Addendum Plan SheetsPart-7.pdf
PDF 6 MB Posted
- Solicitation number
- 36C26322R0065
About this file
This notice provides details for a construction project solicitation for the Department of Veterans Affairs Nebraska-Western Iowa Health Care System. The solicitation will construct a new chiller plant adjacent to the existing boiler plant to house two centrifugal chillers and relocate a temporary chiller. The project is identified as number 636-18-304 and requires constructing the chiller plant building to later accommodate future campus growth. An existing metal storage shed must be removed. The estimated construction cost is $10-20 million. Deductive bid alternates are included. The solicitation number is 36C26322R0065 and will post on www.fedbizopps.gov on February 8th, 2022, containing specifications, drawings and bidding instructions. Bids are due on March 8th, 2022. The awarded bidder must provide performance, payment or letter of credit within 10 days of notification. The period of performance is 550 calendar days from notice to proceed. This is a service-disabled veteran-owned small business set-aside under Public Law 109-461.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26322R0065 0004.docx | DOCX document | |
| 36C26322R0065 0003.docx | DOCX document | |
| Addendum Plan SheetsPart-4.pdf | ||
| Addendum specs 040822.pdf | ||
| Addendum Plan SheetsPart-2.pdf | ||
| Addendum Plan SheetsPart-6.pdf | ||
| Addendum Plan SheetsPart-1.pdf | ||
| Addendum 040822.pdf | ||
| Addendum Plan SheetsPart-3.pdf | ||
| Addendum Plan SheetsPart-8.pdf | ||
| Addendum Plan SheetsPart-5.pdf | ||
| Geotechnical Report Terracon no 05215161R01.pdf | ||
| HMS VA Omaha 103119.pdf | ||
| S02_Specs - Volume 1 revised.pdf | ||
| S02_ATTACH - Specs - Volume 2 (1376 pages).pdf | ||
| Omaha VA Chiller photos.pdf | ||
| S02_ATTACH - Drawings (132 pages).pdf | ||
| 36C26322R0065 0002.docx | DOCX document | |
| 36C26322R0065 Final.docx | DOCX document | |
| Site Vist Sign In sheet.pdf | ||
| 36C26322R0065 0001.docx | DOCX document | |
| 36C26322R0065.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STEAM PUMP
FIN. FLR. @ 1197.00'
XFIN. FLR. @ 1197.03'
XBLDG. 22
XBLDG. 2
XBLDG. 10
XBLDG. 17
XBLDG. 23
X B
LD
G
XBLDG. X
XCHILLERS
'PT' BLDG. (NIC)
FUTURE
C O N C R
ET
E S
ID
EW
AL
K
6' CONCRETE SIDEWALK
0.9
NEW ACC
16" CWS (EX)
12" CWR (EX)
BLW GRADE
NEW UNDERGROUND
CHILEED WATER
LINES
COOLING
TOWER
ACC OUTDOOR MODULAR
CHILLER (CH-E)
PLANT/COOLING TOWER
0-MS-002
NEW CHILLER PLANT
BLDG. XX
BUILDING 2
FUTURE CHW PLANT
EXPANSION
NEW PIPING TO
TEMPORARY
CHILLER
LOCATION FOR
TEMPORARY CHILLERS
WITH POWER.
7 8
12PROVIDE TEMPORARY PIPING TO
TEMPORARY CHILLERS AND INSTALL
PER MANUFACTURER'S
RECOMMENDED INSTALLATION
INSTRUCTIONS.
VALVE
ACCESS
MANHOLE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :1
P
M
0-MS-001
MECHANICAL SITE PLAN
JES MDS
1" = 30'-0"
MECHANICAL DESIGN PLAN - SITE
1. NEW 16" CHILLED WATER SUPPLY AND CHILLED WATER
RETURN TO TIE INTO EXISTING MAINS IN BUILDING 17.
2. ROUTING FOR NEW 24" CHILLED WATER MAIN SUPPLY
AND RETURN FROM CHILLER PLANT TO EXISTING
BUILDING. PROVIDE DIRECT BURY CHILLED WATER
PIPING AS SPECIFIED UNDER 232113.13 UNDERGROUND
HYDRONIC PIPING. MIN. 42" OF COVER UNLESS NOTED
OTHERWISE ON THE DRAWINGS. REFER TO
UNDERGROUND PIPING SCHEDULE FOR INTERNAL
DIMENSIONS ON SHEET 0-M-601.
3. PROVIDE VALVE MANHOLE WITH SHUT OFF VALVES IN
AREA AS SHOWN. COORDINATE EXACT LOCATION WITH
SITE.
4. EXISTING MODULAR CHILLER PLANT FOR ACC TO
REMAIN.
5. EXISTING TEMPORARY CHILLER TO BE RELOCATED PER
NEW WORK. REFER TO 1/0-MS-002 FOR NEW LOCATION.
6. CONTRACTOR SHALL COORDINATE MECHANICAL SITE
WORK WITH NEW AND EXISTING ELECTRICAL AND/OR
PLUMBING UTILITIES.
7. FORMER CHILLER CH-B (SEE EXISTING CHILLER
SCHEDULE) COOLING TOWER SHALL REMAIN FOR USE
WITH MOBILE CHILLERS IF REQUIRED. ONCE NEW
CHILLER PLAN IS ON LINE THEN DEMOLISH TOWER AND
UNDERGROUND PIPING COMPLETELY.
8. COOLING TOWER ASSOCIATED WITH THE EXISTING
CHILLER CH-B.
9. COORDINATE NEW UG CHILLED WATER LINES WITH
EXISTING UG CONDENSER WATER LINES AS REQUIRED
TO MAINTAIN TEMP CHILLER OPERATION DURING
CONSTRUCTION.
10. TEMPORARY CHILLER'S TOTAL CAPACITY TO MEET OR
EXCEED 1250 TONS.
11. PROVIDE TEMPORARY CHILLED WATER SUPPLY AND
RETURN PIPING FROM THE TEMPORARY CHILLERS AS
SHOWN AND ROUTE THROUGH EXISTING ABOVE
GRADE PENETRATIONS IN THE LOCATION SHOWN.
PROVIDE GROOVED PIPING PER THE SPECIFICATIONS
AND PRE-ENGINEERED PIPE SUPPORTS. TEMPORARY
PIPING SHALL BE REMOVED UPON COMPLETION OF
WORK AND THE EXISTING PENETRATIONS SHALL BE
RESEALED. SEE SHEET 17-MP-100 FOR RELATED WORK.
12. CONTRACTOR SHALL PROVIDE HEAT TRACE ON ALL
ABOVE GRADE PIPING PER THE SPECIFICATIONS.
13. ROUTING FOR NEW 18" CHILLED WATER MAIN SUPPLY
AND RETURN FROM CHILLER PLANT TO EXISTING
BUILDING. PROVIDE DIRECT BURY CHILLED WATER
PIPING AS SPECIFIED UNDER 232113.13 UNDERGROUND
HYDRONIC PIPING. MIN. 42" OF COVER UNLESS NOTED
OTHERWISE ON THE DRAWINGS. REFER TO
UNDERGROUND PIPING SCHEDULE FOR INTERNAL
DIMENSIONS ON SHEET 0-M-601.
KEYED NOTES#
TRUE
NORTH
A. UNDERGROUND UTILITIES, WHETHER INDICATED OR
NOT, SHALL BE LOCATED PRIOR TO CONSTRUCTION. IT
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO PROTECT ALL EXISTING UTILITIES, PAVEMENT AND
OTHER IMPROVEMENTS. ANY DAMAGE TO EXISTING
UTILITIES AND/OR PAVED STREETS CAUSED BY
CONSTRUCTION OPERATIONS SHALL BE REPAIRED AT
THE CONTRACTOR'S EXPENSE.
B. CONDENSER WATER SUPPLY AND RETURN PIPING
SHALL NOT BE REMOVED UNTIL COOLING TOWERS ARE
OFF-LINE. SERVICE TO THE BUILDING SHALL BE
MAINTAINED BETWEEN 01 MAY THROUGH 01 OCTBER.
GENERAL NOTES
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
04/07/2022
XFIN. FLR. @ 1197.03'
XBLDG. 22
XBLDG. 2
XBLDG. 10
C O N C R
ET
E S
ID
EW
AL
K
0.9
NEW CHILLER PLANT
BLDG. XX
BUILDING 2
FUTURE CHW
PLANT EXPANSION
CH
B
0-M-401
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :1
P
M
0-MS-002
MECHANICAL SITE PLAN - ENLARGED
JES MDS
TRUE
NORTH
1" = 10'-0"
MECHANICAL ENLARGED DESIGN PLAN - SITE
1. RELOCATE THE EXISTING TEMPORARY CHILLER TO THE
LOCATION SHOWN. REFER TO 1/MSD001 FOR RELATED
INFORMATION
2. RELOCATED EXISTING 6" STEAM AND 2" CONDENSATE
PIPE SERVING ACC.
3. RELOCATED FUEL GAS AND RETURN FROM EXISTING
TANKS TO BOILER PLANT.
4. PROVIDE FREEZE PROTECTION FOR TEMPORARY
PIPING DURING OPERATION IN WINTER CONDITIONS.
5. PROVIDE PIPE SUPPORT FOR STACKED CWR, CWS, CR,
AND CS PIPE FROM EXTERIOR OF BUILDING.
COORDINATE WITH STRUCTURAL FOR ADDITIONAL
INFORMATION. PROVIDE WALL PIPE PENETRATION
SLEEVE ALLOWANCE TO ACCOMMODATE THE FULL
SIZE PIPING HEADER PIPING FOR THE FUTURE PLANT
EXPANSION WITHOUT A SHUTDOWN OF THE MAIN
CHILLED WATER AND CONDENSER WATER PIPING.
6. PROVIDE PIPE SUPPORT FOR STACKED CWR, CWS, CR,
AND CS PIPE TO CHILLER WITH SUPPORT STRUCTURE.
COORDINATE WITH STRUCTURAL FOR ADDITIONAL
INFORMATION.
7. CONTINUE 12" CWS AND CWR TO WITHIN CHILLER BOX.
ROUTE TO CHILLER AND CONNECT TO CHILLER.
PROVIDE NEW VALVES AND SPECIALTIES AS PER NEW
CHILLER DETAIL. COORDINATE PENETRATION
THROUGH WALL WITH EXISTING DEVICES.
8. CONTINUE 14" CS AND 14" CR TO WITHIN CHILLER BOX.
ROUTE TO CHILLER AND CONNECT TO CHILLER.
PROVIDE NEW VALVES AND SPECIALTIES AS PER NEW
CHILLER DETAIL.COORDINATE PENETRATION
THROUGH WALL WITH EXISTING DEVICES.
9. RECHARGE REFRIGERANT AS REQUIRED FROM
RELOCATION. PROVIDE NEW CONTROLS WITH BACNET-
IP INTEGRATION ON CHILLER FOR TIE IN TO BAS.
KEYED NOTES#
A. UNDERGROUND UTILITIES, WHETHER INDICATED OR
NOT, SHALL BE LOCATED PRIOR TO CONSTRUCTION. IT
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO PROTECT ALL EXISTING UTILITIES, PAVEMENT AND
OTHER IMPROVEMENTS. ANY DAMAGE TO EXISTING
UTILITIES AND/OR PAVED STREETS CAUSED BY
CONSTRUCTION OPERATIONS SHALL BE REPAIRED AT
THE CONTRACTOR'S EXPENSE.
B. CONDENSER WATER SUPPLY AND RETURN PIPING
SHALL NOT BE REMOVED UNTIL COOLING TOWERS ARE
OFF-LINE. SERVICE TO THE BUILDING SHALL BE
MAINTAINED BETWEEN 01 MAY THROUGH 01 OCTBER.
GENERAL NOTES
Revisions: Date:
I v
XBLDG. 22
XBLDG. 2
XBLDG. 10
XBLDG. 23
'PT' BLDG. (NIC)
FUTURE
C O N C R
ET
E S
ID
EW
AL
K
6' CONCRETE SIDEWALK
0.9
SEE 17-MPD100 FOR
CONTINUATION
1 5
18"
18"
3"
1"
NEW ACC
EXISTING
BLDG. XX
BUILDING 2
BLDG. 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :2
P
M
0-MSD001
MECHANICAL SITE DEMOLITION PLAN
JES MDS
1" = 30'-0"
MECHANICAL DEMOLITION PLAN - SITE
1. EXISTING 4-CELL MARLEY NC9214GS COOLING TOWERS
TO BE REMOVED.
2. REMOVE ALL BELOW GRADE 18" CONDENSER WATER
SUPPLY AND RETURN PIPING FROM CONDENSER
WATER PUMP DISCHARGE TO SOUTH MECHANICAL
CHILLER PLANT. ALL EXISTING 1" AND 3" DOMESTIC
WATER LINES TO TOWERS SHALL ALSO BE REMOVED.
3. REMOVE ASPHALT, CURB, AND GUTTER AS NECESSARY
TO REMOVE PIPING. LIMIT REMOVAL TO KEEP DRIVE
LANE OPERATIONAL.
4. SEE ELECTRICAL SHEET 0-ES-101 FOR ELECTRICAL SITE
DEMOLITION REQUIREMENTS.
5. COOLING TOWERS AND CONCRETE SUMP TO BE
REMOVED. EXISTING SUMP TO BE COLLAPSED AND
FILLED.
6. EXISTING TEMPORARY CHILLER TO BE RELOCATED PER
NEW WORK. REFER TO 1/0-MS-002 FOR NEW LOCATION.
7. PREPARE TEMPORARY CHILLER FOR RELOCATION.
DISCONNECT EXISTING CHILLED WATER PIPE FROM
UNIT AND CONDENSER WATER FROM UNIT.
DISCONNECT EXISTING CONDENSER PUMP. EVACUATE
REFRIGERANT FOR RELOCATION AS REQUIRED.
COORDINATE WITH LOCAL TRANE OFFICE PRIOR TO
DISCONNECTION FOR ANY ADDITIONAL
REQUIREMENTS.
8. EXISTING COOLING TOWER AND SUPPORT STRUCTURE
TO BE REMOVED WITH RELOCATION OF TRANE CONEX
CHILLER (CH-B). REMOVE PIPE TO AND FROM TOWER
TO CHILLER AND COORDINATE REMOVAL OF EXISTING
PIPE WITH PARKING LOT.
9. RELOCATE EXISTING FUEL LINES TO OIL STORAGE
TANKS OUTSIDE OF FOOTPRINT OF NEW BUILDINGS.
SEE SHEET 0-MS-002 FOR RELATED INFORMATION.
10. RELOCATE EXISTING STEAM DISTRIBUTION AND
CONDENSATE LINES OUTSIDE OF FOOTPRINT OF NEW
BUILDING. SEE SHEET 0-MS-0002 FOR RELATED
INFORMATION.
KEYED NOTES#
A. UNDERGROUND UTILITIES, WHETHER INDICATED OR
NOT, SHALL BE LOCATED PRIOR TO CONSTRUCTION. IT
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO PROTECT ALL EXISTING UTILITIES, PAVEMENT AND
OTHER IMPROVEMENTS. ANY DAMAGE TO EXISTING
UTILITIES AND/OR PAVED STREETS CAUSED BY
CONSTRUCTION OPERATIONS SHALL BE REPAIRED AT
THE CONTRACTOR'S EXPENSE.
B. CONDENSER WATER SUPPLY AND RETURN PIPING
SHALL NOT BE REMOVED UNTIL COOLING TOWERS ARE
OFF-LINE. SERVICE TO THE BUILDING SHALL BE
MAINTAINED BETWEEN 01 MAY THROUGH 01 OCTOBER.
C. ALL DEMOLITION WORK TO BE COORDINATED WITH THE
HAZARDOUS BUILDING MATERIALS INSPECTION
REPORT 636-18-304 DATED OCTOBER 22, 2019 -
PROVIDED BY THE CONTRACTING OFFICER'S
REPRESENTATIVE. COORDINATE FINAL REQUIREMENTS
FOR ABATEMENT WHERE REQUIRED.
GENERAL NOTES
TRUE
NORTH
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
C D
B-3 B-2 B-1
2" HPS
10" HPS
6" HPS
1 1/4" HPR
ETR ETR ETR
ETR
ETR
ETR
REFER TO
XX-MP-101 FOR
CONTINUATION
1 1/4" HPR
NO WORK THIS AREA
3" LPR
EXTEND TO NEAREST LOW
PRESSURE CONDENSATE
RETURN IN BOILER
MECHANICAL ROOM
VERIFY FINAL
CONNECTION POINT
WITH BOILER PLANT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :2
P
M
02-MP-101
MECHANICAL PIPING DESIGN PLAN - PARTIAL
BOILER PLANT
JES MDS
1/4" = 1'-0"
BUILDING 2 BOILER PLANT MECHANICAL
PIPING DESIGN PLAN
Revisions: Date:
A B C D
EQUIPMENT
ACCESS
LADDER (TYP.)
ROOF ACCESS
HATCH
CT
CT
48,830
LBS
48,830
LBS
TOTAL OPERATING
WEIGHT OF BOTH
CT-2 CELLS
TOTAL OPERATING
WEIGHT OF BOTH
CT-1 CELLS
PROVIDE DAVIT
FOR SERVICE
(TYP.)
EF
TCP
CT1
TCP
CT2
ROOF
CU
CU
0-M-301
CU
2-PIPE REFRIGERANT ROUTED TO
ASSOCIATED GROUND FLOOR
FCU. INSTALL PIPING PER
MANUFACTURER'S INSTALLATION
REQUIREMENTS. (TYP.)
2 2
EF
4" NPWS-DN
4" NPWR-DN
4" NPWS-DN
4' - 3"
INTERIOR
ACCESS DOOR
& LADDER (TYP.)
16" BOTTOM
OUTLET (TYP.
EACH CELL)
10" BOTTOM
INLET (TYP.
EACH CELL)
FAN DECK
WALKWAY (TYP.)
2 2
4" NPWR-DN
APPROXIMATE
LOCATION FOR NEW JIB
CRANE. SEE
ARCHITECTURAL AND
STRUCTURAL FOR
EXACT LOCATION.
VALVE IN
VERTICAL (TYP. 4)
PROVIDE COMMON BASE
RAILS FOR ROOF MOUNTING.
SEE ARCHITECTURAL FOR
MORE INFORMATION.
18" EQUALIZER
PIPING UP FFB.
4" OVERFLOW DRAIN-DN
4" OVERFLOW DRAIN-DN
2" NPWS 2" NPWS 2" NPWS 2" NPWS
0-M-301
4 4 4 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :3
P
M
XX-M-103
MECHANICAL DESIGN PLAN - CHILLER PLANT
ROOF
JES MDS
1/4" = 1'-0"
MECHANICAL DESIGN PLAN - ROOF
1. COORDINATE FINAL ROUTING OF CONDENSER WATER
SUPPLY TO STAINLESS STEEL SUMP ON BOTTOM OF
COOLING TOWER. COORDINATE ROUTING WITH
STRUCTURAL STEEL.
2. CONDENSER WATER RETURN PIPE TO CONNECT TO
BOTTOM FLANGE OF COOLING TOWER FOR INTERNAL
TOWER PIPING. PROVIDE INTERNAL TOWER BYPASS
WITH TOWER.
3. NON-POTABLE WATER FILL LINE TO COOLING TOWER.
SEE PLUMBING DRAWINGS FOR CONTINUATION.
4. PROVIDE HEAT TRACING ON PIPING AT 1.5 W/FT FOR
PIPE 2" AND UNDER ABOVE ROOF. COORDINATE WITH
DIV 26 FOR CIRCUITS.
5. PROVIDE HEAT TRACING ON PIPING AT 2.0 W/FT FOR
PIPE 2-1/2" TO 4" ABOVE ROOF. COORDINATE WITH DIV
26 FOR CIRCUITS.
6. PROVIDE HEAT TRACING ON PIPING AT 5.5 W/FT FOR
CONDENSER WATER BETWEEN TOWER AND BUILDING.
COORDINATE WITH DIV 26 FOR CIRCUITS.
7. PROVIDE HEAT TRACING ON PIPING AT 7.5 W/FT FOR
CONDENSER WATER BETWEEN TOWER AND BUILDING.
COORDINATE WITH DIV 26 FOR CIRCUITS.
KEYED NOTES#
PLAN
NORTH
TRUE
NORTH
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
XXX-XX
MEZZANINE
XXX-XX
CHILLER PLANT
0-M-301
AHU
FUTURE CHILLER PLANT
EXTENSION
SEE SHEET XX-MH-101 FOR WORK
BELOW THIS AREA
106"x80"
OUTSIDE AIR
INTAKE LOUVER
SD
UP TO EF-1
0-M-301
38x26 SA x S
A
TO EF-2
12x6 SA-DN
LU-1
16850
96x54 OA
HHW HX SKID --
SEE XX-MP-102
FOR MORE INFO
10x6 EA-UP
ACCESS DOOR
106x90 OA SHEET
METAL PLENUM
LU-2
CT-1 ON
ROOF ABV
ELECTRICAL ROOM
WEST WALL BELOW
TCP
VFD
RF1
HOUSEKEEPING PAD.
SEE ARCHITECTURAL.
HOUSEKEEPING PAD.
SEE ARCHITECTURAL.
TCP
VFD
SF2 TCP
60"x50"
OUTSIDE AIR
INTAKE LOUVER
ELECTRICAL
EQUIPMENT
BELOW
16x36 SA-DN 16x36 SA-DN x E
A
14x20 EA
14x20 EA-DN20x14 EA-DN
FUTURE EXPANSION
DUCT PATH
30x24 SA 50x26 SA
36x34 SA 36x34 SA
S-4
S-4
CONDENSER WATER
PIPING RISERS
CT-2 ON
ROOF ABV
S-2
20x14 EA
T
MONITORING
12x8 SA
ROUTE DUCT AS HIGH AS
POSSIBLE SUCH THAT ACCESS
TO MEZZANINE FROM PLANT
FLOOR IS NOT IMPEDED
ACCESS TO MEZZANINE
FOR STORAGE &
EQUIPMENT TRANSFER
DISCHARGE SHALL NOT
BE IMPEDED BY PIPING.
TYPICAL.
70x34 RA
SAFETY GATE. SEE ARCHITECTURAL.
PROVIDE 6990 CFM
OF SUPPLY AIR
FOR FUTURE
EXPANSION.
AHU
0-M-301
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :3
P
M
XX-MH-102
MECHANICAL HVAC DESIGN PLAN - CHILLER
PLANT MEZZANINE
JES MDS
1/4" = 1'-0"
MECHANICAL HVAC DESIGN PLAN -
MEZZANINE PLAN
NORTH
TRUE
NORTH
1. PROVIDE HORN/STROBE ALARM AND SIGNAGE FOR
REFRIGERANT LEAK DETECTION IN THE LOCATION
SHOWN. MOUNT DEVICE AT 6'-0" AFF. SEE SHEET XX-
MH-101 FOR ADDITIONAL LOCATIONS.
2. PROVIDE WALL PIPE PENETRATION SLEEVE
ALLOWANCE TO ACCOMMODATE THE FULL SIZE DUCT
HEADER FOR THE FUTURE PLANT EXPANSION WITHOUT
A SHUTDOWN OF THE AIR HANDLING UNIT.
3. COORDINATE HOUSEKEEPING PAD SIZE WITH
MANUFACTURER EQUIPMENT PROVIDED. MINIMUM PAD
THICKNESS SHALL BE 4" WITH 4" SUPPLEMENTAL STEEL
SUPPORT. COORDINATE FINAL THICKNESS WITH
CONDENSATE TRAP HEIGHT AND REQUIRED SLOPE OF
CONDENSATE DRAIN LINE. SEE DETAIL 7/0-M-501 FOR
RELATED INFORMATION
4. PROVIDE FLEX DUCT CONNECTORS AT DUCT
CONNECTIONS TO THE AIR HANDLING UNIT.
KEYED NOTES#
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
FUTURE EXPANSION
T T
T T
XXX-11
CHILLER PLANT
XXX-12
I.T. CLOSET
XXX-14
EMERGENCY
ELECTRICAL ROOM
XXX-15
CONTROL ROOM
XXX-16
STAFF TOILET
XXX-17
FIRE / WATER
SERVICE ROOMXXX-13
CORRIDOR / STAIRS
XXX-18
ELECTRICAL ROOM
A B C D
CWP
CWP
CWP
CWP
(FUTURE)
CTP
CTP
CTP
CTP
(FUTURE)
STRUCTURAL
FOUNDATION BLW
GRADE (TYP)
C W
S
C S
C S
C S
WCC
WCC
24" CR
C W
S
C W
R
C R
C W
S
C W
R
WATER TREATMENT
SKID W/ CHEMICAL
FEED PUMPS
ACCESSORIES
24" CWS/R DN TO CAMPUS LOOP. SEE
SITE PLAN ON SHEET 0-MS-001 FOR
CONTINUATION. SEE UNDERGROUND
PIPE SCHEDULE ON SHEET 0-M-601 FOR
TRANSITION TO LARGER PIPE SIZES DUE
TO INCREASED WALL THICKNESS.
CS/R UP. SEE
SHEET XX-MP102
FOR CONTINUATION
C H
IL
L E
R C
O N
T R
O L P
A N
E L
C H
IL
L E
R C
O N
T R
O L P
A N
E L
ACU
ACU
2" HPS
1 1/4" HPR
0-M-301
ACU
CONCRETE
PAD (TYP.)
PROVIDE TEMPORARY
PIPING ABOVE GRADE TO
TEMPORARY CHILLER. SEE
MECHANICAL SITE PLAN FOR
CONTINUATION.
2-PIPE REFRIGERANT DN
FROM ROOF. SEE SHEET
XX-M-103 FOR MORE
INFORMATION (TYP.)
REFER TO
02-MP-101 FOR
CONTINUATION
CTF
CTF
3/4" D
CWP-X TCP
(TYP. 3)
CTP-X TCP
(TYP. 3)
CWP-4 TCP
(FUTURE)
CTP-4 TCP
(FUTURE)
20" CWR
20" CWS
24" CS
24" CR
20" CWS
24" CS
4" NPWS/R DN TO
FILTRATION UNIT
C R
EXTEND TO NEAREST LOW PRESSURE
CONDENSATE RETURN IN BOILER
MECHANICAL ROOM
AHU-2 ON
LVL ABV
C S
C S
ADS CWR
BYPASS
ADS
EF
C W
R
20" CWR
F U
T U
R E
E L E
C
F U
T U
R E
E L E
C
24" CS
CONDENSER WATER
BYPASS & BYPASS
CTRL VALVE
24" CR
C R
3" RUPTURE
GAURD (TYP.)
3" V-UP
BRANCH TAP &
REMOVABLE CAP
FOR PURGE UNIT
CONN. (TYP.)
3" V-UP
SIZES SHOWN ARE FOR REFERENCE
ONLY. THE CHILLER INSTALLER
SHALL COORDINATE FINAL
PRESSURE RELIEF VENT SIZING WITH
THE CHILLER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
CHILLER BRANCH PIPING
B.O.P. ELEV @ MIN. 7'-6"
AFF FOR CLEAR PATH OF
TRAVEL. (TYP.)
M
M
M
CWS/R DECOUPLER,
CTRL VALVE, AND
FLOW METER
C S
M
M
20" CWR
A D
S -1
F U
T U
R E
P A
T H
O F
T R
A V
E L
MAINTAIN CLEAR
PATH FOR FUTURE
EQUIPMENT REMOVAL
BASED ON APPROVED
ADS-1 SELECTION
DIMENSIONS.
PROVIDE DRIP LEG SIZED
FOR 1 GAL. LIQUID STORAGE
PER DETAIL. (TYP.)
VALVE IN VERTICAL
UPSTREAM OF 6"
CWS BRANCH TAP
VALVE IN VERTICAL
DOWNSTREAM OF 6"
CWR BRANCH TAP
AHU-1 ON
LVL ABV
20" CWR
6" CWR-UP
6" CWS-UP
3/4" D 3/4" D
BOP AT 10'-0" ABOVE GRADE
SEE CIVIL FOR PROFILES
24" CS24" CS
20" CS
20" CR
REFRIGERANT CONTROL
PANEL. SEE XX-MH-101 FOR
RELATED INFORMATION.
D
1" D-UP
F.S.
3/4" D
/4
D
D
1" D
ET
C R
C S
C W
S
C W
R
12" CWR
12" CWS
14" CS
14" CR
REFRIGERANT ALARM (TYP).
SEE XX-MH-101 FOR RELATED
INFORMATION.
MOUNT 14" CS AND 14" CR
ABOVE 12" CWR AND 12"
CWS TO CHILLER. PROVIDE
PIPE SUPPORT FROM
EXTERIOR WALL.
14" CR
14" CS
12" CWS
12" CWR
1 1/4" HPR-UP
2" HPS-UP
0-M-301
3" LPR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :4
P
M
XX-MP-101
MECHANICAL PIPING DESIGN PLAN - CHILLER
PLANT GROUND FLOOR
JES MDS
1/4" = 1'-0"
MECHANICAL PIPING DESIGN PLAN -
GROUND FLOOR
1. PROVIDE NEW WATER COOLED CHILLER AND
ASSOCIATED PIPING, ACCESSORIES, AND CONTROLS
AS SHOWN.
2. PROVIDE NEW CHILLED WATER AND CONDENSER
WATER PUMPS AND ASSOCIATED PIPING,
ACCESSORIES, AND CONTROLS AS SHOWN.
3. THE EQUIPMENT SHOWN IS REPRESENTATIVE OF
FUTURE PUMP INSTALLATION. THE CONTRACTOR
SHALL INCLUDE PROVISIONS FOR SPACE ON THE
ASSOCIATED CONCRETE PAD AND PROVIDE BRANCH
PIPING TAPS WITH ISOLATION VALVES AND CAP FOR
FUTURE EXTENSION AS SHOWN.
4. SEE SHEET XX-MP-102 FOR CONTINUATION OF PIPE
ROUTE.
KEYED NOTES#
PLAN
NORTH
TRUE
NORTH
Revisions: Date:
XXX-XX
MEZZANINE
XXX-XX
CHILLER PLANT
0-M-301
SEE SHEET
XX-MP-101 FOR
WORK BELOW
THIS AREA
AHU
FUTURE CHILLER PLANT
EXTENSION
4" HWS
4" HWR
0-M-301
4" CWR
4" CWS
1 1/4" D
1 1/4" D
4" NPWR-UP
4" NPWS-UP
4" HWS
4" HWR
ADS
HX
HX
LU-1
16850
HWP
HWP
ET
4" NPWS/R
DN TO
FILTRATION
UNIT (TYP. 2)
FD
26" CS
24" CS
C S
C S
C S
24" CS24" CR
C R
16" CR
14" CS UTR
(TYP. 4)
16" CR UTR
(TYP. 4)
CT-1 ON
ROOF ABV
CT-2 ON
ROOF ABV
24" CR 24" CR
26" CS
4" NPWS-UP
4" NPWR-UP4" NPWR
4" NPWS
4" NPWS
4" NPWR
3" LPS
HANDRAIL
HANDRAIL
CAP FOR FUTURE
EXTENSION (TYP. 4)
EXHAUST FAN
ON ROOF ABV
STEAM PRV
STATION
1 1/4" HPR
2" HPS
1 1/4" HPR-DN
2" HPS-DN
LU-2
AHU
TCP
VFD
RF1
TCP
VFD
SF2
TCP
HOUSEKEEPING PAD.
SEE ARCHITECTURAL.
HOUSEKEEPING PAD.
SEE ARCHITECTURAL.
ELECTRICAL
EQUIPMENT
BELOW
VFD
RF2
VFD
SF1
2" HWR
2" HWS
2" CWR
2" CHS
2" CHS
2" CWR
2" HWS
2" HWR
4" CWR
4" CWS
EXHAUST FAN
ON ROOF ABV
4" NPWS
4" NPWR
4" NPWS
4" NPWR
4" NPWR
4" NPWS
4" HWS
4" HWR
4" HWR
4" HWS
4" CWR
4" CWS
4" CWR
4" CWS
6" CWS
6" CWR-DN
6" CWR
6" CWR
4" HWS
4" CWS
4" CWR
4" CWR
4" CWS
DISCHARGE DN.
MIN. DISCHARGE
ELEV. @ 15'-0" AFG
3" V-DN
3" V-DN
SIZES SHOWN ARE FOR REFERENCE ONLY. THE
CHILLER INSTALLER SHALL COORDINATE FINAL
PRESSURE RELIEF VENT SIZING WITH THE CHILLER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
6" CWS
6" CWS
6" CWR
6" CWS-DN
ACCESS TO MEZZANINE
FOR STORAGE &
EQUIPMENT TRANSFER
4" HWR
4" CWS
4" CWR
ROUTE PIPING TO
ACCOMODATE MEZZANINE
ACCESS FROM PLANT FLOOR
20" CR
20" CS
CAP FOR FUTURE
EXTENSION (TYP. 3)
24" CR-DN
24" CS-DN
1" D
14" CS14" CS
1" D-DN
14" CR
14" CS
12" CWS
12" CWR
CAP FOR FUTURE
EXTENSION (TYP. 4)
18" EQUALIZING
LINE
4" OVERFLOW DRAIN-UP
4" OVERFLOW DRAIN-UP
4" OVERFLOW
DRAIN DN TO
FLOOR SINK
(TYP 2)
SAFETY GATE. SEE ARCHITECTURAL.
0-M-301
SPCP
3" LPR
3" LPR
3" LPR
3" LPR-DN
3" LPR
3" LPS
3" LPR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :4
P
M
XX-MP-102
MECHANICAL PIPING DESIGN PLAN - CHILLER
PLANT MEZZANINE
JES MDS
1/4" = 1'-0"
MECHANICAL PIPING DESIGN PLAN -
MEZZANINE PLAN
NORTH
TRUE
NORTH
1. COORDINATE FLOOR DRAIN LOCATION WITH PLUMBING
DRAWINGS.
2. FIELD ROUTE LOW AND HIGH PRESSURE STEAM
CONDENSATE PIPING TO BUILDING 2. COORDINATE
WITH EXISTING PIPING IN BUILDING AND CONNECT TO
EXISTING LOW AND HIGH PRESSURE STEAM
CONDENSATE RETURN, RESPECTIVELY, IN
MECHANICAL ROOM.
3. SKID ASSEMBLY TO BE MOUNTED IN FABRICATED
STAINLESS STEEL DRAIN PAN. PROVIDE 1" DRAIN FROM
DRAIN PAN TO NEAREST FLOOR DRAIN.
4. COORDINATE HOUSEKEEPING PAD SIZE WITH
MANUFACTURER EQUIPMENT PROVIDED. MINIMUM PAD
THICKNESS SHALL BE 4" WITH 4" SUPPLEMENTAL STEEL
SUPPORT. COORDINATE FINAL THICKNESS WITH
CONDENSATE TRAP HEIGHT AND REQUIRED SLOPE OF
CONDENSATE DRAIN LINE. SEE DETAIL 7/0-M-501 FOR
RELATED INFORMATION
5. PROVIDE WALL PIPE PENETRATION SLEEVE
ALLOWANCE TO ACCOMMODATE THE FULL SIZE PIPING
HEADER PIPING FOR THE FUTURE PLANT EXPANSION
WITHOUT A SHUTDOWN OF THE MAIN CHILLED WATER
AND CONDENSER WATER PIPING.
KEYED NOTES#
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
E
E
E
E
E
E
E
E
E
E E
E
E E
E E
E
T
T
T
T
T
T
EE
E
D
D
D D
D
D
D
D
D
G
SS
SS
EE
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
XF
WV
XFXF
XF
XF
XF
XF XF XFXFXFXFXF XFXF XF XFXFXFXFXF
XF
XF
XF
XF
XF
XF
XF
XF
GV
XG XG
XG
XG
XG
XSD/SS
XSD/SS
XSD/SS
XSD/SS
XSD/SS
XSD
XSD
XSD
XSD
XSD
XSD
XS
D
XS
D
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XSD
XS
D
XSD
XS
D
XS
D
XSD
XF
XG
XG
XG
XG
XG
XG
XG
XG
XG
XG
XW
XW
XW
XW
XW
XW
XW
XW
XW
XW
XFL
XFL
XFL
XST
XST
XST
XST
XST
XST
XST
XSTXSTXST
XST
WV WV
WV
WV
WV
T
T
T
DY
H
DY
H
DY
H
DY
H
29 1 2
PULLERDRIVE
STEAM PUMP
XE
XE
XE
XE
XE
XE
XFIN. FLR. @ 1197.03'
S
6' C
ON
CR
ET
E
SI
DE
WA
LK
6' CONCRETE SIDEWALK
CP 96
0 .92
1'x 2'
ELE
CTR
IC
VAU
LT
BUI
LDI
NG
BUI
LDI
NG
BUI
LDI
NG
BUI
LDI
NG
BUI
LDI
NG
BUI
LDI
NG
8.8
8.1
8.2
8.0
STE
AM
VEN
T
GEN
ERA
TOR
STE
AM
VEN
T
POL
E W
ITH
R
ADA
R
STE
AM
VEN
T
STE
AM
VEN
T
OXY
GEN
TA
NK
S
A/C C
ONC
RET
E P
AD
CO
NC
RET
E S
TEP
S
CO
NC
RET
E S
TEP
S
CO
NC
RET
E P
AT I
O
CO
NC
RET
E
ASP
HAL
T
ASP
HAL
T
6"
CO
NC
RET
E
CU
RB
GU
TTE
R (
TYP
ASP
HAL
T
CO
NC
RET
E
CO
NC
RET
E
CO
NC
RET
E
CO
NC
RET
E
ASP
HAL
T
CO
NC
RET
E
GRA
VEL
ASP
HAL
T
ASP
HAL
T
CO
NC
RET
E
6"
CO
NC
RET
E
CU
RB
GU
TTE
R (
TYP
CO
NC
RET
E
6'
CO
NC
RET
E S
IDE
WAL
K
ASP
HAL
T
CO
NC
RET
E
CO
NC
RET
E
ASP
HAL
T
6'
CO
NC
RET
E S
IDE
WAL
K
CO
NC
RET
E
6'
CO
NC
RET
E S
IDE
WAL
K
6'
CO
NC
RET
E S
IDE
WAL
K
4'
CO
NC
RET
E S
IDE
WAL
K
6"
CO
NC
RET
E
CU
RB
GU
TTE
R (
TYP
6"
CO
NC
RET
E
CU
RB
GU
TTE
R (
TYP
ASP
HAL
T
PLA
RKI
NG
LOT
CO
NC
RET
E
ASP
HAL
T
PLA
RKI
NG
LOT
BEE
H
IVE
GR
ATE
RIM
EL
EV.
: 1
.00
(N)
" I .E:
7.0
(W)
" I .E.:
06.
5"
STO
RM
DR
A IN
STO
RM
M
ANH
OLE
RIM
EL
EV.
: 1
.75
(E)
" R
CP
I.E .: 1
.00
(S)
" I .E.:
27.
1X1 S
TOR
M
INL
ET
RIM
EL
EV.
: 1
.37
(E)
" I .E.:
08.
BU
ILD
ING
"D
STO
RM
M
ANH
OLE
FUL
L O
F W
ATE
R &
DE
BR
IS
STO
RM
IN
LET
RIM
.: 1
.26
(NW
) 1
8" I.E.
: 1
.29
(SW
) 1
8" I.E.
: 1
.29
CO
VER
ED
NYL
OPL
AST
STO
RM
DR
AIN
RIM
EL
EV.
: 1
.15
STO
RM
IN
LET
RIM
EL
EV.
: 1
.60
(W)
" I .E.:
13.
(S)
" P
VC
I.E.
: 1
.68
STO
RM
IN
LET
RIM
EL
EV.
: 1
.17
(E)
" I .E.:
14.
STO
RM
IN
LET
RIM
EL
EV.
: 1
.06
(SW
) 1
2"
RC
P I .E.:
06.
STO
RM
IN
LET
RIM
EL
EV.
: 1
.01
I.E.
: 1
.93
STO
RM
IN
LET
RIM
EL
EV.
: 1
.58
I.E.
: 1
.58
STO
RM
IN
LET
RIM
EL
EV.
: 1
.73
(SW
) 1
2"
RC
P I .E.:
07.
(NW
) 1
8" I.E.
: 1
.83
SAN
ITAR
Y M
ANH
OLE
RIM
EL
EV.
: 1
.10
(S) 8"
DI
P i
.E.:
29 .
(N) " D
IP
I.E.
: 1
.10
DUM
PST
ERS
F.F .E.:
34.
F.F .E.:
13.
STO
RM
M
ANH
OLE
RIM
EL
EV.
: 1
.55
(N) I.E
.: 1
.15
(NE
) V
CP
I .E
.: 1
.30
(E) 4"
HD
PE
I.E.
: 1
.00
(SE
) I.
E.:
2.5
(SW
) I
.E.:
12.
STO
RM
IN
LET
RIM
EL
EV.
: 1
.08
(W)
" H
DPE
I.E .: 1
.38
(E)
" R
CP
I.E .: 1
.38
STO
RM
IN
LET
RIM
EL
EV.
: 1
.41
(S)
" H
DPE
I.E .: 1
.51
(NW
) 1
2"
RC
P I.E.
: 1
.41
(E)
" R
CP
I.E .: 1
.41
F.F .E.:
21.
TRE
NC
H
DRA
IN
F.F .E.:
34.
F.F .E.:
34.
F.F .E.:
21.
F.F .E.:
21.
F.F .E.:
34.
MET
AL
STA
IRC
ASE
F.F .E.:
34.
RET
A IN
ING
WA
LL
CP
CP
STE
AM
PUM
P
F.F .E.:
34.
MU
LCH
E
E
E
A/CA/C
EXISTING
ELECTRICAL
MANHOLE #4 EXISTING
ELECTRICAL
MANHOLE #7
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
D U s e rs \j w h e e le r\
D o c u m e n ts \2
-1
E
L E
C v jw h e e le rD S
Y A
F .r v t
/5
/2
:0
:1
P M
0-ES-101
ELECTRICAL SITE PLAN
JGW CRP
1" = 30'-0"
ELECTRICAL SITE PLAN
1. ROUTE NEW LOCATIONS OF ELECTRIC LINES TO OIL
STORAGE TANKS OUTSIDE OF FOOTPRINT OF NEW
BUILDING. FIELD VERIFY EXISTING ELECTRICAL
CONNECTIONS AND MATCH FOR NEW.
2. EXISTING PAD-MOUNTED SWITCH FOR CIRCUIT #95 TIE-
IN.
3. NEW 15KV PAD-MOUNTED SWITCHES FOR
INTERCEPTION AND EXTENSION OF CIRCUITS #90 AND #
95 TO NEW BUILDING. REFER TO XX-E-601 FOR
ADDITIONAL INFORMATION.
4. NEW 15KV PAD-MOUNTED SWITCH AND TRANSFORMER
FOR EXTENSION OF CIRCUIT #95 TO NEW LOCATION OF
TEMP CHILLER.
5. NEW 15KV EXTENSION OF CIRCUIT #95. REFER TO
DETAIL 3, DRAWING XX-E-501 AND DRAWING XX-E-601
FOR FEEDER REQUIREMENTS.
6. NEW 15KV ELECTRICAL MANHOLE. REFER TO DETAILS
1 AND 2, DRAWING XX-E-501.
7. NEW LOCATION OF EXISTING TEMP CHILLER, PAD-
MOUNTED TRANSFORMER, AND MAIN SWITCH.
8. NEW 15KV PAD-MOUNTED SWITCH AND TRANSFORMER
FOR EXTENSION OF CIRCUIT #95 TO NEW LOCATION OF
TEMP CHILLER.
9. NEW 15KV DUCT BANK FOR CIRCUIT #90. REFER TO
DRAWING XX-E-601 FOR ADDITIONAL INFORMATION AND
FEEDER REQUIREMENTS.
10. CONNECT ATS-LS1 EMERGENCY FEED TO EXISTING
LIFE SAFETY DISTRIBUTION PANELBOARD AND
GENERATOR IN BUILDING 2 LOCATED IN SOUTHEAST
CORNER OF BUILDING. VERIFY EXACT LOCATION WITH
VA COR. REFER TO XX-E-601 FOR ADDITIONAL
INFORMATION.
KEYED NOTES#
PLAN
NORTH
TRUE
NORTH
PLAN
NORTH
TRUE
NORTH
1. REFER TO MECHANICAL DRAWINGS FOR PHASING
REQUIREMENTS FOR RELOCATION OF THE TEMPORARY
MODULAR OUTDOOR CHILLER.
GENERAL NOTES
Revisions: Date:
T
T T
PC
F3
F3 F1E
F2
A2 A2
A2E A2
A1
A3
W1E
W1E
W1E
OC OC D OC
W1 W1
W1 W1 W1
EM
EM
F U
T U
R E
D
IS
T
D
IS
T
M A
IN
S U
B -B
S U
B -A
S U
B
S U
B
S U
B -A
S U
B -B
M A
IN
D
IS
T
D
IS
T
F U
T U
R E
X F
M R
X F
M R
W1
W1
F2
XXX-11
CHILLER PLANT
3431 SQFT
XXX-12
I.T. CLOSET
84 SQFT
XXX-14
EMERGENCY
ELECTRICAL ROOM
101 SQFT
XXX-15
CONTROL ROOM
129 SQFT
XXX-16
STAFF TOILET
109 SQFT
XXX-17
FIRE / WATER
SERVICE ROOM
139 SQFT
XXX-13
CORRIDOR / STAIRS
177 SQFT
XXX-18
ELECTRICAL ROOM
1324 SQFT
EQPH2A
NDPH1B
NDPH2B
NDPH2A
NDPH1A
NPH1A
X1E
NPL1AEQPL2A
CRPL1A
LSPL1A
NPL1A-4
(PART)
CRPL1A-1
LSPL1A-5
NPL1A-2
(PART)
NPL1A-2
(PART)
LSPL1A-7
CTP
F2 F2 F2 F2
F2E F2E F2E
F2E
EM
F2E F2 F2E F2 F2 F2E
F2 F2 F2 F2 F2 F2E
F2 F2E F2 F2E F2 F2
1 1
LC01
LC01
LC01
LC01
LC01
LC01
LC02LC04
(PART)
W1
DCBA
X1E
LSPL1A-7
(PART)
X1E
X1E
F1 F1F1EF1E
XXX-XX
MEZZANINE
803 SQFT
XXX-11
CHILLER PLANT
3431 SQFT
LC03
LSPL1A-5
F1 F1 F1 F1
F1 F1 F1 F1
(PART)
(PART
DCBA
NPL1A-4
F1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
D U s e rs \j w h e e le r\
D o c u m e n ts \2
-1
E
L E
C v jw h e e le rD S
Y A
F .r v t
/5
/2
:0
:1
P M
XX-EL-101
NEW CHILLER PLANT, BLDG XX - FIRST FLOOR
LIGHTING PLAN
JGW CRP
1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN
1/8" = 1'-0"
MEZZANINE LIGHTING PLAN
A. PROVIDE EMERGENCY LIFE SAFETY AND CRITICAL
BRANCH FIXTURES WITH UL924 EMERGENCY SHUNT-
RELAY TO BYPASS LOCAL LIGHTING CONTROLS WITHIN
EACH SPACE AND TURN FIXTURES ON TO 100% OUTPUT
DURING LOSS OF POWER
GENERAL SHEET NOTES
TRUE
NORTHPLAN
NORTH
TRUE
NORTHPLAN
NORTH
1. MOUNT LIGHT FIXTURE AT 7'-0" AFF.
2. MOUNT LIGHT FIXTURE AT 10'-0" AFF.
3. MOUNT LIGHT FIXTURES IN CHILLER ROOM AT
APPROXIMATELY 12'-0" AFF. COORDINATE FINAL
LIGHTING LAYOUT AND HEIGHT WITH CHILLER PLANT
PIPING. REFER TO MECHANICAL DRAWINGS FOR
ADDITIONAL INFORMATION.
4. MOUNT LIGHT FIXTURES IN ROOM AT 9-'0" AFF.
5. MOUNT LIGHT FIXTURES IN ROOM AT 10'-0" AFF.
6. MOUNT LIGHT FIXTURES IN MEZZANINE TIGHT TO
STRUCTURE.
7. PROVIDE TIMECLOCK AND (2) CONTACTORS C1 AND C2
TO CONTROL EXTERIOR LIGHTING. (1) CONTACTOR FOR
NORMAL POWER AND (1) CONTACTOR FOR LIFE
SAFETY POWER. SEE DETAIL 11/XX-E-501.
KEYED NOTES#
LIGHTING CONTROL SEQUENCE
S - "INDIVIDUAL ZONE WALL CONTROLLER". REFER TO FLOOR PLAN FOR QUANTITY OF ZONES SHOWN IN THE AREA. EACH ZONE SHALL HAVE A ITS OWN INDEPENDENT CONTROLLER WITHIN THE WALL CONTROLLER.
D - "INDIVIDUAL DIMMING ZONE WALL CONTROLLER". EACH ZONE SHALL ITS OWN INDEPENDENT CONTROLLER CAPABLE OF ON, OFF AND DIMMING WITIN THE WALL CONTROLLER. REFER TO FLOOR PLAN FOR QUANTITY OF ZONES SHOWN IN THE AREA.
P -"PRESET SCENE CONTROLLER". NUMBER INDICATES QUATITY OF PRESET SCENE CONTROLS. EACH PRESET SCENE SHALL EACH BE CAPABLE OF TURNING SCENE ON, OFF AND DIM.
DL - "DAY LIGHT PHOTO SENSOR". MUST AUTOMATICALLY DIM INDICATED LUMNINAIRES SHOWN ON FLOOR PLANS WITH DAY LIGHT ZONES. MAINTAIN MAXIMUM FOOT CANDLE RATING INDICATED AS MEASURED FROM +30" AFF.
SEQUENCE ID AREA DESCRIPTION
WALL AUTOMATIC CONTROLS
DL
Ft. Cd. REMARKS
CONTROLLER ON (X=100%) OFF (X=0%)
S D P MAN OCC TC NC MAN OCC TC NC
LC01 MECHANICAL/ELECTRICAL ROOMS X X X
LC02 RESTROOMS X X X X
LC03 STORAGE X X X X
LC04 STAIRWAY X X X X
T
T T
E
E
E E
E
E E E
E E E
E
E
E
E
E
E
E
E
E
EE
E
E E
E
E
E
E
E
E
E E E
E
E
E
CRPL1A
LSPL1A
CRPL1B
EQPH2A EQPL2A NPL1ANPH1A
TX-CRPL1A
TX-LSPL1A
TX-EQPL2A TX-NPL1A
NDPH1B
NDPH2B
NDPH2A
NDPH1A
A
ATS-LS1
ATS-CR1
ATS-EQ2
F U
T U
R E
D
IS
T
D
IS
T
M A
IN
S U
B -B
S U
B -A
S U
B
S U
B
S U
B -A
S U
B -B
M A
IN
D
IS
T
D
IS
T
F U
T U
R E
X F
M R
X F
M R
CTP
CTP
CTP
CWP
CWP
CWP
WCC
WCC
XX-E-601
XX-E-601
+50"
XXX-11
CHILLER PLANT
3431 SQFT
XXX-12
I.T. CLOSET
84 SQFT
XXX-14
EMERGENCY
ELECTRICAL ROOM
101 SQFT
XXX-15
CONTROL ROOM
129 SQFT
XXX-16
STAFF TOILET
109 SQFT
XXX-17
FIRE / WATER
SERVICE ROOM
139 SQFT
XXX-13
CORRIDOR / STAIRS
177 SQFT
XXX-18
ELECTRICAL ROOM
1324 SQFT
WP
WP
WP
WP
CRPL1A-9
NPL1A-1
NPL1A-1
NPL1A-1
NPL1A-1
(PART)
(PART)
(PART)
(PART)
CRPL1A-13
EQPL2A-1
NPL1A-3
CRPL1A-3
CRPL1A-7
CRPL1B-3
CRPL1B-11
CRPL1B-5
CRPL1B-5
CRPL1B-1
CRPL1B-7,9
CRPL1B-1
ACU
ACU
DCBA
FACP
LSPL1A-1
CRPL1A-2
CRPL1A-4 CRPL1A-6
CRPL1A-8
CRPL1A-12
CRPL1A-10
NPH1A-2,4,6
NPL1A-7
CRPL1B-2,4
NPL1A-11
CRPL1A-11
CRPL1B-13
CRPL1B-15
EQPL2A-2,4
(PART)
(PART)
NPL1A-5
NPL1A-6,8
NSWBD2-1
NSWBD1-1
EF
EQPH2A-7,9,11
DWH
HWRP
CTF
CTF
XX-E-601
(TYPICAL)
LSPL1A-3
ACU
3(PART)
CWP
CTP
(FUTURE)
(FUTURE)
NDPH2A-4
NDPH1A-5
NDPH2A-5
NDPH1A-3
NDPH2A-3
NDPH1A-4
NDPH1A-6
NDPH2A-6
EQPL2A-16
EQPL2A-18
EQPL2A-20
EQPL2A-22
7(TYP. OF 4)
8 1 8 1
XXX-XX
MEZZANINE
803 SQFT
NPH1A-1,3,5
AHU
DCBA
CRPL1A-14
CRPL1A-16
EQPL2A-1
CRPL1A-18
EQPH2A-2,4,6
AHU
CRPL1A-13
(PART)
(PART)
HWP
HWP
EQPH2A-14,16,18
EQPH2A-8,10,12
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
D U s e rs \j w h e e le r\
D o c u m e n ts \2
-1
E
L E
C v jw h e e le rD S
Y A
F .r v t
/5
/2
:0
:1
P M
XX-EP-101
NEW CHILLER PLANT, BLDG XX - FIRST FLOOR
POWER PLAN
JGW CRP
1/8" = 1'-0"
FIRST FLOOR POWER PLAN
1/8" = 1'-0"
MEZZANINE POWER PLAN
TRUE
NORTHPLAN
NORTH
TRUE
NORTHPLAN
NORTH
1. PROVIDE 480V/3-PHASE, 30A, 3-POLE, NON-FUSED
DISCONNECT SWITCH FOR WATER HEATER.
2. PROVIDE 20A, 120V MANUAL MOTOR STARTER.
3. PROVIDE 480V/3-PHASE, 30A, 3-POLE, 6.25A FRS-R
FUSED COMBINATION MOTOR STARTER DISCONNECT
SWITCH.
4. PROVIDE 480V/3-PHASE, 60A, 3-POLE, 35A FRS-R FUSED
DISCONNECT SWITCH.
5. INSTALL DISCONNECT SWITCH FURNISHED BY DIVISION
23.
6. INSTALL COMBINATION DISCONNECT SWITCH/VARIABLE
FREQUENCY DRIVE FURNISHED BY DIVISION 23.
7. PROVIDE POWER FOR HEAT TRACE ON ALL CHILLED
WATER PIPING AND CONDENSATE PIPING FOR THE
TEMPORARY CHILLER. COORDINATE FINAL CIRCUIT
BREAKER SIZE AND CONDUIT/CONDUCTOR SIZE WITH
HEAT TRACE SYSTEM PROVIDED BY DIVISION 23.
8. PROVIDE 12" TALL LEAK CONTAINMENT BASIN BELOW
TRANSFORMER SECTION FOR CONTAINMENT OF MINOR
OIL LEAKS. FULL LEAK CONTAINMENT OF
TRANSFORMER BY DEPRESSION OF ELECTRICAL ROOM
FLOOR BARRIERS AT MAN- AND OVERHEAD-DOORS.
REFER TO ARCHITECTURAL AND STRUCTURAL
DRAWINGS FOR ADDITIONAL INFORMATION.
KEYED NOTES#
G F
R
MB
DM SPD G
F R
G F
R
N
G
TO GROUND BAR AT
TO WATER SERVICE
TO STRUCTURAL STEEL
TO CONCRETE-ENCASED
TO ABOVE GROUND
RODS
MAIN TEL. BOARD (TTB)
ELECTRODE (UFER)
METAL PIPING
TO GROUND
MBJ
EBJ
G F
R
V F
D
1 2
4 3
V F
D
V F
D
V F
D
1 2
4 3
G F
R
MB
DM SPD G
F R
G F
R
N
G
TO GROUND BAR AT
TO WATER SERVICE
TO STRUCTURAL STEEL
TO CONCRETE-ENCASED
TO ABOVE GROUND
RODS
MAIN TEL. BOARD (TTB)
ELECTRODE (UFER)
METAL PIPING
TO GROUND
MBJ
EBJ
G F
R
V F
D
V F
D
1 2
4 3
V F
D
V F
D
V F
D
V F
D
V F
D
V F
D
ELECTRICAL SERVICE #1
LOAD SUMMARY
SERVICE DESCRIPTION: 480Y/277V, 3PH, 4W
OCCUPANCY TYPE: I
BUILDING AREA: 6,044
LOAD DESCRIPTION
CONNECTED
KVA
DEMAND
FACTOR
DEMAND
KVA
COOLING (C) 801.86 100% 801.86
HEATING (H) 0.00 0% 0.00
LIGHTING (L) (Per NEC T220.12) 12.09 125% 15.11
EXTERIOR LIGHTING 0.30 125% 0.37
RECEPTACLES (R) (Per NEC T220.44) 3.60 100% 3.60
MOTORS (M) 357.50 100% 357.50
LARGEST MOTOR 103.09 125% 128.87
SUPPLEMENTAL ELECTRIC HEAT (Y) 48.00 100% 48.00
MISCELLANEOUS EQUIPMENT (Z) 42.30 100% 42.30
TOTAL LOAD 1368.74 KVA 1397.61
TOTAL AMPACITY 1646 AMPS 1681
SERVICE AMPACITY 2500 AMPS 2500
SPARE CAPACITY AMPS 819
DISTRIBUTION PANELBOARD NDPH1A
LOAD SUMMARY
VOLTS/PHASE: 480Y/277V, 3PH, 4W
LOAD DESCRIPTION
CONNECTED
KVA
DEMAND
FACTOR
DEMAND
KVA
COOLING (C) 0.00 100% 0.00
HEATING (H) 0.00 0% 0.00
LIGHTING (L) 0.00 125% 0.00
RECEPTACLES (R) (Per NEC T220.44) 0.00 100% 0.00
MOTORS (M) 310.11 100% 310.11
LARGEST MOTOR 129.70 125% 162.12
SUPPLEMENTAL ELECTRIC HEAT (Y) 48.00 100% 48.00
MISCELLANEOUS EQUIPMENT (Z) 0.00 100% 0.00
TOTAL LOAD 487.80 KVA 520.23
TOTAL AMPACITY 587 AMPS 626
DISTRIBUTION PANELBOARD AMPACITY 1000 AMPS 1000
SPARE CAPACITY AMPS 374
DISTRIBUTION PANELBOARD NDPH1B
LOAD SUMMARY
VOLTS/PHASE: 480Y/277V, 3PH, 4W
LOAD DESCRIPTION
CONNECTED
KVA
DEMAND
FACTOR
DEMAND
KVA
COOLING (C) 6.48 100% 6.48
HEATING (H) 0.00 0% 0.00
LIGHTING (L) 1.98 125% 2.48
RECEPTACLES (R) (Per NEC T220.44) 3.60 100% 3.60
MOTORS (M) 20.79 100% 20.79
LARGEST MOTOR 0.00 125% 0.00
SUPPLEMENTAL ELECTRIC HEAT (Y) 0.00 100% 0.00
MISCELLANEOUS EQUIPMENT (Z) 42.30 100% 42.30
TOTAL LOAD 75.15 KVA 75.64
TOTAL AMPACITY 90 AMPS 91
DISTRIBUTION PANELBOARD AMPACITY 400 AMPS 400
SPARE CAPACITY AMPS 309
ELECTRICAL SERVICE #2
LOAD SUMMARY
SERVICE DESCRIPTION: 480Y/277V, 3PH, 4W
OCCUPANCY TYPE: I
BUILDING AREA: 0
LOAD DESCRIPTION
CONNECTED
KVA
DEMAND
FACTOR
DEMAND
KVA
COOLING (C) 798.63 100% 798.63
HEATING (H) 0.00 0% 0.00
LIGHTING (L) (Per NEC T220.12) 0.00 125% 0.00
EXTERIOR LIGHTING 0.00 125% 0.00
RECEPTACLES (R) (Per NEC T220.44) 1.44 100% 1.44
MOTORS (M) 396.41 100% 396.41
LARGEST MOTOR 103.09 125% 128.87
SUPPLEMENTAL ELECTRIC HEAT (Y) 48.00 100% 48.00
MISCELLANEOUS EQUIPMENT (Z) 18.00 100% 18.00
TOTAL LOAD 1365.57 KVA 1391.34
TOTAL AMPACITY 1643 AMPS 1674
SERVICE AMPACITY 2500 AMPS 2500
SPARE CAPACITY AMPS 826
DISTRIBUTION PANELBOARD NDPH2A
LOAD SUMMARY
VOLTS/PHASE: 480Y/277V, 3PH, 4W
LOAD DESCRIPTION
CONNECTED
KVA
DEMAND
FACTOR
DEMAND
KVA
COOLING (C) 0.00 100% 0.00
HEATING (H) 0.00 0% 0.00
LIGHTING (L) 0.00 125% 0.00
RECEPTACLES (R) (Per NEC T220.44) 0.00 100% 0.00
MOTORS (M) 336.71 100% 336.71
LARGEST MOTOR 129.70 125% 162.12
SUPPLEMENTAL ELECTRIC HEAT (Y) 48.00 100% 48.00
MISCELLANEOUS EQUIPMENT (Z) 0.00 100% 0.00
TOTAL LOAD 514.41 KVA 546.83
TOTAL AMPACITY 619 AMPS 658
DISTRIBUTION PANELBOARD AMPACITY 1000 AMPS 1000
SPARE CAPACITY AMPS 342
DISTRIBUTION PANELBOARD NDPH2B
LOAD SUMMARY
VOLTS/PHASE: 480Y/277V, 3PH, 4W
LOAD DESCRIPTION
CONNECTED
KVA
DEMAND
FACTOR
DEMAND
KVA
COOLING (C) 3.24 100% 3.24
HEATING (H) 0.00 0% 0.00
LIGHTING (L) 0.00 125% 0.00
RECEPTACLES (R) (Per NEC T220.44) 1.44 100% 1.44
MOTORS (M) 33.09 100% 33.09
LARGEST MOTOR 0.00 125% 0.00
SUPPLEMENTAL ELECTRIC HEAT (Y) 0.00 100% 0.00
MISCELLANEOUS EQUIPMENT (Z) 18.00 100% 18.00
TOTAL LOAD 55.77 KVA 55.77
TOTAL AMPACITY 67 AMPS 67
DISTRIBUTION PANELBOARD AMPACITY 400 AMPS 400
SPARE CAPACITY AMPS 333
FEEDER/BRANCH CIRCUIT SCHEDULE
TAG
AMPS DESCRIPTION
M200/N/- 200A
(1) 4" C W/(3)15KV #2/0, (1)600V #2/0 N. + (1) 4" C W/ PULL STRING IN
CONCRETE ENCASED DUCT BANK
M125/N/- 125A
(1) 4" C W/(3)15KV #2, (1)600V #2 N. + (1) 4" C W/ PULL STRING IN
CONCRETE ENCASED DUCT BANK
30/-/G 30A (3)#10, (1)#10G, 1/2" C
40/-/G 40A (3)#8, (1)#10G, 3/4" C
50/-/G 50A (3)#6, (1)#10G, 3/4" C
60/N/G 60A (4)#4, (1)#8G, 1-1/4" C
90/-/G 90A (3)#2, (1)#8G, 1-1/4" C
125/-/G 125A (3)#1, (1)#6G, 1-1/2" C
125/N/G 125A (4)#1, (1)#6G, 1-1/2" C
150/-/G 150A (3)#1/0, (1)#6G, 1-1/2" C
150/N/G 150A (4)#1/0, (1)#6G, 1-1/2" C
200/-/G 200A (3)#3/0, (1)#6G, 2" C
225/-/G 225A (3)#4/0, (1)#4G, 2" C
400/N/G 400A (2) 2" C, EACH W/ (4)#3/0, (1)#3G
1000/N/G 1000A (3) 3" C, EACH W/ (4) 400KCMIL, (1)#2/0G
1600/-/G 1600A (6) 3" C, EACH W/ (3) 300KCMIL, (1)#4/0G
T50/N/G 60A (4 )#6, (1 )#8G, 1" C
T100/N/G 100A (4)#1, (1)#6G, 1-1/2" C
T225/N/G 225A (4)#4/0, (1)#2G, 2-1/2" C
G100 GND #8 COPPER GROUND, 3/4" C
G150 GND #6 COPPER GROUND, 3/4" C
G300 GND #2 COPPER GROUND, 3/4" C
G800 GND #2/0 COPPER GROUND, 3/4" C
G4000 GND #3/0 COPPER GROUND, 3/4" C
ETD N/A EXISTING TO DEMO
ETR N/A EXISTING TO REMAIN
EBJ N/A EQUIPMENT BONDING JUMPER
MBJ N/A MAIN BONDING JUMPER
NOTE: ALL CONDUCTOR SIZES ARE BASED ON 75 DEGREE C RATED TERMINATION AND
COPPER CONDUCTORS WITH TYPE THHN/THWN-2 INSULATION. FOR TERMINATION OR
INSULATION TYPES RATED LESS THAN 75 DEGREE C, MODIFY SIZES ACCORDING TO NFPA 70.
ELECTRICAL ONE-LINE DIAGRAM
NO SCALE
3200AF
2500AT
3P
600AS
3P
600AS
3P
XFMR
13,800V-
480Y/277V
3PH, 4W
2000KVA
SWITCHBOARD NSWBD1
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
3200 AMPS 480Y/277V, 3PH, 4W 48,506 FCA, 100KAIC MINIMUM
125AF
3P
UNIT SUBSTATION #1
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
FUTURE DISTRIBUTION SECTION
2000AF
1600AT
3P
2000AF
1000AT
3P
/G
/N /G
G
G
G
G
G
G
1600AF
400AT
3P
1600AF
SPARE
3P
1600AF
SPARE
3P
1600AF
SPARE
3P
FURN. AND
INSTALLED BY
DIV. 23
CHILLER
WCC-1
/N
/G
PAD-MOUNTED
SWITCH PMS-1.90
S&C PME-9 STYLE
13.8KV/7.97KV
600AS
3P
NC
600AS
3P
NC
125AF
3P
125AF
3P
G
DISTRIBUTION PNLBD NDPH1A (NORMAL)
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
1200 AMPS 480Y/277V, 3PH, 4W 65KAIC MINIMUM
100AF
90AT
3P
/G
COOLING
TOWER
CT-1A
200AF
200AT
3P
/G
CHILLED WATER
PUMP
CWP-1
+30%
SPACE
FULLY
BUSSED
400AF
225AT
3P
/G
CONDENSER
PUMP
CTP-2
CHILLED WATER
PUMP
CWP-3
NONC
ATS-LS1
150A
4P
LIFE SAFETY
200AF
125AT
3P
/N
/G
PNLBD
NHP1A
100AF
25AT
3P
/G
/G
TX-LSPL1A
15KVA
480V-
208Y/120V
3PH, 4W
T
/N
/G
G
/G
TX-NPL1A
30KVA
480V-
208Y/120V
3PH, 4W
T
/N /G
G
PNLBD
NPL1A
PNLBD
LSPL1A
/G
BRANCH
ATS-CR1
150A
4P
CRITICAL
200AF
150AT
3P
/G
/G
TX-CRPL1A
75KVA
480V-
208Y/120V
3PH, 4W
T
/N /G
G
PNLBD
CRPL1A
BRANCH
DISTRIBUTION PNLBD NDPH1B (NORMAL)
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
400 AMPS 480Y/277V, 3PH, 4W 65KAIC MINIMUM
PAD-MOUNTED
SWITCH PMS-1.95
S&C PME-9 STYLE
13.8KV/7.97KV
600AS
3P
NC
600AS
3P
NC
125AF
3P
125AF
3P
G
600AS
3P
600AS
3P
XFMR
13,800V-
480Y/277V
3PH, 4W
2000KVA
SWITCHBOARD NSWBD2
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
3200 AMPS 480Y/277V, 3PH, 4W 48,756 FCA, 100KAIC MINIMUM
125AF
3P
UNIT SUBSTATION #2
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
FUTURE DISTRIBUTION SECTION
3200AF
2500AT
3P 2000AF
1600AT
3P
2000AF
1000AT
3P
/G
/N /G
G
G
G
G
G
G
1600AF
400AT
3P
1600AF
SPARE
3P
1600AF
SPARE
3P
1600AF
SPARE
3P
CHILLER
WCC-2
/N
/G
DISTRIBUTION PNLBD NDPH2A (NORMAL)
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
1200 AMPS 480Y/277V, 3PH, 4W 65KAIC MINIMUM
NCNO
ATS-EQ1
150A
4P
EQUIPMENT
200AF
150AT
3P
/N
/G
/N
/G
TX-EQPL2A
30KVA
480V-
208Y/120V
3PH, 4W
T
/N /G
G
PNLBD
EQPL2A
BRANCH
200AF
150AT
3P
/G
DISTRIBUTION PNLBD NDPH2B (NORMAL)
NORMAL ELECTRICAL ROOM NEMA 1 ENCLOSURE
400 AMPS 480Y/277V, 3PH, 4W 65KAIC MINIMUM
PNLBD
EQPH2A5
/G
+30% SPACE
FULLY
BUSSED
+30% SPACE
FULLY
BUSSED
1 2 3 4 5 6
1 2 3 4 5 6
M
/N
M
/N
M
/N
E T
R
200AF
150AT
3P
/N
/G
PNLBD
CRPL1B
60A MCB
/N /G
M
/N
M
/N
M
/N
M
/N
15KV CIRCUIT #90
FROM POWER
PLANT, BUILDING 24
E T
D
15KV ELECTRICAL
MANHOLE #4
(EXISTING)
15KV ELECTRICAL
MANHOLE #7
(EXISTING)
15KV ELECTRICAL
MANHOLE (NEW)
15KV ELECTRICAL
MANHOLE (NEW)
15KV ELECTRICAL
MANHOLE (NEW)
TO EXISTING 15KV
CIRCUIT #95
ELECTRICAL
DISTRIBUTION
EQUIPMENT AT
BUILDING 17
TO BOILER PLANT,
BUILDING 2
E T
R
E T
R
(2) SERVICES TO
BUILDING 9 WHICH
SERVES BUILDING
8 AND BUILDING D.
TO BOILER PLANT,
BUILDING 2 LIFE
SAFETY
GENERATOR
FURN. AND
INSTALLED BY
DIV. 23
COOLING
TOWER
CT-1B
100AF
90AT
3P
/G
200AF
200AT
3P
/G
100AF
90AT
3P
/G
COOLING
TOWER
CT-2A
200AF
200AT
3P
/G
CHILLED WATER
PUMP
CWP-2
/G
CONDENSER
PUMP
CTP-3
CONDENSER
PUMP
CTP-1
COOLING
TOWER
CT-2B
100AF
90AT
3P
/G
/G
XFMR MV-30-T-1
1,500KVA
PAD-MTD XFMR
13800V-
480Y/277V
3PH, 4W
RELOCATE EXISTING
PAD-MOUNTED
SWITCH PMS-1.95
S&C PME-9 STYLE
13.8KV/7.97KV
600AS
3P
NC
600AS
3P
NO
FUTURE
3P
65AF
3P
G
/N
E T
R
M
/N
/- 2000AS
2000AF
3P
EXISTING
NEMA 3R
RELOCATE EXISTING
/N
M
/N
RECONNECT TO EXISTING
SWITCHBOARD IN TEMP CHILLER
ENCLOSURE. COORDINATE
WITH DIVISION 23.
RE-ESTABLISH N-G BOND
AND PROVIDE G150
GROUND TO GROUND RODS.
400AF
225AT
3P
400AF
225AT
3P
100AF
40AT
3P
/G
COOLING TOWER
FILTRATION PUMP
CTF-1
100AF
40AT
3P
/G
COOLING TOWER
FILTRATION PUMP
CTF-2
GENERAL SHEET NOTES
A. PRELIMINARY FAULT CURRENT CALCULATIONS ARE
SHOWN. SUBSTATION TRANSFORMER IMPEDANCE OF
5.75% WITH AN INFINITE PRIMARY HAS BEEN UTILIZED
FOR PRELIMINARY FAULT CURRENT CALCULATIONS.
ADJUST FOR ACTUAL TRANSFORMER PROVIDED.
FEEDER AND BRANCH CIRCUIT LENGTHS SHOWN ARE
FOR PRELIMINARY CALCULATION PURPOSES ONLY AND
NOT TO BE USED FOR BIDDING PURPOSES. FIELD VERIFY
EXACT ROUTINGS AND REQUIRED LENGTHS. PROVIDE
FINAL CALCULATIONS FOR ALL EQUIPMENT IN
ACCORDANCE WITH SPECIFICATION SECTION 260573
OVERCURRENT PROTECTIVE DEVICE STUDY.
B. DEFINITIONS: PRELIMINARY FAULT CURRENT AMPS (FCA)
CUMULATIVE VOLTAGE DROP %CVD
45,208 FCA
0.24% CVD
70 FEET
45,416 FCA
0.10% CVD
30 FEET
44,012 FCA
0.04% CVD
40 FEET
14,402 FCA
0.38% CVD
75 FEET
14,402 FCA
0.38% CVD
75 FEET
27,108 FCA
0.34% CVD
60 FEET
28,287 FCA
0.34% CVD
55 FEET
27,008 FCA
0.40% CVD
70 FEET
8,066 FCA
0.30% CVD
40 FEET
27,177 FCA
0.22% CVD
30 FEET
1,858 FCA
0.25% CVD
5 FEET
22,639 FCA
0.23% CVD
5 FEET
1,353 FCA
0.15% CVD
5 FEET
7,248 FCA
0.14% CVD
30 FEET
5,819 FCA
0.21% CVD
5 FEET
29.080 FCA
0.17% CVD
30 FEET
4,292 FCA
0.45% CVD
25 FEET
44,572 VA
0.31% CVD
90 FEET
47,173 FCA
0.06% CVD
15 FEET
44,202 FCA
0.02% CVD
20 FEET
14,608 FCA
0.32% CVD
75 FEET
14,608 FCA
0.32% CVD
75 FEET
26,979 FCA
0.30% CVD
65 FEET
28,635 FCA
0.30% CVD
65 FEET
29,602 FCA
0.30% CVD
60 FEET
8,143 FCA
0.25% CVD
40 FEET
24,528 FCA
0.18% CVD
45 FEET
1,852 FCA
0.23% CVD
5 FEET
20,750 FCA
0.20% CVD
5 FEET
VFD'S/MOTOR STARTERS/DISCONNECT SWITCHES
FURNISHED BY DIVISION 23 AND INSTALLED BY DIVISION 26
VFD'S/MOTOR STARTERS/DISCONNECT SWITCHES
FURNISHED BY DIVISION 23 AND INSTALLED BY DIVISION 26
60AS
40AF
3P
NEMA 3R
CT-1A BASIN
HEATER
CT-1A-BH
100AF
40AT
3P
/G
4,392 FCA
0.62% CVD
75 FEET
60AS
40AF
3P
NEMA 3R
CT-1B BASIN
HEATER
CT-1B-BH
100AF
40AT
3P
/G
4,392 FCA
0.62% CVD
75 FEET
+30%
SPACE
FULLY
BUSSED
60AS
40AF
3P
NEMA 3R
CT-2A BASIN
HEATER
CT-2A-BH
100AF
40AT
3P
/G
4,409FCA
0.56% CVD
75 FEET
60AS
40AF
3P
NEMA 3R
CT-2B BASIN
HEATER
CT-2B-BH
100AF
40AT
3P
/G
4,409 FCA
0.56% CVD
75 FEET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
D U s e rs \j w h e e le r\
D o c u m e n ts \2
-1
E
L E
C v jw h e e le rD S
Y A
F .r v t
/5
/2
:0
:1
P M
XX-E-601
NEW CHILLER PLANT, BLDG XX - ELECTRICAL
ONE-LINE DIAGRAM
JGW CRP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
D U s e rs \j w h e e le r\
D o c u m e n ts \2
-1
E
L E
C v jw h e e le rD S
Y A
F .r v t
/5
/2
:0
:1
P M
XX-E-602
NEW CHILLER PLANT, BLDG XX - ELECTRICAL
SCHEDULES
JGW CRP
8. VERIFY COMPATIBILITY OF ALL DIMMING BALLASTS WITH SPECIFIED DIMMING CONTROLS PRIOR TO ORDERING AND PROVIDE APPROPRIATE COMPONENTS TO CREATE A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
7. ALL LUMINAIRES SHALL HAVE A U.L. LABEL.
6. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS OF LUMINAIRES AND CEILING TYPES. PROVIDE SUITABLE MOUNTING FRAME FOR CEILING.
5. UTILIZE THE LUMINAIRE MANUFACTURER'S MOUNTING HARDWARE AND FOLLOW ALL MANUFACTURER'S INSTALLATION DIRECTIONS WHEN INSTALLING LUMINAIRES.
4. PROVIDE ALL MISCELLANEOUS HARDWARE, CLIPS, ANGLES, FRAMES, ETC. AS REQUIRED TO MOUNT THE LUMINAIRES ON THE SURFACES THEY ARE TO BE INSTALLED.
3. PROVIDE A LUMINAIRE UTILIZING +/- 10% OF THE LED LUMENS INDICATED WHEN VARYING FROM THE BASIS-OF-DESIGN LUMINAIRE.
2. COMPLETE CATALOG NUMBER MAY NOT BE LISTED. ORDER LUMINAIRE BASED ON DESCRIPTION, PARTIAL CATALOG NUMBER AND SPECIFICATIONS. THE MANUFACTURER LISTED IS THE BASIS-OF-DESIGN. WHEN VARYING FROM THE BASIS-OF-DESIGN MANUFACTURER, PROVIDE FIXTURE WITH COMPARABLE QUALITIES AND FEATURES THAT MEETS THE REQUIREMENTS OF THE BASIS-OF-DESIGN MANUFACTURER AND SPECIFICATIONS.
1. REFER TO SPECIFICATION SECTION 265100 LIGHTING FOR ADDITIONAL INFORMATION CONCERNING LUMINAIRES, FINISHES, DRIVERS, LAMPS, ETC.
LUMINAIRE SCHEDULE GENERAL NOTES:
LUMINAIRE SCHEDULE
PLAN
MARK
BASIS OF
DESIGN
MANUFACTURER BASIS OF DESIGN MODEL NUMBER MOUNTING
LAMP TYPE LED LUMENS COLOR TEMP.
'K' DRIVER
WATTAGE VOLTAGE DESCRIPTION
A1 H.E. WILLIAMS 50G-S24-L33/835-SAF12125-DRV-UNV RECESSED LED 3300 3500 K STANDARD
ELECTRONIC DRIVER
49 W 120 V 2'X4' STATIC LENSED TROFFER, RECESSED, DIE-FORMED COLD-ROLLED STEEL
HOUSING, POSITIVE CAM ACTION STEEL LATCHES, INTEGRAL SAFETY HINGES,
ACRYLIC LENS, PREMIUM REFLECTANCE BAKED WHITE ENAMEL FINISH, UL LISTED
FOR DAMP LOCATIONS
A2 H.E. WILLIAMS 50G-S22-L26/835-SAF12125-DIM-UNV RECESSED LED 2600 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
45 W 120 V 2'X2' STATIC LENSED TROFFER, RECESSED, DIE-FORMED COLD-ROLLED STEEL
HOUSING, POSITIVE CAM ACTION STEEL LATCHES, INTEGRAL SAFETY HINGES,
ACRYLIC LENS, PREMIUM REFLECTANCE BAKED WHITE ENAMEL FINISH, UL LISTED
FOR DAMP LOCATIONS
A2E H.E. WILLIAMS 50G-S22-L26/835-SAF12125-DIM-UNV RECESSED LED 2600 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
45 W 120 V EMERGENCY 2'X2' STATIC LENSED TROFFER, RECESSED, DIE-FORMED
COLD-ROLLED STEEL HOUSING, POSITIVE CAM ACTION STEEL LATCHES, INTEGRAL
SAFETY HINGES, ACRYLIC LENS, PREMIUM REFLECTANCE BAKED WHITE ENAMEL
FINISH, UL LISTED FOR DAMP LOCATIONS
A3 H.E. WILLIAMS 50G-S14-L27/835-SAF12125-DRV-UNV RECESSED LED 2700 3500 K STANDARD
ELECTRONIC DRIVER
23 W 120 V 1'X4' STATIC LENSED TROFFER, RECESSED, DIE-FORMED COLD-ROLLED STEEL
HOUSING, POSITIVE CAM ACTION STEEL LATCHES, INTEGRAL SAFETY HINGES,
ACRYLIC LENS, PREMIUM REFLECTANCE BAKED WHITE ENAMEL FINISH, UL LISTED
FOR DAMP LOCATIONS
EM SURE-LITE SEL50 WALL LED -- 3500 K STANDARD
ELECTRONIC DRIVER
7 W 120 V LED EMERGENCY LIGHTING UNIT WITH MIN. 90 MIN BATTERY BACKUP, FLAME- AND
IMPACT- RESISTANT, WHITE POLYCARBONATE HOUSING, WITH MAINTANENCE FREE
NI-CAD BATTERY AND SOLID STATE CHARGING SYSTEM. MOUNT 8'-0" A.F.F.
F1 H.E. WILLIAMS 76-4-L32/835-DRV-UNV SUSPENDED LED 3200 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
22 W 120 V LED SUSPENDED [6"W x 12'L x 3-1/2" D] LUMINAIRE
F1E H.E. WILLIAMS 76-4-L32/835-DRV-UNV SUSPENDED LED 3200 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
22 W 120 V EMERGENCY LED SUSPENDED [6"W x 12'L x 3-1/2" D] LUMINAIRE
F2 H.E. WILLIAMS 76-4-L53/835-DRV-UNV SUSPENDED LED 5300 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
34 W 120 V LED SUSPENDED [6"W x 12'L x 3-1/2" D] LUMINAIRE
F2E H.E. WILLIAMS 76-4-L53/835-DRV-UNV SUSPENDED LED 5300 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
34 W 120 V EMERGENCY LED SUSPENDED [6"W x 12'L x 3-1/2" D] LUMINAIRE
F3 H.E. WILLIAMS 76-4-L77/835-DRV-UNV SUSPENDED LED 7700 3500 K 0-10V LOW VOLTAGE
DIMMING DRIVER
53 W 120 V LED SUSPENDED [6"W x 12'L x 3-1/2" D] LUMINAIRE
W1 H.E. WILLIAMS WPCS-L30/840-BZ-OCC-S23-DIM-UNV WALL LED 3000 4000 K 0-10V LOW VOLTAGE
DIMMING DRIVER
28 W 120 V EXTERIOR LED WALL SCONCE, DIM TO 50% BASED ON OCCUPANCY LEVELS
W1E H.E. WILLIAMS WPCS-L30/840-BZ-OCC-S23-DIM-UNV WALL LED 3000 4000 K 0-10V LOW VOLTAGE
DIMMING DRIVER
28 W 120 V EMERGENCY EXTERIOR LED WALL SCONCE, DIM TO 50% BASED ON OCCUPANCY
LEVELS
X1E H.E. WILLIAMS EXIT-R-EM-WHT SURFACE LED -- 3500 K -- 5 W 120 V --
File details come from the government source that posted it. Updated .