This is an architectural drawing showing wall elevations with reinforced elevations from a VA facility boiler plant replacement project. The drawing includes four detailed wall elevation views with technical specifications, a wall opening schedule table, and general notes section in the top right corner. The drawing is stamped by the Office of Construction and Facilities Management, U.S. Department of Veterans Affairs and includes approval stamps from Moon Tree (consultant) and Paradigm (Architecture Engineering Design-Build).
The elevations show structural details including floor heights (first floor at 100'-0", mezzanine at 111'-9", roof at 127'-0", and top of CMU at 131'-4"), wall openings, and reinforcement patterns. The drawing contains specific technical requirements for wall construction and openings, though the detailed notes are not fully legible in this image. This appears to be part of a larger set of construction documents for a boiler plant replacement project at a VA facility.
View the file
Other files
Show 40 more
Latest 50 of 134 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1ST FLOOR
100'-0"
ROOF
127'-0"
MEZZANINE
111'-9"
T.O. CMU
131'-4"
AC B.2 A.1BB.3
T.O. FTG
95'-4"
1ST FLOOR
100'-0"
ROOF
127'-0"
MEZZANINE
111'-9"
T.O. CMU
131'-4"
A CB.2A.1 B B.3
T.O. FTG
95'-4"
1ST FLOOR
100'-0"
ROOF
127'-0"
MEZZANINE
111'-9"
T.O. CMU
131'-4"
61 2 31.1 5.1
T.O. FTG
95'-4"
1ST FLOOR
100'-0"
ROOF
127'-0"
MEZZANINE
111'-9"
T.O. CMU
131'-4"
6 123 1.15.1
T.O. FTG
95'-4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Architecture Engineering Design-Build paradigm
AutoCAD SHX Text D1
AutoCAD SHX Text 1/8" = 1'-0"
AutoCAD SHX Text
NORTH WALL REINFORCING ELEVATION
AutoCAD SHX Text F1
AutoCAD SHX Text 1/8" = 1'-0"
AutoCAD SHX Text
SOUTH WALL REINFORCING ELEVATION
AutoCAD SHX Text D5
AutoCAD SHX Text 1/8" = 1'-0"
AutoCAD SHX Text
WEST REINFORCING ELEVATION
AutoCAD SHX Text F5
AutoCAD SHX Text 1/8" = 1'-0"
AutoCAD SHX Text
EAST WALL REINFORCING ELEVATION
AutoCAD SHX Text W16x26
AutoCAD SHX Text L02
AutoCAD SHX Text L04
AutoCAD SHX Text D01
AutoCAD SHX Text D03
AutoCAD SHX Text D03
AutoCAD SHX Text L03
AutoCAD SHX Text D01
AutoCAD SHX Text D01
AutoCAD SHX Text D01
AutoCAD SHX Text D01
AutoCAD SHX Text L02
AutoCAD SHX Text D01
AutoCAD SHX Text D02
AutoCAD SHX Text L02
AutoCAD SHX Text L01
AutoCAD SHX Text L01
AutoCAD SHX Text L01
AutoCAD SHX Text L05
AutoCAD SHX Text L05
AutoCAD SHX Text L05
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text W01
AutoCAD SHX Text L06
AutoCAD SHX Text L06
AutoCAD SHX Text NOTES: 1. SEE ARCH ELEVATIONS FOR ADDITIONAL INFORMATION ON OPENINGS IN WALLS SEE ARCH ELEVATIONS FOR ADDITIONAL INFORMATION ON OPENINGS IN WALLS 2. SEE SE201 ELEVATIONS FOR CONFIGURATION OF REINFORCING IN ADDITION TO TYPICAL SEE SE201 ELEVATIONS FOR CONFIGURATION OF REINFORCING IN ADDITION TO TYPICAL REINFORCING CALLED OUT FOR WALLS. 3. ENVELOPE BLAST RATING MINIMUM REQUIREMENTS FOR DESIGN/CERTIFICATION OF ENVELOPE BLAST RATING MINIMUM REQUIREMENTS FOR DESIGN/CERTIFICATION OF COMPONENTS LOADING SHALL BE MIN. 13.44 PSI AT 50.78 PSI-MSEC. 4. WINDOWS SHALL BE LAMINATED AND DESIGNED FOR BLAST LOADING, IF IGU SYSTEMS WINDOWS SHALL BE LAMINATED AND DESIGNED FOR BLAST LOADING, IF IGU SYSTEMS ARE USED, ONLY THE INNER PANE SHALL BE LAMINATED, MIN 1/4" PANE THICKNESS. 5. WINDOW AND DOOR FRAMES AND ANCHORAGE SHALL BE DESIGNED FOR COLLECTED WINDOW AND DOOR FRAMES AND ANCHORAGE SHALL BE DESIGNED FOR COLLECTED BLAST LOADING INDICATED IN NOTE 3.
AutoCAD SHX Text
WALL OPENING SCHEDULE
AutoCAD SHX Text
MARK
AutoCAD SHX Text
BOTTOM ELEVATION
AutoCAD SHX Text
TOP ELEVATION
AutoCAD SHX Text 0'-0"
AutoCAD SHX Text 7'-4"
AutoCAD SHX Text
DO1
AutoCAD SHX Text 0'-0"
AutoCAD SHX Text 8'-8"
AutoCAD SHX Text D03
AutoCAD SHX Text D02
AutoCAD SHX Text L01
AutoCAD SHX Text
WO#
AutoCAD SHX Text
OPENING HEIGHT
AutoCAD SHX Text 7'-4"
AutoCAD SHX Text 8'-8"
AutoCAD SHX Text
OPENING WIDTH
AutoCAD SHX Text 3'-4"
AutoCAD SHX Text 14'-0"
AutoCAD SHX Text 0'-0"
AutoCAD SHX Text 7'-4"
AutoCAD SHX Text 7'-4"
AutoCAD SHX Text 6'-4"
AutoCAD SHX Text
JAMB REINFORCING
AutoCAD SHX Text
HEADER/SILL REINFORCING
AutoCAD SHX Text L02
AutoCAD SHX Text L03
AutoCAD SHX Text W01
AutoCAD SHX Text L04
AutoCAD SHX Text 12'-5 1/2"
AutoCAD SHX Text 21'-1"
AutoCAD SHX Text 8'-7 1/2"
AutoCAD SHX Text 3'-4"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text 9'-0"
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text 1'-4"
AutoCAD SHX Text 9'-4"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text
LO#
AutoCAD SHX Text
DO#
AutoCAD SHX Text
SEE SHEET SE201
AutoCAD SHX Text
SEE SHEET SE201
AutoCAD SHX Text 1'-4"
AutoCAD SHX Text 9'-4"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text
DOOR OPENINGS - EXTERIOR, BLAST RATED, SEE SPECS
AutoCAD SHX Text
LOUVER OPENINGS - EXTERIOR, BLAST RATED, SEE SPECS
AutoCAD SHX Text
WINDOW OPENINGS - EXTERIOR, BLAST RATED, SEE SPECS
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 10'-0"
AutoCAD SHX Text L05
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 16'-8"
AutoCAD SHX Text 24'-8"
AutoCAD SHX Text L06
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text 21'-0"
AutoCAD SHX Text 25'-0"
AutoCAD SHX Text L07
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text 4'-0"
AutoCAD SHX Text 16'-8"
AutoCAD SHX Text 24'-8"
AutoCAD SHX Text L07
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WALL ELEVATION REINFORCING DIAGRAMS
AutoCAD SHX Text
SE201
AutoCAD SHX Text 200 Envoy Circle, Suite 201, Louisville KY 40299 - www.paradigmusa.com
AutoCAD SHX Text
FULLY SPRINKLERED
AutoCAD SHX Text
DESIGN REPLACE BOILER PLANT
AutoCAD SHX Text 438-22-900
AutoCAD SHX Text
AutoCAD SHX Text
SIOUX FALLS VAMC
AutoCAD SHX Text
SIOUX FALLS, SD 57105
AutoCAD SHX Text
TWW
AutoCAD SHX Text
DRW
AutoCAD SHX Text
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text 08-09-2024
AutoCAD SHX Text
1808 DEEP CREEK RD. OKC, OK 73131 918.527.7166 INFO@MOONTREELLC.COM
AutoCAD SHX Text
ADDENDUM 1
AutoCAD SHX Text
AutoCAD SHX Text 08-09-24
AutoCAD SHX Text
ADDENDUM 2 (NO STRUCTURAL CHANGES)
AutoCAD SHX Text
AutoCAD SHX Text
XX-XX-XX
AutoCAD SHX Text
ADDENDUM 3
AutoCAD SHX Text
AutoCAD SHX Text 01-17-25
AutoCAD SHX Text GENERAL NOTES A. GROUND FINISHED FLOOR ASSUMED ELEVATION = 100'-0" (35.50') ALL ELEVATIONS ARE GROUND FINISHED FLOOR ASSUMED ELEVATION = 100'-0" (35.50') ALL ELEVATIONS ARE BASED ON THIS DATUM UNLESS NOTED OTHERWISE. B. SEE PLANS FOR DETAIL REFERENCES RELATIVE TO ITEMS SHOWN THIS SHEET. SEE PLANS FOR DETAIL REFERENCES RELATIVE TO ITEMS SHOWN THIS SHEET. C. COORDINATE LIMITS AND LOCATION OF VENEER WITH ARCHITECTURAL DRAWINGS. DIMENSIONS COORDINATE LIMITS AND LOCATION OF VENEER WITH ARCHITECTURAL DRAWINGS. DIMENSIONS SHOWN TO OUTSIDE OF BUILDING ARE TO FACE OF CONCRETE WALL, TYP. D. VERIFY ALL WALL OPENING AND INTERIOR WALL DIMENSIONS AND LOCATIONS WITH VERIFY ALL WALL OPENING AND INTERIOR WALL DIMENSIONS AND LOCATIONS WITH ARCHITECTURAL DRAWINGS. E. SEE ARCH. FOR CONTROL JOINT SPACING IN BRICK FACADE. BRICK JOINTS ARE REQUIRED SEE ARCH. FOR CONTROL JOINT SPACING IN BRICK FACADE. BRICK JOINTS ARE REQUIRED AS SHOWN ON ARCH DRAWINGS.
AutoCAD SHX Text KEY NOTES 1. BRACING AND BACKUP FRAME ABOVE AND AROUND WALL OPENINGS GREATER THAN 8'-0" BRACING AND BACKUP FRAME ABOVE AND AROUND WALL OPENINGS GREATER THAN 8'-0" WIDTH, SEE DETAIL REFERENCES AT THESE LOCATIONS, TYP. 2. FULL HEIGHT CMU WALL EXPANSION JOINT, SEE ARCH FOR BRICK EXPANSION JOINTS. EA. FULL HEIGHT CMU WALL EXPANSION JOINT, SEE ARCH FOR BRICK EXPANSION JOINTS. EA. SIDE OF JOINT, 2 CELLS GROUTED AND REINFORCED WITH (1) #5 BARS EA. FACE OF WALL, 2.5" CLEAR FROM FACE, SEE CMU REINFORCING DETAILS, TYP. 3. TYPICAL WALL REINFORCING IN CMU WALLS (2) #5 AT 16" O.C. (1 BAR EA. FACE). TYPICAL WALL REINFORCING IN CMU WALLS (2) #5 AT 16" O.C. (1 BAR EA. FACE). 4. ALL VERTICAL CMU CELL REINFORCING AND HORIZONTAL BOND BEAM BARS SHOWN ARE #5 ALL VERTICAL CMU CELL REINFORCING AND HORIZONTAL BOND BEAM BARS SHOWN ARE #5 BARS EA. FACE OF WALL, 2.5" CLEAR FROM FACE, TYP. 5. ADDITIONAL REINFORCED CELLS AT JAMBS AS SHOWN. ADDITIONAL REINFORCED CELLS AT JAMBS AS SHOWN. 6. BOND BEAMS WITH REINFORCING TOP AND BOTTOM OF OPENING AS SHOWN, EXTEND BOND BEAMS WITH REINFORCING TOP AND BOTTOM OF OPENING AS SHOWN, EXTEND REINFORCING MIN 24" BEYOND OPENING EA. SIDE., TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
C2/SF401
AutoCAD SHX Text
AutoCAD SHX Text MASONRY SPECIFICATION NOTES 1. HOLLOW CONCRETE MASONRY UNITS SHALL MEET ASTM SPECIFICATION C90, TYPE II. THE HOLLOW CONCRETE MASONRY UNITS SHALL MEET ASTM SPECIFICATION C90, TYPE II. THE SPECIFIED DESIGN COMPRESSIVE STRENGTH OF CONCRETE MASONRY (f'm) SHALL BE 2000 PSI. THE NET AREA COMPRESSIVE STRENGTH OF THE CONCRETE MASONRY UNITS SHALL BE 2800 PSI. 2. MORTAR SHALL MEET THE PROPERTY SPECIFICATIONS OF A.S.T.M. C270 TYPE "S" MORTAR. MORTAR SHALL MEET THE PROPERTY SPECIFICATIONS OF A.S.T.M. C270 TYPE "S" MORTAR. 3. GROUT SHALL MEET A.S.T.M. SPECIFICATION C476 AND HAVE A MINIMUM 28 DAY GROUT SHALL MEET A.S.T.M. SPECIFICATION C476 AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2000 PSI. 4. GROUT PLACED BY THE LOW LIFT GROUTING METHOD SHALL BE MECHANICALLY GROUT PLACED BY THE LOW LIFT GROUTING METHOD SHALL BE MECHANICALLY CONSOLIDATED USING A VIBRATOR WITH A MAXIMUM 3/4 INCH DIAMETER HEAD. REFER TO SPECIFICATION FOR HIGH LIFT GROUTING PROCEDURES. 5. HORIZONTAL JOINT REINFORCEMENT SHALL BE LADDER TYPE (REFER TO SPECIFICATIONS). HORIZONTAL JOINT REINFORCEMENT SHALL BE LADDER TYPE (REFER TO SPECIFICATIONS). JOINT REINFORCEMENT SHALL BE SPACED AT 8 INCHES ON CENTER BELOW FINISHED FLOOR AND IN PARAPETS, AND 16 INCHES ON CENTER ABOVE FINISHED FLOOR. 6. REINFORCING STEEL SHALL MEET ASTM SPECIFICATION A615, GRADE 60. REINFORCING STEEL SHALL MEET ASTM SPECIFICATION A615, GRADE 60. 7. CONCRETE MASONRY SHALL BE LAID IN RUNNING (COMMON) BOND. CONCRETE MASONRY SHALL BE LAID IN RUNNING (COMMON) BOND. 8. CONCRETE MASONRY BELOW FINISHED FLOOR/GRADE SHALL BE NORMAL WEIGHT UNITS CONCRETE MASONRY BELOW FINISHED FLOOR/GRADE SHALL BE NORMAL WEIGHT UNITS AND SHALL HAVE ALL THE CELLS FULLY GROUTED. CONCRETE MASONRY ABOVE FINISHED FLOOR/GRADE SHALL BE MEDIUM WEIGHT OR LIGHT WEIGHT. REFER TO DETAILS FOR PARTIAL OR SOLID GROUT REQUIREMENTS FOR CMU ABOVE FINISHED FLOOR/GRADE ALL CELLS WITH REINFORCING SHALL BE GROUTED SOLID. 9. REFER TO CMU WALL REINFORCING DIAGRAM AND CMU WALL VERTICAL REINFORCING REFER TO CMU WALL REINFORCING DIAGRAM AND CMU WALL VERTICAL REINFORCING SCHEDULE FOR PRIMARY WALL REINFORCEMENT. SEE WALL ELEVATIONS FOR JAMB, LINTEL, EXPANSION JOINT AND OTHER ADDITIONAL REINFORCING REQUIREMENTS. 10. REFER TO CMU SPECIFICATIONS, WALL REINFORCING DIAGRAM, DETAILS, TYPICAL MASONRY REFER TO CMU SPECIFICATIONS, WALL REINFORCING DIAGRAM, DETAILS, TYPICAL MASONRY WALL OPENING DIAGRAM AND SCHEDULE, AND EQUIPMENT SUPPLIER DRAWINGS AND DETAILS FOR ADDITIONAL REINFORCING AT OPENINGS, CONTROL JOINTS, CORNERS AND ENDS OF WALL PANELS. 11. REFER TO WALL SECTIONS, DETAILS AND EQUIPMENT SUPPLIER DRAWINGS AND DETAILS REFER TO WALL SECTIONS, DETAILS AND EQUIPMENT SUPPLIER DRAWINGS AND DETAILS FOR MISCELLANEOUS BOND BEAM LOCATIONS AND EMBEDDED ITEMS. USE OPEN KNOCK OUT BOND BEAM BLOCK. DO NOT USE TROUGH TYPE BLOCKS FOR BOND BEAMS. DO NOT CONTINUE BOND BEAM REINFORCING THROUGH CONTROL JOINTS. 12. CMU WALLS SHALL RECEIVE TEMPORARY BRACING. TEMPORARY BRACING SHALL NOT BE CMU WALLS SHALL RECEIVE TEMPORARY BRACING. TEMPORARY BRACING SHALL NOT BE REMOVED UNTIL WALL IS PERMANENTLY BRACED BY CONNECTION TO THE STRUCTURE AND ROOF DIAPHRAGM IS FULLY CONNECTED. CONSTRUCTION BRACING FOR MASONRY WALLS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE BUILDING IS LOCATED. MASONRY SUBMITTALS SHALL CONTAIN A LETTER, SEALED BY THE PROFESSIONAL ENGINEER, STATING THE DESIGN LOADS AND CRITERIA WHICH WERE USED IN THE BRACING DESIGN. THE BRACING DESIGN SHALL BE SIGNED AND SEALED BY THE PROFESSIONAL ENGINEER AND SHALL BE ISSUED TO THE OWNER AFTER SUBMITTAL REVIEW AND PRIOR TO STARTING MASONRY CONSTRUCTION. 13. PROVIDE L6 X 4 X 3/8 (LLV) LOOSE LINTEL FOR OPENINGS UP TO 6'-0" IN WIDTH. PROVIDE L6 X 4 X 3/8 (LLV) LOOSE LINTEL FOR OPENINGS UP TO 6'-0" IN WIDTH. PROVIDE L8 X 4 X 1/2 (LLV) LOOSE LINTEL FOR OPENINGS 6'-0" WIDE TO 10'-0" WIDE. ANY LINTEL OVER 10'-0" SHALL BE AS SHOWN IN STRUCTURAL DETAILS. . 14. CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL NEW ADHESIVE ANCHORS INSTALLED INTO CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL NEW ADHESIVE ANCHORS INSTALLED INTO EXISTING WALLS AND DETERMINE IF EXISTING GROUT IS SUFFICIENT FOR INSTALLATION OF ANCHOR. ANCHORS INSTALLED IN GROUT FILLED CONCRETE MASONRY UNITS SHALL ONLY BE USED WHERE SPECIFIED ON THE DRAWINGS. ANCHORS MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS. REFER TO DETAILS FOR ANCHOR SIZE AND EMBEDMENT. SUBSTITUTIONS TO THE SPECIFIED ANCHORS MUST BE APPROVED BY THE COR.