 1 CLG TR01-4199-2

229'

4143-A 1 (D373) 2 WALL TR01-4199-2

233'

4143-B 3 (V36)(D51)(D52) 2 WALL TR01-4199-2

245'

4143-C 3 (V067)(D360)(D361) 2 WALL TR01-4199-2

246'

4143-D 3 (V068)(D362)(D363) 2 WALL TR01-4199-2

241'

4143-E 3 (V069)(D364)(D365) 2 WALL TR01-4199-2

231'

4143-F 4 (ASSUMED) 2 WALL TR01-4199-2

206'

C4-2-AP-A 1 (AMAAP23-1-4) 1 CLG TR01-4199-2

250'

4149A-A 3 (V45)(D89)(D90) 2 WALL TR01-4199-2

255'

4149A-B 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

245'

4149A-C 3 (V46)(D91)(D92) 2 WALL TR01-4199-2

260'

4151-A 3 (TELEPHONE)(1D)(2D) 1 WALL TR01-4199-2

257'

4151-B 4 (V40)(D79)(D80) 2 WALL TR01-4199-2

261'

4153-A 4 (ASSUMED) 2 WALL TR01-4199-2

272'

4153-B 4 (V41)(D81)(D82) 2 WALL TR01-4199-2

276'

4155-A 2 (UNLABELED) 2 WALL TR01-4199-2

277'

4155-B 1 (4128.3V) 2 WALL TR01-4199-2

286'

4155-C 2 (UNLABELED) 2 WALL TR01-4199-2

271'

4155-D 4 (V30)(D59)(D60) 2 WALL TR01-4199-2

285'

DATA DEVICE AND CIRCUIT SCHEDULE - TR #4199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW PORT QTY - EXISTING

OUTLET DESIGNATOR -

EXISTING PORT QUANTITIES - NEW MOUNTING RACK ID

4155-AP-A 1 (AMAAP25-1-4) 1 CLG TR01-4199-2

279'

4157-A 3 (VA)(114-1) 2 WALL TR01-4199-2

283'

4157-B 1 (D359) 2 WALL TR01-4199-2

290'

4157-C 3 (V31)(D61)(D62) 2 WALL TR01-4199-2

283'

4157-D 2 (D63)(D64) 2 WALL TR01-4199-2

284'

4157-AP-A 1 (AMAAP24-1-4) 1 CLG TR01-4199-2

279'

4156-A 3 (V33)(D65)(D66) 2 WALL TR01-4199-2

284'

4156-B 3 (V34)(D67)(D68) 2 WALL TR01-4199-2

269'

4154-A 3 (V35)(D69)(D70) 2 WALL TR01-4199-2

259'

4154-B 3 (V36)(D71)(D72) 2 WALL TR01-4199-2

260'

4152-A 3 (V47)(D73)(D74) 2 WALL TR01-4199-2

252'

4152-B 3 (V39)(D77)(D78) 2 WALL TR01-4199-2

260'

4152-C 3 (V43)(D85)(D86) 2 WALL TR01-4199-2

250'

4152-D 3 (V123)(D245)(D246) 2 WALL TR01-4199-2

42'

4199-CAM-01 - NEWLY INSTALLED DEVICE, NOT

EXISTING

1 WALL TR01-4199-1

233'

C4-4-AP-A 1 (AMAAP20-1-4) 1 CLG TR01-4199-2

239'

4143-AP-A 1 (AMAAP22-1-4) 1 CLG TR01-4199-2

34'

4199-A - NEWLY INSTALLED DEVICE, NOT

EXISTING

1 WALL TR01-4199-1

159'

C4-6-A - (TELEPHONE) 1 WALL TR01-4199-1

Grand total: 143

WAO CAPACITY FOR TR #4199

143 WAO TOTAL

480 WAO AVAILABLE

70.2% EXPANSION CAPACITY

259 TOTAL PORT QUANTITIES

284 TOTAL PORT QUANTITIES WITH 10% ALLOWANCE

1.

2.

3.

4.

5.

6.

7.

8.

9.

CABLING COMMENTS:

MAXIMUM ALLOWABLE CABLE LENGTH SHALL NOT EXCEED 100 METERS / 328 FEET.

WHEREVER POSSIBLE A MAXIMUM OF 260 FEET HAS BEEN UTILIZED TO ALLOW FOR FUTURE EXPANSION/SLACK LOOP.

WHILE ALL POSSIBLE DUE DILIGENCE WAS PERFORMED THE BIDDERS ARE REQUIRED TO PROVIDE A 10% ALLOWANCE FOR NEW DATA PORTS. ALL DEVIATIONS FROM THE DESIGN DOCUMENTS FOR LOCATIONS AND QUANTITIES OF DATA PORTS ARE REQUIRED TO BE VERIFIED BY THE VA COR AND A/E. AS AN EXAMPLE, IF 100 DATA DROPS WERE IDENTIFIED AND DOCUMENTED IN A BUILDING, THE CONTRACTOR SHALL BID 110 DATA DROPS AND CABLE, CONNECTION, TESTING, AND LABELING FOR THAT BUILDING. DURING THE COURSE OF THE INSTALLATION THE CONTRACTOR SHALL IDENTIFY ANY ADDITIONAL DATA PORTS AND ANY DATA DROPS NOT FOUND TO ENSURE THE AGGREGATE SUM IS CAPTURED IN THE RECORD DRAWINGS AND THE OWNER HAS AN ACCURATE COUNT AT THE END OF THE PROJECT.

"PORT QTY" LISTED IN TELECOMMUNICATION SCHEDULES ARE EXISTING AND NEW QUANTITIES.

1-RACK TR SOLUTIONS CAN HOLD UP TO 144 WAO (WORK AREA OUTLETS).

2-RACK TR SOLUTIONS CAN HOLD UP TO 240 WAO (WORK AREA OUTLETS).

3-RACK TR SOLUTIONS CAN HOLD UP TO 480 WAO (WORK AREA OUTLETS).

4-RACK TR SOLUTIONS CAN HOLD UP TO 720 WAO (WORK AREA OUTLETS).

WHEN CABLES ARE SPLIT FOR VOICE, 2 NEW CABLES WILL BE PROVIDED.

KEYNOTES:

EXISTING WORK AREA OUTLETS WITH (3)OR(4)EXISTING DATA PORTS SHALL BE REDUCED AND PROVIDED WITH (2)NEW PORTS (2)NEW CAT 6a CABLES.COORDINATE

WITH OWNER PRIOR TO REDUCTION AT EACH LOCATION.1

Revisions: Date:

171 SF

LEGENDLEGEND

TR #5199 - PROPOSED AREA OF SERVICE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group 325 N. Saint Paul Street, Suite 3100 Dallas, TX 75201

MAT PERKINS

469-330-9710

STAMP

UPDATED AND RE-ISSUED FOR CONSTRUCTION 09/18/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 11/02/2023

UPDATED AND RE-ISSUED FOR CONSTRUCTION 10/25/2024

Au to de sk

D oc s:

//5

-2

1-

EH

R M

In fra st ru ct ur e U pg ra de s at A m ar illo V

AM

C

/5

-2 1-

0.

EH

R

M .A m ar illo .B

.M

EP

.rv t

-0 3-

2:

:0

01T-705

TELECOMMUNICATION SCHEDULES 504-21-700

B01

11/02/2023 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

6010 Amarillo Blvd. West, Amarillo, TX 79106

SCALE: 1/32" = 1'-0"F7

TELECOMMUNICATION PLAN - FIFTH

LEVEL - WAO COUNTS - #5199

DATA DEVICE AND CIRCUIT SCHEDULE - TR #5199

TYPE

EST. LENGTH PER

PORT

OUTLET DESIGNATOR -

NEW

PORT QTY -

EXISTING OUTLET DESIGNATOR - EXISTINGPORT…