Addendum specs 040822.pdf
PDF 375 KB Posted
- Solicitation number
- 36C26322R0065
About this file
This pre-solicitation notice seeks proposals for a construction project to build a new chiller plant at the Omaha VA Medical Center in Omaha, Nebraska. The project involves constructing a new building to house two centrifugal chillers and relocate a temporary chiller, designed to be expandable for future campus growth. A metal storage shed will be removed. The estimated construction cost is $10-20 million. Deductive bid alternates are included. The solicitation will be posted on February 8th, with a request for proposal due date of March 8th. The award period of performance is 550 calendar days from notice to proceed. The solicitation requires performance, payment, and irrevocable letter of credit bonds within 10 days of award. This opportunity is set aside for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26322R0065 0004.docx | DOCX document | |
| 36C26322R0065 0003.docx | DOCX document | |
| Addendum Plan SheetsPart-4.pdf | ||
| Addendum Plan SheetsPart-2.pdf | ||
| Addendum Plan SheetsPart-6.pdf | ||
| Addendum Plan SheetsPart-1.pdf | ||
| Addendum 040822.pdf | ||
| Addendum Plan SheetsPart-7.pdf | ||
| Addendum Plan SheetsPart-3.pdf | ||
| Addendum Plan SheetsPart-8.pdf | ||
| Addendum Plan SheetsPart-5.pdf | ||
| Geotechnical Report Terracon no 05215161R01.pdf | ||
| HMS VA Omaha 103119.pdf | ||
| S02_Specs - Volume 1 revised.pdf | ||
| S02_ATTACH - Specs - Volume 2 (1376 pages).pdf | ||
| Omaha VA Chiller photos.pdf | ||
| S02_ATTACH - Drawings (132 pages).pdf | ||
| 36C26322R0065 0002.docx | DOCX document | |
| 36C26322R0065 Final.docx | DOCX document | |
| Site Vist Sign In sheet.pdf | ||
| 36C26322R0065 0001.docx | DOCX document | |
| 36C26322R0065.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSTRUCT COMBINED ENERGY PLANT PHASE 1
PROJECT #636-18-304
OMAHA VA MEDICAL CENTER 11-30-21
08 71 00-1
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
Section 07 92 00 JOINT SEALANTS: caulking
Section 08 11 13 HOLLOW METAL DOORS & FRAMES: hardware application
Section 09 06 00 SCHEDULE FOR FINISHES.
Section 09 91 00 PAINTING.
Division 26 ELECTRICAL.
Section 28 31 00 FIRE DETECTION AND ALARM.
1.3 GENERAL
All hardware shall comply with ABAAS, (Architectural Barriers Act
Accessibility Standard) unless specified otherwise.
Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
Hardware for Labeled Fire Doors and Exit Doors: conform to NFPA 80 requirements for labeled fire doors and NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified under paragraph HARDWARE SETS. In lieu of UL labeling/listing, test reports from a nationally recognized testing agency may be submitted showing hardware has been tested per UL test methods and conforms to NFPA requirements.
Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
The following items shall be of same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
08 71 00-2
1.4 WARRANTY
Automatic door operators shall be subject to FAR Clause 52.246-21, except the Warranty period shall be 2-years in lieu of 1-year for all items except as noted:
1. Locks, latch-sets, and panic hardware: 5-years.
2. Door closers and continuous hinges: 10-years.
1.5 MAINTENANCE MANUALS
Section 01 00 00 GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals/instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
Submittals shall be per Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6-copies of schedule per Section 01 33 23. Submit 2 final copies of approved schedules to VAMC Locksmith as record copies
(VISN Locksmith if the VAMC does not have a locksmith).
Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:
Hardware
Item
Quantity Size Reference
Publication
Type No.
Finish Mfr.
Name &
Catalog
No.
Key
Control
Symbols
UL Mark
(fire rated and listed)
ANSI/BHMA
Finish
Designation
Ligature Resistant Door Alarm Riser Diagram: prepare/submit 6-copies of shop drawings of electric riser diagram complete with all required equipment components. Submission shall be per Section 01 33 23 for review/approval by project CO. Along with shop drawing submittal provide installation data. At completion of project provide CO with operation and maintenance manuals
Samples and Manufacturers' Literature:
1. Samples: all proposed hardware items not previously approved by
Builders Hardware Manufacturers Association shall be submitted for approval. Tag/mark all items with manufacturer name, catalog number and project number.
08 71 00-3
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if Contractor proposes to use the manufacturer's product specified.
Certificate of Compliance & Test Reports: submit certificates that hardware conforms to requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. Testing shall have been conducted either in manufacturer plant/certified by an independent testing laboratory or conducted in an independent laboratory, within 4-years of submittal of reports for approval.
1.7 DELIVERY & MARKING
Deliver items of hardware to job site in original containers, complete with necessary appurtenances including screws, keys, and instructions.
Tag one of each different item of hardware. Deliver to COR for reference purposes. Tag shall identify items by Project Specification number and manufacturer's catalog number. Items shall remain on file in COR's office until all similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
Convene a preinstallation meeting not less than 30-days before start of door hardware installation. Require attendance of parties directly affecting work, including Contractor and Installer, Architect, Project
Engineer and VA Locksmith, Hardware Consultant, and Hardware
Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
Hardware Set Symbols on Drawings: except protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements
08 71 00-4 for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
Keying: All cylinders shall be keyed into existing Great or Grand Master
Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset.
Cylinders shall be 6 or 7 pin type. Keying information shall be furnished by the COR.
Keying: new Great Grandmaster key shall be established for the project.
Key system shall be small format (best size/profile) removable core type as previously described. Key blanks shall be protected by a utility patent with min.7-years remaining on patent from construction start and protected by contract-controlled distribution. Manufacturer shall furnish code pattern listings in both paper and electronic formats so keys may be reproduced by code. Provide electronic format in file type required by project’s key control software. Manufacturer shall design the new key system with capacity to rekey existing system and provide for 25% expansion capability beyond this requirement. Submit key chart for approval showing proposed keying layout/listing expansion capacity
1. Keying information will be furnished to Contractor by COR.
2. Supply information regarding cylinder lock key control to equipment manufacturer having cylinder type locks. Notify COR when and to whom keys/keying information is supplied. Return all such keys to COR
1.10 APPLICABLE PUBLICATIONS
Publications listed below form a part of this specification to the extent referenced and in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
ASTM International (ASTM):
F883-13.................Padlocks
E2180-18................Standard Test Method Determining the Activity of
Incorporated Antimicrobial Agent(s) In Polymeric or Hydrophobic Materials
American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
08 71 00-5
A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.11-14..............Cabinet Locks
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
Underwriters Laboratories (UL):
Building Materials Directory
PART 2 - PRODUCTS
2.1 BUTT HINGES
ANSI A156.1. Provide 3-knuckle hinges, except 5-knuckle when required hinge type is not available in 3-knuckle version (some types of swing-
08 71 00-6 clear hinges). The following butt hinges shall be used for types of doors listed, except where otherwise specified:
1. Exterior Doors: Type A2112/A5112 doors 900mm (36”) wide or less and
Type A2111/A5111 doors over 900mm (36”) wide. Hinges for exterior outswing doors shall have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless-steel material.
2. Interior Doors: Type A8112/A5112 doors 900mm (36”) wide or less and
Type A8111/A5111 doors over 900mm (36”) wide. Hinges for doors exposed to high humidity areas (toilet rooms, janitor rooms, etc.)
shall be of stainless-steel material.
Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210mm (48”) high: 2-hinges.
2. Doors 1210mm (48”) to 2260mm (7’-5”) high: 3-hinges min.
3. Doors greater than 2260mm (7’-5”) high: 4-hinges.
4. Doors up to 900mm (36”) wide, standard weight: 114mm x 114mm (4-1/2” x 4-1/2”) hinges.
5. Doors over 900mm (36”) to 1065mm (42”) wide, standard weight: 127mm x
114mm (5” x 4-1/2”).
6. Doors over 1065mm (42”) to 1210mm (48”), heavy weight: 127mm x 114mm
(5” x 4-1/2”).
7. Provide heavy-weight hinges where specified.
8. Doors weighing 330 kg (150 pounds) or more, furnish 127mm (5”) high hinges.
See Articles "MISCELLANEOUS HARDWARE" "HARDWARE SETS" for pivots/hinges other than butts specified above and continuous hinges specified below.
2.2 CONTINUOUS HINGES
ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
General: Minimum 0.120” (3mm) thick, hinge leaves with minimum overall width of 4” (102mm); fabricated to full door and frame height and to template screw locations with components finished after milling and drilling are complete
Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a
Teflon-coated 6.35mm (0.25”) minimum diameter pin that extends entire length of hinge.
1. Base Metal Exterior Hinges: Stainless-steel.
2. Base Metal Interior Hinges: Stainless-steel or Steel.
08 71 00-7
3. Base Metal Hinges Fire-Rated Assemblies: Stainless-steel or Steel.
4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
7. Where thru-wire power transfers are integral to hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
8. Where models are specified provide an integral wrap-around edge guard for door’s hinge edge, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow door to be adjusted within the wrap-around edge guard.
2.3 DOOR CLOSING DEVICES
Closing devices shall be products of 1-manufacturer for each type specified.
2.4 OVERHEAD CLOSERS
Conform to ANSI A156.4, Grade 1.
Closers shall conform to the following:
1. Minimum 50% adjustable closing force over minimum value for that closer and adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: provide multi-size closers, sizes 1 thru 6, except where multi-size closer not available for the required application
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where exposed to exterior or mounted in rooms experiencing high humidity, provide closer body/arm assembly of stainless-steel material
7. Have full size metal cover plastic covers will not be accepted.
8. Have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
08 71 00-8
9. Provide with required accessories for mounting application, including
(not limited to) drop or special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull nose/other regular arm brackets, longer or shorter arm assemblies, and special factory templating.
Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders
10. Arms/backcheck valve not used to stop door from overswing, except in applications where separate wall, or overhead stop cannot be used
11. Provide parallel arm closers with heavy duty rigid arm.
12. Where installed on push side of door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1½” (38mm) minimum piston diameter.
2.5 FLOOR CLOSERS AND FLOOR PIVOT SETS
Comply with ANSI A156.4. Provide stainless-steel floor plates for floor closers and floor pivots, except where metal thresholds occur. Provide cement case for all floor closers which are specified for fire doors complying with Underwriters Laboratories requirements: concealed type floor closers for classes of fire doors noted on drawings. Hold-open mechanism, when required, shall engage when door is opened 105 degrees, except when door swing is limited by building construction/equipment, hold-open feature shall engage when door is opened approximately 90 degrees. Hold-open mechanism shall be selectable on/off by turning a screw thru the floor plate. Shall have adjustable hydraulic back-check, adjustable close speed, and adjustable latch speed. Provide with delayed action when a hold-open mechanism not required. Floor closers shall be multi-sized. Single acting floor closers shall have built in dead stop.
Where required, provide closers with special cement cases appropriate for shallow deck installation or when concrete joint lines run thru the floor block-out. At offset-hung doors installed in deep reveals, provide special closer arm and spindle to allow for installation. Where stone or terrazzo applied over floor closer case, provide without floor plate, extended spindle (length as required) and special cover pan (depth as required) to allow closer to be accessed without damaging material applied over the closer. Pivots for non-labeled doors shall be cast, forged or extruded brass or bronze.
08 71 00-9
Where floor closer appears in hardware set provide the following:
1. Double Acting Floor Closers: Type C06012.
2. Single Acting Floor Closer: Type C06021 (center pivoted).
(intermediate pivot not required).
3. Single Acting Floor Closers: Type C06041 (offset pivoted).
4. Single Acting Floor Closer for Labeled Fire Doors: Type C06051
(offset pivoted).
5. Single Acting Floor Closers Lead Lined Doors: Type C06071 (offset pivoted)
2.6 DOORSTOPS
Conform to ANSI A156.16.
Provide door stops wherever an opened door/any item of hardware item strikes a wall, column, equipment, or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.
Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
Provide floor stops (Type L02141 or L02161) office areas: Type L02121 x
3-screws into floor elsewhere. Wall bumpers, where used, must be installed to impact trim or door within leading half of its width. Floor stops, where used, must be installed within 4” of wall face and impact the door within leading half of its width.
Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
Provide stop Type L02011 for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3”) core-drilled hole and filled with quick-setting cement
Omit stops where floor mounted door holders are required and when automatic operated doors occur.
Provide appropriate roller bumper for each set of doors (except where closet doors occur) where 2-doors interfere with each other’s swinging
Provide appropriate door mounted stop in individual toilets where floor or wall mounted stops cannot be used.
Provide door stops where combination closer magnetic holders are specified, except where wall stops cannot be used or floor stops cannot be installed within 4” of the wall.
08 71 00-10
Where specified wall/floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.7 OVERHEAD DOOR STOPS AND HOLDERS
Conform to ANSI Standard A156.8. Overhead holders shall be sized by holder manufacturer for each door width. Set overhead holders for 110 degree opening, unless limited by building construction/equipment.
Provide Grade 1 overhead concealed slide type: stop-only at rated and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.8 FLOOR DOOR HOLDERS
Conform to ANSI Standard A156.16. Provide extension strikes for Types
L01301 and L01311 holders where necessary.
2.9 LOCKS AND LATCHES
Conform to ANSI A156.2. Locks/latches for doors 45mm (1-3/4”) thick or over shall have beveled fronts. Lock cylinders shall have not less than
6-pins. Cylinders for locksets shall be removable core type & furnished with construction removable cores/construction master keys. Cylinder shall be removable by special key/tool. Construct all cores so they are interchangeable into core housings of all mortise locks, rim locks, cylindrical locks, and other type lock included in Great Grand Master
Key System. Disassembly of lever/lockset shall not be required to remove core from lockset. All locksets/latches on double doors with fire label shall have latch bolt with 19mm (3/4”) throw unless allowed by door manufacturer’s fire label. Provide temporary keying device/construction core to allow opening/closing during construction and prior to final core installation
In addition to above requirements, locks and latches shall comply with:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets & latch-sets, shall have lever handles fabricated from cast stainless-steel.
Provide sectional (lever x rose) lever design. No substitute lever material shall be accepted. All locks and latch-sets shall be furnished with 122.55mm (4-7/8”) curved lip strike and wrought box.
At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8”) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before
08 71 00-11 applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks installed in high-humidity locations or exposed to exterior on both sides of opening, provide non-ferrous mortise lock case.
2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latch-sets shall be furnished with
122.55mm (4-7/8”) curved lip strike/wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8”) lip-to-center dimension. Provide lever design to match Architect design or existing lever design. Where 2-turn pieces are specified for lock F76, turn piece on inside knob shall lock/unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in locked position. (This function allows emergency entry into rooms without an emergency key or special tool.)
3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
2.10 PUSH-BUTTON COMBINATION LOCKS
ANSI/BHMA A156.5 Grade 1. Battery operated pushbutton entry.
Construction: heavy duty mortise lock housing per ANSI/BHMA A156.13, Grade 1. Lever handles/operating components in compliance with ABAAS and
ADA Accessibility Guidelines. Match lever handles of locks and latch-sets on adjacent doors.
Special Features: key override to permit a master keyed security system and pushbutton security code activated passage feature to allow access without using the entry code.
2.11 ELECTROMAGNETIC LOCKS
ANSI/BHMA A156.23 electrically powered of strength/configuration noted with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA "Certified Product Directory"
1. Full exterior or interior type as required by application indicated.
2. Strength Ranking: 1500pound force (6672 N)
3. Inductive Kickback Peak Voltage: not more than 530 V.
4. Residual Magnetism: not more than 4pound force (18 N) to separate door from magnet.
Delayed-Egress Locks: BHMA A156.24 Listed under Category G in BHMA
"Certified Product Directory"
08 71 00-12
1. Means of Egress Doors: lock releases within 15 seconds after applying a force not more than 15pound force (67 N) for not more than 3-seconds, as required by NFPA 101.
2. Security Grade: activated from door’s secure side by initiating device.
3. Movement Grade: activated by door movement as initiating device.
4. Lock housing shall not project more than 4” (101mm) from underside of frame head stop.
2.12 ELECTRIC STRIKES
ANSI/ BHMA A156.31 Grade 1.
Use fail-secure electric strikes at fire-rated doors.
2.13 KEYS
Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks
100 each different keyway
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
Psychiatric keys shall be cut so first 2-bittings closest to key shoulder are shallow to provide greater strength at point of greatest torque.
2.14 KEY CABINET
ANSI Standard A156.11. Provide key cabinet made of cold rolled, 1.2mm
(0.0478”) thick furniture steel electro-welded. Doors shall have "no sag" continuous brass-pin piano type hinge and be equipped with chrome plated locking door handles, hook cam/mechanical pushbutton door lock.
Key Cabinet/Key Control System shall accommodate all project keys +25%.
Provide min. number of multiple cabinets where single cabinet of largest size will not accommodate the required number of keys.
Key tags shall consist of 2-sets: permanent self-locking/loan key snap-hook type with tag colors: red fiber marker of permanent self-locking type approximately 32mm (1-1/4”) in diameter engraved with legend "FILE
08 71 00-13
KEY MUST NOT BE LOANED." Also furnish for each hook a white cloverleaf key marker with snap-hooks engraved with legend "LOAN KEY"
Lock cylinder and lock manufacturer shall attach a key tag to keys of each lock cylinder and mark the respective item and key change number.
Provide each key group in a key gathering envelope (supplied by Key
Cabinet Manufacturer) in which lock manufacturer shall include item number, key change number, and door number. Contractor shall furnish Key
Cabinet Manufacturer the hardware and keying schedules and change keys.
Key Cabinet Manufacturer shall set up a 3-way cross index system, including master keys, alphabetically listing the keys, hooks numerically and key changes numerically on different colored index cards. Index cards shall be typewritten/inserted in durable binder.
Attach keys to 2-sets numbered tags supplied with the cabinet.
(permanent tag and loan key tag). Instruct Owner in proper use of the system. Install cabinet as directed by COR.
2.15 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
Conform to ANSI Standard A156.6.
Provide protective plates and door edging as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick/mop plates where specified. Kick plates: 254mm (10”) or
305mm (12”) high. Mop plates: 152mm (6”) high. Both kick/mop plates shall be min. 1.27mm (0.050”) thick. Provide kick/mop plates beveled on all 4 edges (B4E). On push door’s side where jamb stop extends to floor, make kick plates 38mm (1-1/2”) less than width of door, except pairs of metal doors which shall have plates 25mm (1”) less than width of each door. Extend all other kick/mop plates to within 6mm
(1/4”) of each edge of doors. Kick/mop plates shall butt astragals.
Jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates not required on following door sides:
a. Armor plate side of doors
b. Exterior side of exterior doors
c. Closet side of closet doors
d. Both sides of aluminum entrance doors.
4. Armor plates for doors listed under Article "Hardware Sets". Armor plates shall be thickness as noted in hardware set, 875mm (35”) high and 38mm (1-1/2”) less than door width, except pairs of metal doors.
08 71 00-14
Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25mm (1”) less than door width. Where top of intermediate door rail is less than 875mm (35”) from door bottom, extend armor plates to within 13mm (1/2”) of intermediate rail top.
On doors equipped with panic devices, extend armor plates to within
13mm (1/2”) of panic bolt push bar.
5. Where louver/grille occurs in lower portion of doors, substitute stretcher plate and kick plate in lieu of armor plate. Size of stretcher plate and kick plate shall be 254mm (10”) high.
6. Provide stainless-steel edge guards where specified at wood doors.
Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel/thickness to match wood door. Provide edge guards with factory cut-outs for door hardware installed or extend thru edge guard.
Provide full-height edge guards except where door rating does not allow. In such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
2.16 EXIT DEVICES
Conform to ANSI Standard A156.3. Exit devices shall be Grade 1 type and function as specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in building’s interior. Trim shall have cast satin stainless-steel lever handles of similar design as locksets. Provide key cylinders for keyed operating trim and where specified, cylinder dogging.
Surface vertical rod panics shall only be provided less bottom rod, provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.
Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.
Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.
Non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.
08 71 00-15
Exit devices for fire doors shall comply with Underwriters Laboratory requirements for Fire Exit Hardware. Submit proof of compliance.
2.17 FLUSH BOLTS (LEVER EXTENSION)
Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI
A156.16, for flush bolts required on lower part of doors.
Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
Face plates for cylindrical strikes shall be rectangular and not less than 25mm by 63mm (1” by 2-1/2”).
Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
Provide extension rods at top bolt when door height exceeds 2184mm (7’-
2”)
2.18 FLUSH BOLTS (AUTOMATIC)
Conform to ANSI A156.3 flush bolt dimension shall conform to ANSI A115.
Bolts shall conform to Underwriters Laboratory requirements for fire door hardware. Flush bolts shall automatically latch/unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flush bolt. Face plates for dustproof strike shall be rectangular and not less than 38mm by 90mm (1-1/2” by 3-1/2”)
Interior doors: provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.19 LIGATURE RESISTANT DOOR ALARM:
Provide ligature resistant, monitoring/notification system capable of detecting a ligature-initiated event at patient bedroom door. An alarm system will trigger audio & visual notification devices at the bedroom door and nurse station to alert staff of ligature emergency. System shall be addressable, self-monitoring, and able to diagnose alarm and system problems. System shall be capable of documenting ligature-initiated events
Components of Alarm System:
1. Ligature-initiating Alarm:
08 71 00-16
a. Pressure alarm assembly: nominal 1-pound pressure activated alarm.
Door alarm assembly must be constructed of stainless-steel and made by the door alarm manufacturer
b. Photoelectric sensor alarm assembly: sensors shall be positioned on door and frame within anti-ligature casings constructed of
Acetal (Polyoxmethylene-POM) an impact resistant plastic commonly called Delrin. Provide the following installation configuration for the sensors
1) 2-sensor sets at top of door at door and frame
2) 2-sensor sets at top of door at door and frame and 1-sensor set at bottom at door undercut
c. Alarm assembly circuit shall be concealed/redundant with a tamper resistant, failsafe operation.
d. Alarm assemblies to be installed with tamper resistant fasteners only
2. Hinge and Power Transfer
a. Power transfer section of hinge shall be housed at top end of continuous hinge to eliminate potential of exposed wires/flex conduit
b. Power transfer section of hinge shall be field removable to eliminate need to remove door when addressing electrical service issues
3. Local Visual Alarm (Strobe)
a. Install in corridor above monitored room doors throughout facility
b. Alarm unit: anti-ligature with sloped top, made of resilient material and fastened with tamper resistant hardware.
c. Door alarm units shall flash when any monitored door alarm is triggered at a ligature point initiated event.
d. Door alarm strobe turned off when a user code is entered at room door keypad.
4. Local Keyswitch:
a. Wall mounted, flush mounted or designed to be anti-ligature.
b. Coordinate specific location with COR and Unit Manager
c. Designed for momentary actuation with spring return.
5. Keypad:
a. Provide LCD display notification for activation of all monitored patient bedroom doors.
08 71 00-17
b. Flush mounted or designed to be anti-ligature
6. Remote Monitoring Panel and Audible Alarm:
a. Shall allow monitoring of each patient bedroom door from nurse station with visual indicator of ligature-initiated event location
b. Remote audible alarm will be a distinct tone not confused with other alarms located in the vicinity.
7. Control Panel:
a. Panel and all elements of alarm system shall be equipped with a dedicated battery backup system and emergency power feed for maintaining power to control panel in a power failure event.
b. Provide software for printing documented alarm events
2.20 DOOR PULLS WITH PLATES
Conform to ANSI A156.6 pull Type J401 152mm CTC (6” CTC) length by 19mm
(3/4”) min. diameter with plate Type J302, 90mm by 381mm (3-1/2” by 15”) unless otherwise specified. Provide pull with projection of 57.2mm (2
¼”) minimum and clearance of 38.1 mm (1 ½”) min. Cut plates of door pull plate for cylinders or turn pieces where required.
2.21 PUSH PLATES
Conform to ANSI A156.6 metal Type J302, 203mm (8”) wide by 406.4mm (16”) high. Provide metal Type J302 plates 102mm (4”) wide by 406.4mm (16”) high where push plates are specified for doors with stiles min. 203mm
(8”) wide. Cut plates for cylinders, and turn pieces where required.
2.22 COMBINATION PUSH AND PULL PLATES
Conform to ANSI 156.6. Type J303, stainless-steel 3mm (1/8”) thick, 80mm
(3-1/3”) wide by 800mm (16”) high, top and bottom edges shall be rounded. Secure plates to wood doors with 38mm (1-1/2”) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
2.23 COORDINATORS
Conform to ANSI A156.16. Coordinators, specified fire doors, shall comply with Underwriters Laboratory requirements fire door hardware.
Coordinator may be omitted on exterior door pairs when either door closes independently regardless of other door’s position. Coordinator may be omitted on interior pairs of non-labeled open when open back strike used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames unless coordinators are plated.
Provide bar type coordinators, except where gravity coordinators are
08 71 00-18 required at acoustic pairs. Bar type coordinators provide filler bars for full width and as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.24 THRESHOLDS
Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in bed of sealant with ¼-20 stainless-steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for full width of the openings.
Thresholds at elevators entrances see other specification sections.
Exterior doors/any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.
Provide with miter returns where threshold extends more than 12mm (0.5”) beyond face of frame.
2.25 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR SOUND
CONTROL DOORS
Conform to ANSI A156.22. Provide mortise/under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).
2.26 WEATHERSTRIPS (FOR EXTERIOR DOORS)
Conform to ANSI A156.22. Air leakage max. 0.50 CFM per foot of crack length (0.000774m3/s/m).
2.27 MISCELLANEOUS HARDWARE
Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):
except fire-rated doors, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to door manufacturer. Hinges shall be provided by door manufacturer.
Cylinders for Various Partitions and Doors: key cylinders same as entrance doors in which partition/door occur, except as otherwise specified. Provide cylinders to operate locking devices where specified for following partitions and doors:
1. Folding doors and partitions.
2. Wicket door (in roll-up door assemblies).
3. Slide-up and swing-up doors.
4. Fire-rated access doors-Engineer's key set.
08 71 00-19
Mutes: conform to ANSI A156.16. Provide door mutes or silencers Type
L03011 or L03021, depending on frame material (white/light gray color), on each steel/wood door frame, except fire-rated, lead-lined, and frames for sound-resistant, lightproof, and electromagnetically shielded doors.
Furnish 3-mutes for single doors and 2-mutes for each pair of doors, except double-acting doors. Provide 2-mutes for each edge of sliding door which would contact door frame.
2.28 PADLOCKS FOR VARIOUS DOORS, GATES AND HATCHES
ASTM E883, size 50mm (2”) wide chain, furnish extended shackles as required by job conditions. Provide padlocks, with key cylinders, for each door as noted.
Key padlocks as follows:
1. Constant Temperature & Cold Rooms in Research Departments: laboratory
2. Cold Room in Morgue Department: autopsy set
3. Refrigerators in Canteen Department: storage set
4. Refrigerator Room Main Kitchen Department: storage set
5. Chain Link Fence Gates for Oxygen Storage Buildings: maintenance supply set
6. Roof Access and Scuttles: engineer set
Omit padlocks on communicating refrigerator doors.
2.29 THERMOSTATIC TEMPERATURE CONTROL VALVE CABINETS
Where lock shown, equip each cabinet door (metal) with lock Type
E06213, conforming to ANSI A156.36. Key locks in Key Sets approved by
COR. See mechanical drawings/specifications for location of cabinets
Cabinet manufacturer shall supply hinges, bolts, and pulls. Ship locks to cabinet manufacturer for installation.
2.30 HINGED WIRE GUARDS (WINDOWS, DOORS & TRANSOMS) & WIRE PARTITION DOORS
Butt hinges, type A8133 (special swaging) 100mm by 90mm (4” by 3-1/2”), Finish US2C.
1. 3-hinges guards over 1060mm (42”) high.
2. 2-hinges guards less than 1060mm (42”) high.
Conform ANSI A156.36. Lock Type E06081 guards & Type E06061 partitions
1. Except as noted otherwise, key locks like entrance door/space wherein guards and partitions are located except as otherwise specified.
2. Key locks for partitions enclosing mechanical/electrical equipment in
Engineer Set. (Detailed drawings for required number of locks/butt hinges for each guard).
08 71 00-20
2.31 FINISHES
Exposed hardware surfaces shall have ANSI A156.18. Finishes on all hinges, pivots, closers, thresholds, etc. shall be as specified under
"Miscellaneous Finishes." Field painting (final coat) of ferrous hardware, see Section 09 91 00 PAINTING.
626 or 630: all exterior and interior surfaces of buildings, except where other finishes are specified.
Miscellaneous Finishes:
1. Hinges exterior doors: 626 or 630.
2. Hinges interior doors: 652 or 630.
3. Pivots: match door trim.
4. Door Closers: factory applied paint finish. Dull or Satin Aluminum color.
5. Thresholds: mill finish aluminum.
6. Cover plates for floor hinges and pivots: 630.
7. Other primed steel hardware: 600.
Hardware Finishes Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.
Special Finish: exposed hardware surfaces for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors.
Anti-microbial Coating: all hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with anti-microbial/anti-fungal coating having passed ASTM E2180 tests. Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.
2.32 BASE METALS
Apply specified U.S. Standard finishes on different base metals:
Finish Base Metal
652 Steel
626 Brass or bronze
630 Stainless steel
08 71 00-21
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
Existing buildings locate door hardware at heights matching existing hardware. Contractor shall visit site, verify existing hardware locations, and submit locations to VA COR for approval.
New buildings locate hardware on doors at specified heights, with all hand-operated hardware centered within 864mm (34”) to 1200mm (48”), unless otherwise noted:
Hardware Heights from Finished Floor:
1. Exit devices strike centerline (where applicable) 1024mm (40-5/16”)
2. Locksets & latch sets centerline of strike 1024mm (40-5/16”)
3. Dead-locks centerline of strike 1219mm (48”)
4. Hospital arm-pull 1168mm (46”) to centerline of bottom supporting bracket
5. Centerline of door pulls to be 1016mm (40”)
6. Push plates & push-pull shall be 1270mm (50”) to top of plate.
7. Push-pull latch 1024mm (40-5/16”) to centerline of strike.
8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
Closer devices and those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction/equipment. Closers shall be mounted on side of door inside rooms, stairs, and away from corridors except anteroom doors which shall have closer installed parallel arm on exterior side of doors. Exterior doors, closers shall be mounted on interior side. Where closers mounted on doors they shall be with hex nuts and bolts: foot shall be fastened to frame with machine screws.
Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45mm (1-3/4”) 900mm (36”) and less 113mm (4-1/2”)
45mm (1-3/4”) Over 900mm (36”) not more than 1200mm (48”)
125mm (5”)
35mm (1-3/8”)
(hollow core wood)
Not over 1200mm (48”) 113mm (4-1/2”)
08 71 00-22
Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
Where new hinges specified for new doors in existing frames or existing doors in new frames, new hinge sizes shall match sizes of existing hinge sizes or Contractor may reuse existing hinges provided hinge restored to satisfactory operating condition as approved by COR. Existing hinges shall not be reused on door openings of new doors and frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors/frames.
Hinges Required Per Door:
Door Description Number butts
Doors 1500mm (60”) or less in height 2 butts
Doors over 1500mm (60”)/not over 2280mm (7’-6”) high 3 butts
Doors over 2280mm (7’-6”) high 4 butts
Dutch type doors 4 butts
Doors with spring hinges 1370mm (54”) high or less 2 butts
Doors with spring hinges over 1370mm (54”) 3 butts
Fastenings: suitable size/type and harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic/quarry floor tile, or solid masonry. Fiber or Rawl-plugs and adhesives not permitted. All fastenings exposed to weather shall be of nonferrous metal.
After locks installed show in presence of COR keys operate respective locks per keying requirements. (keys, Master Key level and above shall be sent Registered Mail to Medical Center Director as well as the biting list and copy of invoice sent to COR for their records). Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
3.3 FINAL INSPECTION
Installer to provide letter to VA Resident/Project Engineer upon completion installer has visited the Project and accomplished:
1. Re-adjust hardware.
2. Evaluate maintenance procedures, recommend changes/additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
08 71 00-23
3.4 DEMONSTRATION
Demonstrate efficacy of mechanical hardware/electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA Locksmith.
3.5 HARDWARE SETS
Following sets of hardware correspond to hardware symbols shown on drawings. Those hardware sets shown on drawings will be required.
Disregard hardware sets listed in specifications not shown on drawings
Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. Numbers shown in the following sets come from BHMA standards.
ELECTRIC HARDWARE ABBREVIATIONS LEGEND:
ADO = Automatic Door Operator
EMCH = Electro-Mechanical Closer-Holder
MHO = Magnetic Hold-Open (wall- or floor-mounted)
INTERIOR SINGLE DOORS
HW-4A
Each Door to Have RATED
1 Continuous Transfer Hinge x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFER
X IN-HINGE ACCESS PANEL
1 Classroom Lock F05
1 Electric Strike E09311 (FAIL-SECURE), 24VDC
1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE
AS REQUIRED
1 Kick Plate J102
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0Y154
08 71 00-24
HW-4F
Each Door to Have: RATED
1 Continuous Hinge x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SCREWS
1 Utility Lock F09
1 Closer C02011/C02021
1 Armor Plate J101 x 1.275 MM (0.050 INCH) THICKNESS
1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE
1 Floor Stop (@ Outswing Doors) L02121 x 3 FASTENERS
1 Wall Stop (@ Inswing Doors) L02101 CONVEX
HW-4U
Each Door to Have: NON-RATED/RATED
1 Continuous Hinge -
1 Public Restroom Lock F09
1 Closer C02011/C02021
1 Closer CO2051/CO2061
1 Kick Plate J102
1 Mop Plate (@ Inswing Doors) J103
1 Floor Stop (@ Outswing Doors) L02121 x 3 FASTENERS
1 Wall Stop (@ Inswing Doors) L02101 CONVEX
1 Set Self-Adhesive Seals R0Y154
PROVIDE NON-HOLD-OPEN CLOSER AT TOILET ROOMS.
STONE THRESHOLD BY OTHER TRADES.
HW-11B
Each Pair to Have: RATED
2 Continuous Hinges x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SCREWS
1 Set Auto Flush Bolts TYPE 25
1 Storeroom Lock F07
1 Coordinator TYPE 21A
1 Overlapping Astragal with R0Y634 x R0Y154 x THRU-BOLTS
Self-Adhesive Seal
08 71 00-25
2 Closers C02011/C02021
2 Armor Plates J101 x 1.275 MM (0.050 INCH) THICKNESS
2 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE
2 Floor Stops L02121 x 3 FASTENERS
HW-E4
Each Door to Have:
NON-RATED
1 Continuous Hinge
1 Anti-Vandal Pull
1 Exit Device TYPE 1 F03 LESS TRIM
1 Latch Protector (outswing dr.)
1 Key Cylinder TYPE AS REQUIRED
1 Closer C02011
1 Kick Plate J102
1 Floor Stop L02121 x 3 FASTNERS
1 Threshold J32120 x SILICONE GASKET
1 Door Sweep R0Y416
1 Set Frame Seals R0Y164
1 Drip R0Y976
HW-E5
Each Roll-up Door to Have: NON-RATED
1 Padlock or 2 Cylinders
TYPE AS REQUIRED
BALANCE OF HARDWARE BY SECTION 08 33 00, COILING DOORS AND GRILLES
08 71 00-26
HW-E9
Each Door to Have: NON-RATED
2 Continuous Hinge
1 Exit Device TYPE 8 F01
1 Exit Device TYPE 8 F12 LESS PULL
1 Key Cylinder TYPE AS REQUIRED
2 Latch Protectors (outswing dr.)
1 Set Meeting Stile Astragals R0Y834
2 Closer C02011
2 Kick Plate J102
2 Floor Stop L02121 x (3) FASTNERS
1 Threshold J32120 x SILICONE GASKET
2 Door Sweep R0416
1 Set Frame Seals R0Y164
1 Drip
- - - E N D - - -
COMBINED ENERGY PLANT PHASE 1 (CHILLER PLANT)
OMAHA VA MEDICAL CENTER 01-01-21
10 21 13 - 1
SECTION 10 21 13
TOILET COMPARTMENTS
A. This section specifies metal toilet partitions, and urinal screens.
1.2 RELATED WORK
A. Section 05 50 00, METAL FABRICATIONS: Overhead structural steel supports for ceiling hung pilasters.
B. Section 09 06 00, SCHEDULE FOR FINISHES: Color of baked enamel finish.
C. Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES: Grab bars and toilet tissue holders.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Samples: Prime coat of paint on 150 mm (six-inch) square of metal panel with baked enamel finish coat over half of panel.
C. Manufacturer's Literature and Data: Specified items indicating all hardware and fittings, material, finish, and latching.
D. Shop Drawings: Construction details at 1/2 scale, showing installation details, anchoring and leveling devices.
E. Manufacturer's certificate, attesting that zinc-coatings conform to specified requirements.
1.4 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.
B. Federal Specifications (Fed. Spec.):
FF-B-575C...............Bolt, Hexagon and Square
C. Code of Federal Regulations (CFR):
40 CFR 247..............Comprehensive Procurement Guidelines for
Products Containing Recovered Materials
D. Commercial Item Descriptions (CID):
A-A-1925................Shield, Expansion (Nail Anchors)
A-A-60003...............Partitions, Toilet, Complete
PART 2 - PRODUCTS
10 21 13 - 2
2.1 TOILET PARTITIONS
A. Metal: water resistant; graffiti resistant; Class A flame spread rating.
B. Conform to Fed. CID A-A-60003, except as modified herein.
C. Fabricate to dimensions shown or specified.
D. Toilet Enclosures:
1. Type 1, Style B (Ceiling hung).
2. Reinforce panels shown to receive toilet tissue holders or grab bars.
3. Upper pivots and lower hinges adjustable to hold doors open 30 degrees.
4. Latching devices and hinges for handicap compartments shall comply with ADA requirements.
5. Keeper:
a. U-slot to engage bar of throw latch.
b. Combined with rubber bumper stop.
6. Wheelchair Toilets:
a. Upper pivots and lower hinges to hold out swinging doors in closed position.
b. Provide U-type doors pulls, approximately 100 mm (four inches) long on pull side.
7. Finish:
a. Finish 1 (baked enamel) on steel doors, pilasters, and enclosure panels except those adjacent to urinals and as specified.
E. Urinal Screens:
1. Type III, Style E (wall hung), finish 2 or 3.
a. With integral flanges and continuous, full height wall anchor plate.
b. Option: Full height U-Type bracket.
c. Wall anchor plate drilled for 4 anchors on both sides of screen.
2. Screen 600 mm (24 inches) wide and 1060 mm (42 inches high).
2.2 FASTENERS
A. Partition Fasteners: CID A-A-60003.
B. Use expansion bolts, CID A-A-60003, for anchoring to solid masonry or concrete.
10 21 13 - 3
C. Use toggle bolts, CID A-A-60003, for anchoring to hollow masonry or stud framed walls.
D. Use steel bolts FS-B-575, for anchoring pilasters to overhead steel supports.
PART 3 - EXECUTION
3.1 INSTALLATION
A. General:
1. Install in rigid manner, straight, plumb and with all horizontal lines level.
2. Conceal evidence of drilling,…
This is the start of the file's text. The full file is on GovTribe.