MP500 - PIPING DETAILS.pdf
PDF 586 KB Posted
- Solicitation number
- 36C26324R0136
About this file
This file contains mechanical engineering drawings showing detailed piping specifications and installation requirements for a boiler plant project at the Sioux Falls VA Medical Center. The drawings include schedules and diagrams for pipe anchors, hangers, supports, and equipment mounting details for packaged boilers, deaerators, and condensate storage tanks.
The drawings specify dimensions and requirements for pipe anchor bolt patterns, insulation shields, trapeze hangers (rated for up to 1000 lb uniform load), equipment concrete bases, and pipe trench details. Key specifications include maximum pipe support spacing charts for various pipe sizes, insulation requirements for chilled water/steam/condensate systems, and concrete foundation details for boiler mounting. The drawings are part of a 100% Construction Documents package dated June 25, 2024, with Addendum 3 dated January 16, 2025, for VA project number 438-22-900.
View the file
Other files
Show 40 more
Latest 50 of 134 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
E
P
T
L
L + 3"
L + 4"
L + 8"
D+4"
D+8"
PIPE ANCHOR SCHEDULE
D L P T E N S BOLT PATTERN
NOTES:
A. INSTALL WALL PLATE FIRST THEN
WELD ON REMAINING ASSEMBLY. ONE
WALL PLATE FOR BOTH CHILLED
WATER S.&R. IS OPTIONAL.
ANCHOR BOLTS
N=NUMBER S=SIZE
DRILLØ = S+[ 1/8"]
in in in in in in in 7/8
7/8
7/8
7/8
7/8
7/8
1/4
1/4
1/4
1/4
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
5/8
3/8
3/4
3/4
3/4
3/4
3/4
3/4
81/2
INSULATE AS INDICATED FOR ALL CHILLED WATER.
INSULATE PIPE ONLY FOR STEAM, CONDENSATE &
HEATING WATER.
NOTE A
D=PIPE O.D.
P
D
C
D+[1"]
INSULATE AS INDICATED FOR ALL CHILLED
WATER. INSULATE PIPE ONLY FOR STEAM,
CONDENSATE & HEATING WATER.
NOTE:
WHERE USED FOR COPPER TUBE OR PIPE, BRAZE TO FABRICATED STEEL ANCHOR
D+[21/2"]
D+[43/4"]
D+[11/2"]
D+[33/4"]
[5/16"]
ANCHOR BOLTS N=NUMBER
S=SIZE
DRILLØ = S+[ 1/16"]
STL PIPE OR
COPPER TUBE
D=PIPE O.D.
NOTE A
PIPE ANCHOR SCHEDULE
D P C N S BOLT PATTERN
in in in in in
1/2"
43/4
21/2
11/2
5/8
1/2
3/8
3/8
3/8
1/2
3/8
3/8
1/4
3/4
5/8
5/8
5/8 m m 1"
M
AX
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS
HANGER SEE
SPECIFICATIONS
TYPE 1 - ADJUSTABLE CLEVIS
HANGER SEE
SPECIFICATIONS
TYPE 43 -
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN
[FT]
[FT]
[THRU3/4]
[7]
[5]
[1]
[7]
[6]
[11/4]
[7]
[7]
[11/2]
[9]
[8]
[2]
[10]
[8]
[21/2]
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
PROVIDE INSULATION
SHIELD & INSERT FOR
ALL PIPING 8" MIN
BAND
1-5/8" 12 GAUGE
CHANNEL OR
2"X2"X1/4" ANGLE
1/2" DIA. HANGER
RODS 36" MAX
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9PSF MIN
DENSITY) UNDER
INSULATION
INSULATION
(VAPOR BARRIER
TYPE IS REQUIRED
FOR LOW
TEMPERATURE
PIPE
HANGER ROD
NOTE:
SEE SPECIFICATIONS FOR DETAILED HANGER
REQUIREMENTS
4 PIPE HANGERS
NTS
3 LARGE PIPE ANCHOR 6"-8"
NTS
SMALL PIPE ANCHOR 1 12" - 4"
NTS
EQUIPMENT ANCHORING - PACKAGED BOILER AND DEAERATOR
AND CONDENSATE STORAGE TANKS
NTS
CONCRETE
FOUNDATION
BOILER BASE
FRAME
PLATE WELDED TO BASE
(PLATE DESIGNED BY BOILER
FRAME MANUFACTURER)
ANCHOR BOLTS SIZE AND
QUANTITY DETERMINED BY
CONTRACTOR BASED ON
BOILER FURNISHED
NOTES:
1. PROVIDE SLOTTED HOLES IN PLATES TO ALLOW THERMAL EXPANSION IF
RECOMMENDED
BY BOILER MANUFACTURER
ANCHOR BOLT
PLATE
CONC.
FOUNDATION
REBAR
BOILER BASE
FRAME
CONC.
PIERS
TANK
SADDLES
ANCHOR
BOLTS
(TYPICAL)
PLAN
SLOTTED HOLE
LENGTH = BOLT SIZE
15mm [+0.5"] EACH
SIDE
10mm [3/8"] THK.
STEEL PLATE
BOLTED TO PIER
TANK
SADDLE
CONCRETE
PIER
SADDLE
BEAM
ALTERNATE
FOR TANKS
SUPPORTED
BY STEEL
BEAMS
REINFORCEMENT
PLATES
BOLTS
ELEVATION
REBAR
ANCHOR BOLT
FLOOR
PLAN
ELEVATION
BOILER
NOTES:
1.
2.
COORDINATE TRENCH DETAIL
WITH ARCHITECTURAL &
STRUCTURAL.
REFER TO SPECIFICATION,
SEALING & CAULKING.
VA
R
IE
S
2 - SUPPORTS UP TO 24" [600mm] SPAN
VARIES
CENTER BOLT FOR SPAN
GREATER THAN 24"[600mm]
4"[100mm] 5.4#7/8"[22mm]Ø
TYPE 40 SHIELD
BANDED TO PIPE
HIGH DENSITY INSERT
TYPICAL COLD PIPE TYPICAL HOT
PIPE
TYPE 39
SADDLE
REMOVABLE COVER
CAULK AND
SEAL
3/ 4"
[1 9m m
SLOPE
6 PIPE TRENCH IN A BUILDING
NTS
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR SLAB)
PLAN
TYPICAL ANCHOR BOLT
NUT & WASHER
SECTION B-B
EQUIPMENT BASE PLATE
PROVIDE #3 BARS 12" [300mm] O.C. EACH
WAY IN THE BASE & DOWEL BASE TO
FLOOR
EQUIPMENT BASE PLATE
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
WELD HEAD TO PLATE OR
BEND OVER END 5D
FLOOR
PIPE SLEEVE (5D, 3" [75mm]
MIN.)
ANCHOR BOLT
(TYP)
CONCRETE BASE
NOTE:
L & W DIMENSIONS SHALL BE 6"
[150mm] GREATER THAN THE
EQUIPMENT BASE PLATE.
L
W
A
A
BB
D
2D
[400mm] 16"
5" M
IN
[1 m m
L /1
5"
M
IN
[1 m m
L /1
5D
TYPICAL ANCHOR BOLT
NUT & WASHER
[2 5m m
5D
CONCRETE EQUIPMENT BASES
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Revisions: Date:
Architecture Engineering Design-Build paradigm
PIPING DETAILS
CONTROLLED UNCLASSIFIED INFORMATION
BDI MFM
SIOUX FALLS BOILER PLANT 438-22-900
VAMC-Sioux Falls: 2501 W 22nd St, Sioux Falls, SD 57105
100% CONSTRUCTION DOCUMENTS
06/25/2024
FULLY SPRINKLERED
Burns & McDonnell Engineering Company, Inc.
9450 WARD PARKWAY, KANSAS CITY, MO
Burns & McDonnell Engineering Company, Inc.
9450 WARD PARKWAY, KANSAS CITY, MO
Burns & McDonnell Engineering Company, Inc.
9450 WARD PARKWAY, KANSAS CITY, MO
3 Addendum 3 01-17-2025
Jan-16-2025
File details come from the government source that posted it. Updated .